3” to 24” Diameter Vent For use on Positive, Neutral and
Negative Pressures up to 35” W.C.
Also for venting listed gas or oil fired appliances listed for
venting with TYPE L low temperature venting system
(DSD / DSID ONLY)
MODEL DuraSeal® DS/DSD/DSID
Single Wall or Double Wall AL29-4C® or 316L.
Special Gas Vent for Category I, II, III and IV.
TYPE L VENT Low temperature venting system
SUBMITTAL RECORD
SFDS REV. 11 08-07-19
Reference to the installation instructions will enable you to obtain a safe,
efficient and dependable installation of this vent system. Please read
and understand these instructions before beginning your installation.
Do not alter or modify the components of this chimney system under
any circumstances. Any modification or alteration of the vent system
or approved accessories, including but not limited to the appliance
it is connected to, may void the warranty, listings and approvals of
this system and could result in an unsafe and potentially dangerous
installation.
A. Examine all components for possible shipping damage prior to
installation;
B. Proper joint assembly is essential for a safe installation. Follow
these instructions exactly as written: Check severeness of joints
upon completion of assembly;
C. This venting system must be free to expand and contract. This venting
system must be supported in accordance with these instructions;
D. Check for unrestricted vent movement through walls, ceilings, and
roof penetrations;
E. Different manufacturers have different joint systems and adhesives.
Do not mix pipe, fittings, or joining methods from different manu-
facturers.
Listed to standards:
UL-1738
ULC-S636
UL-641
ULC-S609
Report # G100215896MTL-006
MODEL DS
MODEL DSD
MODEL DSID
SUBMITTAL RECORD
PREPARED FOR:
REFERENCE:
LOCATION:
CONTACT:
TELEPHONE:
FAX:
EMAIL:
PREPARED BY:
} DSD / DSID ONLY
Material Selection
FLUE (INNER WALL)
AL29-4C
316L
TABLE OF CONTENTS
Introduction ................................................................................. page
2
Testing / listing information ......................................................... page
2
Clearances to combustibles ......................................................... page
3
General installation requirements ................................................ page
3
Typical installations .................................................................... page 4-5
Chimney and fitting joint assembly .............................................. page
6
Chimney weight ........................................................................... page
6
Support methods and height ....................................................... page
7
Horizontal installation requirements ............................................ page
8
Maintain proper slope ................................................................. page
9
Vertical installation requirements ................................................ page
9
Wall penetration .......................................................................... page 10
Roof / floor penetration ............................................................... page 10
Condensate drains ...................................................................... page 10
DuraSeal as a liner ...................................................................... page 12
Adjustable length ........................................................................ page 13
DuraSeal Flex .............................................................................. page 14
Maintenance instructions ............................................................. page 15
DuraSeal Labels ........................................................................... page 16
Warranty ...................................................................................... page 44
Product reference information ...................................................... page 48
INTRODUCTION
DuraSeal® single wall (DS) or double wall (DSD) or double wall insulated
(DSID) is a special stainless steel vent system for gas fired appliances listed
as Category I, II, III, and IV or in Canada as Type BH Gas Venting as noted
in ULC-636, with a maximum operating temperature of 550 Degrees F (288
Degrees C), and a maximum rated positive pressure of 35” Water Column. It
can also vent listed gas or oil fired appliance rated to be vent with TYPE L low
temperature venting system (DSD & DSID only). DuraSeal must be installed
by an experienced professional familiar with the operation and maintenance
of heating appliances and venting. Before installing this product, examine all
components for possible shipping damage and read the complete installation
manual. Failure to follow proper installation procedures, including vent pitch
and improper appliance connections, may cause unsafe conditions. DuraVent
recommends the system to be inspected once a year by a qualified service
technician
TESTING / LISTING INFORMATION
DuraVent DuraSeal model DS, DSD and DSID venting system is listed with
Intertek Testing Services (ETL) to UL/ULC standards:
U.S.A.
•
UL-1738
Special Gas Vent for Category I, II, III
and IV appliances
•
UL-641 (DSD & DSID only)
TYPE L VENT venting listed gas
or oil burning appliances
CANADA
•
ULC-S636
Type BH Gas Vent Class I/II
•
ULC-S609 (DSD & DSID only)
TYPE L VENT venting of flue gases with temperature not exceeding 300°C
from oil or gas burning appliances
This product must be installed in accordance with local building code require-
ments as well as National codes: USA - National Fuel Gas code ANSI-Z223.1
or NFPA Standard 54, or NFPA 211. In CANADA - CAN/CGA-B149.1 or CAN/
CGA-B149.2 Propane Installation Code as applicable.
CLEARANCES TO COMBUSTIBLES
Table 1 shows the required MINIMUM AIRSPACE CLEARANCE TO COMBUS-
TIBLES. “Combustibles” include framing lumber, drywall, plywood, paneling,
insulation, wiring and other building materials.
Minimum Clearance to Combustibles Single Wall DS
Diameter
Rated
operating
temperature
Max.
operating
temperature
Enclosed
(4 sides)
Unenclosed
(2 sides Max.)
Horiz.
Vert.
Horiz.
Vert.
3” to 12”
480º F
(250º C)
550º F
(288º C)
N/A
N/A
2”
2”
14” to 24”
480º F
(250º C)
550º F
(288º C)
N/A
N/A
4”
4”
Minimum Clearance to Combustibles Double Wall DSD / DSID
Diameter
Rated
operating
temperature
Max.
operating
temperature
Enclosed
(4 sides)
Unenclosed
(2 sides Max.)
Horiz.
Vert.
Horiz.
Vert.
3” to 12”
480º F
(250º C)
550º F
(288º C)
N/A
1”
1”
1”
14” to 24”
480º F
(250º C)
550º F
(288º C)
N/A
1”
3”
1”
3” to 12”
L-VENT
480º F
(250º C)
550º F
(288º C)
N/A
2”
2”
2”
14” to
24”
L-VENT
480º F
(250º C)
550º F
(288º C)
N/A
2”
3”
2”
Table 1 - Minimum Clearances for DuraSeal®
Auxiliary parts such as combination Roof Supports, Roof Thimble, Flashings
and Wall Thimble outer shields are intended to be attached directly to the
framing or to ceilings, floors, or walls in accordance with their respective
instructions. These parts, which are installed in contact with wood or other
combustibles, are designed and tested to assure that they do not overheat
at points of contact.
Notes:
1. Unenclosed requires at least two sides open.
2. Single Wall (DS) may be enclosed only in non-combustible enclosure.
3. Reduced clearances may be attained by using non-combustible enclosures.
4. Combustible Material is any material made of or surfaced with wood,
compressed paper, plant fibers or other materials that are capable of being
ignited or burned. Such material shall be considered combustible even
though it is flame-proofed, fire-retardant treated, or plastered. (Source:
NFPA 54/ANSI Z223.1)
5. Design any enclosure to permit inspection of the system.
6. Do not place insulation in any required clearance spaces surrounding the
vent system unless these instructions suggest otherwise and the insulation
is specified or supplied.
7. When using Viton caulking, follow the manufactures required drying times.
GENERAL INSTALLATION REQUIREMENTS
When venting Category I, II, III, or IV appliances or TYPE L vented appliance,
DuraSeal must be used for the entire length of the system. Do not mix pipe,
fittings, or joining methods from different manufacturers. See the DuraSeal
catalog for a complete list of parts and products. Every vent system
must be planned and installed for optimum performance and safety. The
venting system must be free to expand and contract and must be supported
in accordance with these instructions. (Check for unrestricted vent movement
through walls, ceilings, and roof penetrations). Refer to the gas appliance
manufacturer’s instructions to determine venting requirements and limitations
with respect to installation and use of the appliance. It is the responsibility
of the installer to contact local building and fire officials concerning
any installation restrictions and/or inspection requirements that may
apply. Permits may be required before starting an installation.
• If required by the appliance manufacturer, a Drain Tee Cap must be
located as close as possible to the appliance flue outlet. Depending on
the arrangement of the vent, more than one drain may be required.
Unless a Drain Tee Cap is supplied with the appliance, install a DuraSeal
Drain Tee Cap.
• More than one Category II, III or IV appliance may not be connected into
the same vent system, unless the appliance manufacturer specifically
approved such a system and the appliance are designed for multiple
venting. Cat. II, III or IV appliances MAY NOT be common vented with Cat.
I, natural draft appliances. This limitation can be removed if an engineering
analysis demonstrates normal and safe operation of appliances.
• DuraSeal must not come in contact with plumbing or electrical systems.
• Maintain rated clearances to combustibles over the entire length of the
vent system.
• DuraSeal shall not be routed into, through, or within any vent, such as an
existing masonry or factory-built chimney, that is connected to another
appliance.
Material Thickness
*all seams are laser welded
DuraSeal DS
DuraSeal DSD / DSID
Diameter
Flue
Diameter
Flue
Casing
3” to 9”
AL29-4C - .015”
316L - .015”
3” to 9”
AL29-4C - .015”
316L - .015”
441 stainless - .015”
10” to 16”
AL29-4C - .020”
316L - .019”
10” to 16”
AL29-4C - .020”
316L - .019”
441 stainless - .020”
18” to 24”
AL29-4C - .024”
316L - .024”
18” to 24”
AL29-4C - .024”
316L - .024”
441 stainless - .024”
Material Code Designations
B
Type 316 Stainless Steel
H
Type 430 Stainless Steel
K
Type 441 Stainless Steel
P
Type 439 Stainless Steel
U
Type AL29-4C Stainless Steel
PART NUMBERS
These instructions identify major model DS-DSD-DSID parts by name and part number.
Example:
DSD 36” length with inside diameter 14” made of AL29-4C inner flue and
SS441 outer casting.
DS 30° elbow with inside diameter 22” made of 316L.
DSD wall support for 8” diameter chimney made of stainless 439.
DSD
14
L36
UK
Model
Dia.
Part
Material
DS
22
E30
B
Model
Dia.
Part
Material
DSD
8
WSHD
P
Model
Dia.
Part
Material
Cables, rods or
braces By other
500 lbs rated
Minimum slope
1/4” per foot
Minimum Clearances
See table 1
Maximum distance between
support (MHS), see table 6
30º Termination
(STA)
Opening dimension
See table 6
Wall Thimble
(WT/WTI)
Roof Support
(RS)
Suspension Band (SB)
Anchor Plate HD
(APHD)
Appliance
Maximum distance
suspended (S), see table 6
Figure 1 - Horizontal
Refer to condensate drain
section for proper installation
Appliance
adaptor
Exit Cone (EC)
Guy wires by others
500 lbs rated
Flashing
(F)
Roof
support
(RS)
Guy Support
(GS)
Wall guide
(WG)
Wall guide
(WG)
Wall support HD
(WSHD)
Appliance
Wall support
(WS)
Roof
thimble
(RT/RTI)
Maximum distance
between guides (MVS)
See table 6
Opening
dimension
See table
7,8 & 9
Minimum
Clearance
See table 1
Maximum distance
between supports
See table 4 & 5
Maximum distance
between elbows without
any support or guide
See table 6 (MDE)
Maximum distance
between guides
See table 6 (MVS)
Maximum distance
between supports
See table 4 & 5
Maximum free-
standing height
See table 6 (H)
Figure 2 - Vertical
Appliance adaptor
CHIMNEY AND FITTING JOINT ASSEMBLY
All components have a male and female end, the male end has the gasket.
The installation orientation is indicated on the labeling of each chimney section
with an arrow. The arrow indicated the direction of the flow.
CHIMNEY WEIGHT
Chimney weight is given in pounds per foot of each diameter. It is important
to know the weight of the chimney section for chimney support or guiding.
Chimney weight (table 3) along with the maximum chimney height (table 4)
is necessary to calculate the proper anchor strength needed with supports.
1. Add a thin film of
silicone lubricant
on the o-ring.
2. Insert the male
end into the
female end.
3.Close the clips to
secure the joint.
NOTE:
Clips are self-locking
Figure 3 - Joint assembly steps
Figure 4 - Opening clips
DuraSeal® DS
DuraSeal DSD / DSID
CHIMNEY WEIGHT IN LB/FT
INSIDE DIAMETER
DS
DSD
DSID
3”
0.7
1.7
2.1
4”
0.9
2.1
2.6
5”
1.1
2.6
3.0
6”
1.3
3.0
3.4
7”
1.5
3.4
3.9
8”
1.7
3.8
4.3
9”
1.9
4.3
N/A
10”
2.1
4.7
5.5
12”
2.6
6.2
7.0
14”
3.6
7.7
8.2
16”
4.1
8.7
9.3
18”
4.6
9.8
10.3
20”
5.1
10.8
11.3
22”
5.7
11.8
12.4
24”
6.2
12.8
N/A
Table 3 - Chimney weight
Example: Model DuraSeal DSD 6” diameter section of 25 feet in length from
table 3, weight in lb/ft = 3. Total length 3 x 25 = 75lbs.
ASSEMBLY JOINT DS/DSD/DSID LUBE REQUIREMENT
Inside diameter
Qty (oz)
3”
0.1
4”
0.1
5”
0.1
6”
0.1
7”
0.1
8”
0.2
9”
0.2
10”
0.2
12”
0.3
14”
0.3
16”
0.3
18”
0.4
20”
0.4
22”
0.5
24”
0.5
Table 2
To open clips, push the secondary catch while pulling up the lever
Push
Pull Up
SUPPORT METHODS AND HEIGHT
1. Several support and guiding methods are used to anchor a chimney
against upward, downward and angular placement.
2. These supports and guides prevent bending stresses on the chimney
elbows and joints.
3. Certain limitations apply for proper installation of supports and guides.
See tables 4 and 5.
4. See figure 1 and 2 for typical installations.
MAXIMUM CHIMNEY HEIGHTS AND SUPPORT METHOD FOR MODEL DS
Inside
dia.
Anchor
Plate
(AP)
Anchor
Plate
HD
(APHD)
Anchor
Plate
Length
(APL)
Wall
Support
(WS)
Wall
Support
HD
(WSHD)
Roof
support
(RS)
Guy
support
(GS)
3”
200
200
200
100
200
100
250
4”
200
200
200
100
200
100
250
5”
195
195
195
97.5
195
97.5
225
6”
190
190
190
95
190
95
190
7”
185
185
185
92.5
185
92.5
160
8”
180
180
180
90
180
90
140
9”
175
175
175
87.5
175
87.5
130
10”
170
170
170
85
170
85
115
12”
160
160
160
80
160
80
90
14”
150
150
150
75
150
75
65
16”
140
140
140
70
140
70
60
18”
130
130
130
65
130
65
55
20”
120
120
120
60
120
60
50
22”
110
110
110
55
110
55
45
24”
100
100
100
50
100
50
40
MAXIMUM CHIMNEY HEIGHTS AND SUPPORT METHOD FOR MODEL DSD
Inside
dia.
Anchor
Plate
(AP)
Anchor
Plate
HD
(APHD)
Anchor
Plate
Length
(APL)
Wall
Support
(WS)
Wall
Support
HD
(WSHD)
Roof
support
(RS)
Guy
support
(GS)
3”
100
100
100
50
100
50
115
4”
100
100
100
50
100
50
115
5”
97.5
97.5
97.5
48.75
97.5
48.75
95
6”
95
95
95
47.5
95
47.5
80
7”
92.5
92.5
92.5
46.25
92.5
46.25
70
8”
90
90
90
45
90
45
65
9”
87.5
87.5
87.5
43.75
87.5
43.75
55
10”
85
85
85
42.5
85
42.5
50
12”
80
80
80
40
80
40
40
14”
75
75
75
37.5
75
37.5
30
16”
70
70
70
35
70
35
27
18”
65
65
65
32.5
65
32.5
25
20”
60
60
60
30
60
30
22
22”
55
55
55
27.5
55
27.5
21
24”
50
50
50
25
50
25
20
Table 4 - Dimensions are in feet
MAXIMUM CHIMNEY HEIGHTS AND SUPPORT METHOD FOR MODEL DSID
Inside
dia.
Anchor
Plate
(AP)
Anchor
Plate
HD
(APHD)
Anchor
Plate
Length
(APL)
Wall
Support
(WS)
Wall
Support
HD
(WSHD)
Roof
support
(RS)
Guy
support
(GS)
3”
95
95
95
47.5
95
47.5
80
4”
95
95
95
47.5
95
47.5
80
5”
92.5
92.5
92.5
46.25
92.5
46.25
70
6”
90
90
90
45
90
45
65
7”
87.5
87.5
87.5
43.75
87.5
43.75
55
8”
85
85
85
42.5
85
42.5
50
9”
N/A
N/A
N/A
N/A
N/A
N/A
N/A
10”
80
85
85
42.5
85
42.5
40
12”
75
75
75
37.5
75
37.5
30
14”
70
70
70
35
70
35
27
16”
65
65
65
32.5
65
32.5
25
18”
60
60
60
30
60
30
22
20”
55
55
55
27.5
55
27.5
21
22”
50
50
50
25
50
25
20
24”
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Table 5 - Dimensions are in feet
Figure 5 - Position of support
*Important Notes:
1. For Anchor Plate (AP) / Anchor Plate Heavy Duty (APHD) / Wall Support
Heavy Duty (WSHD), the support must be installed below a bead. See
figure 5.
2. For Wall Support (WS) / Roof Support (RS) , the support can be installed
anywhere on the part.
3. For Anchor plate length, the support is already integrated to a length. Directly
attached to the building structure or supported by non combustible structural
elements (not included). No other installation is required than the standard
installation for a regular length.
Anchor plate,
Anchor plate HD or
Wall support HD
A. Pass the female end through the
hole of the one part plate.
B. Install the two parts plate below
a bead and bolt it to the one part
plate.
Bead
Bead
Bolts and
nuts
Two parts
plate
One part plate
HORIZONTAL INSTALLATION REQUIREMENTS
• When venting through a sidewall, terminate the system not less than 12” (.3m)
above the ground and above the snow line in geographical areas where snow
accumulates. The termination area must be kept clear of snow and ice at all
times.
• Terminate the system at least 7’ (2.1m) above a public walkway or driveway,
no less than 6’ (1.8m) from the combustion air intake of any appliance or 3’
(.9m) from any other building opening, gas utility meter, service regulator or
the like. Less distance is permitted if specified in the appliance’s installation
instructions. It also shall terminate at least 3’ (.9M) above any forced air inlet
within 10’ (3.1m) and shall terminate at least 4’ (1.2m) below, 4’ horizontally
from, or 1’ (.3m) above any door, window, or gravity air inlet into any building
as provided in the National Fuel Gas Code ANSI Z223.1 and NFPA 54. See
figure 6. Proper judgment may require greater distances depending on the
side of the equipment installed or to allow for snow drifting or falling from
falling from overhead roofs or trees. The termination should be far enough
away from trees, shrubs, or decorative items to prevent damage.
• The total horizontal vent length from the appliance flue collar to the outside
termination shall be in accordance with the appliance manufacturer’s instruc-
tions.
SUPPORT AND GUIDE SPACING FOR MODEL DS
Inside
diameter
MVS
MHS
MDE
H
S
Interior
Exterior
3”
10
8
12
12
10
50
4”
10
8
12
12
10
100
5”
10
8
12
12
10
100
6”
10
8
12
12
10
100
7”
10
8
12
12
10
100
8”
10
8
12
12
10
100
9”
10
8
12
12
10
100
10”
10
8
12
12
10
100
12”
10
8
12
12
10
100
14”
10
8
12
12
10
100
16”
10
8
12
12
10
100
18”
10
8
12
12
10
100
20”
10
8
12
12
10
100
22”
10
8
12
12
10
100
24”
10
8
12
12
10
100
SUPPORT AND GUIDE SPACING FOR MODEL DSD & DSID
Inside
diameter
MVS
MHS
MDE
H
S
Interior
Exterior
3”
10
8
12
12
10
50
4”
10
8
12
12
10
50
5”
10
8
12
12
10
50
6”
10
8
12
12
10
50
7”
10
8
12
12
10
50
8”
10
8
12
12
10
50
9”
10
8
12
12
10
50
10”
10
8
12
12
10
50
12”
10
8
12
12
10
50
14”
10
8
12
12
10
50
16”
10
8
12
12
10
50
18”
10
8
12
12
10
50
20”
10
8
12
12
10
50
22”
10
8
12
12
10
50
24”
10
8
12
12
10
50
Table 6 - Dimensions are in feet
MVS : Maximum Vertical Spacing between Guides/Supports
MHS: Maximum Horizontal Spacing between Guides/Supports
MDE: Maximum Distance between Elbows
H: Maximum Freestanding Height above the Roof
S: Maximum Suspended Length
7 ft above
public
walkways
and drives
1 ft. above doors and windows
4 ft below any
window or fresh
air inlet
1 ft. above ground
or snow line
Sidewalk
Figure 6 - Horizontal termination requirements
MAINTAIN PROPER SLOPE
• Install with a continuous 1/4” per foot (minimum) slope, as is required by the
National Fuel Gas Code for all gas-fired appliances.
• Vent systems for condensing appliances must have a continuous 1/4” per foot
(minimum) slope toward the appliance or a condensate drain. Always check
the appliance manufacturer’s instructions for proper drain requirements.
• DuraSeal® offers a range of tees and elbows that are built incorporating a 2
degree slope, we recommend that you use these to generate your slope.
• Some appliances require the venting system to be sloped toward the horizontal
termination.
• Remember, if you raise the appliance or lower the ceiling you must adjust
the slope of the vent to maintain the 1/4” per foot minimum.
4 ft. horizontally from
door and windows
Figure 7 - Vertical installation requirements
VERTICAL INSTALLATION REQUIREMENTS
1. The vent system must terminate at least 3 feet above the roof line and
at least 2 feet higher than any portion of the building within 10 feet.
See figure 7. This limitation can be removed if an engineering analysis
demonstrates normal and safe operation of appliance.
2. When terminated at a height of more than 10 feet, the stack must be
supported by a Guy Section.
3. The vent system must terminate with one of the DuraSeal® terminations.
Except;
a) Category I appliances (natural draft) must use a Rain Cap. It is optional
on Category II. This limitation can be removed if an engineering analysis
demonstrates normal and safe operation of appliance.
b) Vent systems without provisions for draining rain water must use a Rain
Cap.
c) Terminations or approved mechanical vent devices specified or provided
by the appliance manufacturer are permitted.
4. The total continuous distance of the vent system from the appliance flue
collar to the termination shall not exceed that specified in the appliance
manufacturer’s installation instructions. When venting natural draft ap-
pliances the termination must be at least 5 feet above the topmost draft
hood. Otherwise a listed mechanical draft inducing device is required.
This limitation can be removed if an engineering analysis demonstrates
normal and safe operation of appliance.
5. In general, systems installed in cold climates perform best, and conden-
sation is reduced, when the system is fully enclosed by some part of the
building structure or by using insulated SSID venting system.
6. In cold climates do not install a condensate drain on the exterior of the
building. Doing so may result in dangerous icy conditions on surfaces near
the drain and may cause damage to the vent system and/or the building
exterior. Security Chimneys will NOT be held liable for any personal injury
or property damage due to any formation of ice.
7. Vertical supports are required after every transition to vertical. Vertical
supports are also required after every offset elbow.
8. Unless DuraSeal is installed in a fire rated shaft, a roof thimble and support
is required when penetration fire rated floors, walls or ceilings.
10’
2’
2 ft. above structures within 10 ft.
ROOF / FLOOR PENETRATION
1. A roof thimble (RT) or roof thimble insulated (RTI) for cold climate must be installed
every time the vent system passes through a floor or roof.
2. Prepare the roof / floor by cutting a square opening. See table 6.
3. Install the roof thimble. You may cut the radiation sleeve if it is too long. See
figure 9.
4. For roof installation, install a flashing.
Roof support
Roof thimble
Opening dimension
See table 6
Air gap
or insulated
Flashing
CONDENSATE DRAINS
When an internal condensate drain is NOT part of the appliance:
1. A Drain length (DL) or a Tee with a drain tee cap (DTC) is strongly recommended.
Install this drain as close as possible to the appliance flue collar.
2. A condensate drain is required for every 30 feet of horizontal vent and at the bottom
of a vertical stack.
3. Use the Drain length for a straight horizontal run. Rotate the fitting so that the
drain tube is as vertical as possible.
4. Use a Tee at a transition from horizontal to vertical, and attach the Drain Tee Cap
to the appropriate branch of the tee.
5. A condensate drain tube kit is available to direct the condensate to an appropriate
location. A trap loop must be formed into the drain hose and must be a diameter
that is at least four times the appliance’s rated stack pressure in inches of water
column or minimum 3 inches. Secure the loop with a cable tie.
6. Flue gas condensate can have a low (3 to 5) PH level, follow all local and national
codes and regulations for the draining of acidic condensate.
7. In cold climate, do not install a condensate drain on the exterior of the building.
Doing so may result in dangerous icy conditions on surfaces near the drain and
may cause damage to the vent system and the building exterior. DuraVent will
NOT be held liable for any injury or property damage due to formation of ice.
Figure 8 - Wall penetration
WALL PENETRATION
1. Prior to installation, determine proper location of wall thimble (WT) or wall thimble
insulated (WTI) so that a minimum slope of 1/4” (6mm) per foot is maintained in
the horizontal section of vent to ensure proper flow of condensation.
2. Prepare the wall by cutting a square opening. See table 6 for opening dimension.
3. Install the wall thimble by inserting the larger of the two parts on the appliance
(interior side). See figure 8.
4. Next, apply a bead of sealant around the edges of the exterior (smaller of the
two parts) wall thimble component. Then install this part of the wall thimble by
inserting the smaller collar into the other component from the previous step.
NOTE: The two horizontal cylinders of the thimble must engage a
minimum of two inches.
5. Fasten both sides of the wall thimble using screws or nails.
6. Once the thimble is installed, DuraSeal® vent pipe can be inserted into
the thimble.
7. Close the gap between the thimble and the vent by installing the two half
plate and fasten it using screws or nails.
8. Install horizontal termination to complete the assembly.
9. Once assembly is completed, apply a bead of high-temp sealant around
the pipe and the exterior two half plates of the thimble to protect against
weather.
10. The air gap is filled with insulation when using the insulated wall thimble
(WTI).
Add sealant
Termination
Two half plate
Wall Thimble
(WT/WTI)
Air gap or
insulated
Opening dimension
See table 6
2” Minimum overlap
Figure 9 - Roof penetration
OPENING DIMENSIONS FOR WALL/ROOF PENETRATION
FOR MODEL DS
Inside
diameter
Wall
Thimble
(WT)
Wall
Thimble
Insulated
(WTI)
Roof
Thimble
(RT)
Roof
Thimble
Insulated
(RTI)
3”
8x8
9x9
7x7
11x11
4”
9x9
10x10
8x8
12x12
5”
10x10
11x11
9x9
13x13
6”
11x11
12x12
10x10
14x14
7”
12x12
13x13
11x11
15x15
8”
13x13
14x14
12x12
16x16
9”
14x14
15x15
13x13
17x17
10”
15x15
16x16
14x14
18x18
12”
17x17
18x18
16x16
20x20
14”
22x22
22x22
22x22
22x22
16”
24x24
24x24
24x24
24x24
18”
26x26
26x26
26x26
26x26
20”
28x28
28x28
28x28
28x28
22”
30x30
30x30
30x30
30x30
24”
32x32
32x32
32x32
32x32
Table 7 - Dimensions are in inches
OPENING DIMENSIONS FOR WALL/ROOF PENETRATION
FOR MODEL DSID
Inside
diameter
Wall
Thimble
(WT)
Wall
Thimble
Insulated
(WTI)
Roof
Thimble
(RT)
Roof
Thimble
Insulated
(RTI)
3”
10x10
11x11
7x7
11x11
4”
13x13
14x14
10x10
14x14
5”
14x14
15x15
11x11
15x15
6”
15x15
16x16
12x12
16x16
7”
16x16
17x17
13x13
17x17
8”
17x17
18x18
14x14
18x18
9”
N/A
N/A
N/A
N/A
10”
19x19
20x20
16x16
20x20
12”
22x22
22x22
18x18
22x22
14”
24x24
24x24
20x20
24x24
16”
26x26
26x26
22x22
26x26
18”
28x28
28x28
24x24
28x28
20”
30x30
30x30
26x26
30x30
22”
32x32
32x32
28x28
32x32
24”
N/A
N/A
N/A
N/A
Table 9 - Dimensions are in inches
OPENING DIMENSIONS FOR WALL/ROOF PENETRATION
FOR MODEL DSD
Inside
diameter
Wall
Thimble
(WT)
Wall
Thimble
Insulated
(WTI)
Roof
Thimble
(RT)
Roof
Thimble
Insulated
(RTI)
3”
12x12
13x13
9x9
13x13
4”
11x11
12x12
8x8
12x12
5”
12x12
13x13
9x9
13x13
6”
13x13
14x14
10x10
14x14
7”
14x14
15x15
11x11
15x15
8”
15x15
16x16
12x12
16x16
9”
16x16
17x17
13x13
17x17
10”
17x17
18x18
14x14
18x18
12”
19x19
20x20
16x16
20x20
14”
22x22
22x22
18x18
22x22
16”
24x24
24x24
20x20
24x24
18”
26x26
26x26
22x22
26x26
20”
28x28
28x28
24x24
28x28
22”
30x30
30x30
26x26
30x30
24”
32x32
32x32
28x28
32x32
Table 8 - Dimensions are in inches
INSTALLING DURASEAL® AS A LINER IN A MASONRY CHIMNEY OR
AS A LINER IN AN EXISTING VENT
* Stainless Steel Wire Rope (by others) is to be used to hang the vent
system from the top of the masonry chimney or from the top of the
existing vent.
- The stainless wire rope is attached to the Guy Support Band and is
secured with cable clamps (by others).
- The Stainless Steel Wire Rope is secured in a similar manner to the
top platform of the masonry chimney or existing vent.
- Use the appropriate size of Stainless Steel Wire Rope to accommodate
the required total loads of the vent system.
It may be necessary to fabricate a platform (at top of chimney / vent
- by others).
Consult DuraVent for guidelines.
DO NOT USE GALVANIZED WIRE ROPE.
Note: When installed as a liner in a masonry chimney or to reline an existing vent no other appliance
can be vented into the same chimney or vent.
Exit cone (EC)
1” Minimum
Masonry chimney
Combustible wall
Centering band
(CB)
Guy support (GS)
Maximum distance
between guides
See table 6 (MVS)
Maximum distance
between guides
See table 6 (MVS)
Elbow or tee
Stainless steel
wire rope *
(by other)
Maximum distance
between supports
See table 4 & 5
Storm Collar (SC)
Flat Flashing (F)
Figure 10 - Installing DuraSeal as a liner
For installations that requires non-standard vent lengths, DuraSeal® Adjustable Length
(AL) should be used.
The part consists of an inner conduit that slips into the downstream part and over the
upstream part, a collar holds the conduit in place and an outer shell (for double wall
only). See figure 11 for installation steps.
Note: The inner conduit may be cut to desired length to limit interference with down-
stream part.
1. Keep a play about
1/8” to 1/4” to
allow thermal
expansion
1. Keep a play about
1/8” to 1/4” to
allow thermal
expansion
2. Apply a 1/8” to 1/4”
bead (may vary) of
Viton caulking to fill
the gap between the
adjustable length
inner wall and
the female end of
the standard part.
Please allow 24-36
hours for Viton to
cure.”
2. Apply a 1/8” to 1/4”
bead (may vary) of
Viton caulking to fill
the gap between the
adjustable length
inner wall and
the female end of
the standard part.
Please allow 24-36
hours for Viton to
cure.
3. Slide the collar
down over the
female end of the
downstream part
and tighten the
collar
3. Slide the collar
down over the
female end of the
downstream part
and tighten the
clamp
4. Install the outer shell over end of
downstream part and under the
end of upstream part and tighten
the clamps. Need to cut outer
shell to correct length.
ADJUSTABLE LENGTH DS/DSD CAULKING REQUIREMENT
Inside diameter
Qty (oz)
3”
0.2
4”
0.3
5”
0.4
6”
0.5
7”
0.6
8”
0.7
9”
0.8
10”
0.9
12”
1.0
14”
1.2
16”
1.4
18”
1.5
20”
1.7
22”
1.9
24”
2.1
Table 10
Figure 11 - Adjustable length installation steps
DuraSeal DS
DuraSeal DSD
When installing DuraSeal Flex, the direction of exhaust flow is always from the ap-
pliance. There is an arrow printed on each section of liner and component that will
point in the direction of the exhaust gas. If the inner liner is installed correctly the
proper direction can be determined by running your fingernails up the inside wall of
the liner. If the direction is correct, your nails will catch at the seams of the inner
wall. If it is incorrect, your nails will slide smoothly across the inner surface.
Attaching adapters to DURASEAL FLEX liner
1- The adapter without the latches is the Female Flex Adapter and designed for the
top of the flex liner. The Adapter with the latches and the black Viton O-ring is
the Male Flex Adapter and is designed for the bottom of the flex liner. If cutting
the liner on the field is required, make sure the cut is square.
2- Make a mark on both ends of liner at 1 5/8” from each end. (Figure 12a) That
mark will act as a reference point when the adapters are fully seated onto the flex
liner. (Figure 12b)
3- To be sure everything is right before putting the sealant between both tubes, do a
dry fit test by pushing the liner into the adapter until it reach the bottom between
the inner tube and the outer tube, then remove it. (Figure 13)
4- Add the sealant S-650 in the channel of the Male Flex Adapter. Put enough sealant
so the channel gap is evenly covered all around. (Figure 14)
5- Push the adapter on the liner (the inner tube fits inside the liner and the outer tube
fits outside the liner) all the way in. (Figure 15)
6- Push the little natches. (Figure 16)
7- Repeat steps 3 through 6 for the other end with the female flex adapter or the flex
to flex adapter.
8- Before installation, cure for a minimum of 24 hours or follow the cure time called
out by the silicone manufacturer.
Figure 14 - Flex Adapter apply sealant
apply sealant
Figure 12a - DuraSeal Flex liner
1 5/8”
1 5/8”
Figure 12b - Flex Adapter small cut / catch
Small cut / catch
1 5/8 min
1 7/8 MAX
Figure 13 - Flex Adapter dry fit test
As with all vents, the DuraSeal vent system should be inspected at least annually for
the presence of deposits or debris and any accumulation should be removed. The vent
system should also be inspected at regular periods for signs of leakage of condensate
or combustion products at any joints.
If the vent system incorporates a drain hose from either a Drain length or a Drain tee
cap, the hose must be inspected periodically to ensure that water is in the trap loop.
If a proper trap loop is not maintained, exhaust from the connected appliances may
accumulate in the building area.
BASIC DURASEAL FLEX LINER INSTALLATION
1- Determine the required location and opening in the masonry chimney. For a
basic DuraSeal Flex installation the opening must be large enough for the mortar
sleeve and Male Flex Adapter and the DuraSeal Flex to easily pass through. If a
Tee application is necessary, a larger hole may be required.
2- Make sure the DuraSeal Flex is supported at the bottom of the chimney. Refer to
Figure 10 for guiding and support installation in the masonry chimney.
3- The DuraSeal Flex liner must be installed from the top of the masonry chimney.
To prevent damage, one person should feed the liner through the chimney and
another person should pull the liner from the bottom. To ease the installation, you
can attach a rope to the DuraSeal Flex liner above the Male Flex Adapter. Doing
this will reduce the chance of breaking the seal between the DuraSeal Flex and
the Male Flex Adapter.
4- The DuraSeal Flex must stay within the masonry chimney; however the Elbow or
other DuraSeal components will extend beyond the masonry chimney. (Figure
16)
5- It is strongly recommended to use a drain between the Male Flex Adapter and the
appliance (refer to Condensate Drains section).
Figure 17 - Flex Adapter Elbow in masonry
Figure 15 - Flex Adapter, seating flex
Small cut / catch
Push natches
Figure 16 - Flex Adapter push natch to lock
Guy support (GS)
DS, DSD / DSID DURASEAL® CHIMNEY LABELS
The labels supplied for product identification are shown here and indicates the flow of the flue gases in the venting system.
DSD / DSID VENT LENGTHS
DSD & DSID Lengths
Ø
(in.)
Effective Length
(in.)
Product Code
DSD
Product Code
DSID
3 to 24
6-5/8
DSDØL9
DSIDØL9
3 to 24
9-5/8
DSDØL12
DSIDØL12
3 to 24
15-5/8
DSDØL18
DSIDØL18
3 to 24
21-5/8
DSDØL24
DSIDØL24
3 to 24
33-5/8
DSDØL36
DSIDØL36
DSD & DSID Adjustable Lengths
Ø
(in.)
Effective Length
(in.)
Product Code
DSD
Product Code
DSID
3 to 24
3 to 5
DSDØAL9
DSIDØAL9
3 to 24
3 to 14
DSDØAL18
DSIDØAL18
DSD & DSID Test Port Lengths
Ø
(in.)
Effective Length
(in.)
Product Code
DSD
Product Code
DSID
3 to 24
6-5/8
DSDØTPL
DSIDØTPL
Drain Ø4–Ø24, 1/4 NPT, 1/2 O.D.
DSD & DSID Drain Lengths
Ø (in.)
Effective Length
(in.)
Product Code
DSD
Product Code
DSID
K
Factor
3 to 24
6-5/8
DSDØDL
DSIDØDL
0.25
Drain Ø4–Ø10, 1/4 NPT, 1/2 O.D.
Drain 12–Ø24, 1/2 NPT, 5/8 O.D.
Figure 18
Figure 19
Figure 20
Figure 21
Effective
length
Effective
length
3-5/8”
Ø
Ø
Effective
length
Effective
length
3-1/4”
Ø
Ø
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
Ø
EFFECTIVE
LENGTH
MAX
DSD Telescopic Lengths
Ø (in.)
Effective Length (in.)
Product Code
3 to 24
14 to 20
DSDØLAT20
3 to 24
20 to 32
DSDØLAT32
Figure 21a
NOTE: Not available for DSID.
DSD & DSID VENTING ELBOWS
DSD & DSID Damper Lengths
Ø
(in.)
Effective Length
(in.)
Product Code
DSD
Product Code
DSID
K
Factor
3 to 24
15-5/8
DSDØDAMP
DSIDØDAMP
0.60-9999
DSD & DSID Damper Length Short Manual
Ø
(in.)
Effective Length
(in.)
Product Code
DSD
Product Code
DSID
K
Factor
3 to 24
6-5/8
DSDØDAMPS
DSIDØDAMPS
0 to 9999
DSD & DSID Vent Flow Regulator
Ø
(in.)
Effective Length
(in.)
Product Code
DSD
Product Code
DSID
K
Factor
3 to 24
5-7/8
DSDØVFR
DSIDØVFR
0 to 9999
DSD 2-Degree Elbow
Ø (in.)
Offset (in.)
Rise (in.)
Product Code SSD
K Factor
3
1/8
7-3/4
DSD3E2
.04
4
1/8
7-3/4
DSD4E2
.04
5
1/8
7-3/4
DSD5E2
.04
6
1/8
7-7/8
DSD6E2
.04
7
1/8
7-7/8
DSD7E2
.04
8
1/8
7-7/8
DSD8E2
.04
9
1/8
8
DSD9E2
.04
10
1/8
8
DSD10E2
.04
12
1/8
8
DSD12E2
.04
14
1/8
8-1/8
DSD14E2
.03
16
1/8
8-1/4
DSD16E2
.03
18
1/8
8-1/4
DSD18E2
.03
20
1/8
8-3/8
DSD20E2
.03
22
1/8
8-3/8
DSD22E2
.03
24
1/8
8-1/2
DSD24E2
.03
DSID 2-Degree Elbow
Ø (in.)
Offset (in.)
Rise (in.)
Product Code SSID
K Factor
3
1/8
7-3/4
DSID3E2
.04
4
1/8
7-3/4
DSID4E2
.04
5
1/8
7-3/4
DSID5E2
.04
6
1/8
7-7/8
DSID6E2
.04
7
1/8
7-7/8
DSID7E2
.04
8
1/8
7-7/8
DSID8E2
.04
9
N/A
N/A
N/A
N/A
10
1/8
8
DSID10E2
.04
12
1/8
8
DSID12E2
.04
14
1/8
8-1/8
DSID14E2
.03
16
1/8
8-1/4
DSID16E2
.03
18
1/8
8-1/4
DSID18E2
.03
20
1/8
8-3/8
DSID20E2
.03
22
1-3/4
8-3/8
DSID22E2
.03
24
N/A
N/A
N/A
N/A
Figure 22
Figure 23
Figure 24
Figure 25
Figure 26
Effective
length
Plate for
actuator
Ø
Offset
Rise
2º
Ø
Cross Section View
Cross Section View
Ø INT.
Ø INT.
6-5/8
7-5/8
4-3/4
4
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
DSD 15-Degree Elbow
Ø (in.)
Offset (in.)
Rise (in.)
Product Code SSD
K Factor
3
1
8-3/4
DSD3E15
.31
4
1
8-3/4
DSD4E15
.31
5
1
8-3/4
DSD5E15
.30
6
1-1/8
9
DSD6E15
.30
7
1-1/8
9-3/8
DSD7E15
.29
8
1-1/4
9-5/8
DSD8E15
.29
9
1-1/4
9-7/8
DSD9E15
.28
10
1-1/4
10-1/8
DSD10E15
.28
12
1-3/8
10-5/8
DSD12E15
.27
14
1-3/8
11-1/8
DSD14E15
.27
16
1-1/2
11-5/8
DSD16E15
.26
18
1-1/2
12-1/8
DSD18E15
.26
20
1-5/8
12-5/8
DSD20E15
.26
22
1-5/8
13-1/4
DSD22E15
.26
24
1-3/4
13-3/4
DSD24E15UK
.26
Figure 27
Offset
Rise
15º
Ø
DSID 15-Degree Elbow
Ø (in.)
Offset (in.)
Rise (in.)
Product Code SSID
K Factor
3
1-1/8
9
DSID3E15UK
.31
4
1-1/8
9
DSID4E15UK
.31
5
1-1/8
9-3/8
DSID5E15UK
.30
6
1-1/4
9-5/8
DSID6E15UK
.30
7
1-1/4
9-7/8
DSID7E15UK
.29
8
1-1/4
10-1/8
DSID8E15UK
.29
9
N/A
N/A
N/A
N/A
10
1-3/8
10-5/8
DSID10E15UK
.28
12
1-3/8
11-1/8
DSID12E15UK
.27
14
1-1/2
11-5/8
DSID14E15UK
.27
16
1-1/2
12-1/8
DSID16E15UK
.26
18
1-5/8
12-5/8
DSID18E15UK
.26
20
1-5/8
13-1/4
DSID20E15UK
.26
22
1-3/4
13-3/4
DSID22E15UK
.26
24
N/A
N/A
N/A
N/A
Figure 28
DSD 30-Degree Elbow
Ø (in.)
Offset (in.)
Rise (in.)
Product Code SSD
K Factor
3
2-3/8
9-5/8
DSD3E30
.61
4
2-3/8
9-5/8
DSD4E30
.61
5
2-3/8
9-5/8
DSD5E30
.60
6
2-5/8
10-1/8
DSD6E30
.59
7
2-3/4
10-5/8
DSD7E30
.58
8
2-7/8
11-1/8
DSD8E30
.57
9
3
11-5/8
DSD9E30
.56
10
3-1/8
12-1/8
DSD10E30
.55
12
3-3/8
13-1/8
DSD12E30
.54
14
3-5/8
14-1/8
DSD14E30
.54
16
3-7/8
15-1/8
DSD16E30
.53
18
4-1/8
16-1/8
DSD18E30
.52
20
4-1/2
17-1/8
DSD20E30
.52
22
4-3/4
18-1/8
DSD22E30
.51
24
5
19-1/8
DSD24E30UK
.51
DSID 30-Degree Elbow
Ø (in.)
Offset (in.)
Rise (in.)
Product Code SSID
K Factor
3
2-5/8
10-1/8
DSID3E30UK
0.61
4
2-5/8
10-1/8
DSID4E30UK
0.61
5
2-3/4
10-5/8
DSID5E30UK
0.60
6
2-7/8
11-1/8
DSID6E30UK
0.59
7
3
11-5/8
DSID7E30UK
0.58
8
3-1/8
12-1/8
DSID8E30UK
0.57
9
N/A
N/A
N/A
N/A
10
3-3/8
13-1/8
DSID10E30UK
0.55
12
3-5/8
14-1/8
DSID12E30UK
0.54
14
3-7/8
15-1/8
DSID14E30UK
0.54
16
4-1/8
16-1/8
DSID16E30UK
0.53
18
4-1/2
17-1/8
DSID18E30UK
0.52
20
4-3/4
18-1/8
DSID20E30UK
0.52
22
5
19-1/8
DSID22E30UK
0.51
24
N/A
N/A
N/A
N/A
Figure 29
Figure 30
Offset
30º
Ø
Rise
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
DSD 45-Degree Elbow
Ø (in.)
Offset (in.)
Rise (in.)
Product Code SSD
K Factor
3
3-7/8
10-1/8
DSD3E45
.26
4
3-7/8
10-1/8
DSD4E45
.26
5
3-7/8
10-1/8
DSD5E45
.22
6
4-1/4
10-7/8
DSD6E45
.17
7
4-1/2
11-1/2
DSD7E45
.16
8
4-7/8
12-1/4
DSD8E45
.14
9
5-1/8
13
DSD9E45
.13
10
5-3/8
13-5/8
DSD10E45
.12
12
6
15-1/8
DSD12E45
.11
14
6-5/8
16-1/2
DSD14E45
.11
16
7-1/8
17-7/8
DSD16E45
.10
18
7-3/4
19-3/8
DSD18E45
.09
20
8-3/8
20-3/4
DSD20E45
.08
22
8-7/8
22-1/8
DSD22E45
.08
24
9-1/2
23-5/8
DSD24E45
.08
DSID 45-Degree Elbow
Ø (in.)
Offset (in.)
Rise (in.)
Product Code SSID
K Factor
3
4-1/4
10-7/8
DSID3E45
0.26
4
4-1/4
10-7/8
DSID4E45
0.26
5
4-1/2
11-1/2
DSID5E45
0.22
6
4-7/8
12-1/4
DSID6E45
0.17
7
5-1/8
13
DSID7E45
0.16
8
5-3/8
13-5/8
DSID8E45
0.14
9
N/A
N/A
N/A
N/A
10
6
15-1/8
DSID10E45
0.12
12
6-5/8
16-1/2
DSID12E45
0.11
14
7-1/8
17-7/8
DSID14E45
0.11
16
7-3/4
19-3/8
DSID16E45
0.1
18
8-3/8
20-3/4
DSID18E45
0.09
20
8-7/8
22-1/8
DSID20E45
0.08
22
9-1/2
23-5/8
DSID22E45
0.08
24
N/A
N/A
N/A
N/A
DSD 88-Degree Elbow
Ø (in.)
Offset (in.)
Rise (in.)
Product Code SSD
K Factor
3
8-3/8
9-1/4
DSD3E88
.54
4
8-3/8
9-1/4
DSD4E88
.54
5
8-3/8
9-1/4
DSD5E88
.48
6
9-1/4
10-1/4
DSD6E88
.42
7
10-1/4
11-1/4
DSD7E88
.39
8
11-1/4
12-1/4
DSD8E88
.37
9
12-1/4
13-1/4
DSD9E88
.34
10
13-1/8
14-1/4
DSD10E88
.32
12
15-1/8
16-1/4
DSD12E88
.29
14
17
18-1/4
DSD14E88
.27
16
19
20-1/4
DSD16E88
.25
18
20-7/8
22-1/4
DSD18E88
.24
20
22-7/8
24-1/4
DSD20E88
.23
22
24-3/4
26-1/4
DSD22E88
.21
24
26-5/8
28-1/4
DSD24E88
.20
DSID 88-Degree Elbow
Ø (in.)
Offset (in.)
Rise (in.)
Product Code
SSID
K Factor
3
9-1/4
10-1/4
DSID3E88
0.54
4
9-1/4
10-1/4
DSID4E88
0.54
5
10-1/4
11-1/4
DSID5E88
0.48
6
11-1/4
12-1/4
DSID6E88
0.42
7
12-1/4
13-1/4
DSID7E88
0.39
8
13-1/8
14-1/4
DSID8E88
0.37
9
N/A
N/A
N/A
N/A
10
15-1/8
16-1/4
DSID10E88
0.32
12
17
18-1/4
DSID12E88
0.29
14
19
20-1/4
DSID14E88
0.27
16
20-7/8
22-1/4
DSID16E88
0.25
18
22-7/8
24-1/4
DSID18E88
0.24
20
24-3/4
26-1/4
DSID20E88
0.23
22
26-5/8
28-1/4
DSID22E88
0.21
24
N/A
N/A
N/A
N/A
Figure 31
Figure 32
Figure 33
Figure 34
Offset
Rise
45º
Ø
Offset
Rise
Ø
88º
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
DSD 90-Degree Elbow
Ø (in.)
Offset (in.)
Rise (in.)
Product Code SSD
K Factor
3
8-1/2
9-1/8
DSD3E90
.54
4
8-1/2
9-1/8
DSD4E90
.54
5
8-1/2
9-1/8
DSD5E90
.48
6
9-1/2
10-1/8
DSD6E90
.42
7
10-1/2
11-1/8
DSD7E90
.39
8
11-1/2
12-1/8
DSD8E90
.37
9
12-1/2
13-1/8
DSD9E90
.34
10
13-1/2
14-1/8
DSD10E90
.32
12
15-1/2
16-1/8
DSD12E90
.29
14
17-1/2
18-1/8
DSD14E90
.27
16
19-1/2
20-1/8
DSD16E90
.25
18
21-1/2
22-1/8
DSD18E90
.24
20
23-1/2
24-1/8
DSD20E90
.23
22
25-1/2
26-1/8
DSD22E90
.21
24
27-1/2
28-1/8
DSD24E90
.20
DSID 90-Degree Elbow
Ø (in.)
Offset (in.)
Rise (in.)
Product Code SSID
K Factor
3
9-1/2
10-1/8
DSID3E90
.54
4
9-1/2
10-1/8
DSID4E90
.54
5
10-1/2
11-1/8
DSID5E90
.48
6
11-1/2
12-1/8
DSID6E90
.42
7
12-1/2
13-1/8
DSID7E90
.39
8
13-1/2
14-1/8
DSID8E90
.37
9
N/A
N/A
N/A
N/A
10
15-1/2
16-1/8
DSID10E90
.32
12
17-1/2
18-1/8
DSID12E90
.29
14
19-1/2
20-1/8
DSID14E90
.27
16
21-1/2
22-1/8
DSID16E90
.25
18
23-1/2
24-1/8
DSID18E90
.24
20
25-1/2
26-1/8
DSID20E90
.23
22
27-1/2
28-1/8
DSID22E90
.21
24
N/A
N/A
N/A
N/A
Figure 35
Figure 36
Offset
Rise
Ø
90º
DSD 43-Degree Tee
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
16-1/2
8-1/4
13-3/8
DSD3T43
0.4
4
16-1/2
8-1/4
13-3/8
DSD4T43
0.4
5
18-1/2
8-7/8
14-3/8
DSD5T43
0.4
6
19-1/2
9-5/8
15-3/8
DSD6T43
0.4
7
20-1/2
10-1/4
16-1/4
DSD7T43
0.4
8
22-1/2
11-5/8
18
DSD8T43
0.4
9
23-1/2
12-1/4
18-7/8
DSD9T43
0.4
10
25-1/2
13
19-3/4
DSD10T43
0.4
12
28-1/2
15
22-3/8
DSD12T43
0.4
14
31-1/2
16-3/8
24-1/4
DSD14T43
0.4
16
33-1/2
18-1/2
26-1/4
DSD16T43
0.4
18
38-1/4
20-1/2
29-3/8
DSD18T43
0.4
20
42-1/4
23-7/8
33-1/2
DSD20T43
0.4
22
45-1/4
23-7/8
33-7/8
DSD22T43
0.4
24
51-1/4
27-7/8
38-1/2
DSD24T43
0.4
Available with smaller snout and custom height.
DSID 43-Degree Tee
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
19-1/2
9-5/8
15-3/8
DSID3T43
0.4
4
19-1/2
9-5/8
15-3/8
DSID4T43
0.4
5
20-1/2
10-1/4
16-1/4
DSID5T43
0.4
6
22-1/2
11-5/8
18
DSID6T43
0.4
7
23-1/2
12-1/4
18-7/8
DSID7T43
0.4
8
25-1/2
13
19-3/4
DSID8T43
0.4
9
N/A
N/A
N/A
N/A
N/A
10
28-1/2
15
22-3/8
DSID10T43
0.4
12
31-1/2
16-3/8
24-1/4
DSID12T43
0.4
14
33-1/2
18-1/2
26-1/4
DSID14T43
0.4
16
38-1/4
20-1/2
29-3/8
DSID16T43
0.4
18
42-1/4
23-7/8
33-1/2
DSID18T43
0.4
20
45-1/4
23-7/8
33-7/8
DSID20T43
0.4
22
51-1/4
27-7/8
38-1/2
DSID22T43
0.4
24
N/A
N/A
N/A
N/A
N/A
Available with smaller snout and custom height.
Figure 37
Figure 38
DSD & DSID VENTING TEES
Offset
Rise
Height
Ø
43º
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
DSD 45-Degree Tee
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
16-1/2
8-1/4
13-1/4
DSD3T45
.04
4
16-1/2
8-1/4
13-1/4
DSD4T45
.04
5
18-1/2
9-1/4
14-1/8
DSD5T45
.04
6
19-1/2
9-7/8
15-1/8
DSD6T45
.04
7
20-1/2
10-5/8
16
DSD7T45
.04
8
22-1/2
12
17-5/8
DSD8T45
.04
9
23-1/2
12-3/4
18-1/2
DSD9T45
.04
10
25-1/2
13-1/2
19-1/2
DSD10T45
.04
12
28-1/2
15-5/8
22
DSD12T45
.04
14
31-1/2
17
23-7/8
DSD14T45
.04
16
33-1/2
19-1/8
26-3/8
DSD16T45
.04
18
38-1/4
21-1/4
28-7/8
DSD18T45
.04
20
42-1/4
24-3/4
32-7/8
DSD20T45
.04
22
45-1/4
24-3/4
33-1/4
DSD22T45
.04
24
51-1/4
28-7/8
37-3/4
DSD24T45
.04
Available with smaller snout and custom height.
DSID 45-Degree Tee
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
19-1/2
9-7/8
15-1/8
DSID3T45
.04
4
19-1/2
9-7/8
15-1/8
DSID4T45
.04
5
20-1/2
10-5/8
16
DSID5T45
.04
6
22-1/2
12
17-5/8
DSID6T45
.04
7
23-1/2
12-3/4
18-1/2
DSID7T45
.04
8
25-1/2
13-1/2
19-1/2
DSID8T45
.04
9
N/A
N/A
N/A
N/A
N/A
10
28-1/2
15-5/8
22
DSID10T45
.04
12
31-1/2
17
23-7/8
DSID12T45
.04
14
33-1/2
19-1/8
26-3/8
DSID14T45
.04
16
38-1/4
21-1/4
28-7/8
DSID16T45
.04
18
42-1/4
24-3/4
32-7/8
DSID18T45
.04
20
45-1/4
24-3/4
33-1/4
DSID20T45
.04
22
51-1/4
28-7/8
37-3/4
DSID22T45
.04
24
N/A
N/A
N/A
N/A
N/A
Available with smaller snout and custom height.
DSD 88-Degree Tee
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
13-1/2
7
6-5/8
DSD3T88
1.21
4
13-1/2
7
6-5/8
DSD4T88
1.21
5
14-1/2
8
7-1/4
DSD5T88
1.21
6
15-1/2
8
7-5/8
DSD6T88
1.21
7
16-1/2
9
8-1/4
DSD7T88
1.21
8
17-1/2
9
8-5/8
DSD8T88
1.21
9
18-1/2
10
9-1/4
DSD9T88
1.21
10
19-1/2
10
9-5/8
DSD10T88
1.21
12
21-1/2
11
10-5/8
DSD12T88
1.21
14
23-1/2
12
11-5/8
DSD14T88
1.21
16
25-1/2
13
12-5/8
DSD16T88
1.21
18
27-1/2
14
13-5/8
DSD18T88
1.21
20
29-1/2
15
14-5/8
DSD20T88
1.21
22
31-1/2
16
15-5/8
DSD22T88
1.21
24
33-1/2
17
16-5/8
DSD24T88
1.21
Available with smaller snout and custom height.
Figure 39
Figure 40
Figure 41
Offset
Offset
Rise
Rise
Height
Height
Ø
Ø
45º
88º
DSID 88-Degree Tee
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
15-1/2
8
7-5/8
DSID3T88
1.21
4
15-1/2
8
7-5/8
DSID4T88
1.21
5
16-1/2
9
8-1/4
DSID5T88
1.21
6
17-1/2
9
8-5/8
DSID6T88
1.21
7
18-1/2
10
9-1/4
DSID7T88
1.21
8
19-1/2
10
9-5/8
DSID8T88
1.21
9
N/A
N/A
N/A
N/A
N/A
10
21-1/2
11
10-5/8
DSID10T88
1.21
12
23-1/2
12
11-5/8
DSID12T88
1.21
14
25-1/2
13
12-5/8
DSID14T88
1.21
16
27-1/2
14
13-5/8
DSID16T88
1.21
18
29-1/2
15
14-5/8
DSID18T88
1.21
20
31-1/2
16
15-5/8
DSID20T88
1.21
22
33-1/2
17
16-5/8
DSID22T88
1.21
24
N/A
N/A
N/A
N/A
N/A
Available with smaller snout and custom height.
Figure 42
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
DSD 90-Degree Tee
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
13-1/2
7
6-1/2
DSD3T90
1.21
4
13-1/2
7
6-1/2
DSD4T90
1.21
5
14-1/2
8
7
DSD5T90
1.21
6
15-1/2
8
7-1/2
DSD6T90
1.21
7
16-1/2
9
8
DSD7T90
1.21
8
17-1/2
9
8-1/2
DSD8T90
1.21
9
18-1/2
10
9
DSD9T90
1.21
10
19-1/2
10
9-1/2
DSD10T90
1.21
12
21-1/2
11
10-1/2
DSD12T90
1.21
14
23-1/2
12
11-1/2
DSD14T90
1.21
16
25-1/2
13
12-1/2
DSD16T90
1.21
18
27-1/2
14
13-1/2
DSD18T90
1.21
20
29-1/2
15
14-1/2
DSD20T90
1.21
22
31-1/2
16
15-1/2
DSD22T90
1.21
24
33-1/2
17
16-1/2
DSD24T90
1.21
Available with smaller snout and custom height.
DSID 90-Degree Tee
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
15-1/2
8
7-1/2
DSID3T90
1.21
4
15-1/2
8
7-1/2
DSID4T90
1.21
5
16-1/2
9
8
DSID5T90
1.21
6
17-1/2
9
8-1/2
DSID6T90
1.21
7
18-1/2
10
9
DSID7T90
1.21
8
19-1/2
10
9-1/2
DSID8T90
1.21
9
N/A
N/A
N/A
N/A
N/A
10
21-1/2
11
10-1/2
DSID10T90
1.21
12
23-1/2
12
11-1/2
DSID12T90
1.21
14
25-1/2
13
12-1/2
DSID14T90
1.21
16
27-1/2
14
13-1/2
DSID16T90
1.21
18
29-1/2
15
14-1/2
DSID18T90
1.21
20
31-1/2
16
15-1/2
DSID20T90
1.21
22
33-1/2
17
16-1/2
DSID22T90
1.21
24
N/A
N/A
N/A
N/A
N/A
Available with smaller snout and custom height.
Figure 43
Figure 44
Offset
Rise
Height
Ø
90º
SSD 90-Degree Tee Y
Ø (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
5
10-3/8
DSD3TY90
0.6
4
5
10-3/8
DSD4TY90
0.6
5
5-5/8
11-1/8
DSD5TY90
0.6
6
5-5/8
11-1/8
DSD6TY90
0.6
7
6-3/8
11-3/4
DSD7TY90
0.6
8
6-3/8
11-3/4
DSD8TY90
0.6
9
7-1/8
13-1/2
DSD9TY90
0.6
10
7-1/8
13-1/2
DSD10TY90
0.6
12
7-3/4
14-1/4
DSD12TY90
0.6
14
8-1/2
15-7/8
DSD14TY90
0.6
16
9-1/4
17-5/8
DSD16TY90
0.6
18
9-7/8
18-3/8
DSD18TY90
0.6
20
10-5/8
21
DSD20TY90
0.6
22
11-3/8
21-3/4
DSD22TY90
0.6
24
12
22-1/2
DSD24TY90
0.6
Available with smaller snout.
DSID 90-Degree Tee Y
Ø (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
5-5/8
11-1/8
DSID3TY90
0.6
4
5-5/8
11-1/8
DSID4TY90
0.6
5
6-3/8
11-3/4
DSID5TY90
0.6
6
6-3/8
11-3/4
DSID6TY90
0.6
7
7-1/8
13-1/2
DSID7TY90
0.6
8
7-1/8
13-1/2
DSID8TY90
0.6
9
N/A
N/A
N/A
N/A
10
7-3/4
14-1/4
DSID10TY90
0.6
12
8-1/2
15-7/8
DSID12TY90
0.6
14
9-1/4
17-5/8
DSID14TY90
0.6
16
9-7/8
18-3/8
DSID16TY90
0.6
18
10-5/8
21
DSID18TY90
0.6
20
11-3/8
21-3/4
DSID20TY90
0.6
22
12
22-1/2
DSID22TY90
0.6
24
N/A
N/A
N/A
N/A
Available with smaller snout.
Figure 45
Figure 46
Offset
Rise
Ø
45º
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
DSD Lateral Tee
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
14-3/8
11-5/8
10
DSD3BT
0.55
4
14-3/8
11-5/8
10
DSD4BT
0.55
5
16-3/8
12-1/4
11
DSD5BT
0.55
6
17-3/8
13-3/4
12-1/4
DSD6BT
0.55
7
19-3/8
14-3/4
13-1/4
DSD7BT
0.55
8
20-3/8
16
14-3/8
DSD8BT
0.55
9
23-3/8
14-1/4
14-1/4
DSD9BT
0.55
10
25-3/8
15-1/4
15-1/4
DSD10BT
0.55
12
27-3/8
16-7/8
17
DSD12BT
0.55
14
30-3/8
18-7/8
18-7/8
DSD14BT
0.55
16
33-3/8
20-3/4
20-3/4
DSD16BT
0.55
18
38-1/8
22-1/2
22-1/2
DSD18BT
0.55
20
42-1/8
24-3/8
24-3/8
DSD20BT
0.55
22
45-1/8
26-1/4
26-1/4
DSD22BT
0.55
24
51-1/8
28
28-1/8
DSD24BT
0.55
Available with smaller snout and custom height.
DSID Lateral Tee
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
17-3/8
13-3/4
12-1/4
DSID3BT
0.55
4
17-3/8
13-3/4
12-1/4
DSID4BT
0.55
5
19-3/8
14-3/4
13-1/4
DSID5BT
0.55
6
20-3/8
16
14-3/8
DSID6BT
0.55
7
23-3/8
14-1/4
14-1/4
DSID7BT
0.55
8
25-3/8
15-1/4
15-1/4
DSID8BT
0.55
9
N/A
N/A
N/A
N/A
N/A
10
27-3/8
16-7/8
17
DSID10BT
0.55
12
30-3/8
18-7/8
18-7/8
DSID12BT
0.55
14
33-3/8
20-3/4
20-3/4
DSID14BT
0.55
16
38-1/8
22-1/2
22-1/2
DSID16BT
0.55
18
42-1/8
24-3/4
24-3/8
DSID18BT
0.55
20
45-1/8
26-1/4
26-1/4
DSID20BT
0.55
22
51-1/8
28
28-1/8
DSID22BT
0.55
24
N/A
N/A
N/A
N/A
N/A
Available with smaller snout and custom height.
DSD Lateral Tee 88-Degree
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
14-3/8
11-5/8
10-1/4
DSD3BT88
0.55
4
14-3/8
11-5/8
10-1/4
DSD4BT88
0.55
5
16-3/8
12-1/4
11-3/8
DSD5BT88
0.55
6
17-1/2
13-3/4
12-3/4
DSD6BT88
0.55
7
19-3/8
14-7/8
13-3/4
DSD7BT88
0.55
8
20-3/8
16-1/8
15
DSD8BT88
0.55
9
23-3/8
14-1/2
15-1/4
DSD9BT88
0.55
10
25-3/8
15-3/8
16-1/8
DSD10BT88
0.55
12
28-3/8
17
17-7/8
DSD12BT88
0.55
14
31-3/8
19-1/8
20-1/8
DSD14BT88
0.55
16
33-3/8
21
22
DSD16BT88
0.55
18
38-3/8
22-7/8
24
DSD18BT88
0.55
20
42-1/8
24-3/4
26
DSD20BT88
0.55
22
45-1/8
26-5/8
28
DSD22BT88
0.55
24
51-1/8
28-1/2
29-7/8
DSD24BT88
0.55
Available with smaller snout and custom height.
DSID Lateral Tee 88-Degree
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
17-1/2
13-3/4
12-3/4
DSID3BT88
0.55
4
17-1/2
13-3/4
12-3/4
DSID4BT88
0.55
5
19-3/8
14-7/8
13-3/4
DSID5BT88
0.55
6
20-3/8
16-1/8
15
DSID6BT88
0.55
7
23-3/8
14-1/2
15-1/4
DSID7BT88
0.55
8
25-3/8
15-3/8
16-1/8
DSID8BT88
0.55
9
N/A
N/A
N/A
N/A
N/A
10
28-3/8
17
17-7/8
DSID10BT88
0.55
12
31-3/8
19-1/8
20-1/8
DSID12BT88
0.55
14
33-3/8
21
22
DSID14BT88
0.55
16
38-3/8
22-7/8
24
DSID16BT88
0.55
18
42-1/8
24-3/4
26
DSID18BT88
0.55
20
45-1/8
26-5/8
28
DSID20BT88
0.55
22
51-1/8
28-1/2
29-7/8
DSID22BT88
0.55
24
N/A
N/A
N/A
N/A
N/A
Available with smaller snout and custom height.
Figure 47
Figure 48
Figure 49
Figure 50
Offset
Offset
Rise
Rise
Height
Height
4 to 8
9 to 24
Offset
Offset
Rise
Rise
Height
Height
4 to 8
9 to 24
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
DSD Barometric Tee
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
13-1/2
5
6-1/2
DSD3BMT
0.2
4
13-1/2
5
6-1/2
DSD4BMT
0.2
5
14-1/2
5
7
DSD5BMT
0.2
6
15-1/2
6
7-1/2
DSD6BMT
0.2
7
16-1/2
7
8
DSD7BMT
0.2
8
17-1/2
8
8-1/2
DSD8BMT
0.2
9
18-1/2
9
9
DSD9BMT
0.2
10
19-1/2
10
9-1/2
DSD10BMT
0.2
12
21-1/2
12
10-1/2
DSD12BMT
0.2
14
23-1/2
14
11-1/2
DSD14BMT
0.2
16
25-1/2
16
12-1/2
DSD16BMT
0.2
18
27-1/2
18
13-1/2
DSD18BMT
0.2
20
29-1/2
20
14-1/2
DSD20BMT
0.2
22
31-1/2
22
15-1/2
DSD22BMT
0.2
24
33-1/2
24
16-1/2
DSD24BMT
0.2
Available with smaller snout and custom height.
DSID Barometric Tee
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
15-1/2
6
7-1/2
DSID3BMT
0.2
4
15-1/2
6
7-1/2
DSID4BMT
0.2
5
16-1/2
7
8
DSID5BMT
0.2
6
17-1/2
8
8-1/2
DSID6BMT
0.2
7
18-1/2
9
9
DSID7BMT
0.2
8
19-1/2
10
9-1/2
DSID8BMT
0.2
9
N/A
N/A
N/A
N/A
N/A
10
21-1/2
12
10-1/2
DSID10BMT
0.2
12
23-1/2
14
11-1/2
DSID12BMT
0.2
14
25-1/2
16
12-1/2
DSID14BMT
0.2
16
27-1/2
18
13-1/2
DSID16BMT
0.2
18
29-1/2
20
14-1/2
DSID18BMT
0.2
20
31-1/2
22
15-1/2
DSID20BMT
0.2
22
33-1/2
24
16-1/2
DSID22BMT
0.2
24
N/A
N/A
N/A
N/A
N/A
Available with smaller snout and custom height.
Figure 51
Figure 52
Offset
Rise
Height
Ø
DSD & DSID Tee Cap
Ø (in.)
Height (in.)
Product Code DSD
Product Code DSID
3 to 24
4-1/8
DSDØTC
DSIDØTC
DSD & DSID Tapered Increaser
Ø (in.)
ØB
Available
(in.)
Height
(in.)
Product Code
DSD
Product Code
DSID
K
Factor
3 to 9
Ø+1
12-1/8
DSDØTIN(ØB)
DSIDØTIN(ØB)
0.05
3 to 22
Ø+2
13-1/8
DSDØTIN(ØB)
DSIDØTIN(ØB)
0.10
3 to 9
Ø+3
14-1/8
DSDØTIN(ØB)
DSIDØTIN(ØB)
0.15
3 to 20
Ø+4
15-1/8
DSDØTIN(ØB)
DSIDØTIN(ØB)
0.20
3 to 7
Ø+5
16-1/8
DSDØTIN(ØB)
DSIDØTIN(ØB)
0.25
3 to 18
Ø+6
17-1/8
DSDØTIN(ØB)
DSIDØTIN(ØB)
0.30
DSD & DSID Drain Tee Cap
Ø (in.)
Height (in.)
Product Code DSD
Product Code DSID
3 to 24
4-1/8
DSDØDTC
DSIDØDTC
Drain Ø4 – Ø10, 1/4 NPT, 1/2 0.D
Drain Ø12 – Ø24, 3/8 NPT, 5/8 0.D
Figure 53
Figure 54
Figure 55
4-1/8
3-3/4
Drain NPT
Height
Ø
Ø
ØB
Ø
SSD & SSID VENTING ACCESSORIES
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
DSD & DSID Step Increaser
Ø
(in.)
ØB Available
(in.)
Height
(in.)
Product Code
DSD
Product Code
DSID
K
Factor
3 to 22
5 to 24
8
DSDØSIN(ØB)
DSIDØSIN(ØB)
KØ = (1-β2)2
KØB = KØ/β4
β = Ø/ØB
DSD & DSID Eccentric Tapered Increaser
Ø (in.)
ØB
Available
(in.)
Height
(in.)
Offset
(in.)
Product Code
DSD
Product Code
DSID
K
Factor
3 to 9
Ø+1
12-1/2
1/2
DSDØETIN(ØB)
DSIDØETIN(ØB)
0.05
3 to 22
Ø+2
13-1/2
1
DSDØETIN(ØB)
DSIDØETIN(ØB)
0.10
3 to 9
Ø+3
14-1/2
1-1/2
DSDØETIN(ØB)
DSIDØETIN(ØB)
0.15
3 to 20
Ø+4
15-1/2
2
DSDØETIN(ØB)
DSIDØETIN(ØB)
0.20
3 to 7
Ø+5
16-1/2
2-1/2
DSDØETIN(ØB)
DSIDØETIN(ØB)
0.25
3 to 18
Ø+6
17-1/2
3
DSDØETIN(ØB)
DSIDØETIN(ØB)
0.30
DSD & DSID Eccentric Step Increaser
Ø
(in.)
ØB
Available
(in.)
Height
(in.)
Offset
(in.)
Product Code
DSD
Product Code
DSID
K
Factor
3 to 22
5 to 24
8
(ØB-ØA)/2
DSDØESIN(ØB)
DSIDØESIN(ØB)
KØ = (1-β2)2
KØB = KØ/β4
β = Ø/ØB
Figure 56
Figure 57
Figure 58
Height
Height
Height
ØB
ØB
ØB
Offset
Offset
Ø
Ø
Ø
DSD & DSID Tapered Reducer
Ø (in.)
ØB
Available
(in.)
Height
(in.)
Product Code
DSD
Product Code
DSID
K
Factor
5 to 10
Ø-1
12-7/16
DSDØTRD(ØB)
DSIDØTRD(ØB)
0.07
6 to 24
Ø-2
13-7/16
DSDØTRD(ØB)
DSIDØTRD(ØB)
0.09
6 to 12
Ø-3
14-7/16
DSDØTRD(ØB)
DSIDØTRD(ØB)
0.11
8 to 24
Ø-4
15-7/16
DSDØTRD(ØB)
DSIDØTRD(ØB)
0.13
9 to 24
Ø-5
16-7/16
DSDØTRD(ØB)
DSIDØTRD(ØB)
0.15
10 to 24
Ø-6
17-7/16
DSDØTRD(ØB)
DSIDØTRD(ØB)
0.17
DSD & DSID Step Reducer
Ø (in.)
ØB
Available
(in.)
Height
(in.)
Product Code
DSD
Product Code
DSID
K Factor
5 to 24
3 to 22
8
DSDØSRD(ØB)
DSIDØSRD(ØB)
KØB = 0.5 (1-β2)
KØ = KØB/β4
β = ØB/Ø
Figure 59
Figure 60
Height
Height
ØB
ØB
Ø
Ø
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
DSD & DSID Eccentric Tapered Reducer
Ø
(in.)
ØB
Available
(in.)
Height
(in.)
Offset
(in.)
Product Code
DSD
Product Code
DSID
K
Factor
5 to 10
Ø-1
12-1/2
1/2
DSDØETRD(ØB)
DSIDØETRD(ØB)
0.07
6 to 24
Ø-2
13-1/2
1
DSDØETRD(ØB)
DSIDØETRD(ØB)
0.09
6 to 12
Ø-3
14-1/2
1-1/2
DSDØETRD(ØB)
DSIDØETRD(ØB)
0.11
8 to 24
Ø-4
15-1/2
2
DSDØETRD(ØB)
DSIDØETRD(ØB)
0.13
9 to 24
Ø-5
16-1/2
2-1/2
DSDØETRD(ØB)
DSIDØETRD(ØB)
0.15
10 to 24
Ø-6
17-1/2
3
DSDØETRD(ØB)
DSIDØETRD(ØB)
0.17
DSD & DSID Eccentric Step Reducer
Ø (in.)
ØB Available (in.)
Height (in.)
Offset (in.)
5 to 24
3 to 22
8
(ØA-ØB)/2
Product Code DSD
Product Code DSID
K Factor
DSDØESRD(ØB)
DSIDØESRD(ØB)
KØB = 0.5 (1-2)
KØ = KØB/4 =ØB/Ø
DSD & DSID Wall Thimble
Ø (in.)
Width (in.)
Product Code DSD
Product Code DSID
3 to 24
9 to 17
DSDØWT
DSIDØWT
DSD & DSID Wall Thimble Insulated
Ø (in.)
Width (in.)
Product Code DSD
Product Code DSID
3 to 24
9 to 17
DSDØWTI
DSIDØWTI
Figure 61
Figure 62
Figure 63
Figure 64
Height
DSD Ø + Clearance + 5
DSID Ø + Clearance + 7
DSD Ø + Clearance +9
DSID Ø + Clearance +11
Height
ØB
Offset
Width
Width
Offset
ØB
Ø
Ø
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
DSD & DSID Roof Thimble
Ø (in.)
Width (in.)
Product Code DSD
Product Code DSID
3 to 24
10
DSDØRT
DSIDØRT
DSD & DSID Wall Support
Ø (in.)
A (in.)
Product Code DSD
Product Code DSID
3 to 24
1 to 3
DSDØWS
DSIDØWS
DSD Wall Suort HD
Ø (in.)
A (in.)
B (in.)
C (in.)
roduct Code
3
1-1/2 to 6-1/2
9
12
DSD3WSHD
4
1-1/2 to 6-1/2
9
12
DSD4WSHD
5
1-1/2 to 6-1/2
10
12
DSD5WSHD
6
1-1/2 to 6-1/2
11
12
DSD6WSHD
7
1-1/2 to 6-1/2
12
14
DSD7WSHD
8
1-1/2 to 6-1/2
13
14
DSD8WSHD
9
1-1/2 to 6-1/2
14
14
DSD9WSHD
10
1-1/2 to 6-1/2
15
16
DSD10WSHD
12
1-1/2 to 6-1/2
17
16
DSD12WSHD
14
1-1/2 to 6-1/2
19
22
DSD14WSHD
16
1-1/2 to 6-1/2
21
22
DSD16WSHD
18
1-1/2 to 6-1/2
23
26
DSD18WSHD
20
1-1/2 to 6-1/2
25
30
DSD20WSHD
22
1-1/2 to 6-1/2
27
30
DSD22WSHD
24
1-1/2 to 6-1/2
29
30
DSD24WSHD
DSD & DSID Roof Thimble Insulated
Ø (in.)
Width (in.)
Product Code DSD
Product Code DSID
3 to 24
10
DSDØRTI
DSIDØRTI
DSD & DSID Suspension Band
Ø (in.)
Product Code DSD
Product Code DSID
3 to 24
DSDØSB
DSIDØSB
DSD & DSID Cradle Support
Ø (in.)
Product Code DSD
Product Code DSID
3 to 24
DSDØCS
DSIDØCS
Figure 65
Figure 69
Figure 70
Figure 66
Figure 67
Figure 68
DSD Ø + Clearance + 5
DSID Ø + Clearance + 7
DSD Ø + 2
DSID Ø + 4
DSD Ø + Clearance +5
DSID Ø + Clearance +7
SSD Ø+2
SSID Ø+4
DSD Ø+2
DSID Ø+4
SSD Ø+2
SSID Ø+4
10
A
A
B
C
10
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
DSID Wall Support HD
Ø (in.)
A (in.)
B (in.)
C (in.)
Product Code
3
1-1/2 to 6-1/2
11
12
DSID3WSHD
4
1-1/2 to 6-1/2
11
12
DSID4WSHD
5
1-1/2 to 6-1/2
12
14
DSID5WSHD
6
1-1/2 to 6-1/2
13
14
DSID6WSHD
7
1-1/2 to 6-1/2
14
14
DSID7WSHD
8
1-1/2 to 6-1/2
15
16
DSID8WSHD
9
N/A
N/A
N/A
N/A
10
1-1/2 to 6-1/2
17
16
DSID10WSHD
12
1-1/2 to 6-1/2
19
22
DSID12WSHD
14
1-1/2 to 6-1/2
21
22
DSID14WSHD
16
1-1/2 to 6-1/2
23
26
DSID16WSHD
18
1-1/2 to 6-1/2
25
30
DSID18WSHD
20
1-1/2 to 6-1/2
27
30
DSID20WSHD
22
1-1/2 to 6-1/2
29
30
DSID22WSHD
24
N/A
N/A
N/A
N/A
Figure 71
DSD Ø+2
DSID Ø+4
A
B
C
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
DSD & DSID Roof Support
Ø (in.)
A (in.)
B (in.)
Product Code DSD
Product Code
DSID
3 to 24
6-1/2
7-5/8
DSDØRS
DSIDØRS
DSD & DSID Anchor Plate
Ø (in.)
A (in.)
Product Code DSD
Product Code DSID
3 to 24
Ø+7
DSDØAP
DSIDØAP
DSD & DSID Anchor Plate HD
Ø (in.)
A (in.)
Product Code DSD
Product Code DSID
3 to 24
Ø+7
DSDØAPHD
DSIDØAPHD
Figure 73
Figure 74
Figure 75
A
B
A
A
A
2-1/2
DSD Ø+2
DSID Ø+4
DSD Ø+2
DSID Ø+4
DSD Ø+2
DSID Ø+4
DSD Anchor Plate Length (APL)
Ø (in.)
A (in.)
Product Code
3 to 24
Ø + 7
DSDØAPL
DSID Anchor Plate Length (APL)
Ø (in.)
A (in.)
Product Code
3 to 22
Ø + 9
DSIDØAPL
Figure 72
NOTE: DSID 9” and 24” not available.
9-9/32
Ø
A
DSD & DSID Roof Brace
Ø (in.)
Product Code DSD
Product Code DSID
3 to 24
DSDØRB
DSIDØRB
DSD & DSID Guy Wire Band
Ø (in.)
Product Code DSD
Product Code DSID
3 to 24
DSDØGWB
DSIDØGWB
DSD & DSID Centering Band
Ø (in.)
Product Code DSD
Product Code DSID
3 to 24
DSDØCB
DSIDØCB
DSD & DSID Guy Support
Ø (in.)
Product Code DSD
Product Code DSID
3 to 24
DSDØGS
DSIDØGS
Figure 76
Figure 77
Figure 78
Figure 80
6
DSD Ø+2
DSID Ø+4
3/4
3
DSD & DSID Wall Guide
Ø (in.)
A (in.)
Product Code DSD
Product Code DSID
3 to 24
1 to 4-1/2
DSDØWG
DSIDØWG
DSD & DSID Double Male Adaptor
Ø
(in.)
Effective Length
(in.)
Product Code
DSD
Product Code
DSID
3 to 24
7-1/8
DSDØDMAU
DSIDØDMAU
Figure 79
Figure 81
DSD Ø+2
DSID Ø+4
Effective
Length
A
Ø
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
Flexible strap by other
DSD Ø+2
DSID Ø+4
DSD Ø+2
DSID Ø+4
DSD & DSID Male Flange Adaptor
Ø (in.)
Effective Length (in.)
Product Code DSD
Product Code
DSID
3 to 24
5-1/2
DSDØMFA
DSIDØMFA
DSD & DSID Female Flange Adaptor
Ø (in.)
Effective Length (in.)
Product Code DSD
Product Code DSID
3 to 24
6-7/8
DSDØFFA
DSIDØFFA
DSD & DSID to DS Adaptor
Ø (in.)
Effective Length (in.)
Product Code DSD
Product Code DSID
3 to 24
7-7/8
DSDØDSA
DSIDØDSA
DSD Flat Flashing
Ø (in.)
A (in.)
Product Code
3
16
DSD3F
4
16
DSD4F
5
18
DSD5F
6
26
DSD6F
7
26
DSD7F
8
28
DSD8F
9
30
DSD9F
10
30
DSD10F
12
31
DSD12F
14
34
DSD14F
16
36
DSD16F
18
38
DSD18F
20
40
DSD20F
22
42
DSD22F
24
44
DSD24F
Figure 82
Figure 83
Figure 84
Figure 85
Effective
Length
Effective
Length
Effective
Length
Ø
Ø
Ø
DSD Ø+2
DSID Ø+4
A
12
1/2
1/2
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
DSID Flat Flasing
Ø (in.)
A (in.)
Product Code
3
26
DSID3F
4
26
DSID4F
5
26
DSID5F
6
28
DSID6F
7
30
DSID7F
8
30
DSID8F
9
N/A
N/A
10
31
DSID10F
12
34
DSID12F
14
36
DSID14F
16
38
DSID16F
18
40
DSID18F
20
42
DSID20F
22
44
DSID22F
24
N/A
N/A
Figure 86
NOTE: DSID 9” and 24” not available.
DSD Adjustable Flashing
Ø (in.)
A (in.)
Height (in.)
Product Code
3
32
12-1/2
DSD3FA
4
32
12-1/2
DSD4FA
5
32
12-1/2
DSD5FA
6
34
12-1/2
DSD6FA
7
35-3/8
12-1/2
DSD7FA
8
36-1/2
12-1/2
DSD8FA
9
38
12-1/2
DSD9FA
10
38-1/2
12-1/2
DSD10FA
12
41
12-1/2
DSD12FA
14
43
12-1/2
DSD14FA
16
45
12-1/2
DSD16FA
18
47-1/4
12-1/2
DSD18FA
20
49-1/2
12-1/2
DSD20FA
22
51-1/2
12-1/2
DSD22FA
24
53-1/2
12-1/2
DSD24FA
DSID Adjustable Flashing
Ø (in.)
A (in.)
Height (in.)
Product Code
3
34
12-1/2
DSID3FA
4
34
12-1/2
DSID4FA
5
35-3/8
12-1/2
DSID5FA
6
36-1/2
12-1/2
DSID6FA
7
38
12-1/2
DSID7FA
8
38-1/2
12-1/2
DSID8FA
9
N/A
N/A
N/A
10
41
12-1/2
DSID10FA
12
43
12-1/2
DSID12FA
14
45
12-1/2
DSID14FA
16
47-1/4
12-1/2
DSID16FA
18
49-1/2
12-1/2
DSID18FA
20
51-1/2
12-1/2
DSID20FA
22
53-1/2
12-1/2
DSID22FA
24
N/A
N/A
N/A
Figure 87
Figure 88
DSD Ø+2
DSID Ø+4
A
12-1/2
DSD & DSID Storm Collar
Ø (in.)
Product Code DSD
Product Code DSID
3 to 24
DSDØSC
DSIDØSC
Figure 89
Ø+2 DSD
Ø+4 DSID
7
DSD Rain Cap
Ø
(in.)
Product Code
DSD
Product Code with Bird Screen
DSD
K
Factor
3 to 24
DSDØRC
DSDØRCB
.50
DSID Rain Cap
Ø
(in.)
Product Code
DSID
Product Code with Bird Screen
DSID
K
Factor
3 to 24
DSIDØRC
DSIDØRCB
.50
Figure 90
DSD & DSID VENTING TERMINATIONS
NOTE: DSID 9” and 24” not available.
Adjustable from 5° to 30°.
Roof pitch 1/12 to 7/12.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
Ø
DSD & DSID Screened Termination
Ø (in.)
Product Code DSD
Product Code DSID
K Factor
3 to 24
DSDØSTU
DSIDØST
.14
Figure 91
5
Ø + 6
Ø + 6
Ø + 6
90% Ø
Ø
Ø
Ø
Ø
15
30°
DSD & DSID 30° Screen Termination
Ø (in.)
Product Code DSD
Product Code
DSID
K Factor
3 to 24
DSDØSTAU
DSIDØSTA
.70
DSD & DSID Termination Tee
Ø (in.)
Product Code DSD
Product Code DSID
K Factor
3 to 24
DSDØTT
DSIDØTT
.35
DSD & DSID Exit Cone
Ø (in.)
Product Code DSD
Product Code DSID
K Factor
3 to 24
DSDØEC
DSIDØEC
.60
Figure 92
Figure 94
Figure 93
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
Ø + 5
5
Effective
length
Effective
length
Ø
Ø
Ø
Ø
DSD & DSID Mitre Cut
Ø (in.)
Product Code DSD
Product Code DSID
K Factor
3 to 24
DSDØMCU
DSIDØMCU
.14
DSD & DSID Closer Termination
Ø (in.)
Product Code DSD
Product Code DSID
K Factor
3 to 24
DSDØCTU
DSIDØCTU
0
DSD & DSID OEM Termination
Ø (in.)
Product Code DSD
Product Code DSID
K Factor
3 to 24
DSDØOEMTAU
DSIDØ0EMTAU
0
DS Lengths
Ø (in.)
Effective Length (in.)
Product Code
3 to 24
6-1/2
DSØL9
3 to 24
9-1/2
DSØL12
3 to 24
15-1/2
DSØL18
3 to 24
21-1/2
DSØL24
3 to 24
33-1/2
DSØL36
DS Adjustable Lengths
Ø (in.)
Effective Length (in.)
Product Code
3 to 24
4 to 5
DSØAL9
3 to 24
4 to 14
DSØAL18
Figure 95
Figure 96
Figure 97
Figure 98
Figure 99
DS VENTING LENGTHS
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
NOTE: DSID 9” and 24” not available.
Ø
20 24
Ø
EFFECTIVE
LENGTH
MAX
Figure 99a
DS Telescopic Lengths
Ø (in.)
Effective Length (in.)
Product Code 32”
Product Code 20”
3 to 24
14 to 20
DSØLAT32
DSØLAT20
3 to 24
20 to 32
DSØLAT32
DSØLAT20
DS Test Port Lengths
Ø (in.)
Effective Length (in.)
Product Code
3 to 24
6-1/2
DSØTPL
Drain Ø4 – Ø24, 1/4 NPT, 1/2 0.D
DS Drain Length
Ø (in.)
Effective Length (in.)
Product Code
K Factor
3 to 24
6-1/2
DSØDL
0.25
Drain Ø4 – Ø10, 1/4 NPT, 1/2 0.D
Drain Ø12 – Ø24, 1/2 NPT, 5/8 0.D
Figure 100
Figure 101
Effective
length
Ø
Plate for
actuator
DS Damper Lengths
Ø (in.)
Effective Length (in.)
Product Code
K Factor
3 to 24
15-1/2
DSØDAMP
0.60 to 9999
Figure 102
DS Damper Length Short Manual
Ø (in.)
Effective Length (in.)
Product Code
K Factor
3 to 24
6-1/2
DSØDAMPS
0 to 9999
DS Damper Length Short
Ø (in.)
Effective Length (in.)
Product Code
K Factor
3 to 24
7-1/8
DSØVFR
0 to 9999
DS Vent Flow Regulator Damper Blade
Ø (in.)
Product Code
3 to 24
DSØVFN
For use on Cat. I and II boilers only
Figure 103
Figure 104
Figure 105
Cross Section View
Ø
Ø
6-1/2
7-1/2
1-11/16
3-3/8
Ø
7-1/2
3-3/8
Cross Section View
DS 2-Degree Elbow
Ø (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
1/8
7-1/8
DS3E2
0.04
4
1/8
7-1/8
DS4E2
0.04
5
1/8
7-1/4
DS5E2
0.04
6
1/8
7-1/4
DS6E2
0.04
7
1/8
7-1/4
DS7E2
0.04
8
1/8
7-1/4
DS8E2
0.04
9
1/8
7-3/8
DS9E2
0.04
10
1/8
7-3/8
DS10E2
0.04
12
1/8
7-3/8
DS12E2
0.04
14
1/8
7-1/2
DS14E2
0.03
16
1/8
7-5/8
DS16E2
0.03
18
1/8
7-5/8
DS18E2
0.03
20
1/8
7-3/4
DS20E2
0.03
22
1/8
7-3/4
DS22E2
0.03
24
1/8
7-7/8
DS24E2
0.03
Figure 106
DS VENTING ELBOWS
Rise
Rise
Rise
15°
30°
45°
Ø
Ø
Ø
Offset
Offset
Offset
DS 15-Degree Elbow
Ø (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
1
7-5/8
DS3E15
0.31
4
1
7-7/8
DS4E15
0.31
5
1-1/8
8-1/4
DS5E15
0.30
6
1-1/8
8-1/2
DS6E15
0.30
7
1-1/8
8-3/4
DS7E15
0.29
8
1-1/4
9
DS8E15
0.29
9
1-1/4
9-1/4
DS9E15
0.28
10
1-1/4
9-1/2
DS10E15
0.28
12
1-3/8
10
DS12E15
0.27
14
1-3/8
10-1/2
DS14E15
0.27
16
1-1/2
11
DS16E15
0.26
18
1-1/2
11-1/2
DS18E15
0.26
20
1-5/8
12-1/8
DS20E15
0.26
22
1-5/8
12-5/8
DS22E15
0.26
24
1-3/4
13-1/8
DS24E15U
0.26
DS 30-Degree Elbow
Ø (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
2-1/8
8
DS3E30
0.61
4
2-1/4
8-1/2
DS4E30
0.61
5
2-3/8
9
DS5E30
0.60
6
2-5/8
9-1/2
DS6E30
0.59
7
2-3/4
10
DS7E30
0.58
8
2-7/8
10-1/2
DS8E30
0.57
9
3
11
DS9E30
0.56
10
3-1/8
11-1/2
DS10E30
0.55
12
3-3/8
12-1/2
DS12E30
0.54
14
3-5/8
13-1/2
DS14E30
0.54
16
3-7/8
14-1/2
DS16E30
0.53
18
4-1/8
15-1/2
DS18E30
0.52
20
4-1/2
16-1/2
DS20E30
0.52
22
4-3/4
17-1/2
DS22E30
0.51
24
5
18-1/2
DS24E30
0.51
DS 45-Degree Elbow
Ø (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
3-3/8
8-1/8
DS3E45
0.26
4
4-1/4
10-1/4
DS4E45
0.26
5
4
9-1/2
DS5E45
0.22
6
4-1/4
10-1/2
DS6E45
0.17
7
4-1/2
10-7/8
DS7E45
0.16
8
4-7/8
11-5/8
DS8E45
0.14
9
5-1/8
12-3/8
DS9E45
0.13
10
5-3/8
13
DS10E45
0.12
12
6
14-1/2
DS12E45
0.11
14
6-5/8
15-7/8
DS14E45
0.11
16
7-1/8
17-1/4
DS16E45
0.10
18
7-3/4
18-3/4
DS18E45
0.09
20
8-3/8
20-1/8
DS20E45
0.08
22
8-7/8
21-1/2
DS22E45
0.08
24
9-1/2
23
DS24E45
0.08
Figure 107
Figure 108
Figure 109
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
DS VENTING TEES
Rise
88°
Ø
Offset
Offset
Offset
Offset
Height
Height
DS 88-Degree Elbow
Ø (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
6-3/8
6-5/8
DS3E88
0.60
4
7-3/8
7-5/8
DS4E88
0.54
5
8-3/8
8-5/8
DS5E88
0.48
6
9-1/4
9-5/8
DS6E88
0.42
7
10-1/4
10-5/8
DS7E88
0.39
8
11-1/4
11-5/8
DS8E88
0.37
9
12-1/4
12-5/8
DS9E88
0.34
10
13-1/8
13-5/8
DS10E88
0.32
12
15-1/8
15-5/8
DS12E88
0.29
14
17
17-5/8
DS14E88
0.27
16
19
19-5/8
DS16E88
0.25
18
20-7/8
21-5/8
DS18E88
0.24
20
22-7/8
23-5/8
DS20E88
0.23
22
24-3/4
25-5/8
DS22E88
0.21
24
26-5/8
27-5/8
DS24E88
0.20
DS 90-Degree Elbow
Ø (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
6-1/2
6-1/2
DS3E90
0.54
4
7-1/2
7-1/2
DS4E90
0.54
5
8-1/2
8-1/2
DS5E90
0.48
6
9-1/2
9-1/2
DS6E90
0.42
7
10-1/2
10-1/2
DS7E90
0.39
8
11-1/2
11-1/2
DS8E90
0.37
9
12-1/2
12-1/2
DS9E90
0.34
10
13-1/2
13-1/2
DS10E90
0.32
12
15-1/2
15-1/2
DS12E90
0.29
14
17-1/2
17-1/2
DS14E90
0.27
16
19-1/2
19-1/2
DS16E90
0.25
18
21-1/2
21-1/2
DS18E90
0.24
20
23-1/2
23-1/2
DS20E90
0.23
22
25-1/2
25-1/2
DS22E90
0.21
24
27-1/2
27-1/2
DS24E90
0.20
Figure 110
Figure 111
Figure 112
Figure 113
90°
43°
45°
Rise
Rise
Rise
Ø
Ø
Ø
DS 43-Degree Tee
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Prodct Code
K Factor
3
14-1/4
6-3/8
11-1/8
DS3T43
0.4
4
14-1/4
6-3/8
11-1/8
DS4T43
0.4
5
15-1/4
7-3/4
12-7/8
DS5T43
0.4
6
17-1/4
8-1/2
13-3/4
DS6T43
0.4
7
18-1/4
9-1/8
14-3/4
DS7T43
0.4
8
20-1/4
10-1/2
16-3/8
DS8T43
0.4
9
21-1/4
11-1/4
17-1/4
DS9T43
0.4
10
22-1/4
12-5/8
19
DS10T43
0.4
12
25-1/4
13-7/8
20-3/4
DS12T43
0.4
14
29-1/4
16
23-3/8
DS14T43
0.4
16
32-1/4
17-3/8
25-1/4
DS16T43
0.4
18
35
19-3/8
27-7/8
DS18T43
0.4
20
38
21-3/8
30-3/8
DS20T43
0.4
22
41
22-3/4
32-1/4
DS22T43
0.4
24
44
24-5/8
34-5/8
DS24T43
0.4
DS 45-Degree Tee
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Product Code
3
14-1/4
6-5/8
11
DS3T45
4
14-1/4
6-5/8
11
DS4T45
5
15-1/4
8-1/8
12-5/8
DS5T45
6
17-1/4
8-3/4
13-1/2
DS6T45
7
18-1/4
9-1/2
14-3/8
DS7T45
8
20-1/4
10-7/8
16
DS8T45
9
21-1/4
11-5/8
17
DS9T45
10
22-1/4
13
17-5/8
DS10T45
12
25-1/4
14-1/2
20-3/8
DS12T45
14
29-1/4
15-7/8
22-1/4
DS14T45
16
32-1/4
18-1/8
24-7/8
DS16T45
18
35
20-1/4
27-1/2
DS18T45
20
38
22-1/4
29-7/8
DS20T45
22
41
23-5/8
31-5/8
DS22T45
24
44
25-1/2
34
DS24T45
Available with smaller
snout and custom height.
Available with smaller
snout and custom height.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
DS 88-Degree Tee
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
11-1/4
6-3/8
5-5/8
DS3T88
1.21
4
11-1/4
6-3/8
5-5/8
DS4T88
1.21
5
12-1/4
7-3/8
6-1/4
DS5T88
1.21
6
13-1/4
7-3/8
6-5/8
DS6T88
1.21
7
14-1/4
8-3/8
7-1/4
DS7T88
1.21
8
15-1/4
8-3/8
7-5/8
DS8T88
1.21
9
16-1/4
9-3/8
8-1/4
DS9T88
1.21
10
17-1/4
9-3/8
8-5/8
DS10T88
1.21
12
19-1/4
10-3/8
9-3/4
DS12T88
1.21
14
21-1/4
11-3/8
10-3/4
DS14T88
1.21
16
23-1/4
12-3/8
11-3/4
DS16T88
1.21
18
25-1/4
13-3/8
12-3/4
DS18T88
1.21
20
27-1/4
14-3/8
13-3/4
DS20T88
1.21
22
29-1/4
15-3/8
14-3/4
DS22T88
1.21
24
31-1/4
16-3/8
15-3/4
DS24T88
1.21
Available with smaller
snout and custom height.
Available with smaller
snout and custom height.
Available with smaller
snout and custom height.
Offset
Offset
Height
90°
45°
Rise
Rise
Ø
Ø
DS 90-Degree Tee
Ø (in.)
Height (in.) Offset (in.)
Rise (in.)
Prodct Code
K Factor
3
11-1/4
6-3/8
5-1/2
DS3T90
1.21
4
11-1/4
6-3/8
5-1/2
DS4T90
1.21
5
12-1/4
7-3/8
6
DS5T90
1.21
6
13-1/4
7-3/8
6-1/2
DS6T90
1.21
7
14-1/4
8-3/8
7
DS7T90
1.21
8
15-1/4
8-3/8
7-1/2
DS8T90
1.21
9
16-1/4
9-3/8
8
DS9T90
1.21
10
17-1/4
9-3/8
8-1/2
DS10T90
1.21
12
19-1/4
10-3/8
9-1/2
DS12T90
1.21
14
21-1/4
11-3/8
10-1/2
DS14T90
1.21
16
23-1/4
12-3/8
11-1/2
DS16T90
1.21
18
25-1/4
13-3/8
12-1/2
DS18T90
1.21
20
27-1/4
14-3/8
13-1/2
DS20T90
1.21
22
29-1/4
15-3/8
14-1/2
DS22T90
1.21
24
31-1/4
16-3/8
15-1/2
DS24T90
1.21
DS 90-Degree Tee Y
Ø (in.)
Offset (in.)
Rise (in.)
Prodct Code
K Factor
3
4-1/2
8-1/2
DS3TY90
0.6
4
4-1/2
8-1/2
DS4TY90
0.6
5
5-1/4
10-1/8
DS5TY90
0.6
6
5-1/4
10-1/8
DS6TY90
0.6
7
6
10-7/8
DS7TY90
0.6
8
6
10-7/8
DS8TY90
0.6
9
6-5/8
12-5/8
DS9TY90
0.6
10
6-5/8
12-5/8
DS10TY90
0.6
12
7-3/8
13-1/4
DS12TY90
0.6
14
8-1/8
15
DS14TY90
0.6
16
8-3/4
16-3/4
DS16TY90
0.6
18
9-1/2
17-3/8
DS18TY90
0.6
20
10-1/4
18-1/8
DS20TY90
0.6
22
10-7/8
18-7/8
DS22TY90
0.6
24
11-5/8
20-1/2
DS24TY90
0.6
Available with smaller
snout and custom height.
DS Lateral Secre Tee
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Prodct Code
K Factor
3
10-1/8
9-1/4
8-7/8
DS3BT
0.55
4
10-1/8
9-1/4
8-7/8
DS4BT
0.55
5
12-1/8
10-1/2
10
DS5BT
0.55
6
13-1/8
11-3/4
11-1/8
DS6BT
0.55
7
15-1/8
13
12-1/4
DS7BT
0.55
8
16-1/8
14-1/4
13-3/8
DS8BT
0.55
9
18-1/8
12-1/2
12-1/2
DS9BT
0.55
10
19-1/8
13-3/8
13-3/8
DS10BT
0.55
12
22-1/8
15-1/4
15-1/4
DS12BT
0.55
14
25-1/8
17
17
DS14BT
0.55
16
28-1/8
18-7/8
18-7/8
DS16BT
0.55
18
30-7/8
20-3/4
20-3/4
DS18BT
0.55
20
33-7/8
22-1/2
22-1/2
DS20BT
0.55
22
36-7/8
24-3/8
24-3/8
DS22BT
0.55
24
39-7/8
26-1/8
26-1/4
DS24BT
0.55
Offset
4 to 8
9 to 24
Offset
Height
Height
Rise
Rise
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
DS VENTING ACCEDSORIES
Figure 118
Figure 119
Figure 120
Height
Available with smaller
snout and custom height.
Offset
Rise
Ø
DS Lateral Secre Tee 88-Degree
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Prodct Code
K Factor
3
11-1/8
9-1/4
9-1/4
DS3BT88
0.55
4
11-1/8
9-1/4
9-1/4
DS4BT88
0.55
5
12-1/8
10-1/2
10-1/2
DS5BT88
0.55
6
14-1/8
11-3/4
11-3/4
DS6BT88
0.55
7
16-1/8
13
13
DS7BT88
0.55
8
17-1/8
14-1/4
14-1/8
DS8BT88
0.55
9
19-1/8
12-5/8
13-1/4
DS9BT88
0.55
10
20-1/8
13-1/2
14-1/4
DS10BT88
0.55
12
23-1/8
15-3/8
16-1/8
DS12BT88
0.55
14
26-1/8
17-3/8
18-1/8
DS14BT88
0.55
16
29-1/8
19-1/8
20-1/8
DS16BT88
0.55
18
31-7/8
21
22
DS18BT88
0.55
20
34-7/8
22-7/8
24
DS20BT88
0.55
22
37-7/8
24-3/4
26
DS22BT88
0.55
24
40-7/8
26-5/8
28
DS24BT88
0.55
DS Barometric Tee
Ø (in.)
Height (in.)
Offset (in.)
Rise (in.)
Product Code
K Factor
3
11-1/4
5
5-1/2
DS3BMT
0.2
4
11-1/4
5
5-1/2
DS4BMT
0.2
5
12-1/4
5
6
DS5BMT
0.2
6
13-1/4
6
6-1/2
DS6BMT
0.2
7
14-1/4
7
7
DS7BMT
0.2
8
15-1/4
8
7-1/2
DS8BMT
0.2
9
16-1/4
9
8
DS9BMT
0.2
10
17-1/4
10
8-1/2
DS10BMT
0.2
12
19-1/4
12
9-1/2
DS12BMT
0.2
14
21-1/4
14
10-1/2
DS14BMT
0.2
16
23-1/4
16
11-1/2
DS16BMT
0.2
18
25-1/4
18
12-1/2
DS18BMT
0.2
20
27-1/4
20
13-1/2
DS20BMT
0.2
22
29-1/4
22
14-1/2
DS22BMT
0.2
24
31-1/4
24
15-1/2
DS24BMT
0.2
DS Tee Cap
Ø (in.)
Height (in.)
Product Code
3 to 24
3-1/2
DSØTC
Figure 121
Figure 122
DS Drain Tee Cap
Ø (in.)
Height (in.)
Product Code
3 to 24
3-1/2
DSØDTC
Drain Ø4 – Ø10, 1/4 NPT, 1/2 0.D
Drain Ø12 – Ø24, 3/8 NPT, 5/8 0.D
3-1/2
Drain NPT
Ø
DS Tapered Increaser
Ø (in.)
ØB Available (in.)
Height (in.)
Product Code
K Factor
3 to 9
Ø+1
11-7/8
DSØTIN(ØB)
0.05
3 to 22
Ø+2
12-7/8
DSØTIN(ØB)
0.10
3 to 9
Ø+3
13-7/8
DSØTIN(ØB)
0.15
3 to 20
Ø+4
14-7/8
DSØTIN(ØB)
0.20
3 to 7
Ø+5
15-7/8
DSØTIN(ØB)
0.25
3 to 18
Ø+6
16-7/8
DSØTIN(ØB)
0.30
Ø
Ø B
Height
Available with smaller
snout and custom height.
Offset
4 to 8
9 to 24
Offset
Height
Height
Rise
Rise
3-1/2
Ø
Drain NPT
DS Step Increaser
Ø (in.)
ØB Available (in.)
Height (in.)
Product Code
K Factor
3 to 22
5 to 24
10
DSØSIN(ØB)
KØ = (1-B2)2
KØB = KØ/B4
Ø
Ø B
Height
Figure 124
DS Eccentric Tapered Increaser
Ø
(in.)
ØB Available
(in.)
Height
(in.)
Offset
(in.)
Product Code
K Factor
3 to 9
Ø+1
12-1/4
1/2
DSØETIN(ØB)
0.05
3 to 22
Ø+2
13-1/4
1
DSØETIN(ØB)
0.10
3 to 9
Ø+3
14-1/4
1-1/2
DSØETIN(ØB)
0.15
3 to 20
Ø+4
15-1/4
2
DSØETIN(ØB)
0.20
3 to 7
Ø+5
16-1/4
2-1/2
DSØETIN(ØB)
0.25
3 to 18
Ø+6
17-1/4
3
DSØETIN(ØB)
0.30
Ø
Ø B
Height
Offset
DS Eccentric Step Increaser
Ø
(in.)
ØB Available
(in.)
Height
(in.)
Offset
(in.)
Product Code
K Factor
3 to 22
5 to 24
10
(ØB-ØA)/2
DSØESIN(ØB)
KØ = (1-B2)2
KØB = KØ/B4
Ø
Ø B
Height
Offset
Figure 125
Figure 126
Figure 127
Figure 128
DS Tapered Reducer
Ø (in.)
ØB Available (in.)
Height (in.)
Product Code
K Factor
5 to 10
Ø-1
11-7/8
DSØTRD(ØB)
0.07
6 to 24
Ø-2
12-7/8
DSØTRD(ØB)
0.09
6 to 12
Ø-3
13-7/8
DSØTRD(ØB)
0.11
8 to 24
Ø-4
14-7/8
DSØTRD(ØB)
0.13
9 to 24
Ø-5
15-7/8
DSØTRD(ØB)
0.15
10 to 24
Ø-6
16-7/8
DSØTRD(ØB)
0.17
Height
Ø
Ø B
DS Step Reducer
Ø (in.) ØB Available (in.) Height (in.)
Product Code
K Factor
5 to 24
4 to 22
10
DSØSRD(ØB)
KØ = (1-B2)2
KØB = KØ/B4
Height
Ø
Ø B
Ø
Ø B
Height
Offset
DS Eccentric Tapered Reducer
Ø (in.)
ØB Available
(in.)
Height
(in.)
Offset (in.)
Product Code
K Factor
5 to 10
Ø+1
12-1/4
1/2
DSØETRD(ØB)
0.07
6 to 24
Ø+2
13-1/4
1
DSØETRD(ØB)
0.09
6 to 12
Ø+3
14-1/4
1-1/2
DSØETRD(ØB)
0.11
8 to 24
Ø+4
15-1/4
2
DSØETRD(ØB)
0.13
9 to 24
Ø+5
16-1/4
2-1/2
DSØETRD(ØB)
0.15
10 to 24
Ø+6
17-1/4
3
DSØETRD(ØB)
0.17
B= Ø/ØB
DS Eccentric Step Reducer
Ø (in.) ØB Available
(in.)
Height
(in.)
Offset (in.)
Product Code
K Factor
5 to 10
4 to 22
10
(ØA-ØB0/2
DSØESRD(ØB)
KØ = (1-B2)2
KØB = KØ/B4
Figure 130
Figure 131
Width
Width
4 to 12 : Ø + 10
4 to 24 : Ø + 11
DS Wall Thimble
Ø (in.)
Height (in.)
Product Code
3 to 24
9 to 17
DSØWT
DS Wall Thimble Insulated
Ø (in.)
Height (in.)
Product Code
3 to 24
9 to 17
DSØWTI
Figure 132
10
Ø + Clearance + 3
DS Roof Thimble
Ø (in.)
Height (in.)
Product Code
3 to 24
10
DSØRT
Figure 133
Figure 134
Figure 135
10
Ø + Clearance + 3
Ø
Ø
1-1/2”
DS Roof Thimble Insulated
Ø (in.)
Height (in.)
Product Code
3 to 24
10
DSØRTI
DS Suspension Band
Ø (in.)
Product Code
3 to 24
DSØSB
DS Cradle Support
Ø (in.)
Product Code
3 to 24
DSØCS
B = Ø/ØB
4 to 12 : Ø + 10
4 to 24 : Ø + 11
DS Wall Support HD
Ø (in.)
A (in.)
B (in.)
C (in.)
Product Code
3
2 to 7
7
8
DS3WSHD
4
2 to 7
7
8
DS4WSHD
5
2 to 7
9
9
DS5WSHD
6
2 to 7
12
10
DS6WSHD
7
2 to 7
12
11
DS7WSHD
8
2 to 7
12
12
DS8WSHD
9
2 to 7
14
13
DS9WSHD
10
2 to 7
14
14
DS10WSHD
12
2 to 7
16
16
DS12WSHD
14
4 to 9
22
20
DS14WSHD
16
4 to 9
22
22
DS16WSHD
18
4 to 9
26
24
DS18WSHD
20
4 to 9
26
26
DS20WSHD
22
4 to 9
30
28
DS22WSHD
24
4 to 9
30
30
DS24WSHD
DS Roof Support
Ø (in.)
A (in.)
B (in.)
Product Code
3 to 12
6-1/2
7-5/8
DSØRS
14 to 24
22 to 32
1-1/2
DSØRS
DS Anchor Plate
Ø (in.)
A (in.)
Product Code
3 to 12
Ø+7
DSØAP
14 to 24
Ø+11
DSØAP
DS Anchor Plate HD
Ø (in.)
A (in.)
Product Code
3 to 12
Ø+7
DSØAPHD
14 to 24
Ø+11
DSØAPHD
Figure 136
Figure 137
Figure 138
Figure 139
Figure 140
A
B
A
Ø
A
A
A
B
22 to 32
Ø > = 12
Ø < = 14
Ø
C
DS Wall Support
Ø (in.)
Height (in.)
Product Code
3 to 12
2 to 5
DSØWS
14 to 24
4 to 7
DSØWS
Ø
Ø
2-1/2
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
DS Roof Brace
Ø (in.)
Product Code
3 to 24
DSØRB
DS Guy Wire Band
Ø (in.)
Product Code
3 to 24
DSØGWB
DS Centering Band
Ø (in.)
Product Code
3 to 24
DSØCB
Figure 142
Figure 143
Figure 144
3
Ø
Ø
Ø
6
DS Wall Guide
Ø (in.)
A (in.)
Product Code
3 to 24
2 to 5-1/2
DSØWG
14 to 24
4 to 7-1/2
DSØWG
DS Guy Support
Ø (in.)
Product Code
3 to 24
DSØGS
DS Double Male Adaptor
Ø (in.)
Effective Length (in.)
Product Code
3 to 24
3-7/8
DSØDMA
DS Male Flange Adaptor
Ø (in.)
Effective Length (in.)
Product Code
3 to 24
4-7/8
DSØMFA
Figure 145
Figure 146
Figure 147
Figure 148
Ø
Ø
1/2
Effective
length
Effective
length
Ø
A
3/4
3
Ø
DS Anchor Plate Length (APL)
Ø (in.)
A (in.)
Product Code
3 to 12
Ø + 7
DSØAPL
14 to 24
Ø + 11
DSØAPL
Figure 141
9-9/32
Ø
A
DS Female Flange Adaptor
Ø (in.)
Effective Length (in.)
Product Code
3 to 24
4-1/4
DSØFFA
DS to DSD Adaptor
Ø (in.)
Effective Length (in.)
Product Code
3 to 24
7-7/8
DSØDSDA
Figure 149
Figure 150
Ø
1/2
Effective
length
Ø
7-7/8
DS Storm Collar
Ø (in.)
Effective Length (in.)
Product Code
3 to 24
6-1/4
DSØSC
Figure 155
Ø
7
DuraSeal-Flex
Ø (in.)
Flex Length (ft.)
Product Code
3 to 9
20
DSØFLX-20
25
DSØFLX-25
30
DSØFLX-30
35
DSØFLX-35
4
200
DS4FLX-200
5
125
DS5FLX-125
6 & 7
100
DSØFLX-100
8
50
DS8FLX-50
3 to 12
CUSTOM
DSØFLX-XX
Figure 151
DuraSeal-Flex Female Adapter
Ø (in.)
Effective Length (in.)
Product Code
3 to 12
9-11/32
DSØAFF
Figure 152
DuraSeal-Flex Male Adapter
Ø (in.)
Effective Length (in.)
Product Code
3 to 12
7
DSØAMF
Figure 153
DuraSeal-Flex to DuraSeal-Flex
Ø (in.)
Effective Length (in.)
Product Code
3 to 12
__
DSØAF
Figure 154
DS Flat Flashing
Ø (in.)
A (in.)
Product Code
3
16
DS3FH
4
16
DS4FH
5
16
DS5FH
6
16
DS6FH
7
18
DS7FH
8
26
DS8FH
9
26
DS9FH
10
28
DS10FH
12
30
DS12FH
14
31
DS14FH
16
34
DS16FH
18
36
DS18FH
20
38
DS20FH
22
40
DS22FH
24
42
DS24FH
Ø
A
12
Ø
A
12-1/2
DS Adjustable Flashing
Ø (in.)
A (in.)
Height (in.)
Product Code
3
30
12-1/2
DS3FAH
4
30
12-1/2
DS4FAH
5
30
12-1/2
DS5FAH
6
32
12-1/2
DS6FAH
7
32
12-1/2
DS7FAH
8
34
12-1/2
DS8FAH
9
35-3/8
12-1/2
DS9FAH
10
36-1/2
12-1/2
DS10FAH
12
38-1/2
12-1/2
DS12FAH
14
41
12-1/2
DS14FAH
16
43
12-1/2
DS16FAH
18
45
12-1/2
DS18FAH
20
47-1/4
12-1/2
DS20FAH
22
19-1/2
12-1/2
DS22FAH
24
51-1/2
12-1/2
DS24FAH
Adjustable from 5° to 30°
Roof pitch 1/12 to 7/12
DS Rain Cap
Ø (in.)
Product Code
Product Code with Bird Screen
K Factor
3 to 24
DS3RC
DSØRCB
.50
Figure 158
Ø
DS Screened Termination
Ø (in.)
Product Code
K Factor
3 to 24
DSØST
.14
DS 30° Screen Termination
Ø (in.)
Product Code
K Factor
3 to 24
DSØSTA
.70
Figure 159
Figure 160
Ø
Ø
Ø + 4
3-1/2
30°
DS Exit Cone
Ø (in.)
Product Code
K Factor
3 to 24
DSØEC
.60
Figure 161
Ø
90% Ø
15
DS Termination Tee
Ø (in.)
Product Code
K Factor
3 to 24
DSØTT
.35
Figure 162
Ø
Ø
Ø + 6
Ø + 4-1/2
DS Mitre Cut
Ø (in.)
Product Code
K Factor
3 to 24
DSØMC
.14
DS OEM Termination
Ø (in.)
Product Code
K Factor
3 to 24
DSØOEMTAU
0
Figure 163
Figure 164
Ø
Ø + 3-1/2
M&G DuraVent, Inc. (“DuraVent”) provides this limited lifetime
warranty for all of its products with the exception of Ventinox®
(lifetime), and PolyPro® (ten years). Subject to the limitations
set forth below, DuraVent warrants that its products will be free
from defects in material or manufacturing, if properly installed,
maintained and used. DuraVent products are fully warranted
if installed only by a professional installer. This Warranty is
transferable from the original homeowner to the buyer of the home.
This warranty does not cover normal wear and tear, smoke damage
or damage caused by chimney fires, acts of God, or any product
that was: (1) purchased other than from an authorized DuraVent
dealer, retailer or distributor; (2) modified or altered; (3) improperly
serviced, inspected or cleaned; or (4) subject to negligence or any
use not in accordance with the installation instructions included with
the product as determined by DuraVent. Installation instructions are
available online at www.duravent.com under Support/Literature
and through our Customer Service Department 800-835-4429 or
[email protected]. This limited lifetime warranty
applies only to parts manufactured by DuraVent.
DuraVent provides the following warranties for its products: One
Hundred Percent (100%) MSRP 15 years from the date of purchase,
and Fifty Percent (50%) thereafter, except for the following
limitations on: all Termination Caps and DuraBlack® are warranted
at One Hundred Percent (100%) for five years.
All warranty obligations of DuraVent shall be limited to repair or
replacement of the defective product pursuant to the terms and
conditions applicable to each product line. These remedies shall
constitute DuraVent’s sole obligation and sole remedy under this
warranty. This warranty provides no cash surrender value. The
terms and conditions of this warranty may not be modified, altered
or waived by any action, inaction or representation, whether oral or
in writing, except upon the express, written authority of an executive
officer of DuraVent.
Corn, bio-fuels, driftwood or other wood containing salt,
preservative-treated lumber, plastic and household trash or garbage,
or wood pellets containing such materials must not be burned in the
appliance or fireplace. In case of a chimney fire, the chimney must
be inspected and approved by a certified Chimney Sweep before
reuse. After each annual inspection, maintenance, and cleaning,
the certified Chimney Sweep must fill out and date the appropriate
section of the warranty card provided with the chimney liner.
LIMITATIONS ON INTERNET SALES: Notwithstanding any other
terms or conditions of this Limited Lifetime Warranty, DuraVent
provides no warranty for the following specific products if such
products are not installed by a qualified professional installer:
DuraTech®, DuraTech® DTC, DuraPlus HTC®, DuraChimney® II,
PelletVent Pro®, DirectVent Pro®, FasNSeal®, FasNSeal® W2,
FasNSeal® Flex, and PolyPro®, and DuraVent’s relining products
including DuraLiner®, DuraFlex® (SW, Pro, 316, 304), and
Ventinox®. For purposes of this warranty, a trained professional
installer is defined as one of the following: licensed contractors
with prior chimney installation experience, CSIA Certified Chimney
Sweeps, NFI Certified Specialists, or WETT Certified Professionals.
DuraVent must be notified and given the opportunity to inspect
defective product prior to replacement under the terms of this
limited lifetime warranty. All warranty claims must be submitted
with proof of purchase. Labor and installation costs are not covered
under this warranty. To obtain warranty service contact: DuraVent
Warranty Service, 877 Cotting Ct., Vacaville CA 95688, or call 800-
835-4429.
WHERE LAWFUL, DURAVENT DISCLAIMS ALL OTHER
WARRANTIES, INCLUDING BUT NOT LIMITED TO IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE. IN NO EVENT WILL DURAVENT BE
LIABLE FOR INCIDENTAL, CONSEQUENTIAL, PUNITIVE OR
SPECIAL DAMAGES OR DIRECT OR INDIRECT LOSS OF ANY KIND,
INCLUDING BUT NOT LIMITED TO PROPERTY DAMAGE AND
PERSONAL INJURY. DURAVENT’S ENTIRE LIABILITY IS LIMITED
TO THE PURCHASE PRICE OF THIS PRODUCT. SOME STATES DO
NOT ALLOW LIMITATIONS ON IMPLIED WARRANTIES, OR THE
EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL
DAMAGES, SO THE ABOVE LIMITATIONS AND EXCLUSIONS
MAY NOT APPLY TO YOU. THIS LIMITED WARRANTY GIVES YOU
SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER
RIGHTS THAT VARY FROM STATE TO STATE.
For the most up-to-date installation instructions, see
www. duravent.com
REV 2.27.2013
Manufactured in Vacaville CA and Albany NY
DuraVent Limited Lifetime Warranty
This product has a 15 year limited warranty. Please read the warranty to be
familiar with its coverage.
Retain this manual. File it with your other documents for future reference.
PRODUCT REFERENCE INFORMATION
Please contact DuraVent for the phone number of your nearest DuraVent dealer
who will answer your questions or address your concerns.
Normally, all parts should be ordered through your DuraVent distributor or
dealer. Parts will be shipped at prevailing prices at time of order.
When ordering repair parts, always give the following information:
1. The model number of the vent system.
2. The part number.
3. The description of the part.
4. The quantity required.
5. The installation date of the chimney system.
If you encounter any problems or have any questions concerning the installation
or application of this system, please contact your dealer.