Froling RBG 3200 Touch Operating Instructions Manual
Read Online
Read the Froling RBG 3200 Touch Operating Instructions Manual online using the built-in PDF viewer.
Text of the manual
Room console RBG 3200 Touch
Translation of the original German operating instructions for the operator
Read and follow the instructions and safety information!
Technical changes, typographical errors and omissions reserved!
B0780115_en | Edition 08/06/2015
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
Table of contents
1
General
4
1.1
About these instructions
4
1.2
Safety information
4
2
Installation
5
2.1
Initial start-up
5
2.1.1
Connecting the bus cable
5
2.1.2
Setting end jumpers
6
2.1.3
Calibrate the display
6
2.1.4
Setting the module address
6
3
Overview of the basic functions
8
3.1
Visual display
8
3.1.1
Status LED
8
3.1.2
Icons
9
4
Operation
10
4.1
Navigation within the info menu
10
4.2
Navigation within the system menu
10
4.2.1
Navigating the menus
10
4.3
Adjusting parameters
12
4.4
Setting times
13
4.5
Setting the room temperature setpoints
15
4.6
Set the heating circuit mode
15
4.6.1
“OFF” mode
16
4.6.2
“Auto” mode
16
4.6.3
“Party” mode
16
4.6.4
“Setback” mode
16
5
Menu overview and parameters
17
5.1
Heating
17
5.1.1
Heating - Status
17
5.1.2
Heating - Temperatures
18
5.1.3
Heating - Times
19
5.2
Water
20
5.2.1
Water - Status
20
5.2.2
Water - Temperatures
21
5.2.3
Water - Times
21
5.3
Solar
22
5.3.1
Solar - Status
22
5.3.2
Solar - Temperatures
24
5.3.3
Solar - Heat meter
25
5.4
Buffer tank
26
5.4.1
Buffer tank - Status
26
5.4.2
Buffer tank - Temperatures
27
5.4.3
Buffer tank - Times
27
5.5
Boiler 2
28
Table of contents
2
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
Boiler 2 - Status
28
5.5.2
Boiler 2 - Temperatures
29
5.6
Difference regulator
30
5.6.1
Difference regulator - Status
30
5.7
Circulation pump
31
5.7.1
Circulation pump - Status
31
5.7.2
Circulation pump - Temperatures
31
5.7.3
Circulation pump - Times
31
5.8
System
32
5.8.1
System - Current values
32
5.8.2
System - Display operating rights
33
Froling Connect
33
5.9
Diagnostics
34
5.9.1
Diagnostics - Error display
34
5.10
Display settings
34
5.10.1
Display settings - General
34
Network settings
35
5.10.2
Display settings - Date / Time
35
6
Troubleshooting
36
6.1
Procedure for fault messages
36
7
FAQ
38
7.1
Updating the software of the touch control
38
7.2
Calibrating the touchscreen
40
Table of contents
Operating Instructions RBG 3200 Touch | B0780115_en
3
1.1 About these instructions
These instructions contain information about the electrical connection, operation,
control parameters and troubleshooting for the RBG 3200 Touch room console. All
parameters, which are visible at the “customer” operator level, are shown. The
parameters actually displayed may vary depending on system configuration and
operating level.
The constant further development of our products means that there may be minor
differences from the pictures and content. If you discover any errors, please let us
know: [email protected].
Subject to technical change.
Froling's RBG 3200 Touch room console is a multifunctional device for convenient
operation of the boiler from your living room.
1.2 Safety information
DANGER
When working on electrical components:
Risk of electrocution!
When work is carried out on electrical components:
❒Only have work carried out by a qualified electrician
❒Observe the applicable standards and regulations
➥Work must not be carried out on electrical components by unauthorised
persons
1
General
About these instructions
4
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
❒Run the bus cable through the large grommet
❒Fit the holding frame as shown at the desired position in the room using the
anchors and screws provided
➥The large grommet must be on the right!
➥It is recommended to install the device above a flush-mounted socket so that
there is plenty of space to stow away the bus cable.
2.1 Initial start-up
NOTICE
You should have the initial startup carried out by the authorised heating engineer
from Froling customer services.
2.1.1 Connecting the bus cable
For the bus connections between the individual modules, cable type
LIYCY paired 2x2x0.5 should be used. The connection to the 5-pin plugs should be
carried out according to the following diagram:
+UBUS
CAN H
CAN L
+UBUS
CAN H
CAN L
Braided shield
White
Green
Yellow
Brown
Braided shield
White
Green
Yellow
Brown
Installation
2
Initial start-up
Operating Instructions RBG 3200 Touch | B0780115_en
5
2.1.2 Setting end jumpers
To ensure that the bus system continues to work properly,
the end jumpers (J) need to be set.
❒If there is an RBG 3200 Touch at the end of a bus
system, the end jumper at this module must be set. All
the previous ones, with the exception of that at the
core module, have to be deleted.
2.1.3 Calibrate the display
Once the power supply has been switched on for the first time, the RBG 3200 Touch
starts by calibrating the display. To calibrate the touchscreen, you much press five
points indicated by a crosshair in the order shown.
NOTICE
Inaccurate calibration
If you do not tap the indicated points accurately, the control may stop working
properly and a software update may be required.
2.1.4 Setting the module address
Once the display has been calibrated, the module address must be set. If it is the first
RBG 3200 Touch in the bus system, set module address 1. Number any others in
sequence.
NOTICE! Do not select an address of 0 as it leads to malfunctions with the RBG 3200
Touch!
2
Installation
Initial start-up
6
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
Once you have set the module address, you will need to restart the boiler controller
(switch main switch on boiler off and on). All of the system information will then be
loaded into the RBG 3200 Touch. This process can be time-consuming.
The following screen appears after the RBG 3200 Touch’s first system start:
The basic screen displays only the external temperature as no components have been
assigned to the RBG 3200 Touch yet.
Installation
2
Initial start-up
Operating Instructions RBG 3200 Touch | B0780115_en
7
3 Overview of the basic functions
3.1 Visual display
A
B
F
C
D
G
H
I
E
J
K
Number
Description
A
Date and time display
B
Shows the current external temperature
C
Shows the current temperature at the allocated DHW tank. This field is hidden if
no DHW tank has been assigned.
D
Shows the current room temperature of the allocated heating circuit. This field is
hidden if no heating circuit has been assigned.
E
Down arrow to decrease the desired temperature setpoint for the room
F
Shows the temperature setpoint for the room
G
Up arrow to increase the desired temperature setpoint for the room
H
Info menu icon for viewing all system information
I
System menu icon for opening the system settings All parameters can be
displayed/edited depending on the user level
J
Favourites menu icon for viewing the available quick functions
K
Mode icon for setting the mode of the allocated heating circuit
3.1.1 Status LED
The status LED shows the operating status of the system:
▪GREEN flashing (interval: 5 sec OFF, 1 sec ON): Off / Boiler off
▪GREEN constant: BOILER SWITCHED ON
▪ORANGE flashing: WARNING
▪RED flashing: FAULT
3
Overview of the basic functions
Visual display
8
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
Tapping the Home icon takes you back to the basic display from any menu.
Back icon
Takes you back up one menu level of the system menu. Can be used to return to the
basic display.
Info menu icon
To access all system information. The information is ordered in a circular buffer. The
right and left arrows are used to switch between the individual pages.
System menu icon
Opens the system settings. Depending on the operating level and system
configuration, the various menu items available are organised in a circular buffer
which can be navigated using the right and left arrow.
Quick menu icon
Opens the quick menu. Various functions are available depending on the user level,
system configuration and current status.
Pen icon
If a parameter has the pen symbol beside it, it means that the parameter can be
adjusted. If you open the parameter, either the numeric keypad or a list box for
changing the value of the parameter will appear.
Confirm icon
Confirms any values entered and activates parameters.
Cancel icon
Discards any values entered without saving and closes messages.
An “i” at the top left after selecting a parameter indicates additional information
available for this parameter. Pressing the Cancel icon takes you back to the selected
parameter.
Overview of the basic functions
3
Visual display
Operating Instructions RBG 3200 Touch | B0780115_en
9
4.1 Navigation within the info menu
The info menu displays all the information about the system. Use the right and left
arrows to go to the individual menu items for the relevant information. The next time
you open the info menu, the last page viewed will be displayed.
4.2 Navigation within the system menu
The system menu shows the menu items available depending on the user level and
the system configuration. Tap the icon to open the corresponding menu item. The
system menu is structured in a circular buffer, which can be navigated using the right
and left arrows. The next time you open the system menu, the last page viewed will be
displayed.
4.2.1 Navigating the menus
After you open a menu item, the corresponding status display with current values will
appear. If, for example, several heating circuits are installed, you can use the right and
left arrows to navigate to the desired heating circuit. You can open any other menu
items available in the same way.
4
Operation
Navigation within the info menu
10
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
The individual menus are divided into tabs for quicker navigation.
❒Tap on the desired tab
➥The list of parameters for the selected area will appear
The parameter list shows three parameters. The up and down arrows can be used to
scroll through longer lists of parameters. If you have reached the start or end of the
parameter list, the relevant arrow symbol will become inactive.
Operation
4
Navigation within the system menu
Operating Instructions RBG 3200 Touch | B0780115_en
11
4.3 Adjusting parameters
A parameter can only be adjusted if there is a pen icon beside it. Depending on the
type of parameter, either the numeric keypad...
... or a list box will appear.
In both cases you need to tap the confirm icon to save the entry.
4
Operation
Adjusting parameters
12
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
4.4 Setting times
The desired time window for the component can be set in the "Times" tab in the
individual menus of the heating components (heating circuits, DHW tanks etc.). The
structure of the time menu and the procedure for changing the times are always the
same.
❒Use the left or right arrow to navigate to the desired day of the week
❒Tap the symbol under the day of the week
➥The edit window will appear
You can specify up to four time windows per component and day.
❒Tap the desired time window
❒The time window will open for editing
❒Set the start and end time for the time window using the up and down arrows
❒Save the time window setting by tapping on the confirm icon
Operation
4
Setting times
Operating Instructions RBG 3200 Touch | B0780115_en
13
To delete a time window, set the times so that the hour and minute displays are
replaced by two dashes.
If you want to apply the time window setting to another day in addition, you can do this
by activating the relevant day.
4
Operation
Setting times
14
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
4.5 Setting the room temperature setpoints
The desired room temperature setpoint can be set in the lower left area of the basic
display:
❒Change the temperature in the room using the up and down arrows
NOTICE! The room temperature can only be changed in automatic mode (when the
heating circuit control is active) and in party mode!
4.6 Set the heating circuit mode
The current mode for the allocated heating circuit is displayed in the basic display to
the left of the mode icon.
Operation
4
Setting the room temperature setpoints
Operating Instructions RBG 3200 Touch | B0780115_en
15
Setting another mode:
❒Tap the mode icon
➥Mode-select is displayed
❒Tap the appropriate icon to change the heating circuit mode
The following modes are available:
4.6.1 “OFF” mode
The allocated heating circuit is switched off, the frost protection function remains
active.
4.6.2 “Auto” mode
The allocated heating circuit and the allocated DHW tank are controlled according to
the timed program settings.
4.6.3 “Party” mode
The allocated heating circuit is set to heating mode until the end of the next heating
phase or until a different mode is activated.
4.6.4 “Setback” mode
The allocated heating circuit is set to setback mode until the start of the next heating
phase or until a different mode is activated. The temperature setpoint displayed in
setback mode on the basic screen is for display purposes only and cannot be
changed. To change this, go to the “Heating” menu → under the “Temperature” tab.
4
Operation
Set the heating circuit mode
16
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
5 Menu overview and parameters
5.1 Heating
5.1.1 Heating - Status
System menu
Heating
Control heating circuit according to program (NO -> heating circuit is switched off)
YES
▪YES: The heating circuit is operated according to the selected heating times.
▪NO: Heating circuit is completely switched off, frost protection remains active!
Actual flow temperature
46°C
Shows the current flow temperature.
Flow temperature setpoint
52°C
Shows the calculated flow temperature setpoint.
Room temperature
20°C
Prerequisite: Heating circuit used in conjunction with remote control
Shows the current room temperature.
Override switch
Auto
Prerequisite: Heating circuit used in conjunction with remote control
Shows the current heating circuit mode:
▪Party: party mode; the current or next setback program is ignored
▪Setback: setback mode; the heating phases are ignored
▪Auto: automatic mode: heating phases according to the set heating times
▪Off: switched-off; heating circuit deactivated, only frost protection!
Outside air temperature
2°C
Shows the current external temperature.
Menu overview and parameters
5
Heating
Operating Instructions RBG 3200 Touch | B0780115_en
17
5.1.2 Heating - Temperatures
System menu
Heating
Desired room temperature during heating mode
20°C
Prerequisite: Heating circuit used in conjunction with remote control
Room temperature which is regulated during the set heating times
Desired room temperature during setback mode
16°C
Prerequisite: Heating circuit used in conjunction with remote control
Room temperature which is regulated outside of the set heating times
Flow temperature SP at external temperature of +10°C
40°C
First setting point for definition of heating curve
Flow temperature SP at external temperature of -10°C
60°C
Second setting point for definition of heating curve
Reduction of flow temperature in setback mode
15°C
The flow temperature is reduced by this value during setback mode.
External temperature below which the heating circuit pump switches on in heating mode
18°C
If the external temperature exceeds this value during heating, the heating circuit pumps and mixing valve are
deactivated.
5
Menu overview and parameters
Heating
18
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
External temperature below which the heating circuit pump switches on in setback mode
7°C
If the external temperature falls below this value in setback mode, the heating circuit pumps and mixing valve
are activated.
Frost protection temperature
10°C
If the room temperature or the flow temperature is lower than the set value, the heating circuit pump will be
switched on and the heating circuit mixer keeps to the maximum heating circuit flow temperature that is set.
5.1.3 Heating - Times
System menu
Heating
⇨ See "Setting times" [page 13]
Menu overview and parameters
5
Heating
Operating Instructions RBG 3200 Touch | B0780115_en
19
5.2.1 Water - Status
System menu
Water
DHW tank top temperature
58°C
Current temperature of the DHW tank. The DHW tank is heated when the time window for the DHW tank load‐
ing is reached and the current temperature of the DHW tank has fallen below the value using the parameter
“Reload if DHW tank temperature is below”. A loading of the DHW tank takes place when either
the time window has elapsed or the temperature value which is set under “Set DHW temperature” is
reached.
DHW tank bottom temperature
55°C
Prerequisite: Solar panel system is regulated by Froling!
Current temperature in the area of the reference sensor of the solar panel system.
DHW tank pump control
0%
Specifies the speed of the DHW tank pump as a percentage of maximum speed.
5
Menu overview and parameters
Water
20
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
5.2.2 Water - Temperatures
System menu
Water
Set DHW temperature
58°C
When this DHW temperature is reached, DHW tank loading is stopped.
Reload if DHW tank temperature is below
45°C
If the DHW tank temperature falls below the value set here, the time window is active and the loading source
(boiler or buffer tank) indicates the set loading increase, and the DHW tank loading is started.
5.2.3 Water - Times
System menu
Water
⇨ See "Setting times" [page 13]
Menu overview and parameters
5
Water
Operating Instructions RBG 3200 Touch | B0780115_en
21
5.3.1 Solar - Status
System menu
Solar
Collector temperature
80°C
Display of the current temperature at the solar collector.
Solar temperature buffer tank bottom
43°C
Display of the current temperature at the solar collector in the buffer tank.
Actual power from solar heat meter [kW]
0.00
Display of the current output which is generated by the solar collector. The calculation of the output is only
performed either when a per litre output of the collector pump has been set or an external volume pulse trans‐
mitter is used. In order to perform the calculation more precisely, the use of a collector return feed sensor is
recommended.
Flow through [l/h]
0l
Prerequisite: External volume pulse transmitter installed
Display of the water quantity currently being pumped through the solar collector.
Todays yield [kWh]
0
Display of the heat quantity that has been supplied by the solar panel system today.
Total yield [kWh]
0
Display of the heat quantity which has been supplied by the solar panel system since activation of the heat
meter.
DHW tank bottom temperature
55°C
Current temperature in the area of the reference sensor of the solar panel system.
5
Menu overview and parameters
Solar
22
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
Heat exchanger sec. return temperature (line to buffer tank)
78°C
Prerequisite: Hydraulic System 12 or Hydraulic System 13
Current temperature at heat exchanger flow on the secondary side.
Collector pump runtime
1h
Display of the total runtime of the collector pump.
Collector pump control
52%
Display of the current speed of the collector pump as a percentage of maximum speed.
Pump between heat exchanger and buffer tank
100%
Prerequisite: Hydraulic System 12 or Hydraulic System 13
Display of the current speed of the pump between heat exchanger and buffer tank.
Pump between heat exchanger and DHW tank
0%
Prerequisite: Hydraulic System 12
Display of the current speed of the pump between heat exchanger and DHW tank.
Diverter valve for top/bottom coils
100%
Prerequisite: Hydraulic System 12 or Hydraulic System 13
Current control of the isolating valve on the solar side.
▪0% … bottom buffer tank
▪100% … top buffer tank
Menu overview and parameters
5
Solar
Operating Instructions RBG 3200 Touch | B0780115_en
23
5.3.2 Solar - Temperatures
System menu
Solar
Boiler target temperature during solar charging
75°C
Up to this temperature the DHW tank is heated by the solar system If the solar panel system is equipped with
an isolating valve for switching between DHW tank and buffer solar element, then this parameter is responsible
for switching between both of these solar elements.
Temp differential to start collector pump
10°C
The collector pump activates when the collector temperature exceeds the reference temperature in the DHW
tank or buffer tank by this value.
Temp difference to stop collector pump
5°C
The collector pump switches off when the difference between the collector temperature and reference temper‐
ature in the DHW tank or buffer tank is lower than this value.
Maximum buffer tank bottom temperature during solar charging
85°C
If the sensor for the solar reference temperature in the buffer tank exceeds the specified value, the collector
pump is switched off.
NOTICE! This parameter is only relevant for systems used in conjunction with a buffer tank!
5
Menu overview and parameters
Solar
24
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
5.3.3 Solar - Heat meter
System menu
Solar
Collector temperature
80°C
Display of the current temperature at the solar collector.
Actual power from solar heat meter [kW]
0.00
Display of the current output which is generated by the solar collector. The calculation of the output is only
performed either when a per litre output of the collector pump has been set or an external volume pulse trans‐
mitter is used. In order to perform the calculation more precisely, the use of a collector return feed sensor is
recommended.
Flow through [l/h]
0l
Prerequisite: External volume pulse transmitter installed
Display of the water quantity currently being pumped through the solar collector.
Todays yield [kWh]
0
Display of the heat quantity that has been supplied by the solar panel system today.
Total yield [kWh]
0
Display of the heat quantity which has been supplied by the solar panel system since activation of the heat
meter.
Menu overview and parameters
5
Solar
Operating Instructions RBG 3200 Touch | B0780115_en
25
5.4 Buffer tank
5.4.1 Buffer tank - Status
System menu
Buffer tank
Buffer tank top temperature
67°C
Shows the current temperature in the top part of the buffer tank.
Buffer tank temperature, sensor 2
58°C
Prerequisite: Master boiler in the cascade or hydraulic system 4 or fuel amount calculation
Shows the current temperature in the top part of the buffer tank.
Buffer tank temperature, sensor 3
56°C
Prerequisite: Master boiler in the cascade or hydraulic system 4 or fuel amount calculation
Shows the current temperature in the lower part of the buffer tank.
Buffer tank bottom temperature
40°C
Shows the current temperature in the lower part of the buffer tank.
Buffer tank pump control
40%
Display of the current speed of the buffer loading pump.
Buffer tank charge
65%
Prerequisite: Master boiler in the cascade or hydraulic system 4 or fuel amount calculation
Displays the current buffer tank charge.
5
Menu overview and parameters
Buffer tank
26
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
5.4.2 Buffer tank - Temperatures
System menu
Buffer tank
Heating circuit release from following buffer tank temperature
30°C
Temperature value which must be reached to release the heating circuit pumps in the top part of the buffer
tank.
NOTICE! This parameter applies for all available heating circuits!
Buffer tank fully loaded if temperature difference between boiler and bottom buffer tank
10°C
From this difference between the boiler temperature setpoint that has been set and the current temperature in
the lower part of the buffer tank, buffer tank loading is stopped.
5.4.3 Buffer tank - Times
System menu
Buffer tank
⇨ See "Setting times" [page 13]
Menu overview and parameters
5
Buffer tank
Operating Instructions RBG 3200 Touch | B0780115_en
27
5.5 Boiler 2
5.5.1 Boiler 2 - Status
System menu
Boiler 2
Temperature of secondary boiler
28°C
Display of the current boiler temperature of the secondary boiler.
Burner relay status
0
Shows the current status of the burner relay:
▪0: Secondary boiler not active
▪1: Secondary boiler active
Manual start of secondary boiler (only when ID fan is switched off)
OFF
▪OFF: Secondary boiler is controlled according to the program that is set
▪ON: Secondary boiler is activated immediately
NOTICE! Burner blockage noted.
5
Menu overview and parameters
Boiler 2
28
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
5.5.2 Boiler 2 - Temperatures
System menu
Boiler 2
Secondary boiler start delay
10m
If there is a requirement from the heating circuit or DHW tank and the buffer tank or boiler has insufficient tem‐
perature, the secondary boiler starts after the specified delay time set here.
Secondary boiler minimum runtime
10m
If the secondary boiler is started, it will run for at least the length of time set here.
Minimum temperature of secondary boiler
55°C
When the secondary boiler reaches the specified temperature, the loading pump is started and switches the
isolating valve.
Temperature difference between secondary boiler and buffer tank
10°C
Temperature difference between secondary boiler and upper temperature in layered tank to activate the load‐
ing pump of the secondary boiler.
Secondary boiler delivery temperature
95°C
Prerequisite: Hydraulic system 3 in conjunction with a manually loaded secondary boiler.
If the secondary boiler exceeds the specified temperature, the isolating valve switches and skims the boiler.
Menu overview and parameters
5
Boiler 2
Operating Instructions RBG 3200 Touch | B0780115_en
29
5.6 Difference regulator
5.6.1 Difference regulator - Status
System menu
Diff. control
Heat source sensor
27°C
Display of the current heat source temperature of the differential controller (e.g. tiled stove with water pock‐
et, ...)
Heat sink sensor
40°C
Display of the current temperature of the heat sink for the differential controller (e.g. layered tank, ...)
Pump speed
0%
Specifies the current speed of the differential controller pump.
5
Menu overview and parameters
Difference regulator
30
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
5.7 Circulation pump
5.7.1 Circulation pump - Status
System menu
Circ. pump
Return temperature in secondary circulation line
45°C
Display of the current temperature at the return feed sensor of the circulation line.
NOTICE! If the parameter “Return sensor present” is set to “NO”, 0°C is permanently displayed.
Flow switch on the domestic hot water line
0
▪0: Flow switch detects no flow rate.
▪1: Flow switch detects flow rate.
Speed of the circulation pump
100%
Specifies the current speed of the circulation pump.
5.7.2 Circulation pump - Temperatures
System menu
Circ. pump
Switch off the pump at what return temperature in the circulation line
35°C
If the set temperature at the return circulation line is reached, the circulation pump will be deactivated.
NOTICE! Parameter only relevant when using a return feed sensor in the circulation line!
5.7.3 Circulation pump - Times
System menu
Circ. pump
⇨ See "Setting times" [page 13]
Menu overview and parameters
5
Circulation pump
Operating Instructions RBG 3200 Touch | B0780115_en
31
5.8.1 System - Current values
System menu
System
Current values
Display of the current value for the relevant parameter. The parameters displayed depend on the boiler config‐
uration!
Boiler temperature
25°C
Flue gas temperature
28°C
ID fan control
0%
Residual oxygen content
1.9%
Outside air temperature
2°C
Service hours
15h
Hours since last maintenance
15h
Software version
Version 50.04
Build 05.10
5
Menu overview and parameters
System
32
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
5.8.2 System - Display operating rights
System menu
System
Display
operating rights
Froling Connect
System menu
System
Display
operating rights
Froling Connect
For connection via the froeling-connect.com online platform using a touch display, the issue of a password is
required.
NOTICE! The same password can be assigned for each touch display!
Password for boiler display
-1
Password for Touch display with address 1
-1
:
:
Password for touch display with address 7
-1
Menu overview and parameters
5
System
Operating Instructions RBG 3200 Touch | B0780115_en
33
5.9.1 Diagnostics - Error display
System menu
Diagnostics
Error display
Display of the current fault messages. In addition, you can also invoke time information here, such as when the
fault occurred, when the fault was acknowledged and when the fault was cleared.
5.10 Display settings
5.10.1 Display settings - General
System menu
Display settings
General
Room temperature
26.0°C
Shows the current room temperature.
Brightness
51
Display of the light sensor’s evaluation of the current brightness in the room for adjusting the backlight.
Maximum backlight
80%
The brighter it is in the room, the more the background of the touch display is illuminated. This is where you
can limit the maximum backlight.
Minimum backlight
20%
The darker it is in the room, the less the background of the touch display is illuminated. This is where you can
set the minimum backlight.
Delay for screensaver (0 disables the screensaver)
60s
If the screen of the touch display is not touched within the set time, the screensaver will activate and the dis‐
play will go dark. To disable the screensaver, set the delay time to “0”.
5
Menu overview and parameters
Diagnostics
34
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
▪On: IP address of touch control is automatically obtained from the network
▪Off: IP address, subnet mask, standard gateway and DNS server can be manually set.
IP address
127.0.0.0
Subnet mask
255.255.0.0
Default gateway:
0.0.0.0
DNS server
0.0.0.0
5.10.2 Display settings - Date / Time
System menu
Display settings
Date / Time
Date
08.01.2015
Display and setting of current date.
Time
14:40:15
Display and setting the current time.
Menu overview and parameters
5
Display settings
Operating Instructions RBG 3200 Touch | B0780115_en
35
The term "fault" is a collective term for warnings, errors and alarms. The boiler reacts
differently to the three types of message:
WARNING
In case of warnings the status LED flashes orange and the boiler initially
continues controlled operation.
ERROR
When there is an error, the status LED flashes red, the boiler follows the
shutdown procedure and remains in “Fault / Off“ status until the problem
is resolved.
ALARM
An alarm triggers a system emergency stop. The status LED flashes red,
the boiler switches off immediately and the heating circuit controller and
pumps remain active.
A window with the corresponding fault text will also appear. Pressing the Cancel icon
takes you back to the basic display. If the quick select icon and the warning triangle
flash alternately, there is still a fault. The “Error display” button will now appear in the
quick menu.
6.1 Procedure for fault messages
If you open the window with the respective fault text, the right arrow will take you to
possible causes of the fault.
6
Troubleshooting
Procedure for fault messages
36
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
Tapping “Solution” will also display action to be taken to resolve the problem. If there
are several options available, these will be listed one below the other.
Once the fault has been resolved, tap the Cancel icon to return to the basic display.
Troubleshooting
6
Procedure for fault messages
Operating Instructions RBG 3200 Touch | B0780115_en
37
7.1 Updating the software of the touch control
❒Insert the USB stick with the necessary data (linux.bin; rootfs.img; update) into the
USB port
❒“Display settings” menu → “Software update / Service”
❒Set “Restart control / Update” parameter to “Yes”
➥Update will begin
Display during the update:
7
FAQ
Updating the software of the touch control
38
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
Once the update is complete, a message will appear that you can remove the stick
❒Remove the USB stick
❒Close the USB cover cap on the barrel
➥The cap must click into place
❒Tap the touch screen
After restarting the display will start calibrating.
Once the calibration is complete, it will restart again to finish. The touch control
software is now up to date.
NOTICE
Inaccurate calibration
If you do not tap the indicated points accurately, the control may stop working
properly and a software update may be required.
FAQ
7
Updating the software of the touch control
Operating Instructions RBG 3200 Touch | B0780115_en
39
7.2 Calibrating the touchscreen
If the touchscreen stops working properly, it will need to be calibrated.
❒Go to the “Display settings” menu
❒Scroll down with the down arrow until the “Software update / Service" submenu
appears and open the submenu
❒In the “Software update / Service" menu open the “Recalibrate touch
control” parameter
7
FAQ
Calibrating the touchscreen
40
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
❒Set the parameter to “YES” and confirm at the bottom right
➥The touchscreen will restart and begin calibrating
To calibrate the touchscreen, you much press five points indicated by a crosshair in
the order shown. The control will restart after calibration.
NOTICE
Inaccurate calibration
If you do not tap the indicated points accurately, the control may stop working
properly and a software update may be required.
FAQ
7
Calibrating the touchscreen
Operating Instructions RBG 3200 Touch | B0780115_en
41