RCI 8371 Installation Manual

Specifications

Brand: RCI
Category: Locks
Model: 8371 (Installation Manual)
File Type: PDF
File Size: —
Pages: 4

Read Online

Read the RCI 8371 Installation Manual online using the built-in PDF viewer.

Text of the manual

1. Please read template mounting instructions and use template that is provided for installing the

electromagnetic lock. 2. Connecting wire should be of sufficient gauge to prevent line loss. 3. The 8371/8372 electromagnetic lock requires either 12 or 24 VDC for correct operation. The voltage is jumper selectable. (See Fig. 1) For 12-volt operation two jumpers are used; contact pins one to two and three to four are jumpered. For 24-volt operation only one jumper is used; contact pins two to three are jumpered. Note: The 8371/8372 is shipped with jumpers installed for 24-volt operation. 12 or 24 VDC Supply Connect the positive (+) lead from the power supply to TB1-1. Connect the negative (-) lead from the power supply to TB1-2. For wiring installation, refer to Figure 1. 4. Do not tighten the armature plate tightly against the door. The armature plate must remain movable to allow surface alignment with the magnet face. The magnetic lock will lose holding force without this floating alignment. 5. Do not trim the rubber washer mounted on the head of the armature center bolt. Trimming this rubber washer will adversely affect the operation of the electromagnetic lock. Optional LSS (Lock Sensor Status Remote Indication) Magnet Locked – When the magnet is locked, the common contact (TB1-3) and the normally open contact (TB1-5) are closed. The normally closed contact (TB1-4) would be open. Magnet Unlocked – When the magnet is unlocked, the common contact (TB1-3) and the normally closed contact (TB1-4) are closed. Note: The LSS relay contacts are rated 24 VDC @ 1 amp maximum. The optional LSS includes a local Light Emitting Diode (LED) indication: no LED – no power; red LED – lock is unlocked; green LED – lock is locked. Switching Accessories RCI also carries a full line of switching devices and other accessories to interface with the 8300 series electromagnetic locks. ® ©2006 RUTHERFORD CONTROLS INT’L CORP. WWW.RUTHERFORDCONTROLS.COM USA: 2697 INTERNATIONAL PARKWAY, PKWY 5, VIRGINIA BEACH, VA 23452 • CANADA: 210 SHEARSON CRESCENT, CAMBRIDGE, ON N1T 1J6 PHONE • 1.800.265.6630 • 519.621.7651 • FAX: 1.800.482.9795 • 519.621.7939 • E-MAIL: [email protected] IS8371/72 R02/06 DA P07/06 DA In or Out... we make it Easy!®

8371/8372 Electromagnetic Lock Installation Instructions (Continued)

Figure 1. Wiring Schematic Problem Possible Cause Solution Door will not lock Absence of DC voltage at Check power supply and wiring. (no magnetic attraction) magnet terminals Reduced holding force Inadequate contact between Ensure mating surfaces are clean and in proper armature plate and face of magnet. alignment. Armature floats freely. Check for low voltage. Delay in lock release Circuit not broken (open) between Reposition switch so that it is between power supply power supply and magnetic lock. and magnetic lock. Secondary diode installed Remove (not necessary). LED status incorrect Misalignment of armature plate Check to see that alignment agrees with template. To Ensure Instant Magnetic Release • Wire the DC filtered power to the line side of the power switch to avoid simulated delays on unlocking. The local “ON/OFF” switch must be wired between the DC source voltage and magnet, as shown below. • All solid state switches or switching devices must be installed between the DC power source and the positive (+) line of the magnetic lock. Note: All RCI magnets have MOV surge suppression as a standard feature.Additional suppression (i.e., diodes) may cause a delay in release. Troubleshooting LSS Light Emitting Diode (LED) Magnet power from Power Supply +12/24VDC input - (Ground) Common N.C. N.O. Lock Status Sensor Output contacts SPDT rated 24VDC @ 1A maximum Jumper 12VDC Jumper 24VDC (preset) TB1 NOTE: Specifications are subject to change without notice. ©2006 RUTHERFORD CONTROLS INT’L CORP. WWW.RUTHERFORDCONTROLS.COM USA: 2697 INTERNATIONAL PARKWAY, PKWY 5, VIRGINIA BEACH, VA 23452 • CANADA: 210 SHEARSON CRESCENT, CAMBRIDGE, ON N1T 1J6 PHONE • 1.800.265.6630 • 519.621.7651 • FAX: 1.800.482.9795 • 519.621.7939 • E-MAIL: [email protected] - + - + INCORRECT CORRECT

Contacting surfaces of the electromagnetic lock and armature plate must be kept free of contaminating

materials. Surfaces should be cleaned periodically with a non-abrasive cleaner. We recommend all mounting fasteners be inspected/tightened regularly to prevent them from loosening through normal vibration of the door and frame. RCI offers a full line of listed power supplies, switching devices and other accessories to interface with the 8300 series electromagnetic locks. NOTE: 8300 series electromagnetic locks should be powered with filtered and regulated UL listed power supplies. Voltage These locks are now shipped with the default voltage set for 24VDC. If you need to change the voltage to 12VDC, see detailed instructions included.This change was made to prevent damage to the lock when 24VDC is applied with the jumpers set to 12VDC. Anti-Tamper Screws We are currently shipping 8371 and 8372 Electromagnetic Locks with new anti-tamper screws installed in the front face of the housing. These screws, when in place, prevent the insertion of an Allen wrench into the mounting screw openings on the underside of the lock. These screws will need to be removed prior to installing the lock so as to allow the mounting plate to be removed from the top of the lock. The cavity cover screw needs to be removed to access the security screw on the right hand side, while the screw on the left is clearly visible on the face of the lock. ©2006 RUTHERFORD CONTROLS INT’L CORP. WWW.RUTHERFORDCONTROLS.COM USA: 2697 INTERNATIONAL PARKWAY, PKWY 5, VIRGINIA BEACH, VA 23452 • CANADA: 210 SHEARSON CRESCENT, CAMBRIDGE, ON N1T 1J6 PHONE • 1.800.265.6630 • 519.621.7651 • FAX: 1.800.482.9795 • 519.621.7939 • E-MAIL: [email protected] 8371/8372 Electromagnetic Lock Installation Instructions (Continued)

©2006 RUTHERFORD CONTROLS INT’L CORP. WWW.RUTHERFORDCONTROLS.COM

USA: 2697 INTERNATIONAL PARKWAY, PKWY 5, VIRGINIA BEACH, VA 23452 • CANADA: 210 SHEARSON CRESCENT, CAMBRIDGE, ON N1T 1J6 PHONE • 1.800.265.6630 • 519.621.7651 • FAX: 1.800.482.9795 • 519.621.7939 • E-MAIL: [email protected] R E F E R E N C E C H A R T WIRE GAUGE SELECTION ® Total One-Way Length of Wire Run (ft.) Load Current @ 24V 1/4A 1/2A 3/4A 1A 1-1/4A 1-1/2A 2A 3A 100 24 20 18 18 16 16 14 12 150 22 18 16 16 14 14 12 10 200 20 18 16 14 14 12 12 10 250 18 16 14 14 12 12 12 10 300 18 16 14 12 12 12 10 — 400 18 14 12 12 10 10 — — 500 16 14 12 10 10 — — — 750 14 12 10 10 — — — — 1000 14 10 10 — — — — — 1500 12 10 — — — — — — Total One-Way Length of Wire Run (ft.) Load Current @ 12V 1/4A 1/2A 3/4A 1A 1-1/4A 1-1/2A 2A 3A 100 20 18 16 14 14 12 12 10 150 18 16 14 12 12 12 10 — 200 16 14 12 12 10 10 — — 250 16 14 12 10 10 10 — — 300 16 12 12 10 10 — — — 400 14 12 10 — — — — — 500 14 10 10 — — — — — 750 12 10 — — — — — — 1000 10 — — — — — — — 1500 10 — — — — — — — Wire Gauge Chart courtesy of Electronic Locking Devices by John L. Schum In or Out... we make it Easy!®