Simon EA-K-30 Series Operating Manual
Read Online
Read the Simon EA-K-30 Series Operating Manual online using the built-in PDF viewer.
Text of the manual
Issue: 1.2 / 01.2019
[email protected]
BA EA-K-30/xxx-T(-DA) / EA230-K-30/xxx(-S) EN 1.2
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
Copyright by SIMON PROtec Systems GmbH
Subject to technical changes and errors. All figures are exemplary.
Only valid with the supplementary sheet: “Safety Instructions and Warranty Conditions”!
Operating Manual
Valid for the following article numbers:
EA-K-30/xxx-T(-DA)
•
M2 5315 (DA) 400 mm stroke
•
M2 5316 (DA) 600 mm stroke
•
M2 5317 (DA) 800 mm stroke
•
M2 5318 (DA) 1 000 mm stroke
•
M2 5319 (DA) 1 200 mm stroke
EA230-K-30/xxx
•
M2 5140 300 mm stroke
•
M2 5141 600 mm stroke
•
M2 5142 800 mm stroke
•
M2 5143 1 000 mm stroke
EA230-K-30/xxx-S
•
M2 5144 300 mm stroke
•
M2 5145 600 mm stroke
•
M2 5146 800 mm stroke
•
M2 5147 1 000 mm stroke
For further information please visit
our product website
short.simon-protec.com/eaken
Issue: 1.2 / 01.2019
Table of Contents
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
Page 2
1. General ................................................................................................................................................................4
1.1 Foreword to this manual ....................................................................................................................................4
1.2 Intended use ....................................................................................................................................................4
1.3 EA-K-30 – Product description ...........................................................................................................................4
1.4 EA230-K-30 – Product description ......................................................................................................................4
2. Safety Regulations ...............................................................................................................................................5
2.1 Risk assessment ..............................................................................................................................................5
2.2 Restrictor stay ..................................................................................................................................................5
3. Figures .................................................................................................................................................................5
4. EA-K-30 – Functions ............................................................................................................................................7
4.1 Soft-close range ...............................................................................................................................................7
4.1.1 Speed reduction ........................................................................................................................................7
4.1.2 Current reduction ......................................................................................................................................7
4.2 SIMON LINK ....................................................................................................................................................7
4.3 Configurable ranges ..........................................................................................................................................8
5. EA230-K-30 – Functions ......................................................................................................................................8
5.1 End position cut-off while closing ........................................................................................................................8
5.2 End position cut-off while opening ......................................................................................................................8
5.3 DIP switches ....................................................................................................................................................8
5.4 RESET ............................................................................................................................................................9
5.5 Teach-in run .....................................................................................................................................................9
5.6 Performing a teach-in run ..................................................................................................................................9
5.7 LED displays ..................................................................................................................................................10
6. Mounting ............................................................................................................................................................11
6.1 Mechanical connection ....................................................................................................................................11
6.1.1 Mounting brackets ...................................................................................................................................12
6.1.2 Top bracket K-K50-OK ............................................................................................................................13
6.1.3 Inward opening bracket K-K30-AKI ...........................................................................................................14
6.1.4 Top bracket K-K-OK-SK ...........................................................................................................................15
6.1.5 Inward opening top / bottom hung window, mounting on a blind frame ...........................................................15
6.1.6 Outward opening top / bottom hung window, mounting on a blind frame .........................................................15
6.1.7 Inward opening top / bottom hung window, actuator mounted on the window sash ..........................................16
6.1.8 Inward opening bottom hung window, actuator K-K30-FLEX mounted on the window sash .............................16
6.1.9 Rotary window ........................................................................................................................................17
6.1.10 Calculating forces/stroke ........................................................................................................................18
6.1.11 Permissible pushing force on the chain ....................................................................................................18
6.2 EA-K-30 Electrical connection ..........................................................................................................................19
6.2.1 Supply ...................................................................................................................................................19
6.2.2 Supply / connection cable .......................................................................................................................19
6.2.3 Feedback signal – “F” contact ..................................................................................................................20
6.2.4 Feedback signal – dry contact .................................................................................................................20
6.2.5 Feedback signal – tandem port ................................................................................................................20
6.2.6 Single connection – dry contact ................................................................................................................20
6.2.7 Single connection – “F” contact ................................................................................................................20
Issue: 1.2 / 01.2019
[email protected]
Table of Contents
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
Page 3
6.2.8 DUO operation / parallel connection ..........................................................................................................21
6.3 EA230-K-30 Electrical connection .....................................................................................................................22
6.4 Single connection – standard variante (EA230-K-30 / xxx) ....................................................................................22
6.4.1 Parallel connection (EA230-K-30 / xxx) ......................................................................................................23
6.4.2 Synchronous connection (EA230-K-30 / xxx-S) ...........................................................................................23
7. EA-K-30 – Technical Data ..................................................................................................................................24
8. EA230-K-30 – Technical Data ............................................................................................................................26
9. Commissioning ...................................................................................................................................................27
9.1 EA230-K-30 ...................................................................................................................................................27
10. Troubleshooting ...............................................................................................................................................27
10.1 EA-K-30 .......................................................................................................................................................27
10.2 EA230-K-30 .................................................................................................................................................27
11. Annex ...............................................................................................................................................................28
11.1 Care and Maintenance ..................................................................................................................................28
11.2 General business and delivery terms ..............................................................................................................28
11.3 Company Addresses .....................................................................................................................................28
11.3.1 System manufacturer ............................................................................................................................28
11.3.2 Germany ..............................................................................................................................................28
11.3.3 Switzerland ..........................................................................................................................................28
11.3.4 Hungary ...............................................................................................................................................28
12. Manufacturer's declaration ...............................................................................................................................28
13. EC manufacturer’s declaration (distributor) ......................................................................................................28
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
[email protected]
Issue: 1.2 / 01.2019
Page 4
Operating Manual
1. General
1.1 Foreword to this manual
This manual is intended for professional operation, installation
and maintenance by trained, knowledgeable and qualified
personnel (such as mechatronics engineer or electrician) and /
or qualified personnel who know how to install electrical
equipment.
Read this operating manual carefully and pay particular
attention to the hazard warnings. Store this operating manual
for future reference / maintenance. Please pay close attention
to the terminal assignment, the minimum and maximum
performance data (see “Technical Data”) and the installation
instructions. Incorrect use or improper operation / mounting
may cause loss of system functionality and damage to
property and / or people.
The following symbols can be found in this manual:
Operating procedures are marked this way.
Consequences are presented this way.
•
Buttons or switches to be pressed / activated are shown
in bold.
•
“Indicators” are placed in quotation marks.
1.2 Intended use
Opening units (actuators) are used for the power-operated
opening and closing of building covers that are installed in
walls or in roofs and are used for the ventilation of rooms or
for the removal of fire smoke.
See chapter 2.1 “Risk assessment” on page 5.
1.3 EA-K-30 – Product description
The EA-K-30 / xxx-T(-DA) is an an electromotive chain
actuator that can be used in accordance with Chapter 1.2 of
this operating manual.
The technical features include:
•
soft start
•
intelligent, microprocessor-controlled overload cut-off
•
low noise emission
•
soft-close range
•
configurable stroke and force
•
double-sided connection option (EA-K-30 / xxx-T-DA) for
the supply cable (with connector)
•
DUO operation of two actuators1 with a connection cable,
the power supply is looped through from one actuator to
the other
1.4 EA230-K-30 – Product description
The EA230-K-30 / xxx(-S) is an electromotive chain actuator
that can be used in accordance with Chapter 1.2 of this
operating manual.
The technical features include:
•
soft start
•
low noise emission
•
soft - close
•
electronic zero point reset by means of a teach-in run in
the “CLOSED” direction
•
stroke programming
•
synchro operation of up to eight EA230-K-30 / xxx-S
actuators
INFORMATION
An information text gives you additional hints!
ATTENTION
This warning notice alerts you to potential hazards that
may impact the product!
DANGER
This warning notice alerts you to potential hazards to your
life or health!
ENVIRONMENT NOTICE
This notice alerts you to potential environmental hazards!
1. A minimum of one actuator is required with a double-sided
connection – EA-K-30/xxx-DA.
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
Page 5
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
Issue: 1.2 / 01.2019
[email protected]
2. Safety Regulations
See supplementary sheet “Safety
Instructions
and
Warranty Conditions”!
2.1 Risk assessment
2.2 Restrictor stay
3. Figures
Figure 1: EA-K-30/xxx-T(-DA) chain actuator
Figure 2: EA230-K-30/xxx(-S) chain actuator
INFORMATION
Perform a risk assessment according to the application
(e.g. the mounted system).
Information can be found in the guidance sheet KB.01
“Power-operated windows” issued by the VFF (window,
door and facade manufacturers)
www.eurowindoor.eu/news-and-proceeding/
position-papers-and-publications/
ATTENTION
A restrictor stay with an adequate stroke must be installed
in bottom hung wings.
It is important to ensure that the fastening of the actuator
on the window or wing frame is designed to be permanent
and suitable for the actuator force specified on the type
plate.
46VWURNHPP / 56VWURNHPP / 66 VWURNHPP/ 76VWURNHPPVWURNHPP
35
43,6
37
183,7
Connection
EA-K-30/xxx-T & EA-K-30/xxx-T-DA
Gear side
Supply cable / USB-300
Optional connection
Supply cable, only EA-K-30/xxx-T-DA
Chain side
37
43,6
234,3
468VWURNHPP/624VWURNHPP/727VWURNHPP/824VWURNHPP
35
DIP switches &
LED display
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
[email protected]
Issue: 1.2 / 01.2019
Page 6
Figure 3: Top bracket K-K50-OK
Figure 4: Top bracket K-K-OK-SK
Figure 5: Inward opening bracket K-K30-AKI
Figure 6: Lower bracket K-K30-A
Figure 7: Lower bracket K-K30-K
Figure 8: Lower bracket – K-K30-FLEX
C
D
E
F
C
D
E
F
EA-K-30 – Functions
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
Page 7
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
Issue: 1.2 / 01.2019
[email protected]
4. EA-K-30 – Functions
4.1 Soft-close range
4.1.1 Speed reduction
The actuator has a factory-activated speed reduction
function, the last 75 mm before reaching the “CLOSED” end
position (see Table 1: “Electrical properties” on page 24 and
Figure 10: “Configurable ranges” on page 8).
4.1.2 Current reduction
After reaching the last 75 mm before end position "CLOSED",
the soft-close current becomes active, 0.3 A by default. This
value can be increased to 1.0 A via SIMON LINK (when the
speed reduction function is deactivated).
4.2 SIMON LINK
The actuator has a configuration interface (gear side) on
which the following functions can be performed via SIMON
LINK:
•
The stroke can be electronically limited from 100 mm on.
•
Forces can be set in the “OPEN” and “CLOSED”
direction.
•
The soft - close current can be adjusted.
•
The speed reduction before the “CLOSED” end position
for the soft - close range can be set (see Figure 10:
“Configurable ranges” on page 8).
•
The switching behaviour of the dry contact can be set.
•
A detailed status message from the actuator and data
logger can be read.
Figure 9: Configuration interface for SIMON LINK
ATTENTION
In order to avoid damage to the window and actuator or
injuries to individuals, the cut-off current limit is
automatically reduced to 0.3 A when the speed reduction
function is activated; this corresponds to a force of
approx. 150 N. The cut-off current limit can be increased
to a maximum of 0.5 A (300 N) via SIMON LINK when the
speed reduction function is activated.
INFORMATION
You need a service cable (USB-300)
and the associated software (from
version 2.0.0) for configuration of the
actuator via SIMON LINK.
For more information visit
short.simon-protec.com/slen
ATTENTION
The cut-off of the actuator in the configuration is provided
by the USB-300 cable.
There must be no external power supply at this point in
time (EA-K-30/xxx-T-DA on the chain side).
gear side
connector for USB-300 cable
EA230-K-30 – Functions
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
[email protected]
Issue: 1.2 / 01.2019
Page 8
4.3 Configurable ranges
Soft-close range: moves with the electronic zero point, the soft-close current ISC and the speed reduction can be configured via
SIMON LINK.
Reset range: the electronic zero point is reset when switching off via load in direction of the “CLOSED” driving direction within the
first 30 mm before the “CLOSED” end position.
Stroke: electronic stroke limitation depending on programming.
Figure 10: Configurable ranges
5. EA230-K-30 – Functions
5.1 End position cut-off while closing
The end position cut-off while closing occurs automatically
(load depending) and is not programmable. The electronic
switches off the actuator, when reaching a threshold value, if,
for example, the window is completely closed and moved into
the gaskets.
After the window is closed each time or the cut-off current has
been exceeded, the chain is extended slightly again to protect
the gaskets and the window.
5.2 End position cut-off while opening
The cut-off in the OPEN end position occurs automatically
and can be set with the DIP switches 1-2.
A teach-in run must be performed after setting the DIP
switches (three switch combinations for the STROKE setting).
5.3 DIP switches
(See Figure 2: “EA230-K-30/xxx(-S) chain actuator” on page 5.)
mechanical ]HUR
electronical ]HUR
mechanical “max”
30 mm
75 mm
reset
range
soft-closerange
electronical stroke
50 mm
stopping time 3 s
stopping time 3 s
50 mm
before max. electr. stroke
stopping time 0 s
ATTENTION
The actuator must be de-energised before the DIP
switches can be changed. After setting the DIP switches, a
pause of approx. 5 seconds must be observed before the
drive can be supplied with power again.
DIP
switch 1
DIP
switch 2
Function
ON
ON
Maximum stroke
(delivery condition)
OFF
ON
STROKE reduced by 100 mm
ON
OFF
STROKE reduced by 200 mm
OFF
OFF
RESET
(See chapter 5.4 “RESET” on
page 9)
EA230-K-30 – Functions
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
Page 9
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
Issue: 1.2 / 01.2019
[email protected]
5.4 RESET
If necessary, release the connection between the chain
end piece and the top bracket.
Drive the actuator in the OPEN direction and extend the
chain by approx. 10 cm.
Disconnect the actuator from the power supply.
Check the communication cables in the case of actuators
connected in parallel (red / white).
Set both of the DIP switches 1 and 2 to OFF.
Wait for five seconds.
Drive the actuator in the OPEN direction.
The RESET procedure is performed, the orange LED
lights up continuously during this procedure. The
actuator immediately moves in the CLOSED direction
up to the end position, then approx. 5 cm back in
OPEN direction.
The orange LED flashes continuously after performing
the RESET process correctly.
Disconnect the actuator from the power supply again.
Set the DIP switches 1 and 2 to the desired setting.
Wait for five seconds.
Connect the chain end piece to the top bracket again.
Let the actuator perform a teach-in run
(see chapter 5.6 “Performing a teach-in run” on page 9).
5.5 Teach-in run
The actuators detect and store the distance between sash
and frame fully automatically during operation (when the
window is fully closed). The dimensional difference between
wing and frame is called overhang.
This teach-in takes place when the actuator fully closes the
window for the first time after a RESET.
5.6 Performing a teach-in run
Open the actuator slightly and then drive it in the
CLOSED direction and let it cut off in the end position.
If the teach-in process has worked correctly, the
actuator signals this by the flashing of the orange LED
(next to the DIP switches) for approx. 3 seconds.
If the orange LED does not flash as described, a RESET
must initially be performed (see chapter 5.4 “RESET“).
ATTENTION
The chain end piece must not be connected to the bracket
when performing the RESET process.
ATTENTION
The communication cables of the actuators must be
connected to each other during the RESET process in
synchronous mode (red with red and white with white).
ATTENTION
After RESET, e.g. after a stroke setting via the DIP
switches or after installation, you must perform a teach-in
run.
EA230-K-30 – Functions
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
[email protected]
Issue: 1.2 / 01.2019
Page 10
5.7 LED displays
The EA230-K-30 has three status LEDs (see Figure 2: “EA230-K-30/xxx(-S) chain actuator” on page 5) with the following
meanings.
Red LED
Number
of
flashes
Type of error
Possible solution
1
Overload cut-off
•
Check the drives for correct installation
(mechanical / electrical);
•
Is the force of the installed actuators adequate.
2
Communication error (Synchro)
•
Perhaps there are actuators connected that do not have a
common RESET.
•
Check the red / white connection cable;
•
Perform a RESET procedure for the interconnected
actuators.
3
—
—
4
Inconsistent DIP switch settings (Synchro)
•
The DIP switch settings of the interconnected actuators do
not match.
•
Check and correct the DIP switch settings.
5
Error during the RESET procedure
•
Repeat the RESET procedure.
6
Cabling error (Synchro)
•
The power input of the the interconnected actuators does
not match.
•
Check and correct the connection of the actuators.
7
Addressing error (Synchro)
•
The assignment of the internal addresses of interconnected
actuators has failed.
•
Perform a RESET procedure.
8
Power supply error
•
The supply voltage is not within the permissible range or is
not stable.
•
Check the electrical connection;
•
Check the supply voltage.
9
Chain alignment error (Synchro)
•
The chain position (STROKE) of the interconnected
actuators is not within the permissible range
•
Perform a RESET procedure.
10
Memory error (Synchro)
•
The storage process in the internal memory was not
successful.
•
Repeat the RESET procedure.
11
Connection error
•
A RESET procedure is performed at the same time in the
case of several non-synchronous actuators.
•
Perform the RESET procedures individually.
Green LED
LED status
Meaning
Continuously
lighting
The voltage supply to the actuator is correct.
The actuator is closed correctly and the storage of the STROKES has been performed successfully.
Flashing
The voltage supply to the actuator is correct.
The set STROKE has been reached. The number of flashes indicates the internal address to which the actuator
has been assigned during the RESET procedure in the case of synchronous actuators.
Mounting — Mechanical connection
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
Page 11
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
Issue: 1.2 / 01.2019
[email protected]
6. Mounting
See supplementary sheet “Safety
Instructions
and
Warranty Conditions”!
6.1 Mechanical connection
— Mechanical connection
You need different combinations of brackets for mounting the
actuator depending on the mounting position and the shape
of the window or building cover; the brackets (see page 6),
with the exception of the top bracket K-K50-OK, must be
ordered separately.
In order to ensure that the window is sealed securely,
check that the chain of the actuator is extended slightly
before mounting the actuator. However, the chain should
not extend more than 30 mm after mounting the actuator
otherwise the electronic zero point reset can no longer be
guaranteed (see Figure 10: “Configurable ranges” on
page 8).
Orange LED
LED status
Meaning
Continuously
lighting
duration < 0.5 sec.
Write process in the internal memory of the actuator is running.
Continuously
lighting
RESET procedure is running.
Continuously
lighting for 3 sec.
Teach-in procedure of the teach-in run has been completed correctly.
Flashing
RESET procedure completed correctly. The number of flashes indicates the internal address to which the
actuator has been assigned during the RESET procedure in the case of synchronous actuators.
INFORMATION
Further information on mounting can be found in the
guidance sheet KB.01 “Power-operated windows” issued
by the VFF (window, door and facade manufacturers)
www.eurowindoor.eu/news-and-proceeding/
position-papers-and-publications/
DANGER
The system must be mounted by specialist
personnel (qualified electricians) only. All
relevant national safety regulations and
directives apply to mounting, installation and
commissioning.
Improper mounting can create a risk of
electric shock. All safety regulations must be
complied with. Follow the current assembly
instructions. Incorrect mounting can lead to
serious injury.
ATTENTION
Please note the static properties of the window frame
when mounting the actuator.
Use suitable fixings depending on the window material on
which the actuator is to be mounted. (The fixings are not
included in the delivery!)
Mounting — Mechanical connection
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
[email protected]
Issue: 1.2 / 01.2019
Page 12
6.1.1 Mounting brackets
Determine the mounting position of the brackets so that the chain of the actuator will not collide with the (window / wing) frame
in any opening position of the window and the position of the chain is in the centre of the window; centre line markings are
provided on the K-K-50-OK for this purpose (see Figure 14 on page 13). In parallel / duo operation the actuators should be
positioned in such a way that the chains are located on 1/4 of the edges (left/right) of the window sash.
Secure the brackets with screws that are suitable for the respective window or the desired surface (screws / fixings are not
included in the delivery), see Figures page 15 and page 16.
Insert the actuator in the support brackets and secure it with the two self-locking screws.
Figure 11: K-K30-K
Figure 12: K-K30-A
Figure 13: K-K30-FLEX
Mounting — Mechanical connection
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
Page 13
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
Issue: 1.2 / 01.2019
[email protected]
6.1.2 Top bracket K-K50-OK
Figure 14
Extend the chain approx. 10 cm and connect the chain end piece to the K-K50-OK (1). To do this, insert the fixing bolt from
the side with the logo (2) and secure it on the other side with the retaining ring (3).
Figure 15
Figure 16: Incorrect positioning of the K-K50-OK
ATTENTION
The top bracket must always be aligned in such a way
that the SIMON logo on the bracket is on the same side of
the chain as the SIMON logo on the chain exit.
INFORMATION
Centre line marking (see Figure 14) for aligning the
bracket on the middle of the wing (single variant) or at a
distance of 1/4 away from the edge (left / right) in parallel
operation.
SIMON
logos
centre line
marking
2
1
3
4
ATTENTION
The top bracket K-K50-OK must not be mounted turned,
otherwise its function can no longer be fully guaranteed
(see Figure 16: “Incorrect positioning of the K-K50-OK”).
INFORMATION
With the help of the alternative upper bracket K-K-OK-SK,
turned mounting with lateral force flow is possible (see
6.1.4 “Top bracket K-K-OK-SK” on page 15).
So nicht!
Not in this way!
Mounting — Mechanical connection
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
[email protected]
Issue: 1.2 / 01.2019
Page 14
6.1.3 Inward opening bracket K-K30-AKI
Figure 17
Extend the chain approx. 10 cm and connect the chain end piece to the K-K30-AKI (1). To do this, insert the fixing bolt from
the side with the logo (2) and secure it on the other side with the retaining ring (3).
Figure 18
ATTENTION
In the case of a compression force application (e.g. top
hung window),the mounting bracket must always be
aligned so that the SIMON logo of the bracket is on the
same side as the SIMON logo of the chain outlet.
INFORMATION
Window heights in a ratio of approx. 2 : 1 to the actuator
stroke (opening width) are possible for the inner hole
pairs (for the fixing bolt) depending on the quality and
shape of the window sash. This ratio changes to approx.
3 : 2 for the outer hole pair.
These are only approximate guideline values and must be
clarified before any mounting in case of doubt!
SIMON logos
1
2
3
4
Mounting — Mechanical connection
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
Page 15
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
Issue: 1.2 / 01.2019
[email protected]
6.1.4 Top bracket K-K-OK-SK
Figure 19
6.1.5 Inward opening top / bottom hung window, mounting on a blind frame
Figure 20: Inward opening bottom hung window
6.1.6 Outward opening top / bottom hung window, mounting on a blind frame
Figure 21: Outward opening top hung window
ATTENTION
The top bracket must always be aligned in such a way
that the SIMON logo on the bracket is on the same side of
the chain as the SIMON logo on the chain exit in the case
of top hung wing applications.
Note the resulting alignment of the actuator (see
Figure 19). The combination of actuator and bracket must
only be used in this alignment to one another. Any other
alignment will lead to the loss of the function of the
bracket.
min.
min. 39.5 mm*
plus pivoting range
depending on the wing height
min. 70.5 mm*
min.
61.8 mm
16.8
Mounting — Mechanical connection
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
[email protected]
Issue: 1.2 / 01.2019
Page 16
6.1.7 Inward opening top / bottom hung window, actuator mounted on the window sash
Figure 22: Inward opening bottom hung window, at the window sash
6.1.8 Inward opening bottom hung window, actuator K-K30-FLEX mounted on the window sash
Figure 23
min.
min.
ATTENTION
Position the actuator so that the chain is as far as
possible away from the window sash in order to avoid
damage to the window and the chain while opening it.
6
min. mm
Mounting — Mechanical connection
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
Page 17
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
Issue: 1.2 / 01.2019
[email protected]
6.1.9 Rotary window
Figure 24: Mounted on a blind frame
Figure 25: Mounted on the window sash
ATTENTION
The chain actuator EA-K-30 / EA230-K-30 must only be
mounted upright (with the actuator side at the top) on
DIN right windows!
Mounting — Mechanical connection
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
[email protected]
Issue: 1.2 / 01.2019
Page 18
Figure 26: K-K30-FLEX mounted on the window sash
6.1.10 Calculating forces/stroke
This calculation is only valid for wall windows mounted
vertically. A detailed calculation must be made for all other
mounting positions, which we will be pleased to assist you
with.
F := the force of the actuator [N]
S := the stroke of the actuator [mm]
H := the height of the window sash [mm]
W := the weight of the window sash [kg]
Required actuator force for the specified stroke:
F = (W / 2) x (S / H) x 10
= (W x S x 5) / H
Maximum possible actuator stroke for the specified force:
S = (2 x F x H) / (W x 10)
= (F x H) / (W x 5)
Figure 27
6.1.11 Permissible pushing force on the chain
Figure 28
height of the frame – H
weight of the
frame – W
force F
stroke S
bottom hung window
height of the frame – H
weight of the
frame – W
force F
stroke S
top hung window
250
200
150
100
50
force[N]
500
600
750
1000
0
stroke [mm]
700
800
700
900
static push force
dynamic push force
(eg. wind load)
650
850
950
300
550
400
450
1100
1050
1200
1150
pull force
Mounting — EA-K-30 Electrical connection
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
Page 19
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
Issue: 1.2 / 01.2019
[email protected]
6.2 EA-K-30 Electrical connection
— EA-K-30 Electrical connection
6.2.1 Supply
The power supply must be designed for the actuator. The
voltage and current must correspond with the information on
the type plate. The supply cabling must be checked before
the initial commissioning, the cable cross section in particular
must be taken into account. The valid regulations regarding
minimum values for the cable sizing must be observed!
Sample calculation (this is only an approximate value and
does not replace an exact calculation):
The power is supplied to the EA-K-30/xxx-T on the gear side.
The power can also be supplied via the chain side on the
EA-K-30/xxx-T-DA (double-sided connection). The supply
voltage is relayed internally to the opposite connection point,
this can then be used to connect another actuator (see
chapter 6.2.8 “DUO operation / parallel connection” on
page 21).
6.2.2 Supply / connection cable
It is possible to supply power to the second actuator directly
through the first actuator (DA variant) in tandem / duo
operation. The supply cable can therefore be changed into a
connection cable.
Cut the second supply cable to the desired length (plus
approx. 3 cm).
Strip the cable over a length of 18 mm and remove 4 mm
of insulation from the 5 cores.
Screw the 5 cores into the connector and secure the
cable with a cable binder (e.g. 100 x 2.5) as traction
relief.
black
yellow
red
blue
brown
ATTENTION
Make sure that the loops of the supply cable are
adequately sized on moving parts, taking account of the
bending radii, in order to prevent the pinching or tearing of
the supply cable.
DANGER
Connect to the power supply (24 V DC) only after checking
the entire system.
INFORMATION
We recommend performing a trial run with a suitable
mobile power supply (incl. a control device, not just a
battery). This means that it is quick and easy to respond to
malfunctions.
ATTENTION
Do not earth the electrical connection.
The actuator must only be operated with a 24 V DC safety
extra-low voltage.
Unused cores must be insulated.
+
+
24 V
INFORMATION
Size information for actuator cable (empirical formula):
Cable cross section [mm²] = single cable length [m]
x number of actuators
x current consumption
per actuator [A]
/ 73.
The DIN VDE 0100 and DIN VDE 0298 regulations
continue to apply.
Mounting — EA-K-30 Electrical connection
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
[email protected]
Issue: 1.2 / 01.2019
Page 20
Place the green connector and the cable binder in the
upper shell of the connector housing and screw the top
shell to the bottom shell.
6.2.3 Feedback signal – “F” contact
It is possible to create a classic “F” contact via the dry contact
by connecting the yellow core (NO2) to the blue (S) core (see
chapter 6.2.7 “Single connection – “F” contact” on page 20).
The alarm triggering of the contact must therefore be
activated in the “OPEN” and “CLOSED” end position via
SIMON LINK.
6.2.4 Feedback signal – dry contact
The normally open contact (NO1, NO2) is activated in the
CLOSED driving direction when the actuator is cut off in the
“CLOSED” end position, the message is stroke-dependent
and can be evaluated as a “CLOSED message”.
Other switching settings, such as in “OPEN” end position, can
be set via SIMON LINK.
6.2.5 Feedback signal – tandem port
6.2.6 Single connection – dry contact
Connect the cables according to the connection plan.
6.2.7 Single connection – “F” contact
Connect the cables according to the connection plan.
INFORMATION
The output of the dry contact occurs only on the gear side
of the actuator (see Figure 9: “Configuration interface for
SIMON LINK” on page 7).
ATTENTION
Only a cut-off signal (e.g. overload cut-off) is switched over
to the actuator connected in parallel. Monitoring of the
cables or function of the actuators connected in parallel
does not take place and therefore also does not lead to the
cut-off of the actuators connected in parallel.
ATTENTION
When not in use, the red wire (T) must be electrically
insulated. The red core must only be connected to the red
core of an actuator connected in parallel.
ATTENTION
When not in use, the red wire (T) must be electrically
insulated. The red core must only be connected to the red
core of an actuator connected in parallel.
The “F” contact (black) must not be earthed or clamped in
parallel!
volt-free contact
(max. 28 V / 1.0 A)
24V DC
T
NO1
S
OPEN: S = +
O = -
CLOSE: umpolen
actuator
NO2
O
tandem-port
(electr. insulate)
blue
brown
black
yellow
red
“F”-contact
(max. 1.0 A)
24V DC
blue
T
NO1
S
OPEN: S = +
O = -
CLOSE: pole change
actuator
brown
NO2
O
black
yellow
red
tandem-port
(electr. insulate)
Mounting — EA-K-30 Electrical connection
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
Page 21
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
Issue: 1.2 / 01.2019
[email protected]
6.2.8 DUO operation / parallel connection
A maximum of 2 actuators can be operated in parallel in DUO operation (via a connection cable) with the associated tandem.
A maximum of 4 actuators can be operated in parallel with the associated tandem (e.g. on large wings).
If an actuator stops due to overloading, the actuator connected in parallel is also stopped after a predetermined run-on time (see
Table 1: “Electrical properties” on page 24 and Figure 10: “Configurable ranges” on page 8).
DUO operation: Connect the cables according to the connection plan.
blue
T
NO1
S
1. actuator (DA)
brown
NO2
O
black
yellow
red
blue
T
NO1
S
2. actuator
brown
NO2
O
red
O
S
T
blue
brown
red
connected
internally
connection cable
black
yellow
black
yellow
24V DC
OPEN: S = +
O = -
CLOSE: pole change
volt-free contact
(max. 28 V / 1.0 A)
tandem-port
(electr. insulate)
EA-K-30/xxx-T
EA-K-30/xxx-T-DA
connection cable
power connection cable
Parallel connection: Connect the cables according to the connection plan.
24V DC
T
NO1
S
OPEN: S = +
O = -
CLOSE: pole change
1. actuator
NO2
O
volt-free contact
(max. 28 V / 1.0 A)
T
NO1
S
2. actuator
NO2
O
volt-free contact
(max. 28 V / 1.0 A)
blue
brown
black
yellow
red
blue
brown
black
yellow
red
up to
4 actuators
at all
ATTENTION
The actuators run at the same time, the power supply and the cable dimensions must be adapted to the total current of the
system.
ATTENTION
Only connect 2 actuators to each other. Maximum cable length of 10 m between the actuators.
ATTENTION
Only connect 4 actuators in parallel to each other. Maximum cable length of 10 m between two actuators.
Mounting — EA230-K-30 Electrical connection
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
[email protected]
Issue: 1.2 / 01.2019
Page 22
6.3 EA230-K-30 Electrical connection
— EA230-K-30 Electrical connection
6.4 Single connection – standard variante
(EA230-K-30 / xxx)
Connect the cables according to the connection plan.
230 V AC
blue
LZ
N
OPEN
black
factory
provided
actuator
brown
LA
CLOSE
N
L
0
DANGER
Please note
• The VDE 0833 standard for hazard alert systems,
• The VDE 100 standard for electrical systems,
• The local fire department regulations,
• The energy supply company regulations for the mains
connection,
• And the DGUV V3 / V3DA / V4 regulations and the
workplace regulation ASR A 1.6.
All the relevant national safety regulations and directives
apply when installing, commissioning and putting the
actuator into operation outside the country of manufacture
(Germany).
DANGER
It is important to observe the five safety rules
in accordance with EN 50110-1 or DIN VDE
0105-100.
1. Disconnect completely!
2. Secure against reconnection!
3. Verify that the installation is dead!
4. Carry out earthing and short circuiting!
5. Provide protection from adjacent live
parts!
ATTENTION
Make sure that the loops of the supply cable are
adequately sized on moving parts, taking account of the
bending radii, in order to prevent the pinching or tearing of
the supply cable.
ATTENTION
Never supply 230 V AC to LA (OPEN) and LZ (CLOSE) at
the same time and observe the prescribed pause time of
300 ms for the switchover. Any infringement will lead to
the destruction of the actuator.
Mounting — EA230-K-30 Electrical connection
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
Page 23
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
Issue: 1.2 / 01.2019
[email protected]
6.4.1 Parallel connection (EA230-K-30 / xxx)
Connect the cables according to the connection plan.
230 V AC
N
1. actuator
N
8. actuator
OPEN
CLOSE
N
L
LZ
LA
LZ
LA
0
brown
blue
black
max. 8 actuators in parallel
behind a switching element
brown
black
blue
factory
provided
6.4.2 Synchronous connection (EA230-K-30 / xxx-S)
Connect the cables according to the connection plan.
230 V AC
N
1. actuator
2. actuator
OPEN
CLOSE
N
L
LZ
LA
0
C1 C2
N
LZ
LA
C1 C2
blue
brown
red
white
black
max. 8 actuators in parallel
behind a switching element
factory
provided
blue
brown
red
white
black
ATTENTION
Connect a maximum of 8 actuators in parallel to a switching element.
ATTENTION
Connect a maximum of 8 actuators in parallel to a switching element.
EA-K-30 – Technical Data
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
[email protected]
Issue: 1.2 / 01.2019
Page 24
7. EA-K-30 – Technical Data
Table 1: Electrical properties
Actuator type/version
EA-K-30
Rated voltage
Permissible rated voltage range
Ripple of the rated voltage Vpp
Undervoltage detection
Nominal current1
1.
Maximum current consumption at nominal load
Maximum starting current in
“OPEN” and “CLOSED”
direction
Maximum cut-off current in
“OPEN” and “CLOSED”
direction, after start-up2
2.
Can be configured via SIMON LINK.
soft - close current3
3.
Soft - close range: last 75 mm before reaching the “CLOSED” end
position, soft - close current can be configured via SIMON LINK – current
range: 0.3 A – 1,0 A; when the speed reduction function is activated
0.3 A – 0.5 A.
Current consumption after cut-
off (closed current)
Cut-off via
Maximum permissible number
of actuator units connected in
parallel in tandem operation4
4.
With a common cut-off function (tandem function).
Cable length between two
actuators in tandem operation
Tandem run-on time5
5.
The tandem run-on time indicates how long the actuator connected in
parallel continues to run after cutting off the triggering actuator.
The run-on time is 3 s in each case 50 mm before reaching the end
position and 0 s in the range between (see Figure 10: “Configurable
ranges” on page 8).
Pulse time6
6.
The pulse time indicates how long the internal or external overload cut-
off provides the cut-off signal at the output.
Protection class
Table 2: Dry contact (NO1, NO2)
Actuator type/version
EA-K-30
Rated voltage
Contact load relay
The normally open contact (NO) is only activated in the
“CLOSED” end position when the actuator is cut off. This
means that the message is stroke-dependent and can be
evaluated as a “CLOSED message”. Activation of the
actuator at the “OPEN” end position can also be configured
via SIMON LINK, as well as other settings.
Table 3: Connection and operation
Actuator type/version
EA-K-30
Silicone connection cable with
connector
Supply cable length1
1.
Optional lengths possible.
Pause time at a change in the
driving direction2
2.
It is necessary that the supply voltage ensures a pause time (zero volt
range) of at least 500 ms for a change in the driving direction (pole
reversal) (see Figure 29: “Zero volt range at a change in the driving
direction” on page 25).
Switch-on duration
S2 ED 30% (short-time duty
Stability of opening and closing
cycles
Sound level3
3.
Measured at a distance of one metre under normal conditions.
Re-triggering in accordance
with prEN 12101-9
Re-triggering after a stop
Maintenance
24 V DC
24 V DC -15%; +15%
max. 500 mV
yes
1.0 A
1.1 A
1.1 A
0.3 A
40 mA
Integrated electronic overload
cut-off
2 in DUO operation
4 in parallel operation
(see chapter 6.2 “EA-K-30
Electrical connection” on
page 19)
max. 10 m
3 s
300 ms
III
max. 28 V DC
1.0 A
ATTENTION
The maximum load capacity of the contact must not be
exceeded (see Table 2: “Dry contact (NO1, NO2)”).
INFORMATION
The output of the dry contact occurs only on the gear side
of the actuator (see Figure 1: “EA-K-30/xxx-T(-DA) chain
actuator” on page 5)!
5 x 0.75 mm²
3 m
at least 500 ms
3 of 10 minutes)
11 000
≤ 55 dB (A)
permitted
permitted
See chapter 11.1 “Care and
Maintenance” on page 28.
EA-K-30 – Technical Data
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
Page 25
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
Issue: 1.2 / 01.2019
[email protected]
Figure 29: Zero volt range at a change in the driving
direction
Table 4: Installation and ambient conditions
Actuator type/version
EA-K-30
Nominal operating temperature
Permissible ambient
temperature range
Temperature stability (smoke
and heat exhaustion)
Protection rating
Area of application
Table 5: Approvals and certificates
Actuator type/version
EA-K-30
CE-compliant
Further approvals
Table 6: Mechanical properties
Actuator type/version
EA-K-30
Nominal pushing force1
1.
Only under optimum conditions, up to a 600 mm stroke (see
chapter 6.1.11 “Permissible pushing force on the chain” on page 18),
pushing force can be configured via SIMON LINK.
Nominal pulling force2
2.
Pulling force can be configured via SIMON LINK.
Conditions of loading
Nominal locking force3
3.
The force may vary depending on the design of the actuator, bracket,
fixing type, window material etc.
Nominal stroke4
4.
In the case of a stretched chain, e.g. traction relief. The nominal stroke
may deviate by ± 3%, but no more than 20 mm, due to mechanical
damping.
– EA-K-30 / 400-T(-DA)
– EA-K-30 / 600-T(-DA)
– EA-K-30 / 800-T(-DA)
– EA-K-30 / 1000-T(-DA)
– EA-K-30 / 1200-T(-DA)
Stroke speed5
5.
Based on a 600 mm stroke; deviation ± 5%.
– 300 N
– 200 N
– 100 N
Material – surface
Material – chain
Dimensions (W x H7
7.
Plus chain exit (7 mm).
x D)
– EA-K-30 / 400-T(-DA)
– EA-K-30 / 600-T(-DA)
– EA-K-30 / 800-T(-DA)
– EA-K-30 / 1000-T(-DA)
– EA-K-30 / 1200-T(-DA)
Weight8
8.
Information without supply cable and brackets.
– EA-K-30 / 400-T(-DA)
– EA-K-30 / 600-T(-DA)
– EA-K-30 / 800-T(-DA)
– EA-K-30 / 1000-T(-DA)
– EA-K-30 / 1200-T(-DA)
Table 7: Accessories
Actuator type/version
EA-K-30
Mechanical connection to the
actuator medium (chain)
Mechanical connection to the
actuator housing
ATTENTION
Voltage stability/quality: only defined cut-off processes
are permitted (cut-off time of 24 V DC rated voltage to
0 volts in t < 10 ms).
This also applies in particular to switching processes from
a primary (mains operation) to secondary energy source
(backup batteries).
20 °C
from 0 to 75 °C
300 °C
IP 32
Central European
environmental conditions
2000 metres obove sealevel
In accordance with the EMC
Directive 2014 / 30 / EU and the
Low Voltage Directive
2014 / 35 / EU
on request
300 N
300 N
S: +24 V
O: GND
O: +24 V
S: GND
0 V
U[V] (DC)
t [ms]
D 500 ms
“OPEN”
“CLOSE”
Opening against the nominal
load /closing with nominal load
support
≤ 2000 N
400 mm
600 mm
800 mm
1 000 mm
1 200 mm
N2
9.7 mm / s
11.1 mm / s
12.5 mm / s
Aluminium E6 / EV1
Coatings6are possible in all
RAL and DB colours
Corrosion-resistant,
monostable steel chain, silver
nickel-plated
(a high-grade steel chain is
optionally available)
467 x 37 x 35 mm
564 x 37 x 35 mm
667 x 37 x 35 mm
764 x 37 x 35 mm
867 x 37 x 35 mm
1.30 kg
1.52 kg
1.80 kg
2.02 kg
2.30 kg
6.
Attention: Screws, nuts, discs, sliders and similar individual components
are not coated.
A wide selection of bracket sets
is available. The technical data
only applies in connection with
original accessories!
Actuator type/version
EA-K-30
EA230-K-30 – Technical Data
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
[email protected]
Issue: 1.2 / 01.2019
Page 26
8. EA230-K-30 – Technical Data
Table 8: Electrical properties
Actuator type/version
EA230-K-30
Rated voltage
Permissible rated voltage range
Undervoltage detection
Nominal current1
1.
Maximum current consumption at nominal load
Maximum starting current in
“OPEN” and “CLOSED”
direction
Maximum cut-off current in
“OPEN” and “CLOSED”
direction, after start-up
Current consumption after cut-
off (closed current)
Cut-off via
Maximum permissible number
of actuators connected in
parallel
Cable length between two
actuators in synchronous
operation
Protection class
II
Table 9: Connection and operation
Actuator type/version
EA230-K-30
Plastic connection cable
Supply cable length
Pause time at a change in the
driving direction
Switch-on duration
Stability of opening and closing
cycles
Sound level1
1.
Measured at a distance of one metre under normal conditions.
Maintenance
See chapter 11.1 “Care and
Maintenance” on page 28.
Table 10: Installation and ambient conditions
Actuator type/version
EA230-K-30
Nominal operating temperature
Permissible ambient
temperature range
Protection rating
Area of application
Table 11: Approvals and certificates
Actuator type/version
EA230-K-30
CE-compliant
Further approvals
Table 12: Mechanical properties
230 V AC
230 V AC -10 %; +10 %
no
0.23 A
0.25 A
0.25 A
10 mA
Integrated electronic overload
cut-off
8
max. 10 m
3 x 0.5 mm²
5 x 0.5 mm² (synchronous)
2 m
2.5 m (synchronous)
at least 300 ms
S2 ED 30% (short-time duty
3 of 10 minutes)
11 000
≤ 55 dB (A)
20 °C
from 0 to 75 °C
IP 32
Central European
environmental conditions
2000 metres obove sealevel
In accordance with the EMC
Directive 2014 / 30 / EU and the
Low Voltage Directive
2014 / 35 / EU
on request
Actuator type/version
EA230-K-30
Nominal pushing force1
300 N
Nominal pulling force
300 N
Conditions of loading
Opening against the
nominal load /
closing with nominal load
support
Nominal locking force2
≤ 2000 N
Nominal stroke3
– EA230-K-30 / 300(-S)
– EA230-K-30 / 600(-S)
– EA230-K-30 / 800(-S)
– EA230-K-30 / 1000(-S)
300 mm
600 mm
800 mm
1 000 mm
Stroke speed4
– 300 N
– 200 N
– 100 N
N2
9.7 mm/s
10.0 mm/s
10.3 mm/s
Material – surface
Aluminium E6 / EV1
Coatings5 are possible in all
RAL and DB colours
Material – chain
Corrosion-resistant,
monostable steel chain, silver
nickel-plated
(a high-grade steel chain is
optionally available)
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator – EA230-K-30/xxx(-S)
Page 27
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
Issue: 1.2 / 01.2019
[email protected]
Table 13: Accessories
Actuator type/version
EA230-K-30
Mechanical connection to the
actuator medium (chain)
A wide selection of bracket sets
is available. The technical data
only applies in connection with
original accessories!
Mechanical connection to the
actuator housing
9. Commissioning
See supplementary sheet "Safety Instructions and Warranty
Conditions"!
9.1 EA230-K-30
Perform
a
RESET
procedure
(see
chapter 5.4 “RESET” on page 9) and a teach-in
run (see chapter 5.5 “Teach-in run” on page 9)
after mounting the actuators.
10. Troubleshooting
10.1 EA-K-30
10.2 EA230-K-30
See chapter 5.7 “LED displays” on page 10.
Dimensions (W x H6 x D)
– EA230-K-30/300(-S)
– EA230-K-30 / 600(-S)
– EA230-K-30 / 800(-S)
– EA230-K-30 / 1000(-S)
468 x 37 x 35 mm
624 x 37 x 35 mm
727 x 37 x 35 mm
824 x 37 x 35 mm
Weight7
– EA230-K-30 / 300(-S)
– EA230-K-30 / 600(-S)
– EA230-K-30 / 800(-S)
– EA230-K-30 / 1000(-S)
0.90 kg
1.40 kg
1.80 kg
2.20 kg
1.
Only under optimum conditions, up to a 600 mm stroke (see
chapter 6.1.11 “Permissible pushing force on the chain” on page 18).
2.
The force may vary depending on the design of the actuator, bracket,
fixing type, window material etc.
3.
In the case of a stretched chain, e.g. traction relief. The nominal stroke
may deviate by ± 3%, but no more than 20 mm, due to mechanical
damping.
4.
Based on a 600 mm stroke; deviation ± 5%.
5.
Attention: Screws, nuts, discs, sliders and similar individual components
are not coated.
6.
Plus chain exit (7 mm).
7.
Information without supply cable and brackets.
Actuator type/version
EA230-K-30
Malfunction
Possible causes
Troubleshooting
The actuator is not working.
– Mains power supply is missing;
– Supply cable is faulty;
– Wind/rain sensor has triggered.
– Check the fuse and the supply cable;
– Check the supply cable;
– No failure
The actuator has the wrong running
direction.
– Terminals “+ / -”
are mixed up; S = blue; O = brown.
– Change the polarity of terminals “S” and “O”.
The actuator continues to run beyond
its programmed stroke.
– Displacement of the electronic zero
point.
– Drive the actuator in the “CLOSED” direction and let it
cut off in the “CLOSED” end position.
Chain actuator – EA-K-30/xxx-T(-DA)
– EA230-K-30/xxx(-S)
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
[email protected]
Issue: 1.2/ 01.2019
Page 28
Operating Manual
BA_EA(230)-K-30-XXX_EN_12
11 Annex
11.1 Care and Maintenance
See supplementary sheet "Safety Instructions and Warranty
Conditions"!
short.simon-protec.com/sugen
11.2 General business and delivery terms
Deliveries and services are subject to the currently applicable
terms for products and services of the electrical industry
(green delivery terms), including the supplementary clause
“Extended retention of title”. These are published by the
German Electrical and Electronic Manufacturers' Association
(ZVEI), Frankfurt. If you are not aware of these, we will gladly
send them to you. You can also download these agreements
from
short.simon-protec.com/agben
The place of jurisdiction is Passau.
11.3 Company Addresses
11.3.1 System manufacturer
SIMON PROtec Systems GmbH
Medienstraße 8
94036 Passau
Tel.: +49 (0) 851 988 70 - 0
Fax: +49 (0) 851 988 70 - 70
E-Mail: [email protected]
Internet: www.simon-protec.com
11.3.2 Germany
SIMON PROtec Deutschland GmbH
Medienstraße 8
94036 Passau
Tel.: +49 (0) 851 379 368 - 0
Fax: +49 (0) 851 379 368 - 70
SIMON PROtec Deutschland GmbH
Ammerseestraße 75
D – 82061 Neuried
Tel.: +49 (0) 89 79 17 0 - 11
Fax: +49 (0) 89 79 17 9 - 72
E-Mail: [email protected]
Internet: www.simon-protec.de
11.3.3 Switzerland
SIMON PROtec Systems AG
Allmendstrasse 38
8320 Fehraltorf
Tel.: +41 (0) 44 956 50 30
Fax: +41 (0) 44 956 50 40
E-Mail: [email protected]
Internet: www.simon-protec.ch
11.3.4 Hungary
SIMON PROtec Systems Kft.
Sodras utca 1. fszt. 1
1026 Budapest
Tel.: +36 (0) 30 552 0424
E-Mail: [email protected]
Internet: www.simon-protec.hu
12 Manufacturer's declaration
We hereby declare that the product complies with the applicable directives. The declaration of conformity can be read
at the company's premises and will be sent to you upon request. This declaration certifies that the product complies
with the mentioned directives, but does not represent any guarantee of the product's features. This declaration loses
its validity, if the product is modified without seeking our prior authorisation.
13 EC manufacturer’s declaration (distributor)
The installer is responsible for the proper mounting or commissioning, the preparation of the declaration of conformity in accordan-
ce with the EU directives and for affixing the CE marking. The CE marking must be affixed visibly!