Emerson 3051S Quick Start Manual
Text of the manual
Quick Start Guide
00825-0100-4851, Rev AH
February 2019
Rosemount
™ 3051S High Static
Differential Pressure Transmitter
This guide provides basic guidelines for the Rosemount™ 3051S High Static Differential Pressure
Transmitter (3051SHP). It does not provide instructions for diagnostics, maintenance, service,
troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations. Refer to the
Rosemount 3051SHP Reference Manual for more information. This document is also available
electronically on Emerson.com/Rosemount.
Shipping considerations for wireless products.
The unit was shipped to you without the power module installed. Remove the power module prior to
shipping.
Each power module contains two “C” size primary lithium batteries. Primary lithium batteries are
regulated in transportation by the U. S. Department of Transportation, and are also covered by IATA
(International Air Transport Association), ICAO (International Civil Aviation Organization), and ARD
(European Ground Transportation of Dangerous Goods). It is the responsibility of the shipper to ensure
compliance with these or any other local requirements. Consult current regulations and requirements
before shipping.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate
local, national, and international standards, codes, and practices. Review the approvals section of this
manual for any restrictions associated with a safe installation.
•
Before connecting a handheld communicator in an explosive atmosphere, make sure the
instruments in the loop are installed in accordance with intrinsically safe or non-incendive field
wiring practices.
•
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power
is applied to the unit.
Process leaks could result in death or serious injury.
•
To avoid process leaks, ensure secure connection with coned-and-threaded connection.
•
Install and tighten process connectors before applying pressure.
Power module considerations.
•
The power module may be replaced in a hazardous area. The power module has surface resistivity
greater than one gigaohm and must be properly installed in the wireless device enclosure. Care
must be taken during transportation to and from the point of installation to prevent electrostatic
charge build-up.
•
This device complies with Part 15 of the FCC Rules. Operation is subject to the following
conditions:
—
This device may not cause harmful interference.
—
This device must accept any interference received, including interference that may cause
undesired operation.
—
This device must be installed to ensure a minimum antenna separation distance of 20 cm
from all persons.
•
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause
electrical shock.
Quick Start Guide
February 2019
2
Rosemount 3051SHP
System readiness........................................... 5
Mount the transmitter................................... 7
Rotate housing............................................ 14
Set switches and jumpers.............................16
Power up transmitter...................................18
Verify configuration..................................... 31
Trim the transmitter.................................... 35
Safety Instrumented Systems (4-20 mA only)..
37
Product certifications...................................38
February 2019
Quick Start Guide
Quick Start Guide
3
Confirm HART® revision capability
If using HART based control or asset management systems, confirm the HART
capability of those systems prior to transmitter installation. Not all systems
are capable of communicating with HART Revision 7 protocol. This
transmitter can be configured for either HART Revision 5 or 7.
For instructions on how to change the HART revision of the transmitter, see
the Rosemount 3051S Reference Manual.
1.2
Confirm correct device driver
Procedure
1. Verify the latest device driver (DD/DTM™) is loaded on your systems to
ensure proper communications.
2. Download the latest device driver at Emerson.com or
FieldCommGroup.org.
1.3
Rosemount™ 3051S device revisions and drivers
Table 1-1 provides the information necessary to ensure you have the correct
device driver and documentation for your device.
Table 1-1: Rosemount 3051S Device Revisions and Files
Identify device
Find device driver
Review
instructio
ns
Review
functiona
lity
Software
Release
Date
NAMUR
Software
Revision(1)
HART
Software
Revision(2)
HART
Universal
Revision
Device
Revision(3)
Manual
Documen
t Number
Changes
to
Software(4
)
Apr-16
1.0.0
20
7
4
00809-01
00-4801
See (4) for
list of
changes.
5
3
Oct-10
N/A
12
5
3
00809-01
00-4801
Added
Power
Advisory,
mA
Output,
Power
Consumpt
ion,
Coefficien
t of
Variation
February 2019
Quick Start Guide
Quick Start Guide
5
Table 1-1: Rosemount 3051S Device Revisions and Files (continued)
Identify device
Find device driver
Review
instructio
ns
Review
functiona
lity
May-07
N/A
7
5
2
00809-01
00-4801
Update
Statistical
Process
Monitorin
g
Capability
Sep-06
N/A
4, 5, 6
5
1
00809-01
00-4801
N/A
(1)
NAMUR software revision is located on the hardware tag of the device. In
accordance with NE53, revisions of the least significant level X (of 1.0.X) do not
change functionality or operation of the device and will not be reflected in the
review functionality column.
(2)
HART software revision can be read using a HART capable configuration tool.
(3)
Device driver file names use Device and DD Revision, e.g. 10_01. HART Protocol is
designed to enable legacy device driver revisions to continue to communicate with
new HART devices. To access new functionality, the new device driver must be
downloaded. It is recommended to download new device driver files to ensure full
functionality.
(4)
HART Revision 5 and 7 selectable.
Quick Start Guide
February 2019
6
Rosemount 3051SHP
Mount the transmitter
2.1
Mount the transmitter in liquid applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so the drain/vent valves are oriented upward.
Figure 2-1: Mounting the Transmitter in Liquid Applications
Coplanar
In-line
Flow
2.2
Mount the transmitter in gas applications
Procedure
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
Figure 2-2: Mounting the Transmitter in Gas Applications
Coplanar
Inline
February 2019
Quick Start Guide
Quick Start Guide
7
Using a mounting bracket
If the transmitter requires the use of a mounting bracket, use the images
below for instructions on how to properly mount the transmitter using the
Emerson™ provided mounting brackets. Use only bolts provided with the
transmitter or sold as Emerson spare parts.
Bolts should be tightened to a torque of 125 in-lb.
Panel mount
Pipe mount
Quick Start Guide
February 2019
8
Rosemount 3051SHP
Environmental seal for housing
Thread sealing (PFTE) tape or paste on male threads of conduit is required to
provide a water/dust tight conduit seals and meets requirements of NEMA®
Type 4X, IP66, and IP68. Consult factory if other Ingress Protection ratings are
required.
For M20 threads, install conduit plugs to full thread engagement or until
mechanical resistance is met.
2.5
Installing high pressure coned and threaded connection
The transmitter comes with an autoclave connection designed for high
pressure applications. Follow the steps below to properly connect the
transmitter to your process:
February 2019
Quick Start Guide
Quick Start Guide
9
1. Apply a process-compatible lubricant to the gland nut threads.
2. Slip the gland nut onto the tube, then thread the collar onto the tube
end (the collar is reverse threaded).
3. Apply a small amount of process-compatible lubricant applied to the
tube cone to help prevent galling and facilitate sealing. Insert the
tubing into the connection and tighten finger tight.
4. Tighten the gland nut to a torque of 25 ft-lb.
Need help?
A weep hole has been designed into the transmitter for safety and leak
detection. If fluid begins to leak from the weep hole, isolate the process
pressure, disconnect the transmitter, and reseal until the leak is resolved. All
Rosemount™ 3051SHP Transmitters come with a 316L SST tag attached to the
module.
2.6
Wireless considerations (if applicable)
Power up sequence
The power module should not be installed on any wireless device until the
Emerson™ Wireless Gateway (Gateway) has been installed and functioning
properly. See Connect the power module for WirelessHART® transmitter for
more details.
Antenna position
Position the antenna vertically, either straight up or straight down (see Figure
2-3). The antenna should be approximately 3 ft. (1 m) from any large structure
or building to allow clear communication to other devices.
Figure 2-3: Antenna Position
Quick Start Guide
February 2019
10
Rosemount 3051SHP
Mount the high gain, remote antenna (WN wireless option
only)
The high gain, remote antenna option provides flexibility for mounting the
transmitter based on wireless connectivity, lightning protection, and current
work practices (see Figure 2-4).
WARNING
When installing the remote mount antenna for the transmitter, always use
established safety procedures to avoid falling or contact with high-power
electrical lines.
Install remote antenna components for the transmitter in compliance with
local and national electrical codes and use best practices for lightning
protection.
Before installing, consult with the local area electrical inspector, electrical
officer, and work area supervisor.
The remote antenna option is specifically engineered to provide installation
flexibility while optimizing wireless performance and local spectrum
approvals. To maintain wireless performance and avoid non-compliance with
spectrum regulations, do not change the length of cable or the antenna type.
If the supplied remote mount antenna kit is not installed per these
instructions, Emerson™ is not responsible for wireless performance or non-
compliance with spectrum regulations.
The high gain, remote mount antenna kit includes coaxial sealant for the
cable connections for the lightning arrestor and antenna.
Procedure
1. Find a location where the remote antenna has optimal wireless
performance. Ideally this will be 15–25 ft. (4,6–7,6 m) above the
ground or 6 ft. (2 m) above obstructions or major infrastructure.
2. Mount the antenna on a 1.5- to 2-in. pipe mast using the supplied
mounting equipment.
3. Connect the lightning arrestor directly to the top of the transmitter.
4. Install the grounding lug, lock washer, and nut on top of lightning
arrestor.
5. Connect the antenna to the lightning arrestor using the supplied
LMR-400 coaxial cable ensuring the drip loop is not closer than 1 ft.
(0,3 m) from the lightning arrestor.
6. Use the coaxial sealant to seal each connection between the wireless
field device, lightning arrestor, cable, and antenna.
February 2019
Quick Start Guide
Quick Start Guide
11
7. Ensure the mounting mast and lightning arrestor are grounded
according to local/national electrical code.
Example
Figure 2-4: Rosemount 3051S with High Gain, Remote Antenna
A
B
D
C
A. Lightning arrestor
B. Antenna
C. Mounting mast
D. Drip loop
Weather proofing is required! The remote mount antenna kit includes
coaxial sealant for weather proofing the cable connections for the
lightning arrestor, antenna, and the transmitter. Coaxial sealant must
be applied to guarantee performance of the wireless field network.
See Figure 2-5 for details on how to apply coaxial sealant.
Quick Start Guide
February 2019
12
Rosemount 3051SHP
Figure 2-5: Applying Coaxial Sealant to Cable Connections
Postrequisites
Any spare lengths of coaxial cable should be placed in 1 ft. (0,3 m) coils.
February 2019
Quick Start Guide
Quick Start Guide
13
To improve field access to wiring or to better view the optional LCD display:
Procedure
1. Loosen the housing rotation set screw.
2. Rotate the housing clockwise to the desired location. If the desired
location cannot be achieved due to thread limit, rotate the housing
counter clockwise to the desired location (up to 360° from thread
limit).
CAUTION
Do not rotate the housing more than 180° without first performing a
disassembly procedure. Over-rotation may sever the electrical
connection between the sensor module and the feature board
electronics.
3. Retighten the housing rotation set screw up to 30 in-lb.
4. For wireless, consider access to the power module when selecting
housing rotation.
Figure 3-1: Transmitter Housing Set Screw (Plantweb)
A
A. Housing rotation set screw (3/32-in.)
Quick Start Guide
February 2019
14
Rosemount 3051SHP
Figure 3-2: Transmitter Housing Set Screw (Junction Box)
A
A. Housing rotation set screw (3/32-in.)
February 2019
Quick Start Guide
Quick Start Guide
15
Set switches and jumpers
If alarm and security adjustment option is not installed, the transmitter will
operate normally with the default alarm condition alarm “high” and the
security “off”.
Procedure
1. Do not remove the transmitter covers in explosive atmospheres when
the circuit is live. If the transmitters is live, set the loop to manual and
remove power.
2. Remove the electronics compartment cover. On the Plantweb housing
the cover is opposite the field terminals side, or on the junction box
housing remove the terminal block cover. Do not remove the housing
cover in explosive environments.
3. On the Plantweb housing, slide the security and alarm switches into
the preferred position by using a small screwdriver (An LCD display or
an adjustment module must be in place to activate the switches). On
the junction box housing pull the pins out and rotate 90° into desired
position to set the security and alarm.
4. Reinstall the housing cover so metal contacts metal to meet explosion-
proof requirements.
Figure 4-1: Transmitter Switch and Jumper Configuration
(Plantweb)
A
B
C
A. Meter/adjustment module
B. Security
C. Alarm
Quick Start Guide
February 2019
16
Rosemount 3051SHP
Figure 4-2: Transmitter Switch and Jumper Configuration (Junction
Box)
B
C
A. Meter/adjustment module
B. Security
C. Alarm
February 2019
Quick Start Guide
Quick Start Guide
17
Power up transmitter
This section provides the steps needed to power up transmitters. These steps
are unique based on the specific protocol used. Reference the appropriate
section listed below for the specific steps.
•
Connect wiring and power up for wired HART configuration
•
Connect wiring and power up FOUNDATION™ Fieldbus transmitter
•
Connect the power module for WirelessHART® transmitter
5.1
Connect wiring and power up for wired HART
configuration
Use the following steps to wire the transmitter:
Procedure
1. Remove and discard orange conduit plugs.
2. Remove the housing cover labeled “Field Terminals.”
3.
CAUTION
Do not connect the power across the test terminals. Power could
damage the test diode in the test connection. Twisted pairs yield best
results. Use 24 AWG to 14 AWG wire and do not exceed 5,000 feet
(1500 meters). For single compartment housing (Junction Box
housing), shielded signal wiring should be used in high EMI/RFI
environments.
Connect the positive lead to the “+” terminal, and the negative lead to
the “–” terminal.
4. Ensure full contact with terminal block screw and washer. When using
a direct wiring method, wrap wire clockwise to ensure it is in place
when tightening the terminal block screw.
The use of a pin or ferrule wire terminal is not recommended as the
connection may be more susceptible to loosening over time or under
vibration.
5. If the optional process temperature input is not installed, plug and seal
the unused conduit connection. If the optional process temperature
input is being utilized, see Install optional process temperature input
(Pt 100 RTD sensor) for more information.
When the enclosed threaded plug is utilized in the conduit opening, it
must be installed with a minimum thread engagement in order to
comply with explosion-proof requirements. For straight threads, a
Quick Start Guide
February 2019
18
Rosemount 3051SHP
minimum of seven threads must be engaged. For tapered threads, a
minimum of five threads must be engaged.
6. If applicable, install wiring with a drip loop. Arrange the drip loop
so the bottom is lower than the conduit connections and the
transmitter housing.
7. Reinstall the housing cover and tighten so the cover is fully seated with
metal to metal contact between the housing and cover in order to
meet explosion proof requirements.
Example
Transmitter wiring shows the wiring connections necessary to power a wired
HART transmitter and enable communications with a handheld
communicator.
5.2
Transmitter wiring
Figure 5-1: Plantweb™ Housing
A
B
A. RL ≥ 250 Ω
B. Power supply
Figure 5-2: Junction Box
A
B
A. RL ≥ 250 Ω
B. Power supply
February 2019
Quick Start Guide
Quick Start Guide
19
Figure 5-3: With Optional Process Temperature Connection
B
A
A. RL ≥ 250 Ω
B. Power supply
Note
Installation of the transient protection terminal block does not provide
transient protection unless the transmitter case is properly grounded.
5.3
Signal wiring grounding
Do not run signal wiring in conduit or open trays with power wiring, or near
heavy electrical equipment. Grounding terminations are provided on the
sensor module and inside the terminal compartment. These grounds are used
when transient protection terminal blocks are installed or to fulfill local
regulations.
Procedure
1. Remove the field terminals housing cover.
2. Connect the wiring pair and ground as indicated in Figure 5-4.
The cable shield should:
•
Be trimmed close and insulated from touching the transmitter
housing
•
Continuously connect to the termination point
•
Be connected to a good earth ground at the power supply end
Quick Start Guide
February 2019
20
Rosemount 3051SHP
Figure 5-4: Wiring
DP
C
A
B
B
D
E
B
A. Insulate shield
B. Minimize distance
C. Connect shield back to the power supply ground
D. Trim shield and insulate
E. Safety ground
3. Replace the housing cover. It is recommended the cover be tightened
until there is no gap between the cover and the housing.
4. Plug and seal unused conduit connections with the provided conduit
plug.
When the enclosed threaded plug is utilized in the conduit opening, it
must be installed with a minimum thread engagement in order to
comply with explosion-proof requirements. For straight threads, a
minimum of seven threads must be engaged. For tapered threads, a
minimum of five threads must be engaged.
5.4
Remote display wiring and power up (if applicable)
The remote mount display and Interface system consists of a local transmitter
and a remote mount LCD display assembly. The local Rosemount 3051S
assembly includes a Junction Box housing with a three-position terminal block
integrally mounted to a sensor module. The remote mount LCD display
assembly consists of a dual compartment Plantweb housing with a seven
position terminal block. See Figure 5-5 for complete wiring instructions. The
following is a list of necessary information specific to the remote mount
display system:
•
Each terminal block is unique for the remote display system.
•
A 316 SST housing adaptor is permanently secured to the remote mount
LCD display Plantweb housing, providing an external ground and a means
for field mounting with the provided mounting bracket.
February 2019
Quick Start Guide
Quick Start Guide
21
A cable is required for wiring between the transmitter and remote mount
LCD display. The cable length is limited to 100 ft.
•
50 ft. (option M8) or 100 ft. (option M9) cable is provided for wiring
between the transmitter and remote mount LCD display. Option M7 does
not include cable; see recommended specifications below.
Cable type
Recommend Madison AWM Style 2549 cable. Other comparable cable may be
used as long as it has independent dual twisted shielded pair wires with an
outer shield. The power wires must be 22 AWG minimum and the CAN
communication wires must be 24 AWG minimum.
Cable length
The cable length is up to 100 ft .depending upon cable capacitance.
Cable capacitance
The capacitance from the CAN communications line to the CAN return line as
wired must be less than 5,000 picofarads total. This allows up to 50 picofarads
per foot for a 100 foot cable.
Intrinsic safety consideration
The transmitter assembly with remote display has been approved with
Madison AWM Style 2549 cable. Alternate cable may be used as long as the
transmitter with remote display and cable is configured according to the
installation control drawing or certificate. Refer to appropriate approval
certificate or control drawing in Appendix B of the Rosemount 3051S
Reference Manual for remote cable IS requirements.
CAUTION
Do not apply power to the remote communications terminal. Follow wiring
instructions carefully to prevent damage to system components.
Quick Start Guide
February 2019
22
Rosemount 3051SHP
Figure 5-5: Remote Mount Display Wiring Diagram
A
B
C
(white) 24 AWG
(blue) 24 AWG
(black) 22 AWG
(red) 22 AWG
A. Remote mount display
B. Junction box housing
C. 4–20 mA
Note
Wire colors provided are per Madison AWM Style 2549 cable. Wire color may
vary depending on cable selected.
Madison AWM Style 2549 cable includes a ground shield. This shield must be
connected to earth ground at either the sensor module or the remote display,
but not both.
5.5
Quick connect wiring (if applicable)
As standard, the Rosemount 3051S Quick Connect arrives properly assembled
to the sensor module and is ready for installation. Cordsets and field wireable
connectors (in shaded area) are sold separately.
February 2019
Quick Start Guide
Quick Start Guide
23
Figure 5-6: Rosemount 3051S Quick Connect Exploded View
A
B
D
E
F
C
A. Straight field wireable connector (part number 03151-9063-0001),
supplied by customer
B. Right angle field wireable connector (part number 03151-9063-0002),
supplied by customer
C. Quick Connect housing
D. Cordset, supplied by vendor
E. Coupling nut
F. Quick Connect coupling nut
Important
If Quick Connect is ordered as a Rosemount 300S spare housing or is removed
from the sensor module, follow the instructions below for proper assembly
prior to field wiring.
Procedure
1. Place the Quick Connect onto the sensor module. To ensure proper pin
alignment, remove coupling nut prior to installing quick connect onto
the sensor module.
2. Place coupling nut over quick connect and wrench tighten to a
maximum of 300 in-lb (34 N-m).
3. Tighten the set screw up to 30 in-lb using a 3/32-in. hex wrench.
4. Install cordset/field wireable connectors onto the Quick Connect. Do
not over tighten.
Quick Start Guide
February 2019
24
Rosemount 3051SHP
Figure 5-7: Quick Connect Housing Pin-Out
A
B
“+”
“-”
A. Ground
B. No connection
Note
For other wiring details, refer to pin-out drawing and the cordset
manufacturer’s installation instructions.
5.6
Power supply
The DC power supply should provide power with less than two percent ripple.
The total resistance load is the sum of the resistance of the signal leads and
the load resistance of the controller, indicator, and related pieces. Note the
resistance of intrinsic safety barriers, if used, must be included.
he Field Communicator requires a minimum loop resistance of 250Ω for
communication.
Figure 5-8: Load Limitation (Standard Transmitter)
Load (Ohms)
1387
1000
500
0
10.5
20
30
42.4
Operating
Region
Voltage (Vdc)
Maximum Loop Resistance = 43.5 x (Power Supply Voltage – 10.5)
February 2019
Quick Start Guide
Quick Start Guide
25
Figure 5-9: Load Limitation (HART Diagnostic Transmitter [Option Code
DA2] Differential Pressure and Temperature Transmitter)
1322
1000
500
0
12.0
20
30
42.4
Voltage (Vdc)
Load (Ohms)
Operating
region
Maximum Loop Resistance = 43.5 x (Power Supply Voltage – 12.0)
5.7
Install optional process temperature input (Pt 100 RTD
sensor)
Use only ATEX/IECEx Flameproof cables (Temperature Input Code C30, C32,
C33, or C34) to meet ATEX/IECEx Flameproof certification.
Procedure
1. Mount the Pt 100 RTD sensor in the appropriate location.
2. Note
Use shielded four-wire cable for the process temperature connection.
Connect the RTD cable to the transmitter by inserting the cable wires
through the unused housing conduit and connect to the four screws
on the transmitter terminal block. An appropriate cable gland should
be used to seal the conduit opening around the cable.
3. Connect the RTD cable shield wire to the ground lug in the housing.
Quick Start Guide
February 2019
26
Rosemount 3051SHP
Figure 5-10: Transmitter RTD Wiring Connection
C
A
B
Red
Red
White
White
A. Pt 100 RTD sensor
B. RTD cable assembly wires
C. Ground lug
5.8
Connect wiring and power up FOUNDATION™ Fieldbus
transmitter
Cable connection
The segment cable can enter the transmitter through either conduit
connection on the housing. Cable entering the housing vertically should be
avoided. Drip loops are recommended for installations where moisture can
accumulate and enter the terminal compartment.
Power supply
The transmitter requires between 9 and 32 Vdc (9 and 15 Vdc for FISCO) at
the terminals to operate and provide complete functionality.
Power conditioner
A fieldbus segment requires a power conditioner to isolate the power supply
filter and decouple the segment from other segments attached to the same
power supply.
February 2019
Quick Start Guide
Quick Start Guide
27
Every fieldbus segment requires terminators at each end of the segment.
Failure to properly terminate segments may cause communication errors with
devices on the segment.
Transient protection
Transient protection devices require the transmitter be grounded for proper
operation. Refer to Figure 5-11 for further information.
5.8.1
Grounding
Grounding terminations are provided on the sensor module and inside the
terminal compartment. These grounds are used when transient protect
terminal blocks are installed or to fulfill local regulations.
Procedure
1. Remove the FIELD TERMINALS housing cover.
2. Note
The terminals are not polarity sensitive. The cable shield should:
•
Be trimmed close and insulated from touching the transmitter
housing
•
Continuously connect to the termination point
•
Be connected to a good earth ground at the power supply end
Connect the wiring pair and ground as indicated in Figure 5-11.
Quick Start Guide
February 2019
28
Rosemount 3051SHP
Figure 5-11: Wiring
FIELDBUS WIRING
DP
C
A
D
E
B
B
B
A. Insulate shield
B. Minimize distance
C. Connect shield back to the power supply ground
D. Trim shield and insulate
E. Safety ground
3. Replace the housing cover. It is recommended the cover be tightened
until there is no gap between the cover and the housing.
4. NOTICE
When the enclosed threaded plug is utilized in the conduit opening, it
must be installed with a minimum thread engagement in order to
comply with explosion-proof requirements. For straight threads, a
minimum of seven threads must be engaged. For tapered threads, a
minimum of five threads must be engaged.
Plug and seal the unused conduit connection with the provided
conduit plug.
5.9
Connect the power module for WirelessHART® transmitter
The power module should not be installed on any wireless device until the
Gateway is installed and functioning properly. This transmitter uses the black
power module (order model number 701PBKKF). Wireless devices should also
be powered up in order of proximity from the Gateway, beginning with the
closest. This will result in a simpler and faster network installation. Enable
active advertising on the Gateway to ensure new devices join the network
faster. For more information, see the Emerson 1420 Wireless Gateway
Reference Manual.
February 2019
Quick Start Guide
Quick Start Guide
29
1. Remove the housing cover on the field terminal side.
2. Connect the black power module.
Figure 5-12: Power module for WirelessHART transmitter
connections
Quick Start Guide
February 2019
30
Rosemount 3051SHP
Use any compliant master to communicate with and verify configuration of
the transmitter. Make sure to download the latest device driver from the
Device Install Kit site. Refer to Table 6-1 for the latest device revision for each
potential configuration.
Configuration can be verified using two methods:
1. Using the Field Communicator
2. Via AMS Device Manager
Fast Keys for using a Field Communicator are provided in Table 6-2.
To verify wireless operation, refer to Verify WirelessHART operation using the
Local display (LCD); verification can also be done at the device via the LCD
display.
Table 6-1: Device Revisions
Device configuration
Device revision
Rosemount™ 3051S HART (wired)
Rev. 7
Rosemount 3051S FOUNDATION™ Fieldbus
Rev. 23
Rosemount 3051S WirelessHART
Rev. 3
Rosemount 3051S MultiVariable™
Rev. 1
Rosemount 3051S HART® Diagnostics (DA2)
Rev. 3
6.1
Verify with Field Communicator
Connecting to a Field Communicator
For the Field Communicator to interface with the transmitter, power must be
supplied to the transmitter. For wireless configuration, the communicator
connections are located behind the power module on the terminal block (see
Figure 6-1). For wired configurations, the connections are on the terminal
block (see Figure 6-2, Figure 6-3, or Figure 6-4).
February 2019
Quick Start Guide
Quick Start Guide
31
Field Communicator connections
Figure 6-1: WirelessHART® terminal block
COMM
P/N 00753-9200-0010
Figure 6-2: HART® and DA2 terminal block
Figure 6-3: Multivariable terminal block
Quick Start Guide
February 2019
32
Rosemount 3051SHP
Figure 6-4: FOUNDATION™ Fieldbus terminal block
FIELDBUS WIRING
6.2
Fast Key sequence for critical parameters
Basic configuration parameters can be verified using a Field Communicator.
At a minimum, the parameters below should be verified as part of the
configuration and startup procedure.
Note
If no Fast Key sequence is provided, that parameter is not required to be
verified for that configuration.
Table 6-2: Fast Key Sequences
Function
HART®
protocol
FOUNDATION™
Fieldbus
protocol
Wireless
HART®
protocol
Differential
pressure and
temperature
measuremen
t
Advanced
diagnostics
Damping
2, 2, 1, 5
2, 1, 2
2, 2, 2, 4
1, 3, 7
2, 2, 1, 1, 3
DP Zero Trim
3, 4, 1, 3
2, 1, 1
2, 1, 2
1, 2, 4, 3, 1
3, 4, 1, 1, 1, 3
DP Units
2, 2, 1, 2
3, 2, 1
2, 2, 2, 3
1, 3, 3, 1
2, 1, 1, 1, 2, 1
Range Analog
Output
2, 2, 1, 4
N/A
N/A
1, 2, 4, 1
3, 4, 1, 2, 3
Tag
2, 2, 5, 1
4, 1, 3
2, 2, 9, 1
1, 3, 1
2, 1, 1, 1, 1, 1
Transfer
2, 2, 1, 4
N/A
2, 2, 4, 2
1, 3, 6
2, 2, 1, 1, 4
For instructions on how to configure an AI block in your FOUNDATION
Fieldbus transmitter, refer to the Rosemount™ 3051S FOUNDATION Fieldbus
Reference Manual.
Verify WirelessHART operation using the Local display (LCD)
The LCD display will show the output values based on the wireless update
rate. Refer to the Rosemount 3051S Wireless Reference Manual for error
codes and other LCD display messages. Press and hold the Diagnostic button
February 2019
Quick Start Guide
Quick Start Guide
33
for at least five seconds to display the TAG, Device ID, Network ID, Network
Join Status, and Device Status screens.
Searching for
network
Joining network
Connected with
limited bandwidth
Connected
N E T w K
S R C H N G
n e t w k
N E G O T
n e t w k
L I M - O P
n e t w k
O K
Note
It may take several minutes for the device to join the network. For advanced
troubleshooting of the wireless network or Gateway, see the Rosemount
3051S WirelessHART Reference Manual, Emerson™ 1410 Wireless Gateway
Reference Manual, Emerson 1420 Wireless Gateway Reference Manual or
Quick Start Guide.
Quick Start Guide
February 2019
34
Rosemount 3051SHP
Trim the transmitter
Transmitters are shipped fully calibrated per request or by the factory default
of full scale (lower range value = zero, upper range value = upper range limit).
7.1
Zero trim
A zero trim is a single-point adjustment used for compensating mounting
position and line pressure effects. When performing a zero trim, ensure the
equalizing valve is open and all wet legs are filled to the correct level.
•
If zero offset is less than 3% of true zero, follow the Using the Field
Communicator instructions to perform a zero trim.
•
If zero offset is greater than 3% of true zero, follow the Using the
transmitter zero adjustment button instructions below to rerange.
•
If hardware adjustments are not available, see the Rosemount™ 3051S
Reference Manual to perform a rerange using the Field Communicator.
7.1.1
Using the Field Communicator
Procedure
1. Equalize or vent the transmitter and connect Field Communicator.
2. At the menu, input the Fast Key sequence (see Table 6-2).
3. Follow the commands to perform a zero trim.
7.1.2
Using the transmitter zero adjustment button
Procedure
Push and hold the Zero adjustment button for at least two seconds but no
longer than ten seconds.
Figure 7-1: Transmitter Adjustment Buttons (Plantweb™)
A
B
A. Zero
B. Span
February 2019
Quick Start Guide
Quick Start Guide
35
Figure 7-2: Transmitter Adjustment Buttons (Junction Box)
A
B
A. Zero
B. Span
Quick Start Guide
February 2019
36
Rosemount 3051SHP
Safety Instrumented Systems (4-20 mA only)
For safety certified installations, refer to the appropriate manual for
installation procedure and system requirements.
February 2019
Quick Start Guide
Quick Start Guide
37
Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that
the design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited
by the Federal Occupational Safety and Health Administration (OSHA).
European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the
Quick Start Guide. The most recent revision of the EU Declaration of
Conformity can be found at Emerson.com/Rosemount.
Installing Equipment in North America
The US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC)
permit the use of Division marked equipment in Zones and Zone marked
equipment in Divisions. The markings must be suitable for the area
classification, gas, and temperature class. This information is clearly defined in
the respective codes.
9.1
USA
E5 US Explosionproof, Dust Ignition-proof
Certificate 1143113
Standards
FM Class 3600 - 2011, FM Class 3615 - 2006, FM Class 3810 -
2005, UL 1203 5th Ed., UL 50E 1st Ed., UL 61010-1 (3rd
Edition)
Markings
XP CL I, DIV 1, GP B, C, D; T5; DIP CL II, DIV 1, GP E, F, G; CL III; –
50 °C ≤ Ta ≤ +85 °C; Seal Not Required; Type 4X
I5 US Intrinsically Safe; Nonincendive
Certificate 1143113
Standards
FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 -
2004, FM Class 3810 - 2005, UL 50E 1st Ed., UL 61010-1 (3rd
Edition)
Markings
IS CL I,II,III, DIV 1, GP A, B, C, D, E, F, G, T4; Class 1, Zone 0 AEx ia
IIC T4 (-50 °C ≤ Ta ≤ +70 °C) [HART]; T4(-50 °C ≤ Ta ≤ +60 °C)
[Fieldbus]; NI CL 1, DIV 2, GP A, B, C, D, T5, Ta = 70 °C;
Rosemount drawing 03251-1006; Type 4X
Quick Start Guide
February 2019
38
Rosemount 3051SHP
IE US FISCO Intrinsically Safe
Certificate 1143113
Standards
FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3810 -
2005, UL 50E 1st Ed., UL 61010-1 (3rd Edition)
Markings
IS CL I, DIV 1, GP A, B, C, D, T4(-50 °C ≤ Ta ≤ +60 °C); Class 1,
Zone 0 AEx ia IIC T4; Rosemount drawing 03251-1006; Type 4X
9.2
Canada
E6 Canada Explosion-proof, Dust Ignition-proof, Division 2
Certificate 1143113
Standards
CAN/CSA C22.2 No. 0-10, CSA C22.2 No. 25-1966 (R2014), CSA
C22.2 No. 30-M1986 (R2012), CSA C22.2 No. 94.2-07, CSA
C22.2 No. 213-M1987 (R2013), CAN/CSA-C22.2 No.
61010-1-12, ANSI/ISA 12.27.01-2011
Markings
Class I, Groups B, C, D, –50 °C ≤ Ta ≤ +85 °C; Class II, Groups E, F,
G; Class III; suitable for Class I, Zone 1, Group IIB+H2, T5; Class I,
Division 2, Groups A, B, C, D; suitable for Class I, Zone 2, Group
IIC, T5; Seal Not Required; Dual Seal; Type 4X
I6 Canada Intrinsically Safe
Certificate 1143113
Standards
CAN/CSA C22.2 No. 0-10, CAN/CSA-60079-0-11, CAN/CSA
C22.2 No. 60079-11:14, CSA C22.2 No. 94.2-07, ANSI/ISA
12.27.01-2011
Markings
Intrinsically Safe Class I, Division 1; Groups A, B, C, D; suitable
for Class 1, Zone 0, IIC, T3C, Ta = 70 °C; Rosemount drawing
03251-1006; Dual Seal; Type 4X
IF Canada FISCO Intrinsically Safe
Certificate 1143113
Standards
CAN/CSA C22.2 No. 0-10, CAN/CSA-60079-0-11, CAN/CSA
C22.2 No. 60079-11:14, CSA C22.2 No. 94.2-07, ANSI/ISA
12.27.01-2011
Markings
Intrinsically Safe Class I, Division 1; Groups A, B, C, D; suitable
for Class 1, Zone 0, IIC, T3C, Ta = 70 °C; Rosemount drawing
03251-1006; Dual Seal; Type 4X
February 2019
Quick Start Guide
Quick Start Guide
39
E1 ATEX Flameproof
Certificate DEKRA 15ATEX0108X
Standards
EN 60079-0:2012 + A11:2013, EN60079-1:2014,
EN60079-26:2015
Markings
II 1/2 G Ex db IIC T6…T4 Ga/Gb, T6 (–60 °C ≤ Ta ≤ +70 °C),
T4/T5 (–60 °C ≤ Ta ≤ +80 °C); Vmax = 42.4 VDC
Temperature class
Process temperature
Ambient temperature
T6
–60 °C to +70 °C
–60 °C to +70 °C
T5
–60 °C to +80 °C
–60 °C to +80 °C
T4
–60 °C to +120 °C
–60 °C to +80 °C
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm less than 1 mm thickness
that forms a boundary between zone 0 (process connection) and zone
1 (all other parts of the equipment). The model code and datasheet
are to be consulted for details of the diaphragm material. Installation,
maintenance and use shall take into account the environmental
conditions to which the diaphragm will be subjected. The
manufacturer's instructions for installation and maintenance shall be
followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic build-up
on painted surfaces, and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
4. Appropriate cable, glands and plugs need to be suitable for a
temperature of 5 °C greater than maximum specified temperature for
location where installed.
I1 ATEX Intrinsic Safety
Certificate
BAS01ATEX1303X
Standards
EN 60079-0:2012, EN 60079-11:2012
Markings
II 1 G Ex ia IIC T4 Ga, T4(–60 °C ≤ Ta ≤ +70 °C)
Quick Start Guide
February 2019
40
Rosemount 3051SHP
3051S…F…IA; 3051SF …F…
IA; 3051SHP…D…F…IA
17.5 V
380 mA
5.32 W
0
0
3051S …A…M7, M8, or M9;
3051SF …A…M7, M8, or
M9;
3051SAL…C… M7, M8, or
M9;
3051SHP…D… M7, M8, or
M9;
30 V
300 mA
1.0 W
12 nF
60 μH
3051SAL; 3051SAM
30 V
300 mA
1.0 W
12 nF
33 μH
3051SAL…M7, M8, or M9
3051SAM…M7, M8, or M9
30 V
300 mA
1.0 W
12 nF
93 μH
RTD option for 3051SF
5 V
500 mA
0.63 W
N/A
N/A
3051SHP…7…A
30 V
300 mA
1.0 W
14.8 nF
0
RTD option for 3051SHP…
7…A
30 V
2.31 mA
17.32
mW
N/A
N/A
3051SHP…7…F
30 V
300 mA
1.3 W
0
0
3051SHP…7…F…IA
17.5 V
380 mA
5.32 W
0
0
RTD option for 3051SHP…
7…F
30 V
18.24 mA
137 mW
0.8 nF
1.33 mH
Special Conditions for Safe Use (X):
1. The Rosemount 3051S Transmitters fitted with transient protection
are not capable of withstanding the 500 V test as defined in Clause
6.3.13 of EN 60079-11:2012. This must be taken into account during
installation.
2. The terminal pins of the Rosemount 3051S SuperModule must be
provided with a degree of protection of at least IP20 in accordance
with IEC/EN 60529.
3. The Rosemount 3051S enclosure may be made of aluminum alloy and
given a protective polyurethane paint finish; however, care should be
taken to protect it from impact or abrasion if located in a zone 0 area.
February 2019
Quick Start Guide
Quick Start Guide
41
IA ATEX FISCO
Certificate
BAS01ATEX1303X
Standards
EN 60079-0:2012, EN 60079-11:2012
Markings
II 1 G Ex ia IIC T4 Ga, T4(–60 °C ≤ Ta ≤ +70 °C)
Parameter
FISCO
Voltage Ui
17.5 V
Current Ii
380 mA
Power Pi
5.32 W
Capacitance Ci
0
Inductance Li
0
Special Conditions for Safe Use (X):
1. The Rosemount 3051S Transmitters fitted with transient protection
are not capable of withstanding the 500 V test as defined in Clause
6.3.13 of EN 60079-11:2012. This must be taken into account during
installation.
2. The terminal pins of the Rosemount 3051S SuperModule must be
provided with a degree of protection of at least IP20 in accordance
with IEC/EN 60529.
3. The Rosemount 3051S enclosure may be made of aluminum alloy and
given a protective polyurethane paint finish; however, care should be
taken to protect it from impact or abrasion if located in a zone 0 area.
ND ATEX Dust
Certificate BAS01ATEX1374X
Standards
EN 60079-0:2012, EN 60079-31:2009
Markings
II 1 D Ex ta IIIC T105 °C T500 95 °C Da, (–20 °C ≤ Ta ≤ +85 °C),
Vmax = 42.4 V
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of
the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which
maintain the ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient
temperature range of the apparatus and capable of withstanding a 7 J
impact test.
Quick Start Guide
February 2019
42
Rosemount 3051SHP
4. The SuperModule(s) must be securely screwed in place to maintain the
ingress protection of the enclosure(s).
N1 ATEX Type n
Certificate
BAS01ATEX3304X
Standards
EN 60079-0:2012, EN 60079-15:2010
Markings
II 3 G Ex nA IIC T5 Gc, (–40 °C ≤ Ta ≤ +85 °C), Vmax = 45 V
Special Condition for Safe Use (X):
1. The equipment is not capable of withstanding the 500 V insulation test
required by clause 6.5 of EN 60079-15:2010. This must be taken into
account when installing the equipment.
Note
RTD Assembly is not included with the Rosemount 3051SFx Type n Approval.
9.4
International
E7 IECEx Flameproof and Dust
Certificate IECEx DEK 15.0072X, IECEx BAS 09.0014X
Standards
IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-26:2014, IEC
60079-31:2008
Markings
Ex db IIC T6…T4 Ga/Gb, T6 (–60 °C ≤ Ta ≤ +70 °C), T4/T5 (–60 °C
≤ Ta ≤ +80 °C); Vmax = 42.4 VDC Ex ta IIIC T105 °C T500 95 °C Da
(–20 °C ≤ Ta ≤ +85 °C)
Temperature class
Process temperature
Ambient temperature
T6
–60 °C to +70 °C
–60 °C to +70 °C
T5
–60 °C to +80 °C
–60 °C to +80 °C
T4
–60 °C to +120 °C
–60 °C to +80 °C
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm less than 1 mm thickness
that forms a boundary between zone 0 (process connection) and zone
1 (all other parts of the equipment). The model code and datasheet
are to be consulted for details of the diaphragm material. Installation,
maintenance and use shall take into account the environmental
conditions to which the diaphragm will be subjected. The
manufacturer’s instructions for installation and maintenance shall be
followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
February 2019
Quick Start Guide
Quick Start Guide
43
3. Non-standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic build-up
on painted surfaces, and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
4. Appropriate cable, glands and plugs need to be suitable for a
temperature of 5 °C greater than maximum specified temperature for
location where installed.
5. Cable entries must be used which maintain the ingress protection of
the enclosure to at least IP66.
6. Unused cable entries must be filled with suitable blanking plugs which
maintain the ingress protection of the enclosure to at least IP66.
7. Cable entries and blanking plugs must be suitable for the ambient
temperature range of the apparatus and capable of withstanding a 7 J
impact test.
8. The Rosemount 3051S SuperModule must be securely screwed in
place to maintain the ingress protection of the enclosure.
I7 IECEx Intrinsic Safety
Certificate
IECEx BAS 04.0017X
Standards
IEC 60079-0:2011, IEC 60079-11:2011
Markings
Ex ia IIC T4 Ga, T4(–60 °C ≤ Ta ≤ +70 °C)
Model
Ui
Ii
P i
C i
Li
SuperModule
30 V
300 mA
1.0 W
30 nF
0
3051S...A; 3051SF…A;
3051SAL…C; 3051SHP…
D…A
30 V
300 mA
1.0 W
12 nF
0
3051S…F; 3051SF…F;
3051SHP…D…F
30 V
300 mA
1.3 W
0
0
3051S…F…IA; 3051SF …F…
IA; 3051SHP…D…F…IA
17.5 V
380 mA
5.32 W
0
0
3051S …A…M7, M8, or M9;
3051SF …A…M7, M8, or
M9;
3051SAL…C… M7, M8, or
M9;
3051SHP…D… M7, M8, or
M9
30 V
300 mA
1.0 W
12 nF
60 μH
3051SAL; 3051SAM
30 V
300 mA
1.0 W
12 nF
33 μH
Quick Start Guide
February 2019
44
Rosemount 3051SHP
3051SAL…M7, M8, or M9
3051SAM…M7, M8, or M9
30 V
300 mA
1.0 W
12 nF
93 μH
RTD option for 3051SF
5 V
500 mA
0.63 W
N/A
N/A
3051SHP…7…A
30 V
300 mA
1.0 W
14.8 nF
0
RTD option for 3051SHP…
7…A
30 V
2.31 mA
17.32
mW
N/A
N/A
3051SHP…7…F
30 V
300 mA
1.3 W
0
0
3051SHP…7…F…IA
17.5 V
380 mA
5.32 W
0
0
RTD option for 3051SHP…
7…F
30 V
18.24 mA
137 mW
0.8 nF
1.33 mH
Special Conditions for Safe Use (X):
1. The Rosemount 3051S Transmitters fitted with transient protection
are not capable of withstanding the 500 V test as defined in Clause
6.3.13 of EN 60079-11:2012. This must be taken into account during
installation.
2. The terminal pins of the Rosemount 3051S SuperModule must be
provided with a degree of protection of at least IP20 in accordance
with IEC/EN 60529.
3. The Rosemount 3051S enclosure may be made of aluminum alloy and
given a protective polyurethane paint finish; however, care should be
taken to protect it from impact or abrasion if located in a zone 0 area.
IG IECEx FISCO
Certificate
IECEx BAS 04.0017X
Standards
IEC 60079-0: 2011, IEC 60079-11: 2011
Markings
Ex ia IIC T4 Ga, T4(–60 °C ≤ Ta ≤ +70 °C)
Parameter
FISCO
Voltage Ui
17.5 V
Current Ii
380 mA
Power Pi
5.32 W
Capacitance Ci
0
Inductance Li
0
February 2019
Quick Start Guide
Quick Start Guide
45
Special Conditions for Safe Use (X):
1. The Rosemount 3051S Transmitters fitted with transient protection
are not capable of withstanding the 500 V test as defined in Clause
6.3.13 of EN 60079-11:2012. This must be taken into account during
installation.
2. The terminal pins of the Rosemount 3051S SuperModule must be
provided with a degree of protection of at least IP20 in accordance
with IEC/EN 60529.
3. The Rosemount 3051S enclosure may be made of aluminum alloy and
given a protective polyurethane paint finish; however, care should be
taken to protect it from impact or abrasion if located in a zone 0 area.
N7 IECEx Type n
Certificate
IECEx BAS 04.0018X
Standards
IEC 60079-0: 2011, IEC 60079-15: 2010
Markings
Ex nA IIC T5 Gc, (–40 °C ≤ Ta ≤ +85 °C)
Special Condition for Safe Use (X):
1. The equipment is not capable of withstanding the 500 V insulation test
required by clause 6.5 of EN 60079-15:2010. This must be taken into
account when installing the equipment.
9.5
EAC - Belarus, Kazakhstan, Russia
EM Technical Regulation Customs Union (EAC) Flameproof and Dust
Certificate
RU C-US.AA87.B.00378
Markings
Ga/Gb Ex d IIC T6…T4 X
Ex tb IIIC T105 °C T500 95 °C Db X
Ex ta IIIC T105 °C T500 95 °C Da X
See certificate for special conditions for safe use.
IM Technical Regulation Customs Union (EAC) Intrinsic Safety
Certificate
RU C-US.AA87.B.00378
Markings
0Ex ia IIC T4 Ga X
See certificate for special conditions for safe use.
9.6
Combinations
K1 Combination of E1, I1, N1, and ND
Quick Start Guide
February 2019
46
Rosemount 3051SHP
K7 Combination of E7, I7, and N7
KC Combination of E1, E5, I1, and I5
KD Combination of E1, E5, E6, I1, I5, and I6
KG Combination of IA, IE, IF, and IG
KM Combination of EM and IM
February 2019
Quick Start Guide
Quick Start Guide
47
Rosemount 3051SHP Declaration of Conformity
EU Declaration of Conformity
No: RMD 1104 Rev. F
Page 1 of 4
We,
Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN 55317-9685
USA
declare under our sole responsibility that the product,
Rosemount™ 3051SHP Pressure Transmitter
manufactured by,
Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN 55317-9685
USA
to which this declaration relates, is in conformity with the provisions of the European Union
Directives, including the latest amendments, as shown in the attached schedule.
Assumption of conformity is based on the application of the harmonized standards and, when
applicable or required, a European Union notified body certification, as shown in the attached
schedule.
(signature)
Vice President of Global Quality
(function)
Chris LaPoint
(name)
1-Feb-19; Shakopee, MN USA
(date of issue & place)
Quick Start Guide
February 2019
48
Rosemount 3051SHP
EU Declaration of Conformity
No: RMD 1104 Rev. F
Page 2 of 4
EMC Directive (2014/30/EU)
Harmonized Standards:
EN 61326-1:2013, EN61326-2-3: 2013
Radio Equipment Directive (RED) (2014/53/EU)
Harmonized Standards:
EN 300 328 V2.1.1
EN 301 489-1 V2.2.0
EN 301 489-17 V3.2.0
EN 61010-1: 2010
EN 62479: 2010
PED Directive (2014/68/EU)
QS Certificate of Assessment - Certifcate No. 12698-2018-CE-ACCREDIA
Module H Conformity Assessment
Other Standards Used: ANSI / ISA 61010-1:2004
Note – previous PED Certificate No. 59552-2009-CE-HOU-DNV
ATEX Directive (2014/34/EU)
DEKRA 15ATEX0108X - Flameproof Certificate
Equipment Group II Category 1/2 G
Ex db IIC T6…T4 Ga/Gb
Harmonized Standards Used:
EN60079-0:2012+A11:2013, EN60079-1:2014, EN60079-26:2015
BAS01ATEX1303X – Intrinsic Safety Certificate
Equipment Group II, Category 1 G
Ex ia IIC T4 Ga
Harmonized Standards Used:
EN 60079-0:2012+A11:2013, EN 60079-11:2012
February 2019
Quick Start Guide
Quick Start Guide
49
EU Declaration of Conformity
No: RMD 1104 Rev. F
Page 3 of 4
BAS01ATEX3304X – Type n Certificate
Equipment Group II, Category 3 G
Ex nA IIC T5 Gc
Harmonized Standards Used:
EN 60079-0:2012+A11:2013, EN 60079-15:2010
BAS01ATEX1374X – Dust Certificate
Equipment Group II, Category 1 D
Ex ta IIIC T105°C T50095°C Da
Harmonized Standards Used:
EN 60079-0:2012+A11:2013,
Other Standards Used:
EN 60079-31:2009 (a review against EN 60079-31:2014, which is
harmonized, shows no significant changes relevant to this equipment so
EN 60079-31:2009 continues to represent “State of the Art”)
PED Notified Body
DNV GL Assurance Italia S.r.l. [Notified Body Number: 0496]
Via Energy Park 14, N-20871
Vimercate (MB), Italy
Note – equipment manufactured prior to 20 October 2018 may be marked with the previous PED
Notified Body number; previous PED Notified Body information was as follows:
Det Norske Veritas (DNV) [Notified Body Number: 0575]
Veritasveien 1, N1322
Hovik, Norway
ATEX Notified Bodies for EU Type Examination Certificate
DEKRA Certification B.V. [Notified Body Number: 0344]
Utrechtsewg 310
Postbus 5185
6802 ED Arnhem
Netherlands
SGS FIMCO OY [Notified Body Number: 0598]
P.O. Box 30 (Särkiniementie 3)
00211 HELSINKI
Finland
Quick Start Guide
February 2019
50
Rosemount 3051SHP
EU Declaration of Conformity
No: RMD 1104 Rev. F
Page 4 of 4
ATEX Notified Bodies for Quality Assurance
SGS FIMCO OY [Notified Body Number: 0598]
P.O. Box 30 (Särkiniementie 3)
00211 HELSINKI
Finland
February 2019
Quick Start Guide
Quick Start Guide
51
ਜ਼ᴹChina RoHS㇑᧗⢙䍘䎵䗷ᴰབྷ⎃ᓖ䲀٬Ⲵ䜘Ԧරਧࡇ㺘Rosemount 3051SHP
List of Rosemount 3051SHP Parts with China RoHS Concentration above MCVs
䜘Ԧ〠
Part Name
ᴹᇣ⢙䍘/ Hazardous Substances
䫵
Lead
(Pb)
⊎
Mercury
(Hg)
䭹
Cadmium
(Cd)
ޝԧ䬜
Hexavalent
Chromium
(Cr +6)
ཊⓤ㚄㤟
Polybrominated
biphenyls
(PBB)
ཊⓤ㚄㤟䟊
Polybrominated
diphenyl ethers
(PBDE)
⭥ᆀ㓴Ԧ
Electronics
Assembly
X
O
O
O
O
O
༣փ㓴Ԧ
Housing
Assembly
X
O
O
X
O
O
Րᝏಘ㓴Ԧ
Sensor
Assembly
X
O
O
X
O
O
ᵜ㺘Ṭ㌫ᦞSJ/T11364Ⲵ㿴ᇊ㘼ࡦ
This table is proposed in accordance with the provision of SJ/T11364.
O: Ѫ䈕䜘ԦⲴᡰᴹ൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵਜ਼䟿൷վҾGB/T 26572ᡰ㿴ᇊⲴ䲀䟿㾱≲
O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of
GB/T 26572.
X: Ѫ൘䈕䜘Ԧᡰ֯⭘Ⲵᡰᴹ൷䍘ᶀᯉ䟼ˈ㠣ቁᴹа㊫൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵਜ਼䟿儈ҾGB/T 26572ᡰ㿴ᇊⲴ䲀䟿㾱≲
X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above
the limit requirement of GB/T 26572.
Quick Start Guide
February 2019
52
Rosemount 3051SHP
Quick Start Guide
00825-0100-4851, Rev. AH
February 2019
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd.
Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 949 7001
[email protected]
North America Regional Office
Emerson Automation Solutions
8200 Market Blvd.
Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 949 7001
[email protected]
Latin America Regional Office
Emerson Automation Solutions
1300 Concord Terrace, Suite 400
Sunrise, FL 33323, USA
+1 954 846 5030
+1 954 846 5121
[email protected]
Europe Regional Office
Emerson Automation Solutions Europe
GmbH
Neuhofstrasse 19a P.O. Box 1046
CH 6340 Baar
Switzerland
+41 (0) 41 768 6111
+41 (0) 41 768 6300
[email protected]
Asia Pacific Regional Office
Emerson Automation Solutions
1 Pandan Crescent
Singapore 128461
+65 6777 8211
+65 6777 0947
[email protected]
Middle East and Africa Regional Office
Emerson Automation Solutions
Emerson FZE P.O. Box 17033
Jebel Ali Free Zone - South 2
Dubai, United Arab Emirates
+971 4 8118100
+971 4 8865465
[email protected]
Linkedin.com/company/Emerson-
Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/
RosemountMeasurement
Google.com/+RosemountMeasurement
©2019 Emerson. All rights reserved.
Emerson Terms and Conditions of Sale are
available upon request. The Emerson logo is a
trademark and service mark of Emerson Electric
Co. Rosemount is mark of one of the Emerson
family of companies. All other marks are the
property of their respective owners.