R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 1 von 65
Version: 01A
Safety-M Communication Modules
BMxx
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 2 von 65
Version: 01A
Configuration
On the backplane bus of the Safety-M device (MS1, MSP1, MS2, MSP2) there can
be send one or two CAN standard messages which contain diagnostic data.
Basic Settings
CAN-Baudrate
500 kBit/s
Settings “cycle time”:
Zyklisch
X * Zykluszeit (X: 1 ... 255)
Nicht zyklisch
alle 500ms, oder bei Datenänderung
CAN ID message 1
CAN ID message 2
Cycle time CAN
messages
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 3 von 65
Version: 01A
Settings CAN message 1
Settings CAN message 2
Example: When the Actual position axes 1(24 Bit) , Actual SLP Teach In Position (24
Bit) and Alarm and Operation Notification is set the process data frame is arranged:
Bit 0…23: Actual position axes 1
Bit 24…47: Actual SLP Teach In Position
Bit 48…63: Alarm and Operation Notification
User data selection
Moving the selected data
bit position
View of all added logic
data
Size of selected data
Choise of process data
View of used bits
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 4 von 65
Version: 01A
CAN Messages
Message 1
Byte
Bit
„Run“ mode (2, 3, 4)
“Alarm” mode (A, F)
Byte 0
0...3
Safety-M Staus 1, 2, 3, 4, 5, 6 = FatalError, 7 = Alarm
4
0x1 (define)
5..7
Alive counter (3 Bit)
Byte 1
0...7
diagnostic data (Bit: 48..55)
Byte 2
0...7
diagnostic data (Bit: 40..47)
Byte 3
0...7
diagnostic data (Bit: 32..39)
Byte 4
0...7
diagnostic data (Bit: 8..15)
Byte 5
0...7
diagnostic data (Bit: 0...7)
Byte 6
0..6
diagnostic data (Bit 24.. 30)
error code high Byte
7
„0“
„1“
Byte 7
0..7
diagnostic data (Bit: 16..23)
error code low Byte
Message 2
Selectable process data (extended diagnostic data)
Byte
Data
BYTE 0
Process data (Bit 56..63)
BYTE 1
Process data (Bit 48..55)
BYTE 2
Process data (Bit 40..47)
BYTE 3
Process data (Bit 32..39)
BYTE 4
Process data (Bit 24..31)
BYTE 5
Process data (Bit 16..23)
BYTE 6
Process data (Bit 8..15)
BYTE 7
Process data (Bit 0..7)
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 5 von 65
Version: 01A
Connection and installation
The BMxx modules must be connected via backplane connector with a Safety-M
basic module.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 6 von 65
Version: 01A
Start-Up BM11
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 7 von 65
Version: 01A
Definitions
BM11 is a shorthand term for communication module BM11 - DeviceNet.
Intended Use
The module BM11 can not be used for safety-related reactions, it is used exclusively
for non-secure data transmission with DeviceNet protocol.
Scope of delivery
Is included:
Communication module BM11 – DeviceNet
EDS file (on CD-ROM)
Unit Design
The BM11 module has three LEDs.
These functions of the LED shows the following table:
LED
colour
mode
description
RUN
green
„flashing“
Status OK
DP
green
„permanently“ DeviceNet connection aktiv
green
„flashing “
DeviceNet at IDLE mode
red
„flashing “
Error in device (contact manufacturer)
red
„flashing “
connection timeout
24V bus supply voltage is missing
Incorrect setting the bus address or baud
rate
red/green „alternating“
self-test mode
XB
green
„permanently“ processing OK
green
„flicker“
missing CAN-Telegramm
green
„flashing “
processing auto-baud
red
„permanently“ Error in device (contact manufacturer)
red
„flashing “
Resettable error message
red/green „alternating“
self-test mode
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 8 von 65
Version: 01A
Procedure
A start-up may only be carried out by qualified personnel!
Please note when commissioning the safety instructions!
In the following, a startup using RSNetWorx and shown as an example.
Expiry
First, the provided EDS file must be loaded and included in the network.
Then setting the address and configuration for the BM11 must be made. Then the
data of the BM11 can be displayed and validated.
Integration of EDS file
The integration of the EDS file is done via the menu Tools> EDS Wizard.
In this window EDS files
integrated,
(Register an EDS file(s))
removed,
(Unregister a device)
Icons assigned
(Change a device’s graphic image)
Newly created
(Create an EDS file)
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 10 von 65
Version: 01A
Integrated into the network
Can then be drawn by "drag and drop" into the plan in the device vendor hardware
menu under "Anybus-IC DEV".
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 11 von 65
Version: 01A
Setting the BM11 address
Double-click on "Anybus-IC DEV", the following information can be displayed.
The only setting that needs to be made here is assignment of the bus address
(node), which must be the same setting on the unit BM11.
General Settings:
CAN-ID and IO-Dates:
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 12 von 65
Version: 01A
DeviceNet scanner configuration
By selecting the scanner (here: 1756-DNB), the following settings must be made.
• Select the I/O parameters:
In the Scan List menu the I/O parameters must be selected.
mapping of the input data:
In the Input menu, input information (16 bytes Cyclic) must be "mapped" into the
address space of the scanner.
When all settings are made, the network must be saved.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 13 von 65
Version: 01A
Integration into RSLogix 5000
To validate the data from the scanner (1756-DNB), the scanner must be included in
the "I / O Configuration".
By selecting the module can be in the "Module Properties" in the menu of saved
RSNetWorx network load.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 14 von 65
Version: 01A
Validation of BM11 dates
You can activate the Controller Tags window from the Logic menu.
Before the data can be validated, the DeviceNet scanner must be placed in the
"RUN" mode.
This is done by setting bit "Local: 4: O.CommandRegister.Run".
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 15 von 65
Version: 01A
Start-Up BM21
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 16 von 65
Version: 01A
Device settings
Version1:
Rotary dip switches for
selecting address and
baudrate
CAN Interface
3 LEDs show
operating mode
Dip switches for bus
termination
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 17 von 65
Version: 01A
Version2:
Rotary dip switch for selecting
addres s and baudrate ( LOW )
CAN Interface
3 LEDs show
operating mode
Dip switches for bus
termination TS )
(
Rotary dip switch for selecting
address and baudrate ( HIGH )
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 18 von 65
Version: 01A
LEDs
There are 3 LEDs on the front side of the BM21:
LED name
state
meaning
solution
RUN
Constant red or
green
Internal error
BM21 damaged
green blinking
BM21 is working
-
ST
Constant red
The CANopen controller is bus off
Check connection
Red single flash
Warning limit
At least one of the error counters of
the CAN controller has reached or
exceeded the warning level (too many
error frames)
Red double flash
Error control event
A
guard
event
(NMT-slave
or
NMTmaster) or a heartbeat event
(heartbeat consumer) has occurred
Green blinking
CANopen state PREOPERATIONAL
The device is in state
PREOPERATIONAL
Green single flash
CANopen state STOPPED
The device is in state STOPPED
Constant green
CANopen is operating
XB
Constant red
No device mapping has been configured.
Write the mapping into the OD index
0x6200, subindex 1 to 8
Orange blinking
At least one device is mapped. For at
least 1 second no diagdata was received
from at least one mapped device
Is the OD index 0x6200 configured
with the right values?
They has to match with the CAN ID of
the mapped Safety-M.
Is the the Safety-M up and working?
Green flashing
Within the last second diagdata was
received from all mapped devices.
-
RUN
ST
XB
off
red
off
Invalid NodeID
Select a NodeID with the rotary
dipswich within the range from 1 to
126.
Note: if both LEDs (green/red) are switched on at the same time, the color of the
LED is orange
CAN bus termination
For CAN to work properly it is necessary to terminate both ends of the wires with a
resistor with 120 ohm.
Is the BM21 at an end of the wire and the terminator resistor is not integrated in the
jack, it can be patched in with the dipswitch XB.
dipswitchindex XB
Assigned bus
1
CANopen Interface
2
Back plane bus
In the ON position, the 120 ohm resistor for termination is active.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 19 von 65
Version: 01A
Parameterising the back plane
communication
The used BM21 devices have to be configured with for the network unique CAN IDs.
This CAN IDs have to be entered per SDO into the OD index 0x6200 and the
corresponding subindex for the device.
Index
Subindex
meaning
0x6200 1
CAN ID of the 1. mapped device or 0, if not used
0x6200 2
CAN ID of the 2. mapped device or 0, if not used
0x6200 3
CAN ID of the 3. mapped device or 0, if not used
0x6200 4
CAN ID of the 4. mapped device or 0, if not used
0x6200 5
CAN ID of the 5. mapped device or 0, if not used
0x6200 6
CAN ID of the 6. mapped device or 0, if not used
0x6200 7
CAN ID of the 7. mapped device or 0, if not used
0x6200 8
CAN ID of the 8. mapped device or 0, if not used
An example: If you want the TPDO5 contain the diagdata of the BM21 with the CAN
ID 0x107, then you have to write the value 0x107 into the OD index 0x6200,
subindex 5.
Parameterising the CANopen
communication
Every CANopen participant has to have an unique NodeID.
The NodeID of a BM21 is configured with the rotary dipswitches on the front side.
Each of the rotary dipswitches has 16 possible positions. You can understand the
two rotary dipswitches as high and low nibble of a byte. They are labeled „HIGH“ and
„LOW“ on the front side. So the value of the rotary dipswitches can be calculated as
follows:
RDSvalue = 16 x (value of the „HIGH“ rotary dipswitch) + (value of the „LOW“ rotary
dipswitch).
Please take into account, that if you use more than one BM21 in the same CANopen
network, their adresses has to differ by 2 at least! As for the fact a CANopen
participant can have only an address within the range from 1 to 127, the most
significant bit is used for selecting the baurate. The BM21 supports 500 kBaud and 1
MBaud. If the most significant bit of RDSvalue is 0, the device uses 500 kBaud, if it is
1, the device uses 1 MBaud. Because of the number of generated TPDOs as further
restriction a limitation for the highest configurable address applies. So the range for
the address is 1 to 126.
(If you configure the address as 127, the device sees it as 126)
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 20 von 65
Version: 01A
If you want the BM21 to generate heartbeat messages, you can configure the
„producer heartbeat time“ as described in „Heartbeat producer“ below.
An example: „HIGH“ rotary dipswitch has the value 10, the „LOW“ rotary dipswitch
has the value 3.
RDSvalue = 10*16 + 3 = 163 = 0xA3
The most significant bit is set, so the BM21 CANopen interface would be configured
with 1 MBaud.
The NodeID is represented from the lower significant 7 bit, so it can be calculated
with: (0xA3 & 0x7F) = 0x23 = 35.
As described in „TPDOs“ below, knowing the NodeID, the COB-IDs can be
calculated:
TPDO
COB-ID
TPDO1
0x180 + 0x23 = 0x1A3
TPDO2
0x280 + 0x23 = 0x2A3
TPDO3
0x380 + 0x23 = 0x3A3
TPDO4
0x480 + 0x23 = 0x4A3
TPDO5
0x180 + 0x23 +1 = 0x1A4
TPDO6
0x280 + 0x23 +1 = 0x2A4
TPDO7
0x380 + 0x23 +1 = 0x3A4
TPDO8
0x480 + 0x23 +1 = 0x4A4
If you want to, you can change the COB-IDs of the TPDOs by writing the desired
values into the appropriate positions into the OD.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 21 von 65
Version: 01A
Device specific OD entries
Index
Subindex Type
Meaning
0x6000 0x00
UINT8
Number of used subindexes (const 8)
0x6000 0x01
UINT8
1. byte diagdata of the 1. mapped device
0x6000 0x02
UINT8
2. byte diagdata of the 1. mapped device
0x6000 0x03
UINT8
3. byte diagdata of the 1. mapped device
0x6000 0x04
UINT8
4. byte diagdata of the 1. mapped device
0x6000 0x05
UINT8
5. byte diagdata of the 1. mapped device
0x6000 0x06
UINT8
6. byte diagdata of the 1. mapped device
0x6000 0x07
UINT8
7. byte diagdata of the 1. mapped device
0x6000 0x08
UINT8
8. byte diagdata of the 1. mapped device
0x6001 0x00
UINT8
Number of used subindexes (const 8)
0x6001 0x01
UINT8
1. byte diagdata of the 2. mapped device
0x6001 0x02
UINT8
2. byte diagdata of the 2. mapped device
0x6001 0x03
UINT8
3. byte diagdata of the 2. mapped device
0x6001 0x04
UINT8
4. byte diagdata of the 2. mapped device
0x6001 0x05
UINT8
5. byte diagdata of the 2. mapped device
0x6001 0x06
UINT8
6. byte diagdata of the 2. mapped device
0x6001 0x07
UINT8
7. byte diagdata of the 2. mapped device
0x6001 0x08
UINT8
8. byte diagdata of the 2. mapped device
0x6002 0x00
UINT8
Number of used subindexes (const 8)
0x6002 0x01
UINT8
1. byte diagdata of the 3. mapped device
0x6002 0x02
UINT8
2. byte diagdata of the 3. mapped device
0x6002 0x03
UINT8
3. byte diagdata of the 3. mapped device
0x6002 0x04
UINT8
4. byte diagdata of the 3. mapped device
0x6002 0x05
UINT8
5. byte diagdata of the 3. mapped device
0x6002 0x06
UINT8
6. byte diagdata of the 3. mapped device
0x6002 0x07
UINT8
7. byte diagdata of the 3. mapped device
0x6002 0x08
UINT8
8. byte diagdata of the 3. mapped device
0x6003 0x00
UINT8
Number of used subindexes (const 8)
0x6003 0x01
UINT8
1. byte diagdata of the 4. mapped device
0x6003 0x02
UINT8
2. byte diagdata of the 4. mapped device
0x6003 0x03
UINT8
3. byte diagdata of the 4. mapped device
0x6003 0x04
UINT8
4. byte diagdata of the 4. mapped device
0x6003 0x05
UINT8
5. byte diagdata of the 4. mapped device
0x6003 0x06
UINT8
6. byte diagdata of the 4. mapped device
0x6003 0x07
UINT8
7. byte diagdata of the 4. mapped device
0x6003 0x08
UINT8
8. byte diagdata of the 4. mapped device
0x6004 0x00
UINT8
Number of used subindexes (const 8)
0x6004 0x01
UINT8
1. byte diagdata of the 5. mapped device
0x6004 0x02
UINT8
2. byte diagdata of the 5. mapped device
0x6004 0x03
UINT8
3. byte diagdata of the 5. mapped device
0x6004 0x04
UINT8
4. byte diagdata of the 5. mapped device
0x6004 0x05
UINT8
5. byte diagdata of the 5. mapped device
0x6004 0x06
UINT8
6. byte diagdata of the 5. mapped device
0x6004 0x07
UINT8
7. byte diagdata of the 5. mapped device
0x6004 0x08
UINT8
8. byte diagdata of the 5. mapped device
0x6005 0x00
UINT8
Number of used subindexes (const 8)
0x6005 0x01
UINT8
1. byte diagdata of the 6. mapped device
0x6005 0x02
UINT8
2. byte diagdata of the 6. mapped device
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 22 von 65
Version: 01A
0x6005 0x03
UINT8
3. byte diagdata of the 6. mapped device
0x6005 0x04
UINT8
4. byte diagdata of the 6. mapped device
0x6005 0x05
UINT8
5. byte diagdata of the 6. mapped device
0x6005 0x06
UINT8
6. byte diagdata of the 6. mapped device
0x6005 0x07
UINT8
7. byte diagdata of the 6. mapped device
0x6005 0x08
UINT8
8. byte diagdata of the 6. mapped device
0x6006 0x00
UINT8
Number of used subindexes (const 8)
0x6006 0x01
UINT8
1. byte diagdata of the 7. mapped device
0x6006 0x02
UINT8
2. byte diagdata of the 7. mapped device
0x6006 0x03
UINT8
3. byte diagdata of the 7. mapped device
0x6006 0x04
UINT8
4. byte diagdata of the 7. mapped device
0x6006 0x05
UINT8
5. byte diagdata of the 7. mapped device
0x6006 0x06
UINT8
6. byte diagdata of the 7. mapped device
0x6006 0x07
UINT8
7. byte diagdata of the 7. mapped device
0x6006 0x08
UINT8
8. byte diagdata of the 7. mapped device
0x6007 0x00
UINT8
Number of used subindexes (const 8)
0x6007 0x01
UINT8
1. byte diagdata of the 8. mapped device
0x6007 0x02
UINT8
2. byte diagdata of the 8. mapped device
0x6007 0x03
UINT8
3. byte diagdata of the 8. mapped device
0x6007 0x04
UINT8
4. byte diagdata of the 8. mapped device
0x6007 0x05
UINT8
5. byte diagdata of the 8. mapped device
0x6007 0x06
UINT8
6. byte diagdata of the 8. mapped device
0x6007 0x07
UINT8
7. byte diagdata of the 8. mapped device
0x6007 0x08
UINT8
8. byte diagdata of the 8. mapped device
0x6200 0x00
UINT8
Number of used subindexes (const 8)
0x6200 0x01
UINT32 CAN ID of the 1. mapped device or 0, if not used
0x6200 0x02
UINT32 CAN ID of the 2. mapped device or 0, if not used
0x6200 0x03
UINT32 CAN ID of the 3. mapped device or 0, if not used
0x6200 0x04
UINT32 CAN ID of the 4. mapped device or 0, if not used
0x6200 0x05
UINT32 CAN ID of the 5. mapped device or 0, if not used
0x6200 0x06
UINT32 CAN ID of the 6. mapped device or 0, if not used
0x6200 0x07
UINT32 CAN ID of the 7. mapped device or 0, if not used
0x6200 0x08
UINT32 CAN ID of the 8. mapped device or 0, if not used
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 23 von 65
Version: 01A
TPDOs
When initialising the BM21, the following COB-IDs are used for the TPDOs. They can
be changed on the default position within the OD (index 0x1800 to 0x1807, subindex
1).
TPDO
COB-ID
assigned device
TPDO1
0x180 + NodeID
device 1
TPDO2
0x280 + NodeID
device 2
TPDO3
0x380 + NodeID
device 3
TPDO4
0x480 + NodeID
device 4
TPDO5
0x180 + NodeID +1
device 5
TPDO6
0x280 + NodeID +1
device 6
TPDO7
0x380 + NodeID +1
device 7
TPDO8
0x480 + NodeID +1
device 8
The mapping of the TPDOs can not be changed, but can be readed from the OD
index 0x1A00 to 0x1A07.
A TPDO telegram is generated whenever there is a change in the received diagdata
from the mapped device.
As example: if there is a change in at least one byte of the diagdata received from
the BM21 on the back plane bus from device 3, then a TPDO3 will be generated.
SDO
The data communication with SDO uses the standard COB-IDs 0x580 + NodeID for
sending and 0x600 + NodeID for receiving.
The OD entry 0x2000 contains type information about the Safety-M installed. These
information are only valid if only one Safety-M is connected to the BM21!!!
Index
Subindex
Description
0x2000
0x00
number of used
subindexes
(6)
0x2000
0x01
4 Byte Serial number
0x2000
0x02
First byte firmware version
0x2000
0x03
Second byte firmware
version
0x2000
0x04
Third byte firmware
version
0x2000
0x05
Fourth byte firmware
version
0x2000
0x06
2 Byte Device ID
The version number consists of four numbers. For example “2.0.2.46”.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 24 von 65
Version: 01A
Heartbeat producer
The BM21 is a heartbeat producer in terms of the CANopen standard.
The „producer heartbeat time“ is adjustable and can be change by writing into the OD
index 0x1017.
The default value is 0, which means the production of heartbeat messages is
switched off.
Valid values are in the range from 0 to 60000. The unit is 1 ms.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 25 von 65
Version: 01A
Start-Up BM31
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 26 von 65
Version: 01A
Description of function
The BM31 enables the user to transmit CAN telegrams (diagnostic telegram e.g.
Safety-M) via PROFIBUS DP. The system will receive and pass on a maximum
number of 8 CAN telegrams.
Make sure to parameterize the subassembly as Profibus participant (slave). The
relevant GSD files are enclosed with the device.
The device will automatically identify the PROFIBUS baud rate ranging from
9.6kbaud to 12Mbaud. The maximum size of any output information is 64 Byte.
Definitely make sure to connect the BM31 to one or several „master
subassemblies“(Safety-M Basic modules)“using the plug-in connectors available on
the rear panel.
Make sure to perform the Profibus connection in compliance with the installation
regulations of PNO.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 27 von 65
Version: 01A
Device settings
Version1:
The settings specified below are adjustable at the front panel:
Diagnostic LED‘s
PROFIBUS
connector
PROFIBUS
address switch
Coding switch for bus termination
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 28 von 65
Version: 01A
Version2:
Rotary dip switch for selecting
addres s and baudrate ( LOW )
Profibus Interface
3 LEDs show
operating mode
Dip switches for bus
termination TS )
(
Rotary dip switch for selecting
address and baudrate ( HIGH )
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 29 von 65
Version: 01A
Address dials
Enter Profibus address using hexadecimal code.
e.g. address: 5:
ADDR HIGH = “0”
ADDR LOW = “5“
e.g. address: 46:
ADDR HIGH = “2”
ADDR LOW = “E“
Coding switch
Terminating resistors for CAN bus connection
1
2
ON
Switch 1
120 Ohm terminating resistor for CAN on rear
panel
Switch 2
120 Ohm terminating resistor for 2nd CAN
interface via SUB-D jack
Diagnosis
LED
Colour Mode
Designation
RUN
green
„flashing“
subassembly OK
DP
green
„permanent“ Profibus connection active
green
„flashing“
Profibus connection interrupted
red
„flashing“
Transmitted parameter data are invalid
XB
green
„flashing“
„internal“ CAN telegram (Safety-M) being
received
red
„flashing“
CAN telegram missing or
CAN telegram not received within „CAN WD
Timeout“ period
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 30 von 65
Version: 01A
How to proceed
Make sure to have the system put into operation by qualified personnel only! Make
sure to respect the safety instructions when putting the system into operation!
Following below is an example which shows the start-up in Step7.
Integration of the GSD file
First, copy the GSD to the Step7 software directory.
Installation of GSD file
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 31 von 65
Version: 01A
Integration into Step7 network plan
Go to subitem „Additional Field Devices“->“General“-> BM31 DP-V0 to drag to
network plan and assign Profibus address.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 32 von 65
Version: 01A
Integration into HW-Konfig
Select subassembly BM31 and enter CAN objects at plug-in locations (INPUT: 8
Byte).
You may enter 1 to 8 CAN objects depending on the application.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 33 von 65
Version: 01A
Configuration of BM31
Below, the configurations required for the internal CAN bus (bus on rear panel) of
the Safety-M series of subassemblies are shown.
The settings specified below are available:
CAN baud rate
Set baud rate for CAN communication (currently the
only setting admissible is 500kBit/s)
No. of CAN modules
Number of CAN objects available at plug-in locations.
Module ID
Fixed setting „1“
Timeout CAN WD
Timeout
Timeout period „internal“ CAN communication (refer to
configuration of diagnosis described by programming
manual)
Note:
The configured data shall be adopted by the BM31 only after connection to the
PROFIBUS master system. Otherwise the „Default settings“ shall prevail:
Parameter
Default value
CAN baud rate
500 kBit/s
No. of CAN modules
8
Module ID
1
Timeout CAN WD
Timeout
8ms
CAN ID
192
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 34 von 65
Version: 01A
Configuration of CAN objects
The settings specified below are available:
CAN ID:
CAN Identifier (type: Standard ID)
Setting range: 1 …. 2047
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 35 von 65
Version: 01A
Start-Up BMB1
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 36 von 65
Version: 01A
Device description and operation
Together with the Safety-M basic module this device works as a gateway from
backplane CAN bus to EtherCAT. The user has the possibility to send the status
message data to EtherCAT.
Max. user data from 8 CAN messages can be send.
Till 32 byte user data can be received from EtherCAT and send to the Safety-M
device. This 32 byte data will be transmitted with 4 CAN messages to 4 basic
devices.
Device has to be configured as an EtherCAT slave device.
Ethernet data rate will be 100Mbit/s in full duplex mode. Size of output data is 64
byte, input data is 32 Byte.
Characteristic data
Device BMB1
Response time
Cycletime 10 ms
Number of CAN objects
1 to 8
Data size CAN telegram
8 Byte
CAN ID
Standard (11 bBit)
Table 3: Characteristic data
Device settings
Image 1: Front side
No settings on the device needed.
Diagnostic-LEDs
EtherCAT-plug IN/OUT
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 37 von 65
Version: 01A
Safety related characteristics
BMB1 can only be used as a non safe communication with EtherCAT protocol.
Connection and installaation
BMB1 has to be connected to a basic device (MS1, MSP1, MS2, MSP2) with a back
plan connetor.
Installation Safety-M-module
The module is solely to be installed in control cabinets with a degree of protection of
at least IP54.
The modules must be vertically fastened on a top hat rail
The ventilation slots must be kept unobstructed, to ensure adequate air circulation
inside the module.
Terminal assignment
Image 4: Assignment RJ45
Pins
1 … 8
RJ45
Pin
Name
Description
Colour
1
TX+
Tranceive Data +
white-orange
2
TX-
Tranceive Data -
orange
3
RX+
Receive Data +
white-grün
4
nc.
Not used
blue
5
nc.
Not usedt
white-blue
6
RX-
Receive Data -
green
7
nc.
Not used
white-brown
8
nc.
Not usedt
brown
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 38 von 65
Version: 01A
Start up
Procedure
Start-up must only be performed by qualified personnel!
Strictly follow the safety regulations when commissioning!
Parameterization
Usage of program TwinCAT from Beckhoff.
Installation ESI-File
Copy ESI-File into ESI-Folder of TwinCAT program.
TwinCAT program has to be closed for this step.
After starting TwinCAT the ESI cache will be reinitialized.
Image 5: TwinCAT root for ESI-File
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 39 von 65
Version: 01A
Settings SafePLC
CAN-IDs for the status message data can be configured in the connection settings
SafePLC.
Image 6: Connection settings SafePLC
Note:
The 4 CAN messages with input bytes for BMB1 are transmitted via the
backplane bus with CAN ID’s - 0x9D up to 0xA0 – and can’t be use for other
points.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 40 von 65
Version: 01A
Following table shows the defined CAN ID’s for input and output bytes for EtherCAT.
Bytes
CAN-ID
Direction
0 bis 7
0xA1
Output (BMB1->EtherCAT Master)
8 bis 15
0xA2
Output (BMB1->EtherCAT Master)
16 bis 23
0xA3
Output (BMB1->EtherCAT Master)
24 bis 31
0xA4
Output (BMB1->EtherCAT Master)
32 bis 39
0xA5
Output (BMB1->EtherCAT Master)
40 bis 47
0xA6
Output (BMB1->EtherCAT Master)
48 bis 55
0xA7
Output (BMB1->EtherCAT Master)
56 bis 63
0xA8
Output (BMB1->EtherCAT Master)
0 bis 7
0x9D
Input (EtherCAT Master-> BMB1)
8 bis 15
0x9E
Input (EtherCAT Master-> BMB1)
16 bis 23
0x9F
Input (EtherCAT Master-> BMB1)
24 bis 31
0xA0
Input (EtherCAT Master-> BMB1)
Table 4: Defined CAN-IDs CAN messages to EtherCAT
Integration BMB1 into TwinCAT
Open TwinCAT System Manager and if necessary create a new project.
Image 7: TwinCAT System Manager
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 41 von 65
Version: 01A
Click “I/O Device” -> “Append Device“.
Image 8: TwinCAT System Manager with context menu “I/O Device“
Confirm “EtherCAT“
Image 9: TwinCAT menu “I/O device“
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 42 von 65
Version: 01A
Now a EtherCAT master is added into TwinCAT and searching for EtherCAT slave
can be started. The EtherCAT –Slave should be running and connected to the PC
(TwinCAT program).
Image 10: TwinCAT with EtherCAT master device
Click “Device 1 (EtherCAT)“ and then „Scan boxes“.
Searching for slave device is starting.
Image 11: TwinCAT with context menu of EtherCAT master.
By clicking on the „ BMB1“, the input and output bytes are displayed.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 43 von 65
Version: 01A
Image 12: TwinCAT with founded EtherCAT-slaves
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 44 von 65
Version: 01A
If “Free Run Status change“ in the toolbar is selected, the EtherCAT connection is
opened.
Status message data sent from BMB1 over EtherCAT are displayed in TwinCAT.
Image 13: TwinCAT with Free Run mode
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 45 von 65
Version: 01A
Output bytes, sent to BMB1 device can be selected and be set in here.
Image 14: TwinCAT output bytes
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 46 von 65
Version: 01A
Bild 15: TwinCAT with dialog „Set Value Dialog“
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 47 von 65
Version: 01A
Diagnostic-LED
Device BMB1 has three LEDs.
Conditions:
LED
Color
Mode
Description
RUN
green
„blinking“
Device OK
DP
green
„constant“
EtherCAT Connection is active
green
„ blinking “
BMB1 initialized, waiting for EtherCAT
connection
red
„ blinking “
BMB1 in startup mode
XB
green
„ blinking “
Minimum one CAN message (Safety-M)
received
red
„ blinking “
no CAN message received
Table 5: LED-conditions
Modification / handling changes to the device
Maintenance work must solely be carried out by qualified personnel.
Regular maintenance work is not required.
Repair
The devices must always be replaced as whole units
Repair work on the device can only be performed in the factory.
Warranty
By opening the module without permission the warranty will become null and void.
Note:
By modifying the module the safety approval will become null and void!
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 48 von 65
Version: 01A
Start-Up BMC1
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 49 von 65
Version: 01A
Device description and operation
SM53 is a communication device and can only be used with a Safety-M basic Module
(and their variants).
Together with the Safety-M basic module this device works as a gateway from
backplane CAN bus to PROFINET. The user has the possibility to send the status
message data () to PROFINET DP.
Max. user data from 8 CAN messages can be send.
Starting at software version 1.2.0.1 data from SPS to Safety-M device can be
transferred via PROFINET IO. These data are sent from BMC1 device via
configurable CAN telegram to the Safety-M Basic device. This is to control the
functional inputs of the Safety-M.
Device has to be configured as a PROFINET slave device.
Corresponding GSDML-file is included with the device.
Ethernet data rate will be 100Mbit/s in full duplex mode. Size of output data is
maximum 64 byte.
Characteristic data
Device BMC1
Response time
Variable, depends on used slots, between 24
and 68 ms
Number of CAN objects
1 … 8
Data size CAN telegram
8 Byte
CAN ID
Standard
Table 3: Characteristic data
Device settings
On front side of the device following components are visible:
Image 1: Front side
Dip switches for bus termination
(See chapter CAN bus termination)
Diagnostic-LED
(See chapter „Diagnostic-LED‘)
PROFINET-plug
(See chapter Terminal assignment)
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 50 von 65
Version: 01A
Safety related characteristics
BMC1 can only be used as a non safe communication with PROFINET-protocol.
The Proof-Test-interval according to EN61508 is up to 20 years – after this time the
device hast o be replaced
Safety note:
The safety regulations and EMC guidelines hast o be observed.
Connection and installation
BMC1 has to be connected to a Safety-M basic module with a back plan connector.
Installation of PROFINET connector sees installation instructions of PNO.
Installation Safety-M-module
The module is solely to be installed in control cabinets with a degree of protection of
at least IP54.
The modules must be vertically fastened on a top hat rail
The ventilation slots must be kept unobstructed, to ensure adequate air circulation
inside the module.
CAN bus termination
Dip switch 1 activates the termination resistor for CAN backplane communication. Dip
switch 2 is not used.
1
2
ON
Dip switch
1
120 ohm resistor for termination
(ON (= right position) = active, OFF = open)
Dip switch
2
Not used
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 51 von 65
Version: 01A
Terminal assignment
Image 4: Assignment RJ45
Pins
1 … 8
RJ45
Pin
Name
Description
Colour
1
TX+
Tranceive Data +
white-orange
2
TX-
Tranceive Data -
orange
3
RX+
Receive Data +
white-grün
4
nc.
Not used
blue
5
nc.
Not usedt
white-blue
6
RX-
Receive Data -
green
7
nc.
Not used
white-brown
8
nc.
Not usedt
brown
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 52 von 65
Version: 01A
Procedure
Start-up must only be performed by qualified personnel!
Strictly follow the safety regulations when commissioning!
The following shows an example of a start-up in Step7.
Note:
The S7 CPU hast o be activated before the BMC1 device is switched
on.
Parameterization
First the GSDML File hast o be included
Therefore the GSDML file (short GSD file) has to copy into the Step7 program folder.
Installation GSDML-File
In the window „HW-Config“ of the Siemens SIMATIC software in the menu tab
„Options / Install GSD File...“ the installation of the GSDML file can be done:
Image 5: SIMATIC HW Config with menu „Install GSD File“
Window „Install GSD File“ is opened and select the entry in the drop down menu.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 53 von 65
Version: 01A
One click to „Browse …“ and the root directory where the GSDML file is can be
selected.
Image 6: Choice of GSDML file
Afterwards in the listing GSD/GSDML-File the corresponding GSDML file can be
selected via mouse click and with activation of button „Install“ the file can be installed.
Note:
In the window „HW-Config“ and „NetPro“ of the SIMATIC-software no projects should
be opened otherwise the GSDML file cannot be installed.
Integration NetPro
After the installation of the GSD file the device has to be integrated in the network
plan of Step7. In the program “NetPro” the network plan for this project has to be
opened.
Image 7: NetPro
In window „Selection of the network“ the BMC1 device can be selected.
You can find the device under
„PROFINET IO / Additional Field Devices / General / BMxx / BMC1 / BMC1 V1.1“
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 54 von 65
Version: 01A
Image 8: Selection of the network
Device BMC1 can be dragged with the mouse into the network plan and is then inserted
there.
Image 9: Program NetPro with opened network plan and inserted BMC1 device.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 55 von 65
Version: 01A
Afterwards the network plan has to be saved and compiled.
Image 10: Save and compile network plan
With menu tab „PLC / Ethernet / Edit Ethernet node“ the window for changing the IP
address and device name can be opened.
Image 11: IP address and device name setting
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 56 von 65
Version: 01A
Image 12: Edit Ethernet nodes
By clicking „Browse...“ the following window „Browse Network “ is opened:
Image 13: Dialog box „Browse Network“ with two PROFINET nodes
This dialog box shows all PROFINET nodes with their IP address, MAC address,
device type and station name.
Here the BMC1 device (see MAC address, device type and station name) can be
selected and confirmed with button “OK”.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 57 von 65
Version: 01A
Then in the dialog box „Edit Ethernet Node“ in field „Assign device name“ the station
name can be reassigned:
Image 14: Dialog box “Edit Ethernet Node“ for BMC1 settings
The chosen station name must have the file extension of the PROFINET connection,
in this case „.profinet-io-system“.
IP address and the subnet mask cannot be processed in this point-these settings
have to be done in the HW Config (following page).
Integration HW Config
Program „HW Config“ and the corresponding Step project has to be opened.
In this window all existing devices are displayed which can be configured.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 58 von 65
Version: 01A
Image 15: Program HW Config
Device BMC1 has to be selected.
Now a list of slots and their assignment is shown.
Each slot represents 8 bytes or a CAN message on the backplane bus.
When fully used all 8 slots = 64 bytes has to be supported.
For one basic device one CAN message with logic data and optional one with analog
data can be used.
Maximum use for 8 basic devices only with logic data or 4 basic devices with
logic and analog data.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 59 von 65
Version: 01A
Image 16: Selection input module BMC1
Extended functionality starting at version 1.2.0.1
The BMC1 starting at version 1.2.0.1 contains a backchannel functionality, which
allows data to be transferred from SPS to BMC1.
So it is possible to control functional inputs on the Safety-M modules.
At this point output modules can now be configured. Here, the slots 8 to 16 are
reserved.
The output modules can only be configured in those slots while the input modules
can only be programmed in slots 1 through 8.
Each slot represents 8 bytes or a CAN message on the backplane bus.
When fully used all 8 slots = 64 bytes has to be supported.
For one basic device one CAN message with logic data can be used.
Maximum use for 8 basic devices.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 60 von 65
Version: 01A
Image 17: HW Config with opened project and BMC1 device
The input and output module is now available in the hardware configuration. By
double clicking on the corresponding module start address of the inputs or outputs
can be changed.
Then close dialog „Properties“ of the module.
Double-clicking object BMC1 in the dialog box “Properties” via the menu item
“Ethernet…” the IP address of BMC1 can be configured.
This IP address is assigned automatically to the BMC1 device when connected.
Control
The check box „Assign IP address via IO-Controller “ in window „Properties“ has to
be activated. The station name has to match to the configured name in the network
plan.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 61 von 65
Version: 01A
Image 18: Dialog box „Eigenschaften“ of BMC1 device in HW Config
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 62 von 65
Version: 01A
Configuration of BMC1
Now the configuration possibilities for the internal CAN bus (backplane) of the
Safety-M series will be explained.
The configuration data are shown in dialog box „ Properties“ of the Safety-M device
on tab „Parameter“ and can be changed there.
For one basic device maximum 2 CAN messages for output data (input data SPS)
and 1 message for input data (output data SPS) can be used.
Maximum 8 (only logic data) or 4 (logic and analog data) basic devices can operate
with the available 8 slots
By configuring the CAN ID an allocation to the slots of the basic devices is generated.
Image 19: Adjustable parameters of the BMC1 for CAN module backplane bus
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 63 von 65
Version: 01A
Followed settings can be made:
Interval Time
Timeout for „internal“ CAN communication
CAN-ID Slot 1...8
CAN identifier for the particular slot CAN input data.
This has to match the configured CAN ID of this slot
assigned basic device. CAN ID of the basic device is
configured in the SafePLC.
If a slot is not used the value for CAN ID is set to
„0“.
CAN-ID Slot 9...16
Starting with version1.2.0.1 CAN ID for slot 9 … 16 are
set additionally. This corresponds to the CAN ID for
sending data from BMC1 to the Safety-M basic device.
This has to match the configured CAN ID of this slot
assigned basic device.
CAN ID of the basic device is configured in the
SafePLC.
If a slot is not used the value for CAN ID is set to
„0“.
Table 4: CAN-ID slots
Note:
Only when connected to the PROFINET master system the configured data is
transferred to the BMC1– otherwise the default settings are valid:
Parameter
Default-value
Interval Time
500
CAN-ID slot 1
192
CAN-ID slot 2
194
CAN-ID slot 3
196
CAN-ID slot 4
198
CAN-ID slot 5
200
CAN-ID slot 6
202
CAN-ID slot 7
204
CAN-ID slot 8
206
Table 5: CAN-ID Default values
Starting with version 1.2.0.1 following modifications applies:
The BMC1 from this version contains feedback functionality.
This data can be transferred from the SPS to the BMC1; the data is send over
backplane bus to basic device.
In dialog box „Eigenschaften“ of slot 0 the CAN IDs can be set for both the input
modules as well as for the output modules per slot
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 64 von 65
Version: 01A
Unused slots are set to CAN ID = 0
Note:
There must be at least one input and one output module.
Starting with version 1.3.0.1 this restriction no longer applies but unused slots
has to be occupied with empty modules and the CAN ID is set to “0”.
R61363.7000 | Safety-M Kommunikationsmodule (English) 27.09.2013
Seite 65 von 65
Version: 01A
Diagnostic-LED
The BMC1 device has three LEDs.
Conditions:
LED
Colour
Mode
Description
RUN
green
„blinking“
Device OK
DP
green
„constant“
PROFINET-Connection active
green
„blinking“
PROFINET-connection lost, parameters valid
red
„blinking“
Transfered parameters not valid
XB
green
„blinking“
„internal“ CAN-message (Safety-M) received
green
„constant“
Verarbeitung OK
red
„blinking“
Missing CAN message or CAN message out of
„CAN WD Timeout“ time
red
„constant“
Device error (contact the manufacturer)
Table 6: LED-conditions
Diagnostic Message
The BMC1 can send in case of error channel specific diagnostic message via
PROFINET. These can be displayed on the SIEMENS SIMATIC software.
The following table gives an overview of the possible diagnostic messages.
Error code
Description
300
Parameters not correct received or not
valid.
Table 7: Error codes