EVAX 25 Installation Manual
Text of the manual
Installation Manual: EVAX 25/50/100/150/200 Voice Evacuation System
NOTICE TO THE INSTALLER
This manual provides an overview and the installation instructions for the EVAX 25/50/100/150/200 Voice Evacuation Interface System.
All terminals are power limited and should be wired in accordance with the requirements of NFPA 70 (NEC), NFPA 101 (Life Safety
Code) a
INSTALLATION MANUAL: EVAX 25/50/100/150/200
5403670 Rev A 12/17
Evax by Potter • Phone: (888) 382-9835 • www.evax.com
PAGE 2 OF 8
4.
Connect FACP signaling circuit to TB1 - 3(+) & 4(-), Alarm Polarity (alarm polarity is shown).
5.
Connect 120 VAC, 60 Hz, power to the white Terminal Block on the l
INSTALLATION MANUAL: EVAX 25/50/100/150/200
5403670 Rev A 12/17
Evax by Potter • Phone: (888) 382-9835 • www.evax.com
PAGE 3 OF 8
Factory Default Switch/Jumper Settings:
SN1
SN2
1 = OFF 25V
1 = OFF
2 = OFF
2 = ON
3 = OFF
3 = OFF Std. Evac Message
4 = OFF Normal Op
4 = OFF
5 = OFF Do Not Use
5 = O
INSTALLATION MANUAL: EVAX 25/50/100/150/200
5403670 Rev A 12/17
Evax by Potter • Phone: (888) 382-9835 • www.evax.com
PAGE 4 OF 8
EVAX 25 / 25E
EVAX 50 / 50E
EVAX 100 / 100E
Primary Input Voltage
240 Vac @ 50 Hz
240 Vac @ 50 Hz
240 Vac @ 50 Hz
Primary Input Current
0.4 A @ 240 Vac
0.27 A @ 240 Va
INSTALLATION MANUAL: EVAX 25/50/100/150/200
5403670 Rev A 12/17
Evax by Potter • Phone: (888) 382-9835 • www.evax.com
PAGE 5 OF 8
TB1
1
2
3
4
5
6
7
8
TB3
1
2
3
4
5
6
7
8
TB2
1
2
3
4
5
6
7
8
9
10
11
Input Power connection is
Non-Power Limited.
DO NOT route any Power
Limited wiring within ¼" of
In