IFM Electronic efector300 E40212 Operating Instructions
Text of the manual
1 Functions and features
E40211
Teach button for setting the SC flow sensors with PNP output
E40212
Teach button for setting the SC flow sensors with normally open relay
output
2 Electrical connection
1
2
1: Connector (socket) - connection to SC flow sensor
2: Connector (plug) - connection to supply voltage
E40211
SC
E40211
4
1
3
2
n.c.
L1
L+
N
L
n.c.
1
2
4
5
3
n.c.
E40212
L1
L+
N
L
SC
E40212
4
1
3
2
n.c.
n.c.
1
2
4
5
3
n.c. = not connected
3 Switch point setting
►Press button briefly and release it.
►After 1 - 2 s press it again and keep it pressed for the time indicated.
> The flow sensor gives its output signals to the teach button. They are displayed
by the illuminated pushbutton:
Output closed (OUT = 1)
button lights
Output closed (OUT = 0)
button does not light
Button
OUT = 1
OUT = 0
Time window
Duration [s]
Within the time windows A, B, C the output is switched depending on the flow: output closed
(OUT = 1/ button lights) if flow ≥ SP / output open (OUT = 0 / button does not light) if flow < SP.
If flow rises or falls within the time windows A, B, C the switching status / display of the il-
luminated pushbutton can change.
In the time windows D, E, F the output is used for feedback signals (-> table below). It does
not react to flow changes.
Time window
Operation
A
Initialisation of the setting operation.
B
Confirmation of the initialisation.
C
Setting of the switch point (SP)*
Push of the button in s
5
10
15
20
...
55
60
65
corresponds to SP in
cm/s
min.
10
15
20
...
55
60
max.
D
The last switching status from C is maintained (= internal monitoring).
E
Output signal is inverted (= confirmation of the setting);
duration = setting time of the selected switch point
F
Output signal is inverted again (= internal monitoring), then this new switch
point is active.
* Accuracy: ± 1s
min.: flow < 10 cm/s; max.: flow > 60 cm/s