Eliwell ID 985 E Manual
Read Online
Read the Eliwell ID 985 E Manual online using the built-in PDF viewer.
Text of the manual
The user has a display and four buttons
for controlling instrument status and pro-
gramming. The device can also be con-
nected to a remote display.
At start-up the instrument performs a
Lamp Test; the display and LEDs flash for a
few seconds to check that they are work-
ing correctly. The instrument has two main
menus: the Machine Status menu and the
Programming menu.
ACCESSING AND USING MENUS
The resources are arranged in a menu that
can be accessed by pressing and quickly
releasing the “set” button (Machine Status
menu) or holding down the “set” button
for more than 5 seconds (Programming
menu). To access the contents of each
folder indicated by the relevant label, just
press the “set” button once.
You can now scroll through the contents
of each folder, modify it or use its func-
tions.
If you do not use the keyboard for over 15
seconds (time-out) or if you press the
“fnc” button once, the last value shown on
the display is confirmed and you are taken
back to the previous screen mask.
REMOTE DISPLAY
This has a display with 3 digits + sign that
displays the parameter programming and
alarm display values on the controller it is
connected to during probe reading.
MACHINE STATUS MENU
(See Machine Status Menu Diagram)
To access the Machine Status menu, press
the “set” button and quickly release it.
If no alarms are present, the label “SEt”
appears. By using the “UP” and “DOWN”
buttons you can scroll through the other
folders in the menu:
-AL: alarm folder (if alarms present, except
for faulty probes/probe errors;
-SEt: Set point setting folder.
-rtc: Real Time Clock folder
-Pb1: probe 1 value folder;
-Pb2: probe 2 value folder;
-Pb3: probe 3 value folder (if present);
Set setting
Access the “Machine Status” menu, press
the “set” button and quickly release it. The
“Set” folder label appears. To display the
Set point value, press the “set” button
again.
The Set point value appears on the display.
To change the Set point value, use the
“UP” and “DOWN” buttons within 15 sec-
onds. If the parameter is LOC = y the Set
point cannot be changed.
Alarm on
If an alarm condition exists when the
Machine Status menu is accessed the “AL”
folder label appears (see section on
“Diagnostics”).
Real Time Clock
By pressing the “set” button when the
“rtc” label appears, the label d00 (days) is
Position
Associated function
Status
Set point/Reduced set point ON for parameter programming level 2
blinking when reduced set point is entered
(set point ON for setting set point)
Compressor or relay 1
ON for compressor on; blinking
for protection delay or enabling blocked
Defrosting
ON when defrosting in progress; blinking when activated
manually or by digital input
Alarm
ON for active alarm; blinking for silenced alarm
Fans
ON when fan is on
aux
ON when auxiliary output is operating
ID 985 /E LX
electronic controllers for “ventilated” refrigeration
units with remote display
fnc
set
ID985/E LX
aux
set
fnc
cod. 9IS43080
rel. 3/05
GB
aux
UP button
Scrolls through the menu items
Increases values
Activates manual defrosting
(see H31 parameter)
DOWN button
Scrolls through the menu items
Decreases the values
Parameter programmable
(see H32 parameter)
fnc button
ESC function (quit)
Parameter programmable
(see H33 parameter
Set button
Accesses Set point and rtc folder
Accesses the Menus
Confirms the commands
Displays the alarms (if active)
Stores hours/min
LEDs
BUTTONS AND DISPLAY
displayed. Use the “UP” and “DOWN” but-
tons to set days. If you do not use the but-
tons for over 2 seconds or if you press
“set” you switch to the hours (h00) and
minutes (‘00) folders: use the “UP” and
“DOWN” buttons to set the hours and
minutes respectively. If you do not use the
keyboard for over 15 seconds (time-out)
or if you press the “fnc” button once, the
last value shown on the display is con-
firmed and you are taken back to the pre-
vious screen mask.
NOTE: Always use the “set” button to
confirm the hours/minutes/days setting.
NOTE2: We recommend considering the
first day d00 as SUNDAY.
Displaying probes
If you press the “set” button when the
corresponding label appears, the value of
the probe associated with it is displayed.
PROGRAMMING MENU
(See Programming Menu Diagram)
1) Displaying level 1 parameters
To access the Programming menu, hold
the “set” button for more than 5 seconds.
If specified, the level 1 access PASSWORD
will be requested (see parameter “PA1”)
and (if the password is correct) the label
of the first folder will appear. If the pass-
word is incorrect, the display will show the
PA1 label again.
When the instrument is on stand-by, para-
meter programming can be accessed with
the display both on and off.
Use the “UP” and “DOWN” buttons to
scroll through the other folders; the fold-
ers will only display level 1 parameters.
NOTE: at this point level 2 parameters
are NOT visible even if NOT password-
protected.
2) Displaying level 2 parameters
Go to the “CnF” folder in the
Programming Menu and scroll down the
parameters until you reach the PA2 label.
By pressing and releasing the “set” button
you will enter the level 2 parameters and
the label of the first folder in the pro-
gramming menu will appear.
Level 2 parameters can be protected by a
second password (see “PA2” parameter in
“diS” folder, not to be confused with PA2
label in the “CnF” folder). If specified, level
2 parameters are hidden from the user;
when accessing the “CnF” folder the level
2 access PASSWORD will be requested and
(if the correct password is entered) the
label of the first folder in the program-
ming menu will appear.
NOTE: At this point the folders will
only display all the level 2 parameters.
Therefore level 1 parameters will only be
visible if you quit the Programming Menu
and repeat procedure 1).
To enter the folder, press “set”. The label
of the first visible parameter will appear.
To scroll through the other parameters,
use the “UP” and “DOWN” buttons. To
change the parameter, press and release
“set”, then set the desired value using the
“UP” and “DOWN” buttons and confirm
with the “set” button. Move on to the next
parameter.
NOTE: We strongly recommend that you
switch the instrument off and on again
each time parameter configuration is
changed in order to prevent malfunction-
ing of the configuration and/or ongoing
timings.
PASSWORD
Passwords “PA1” and “PA2” allow level 1
and level 2 parameters to be accessed.
There are no passwords in the standard
configuration. To enable them (value 0)
and assign them the desired value, access
the Programming menu in the “diS” folder.
If passwords are enabled, they will be
requested:
- PA1 when entering the Programming
menu (see the “Programming Menu“ sec-
tion);
- PA2 in the “Cnf” folder containing the
level 1 parameters.
FnC FUNCTION FOLDER
The FnC folder (last folder visible from
the Programming Menu, level 1) con-
tains the following functions.
They are activated using the “set” but-
ton
If the unit is switched off, the function
labels go back to their default status.
ACTIVATING MANUAL DEFROST CYCLE
To activate the defrost cycle manually,
press the “UP” button (if configured =1)
for 5 seconds. If the right defrosting con-
ditions are not present (the temperature
of the evaporator probe is higher than the
end of defrost temperature, for example)
or parameter OdO 0, the display will flash
three (3) times to indicate that the opera-
tion will not be performed.
USING THE COPY CARD
The Copy Card is an accessory connected
to the TTL serial port and used for quick
programming of the unit parameters
(upload and download parameter map to
one or more units of the same type).
Operations are described below:
Fr-Format (level 2 parameter)
This command can be used to format the
copy card necessary when used for the
first time or when used with models that
are not compatible. Warning: when the
copy card has been programmed all the
data entered is cancelled when the “Fr”
parameter is used. This operation cannot
be undone.
UL-Upload
This operation uploads the programming
parameters from the instrument.
dL-Download
This operation downloads the program-
ming parameters to the instrument.
NOTE:
• UPLOAD: instrument —> Copy Card
• DOWNLOAD: Copy Card —> instr.
The operations are performed by accessing
the folder identified by the “FPr” label and
selecting the “UL”, “dL” or “Fr” commands.
The operation is confirmed by pressing the
“set” button.
If the operation is successful, a “y” is dis-
played whereas if it is unsuccessful an “n”
will be displayed.
Download “from reset”
Connect the copy card with the instrument
OFF.
When the instrument is switched on the
programming parameters will be down-
loaded; when the lamp test has been com-
pleted, the following appear on the display
for about 5 seconds:
• label dLY if copy operation is successful
• label DLn if operation fails
NOTE:
• after downloading the instrument will
work with the parameter map settings that
have just been downloaded.
DISTANCE-MANAGED SYSTEMS
The Televis remote control systems can be
connected using the TTL serial port (the
TTL- RS 485 BUS ADAPTER 100 interface
module must be used).
To configure the instrument to do this,
you need to access the folder with the
“Add” label and use the “dEA” and “FAA”
parameters.
KEYBOARD LOCKED
Keyboard operating can be locked by pro-
gramming the “Loc” parameter (see folder
with “diS” table). If the keyboard is locked
you can access the Programming Menu by
pressing the “set” button.
The Set point can also be displayed.
ADVANCED FUNCTIONS
DOOR SWITCH INPUT
This is a clean contact digital input with
programmable polarity.
The door switch input functions are con-
trolled by the values of the following para-
meters:
ID 985/E LX
2/13
Function
Reduced set point
Aux
Pressure switch alarm reset
**default
Function label
NOT ACTIVE
SP**
AoF
rPA
Label
Function
ACTIVE
OSP
Aon
rPA
If activation state forcing is enabled (dOA
is not 0), the compressor and/or fan out-
puts can be activated when the time set in
parameters dCO and dFO expires.
Parameter H11 is used to configure the
digital input with values between -9 and
+9. Positive and negative values are used
to select the polarity assigned to the input
and:
NOTE:
the sign “-” indicates that the input is
activated when the contact is closed
The ‘+’ sign indicates that the input is
activated when the contact is open
DEVICE STAND-BY CONTROLLER
This controls the operating mode of the
device when it is on stand by according to
the following parameters:
The Stand-by controller can be digital input
or button enabled if suitably configured.
The status of the instrument when on
stand-by is determined by the value of
parameter H08. Three possible operating
modes are defined:
EXAMPLE 1: the display is off and the con-
trollers active, the instrument signals any
alarms by reactivating the display - OFF DIS-
PLAY
EXAMPLE 2: the display is off and all the
controllers, including the alarms, are also
disabled - STAND-BY
EXAMPLE 3: the display shows the “OFF”
label and all the controllers, including the
alarms, are also disabled- STAND-BY
LINK
The Link function is used to connect up to
8 instruments (1 Master device and 7 slave
devices). The distance between one device
and another must be 7 metres maximum
whereas the maximum distance between
the first and last instrument in the network
must be approximately 50m.
NOTE: the serial link between the devices is
powered.
Master
Instrument that controls the networks and
sends commands to the Slaves. The Master
is selected using parameter L00 (the value 0
defines the Master)
Slave
Instrument(s) with own controllers that also
perform(s) commands issued by the Master
(with parameters L03..L06).
Echo
This only displays the values of the instru-
ment that it is associated with (it does not
therefore have its own I/O resources but
only serves as a repeater).
NOTE: only one Echo can be connected to
anyone instrument.
Defrosting
The Link network controls defrosting. The
Master sends the defrost command which
can be performed synchronously (at the
same time) or sequentially (one defrost
after another) without affecting the normal
protections or delays for each instrument
(see parameter L03).
Other Functions
The Master can also activate the functions
associated with buttons or the Digital Input
for all the Slaves: switching lights on/off,
alarm silencing, auxiliary set point, auxiliary
relay, stand-by (on/off) and functions relat-
ed to Night & Day controller (see parame-
ter L05).
The Master can also synchronize the Slave
(or Echo device) displays with the Master
device display (see parameter L04).
NOTE: synchronized defrosting refers to
actual defrosting and not to dripping and
subsequent defrosting. The defrost LED on
the Slave units blinks when synchronized
defrosting has terminated and the Slaves
are awaiting for the thermostat control to
be enabled by the Master.
The functions are associated with the
instruments by correctly setting the para-
meters (see the parameter table for the
“Lin” label folder)
DEFROST CONTROL
The instrument can be used to select dif-
ferent types of defrosting with the para-
meter dty, defrost type.
(defrost execution mode).
The dty parameter can have these values:
0 = electrical defrosting; the compressor is
turned off.
1 = cycle reversing defrosting (hot gas);
the compressor continues operating.
2 = Free mode defrosting (compressor dis
abled).
Configuration of 3rd probe as 2nd evap-
orator probe
The 3a probe can be used to control the
defrosting of a second evaporator by con-
figuring a relay output as a 2nd evaporator
defrost relay (see par. H21…H26).
To implement this function:
a) configure the 3rd probe in 2nd evapora-
tor defrost control mode (par. H43=2EP).
b) configure a relay output as 2nd evapo-
rator defrost relay (configuration parame-
ters H21…H26).
c) define the defrost mode by setting
parameter H45.
Start of defrosting
If two evaporators are used, defrosting
starts in three different ways that are
determined by parameter H45.
• H45=0: Defrosting is enabled by con-
trolling the temperature of the 1st evapo-
rator so it is lower than parameter dSt,
•H45=1: Defrosting is enabled by control-
ling so that at least one of the two probes
is below its end of defrosting temperature
(dSt for the 1st evaporator and dS2 for
the 2nd evaporator)
• H45=2: Defrosting is enabled by control-
ling so that both the probes are below
their respective end of defrosting set
points (dSt for the 1st evaporator and dS2
for the 2nd evaporator)
The probe error condition is considered
the defrost calling probe.
When defrosting is terminated by a probe
or is timed out (see par. dEt), dripping fol-
lows (see par. dt).
End of defrosting
If two evaporators are used, defrosting
ends when both the probes have reached
or exceeded their respective end of
defrosting set points (dSt for the 1st evap-
orator and dS2 for the 2nd evaporator)
If one or both the probes are faulty,
defrosting is ended by a time-out.
NOTE:
• If there are no conditions for defrosting,
the request is ignored.
Defrosting of a single evaporator ends
when the value read by the respective
probe is equal to or higher than the end
of defrosting temperature or a time-out
occurs. Dripping starts when both defrosts
have been completed.
• If one or both the probes are faulty,
defrosting in the corresponding evaporator
is ended by a time-out.
The start of defrosting is permitted when
the corresponding temperature is lower
than the corresponding set point (dSt or
dS2).
• If probe 3 is not configured as a probe
on the second evaporator (H43 2),
defrosting on the second evaporator
occurs if a digital output is configured to
control defrosting on the second evapora-
tor (see par. H21..H25). If this is the case,
defrosting is confirmed (as if ST3
GENERAL PRESSURE SWITCH INPUT
CONTROLLER
This controller performs diagnostics on an
associated digital input using a configura-
tion table. It is activated by setting para-
meters H11 and H12 = 9.
If the pressure switch input trips, the com-
pressor loads are immediately deactivated,
the alarm LED lights up to signal tripping
and the label nPA in the alarm folder
appears on the display.
Controlling is performed using 2 parame-
ters PEn and PEI:
nPA is a subfolder of AL (Alarms), and
keeps a record of each time the pressure
switch is activated if the value indicated by
PEn is reached in a period of time that is
less than or equal to PEI, the label nPA is
replaced by PA (pressure alarm).
The alarm conditions only occurs when the
maximum number of alarms is reached
before the time indicated by parameter
PEI expires. As soon as the first alarm
occurs, the time PEI is calculated.
If the number of times the pressure switch
is activated exceeds the number estab-
lished PEn in the period PEI:
- compressor outputs, fans and defrosting
are deactivated
- the label PA is displayed in the subfolder
nPA
- the alarm LEDs and alarm relay if config-
ured are switched on.
NOTE: Once the device is in alarm mode,
it must be switched off and on again or
reset by activating the rAP parameter in
the functions menu. The nPA folders can
be reset using the rPA function in the Fnc
folder.
NOTE: If parameter PEn is set to 0 the
function is excluded and the alarms and
counts are disabled.
CONDENSER FAN CONTROLLER
This controller is associated with probe
Pb3 and features:
- operating set point
- operating differential
- exclusion of fans in defrosting mode
- start-up delay after end of defrosting If a
digital output is set as condenser fans
(H21...H24=10) the output will behave as
shown below:
If probe Pb3 is not present and alarm E3 is
active, the controller will always be on
during the defrost cycle.
Probe 3 can be excluded and the failed
connection with the instrument will not
trigger an error message.
NOTE: During dripping time the output is
OFF.
NOTE: If a digital output is programmed
as condenser fans (H21...H25 =10) parame-
ter SA3 is always an absolute value irre-
spective of the value of parameter Att.
DIAGNOSTICS
The alarm condition is always signalled by
a buzzer (if present) and the alarm icon
LED. The alarms from the faulty thermo-
stat control probe (probe 1), the faulty
evaporator probe (probe 2), and the faulty
display probe (probe 3) appear directly on
the instrument display as E1, E2, and E3
respectively.
An error condition in probe 1 (thermostat
control) causes the following:
• E1 code appears on display
• compressor is activated as indicated by
“Ont” and “Oft” parameters if these are
programmed for duty cycle or:
The error condition for probe 2 (evapora-
tor) causes the following:
• E2 code appears on display
• end of defrost due to time-out.
The error condition for probe 3 (display)
causes the following:
• E3 code appears on display Other alarms
do not appear on the instrument display
but can be seen in the “Machine Status”
menu in the “AL” folder.
The maximum and minimum temperature
alarm is regulated according to the ther-
mostat control probe (probe1) and/or dis-
play probe (probe 3). The temperature
limits are defined by the “HAL” (maximum
alarm), “LAL” (minimum alarm) and PbA
(alarm configuration on probe 1,3 or both)
parameters.
MAXIMUM AND MINIMUM TEMPERA-
TURE ALARM
If an alarm condition occurs and alarm
exclusion times are not in progress (see
alarm exclusion parameters), the alarm
icon lights up permanently and the relay
that is configured as an alarm is activated.
This type of alarm does not affect the reg-
ulating in progress.
Alarms are considered as absolute
(default) values or as values related to the
Set point (the distance from the Set point
itself) and based on the Att parameter.
If the alarms are relative (Att=1), the para-
meter HA1 is set to positive values and
LA1 to negative values.
This alarm condition can be viewed in the
folder “AL” with labels “AH1-AL1”.
ALARM WITH THRESHOLD (PROBE 3)
By setting the PbA=3 parameter an alarm
is associated to probe 3. It refers to a spe-
cific threshold (defined by the SA3 para-
meter). An over-temperature or an under-
temperature alarm is generated and the
icon is turned on. This alarm condition can
be viewed in the “AL” folder with the
labels “AH3-AL3”.
The alarm is handled as a temperature
alarm referring to probe 3: for delays and
backswings, refer to standard alarms
DEFROST ALARM
If the end of defrosting is due to a time-
out (rather then because an end of
defrosting temperature is detected by the
defrosting probe), an alarm is generated
and the icon lights up.
This condition can be viewed in the “AL”
folder with the label “Ad2”.
Automatic back swinging occurs when the
next defrost starts. By pressing any button
during the alarm condition, the signal light
disappears. In order to cancel the alarm
properly, you must wait until the next
defrost.
EXTERNAL ALARM
The device can also control an external
alarm, i.e. from a digital input. If the digital
input is enabled, the alarm control is acti-
vated by programming and remains
enabled until the next time the digital
input is deactivated. When an alarm is set
off, the alarm icon lights up permanently,
a buzzer (if present) and the relay config-
ured as alarm are activated and the com-
pressor, defrost and fan controllers are
deactivated according to the value of the
rLOparameter):
This alarm condition can be displayed in
the “AL” folder using the “EA” label. The
relay can be silenced; even if the alarm
icon starts blinking, the controllers remain
locked until the next time the digital input
is deactivated.
OPEN DOOR ALARM
If a door is open, the Open Door alarm is
signalled in response to a delay defined by
the tdO parameter. The alarm is signalled
by the flashing alarm icon. This alarm con-
dition can be viewed in the “AL” folder
with the label “Opd”.
ID 985/E LX
4/13
DISPLAY
E1
E2
E3
If simultaneous, they will be showed on the display
alternately every 2 seconds
FAULT
Faulty probe 1 (thermostat control)
Faulty probe 2 (1st evaporator)
Faulty probe 3 (display or 2nd evap-
orator)
Table of faulty probes
Ont
0
0
>0
>0
Oft
0
>0
0
>0
Compressor output
OFF
OFF
ON
dc
Par.
Description
PEn
number of errors allowed per maximum/
minimum pressure switch input switch
input (number)
PEI
Minimum/maximum pressure switch error
count time (minutes)
Output Value
Pb3 Value
ON
SCF OFF
SCF - dCF
Value
Description
0
no resources are disabled
1
disables compressor and defrosting
2
disables compressor, defrosting and fans
NOTE: Do not set parameter tAo to
zero when the door is closed since if
the door is continually opened and
closed, any alarms would never be sig-
nalled.
LINK ALARM
In the event of a master/slave/echo com-
munication failure, the No Link alarm is
signalled. This alarm condition can be
viewed on the master and slaves, if pre-
sent, in the “AL” folder with the “E7” label.
Error status is also signalled by any con-
nected echo devices with signal “- - -”
appearing on the display.
NOTE:
•The E7 error is signalled after approx. 20
seconds in “no link” condition to avoid any
link disturbance causing communication
errors.
•The E7 error is also signalled for address-
ing conflicts when:
a) the number of Slaves set on the MAS-
TER is different from the actual number of
Slaves on the network
b) 2 or more Slaves have the same
address.
ELECTRICAL
CONNECTIONS
Warning! Always switch off machine
before working on electrical connections.
The instrument has screw terminals for
connecting electrical cables with a maxi-
mum diameter of 2.5 mm2 (only one con-
ductor per terminal for power connec-
tions): for terminal capacity, see the label
on the instrument.
The relay contacts are voltage free. Do not
exceed the maximum current allowed. For
higher loads, use a suitable contactor.
Make sure that the power voltage com-
plies with the device voltage.
Probes have no connection polarity and
can be extended using an ordinary bipolar
cable (note that if probes are extended
this affects the electromagnetic compati-
bility (EMC) of the instrument: special care
must be used when wiring).
Probe cables, power supply cables and the
TTL serial cable should be kept separate
from power cables.
MECHANICAL ASSEMBLY
The unit has been designed for panel-
mounting. Drill a 29x71 mm hole, insert
the keyboard and fix it in place with the
special brackets provided. The remote dis-
play has also been designed for panel-
mounting on a cut-out measuring 45.9 x
26.4 mm. It is pressure-mounted using
special brackets.
Do not install the instruments in excessive-
ly humid and/or dirty locations. They are
suitable for use in locations with normal
pollution levels.
Always make sure that the area next to the
instrument cooling slits is adequately ven-
tilated.
TECHNICAL DATA
ID 985/E LX
Front protection: IP65.
Casing: PC+ABS UL94 V-0 resin plastic
body, polycarbonate front, thermoplastic
resin buttons.
Dimensions: front 74x32 mm, 60 mm
depth.
Mounting: on panel, with drilling template
71x29 mm (+0.2/-0.1 mm).
Operating temperature: -5…55 °C.
Storage temperature: -30…85 °C.
Usage ambient humidity: 10…90 % RH
(non-condensing).
Storage ambient humidity: 10…90% RH
(non-condensing).
Display range: -50…110 (NTC); -55…140
(PTC) °C without decimal point (parameter
selectable), on display 3 digits + sign.
Analogue inputs: three PTC or NTC inputs
(parameter-selectable).
Digital inputs: 2 voltage-free parameter-
configurable digital inputs.
Serial: TTL for Televis or Copy Card con-
nection.
Digital outputs:
4 outputs on relays: first output (A) SPDT
8(3)A 250Va, second and third output (B-
C) SPST 8(3)A 250Va, fourth output (D)
SPST 5(2)A 250Va.
Measurement range: from -55 a 140 °C.
Accuracy: better than 0.5% of bottom scale
+1 digit.
Resolution: 1 or 0.1 °C.
Consumption: 3 VA.
Power supply: 12 Va/c ±10% 50/60 Hz
Caution: check the power supply specified
on the instrument label; for information
on relay capacity and power supplies con-
tact the Sales Office.
ECHO
Front protection: IP65.
Casing: PC+ABS UL94 V-0 resin plastic
body, polycarbonate front
Dimensions: front 48x28.6 mm, 15 mm
deep.
Mounting: on panel, with drilling template
45.9x28.6 mm
Operating temperature: -5…55 °C.
Storage temperature: -30…85 °C.
Usage ambient humidity: 10…90 % RH
(non-condensing).
Storage ambient humidity: 10…90% RH
(non-condensing).
Display range: -50…110 (NTC); -55…140
(PTC) °C without decimal point (parameter
selectable), on display 3 digits + sign.
Serial: 3-way connection (GND, DATI, 12V)
on quick connection terminal block.
Resolution: 1 or 0.1 °C.
Power supply: from instrument it is con-
nected to
ID 985/E LX
5/13
DISPLAY
AH1
AL1
AH3
AL3
Ad2
EA
Opd
E7
Press any button to silence the alarm. The LED will
start to blink. If simultaneous, they will be showed
on the display alternately every 2 seconds
*No-link alarms and addressing conflicts alter-
nate with the temperature or probe error val-
ues normally displayed on the Master or Slave.
ALARM
High temperature alarm (referring to
room probe or probe 1)
Low temperature alarm (referring to
room probe or probe 1)
High temperature alarm (referring to
probe 3)
Low temperature alarm (referring to
probe 3)
Defrosting timed out
External alarm
Door Open Alarm
Master-Slave Communication failure
CONDITIONS OF USE
PERMITTED USE
For safety reasons the instrument must be installed and
used in accordance with the instructions supplied.
Users must not be able to access parts with dangerous
voltage levels under normal operating conditions.
The device must be suitably protected from water and
dust according to the specific application and only be
accessible using special tools (except for the front key-
pad)
The device can be fitted to equipment for household
use and/or similar use in the refrigeration sector and
has been tested with regard to safety in accordance
with the European harmonized reference standards.
It is classified as follows:
• as an automatic electronic control device to be inde-
pendently mounted as regards its construction;
• as a 1 B type operated control device as regards its
automatic operating features;
• as a Class A device as regards the category and struc-
ture of the software.
UNPERMITTED USE
The use of the unit for applications other than those
described is forbidden.
It should be noted that the relay contacts supplied
with the device are functional and therefore exposed
to potential faults. Any protection devices required to
comply with product requirements or dictated by com-
mon sense due to obvious safety reasons should be
installed externally.
ID 985/E LX
6/13
PAR.
DESCRIPTION
RANGE
DEFAULT
VALUE
LEVEL
U.M.
SEt
Set point with range falling between the minimum
LSE set point and the maximum HSE set point.
The value of the set point is in the ma chine sta tu s
menu
LSE...HSE
0.0
°C/°F
diF
The compressor stops when it reaches the set
point value, and restarts at a value corresponding
to the set point plus the value of the differential It
must not be 0
0.1...30.0
2.0
1-2
°C/°F
HSE
Maximum set point value
LSE...302
50.0
1-2
°C/°F
LSE
Minimum set point value
-55.0...HSE
-50.0
1-2
°C/°F
OSP
Offset point. Value to be added to set point if
reduced set point is activated (economy function).
-30.0...30.0
0
2
°C/°F
Cit
Minimum compressor ON time. Minimum time for
activating a compressor before deactivation Not
active if=0
0...250
0
2
min
CAt
Maximum compressor ON time. Maximum time for
activating a compressor before deactivation Not
active if=0
0...250
0
2
min
Ont (1)
Compressor activation time if probe is faulty. If set
to 1 with OFt=0 the compressor always remains on
whereas if Oft>0 it operates in duty cycle mode
(see diagram x)
0...250
0
1-2
min
OFt (1)
Compressor shut-down time if probe is faulty. If set
to 1 with Ont=0 the compressor always remains off
whereas if Oft>0 it operates in duty cycle mode
(see diagram x)
0...250
1
1-2
min
dOn
Delay in activating compressor relay after start-up
0...250
0
1-2
sec
dOF
Delay after shut-down; between compressor relay
shut-down and subsequent start-up the specified
time must elapse.
0...250
0
1-2
min
dbi
Delay between switch-ons; the specified time must
elapse between two subsequent switch-ons
0...250
0
1-2
min
OdO
Delay in enabling outputs after start-up of instru-
ment or after a power failure.
Not active if=0
0...250
0
1-2
min
dty
Type of defrost.
0 = electrical defrosting;
1 = cycle reversing defrosting (hot gas);
2 = Free mode defrosting (compressor disabled).
0/1/2
0
1-2
flag
dit
Period of time elapsing between the start of two
defrosts 0=function disabled
0...250
6
1-2
hours
dt1
Unit of measurement for defrost times (par. dit)
0=”dit” expressed in hours
1=”dit” expressed in minutes
2=”dit” expressed in seconds
0/1/2
0
2
flag
NOTE: At level 1 the folders will only display all the level 1 parameters. At level 2 the folders will only display all the
level 2 parameters. The level marked 1-2 allows the parameter to be displayed at both levels.
Defrosting controller-deF label
Compressor controller-CP label
dt2
Unit of measurement for duration of defrosting
(dEt parameter)
0= “dEt” parameter expressed in hours
1= “dEt” parameter expressed in minutes
2= “dEt” parameter expressed in seconds
0/1/2
1
2
flag
dCt
Selection of defrosting time count mode.
0=compressor operating hours DIGIFROST®
method). Defrosting active only if compressor is
on.
1 = equipment operating hours; defrost counting is
always active when the machine is on
2=compressor stop Each time the compressor
stops a defrosting cycle is performed according to
par. dtY
0/1/2
1
1-2
flag
dOH
Delay between start of first defrosting operation
and start-up of instrument.
1-2
min
dEt
Defrosting time-out; determines maximum dura-
tion of defrosting.
1-2
min
dSt
End of defrost temperature (determined by evapo-
rator probe)
-50.0...150
8.0
1-2
°C/°F
0...59
0
1...250
30
dE2
Defrost time-out on 2nd evaporator
1...250
30
1-2
min/sec
dS2
End of defrost temperature on 2nd evaporator
-50.0...150
8.0
1-2
°C/°F
ID 985/E LX
7/13
PAR.
DESCRIPTION
RANGE
DEFAULT
VALUE*
LEVEL**
U.M.
dPO
Determines when instrument starts up if the
defrosting cycle must be activated (if the tempera-
ture on the evaporator allows this)
y=defrosting activated at start-up
n=defrosting not activated at start-up
n/y
n
1-2
flag
tcd
Minimum time for each compressor state before
defrosting “Ontime if >0; “Offtime if >0
-31...31
0
2
min
Cod
Compressor “Off” time before defrost cycle. The
compressor is not turned on if a defrost cycle is
expected in the time indicated by the parameter.
0=Function excluded
0...60
0
2
min
Fan controller-FAn label
Defrosting controller-deF label
FPt
Determines if “FSt” and “Fot” are expressed as
absolute values or in relation to set point
0=absolute value; 1=value related to set point
0/1
0
2
flag
FSt
Fan stop temperature. Temperature limit that, if
exceeded by the value read by the evaporator
probe, stops the fans.
-50.0...150.0
2.0
1-2
°C/°F
Fot
Fan start temperature. If the temperature read by
the evaporator probe is lower than the set value
the fans remain off.
-50.0...150.0
-50.0
2
°C/°F
NOTE: At level 1 the folders will only display all the level 1 parameters. At level 2 the folders will only display all the
level 2 parameters. The level marked 1-2 allows the parameter to be displayed at both levels.
FAd
Fan activation intervention differential.
(see “FSt”, “Fot”)
1.0...50.0
2.0
1-2
°C/°F
Fdt
Delay before fan activation after defrosting
0...250
0
1-2
min
dt
Dripping time
0...250
0
1-2
min
FCO
Disables fans with compressor off
(Off)
y = fans active (with thermostat; in response to
value read by defrost probe, see “FSt” parameter);
n = fans off;
dc = duty cycle (using parameters “Fon” and “FoF”
n/y/dc
y
1-2
flag
dFd
Disables evaporator fans.
y=fans disabled
n=fans enabled
y/n
y
1-2
flag
Fod
Enables fan stop with door open and fan re-start
when door is closed (if fans were on).
n=fans stop;
y=fans unchanged
n/y
n
2
flag
FdC
Fan shut-down delay after compressor stop
0=function excluded
0...99
0
2
min
Fon
Fan start-up time in Duty mode
Cycle; valid for FCO=dc
0...99
0
2
min
FoF
Fan shut-down time in Duty
Cycle; valid for FCO=dc
0...99
0
2
min
“dd (2)
dE1...dE8; daily defrost start time
0...23/0...59
24
1
hours/min
“Fd (2)
F1...F8 festive defrost start time
0...23/0...59
24
1
hours/min
(3)
SCF
Condenser fan set point
-50.0...150.0
10
2
°C/°F
dCF
Condenser fan differential
-30...30
2
2
°C/°F
tCF
Condenser fan start-up delay after defrost
0...59
0
2
min
dCd
exclusion of condenser fans in defrost mode
n/y
y
2
Flag
ID 985/E LX
8/13
PAR.
DESCRIPTION
RANGE
DEFAULT
VALUE*
LEVEL**
U.M.
OAO
High and low temperature alarm delay after dis-
abling digital input (door closed)
0...10
0
2
hours
Alarms-AL label
tdO
Time out after alarm signal when disabling digital
input (door open)
0...250
0
2
min
tAO (5)
Temperature alarm delay time
0...250
0
1-2
min
dAT
Alarm for defrosting ended due to time out.
n=alarm not active
y=alarm active
n/y
n
2
flag
rLO
Controllers disabled by external alarm
0=no resources are disabled
1=disables compressor and defrosting
2=disables compressor, defrosting and fans
0/1/2
0
2
num
AOP
Polarity of alarm output:
0 = alarm active and output disabled;
1 = alarm active and output enabled
0/1
1
2
flag
PbA
Configuration of temperature alarm on probe 1
and/or 3:
0=on probe 1 (thermostat control)
1=on probe 3 (display)
2=on probe 1 and 3 (thermostat control and display)
3=on probe 1 and 3 (thermostat control and display)
on external threshold
0/1/2/3
0
2
num
SA3
Probe 3 alarm set point
-50.0...150.0
50
2
°C/°F
dA3
Probe 3 alarm differential
-30.0...30.0
2.0
2
°C/°F
Light & digital inputs
Lit Label
dSd
Light relay enable from door switch.
n = door open, light does not turn on;
y = door open, light turns on (if it was off)
n/y
y
2
flag
dLt
Light relay disabling delay after closing door if
“dSd”=y
0...31
0
2
min
OFL
Light relay disabled even if disabling delay
“dLt” is active
n/y
n
2
flag
dAd
Delay in enabling digital input
0...255
0
2
min
dOd
Digital input switches off loads
n/y
n
2
flag
Att
Determines if “LAL” and “HAL” are expressed as
absolute values or as a differential related to the
set point
0=absolute value
1=value related to set point
0/1
0
2
flag
Afd
Alarm differential
1.0...50.0
2.0
1-2
°C/°F
HAL (4)
Maximum alarm. Temperature limit (whose
absolute or relative value status is regulated by
“Att”) above which the alarm is activated.
LAL...150.0
50.0
1-2
°C/°F
LAL (4)
Minimum alarm. Temperature limit (whose
absolute or relative value status is regulated by
“Att”) below which the alarm is activated.
-50.0...HAL
-50.0
1-2
°C/°F
PAO (5)
Alarm exclusion time after start-up of instrument
following a power failure
0...10
0
1-2
hours
dAO
Alarm exclusion time after defrosting
0...999
0
1-2
min
dOA
Forced behaviour from digital input:
0=no enabling;
1=compressor enabled
2=fans enabled;
3=compressor and fans enabled
0/1/2/3
0
2
num
PEA
Enables forced behaviour from door light and/or
from external alarm
0=function disabled;
1=associated with door light
2=associated with external alarm;
3=associated with door light and external alarm
0/1/2/3
0
2
num
dCO
Delay in enabling compressor with consensus
0...250
0
2
min
dFO
Delay in enabling fans with consensus
0...250
0
2
min
NOTE: At level 1 the folders will only display all the level 1 parameters. At level 2 the folders will only display all the
level 2 parameters. The level marked 1-2 allows the parameter to be displayed at both levels.
ID 985/E LX
9/13
Communication
Add label
dEA
Device address in family
(valid values from 0 to 14)
0...14
0 (Televis models)
1=(Modbus models)
1-2
num
FAA
Device family (valid values from 0 to 14)
0...14
0
1-2
num
Night & Day Control-
nAd label
E00
Functions enabled during events;
0=control disabled
1=reduced set point
2=reduced set point+light 3=reduced set point+light+aux
4=instrument off
0...4
0
2
num
E01
Hours/minutes of start of intervention. Starting
from this time, the “NIGHT” mode will be enabled.
The duration is determined by EO2
0...23/0...59
0
2
hours/min
E02
Duration of event. Sets the duration of the event
that begins at time E01 determined by value E00
0...99
0
2
hours
E03 (6)
Blocking/unblocking daily or holidays defrosting.
0= “work days” defrost sequence defined by para-
meters dE1...dE8;
1= “festive/holidays” defrost sequence defined by
parameters F0...F8
0/1
0
2
flag
PAR.
DESCRIPTION
RANGE
DEFAULT
VALUE*
LEVEL**
U.M.
Link-label Lin
L00
Selects the instrument as Master
(0), Slave (from 1 to 7).
0...7
0
2
num
L01
Number of Slaves in the Network Refers to Master
only Number of Slaves in network (from 0 to 7).
Per Slaves/Echo leave value =0
0...7
0
2
num
L02
Enables ECHO control on slave:
0=instrument does not control ECHO
1=instrument controls ECHO
0/1
0
2
num
L03
Refers to Master and Slave Defrosting
Simultaneous/sequential. Master: n = simul
taneous; y = sequential. Slave: y = accept; n = ignore.
n/y
n
2
Flag
L04
Refers to Slave only. Distributed display.
n = Slave displays local values;
y = Slave displays Master display
n/y
y
2
Flag
L05
Activation of Master network functions: n = does
not ask Slaves for activation of remote functions;
y =asks Slaves for activation of remote functions.
Slave: n = ignores activation of remote functions
from Master; y = accepts activation of remote
functions from Master.
n/y
n
2
Flag
L06
Shuts down resources (compressors, fans, etc) at
end of defrosting. n=no; y=yes
n/y
y
2
Flag
Display - diS label
NOTE: At level 1 the folders will only display all the level 1 parameters. At level 2 the folders will only display all the
level 2 parameters. The level marked 1-2 allows the parameter to be displayed at both levels.
LOC
Keyboard locked. Parameters can still be pro-
grammed.
n= keyboard not locked
y= keyboard locked
n/y
n
1-2
flag
PA1
Contains the password for level 1 parameters.
Enabled if not 0
0...250
0
1-2
num
PA2
Contains the password for level 2 parameters.
Enabled if not 0
0...250
0
2
num
ndt
Display with decimal point.
n= without decimal point (only whole numbers)
y= with decimal point
n/y
n
1-2
flag
CA1
Temperature value to be added to that read by
probe 1 as specified by parameter CA
-12.0...12.0
0
1-2
°C/°F
CA2
Temperature value to be added to that read by
probe 2 as specified by parameter CA
-12.0...12.0
0
1-2
°C/°F
CA3
Temperature value to be added to that read by
probe 3 as specified by parameter CA
-12.0...12.0
0
1-2
°C/°F
CA
Application of offset
0 = modifies the temperature displayed
1 = is added to the temperature used by con-
trollers not the temperature displayed that remains
unchanged.
2= adds to temperature displayed that is
also used by controllers.
0/1/2
2
2
num
PTY(9)
Parity bit Modbus
n=none
E=even
o=odd
n/E/o
0
1-2
num
StP(9)
Stop bit Modbus
1b/2b
1b
1-2
flag
ID 985/E LX
10/13
PAR.
DESCRIPTION
RANGE
DEFAULT
VALUE*
LEVEL**
U.M.
Display - diS label
LdL
Minimum value that can be displayed
-55.0...302
-50.0
2
°C/°F
HdL
Maximum value that can be displayed
-55.0...302
140.0
2
°C/°F
ddL
Display during defrosting:
0= displays temperature read by thermostat con-
trol probe
1= displays temperature read entering defrost
cycle until set point is reached
2= displays “deF” label during defrosting until set
point is reached
(or when Ldd expires)
0/1/2
1
1-2
flag
Ldd
Time out for unlocking display (with ddL=2) if
defrosting lasts too long or E07 error occurs
0...255
0
1-2
min
dro (7)
Select °C or °F to display temperature:
0= °C
1= °F
0/1
0
1-2
flag
ddd
Value to be displayed:
0 = Set point
1 = probe 1 (thermostat control)
2 = probe 2 (evaporator)
3 = probe 3 (display)
0/1/2/3
1
2
num
Ero
Establishes which analogue input to display on the
ECHO including: 0= display of associated device
1=probe 1
2=probe 2
3=probe 3
4=Set-Point
0...4
1
1-2
num
H11 (6)
Configuration of digital inputs/polarity:
0= disabled
1 = defrost
2 = reduced set point
3 = auxiliary
4 = door switch
5= external alarm
6= disables storage of HACCP alarms
7= stand-by (On/Off)
8= maintenance request
9= HACCP alarm reset
-9...9
0
2
num
H08
Stand-by operating mode
0= only display switched off;
1= display on and controls locked;
2= display off and controls locked
0/1/2
2
2
num
H12 (6)
Configuration of digital inputs/polarity Same as
H11
-9...9
0
2
num
Configuration- CnF label
H00
Selects probe PTC or NTC
0= PTC
1= NTC
0/1
1
1-2
flag
H02
Quick activation time for functions with configured
buttons. Not possible for aux
(time expected = 1 second)
0...15
5
2
sec
H06
Button/input aux/door switch light active when
instrument is off
n/y
y
2
flag
NOTE: At level 1 the folders will only display all the level 1 parameters. At level 2 the folders will only display all the
level 2 parameters. The level marked 1-2 allows the parameter to be displayed at both levels.
H21
Digital output 1 configurability:
0= disabled 1= compressor
2= defrost 3= fans 4= alarm
5= auxiliary 6= stand-by 7= light
8= buzzer
9=Defrost 2nd evaporator
10=Condenser fans
0...10
1
2
num
H22
Digital output 2 configurability Same as H21
(default defrost)
0...10
2
2
num
H23
Digital output 3 configurability Same as H21
(default fans)
0...10
3
2
num
ID 985/E LX
11/13
PAR.
DESCRIPTION
RANGE
DEFAULT
VALUE*
LEVEL**
U.M.
Configuration- CnF label
H24
Digital output 4 configurability Same as H21
(default alarm)
0...10
4
2
num
H25 (7)
BUZZER output configurability
0= disabled
1...7= not used
8=enabled (default) if buzzer is present
0...10
8
2
num
H31
UP button configurability
0=disabled 1=defrost 2=auxiliary
3=reduced set point 4=HACCP alarm reset
5=disables alarm HACCP 6=light
7=stand-by
8= maintenance request
H32
DOWN button configurability Same as
H31(0=disabled default)
0...8
0
2
num
H33
ESC button configurability Same as
H31(0=disabled default)
0...8
0
2
num
0...8
1
2
num
H40
Enabling inversion of probe 1 and probe 2
0=Pb1 on channel 1, Pb2 on channel 2
1=Pb1 on channel 2, Pb2 on channel 1
0...1
0
2
Flag
H41
Presence of control probe:
n= not present
y= present
n/y
y
2
flag
H42
Presence of evaporator probe:
n= not present;
y= present
n/y
y
2
flag
H43
Presence of display probe:
n= not present
y= present (display probe)
2EP= probe on 2nd evaporator
n/y/2EP
n
2
flag
H45
Start of defrosting for dual evaporator:
0= defrost activated if temperature of 1st
evaporator
ID 985/E LX
12/13
if alarm(s)
present
AL
Pb1
Pb2
SEt
set
alarms
Pb1 value
Pb2 value
SEt value
set
set
set
set
change SEt
value
show alarms
if present
press and release
(single press)
Pb3
Pb3 value
set
if present
rtc
set
h00
d00
'00
2 sec
2 sec
set
hours
set
days
set
minutes
se presente
d00= Sunday
Machine Status Menu Diagram
CP
dEF
FAn
AL
level 1 par
level 1 par
level 1 par
level 1 par
PA1 0
set PA1 value
Add
diS
CnF
Fpr
level 1 par
level 1 par
level 1 par
level 1 par
PA2
level 2 par
level 2 par
level 2 par
level 2 par
level 2 par
level 2 par
level 2 par
CP
dEF
FAn
AL
Add
diS
CnF
PA2 0
set PA2 value
level 2
level 1
change
par value
scroll
parameters
press for 5 sec
dd
Fd
level 2 par
Lit
level 2 par
nAd
level 2 par
Lin
set
set
set
set
set
set
set
set
set
set
set
set
set
set
set
set
set
set
set
set
set
set
Programming Menu Diagram
PARAMETERS
level 1 folders
CP
dEF
FAn
AL
Lit
Lin
nad
Add
diS
CnF
level 2 folders
CP
dEF(+dd+Fd)
FAn
AL
Add
diS
CnF
FPr
OUT
On
Off
OFt
Ont
Ont
The error condition for probe 1
(compressor) causes the follow-
ing:
• E1 code appears on display
• the controller is activated as
indicated by the “Ont” and
“OFt” parameters if pro-
grammed for the duty cycle
Ont
0
0
>0
>0
OFt
0
>0
0
>0
Compressor output
OFF
OFF
ON
dc
Duty Cycle Diagram
Ont, OFt parameters programmed for
Duty Cycle
NOTE: The technical characteristics in this document concerning measurements (range, accuracy, resolution, etc.) refer to
the instrument in the strictest sense and not to any accessories provided such as probes, for example. This means, for exam-
ple, that an error introduced by the probe is added to any error that is characteristic of the instrument.
ID 985/E LX
13/13
Eliwell & Controlli s.r.l.
Via dell'Industria, 15 Zona Industriale Paludi
32010 Pieve d'Alpago (BL) ITALY
Telephone +39 0437 986111
Facsimile +39 0437 989066
Internet http://www.eliwell.it
Technical Customer Support:
Email: [email protected]
Telephone +39 0437 986300
Invensys Controls Europe
Part of the Invensys Group
3/2005 eng
cod. 9IS43080
1 2 3 4 5 6 7
8 9 10 11
ECH 985 - 12 V
12 13 14 15 16 17 18 19
A
(A)
(B) (C)
(D)
Supply
Pb2
Pb1
Pb3
D.I.2
D.I.1
TERMINALS
1 - 2
Probe input 1 (thermostat control)
1 - 3
Probe input 2 (1st evaporator)
1 - 4
Probe input 3 (display or 2nd evaporator see par. H43)
5 - 6
Digital input 2
5 - 7
Digital input 1
8 - 9
Link (powered; 8=-, 9=+)
10 - 11
Power supply
12 - 13
N.O. relay output (A) see H22 (defrosting default)
12 - 14
N.C. relay output (A) see H22 (defrosting default)
15 - 16
N.O. relay output (B) see H21 (compressor default)
15 - 17
N.O. relay output (C) see H23 (fan default)
18 - 19
N.O. relay output (D) see H24 (condensing fan default)
A
TTL input for Copy Card and connection to Televis
Wiring Diagram
LAL
AFd
HAL
AFd
set+ LAL
AFd
Off
set+HAL
AFd
set
1
2
Max/Min. Alarm Diagram (minimum
and maximum temperature)
The maximum temperature alarm back swing occurs when the probe temperature is:
(1) lower than or equal to HAL - AFd
if Att=Ab(solute)
(2) lower than or equal to + HAL- AFd
if Att=rE(lative)
The minimum temperature alarm back swing occurs when the probe temperature is:
(1) higher than or equal to LAL + AFd
if Att=Ab(solute)
(2) greater than or equal to set + LAL + AFd
if Att=rE(lative)
* (set -|LAL|+AFd)
The maximum temperature alarm occurs
when the probe temperature is:
(1) higher than or equal to HAL if
Att=Ab(solute)
(2) higher than or equal to Set + HAL if
Att=rEl(ative)
• if Att=Abs(olute) HAL must be with a
sign;
• if Att=rEL(ative) HAL must be only
positive.
The minimum temperature alarm occurs
when the probe temperature is:
(1) lower than or equal to LAL if
Att=Ab(solute)
(2) lower than or equal to Set + LAL if
Att=rEl(ative)
• if Att=Abs(olute) LAL must be with a
sign;
• if Att=rEL(ative) LAL must be only pos-
itive.
*NOTE: if Att=rEL(ative) LAL must be negative: therefore set point+LAL