GESTRA LRG 16-60 Installation & Operating Manual
Read Online
Read the GESTRA LRG 16-60 Installation & Operating Manual online using the built-in PDF viewer.
Text of the manual
Original Installation & Operating
Manual
Conductivity Electrodes
LRG 16-60
LRG 16-61
LRG 17-60
819878-00
E N
English
all-guides
com
LRG 1x-6x - Installation & Operating Manual - 819878-00
Contents
Content of this Manual....................................................................................................................................4
Scope of delivery/Product package................................................................................................................4
How to use this Manual...................................................................................................................................5
Illustrations and symbols used.......................................................................................................................5
Hazard symbols in this Manual.......................................................................................................................5
Types of warning.............................................................................................................................................6
Specialist terms/Abbreviations......................................................................................................................7
Usage for the intended purpose......................................................................................................................8
Applicable directives and standards............................................................................................................8
Admissible system components, dependent on the required safety level.....................................................9
Improper use.................................................................................................................................................10
Basic safety notes.........................................................................................................................................11
Required personnel qualifications................................................................................................................12
Notes on product liability..............................................................................................................................12
Functional safety, safety integrity level (SIL)...............................................................................................13
Check the safety function regularly...........................................................................................................13
Reliability data as per EN 61508...................................................................................................................14
Function.........................................................................................................................................................15
Technical data...............................................................................................................................................18
Name plate/Identification.............................................................................................................................21
Factory settings.............................................................................................................................................23
Overall view...................................................................................................................................................24
LRG 16-60................................................................................................................................................24
LRG 16 -61...............................................................................................................................................24
LRG 17-60................................................................................................................................................24
Dimensions of LRG 16-60..............................................................................................................................26
Dimensions of LRG 17-60..............................................................................................................................27
Dimensions of LRG 16-61..............................................................................................................................28
Installation.....................................................................................................................................................29
Additional installation notes......................................................................................................................30
Example LRG 1x-60..................................................................................................................................31
Installation examples with dimensions........................................................................................................33
Conductivity measurement.......................................................................................................................33
Conductivity measurement and continuous blowdown control..................................................................34
Conductivity measurement and continuous blowdown control via a separate measuring vessel................35
Key Fig. 14 to Fig. 16................................................................................................................................36
Aligning the terminal box..............................................................................................................................36
LRG 1x-6x - Installation & Operating Manual - 819878-00
Contents
Functional elements.............................................................................................................................. 37
Connecting the CAN bus system...................................................................................................................38
Bus line, cable length and cross-section...................................................................................................38
Example...................................................................................................................................................38
Important notes on connecting the CAN bus system..................................................................................39
Bringing into service.....................................................................................................................................40
Changing the factory settings if necessary................................................................................................40
Notes on changing communication parameters “bd.rt, Id.Hi or GrP”..........................................................42
Changing the baud rate............................................................................................................................42
Changing the limiter ID.............................................................................................................................42
Changing the controller group ..................................................................................................................43
Changing the alarm limit value of the limiter function................................................................................43
Changing the cell constant........................................................................................................................44
Changing the temperature coefficient.......................................................................................................44
Using the “CAL” function...........................................................................................................................45
Using the “FiLt” function...........................................................................................................................46
Changing the scaling of 4 - 20 mA actual output at LRR 1-60...................................................................46
Changing the unit of the display value (µS/cm or ppm)..............................................................................47
Triggering a display test manually.............................................................................................................47
Comparing the measured value with the reference measurement of a reliable sample..............................48
Checking the alarm limit value Al.Hi by triggering a test function..............................................................48
Lockout function.......................................................................................................................................48
Start, operation, alarm and test....................................................................................................................49
System errors................................................................................................................................................53
Causes.....................................................................................................................................................53
Indication of system malfunctions using fault codes..................................................................................54
Errors without shutoff...............................................................................................................................56
Checking installation and function............................................................................................................57
Taking out of service/Disassembly...............................................................................................................58
Cleaning the conductivity electrode.............................................................................................................59
Monthly comparison of the measured values ...........................................................................................59
Cleaning interval.......................................................................................................................................59
Disposal.........................................................................................................................................................60
Returning decontaminated equipment.........................................................................................................60
EU Declaration of Conformity........................................................................................................................61
LRG 1x-6x - Installation & Operating Manual - 819878-00
Content of this Manual
Product:
■
■
Conductivity electrode LRG 16-60
■
■
Conductivity electrode LRG 16-61
■
■
Conductivity electrode LRG 17-60
First edition:
BAN 819878-00/08-2019cm
© Copyright
All rights reserved. Any misuse, particularly reproduction and dissemination to third parties, is not permitted.
The General Terms & Conditions of GESTRA AG apply.
Scope of delivery/Product package
■
■
1 x Conductivity electrode LRG 1x-6x
■
■
1 x Sealing ring, D 33 x 39, form D, DIN 7603-2.4068, bright annealed
■
■
1 x Installation & Operating Manual
Accessories
■
■
1 x M12 CAN bus connector, 5-pole, A-coded, with 120 Ω terminating resistor
LRG 1x-6x - Installation & Operating Manual - 819878-00
How to use this Manual
This Installation & Operating Manual describes how to correctly use LRG 16-60/LRG 16-61/LRG 17-60
conductivity electrodes. It applies to persons who integrate this equipment in control systems, install,
bring into service, operate, maintain and dispose of this equipment. Anyone carrying out the above-men-
tioned activities must have read this Installation & Operating Manual and understood its contents.
■
■
Read this Manual in full and follow all instructions.
■
■
Please also read the instructions for use of any accessories.
■
■
The Installation & Operating Manual is part of the equipment package. Keep it in an easily accessible
location.
Availability of this Installation & Operating Manual
■
■
Make sure this Installation & Operating Manual is always available to the operator.
■
■
If you pass on or sell the equipment to a third party, please also hand over the Installation & Operating
Manual.
Hazard symbols in this Manual
Danger zone/Dangerous situation
Illustrations and symbols used
1. Action to be taken
2.
■
■
Lists
◆
◆Bullet points in lists
A
Keys to illustrations
Additional
information
Read the relevant
Installation & Operating Manual
LRG 1x-6x - Installation & Operating Manual - 819878-00
Types of warning
DANGER
Warning of a dangerous situation that results in death or serious injury.
WARNING
Warning of a dangerous situation that may possibly result in death or serious injury.
CAUTION
Warning of a situation that may result in minor or moderate injury.
ATTENTION
Warning of a situation that results in damage to property or the environment.
all-guides
com
LRG 1x-6x - Installation & Operating Manual - 819878-00
Specialist terms/Abbreviations
Here, we explain some abbreviations, specialist terms, etc., which are used in this Manual.
IEC 61508
International standard IEC 61508 describes both the type of risk assessment and actions taken to provide
appropriate safety functions.
SIL (safety integrity level)
Safety integrity levels SIL 1 to 4 are used to quantify risk reduction. SIL 4 is the highest level of risk reduction.
International standard IEC 61508 forms the basis for establishing, testing and operating technical safety
systems.
CAN (Controller Area Network) bus
Data transmission standard and interface for connecting electronic equipment, sensors and control systems.
Data can be sent and received.
LRG .. / URS .. / URB .. / SRL .. / NRG .. / etc.
Equipment and type designations of GESTRA AG, see page 9.
SELV
Safety Extra Low Voltage
LRG 1x-6x - Installation & Operating Manual - 819878-00
Usage for the intended purpose
LRG 16-60/LRG 16-61/LRG 17-60 conductivity electrodes may only be used for measuring electrical
conductivity in liquid media.
LRG 1x-6x conductivity electrodes are used in combination with the URS 60/URS 61 safety control unit
as a conductivity limiter and in combination with an LRR 1-60 conductivity controller as a continuous
blowdown regulator and limit indicator in steam boiler systems and hot-water plants.
■
■
To guarantee trouble-free operation, observe the water quality requirements as specified
in the Technical Rules (TRD) and EN standards for steam boiler systems.
■
■
The equipment may only be used within the admissible pressure and temperature limits; see
“Technical data” on page 18 and “Rating plate/Identification” on page 21.
■
■
Visualisation and operation take place via an operating unit of type URB 60 or SPECTORcontrol.
Applicable directives and standards
LRG 16-60/LRG 16-61/LRG 17-60 conductivity electrodes have been tested and approved for use in the
area governed by the following directives and standards:
Directives:
■
■
Directive 2014/68/EU
EU Pressure Equipment Directive
■
■
Directive 2014/35/EU
Low Voltage Directive
■
■
Directive 2014/30/EU
EMC Directive
■
■
Directive 2011/65/EU
RoHS II Directive
Standards:
■
■
EN 12953-09
Shell boilers, requirements for limiting devices
■
■
EN 12952-11
Water-tube boilers, requirements for limiting devices
■
■
EN 60730-1
Automatic electrical controls – Part 1:
General requirements
■
■
EN 61508
Functional safety of electronic systems
Standards documents:
■
■
VdTÜV Bulletin BP WAUE 0100-RL
Requirements for the testing of water monitoring equipment
Technical rules for steam boilers - as a knowledge base:
This Manual occasionally refers to the TRD regulations as a knowledge base.
These regulations have not been in force since 1 March 2019 and are no longer updated.
They are replaced by the TRBS (German Technical Rules for Industrial Health & Safety).
Always observe the current regulations (EU directives, EN standards, information from emplo-
yers’ liability insurance associations, etc.) in order to comply with the current state of the art.
LRG 1x-6x - Installation & Operating Manual - 819878-00
Usage for the intended purpose
Admissible system components, dependent on the required safety level
In accordance with EU Pressure Equipment Directive 2014/68/EU and standards EN12952, EN12953,
EN 61508, and the technical rules of VdTÜV Bulletin BP WAUE 0100-RL, the conductivity electrodes can be
operated with the following system components, depending on the required safety level.
Conductivity
electrodes
Safety
control unit for
limiter
Control unit as
continuous blowdown controller,
limit indicator
or automatic intermittent
blowdown
Operating unit
SIL 2
as per
EN 61508
LRG 16-60
LRG 17-60
LRG 16-61
URS 60
URS 61
−
URB 60,
SPECTOR
control
without
safety level in line
with
EN 61508
LRG 16-60
LRG 17-60
LRG 16-61
−
LRR 1-60
URB 60,
SPECTOR
control
Fig. 1
Key to Fig. 1:
LRG =
Conductivity electrode
URS = Safety control unit
URB =
Visual display and operating unit
LRR = Conductivity controller
To ensure the proper use of equipment during all types of use, you must also read the Installa-
tion & Operating Manuals for the system components used.
■
■
You will find the latest Installation & Operating Manuals for the system components named
in Fig. 1 on our website:
http://www.gestra.com/documents/brochures.html
LRG 1x-6x - Installation & Operating Manual - 819878-00
Improper use
There is a danger of death due to explosion if the equipment is used in potentially explo-
sive atmospheres.
Do not use the equipment in potentially explosive atmospheres.
Do not bring any equipment into service that does not have its own specific name plate.
The name plate indicates the technical features of the equipment.
LRG 1x-6x - Installation & Operating Manual - 819878-00
Basic safety notes
There is a danger to life from scalding if the conductivity electrode is removed under
pressure. Steam or hot water can spurt forcefully out of the equipment.
■
■
Only remove the conductivity electrode at 0 bar boiler pressure.
There is a risk of severe burns when working on conductivity electrodes that have not
been allowed to cool. The conductivity electrode becomes very hot during operation.
■
■
Always allow the conductivity electrode to cool.
■
■
Perform all installation and maintenance work only on conductivity electrodes that have
been allowed to cool.
There is a danger to life from electric shock when working on electrical systems.
■
■
Always switch off the voltage to the system before performing connection work.
■
■
Check that the system is not carrying live voltage before commencing work.
Danger to life from faulty LRG 1x-6x conductivity electrodes due to the sudden escape of
hot steam or hot water.
Impacts or knocks during transportation or installation can cause the 1x-6x conductivity elec-
trodes to become damaged, whereby hot steam or hot water can escape through the pressure
relief hole.
■
■
Avoid damage, for example from strong knocks to the electrode rods,
during transportation and installation.
■
■
Before and after installation, check that the conductivity electrode is completely undam-
aged.
When bringing it into service, check that it is leak-tight.
Attempts to repair the equipment will cause the system to become unsafe.
■
■
LRG 1x-6x conductivity electrodes may only be repaired by the manufacturer, GESTRA AG.
■
■
Only replace faulty equipment with identical equipment from GESTRA AG.
all-guides
com
LRG 1x-6x - Installation & Operating Manual - 819878-00
Required personnel qualifications
Activity
Personnel
Integration in control system
Specialist staff
Plant designer
Installation/electrical
connection/bringing into service
Specialist staff
The device is an item of equipment with a
safety function (EU Pressure Equipment
Directive) and may only be installed, electri-
cally connected and brought into service by
suitable, trained staff.
Operation
Boiler service technician
Staff trained by the plant operator.
Maintenance work
Specialist staff
Maintenance and modifications may only
be performed by authorised staff who have
undergone specific training.
Modifications
Specialist staff
Persons trained by the plant operator to work
with pressure and temperature.
Fig. 2
Notes on product liability
We the manufacturer cannot accept any liability for damages resulting from improper use of the equip-
ment.
Basic safety notes
Deficient maintenance and cleaning can lead to the conductivity electrodes becoming
damaged and/or to incorrect measurement results and false alarms.
■
■
Once a year, perform a check on the conductivity electrodes using comparative
measurements.
■
■
Adhere to the maintenance and cleaning intervals; see page 59.
LRG 1x-6x - Installation & Operating Manual - 819878-00
Functional safety, safety integrity level (SIL)
In combination with the URS 60/URS 61 safety control unit, LRG 16-60/LRG 16-61/LRG 17-60
conductivity electrodes are suitable for use with safety functions up to SIL 2.
They are each elements of a safety circuit up to a rating of SIL 2 as per EN 61508 in the SPECTORconnect system, and
can transmit alarm notifications.
Combining them with accessories produces a type B subsystem. The following information on the techni-
cal and safety characteristics in Fig. 4 are based solely on LRG 1x-6x conductivity electrodes.
Breakdown of safety function failure rates (safety shutoff)
LRG 1x-6x
LRG 1x-6x
Mechanical
LRG 1x-6x
Electronic
CANopen
URS 60,
URS 61
Safety circuit
Fig. 3
The CANopen interface
is a “Black Channel”
be ignored during calculation due to
the low failure rate of < 1FIT.
type, and can
Check the safety function regularly
The functioning of the conductivity electrode must be monitored once a year by triggering the test func-
tion (T1 = 1 year). The test function can be triggered on site via the integrated rotary knob of the terminal
box; see page 52.
Furthermore, it is possible to trigger the test function remotely from URS 60/URS 61 or the external oper-
ating units URB 60 or SPECTORcontrol system.
LRG 1x-6x - Installation & Operating Manual - 819878-00
Reliability data as per EN 61508
Description
Characteristic values
Electrode type
LRG 1x-60
LRG 16-61
Safety integrity level
SIL 2
SIL 2
Architecture
1oo1
1oo1
Equipment type
Type B
Type B
Hardware error tolerance
HFT = 0
HFT = 0
Overall failure rate for dangerous undetected
failures
λDU = < 20 * 10-8 1/h
λDU = < 35 * 10-8 1/h
Overall failure rate for dangerous detected
failures
λDD = < 5000 * 10-9 1/h
λDD = < 5000 * 10-9 1/h
Safe failure fraction
SFF > 96.0 %
SFF > 95.0 %
Test interval
T1 = 1 year
T1 = 1 year
Probability of dangerous failure on demand
PFD < 100 * 10-5
PFD < 160 * 10-5
Diagnostic coverage. Percentage of dangerous
failures detected by a test.
DC > 95.0 %
DC > 91.0 %
Mean time to dangerous failure
MTTFd > 30 a
MTTFd > 30 a
Diagnostic interval
T2 = 1 hour
T2 = 1 hour
Performance level (as per ISO 13849)
PL = d
PL = d
Probability of dangerous failure per hour
PFH < 20 * 10-8 1/h
PFH < 35 * 10-8 1/h
Ambient temperature as a basis for calculation
Tu = 60 °C
Tu = 60 °C
Mean time to repair
MTTR = 0
(no repair)
MTTR = 0
(no repair)
Fraction of undetected dangerous failures that
have a common cause
beta = 2 %
beta = 2 %
Fraction of detected dangerous failures that
have a common cause
beta d = 1 %
beta d = 1 %
Fig. 4
LRG 1x-6x - Installation & Operating Manual - 819878-00
Function
The equipment measures the electrical conductivity in electroconductive liquid media.
Measuring process - LRG 16-60/LRG 17-60
The LRG 16-60/LRG 17-60 conductivity electrodes work as per the conductometric two-electrode
measuring process. A measuring current is passed through the medium with a frequency adapted to the
measuring range. This causes a potential gradient between the electrode and measuring tube, which is
evaluated as measuring voltage.
Measuring process - LRG 16-61
The LRG 16-61 conductivity electrode works as per the conductometric four-electrode measuring pro-
cess. It consists of two current and two voltage electrodes. From the current electrodes, a measuring
current with a set frequency is introduced into the medium. This causes a potential gradient between
these electrodes. This potential gradient is picked up in the media by the voltage electrodes and is evalu-
ated as measuring voltage.
Temperature compensation of the measured values based on a reference temperature (25 °C)
The electrical conductivity is a function of the temperature. In order to base the measured values on a
reference temperature, an integrated resistance thermometer therefore measures the medium’s
temperature. The electrical conductivity is calculated from the measuring current and the measuring
voltage and is based on the reference temperature of 25°C through temperature compensation.
Compensation process
The measured value of the conductivity is corrected linearly depending on a set temperature
coefficient. The coefficient (standard is 2.1%/°C) is usually used for steam generating units with
constant pressure. The conductivity is determined for an ambient temperature (25 °C).
The gradients are then verified at operating pressure with a calibrated conductivity measuring device.
Application
LRG 1x-6x conductivity electrodes are used in combination with the URS 60/URS 61 safety control unit
as a conductivity limiter and in combination with an LRR 1-60 control unit as a continuous blowdown
regulator in steam boiler systems and hot-water plants.
Automatic self-test
An automatic self-test cyclically monitors the safety and function of the conductivity electrode and
measured value recorder.
The data are transferred to the URS 60/URS 61 safety control unit in the form of a Black Channel data
telegram using the CANopen protocol on the basis of a CAN bus as per ISO 11898.
LRG 1x-6x - Installation & Operating Manual - 819878-00
Function
The following information is transferred as data telegrams:
■
■
Measured value of the conductivity, temperature-compensated
■
■
The temperature of the medium
■
■
MAX limit value setting limiter
■
■
Temperature coefficient (tC) and cell constant (CF)
■
■
Limiter test command
■
■
Status and fault information
◆
◆Alarm signals from the conductivity electrode if the limit values are exceeded
◆
◆Error messages in the event of faults in electronic or mechanical parts
◆
◆Temperature in the terminal box of the conductivity electrode
Displays and signals; see page 49 / 54*
The LRG 1x-6x conductivity electrodes have a 4-digit green 7-segment display for showing measured
value and status information as well as fault codes. Several coloured LEDs are used to display alarm
states and the set unit.
Behaviour in the event of alarms *
The alarm state for an exceeded limit value is shown on the display as “Hi.C” alternately with the actual
value of the conductivity.
The alarm is transferred to the URS 60 or URS 61 safety control unit via CAN data telegram. Once the time
delay has elapsed, the alarm signal triggers the safety shutoff in the safety control unit. The URS 60 or
URS 61 safety control unit does not lock automatically for this.
The LEDs 1 and 4 signal the corresponding MAX alarm case see page 51 .
The safety circuit is interrupted without a delay if the following faults occur:
■
■
Fault in the sensors (open circuit, short circuit, faulty component, excessive temperature)
■
■
Communication failure
Behaviour in the event of faults *
The safety functions of the equipment are monitored in the sensors through periodic self-tests. Fault
messages are updated with each self-test and are permanently stored in the fault memory. If there are no
faults, only the list of current faults and their display is deleted.
Alarm and fault signals are indicated by LEDs and shown on the 7-segment display of the conductivity
electrodes and are transferred to the URS 60/URS 61 safety control unit via CAN data telegram.
Electrode alarms and errors faults cannot be acknowledged.
When the alarm or error is cancelled the display also goes blank, and the URS 60/URS 61
safety control unit closes the safety contacts again.
all-guides
com
LRG 1x-6x - Installation & Operating Manual - 819878-00
Simulating the alarm state *
The triggering of an alarm can be simulated by a keystroke on the rotary knob of the LRG 1x-6x, by
pressing the appropriate button on the URS 60/URS 61, or by using the URB 60. The device combination
will then behave as if a normal alarm had been triggered.
* The tables from page 49 clearly show the relationship between the
equipment status, the display and the alarm LEDs.
Parametrising or changing the factory settings
If necessary, you can adapt the conductivity electrode to the system conditions on site. You can set the
parameters or change the factory settings by means of a rotary knob on the terminal box; see page 40.
Function
LRG 1x-6x - Installation & Operating Manual - 819878-00
Technical data
Model and mechanical connection
■
■LRG 16-60, LRG 16-61, LRG 17-60
Thread G1 A, EN ISO 228-1, see Fig. 9, 10, 11
Nominal pressure rating, admissible service pressure and temperature
■
■LRG 16-60
PN 40
32 bar (g) at 238 °C
■
■LRG 16-61
PN 40
32 bar (g) at 238 °C
■
■LRG 17-60
PN 63
60 bar (g) at 275 °C
Materials
■
■Terminal box
3.2581 G AlSi12, powder-coated
■
■Sheath
1.4301 X5 CrNi 18-10
■
■Measuring electrodes
1.4571 X6CrNiMoTi17-12-2
■
■Electrode insulation
PTFE
■
■Screw-in body:
◆
◆Measuring tube, measuring screw
LRG 16-60, LRG 17-60
1.4571, X6CrNiMoTi17-12-2
◆
◆Spacer
LRG 16-60, LRG 16-61, LRG 17-60
PEEK
Deliverable installation lengths of the electrodes (cannot be shortened)
■
■LRG 16-60, LRG 17-60
200, 300, 400, 500, 600, 800, 1000 (mm)
■
■LRG 16-61
180, 300, 380, 500, 600, 800, 1000 (mm)
Temperature sensor
■
■Resistance thermometer
Pt 1000
■
■Measuring range for the temperature of the medium
0 to 280 °C
Conductivity range at 25 °C
■
■LRG 16-60, LRG 17-60
0.5 μS/cm to 6,000 μS/cm, 0.25 - 3000 ppm *
◆
◆Preferred measuring range
up to 1000 µS/cm
■
■LRG 16-61
50 μS/cm to 10,000 μS/cm, 25 - 5000 ppm *
◆
◆Preferred measuring range
from 500 µS/cm
* Conversion µS/cm in ppm (parts per million):
1 μS/cm = 0.5 ppm
Measuring cycle
■
■1 second
LRG 1x-6x - Installation & Operating Manual - 819878-00
Technical data
Measuring quality (information for value ranges between the factory calibrating points)
■
■LRG 1x-60
Triggering internal processing *
Measurement deviation Linearity deviation
◆
◆Range 1:
0.5 µS - 10 µS
7 %
2 %
◆
◆Range 2:
10 µS - 250 µS
3 %
2 %
◆
◆Range 3:
250 µS - 2600 µS
3 %
1 %
◆
◆Range 4:
2600 µS - 21000 µS
3 %
1 %
■
■LRG 16-61
Triggering internal processing *
Measurement deviation Linearity deviation
◆
◆Range 1:
10 µS - 100 µS
2 %
2 %
◆
◆Range 2:
100 µS - 2000 µS
2 %
1.5 %
◆
◆Range 3:
2000 µS - 50000 µS
2 %
1 %
* Triggering internal processing based on 15 bit with sign before (16 bit).
The aforementioned values are related to uncompensated conductivity.
Time constant “T” (measured using the two-bath process)
Temperature
Conductivity
■
■LRG 16-60, LRG 17-60
9 seconds
14 seconds
■
■LRG 16-61
11 seconds
19 seconds
Temperature compensation
■
■The temperature compensation process is linear and is adjustable via parameter tC; see page 44.
Supply voltage
■
■24 V DC +/-20 %
Power consumption
■
■max. 7 VA
Current input
■
■max. 0.35 A
Internal fuse
■
■T 2 A
Safety cutout at excessive ambient temperature
■
■The cutout takes place at excessive ambient temperatures Tamb. = 75 °C
Electrode voltage
■
■< 500 mV (RMS) at no load
LRG 1x-6x - Installation & Operating Manual - 819878-00
Technical data
Input/output
■
■Interface for CAN bus as per ISO 11898, CANopen, insulated
■
■M12 CAN bus connector, 5-pole, A-coded
■
■M12 CAN bus socket, 5-pole, A-coded
Indicators and controls
■
■1 x 4-digit green 7-segment display for showing measured values and status information
■
■1 x red LED for indicating an alarm state
■
■3 x green LED for indicated the unit μS/cm / ppm and the OK state
■
■1 x rotary knob IP65 with button for menu navigation and test function
Protection class
■
■III Safety Extra Low Voltage (SELV)
IP rating as per EN 60529
■
■IP 65
Admissible ambient conditions
■
■Service temperature:
0 °C – 70 °C
■
■Storage temperature:
- 40 °C – 80 °C
■
■Transport temperature:
- 40 °C – 80 °C
■
■Air humidity:
10 % – 95 %, non-condensing
Weight
■
■LRG 16-60/LRG 16-61/LRG 17-60
approx 2.1 kg
LRG 1x-6x - Installation & Operating Manual - 819878-00
Name plate/Identification
Power consumption
Safety
note
Equipment designation
Equipment
function
Nominal pressure rating,
connection thread
material of screw-in body
Current
approval
Manufacturer
Serial number
IP rating
Supply voltage
CE marking
Appointed authority
Disposal information
Protection class
Fig. 5
The production date (quarterly and annual) is stamped in at the screw-in body of each conduc-
tivity electrode.
Admissible operating pressure,
admissible temperature
Admissible ambient
temperature
Measuring range
Safety integrity level
Data interface
Betriebsanleitung
beachten
See installation instructions
Voir instructions de
montage
0525
GESTRA AG
Münchener Str. 77
28215 Bremen
GERMANY
TÜV. XXX . XX-XXX
IEC 61508 SIL 2
LRG 16 - 60
Leitfähigkeitselektrode
Conductivity electrode
Electrode de mesure
de conductibilitè
70°C (158 °F)
T
Pmax
Pmax
Tmax
Tmax
PN40 G1 1.4571 IP65
32 bar (464psi)
238°C (460°F)
7 VA
0,5-6000µS/cm
0,25-3000ppm
IN/OUT: CAN-Bus
V
20%
24
±
all-guides
com
LRG 1x-6x - Installation & Operating Manual - 819878-00
Name plate/Identification
Fig. 6
IEC 61508 SIL 2
Betriebsanleitung
beachten
See installation instructions
Voir instructions de
montage
LRG 16 - 61
0525
GESTRA AG
Münchener Str. 77
28215 Bremen
GERMANY
TÜV. XXX . XX-XXX
Leitfähigkeitselektrode
Conductivity electrode
Electrode de mesure
de conductibilitè
70°C (158 °F)
T
Pmax
Pmax
Tmax
Tmax
PN40 G1 1.4571 IP65
32 bar (464psi)
238°C (460°F)
7 VA
50-10000µS/cm
25-5000ppm
IN/OUT: CAN-Bus
V
20%
24
±
Betriebsanleitung
beachten
See installation instructions
Voir instructions de
montage
0525
GESTRA AG
Münchener Str. 77
28215 Bremen
GERMANY
TÜV. XXX . XX-XXX
IEC 61508 SIL 2
LRG 17 - 60
Leitfähigkeitselektrode
Conductivity electrode
Electrode de mesure
de conductibilitè
70°C (158 °F)
T
Pmax
Pmax
Tmax
Tmax
PN63 G1 1.4571 IP65
60 bar (870psi)
275°C (527°F)
7 VA
0,5-6000µS/cm
0,25-3000ppm
IN/OUT: CAN-Bus
V
20%
24
±
LRG 1x-6x - Installation & Operating Manual - 819878-00
Factory settings
LRG 1x-6x conductivity electrodes are delivered ex works as follows.
Parameter
Display in menu
Unit
Parameter values
LRG 16-60
LRG 17-60
LRG 16-61
Limiter ID
Id.Hi
OFF
Controller group
GrP
0001
Baud rate
bd.rt
kBit/s
0050
Alarm limit value
AL.Hi
µS/cm
3000
5000
Cell constant
CF
0.210
Temperature coefficient
tC
%/°C
002.1
Filter constant (damping)
FiLt
Seconds
0025
Scale of current output LRR 1-60
Sout
µS
0500
7000
Display unit
Unit
µS
Fig. 7
LRG 1x-6x - Installation & Operating Manual - 819878-00
OK
!
+
-
Overall view
Fig. 8
OK
!
+
-
A
B
C
D
E
G
K
LRG 16-60
LRG 16 -61
J
H
F
I
L
LRG 17-60
OK
!
+
-
LRG 1x-6x - Installation & Operating Manual - 819878-00
Overall view
Key to Fig. 8
A
Terminal box
B
Operating panel with 4-digit LCD display/alarm LEDs and rotary knob; see page 49
C
Cover screws M4 x 16 mm
D
M12 CAN bus socket, 5-pole, A-coded
E
M12 CAN bus connector, 5-pole, A-coded
F
Sheath
G
Seal seat for sealing ring
H
Sealing ring, D 33 x 39, form D, DIN 7603-2.4068, bright annealed
I
Electrode thread
J
Threaded pin M2.5 mm (LRG 16-60/LRG 17-60)
K
Measuring tube with measuring electrode (LRG 16-60/LRG 17-60), measuring electrodes (LRG 16-61)
L
Spacer
LRG 1x-6x - Installation & Operating Manual - 819878-00
Dimensions of LRG 16-60
Fig. 9
All lengths and diameters in mm
OK
!
+
-
G 1
Size 41
0
Nm
50
70
90
110
120
100
80
60
41
140
175
338
x
b = 70
x = available installation lengths:
■
■
200 mm
■
■
300 mm
■
■
400 mm
■
■
500 mm
■
■
600 mm
■
■
800 mm
■
■
1000 mm
Thermal insulation
provided at the
site of installation
20
all-guides
com
LRG 1x-6x - Installation & Operating Manual - 819878-00
OK
!
+
-
Dimensions of LRG 17-60
140
175
338
x
x = available installation lengths:
■
■
200 mm
■
■
300 mm
■
■
400 mm
■
■
500 mm
■
■
600 mm
■
■
800 mm
■
■
1000 mm
Size 41
G 1
All lengths and diameters in mm
Fig. 10
b = 70
0
Nm
50
70
90
110
120
100
80
60
41
Thermal insulation
provided at the site
of installation
20
LRG 1x-6x - Installation & Operating Manual - 819878-00
E
OK
!
+
-
Dimensions of LRG 16-61
140
175
338
x
x = available installation lengths:
■
■
180 mm
■
■
300 mm
■
■
380 mm
■
■
500 mm
■
■
600 mm
■
■
800 mm
■
■
1000 mm
b = 70
Size 41
G 1
Fig. 11
All lengths and diameters in mm
0
Nm
50
70
90
110
120
100
80
60
41
Thermal insulation
provided at the
site of installation
20
LRG 1x-6x - Installation & Operating Manual - 819878-00
Installation
If the equipment is to be installed outdoors, outside the protection of a building, environ-
mental influences may adversely affect function.
■
■
Pay attention to the admissible ambient conditions in the technical data;
see page 20.
■
■
Do not operate the equipment if the temperature is below freezing.
◆
◆At temperatures below freezing, use a suitable heat source
(e.g. control cabinet heater, etc.).
■
■
Connect all system parts to a central earthing point to prevent equalisation currents.
■
■
Use a cover to protect the equipment from direct sunlight, condensation and
heavy rain.
■
■
Use UV-resistant cable ducts for routing the connecting cable.
■
■
Take further measures to protect the equipment from lightning, insects and animals, and
salty air.
You will need the following tools:
■
■
Torque wrench (with size 41 open-ended spanner attachment), see pages 26 to 28 and
page 32.
DANGER
Danger to life from scalding caused by sudden escape of hot steam.
Hot steam or hot water can escape suddenly if conductivity electrodes are unscrewed under
pressure.
■
■
Reduce the boiler pressure to 0 bar and check the pressure before unscrewing the
conductivity electrodes.
■
■
Only remove conductivity electrodes at a boiler pressure of 0 bar.
WARNING
Hot conductivity electrodes can cause severe burns.
Conductivity electrodes are extremely hot during operation.
■
■
Perform installation and maintenance work only on conductivity electrodes that have been
allowed to cool.
■
■
Only remove conductivity electrodes that have cooled down.
LRG 1x-6x - Installation & Operating Manual - 819878-00
Installation
ATTENTION
Incorrect installation can lead to destruction of the system or the conductivity
electrode.
■
■
Inspect the sealing surfaces of respective tank threaded standpipes or flange covers to
ensure they are perfectly machined; see Fig. 12.
■
■
Take care not to bend conductivity electrodes during installation!
■
■
Avoid hard knocks against the measuring electrodes during installation.
■
■
You must not install the terminal box A and the sheath F of the measuring electrode in the
thermal insulation of the boiler!
■
■
Please note the installation dimensions of the conductivity electrode; see installation exam-
ples on pages 33 to 36.
■
■
Check the boiler connection and flange during the preliminary boiler inspection.
■
■
Adhere to the specified tightening torques.
Additional installation notes
ATTENTION
An electrode that is not fully immersed in the medium leads to incorrect measurement
results and jeopardises system safety.
■
■
Install the conductivity electrode such that it is always fully immersed in the medium.
■
■
As far as possible, always install the conductivity electrode below the admissible LW mark.
Measuring points (metallic objects) between the boiler wall and electrode
impair the measurement. Incorrect measurement results jeopardise the system’s safety.
Therefore, adhere to the distances mentioned subsequently.
LRG 16-60/LRG 17-60
■
■
Provide spacing of approx. 30 mm between the lower end of the measuring tube and the
boiler wall, the smoke tubes, other metallic fittings and the low water level (LW).
■
■
The measuring electrodes and the measuring tube cannot be shortened.
LRG 16-61
■
■
Provide spacing of approx. 60 mm between the lower end of the measuring electrodes and
the boiler wall, the smoke tubes, other metallic fittings and the low water level (LW).
LRG 1x-6x - Installation & Operating Manual - 819878-00
Installation
1. Inspect the sealing surfaces of the tank thread-
ed standpipe or flange cover.
Sealing surfaces must be perfectly machined
according to Fig. 12.
Ø 40 mm
G 1
Ra 3.2
Ra 12.5
0.5 mm
Sealing surface dimensions for
LRG 16-60/LRG 16-61/LRG 17-60
Fig. 12
Example LRG 1x-60
G
H
Fig. 13
DANGER
Danger to life from escaping
hot steam if incorrect or
defective seals are used.
■
■
Only use the supplied sealing ring
for sealing the electrode thread I.
◆
◆Sealing ring D 33 x 39
DIN 7603-2.4068, bright
annealed
Prohibited seal materials:
■
■
Hemp, PTFE tape
■
■
Conductive paste or grease
2. Push the supplied sealing ring H onto the
seal seat G of the electrode, or lay it on the
sealing surface of the flange.
I
all-guides
com
LRG 1x-6x - Installation & Operating Manual - 819878-00
Installation
3. If necessary, apply a small quantity of silicone grease (e.g. Molykote® III) to the electrode thread I.
4. Screw the conductivity electrode into the threaded standpipe of the tank or flange cover, and tighten
securely using a torque wrench (with size 41 open-ended spanner attachment).
Tightening torque when cold:
■
■
LRG 16-60/LRG 16-61/LRG 17-60 = 250 Nm
Installation examples with dimensions, see Fig. 14, Fig. 15, Fig. 16, from page 33
LRG 1x-6x - Installation & Operating Manual - 819878-00
NW
LW
NB
R*
OK
!
+
-
Installation examples with dimensions
Conductivity measurement
Installation of conductivity electrodes via a side flange.
Key, see page 36
Fig. 14
400
All lengths and diameters in mm
338
~ 250
G1
1
e.g. LRG 16-60
* Minimum distances (R)
■
■
LRG 16-60/LRG 17-60
R = 30 mm
■
■
LRG16-61
R = 60 mm
Sealing ring D 33 x
39 DIN 7603-2.4068,
bright annealed
LRG 1x-6x - Installation & Operating Manual - 819878-00
Conductivity measurement and continuous blowdown control
Installation of the conductivity electrode via a measuring vessel with connection of a continuous blow-
down valve.
Key, see page 36
* Minimum distances (R):
■
■
LRG 16-60/LRG 17-60
R = 30 mm
■
■
LRG16-61
R = 60 mm
Fig. 15
Installation examples with dimensions
All lengths and diameters in mm
NW
LW
NB
R*
A
OK
!
+
-
600
338
~ 250
197
G1
1
2
3
Sealing ring
D 33 x 39
DIN 7603-2.4068,
bright annealed
e.g. LRG 16-60
4
Distance (A), depending on connection flange:
■
■
DN 15 mm
A = 182 mm
■
■
DN 20 mm
A = 184 mm
■
■
DN 25 mm
A = 184 mm
■
■
DN 40 mm
A = 189 mm
LRG 1x-6x - Installation & Operating Manual - 819878-00
Installation examples with dimensions
Conductivity measurement and continuous blowdown control via a separate measuring vessel
Installation of conductivity electrode in the continuous blowdown line via a separate measuring vessel.
Key, see page 36
M
OK
!
+
-
Outlet
3
2
DN 15 - 40
G1
Inlet
DN 15 - 40
5
Sealing ring D 33 x
39 DIN 7603-2.4068,
bright annealed
e.g. LRG 16-60
All lengths and diameters in mm
Fig. 16
LRG 1x-6x - Installation & Operating Manual - 819878-00
Installation examples with dimensions
Key Fig. 14 to Fig. 16
1
Boiler drum
2
Stop valve GAV
3
Continuous blowdown valve BAE
4
Connection piece in T-shape
5
Measuring vessel
Aligning the terminal box
If necessary, you can orientate the display in the desired direction by rotating the terminal box.
ATTENTION
Rotating the terminal box ≥ 180° will damage the conductivity electrode’s
internal wiring.
■
■
Never rotate the terminal box more than 180 degrees in either direction.
all-guides
com
LRG 1x-6x - Installation & Operating Manual - 819878-00
Functional elements
A
Terminal box
B
Cover screws M4 x 16 mm
C
Operating panel with 4-digit LCD display/alarm and status LEDs and
rotary knob, see page 49
D
M12 CAN bus socket, 5-pole, A-coded
E
M12 CAN bus connector, 5-pole, A-coded
Fig. 17
OK
!
+
-
A
B
C
D
E
LRG 1x-6x - Installation & Operating Manual - 819878-00
Bus line, cable length and cross-section
■
■
A shielded, multi-core, twisted-pair control cable, e.g. UNITRONIC® BUS CAN 2 x 2 x .. mm2 or
RE-2YCYV-fl 2 x 2 x .. mm2 must be used as the bus line.
■
■
Pre-wired control cables (with plug and coupling) are available as accessories in various lengths.
■
■
The baud rate (transfer rate) is determined by the cable length between the bus terminal devices, and
the wire cross-section is determined by the overall power input of the measuring sensors.
■
■
0.2 A at 24 V is required per sensor. With 5 sensors, there is therefore a voltage drop of approx. 8 V
per 100 m when using cables of 0.5 mm². In this case, the system is operating at its limits.
■
■
With 5 sensors or more and a cable length of ≥ 100 m, the wire cross-section needs to be doubled to
1.0 mm².
■
■
At larger distances of > 100 m, the 24 V DC supply can also be connected on site.
Connecting the CAN bus system
Example
5
Shield
3
3
5
5
120 Ω
CH
CL
120 Ω
CH
CL
S
+ 24 V
- 0 V
CH
CL
S
CL
-
CH
+ 24 V
S
+ 24 V
- 0 V
CH
CL
S
+ 24 V
- 0 V
CH
CL
S
+ 24 V
- 0 V
CH
CL
S
CH
CH
CH
CH
CL
CL
CL
CL
S
S
S
S
+
+
+
–
–
–
–
+
24V DC
24 V DC
100 - 240 V AC
120 Ω
2
7
+ 24 V
CL
CH
- 0 V
+
+
-
–
CH CL
Option
URB
URS, NRR, LRR,
URW
NRG, LRG, TRV
NRG, LRG,TRV
CH = CAN High
CL = CAN Low
S = Shield
Terminating
resistor
Fig. 18
LRG 1x-6x - Installation & Operating Manual - 819878-00
Important notes on connecting the CAN bus system
■
■
A dedicated 24 V DC SELV power supply unit that is isolated from connected loads must be used to
supply the SPECTORconnect system.
■
■
Make sure wiring is in line, not in a star!
■
■
Avoid potential differences in system parts by connection to a central earthing point.
◆
◆Connect the bus line shields to one another all the way along, and connect them to the central
earthing point (CEP).
■
■
If two or more system components are connected in a CAN bus network, a 120 Ω terminating resistor
must be connected to the first and last devices between terminals CL / CH.
■
■
Use the CAN bus connector with terminating resistor if you are using the conductivity electrode as the
first or last device.
■
■
Only one URS 60 and one URS 61 safety control unit may be used in the CAN bus network.
■
■
The CAN bus network must not be interrupted during operation!
If it is, an alarm signal is triggered.
Pin assignment of the CAN bus connector and coupling for non pre-wired
control cables
If non pre-wired control cables are used, you must wire the CAN bus connector and couplings as shown in
the wiring diagram Fig. 19.
1
S
Shield (screen)
2
+ 24 V
Power supply
3
− 0 V
Power supply
4
CH
CAN High data line
5
CL
CAN Low data line
1
2
3
4
5
1
2
3 4
5
Connector
Coupling
Fig. 19
Connecting the CAN bus system
LRG 1x-6x - Installation & Operating Manual - 819878-00
Bringing into service
Before bringing into service, check that all equipment is correctly connected:
■
■
Is the polarity of the CAN bus control line correct throughout?
■
■
Is a 120 Ω terminating resistor connected to the terminal devices of the CAN bus line?
Next, switch on the supply voltage.
Changing the factory settings if necessary
You will need the following tools
■
■
Slotted screwdriver, size 2.5
Select and set a parameter:
1.
+
-
Using the screwdriver, turn the rotary knob clockwise or anti-clockwise until the
desired parameter appears on the display. The set value is displayed after approx.
3 seconds.
The following parameters are shown one after the other when you turn the
rotary knob clockwise:
1234
Id.Hi
GrP
bd.rt
°C.in
°C.Pt
AL.Hi
CF
tC
CAL
FiLt
Sout
Unit
diSP
Key to parameters, see page 41.
4.
+
-
Save your set value by pressing the rotary knob for approx. 1 second.
The message “donE” is shown and the parameter appears on the display again.
If you do not enter anything for 30 seconds, the display automatically shows the
actual value again.
2.
+
-
Once you have selected a parameter, press and hold the rotary knob until the current
value of this parameter flashes on the display.
3.
+
-
Set the desired value.
Reducing/increasing the value
Each parameter has an individual, admissible value range.
By pressing the knob briefly, you can jump to the next digit. This is a more convenient
way of making large changes to values.
If you do not set a parameter within 10 seconds, the process is aborted (quit) and
the old parameter value is retained.
LRG 1x-6x - Installation & Operating Manual - 819878-00
Key to parameters:
■
■
1234 = Measuring value display (normal operating state, example)
■
■
Id.Hi
= Identifier for the limiter function (effect on the safety control unit URS 6x)
■
■
GrP
= Controller group, identifier of regulation function (effect on URB 60/SPECTORcontrol)
■
■
bd.rt
= Baud rate
■
■
°C.in = Display ambient temperature of housing
■
■
°C.Pt = Display temperature of measuring medium
■
■
AL.Hi = Set alarm limit value of limiter function
■
■
CF
= Cell constant of electrode
■
■
tC
= Temperature coefficient of measuring medium
■
■
CAL
= Calibration function to compare the display with a comparative value (sample)
■
■
FiLt
= Filter constant
■
■
Sout
= Scaling of 4-20 mA actual output at controller LRR 1-60
■
■
Unit
= Unit of display value (µS or ppm)
■
■
diSP
= Trigger a display test
Upstream display test for safety-relevant parameters
There is a display test upstream of some safety-relevant parameters (e.g. AL.Hi). This is intended to pre-
vent an incorrect value being entered due to faulty display segments that have not yet been noticed.
Setting example, see page 43
Using the alarm limit value for the limiter function (AL.Hi) as an example, we show you the procedure for
setting the parameters incl. the display test. This is representative of all safety parameters.
A display test performed once opens a 10 minute input window in which several safety-
relevant parameters can then also be changed without the display test repeating itself.
Triggering a display test manually.
Alternatively, you can also specifically trigger the display test with “diSP”; see page 47.
Bringing into service
all-guides
com
LRG 1x-6x - Installation & Operating Manual - 819878-00
Bringing into service
Notes on changing communication parameters “bd.rt, Id.Hi or GrP”
All CAN bus devices from GESTRA AG have preset communication parameters,
which enable a standard system to be brought into operation without making any changes.
Please follow the steps below if you need to make changes to communication
parameters:
■
■
Set the same baud rate for all bus participants.
■
■
To apply changed communication parameters, perform the steps below on the URB 60
visual display and operating unit or the SPECTORcontrol:
◆
◆Device list - Reimport
To do this, please read the instructions in the Installation & Operating Manual of the URB 60
visual display and operating unit or the SPECTORcontrol.
Changing the baud rate
Note the setting instructions on page 40 and proceed as follows:
1. Select the parameter “bd.rt”.
2. Press and hold the rotary knob until the current baud rate flashes on the display.
3. Set the desired baud rate (50 kBit/s / 250 kBit/s).
4. Save your set value by pressing the rotary knob for approx. 1 second.
Changing the limiter ID
To set the limiter ID, please also read the instructions in the Installation & Operating Manual
of the URS 60/URS 61 safety control unit.
Note the setting instructions on page 40 and proceed as follows:
1. Select the parameter “Id.Hi”.
2. Press and hold the rotary knob until the current limiter ID flashes on the display.
3. Set the desired ID (0001 to 0008).
4. Save your set value by pressing the rotary knob for approx. 1 second.
LRG 1x-6x - Installation & Operating Manual - 819878-00
Changing the controller group
To set the controller group, please also observe the instructions in the Installation & Operating
Manual of the LRR 1-60 conductivity controller.
Note the setting instructions on page 40 and proceed as follows:
1. Select the parameter “GrP”.
2. Press and hold the rotary knob until the currently assigned controller group flashes on the display.
3. Set the desired ID (0001 to 0004).
4. Save your set value by pressing the rotary knob for approx. 1 second.
Changing the alarm limit value of the limiter function
Notes on setting the alarm limit value “AL.Hi”
This setting only concerns the limit value for the safety shutoff via the URS 60/URS 61
safety control unit.
The limit value indicator contacts of the LRR 1-60 conductivity controller are independent from this.
For this, also observe the information in the relevant Installation & Operating Manual.
Note the setting instructions on page 40 and proceed as follows:
1. Select the parameter “AL.Hi”.
2. Press and hold the rotary knob until the display test starts by showing “....”.
3. The following numbers and decimal points run across the display from right to left:
“...., 1, 2, 3, 4, 5, 6, 7, 8, 9, ....”
4. Check that all numbers and decimal points are displayed correctly.
The display test runs automatically until it has finished, and cannot be interrupted.
5. The display test ends with the message “donE”.
6. When the display test is complete, the last digit of the limit value flashes.
7. Set the following required limit values:
■
■
LRG 1x-60: 0000 – 6000
■
■
LRG 16-61: 0000 - 9999
8. Save your set value by pressing the rotary knob for approx. 1 second.
A display test performed once opens a 10 minute input window in which several safety-
relevant parameters can then also be changed without the display test repeating itself.
Bringing into service
LRG 1x-6x - Installation & Operating Manual - 819878-00
Replacing faulty equipment
Faulty equipment jeopardises system safety.
■
■
If numbers or decimal points are displayed incorrectly or not at all, you must replace the
conductivity electrode with an identical one from GESTRA AG.
Changing the cell constant
Notes on adjusting the cell constant
The cell constants of each LRG 1x-6x conductivity electrode is finely adjusted ex works. If the installation
situation at the installation location makes a readjustment necessary, (see page 48, comparison of the
measured value with a reference measured vale), the cell constant can be changed on site.
Requirements for performing the readjustment:
■
■There must be a sufficient boiler fill level to compare the cell constants.
■
■The comparison with a reference measurement may only be performed at a low boiler output in order
to minimise distortion from steam bubbles.
By means of this parameter, the display value can be correlated manually with a reference
measured value from a reliable sample at the operation site.
Alternatively, the readjustment can be performed using a convenient solution by means of the “CAL”
function; see page 45.
Note the setting instructions on page 40 and proceed as follows:
1. Select the parameter “CF”.
2. Press and hold the rotary knob until the current value flashes on the display.
3. Set the desired value ( 0.050 – 5.000 ).
4. Save your set value by pressing the rotary knob for approx. 1 second.
Increasing the “CF” value causes the display value to increase.
With increased contamination, the display value will have decreased. This is to be compensa-
ted by increasing the “CF” value as described previously in points 1 to 4.
Changing the temperature coefficient
The temperature coefficient of the measuring medium can be adjusted manually as long as a
corresponding value has been determined.
The factory setting of “2.1” is usually set for steam generating units with constant pressure.
For newly implemented electrodes, this value is to be adjusted to the temperature coefficients
of the boiler water if necessary.
Bringing into service
LRG 1x-6x - Installation & Operating Manual - 819878-00
Bringing into service
Note the setting instructions on page 40 and proceed as follows:
1. Select the parameter “tC”.
2. Press and hold the rotary knob until the current value flashes on the display.
3. Set the desired value ( 000.0 – 003.0 ).
4. Save your set value by pressing the rotary knob for approx. 1 second.
Increasing the “tC” value causes the display value to decrease.
Using the “CAL” function
The CAL function allows the cell constants “CF” to be conveniently updated when the electrodes are
increasingly contaminated in operation. For this, the reference measured value of a reliable sample is
made the display value at the operating point. The internal evaluation then automatically calculates the
cell constants “CF” again and corrects it.
ATTENTION
If the “CF” value (cell constant) 003.0 is exceeded, there is a warning message
“CF.Hi”.
■
■
Clean the electrode as a matter of urgency, see page 59.
■
■
Operation continues to be possible.
Note the setting instructions on page 40 and proceed as follows:
1. Determine a reference measured value for the current conductivity by means of a reliable sample in
the operating point of the system.
2. Select the parameter “CAL”.
After this, the current value of the cell constant “CF” is shown first.
3. Press and hold the rotary knob until the current conductivity value flashes on the display.
4. Set the previously determined reference value (conductivity from the comparative sample) as the new
display value.
5. Save your set value by pressing the rotary knob for approx. 1 second.
An adjustment to the “CF” to values over 005.0 is cancelled. “Quit”
then appears on the display and the display reverts to the menu item “cal”.
Now, it is compulsory to clean the electrodes as described on pages 58 and 59.
LRG 1x-6x - Installation & Operating Manual - 819878-00
Bringing into service
Using the “FiLt” function
This function’s purpose is to “calm” the measured value for the controller function and the 4 - 20 mA
actual output at the LRR1-60.
■
■
If the limiter is deactivated (Id.Hi = 0), the adjustable time constant (1 - 30 seconds) also has an effect
on the display at the conductivity electrode.
■
■
If the limiter is activated (Id.Hi = 1 – 8), the filter does not have an effect on the limiter and no longer
has an effect on the display. The time constant for the limiter is safety-relevant and fixed.
Note the setting instructions on page 40 and proceed as follows:
1. Select the parameter “FiLt”.
After this, the current value of the filter constant is shown first.
2. Press and hold the rotary knob until the current value flashes on the display.
3. Set the desired value.
4. Save your set value by pressing the rotary knob for approx. 1 second.
Changing the scaling of 4 - 20 mA actual output at LRR 1-60
Note the setting instructions on page 40 and proceed as follows:
1. Select the parameter “Sout”.
2. Press and hold the rotary knob until the current value flashes on the display.
3. Set the desired value.
The selectable measuring ranges are:
■
■
LRG1x-60:
0.5 - 20, 100, 200, 500, 1000, 2000 or 6000 µS/cm
■
■
LRG16-61:
50 - 3000, 5000, 7000, 9999 µS/cm
4. Save your set value by pressing the rotary knob for approx. 1 second.
all-guides
com
LRG 1x-6x - Installation & Operating Manual - 819878-00
Changing the unit of the display value (µS/cm or ppm)
The unit of the displayed measured value can be switched between µS/cm and ppm (parts per million).
The conversion from µS/cm to ppm is: 1 µS/cm = 0.5 ppm
Note the setting instructions on page 40 and proceed as follows:
1. Select the parameter “Unit”.
2. Press and hold the rotary knob until the current value flashes on the display.
3. Set the desired display unit (µS or ppm).
Display of the set unit by means of LEDs:
■
■
LED 3 (green)
= µS/cm
■
■
LED 4 (green) = ppm
4. Save your set value by pressing the rotary knob for approx. 1 second.
Triggering a display test manually
Note the setting instructions on page 40 and proceed as follows:
1. Select the parameter “diSP”.
2. Press and hold the rotary knob until the display test starts by showing “....”.
3. The following numbers and decimal points run across the display from right to left:
“...., 1, 2, 3, 4, 5, 6, 7, 8, 9, ....”
4. Check that all numbers and decimal points are displayed correctly.
The display test runs automatically until it has finished, and cannot be interrupted.
5. The display test ends with the message “donE”.
Replacing faulty equipment
Faulty equipment jeopardises system safety.
■
■
If numbers or decimal points are displayed incorrectly or not at all, you must replace the
conductivity electrode with an identical one from GESTRA AG.
Bringing into service
LRG 1x-6x - Installation & Operating Manual - 819878-00
Bringing into service
Notes on bringing into service:
After installing a new or cleaned conductivity electrode, the parameter “tC” must be adapted to the boiler
water. The value of the cell constant “CF” should be monitored and should have the value 0.210.
Comparing the measured value with the reference measurement of a reliable sample
Incorrectly installed or bent conductivity electrodes jeopardise
the system safety through loss of function.
For each bringing into service and after each replacement of the LRG 1x-6x
conductivity electrode, proceed as follows:
■
■
Determine the current conductivity of the boiler water with a reference measurement from a
monitored sample in the desired operating state of the system.
■
■
Compare the measured value with the actual reference measured value.
■
■
Never bring any system into operation without successfully checking the conductivity value.
■
■
For new or cleaned electrodes and identified deviations, the parameter “tC” is to be changed
until the displayed measured value corresponds with the reference measurement. Also see
parameter description “tC” on page 44.
■
■
LRG 1x-6x conductivity electrodes may only be repaired by the manufacturer, GESTRA AG.
■
■
Only replace faulty equipment with identical equipment from GESTRA AG.
Checking the alarm limit value Al.Hi by triggering a test function
Inspect the alarm limit value of the limiter function Al.Hi by triggering the test function by means of the
rotary knob; see page 52.
In this case, the equipment must behave as if there were an alarm.
Lockout function
If the installation requires a lockout function, this must be implemented in the downstream
(safety) circuit. This circuit must conform to the requirements of EN 50156.
LRG 1x-6x - Installation & Operating Manual - 819878-00
Start, operation, alarm and test
Fig. 20
The operating panel:
1
Display of actual value/fault code/limit value - green, 4 digits
2
LED 1, alarm/error, red
3
LED 3, unit µS/cm - green
4
LED 4, unit ppm - green
5
LED 2, function OK - green
6
Rotary knob/push-button for operation and settings
1
2
3
6
4
5
Notes on the display priority of the various messages
Error messages and alarms are displayed based on their priority. Messages with higher priority
are shown continuously before those with low priority. if several messages need attention, the
display does not alternate between them.
Priority 1 = Error messages according to fault code table, see page 54 ff.
Priority 2 = Conductivity MAX alarm
Priority of fault code display
Higher priority fault codes overwrite lower ones on the display!
LRG 1x-6x - Installation & Operating Manual - 819878-00
Allocation of display and LEDs to each operating state of the conductivity electrode:
Start
Switch on
supply voltage
All LEDs light up - test
Display:
S-xx = Software version
t-04 = Equipment type
LRG 1x-60
t-05 = Equipment type
LRG 16-61
The system is started and tested.
The LEDs and display are tested.
Normal operation
The conductivity electrode
is immersed
Display: 1234
LED 1: is Off
LED 3 or 4: lights up green
Display of the current, temperature-compensated
conductivity
Display of the set unit
LED 2: flashes green
The equipment is performing a self-test *
LED 2: lights up green
The self-test is complete - the equipment is OK
* During the self-test phase, the measured value
is not updated.
See the following pages for more information and tables.
Start, operation, alarm and test
LRG 1x-6x - Installation & Operating Manual - 819878-00
Behaviour on the occurrence of alarms
The conductivity electrode
is immersed
The conductivity limit value is
exceeded = Alarm limit value
AL.Hi
Display:
Hi.C and 1234 alternately
LED 1:
Alarm LED lights up red
The alarm signal and the actual measured value
are displayed alternately
The MAX alarm is active
LED 3 or 4: lights up green
Display of the set unit
LED 2: flashes green
The equipment is performing a self-test
LED 2: is OFF
MAX alarm occurrence
■
■
The alarm state is transferred to the URS 60/URS 61 safety control unit via CAN data telegram.
■
■
Once the time delay has elapsed, the alarm signal triggers the safety shutoff.
■
■
The signal outputs are activated.
■
■
The URS 60/URS 61 safety control unit does not automatically lock the safety contacts.
Behaviour in the event of an error (fault code display)
The conductivity electrode
is immersed or not immersed.
There is an error.
Display:
e.g. E005
LED 1:
Alarm LED lights up red
A fault code is permanently displayed;
fault code display see page 54
There is an active error
LED 3 or 43: lights up green
Display of the set unit
LED 2: flashes green
The equipment is performing a self-test
LED 2: is OFF
Error or internal fault
■
■
The error or fault state is transferred to the URS 60/URS 61 safety control unit via
CAN data telegram.
■
■
The error causes this unit to execute the safety shutoff without a delay.
■
■
The URS 60/URS 61 safety control unit does not automatically lock the safety contacts.
Electrode alarms and errors faults cannot be acknowledged.
When the alarm or error is cancelled the display also goes blank, and the URS 60/URS 61
safety control unit closes the safety contacts again.
Start, operation, alarm and test
all-guides
com
LRG 1x-6x - Installation & Operating Manual - 819878-00
Start, operation, alarm and test
Test
Checking the safety function by simulating the alarm state
In operating mode:
Press the rotary knob on the
LRG 1x-6x and hold until the
end of the test
or
press associated button 1, 2,
3 or 4 of the URS 60/URS 61
safety control unit and hold
until the end of the test
or
trigger the limiter test for
the LRG 1x-6x conductivity
electrode on the URB 60
or
trigger the test function at the
SPECTORcontrol.
Display:
Hi.C and 1234 alternately
LED 1:
Alarm LED lights up red
The alarm signal and the actual measured value
are displayed alternately
The MAX alarm is active
LED 3 or 4: lights up green
Display of the set unit
LED 2: flashes green
The equipment is performing a self-test
LED 2: is OFF
MAX alarm occurrence
■
■
The URS 60/URS 61 safety control unit or the device combination behaves as if
there were a real alarm; see page 51.
■
■
After the test simulation has been cancelled (letting go of the test button), the
test is concluded and the equipment goes back to normal operation.
Faulty equipment jeopardises system safety.
■
■
If the conductivity electrode does not behave as described above, it may be faulty.
■
■
Perform failure analysis.
■
■
LRG 1x-6x conductivity electrodes may only be repaired by the manufacturer, GESTRA AG.
■
■
Only replace faulty equipment with identical equipment from GESTRA AG.
LRG 1x-6x - Installation & Operating Manual - 819878-00
System errors
Causes
System errors occur if CAN bus components have been incorrectly installed or configured, if the equip-
ment has overheated, if there is interference in the supply network or if electronic components are faulty.
Check the installation and configuration before systematic troubleshooting
Installation:
■
■
Check that the installation location complies with the admissible ambient conditions in terms of
temperature, vibration, interference sources, minimum distances, etc.
Wiring:
■
■
Does the wiring conform to the wiring diagrams?
■
■
Is the bus line polarity correct throughout?
■
■
Is a 120 Ω terminating resistor terminated at the terminal devices of the CAN bus line?
Configuration of the conductivity electrodes:
■
■
Is the conductivity electrode set to the correct limiter ID 1,2,3,4,5,6,7,8?
■
■
Limiter IDs must not be assigned in duplicate.
Baud rate:
■
■
Is the cable length correct for the set baud rate?
■
■
Is the baud rate identical for all units?
ATTENTION
Interrupting the CAN bus causes a system shutdown and triggers an alarm.
■
■
Bring the system into a safe operating mode before commencing work on the system
installation!
■
■
Switch off the voltage to the system and secure so that it cannot be switched back on.
■
■
Check that the system is not carrying live voltage before commencing work.
LRG 1x-6x - Installation & Operating Manual - 819878-00
System errors
Indication of system malfunctions using fault codes
Fault code table
Fault code
Internal
designation
Possible faults
Remedy
E.001
LFKurzschlussErr
Short circuit in the LF measurement
(electrode wires)
Replace the conductivity electrode
E.002
LFKabelbruchErr
Cable break in the LF measurement
(electrode wires)
Check installation location.
Is the electrode immersed?
Replace the conductivity electrode
E.003
Ch1Ch2LFDiffErr
Difference of the redundant measuring
channels of the LF measurement too high
Replace the conductivity electrode
E.004
PtMinTempErr
Minimum temperature at Pt1000 fallen
below or short circuit
Check installation location.
Replace the conductivity electrode
E.005
PtMaxtempErr
Maximum temperature at Pt1000 exceed-
ed or cable break
Check installation location.
Replace the conductivity electrode
E.006
Ch1Ch2PtDiffErr
Difference of redundant Pt1000 measure-
ment too high
Replace the conductivity electrode
E.007
USIGTSTErr
Measuring voltage of test signal outside
limits
Replace the conductivity electrode
E.008
ISIGTSTErr
Measuring current of test signal outside
limits
Replace the conductivity electrode
E.009
ADCTSTErr
Measuring voltage of Pt1000 test outside
limits
Replace the conductivity electrode
E.010
ICONErr
Measuring current of Pt1000 test outside
limits
Replace the conductivity electrode
E.011
ADVTSTErr
Comparison of AD converter 12 bit/16 bit
outside tolerance
Replace the conductivity electrode
E.012
FREQTSTErr
Frequency of test signal
outside limits
Replace the conductivity electrode
E.013
VMessErr
Control voltage of 4-20 mA output (only
LRGT models)
Replace the conductivity electrode
OK
!
+
-
1
Fig. 21
1
Display of actual value/fault code/limit value - green, 4 digits
LRG 1x-6x - Installation & Operating Manual - 819878-00
Fault code table
Fault code
Internal
designation
Possible faults
Remedy
E.014
ADSReadErr
16 bit AD converter
not responding
Replace the conductivity electrode
E.015
UnCalibErr
Calibration invalid
Replace the conductivity electrode
E.017
ENDRVErr
Second shutoff path of 4-20 mA
current output faulty
Replace the conductivity electrode
E.018
V12NegErr
System voltage -12 V outside limits
Replace the conductivity electrode
E.019
V6Err
System voltage 6 V outside limits
Replace the conductivity electrode
E.020
V5Err
System voltage 5 V outside limits
Replace the conductivity electrode
E.021
V3Err
System voltage 3 V outside limits
Replace the conductivity electrode
E.022
V1Err
System voltage 1 V outside limits
Replace the conductivity electrode
E.023
V12Err
System voltage 12 V outside limits
Replace the conductivity electrode
E.024
CANErr
Communication failure
Check the baud rate, wiring and
terminating resistors
E.025
ESMG1Err
µC fault
Replace the conductivity electrode
E.026
BISTErr
µC periphery self-test fault
Replace the conductivity electrode
E.027
OvertempErr
PCB/ambient
temperature > 75 °C
Check installation location. Lower the
ambient temperature of the terminal
box (cool if necessary)
All fault codes not listed here, e.g. E.016, are available as reserves
Virtually all of the aforementioned fault codes can be caused by EMC interference. This is less
likely to be the case in the event of permanent faults, but should be considered for sporadic
fault messages.
The installation should then be examined for a correctly wired shield and the general
EMC before the electrode is replaced.
System errors
LRG 1x-6x - Installation & Operating Manual - 819878-00
System errors
Errors without shutoff
The displayed conductivity fluctuates, moisture in the area of the cover tube of the electrode
Possible causes if no fault messages are present
Remedy
From outside, moisture enters into the
cover tube.
■
■
Check the installation location for possible water leak-
ages from which the water/steam could enter into the
conductivity electrode.
■
■
Check the seal of the conductivity electrode.
■
■
Is the containment of the electrode executed as per the
specifications?
■
■
Only replace the conductivity electrode with equipment
from GESTRA AG that is identical in construction.
The inner seals of the electrode rods
are damaged.
■
■
Only replace the conductivity electrode with equipment
from GESTRA AG that is identical in construction.
The displayed conductivity shows rare but sporadically recurring extreme values.
Possible causes if no fault messages are present
Remedy
The electrode rods are not permanently immersed.
■
■
Check the executed installation using the Manual.
■
■
Note the installation examples and the specified mini-
mum distances.
Flashing values from t-71 to t-75 appear on the display
Possible causes
Remedy
The ambient temperature of the terminal box of the
electrode is high, between 71 °C and 75 °C.
If the temperature rises above 75 °C, the fault code
E.027 (OvertempErr) appears and the system is
shutoff.
■
■
The ambient temperature in the area of the terminal box
must be reduced, e.g. by cooling.
The message CF.Hi flashes on the display
Possible causes
Remedy
The cell constant is inadmissibly high after the calibra-
tion procedure “CAL” or after manual adjustment
LRG 1x-6x CF > 3.0
■
■
Remove the conductivity electrode;
see page 58.
■
■
Check and clean the electrode; see page 59
System errors
all-guides
com
LRG 1x-6x - Installation & Operating Manual - 819878-00
Checking installation and function
When you have remedied system errors, perform a function test as follows.
■
■
Checking installation and function.
■
■
Perform an equipment test; see page 52. In this case, the equipment must behave as if there were
an alarm.
■
■
When bringing into service and after each replacement of the LRG 1x-6x conductivity electrode
the displayed measured value and the set alarm limit value must be checked and an equipment test
must be performed.
System errors in the LRG 1x-6x conductivity electrode also trigger a system error
in the URS 60/URS 61 safety control unit. The output contacts open without a delay and the
relevant signal output is activated.
If you require assistance, please tell us the indicated fault code.
In the event of errors or faults that cannot be remedied with the aid of this Installation & Opera-
ting Manual, please contact our service centre or authorised agent in your country.
LRG 1x-6x - Installation & Operating Manual - 819878-00
Taking out of service/Disassembly
DANGER
Danger to life from scalding caused by sudden escape of hot steam.
Hot steam or hot water can escape suddenly if conductivity electrodes are unscrewed under
pressure.
■
■
Reduce the boiler pressure to 0 bar and check the pressure before unscrewing the conduc-
tivity electrodes.
■
■
Only remove conductivity electrodes at a boiler pressure of 0 bar.
WARNING
Hot conductivity electrodes can cause severe burns.
The conductivity electrodes are extremely hot during operation.
■
■
Perform installation and maintenance work only on conductivity electrodes that have been
allowed to cool.
■
■
Only remove conductivity electrodes that have cooled down.
Proceed as follows:
1. Reduce the boiler pressure to 0 bar.
2. Allow the conductivity electrode to cool to room temperature.
3. Switch off the supply voltage.
4. Unplug the connections of the CAN bus control lines and plug them into one another.
5. Next, remove the conductivity electrode.
An alarm is triggered when the CAN bus cable is interrupted.
LRG 1x-6x - Installation & Operating Manual - 819878-00
Cleaning the conductivity electrode
Monthly comparison of the measured values
In line with the recommendations about monitoring the equipment to protect the water quality from
standards DIN EN12952/12953, the measured values must be compared on a monthly basis with reliable
samples by an appropriately qualified and competent person.
If a deviation is discovered, the conductivity electrode must be compared via the “CAL” function;
see page 45.
Cleaning interval
Depending on the operating behaviours, it is recommended that the electrode is cleaned at least once a
year, e.g. as part of maintenance work.
To clean the measuring electrode(s), the conductivity electrode must be taken out of operation
and removed; see page 58.
LRG 16-60/LRG 17-60
1. Loosen the threaded pin J and unscrew the measuring tube K by hand.
2. Clean the electrode rod and the measuring surfaces.
3. Then screw the measuring tube K back on and secure it with the
threaded pin J *.
LRG 16-61
1. Clean the measuring electrodes K*.
Continue with the following points:
* J / K = Key to the overall view; see page 25
LRG 16-60, LRG 17-60, LRG 16-61
1. Use a fat-free cloth to wipe off loose deposits.
Remove stubborn deposits with sandpaper (medium grade).
2. Install the cleaned conductivity electrodes according to the information on page 29.
3. Switch on the supply voltage.
4. Put the equipment or the system into operation; see page 40.
5. Compare the measured value with the directly determined conductivity from a reference measure-
ment; see page 48.
6. Check the safety function by simulating the alarm state; see page 48 / 52.
LRG 1x-6x - Installation & Operating Manual - 819878-00
Disposal
The statutory waste disposal provisions must be observed when disposing of conductivity electrodes.
Returning decontaminated equipment
If goods have come into contact with media that are hazardous to health, they must be
drained and decontaminated before being returned to GESTRA AG!
Such media include solid, liquid or gaseous substances, mixtures of these, or radiation.
GESTRA AG can accept returned goods only if accompanied by a completed and signed return
note and also a completed and signed decontamination declaration.
The return confirmation and decontamination declaration must be attached to the returned
goods and be accessible from the outside. Otherwise, the goods cannot be dealt with and will
be returned, carriage unpaid.
Please proceed as follows:
1. Let GESTRA AG know about the return beforehand by e-mail or phone.
2. Wait until you have received the return confirmation from GESTRA.
3. Return the goods to GESTRA AG together with the completed return confirmation (and
decontamination declaration).
LRG 1x-6x - Installation & Operating Manual - 819878-00
EU Declaration of Conformity
We hereby declare that the LRG 1x-6x conductivity electrode conforms to the following European Direc-
tives:
■
■
Directive 2014/68/EU
EU Pressure Equipment Directive
■
■
Directive 2014/35/EU
Low Voltage Directive
■
■
Directive 2014/30/EU
EMC Directive
■
■
Directive 2011/65/EU
RoHS Directive
Please see our Declaration of Conformity for details on the conformity of our equipment with European
Directives.
The current Declaration of Conformity can be found on the Internet at www.gestra.com or requested from
us.