TZID-C110 Intelligent positioner for PROFIBUS PA
for PA Profile V3.0
Short manual
Document No. 41/18-77 EN
Issue date
07.02
Revision
01
Manufacturer:
ABB Automation Products GmbH
Schillerstrasse 72
32425 Minden
GERMANY
Tel:
+49 571 830-1494
Fax:
+49 571 830-1860
Mail: [email protected]
Note:
This document is a short manual providing the essential information needed for mounting
and commissioning the TZID-C110 positioner. For details on other subjects like configuration,
operation and ordering details please refer to Data sheet 10/18-0.23 EN or the Operating
manual (CD version) 42/18-74 EN.
© Copyright 2002 by ABB Automation Products GmbH
Subject to changes without notice.
This technical documentation is protected by copyright. Translating, photocopying and dissem-
inating it in any form whatsoever - even editings or excerpts thereof - especially as reprint, pho-
tomechanical or electronic reproduction or storage on data processing systems or networks is
not allowed without the permission of the copyright owner and non-compliance will lead to both
civil and criminal prosecution.
Table of contents
41/18-77 EN
Table of contents
i
Table of contents
1
Safety and precautions .............................................................................................. 1
1.1
General ......................................................................................................................1
1.2
Explanation of warning signs and notes................................................................2
1.3
Notes on electrical and pneumatic safety .............................................................2
1.4
Proper use.................................................................................................................2
1.5
Qualified personnel ..................................................................................................3
2
Manufacturer’s information...................................................................................... 3
2.1
Delivery......................................................................................................................3
2.2
CE compliance information .....................................................................................3
3
Installing and commissioning ................................................................................. 4
3.1
Mechanical mounting...............................................................................................4
3.1.1
General........................................................................................................... 4
3.1.2
Operating conditions at the installation site ................................................... 5
3.1.3
Mounting to linear actuators ........................................................................... 5
3.1.4
Mounting the positioner to rotary actuators .................................................. 10
3.2
Pneumatic connection. ..........................................................................................13
3.2.1
Safety instructions ........................................................................................ 13
3.2.2
Making the pneumatic connection ................................................................ 14
3.2.3
Mounting the splash guard cap..................................................................... 15
3.3
Electrical connection..............................................................................................16
3.3.1
Safety instructions ........................................................................................ 16
3.3.2
Overview....................................................................................................... 17
3.3.3
Making the connections................................................................................ 18
Table of contents
ii
Table of contents
41/18-77 EN
3.4
Commissioning.......................................................................................................19
3.4.1
Commissioning procedure............................................................................ 19
3.4.2
Setting the bus address................................................................................ 20
3.4.3
Overview of the operating modes and how to select (from operating level). 21
3.4.4
Parameter setting example:.......................................................................... 22
4
Technical data ............................................................................................................. 24
4.1
Basic model.............................................................................................................24
4.2
Options ....................................................................................................................28
5
Certificates.................................................................................................................... 29
Appendix A: Configuration overview ........................................................................A
Safety and precautions
41/18-77 EN
Safety and precautions
1
1
Safety and precautions
1.1
General
Proper and safe operation of the TZID-C110 positioner requires:
•
proper transportation and storage
•
installation and commissioning by qualified
personnel
•
correct operation according to the instructions in this manual
•
proper use (see chapter 1.4 on page 2)
•
careful maintenance
Only qualified personnel are allowed to work on the device (see chapter 1.5 on page 3).
Observe
•
the present operating instructions
•
the relevant safety regulations and standards for the installation and operation of
electrical systems
•
the standards, regulations and directives governing explosion protection, when using
intrinsically safe devices
The regulations, standards and directives referred to in these operating instructions are
applicable in Germany. When using the TZID-C110 positioner outside the German Fed-
eral jurisdiction, the relevant regulations, standards and directives applicable in the coun-
try where the device is used must be observed.
The TZID-C110 positioner has been designed and tested in accordance with DIN VDE
0411 Part 1.
Safety Requirements for Electronic Measuring Apparatuses
(based on IEC Publication 348) and has been supplied in a safe condition.
The present operating instructions contain warnings and cautions marked with a symbol
(see chapter 1.2). The instructions given in these sections must be observed to retain the
device in a safe condition and to ensure safe operation. Otherwise, persons can be
endangered or the device itself or other devices or equipment may be damaged or fail.
Important instructions for your safety!
Read and observe!
Caution
Safety and precautions
2
Safety and precautions
41/18-77 EN
1.2
Explanation of warning signs and notes
Important information has been marked and emphasized with the following symbols in
these operating instructions:
1.3
Notes on electrical and pneumatic safety
1.4
Proper use
The TZID-C110 positioner is an electro-pneumatic valve positioner for use with pneu-
matic linear and rotary actuators.
The device may only be used for the applications listed in these operating instructions
and in the relevant data sheet (if available).
This symbol is printed next to warnings indicating a direct endangerment of a
person’s health or life. Also, major property damage may occur.
Warning
If the safety notes marked with this symbol are not observed, minor personal
injuries and property damage may result.
Caution
This symbol is printed next to notes containing important informationen pertai-
ning to your TZID-C110 or its operation.
•
Only qualified persons may mount, electrically and pneumatically connect,
and commission the TZID-C110 positioner.
•
Ensure the electrical safety of all feeding devices.
•
When connecting the electrical wiring, observe the specifications according
to chapter 4 "Technical data".
•
For the electrical installation of ex-protected devices, observe all national
regulations, DIN/VDE directives, especially VDE 0165, the directives for
explosion protection, and the specifications in the EC type examination cer-
tificates (see chapter “Certificates” on page 29 of this manual).
•
Do not use the internal communication interfaces LKS or X5 on the printed
circuit board if the positioner is installed in the hazardous area.
•
Observe the safety instructions of the pneumatic actuators when mounting
and commissioning the devices. There is danger of injuries due to the high
displacement forces of the actuators.
Warning
all-guides
com
Only those persons familiar with the installation, commissioning, operation and mainte-
nance of the TZID-C110 positioner or similar instruments and who have the required
qualification are authorized to work on the device.
These persons are:
•
Project specialists who are familiar with the security concepts of process automation.
•
Commissioning and service personnel, i.e. persons who have been trained ade-
quately to mount, commission, repair, and maintain the TZID-C110 positioner or sim-
ilar automation instruments or who are – according to safety standards and
guidelines – permitted to commission, ground, and label electrical circuitry, devices,
and systems.
•
Operating personnel who is familiar with handling automation equipment and with the
contents of these operating instructions and the instructions in the operating manual
42/18-74 EN.
2
Manufacturer’s information
2.1
Delivery
When receiving the delivery please immediately check items and scope for damages and
completeness. The scope of delivery is stated in the shipping documents. If ordered, the
accessories (e.g. mounting material, pressure gauge block, filter regulator) are added to
the delivery as individual items. Check items and scope of the delivery by means of the
catalog numbers to see if types and quantities are in accordance with your order.
If the positioner is delivered already mounted to the actuator, the positioner, accessories,
and actuator are considered as a common delivery item.
A list of catalog numbers and details of the different versions and accessories can be
found in data sheet 10/18-0.23 EN.
2.2
CE compliance information
We declare that we are the manufacturer of the TZID-C110 positioner and that the prod-
uct conforms with the regulations listed below and meets the following requirements of
EC regulation 89/336/CEE as of May 1989:
Basic technical standards/product standards
RFI suppression
EN 55022 as of May 1995
EN 50081-1 as of March 1993
EMI/RFI shielding
EN 50082-1 as of March 1993
The TZID-C110 positioner meets the EC regulation for CE conformity.
Installing and commissioning
4
Installing and commissioning
41/18-77 EN
3
Installing and commissioning
3.1
Mechanical mounting
3.1.1 General
The arrow (1) on the feedback
shaft (and thus the lever) must
travel within the area marked with
the small arrows (2).
When
mounting,
ensure that the
transfer
of
the
stroke or rotation
angle for the posi-
tion feedback is
correct. The maxi-
mum
rotation
angle is 60° for
mounting to linear
actuators
and
120° for mounting
to rotary actua-
tors.
The
mini-
mum
range
for
both applications
is 25°.
Fig. 1
Operating range
1
2
TZID-C
+60°
-60°
+30°
-30°
100%
0%
100%
0%
Sensor range for rotary actuators
Stroke range
Valve range
Sensor range for linear actuators
Fig. 2
Positioner ranges
Installing and commissioning
41/18-77 EN
Installing and commissioning
5
3.1.2 Operating conditions at the installation site
Ambient temperature:
-40 ... +85 °C (-40 ... +185 °F)
Relative humidity
< 75% (95% for a short time), non-condensing
Observe the specifications for protection class
IP65 / NEMA 4X
Explosion protection:
Observe the specifications in the certificate, see section
“Certificates” on page 29.
Mounting position:
any orientation allowed, provided that the splash guard
cap is in place, see section “Mounting the splash guard
cap” on page 15.
3.1.3 Mounting to linear actuators
A special attachment kit is available for mounting the positioner to a linear actuator
according to DIN/IEC 534 (lateral mounting to NAMUR) comprising the following parts:
Tools required:
Wrench 10 mm/13 mm
Allen key 4 mm
• Lever (1.0) w. follower
pin, for 10...35 mm or
25...90 mm actuator
stroke
• Follower guide (2.0)
with two screws (2.1)
and clamp plates (2.2)
• Angle bracket (3.0)
with two screws (3.1),
two spring washers
(3.2), and two plain
washers (3.3)
• Screw (3.4) and plain
washer
(3.5)
for
mounting to cast iron
yoke
• Two
U-bolts
(3.7),
each with two nuts
(3.8),
two
spring
washers
(3.9),
and
two
plain
washers
(3.10) for mounting to
columnar yoke
Before installing check to ensure that the specifications in terms of safety
and control applicable to the TZID-C110 will not be exceeded.
Warning
3.4
3.5
3.7
3.10
3.8
3.1 3.2 3.3
3.0
2.1
2.2
2.0
1.0
3.9
Installing and commissioning
6
Installing and commissioning
41/18-77 EN
1. Mount the follower guide to the actuator
2. Assemble the lever (if not yet pre-assembled)
• Fasten the follower guide (1)
and the clamp plates (2) with
screws (3) to the spindle of the
actuator;
hand-tighten
the
screws.
• Slip the spring (2) onto the bolt
with the follower pin (1).
• Slip the plastic washer (3) onto
the bolt and compress the
spring with it.
• Insert
the
bolt
with
com-
pressed spring into the oblong
hole in the lever (4) and fasten it
in the desired position using the
plain washer (5) and nut (6) at
the lever; the scale on the lever
indicates the link point for the
stroke range.
• Slip the plain washer (8) onto
the screw (7), insert the screw
into the lever and counter with
the nut (9).
3
2
1
1
2
3
4
5
6
9
8
7
Installing and commissioning
41/18-77 EN
Installing and commissioning
7
3. Mount the lever and the mounting plate to the TZID-C110 positioner
• Attach the lever (1) to the feedback shaft (2) at the rear of TZID-C110 (can only be
mounted in one position due to the flat on the side of the feedback shaft).
• Check whether the lever travels within the operating range (between the arrows) by
observing the arrow marks (3).
• Hand-tighten the counter nut (4) at the lever.
• Hold the preassembled TZID-C110 with the angle bracket (5) still loose in such a
way against the actuator that the follower pin on the lever introduces into the follower
guide, in order to determine the bore holes of the TZID-C110 to be used for the
angle bracket.
• Fasten the angle bracket (5) with screws (6), spring washers (7), and plain washers
(8) to the corresponding bore holes in the TZID-C110 case; if possible, tighten the
screws evenly to ensure linearity during operation. Align the angle bracket in the
oblong hole to achieve a symmetrical operating range (between the arrow marks
(3)).
1
2
3
4
5
6
8
7
all-guides
com
Installing and commissioning
8
Installing and commissioning
41/18-77 EN
4.a Mount the positioner to a cast iron yoke
or
4.b Mount the positioner to a columnar yoke
• Fasten the angle bracket (1)
with screw (2), plain washer (3)
to the cast iron yoke (4).
• Hold the angle bracket (1) in the
appropriate position against the
columnar yoke (2).
• Insert the U-bolts (3) from the
inner side of the columnar yoke
through the thru holes in the
angle bracket.
• Slip on the plain washers (4),
spring washers (5), and nuts
(6). Hand- tighten nuts evenly.
2
4
1
3
TZID-C110
TZID-C110
6
1
2
3
5
4
Adjust the height of the TZID-C110 positioner at the cast iron yoke or the colum-
nar yoke until the lever is horizontal (at visual check) at half stroke (+0° sensor
position in mode 1.3). Check for proper mounting (see chapter “Commissioning”
on page 19 for details).
Installing and commissioning
41/18-77 EN
Installing and commissioning
9
5. Adjust the stroke
The scale on the lever indicates the link point for the various stroke ranges.
By shifting the bolt with follower pin in the oblong bore hole of the lever you can change
the stroke range. If the link point is shifted to the inside, the stroke range is increased;
shifting to the outside decreases the range.
The fine adjustment of the link point is done automatically later during Autoadjust.
Decrease stroke range
Increase stroke range
After mounting, check whether the positioner operates within the lever range.
Apply air to the actuator and determine whether the lever travels within the range
marked by the arrows. Check for proper mounting (see chapter “Commissioning”
on page 19 for details).
Installing and commissioning
10
Installing and commissioning
41/18-77 EN
3.1.4 Mounting the positioner to rotary actuators
For mounting to a rotary actuator according to VDI/VDE 3845 the following mounting kit
is available:
Tools required:
Wrench 10 mm/13 mm
Allen key 3 mm
• Namur
feedback
shaft adapter (1.0)
• Four
screws,
M6
(1.1),
four
spring
washers (1.2), and
four plain washers
(1.3) for fastening
the
mounting
bracket (2.0) to the
positioner
• Mounting
bracket
(2.0)
• Four
screws,
M5
(2.1),
four
spring
washers (2.2), and
four plain washers
(2.3) for fastening
the
mounting
bracket to the actua-
tor
1.3
1.0
1.1
2.0
2.1
2.2
2.3
1.2
Installing and commissioning
41/18-77 EN
Installing and commissioning
11
1. Mount the adapter to the positioner
2. Attach the mounting bracket (1) to the positioner
• Determine the mounting position (in parallel
to the actuator or shifted by 90°).
• Determine the direction of rotation of the
actuator (clockwise or counterclockwise).
• Move rotary actuator to its home position.
• On the basis of the mounting position, the
home position, as well as the direction of
rotation it must be determined in which
position the feedback shaft (1) of the posi-
tioner must be pre-adjusted and in which
position the adapter (2) must be placed, to
enable the positioner to travel within the
proper range (the arrow on the rear of the
device must travel within the admissible
range, see Fig. 1 on page 4).
• Pre-adjust the feedback shaft.
• Place the adapter on the feedback shaft in
the appropriate position and fix it by set-
screws (3); ensure that one of the set-
screws is engaged on the side of the
feedback shaft with the flat.
1
2
3
1
M6 Screws
Installing and commissioning
12
Installing and commissioning
41/18-77 EN
3. Attach the TZID-C110 positioner to the actuator
For mounting to control valves 23/24, 23/25 and 23/26 see the instructions in document
42/18-74 EN delivered to you on a CD-ROM.
M5 Screws
After mounting, check whether the positioner operates within the permissible
range. Apply air to the actuator and determine whether the actuator travels within
the range marked by the arrows. Check for proper mounting (see chapter “Com-
missioning” on page 19 for details).
all-guides
com
Installing and commissioning
41/18-77 EN
Installing and commissioning
13
3.2
Pneumatic connection.
3.2.1 Safety instructions
When mounting and commissioning observe the safety regulations of
the pneumatic actuators and the accident prevention rules of the Em-
ployers Liability Insurance Association.
There is danger of injuries caused by the high torque forces produced by
the actuators!
Take suitable measures to ensure that even in case of malfunctions the
positioner’s max. admissible operating pressure of 6 bar (90 psi) is not
exceeded.
Otherwise, the positioner and/or the actuator can be damaged.
Do not exceed the maximum operating pressure of the actuator.
The positioner must be supplied with instrument air that is free of oil, wa-
ter and dust according to DIN/ISO 8573-1, Class 3
Purity
max. particle size:
5 µm
max. particle density:
5 mg/m3
Oil contents
max. concentration:
1 mg/m3
Pressure dew point
Maximum value:
10 K below operating temperature
Before connecting the air pipes, remove dust, splinters and other parti-
cles by blowing them out.
Warning
Caution
Installing and commissioning
14
Installing and commissioning
41/18-77 EN
3.2.2 Making the pneumatic connection
All pneumatic piping connections are located at the right-hand side of the device (see
Fig. 3).
The threaded bores G
1/4 or 1/4-18 NPT, respectively, are provided. The corresponding
screwed pipe connections have to be supplied by the customer. We recommend pipes
with the dimension 6x1 mm for the pneumatic piping.
The amount of supply pressure has to be matched to the working pressure necessary
for the actuation. The values 1.4 and 6 bar are the limit values of the positioner.
The connections have to be arranged, according to their marks, in the following way:
Mark
Connection piping
-
Air supply, pressure 1.4...6 bar
(20...90 psi)
OUT1
Output pressure, to actuator
OUT2
Output pressure, to actuator
(for double-acting actuators)
Filter
OUT 1
OUT 2
NPT ¼
M12x1
G ¼
Pneumatic outputs
Air supply
Filter screw plug
Fig. 3
Pneumatic connections
Installing and commissioning
41/18-77 EN
Installing and commissioning
15
3.2.3 Mounting the splash guard cap
Screw the splash guard cap delivered with your positioner into the appro-
priate hole in the bottom plate of the case, as seen in the illustration below.
Use a wrench to fasten the cap. Do not use a screw driver!
Make sure that the splash guard cap is always present during operation.
Otherwise, protection class IP65 cannot be ensured.
Caution
Fig. 4
Mounting the splash guard cap
Installing and commissioning
16
Installing and commissioning
41/18-77 EN
3.3
Electrical connection
3.3.1 Safety instructions
During the electrical installation observe the common VDE safety regula-
tions and the accident prevention rules of the Employers Liability Insur-
ance Association.
Observe the common standards/safety regulations for the set-up and the
operation of electrical installations.
Observe the additional standards, regulations and guidelines for the set-up
and the operation of explosion-proof installations, if explosion-proof
devices are used.
Warning
Exclusively connect the PROFIBUS PA line to the bus terminals +(11) and
-(12). When connecting a power source for test purposes without establish-
ing a bus communication (e.g. when executing the Autoadjust function), a
supply voltage between 9.0 V and a maximum of 32 V may be applied.
When connecting a device make sure that the electrical limits specified in
chapter 4 "Technical data" are observed.
Do not run bus/signal lines close to power lines. Power lines produce inter-
ference in their near vicinity which may affect the electrical capabilities of
the bus/signal lines.
Caution
Installing and commissioning
41/18-77 EN
Installing and commissioning
17
3.3.2 Overview
For the cable entry into the
case
two
threaded
holes
PG 13.5,
1/2 - 14 NPT
or
M20 x 1.5 are available on the
left side of the case (see Fig.
5). The front hole is equipped
with a cable gland, in the back
a dummy plug is mounted.
The screw terminals inside the case are assigned as follows (see Fig. 6):
1
Not used
2
Service switch for shut-
down module
3
Terminals for the plug-in
module for the shutdown
function
4
Kit for digital position
feedback,
either proximity switches
or 24 V microswitch (first
connector), terminals
designed for wire sizes
up to 1.5mm2
5
Kit for digital position
feedback, either proxim-
ity switches or
24 V microswitch
(second connector), ter-
minals designed for wire
sizes up to 1.5mm2
6
Bus terminals, designed for wire sizes up to 2.5mm2
7
Grounding screw
Cable gland
Dummy plug
Fig. 5
Cable entry
+41 -42
Limit 2
Limit 1
+85-86
+51 -52
+
(11) -
(12)
1
2
4
6
7
5
3
On
Off2
Off1
Fig. 6
Screw terminals
all-guides
com
Installing and commissioning
18
Installing and commissioning
41/18-77 EN
3.3.3 Making the connections
Connecting the bus lines, the shutdown module and the proximity switches or
microswitches:
•
Remove 7-10 mm (1/4 - 3/8") of the cable insulation
•
Insert the wire ends from the left into the appropriate screw terminal and hand-tighten the
screws (access from above)
Connecting the plug-in module:
•
Remove 7-10 mm (1/4 - 3/8") of the cable insulation
•
Insert the wire ends from the top into the corresponding screw terminal and hand-tighten the
screws (access from the side)
Fig. 7
Terminal assignment
(11) (12)
+
-
+85 -86
Basic model
Bus terminals
+41 -42
Limit 2
Limit 1
+51 -52
Limit 1
Limit 2
Kit for digital position feedback
Pepperl & Fuchs proximity switches
Kit for digital position feedback
24 V Microswitch
41 42 43
Limit 2
51 52 53
Limit 1
Grounding screw
Plug-in module for shutdown function
24 V
NC contact
NO contact
Input
NC contact
NO contact
Input
Installing and commissioning
41/18-77 EN
Installing and commissioning
19
3.4
Commissioning
3.4.1 Commissioning procedure
1.
Turn on the air supply to the positioner.
2.
Connect the bus to the bus terminals, with arbitrary polarity.
After the device has started up, the display indicates the position in % and
REMOTE.
3.
Check for proper mounting:
-
Press and hold MODE and ENTER simultaneously.
-
Wait until the countdown has run down from 3 to 0.
-
Release MODE and ENTER. The operating level (mode 1.x) is reached and
indicated.
-
Press and hold MODE.
-
Additionally briefly press
or until mode 1.3 (manual adjustment within the
sensor range) is displayed.
-
Release MODE.
-
Press or to move the actuator to its mechanical limit stops in both directions,
and note the values. The angle of rotation is indicated in degrees.
4.
Return to the remote level.
-
Press and hold MODE and ENTER.
-
Wait until the countdown has run down from 3 to 0.
-
Release MODE and ENTER.
-
The display indicates the position in % and REMOTE.
See Appendix A for an overview of the operation and the parameter settings.
5.
Run fast Autoadjust.
-
Make sure that the remote level is activated.
a) For linear actuators:
-
Press and hold MODE.
-
Wait until the countdown has run down from 5 to 0.
-
Release MODE.
-
Press and hold MODE again until the countdown has run down from 3 to 0.
-
Release MODE.
Autoadjust is started automatically, and the progress is displayed as in P1.1.
Recommended range is
between -28° and +28° for linear actuators
between -57° and +57° for rotary actuators
Minimum angle: 25° (in case of deviations from these values see chapter 3.1)
Installing and commissioning
20
Installing and commissioning
41/18-77 EN
b) For rotary actuators
-
Press and hold ENTER.
-
is displayed.
-
Wait until the display has changed to
-
Release ENTER.
-
Press and hold ENTER again until the countdown has run down from 3 to 0.
-
Release ENTER.
Autoadjust is started automatically, and the progress is displayed as in P1.1.
When Autoadjust has completed successfully, the determined parameters are saved
automatically, and the remote level is activated again.
If any errors should occur during Autoadjust, the respective error code is displayed as in
P1.1. In this case press ENTER to acknowledge. The operating level, mode 1.3
(MAN-SENS) will be activated automatically, then.
3.4.2 Setting the bus address
•
When the positioner is on the remote level, first change over to the operating level by
pressing and holding MODE and ENTER simultaneously until the countdown has
run down from 3 to 0. Release MODE and ENTER. The positioner changes over
to the operating level.
•
Switch the positioner over to the configuration level: Press and hold and simulta-
neously and then additionally briefly press and release ENTER once. Keep
and
pressed until the countdown from 3 to 0 is finished (approx. 3 seconds) and only
then release them. Otherwise, the change-over to the configuration level will fail.
is displayed
•
Press and hold MODE. Additionally press
or until
is displayed
•
Release MODE.
is displayed (factory setting)
conf
mA
% C
°
conf
mA
% C
°
conf
mA
% C
°
conf
mA
% C
°
conf
mA
% C
°
Installing and commissioning
41/18-77 EN
Installing and commissioning
21
•
Press the or button to increment or decrement the bus address.
•
Press and hold ENTER until the countdown has run down from 3 to 0. Then release
ENTER. The new bus address is saved.
•
Press and hold MODE. Additionally press
or until
is displayed. Set the parameter to NV_SAVE by using
or .
•
Press and hold ENTER until the countdown has run down from 3 to 0 to switch the
positioner back to the operating level.
•
To return from the operating level to the remote level, press and hold MODE and
ENTER simultaneously until the countdown has run down from 3.0. Release
MODE and ENTER. The positioner returns to the remote level.
3.4.3 Overview of the operating modes and how to select (from operating level)
Mode 1.1: Control
•
Press and hold MODE.
•
Additionally briefly press
as often as required.
•
is displayed.
•
Release MODE
•
is displayed, control is running.
Mode 1.2: Manual adjustment within the stroke range
•
Press and hold MODE.
•
Additionally briefly press
as often as required.
•
is displayed.
•
Release MODE.
•
is displayed.
•
Press or to adjust the position within the stroke range.
conf
mA
% C
°
conf
mA
% C
°
conf
mA
% C
°
conf
mA
% C
°
conf
mA
% C
°
Installing and commissioning
22
Installing and commissioning
41/18-77 EN
Mode 1.3: Manual adjustment within the sensor range
•
Press and hold MODE.
•
Additionally briefly press
as often as required.
•
is displayed.
•
Release MODE.
•
is displayed.
•
Press or to adjust the position within the sensor range.
3.4.4 Parameter setting example:
"Changing zero position from clockwise to counter-clockwise"
Starting situation: the TZID-C is operating remote-controlled.
1.
Cange over from the remote level to the operating level
-
Press and hold MODE and ENTER simultaneously.
-
Wait until the countdown has run down from 3 to 0.
-
Release MODE and ENTER. Mode 1.1 is reached and indicated.
2.
Change over to the configuration level:
-
Simultaneously press and hold
and .
-
In addition, briefly press ENTER.
-
Wait until countdown from 3 to 0 has run down.
-
Release
and .
-
is displayed.
3.
Change over to parameter group 3._:
-
Simultaneously press and hold MODE and ENTER.
-
In addition 2x briefly press
.
-
is displayed.
conf
mA
% C
°
conf
mA
% C
°
conf
mA
% C
°
conf
mA
% C
°
all-guides
com
Installing and commissioning
41/18-77 EN
Installing and commissioning
23
-
Release MODE and ENTER.
-
is displayed.
4.
Select parameter 3.2 "Zero position”:
-
Press and hold MODE.
-
In addition, 2 x briefly press .
-
is displayed.
-
Release MODE.
5.
Change parameter setting:
-
Briefly press
to select "CTCLOCKW".
6.
Change over to parameter 3.3 "EXIT" and save the new setting:
-
Press and hold MODE.
-
In addition, 1 x briefly press .
-
is displayed.
-
Release MODE.
-
Briefly press
to select "NV_SAVE.
-
Press and hold ENTER until the displayed countdown from 3 to 0 has run down.
The positioner saves the new settings and automatically returns to the operating level.
7.
Return to the remote level.
-
Press and hold MODE and ENTER.
-
Wait until the countdown has run down from 3 to 0 .
-
Release MODE and ENTER.
The display indicates the position in % and REMOTE.
See Appendix A for an overview of the operation and the parameter settings.
conf
mA
% C
°
conf
mA
% C
°
conf
mA
% C
°
Profibus PA Profile for Process Control Devices
Electro Pneumatic Actuator V3.0
Block types
1 AO Function Block, 1 Transducer Block,1 Physical Block
Physical layer
Compliant to the standard IEC 61158-2
Communication speed
31.25 Kbit/second
Operating voltage
Bus-powered: 9.0 - 32.0 volts
Max. withstand voltage
35 V
Current consumption
10.5 mA
Fault current
15 mA (10.5 mA + 4.5 mA)
Name
Physical device tag
TZID-C110
PNO ID number
0x0639
Device ID
0X3200028xyz
Device address
Between 0 and 126, default node address 126
Output
Range
0...6 bar (0...90 psi)
Air capacity
at supply pressure of 1.4 bar (20 psi)
5.0 kg/h = 3.9 Nm3/h = 2.3 scfm
at supply pressure of 6 bar (90 psi)
13 kg/h = 10 Nm3/h = 6.0 scfm
(Booster, for increasing air capacity, on request)
for single or double acting actuators, air is vented from actuator or actuator is blocked in
case of an electrical power failure
Shut-off function
If the setpoint goes below the set value, the positioner immediately moves the actuator to
the closing position. Range: 0...20% of positioning signal.
Travel
Angle of rotation
Used range
25...120 ° (rotary actuators
optionally 270°)
25...60 ° (linear actuators)
Stroke time
Range 0...200 seconds, individually configurable for each
direction
Dead band time limit
Range 0...200 seconds (monitoring parameter for control until the deviation is within the tol-
erance band)
Stroke limiting
Min. and max. limits,
freely configurable within 0...100% of total travel (> 20 %)
Air supply
Instrument air
free of oil, water and dust to DIN/ISO 8573-1
pollution and oil contents according to Class 3
(Purity: max. particle size 5 µm, max. particle density
5mg/m3; Oil contents: max. concentration 1 mg/m3;
Dew point at least 10 °C below operating temperature)
Supply pressure
1.4...6 bar (20...90 psi)
Caution: Do not exceed the max. operating pressure of the actuator!
Air consumption
< 0.03 kg/h (0.08 scfm) (independent of supply pressure)
Transmission data and influences
Direction (output signal or pressure in the actuator)
Increasing:
Increasing signal 0...100 %
Increas. pressure OUT1 to the actuator
Decreasing:
Increasing signal 0...100 %
Decreas. pressure OUT1 to the actuator
Characteristic curve (travel = f signal)
linear, equal percentage 1:25 or 1:50 or 25:1 or 50:1
and freely configurable with 20 reference points
Characteristic deviation
< 0.5%
Tolerance band (sensitivity threshold)
0.3...10%, adjustable
Resolution (A/D conversion)
16,000 steps
Sample rate
20 ms
Influence of ambient temperature
< 0.5% for every 10 °C change in temperature
Influence of vibration
≤ +/-1% up to 10g and 80 Hz
Seismic requirements
Meets requirements of DIN/IEC 68-3-3 Class III for strong and strongest earthquakes
Influence of mounting position
No effect
Meets the following requirements
EMC directive 89/336/CEE as of May 1989
EC directive for the CE conformity marking
Environmental capabilities
Ambient temperature
- 40 to + 85 °C (- 40 to + 185 °F)
for operation, storage and transport
Relative humidity
< 75% (95% for a short time), non-condensing
Case
Material/surface
Aluminum, protection IP 65 (NEMA 4x)
Bottom part of case varnished black, RAL 9005, matt,
Cover white aluminum RAL 9006
Electrical connections
Screw terminals, internal
for bus connection 2.5 mm2
for options 1.5 mm2
Cable entry
2 threads Pg. 13.5, 1/2-14 NPT or M20x1.5
possible cable diameter 6...12 mm
1 with cable gland and 1 with dummy plug
Pneumatic connections
Threads G 1/4 or 1/4-18 NPT
Weight:
1.7 kg
Mounting position:
any orientation allowed
Dimensions:
see dimensional drawings in data sheet 10/18-0.23 EN or manual (CD
version) 42/18-74 EN
ATEX (applied for)
Type:
Intrins. safe equipment
Device class:
II 2G (EEx ia IIC)
Temperature class:
T4, T5, T6
Permissible ambient temperature: T4:-40 °C ≤ Tamb ≤ 85 °C
T5:-40 °C ≤ Tamb ≤ 50 °C
T6:-40 °C ≤ Tamb ≤ 40 °C
Signal current circuit for Profibus PA, only for connection to a certified intrinsically safe
circuit (e.g. FISCO power unit oder barrier) with the following max. values:
FISCO
ia/ib
for group
IIB/IIC
FISCO
ia/ib
for group IIB/IIC
Barrier or power
supply unit
ia/ib
for group IIB/IIC
Vi = 17.5 V
Vi = 17.5 V
Vi = 24 V
Ii = 360 mA
Ii = 360 mA
Ii = 250 mA
Pi = 5.32 W
Pi = 2.52 W
Pi = 1.2 W
rectangular
trapezoidal
linear
all-guides
com
Plug-in module for the shutdown function
In case of a 24 V DC power failure, the positioner can let the valve move to the safe position
by depressurizing the actuator independently of the processor. To achieve this, the I/P mod-
ule power supply is separated by an optocoupler. Both the communication and feedback are
still active, since the positioner is powered via the bus line. The shutdown input is electrically
isolated from the control signal.
Due to the shutdown function no additional solenoid valves are required. It has a safety cer-
tificate from TÜV Rheinland in accordance with AK4. The plug-in module also has an Ex cer-
tificate for use in intrinsically safe current circuits.
Kit for mechanical position indicator
Indicator disk
Cover with transparent dome
Symbol stickers
Extension for the feedback shaft
Kit for digital position feedback with proximity switches *
2 proximity switches for min. and max. position
(position adjustable within range of 0...100%)
Current circuit to DIN 19234
Supply voltage 5...11 V DC
Control current < 1 mA= switching state logical "0"
Control current > 3 mA= switching state logical "1"
(works independently of the software and the electronics of the positioner)
Direction of action (logical state):
Kit for digital position feedback with 24 V microswitches*
Two 24 V DC/AC microswitches for independent position signalling.
Switching points adjustable between 0 and 100 %
Not approved for use in hazardous areas !
* The “digital position feedback“ option is directly actuated by the rotating shaft of the
TZID-C110 positioner and can only be used together with the mechanical position indicator described above.
Slot-type
initiator
Position
< min. > min. < max. > max.
SJ2-SN (NC)
0 1 1 0
SJ2-S1N (NO)
1 0 0 1
Appendix A:Configuration overview
Par.
Display
Function
Parameter setting
Unit
Factory setting
P1._
STANDARD
P1.0
ACTUATOR
Actuator type
LINEAR, ROTARY
-
LINEAR
P1.1
AUTO_ADJ
Autoadjustment
Action
-
-
P1.2
TOL_BAND
Tolerance band
X...Y.00
%
0.30
P1.3
DEADBAND
Deadband
0.10...5.00
%
0.10
P1.4
TEST
Test
Action
-
-
P1.5
ADDRESS
Bus address
1...126
-
126
P1.6
EXIT
Return to operat. level
Action
-
-
P2._
SETPOINT
P2.0
not used
-
P2.1
not used
-
P2.2
CHARACT
Characteristic curve
LINEAR, EP 1:25, 1:50,25:1, 50:1, USERDEF,
-
LINEAR
P2.3
ACTION
Valve action
DIRECT, REVERSE
-
DIRECT
P2.4
SHUT-OFF
Shut-off value
OFF, 0.1...45.0
%
OFF
P2.5
RAMP UP
Setpoint ramp, up
OFF, 0.1...999.9
sec
OFF
P2.6
RAMP DN
Setpoint ramp, down
OFF, 0.1...999.9
sec
OFF
P2.7
EXIT
Return to operat. level
Action
-
-
P3._
ACTUATOR
P3.0
MIN_RGE
Min. of stroke range
0.0...100.0
%
0.0
P3.1
MAX_RGE
Max. of stroke range
0.0...100.0
%
100.0
P3.2
ZERO_POS
Zero position
CLOCKWISE, CTCLOCKWISE
-
CTCLOCKWISE
P3.3
EXIT
Return to operat. level
Action
-
-
P4._ and P.5_
not used
not used
P6._
MAN_ADJ
P6.0
MIN_VR
Min. valve range
0.0...100.0
%
0.0
P6.1
MAX_VR
Max. valve range
0.0...100.0
%
100.0
P6.2
ACTUATOR
Actuator type
LINEAR, ROTARY
-
LINEAR
P6.3
SPRNG_Y2
Spring action (Y2)
CLOCKWISE, CTCLOCKWISE
-
CTCLOCKWISE
P6.4
ADJ_MODE
Autoadjust mode
FULL, STROKE, CTRL_PAR, ZERO_POS, LOCKED
-
FULL
P6.5
EXIT
Return to operat. level
Action
-
-
KP value, up
1.0...100.0
-
5.0
P7.1
KP DN
KP value, down
1.0...100.0
-
5.0
P7.2
TV UP
TV value, up
0...1000
msec
200
P7.3
TV DN
TV value, down
0...1000
msec
200
P7.4
GOPLS UP
Go pulse, up
0...200
msec
0
P7.5
GOPLS DN
Go pulse, down
0...200
msec
0
P7.6
Y-OFS UP
Y offset, up
Y-Min...100.0
%
24.0
P7.7
Y-OFF DN
Y offset, down
Y-Min...100.0
%
24.0
P7.8
not used
not used
not used
-
-
P7.9
TOL_BAND
Tolerance band
X...10.20
%
0.30
P7.10
TEST
Test
Action
-
-
P7.11
EXIT
Return to operat. level
Action
-
-
P8._ , P9._ P.10_
not used
not used
P11._
FS / IP
P11.0
FAIL_POS
Safe position
ACTIVE, INACTIVE
-
INACTIVE
P11.1
FACT_SET
Factory setting
Action
-
-
P11.2
IP_TYP
I/P module type
NO_F_POS, F_SAFE_1, F_SAFE_2, F_FREEZE1, F_FREEEZE_2
-
NO_F_POS
P11.3
EXIT
Return to operat. level
Action
-
-
Par.
Display
Function
Parameter setting
Unit
Factory setting
all-guides
com
(3 ... 0)
(3 ... 0)
I.2
MANUAL
I.I
CTRL_FIX
Remote Level
MODE
+
ENTER
(3...0)
(Local Operation)
I.3
MAN_SENS
Configuration Level
conf
conf
conf
conf
conf
conf
MODE + ENTER ,
conf
PI.
STANDARD
P2.
SETPOINT
P3.
ACTUATOR
P6.
MAN_ADJ
P7.
CTRL_PAR
PII.
FS / IP
PI.0
PI.I
PI.2
PI.3
PI.4
P1.5
P1.6
P2.0 n.u.
P2.I n.u.
P2.2
P2.3
P2.4
P2.5
P2.6
P2.7
P3.0
P3.I
P3.2
P3.3
MODE
P6.0
P6.I
P6.2
P6.3
P6.4
P6.5
P7.0
P7.I
P7.2
P7.3
P7.4
P7.5
P7.6
P7.7
P7.8 n. u.
P7.9
P7.10
P7.I I
P I I.0
P I I.I
P I I.2
P I I.3
Parameter overview
ABB Automation Products GmbH
Schillerstraße 72
32425 Minden
GERMANY
Tel:
+49 571 830-1494
Fax:
+49 571 830-1860
Subject to technical changes.
This technical documentation is protected by copyright. Translating, photocopying and
disseminating it in any form whatsoever - even editings or excerpts thereof - especially as
reprint, photomechanical or electronic reproduction or storage on data processing systems or
networks is not allowed without the permission of the copyright owner and non-compliance will
lead to both civil and criminal prosecution.
Subject to technical changes
Printed in the Fed. Rep. of Germany
41/18-77 EN Rev. 01
Issue 07.02