Cumberland Evolution S3 Owner's Manual
Text of the manual
Manual No. 4801-2997 Rev 1-15 Owners Manual
Secondary Sensing System
CUMBERLAND Assumption, IL 62510 • Phone 217-226-4421 • Fax 217-226-4420
Secondary Sensing System
Owners Manual
Cumberland
1004 E. Illinois St.
Assumption, IL 62510
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
Table of Contents
Table of Contents
Section
Description
Page
1.
Warnings .........................................................................................................................................................4
2.
Ratings and Specifications ..............................................................................................................................5
3.
Introduction ....................................................................................................................................................5
4.
S3 Front Panel .................................................................................................................................................6
4.1
Control / Editor Section ..........................................................................................................................6
4.1.1
Temperature ....................................................................................................................................7
4.1.2
Target ..............................................................................................................................................7
4.1.3
High Limit .......................................................................................................................................8
4.1.4
Low Limit .......................................................................................................................................8
4.1.5
Status ...............................................................................................................................................9
4.1.6
History ............................................................................................................................................9
4.2
Alarm System Indicators ......................................................................................................................10
4.2.1
Conditions OK Indicator ...............................................................................................................10
4.2.2
Power ............................................................................................................................................10
4.2.3
Low Battery ..................................................................................................................................10
4.2.4
AUX 1 and AUX 2 .......................................................................................................................10
4.2.5
Control System Auxiliary .............................................................................................................11
4.2.6
Zone Temperature Section ............................................................................................................12
4.3
Back-Up System Indicators ..................................................................................................................12
4.3.1
Inlet Overrides Indicators .............................................................................................................12
4.3.2
Ventilation Back-Up Display and Selection Switch .....................................................................12
4.3.3
Back-Up Stages.............................................................................................................................12
4.4
Synchronize / Test Indicators ...............................................................................................................12
4.4.1
Synchronize Systems ....................................................................................................................13
4.4.2
Test/Acknowledge Alarm .............................................................................................................13
5.
Program Mode ..............................................................................................................................................14
5.1
General Parameters ...............................................................................................................................14
5.2
PC Compatible Cumberland Network Parameters ...............................................................................16
5.3
Alarm Function Parameters ..................................................................................................................16
5.4
Sensor Calibration Parameters ..............................................................................................................16
6.
General Operation .........................................................................................................................................17
6.1
Alarm Inputs .........................................................................................................................................17
6.1.1
Temperature Sensors #1 ,#2 and #3 ..............................................................................................17
6.1.2
Auxiliary Inputs #1, #2, and Control System ...............................................................................17
6.1.3
Power Out .....................................................................................................................................17
6.2
Alarm Outputs ......................................................................................................................................17
6.2.1
Siren ..............................................................................................................................................17
6.2.2
Dry Contact (N.O. and N.C. Contacts) .........................................................................................18
7.
Back-Up System Operating Conditions ........................................................................................................19
7.1
Operation with the Evolution 3000/3001 .............................................................................................19
7.1.1
Normal S3 Back-Up Operation .....................................................................................................19
7.1.2
Emergency Operation ...................................................................................................................20
7.1.3
Override Operation .......................................................................................................................20
7.1.4
Fail-Safe Relay Operation .............................................................................................................21
7.1.5
Setting EV Back-Up Stage Jumpers .............................................................................................21
7.1.6
Vent/Tunnel Inlet Override Operation ..........................................................................................21
7.2
Operation as Stand-Alone System ........................................................................................................22
7.2.1
Normal S3 Back-Up Operation .....................................................................................................22
7.2.2
Minimum Ventilation Protection ..................................................................................................23
7.2.3
Fail-Safe Relay Strip .....................................................................................................................23
7.2.4
Vent/Tunnel Inlet Override Operation ..........................................................................................23
8.
Trouble-Shooting Your Alarm .....................................................................................................................24
8.1
Low Battery ..........................................................................................................................................24
8.2
Power Out .............................................................................................................................................24
8.3
No Siren at Test ....................................................................................................................................24
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
Table of Contents
8.4
Replacing the Fuses ..............................................................................................................................24
8.5
Temperature Sensors Disconnected ......................................................................................................25
8.6
Temperature Sensors Out of Calibration ..............................................................................................25
8.7
Trouble-Shooting the Auxiliaries .........................................................................................................25
9.
Controller Installation and Setup ..................................................................................................................25
9.1
Tools Required .....................................................................................................................................25
9.2
Installation Instructions ........................................................................................................................25
9.3
Sensor Recommendations .....................................................................................................................26
10.
Maintenance ..............................................................................................................................................27
11.
Wiring Diagrams, Schematics, etc. ...........................................................................................................27
11.1
S3 Internal Electrical Wiring .................................................................................................................27
11.2
S3 Circuit Board Layout .......................................................................................................................28
11.3
Connecting AC Power to the S3 ...........................................................................................................29
11.4
Connecting Sensors to the S3 ................................................................................................................30
11.5
S3 PowerTrak Override Settings and Wiring ........................................................................................31
11.6
S3 Relay Card Wiring ...........................................................................................................................32
11.7
Connecting an Alarm or Siren to the S3 ................................................................................................33
11.8
Connecting Auxiliary Inputs to the S3 ..................................................................................................34
11.9
Connecting Other Cumberland Controllers to the S3 Auxiliary Input ..................................................35
11.10 Connecting Local Network Connections to the S3 ...............................................................................36
11.11 Connecting the S3 to the HH.Net ..........................................................................................................37
12.
Replacement and Optional Parts ...............................................................................................................38
13.
Temperature vs. Sensor Resistance Table ................................................................................................39
14.
Error Codes ...............................................................................................................................................40
15.
S3 Program Label ......................................................................................................................................40
16.
Warranty ...................................................................................................................................................41
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
4 of 42
1.
Warnings
Warning!
Maximum operating temperature of controller is 50° C (122° F).
Use adequate ventilation to reduce the risk of overheating controller!
Warning!
• Do not perform modifications or wiring with voltage applied!
• Keep high voltage (or AC) separate from low voltage wires!
Warning!
When this controller is used in a life support heating and ventilation system where
failure could result in loss or injury, the user should provide adequate back-up, or
accept the risk of such loss or injury!
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
5 of 42
2.
Ratings and Specifications
•
Power Supply…………………240VAC 50/60 Hz
•
Temperature Range…………..32°F - 122°F (0°C – 50°C)
•
Inputs………………………....Three thermistor temperature sensors 32°F – 120°F (0°C - 49°C)
Three auxiliary inputs (contact closure)
•
Outputs………………………..One siren (1.0 Amps @ 12VDC)
One dry contact (5 Amps @ 240 VAC)
4 - 1 Hp Stage Outputs (Plus Model ONLY)
3.
Introduction
The Evolution Secondary Sensing System, also known as S3 (S cubed), is a unique control system. It combines
the features of two systems into one. The S3 is an alarm system that has the added abilities of the Evolution Back-
Up System. It combines these functions to provide ultimate security at a lower system cost.
•
Alarm System
First, it functions as an alarm system to warn or alert of problem conditions such as Power Outage, High or
Low temperature conditions, and/or out of range conditions in other devices through auxiliary switch inputs
such as alarm relays. It contains an alarm relay that is capable of driving a 12 volt audible siren and also
capable of signaling an external dialer through a N.O./N.C. contact. The S3 is capable of monitoring up to three
auxiliary alarm inputs. It can also monitor up to three temperature sensors for out of range conditions which
allows the S3 the flexibility to monitor any brood setup. In addition, the S3 has a built in Cycle Pressure Alarm
that can be used in conjunction with a static pressure switch or a Photohelic gauge to provide a minimum
ventilation monitor.
•
Back-Up System
As an added bonus, the S3 can also act as the buildings Back-Up System. All of the functionality of the
Evolution Back-Up System is packed into this unit. Therefore, as with the Evolution Back-Up System, it is
capable of driving up to 32 of the Evolution 3000/3001 relay outputs, it can override the vent or tunnel inlets
based on the level of Back-Up necessary, and it contains a back-up timer percentage capable of assisting in
minimum ventilation. This unit is also not limited to use with the Evolution 3000/3001. With the addition of a
fail-safe relay card, this unit is capable of driving four 1 h.p. loads directly. Therefore, it is capable of being
used with any control system. (Note: If used with control systems other than the Evolution 3000/3001, some
functionality will be lost.)
•
Additional Benefits
By combining the alarm system and the Back-Up system, the S3 adds additional benefits other than the obvious
benefit of a lower system cost. The added benefits include the addition of another Back-Up temperature sensor,
a back-up battery to provide power in the case of a breaker failure or a power supply fuse failure, and an
additional back-up stage delay which delays turning equipment on after a power failure to allow proper
generator start-up.
In addition to the above features and benefits, the design of this system focused on providing a system that was
more user-friendly and beneficial to the end user. The S3 added a target temperature in addition to the High and
Low limits for the alarm and the Back-Up System. The High and Low limits are based off of this target,
therefore, keeping your alarm and back-up limits in line is as easy as matching the target temperature of your S3
with the main systems target temperature. In fact, when used in conjunction with the Evolution 3000/3001
controllers, it is as easy as pressing the “Synchronize” button. Another added benefit is the addition of an on
board history that tracks high and low temperatures, alarm conditions, and back-up conditions.
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
6 of 42
Secondary Sensing System Front Panel
Control / Editor
Section
Back-Up Section
Zone Temperature
Section
Synchronize / Test
Section
Power Switch
Alarm Status
Section
4.
S3 Front Panel
The S3 has five main sections on the faceplate. These are the Zone Temperature Section, the Back-Up Section, the
Control / Editor Section, the Synchronize / Test Section, and the Alarm Status Section.
The S3 Power Switch is located on the left side of the controller box as shown below. The switch controls power to
the S3 controller and to the back-up battery.
4.1
Control / Editor Section
Just below the Back-Up Section on the right hand side of the controller is the Control / Editor Section.
This section has three buttons: Mode, Plus (+) and Minus (–). The Mode button is used to navigate thru
settings and conditions. When the Mode button is momentarily pressed, the green LED Indicators changes
to the next reading. By pressing and holding the Mode button for at least 5 seconds, the S3 can be placed
in the Program Mode as discussed in Section 5 of this manual. Press the Plus (+) or Minus (-) button to
change the values (readings) in the Ventilation Back-Up Display or Zone Temperature Section Displays
depending on the specific display selected.
Control / Editor Green Indicator LED’s show the type of information represented. For example, if the
green light beside “Temperature” is lit, then the Zone Displays are showing the current readings from
sensors. The other options for the Display Indicators are Target, High Limit, Low Limit, Status, and
History. These modes are changed by momentarily pressing the Mode button. Each press of the Mode
button steps the Display Indicator to the next reading Mode.
LED
Indicators
+ Scroll
Button
-
Scroll
Button
Mode
Button
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
7 of 42
4.1.1 Temperature
The specific Zone Temperature (Zone 1, 2, or 3) lists the individual sensor temperature for each zone.
The Ventilation Back-Up Temperature shown will be the average of the enabled sensors (Zone 1, 2, and/or
3). In the Zone Temperature Section, a reading of “--.-“ indicates the sensor is disconnected or in error.
Also, if the display is flashing “OFF”, it means the sensor is disabled. Therefore, it will not cause the
alarm to sound or be included in the Back-Up System’s average temperature. The Ventilation Back-Up
Temperature displays the average of the enabled Zone Temperature Sensors.
4.1.2 Target
The Target mode displays the target temperature used for Zone Alarm Limits and Back-Up Limits. The
Zone Alarm Limits and the Back-Up Limits are referenced to the target much like that of a stage on point
in a controller. Therefore, once initially set, the user will only adjust the target which will automatically
adjust the high and low limits appropriately. The Target temperature can be changed (0.5° increments)
using the Plus (+) or Minus (–) buttons. Example: If the Target Temperature is set to 80.0° F; The High
Zone Limit temperature is set to 92.0° F; The Back-Up High Limit temperature set to 90.0° F; When the
Target is dropped to 70.0° F, the High Zone Limits will change to 82.0° F and the Back-Up High Limit
temperature will change to 80.0° F.
Ventilation Back-Up Temperature
Specific Zone Temperatures
Target Temperature
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
8 of 42
4.1.3 High Limit
The High Alarm Temperature is the high temperature at which the controller will indicate an alarm
condition. The High Alarm Temperature is displayed and can be changed using Zone Input Switches
(Zones 1, 2, or 3) then using the Plus (+) or Minus (–) buttons.
The High Back-Up Limit is the high temperature at which Cool 1 of the Back-Up will turn ON.
See Section 7 (Back-Up Operating Conditions). The High Back-Up Temperature is displayed and can
be changed (1.0° increments) using the Select Button then using the Plus (+) or Minus (–) buttons.
NOTE: The High & Low Limits for the temperature sensors can be set individually or can be
programmed to be identical using program parameter P2 (See Section 5).
4.1.4 Low Limit
The Low Alarm Temperature is the low temperature at which the controller will indicate an alarm
condition. The Low Alarm Temperature is displayed and can be changed using Zone Input Switches
(Zones 1, 2, or 3) then using the Plus (+) or Minus (–) buttons.
The Low Back-Up Limit is the low temperature at which Heat of the Back-Up will turn ON.
See Section 7 (Back-Up Operating Conditions). The Low Back-Up Temperature is displayed and can be
changed (1.0° increments) using the Select Button then using the Plus (+) or Minus (–) buttons.
NOTE: The High & Low Limits for the temperature sensors can be set individually or can be
programmed to be identical using program parameter P2 (See Section 5).
High Back-Up Limit Temperature
High Alarm Limit Temperatures for Specific Zones
Zone Input Switches
Select Switch
Low Back-Up Limit Temperature
Low Alarm Limit Temperatures for Specific Zones
Zone Input Switches
Select Switch
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
9 of 42
4.1.5 Status
The Status Mode displays the Sensor Status (ON or OFF) for each specific zone. This setting is used to
remove unused sensors or to deactivate sensors outside of the brood area during ½ or ¾ brood conditions.
Use the Zone Switches for selecting the specific Zone Temperature Sensor then using the + (ON) or –
(OFF) buttons to enable or disable sensors.
4.1.6 History
The History Mode displays the High and Low Temperatures for each specific zone, any Back-Up stages
which have turned ON, as well as any alarm conditions which have occurred since the last reset.
The History Reset function is displayed after pressing the Mode Button once after the Low Temp is
displayed. The Zone 1 display will indicate “HIS” and the Zone 2 display will indicate “no” initially.
Press the “+” button for selecting YES, then press the Mode button to confirm the History Reset to reset all
control history. A new feature added in version V0.10 and later software allows automatic resetting of the
on-board history anytime the Synchronize button is pressed.
Status for Specific Zones
Zone Switches
Status for Specific Zones
(High or Low Temperature Mode)
Temperatures for
Specific Zones
High Temp
Low Temp
Reset
Press
Display History Selection Sequence
Press
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
10 of 42
4.2 Alarm System Indicators
The Alarm Status LED Display indicates if all Conditions are OK (Green LED) or the specific reason for
the alarm condition (Red LED’s).
If a red Alarm LED is blinking, the problem may be one of two causes:
a. If Conditions OK LED is Green, an Alarm condition exists although the 30 second confirmation timer
has not expired.
b. If Conditions OK LED is OFF, the alarm condition has been acknowledged (Acknowledge LED will
also be ON).
Except for the Conditions OK (status) indicator, all of the remaining LED Indicators have red LED’s for
displaying alarm status information.
4.2.1 Conditions OK Indicator
At the top of the Alarm Status Indicators section is an LED indicator labeled “Conditions OK”. This
indicator shows the current alarm status of the S3. If the Conditions OK LED is green, there are no alarms
being generated. If the LED indicator is OFF, the S3 is in the alarm mode. When the LED is OFF, refer to
the other Alarm Status Indicators for specific alarm condition information.
4.2.2 Power
When this RED LED turns ON, the S3 control has lost AC power or the F1 fuse is blown. Refer to Section
8.4 for fuse replacement information.
4.2.3 Low Battery
When the Low Battery RED LED indicator turns ON during loss of AC power, the battery level is
partially depleted and currently operating at a low energy level. If the battery voltage has dropped below
about 10.6 volts, the red LED Indicator will light. If the battery indicates low, the operator should set all
controls so that the siren will not activate, and leave the machine plugged in for about four hours. This
should recharge the battery. If this doesn’t work the battery is probably bad. In this case, contact your
Cumberland dealer for a replacement. Note that it is common for the Low Battery indicator to be lit if the
alarm has sounded for a long time.
4.2.4 AUX 1 and AUX 2
The designated alarm condition exists when the AUX 1 and/or AUX 2 RED LED turns ON. The Auxiliary
inputs can be connected to a variety of external control sources such as curtain drops, control alarm
outputs, pressure switch, or any device with a NC (Normally Closed) dry contact connection. The white
area to the right of the LED indicator can be used to write-in the alarm title/description by using a
Write-In Areas
(for Auxiliary Alarms)
LED Indicators
(for Control System Alarms)
LED Indicators
(for Status and Alarms)
Alarm Indicators
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
11 of 42
Control System
TEMPERATURE:
The temperature is beyond the alarm limits.
PRESSURE:
Indicates a High, Low, or Cycle Pressure alarm.
WATER SYSTEM:
Indicates High or Low water usage.
FEED SYSTEM:
Indicates a feed auger excessive runtime alarm.
SPECIAL FEATURES IF USED WITH EVOLUTION 3000/3001
permanent fine-tipped marker. Each auxiliary alarm can be individually enabled or disabled by using the
circuit board jumpers. Refer to the Circuit Board Layout in Section 11.2. If the jumper is installed, the
AUX 1 or AUX 2 alarm is Disabled; If the jumper is removed, the AUX 1 alarm is Enabled.
4.2.5 Control System Auxiliary
The Control System auxiliary input is a special input that should be connected to the main control system.
It operates similar to Aux1 and Aux2 and yet has special functions associated with it to provide better
protection for the building. The functions are different when the unit is connected to an Evolution
3000/3001 and when it is connected to another type control system. The following details the differences.
Operation with Evolution 3000/3001:
If connected to a Evolution 3000/3001, there is a communication network that allows
communication of the alarm data from the main system to the S3. This allows the system to alarm
even if the hard-wired connection to the Control System Auxiliary does not exist. It also allows
the S3 to provide more detail as to what problem exist using the four LEDs located just below the
Control System indication. The following picture highlights these indicators.
The CONTROL SYSTEM alarm can be enabled or disabled by using the circuit board jumpers.
Refer to the Circuit Board Layout in Section 11.2. If the jumper is installed, the CONTROL
SYSTEM alarm is Disabled; If the jumper is removed, the CONTROL SYSTEM alarm is
Enabled. The Evolution controller communicates with the S3 to display the four alarms described
below:
Operation without the Evolution 3000/3001:
If the unit is used with another type control system, the Control System Auxiliary can take on other
functions on top of just being an alarm. This input can function in one of two ways depending on the
setting in program parameter P62 (See Section 5).
If “P62 = On”, the input becomes a Cycle Pressure input. Therefore, while connected to a Photohelic, or
Static Pressure switch, it will monitor the static pressure through the timer cycle period (P63). If it does
not see a static pressure spike during this cycle, it will assume that the minimum ventilation is not working.
Therefore, it will sound the alarm and also trigger the Back-Up system to run the “Cool1” backup stage on
a minimum ventilation cycle. The minimum ventilation cycle is five minutes and the runtime will be based
on the setting in P3 (See Section
P62 = On – Cycle Pressure Alarm Enabled
5).
If “P62 = OFF”, the input is a normal auxiliary input that will function in much the same way as Aux1 and
Aux2. There is one distinction. If the S3 detects the alarm signal on this input, it will not only sound the
alarm but it will also trigger the Back-Up System to run the “Cool1” backup stage on a minimum
ventilation cycle. The minimum ventilation cycle is five minutes and the runtime will be based on the
setting in P3 (See Section
P62 = OFF – Cycle Pressure Alarm Disabled
5).
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
12 of 42
4.2.6 Zone Temperature Section
The Zone Temperature Section shows the specific zone alarm status and control settings for the
temperature alarms. If the Alarm Indicator is ON, that particular Zone is out of its temperature range based
on the High and Low Limits.
4.3
Back-Up System Indicators
The Back-Up System Indicators display the Back-Up operation status and control settings. Refer to
Section 7 for additional information.
4.3.1 Inlet Overrides Indicators
The Inlet Override Indicators indicate if the Back-Up is calling for vent inlets or tunnel inlets to
open. Vent inlets operate with Cool 1; Tunnel inlets operate with Cool 3.
4.3.2 Ventilation Back-Up Display and Selection Switch
The Ventilation Back-Up Display and Selection Switch are used to select and change the back-up
settings. Refer to Section 7 for additional information.
4.3.3 Back-Up Stages
The Back-Up Stages Indicators indicate if the Heat, Cool 1, Cool 2, or Cool3 stages are ON or
OFF. If Cool 1 is flashing, it indicates that it is operating on a minimum ventilation timer. Refer
to Section 7.1.1 for additional information.
4.4
Synchronize / Test Indicators
The Synchronize / Test Section include two functions. Synchronize Systems and Test/Acknowledge
Alarm.
Alarm Indicators
Zone Selection Switches
Zone Temperature/
Settings Displays
Temperature/Settings
Display
Selection Switch
Back-Up Stages
Indicators
Ventilation Back-Up
Display & Selector
Inlet Overrides
Indicators
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
13 of 42
4.4.1 Synchronize Systems
The Synchronize Systems feature is used with the EV-3000 or EV-3001 controller to update the
S3 target temperatures to the match the controller target temperatures and also automatically reset
the on-board history. The on-board history automatic reset is a new feature added in version
V0.10 and later software. If the S3 and the EV-3000 or EV-3001 temperature targets do not
reflect the same information, the Synchronize Systems LED will flash. Press the Select button to
automatically Synchronize the target temperatures and reset the on-board history. When the
Synchronize Systems Select button is pressed, the target temperatures of the S3 will be changed
to match the Evolution 3000/3001 controller target temperatures. It will also be displayed in the
Back-Up display for verification.
4.4.2 Test/Acknowledge Alarm
The Test/Acknowledge Alarm Section has two functions. It allows the user the ability to test the
alarm contacts or the ability to silence (acknowledge) an active alarm.
Testing Alarm Contacts
To test the Alarm contacts, the user can simply press and hold the “Select” button next to the
Test/Acknowledge Alarm indicator. This allows the user the ability to manually test his
alarm siren and/or alarm dialer. As long as the button is depressed, it will activate the alarm
relay irregardless of the conditions that exist. In applications that use audible sirens, it is
recommended that the operator press the Test/Acknowledge Alarm button for at least five
seconds twice a week. In addition to insuring that the alarm is working correctly, the
sounding of the alarm helps to condition that livestock or poultry so they are not shocked by
the sound when an emergency condition arises.
Acknowledging Alarms
If an active alarm condition exists, you can silence the audible siren, phone dialer, etc. once
you arrive by pressing this button. This indicates to the alarm that you are acknowledging the
problem; therefore, it disables the alarm contacts. If a different alarm occurs after the
acknowledgement, the alarm contacts will be re-enabled. After an acknowledgement, the
alarm indicator will continue to blink and the indicator beside the Test/Acknowledge Alarm
section will also be on. This acknowledged condition is reset by only two ways. First, the
alarm condition is corrected; secondly, the AC power and the battery power are removed
from the controller.
Test/Acknowledge Alarm
Select Buttons
Test/
Acknowledge
Alarm
LED Display
Synchronize Systems
Select Buttons
Synchronize
Systems
LED Displays
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
14 of 42
5.
Program Mode
By pressing and holding the Mode button for at least 5 seconds, the S3 can be placed in the Program Mode as
discussed below and on the following pages.
Settings that are usually set up once per grow-out or maybe even just for summer or winter are referred to as
program parameters and are accessed by taking the controller to program mode. To get to program mode, press and
hold the “Mode” button for five seconds. When the controller has entered program mode, the Zone 1 display will
show the first parameter (P1) and the Zone 2 display will show the current setting of parameter P1 (either C or F).
The “Pxx” is known as a parameter number. All the program items for the controller have a unique parameter
number assigned to them. The numbers are listed in the following subsections with a short description of each
parameter. When in program mode, you change the value of certain parameters by using the + and - buttons as
needed. When you have finished with the current setting, press the “Mode” button to move to the next parameter.
5.1
General Parameters
General parameters are associated with the operation and control of the S3:
P1 – Temperature Limits
This general parameter selects either Celsius (C = Celsius) or Fahrenheit (F = Fahrenheit) temperature
units. If P1 is set to “C”, the temperature units will be displayed in Celsius. If P1 is set to “F”, the
temperature units will be displayed in Fahrenheit.
P2 – Individual Sensor Limits
This general parameter determines how to program the Sensor High and Low temperature limits. As
indicated earlier, these limits can be set individually to different values. However, if it is desired to set
Sensor 1, Sensor 2, and Sensor 3 to the same values, this parameter changes the programming
procedure to allow limits to be entered only once but used for all sensors. If P2 is set to “YES”, the
high and low sensor limits are entered individually. If P2 is “NO” limits are entered once for all
sensors. To change the value of P2, press the Plus (+) button for “YES” or the Minus (-) button for
“NO”.
Parameter Number
Parameter Setting
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
15 of 42
P3 – Back-Up Timer Percentage
This determines the percentage that COOL 1 will be run in an Emergency condition for minimum
ventilation. (10% to 100%). The timer is a five minute timer.
A new timer percentage curve feature (added in version V0.09 and later software) automatically
changes the timer percentage based on the Target Temperature.
The data and table below shows an example:
The table and graph above is representative of the curve. The curve actually has multiple points as the
Target Temperature changes in between these points. The Emergency Back-Up Timer Percentage is
not user selectable although you can view the current timer percentage by going to Program Mode and
displaying P3. As you can see by the table, once the Target Temperature gets to 70 F (21.1 C) or less,
the timer fan will run 100% of the time. In other words, Cool 1 will always run in the event that the
main controller is lost or has a problem operating its timer fans. Timer percentages in between 70 –
100% are not implemented because frequent on-off transitions are very hard on single phase AC
motors.
P4 – Back-Up Stage On Delay
This determines the number of seconds that the S3 will wait before turning Stages ON during power
loss (10 to 60 seconds). This feature is designed to help with generator start-up.
P5 – Fail-Safe Vent Inlets
This determines whether the “Vent Inlet” relay operates with a normal action or a fail-safe action. If
“Yes” (Fail-Safe Action) is chosen, the relay will default to allow the inlet machine to “Open” under
extreme failure. Example – Power removed. If “No” (Normal Action) is chosen, the relay will default
to allow the main controller control of the inlet. If “Fail-Safe” mode is chosen, the wiring must be
reversed as shown in Section 11.5 wiring diagram.
IMPORTANT
11.5
: It is important to ensure that the correct wiring connections are implemented with the
specific P5 or P6 setting selection. Section
shows the required wiring for Normal
Action (P5/P6 = “No”) and also the required wiring for Fail-Safe Action (P5/P6 =
“Yes”).
P6 – Fail-Safe Tunnel Inlets
This determines whether the “Tunnel Inlet” relay operates with a normal action or a fail-safe action. If
“Yes” (Fail-Safe Action) is chosen, the relay will default to allow the inlet machine to “Open” under
extreme failure. Example – Power removed. If “No” (Normal Action) is chosen, the relay will default
to allow the main controller control of the inlet. If “Fail-Safe” mode is chosen, the wiring must be
reversed as shown in Section 11.5 wiring diagram.
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
16 of 42
5.2
PC Compatible Cumberland Network Parameters
These parameters are used with Cumberland’s Farm Manager Software. The controller has four
parameters which are used to function with the Cumberland PC compatible inter-controller network
(HH.Net).
P40 – HHNet Address
HH.Net permits up to 32 controllers to be addressed on a single communications port of a personal
computer (PC). In order for the computer to recognize the communications from the controllers, each
controller must have a unique network address.
P41 – Version Number
This is not settable by the user. It is the version of the controller software.
P42 – Controller Setup
This is not settable by the user. It is a unique number that allows the network software (Farm
Manager) to recognize the type of controller.
P43 – Local Network Enable
The Local Network Enable feature enables the S3 to communicate with an Evolution 3000/3001
controller. If connected to an Evolution 3000/3001 and the Back-Up is enabled, the setting will
automatically change to Yes.
No = Not Connected [Stand-Alone]; Yes = Connected [EV Network]
5.3
Alarm Function Parameters
The Alarm Function Parameters operate special alarm features.
NOTE:
These Features Are Automatically Disabled If Connected To The Evolution
3000/3001 Controller.
P62 – Cycle Pressure Alarm
The Cycle Pressure Alarm is setup to monitor minimum ventilation. It uses a pressure switch or
other pressure/timer fan monitoring device and must be connected to Control Aux. This setting
changes the operation of the control system auxiliary alarm. Contrary to its normal operation where an
open signal would trigger an alarm, it will actually be looking for an open signal during the Minimum
Vent Cycle Time (P63). If it does not see the open signal during this period, it will sound the alarm
and trigger the Back-Up system to run “Cool 1” on a minimum ventilation timer cycle. (ON =
Enabled; OFF = Disabled)
P63 – Minimum Vent Cycle Time
The Minimum Cycle Time is the time in minutes which is being used to provide minimum ventilation
such as 5 or 10 minute timers. (Cycle time for timer fans)
5.4
Sensor Calibration Parameters
The S3 has three temperature sensors that can be calibrated. The parameter(s) for calibration are PSx
where x is the sensor number.
NOTE: A sensor should never be calibrated more than 8 degrees. If a setting is that far out of range, it
indicates that there is a problem other than sensor calibration.
PS1 - Calibrate Sensor 1
This is the calibration temperature for Sensor 1.
Instructions: With the controller operating, use a digital thermometer or similar independent
temperature measuring device to measure the temperature at Sensor 1 location. With PS1 selected, use
the Plus (+) and Minus (-) buttons to set the calibration temperature to the thermometer reading.
PS2 - Calibrate Sensor 2
This is the calibration temperature for Sensor 2.
Instructions: Same as Sensor 1 except substitute PS2 for PS1 in the instructions above.
PS3 - Calibrate Sensor 3
This is the calibration temperature for Sensor 3.
Instructions: Same as Sensor 1 except substitute PS3 for PS1 in the instructions above.
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
17 of 42
6.
General Operation
6.1
Alarm Inputs
The S3 has seven inputs that can be used to sound an alarm; Three from temperature sensors, three
auxiliaries, and one for power out. The temperature sensors can be enabled or disabled. If a sensor is
enabled it will be used to generate an alarm. If a sensor is disabled, it will not generate an alarm, even if
the S3 determines that its readings are out of limits. The Auxiliary and Power Out inputs are always
enabled. The seven alarm inputs are:
6.1.1 Temperature Sensors #1 ,#2 and #3
The S3 comes from the factory with three temperature sensors. The S3 will trigger an alarm if the
temperature goes above the high limit setpoint or below the low limit setpoint of the sensors. The S3 will
wait 30 seconds after a sensor indicates it is out of range before triggering an alarm.
6.1.2 Auxiliary Inputs #1, #2, and Control System
The S3 is equipped with three auxiliary inputs. These inputs are connected in a closed loop circuit. On the
circuit board located on the door of the alarm enclosure there is a terminal block for connecting the
Auxiliary Inputs (See Section 11.8 for a connection diagram). Each of the connections has an IN and OUT
terminal. If, at any time, the connection between the IN and OUT positions is broken (opened), the alarm
will sound. There are many devices on the market that could be used with these inputs. For instance,
water pressure switches, light meters, and thermostats could all be used. The S3 will wait 30 seconds after
an auxiliary input is broken before triggering an alarm.
6.1.3 Power Out
The Power Out alarm indicates that there has been no AC electricity present on the alarm power feed for at
least 30 seconds.
AC Power Fuse:
If it is found that there is power present at the electrical outlet and the Power Alarm is ON at the S3, the 3
Amp slow-blow fuse located on the S3 circuit board (Fuse F1) should be checked for a blown fuse. To
replace a fuse, disconnect AC power, disconnect the positive (+) battery terminal from the battery,
carefully replace the blown fuse with the correctly sized replacement fuse, reconnect the positive (+)
battery terminal to the battery, reapply AC power, and verify the power alarm has cleared. The S3 will wait
60 seconds after a Power Out indication before triggering an alarm. Refer to the S3 Circuit Board Layout
in Section 11.2 and Fuse Replacement in Section 8.4.
Terminal Connections to the Battery:
If AC power is out or disconnected from the S3 AND none of the S3 Displays or LED’s are ON, verify that
the Battery Positive (+) and Battery Negative (-) quick-connect terminals are securely attached to the
battery. Refer to the S3 Wiring in Section 11.2.
If the AC power is OFF for an extended period of time with the alarms ON, the Back-Up Battery will
eventually be drained of all power. Refer to Section 8 for additional troubleshooting information.
6.2
Alarm Outputs
The S3 has two alarm outputs. These can be used individually or simultaneously. The alarm outputs are:
6.2.1 Siren
The siren hookup to the S3 will deliver a 12 volt DC signal with a current up to 1.0 amps. Many operators
want to mount the siren a long distance from the controller. Sometimes, this is desirable in order to locate
the siren closer to their dwelling, sometimes to get it away from their animals. The use of a small gauge
wire to connect the Alert Alarm to the siren could cause a great deal of voltage drop. This voltage drop, in
turn, can cause the siren to become inoperative. If the operator wants to mount the siren more than 50 feet
from the controller, a relay with a 12VDC rated coil should be used to switch current to the siren. When a
relay is added, the operator must provide a separate battery and charger for the siren circuit.
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
18 of 42
6.2.2 Dry Contact (N.O. and N.C. Contacts)
The S3 provides a set of dry contacts that can be used to trigger a modem, auto-dialer or other auxiliary
equipment. Both normally open (N.O.) and normally closed (N.C.) contacts are available. See Section
11.7 for a wiring diagram.
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
19 of 42
SPECIAL FEATURES IF CONNECTED TO EVOLUTION 3000/3001
7. Back-Up System Operating Conditions
The S3 Back-Up System operates differently based on whether it is connected to a Evolution 3000/3001 control
system or if it is a stand-alone (not connected to the Evolution 3000/3001 local network) system. Of course the
system loses some of its functionality when it is not connected to the Evolution 3000/3001 network but its
capabilities are still much better than other Back-Up system alternatives. This section will be divided into two sub-
sections.
Important!
Before continuing, one must determine which type of system is installed for this specific application.
If the S3 is connected to a Cumberland Evolution 3000 or Evolution 3001, refer to Section 7.1 for a
description of the Back-Up operation with the Evolution 3000/3001. Otherwise, refer to Section 7.2
for Back-Up operation as Stand-Alone System.
7.1
Operation with the Evolution 3000/3001
7.1.1 Normal S3 Back-Up Operation
During Normal Operation, the S3 always maintains the temperature between its high and low limits. It
accomplishes this by using its temperature sensors and its four stage outputs. If the temperature drops
below the Low Limit, the Heat stage will come on. That stage will not turn off until it warms the building
at least 2°. The same is true if the temperature goes above the High Limit however, there are three levels
of cooling stages on the Back-Up System. The following example explains the operation of the stages in
relationship to the temperature and the limits. In this example the Low Limit is set as 66º F, and the High
Limit is set as 86º F. If the temperature drops to 66º F, then the HEAT stage turns on. The HEAT stage
turns off when the temperature rises to 68º F (2º above the Low Limit). If the temperature rises to 86º F,
then COOL 1 turns on. If the temperature continues to rise to 87º F (1º above the High Limit), then COOL
2 turns on. If the temperature rises to 89º F, then COOL 3 turns on. When used with EV-3000/3001, Cool
3 comes ON and Cool 1 will go OFF to disable sidewall/negative fans while in tunnel ventilation. Stages
turn off at temperatures as indicated by the arrows in Graph 1.
Graph 1: Cool 1, 2, 3 and Heat
Temperature (°F)
Heat
Cool 3 - Tunnel
Cool 2
Cool 1 - Vents
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
20 of 42
SPECIAL FEATURES IF CONNECTED TO EVOLUTION 3000/3001
7.1.2 Emergency Operation
In this mode of operation, the system still maintains the temperature as it does in Normal Operation. In
addition, it will begin running the first cooling stage (Cool 1) on a 5 minute timer. The timer percentage is
determined by the setting in P3 (Emergency Timer Percentage). This mode of operation is entered if
communication is lost between the master controller and the S3. In this case, the S3 assumes that the master
controller is lost and tries to maintain the minimum ventilation until someone recognizes the problem.
Emergency Operation is indicated by a “LnE” flashing in the display of the S3. The alarm relay on the S3
is also engaged in this mode operation.
7.1.3 Override Operation
In this mode of operation, the system still maintains the temperature as it does in Normal Operation. In
addition, it receives commands from the master controller to turn on certain stages of heating or cooling.
There are many different circumstances that could cause this to happen, in this manual, we will list one of
the most common. For example, if communication were lost inside the EV-3000, the master controller
would be unable to turn the appropriate stages on in the usual way. Therefore, the master controller would
communicate to the S3 and indicate which stages that it is trying to turn on. At this point, the S3 would
obey the command and turn the appropriate stages on. For this mode of operation to work to its fullest
potential, care must be taken to insure that the stage jumpers on the relay strips match the stage setting in
the master controller (Refer to Section 11.6). Override Operation is indicated by a “LnO” flashing in the
display of the Back-Up System. The alarm relay is also engaged in this mode of operation.
“LnE” flashing
in the Display
“Ln0” flashing
in the Display
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
21 of 42
SPECIAL FEATURES IF CONNECTED TO EVOLUTION 3000/3001
7.1.4 Fail-Safe Relay Operation
There are two types of Relay strips used in the Evolution 3000. The Normally Open (NO) strip requires a
signal from the controller board in order to energize a stage of ventilation. Should power be removed from
the EV-3000 the Normally Open Relay strips would not be able to energize a ventilator. On the other hand
the Fail-Safe relay strip would close each of the relays in the strip resulting in energizing the ventilators in
case of a controller power failure. Each of the relay strips contains four relays for controlling four stages.
In the EV-3000 there are a total of four relay strips, three will be N.O. and one will be a Fail-Safe. The
operator must insure that the Fail Safe relay strip is connected only to stages that should be turned on in
case of a controller failure. See the EV-3000 Owners Manual Part No. 4801-5307 for a physical
description of the relay strips. The S3 Stand-Alone Unit (Plus) also contains a Fail-Safe. It is not
recommended to place heating equipment on Fail-Safe stages.
7.1.5 Setting EV Back-Up Stage Jumpers
Pictured at the right is a Stage Relay Board consisting
of four stage relays and the associated stage jumper for
each stage relay. This board is located in the EV-3000
or EV-3001 controller. The stage jumpers are labeled
COOL 1, COOL 2, COOL 3 and HEAT. Location of
the jumper places the equipment on one of these four
Back-Up Stages, or if the jumper is not inserted, the
equipment is not placed on Back-Up. The jumpers
should be placed based on the operation of stage
equipment and should be the same as assigned in the
EV-3000 Controller. Jumpers are placed according the
following table:
Type of Stage
Operation
Jumper
Assignment
Cool Negative Fan
COOL 1
Cool Negative Tunnel Fan
COOL 2
Cool Tunnel Fan
COOL 3
Heat Stage
HEAT
Stage not on Back-Up
No Jumper
Installed
Additional information can be found in the Evolution
3000 Owners Manual, Part Number 4801-5307.
7.1.6 Vent/Tunnel Inlet Override Operation
The S3 contains override relays to operate your Vent or Tunnel inlets during Back-Up situations. It is
intelligent enough to understand how it needs to operate these overrides in a manner that will not disrupt
what the main control system is trying to do.
Typical operation results in the Tunnel inlet being overridden open anytime the Back-Up stage Cool3 is
on. Otherwise, if Cool1 or Cool2 is on, the S3 will override the Vent inlets open. This is the correct
assumption most of the time but there are exceptions. It is important to note that if Cool3 is turned on, the
S3 will turn off Cool1 which, in turn, will disable the Vent inlet override. This allows the Back-Up system
to perform in much that same manner as the main control system would function during tunnel ventilation.
If connected to the Evolution 3000/3001, the S3 communicates with the master controller. Therefore, it is
aware of what type ventilation mode the controller is currently in. For example, if the main controller is in
tunnel ventilation. The S3 will not allow Cool1 to turn on. The reason is due to the fact that it knows that
this is your sidewall fans. Therefore, it understands that it would be detrimental to the ventilation to turn
them on. This, in turn, also disables the Vent inlets from opening.
STAGE RELAY BOARD
Stage Relay
COOL 3
COOL 2
COOL 1
HEAT
Stage
Jumpers
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
22 of 42
7.2
Operation as Stand-Alone System
The S3 contains an integrated back-up system. This system’s purpose is to back up the master controller in
the case of failure. The back-up system is a stand-alone control system. It contains its own three
temperature sensors which are used to divide the building into zones. These are the same temperature
sensors that are used for the alarming functions described earlier. This allows the user to set High and Low
Back-Up limits, in which the system will use to operate one Heat stage and three Cool stages. The system
is equipped with a fail-safe relay card that is capable of driving four separate 1 h.p. loads. The following
shows the Back-Up System interface.
This setup does not use the Local Network connection that would be present if used in conjunction with the
Evolution 3000/3001. Therefore, its functionality is limited to monitoring the temperature sensors for out
of range conditions but it does still contain some protection against minimum ventilation failure.
7.2.1 Normal S3 Back-Up Operation
During Normal Operation, the S3 always maintains the temperature between its high and low limits. It
accomplishes this by using its temperature sensors and its four stage outputs. If the temperature drops
below the Low Limit, the Heat stage will come on. That stage will not turn off until it warms the building
at least 2°. The same is true if the temperature goes above the High Limit however, there are three levels
of cooling stages on the Back-Up System. The following example explains the operation of the stages in
relationship to the temperature and the limits. In this example the Low Limit is set as 66º F, and the High
Limit is set as 86º F. If the temperature drops to 66º F, then the HEAT stage turns on. The HEAT stage
turns off when the temperature rises to 68º F (2º above the Low Limit). If the temperature rises to 86º F,
then COOL 1 turns on. If the temperature continues to rise to 87º F (1º above the High Limit), then COOL
2 turns on. If the temperature rises to 89º F, then COOL 3 turns on. Stages turn off at temperatures as
indicated by the arrows in Graph 1.
Graph 1: Cool 1, 2, 3 and Heat
Temperature (°F)
Heat
Cool 3 - Tunnel
Cool 2
Cool 1 - Vents
Temperature/Settings
Display
Selection Switch
Back-Up Stages
Indicators
Ventilation Back-Up
Display & Selector
Inlet Overrides
Indicators
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
23 of 42
7.2.2 Minimum Ventilation Protection
As explained earlier, this Back-Up System contains a back-up minimum ventilation timer. This timer is
normally off but is triggered upon an alarm occurring on the Control System auxiliary input. There are two
situations that can cause an alarm on the Control
System auxiliary that depends on the setting in P62
(See Section 6.3). Whether P62 is set to be a Cycle
Pressure Alarm or a normal control system alarm, if
the alarm is triggered the S3 will enable the 5
minute timer clock. Then Cool1 will operate based
on the setting in P3. This process will continue as
long as the Control System auxiliary alarm is
present.
7.2.3 Fail-Safe Relay Strip
The stand-alone system will be equipped with a fail-
safe relay strip. This relay strip has four output
relays. Each relay is capable of driving up to 1 h.p.
Also, each relay has a stage jumper. These stage
jumpers can be used to assign each relay to a back-
up stage, Heat, Cool1, Cool2, Cool3. Therefore, the
end user can select what stages that he would like to
back up. For example, you may not care to back up
your heat stages; therefore, you could use one relay
for Cool1, one relay for Cool2, and two relays for
Cool3.
Any combination will be acceptable but it is important that you understand the operation of each output so
that you back up your main control system appropriately. For example, minimum ventilation protection is
provided by Cool1. If you do not assign a relay output to Cool1, you will not have back up protection for
minimum ventilation. It is also important to choose the correct fans to back up. For example, choose a fan
that is not your typical minimum ventilation fan to run off of Cool1, such as one of your initial tunnel fans.
This will help you two ways. First, it will protect against fan mechanical failure. Secondly, by choosing a
tunnel fan it will not affect tunnel ventilation if the back up kicks in on a hot day. The graph in Section
7.2.1 helps to show how the stages operate but it is also important to understand how the inlet overrides
operate in conjunction with the Cool outputs (See Section 7.2.4). The following table helps associate the
Back-Up stage outputs with the type of equipment that you are trying to operate.
Type of Stage Operation
Jumper Assignment
Cool Negative Tunnel Fan
COOL 1 *
Cool Negative Tunnel Fan
COOL 2
Cool Tunnel Fan/Evap.
COOL 3
Heat Stage
HEAT
Stage not on Back-Up
No Jumper Installed
* IMPORTANT NOTE: Cool1 controls your minimum ventilation Back-Up Stage.
7.2.4 Vent/Tunnel Inlet Override Operation
The S3 contains override relays to operate your Vent or Tunnel inlets during Back-Up situations. It is
intelligent enough to understand how it needs to operate these overrides in a manner that will not disrupt
what the main control system is trying to do.
Typical operation results in the Tunnel inlet being overridden open anytime the Back-Up stage Cool3 is
on. Otherwise, if Cool1 or Cool2 is on, the S3 will override the Vent inlets open. This is the correct
assumption most of the time but there are exceptions.
STAGE RELAY BOARD
Stage Relay
COOL 3
COOL 2
COOL 1
HEAT
Stage
Jumpers
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
24 of 42
The exception occurs if the S3 determines that conditions warrant tunnel ventilation. Therefore, it assumes
that opening the Vent inlets would be detrimental to the current ventilation setup. In this case, it will open
the Tunnel inlet upon any Back-Up stage being turned on due to temperature.
It is important to note. If the Back-Up stage Cool1 is ever timed on due to detection of a minimum
ventilation error, then it will always override the Vent inlets only.
8. Trouble-Shooting Your Alarm
8.1
Low Battery
If the battery in the S3 drains down to approximately 10.6 volts, the Low Battery alarm condition will be
active. This is very common if the alarm has sounded for some time. If the Low Battery alarm is active, the
Alarm should be set so that no alarm condition exists and the battery should be allowed to recharge. This
may require the operator to disconnect the siren to allow the battery to build back up. If recharging doesn’t
fix the problem, then the battery must be replaced. Contact your nearest Cumberland dealer for a
replacement.
8.2
Power Out
The Power Out alarm can occur in two cases. One is when the power has been out for more than one minute.
The other situation could be caused by the 120VAC 3 amp fuse blown. If the Power-Out alarm condition is
active and you find that there is power present at the outlet where the alarm is plugged in, then you should
check the fuses.
8.3
No Siren at Test
If the siren fails to sound when the test button is pressed, several conditions could exist. The siren itself
could be bad. Check for 12VDC at the siren leads. And, of course, there could be a bad connection
somewhere in the siren circuit.
8.4
Replacing the Fuses
The S3 includes two fuses located on the circuit board; One AC power fuse (F1 - 3 Amp) and also a Back-
Up Relay circuit fuse (F2 - 3 Amp).
AC Power Fuse (F1, 3 Amp Slow-Blow)
The AC Power Fuse is electrically placed between the S3 operating circuitry and the 4-pin header connector
connected by wires to the AC conversion transformer. If power is present at the AC wall receptacle and the
S3 front panel displays are not ON, check the AC Power Fuse for a blown fuse.
Back-Up Relay Fuse (F2, 3 Amp Slow-Blow)
The Back-Up Relay Fuse helps to provide protection between the S3 circuitry and the EV-3000/3001. If all
AC power is turned OFF or unplugged at the electrical outlet AND the externally powered controls are also
lacking power, the 3 Amp slow-blow fuse located on the S3 circuit board (Fuse F2) should be checked for a
blown fuse.
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
25 of 42
Fuse Replacement
To replace either fuse, disconnect AC power, disconnect the positive (+) battery terminal from the battery,
and carefully replace the blown fuse with the correctly sized replacement fuse. Reconnect the positive (+)
battery terminal to the battery, plug the male plug end of the AC power cord to the electrical outlet, and
verify that power and functional operation has been restored.
AC Power Fuse
Back-Up Relay Fuse
8.5
Temperature Sensors Disconnected
If the temperature Sensors become disconnected or damaged, the Display Indicator for that sensor will show
a line of bars (- - -). This problem should be corrected before any attempt to calibrate the sensor is made.
8.6
Temperature Sensors Out of Calibration
If the operator believes that the temperature sensors are not reading correctly, the following steps should be
followed: Obtain a thermometer that is known to be accurate. Place this thermometer next to the temperature
sensor for at least 10 minutes. Insure that there are no strong breezes or winds blowing on the thermometer
and the sensor being calibrated. Note the temperature from the thermometer and use this reading to calibrate
the sensor. Refer to Section 9.3 for Sensor Recommendations.
8.7
Trouble-Shooting the Auxiliaries
The auxiliary inputs must always form a closed loop circuit. If the loop is ever open, the alarm will sound. If
an auxiliary input is sounding, the trouble can be isolated between the alarm and the circuit by disconnecting
the circuit from the terminal block in the alarm box and replacing it with a jumper (See Section11.8). If the
corresponding auxiliary input still causes an alarm condition, the problem is in the PCB circuitry, otherwise
the wiring is the culprit.
9.
Controller Installation and Setup
9.1
Tools Required
Mini Screwdriver
Standard Screwdriver
Wire Strippers
9.2
Installation Instructions
1. Unpack system, and check that all components are present.
Qty
Description
Qty
1
Description
S3
1
Local Net Cable
3
Temperature Sensors
1
Back-Up Cable
1
Manual
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
26 of 42
2. Hang S3 with four screws.
3. Make sure all power supplies are disconnected before breaking any wires, or reaching into the
system enclosure.
4. Open the S3 and find all connections. Refer to wiring diagrams in Section 11 of this manual.
5. Run temperature sensors out to locations inside the house. Be sure that the sensors are in a safe
location, free from any temperature influences (direct sunlight, water, etc.) Use care when
securing sensor wires so that the wire is not accidentally cut. Any short, or break in the wire will
cause improper sensor operation. Next, run the wires into the enclosure via the watertight
connector at the bottom of the box. The wires should be cut off and stripped. They next should
be attached to the terminal block in the positions marked Sen 1, Sen 2 and Sen 3. Note that the
sensors are not polarity sensitive, and it therefore makes no difference as to which wire goes to
which sensor terminal.
6. After the siren is mounted, it should be wired into the control box. This is done at the terminal
block locations labeled siren red and siren white. Note that polarity is important here and that the
red siren wire must be connected into the siren red terminal block position and the same for the
white wire. Note also, any 12VDC device that uses less than 1.5 Amps of current could be
connected in the siren’s place.
7. Connect wires from Alarm terminals to the alarm circuit or relay box. (See wiring diagrams in
Section 11.7 for locations of terminals.)
8. If using a modem, connect wires from Modem terminals to the modem circuit or relay box. (See
wiring diagrams in Section 11.7 for locations of terminals.)
9. If necessary, connect the S3 to the Cumberland Farm Manager Network. (See the connections in
Section 11.10 of this manual.)
10. Connect the AUX and CONTROL AUX connections. Refer to Section 11.8 diagram.
11. Remove jumpers for AUX & CONTROL connections if being used.
12. If connecting to an EV 3000/3001 controller, connect Local Net and Back-Up Network setting in
Evolution controller (Plus models ONLY).
13. Wire Stage to Relay Card for Back-Up operation.
14. Set Stage Jumpers on Relay Cards in S3 or EV 3000/3001. Refer to Section 11.6 diagram.
15. Connect Vent/Tunnel Overrides.
16. Connect AC Power. Refer to Section 11.3 diagram.
17. Program the S3. Refer to Section 5.
9.3
Sensor Recommendations
It is important to note the Cumberland temperature sensors are fabricated using thermistors and are not
interchangeable with sensors commonly used on controllers from other manufacturers. The three temperature
sensors may be installed in a variety of ways. It is recommended that a sensor be located high enough from
the floor so that livestock or poultry can not peck at it. It is also essential that the sensor not be hung in front
of heaters, fans or other devices that would cause false readings. If a sensor is to be run from one building to
another, it is recommended that the connection be made with underground-rated wire buried between the two
structures. This recommendation is to reduce the effects of lightning.
Once again, the temperature sensors should be dropped as low in the house as possible while still being out
of reach of the livestock or poultry. And, as discussed earlier, it is recommended that the operator press the
Test button for ten to fifteen seconds at least twice a week to verify the operation of the alarm as well as to
condition the livestock or poultry to the sound of the siren.
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
27 of 42
10.
Maintenance
Check the calibration of your temperature sensors at least once per quarter. You will need to have two people, one
at the sensor with a trusted thermometer, and one at the controller to calibrate the sensor.
11.
Wiring Diagrams, Schematics, etc.
The following diagrams the S3 circuit board connections and how the S3 is connected to external equipment.
11.1 S3 Internal Electrical Wiring
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
29 of 42
11.3 Connecting AC Power to the S3
Secondary Sensing System
Inset A
Inset A
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
30 of 42
11.4 Connecting Sensors to the S3
White/
Shield
Sen 3
Black
Black
Sen 2
White/
Shield
White/
Shield
Sen 1
Black
Inset A
SENSOR
SENSOR
SENSOR
White / Shield
White / Shield
White / Shield
Black
Black
Black
Inset A
Secondary Sensing System
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
31 of 42
11.5 S3 PowerTrak Override Settings and Wiring
PowerTrak
Inset A
Vent Override
for Fail-Safe
Action
INLET
MODE
Vent Override
Cool 1
Tunnel Override
Cool 3
Vents & Tunnel Will Wire The Same
NOTE: If curtain is setup to pull curtain up to open, then reverse wires
connected to 'Open' and 'Close' terminals.
Inset B
Tunnel Override
Inset A
Vents Override
PowerTrak
Inset B
PowerTrak
Inset B
Inset A
Vent Override
for Normal
Action
Refer to
Section 5.1
P5 & P6
Settings
Secondary Sensing System
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
32 of 42
11.6 S3 Relay Card Wiring
Secondary Sensing System
Inset A
Relay Card
Relay Card
Wire
Terminals
NOTE: Ensure the Relay Card connector
and the PCB header are properly
aligned during stand-off and Relay
Card installation.
NOTE: The Relay Card is necessary on
Stand-Alone systems ONLY. If
S3 is used in conjunction with
Evolution 3000/3001, this relay
card is optional.
Header Connection
For Relay Card
Six Stand-Off
Attachment Holes
Inset A
Relay Card
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
33 of 42
11.7 Connecting an Alarm or Siren to the S3
Inset A
White
Red
NO
NC
Com
Alarm Out
Siren
Internal
Switch
(Non-alarm)
position
Connect to alarm,
modem, auto-
dialer,etc. as
desired.
White (-)
Red (+12V)
Siren
Inset A
Secondary Sensing System
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
34 of 42
11.8 Connecting Auxiliary Inputs to the S3
Inset B
Inset A
NOTE:
The jumper across J6, J8 and\or J10 must be removed if
an external alarm input is connected.
Secondary Sensing System
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
35 of 42
11.9 Connecting Other Cumberland Controllers to the S3 Auxiliary Input
The diagram below shows the proper way to connect the Cumberland family of auxiliary alarm
outputs to the S3 auxiliary inputs. The alarm activates when the connection is broken between
the OUT and IN terminals.
NOTE 1: As long as a path for current flow is present, the Secondary Sensing System is not
activated. Consequently, if one controller alarms, the path will be broken and the
alarm will be activated.
NOTE 2: Remove the jumper between the OUT and IN terminals when installing external
alarm inputs.
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
36 of 42
11.10 Connecting Local Network Connections to the S3
Warning!
Tape Shield To Prevent Damage!
NOTE:
Harness to connect Local Network and Secondary Sensing system
together are connected & included in the Secondary Sensing System
and 16 Stage Expansion units.
Back-Up
System
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
37 of 42
11.11 Connecting the S3 to the HH.Net
Inset B
Inset A
Secondary Sensing System
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
38 of 42
12.
Replacement and Optional Parts
Controls
6450-5089
/KIT FH-AL to S3 upgrade
6607-8013
EV S3 Plus
6607-8014
EV S3
Replacement Parts
6407-0616
/DOOR ASSY S3
6407-6038
/EV-S3 Stand Alone Relay Card (PCB161)
3014-2174
Battery 12V 5.0 Ah
3006-3115
CONN SKT CLIP (For Tunnel/Vent Relays)
3006-5077
CONN Terminal Block 3 pos
3006-5078
CONN Terminal Block 4 pos
3006-5079
CONN Terminal Block 5 pos
3006-5092
CONN Terminal Block 6 pos
3540-0149
DIGITAL_IC LTC1483CN8 (Network Chips)
3010-2991
FUSE 3 AMP 5mmX20mm slowblow (F1 & F2)
3701-6066
PIC S3 (Processor)
3015-1560
RLY AZ755-1C-12DE (Relay For Tunnel/Vent)
3008-2860
XFMR FD7-16 120/240-16VAC 56VA (Transformer)
Sensors and Wire
1503-2427
CBL SJT 18-2 Yellow (sensor)
6407-6084
/Temperature Sensor Junction Box Assy
Siren/Dialer
3016-1380
SIREN 12 VDC 1 AMP cont/warb
6607-6000
Voice Dialer AVD-45B
Manuals
4801-2997
MANUAL S3
4801-5307
MANUAL Evolution 3000\3001
4801-5331
MANUAL Evolution 1200
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
39 of 42
13.
Temperature vs. Sensor Resistance Table
The following chart gives the resistance when measured between the white and black sensor wires at a
given temperature. To check a sensor, first know the temperature in the area, then, use a multi-meter to
check the resistance.
Resistance
Temp
Temp
Resistance
Temp
Temp
Resistance
Temp
Temp
Kohms
(F)
(C)
Kohms
(F)
(C)
Kohms
(F)
(C)
32.654
32
0
15.714
59
15
8.59
83.3
28.5
32.158
32.5
0.3
15.568
59.4
15.2
8.517
83.7
28.7
31.671
33.1
0.6
15.353
59.9
15.5
8.408
84
28.9
31.191
33.6
0.9
15.211
60.3
15.7
8.336
84.6
29.2
30.72
34.2
1.2
15.001
60.8
16
8.23
85.1
29.5
30.257
34.7
1.5
14.863
61.2
16.2
8.125
85.6
29.8
29.802
35.2
1.8
14.658
61.7
16.5
8.056
86
30
29.355
35.8
2.1
14.457
62.2
16.8
7.954
86.5
30.3
28.915
36.3
2.4
14.325
62.6
17
7.853
87.1
30.6
28.482
36.9
2.7
14.128
63.1
17.3
7.787
87.4
30.8
28.057
37.4
3
13.999
63.5
17.5
7.689
88
31.1
27.777
37.8
3.2
13.808
64
17.8
7.592
88.5
31.4
27.363
38.3
3.5
13.682
64.4
18
7.496
89.1
31.7
26.957
38.8
3.8
13.496
64.9
18.3
7.433
89.4
31.9
26.557
39.4
4.1
13.373
65.3
18.5
7.34
90
32.2
26.164
39.9
4.4
13.192
65.8
18.8
7.248
90.5
32.5
25.777
40.5
4.7
13.073
66.2
19
7.157
91
32.8
25.523
40.8
4.9
12.896
66.7
19.3
7.098
91.4
33
25.147
41.4
5.2
12.779
67.1
19.5
7.009
91.9
33.3
24.777
41.9
5.5
12.607
67.6
19.8
6.922
92.5
33.6
24.413
42.4
5.8
12.493
68
20
6.836
93
33.9
24.055
43
6.1
12.325
68.5
20.3
6.779
93.4
34.1
23.82
43.3
6.3
12.215
68.9
20.5
6.695
93.9
34.4
23.472
43.9
6.6
12.051
69.4
20.8
6.612
94.5
34.7
23.13
44.4
6.9
11.943
69.8
21
6.531
95
35
22.793
45
7.2
11.783
70.3
21.3
6.45
95.5
35.3
22.572
45.3
7.4
11.678
70.7
21.5
6.371
96.1
35.6
22.244
45.9
7.7
11.522
71.2
21.8
6.319
96.4
35.8
21.922
46.4
8
11.42
71.6
22
6.241
97
36.1
21.71
46.8
8.2
11.268
72.1
22.3
6.165
97.5
36.4
21.397
47.3
8.5
11.168
72.5
22.5
6.089
98.1
36.7
21.088
47.8
8.8
11.02
73
22.8
6.015
98.6
37
20.886
48.2
9
10.874
73.6
23.1
5.941
99.1
37.3
20.586
48.7
9.3
10.778
73.9
23.3
5.869
99.7
37.6
20.29
49.3
9.6
10.636
74.5
23.6
5.798
100.2
37.9
20.096
49.6
9.8
10.542
74.8
23.8
5.728
100.8
38.2
19.809
50.2
10.1
10.404
75.4
24.1
5.658
101.3
38.5
19.526
50.7
10.4
10.312
75.7
24.3
5.59
101.8
38.8
19.34
51.1
10.6
10.177
76.3
24.6
5.522
102.4
39.1
19.065
51.6
10.9
10.088
76.6
24.8
5.456
102.9
39.4
18.884
52
11.1
9.956
77.2
25.1
5.39
103.4
39.7
18.616
52.5
11.4
9.869
77.5
25.3
5.326
104
40
18.352
53.1
11.7
9.741
78.1
25.6
5.262
104.5
40.3
18.179
53.4
11.9
9.614
78.6
25.9
5.199
105.1
40.6
17.503
54.9
12.7
9.53
79
26.1
5.137
105.6
40.9
17.339
55.2
12.9
9.407
79.5
26.4
5.076
106.2
41.2
17.095
55.8
13.2
9.325
79.9
26.6
4.995
106.9
41.6
16.856
56.3
13.5
9.205
80.4
26.9
4.936
107.4
41.9
16.698
56.7
13.7
9.086
81
27.2
4.877
108
42.2
16.465
57.2
14
9.007
81.3
27.4
4.82
108.5
42.5
16.312
57.6
14.2
8.891
81.9
27.7
4.763
109
42.8
16.085
58.1
14.5
8.815
82.2
27.9
4.688
109.8
43.2
15.935
58.5
14.7
8.702
82.8
28.2
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
40 of 42
14.
Error Codes
The controller records errors based on the communications links. When errors occur, an alarm will be generated.
Error Codes for the Evolution S3
Error Code
Description
Explanation
LnE
Local Network Error
The Back-Up has lost Communications with the Master Controller.
NOTE: During this condition the Back-Up will run Cool 1 on a 5
minute timer.
LnO
Local Network
Override Error
The Master Controller has lost communications with one or more of the
Stage Units (PCB 168) connected to it. In this condition the Back-Up
takes control over the stages.
15.
S3 Program Label
Manual No. 4801- 2997 Rev 1-15
Secondary Sensing System
41 of 42
Limited Warranty
16.
Warranty
The GSI Group, LLC. (“GSI”) warrants products which it manufactures to be free of defects in materials and
workmanship under normal usage and conditions for a period of 12 months after sale to the original end-
user or if a foreign sale, 14 months from arrival at port of discharge, whichever is earlier. The end-user’s
sole remedy (and GSI’s only obligation) is to repair or replace, at GSI’s option and expense, products that in
GSI’s judgment, contain a material defect in materials or workmanship. Expenses incurred by or on behalf
of the end-user without prior written authorization from the GSI Warranty Group shall be the sole
responsibility of the end-user.
Warranty Extensions: The Limited Warranty period is extended for the following products:
Product
Warranty Period
AP Fans and
Flooring
Performer Series Direct Drive
Fan Motor
3 Years
All Fiberglass Housings
Lifetime
All Fiberglass Propellers
Lifetime
AP/Cumberland
Flex-Flo/Pan Feeding Systems
2 Years
Cumberland
Feeding/Watering
Systems
Feeder System Pan Assemblies
5 Years **
Feed Tubes (1.75" & 2.00")
10 Years *
Centerless Augers
10 Years *
Watering Nipples
10 Years *
Grain Systems
Grain Bin Structural Design
5 Years
Grain Systems
Farm Fans
Zimmerman
Portable & Tower Dryers
2 Years
Portable & Tower Dryer Frames
and Internal Infrastructure †
5 Years
GSI further warrants that the frame, basket and excluding all auger and auger drive components of the portable and
tower dyer shall be free from defects in materials for a period of time beginning on the twelth (12th) month from the date
of purchase and continuing until the sixtieth (60th) month from the date of purchase (extended warranty period). During
the extended warranty period, GSI will replace the frame or basket components that prove to be defective under normal
conditions of use without charge, excluding the labor, transportation, and/or shipping costs incurred in the performance of
this extended warranty.
Conditions and Limitations:
THERE ARE NO WARRANTIES THAT EXTEND BEYOND THE LIMITED WARRANTY DESCRIPTION SET FORTH
ABOVE. SPECIFICALLY, GSI MAKES NO FURTHER WARRANTY OF ANY KIND, EXPRESS OR IMPLIED,
INCLUDING, WITHOUT LIMITATION, WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE OR USE IN CONNECTION WITH: (i) PRODUCT MANUFACTURED OR SOLD BY GSI OR (ii) ANY
ADVICE, INSTRUCTION, RECOMMENDATION OR SUGGESTION PROVIDED BY AN AGENT, REPRESENTATIVE
OR EMPLOYEE OF GSI REGARDING OR RELATED TO THE CONFIGURATION, INSTALLATION, LAYOUT,
SUITABILITY FOR A PARTICULAR PURPOSE, OR DESIGN OF SUCH PRODUCTS.
GSI shall not be liable for any direct, indirect, incidental or consequential damages, including, without limitation, loss of
anticipated profits or benefits. The sole and exclusive remedy is set forth in the Limited Warranty, which shall not exceed
the amount paid for the product purchased. This warranty is not transferable and applies only to the original end-user.
GSI shall have no obligation or responsibility for any representations or warranties made by or on behalf of any dealer,
agent or distributor.
GSI assumes no responsibility for claims resulting from construction defects or unauthorized modifications to products
which it manufactured. Modifications to products not specifically delineated in the manual accompanying the equipment
at initial sale will void the Limited Warranty.
This Limited Warranty shall not extend to products or parts which have been damaged by negligent use, misuse,
alteration, accident or which have been improperly/inadequately maintained. This Limited Warranty extends solely to
products manufactured by GSI.
Prior to installation, the end-user has the responsibility to comply with federal, state and local codes which apply to the location
and installation of products manufactured or sold by GSI.
* Warranty prorated from list price:
0 to 3 years – no cost to end-user
3 to 5 years – end-user pays 25%
5 to 7 years – end-user pays 50%
7 to 10 years – end user pays 75%
** Warranty prorated from list price:
0 to 3 years – no cost to end-user
3 to 5 years – end-user pays 50%
† Motors, burner components and
moving parts not included. Portable
Dryer screens included. Tower Dryer
screens not included.