DSE 7560 Installation Instructions

Text of the manual

D E E P S E A E L E C T R O N I C S

7 5 6 0 I N S T AL L AT I O N I N S T R U C T I O N S 053-054 ISSUE 4 ACCESSING THE FRONT PANEL CONFIGURATION EDITOR. • Press the Stop/Reset and Info buttons simultaneously. • If a module security PIN has been set, the PIN number request is then shown : • Press (up) or (down) to adjust it to the correct value. • Press (right) when the first digit is correctly entered. The digit you have just entered will now show ‘#’ for security. • Repeat this process for the other digits of the PIN number. You can press (left) if you need to move back to adjust one of the previous digits. • When is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct, you must re-enter the PIN. • If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is displayed : EDITING A PARAMETER • Enter the editor as described above. • Press the left or right buttons to cycle to the section you wish to view/change. • To edit the parameter, press to enter edit mode. The parameter begins to flash to indicate that you are editing the value. • Press the up or down buttons to change the parameter to the required value. • Press to save the value. The parameter ceases flashing to indicate that it has been saved. • To exit the editor at any time, press the button. Deep Sea Electronics Plc. Tel:+44 (0)1723 890099 Fax: +44 (0)1723 893303 LO CALL (from UK BT landlines) : Telephone 0845 260 8933 Email: [email protected] Web: www.deepseaplc.com Deep Sea Electronics inc. Phone: +1 (815) 316-8706 Fax: +1 (815) 316- 8708 TOLL FREE (USA only) : Tel: 1 866 636 9703 Email: [email protected] Web: www.deepseausa.com Deep Sea Electronics Plc. (Far East) Tel:+66 (0) 2191 8052 Fax: +66 (0) 81805 5625 Email: [email protected] Web: www.deepseaplc.com NOTE: When the editor is visible, it is automatically exited after 5 minutes of inactivity to ensure security. NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to ensure security. NOTE: More comprehensive module configuration is possible using the 75xx series PC configuration software. Please contact us for further details NOTE: The contents of the tables overleaf may differ depending on the actual module configuration. TYPICAL WIRING DIAGRAM

Front Panel Configuration Editor (Factory default settings are shown in bold italicised text)

Section Parameter as shown on Values Timers Mains Transient Delay 0 -10s (2s) Start Delay 0– 60m (5s) Transfer Delay 0– 10s (0.7s) Return Delay 0– 60m (30sa0 Low battery Delay 0– 10m (1m) High battery Delay 0– 10m (1m)` Mains Mains Under Voltage Alarm 50V-360V ph-N (184V) (184V) (184V) (184V) Mains Over Voltage Alarm 50V-360V ph-N (276V) (276V) (276V) (276V) Mains Under Frequency 0Hz-75Hz (45Hz) (45Hz) (45Hz) (45Hz) Mains Over Frequency 0Hz-75Hz (55Hz) (55Hz) (55Hz) (55Hz) System Plant Battery Under Volt Alarm 0-40V (10V) (10V) (10V) (10V) Plant Battery Over Alarm 0-40V (30V) (30V) (30V) (30V) Misc Language English, Other Alternative Frequency Enable Disable Disable Disable Disable Alternative Voltage Enable Disable Disable Disable Disable AC System 3 phase 4 wire 3 phase 4 wire 3 phase 4 wire 3 phase 4 wire Single phase 2 Wire 3 phase 3 wire 2 phase 3 wire L1 & L2 3 phase 4 wire ED 2 phase 3 wire L1 & L3 Contrast � l � Date and Time dd mmm yyyy hh:mm Auto Scroll Time 0-10s (2s) (2s) (2s) (2s) Mains CT Primary Rating 5A- 6000A (600A) (600A) (600A) (600A) Mains CT Secondary Rating 1A, 5A (5A) (5A) (5A) (5A) Load Ramp Rate 0.1%-100% (2.0%) 2.0%) 2.0%) 2.0%) (% per sec) ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR • The ‘running’ editor can be entered while the engine is running. All protections remain active if the engine is running while the running editor is entered. • Press and hold the button to enter the running editor. EDITING A PARAMETER • Enter the editor as described above. • Press the left or right buttons to cycle to the section you wish to view/change. • Press the up or down buttons to change the parameter to the required value. • To save paremeters scroll to `save changes and exit followed by the down buttton • To cancel changes scroll to `Abandon changes and exit followed by the down button ADJUSTABLE PARAMETERS (Running editor) Running Editor Section Parameter as shown on display Factory Settings DISPLAY Contrast � l � Language English Load power factor % Load parallel power % Enable commissioning screens No Voltage adjust (manual mode only engine running bus breaker open) Raise Steady Lower Frequency adjust (manual mode only engine running bus breaker open) Raise Steady Lower Enable mains decoupling No Abandon changes and exit Save changes and exit DIMENSIONS 240.0mm x 181.1mm x 41.7mm (9.4” x 7.1” x 1.6”) PANEL CUTOUT: 220mm x 160mm (8.7” x 6.3”)

Other Switch Manuals