Quick Start Guide

00825-0100-4851, Rev AH February 2019 Rosemount ™ 3051S High Static Differential Pressure Transmitter

This guide provides basic guidelines for the Rosemount™ 3051S High Static Differential Pressure

Transmitter (3051SHP). It does not provide instructions for diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 3051SHP Reference Manual for more information. This document is also available electronically on Emerson.com/Rosemount. Shipping considerations for wireless products. The unit was shipped to you without the power module installed. Remove the power module prior to shipping. Each power module contains two “C” size primary lithium batteries. Primary lithium batteries are regulated in transportation by the U. S. Department of Transportation, and are also covered by IATA (International Air Transport Association), ICAO (International Civil Aviation Organization), and ARD (European Ground Transportation of Dangerous Goods). It is the responsibility of the shipper to ensure compliance with these or any other local requirements. Consult current regulations and requirements before shipping. WARNING Explosions could result in death or serious injury. Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the approvals section of this manual for any restrictions associated with a safe installation. • Before connecting a handheld communicator in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices. • In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is applied to the unit. Process leaks could result in death or serious injury. • To avoid process leaks, ensure secure connection with coned-and-threaded connection. • Install and tighten process connectors before applying pressure. Power module considerations. • The power module may be replaced in a hazardous area. The power module has surface resistivity greater than one gigaohm and must be properly installed in the wireless device enclosure. Care must be taken during transportation to and from the point of installation to prevent electrostatic charge build-up. • This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: — This device may not cause harmful interference. — This device must accept any interference received, including interference that may cause undesired operation. — This device must be installed to ensure a minimum antenna separation distance of 20 cm from all persons. • Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock. Quick Start Guide February 2019 2 Rosemount 3051SHP

System readiness........................................... 5

Mount the transmitter................................... 7 Rotate housing............................................ 14 Set switches and jumpers.............................16 Power up transmitter...................................18 Verify configuration..................................... 31 Trim the transmitter.................................... 35 Safety Instrumented Systems (4-20 mA only).. 37 Product certifications...................................38 February 2019 Quick Start Guide Quick Start Guide 3

Confirm HART® revision capability

If using HART based control or asset management systems, confirm the HART capability of those systems prior to transmitter installation. Not all systems are capable of communicating with HART Revision 7 protocol. This transmitter can be configured for either HART Revision 5 or 7. For instructions on how to change the HART revision of the transmitter, see the Rosemount 3051S Reference Manual. 1.2 Confirm correct device driver Procedure 1. Verify the latest device driver (DD/DTM™) is loaded on your systems to ensure proper communications. 2. Download the latest device driver at Emerson.com or FieldCommGroup.org. 1.3 Rosemount™ 3051S device revisions and drivers Table 1-1 provides the information necessary to ensure you have the correct device driver and documentation for your device. Table 1-1: Rosemount 3051S Device Revisions and Files Identify device Find device driver Review instructio ns Review functiona lity Software Release Date NAMUR Software Revision(1) HART Software Revision(2) HART Universal Revision Device Revision(3) Manual Documen t Number Changes to Software(4 ) Apr-16 1.0.0 20 7 4 00809-01 00-4801 See (4) for list of changes. 5 3 Oct-10 N/A 12 5 3 00809-01 00-4801 Added Power Advisory, mA Output, Power Consumpt ion, Coefficien t of Variation February 2019 Quick Start Guide Quick Start Guide 5

Table 1-1: Rosemount 3051S Device Revisions and Files (continued)

Identify device Find device driver Review instructio ns Review functiona lity May-07 N/A 7 5 2 00809-01 00-4801 Update Statistical Process Monitorin g Capability Sep-06 N/A 4, 5, 6 5 1 00809-01 00-4801 N/A (1) NAMUR software revision is located on the hardware tag of the device. In accordance with NE53, revisions of the least significant level X (of 1.0.X) do not change functionality or operation of the device and will not be reflected in the review functionality column. (2) HART software revision can be read using a HART capable configuration tool. (3) Device driver file names use Device and DD Revision, e.g. 10_01. HART Protocol is designed to enable legacy device driver revisions to continue to communicate with new HART devices. To access new functionality, the new device driver must be downloaded. It is recommended to download new device driver files to ensure full functionality. (4) HART Revision 5 and 7 selectable. Quick Start Guide February 2019 6 Rosemount 3051SHP

Mount the transmitter

2.1 Mount the transmitter in liquid applications Procedure 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so the drain/vent valves are oriented upward. Figure 2-1: Mounting the Transmitter in Liquid Applications Coplanar In-line Flow 2.2 Mount the transmitter in gas applications Procedure 1. Place taps in the top or side of the line. 2. Mount beside or above the taps. Figure 2-2: Mounting the Transmitter in Gas Applications Coplanar Inline February 2019 Quick Start Guide Quick Start Guide 7

Using a mounting bracket

If the transmitter requires the use of a mounting bracket, use the images below for instructions on how to properly mount the transmitter using the Emerson™ provided mounting brackets. Use only bolts provided with the transmitter or sold as Emerson spare parts. Bolts should be tightened to a torque of 125 in-lb. Panel mount Pipe mount Quick Start Guide February 2019 8 Rosemount 3051SHP

Environmental seal for housing

Thread sealing (PFTE) tape or paste on male threads of conduit is required to provide a water/dust tight conduit seals and meets requirements of NEMA® Type 4X, IP66, and IP68. Consult factory if other Ingress Protection ratings are required. For M20 threads, install conduit plugs to full thread engagement or until mechanical resistance is met. 2.5 Installing high pressure coned and threaded connection The transmitter comes with an autoclave connection designed for high pressure applications. Follow the steps below to properly connect the transmitter to your process: February 2019 Quick Start Guide Quick Start Guide 9

1. Apply a process-compatible lubricant to the gland nut threads.

2. Slip the gland nut onto the tube, then thread the collar onto the tube end (the collar is reverse threaded). 3. Apply a small amount of process-compatible lubricant applied to the tube cone to help prevent galling and facilitate sealing. Insert the tubing into the connection and tighten finger tight. 4. Tighten the gland nut to a torque of 25 ft-lb. Need help? A weep hole has been designed into the transmitter for safety and leak detection. If fluid begins to leak from the weep hole, isolate the process pressure, disconnect the transmitter, and reseal until the leak is resolved. All Rosemount™ 3051SHP Transmitters come with a 316L SST tag attached to the module. 2.6 Wireless considerations (if applicable) Power up sequence The power module should not be installed on any wireless device until the Emerson™ Wireless Gateway (Gateway) has been installed and functioning properly. See Connect the power module for WirelessHART® transmitter for more details. Antenna position Position the antenna vertically, either straight up or straight down (see Figure 2-3). The antenna should be approximately 3 ft. (1 m) from any large structure or building to allow clear communication to other devices. Figure 2-3: Antenna Position Quick Start Guide February 2019 10 Rosemount 3051SHP

Mount the high gain, remote antenna (WN wireless option

only) The high gain, remote antenna option provides flexibility for mounting the transmitter based on wireless connectivity, lightning protection, and current work practices (see Figure 2-4). WARNING When installing the remote mount antenna for the transmitter, always use established safety procedures to avoid falling or contact with high-power electrical lines. Install remote antenna components for the transmitter in compliance with local and national electrical codes and use best practices for lightning protection. Before installing, consult with the local area electrical inspector, electrical officer, and work area supervisor. The remote antenna option is specifically engineered to provide installation flexibility while optimizing wireless performance and local spectrum approvals. To maintain wireless performance and avoid non-compliance with spectrum regulations, do not change the length of cable or the antenna type. If the supplied remote mount antenna kit is not installed per these instructions, Emerson™ is not responsible for wireless performance or non- compliance with spectrum regulations. The high gain, remote mount antenna kit includes coaxial sealant for the cable connections for the lightning arrestor and antenna. Procedure 1. Find a location where the remote antenna has optimal wireless performance. Ideally this will be 15–25 ft. (4,6–7,6 m) above the ground or 6 ft. (2 m) above obstructions or major infrastructure. 2. Mount the antenna on a 1.5- to 2-in. pipe mast using the supplied mounting equipment. 3. Connect the lightning arrestor directly to the top of the transmitter. 4. Install the grounding lug, lock washer, and nut on top of lightning arrestor. 5. Connect the antenna to the lightning arrestor using the supplied LMR-400 coaxial cable ensuring the drip loop is not closer than 1 ft. (0,3 m) from the lightning arrestor. 6. Use the coaxial sealant to seal each connection between the wireless field device, lightning arrestor, cable, and antenna. February 2019 Quick Start Guide Quick Start Guide 11

7. Ensure the mounting mast and lightning arrestor are grounded

according to local/national electrical code. Example Figure 2-4: Rosemount 3051S with High Gain, Remote Antenna A B D C A. Lightning arrestor B. Antenna C. Mounting mast D. Drip loop Weather proofing is required! The remote mount antenna kit includes coaxial sealant for weather proofing the cable connections for the lightning arrestor, antenna, and the transmitter. Coaxial sealant must be applied to guarantee performance of the wireless field network. See Figure 2-5 for details on how to apply coaxial sealant. Quick Start Guide February 2019 12 Rosemount 3051SHP

Figure 2-5: Applying Coaxial Sealant to Cable Connections

Postrequisites Any spare lengths of coaxial cable should be placed in 1 ft. (0,3 m) coils. February 2019 Quick Start Guide Quick Start Guide 13

To improve field access to wiring or to better view the optional LCD display:

Procedure 1. Loosen the housing rotation set screw. 2. Rotate the housing clockwise to the desired location. If the desired location cannot be achieved due to thread limit, rotate the housing counter clockwise to the desired location (up to 360° from thread limit). CAUTION Do not rotate the housing more than 180° without first performing a disassembly procedure. Over-rotation may sever the electrical connection between the sensor module and the feature board electronics. 3. Retighten the housing rotation set screw up to 30 in-lb. 4. For wireless, consider access to the power module when selecting housing rotation. Figure 3-1: Transmitter Housing Set Screw (Plantweb) A A. Housing rotation set screw (3/32-in.) Quick Start Guide February 2019 14 Rosemount 3051SHP

Figure 3-2: Transmitter Housing Set Screw (Junction Box)

A A. Housing rotation set screw (3/32-in.) February 2019 Quick Start Guide Quick Start Guide 15

Set switches and jumpers

If alarm and security adjustment option is not installed, the transmitter will operate normally with the default alarm condition alarm “high” and the security “off”. Procedure 1. Do not remove the transmitter covers in explosive atmospheres when the circuit is live. If the transmitters is live, set the loop to manual and remove power. 2. Remove the electronics compartment cover. On the Plantweb housing the cover is opposite the field terminals side, or on the junction box housing remove the terminal block cover. Do not remove the housing cover in explosive environments. 3. On the Plantweb housing, slide the security and alarm switches into the preferred position by using a small screwdriver (An LCD display or an adjustment module must be in place to activate the switches). On the junction box housing pull the pins out and rotate 90° into desired position to set the security and alarm. 4. Reinstall the housing cover so metal contacts metal to meet explosion- proof requirements. Figure 4-1: Transmitter Switch and Jumper Configuration (Plantweb) A B C A. Meter/adjustment module B. Security C. Alarm Quick Start Guide February 2019 16 Rosemount 3051SHP

Figure 4-2: Transmitter Switch and Jumper Configuration (Junction

Box) B C A. Meter/adjustment module B. Security C. Alarm February 2019 Quick Start Guide Quick Start Guide 17

Power up transmitter

This section provides the steps needed to power up transmitters. These steps are unique based on the specific protocol used. Reference the appropriate section listed below for the specific steps. • Connect wiring and power up for wired HART configuration • Connect wiring and power up FOUNDATION™ Fieldbus transmitter • Connect the power module for WirelessHART® transmitter 5.1 Connect wiring and power up for wired HART configuration Use the following steps to wire the transmitter: Procedure 1. Remove and discard orange conduit plugs. 2. Remove the housing cover labeled “Field Terminals.” 3. CAUTION Do not connect the power across the test terminals. Power could damage the test diode in the test connection. Twisted pairs yield best results. Use 24 AWG to 14 AWG wire and do not exceed 5,000 feet (1500 meters). For single compartment housing (Junction Box housing), shielded signal wiring should be used in high EMI/RFI environments. Connect the positive lead to the “+” terminal, and the negative lead to the “–” terminal. 4. Ensure full contact with terminal block screw and washer. When using a direct wiring method, wrap wire clockwise to ensure it is in place when tightening the terminal block screw. The use of a pin or ferrule wire terminal is not recommended as the connection may be more susceptible to loosening over time or under vibration. 5. If the optional process temperature input is not installed, plug and seal the unused conduit connection. If the optional process temperature input is being utilized, see Install optional process temperature input (Pt 100 RTD sensor) for more information. When the enclosed threaded plug is utilized in the conduit opening, it must be installed with a minimum thread engagement in order to comply with explosion-proof requirements. For straight threads, a Quick Start Guide February 2019 18 Rosemount 3051SHP

minimum of seven threads must be engaged. For tapered threads, a

minimum of five threads must be engaged. 6. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing. 7. Reinstall the housing cover and tighten so the cover is fully seated with metal to metal contact between the housing and cover in order to meet explosion proof requirements. Example Transmitter wiring shows the wiring connections necessary to power a wired HART transmitter and enable communications with a handheld communicator. 5.2 Transmitter wiring Figure 5-1: Plantweb™ Housing A B A. RL ≥ 250 Ω B. Power supply Figure 5-2: Junction Box A B A. RL ≥ 250 Ω B. Power supply February 2019 Quick Start Guide Quick Start Guide 19

Figure 5-3: With Optional Process Temperature Connection

B A A. RL ≥ 250 Ω B. Power supply Note Installation of the transient protection terminal block does not provide transient protection unless the transmitter case is properly grounded. 5.3 Signal wiring grounding Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment. Grounding terminations are provided on the sensor module and inside the terminal compartment. These grounds are used when transient protection terminal blocks are installed or to fulfill local regulations. Procedure 1. Remove the field terminals housing cover. 2. Connect the wiring pair and ground as indicated in Figure 5-4. The cable shield should: • Be trimmed close and insulated from touching the transmitter housing • Continuously connect to the termination point • Be connected to a good earth ground at the power supply end Quick Start Guide February 2019 20 Rosemount 3051SHP

Figure 5-4: Wiring

DP C A B B D E B A. Insulate shield B. Minimize distance C. Connect shield back to the power supply ground D. Trim shield and insulate E. Safety ground 3. Replace the housing cover. It is recommended the cover be tightened until there is no gap between the cover and the housing. 4. Plug and seal unused conduit connections with the provided conduit plug. When the enclosed threaded plug is utilized in the conduit opening, it must be installed with a minimum thread engagement in order to comply with explosion-proof requirements. For straight threads, a minimum of seven threads must be engaged. For tapered threads, a minimum of five threads must be engaged. 5.4 Remote display wiring and power up (if applicable) The remote mount display and Interface system consists of a local transmitter and a remote mount LCD display assembly. The local Rosemount 3051S assembly includes a Junction Box housing with a three-position terminal block integrally mounted to a sensor module. The remote mount LCD display assembly consists of a dual compartment Plantweb housing with a seven position terminal block. See Figure 5-5 for complete wiring instructions. The following is a list of necessary information specific to the remote mount display system: • Each terminal block is unique for the remote display system. • A 316 SST housing adaptor is permanently secured to the remote mount LCD display Plantweb housing, providing an external ground and a means for field mounting with the provided mounting bracket. February 2019 Quick Start Guide Quick Start Guide 21

A cable is required for wiring between the transmitter and remote mount

LCD display. The cable length is limited to 100 ft. • 50 ft. (option M8) or 100 ft. (option M9) cable is provided for wiring between the transmitter and remote mount LCD display. Option M7 does not include cable; see recommended specifications below. Cable type Recommend Madison AWM Style 2549 cable. Other comparable cable may be used as long as it has independent dual twisted shielded pair wires with an outer shield. The power wires must be 22 AWG minimum and the CAN communication wires must be 24 AWG minimum. Cable length The cable length is up to 100 ft .depending upon cable capacitance. Cable capacitance The capacitance from the CAN communications line to the CAN return line as wired must be less than 5,000 picofarads total. This allows up to 50 picofarads per foot for a 100 foot cable. Intrinsic safety consideration The transmitter assembly with remote display has been approved with Madison AWM Style 2549 cable. Alternate cable may be used as long as the transmitter with remote display and cable is configured according to the installation control drawing or certificate. Refer to appropriate approval certificate or control drawing in Appendix B of the Rosemount 3051S Reference Manual for remote cable IS requirements. CAUTION Do not apply power to the remote communications terminal. Follow wiring instructions carefully to prevent damage to system components. Quick Start Guide February 2019 22 Rosemount 3051SHP

Figure 5-5: Remote Mount Display Wiring Diagram

A B C (white) 24 AWG (blue) 24 AWG (black) 22 AWG (red) 22 AWG A. Remote mount display B. Junction box housing C. 4–20 mA Note Wire colors provided are per Madison AWM Style 2549 cable. Wire color may vary depending on cable selected. Madison AWM Style 2549 cable includes a ground shield. This shield must be connected to earth ground at either the sensor module or the remote display, but not both. 5.5 Quick connect wiring (if applicable) As standard, the Rosemount 3051S Quick Connect arrives properly assembled to the sensor module and is ready for installation. Cordsets and field wireable connectors (in shaded area) are sold separately. February 2019 Quick Start Guide Quick Start Guide 23

Figure 5-6: Rosemount 3051S Quick Connect Exploded View

A B D E F C A. Straight field wireable connector (part number 03151-9063-0001), supplied by customer B. Right angle field wireable connector (part number 03151-9063-0002), supplied by customer C. Quick Connect housing D. Cordset, supplied by vendor E. Coupling nut F. Quick Connect coupling nut Important If Quick Connect is ordered as a Rosemount 300S spare housing or is removed from the sensor module, follow the instructions below for proper assembly prior to field wiring. Procedure 1. Place the Quick Connect onto the sensor module. To ensure proper pin alignment, remove coupling nut prior to installing quick connect onto the sensor module. 2. Place coupling nut over quick connect and wrench tighten to a maximum of 300 in-lb (34 N-m). 3. Tighten the set screw up to 30 in-lb using a 3/32-in. hex wrench. 4. Install cordset/field wireable connectors onto the Quick Connect. Do not over tighten. Quick Start Guide February 2019 24 Rosemount 3051SHP

Figure 5-7: Quick Connect Housing Pin-Out

A B “+” “-” A. Ground B. No connection Note For other wiring details, refer to pin-out drawing and the cordset manufacturer’s installation instructions. 5.6 Power supply The DC power supply should provide power with less than two percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator, and related pieces. Note the resistance of intrinsic safety barriers, if used, must be included. he Field Communicator requires a minimum loop resistance of 250Ω for communication. Figure 5-8: Load Limitation (Standard Transmitter) Load (Ohms) 1387 1000 500 0 10.5 20 30 42.4 Operating Region Voltage (Vdc) Maximum Loop Resistance = 43.5 x (Power Supply Voltage – 10.5) February 2019 Quick Start Guide Quick Start Guide 25

Figure 5-9: Load Limitation (HART Diagnostic Transmitter [Option Code

DA2] Differential Pressure and Temperature Transmitter) 1322 1000 500 0 12.0 20 30 42.4 Voltage (Vdc) Load (Ohms) Operating region Maximum Loop Resistance = 43.5 x (Power Supply Voltage – 12.0) 5.7 Install optional process temperature input (Pt 100 RTD sensor) Use only ATEX/IECEx Flameproof cables (Temperature Input Code C30, C32, C33, or C34) to meet ATEX/IECEx Flameproof certification. Procedure 1. Mount the Pt 100 RTD sensor in the appropriate location. 2. Note Use shielded four-wire cable for the process temperature connection. Connect the RTD cable to the transmitter by inserting the cable wires through the unused housing conduit and connect to the four screws on the transmitter terminal block. An appropriate cable gland should be used to seal the conduit opening around the cable. 3. Connect the RTD cable shield wire to the ground lug in the housing. Quick Start Guide February 2019 26 Rosemount 3051SHP

Figure 5-10: Transmitter RTD Wiring Connection

C A B Red Red White White A. Pt 100 RTD sensor B. RTD cable assembly wires C. Ground lug 5.8 Connect wiring and power up FOUNDATION™ Fieldbus transmitter Cable connection The segment cable can enter the transmitter through either conduit connection on the housing. Cable entering the housing vertically should be avoided. Drip loops are recommended for installations where moisture can accumulate and enter the terminal compartment. Power supply The transmitter requires between 9 and 32 Vdc (9 and 15 Vdc for FISCO) at the terminals to operate and provide complete functionality. Power conditioner A fieldbus segment requires a power conditioner to isolate the power supply filter and decouple the segment from other segments attached to the same power supply. February 2019 Quick Start Guide Quick Start Guide 27

Every fieldbus segment requires terminators at each end of the segment.

Failure to properly terminate segments may cause communication errors with devices on the segment. Transient protection Transient protection devices require the transmitter be grounded for proper operation. Refer to Figure 5-11 for further information. 5.8.1 Grounding Grounding terminations are provided on the sensor module and inside the terminal compartment. These grounds are used when transient protect terminal blocks are installed or to fulfill local regulations. Procedure 1. Remove the FIELD TERMINALS housing cover. 2. Note The terminals are not polarity sensitive. The cable shield should: • Be trimmed close and insulated from touching the transmitter housing • Continuously connect to the termination point • Be connected to a good earth ground at the power supply end Connect the wiring pair and ground as indicated in Figure 5-11. Quick Start Guide February 2019 28 Rosemount 3051SHP

Figure 5-11: Wiring

FIELDBUS WIRING DP C A D E B B B A. Insulate shield B. Minimize distance C. Connect shield back to the power supply ground D. Trim shield and insulate E. Safety ground 3. Replace the housing cover. It is recommended the cover be tightened until there is no gap between the cover and the housing. 4. NOTICE When the enclosed threaded plug is utilized in the conduit opening, it must be installed with a minimum thread engagement in order to comply with explosion-proof requirements. For straight threads, a minimum of seven threads must be engaged. For tapered threads, a minimum of five threads must be engaged. Plug and seal the unused conduit connection with the provided conduit plug. 5.9 Connect the power module for WirelessHART® transmitter The power module should not be installed on any wireless device until the Gateway is installed and functioning properly. This transmitter uses the black power module (order model number 701PBKKF). Wireless devices should also be powered up in order of proximity from the Gateway, beginning with the closest. This will result in a simpler and faster network installation. Enable active advertising on the Gateway to ensure new devices join the network faster. For more information, see the Emerson 1420 Wireless Gateway Reference Manual. February 2019 Quick Start Guide Quick Start Guide 29

1. Remove the housing cover on the field terminal side.

2. Connect the black power module. Figure 5-12: Power module for WirelessHART transmitter connections Quick Start Guide February 2019 30 Rosemount 3051SHP

Use any compliant master to communicate with and verify configuration of

the transmitter. Make sure to download the latest device driver from the Device Install Kit site. Refer to Table 6-1 for the latest device revision for each potential configuration. Configuration can be verified using two methods: 1. Using the Field Communicator 2. Via AMS Device Manager Fast Keys for using a Field Communicator are provided in Table 6-2. To verify wireless operation, refer to Verify WirelessHART operation using the Local display (LCD); verification can also be done at the device via the LCD display. Table 6-1: Device Revisions Device configuration Device revision Rosemount™ 3051S HART (wired) Rev. 7 Rosemount 3051S FOUNDATION™ Fieldbus Rev. 23 Rosemount 3051S WirelessHART Rev. 3 Rosemount 3051S MultiVariable™ Rev. 1 Rosemount 3051S HART® Diagnostics (DA2) Rev. 3 6.1 Verify with Field Communicator Connecting to a Field Communicator For the Field Communicator to interface with the transmitter, power must be supplied to the transmitter. For wireless configuration, the communicator connections are located behind the power module on the terminal block (see Figure 6-1). For wired configurations, the connections are on the terminal block (see Figure 6-2, Figure 6-3, or Figure 6-4). February 2019 Quick Start Guide Quick Start Guide 31

Field Communicator connections

Figure 6-1: WirelessHART® terminal block COMM P/N 00753-9200-0010 Figure 6-2: HART® and DA2 terminal block Figure 6-3: Multivariable terminal block Quick Start Guide February 2019 32 Rosemount 3051SHP

Figure 6-4: FOUNDATION™ Fieldbus terminal block

FIELDBUS WIRING 6.2 Fast Key sequence for critical parameters Basic configuration parameters can be verified using a Field Communicator. At a minimum, the parameters below should be verified as part of the configuration and startup procedure. Note If no Fast Key sequence is provided, that parameter is not required to be verified for that configuration. Table 6-2: Fast Key Sequences Function HART® protocol FOUNDATION™ Fieldbus protocol Wireless HART® protocol Differential pressure and temperature measuremen t Advanced diagnostics Damping 2, 2, 1, 5 2, 1, 2 2, 2, 2, 4 1, 3, 7 2, 2, 1, 1, 3 DP Zero Trim 3, 4, 1, 3 2, 1, 1 2, 1, 2 1, 2, 4, 3, 1 3, 4, 1, 1, 1, 3 DP Units 2, 2, 1, 2 3, 2, 1 2, 2, 2, 3 1, 3, 3, 1 2, 1, 1, 1, 2, 1 Range Analog Output 2, 2, 1, 4 N/A N/A 1, 2, 4, 1 3, 4, 1, 2, 3 Tag 2, 2, 5, 1 4, 1, 3 2, 2, 9, 1 1, 3, 1 2, 1, 1, 1, 1, 1 Transfer 2, 2, 1, 4 N/A 2, 2, 4, 2 1, 3, 6 2, 2, 1, 1, 4 For instructions on how to configure an AI block in your FOUNDATION Fieldbus transmitter, refer to the Rosemount™ 3051S FOUNDATION Fieldbus Reference Manual. Verify WirelessHART operation using the Local display (LCD) The LCD display will show the output values based on the wireless update rate. Refer to the Rosemount 3051S Wireless Reference Manual for error codes and other LCD display messages. Press and hold the Diagnostic button February 2019 Quick Start Guide Quick Start Guide 33

for at least five seconds to display the TAG, Device ID, Network ID, Network

Join Status, and Device Status screens. Searching for network Joining network Connected with limited bandwidth Connected N E T w K S R C H N G n e t w k N E G O T n e t w k L I M - O P n e t w k O K Note It may take several minutes for the device to join the network. For advanced troubleshooting of the wireless network or Gateway, see the Rosemount 3051S WirelessHART Reference Manual, Emerson™ 1410 Wireless Gateway Reference Manual, Emerson 1420 Wireless Gateway Reference Manual or Quick Start Guide. Quick Start Guide February 2019 34 Rosemount 3051SHP

Trim the transmitter

Transmitters are shipped fully calibrated per request or by the factory default of full scale (lower range value = zero, upper range value = upper range limit). 7.1 Zero trim A zero trim is a single-point adjustment used for compensating mounting position and line pressure effects. When performing a zero trim, ensure the equalizing valve is open and all wet legs are filled to the correct level. • If zero offset is less than 3% of true zero, follow the Using the Field Communicator instructions to perform a zero trim. • If zero offset is greater than 3% of true zero, follow the Using the transmitter zero adjustment button instructions below to rerange. • If hardware adjustments are not available, see the Rosemount™ 3051S Reference Manual to perform a rerange using the Field Communicator. 7.1.1 Using the Field Communicator Procedure 1. Equalize or vent the transmitter and connect Field Communicator. 2. At the menu, input the Fast Key sequence (see Table 6-2). 3. Follow the commands to perform a zero trim. 7.1.2 Using the transmitter zero adjustment button Procedure Push and hold the Zero adjustment button for at least two seconds but no longer than ten seconds. Figure 7-1: Transmitter Adjustment Buttons (Plantweb™) A B A. Zero B. Span February 2019 Quick Start Guide Quick Start Guide 35

Figure 7-2: Transmitter Adjustment Buttons (Junction Box)

A B A. Zero B. Span Quick Start Guide February 2019 36 Rosemount 3051SHP

Safety Instrumented Systems (4-20 mA only)

For safety certified installations, refer to the appropriate manual for installation procedure and system requirements. February 2019 Quick Start Guide Quick Start Guide 37

Ordinary Location Certification

As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA). European Directive Information A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount. Installing Equipment in North America The US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes. 9.1 USA E5 US Explosionproof, Dust Ignition-proof Certificate 1143113 Standards FM Class 3600 - 2011, FM Class 3615 - 2006, FM Class 3810 - 2005, UL 1203 5th Ed., UL 50E 1st Ed., UL 61010-1 (3rd Edition) Markings XP CL I, DIV 1, GP B, C, D; T5; DIP CL II, DIV 1, GP E, F, G; CL III; – 50 °C ≤ Ta ≤ +85 °C; Seal Not Required; Type 4X I5 US Intrinsically Safe; Nonincendive Certificate 1143113 Standards FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 - 2004, FM Class 3810 - 2005, UL 50E 1st Ed., UL 61010-1 (3rd Edition) Markings IS CL I,II,III, DIV 1, GP A, B, C, D, E, F, G, T4; Class 1, Zone 0 AEx ia IIC T4 (-50 °C ≤ Ta ≤ +70 °C) [HART]; T4(-50 °C ≤ Ta ≤ +60 °C) [Fieldbus]; NI CL 1, DIV 2, GP A, B, C, D, T5, Ta = 70 °C; Rosemount drawing 03251-1006; Type 4X Quick Start Guide February 2019 38 Rosemount 3051SHP

IE US FISCO Intrinsically Safe

Certificate 1143113 Standards FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3810 - 2005, UL 50E 1st Ed., UL 61010-1 (3rd Edition) Markings IS CL I, DIV 1, GP A, B, C, D, T4(-50 °C ≤ Ta ≤ +60 °C); Class 1, Zone 0 AEx ia IIC T4; Rosemount drawing 03251-1006; Type 4X 9.2 Canada E6 Canada Explosion-proof, Dust Ignition-proof, Division 2 Certificate 1143113 Standards CAN/CSA C22.2 No. 0-10, CSA C22.2 No. 25-1966 (R2014), CSA C22.2 No. 30-M1986 (R2012), CSA C22.2 No. 94.2-07, CSA C22.2 No. 213-M1987 (R2013), CAN/CSA-C22.2 No. 61010-1-12, ANSI/ISA 12.27.01-2011 Markings Class I, Groups B, C, D, –50 °C ≤ Ta ≤ +85 °C; Class II, Groups E, F, G; Class III; suitable for Class I, Zone 1, Group IIB+H2, T5; Class I, Division 2, Groups A, B, C, D; suitable for Class I, Zone 2, Group IIC, T5; Seal Not Required; Dual Seal; Type 4X I6 Canada Intrinsically Safe Certificate 1143113 Standards CAN/CSA C22.2 No. 0-10, CAN/CSA-60079-0-11, CAN/CSA C22.2 No. 60079-11:14, CSA C22.2 No. 94.2-07, ANSI/ISA 12.27.01-2011 Markings Intrinsically Safe Class I, Division 1; Groups A, B, C, D; suitable for Class 1, Zone 0, IIC, T3C, Ta = 70 °C; Rosemount drawing 03251-1006; Dual Seal; Type 4X IF Canada FISCO Intrinsically Safe Certificate 1143113 Standards CAN/CSA C22.2 No. 0-10, CAN/CSA-60079-0-11, CAN/CSA C22.2 No. 60079-11:14, CSA C22.2 No. 94.2-07, ANSI/ISA 12.27.01-2011 Markings Intrinsically Safe Class I, Division 1; Groups A, B, C, D; suitable for Class 1, Zone 0, IIC, T3C, Ta = 70 °C; Rosemount drawing 03251-1006; Dual Seal; Type 4X February 2019 Quick Start Guide Quick Start Guide 39

E1 ATEX Flameproof

Certificate DEKRA 15ATEX0108X Standards EN 60079-0:2012 + A11:2013, EN60079-1:2014, EN60079-26:2015 Markings II 1/2 G Ex db IIC T6…T4 Ga/Gb, T6 (–60 °C ≤ Ta ≤ +70 °C), T4/T5 (–60 °C ≤ Ta ≤ +80 °C); Vmax = 42.4 VDC Temperature class Process temperature Ambient temperature T6 –60 °C to +70 °C –60 °C to +70 °C T5 –60 °C to +80 °C –60 °C to +80 °C T4 –60 °C to +120 °C –60 °C to +80 °C Special Conditions for Safe Use (X): 1. This device contains a thin wall diaphragm less than 1 mm thickness that forms a boundary between zone 0 (process connection) and zone 1 (all other parts of the equipment). The model code and datasheet are to be consulted for details of the diaphragm material. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime. 2. Flameproof joints are not intended for repair. 3. Non-standard paint options may cause risk from electrostatic discharge. Avoid installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information. 4. Appropriate cable, glands and plugs need to be suitable for a temperature of 5 °C greater than maximum specified temperature for location where installed. I1 ATEX Intrinsic Safety Certificate BAS01ATEX1303X Standards EN 60079-0:2012, EN 60079-11:2012 Markings II 1 G Ex ia IIC T4 Ga, T4(–60 °C ≤ Ta ≤ +70 °C) Quick Start Guide February 2019 40 Rosemount 3051SHP

3051S…F…IA; 3051SF …F…

IA; 3051SHP…D…F…IA 17.5 V 380 mA 5.32 W 0 0 3051S …A…M7, M8, or M9; 3051SF …A…M7, M8, or M9; 3051SAL…C… M7, M8, or M9; 3051SHP…D… M7, M8, or M9; 30 V 300 mA 1.0 W 12 nF 60 μH 3051SAL; 3051SAM 30 V 300 mA 1.0 W 12 nF 33 μH 3051SAL…M7, M8, or M9 3051SAM…M7, M8, or M9 30 V 300 mA 1.0 W 12 nF 93 μH RTD option for 3051SF 5 V 500 mA 0.63 W N/A N/A 3051SHP…7…A 30 V 300 mA 1.0 W 14.8 nF 0 RTD option for 3051SHP… 7…A 30 V 2.31 mA 17.32 mW N/A N/A 3051SHP…7…F 30 V 300 mA 1.3 W 0 0 3051SHP…7…F…IA 17.5 V 380 mA 5.32 W 0 0 RTD option for 3051SHP… 7…F 30 V 18.24 mA 137 mW 0.8 nF 1.33 mH Special Conditions for Safe Use (X): 1. The Rosemount 3051S Transmitters fitted with transient protection are not capable of withstanding the 500 V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation. 2. The terminal pins of the Rosemount 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN 60529. 3. The Rosemount 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area. February 2019 Quick Start Guide Quick Start Guide 41

IA ATEX FISCO

Certificate BAS01ATEX1303X Standards EN 60079-0:2012, EN 60079-11:2012 Markings II 1 G Ex ia IIC T4 Ga, T4(–60 °C ≤ Ta ≤ +70 °C) Parameter FISCO Voltage Ui 17.5 V Current Ii 380 mA Power Pi 5.32 W Capacitance Ci 0 Inductance Li 0 Special Conditions for Safe Use (X): 1. The Rosemount 3051S Transmitters fitted with transient protection are not capable of withstanding the 500 V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation. 2. The terminal pins of the Rosemount 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN 60529. 3. The Rosemount 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area. ND ATEX Dust Certificate BAS01ATEX1374X Standards EN 60079-0:2012, EN 60079-31:2009 Markings II 1 D Ex ta IIIC T105 °C T500 95 °C Da, (–20 °C ≤ Ta ≤ +85 °C), Vmax = 42.4 V Special Conditions for Safe Use (X): 1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66. 2. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66. 3. Cable entries and blanking plugs must be suitable for the ambient temperature range of the apparatus and capable of withstanding a 7 J impact test. Quick Start Guide February 2019 42 Rosemount 3051SHP

4. The SuperModule(s) must be securely screwed in place to maintain the

ingress protection of the enclosure(s). N1 ATEX Type n Certificate BAS01ATEX3304X Standards EN 60079-0:2012, EN 60079-15:2010 Markings II 3 G Ex nA IIC T5 Gc, (–40 °C ≤ Ta ≤ +85 °C), Vmax = 45 V Special Condition for Safe Use (X): 1. The equipment is not capable of withstanding the 500 V insulation test required by clause 6.5 of EN 60079-15:2010. This must be taken into account when installing the equipment. Note RTD Assembly is not included with the Rosemount 3051SFx Type n Approval. 9.4 International E7 IECEx Flameproof and Dust Certificate IECEx DEK 15.0072X, IECEx BAS 09.0014X Standards IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-26:2014, IEC 60079-31:2008 Markings Ex db IIC T6…T4 Ga/Gb, T6 (–60 °C ≤ Ta ≤ +70 °C), T4/T5 (–60 °C ≤ Ta ≤ +80 °C); Vmax = 42.4 VDC Ex ta IIIC T105 °C T500 95 °C Da (–20 °C ≤ Ta ≤ +85 °C) Temperature class Process temperature Ambient temperature T6 –60 °C to +70 °C –60 °C to +70 °C T5 –60 °C to +80 °C –60 °C to +80 °C T4 –60 °C to +120 °C –60 °C to +80 °C Special Conditions for Safe Use (X): 1. This device contains a thin wall diaphragm less than 1 mm thickness that forms a boundary between zone 0 (process connection) and zone 1 (all other parts of the equipment). The model code and datasheet are to be consulted for details of the diaphragm material. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime. 2. Flameproof joints are not intended for repair. February 2019 Quick Start Guide Quick Start Guide 43

3. Non-standard paint options may cause risk from electrostatic

discharge. Avoid installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information. 4. Appropriate cable, glands and plugs need to be suitable for a temperature of 5 °C greater than maximum specified temperature for location where installed. 5. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66. 6. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66. 7. Cable entries and blanking plugs must be suitable for the ambient temperature range of the apparatus and capable of withstanding a 7 J impact test. 8. The Rosemount 3051S SuperModule must be securely screwed in place to maintain the ingress protection of the enclosure. I7 IECEx Intrinsic Safety Certificate IECEx BAS 04.0017X Standards IEC 60079-0:2011, IEC 60079-11:2011 Markings Ex ia IIC T4 Ga, T4(–60 °C ≤ Ta ≤ +70 °C) Model Ui Ii P i C i Li SuperModule 30 V 300 mA 1.0 W 30 nF 0 3051S...A; 3051SF…A; 3051SAL…C; 3051SHP… D…A 30 V 300 mA 1.0 W 12 nF 0 3051S…F; 3051SF…F; 3051SHP…D…F 30 V 300 mA 1.3 W 0 0 3051S…F…IA; 3051SF …F… IA; 3051SHP…D…F…IA 17.5 V 380 mA 5.32 W 0 0 3051S …A…M7, M8, or M9; 3051SF …A…M7, M8, or M9; 3051SAL…C… M7, M8, or M9; 3051SHP…D… M7, M8, or M9 30 V 300 mA 1.0 W 12 nF 60 μH 3051SAL; 3051SAM 30 V 300 mA 1.0 W 12 nF 33 μH Quick Start Guide February 2019 44 Rosemount 3051SHP

3051SAL…M7, M8, or M9

3051SAM…M7, M8, or M9 30 V 300 mA 1.0 W 12 nF 93 μH RTD option for 3051SF 5 V 500 mA 0.63 W N/A N/A 3051SHP…7…A 30 V 300 mA 1.0 W 14.8 nF 0 RTD option for 3051SHP… 7…A 30 V 2.31 mA 17.32 mW N/A N/A 3051SHP…7…F 30 V 300 mA 1.3 W 0 0 3051SHP…7…F…IA 17.5 V 380 mA 5.32 W 0 0 RTD option for 3051SHP… 7…F 30 V 18.24 mA 137 mW 0.8 nF 1.33 mH Special Conditions for Safe Use (X): 1. The Rosemount 3051S Transmitters fitted with transient protection are not capable of withstanding the 500 V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation. 2. The terminal pins of the Rosemount 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN 60529. 3. The Rosemount 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area. IG IECEx FISCO Certificate IECEx BAS 04.0017X Standards IEC 60079-0: 2011, IEC 60079-11: 2011 Markings Ex ia IIC T4 Ga, T4(–60 °C ≤ Ta ≤ +70 °C) Parameter FISCO Voltage Ui 17.5 V Current Ii 380 mA Power Pi 5.32 W Capacitance Ci 0 Inductance Li 0 February 2019 Quick Start Guide Quick Start Guide 45

Special Conditions for Safe Use (X):

1. The Rosemount 3051S Transmitters fitted with transient protection are not capable of withstanding the 500 V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation. 2. The terminal pins of the Rosemount 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN 60529. 3. The Rosemount 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area. N7 IECEx Type n Certificate IECEx BAS 04.0018X Standards IEC 60079-0: 2011, IEC 60079-15: 2010 Markings Ex nA IIC T5 Gc, (–40 °C ≤ Ta ≤ +85 °C) Special Condition for Safe Use (X): 1. The equipment is not capable of withstanding the 500 V insulation test required by clause 6.5 of EN 60079-15:2010. This must be taken into account when installing the equipment. 9.5 EAC - Belarus, Kazakhstan, Russia EM Technical Regulation Customs Union (EAC) Flameproof and Dust Certificate RU C-US.AA87.B.00378 Markings Ga/Gb Ex d IIC T6…T4 X Ex tb IIIC T105 °C T500 95 °C Db X Ex ta IIIC T105 °C T500 95 °C Da X See certificate for special conditions for safe use. IM Technical Regulation Customs Union (EAC) Intrinsic Safety Certificate RU C-US.AA87.B.00378 Markings 0Ex ia IIC T4 Ga X See certificate for special conditions for safe use. 9.6 Combinations K1 Combination of E1, I1, N1, and ND Quick Start Guide February 2019 46 Rosemount 3051SHP

K7 Combination of E7, I7, and N7

KC Combination of E1, E5, I1, and I5 KD Combination of E1, E5, E6, I1, I5, and I6 KG Combination of IA, IE, IF, and IG KM Combination of EM and IM February 2019 Quick Start Guide Quick Start Guide 47

Rosemount 3051SHP Declaration of Conformity

EU Declaration of Conformity No: RMD 1104 Rev. F Page 1 of 4 We, Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA declare under our sole responsibility that the product, Rosemount™ 3051SHP Pressure Transmitter manufactured by, Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA to which this declaration relates, is in conformity with the provisions of the European Union Directives, including the latest amendments, as shown in the attached schedule. Assumption of conformity is based on the application of the harmonized standards and, when applicable or required, a European Union notified body certification, as shown in the attached schedule. (signature) Vice President of Global Quality (function) Chris LaPoint (name) 1-Feb-19; Shakopee, MN USA (date of issue & place) Quick Start Guide February 2019 48 Rosemount 3051SHP

EU Declaration of Conformity

No: RMD 1104 Rev. F Page 2 of 4 EMC Directive (2014/30/EU) Harmonized Standards: EN 61326-1:2013, EN61326-2-3: 2013 Radio Equipment Directive (RED) (2014/53/EU) Harmonized Standards: EN 300 328 V2.1.1 EN 301 489-1 V2.2.0 EN 301 489-17 V3.2.0 EN 61010-1: 2010 EN 62479: 2010 PED Directive (2014/68/EU) QS Certificate of Assessment - Certifcate No. 12698-2018-CE-ACCREDIA Module H Conformity Assessment Other Standards Used: ANSI / ISA 61010-1:2004 Note – previous PED Certificate No. 59552-2009-CE-HOU-DNV ATEX Directive (2014/34/EU) DEKRA 15ATEX0108X - Flameproof Certificate Equipment Group II Category 1/2 G Ex db IIC T6…T4 Ga/Gb Harmonized Standards Used: EN60079-0:2012+A11:2013, EN60079-1:2014, EN60079-26:2015 BAS01ATEX1303X – Intrinsic Safety Certificate Equipment Group II, Category 1 G Ex ia IIC T4 Ga Harmonized Standards Used: EN 60079-0:2012+A11:2013, EN 60079-11:2012 February 2019 Quick Start Guide Quick Start Guide 49

EU Declaration of Conformity

No: RMD 1104 Rev. F Page 3 of 4 BAS01ATEX3304X – Type n Certificate Equipment Group II, Category 3 G Ex nA IIC T5 Gc Harmonized Standards Used: EN 60079-0:2012+A11:2013, EN 60079-15:2010 BAS01ATEX1374X – Dust Certificate Equipment Group II, Category 1 D Ex ta IIIC T105°C T50095°C Da Harmonized Standards Used: EN 60079-0:2012+A11:2013, Other Standards Used: EN 60079-31:2009 (a review against EN 60079-31:2014, which is harmonized, shows no significant changes relevant to this equipment so EN 60079-31:2009 continues to represent “State of the Art”) PED Notified Body DNV GL Assurance Italia S.r.l. [Notified Body Number: 0496] Via Energy Park 14, N-20871 Vimercate (MB), Italy Note – equipment manufactured prior to 20 October 2018 may be marked with the previous PED Notified Body number; previous PED Notified Body information was as follows: Det Norske Veritas (DNV) [Notified Body Number: 0575] Veritasveien 1, N1322 Hovik, Norway ATEX Notified Bodies for EU Type Examination Certificate DEKRA Certification B.V. [Notified Body Number: 0344] Utrechtsewg 310 Postbus 5185 6802 ED Arnhem Netherlands SGS FIMCO OY [Notified Body Number: 0598] P.O. Box 30 (Särkiniementie 3) 00211 HELSINKI Finland Quick Start Guide February 2019 50 Rosemount 3051SHP

EU Declaration of Conformity

No: RMD 1104 Rev. F Page 4 of 4 ATEX Notified Bodies for Quality Assurance SGS FIMCO OY [Notified Body Number: 0598] P.O. Box 30 (Särkiniementie 3) 00211 HELSINKI Finland February 2019 Quick Start Guide Quick Start Guide 51

ਜ਼ᴹChina RoHS㇑᧗⢙䍘䎵䗷ᴰབྷ⎃ᓖ䲀٬Ⲵ䜘Ԧරਧࡇ㺘Rosemount 3051SHP

List of Rosemount 3051SHP Parts with China RoHS Concentration above MCVs 䜘Ԧ਽〠 Part Name ᴹᇣ⢙䍘/ Hazardous Substances  䫵 Lead (Pb) ⊎ Mercury (Hg) 䭹 Cadmium (Cd) ޝԧ䬜 Hexavalent Chromium (Cr +6) ཊⓤ㚄㤟 Polybrominated biphenyls (PBB) ཊⓤ㚄㤟䟊 Polybrominated diphenyl ethers (PBDE) ⭥ᆀ㓴Ԧ Electronics Assembly X O O O O O ༣փ㓴Ԧ Housing Assembly X O O X O O Րᝏಘ㓴Ԧ Sensor Assembly X O O X O O ᵜ㺘Ṭ㌫׍ᦞSJ/T11364Ⲵ㿴ᇊ㘼ࡦ֌ This table is proposed in accordance with the provision of SJ/T11364. O: ᜿Ѫ䈕䜘ԦⲴᡰᴹ൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵਜ਼䟿൷վҾGB/T 26572ᡰ㿴ᇊⲴ䲀䟿㾱≲ O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB/T 26572. X: ᜿Ѫ൘䈕䜘Ԧᡰ֯⭘Ⲵᡰᴹ൷䍘ᶀᯉ䟼ˈ㠣ቁᴹа㊫൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵਜ਼䟿儈ҾGB/T 26572ᡰ㿴ᇊⲴ䲀䟿㾱≲ X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572. Quick Start Guide February 2019 52 Rosemount 3051SHP

Quick Start Guide

00825-0100-4851, Rev. AH February 2019 Global Headquarters Emerson Automation Solutions 6021 Innovation Blvd. Shakopee, MN 55379, USA +1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 [email protected] North America Regional Office Emerson Automation Solutions 8200 Market Blvd. Chanhassen, MN 55317, USA +1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 [email protected] Latin America Regional Office Emerson Automation Solutions 1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA +1 954 846 5030 +1 954 846 5121 [email protected] Europe Regional Office Emerson Automation Solutions Europe GmbH Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland +41 (0) 41 768 6111 +41 (0) 41 768 6300 [email protected] Asia Pacific Regional Office Emerson Automation Solutions 1 Pandan Crescent Singapore 128461 +65 6777 8211 +65 6777 0947 [email protected] Middle East and Africa Regional Office Emerson Automation Solutions Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates +971 4 8118100 +971 4 8865465 [email protected] Linkedin.com/company/Emerson- Automation-Solutions Twitter.com/Rosemount_News Facebook.com/Rosemount Youtube.com/user/ RosemountMeasurement Google.com/+RosemountMeasurement ©2019 Emerson. All rights reserved. Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is mark of one of the Emerson family of companies. All other marks are the property of their respective owners.