B+B SmartWorx CANOP Quick Start Manual

Text of the manual

1-888-948-2248 | Europe: +353 91 792444

advantech-bb.com 707 Dayton Road | PO Box 1040 | Ottawa, IL 61350 Phone: 815-433-5100 | Fax: 815-433-5109 www.advantech-bb.com | E-mail: [email protected] Fast and easy on the web: www.advantech-bb.com QUICK START GUIDE Document Number: 710-11206-00_CANOP_1717qsg Recommended Accessories Model MDR-40-12 12 VDC, 3.4 A Power Supply DIN Rail Mount Before you begin, be sure you have the following: CANOP CAN (Control Area Network) Optical Isolator + CANOP (included) + 12 VDC power supply (required, not included)

+ The CANOP creates two new ends to the CAN

network. + Connections are made via terminal blocks. + A 10-30 VDC power supply is required (sold seperately). Terminal Blocks Terminal Block 2000V optical isolation protection + Rugged, 35mm DIN Rail Mount Enclosure + The CAN network must be terminated at both ends according to CAN specifications. + Space is provided on the board on each side, R6 and R8, for a termination resistor. A 120 Ohm resistor is recommended for the termination. NOTE: Networks not properly terminated may have data errors, or miss the data completely. If the CANOP is not at the end of the network, it should not be terminated. Baud Rates 2 + Maximum Baud Rate: 250 kbps + The CANOP is bit-wise enabled, allowing it to automatically adjust for different baud rates. + Bit-Wise Enable only enables the driver on every low bit received. It also disables the driver on the Receive side for the low bit, plus a maximum of 2µ seconds. This prevents data from echoing back from the CANOP, but allows the nodes to respond back. LEDs