IBM 3708 Planning And Installation
Text of the manual
Fourth Edition (February 1988)
This edition obsoletes GA27-3766-2.
Changes are made periodically to the information herein; before using this publication in connection with the
operation of IBM systems or equipment, consult the latest IBM System/370, 30xx and 4300 Processors
Bibliography, GC20-0001; System/38 Bibliography, GH30-0233; and 8100 Bibliography, GC20-8100, for the
editions that are applicable and current.
Any reference to an IBM licensed program in this document is not intended to state or imply that only IBM's
licensed program may be used. Any functionally equivalent program may be used instead. It is possible that
this material may contain reference to, or information about, IBM products (machines and programs),
programming, or services that are not announced in your country. Such references or information .must not
be construed to mean that IBM intends to announce such IBM products, programming, or services in your
country.
Publications are not stocked at the address given below; requests for IBM publications should be made to
your IBM representative or to the IBM branch office serving your locality.
A form for reader's comments is provided at the back. of this publication. If the form has been removed,.
comments may be addressed to IBM Corporation, Communication Products Information Development;
Department E02, P.O. Box 12195, Research Triangle Park, North Carolina, U.S.A. 27709. IBM may use or
distribute any of the information you supply in any way it believes appropriate without incurring any
obligation wha~ver .. You may, of course, continue to use the information you supply.
©Copyright 1986,1987,1988
Federal Communications Commission (FCC) Statement
Warning: This equipment generates, uses, and can radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may cause interference to radio communications. It has been
tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15
of FCC rules, which are designed to provide reasonable protection against such interference when operated in
a commercial environment. Operation of this equipment in a residential area is likely to cause interference in
which case the user at his own expense will be required to take whatever measures may be required to correct
the interference.
Instructions to User: In many instances, shielded cables and connectors must be used for connection to
peripherals. Proper IBM cables are available from authorized dealers. The manufacturer is not responsible
for any radio or television interference caused by using other than the recommended cables or by
unauthorized modifications to this equipment; it is the responsibility of the user to correct such interference.
If necessary, the user should consult the dealer or an experienced radio/television technician for additional
suggestions. The user may find the following booklet prepared by the Federal Communications Commission
helpful:
How to Identify and Resolve Radio-TV Interference Problems
This booklet is available from the following:
FOB Public Contact Branch
Room 725
1919 M St. NW
Washington, DC 20554
Tele. (202) 634-1940
Consumer Assistance and
Small Business Division
Room 254
1919 M St. NW
Washington, DC 20554
Tele. (202) 632-7000
The information in this document is current as of the date of its publication but is subject to change by IBM
at any time without notice.
The cable information contained in this document is not intended to be a specification for cable structures
and/or cable connectors and all liability for patent infringements due to manufacture use or sale of cables
and/or connectors in accordance with this document is expressly disclaimed by IBM. No license express or
implied is intended or granted under any patents of IBM or others to make, use, sell, or combine these
structures and/or connector structures alone or in combination with any other devices. Proper operation of
the cable as well as quality ormanufacture are the responsibility of the user and the selected supplier.
This manual contains several trademarks and registered trademarks. Viewpoint is a registered trademark of
Applied Digital Data Systems, Inc. Beehive is a trademark of Beehive International. Dasher is a registered
trademark of the Data General Corporation. DEC is a registered trademark of the Digital Equipment
Corporation. ESPRIT I and ESPRIT II are trademarks of Esprit Systems, Inc. FALCO 500 is a registered
trademark of Falco Data Products, Inc. Dumb Terminal is a registered trademark of Lear Siegler, Inc.
Displayphone is a trademark of Northern Telecom, Inc. TeleVideo is a registered trademark ofTeleVideo
Systems, Inc. WY-50 is a registered trademark ofWyse Technology.
iii
About This Book
This book contains planning and installation information about the IBM 3708
Network Conversion Unit.
This information is for people who plan for and install the 3708. To use the
information, you should be familiar with the following:
• American National Standard Code for Information Interchange (ASCII)
• Asynchronous (start-stop) devices
• IBM 3270 Information Display System
• Systems Network Architecture (SNA).
It is recommended that you read the information in the planning chapters before
installing the 3708. If the configuration planning and site preparation are complete,
begin with the procedures in "Installing the 3708."
How This Book Is Organized
This book is divided into three parts:
"Introducing the 3708" contains the following chapters:
• Chapter 1, "The 3708 and Its Advantages" provides general information about
the 3708.
• Chapter 2, "Operating Mode Functions" describes the functions that the 3708
provides in protocol conversion, protocol enveloping, and ASCII pass-through
modes.
• Chapter 3, "Host and ASCII Device Interfaces" describes the connections
between the 3708 and the hosts, and between the 3708 and the ASCII end-user
devices;
"Planning for the 3708" contains the following chapters:
• Chapter 4, "Planning Checklist" provides a planning checklist and planning
forms.
• Chapter 5, "Planning for Installation" describes the physical requirements for
installing the 3708.
• Chapter 6, "Planning for Service" provides service and warranty information
for the 3708.
• Chapter 7, "Planning for Microcode Updates" describes the 3708 microcode
update procedure.
• Chapter 8, "Planning for Central Site Configuration" provides planning
information for IBM 3708 Network Conversion Unit Feature 3525 (pluggable
Cartridge with Central Site Configuration).
About This Book
V
• Chapter 9; "Planning for File Transfer" describes supported file transfer
programs.
• Chapter 10, "Planning for Cables" provides information to help you plan for
the cables and the cable connections for the 3708.
• Chapter 11, "Ordering the 3708" describes items that can be ordered for the
3708.
"Installing the 3708" contains the following chapters:
• Chapter 12, "Installation Procedures" explains how to configure the 3708 ports
for SNA and ASCII hosts and for end-user devices.
• Chapter 13, "Configuration Procedures" describes the screen sequences that are
used for configuring the 3708.
• Chapter 14, "Defining the General Definition" describes the "General
Definition" screen.
• Chapter 15, "User-Defined Terminal Tables" describes user-defined terminal
tables and explains how to create new ones.
• Chapter 16, "Converting Between Standard and Enhanced UDTs" explains how
to convert standard terminal tables to enhanced, and vice versa.
• Chapter 17, "Creating a User-Defined Translate Table" describes user-defined
translate tables and explains how to create new ones.
This manual also contains 14 appendixes:
• Appendix A, "IBM-Supplied Configuration"
• Appendix B, "3708 Configuration Example"
• Appendix C, "3708 Configuration Forms"
• Appendix 0, "Cable Requirements"
• Appendix E, "Screen Sequences"
• Appendix F, "3708 Control Terminal Messages"
• Appendix G, "Default Terminal Tables"
• Appendix H, "Predefined User-Defined Terminal Tables and Keyboard
Mappings"
• Appendix I, "Terminal Switch Settings"
• Appendix J, "Terminal XON/XOFF Pacing Support"
• Appendix K, "Manuals for Default Protocol Conversion Displays"
• Appendix L, "IBM-Supplied Translate Tables"
• Appendix M, "End-User-Device Reference Cards Order Form"
• Appendix N, "Binary to Hexadecimal Conversion Table."
vi
3708 Planning and Installation
Related 3708 Library Publications
The following lists manuals and information for the 3708:
• IBM 3708 Network Conversion Unit Setup, GA27-3611, is shipped with the 3708
and describes how to set up and test the 3708, how to handle setup problems,
and how to prepare the 3708 for relocation.
• IBM 3708 Network Conversion Unit Description, GA27-3768, describes the
external interfaces and operational characteristics of the 3708.
• IBM 3708 Network Conversion Unit Problem Determination, GA27-3767,
provides procedures for solving 3708 problems.
• Unpacking instructions are printed on the 3708 shipping carton and show how
to unpack the 3708.
• IBM 3708 Network Conversion Unit Problem Report, GA27-3638, which is
shipped with the 3708, provides a means of recording problem diagnosis
information that is used by repair center representatives.
• IBM 3708 Network Conversion Unit End-User Reference, GA27-3765, describes
the procedures for operating terminals attached to the 3708.
• IBM 3708 Network Conversion Unit Registration Address Form is shipped with
the 3708. This form must be completed and returned to IBM for you to
automatically receive notification of changes in the 3708 microcode.
• IBM 3708 reference cards describe the keyboard functions of ASCII displays
that can be connected to a 3708 and describe the general procedures for terminal
users. See Appendix M, "End-User-Device Reference Cards Order Form," for
a list of the end-user devices and the 3708 reference card order numbers.
Service Information
For service on 3708 hardware and microcode problems, call the following number in
the United States or Puerto Rico:
1 800 428-2569 (toll free)
In other countries, call the appropriate support group.
About This Book vii
Changes Since the Last Edition
This edition contains the following new information:
• Descriptions of enhanced terminal support
IBM 3270 Model 2, 3, 4, and 5 emulation
-
Customized UDT names
-
Customized Terminal Logon Initialization Sequence.
• Default terminal tables and switch settings for the following terminals:
IBM 3151
-
FALCO-500®
-
WY-50®.
• A description of a new host port inactivity time out option
• A description of a new printer capability option, "Perform Newline at Begin
Bracket (LU_3)"
• Descriptions of additional support in the non-standard operations field.
Changes Since the Last Edition ix
Introducing the 3708
Chapter 1. The 3708 and Its Advantages ...................... .
Overview
........................................ .
Physical Description .................................. .
Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Network Configurations ............................. .
Control Terminal
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Summary of Advantages ........
....... . . . . . . . . . . . . .
Chapter 2. Operating Mode Functions
. . . . . . . . . . . . . . . . . .
Protocol Conversion .......................... .
Protocol Enveloping .......................... .
ASCn Pass-Through ................................. .
Function Summary .......................... .
Chapter 3. Host and ASCn Device Interfaces . . . . . . . . . . . .
SNA Hosts ............................... .
ASCn Hosts .............................. .
Ascn End-User Devices
1-1
1-1
1-1
1-2
1-2
1-4
1-5
2-1
2-1
2-4
2-4
2-5
3-1
3-1
3-2
3-2
Planning for the 3708
Chapter 4. Planning Checklist ...................... .
Planning Configuration Parameters
. . . . . . . . . . . . . . . . .
Device Information Form ........................ .
Network Planning Form ....................... .
Port Definition Form ......................... .
Chapter 5. Planning for Installation
Specifications and Location Requirements
Interface Requirements ......... .
Power Requirements ........... .
Safety and Security Consid,erations .. .
Chapter 6. Planning for Service ..................... .
Reviewing the Service and Warranty Options ............. .
Calling for Service ............................. .
4-1
4-2
4-3
4-4
4-5
5-1
5-1
5-2
5-2
5-5
6-1
6-1
6-3
Chapter 7. Planning for Microcode Updates ..................... 7-1
How to Register ..................................... 7-1
What to Expect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..
7-1
How to Order ...................................... 7-1
What to Do with Outdated Cartridges ........................ 7-2
Chapter 8. Planning for Central Site Configuration ................ 8-1
IBM 3708 Pluggable Cartridge with Central Site Configuration ......... 8-1
Hardware Requirements ................................ 8-2
Software Requirements ................................. 8-2
Contents xi
Installing the 3708
Software Options that Enhance CSC
3708 Configuration Requirements ..
Modem Configuration Requirements
Technical Assistance ..... .
Ordering Information ........ .
8-3
8-4
8-5
8-5
8-5
Chapter 9. Planning for File Transfer ...................
9-1
IBM PC/HOST File Transfer and Terminal Emulator Program ......... 9-1
Personal Services/PC .......................
9-3
A User-Written File Transfer Program ........................ 9-3
Chapter 10. Planning for Cables
.......... .
· . . . . . . . . . .. 10-1
Cable Descriptions ...................... .
· . . . . . . . . . .. 10-1
Examples of 3708 Cable Connections ....... .
· ........... 10-2
3708 Connection to the IBM Cabling System .. .
3708 Problems Related to Cables or Equipment
· . . . . . . . . .. 10-11
. . . . . . . . . . .. 10-12
Chapter 11. Ordering the 3708
Order Forms .......... .
11-1
11-1
Chapter 12. InstaUation Procedures ...............
12-1
Step 1. Testing the 3708 .....................
12-2
Step 2. Setting Up the Control Terminal
. . . . . . . . .
12-4
Step 3. Logging onto the Control Terminal
.........
. . . . .. 12-5
Step 4. Entering the Configuration Data ...........
. . . . .. 12-9
Step 5. Activating the Configuration ......................... 12-9
Step 6. Ending the Control Terminal Session . . . . . . . . . . . . . . . . . .. 12-10
Step 7. Connecting the Cables
. . . . . . . . . . . . . . . . . . . . . . .. 12-13
Chapter 13. Configuration Procedures ........................ 13-1
Defining a Port for a SNA Host ........................... 13-2
Defining a Port for an ASCII Host .....................
13-10
Defining a Port for an End-User Device ...................... 13-15
What To Do Next ................................... 13-35
Protocol Enveloping Definition for an End-User Device (Screen CI23.4)
13-36
Defining the Printer Authorization Matrix ...............
13-41
Chapter 14. Defining the General Definition
General Definition (Screen CI27.1) ....
Chapter 15. User-Defined Terminal Tables
Standard and Enhanced Terminal Tables
Creating a User-Defined Terminal Table
Looking at the Terminal Table Format
Chapter 16. Converting Between Standard and Enhanced UDTs '"
Converting Standard to Enhanced
. . . . . . . . . . . . . . . . . . .
Converting Enhanced to Standard .............. .
Chapter 17. Creating a User-Defined Translate Table ... .
Looking at the Translate Table Format ................ .
Defining a New Translate Table ..................... .
14-1
14-1
15-1
15-1
15-2
15-3
16-1
16-3
16-3
17-1
17-1
17-2
xii
3708 Planning and Installation
Appendix A. IBM-Snpplied Configuration ...................... A-I
PORTS 1 through 5 ................................... A-I
PORTS 6 through 9 ................................... A-3
PORT 10 ......................................... A-4
Appendix B. 3708 Configuration Example ...................... B-1
Ports Configured for Hosts ............................... B-3
Ports Configured for Terminals Only ......................... B-5
Ports Configured for Multiple LUs .......................... B-9
Ports Configured for Printers Only ......................... B-13
Appendix C. 3708 Configuration Forms ....................... C-l
End-User Device Definitions .............................. C-2
Host Definitions ..................................... C-4
Appendix D. Cable Requirements ........................... D-l
Section 1. 3708 EIA 232C Interface Cables from IBM .............. D-l
Section 2. Minimum Connections Required for IBM 3708 EIA 232C Cable
D-6
Section 3. IBM 3708 EIA 422A Interface Cables ................ D-I0
Section 4. IBM 3708 EIA 422A Interface to IBM Cabling System ...... D-13
Appendix E. Screen Sequences
............................ E-l
SNA Hosts ........................................ E-l
ASCII Hosts ....................................... E-2
Printers .......................................... E-3
Displays, Protocol Conversion Only ......................... E-4
Displays, Protocol Enveloping Only or Dynamic .................. E-5
Displays with Printers, Protocol Conversion Only ................. E-6
Display with Printer, Dynamic
............................ E-7
Appendix F. 3708 Control Terminal Messages ................... F-l
Unnumbered Messages ................................. F-l
Numbered Messages ................................... F-3
Appendix G. Default Terminal Tables ........................ G-i
ADDS (Applied Digital Data Systems) Viewpoint® ................ G-1
Beehive™ ATL-078 ................................... G-6
Data General Dasher® D210 Display Terminal ................. G-l1
DEC® Model VT52 .................................. G-16
DEC® Models VT100 (or VT220 Emulating a VT100) ............. G-21
DEC® Model VT220 ................................. G-26
FALCO 500® (Emulating a DEC® Model VT220) ............... G-31
Hazeltine Esprit ITM and Esprit IITM ........................ G-36
Hazeltine 1500 ..................................... G-4l
Hewlett-Packard 2621B Interactive Terminal ................... G-46
IBM PC/FTTERM Color .............................. G-51
IBM PCfFTTERM Monochrome .......................... G-56
IBM 3101 and IBM PC in 3101 Emulation Mode ................ G-61
IBM 3151/62 (Model 5 Emulation) ......................... G-66
IBM 3151, 3161, 3162, and 3163 ASCII Display Stations ,........... G-71
IBM 3151/61/62/63 with 3708 Feature ....................... G-76
IBM 3164 ASCII Display Station .......................... G-81
IBM 3164 with 3708 Feature ............................. G-86
COntents xiii
Lear Siegler ADM 3A Dumb Terminal® .................... .
Northern Telecom Displayphone™ ........................ .
ROLM Cypress, Cedar, and Juniper ....................... .
Teletype 5410 Asynchronous Display Terminal and 5420 Buffered Display
TeleVideo® 910 ................................... .
TeleVideo® 950 ................................... .
WY-50® ........................................ .
G-91
G-96
G-lOl
G-106
G-ll1
G-116
G-121
Appendix H. Predefined User-Defined Terminal Tables and Keyboard Mappings H-l
ADDS (Applied Digital Data Systems) Viewpoint®/18 .............. H-l
Lear Siegler ADM 24E Video Display Terminal .................. H-7
Lear Siegler ADM 31 Intermediate Terminal™ Video Display Unit
H-12
TeleVideo® 912C ................................... H-17
Appendix I. Terminal Switch Settings ........................ .
ADDS Viewpoint® ................................... .
ADDS Viewpoint®/78
................................. .
Beehive™ ATL-078 ................................... .
Data General® D210 Display Terminal ....................... .
DEC® VT100 and VT52 ................................ .
DEC® VT220 (Emulating a VT100) ......................... .
DEC®VT220 ...................................... .
FALCO 500®
...................................... .
Hazeltine ESPRIT ITM
................................ .
Hazeltine ESPRIT IJTM ................................ .
Hazeltine 1500
1-1
1-2
1-3
1-4
1-5
1-6
1-7
1-8
1-9
1-10
1-11
1-12
Hewlett-Packard 2621B Interactive Terminal .................... 1-13
IBM PC/FTTERM (Color and Monochrome) ................... 1-14
IBM PC in 3101 Emulation Mode .......................... 1-15
IBM 3101 Models 10, 12, 13, 20, 22, 23 ....................... 1-16
IBM 3151 ASCII Display Station ........................... 1-17
IBM 3161 ASCII Display Station ............................ 1-19
IBM 3162 ASCII Display Station ........................... 1-21
IBM 3163 ASCII Display Station ........................... 1-23
IBM 3164 ASCII Display Station ........................... 1-25
Lear Siegler ADM 24E Video Display Terminal .................. 1-27
Lear Siegler ADM 3A Dumb Terminal® ...................... 1-29
Lear Siegler ADM 31 Intermediate Terminal™ Video Display Unit ...... 1-30
Northern Telecom Displayphone™ .......................... 1-31
ROLM® Cypress™, Cedar™, and JuniperTM .................... 1-32
Teletype 5410 Asynchronous Display Terminal ................... 1-33
Teletype 5420 Buffered Display ............................ 1-34
TeleVideo® 910 ..................................... 1-36
TeleVideo® 912C .................................... 1-37
TeleVideo® 950 ..................................... 1-38
WY-50® .......................................... 1-39
Appendix J. Terminal XONjXOFF Pacing Support ............... .
J-l
Appendix K. Manuals for Default Protocol Conversion Displays ......... K-1
Appendix L. mM-Supplied Translate Tables .................... L-l
Standard Default EBCDIC to ASCII Translate Table ............... L-2
Standard Default ASCII to EBCDIC Translate Table ............... L-8
Appendix M. End-User-Device Reference Cards Order Form ........... M-1
xiv
3708 Planning and Iqstallation
Appendix N. Binary to Hexadecimal Conversion Table .............. N-I
list of Abbreviations ................................... X-I
Glossary ...... .
Index ........ .
x-s
X-I3
Contents
XV
3708 Network Conversion Unit
Two Kinds of SNA Host Connections
SNA and ASCII Host Connections
Network Planning Form .......................... .
Network Planning Form Example .................... .
Port Definition Form ........................... .
Port Definition Form Example ...................... .
Power Plugs by Country .......................... .
Power Plugs and Receptacles ....................... .
3708 M120 screen .............................. .
UDT Conversion Screen (MI28.0) .................... .
Sample 3708 Configuration ........................ .
SNA Hosts .................................. .
ASCII Hosts ................................. .
Printers .................................... .
Displays, Protocol Conversion Only ................... .
Displays, Protocol Enveloping Only, or Dynamic ........... .
Displays with Printer, Protocol Conversion Only ........... .
Display with Printer, Dynamic ...................... .
1-2
1-3
1-4
4-4
4-5
4-6
4-7
5-3
5-4
16-1
16-2
B-2
E-l
E-2
E-3
E-4
E-5
E-6
E-7
Figures
xvii
This part contains the following chapters:
Chapter 1. The 3708 and Its Advantages
Overview
..... .
Physical Description
Operating Modes ..
Network Configurations
Control Terminal
Summary of Advantages
Chapter 2. Operating Mode Functions
Protocol Conversion
Display Support
Printer and Keyboard Printer Support
Multiple Logical Unit Support
Protocol Enveloping
ASCII Pass-Through
Function Summary
Chapter 3. Host and ASCII Device Interfaces
SNA Hosts ....... .
ASCII Hosts ...... .
ASCII End-User Devices
Protocol Conversion Mode
Default Mappings .
User-Defined Keyboard Mappings
Printers and Keyboard Printers
Protocol Enveloping Mode
ASCII Pass-Through Mode ..
Introducing the 3708
1-1
1-1
1-1
1-2
1-2
1-4
1-5
2-1
2-1
2-1
2-3
2-3
2-4
2-4
2-5
3-1
3-1
3-2
3-2
3-2
3-3
3-4
3-4
3-5
3-5
Introducing the 3708
Chapter 1. The 3708 and Its Advantages
Overview
This chapter provides the following general information about the 3708:
• Overview
• Physical description
• Operating modes
• Network configurations
• Monitoring and controlling the 3708
• Summary of advantages.
The 3708 provides a physical and logical interface for connecting ASCII end-user
devices! to an SNA network. It has 10 communication ports that can be defined for
various network configurations and operating modes. The network can contain
ASCII hosts, which include personal computers, as well as SNA hosts.
Physical Description
The 3708, which is shown in Figure I-Ion page 1-2, is small, lightweight, and
portable. It consists of two modular, customer-replaceable hardware components: a
base and a cartridge. The back panel of the base contains 10 numbered ports for
connecting hosts and ASCII end-user devices.
The 3708 measures 400 mm by 355 mm by 105 mm (15.8 in. by 14.0 in. by 4.1 in.),
weighs approximately 5.6 kg (12.3Ib), and can be placed on a shelf in a standard
19-inch rack.
1 ASCII end-user devices use asynchronous start~stop data transmission and include displays, printers, keyboard
printers, keyboard displays with attached printers, plotters, personal computers, and devices that use ANSI X3.64.
Chapter 1. The 3708 and Its Advantages
1-1
Figure 1-1. 3708 Network Conversion Unit
Operating Modes
Cartridge
Light
'-----Base
Power On/Off
Light
Not Ready
Light
The 3708 provides three modes of operation, which it can perform simultaneously,
for different network configurations:
• 3270 applications running on an SNA host. The 3708 provides protocol conversion
mode for communication between an ASCII end-user device and 3270
applications running on an SNA host. This mode changes a start-stop data
stream from an ASCII device into a 3270 data stream and provides 3274 Control
Unit functions, including 3270 full-screen support.
• Line-by-line applications running on an SNA host. The 3708 provides protocol
enveloping mode for communication between an ASCII end-user device and line
oriented applications running on an SNA host. In this mode, the 3708
surrounds the data stream from an ASCII device with SNA headers. Devices
that normally communicate with host applications through the start-stop support
of the Network Terminal Option (NTO) can communicate through the 3708.
NTO start-stop support is not required for 3708 operations and can be
eliminated from the communication controller.
• Applications running on an ASCII host. The 3708 provides ASCII pass-through
mode for communication between an ASCII display and applications running on
an ASCII host. This mode passes a start-stop data stream between an ASCII
display and an ASCII host without changing the data stream in any way.
Network Configurations
The 3708 provides 10 communication ports that can be defined for various
configurations of SNA hosts, ASCII hosts, and AscII end-user devices. The host
may be directly attached or may be remotely attached over nonswitched (leased)
lines. ASCII devices may be directly attached or may be. remotely attached over
switched or nonswitched lines. Line speeds of up to 19200 bps can be used.
1-2
3708 Planning and Installation
As many as two ports can be defined for SNA hosts. Each of these ports can
connect to separate hosts, or both can connect to the same host.
SNA
Host*
3708
ASCII Devices
ASCII Devices
Figure 1-2. Two Kinds of SNA Host Connections
*
For a list of SNA hosts that the 3708 supports, refer to "SNA Hosts" on
page 3-1.
As many as nine ports can be defined for ASCII hosts. Each of these ports can
connect to separate hosts, or multiple ports can connect to the same host, depending
on the host. Figure 1-3 on page 1-4 shows a configuration with one SNA host and
one ASCII host.
Chapter 1. The 3708 and Its Advantages 1-3
Figure 1-3. SNA and ASCII Host Connections
*
For a list of SNA hosts that the 3708 supports, refer to "SNA Hosts" on
page 3-1.
When a 3708 port is connected to an SNA host, multiple end-user devices can
communicate at the same time over that one line. When a 3708 port is connected to
an ASCII host, only one end-user device at a time can communicate over that line.
However, multiple devices can communicate at the same time with an ASCII host if
each device has a separate line to the host.
Control Terminal
A control terminal can be used for monitoring and controlling the 3708. Any
display that operates in protocol conversion mode can be the control terminal if it is
logged on to the 3708 in control terminal mode. The 3708 allows only one display at
a time to be logged on in control terminal mode. The control terminal can be either
directly or remotely connected to the 3708.
The control terminal is also used to define the configuration of the 3708. An
IBM-supplied configuration allows many types of displays to be used as a control
terminal for defining the initial configuration of the 3708. The 3708 provides default
keyboard mappings for these terminals. (Refer to "ASCII End-User Devices" on
page 3-2 for a list of the default terminals.) You must have one of these terminals
to define the initial configuration for the 3708. After initial configuration, other
types of displays can be defined for use as a control terminal. "Step 3. Logging
onto the Control Terminal" on page 12-5 contains step-by-step procedures for
logging on to the control terminal.
1-4
3708 Planning and Installation
The control terminal operator can perform the following functions:
• Define or change:
Host ports and host access
Device ports
Control terminal access
Control terminal password
Port passwords
Translate table
Keyboard mappings
Printer access
World Trade language to be used for 3708 logon
Suppression of 3708 logon screens.
• Display information, such as:
Configuration data
Response time statistics
Alert log and other error information.
• Monitor the 3708 by checking:
-
Port status
-
Data transmitted on lines connected to the 3708.
Note: If a printer is connected to the 3708, the control terminal screens showing
configuration information can be printed as a local copy operation.
Summary of Advantages
The 3708 provides the following advantages:
• It reduces communication costs by reducing the number of telecommunications
lines needed, by reducing the number of communication controller ports needed,
and by allowing a display with a connected printer to share a single
communication downstream line.
• It supports personal computer file transfer through the IBM PC/HOST File
Transfer and Terminal Emulator Program (FTTERM).
• It allows you to manage the configuration and microcode fixes of the 3708s in a
network from a central control point. This management capability is provided
by 3708 Feature 3525 (pluggable Cartridge with Central Site Configuration) and
its associated PC aid.
• It supports network management by sending alert messages to NetView or to the
Network Problem Determination Application (NPDA) and response time
statistics to NetView or to the Network Logical Data Manager (NLDM) for
displays that are connected for protocol conversion, and by notifying an SNA
host of changes in the power status of attached ASCII end-user devices.
• It supports multiple modes of operation. Protocol conversion, protocol
enveloping, and ASCII pass-through modes can be supported simultaneously.
• It eliminates the need for NTO start-stop support in the communication controller
by providing protocol enveloping for ASCII end-user devices that are compatible
with TWX 33/35.
Chapter 1. The 3708 and Its Advantages
1-5
• It cQnnects to most ASCII displays using standard 128.:.character ASCII in
protocol conversion mode. The 3708 provides ASCII~to-3270 keyboard
mappings for many displays and allows additional keyboard mappings to be
defined at the control tenriinal.
• It supports IBM 3270 Models 2,3,4, and 5 emulation when operating in protocol
conversion mode.
• It allows the sharing of printers. The printer can be defined to allow output from
the host, local screen copies from one or more ASCII displays operating in
protocol conversion mode, or both host output and local screen copies. It also
supports printers that are connected to displays (MLU).
• It reduces terminal costs by allowing inexpensive ASCII end-user devices to be
used in an SNA network.
• It provides flexibility by allowing a single ASCII device to be connected to either
an SNAhost or an ASCII host (which may be a personal computer) and by
allowing access to ASCII and 3270 applications at an SNA host.
• It helps in migrating to SNA by allowing end users to access 3270 application
programs through ASCII devices.
• It provides security for data and applications by allowing an optional password
for each port, by allowing host and printer access to be defined, and by ending a
session whenever it detects an abnormal disconnection.
• It provides an optional inactivity time-out that may be used to disconnect
terminals, thus reducing security exposures and limiting dial charges on switched
lines.
• It connects to devices that use special characters or nonstandard codes by
providing ASCII-to-EBCDIC translate tables. An additional translate table can
be defined using the control terminal.
• It allows the SN A host to dial out to devices in protocol enveloping mode.
• It alliJws a display to dial out to an ASCII host in ASCII pass-through mode.
• It supports transparent operations in protocol enveloping. Ports can be defined
to allow transparent data flow to and from the host. This feature provides
support for devices such as graphics displays, printers, and plotters.
• It allows an operator to define the 3708 configuration and to monitor and control
the 3708 by using an ASCII display as a control terminal. A password protects
access to control terminal functions. When not used as a control terminal, the
ASCII display is available as an end-user device.
• It allows a port to be defined to allow protocol conversion, protocol enveloping, or
both depending on the type of session requested by a host All ports can be
defined to allow ASCII pass~through.
• It allows a port to be defmed to automatically determine the parity and line speed
(from 110 to 4800 bps and 9600 bps) for both switched and nonswitched lines.
• It attaches to the IBM cabling system.
1-6
3708 Planning and Installation
• It has a built-in diagnostic test that runs each time you power on or initiate a
restart at the control terminal.
• It has a built-in, optional, extended diagnostic test program that is available with
port external wrap testing.
• It provides a one-year warranty and is supported by IBM service.
Chapter 1. The 3708 and Its Advantages
1-7
Chapter 2. Operating Mode Functions
This chapter describes the functions that the 3708 provides in protocol conversion,
protocol enveloping, and ASCII pass-through modes.
Protocol Conversion
Display Support
In protocol conversion mode, the 3708 provides all the functions in IBM 3274
Configurati
• It provides a numeric lock function that reduces the chance of the end-user
entering non-nuinetic data when the application expects numeric data.. The 3708
allows the end-user to override this function by typing:
Any upper case character or symbol into the numeric field.
A blank into the first position in the numeric field. While the blank
occupies the first position in the field, the user can type any character into
the numeric field.
• It provides type-ahead key queuing, that allows the user to enter new keystroke
sequences on the keyboard while a preceding keyboard sequence is being
processed. This function allows a user to request the next screen before the
current screen is completely displayed. The user can turn type-ahead key
queuing on and off.
• It provides enhanced null/blank processing, that allows the user to use either the
space bar or the cursor move keys to edit and separate fields. The 3708 allows
trailing blanks or nulls to move off the end of a line when the user is inserting
data in that line. When the data is sent to the host, the 3708 converts imbedded
nulls to blanks. The user can turn eDhanced null/blank processing on and off.
• It supports highlighting and color for certain classes of displays. Refer to IBM
3708 Network Conversion Unit Description for more information. Light-pen
operations can be simulated using a Cursor Select key sequence.
• It supports the following 3270 commands:
Erase All Unprotected
Erase/Write
Erase/Write Alternate
Read Buffer
Read Modified
Read Modified All
Write.
• It supports the following buffer formatting and control orders:
Start Field
Set Buffer Address
Inset Cursor
Program Tab
Repeat to Address
Erase Unprotected to Address.
• It notifies the user when it detects a framing or parity error by updating the
status line. To continue, the user must reset the display using the 3270 reset
function. This function can be suppressed by configuring the nonstandard
operating bit 5 to 1. Refer to "Non-Standard Operations" on page 14-3 for
more information.
• It allows the conttol terminal operator to display response-time statistics and
error information, such as the alert log, at the control terminal. In addition, the
response~time statistics and alerts can be displayed at the host using NetView or
Network Logical Data Manager (NLDM) and the Network Problem
Determination Application (NPDA). Full support for 3708 alerts is available
only through NetView.
1-1
3708 Planning and Installation
Printer and Keyboard Printer Support
In protocol conversion mode, an ASCII printer or keyboard printer looks like an
IBM 3287 Printer, Model I or 2 to the SNA host. The ASCII printer or keyboard
printer can be configured to operate in three ways:
System mode. The host sends print data to the printer, which is either an LU
type I or an LU type 3. The output format for an LU type I printer is
controlled by SNA character string (SCS) characters. For an LU type 3 printer,
the output can be formatted or unformatted. Unformatted output is controlled
by 3270 data stream compatibility (DSC) print orders.
Local mode. A copy of the screen of a display that is operating in protocol
conversion mode is printed at the printer. The host can start a local copy by
sending a command, or the user of the display can select it with a print key
sequence. When a printer port is configured for local mode, it cannot be used
for LU type I or LU type 3 print operations.
Shared mode. The printer is available for both system mode and local mode
operation. A local copy can be performed whenever the printer is not being
used for an LU type I or LU type 3 print operation.
Keyboard printers operating in protocol conversion mode are supported as output
devices and must be defined as printers.
Up to 256 characters (8-bit data with no parity) can be used with an output device
operating in L U type I SCS transparency mode.
The 3708 supports the following input from a keyboard printer that is directly
connected to the 3708:
• Hold Print/Enable Print
• Cancel Print (LU type I SCS only)
• PAl and PA2 (LU type I SCS only).
Multiple Logical Unit Support
A printer connected to an auxiliary port on a display that supports remote access to
its auxiliary port can be defined as a second LU on the 3708 port to which the
display is connected. The printer can then be used in system mode, local mode, or
shared mode. This support is referred to as multiple logical unit (MLU) support and
operates only in protocol conversion mode.
If a printer is connected to an auxiliary port on a display and is not defined to the
3708, the printer can be used only for screen copy operations that are initiated by
the user. The user enters a predefined key sequence that the 3708 echoes back to the
display.
Input from devices that are connected to the auxiliary port of a display is not
explicitly supported; any such input is assumed to be for the display.
Chapter 2. Operating Mode Functions 2-3
In prptocol enveloping mode, the 3708 supports an ASCII end-user device as an LU
type 1 with a Network Terminal Option (NTO) appearance. The 3708 does not
provide any device-specific support other than that provided by NTO for devices
that are compatible with TWX 33/35. The application program must provide any
device-specific support. The 3708 supports the following functions in protocol
enveloping mode:
• It mayor may not modify the ASCII data, depending on how the port is
configured. The data can be modified by using a translate table, delay
characters, substitution characters, and other options that are defined during
configuration. If the data is translated from ASCII to EBCDIC, the 3708 can
use one of two standard translate tables or a user-defined translate table.
• It can provide a delay after a Carriage Return, Vertical Tab, Form Feed, or
Horizontal Tab.
• It can use either a default substitution character or a user-defined substitution
character when it detects a data error. When it detects a parity error in a
character, the 3708 can replace the character with the Parity Error Substitution
character configured in the 3708. When it detects a framing error, the 3708
always replaces the framing error with the Parity Error Substitution character.
• It can use up to five different turnaround characters, which are defined during
configuration, to control communication. When the 3708 receives a line
turnaround character from an end-user device, the 3708 sends data from the
device to the host.
Because the 3708 does not control the keyboard in protocol enveloping, users
must know when they can and cannot enter data. A character string that tells
the user when to enter data can be defined for each port. To define the
character string, see "Send Read Prompt" on page 13-40. In addition, a port
can be configured to enable the 3708 to echo characters that are entered at the
keyboard.
• It can provide for transparent data flow. The 3708 can support 256-character
sets and output-only devices, such as printers and plotters.
• It can allow the host to dial out to devices. For more information, refer to IBM
3708 Network Conversion Unit Description.
ASCII Pass-Through
In ASCII pass-through mode, the 3708 serves as a wire connection between an
ASCII end-user device and an ASCII host. The host and the end-user device are
responsible for data and protocol error checking.
N~te: A programmable modem can be installed on a port configured as an ASCII
host. The 3708 allows the user to dial out through the programmable modem in
ASCII pass-through mode and gain access to an ASCII host, printer, or other
device.
2-4
3708 Planning and Installation
The following table summarizes the functions that the 3708 provides.
Protocol
Protocol
ASCII
Function
Conversion
Enveloping
Pass-Through
IBM 3178/3278/3279 Model 2, 3, 4, or 5, Display
Standard
n/a
n/a
Station emulation
IBM 3287 printer, Models 1 and 2 emulation
Standard
n/a
n/a
Four color support (3279-2A and 3179 emulation)
Optional
n/a
n/a
Highlighting support
Optional
n/a
n/a
Light pen emulation
Optional
n/a
n/a
Type-ahead
Optional
n/a
n/a
Enhanced null/blank processing
Optional
n/a
n/a
User-defined terminals
Optional
n/a
n/a
3270 status line emulation
Standard
n/a
n/a
Response time monitor (RTM)
Standard
n/a
n/a
Alerts (Alerts generated for ASCII pass-through are
Standard
Standard
Standard
transmitted to SNA hosts.)
NTO-like function (LU type 1 NTO emulation)
n/a
Standard
n/a
Full duplex operations
Standard
Optional
Standard
Half duplex operations
n/a
Optional
n/a
Parity and framing checking
Standard
Optional
n/a
Ignore parity
n/a
Optional
Standard
Character echoplexing
Standard
Optional
nja
No character echoplexing
n/a
Optional
Standard
128-ASCII-character support
Standard
Optional
Optional
256-ASCII -character support
n/a
Optional
Optional
256-ASCII-character support (LU type 1 SCS)
Optional
n/a
n/a
Choose one of two standard translate tables
Optional
Optional
n/a
User-defined translation table
Optional
Optional
n/a
No translation
n/a
Optional
Standard
3708 accepts XON/XOFF pacing
Optional
Optional
n/a
3708 transmits XON/XOFF pacing
Optional
Optional
n/a
LU type I SCS printer data stream support
Optional
n/a
nja
LU type 3 DSC printer data stream support
Optional
n/a
n/a
System, local, or shared printer support
Optional
n/a
n/a
MLU support (a printer attached to the auxiliary port
Optional
n/a
n/a
of a display.)
Chapter 2. Operating Mode Functions 2-5
Autobaud/parity for 110 through 4800 and 9600 bps
Optional
Optional
Optional
for downstream devices
Line speeds up to 19200 bps
Optional
Optional
Optional
EIA 232C support for (SNA and ASCII) host
Standard
Standard
Standard
connection
EIA 232C support for downstream device connection
Optional
Optional
Optional
EIA 422A support for downstream device connection
Optional
Optional
Optional
Selection of 3708 logon screens
Optional
Optional
Optional
2-6
3708 Planning and Installation
Chapter 3. Host and ASCII Device Interfaces
SNA Hosts
This chapter describes the connections between the 3708 and the hosts and between
the 3708 and the ASCII end-user devices.
The 3708 can be connected to as many as two SNA hosts using either point-to-point
or multipoint links. It is defined as a separate physical unit (PU) to each SNA host
link.
In addition, the connection to the host can be direct, or it can be remote using a
nonswitched (leased) line. Line speeds as high as 19200 bps can be used. SNA host
connections use the EIA 232C interface.
The 3708 uses the SDLC protocol to communicate with an SNA host, and it uses
half duplex data transmission on either full duplex or half duplex communication
facilities.
If a particular end-user device will always be used with one specific SNA host, the
3708 port to which the device is connected can be defined to suppress the 3708 logon
and/or host-selection screens.
Because the service priority of the 3708 is in descending order, ports 10 and 9 are
recommended for SNA host connections. Connect the first SNA host to port 10 and
the second SNA host to port 9.
The 3708 can be connected to an SNA host through any of the following:
• IBM 3720 Communications Controller
• IBM 37x5 Communications Controller
• IBM 3710 Network Controller
• IBM 43xx with an Integrated Communication Adapter
• IBM 4701 Model 003 Finance Communication Controller (using Alternate Line
Attachment adapter, SNA Primary to attach to the 4700)
• IBM 4702 Branch Automation Processor (using the Alternate Line Attachment
adapter, SNA Primary to attach to the 4700)
• IBM 8100 System Data Link or Direct Attach
• IBM System/36 Communications Attachment (using the 3274 Remote Attach
Support)
• IBM System/38 Communications Attachment (using the 3274 Remote Attach
Support).
Chapter 3. Host and ASCII Device Interfaces 3-1
For network management at the host, the following programs can be used:
• NetViewfully supports the 3708 alerts and response time monitor (RTM) data.
NetView contains both Network Problem Determination Application (NPDA)
and Network Logical Data Manager (NLDM).
• Network Problem Determination Application (NPDA), Version 3 or later,
supports only the specific and general cause codes of 3708 alerts.
• Network Logical Data Manager (NLDM), Release 2 or later, supports response
time statistics.
The 3708 can be connected to multiple ASCII hosts using point-to-point links. The
connection can be direct, or it can be remote using a nonswitched (leased) line.
ASCII host connections use the EIA 232C interface.
Line speeds as high as 19200 bps can be used. The speed used by the host.and the.
speed used by the end-user device should be the same.
Full duplex transmission must be used.
ASCII End-User Devices
The 3708 can be connected to ASCII end-user devices using either a direct or remote
connection. End-user device connections use the EIA 232C interface or, for
distances over 15 meters (50 feet), the EIA 422A interface. A remote connection can
use either switched or nonswitched lines. Line speeds can be as high as. 19200 bps.
Protocol Conversion Mode
For protocol conversion mode, the 3708 supports various displays, printers, and
keyboard printers.
3-2
3708 Planning and Installation
The 3708 provides default keyboard mappings for the following displays:l
• IBM 3101 Display Terminal Models 10, 12, 13,20,22, and 23
• IBM Personal Computer (PC) in 3101 emulation mode with standard
3101 keyboard functions
• IBM PC with a color monitor running the IBM PC/HOST File Transfer and
Terminal Emulator Program (FTTERM)
• IBM PC with a monochrome monitor running the IBM PC/HOST File Transfer
and Terminal Emulator Program (FTTERM)
• IBM 3151 ASCII Display Station
• IBM 3151 with cartridge to emulate IBM and DEC® terminals (Feature No.
8235)
• IBM 3151 Connectivity Feature Cartridge (Feature No. 8525)
• IBM 3151 with Expansion Feature Cartridge (Feature No. 8535)
• IBM 3161 ASCII Display Station
• IBM 3161 with Enhanced 3708 Attachment (Feature No. 8371)
• IBM 3162 ASCII Display Station
• IBM 3162 with 3708 Support Functions (Feature No. 8232)
• IBM 3163 ASCII Display Station
• IBM 3164 ASCII Color Display Station
• IBM 3163/3164 VT100/3708 Emulation Cartridge (Feature No. 8313)
• ADDS (Applied Digital Data Systems) Viewpoint®
• Beehive™ ATL-078
• Data General Dasher® D210 Display Terminal
• DEC® (Digital Equipment Corporation) Models VT52, VT100, and VT220
• FALCO 500®
• Hazeltine 1500, ESPRIT I™, and ESPRIT IITM
• Hewlett-Packard 2621B Interactive Terminal
• Lear Siegler ADM 3A Dumb Terminal®
• Northern Telecom Displayphone™
• ROLM Cypress, Cedar, and Juniper (connected through ROLM CBX II)
• Teletype 5410 Asynchronous Display Terminal and 5420 Buffered Display
• TeleVideo® 910 and 950
• WY-50® (Wyse 50)
• Other terminals and personal computers emulating and compatible with one of
the named devices.
Appendix K, "Manuals for Default Protocol Conversion Displays" contains a list of
sources for more information about these displays. Refer to
Appendix M, End-User-Device Reference Cards Order Form for the reference
cards.
1 The list of displays contains several trademarks and registered trademarks. Viewpoint is a registered trademark of
Applied Digital. Data Systems, Inc. Beehive is a trademark of Beehive International. Dasher is a registered
trademark of the Data General Corporation. DEC is a registered trademark of the Digital Equipment Corporation.
ESPRIT I and ESPRIT II are trademarks of Esprit Systems, Inc. FALCO 500 is a registered trademark of Falco
Data Products, Inc.. Dumb Terminal is a registered trademark of Lear Siegler, Inc. Displayphone is a trademark of
Northern Telecom, Inc. TeleVideo is a registered trademark of TeleVideo Systems, Inc. WY-50 is a registered
trademark of Wyse Technology.
Chapter 3. Host and ASCII Device Interfaces
3-3
User-Defined Keyboard Mappings
In addition, the user can define as many as six user-defined keyboard mappings for
other ASCII displays that have the following characteristics:
• Operate in character mode using asynchronous full duplex communications
• Use either EIA 232C interface or the EIA 422A signaling
• Use standard .128-character ASCII (7-bit data with odd, even, or no parity)
Note: The 3708 does not support Shift-In and Shift-Out.
• Use duplex communications on a 2- or 4-wire communication facility
• Position the cursor using one of the seven predefined cursor addressing classes
(see page 15-8)
• Provide settings for host echo instead of local terminal echo only
• Use DC1 and DC3 as XON and XOFF for pacing.
Printers and Keyboard Printers
The 3708 supports ASCII printers and keyboard printers that have the following
characteristics:
• Use asynchronous duplex full communications
• Use the EIA 232C serial interface
• Use standard 128-character ASCII (7-bit data with or without parity)
• Have a maximum line length of 132 characters
• Support X I OD I for carriage return and X I OA I for Line Feed
• Do not generate a Line Feed upon receipt of a Carriage Return
• Do not generate a Carriage Return upon receipt of a Line Feed
• Ignore delete characters (X I 7F I )
• Use DCl and DC3 as XON and XOFF for pacing
• Operate at speeds from 110 bps to 19200 bps
• Do not require any special sequences to be sent by the 3708 for initialization.
Note: Keyboard printers operating in protocol conversion mode are supported only
as printers.
3-4
3708 Planning and Installation
(
Protocol. Enveloping Mode
For protocol enveloping mode, the 3708 supports ASCII devices that have the
following characteristics:
• Operate in character mode
• Use either the BIA 232C interface or BIA 422A signaling
• Use 8 bits, which mayor may not include parity
• Use DCI and DC3 as XON and XOFF for pacing
• Are compatible with TWX 33/35.
ASCII Pass-Through Mode
For ASCII pass-through mode, the 3708 supports ASCII devices that have the
following characteristics:
• Operate in character mode
• Use either the BIA 232C interface or BIA 422A signaling
• Use 8 bits, which mayor may not include parity.
Chapter 3. Host and ASCII Device Interfaces
3-5
Planning for the 3708
This part provides the following planning information:
Chapter 4. Planning Checklist ...
Planning Configuration Parameters
Device Information Form
Network Planning Form
Port Definition Form
Chapter 5. Planning for Installation
Specifications and Location Requirements
Size and Weight
...... .
Service and Setup Clearances
Environment . . . .
Interface Requirements
Power Requirements .
Branch Circuits and Grounding
Power Plugs ...... .
Safety and Security Considerations
Chapter 6. Planning for Service ....... .
Reviewing the Service and Warranty Options
Service Options ..... .
Warranty Options
Remote Access Capability
Installation Technical Assistance
Replacement Elements and Remote Problem Assistance
Calling for Service ..... .
Calling the 800 Number
Receiving Remote Assistance
Hardware and Configuration Requirements
Traces and Logs ....
Locating the RID Number
Chapter 7. Planning for Microcode Updates
How to Register
What to Expect ............ .
How to Order
............ .
What to Do with Outdated Cartridges
Chapter 8. Planning for Central Site Configuration
...... .
IBM 3708 Pluggable Cartridge with Central Site Configuration
Hardware Requirements
Software Requirements
Software Options that Enhance CSC
Configuration Downloads from an SNA Host
Control Terminal Emulation
3708 Configuration Requirements ..
Modem Configuration Requirements
Technical Assistance .
Ordering Information
Chapter 9. Planning for File Transfer
4-1
4-2
4-3
4-4
4-5
5-1
5-1
5-1
5-1
5-1
5-2
5-2
5-2
5-3
5-5
6-1
6-1
6-1
6-1
6-2
6-2
6-2
6-3
6-3
6-4
6-4
6-4
6-5
7-1
7-1
7-1
7-1
7-2
8-1
8-1
8-2
8-2
8-3
8-3
8-3
8-4
8-5
8-5
8-5
9-1
Planning for the 3708
IBM PC/HOST File Transfer and Terminal Emulator Program
9-1
Benefits and Functions
9-1
Required Host Programs
9-2
IBM 3708 Plug-In Support
9-3
Technical Assistance
9-3
Ordering Information
9-3
Personal Services/PC
9-3
A User-Written File Transfer Program
9-3
Chapter 10. Planning for Cables
10-1
Cable Descriptions ......
10-1
IBM-Supplied Cables
10-1
Non-IBM Supplied Cables
10-2
Examples of 3708 Cable Connections
10-2
SNA Host to a 3708
10-3
Remote: Using Modems .. .
10-3
Local: Using a Modem Eliminator or Null Modem
10-4
Local: Direct Connection Using an EIA 232C DTE Cable (8100 Only)
10-5
Local: Direct Connection Using a Host EIA 232C DTE Cable and a
3708 EfA 232C DCE Cable
........
10-6
Local: Direct Connection Using a Host EIA 232C DCE Cable and a
3708 ErA 232C DTE Cable
10-7
ASCII Hosts and End-User Devices to a 3708 ......
10-8
Remote: Using Modems . . . . . .
10-8
Local: Using Modem Eliminators and Null Modems
10-8
Local: Direct Connection Using a 3708 ETA 232C DTE Cable (Male -
Male and Male - Female)
. . . . . .
10-9
Local: Direct Connection Using a 3708 EIA 422A Cable
10-10
3708 Connection to the IBM Cabling System
10-11
3708 Problems Related to Cables or Equipment
10-12
Chapter 11. Ordering the 3708
11-1
Order Forms
. . . . . . . .
11-1
3708 Planning and Installation
Chapter 4. Planning Checklist
This chapter provides a planning checklist to help prepare for the installation of the
3708.
The steps in the planning process are:
1. Plan the 3708 network. The following section, "Planning Configuration
Parameters" on page 4-2, contains the forms and information for planning the
network.
2. Plan for the site and other physical requirements of the 3708. See
Chapter 5, "Planning for Installation" for more information.
3. Plan for service. See Chapter 6, "Planning for Service" for more information.
4. Plan for microcode updates. See Chapter 7, "Planning for Microcode Updates"
for more information.
-
5. Plan for central site configuration. See Chapter 8, "Planning for Central Site
Configuration" for more information.
6. Plan for file transfer. See Chapter 9, "Planning for File Transfer" for more
information.
7. Plan for cables. See Chapter 10, "Planning for Cables" for more information.
8. Plan for the parts that need to be ordered. See Chapter 11, "Ordering the
3708" for more information.
9. When the site and configuration planning is complete, follow the procedures in
Chapter 12, "Installation Procedures" to install the 3708 and to enter the
configuration parameters.
Chapter 4. Planning Checklist 4-1
Planning Configuration Parameters
Use the following procedures to plan the 3708 configuration:
• Complete the Network Planning Form on page 4-4 to help visualize the physical
connections to the 3708.
• Complete the Port Definition Form on page 4-5 to help organize and plan the
network connections for the terminals, hosts,and printers. "Protocol
Conversion Mode" on page 3-2 lists the terminals that the 3708 supports.
• After you have defined the types of devices (hosts, terminals, printers) that are
connected to each port, plan the configuration parameters for each device.
Follow the procedures in Chapter 13, "Configuration Procedures" to configure
each port. Chapter 12 provides the following information about the parameters
for each type of device:
The screens that are displayed on the control terminal for each type of
device
The options that you can enter for each field on the screens.
Before starting the configuration, you need the following information:
Host configuration. Prepare the host system generation. Refer to IBM 3708
Network Conversion Unit Description for more information.
Downstream devices. Gather information about XONjXOFF, line speed,
parity, interface type (EIA 232C or EIA 422A), and line type (switched or
leased) for the devices that you are connecting to the 3708. Refer to the
user manuals for the devices for more information. For a list of device
manuals, see Appendix K, "Manuals for Default Protocol Conversion
Displays." Use the Device Information Form on page 4-3 to collect the
information for each device.
Communications network environment. When attaching devices to the 3708
through modems, telephone lines, and public access networks, you should be
aware of certain parameters associated with the connection facilities that can
affect the 3708 operation, such as XONjXOFF, parity, stop bits, and
communication speed.
4-2
3708 Phullling and Installation
To plan each port before entering the configuration parameters at the control
terminal, use the configuration forms in Appendix C, "3708 Configuration Forms"
to indicate the correct option for each configuration parameter. Appendix B, "3708
Configuration Example" contains an example configuration, that may be helpful
when you are deciding what to enter on the configuration screens.
Appendix A, "IBM-Supplied Configuration" contains the IBM-supplied
configuration that is shipped with the 3708. This configuration allows you to
connect a control terminal for initially configuring the 3708. Because the SNA host
port is excluded, the IBM-supplied configuration is not an operating network
configuration.
Device Information Form
Device
Names
1
2
3
4
5
6
7
8
9
10
Use the Device Information Form to collect device-specific information for each
port.
Interface Type
Switched or
EIA 232C or
Leased Line
EIA422A
Line Speed
Parity
XON/XOFF
Chapter 4. Planning Checklist 4-3
Network Planning Form
The Network Planning Form (Figure 4-1) allows the planner to identify the hosts
and end-user devices and the 3708 ports to which they connect.
10
9
1
8
~ /
2
7
3708
V
'\
4
5
Figure 4-1. Network Planning Form
To complete the Network Planning Form, do the following:
1. In each box, write the host or end-user device that connects to the 3708. The
lines between the 3708 and the boxes correspond to the ports on the 3708.
2. In the blank beside each box, write the other port numbers with which the host
or end-user device can communicate.
Figure 4-2 on page 4-5 shows a completed example of the Network Planning
Form.
See Appendix B, "3708 Configuration Example" for details on the network
configuration.
4-4
3708 Planning and Installation
2 (displa.y) 1
I8tr1 4201
I"ILU
2 (prinfer)
I8~ PC-AT
RlJnning FTTE~
3(disp!ay)2 (d,splay)
IB~ '12()1
I'1LU
3 (printer)2 (pr"n~r)
SiVA lIosfA
IBI1 3011
SNA 1105+8
IB~ J090
7
4
2 (diSplo.y)
ASCII #osf
7
of
VT100
10
fl 2 (prti?fer)
Exclvded
10 3 (tf/splay)
IB/'1 PC-XT
1.0
9
g
2 (pr/fller)
-FHEIU'1 /ie.fer.s to the I81'1 PC/ Hos! hie
Transfe.r and E,-"ula.+or
Pr~l'Om
Figure 4-2. Network Planning Form Example
Pori Definition Form
The Port Definition Form (Figure 4-3 on page 4-6) can be used to enter data for
each port on the 3708.
Figure 4-4 on page 4-7 and Appendix B, "3708 Configuration Example." illustrate
completed forms for the example in Figure 4-2.
Chapter 4. Planning Checklist
4-5
PORTS TO COMMUNICATE
#
NAME
WITH
LOCAL
REMOfE
DIRECT/
MODEM
NULL MODEM/
DESC.
MODEMELIM.
I
2
3
4
5
6
7
8
9
10
I
2
3
~
5
6
7
8
9
10
Figure 4-3. Port Definition Form
4 .. 6
3708 Plannil!g and Installation
PORTS TO COMMUNICATE
Chapter 5. Planning for Installation
This chapter provides the following information about planning ·a 3708 installation:
• Specifications and location requirements
• Interface requirements
• Power requirements
• Safety and security considerations.
Specifications and Location Requirements
Size and Weight
This section provides information about the size, weight, environment, and power
specifications for the 3708.
The following table shows the weight and dimensions of the 3708.
Weight 5.3 kg (11.7lb) without cartridge
5.6 kg (12.3 lb) with cartridge
Width
400 mm (15.8 in.)
Length
355 mm (14.0 in.)
Height
105 mm (4.1 in.)
Service and Setup Clearances
Environment
The following table shows the recommended service and setup clearances for the
3708.
Front
600 mm
Back
600 mm
Sides
40 mm
Note: If the 3708 is shelf-mounted in a 19-inch rack, center it in the rack for proper
ventilation. Ventilation slots are located on both sides of the 3708. If the 3708 is
table-mounted, allow 40 mm (1.5 in.) on each side for proper ventilation.
The 3708 operates in normal business environments. The following table shows the
environmental specifications.
Relative
Maximum
Environment
Temperature
Humidity
Wet Bulb
Operating
100 to 40.60 C
8% to 80%
26.70 C (80 0 F)
(500 to 1050 F)
Non-Operating
100 to 51.7 0 C
8% to 80%
26.7 0 C (80 0 F)
(50 0 to 1250 F)
Storage
0.60 to 600 C (330
5% to 80%
0.6 0 to 29.4 0 C
to 1400 F)
(33 0 to 85 0 F)
Shipment
_400 to 60 0 C
5% to 100%
0.60 to 29.40 C
(_400 to 1400 F)
(330 to 85 0 F)
Chapter 5. Planning for Installation 5-1
The 3708 uses two types of interfaces, EIA 232C and EIA 422A. The following
table shows the hosts and end-user devices with which each interface can be used.
Host/Device Type
SNA host
ASCII host
ASCII printer
ASCII display
Interface Type
EIA 232C
EIA 232C
EIA 232C
ASCII keyboard printer
EIA 232C or EIA 422A
EIA 232C or EIA 422A
Power Requirements
The following table shows the electrical specifications of the 3708.
Phase
Power
Frequency
Voltage range:
Noniinal voltage:
Single phase
0.1 kVA
50/60 Hz ± 3 Hz
Low voltage (90 to 137 V)
High voltage (180 to 257 V)
Low voltage (120 V)
High voltage (230 V)
Power Cord Length 4.3 meters (14.1 feet),
shipped with the 3708
Notes:
1. You can order a 1.5-meter (6-foot) power cord in addition to the cord that is
shipped with the 3708.
2. High voltages are not available in the USA and Canada. Make sure that your
site has the electrical power to match the order.
Branch Circuits and Grounding
A dedicated branch circuit of 15 amperes is recommended for the 3708. For safety
and proper machine operation, each branch circuit must be grounded to a dedicated
equipment ground, not to a neutral ground. The branch circuit must have an
insulated grounding conductor that is equal to the size of the phase conductor and is
tied to a common ground point at the distribution panel. A single insulated and
isolated grounding wire should run from the distribution panel ground point to the
service ground or to a suitable building ground. Conduit must not be used as the
only means of grounding.
5-2
3708 Planning and Installation
Figure 5-1 shows, by country, which power plugs are shipped with the 3708. The
alphabetic references in this table refer to the power plugs shown in Figure 5-2 on
page 5-4.
Low-
High-
Low-
High-
Country
Voltage Voltage
Country
Voltage Voltage
Argentina
•
Japan
• •
Australia
•
Korea
•
Austria
•
Netherlands
•
Belgium
•
New Zealand
•
Brazil
•
Norway
•
Bulgaria
•
Peru
•
Canada
•
Poland
•
Chile
•
Portugal
•
Czechoslovakia
•
Rumania
•
Denmark
•
South Africa
f)
Finland
•
Spain
•
France
•
Sweden
•
Germany DR
•
Switzerland
•
Germany FR
•
Taiwan
•
Greece
•
United Kingdom
•
Hungary
•
United States •
Ireland
•
Venezuela
•
Israel
•
Yugoslavia
•
Italy
•
Figure 5-1. Power Plugs by Country
Chapter 5. Planning for Installation 5-3
Plug (3-D View) I Receptacle
Plug (3-D View) I Receptacle
.@ @
~ov~ e
125v
15A
16A
!ov.@
15A
~ .~
250V
Q 0
16A ~
@
• ~~
!ov~ @
250V
13A
10A
0)
XJ~ .~~
250V
250V.
0
0
16A
10A
• ~ (2) !ov~~
250V
10A
16A ~
..
~ ©
250V
10A
Figure 5-2. Power Plugs and Receptacles
5-4
3708 Planning and Installation
Safety and Security Considerations
Electrical grounding of the 3708 is essential for safety and proper machine operation,
so be sure the power receptacle is properly grounded. If you have any questions
about the grounding of the receptacle, contact an electrician.
Since the 3708 is small and lightweight, one person can move it safely during
installation or relocation.
If the 3708 cables are not installed under a raised floor, be sure the cables are
arranged so there is adequate space for people to move around the 3708 safely.
The 3708 cables, particularly those for a direct connection using the EIA 422A
interface, are not protected against lightning. They must not be placed outdoors.
To ensure the physical security of the 3708, do the following:
• Allow only authorized persons to press switches on the 3708 and to use the
control terminal.
• Use unique passwords for port access and control terminal functions rather than
the default passwords.
• Exclude control terminal access to public ports.
Chapter 5. Planning for Installation 5-5
Chapter 6. Planning for Service
This chapter describes the 3708 maintenance service offerings, tells who to call for
installation technical assistance, outlines how to get remote assistance for problems
not solved by problem handling-procedures, and gives the location of the repair
identification number.
The 3708 problem determination and service procedures provide the following:
• Comprehensive internal diagnostics
• Only two replaceable elements, which are a base and a plug-in cartridge
• Communication network management support by providing alerts and by
collecting performance statistics
• Control terminal support for configuration, monitoring, and problem
determination for either local or remote connection
• Remote assistance for diagnosing machine problems and for applying microcode
fixes through a modem and phone line access that you provide.
These features reduce the cost of maintenance and the problem resolution time.
Reviewing the Service and Warranty Options
Service Options
Warranty Options
This section describes various service and warranty options that are available for the
3708.
The IBM Maintenance Agreement provides maintenance service options. The
following service options are available:
Service Option
Description
Customer on-site exchange
IBM arranges for the delivery of an exchange unit to
your location and for pick up of the failing unit.
IBM on-site exchange
An IBM representative comes to your location and
exchanges a functioning unit for the failing unit. If
you purchase the IBM on-site exchange option, you
can also purchase optional periods of maintenance
service, which extend the hours in which service is
available.
The warranty period is for 1 year and is serviced under the customer on-site
exchange service option. However, you can select the IBM on-site exchange service
option during the warranty period for an additional charge. Contact the local IBM
branch office for more information on warranties and maintenance agreements.
Chapter 6. Planning for Service
6-1
Remote Access Capability
The 3708 is designed for remote access by both you and IBM service representatives.
For example, the network personnel using a control terminal from a remote location
can access 3708 alert data and review error logs to perform problem determination.
You can also use the control terminal to monitor data and signaling lines on the
3708's downstream ASCII ports.
Remote assistance is part of the 3708 maintenance service offerings. It allows an
IBM service representative to dial out to a 3708, to run extensive diagnostic tests,
and to apply microcode fixes if necessary. Remote assistance can minimize outages
that would otherwise require the unnecessary iep1acement of the base or cartridge
and can minimize the delay in waiting to receive a new cartridge with updated
microcode. To receive remote assistance, you must provide a modem and phone line
access for the IBM service representative.
Installation Technical Assistance
Contact the marketing representative where the 3708 was purchased if you have
technical questions about any of the following:
• Ordering information for the 3708 base, cartridge, and cables
• Installation
• Configuration
• System integration
• Application/host programming considerations.
Replacement Elements and Remote Problem Assistance
Before calling for service, use the problem-determination procedures in IBM 3708
Network Conversion Unit Problem Determination to isolate the problem to a failing
unit if possible. After completing problem determination, contact IBM for service as
described in "Calling for Service" on page 6-3. To be eligible for this assistance, the
3708 must be either under warranty or covered by an active IBM service agreement.
6-2
3708 Planning and Installation
Calling for Service
Use the following telephone number to receive replacement units, existing microcode
fixes (MCFs), or problem assistance:
• In the continental United States or Puerto Rico, call the following number:
1 800 428-2569 (toll free)
• In other countries, call the appropriate support group.
Note: The telephone numbers are subject to change. If the number has changed,
call the IBM marketing representative or the local IBM branch office.
Calling the 800 Number
When you call the 800 number, an IBM customer service coordinator briefly
discusses your situation and asks for the type of machine, the machine serial number,
the repair identification (RID) number (see page 6-5), the name of your company,
and a phone number where you can be reached. The customer service coordinator
also performs an entitlement check to determine the type of contract or warranty
agreement in effect. The IBM customer service coordinator is not the IBM service
representative for the 3708.
If you wish to obtain existing microcode fixes (MCFs) for your level of microcode,
the customer service coordinator will forward your request to the IBM service
representative, who will make arrangements with you for the installation of the
MCFs.
If you have a problem and have successfully completed the problem determination
procedures and isolated the problem to a unit, you are given instructions on how to
receive a replacement unit.
If you are unable to complete the problem determination procedures or if the
procedures indicate a microcode problem, further assistance in problem
determination will be provided. The information about the problem will be
forwarded to a 3708 specialist who will call you back. The service representative will
call you and either provide a solution for the problem or work with you to solve the
problem.
Chapter 6. Planning for Service
6-3
Receiving Remote Assistance
IBM can help through remote assistance if you are unable to resolve a 3708 problem
using the procedures in IBM 3708 Network Conversion Problem Determination and if
one of the following is true: (1) the 3708 is still under the I-year warranty, or (2)
you have purchased IBM maintenance service.
Remote assistance can include consultation with an IBM service representative for
problem diagnosis by IBM through a remote connection (through a modem and
phone line access that you provide). The network management personnel can also
use the modem for configuration and problem management of devices that are
connected to the 3708.
Hardware and Configuration Requirements
Traces and Logs
For remote assistance, you must provide telephone facilities for a 1200 bps switched,
auto-answer connection. This includes a modem with the following characteristics:
• For the USA only, use a direct-connect, Bell 2I2A-compatible modem with
operating speeds up to 1200 bps in full duplex mode when connected to the
direct distance dial network. The modem must operate over a 2-wire switched
line. For countries other than the USA, use a V.22-compatible modem.
• EIA 232C compatible interface.
Any downstream port used for remote assistance must be configured identically to
port 3 as described in Appendix A, "IBM-Supplied Configuration." If this is not
compatible with the normal mode of operation, reconfigure a port for that mode
before receiving remote assistance by temporarily reinstating the IBM -supplied
configuration. (Refer to IBM 3708 Network Conversion Unit Problem Determination
for more information.) When not in use for remote assistance, the port is available
for connection to an end-user device. The 3708 can be configured to deny access to
the host from a port that is assigned to remote service.
Microcode Fixes (MCFs), patches, and diagnostic traps are applied and stored in the
base unit hardware (EEPROM). They are not stored in the cartridge. If you replace
your base unit, you must have any MCFs, patches, or traps applied to the new base
unit.
As part of the problem determination process, the IBM representative often requires
you to provide certain additional materials.
The most frequently requested are an NCP Line Trace, a VT AM Buffer Trace, or a
PT2 Trace of both upstream link and the failing downstream line. Please be
prepared to obtain and provide these traces when requested.
Also, you may be requested to obtain and provide copies of the 3708 Error Log and
3708 Alert Log at the time of failure.
Making this information available can greatly enhance problem determination and
speed the resolution of your problem.
6-4
3708 Planning and Installation
Locating the RID Number
The repair identification (RID) number enables the IBM customer service
coordinator to perform an entitlement check to determine the warranty or service
option that is in effect.
Locate the machine type and repair identification (RID) number of the failing unit.
The RID number is in the following locations:
• Just above the power cord on the back of the base
• On the cartridge. Apply the RID label that is shipped with the 3708 to the
cartridge when the 3708 first arrives.
• In the vital product data storage area on the logic board of the 3708 base. The
RID number is displayed on the 3708 logon screens when logging on to the
3708.
Generally, the RID number located on the cartridge and the base is the same as the
RID number displayed on the 3708 logon screens. If they are not (they will differ if
you have exchanged the base element), use the control terminal to enter the RID
number located on the base (and cartridge) into the 3708's vital product area
(EEPROM). EEPROM is a nonvolatile logic circuit in the 3708 that retains
information regardless of whether the 3708 power is on or off.
Maintaining the same RID number on the base, the cartridge, and within the 3708's
vital product area ensures smoother and faster service if you need to exchange 3708
elements or need remote service for microcode.
Chapter 6. Planning for Service
6-5
Chapter 7. Planning for Microcode Updates
This chapter describes the 3708 microcode update procedure. It includes how to
register for microcode update notification, what to expect in the notification, how to
order microcode updates, and what to do with outdated microcode.
Note: The cartridge holds all of the 3708's operational microcode. This code
cannot be downloaded from a host. Microcode fixes (MCFs) and patches are stored
in the base unit and can be downloaded from the host. Refer to
Chapter 8, "Planning for Central Site Configuration" for more information.
How to Register
What to Expect
How to Order
To register for microcode update notification, you MUST fill out the registration
form that comes with the 3708 and send it to the address indicated on the form.
You must fill out and send in this registration form to be notified of any microcode
updates.
After you send in your registration form, IBM 3708 Microcode Support personnel
will notify you with Engineering Change (EC) Memos as new engineering changes
for microcode become available. The memo gives you the new EC number for the
microcode and a list of the improvements and corrections contained in the update.
Even if you have not encountered any problems, it is recommended that you install
the updated microcode level to prevent possible future problems that may occur
because of any changes in your operating environment.
To order microcode updates without charge do one of the following:
1. Fill out the IBM 3708 Enhanced-Cartridge Ordering Form that is attached to
the notification memo and send this form to the address indicated on the back
of the ordering form. No postage is necessary.
2. Call the 800 number shown below, and be ready to give your RID number,
customer number, address, and your name or the name of a person to contact.
If you reach a recording when you call, please leave a message on the recorder
and someone will return your call as soon as possible.
If you have questions about receiving replacement cartridges:
• In the continental United States or Puerto Rico, call the following number:
1 800 247-7118 (ton free)
• In other countries, call the appropriate support group.
Chapter 7. Planning for Microcode Updates 7-1
What to Do with Outdated Cartridges
The new microcode will be accompanied by a copy of 3708 Enhanced Cartridge
Receive/Exchange/Re~urn Instructions. The instructions tell you how to do the
, following:
1. Install the new 3708 microcode
2. Return the old cartridge by:
a. Packing the old cartridge in the shipping carton used to send you the new
microcode.
Please be sure the RID number is identified on all cartridges being returned.
b. Attaching the prepaid mailing label enclosed in the carton
c. Mailing the old cartridge within 5 working-days of receiving the new
microcode.
To receive future releases of updated microcode, you must return outdated
cartridges to ffiM.
7-2
3708 Planning and Installation
Chapter 8. Planning for Central Site Configuration
This chapter provides planning information about IBM 3708 Feature 3525
(pluggable Cartridge with Central Site Configuration), Feature 3525 consists of a
plug-in cartridge and a set of diskettes. Together, the cartridge and the diskettes
allow you to manage and distribute configuration updates and microcode fixes to
3708s in a network from a central location. This feature eliminates the task of
entering repeatedly the same configuration or MCF /Patch data into all 3708s in a
network.
IBM 3708 Pluggable Cartridge with Central Site Configuration
IBM 3708 Central Site Configuration (CSC) uses the IBM PC to support
configuration and Microcode Fix (MCF) management for the IBM 3708 Network
Conversion Unit. For central site configuration, you must install the 3708 Feature
3525 plug-in cartridge.
Central site configuration provides the following advantages:
• A single data base of configuration information for all of the IBM 3708s in an
installation
• Menu-driven, user-friendly facilities for the creation, replication, and
modification of IBM 3708 configuration information including these features:
Port definition for host links and downstream terminals
User-defined terminal definitions
User-defined translate table definition.
• A check of configuration information as it is entered and a warning to the user
if potential errors exist
• Configuration summary screens, including a quick reference port summary, a
detailed port summary, a host configuration summary, and printer configuration
summary
• A method to retrieve existing configuration information from an IBM 3708
through a downstream port
• A method to load configuration information through a downstream port or the
SNA host link with NetView or NCCF V2R2
• A method to retrieve a microcode patch area from a 3708 that has been
upgraded by IBM and the ability to distribute the microcode patch area to other
3708s in the network
• Item-specific help screens and an online user's guide.
Chapter 8. Planning for Central Site Configuration
8-1
The following hardware is required for central site configuration:
• A 3708 with Feature 3525 (pluggable Cartridge with Central Site Configuration)
Note: Central site configuration is available with 3708 Feature 3525 only.
• An IBM PC with:
-
A 5.25-inch diskette drive
A fixed disk
An IBM Color/Graphics or Monochrome adapter attached to an 80-column
display
A minimum of 512K bytes of storage (640K bytes of storage are required if
the PC is to run in control terminal mode).
You can use an IBM Personal System/2. To run CSC on the Personal System/2,
you must first convert the 5.25-inch diskettes shipped with the CSC Cartridge to the
3.5-inch format.
If you plan to perform central site configuration through one of the 3708's
downstream ports, you will need:
• An asynchronous communications adapter operating in primary mode
• A normal voice-grade, switched communications line (for switched connections
only)
• Modems (for switched connections only).
A manual-dial Bell 212A-compatible or auto-dial modem that supports the
. Attention Command Set and result codes, such as an IBM PC 2400 bps or IBM
58422400 bps Modem is required for switched connections.
Modem eliminators, null modems, or 3708 DTE cables may also be used to
attach the IBM PC to the 3708. For a description of modem connections as
well as modem eliminator, null modem, and 3708 DTE cabling configurations,
refer to, "ASCII Hosts and End-User Devices to a 3708" on page 10-8.
Software Requirements
The following software is required for central site configuration:
• IBl\l PC DOS Version 2.0 or later
• eZ-VU II Runtime Facility Version 2 (6317025).
8-2
3708 Planning and Installation
Software Options that Enhance esc
The following features are enhanced by the 3708 central site configuration feature
and other network software options.
Configuration Downloads from an SNA Host
The IBM 3708 central site configuration aid can prepare configuration information
in the form of NetView CLISTs for downloading through the SNA host link to the
IBM 3708. NetView and NCCF Version 2 Release 2 support this method of
transfer.
The file transfer software support that sends the CLIST from the IBM PC to the
SNA host must be provided by the end-user. For example, the IBM PC/HOST File
Transfer and Terminal Emulator Program, FTTERM, (6476052) can be installed in
the IBM PC to upload CLIST files to the SNA host.
New 3708s with the CSC feature have port 10 defined as an active host port with the
following characteristics:
Option
Station Address
NRZI Data Encoding
Permanent Request to
Send
Line Speed
Line Type
Field
Length
(2)
(1)
(1)
(2)
(1)
Port 10
X'08'
1 (Yes)
o (No -- Use Controlled Request to
Send)
00 (External Clocking)
L (Leased)
This configuration allows new 3708s to be configured remotely from the host site.
For multipoint lines, no other devices on the line can have SDLC Station Address of
X '08'. If two or more 3708s are to be installed on a single line, each 3708 needs to
be configured from the host one at a time. The SDLC Station Address X' 08 '
should be reserved as a utility address because 3708 hardware or software errors and
user interaction can temporarily or permanently re-instate the IBM-supplied
configuration. If the host line parameters are not compatible with the user's
environment, new 3708s can be configured for host line characteristics at a main site,
shipped to remote locations, and configured over the SDLC links.
Control Terminal Emulation
The 3708 control terminal diagnostic routines can be accessed through the use of the
IBM PC and the central site configuration aid running in control terminal mode. In
this mode, the IBM PC can retrieve the alerts and error logs. IBM software
products that can support this feature are FTTERM, and the IBM 3101 Emulator
Program (6024042).
Notes:
1. If you plan to use your PC as a control terminal for the 3708 and you want CSC
to log you on as a control terminal automatically, you must have the FTTERM
or the IBM 3101 Emulation program installed. The emulation program must
reside in the same directory on your fixed disk as the central site configuration
program.
2. The IBM PC must have 640K bytes of memory to support this function.
Chapter 8. Planning for Central Site Configuration 8-3
3708 Configuration Requirements
If central site configuration is perfonned through one of the 3708's downstream
ports or the IBM PC is to run in control terminal mode, at least one downstream
3708 port must be dermed for the following parameters:
• Port Excluded = N
• Logon Screens Excluded = N
• Terminal Type Screen (C2) = y
• Host Selection Screen (C3) = Y
• Control Terminal Access = Y
• Password Retry Limit = 3 or greater
• Transmit XONjXOFF = 1
• Line speed = 1,2,4,5,6,8, 10, 12, or 19 (110, 150, 300, 600, 1200,2400,4800,
9600 bps, or Autobaud)
• Device Class = 1 (Keyboard Display)
• Operating Mode = 1 or 2 (protocol Conversion or Dynamic)
• Interface Type = 0 (EIA 232C)
• Parity = 2, 3, or 6 (Odd, Even, or Autoparity)
• Receive Queue Size = M or L
• Bits/Character = 7
• Auto On-Hook = 1 (for switched lines)
• Send Answertone = 0 (for switched lines)
• Full Duplex Line = 1
• Echoplex = 1
• Pennanent Request to Send = 1.
Note: Ports 3 and 7 in the IBM-supplied configuration for the 3708 are compatible
with central site configuration.
Refer to Chapter 13, "Configuration Procedures" for a complete description of
these and other 3708 configuration parameters.
8-4
3708 Planning and Installation
Modem Configuration Requirements
If modems are used, the modem at the PC and the modem at the 3708 must be
configured as follows:
• Modems detect a change in Data Terminal Ready (DTR) signal and go on hook
when DTR drops.
• Data Set Ready (DSR) is raised only when a connection is established (not
applicable for internal modems).
• Carrier Detect shows whether or not Carrier is on.
• Modems use the Attention Command Set and send the modem responses in
words (verbose mode) and not in number codes (terse mode).
• PC modem does not answer incoming calls.
• The 3708 modem does answer incoming calls.
• Modems do not echo characters.
• Modems do not take over flow control (that is, the modem does not strip out
XONjXOFF characters from the IBM PC or the IBM 3708).
Technical Assistance
See your IBM representative for assistance with problems related to the central site
configuration aid.
Ordering Information
The Pluggable Cartridge with Central Site Configuration can be ordered with an
IBM 3708 Network Conversion Unit. Spare Pluggable Cartridges with Central Site
Configuration can be ordered by part number. A set of S.2S-inch, double-sided,
double-density diskettes containing the central site configuration aid is included with
each Pluggable Cartridge with Central Site Configuration feature.
Chapter 8. Planning for Central Site Configuration 8-5
Chapter 9. Planning for File Transfer
This chapter describes 3708 support for the following file-transfer programs:
• IBM PC/HOST File Transfer and Terminal Emulator program (PN 6476052)
• IBM Personal Services/PC program (Version 1.4 or higher)
• A user-written file transfer program.
IBM PC/HOST File Transfer and Terminal Emulator Program
This section describes the function of the IBM PC/HOST File Transfer and Terminal
Emulator Program (FTTERM). It also describes the benefits of using FTTERM
and lists the environments under which it works.
Benefits and Functions
FTTERM is a licensed program that supports IBM PCs communicating with an
IBM SNA host through a 3708. The program gives the user of an IBM PC
full-screen 3270 terminal emulation and file transfer capability when operating in
protocol conversion mode with the 3708. The connection between the IBM PC and
the 3708 is through the IBM PC's asynchronous communication adapter.
An IBM PC running FTTERM can also emulate an IBM 3101 terminal and connect
to the 3708 in protocol enveloping mode. This connection provides access to
asynchronous applications at the IBM SNA host that formerly interfaced to the
Network Terminal Option (NTO) licensed program in the 37x5.
The IBM PC can also operate through the 3708 to an ASCII/asynchronous host
connected to another port on the 3708. In addition, FTTERM can access network
services independent of the 3708.
The features of the PC/HOST File Transfer and Terminal Emulator program are
summarized as follows:
• Provides IBM PC file transfer capability both to and from the IBM host 3270
personal computer file-transfer programs while operating in protocol conversion
mode with the 3708. See "Required Host Programs" on page 9-2 for the
program product numbers.
• Provides full-screen 3270 emulation, status line support, and four color or
highlighting while operating in protocol conversion mode through a 3708.
• Supports the 3708 feature that allows a printer and a display to share a single
port in protocol conversion mode.
• Provides 3101 emulation (character mode only) to:
Asynchronous applications at an IBM host in protocol enveloping mode
An ASCII/asynchronous host connected to another port on the 3708
-
Online information services, such as the IBM Information Network.
Chapter> 9. Planning for File Transfer
9-1
• Allows an IBM PC user to redefine the PFandPA keys to 3270 AID functions,
• Provides a resident option that permits the IBM PC user to load FTTERM only
once a day.
• Allows concurrent file transfer and IBM PC DOS application operation.
• Provides key sequence switching between the IBM PC DOS session, the host
session, and file transfer operation without disconnection or loss of the IBM
host session.
• Supports error checking and automatic retransmission of file transfer.
• Provides status messages for monitoring the progress of the file transfer.
• Supports the following text or binary file-transfer operations:
An IBM host file to an IBM PC DOS file or to a personal computer printer
An IBM PC DOS file to a host file or to an IBM PC printer
An IBM host screen to a host file, to an IBM PC DOS file, or to an IBM
PC printer
An IBM PC DOS screen to a host file, to an IBM PC DOS file, or to an
IBM PC printer
Multiple files without operator intervention.
• Provides an online help facility.
• Provides for stored keystroke sequences for repetitive operations, such as a
modem-dialing keystroke sequence.
• Supports the PROFS PC Support Feature, Version 2 (5664-309) while running
FTTERM. This support provides file transfer capability both to and from the
host PROFS while operating in protocol conversion mode with the 3708.
Required Host Programs
File transfers are performed with the following IBM 3270 PC file-transfer programs
installed at the host. One of the following programs must be· installed at the host to
. run FTTERM.
Environment
MVSjTSO
VMjSP
CICS (MVS and VSE)
VSE 2.11
Host File Transfer Program
5665-311
5664-281
5798-DQH
5666-316
1 The PC/HOST File Transfer and Terminal Emulator program works with the integrated Intelligent Work Stations
(IWS) program, which is shipped with VSE, Release 2.1 and higher.
9;.2
3708 Planning and Installation
IBM 3708 Plug-In Support
The 3708 plug-in cartridge supports the PC/HOST File Transfer and Terminal
Emulator Program with the following two types of terminals:
• IA - IBM PC/FTTERM COLOR. Customers using FTTERM with color
monitors would select this option.
• IB - IBM PC/FTTERM MONO. Customers using FTTERM with
monochrome monitors would select this option.
Technical Assistance
Eligible customers can receive installation and usage assistance from the IBM
Workstation Customer Assistance Center (WSCAC). Assistance is provided through
ASKINFO, an electronic data base that provides current information on selected
products. Assistance is also provided by telephone call back. When requesting
assistance from the ASKINFO personnel, your customer technical coordinators
should use the key word FTTERM for search inquiries and questions. The
ASKINFO personnel will then call you back. Contact the IBM marketing
representative to determine if you are eligible to receive ASKINFO support.
Ordering Information
Both a 5.25- and a 3.5-inch diskette are included with a user's guide when you order
the PC/HOST File Transfer and Terminal Emulator Program. Ask the marketing
representative to order feature number 0914 of 5875-MMA.
Personal Services/PC
Personal Services/PC is an office-oriented mail management program for the IBM
personal computer. It provides a comprehensive and easy-to-use set of office
systems functions, such as automatic dialing, receiving and transmitting mail, and
printing and viewing documents.
Document transfer to the host is performed in conjunction with the DISOSS
program product.
Personal Services/PC is supported by the 3708 in protocol enveloping mode.
For more information about the Personal Services/PC, refer to How To Use Personal
Services/PC, SC30-3316.
A User-Written File Transfer Program
For information on developing a user-written file transfer program for personal
computers connected to a 3708, refer to IBM 3708 Network Conversion Unit
Description.
Chapter 9. Planning for File Transfer 9-3
Chapter 10. Planning for Cables
This chapter provides information to help you plan for the cables and the cable
connections for the 3708.
Cable Descriptions
This section describes the cable requirements for the 3708.
IBM-Supplied Cables
The part numbers for the cables are listed in the following table according to length,
interface, and application.
Host devices
Interface
(See note 2.)
Cable Type
(See note 1.)
Connectors
3 meters (10 feet)
8 meters (25 feet)
15 meters (50 feet)
Up to 122 meters
(400 feet)
(See note 4.)
Between 122 meters
(400 feet) and 1219
meters (4000 feet)
(See note 4.)
38 meters (125 feet)
(See note 5.)
Notes:
SNAand
SNA and
ASCII hosts,
ASCII hosts,
ASCII printers
ASCII printers
and displays
and displays
EIA 232C
EIA232C
DCE
DTE
Male-Male
Male-Female
PN 6405390
PN 6405393
PN 6405391
PN 6405394
PN 6405392
PN 6405395
SNA and
ASCII hosts,
ASCII printers
ASCII displays
and displays
(See Dote 1)
EIA232C
EIA 422A
DTE
DTE
Male-Male
Male-Male
PN 6405421
PN 6405422
PN 6405423
PN 6405396
PN 6405397
(See note 3.)
PN 6405398
1. A 3708 DCE cable connects a 3708 to a modem, a modem eliminator, or a null
modem. A 3708 DTE cable directly connects a 3708 to a host or an end-user
device.
2. The IBM EIA 422A cables can only be used with an IBM 3101, an IBM 3151,
an IBM 3161, an IBM 3162, an IBM 3163, an IBM 3164, or a compatible
terminal.
3. Cable PN 6405397 contains surge-suppressing diodes.
4. Variable-length cable is available only in the USA and A/FE countries. See a
marketing representative for the availability in your country.
5. The fixed-length cable PN 6405398 is available only in EMEA countries. See
the marketing representative for the availability in your country.
6. To make your own cables, refer to Appendix D, "Cable Requirements."
Chapter lO. Planning for Cables
10-1
Non-IBM Supplied Cables
Recommendations for cables not supplied by IBM are as follows:
• Do not use 25-pin conductor cables under any circumstances.
• Use cables with the conductors as described in Appendix D, "Cable
Requirements. "
Examples of 3708 Cable Connections
This section provides examples for cable connections from SNA hosts to a 3708 and
from ASCII hosts and end-user devices to a 3708. The examples show connections
using modems, null modems, and modem eliminators. See the glossary for a
definition of these terms.
In these examples, the following meanings apply:
F
M
Blank
10-2
3708 Planning and Installation
Female
Male
Device dependent.
SNA Host to a 3708
This section describes the ways that the 3708 can connect to an SNA host.
Remote: Using Modems
3708
F 1M
SNA Host
3705
PN 6405390
3725
PN 6405391
4300lCA
PN 6405392
4700
3708 DCE Cable
M I F
17
F I M
Host DCE Cable
S/38
Modem
Modem
3720
8100
S/36
3710
Notes:
1. The 3708 DeE cable length must not exceed 15 meters (50 feet).
2. The host may use special connectors. If you have this configuration, use the
cables that are provided with the host.
3. Configure the 3708 SNA host definition option Line Type for leased connection
(LINE TYPE = L).
Chapter 10. Planning for Cables
10-3
Local: Using a Modem Eliminator or Null Modem
3708
FIM
8NA Host
PN 6405390
3705
3725
PN 6405391
4300lCA
PN 6405392
4700
3708 DCE Cable
Modem
Host DCE Cable
8/38
M I F
Eliminator or
F 1M
Null Modem
3720
8100
8/36
3710
Notes:
1. The host may use special connectors. If you have this configuration, use the
cables that are provided with the host.
2. Ensure that the connector genders are correct.
3. The wiring of the modem eliminator or null modem must match that of the 3708
OTE cable described in "Minimum Connections Required for SNA Host OTE
Cables, Modem Eliminators, or Null Modems" on page 0-7.
4. If the modem eliminator redrives the signal, then each cable segment must not
exceed 15 meters (50 feet). Otherwise, the combined cable length must not
exceed 15 meters (50 feet).
5. Clocking is required, and may be provided by one of three different methods:
Clocking from the 3708
The 3708 can provide clocking for all line speeds that the 3708 supports. If
this method is chosen, then the modem eliminator or null modem must not
provide clocking. Configure the 3708 SNA host definition option Line
Speed for the desired speed, and configure the host for external clocking.
Clocking from the host
Some hosts can provide clocking for some line speeds that the 3708
supports. If this method is chosen, then the modem eliminator or null
modem must not provide clocking. Configure the host for the desired
clocking speed, and configure the 3708 SNA host definition option Line
Speed for external clocking (option 00).
Clocking from the modem eliminator or null modem
Some modem eliminators or null modems can provide clocking for some line
speeds that the 3708 supports. If this method is chosen, then set the modem
eliminator or null modem for the desired speed, configure the host for
external clocking, and configure the 3708 SNA host definition option Line
Speed for external clocking (option 00).
6. Configure the 3708 SNA host definition option Line Type for a leased
connection (LINE TYPE = D).
10-4
3708 Planning and Installation
Local: Direct Connection Using an EIA 232C DTE Cable (8100 Only)
PN 6405393
PN 6405394
SNA Host
PN 6405395
3708
F 1
MI-l ---------------11 F I M
8100
I
3708 OTE Cable
I
Notes:
1. The cable length must not exceed 15 meters (50 feet).
2. The host has standard 25-pin D connectors.
3. Clocking should be provided from the 3708. Configure the 3708 SNA host
definition option Line Speed for the desired speed and configure the 8100 for
external clocking.
4. Configure the 3708 SNA host definition option Line Type for a direct
connection (LINE TYPE = D).
Chapter 10. Planning Jot Cables 10 ... 5
Local: Direct Connection Using a Host EIA 232C DTE Cable and a 3708 EIA 232C DCE
Cable
8NA Host
3705
PN 6405390
3725
PN 6405391
4300lCA
F 1M
3708 DCE Cable
I MJ F I
Host DTE Cable
4700
3708
8/38
3720
8/36
3710
Notes:
1. The host DTE cable is sometimes called a direct-connect or direct-attach cable.
2. The combined cable length must not exceed 15 meters (50 feet).
3. The host may use special connectors. If you have this configuration, use the
cables that are provided with the host.
4. Ensure that the connector genders are correct.
5. The host system must be configured to provide clocking. The 3708 must be
configured for external clocking. (Choose 00 for the 3708 SNA host definition
option Line Speed.)
For the 3705, this particular configuration is not supported, except by RPQ
number EHOI70.
For the 3720, the NCP gen must have CLOCKING = EXTERNAL,
ATTACH = DIRECT, and SPEED = (the desired line speed, 2400 bps or
greater). The actual line speed is configured by the MOSS. A 3725 Internal
Clock Card ("ICC Card") feature is required for this configuration.
For the 3725, the NCP gen must have CLOCKING = EXTERNAL,
ATTACH = DIRECT, and SPEED = (the desired line speed, 2400 bps or
greater). The actual line speed is determined by jumpers on the 3725 LAB
board. A 3725 Internal Clock Card ("ICC Card") feature is required for this
configuration.
6. Configure the 3708 SNA host definition option Line Type for a direct
connection (LINE TYPE = D).
10;.6
3708 Planning and Installation
Local: Direct Connection Using a Host EIA 232C DCE Cable and a 3708 EIA 232C DTE
Cable
SNA Host
3705
3725
PN 6405393
4300lCA
PN 6405394
4700
F 1M
3708 DTE Cable
FJ M
Host DCE Cable
5/38
3708
3720
8100
5/36
3710
Notes:
1. The combined cable length must not exceed 15 meters (50 feet).
2. The host may use special connectors. If you have this configuration, use the
cables that are provided with the host.
3. Ensure that the connector genders are correct.
4. Clocking must be provided by the 3708 by configuring the 3708 SNA host
definition option Line Speed with the desired speed (specifically, this parameter
must not be 00). The host system should be configured for external clocking.
For the 3705, 3720, or 3725, the NCP gen must have
CLOCKlNG=EXTERNAL, ATTACH = MODEM, and SPEED = (the desired
line speed). The actual line speed is determined by the clock rate of the 3708. A
standard external modem cable should be connected to the communications
controller.
5. Configure the 3708 host definition option Line Type for a direct connection
(LINE TYPE = D).
Chapter lO. Planning for Cables
10-7
ASCII Hosts and End-User Devices to a 3708
This section describes the ways that the 3708 can connect to ASCII hosts and
end-user devices.
Remote: Using Modems
3708
F 1M.
PN·6405390
PN 6405391
PN 6405392
3708 DCE Cable
MI F Modem /' Modem
ASCII
FI M
Device Cable
I
ASCII
Device
Note: Check the gender and the pin configuration of the equipment's interface
before ordering cables.
Local: Using Modem Eliminators and Null Modems
3708
F 1M
PN 6405390
PN 6405391
PN 6405392
3708 DCE Cable
Notes:
Modem
MI F
Eliminator or
Null Modem
ASCII
Device Cable
ASCII
FI M
I
Device
1. Check the gender and the pin configuration of the equipment's interface before
ordering cables.
2. The wiring of the modem eliminator or null modem must match that of a 3708
DTE cable. (See "Minimum Connections Required for Asynchronous ASCII
DTE Cables, Modem Eliminators, or Null Modems" on page D-9.)
3. If the modem eliminator re.drives the signal then each cable segment must not
exceed 15 meters (50 feet). Otherwise, the combined cable length must not
exceed 15 meters (50 feet).
10·8
3708 Planning and Installation
Local: Direct Connection Using a 3708 EIA 232C DTE Cable (Male - Male and Male -
Female)
PN 6405393
PN 6405394
PN 6405395
37081 F 1MI-I ______
3_70_8_D_T_E_C_a_b_le _____ ~1 F I M I
~~~ I
PN 6405421
PN 6405422
PN 6405423
37081 F 1MI-I ______
3_70_8_D_T_E_C_a_b_le _____ ~1 MI F I
~~~~.I
Note: Check the gender and the pin configuration of the equipment's interface
before ordering cables.
PN 6405393
PN 6405394
3708
F 1M
3708 DTE Cable
F 1M
ASCII Device Cable
ASCII
Device
Notes:
1. The combined cable length must not exceed 15 meters (50 feet).
2. Check the gender and the pin configuration of the equipment's interface before
ordering cables.
Chapter 10. Planning for Cables
10-9
Local: Direct Connection Using a 3708 EIA 422A Cable
PN 6405396
PN 6405397
PN 6405398
3708
F I M,
3708 422 Cable
Notes:
3101
3161
,MI F
3162
3163
3164
1. The 3708 supports a direct connection using the EIA 422A interface to the
following IBM terminals:
• IBM 3101, Model 13
• IBM 3101, Model 23
• IBM 3151 Model 310/410
• IBM 3161, Model 12
• IBM 3162, Model 12/32
• IBM 3163, Model 12
• IBM 3164, Model 12.
2. The length of the cable must not exceed 122 meters (400 feet) unless surge
suppressing diodes are installed, in which case the length can be up to 1219
meters (4,000 feet).
3. Because there is no standard for the EIA 422A pin connections,IBM does not
supply a cable for non-IBM ASCII terminals.
4. The ends of the EIA 422A cable are not identical. The 3708 end of the cable
(marked V.ll on the IBM manufactured cable) has 6 pins and the terminal end
has 4 pins.
10-10
3708 Planning and Installation
3708 Connection to the IBM Cabling System
This diagram. shows the cable connections from the 3708 to an IBM cabling system.
Multi-Function Attachment Cable (PN8310553)
IBM Cablin S stem
Wiring Closet
r------,
Terminal
Notes:
Wiring
Rack
1. Terminal support includes:
• IBM 3101, Model 13
• IBM 3101, Model 23
• IBM 3151 Model 310/4lO
• IBM 3161, Model 12
• IBM 3162, Model 12/32
• IBM 3163, Model 12
• IBM 3164, Model 12
IBM 3708/Cabling
System Attachment
Cable
SNA Host
2. The multi-function attachment cable (PN 83lO553) is approximately 2.4 meters
(8 feet) in length and may be ordered through normal local area network (LAN)
channels.
3. A description of the 3708/Cabling System Attachment cable is contained in
Appendix D.
Note: This cable is NOT available from the IBM Corporation.
4. The connection between the 3708 and SNA host may be accomplished with one
of the host cabling configurations described in this book.
5. Maximum cable path to the 3708 from the terminal is 1220 meters (4000 feet).
For more information on the IBM Cabling System, refer to IBM Cabling System
Planning and Installation Guide, GA27-3361, and Using the IBM Cabling System with
Communication Products, GA27-3620.
Chapter 10. Planning for Cables
10-11
3708 Problems Related to Cables or Equipment
. An incorrectly wired cable or incorrectly operating eqUipment (modem, modem
eliminator, host, or end-user device) that is connected directly to a 3708 port can
prevent the 3708 from operating. This problem occurs if the cable or equipment
applies a signal to one of the following port connector pins: 2,4, 12, 14, 18, 20, 21,
23, or 24.
Example 1: ROLM DTI users must ensure that the DTI is configured correctly and
that the DTI switch SI-1 is set to OPEN (No). Otherwise, the DTI applies a signal
to pin 20 of the 3708, which may prevent the 3708 from turning on.
Recommended switch setting for the ROLM DTI are as follows:
Switch #1 (SI):
Forced DTR On
Carrier Detect and CTS Display
Audible Signal Enabled
Terminal/Computer" Option
Originate Answer/Answer
Off Hook Control Switch
Slide Switch (S3):
Modem/Terminal Option
OPEN (No)
Either OPEN or CLOSED
Either OPEN or CLOSED
OPEN (TERMINAL)
CLOSED (ANSWER)
OPEN
TERMINAL
Example 2: IBM 5841 users must set configuration switch 8 (Data Set Ready
option) to OFF. Setting this switch to ON causes the modem to hold Data Set
Ready high (active) at all times. If the 3708 port is switched, and Data Set Ready is
active all the time, the 3708 does not enable the port.
To avoid signals on pins 2, 4, 12, 14, 18, 20, 21, 23, or 24, it is recommended that
25-pin conductor cables not be used.
Example 3: Some synchronous modems and modem sharing devices do not hold the
TXD line at a MARK level after RTS is dropped. This prevents devices on the
same multi-drop line from communicating with the host. The problem occurs when
the line is configured for NRZI data encoding.
The problem can be prevented by doing one of the following:
• Configure the modem/modem sharing device to hold the TXD line at a MARK
level when RTS is dropped
• Configure the line for NRZ data encoding.
10-12
3708 Planning and Install/ltion
Chapter 11. Ordering the 3708
Order Forms
This chapter provides ordering forms to help you order the 3708 and its accessories.
The following table shows the items that are required for the 3708. All of these
items can be ordered from your Marketing Representative.
Description
3708 base, Model 001
(See note 1.)
3708 cartridge
(See note 2.)
3708 cartridge with
Central Site Configuration
(See note 2.)
3708 manuals
Planning and Installation
Description
Problem Determination
End-User Reference
Terminal Reference Cards,
as needed
Notes:
Order
System
AAS
(See note 4.)
AAS
AAS
AAS
AAS
AAS
AAS
AAS
1. The following items are shipped with the 3708 base:
• 4.3-meter (14 feet) power cord
• EIA 232C wrap plug for diagnostic testing
Order
Number
Machine type
3708
Feature
number 3524
Feature
number 3525
GA27-3766
GA27-3768
GA27-3767
GA27-3765
See note 3.
• IBM 3708 Network Conversion Unit Setup, GA27-3611
• IBM 3708 Network Conversion Unit Problem Report, GA27-3638
• IBM 3708 Network Conversion Unit Address Registration Form.
Quantity
2. A 3708 Cartridge Feature must be ordered with each 3708 base. If you do not
specify Feature Code 3524 or 3525, your order for a 3708 base unit will not be
processed.
3. Refer to Appendix M, "End-User-Device Reference Cards Order Form" for the
order numbers of reference cards for end-user devices.
4. AAS is the Advanced Administrative System.
Chapter 11. Ordering the 3708
11-1
The following table shows the cables that are additional or optional for the 3708.
See Chapter 10, "Planning for Cables" for information about selecting the
appropriate cables. All of these items can be ordered from your Marketing
Representative.
Order
Order
Description
System
Number
Quantity
EIA 232C DCE male - male
3 meters (10 feet)
MES
PN 6405390
8 meters (25 feet)
(See note 2)
15 meters (50 feet)
MES
PN 6405391
MES
PN 6405392
EIA 232C DTE male - female
3 meters (10 feet)
MES
PN 6405393
8 meters (25 feet)
MES
PN 6405394
15 meters (50 feet)
MES
PN 6405395
EIA 232C DTE male - male
3 meters (10 feet)
MES
PN 6405421
8 meters (25 feet)
MES
PN 6405422
15 meters (50 feet)
MES
PN 6405423
EIA 422A DTE male - male **
Up to 122 meters (400 feet)
MES
Specify the length required.
PN 6405396
PN 6405396
PN 6405396
PN 6405396
PN 6405396
EIA 422A DTE male - male **
Between
MES
122 meters (400 feet)
and
1219 meters (4000 feet)
Specify the length required.
PN 6405397
PN 6405397
PN 6405397
PN 6405397
PN 6405397
EIA 422A DTE male - male
38 meters (125 feet) *
PN 6405398
*
Only available in EMEA countries
**
Only available in U.S.A. and A/FE countries
11-2
3708 Planning and Installation
1. Cables are shipped separately from the 3708. Allow 2 weeks for delivery.
See "Cable Descriptions" on page 10-1 for more information.
2. MES is the Miscellaneous Equipment Specifications.
The following table shows the items that are additional or optional for the 3708.
Order
Order
Order
Description
Contact
System
Number
Quantity
Optional base or power cord
(1.8 meters or 6 feet)
Marketing
Representative
AAS
9986
Spare 3708 cartridge without CSC
Spare 3708 cartridge with CSC
PC/HOST File Transfer and
Terminal Emulator Program
(See note 1.)
Shelves (See note 2.)
Rack or table
Modems
Telephone lines
ASCII device manuals
(See note 4.)
Notes:
Marketing
MES
PN 6405322
Representative
PN 6405473
Marketing
AAS
PN 6476052
Representative
OEM (See note 3.)
OEM (See note 3.)
Marketing
AAS
Machine type
Representative
Local telephone
company
OEM (See note 3.)
1. Refer to Chapter 9, "Planning for File Transfer" for more information.
2. The 3708 requires a shelf to be placed in the rack.
3. OEM is Original Equipment Manufacturer.
4. Refer to Appendix K, "Manuals for Default Protocol Conversion Displays" for
more information.
Chapter 11. Ordering the 3708
11-3
Installing the 3708
This part provides the following information on installing the 3708:
Chapter 12. Installation Procedures
Step I. Testing the 3708
Step 2. Setting Up the Control Terminal
Step 3. Logging onto the Control Terminal
Step 4. Entering the Configuration Data
Step 5. Activating the Configuration
Step 6. Ending the Control Terminal Session
Step 7. Connecting the Cables
Chapter 13. Configuration Proccdurco;
Defining a Port for a SNA Host
Port Number Options (Screen MIOO.I)
Port
....... .
Port Excluded
SN A Host Definition (Screen C 122.1)
Host-A Port
Host-B Port
Port
Host Name
Host Keyboard Source Field
Host Printer Source Field
SNA Host Definition (Screen ('122.2)
SNA PU Network Name
SNA PU Line Network Name
Station Address
NRZI Data Encoding
Permanent RTS (Request to Send)
Line Speed
Line Type ..
. .....
Transmit UNBIND or TERM-SELF for Session Security
SDLC Inactivity Time Out
Defining a Port for an ASCII Host
Port Number Options (Screen M I 00.1 )
Port
Port Excluded
ASCII Host Definition (Screen CI22.1)
Host-A Port
Host-B Port
Port
Host Name
Host Keyboard Source Field
Host Printer Source Field
Set Host Termination Sequence
Host Termination Sequence (in ASCII)
Line Speed
Defining a Port for an End-User Device ...
3708 Port Logon Options (Screen MlOO.2)
Port Excluded ..... .
Logon Screens Excluded
TerminalID
12-1
12-2
12-4
12-5
12-9
12-9
12-10
12-13
13-1
13-2
13-2
13-2
13-3
13-4
13-4
13-4
13-5
13-5
13-5
13-5
13-6
13-6
13-7
13-7
13-8
13-8
13-8
13-8
13-9
13-9
13-10
13-10
13-10
13-11
13-12
13-12
13-12
13-12
13-13
13-13
13·13
13-14
13-14
13-14
13-15
13-15
13-15
13-16
13-19
Installing the 3708
End-User Device Definition (Screen C123.1)
13-20
Port Number ...
13-20
Device Name ....... . . . . . . . . . .
13-20
Device Line Name
.............
13-20
SNA LV Network Name (Keyboard, Host A)
13-21
SNA LU Device Number (Keyboard, Host A)
13-21
SNA LU Network Name (Keyboard, Host B)
13-22
SNA LU Device Number (Keyboard, Host B)
13-22
SNA LV Network Name (Printer on Preassigned Host)
13-23
SNA LU Device Number (Printer on Preassigned Host)
13-23
Default SNA LV Device Number Assignments
13-24
End-User Device Definition (Screen C123.2)
13-25
Password .......
13-25
Receive XON/XOFF
13-26
Password Retry Limit
13-26
Transmit XON/XOFF
13-27
Line Speed
13-27
Device Class
13-27
Line Type .
13-28
Operating Mode
13-28
Disconnect
13-28
Interface Type
13-29
Translate Option
13-29
Parity ......
13-30
Receive Queue Size
13-30
3270 Model Emulation
13-31
Receive Queue Pacing Threshold
13-31
End-User Device Definition (Screen C123.3)
13-32
Bits/Character
13-32
Number of Stop Bits
13-33
Inactivity Time Out
13-33
Transmit Data Threshold
13-33
Auto On-Hook
13-33
Transmit Error Threshold
13-33
CDSTL (Connect Data Set To Line)
13-33
Receive Data Threshold
13-34
Send Answertone
13-34
Receive Error Threshold
13-34
Delay after Form Feed .
13-34
Delay after Carriage Return
13-34
Maximum Platen Length .
13-35
What To Do Next .........
13-35
Protocol Enveloping Definition for an End-User Device (Screen C123.4)
13-36
Full Duplex Line
13-36
Full Duplex Control Unit
13-36
Ignore Parity .......
13-37
Parity Error Substitution Character
13-37
EchopJex ...............
13-37
Attention Key Substitution Character
13-37
Delay After Receipt of CR
13-37
Recognize Terminal Attention
13-38
Allow Terminal Break
13-38
Delete Rubout Character
13-38
Line Quiet Time .....
13-38
Recognize System Request Simulation
13-39
Text Time Out ..............
13-39
3708 Planning and Installation
Permanent Request To Send
13-39
Turnaround Characters ...
13-39
Send Read Prompt
13-40
Defining the Printer Authorization Matrix
13-41
Printer Authorization Matrix (Screen CI24.0)
13-41
Printer Port Address
13-41
Printer Mode ...
13-41
Print Class
13-42
Source Device List
13-42
Default Printer Page Length
13-42
Perform Formfeed After Local Copy
13-43
3708 May Transmit Formfeed (LU_l SCS)
13-43
Perform Formfeed at Begin Bracket (LU_I SCS)
13-43
Perform Newline at Begin Bracket (LU_3)
13-43
Chapter 14. Defining the General Definition
14-1
General Definition (Screen C 127.1)
14-1
Name
14-2
Version
14-2
Date
14-2
Time .
14-2
String 1
14-2
String 2
14-2
Non-Standard Operations
14-3
Chapter 15. User-Defined Terminal Tables
15-1
Standard and Enhanced Terminal Tables
IS-I
Creating a User-Defined Terminal Table
IS-2
Looking at the Terminal Table Format
IS-3
General Description Section
IS-S
Terminal ID .......
IS-S
Flags
. . . . . .
IS-6
Cursor Addressing Class
lS-8
Alternate Control Sequence Character
15-10
Intermediate Control Sequence Character
15-10
Keyboard Mapping Definition Section
IS-II
Special Considerations for the Keyboard Mapping Definition Section
15-12
Terminal Control Section ..................
15-13
Special Considerations for the Terminal Control Section
15-14
Customization Section ...
IS-16
Changing an Existing Table
IS-18
Example 1 ........
15-18
Example 2 ........
IS-22
Modifying Extended Function Keys
IS-26
Using Predefined Terminal Tables .
IS-26
Chapter 16. Converting Between Standard and Enhanced UDTs
16-1
Converting Standard to Enhanced
16-3
Converting Enhanced to Standard
16-3
Chapter 17. Creating a User-Defined Translate Table
17-1
Looking at the Translate Table Format
17-1
Defining a New Translate Table ... . . . . . . .
17-2
Installing the 3708
Chapter 12. Installation Procedures
This chapter describes how to install the 3708.
Notes:
1. Before installing the 3708 you must complete initial setup of the 3708. Refer to
IBM 3708 Network Conversion Unit Setup (shipped with the 3708), complete the
initial setup procedures, and then, refer to this book for information on how to
configure and install the 3708 into the network.
2. You should complete the Address Registration Form that is shipped with the
3708.
3. Before installing the 3708, it is recommended that you acquire any known
microcode fixes (MCFs) for your level of microcode. This can be accomplished
by calling the service number (see "Calling for Service" on page 6-3) and
requesting that all existing MCFs be installed.
Installation consists of the following steps:
• Step 1. Testing the 3708
• Step 2. Setting Up the Control Terminal
• Step 3. Logging onto the Control Terminal
• Step 4. Entering the Configuration Data
• Step 5. Activating the Configuration
• Step 6. Ending the Control Terminal Session
• Step 7. Connecting the Cables.
Chapter 12. Installation Procedures
12-1
Step 1. Testing the 3708
This procedure verifies that the 3708 is working correctly before the control terminal
and other devices are connected.
1. Press the power switch to off (0) and disconnect any connected cables.
2. Plug the power cord into the back of the 3708, then plug the power cord into an
electrical outlet.
12-2
3708 Planning and Installation
3. Press the 3708 cartridge, with the light on the left, firmly into the slot in the
base.
Note: After the cartridge is plugged in, do not remove it unless you must do so
to solve a problem.
4. Turn on the 3708. The 3708 automatically runs a self-diagnostic test.
After approximately 10 seconds, the base Not Ready light and the cartridge light
begin blinking alternately. This means that the 3708 is working correctly.
(Refer to Chapter 2, "Using Symptoms to Solve a Problem" of IBM 3708
Network Conversion Unit Problem Determination for other light sequence
meanings.)
=
o
=
Cartridge Light
Base
Not Ready
Light
Chapter .12. Installation Procedures
12-3
Step 2 .. Setting Up the Control Terminal
1; Turn off the 3708.
2. Connect the cable from the control terminal to one of the following 3708 ports.
Note: The control terminal can be any one of the 3708 default terminals listed
in the screen on page 12-6.
• Direct connection: use port 7.
The terminal must be set for the following:
Interface
EIA 232C
Line Speed
9600 bps
Parity
Odd
Bits per character 7
Stop bits
2
Note: See Chapter 10, "Planning for Cables" for information about the
type of cables to use to connect the control terminal.
• Remote connection: use port 3.
The terminal must be set for the following:
Interface
Line Speed
Parity
Bits per character
Stop bits
Notes:
EIA 232C
11 0 - 9600 bps
Odd or even
7
2
a. Port 3 is configured for auto baud/auto parity.
b. Make sure that the modem settings match the device settings.
c. See Chapter 10, "Planning for Cables" for information about the type
of cables to use to connect the control terminal.
See Appendix I, "Terminal Switch Settings" for the required switch settings for
the terminal.
You can use other ports besides ports 3 and 7 for the control terminal
connection. See Appendix A, "IBM-Supplied Configuration" for the initial
port definitions. After configuring the 3708, you can reconfigure all 3708 ports
including ports 3 and 7 to connect to any supported device.
Note: Make sure that the terminal values for XON/XOFF pacing and line
turnaround character agree with the IBM-supplied configuration.
3. Turn on the 3708.
4. Turn on the control terminal.
5. If you are using a modem, establish the connection to the 3708.
12-4
3708 Planning and Installation
Step 3. Logging onto the Control Terminal
1. If the control terminal is remotely connected to port 3, press the carriage return
key to start the logon screens. If the control terminal is directly connected to
port 7, the logon screens should start when the terminal is turned on. If the
logon screens do not start, press the carriage return key.
Notes:
a. At any time during logon and before the first control terminal screen
(MlOO.O) is displayed, you can disconnect the control terminal from the
3708 by typing #### and pressing the carriage return key.
b. The 3708 EC number, RID number, and part number may differ from the
following examples depending on your microcode level, particular machine,
and port.
c. During logon, the control terminal operates in protocol enveloping
(line-by-line) mode. In this mode, use the period key, carriage return key, or
a defined line turnaround character as the ENTER key. You also can use
the backspace function if you want to correct typing errors. Other
cursor-positioning keys are not operational for logon.
The 3708 displays a port password screen as follows:
======IBM 3708===EC
A58809======RID 3708-001 88-0000076========PORT 07======
Cl:
Type port password
To disconnect from the 3708, type n####.n
===>
Chapter 12. Installation Procedures
12-5