Dormakaba ED900 Installation Instructions Manual
Text of the manual
Low Energy Swing Door Operator
(Fine cover)
Double egress doors
Installation Instructions
08125330 – 02-2020
| EN |
dormakaba ED900 Installation Instructions – Double egress door
Table of Contents
Table of contents
2
1
General information
4
1.1
General information
4
1.2
ED900 Arm configurations
4
2
Product description
5
2.1
Product description
5
2.2
Handing of door
5
2.3
Double egress door installation
configurations
6
3
Safety information
7
4
ED900 Product overview
8
4.1
ED900 push arm system
8
4.2
ED900 pull arm system
8
4.3
ED900 – double egress door configurations
9
4.4
ED900 operator component views
10
5
ED900 hardware – double door
12
5.1
ED900 operator and mounting plate
12
5.2
Door decal kit, low energy
12
5.3
Double door communication cable
12
5.4
Arm assemblies
13
5.5
Axle extension sleeves and extensions
13
5.6
ED900 mounting plate screw kit
14
5.7
ED900 arm mounting screw kits
14
5.8
ED900 standard cover kit
14
5.9
ED900 full width cover, mounting plate
extension, and cables – option
15
5.10
Key switch panels – option
16
5.11
Push arm door stop - option
16
5.12
Conduit box and wiring kit – options
17
6
Technical data
18
6.1
ED900 Technical data
18
6.2
Operating specifications
19
7
Operational mode overview
19
7.1
ED900 door closer modes
19
7.2
Low energy product
19
8
User interface
20
8.1
Overview
20
8.2
4 button keypad and display
20
8.3
Program and Exit Only switches
21
8.4
Operator status LEDs
21
9
System accessories
22
9.1
System accessory electrical connections
22
9.2
System accessories
22
9.3
ED900 terminal board interfaces
23
10
ED900 door signage
24
10.1
Low energy operator
24
10.2
Door signage, low energy double egress
swing door
25
10.3
Safety Information label, low energy
swing doors
26
Table of contents
11
Recommended tools and torque chart
27
11.1
Recommended tools
27
11.2
Standard tightening torque
27
11.3
Drill bits
27
12
ED900 installation overview
28
12.1
Installation preparation
28
12.2
ED900 operator installation with standard
covers
30
12.3
ED900 operator installation with full
width cover (option)
30
12.4
ED900 operators – assign active door and
inactive door type
30
12.4
ED900 operators – 115 Vac customer
wiring
31
12.5
ED900 operators – program switch
operation
31
12.6
Interconnecting cables
31
13
ED900 installation templates
32
13.2
Installation templates – pull arm
32
13.3
Installation templates – pull as push
35
13.4
Installation templates – push arm
36
13.3
Installation templates, double doors
38
14
ED900 operator and mounting plate
preparation
42
14.1
Remove mounting plate from each ED900
operator
42
14.2
Mounting plate 115 Vac terminal blocks
43
14.3
Options – Customer 115 Vac connection
to terminal blocks
44
14.4
Full width cover option –
ED900 operator preparation and
mounting plate assembly
46
15
ED900 mounting plate and operator
installation
48
15.1
ED900 mounting plate attachment to
jamb and/or wall examples
48
15.2
Install ED900 mounting plate to jamb
and/or wall
49
15.3
Full width cover option – Install cables
between mounting plates
50
15.4
Connect customer 115 Vac to ED900
mounting plate terminal block
52
15.5
Route accessory wiring to active door
mounting plate
53
15.6
Remove protective film strips from each
ED900 operator
54
15.7
Install each ED900 operator onto its
mounting plate
54
15.8
Full width cover option – Install program
switch, active door ED900
55
15.9
Full width cover option – 115 Vac pair
power cable connections
56
dormakaba ED900 Installation Instructions – Double egress door
Table of Contents
16
J/Push arm installation
57
16.1
Push arm installation templates
57
16.2
Push arm installation
57
17
Arm with track mount installation
60
17.1
Arm with track installation
60
17.2
Splined arm and track assemblies
60
17.3
Splined arm and track hardware
60
17.4
Slide shoe assembly
61
17.5
Install hardware into track
61
17.6
Fasten track assembly to door
62
17.7
Arm assembly
63
17.8
Arm assembly with CPD lever
63
17.9
Fasten arm to ED900 operator
64
18
Measure door width, reveal depth
66
18.1
Door width parameter Tb
66
18.2
Record door width measurement, Tb value
66
18.3
Tb parameter values
66
18.3
Reveal depth parameter rd
67
18.4
Measure and record reveal depth
67
18.5
rd parameter values
67
19
Operator spring tension
68
19.1
Set ED900 operator spring tension
68
20
Braking circuit plug
69
20.1
Braking circuit plug position
69
21
Power fail closing speed
70
21.1
Set power fail closing speed
70
22
Parameters
71
22.1
Parameters
71
23
Single door first commissioning
74
23.1
First commissioning
74
23.2
Set configuration parameters
75
23.3
Set parameter PS, program switch type
76
23.4
Perform learning cycle
77
24
Double door first commissioning
78
24.1
Separately commission active and inactive
doors
78
24.2
Set operator parameters for double door
operation
78
24.3
Connect communication cable between
operators
80
25
Connect accessory wiring and test
81
25.1
Install accessory wiring
81
25.2
Test all accessories
81
26
Set track bumper stop
82
26.1
Set track bumper stop position
82
27
Install push arm door stop
83
27.1
Install push arm door stop
(optional assembly)
83
28
Install ED900 cover, end caps and
spindle caps
84
28.1
Install cover and end caps
84
28.2
Install spindle caps
85
28.3
Full width cover option – Install cover and
end caps
86
29
Install door signage
87
29.1
Install door signage
87
30
ANSI/BHMA standards
88
30.1
A156.19 Low energy power operated doors
88
31
Upgrade cards
90
31.1
Upgrade cards
90
31.2
Container module
90
31.3
Installing upgrade cards
91
32
Maintenance
92
32.1
Safety label, low energy swing doors
92
32.2
ED900 environment and cleaning
93
32.3
Yellow LED, service level
93
32.4
Pull arm maintenance
94
32.5
Arm fasteners – torque requirements
95
32.6
Push arm maintenance
96
32.7
ED900 brake maintenance
97
Appendix A – Driving parameters – detail
99
A.1
Driving parameters detail
99
Appendix B – Troubleshooting
108
B.2
Red LED status codes
109
B.3
Troubleshooting chart, "ln" codes
110
B.4
Troubleshooting chart, "E" codes
111
Appendix C – dormakaba handheld
113
C.1
dormakaba handheld terminal
113
C.2
dormakaba handheld; configuration
parameters
114
C.3
dormakaba handheld; driving parameters
115
C.4
dormakaba handheld; special functions
(Upgrade cards) ED900
116
C.5
dormakaba handheld; diagnostics
117
C.6
New dormakaba handheld; language
change to English
119
C.7
dormakaba handheld; firmware update
120
Appendix D - Wiring diagrams
122
D1.1
Key Switch Panel with RJ45 connector
122
D2.1
Key Switch Panel
123
dormakaba ED900 Installation Instructions – Double egress door
Chapter 1
1.1.1 Installation Instructions
This manual provides installation instructions for
ED900 low energy swing door operators used in double
egress door installations.
1.1.2 Manual storage
This document must be kept in a secure place, and
accessible for reference as required.
If the door system should be transferred to another
facility, insure that this document is transferred as well.
1.1.3 dormakaba.com website
Manuals are available for review, download, and printing
on the dormakaba.com/us website.
1.1.4 Dimensions
Unless otherwise specified, all dimensions are given in
inches (“) and [mm].
1.1.5 Building codes and standards
ED900 installation: observe applicable national and local
building codes.
1 General information
1.1
General information
1.1.6 Symbols used in these instructions.
WARNING
This symbol warns of hazards which could result
in personal injury or threat to health.
CAUTION
This symbol warns of a potentially unsafe
procedure or situation.
NOTICE
Draws attention to important information
presented in this document.
TIPS AND RECOMMENDATIONS
Clarifies instructions or other information
presented in this document.
1.2.1 Arm configurations.
ED900 is suitable for installation using the following arm
configurations:
•
J8 – Standard push arm, 0 - 8" reveal
•
J12 – Deep reveal push arm, 8" - 12" reveal
1.2
ED900 Arm configurations
•
T – Arm and track, 0 - 1" reveal
•
T275 – Deep reveal arm and track, 1" - 2 3/4" reveal
dormakaba ED900 Installation Instructions – Double egress door
Chapter 2
2 Product description
2.1.1 Intended use.
The ED900 is a low energy electromechanical operator
used exclusively for opening and closing interior swing
doors.
The ED900 operator must be installed on an interior
building surface.
2.1.2 Low energy operator.
ED900 is supplied only as a low energy operator.
• The operator is supplied with a reduced power motor
and a brake (Para. 4.4 - component view).
• The brake is used during door hold open time.
WARNING
To reduce risk of injury to persons, use this
ED900 operator only with a swing door for
which the ED900 is designed for.
• Reference Chapter 6, Technical data.
TIPS AND RECOMMENDATIONS
Insure operator door configuration is qualified
for use on the respective smoke or fire rated
door.
2.1.3 ED900 maximum door specifications.
Reference Para. 6.2, Operating specifications.
2.1.4 ED900 hardware – double swing doors.
Reference Chapter 5 for ED900 hardware overview.
Hinge
Hinge
Exterior side of door
Interior side of door
Left hand door (LH)
Left hand reverse door (LHR)
Right hand reverse door (RHR)
Right hand door (RH)
2.2.1 Handing of door.
2.1
Product description
2.2
Handing of door
Fig. 2.1.1
ED900 operator
dormakaba ED900 Installation Instructions – Double egress door
Chapter 2
Inactive door
Active door
2.3
Double egress door installation configurations
Fig. 2.3.1 ED900 installation – separate covers
2.3.1 Standard ED900 cover installation.
1. Each ED900 controlled by its own power switch and
program switches.
Fig. 2.3.1 ED900 installation – separate covers
Fig. 2.3.2 ED900 installation – full width cover (option) installation example
2.3.2 Full width cover (option) installation.
1. Inactive door ED900 power switch controls power to
both ED900 operators.
2. ED900 single program switch located on active door
controls both ED900 operators.
Power switch
Program switches
Program switches
Power switch
Single program switch
Power switch
dormakaba ED900 Installation Instructions – Double egress door
Chapter 3
3.1 Safety instructions.
This document contains important instructions for
installation of the ED900 swing door operators.
Review these instructions thoroughly prior to
installation, and follow them carefully during installation,
commissioning, troubleshooting and maintenance.
3.2 Door signage requirements.
Proper signs and labels, per ANSI/BHMA A156.19
Standard for Power Assist and Low Energy Power
Operated Doors, shall be applied and maintained on the
door controlled by the ED900 swing door operators.
• Reference Chapter 10, ED900 Door Signage.
3.3 Safety warnings.
WARNING
An incorrect installation may result in damage to
equipment or incorrect equipment operation.
WARNING
Hazard to mechanical processes by use of
control settings, elements, or procedures not
documented in this manual!
WARNING
Electric shock hazard!
By use of control elements, settings, or
procedures not documented in this manual!
WARNING
Work on electrical equipment and 115 Vac
wiring installation must be only be performed
by qualified personnel!
WARNING
Metallic doors must be grounded per national
and local codes!
3 Safety information
WARNING
Hand pinch point and crushing hazards at door
closing edges!
WARNING
Crushing hazards at door closing edges!
3.4 Residual hazards.
WARNING
After installation, hazards such as minor
crushing, impact with limited force, and risk to
unsupervised children may exist depending on
structural design of door area, type of door,
and any safeguards that have been
implemented.
WARNING
Hand pinch point and crushing hazards at
push arm and arm and track!
Fig. 3.1
Door closing edges
Fig. 3.3
Arm and track
Fig. 3.2
Push arm
Opposing
closing edge
Main
closing edge
Secondary
closing edge
dormakaba ED900 Installation Instructions – Double egress door
Chapter 4
4 ED900 Product overview
4.1
ED900 push arm system
Fig. 4.1.1
ED900 RH push arm system example
4.2
ED900 pull arm system
Fig. 4.2.1 ED900 RH pull arm system example
1
ED900 operator
2
T/track/arm
assembly
3
Axle extension
4
Standard cover
5
End cap, program
switch
6
End cap, power
switch
7
Mounting plate
7.1
115 Vac terminal
block
8
Spindle cap
9
Spindle cap
1
2
3
4
5
6
7
7.1
8
8
9
1
ED900 operator
2
J/pull arm
assembly
3
Axle extension
4
Standard cover
5
End cap, program
switch
6
End cap, power
switch
7
Mounting plate
7.1
115 Vac terminal
block
8
Spindle cap
9
Spindle cap
1
2
3
4
8
9
8
6
5
7
7.1
dormakaba ED900 Installation Instructions – Double egress door
Chapter 4
4.3
ED900 – double egress door configurations
Fig. 4.3.1 ED900 LH double egress
Fig. 4.3.2 ED900 RH double egress
Standard width cover
27” [686]
0 - 8”
[0 - 203]
5 1/8”
[130]
Fig. 4.3.3 ED900 LH double egress full cover option
Fig. 4.3.4 ED900 RH double egress full cover option
dormakaba ED900 Installation Instructions – Double egress door
Chapter 4
22
4
24
5
28
12
6
11
22
27
7
15
16
18
1
20
21
8
9
20
1
Power switch
2
120 Vac cable
4
Splined shaft
spindle
5
Operator (motor,
gear, spring)
6
Spring tension
adjustment,
closing force
7
Program switches
8
4 button user
interface
9
Information
display
11
Potentiometer,
power fail closing
speed adjustment
12
Terminal jumper
socket, push or pull
mounting
15
RJ45 socket, double
door operator
synchronization
16
Com 1 service
connector
17
Accessories terminal
board
18
Mounting plate
19
Customer ground
terminal
20
Guide pin
21
Ribbon cable
22
Ribbon cable socket
23
Upgrade card socket
24
Motor
25
Encoder socket and
cable
26
Motor socket and
cable
27
Control board
28
Motor brake
Fig. 4.4.1 ED900 component view 1
4.4
ED900 operator component views
Fig. 4.4.2 ED900 component view 2
4
17
6
9
8
20
23
20
1
19
2
dormakaba ED900 Installation Instructions – Double egress door
Blank page
This page left intentionally blank.
dormakaba ED900 Installation Instructions – Double egress door
Chapter 5
5 ED900 hardware – double door
Fig. 5.1.1
Two - ED900 operator and mounting plate
1
Terminals for
accessory wiring
2
Bag containing
terminals and third
guide pin*
3
Guide pin
4
5 mm T-handle hex
key 08120720
* Included with operator
Fig. 5.1.2 Two- Accessory terminals
5.1
ED900 operator and mounting plate
2
1
4
Fig. 5.1.3 5 mm T-handle hex key
1
Communication
cable assembly
08125243
2
RJ45 connector
5
Ferrite bead
Fig. 5.3.1 Communication cable
2
5
5
2
1
Fig. 5.2.1 Two - Decal kit, low energy
08087770
1
Decal, Automatic
Caution door
(both sides)
2
Decal, Activate
Switch to Operate
3
Decal, Push to
Operate
4
Decal, Pull to
Operate
5
Decal, AAADM
safety Information
label, low energy
CAUTION
DOOR
AUTOMATIC
DD0586-010
SAFETY INFORMATION
Low Energy Swinging
Doors
1. Activate the door. Door
should open at a slow
smooth pace (4 or more
seconds), and stop without
impact.
2. Door must remain fully open
for a minimum of 5 seconds
before beginning to close.
3. Door should close at a slow,
smooth pace (4 or more
seconds), and stop without
impact.
4. Inspect the foor area. It
should be clean with no
loose parts that might cause
user to trip or fall. Keep
trafc path clear.
5. Inspect door‘s overall
condition. The appropriate
signage should be present
and the hardware should
be in good condition.
6. Have door inspected by an
AAADM certifed inspector
at least annually.
AAADM
American Association of Automatic
Door Manufacturers
ANNUAL COMPLIANCE
INSPECTION
INSPECT FOR AND
COMPLIES WITH ANSI
A156.19 ON:
DATE:______________
by AAADM Certified
Inspector
Number:___________
AAADM-3044
DO NOT USE DOOR if it fails
any of these safety checks of if
it malfunctions in any way. Call
a qualifed automatic door
service company to have door
repaired or serviced.
See Owner’s manual or
instructions for details on
each of these and other
safety items. If you need
a copy of the manual,
contact the manufacturer.
These minimum safety checks,
in addition to those in the
Owner’s Manual, should be
made each day and after any
loss of electrical power .
1
3
4
2
8
5.2
Door decal kit, low energy
5.3
Double door communication cable
dormakaba ED900 Installation Instructions – Double egress door
Chapter 5
Fig. 5.4.3 T275 – Splined pull arm assembly,
LH, 1 - 2 3/4" reveal
5.4
Arm assemblies
1
Drive arm
2.1
Adjustment shaft
tube, 225 mm
2.2 Adjustment shaft,
225 mm
3
Shoe
4
Axle extension
5.1
Adjustment shaft
tube, 450 mm
5.2 Adjustment shaft,
450 mm
1
Drive arm
2
CPD lever
3
Track
Fig. 5.4.4 T275 – Splined pull arm assembly,
RH, 1 - 2 3/4" reveal
Fig. 5.4.5 T – Splined pull arm assembly,
0 - 1" reveal
1
Drive arm
2
CPD lever
3
Track
1
4
2.1
2.2
3
Fig. 5.4.1 J8 – Splined push arm assembly,
225 mm, 0 - 8" reveal
Fig. 5.4.2 J12 – Splined push arm assembly,
500 mm, 8" - 12" reveal
1
2
3
1
2
3
1
3
1
5.1
5.2
3
4
5.5
Axle extension sleeves and extensions
Fig. 5.5.1
[20 mm]
08125201
Fig. 5.5.2
[30 mm]
08125202
Fig. 5.5.3 [60 mm]
08125203
1
20 mm axle
extension sleeve
1.1
20 mm axle
extension
2
M8 -1.25 x 40
SHCS
3
30 mm axle
extension sleeve
3.1
30 mm axle
extension
4
M8 -1.25 x 50
SHCS
5
60 mm axle
extension sleeve
5.1
60 mm axle
extension sleeve
6
M8 -1.25 x 80
SHCS
1
1.1
2
5
5.1
6
3
3.1
4
dormakaba ED900 Installation Instructions – Double egress door
Chapter 5
5.6
ED900 mounting plate screw kit
Fig. 5.6.1 Two sets - Mounting plate
fasteners
3
2
Fig. 5.8.2 ED900 operator end caps
Fig. 5.8.1 ED900 standard width 27" cover
3
3
Standard width
cover
Fig. 5.8.3 Spindle cops
5.8
ED900 standard cover kit
2
End cap, program
switches
3
End cap, power
switch
4
Spindle cap
5
Spindle cap
4
5
15,16 Mounting plate
fastener kit
08120570
15
1/4-20 x 1" FH
machine screw
16
No. 14 x 1 "FH wood
screw
(12) 15
(12) 16
Fig. 5.7.1
Two sets -Push arm screw kit
Fig. 5.7.2 Two sets -Pull arm screw kit
10
Pull arm screw kit
08122740
10.1 10-24 x 1 1/2" barrel
nut
10.2 10-24 x 1 1/4" FHSCS
(flat head socket
screw
10.3 #14 x 1 1/4" pan
head wood screw
9
Push arm screw kit
08120550
9.1
10-24 x 1 1/2" barrel
nut
9.2
10-24 x 1" PPHMS
9.3
#14 x 1 1/4" pan
head wood screw
9.2
9.1
9.3
10.1
10.2
10.3
5.7
ED900 arm mounting screw kits
dormakaba ED900 Installation Instructions – Double egress door
Chapter 5
Fig. 5.9.2 115 Vac power cable
5.9.2 Power cable
• 1750 mm, 68 7/8"
08125246
• 2400 mm, 94 1/2"
08125247
• 3400 mm, 133 7/8"
08125248
5.9.3 Single program switch
• 3340 mm, 131 1/2"
08122770
Fig. 5.9.3 Single program switch and cable
1
3 position program
switch
2
3 conductor cable
1
3 conductor cable
3
Ring lug
5
Connector
1
2
3
3
5
5
1
5.9
ED900 full width cover, mounting plate extension, and cables – option
1
2
2
13
4
8
9
7
6
14
(4) 16
(4) 15
Fig. 5.9.1 Full width cover kit 08125264
1
Fine cover double
08120370
2
End and spindle
cap set
08121260
4
Mounting plate
connectors
6
Front cover
extension
08121870
7
dormakaba logo
plate
08125241
8
M6 x 10 mm SHS
with washer
9
M6 x 10 mm PFHS
13
Program switch
with cable
08122770
14
Wire retainer
08125242
15
1/4-20 x 1" FH
machine screw
16
No. 14 x 1 "FH wood
screw
dormakaba ED900 Installation Instructions – Double egress door
Chapter 5
5.11
Push arm door stop - option
Fig. 5.11.1
Door stop assembly
Door stop assembly
1/4" thick plate
08121320
Door stop assembly
1/2" thick plate
08121330
1
Plate, bumper
mounting,
1/4" thick
08120774
2
Plate, bumper
mounting,
1/2" thick
08120770
3
Rubber bumper
08120750
4
Shoulder bolt
08104231
5.1
1/4-20 x 1 1/4"
Phillips FHS, black
oxide, SS
5.2 No. 14 x 1 1/4"
Phillips FHMS for
sheet metal, zinc
plated steel
5.1
5.2
1 or 2
3
4
2
3
2
Key switch panel,
with RJ45
3
Key switch panel
4
Communication
cable for program
switch panel comm
port , 10 ft.
Fig. 5.10.1 Key switch panels
Wiring diagrams:
Reference Appendix D
5.10
Key switch panels – option
Fig. 5.10.2 Communication cable
4
dormakaba ED900 Installation Instructions – Double egress door
Chapter 5
Fig. 5.12.2
Power cord wiring kit 08121110
1
Power cord
08075390
2
Wire nut
3
Cord grip
08121130
4
Conduit box
08120730
5
120 Vac label
Fig. 5.12.1
Conduit box
4
Conduit box
08120730
4 11/16”
[119]
2 3/4”
[70]
4
1
2
3
4
5
5.12 Conduit box and wiring kit – options
dormakaba ED900 Installation Instructions – Double egress door
Chapter 6
6 Technical data
Maximum wire size
Connector plug
screw size
16 AWG
1/16”
Door
status
X7
97,98,99
Sr parameter
Door closed
Door open
Door closed, locked
Com, N.O., N.C.
contacts
6.1.5 Integrated functions.
Hold open time:
Automatic opening
dd parameter
0 to 30 s
NIght / bank
dn parameter
0 to 30 s
Manual opening
do parameter
0 to 30 s
Door blocking
behavior
hd parameter
Automatic, manual
door modes
Electric strike
delayed opening for
locking mechanism
Ud parameter
0 to 4 s
Locking
device
feedback
X3
43, 3
Motor lock
Wind load control,
maximum
Fo, Fc parameters
33.7 lb f
150 N
Voltage independent
braking circuit
Chapter 21
Adjustable with
potentiometer
LED status indicators
Chapter 8
Green
Red
Yellow
24 Vdc power
Error codes
Service interval
Program and Exit
Only switches
Chapter 8
Auto, Close, Open
Exit only; Off, On
User interface
Chapter 8
4 button keypad,
2 digit display
Firmware update
Appendix C
Firmware update
TMP, temperature
management program
Overload protection
IDC, initial drive control
Driving phase optimization
Cycle counter
CC parameter
0 to 1,000,000
Power assist function
hA, hF, hS
parameters
Drive support for
manual opening of
door
Push & go function
PG parameter
Auto opening of
door at 4° open
6.1
ED900 Technical data
6.1.1 Required operating conditions.
Ambient temperature
5 to 122 °F
Suitable for dry
rooms only
Relative air humidity:
93% maximum, non-condensing
Power supply
115 Vac ±10%, 50/60 Hz
6.6 A maximum
Branch circuit
protection (provided
by others)
15 A maximum,
dedicated branch circuit
Protection class
NEMA 1
Power wiring:
black, white, bare
copper (ground)
12 AWG
maximum
Operating noise
Maximum 50 db(A)
6.1.2 General specifications.
Operator dimensions
(W x H x D)
27" standard cover
27" x 2 3/4 x 5 1/8",
[685 x 70 x 130 mm]
Operator weight
26.5 lb [12 kg]
Maximum door
opening angle
95 to 110° depending on installation type
6.1.3 Inputs
Maximum wire size
Connector plug
screw size
16 AWG
1/16”
Activation
inputs
X4*
Interior, exterior
N. O. contact
Safety
sensors
X5
Swing, approach
sides
Night-bank
(intercom
system)
X10
57,
57a
8-24 Vdc/Vac +5%
Night-bank
(key switch)
X1
35, 3
d2 parameter
Configure for N.O.
or N.C. contact
Deactivation
of drive
function
X6
4, 4a
d1 parameter
Configure for N.O.
or N.C. contact
6.1.4 Outputs
TIPS AND RECOMMENDATIONS
• *X4: terminal board numbers, reference
Chapter 9, System accessories.
• Parameters, reference Chapter 22.
dormakaba ED900 Installation Instructions – Double egress door
Chapters 6 and 7
Maximum power
consumption
120 watt
Opening force
N (lbf)
Fo parameter
Minimum
20 (4.5)
Maximum
60 (13.5.5)
Manual closing force
N (lbf)
Fc parameter
Minimum
20 (4.5)
Maximum
60 (13.5)
Maximum door
weight, pounds
220 at 48"
door width
Depending on door
width and application
Door width
Minimum
28"
Maximum
48"
Maximum opening
speed, °/s
27
May be limited by
door weight after
learning cycle.
Maximum closing
speed, °/s
27
6.2
Operating specifications
6.2.1 ED900
7 Operational mode overview
7.1
ED900 door closer modes
7.1.1 Automatic mode.
Door closer mode parameter hd=0.
Door opens automatically following pulse generation by
a knowing act device or by push/pull.
7.1.2 Manual mode.
Door closer mode parameter hd=1.
Designed for doors primarily accessed manually.
7.2
Low energy product
7.2.1 ANSI/BHMA 156.19.
ED900 operator is configured to meet requirements of
a low energy application per ANSI/BHMA A156.19, U.S.
Standard for Power Assist and Low Energy Power
Operated Doors.
7.2.2 Low energy power operated door.
A manual door with a power mechanism that opens the
door upon receipt of a knowing act activating signal,
does not generate more kinetic energy than specified in
ANSI 156.19, and is closed by a power mechanism or by
other means.
TIPS AND RECOMMENDATIONS
Parameter descriptions can be found in
Chapter 22; Parameters.
Axle extensions,
[mm] inches
[20] 13/16"
[30] 1 3/16"
[60] 2 3/8"
Reveal depth for pull
arm
1 3/16"
Reveal depth for pull
arm and CPD lever
2 1/4"
Reveal depth for
standard push arm
0 to 8 3/4"
Reveal depth for deep
push arm
8" minimum to 11 13/16"
7.1.3 Power assist.
• Available only in door closer mode (hd=1), manual
opening drive support is automatically adjusted to
operator size.
• Parameter hA sets door activation angle for power
assist function. Once angle reached, drive support
provides easier manual opening of the door.
• Parameter hF, power assist function. Parameter
values greater than 0 provides additional opening
force.
• Parameter hS, power assist function support for
door in closed position.
Required system safety, as a low energy application, is
achieved utilizing the following design factors:
• Reduced dynamic door panel contact forces
• Reduced static door panel contact forces
• Low driving speeds
• Force limitation
dormakaba ED900 Installation Instructions – Double egress door
Chapter 8
8 User interface
8.1
Overview
Fig. 8.1.1
Operator keypad and display
1
2 digit display
2
4 button keypad
8.1.1 Operator user interfaces.
1. 4 button keypad and 2 digit display.
• 4 button keypad; to select, input and
adjust door parameter values.
• 2 digit display; parameter values, error
and information codes.
Fig. 8.2.1 Door hinge side on right
2
2 digit display
5
Button legend
Fig. 8.2.2 Door hinge side on left
8.2
4 button keypad and display
Right button
1.
Access parameter menu,
press button > 3 seconds.
2. Edit selected parameter.
3.
Save changed value.
Left button
1.
Reset, > 3s
2.
Quit process, < 3 s.
Both buttons
together
1.
Acknowledge errors,
press both buttons < 3 s.
2.
Reset, press both
buttons > 3 s.
Up button
1.
Scroll through parameters
and error messages.
2.
Increase parameter value.
Down button
1.
Scroll through parameters
and error messages.
2.
Reduce parameter value.
3.
Opening pulse, press
button < 3 s.
4.
Learning cycle, press
button > 3 s.
5.
Reset with factory setting,
press button > 8 s (program
switches off).
6.
Identify operator
orientation for display
2
2 digit display
6
Button legend
rotated 180°
8.2.1 4 button keypad.
4 button legend is orientated so buttons
have same function and position regardless
of operator orientation. Button legend can
be removed and rotated.
8.2.2 4 button keypad functions.
TIPS AND RECOMMENDATIONS
Symbols
• "<", Less than
• ">", Greater than
1
2
> 3s Reset
< 3s Quit
> 3s
PRG
< 3s
LEARN
Fact-Setup
> 3s
> 8s
2
5
> 3s Reset
< 3s Quit
LEARN
< 3s
> 3s
Fact-Setup
PRG
> 3s
> 8s
6
2
dormakaba ED900 Installation Instructions – Double egress door
Chapter 8
8.3
Program and Exit Only switches
Fig. 8.3.1 Program and Exit Only switches
1
Exit Only switch,
2 position
2
Program switch,
3 position
8.4
Operator status LEDs
Fig. 8.4.1 Operator status LEDs
8.4.1 Operator status LEDs.
1. Red LED
Blinking codes are used to indicate "ln__"
information (system status or operating
conditions) or certain error codes "E__".
2. Yellow LED
Maintenance interval indicator. When
illuminated, an indication the operator
system has to be serviced.
3. Green LED
•
On, internal 24 Vdc power is On.
•
Off, internal 24 Vdc power is Off.
TIPS AND RECOMMENDATIONS
Information on LED status codes
and maintenance intervals can be
found in Appendix B, Troubleshooting.
1
Red LED
2
Yellow LED
3
Green LED
4
Power switch
1
2
1
2
3
4
1
2
3
8.3.1 Program switch control modes.
•
Auto, door opens following pulse
generation by a knowing act device or
push/pull.
• Door will close after hold open time
(adjustable) has expired.
• Knowing act device, Para. 3.2.
Door will remain at full open position
for not less than five seconds.
• Push/pull actuation of door, Chapter 10.
Door will remain at full open position for
not less than three seconds.
•
Close
Auto
•
Open, door opens automatically and
remains open.
•
Close, door closes automatically, or
remains closed.
8.3.2 Exit only switch.
• Disables exterior switch only.
Open
dormakaba ED900 Installation Instructions – Double egress door
Chapter 9
9 System accessories
9.1
System accessory electrical connections
9.2.1 Overview
ED900 operators are normally used with
system accessories available from
dormakabaUSA, Inc. or other manufacturers.
9.2.2 Accessory electrical installation.
Electrical interfaces from system
accessories used with operator must be
planned for. This includes routing of wiring
from accessories to operator.
9.2.3 System accessories, other
manufacturers.
dormakaba USA, Inc. cannot guarantee
compatibility for other manufacturer's
accessories. If any of these accessories are
used despite this caution, the operator's full
range of functions may be unavailable, or
the accessories may not work properly.
WARNING
Damage to operator or to
connected device is also possible!
9.2.4 Power for accessories.
External DC power supply is required
for external consumers
(Para 9.2.6, 9.2.7).
9.2.5 Miscellaneous accessories.
1. Door status display, red, green
9.2
System accessories
9.2.6 Activators
Typical activators:
1. Pushbuttons, key switches
2. Access control systems
3. Telephone systems
4. Intercoms
TIPS AND RECOMMENDATIONS
Refer to Chapter 6, Technical data
for electrical interface
requirements.
9.2.7 Locking devices
Typical locking devices:
1. Electric strike plates
2. Electromagnetic locks
3. Electric locks
To insure that operator and locking device
work safely when connected together,
locking device mus comply with following:
1. Operating voltage, external power
supply, 48 Vdc/Vac maximum.
2. Locking device relay contact, maximum
load, 1 A.
3. Electric strike plate duty factor, 30%
minimum.
4. Motor lock duty factor, 100%.
Fig. 9.1.1
Electrical connections, double egress door
1
External program
switch, mechanical
2
External program
switch, electronic
3
Key switch
4
Pushbutton, night /
bank
5
Pushbutton, interior
6
Pushbutton, exterior
7
Door locking device
8
Manual release
switch
9
ED900, active door
10
ED900, inactive door
1
8 x 18 AWG
8 x 0.8 mm2
2 x 18 AWG
2 x 0.8 mm2
2 x 18 AWG
2 x 0.8 mm2
2 x 18 AWG
2 x 0.8 mm2
4 x 18 AWG
4 x 0.8 mm2
2 x 18 AWG
2 x 0.8 mm2
2 x 18 AWG
2 x 0.8 mm2
2 x 18 AWG
2 x 0.8 mm2
3 x 12 AWG
3 x 4.0 mm2
115 Vac power
2
4
5
6
3
7
8
9
10
dormakaba ED900 Installation Instructions – Double egress door
Chapter 9
9.3
ED900 terminal board interfaces
TIPS AND RECOMMENDATIONS
Do not connect system
accessories to board until
operator has been commissioned
and learning cycle performed.
Reference Chapter 25.
Fig. 9.3.1 Terminal board electrical connections
1
Green LED (Para. 8.4)
2
Yellow LED (Para. 8.4)
3
Red LED (Para. 8.4)
4
Key (red insert)
location in socket.
Assigned plug has
tab in same location
broken off.
5
Jumpers, factory
installed at following
terminals:
•
4 and 4a
•
15 and 3*
•
11 and 3*
*
Remove jumpers if
safety sensors
installed.
6
DCW® upgrade card
plug (n/a)
7
Fire protection
upgrade card plug
97 98 99
30 31 32 34 33 3
3
35
1
3
6
1
4 4a
3
B
A
1
57 57a
1 42 3
1 41 3
1 15 17 3
1 11 13 3
43
3 64 63 62 1G 3
+ 24 V
Signal input
0 V
Partial Open
Permanent Open
Exit Only
Automatic
Off
N.C.
COM
Test output
X5
X4
X3
X6
X9
X1
X7
+ 24 V
X8
0 V
X10
8 - 24 AC/DC
+ 5% Wet
DCW bus
Swing side
Approach side
Safety sensors
Activation inputs
Interior
Exterior
Night-
bank
input
+ 24 V
Signal input
0 V
+ 24 V
+ 24 V
Signal input
Signal input
0 V
0 V
Test output
0 V
24 V
Brake coil signal
Output
COM
N.O.
N.C.
0 V
Locking relay
Maximum current:
1A, 48 V DC/AC
Locking feedback contact
0 V
0 V
+ 24 V
0 V
0 V
Signal input
N.O.
Smoke
detectors
Emergency
close
Night
trigger
Program, exit only
switches
Door status
24 VDC
Class II
1
2
3
4
5
6
7
5
5
dormakaba ED900 Installation Instructions – Double egress door
Chapter 10
10 ED900 door signage
Fig. 10.1.1
AUTOMATIC CAUTION DOOR decal
Fig. 10.1.2 ACTIVATE SWITCH TO OPERATE decal
Fig. 10.1.3 PUSH TO OPERATE, PULL TO OPERATE decals
10.1 Low energy operator
10.1.1 Overview
Signage and warnings are specified in ANSI /BHMA
A156.19, American National Standard for power assist
and low energy power operated doors.
10.1.2 All low energy doors.
1. AUTOMATIC CAUTION DOOR decal.
• All low energy doors shall be marked with signage
visible from both side of door with the words
"AUTOMATIC CAUTION DOOR".
•
Signs shall be mounted 50" ± 12" from floor to
centerline of sign.
10.1.3
Knowing act switch used to initiate door operation.
1. ACTIVATE SWITCH TO OPERATE decal.
•
When a knowing act device is used to initiate operation
of door operator, door shall be provided with sign on
each side of door where switch is operated with
message "ACTIVATE SWITCH TO OPERATE".
10.1.4 Push/Pull used to initiate door operation.
1. PUSH TO OPERATE, PULL TO OPERATE decals.
• When push/pull is used to initiate operation of door
operator, doors shall be provided with the message
"PUSH TO OPERATE" on push side of door and
"PULL TO OPERATE" on pull side of door.
CAUTION
DOOR
AUTOMATIC
DD0586-010
1
Activate Switch to
Operate
DD0758-010
ACTIVATE SWITCH
TO OPERATE
DD0758-010
1
2
Push to Operate
3
Pull to Operate
DD0762-010
PUSH
TO OPERATE
2
DD0762-020
PULL
TO OPERATE
3
10.1.5 Knowing act:
ANSI/BHMA standard A159.19 definition.
Any conscious action with the expected result of
opening a door. This includes but is not limited to::
• Wall or jamb mounted contact or non contact
switches such as push plates.
• The action of manually opening (pushing or pulling)
a door.
• Controlled access devices such as keypads, card
readers, and key switches.
dormakaba ED900 Installation Instructions – Double egress door
Chapter 10
10.2 Door signage, low energy double egress swing door
3
Pull to Operate
Fig. 10.2.1 LH approach side
Fig. 10.2.2 LH swing side
10.2.1
Knowing act switch used to initiate door operation.
1
Activate Switch to
Operate
Fig. 10.2.4 LH swing side
2
Push to Operate
CAUTION
DOOR
AUTOMATIC
DD0586-010
ACTIVATE SWITCH
TO OPERATE
1
CAUTION
DOOR
AUTOMATIC
DD0586-010
1
ACTIVATE SWITCH
TO OPERATE
CAUTION
DOOR
AUTOMATIC
DD0586-010
ACTIVATE SWITCH
TO OPERATE
1
CAUTION
DOOR
AUTOMATIC
DD0586-010
1
ACTIVATE SWITCH
TO OPERATE
1
Activate Switch to
Operate
10.2.2
Push /pull used to initiate door operation.
CAUTION
DOOR
AUTOMATIC
DD0586-010
3
DD0762-020
PULL
TO OPERATE
CAUTION
DOOR
AUTOMATIC
DD0586-010
2
DD0762-010
PUSH
TO OPERATE
Fig. 10.2.3 LH approach side
CAUTION
DOOR
AUTOMATIC
DD0586-010
3
DD0762-020
PULL
TO OPERATE
CAUTION
DOOR
AUTOMATIC
DD0586-010
2
DD0762-010
PUSH
TO OPERATE
3
Pull to Operate
2
Push to Operate
dormakaba ED900 Installation Instructions – Double egress door
Chapter 10
Fig. 10.3.1 Safety
information
label
10.3 Safety Information label, low
energy swing doors
10.3.1 Low energy swinging door safety information
label.
This AAADM label outlines safety checks that should be
performed daily on a swinging door controlled by an
ED900 low energy operator.
10.3.2 Safety information label location.
Place label in a protected, visible location on door frame,
near program switch plate if possible.
10.3.3 Annual compliance section of label.
This section of label is only completed on low energy
swing doors that comply with ANSI/BHMA A156.19
standard and pass inspection by a AAADM certified
dormakaba USA, Inc. technician.
10.3.4 Additional annual compliance inspection labels.
Place additional labels over annual compliance
inspection section of safety information label.
SAFETY INFORMATION
Low Energy Swinging
Doors
1. Activate the door. Door
should open at a slow
smooth pace (4 or more
seconds), and stop without
impact.
2. Door must remain fully open
for a minimum of 5 seconds
before beginning to close.
3. Door should close at a slow,
smooth pace (4 or more
seconds), and stop without
impact.
4. Inspect the foor area. It
should be clean with no
loose parts that might cause
user to trip or fall. Keep
trafc path clear.
5. Inspect door‘s overall
condition. The appropriate
signage should be present
and the hardware should
be in good condition.
6. Have door inspected by an
AAADM certifed inspector
at least annually.
AAADM
American Association of Automatic
Door Manufacturers
ANNUAL COMPLIANCE
INSPECTION
INSPECT FOR AND
COMPLIES WITH ANSI
A156.19 ON:
DATE:______________
by AAADM Certified
Inspector
Number:___________
AAADM-3044
DO NOT USE DOOR if it fails
any of these safety checks of if
it malfunctions in any way. Call
a qualifed automatic door
service company to have door
repaired or serviced.
See Owner’s manual or
instructions for details on
each of these and other
safety items. If you need
a copy of the manual,
contact the manufacturer.
These minimum safety checks,
in addition to those in the
Owner’s Manual, should be
made each day and after any
loss of electrical power .
ANNUAL COMPLIANCE
INSPECTION
INSPECT FOR AND
COMPLIES WITH ANSI
A156.19 ON:
DATE: ______________
by AAADM Certifed
Inspector
Number: ___________
Fig. 10.3.2 Annual
compliance
inspection label
dormakaba ED900 Installation Instructions – Double egress door
Chapter 11
11 Recommended tools and torque chart
Fig. 11.1.1 Recommended tools
11.1
Recommended tools
1
T-handle hex key, 5 mm
Supplied with ED900
2
Hex keys, 2.5 mm,
3 mm, 6 mm
3
Screwdriver, flat
blade
4
Door pressure
gauge, 0 to 35 ft - lbf
5
Screwdriver, Phillips,
#2, #3
6
Torque wrench,
3 to 50 ft lb min.
6.1
Metric hex key
sockets
7
Open end wrench,
13 mm
8
Screwdriver, flat
blade, M2 (1/16 to
3/32")
Fastener size
ft lb
M5
3.7
M6
7
M8
17
M10
34
M12
58
11.2
Standard tightening torque
11.2.1 Standard tightening torque
Fastener
Drill bit size
#10 wood screw
Hardwood
9/64"
Softwood
1/8"
#12 wood screw
Hardwood
5/32"
Softwood
9/64"
#14 wood screw
Hardwood
11/64"
Softwood
5/32"
1/4 -20 metal self
tapping screw
7/32"
10-24 barrel nut
5/32"
11.3
Drill bits
11.3.1 Drill bit sizes for fasteners
Fig. 11.3.1 Drill bit
8
6
6.1
7
5
3
1
4
2
dormakaba ED900 Installation Instructions – Double egress door
Chapter 12
12 ED900 installation overview
12.1 Installation preparation
WARNING
Review safety information in Chapter 3!
WARNING
ED900 system should be installed by trained
and knowledgeable installers experienced in
installation and commissioning of swing door
operators.
The installer should be familiar with all
applicable local and national building code
requirements, and with requirements of
current ANSI/BHMA standard A156.19, Power
Assist and Low Energy Power Operated
Doors.
12.1.1 dormakaba USA, Inc. ED900 hardware.
1. Locate shipping boxes for ED900 operator and
hardware.
NOTICE
Installation steps listed in Chapter 14 through 17
are a recommendation. Structural, local
conditions, available tools, or other factors or
circumstances may require modification to
these steps.
12.1.2 Door frame and door.
CAUTION
Insure area around door frame, adjacent walls
and door is readily accessible and free of
objects and debris.
12.1.3 Accessories
1. Verify accessories planned for or in place for the door.
Chapter 9, system accessories, list typical accessory
types for ED900 operators.
TIPS AND RECOMMENDATIONS
Accessory wiring to ED900 operator should be
planned for prior to operator installation.
12.1.4 ED900 mounting plate installation preparation.
CAUTION
Using applicable ED900 installation template
(Chapter 13), holes for mounting plate
fasteners must be located and drilled into door
frame, wall or substructure prior to mounting
plate installation.
CAUTION
Mounting plate installation must be orientated
with 115 Vac connection towards door hinge side.
12.1.5 ED900 mounting plate extension used with
optional full door width cover.
TIPS AND RECOMMENDATIONS
Mounting plate extension is included
for full width cover installation.
•
Reference Chapter 15.
12.1.6 ED900 115 Vac electrical installation.
WARNING
Work on electrical equipment and 115 Vac
wiring installation must be performed only by
qualified personnel!
WARNING
Electrical shock hazard! 115 Vac branch circuit
disconnect for ED900 must be Off prior to
start of electrical installation.
WARNING
115 Vac wiring to ED900 operator must
conform to local and national electrical codes.
dormakaba ED900 Installation Instructions – Double egress door
Blank page
This page left intentionally blank.
dormakaba ED900 Installation Instructions – Double egress door
Chapter 12
12.2 ED900 operator installation with standard covers
12.4.1 ED900 active and inactive door assignments.
1. Position ED900 operators on a flat surface
orientated as shown in Fig. 12.5.1.
2. Determine ED900 active and inactive door
assignments.
TIPS AND RECOMMENDATIONS
Active and inactive door assignments.
Fig. 12.1.1 shows example of active and
inactive door assignments.
Door assignments may be reversed.
• Use dL door type parameter to assist in determining
ED900 active and inactive door assignments
TIPS AND RECOMMENDATIONS
dL door type parameter.
dL parameter is set during double door
commissioning – Reference Chapter 24.
Door type
Parameter
value
Parameter description
0*
Single door
1
Double door with astragal.
•
Active door operator – door opens first.
2
Double door with astragal.
•
Inactive door operator.
3
Double door, without astragal.
•
Active door operator.
Both doors open simultaneously.
4
Double door, without astragal.
•
Inactive door operator.
Both doors open simultaneously.
*
Factory setting
Table 12.4.1 Door-type parameter dL.
12.4 ED900 operators – assign active door and inactive door type
Fig. 12.2.1 ED900 standard cover installation for double door operation
12.3 ED900 operator installation with full width cover (option)
Fig. 12.3.1
ED900 full width cover installation for double door operation
Power switch
Inactive door
Program switches
Power switch
Active door
Program switches
Single program switch
Power switch
Active door
Inactive door
dormakaba ED900 Installation Instructions – Double egress door
Chapter 12
ED900 – Active door
ED900 – Inactive door
Power switch
Program switches
(Disabled)
Program switches
Power switch
Spindle
Spindle
Fig. 12.5.1 ED900 installation with standard covers
ED900 – Active door
ED900 – Inactive door
Single
program switch
Power switch
Spindle
Spindle
Program switches
(Disabled)
Program switches
(Disabled)
12.4.1 ED900 installation with standard covers
(Fig. 12.2.1)
1. 115 Vac customer power is wired to each
ED900 operator. Reference Para.14.2.
• Power to each operator is controlled by its power
switch.
12.4 ED900 operators – 115 Vac customer wiring
12.5 ED900 operators – program switch operation
12.5.1 ED900 installation with standard covers
(Fig. 12.5.1)
• Inactive door program switches are disabled in
double door operation.
12.5.2 ED900 installation with optional full width
covers (Fig. 12.5.2)
• Single program switch installed on active door
ED900 controls operation of both ED900 controllers.
• Standard program switches are disabled in double
door operation.
• Reference Para.14.7 for single program switch
installation.
Fig. 12.5.2 ED900 installation with optional full width cover
12.4.2 ED900 installation with full width cover option.
(Fig. 12.3.1)
1. 115 Vac customer power is wired to active door
ED900. Reference Para.14.2.
• Power to both operators is controlled by the active
door operator's power switch.
12.6 Interconnecting cables
12.6.1 ED900 installation with standard covers.
1. Communication cable, Para. 5.3.
12.6.2 ED900 installation with full width cover option.
1. Communication cable, Para. 5.3.
2. 115 Vac power cable Para. 5.9.
3. Single program switch and cable, Para. 5.9.
• Active door ED900 program switches control
operation of both ED900 controllers.
dormakaba ED900 Installation Instructions – Double egress door
Chapter 13
Fig. 13.2.1
Assembly on hinge side, pull version with slide channel and long pivot pin
Axle extension
ED900
A
B
C
D
Inches
mm
Inches
mm
Inches
mm
Inches
mm
Standard
●
1 7/32
31
2 1/2
63
7/8
22
2 1/8
54
3/4"
[20]
●
2
51
3 1/4
83
1 21/32
42
2 29/32
74
1 3/16"
[30]
●
2 13/32
61
3 21/32
93
2 1/16
52
3 5/16
84
2 3/8"
[60]
●
3 9/16
91
4 27/32
123
3 7/32
82
4 1/2
114
A
C
B
D
Reveal depth maximum ± 1 3/16” [30]
Upper edge door
Space for cable feed
Door with rabbet
Upper edge door
5 7/8”
[150]
4 3/16”
[106]
1 3/4”
[45]
1 1/4”
[32]
3 15/16”
[100]
1 3/4”
[45]
2 1/2”
[63]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
Ø 1/4”
[6,6]
17 3/4”
[451]
1 1/4”
[32]
6 1/8”
[155]
13.2 Installation templates – pull arm
13 ED900 installation templates
dormakaba ED900 Installation Instructions – Double egress door
Chapter 13
Fig. 13.2.2 Assembly on hinge side, pull version with slide channel CPD and short pivot pin
Axle extension
ED900
A
B
C
D
Inches
mm
Inches
mm
Inches
mm
Inches
mm
Standard
●
1 7/32
31
2 7/16
62
7/8
22
2 3/32
53
3/4"
[20]
●
2
51
3 7/32
82
1 21/32
42
2 7/8
73
1 3/16"
[30]
●
2 13/32
61
3 5/8
92
2 1/16
52
3 1/4
83
2 3/8"
[60]
●
3 9/16
91
4 13/16
122
3 7/32
82
4 7/16
113
B
D
A
C
Reveal depth maximum 2 3/8” [60]
Upper edge door
Upper edge door
Space for cable feed
5 7/8”
[150]
4 3/16”
[106]
1 3/4”
[45]
1 1/4”
[32]
3 15/16”
[100]
1 3/4”
[45]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
7 11/16”
[195]
Ø 1/4”
[6,6]
2 1/2”
[63]
17 3/4”
[451]
1 1/4”
[31]
1/8”
[3]
When CPD lever is used, about 1 3/16” [30]
must be deducted from the actual reveal
depth when the parameter is set.
dormakaba ED900 Installation Instructions – Double egress door
Chapter 13
Axle extension
ED900
A
B
C
D
Inches
mm
Inches
mm
Inches
mm
Inches
mm
Standard
●
1 7/32
31
2 15/16
75
7/8
22
2 19/32
66
3/4"
[20]
●
2
51
3 3/4
95
1 21/32
42
3 3/8
86
1 3/16"
[30]
●
2 13/32
61
4 1/8
105
2 1/16
52
3 25/32
96
2 3/8"
[60]
●
3 9/16
91
5 5/16
135
3 7/32
82
4 31/32
126
Fig. 13.2.3 Assembly on hinge side, pull version with slide channel CPD and long pivot pin
B
D
A
C
Upper edge door
Upper edge door
Space for cable feed
5 7/8”
[150]
4 3/16”
[106]
1 3/4”
[45]
1 1/4”
[32]
3 15/16”
[100]
2 1/2”
[63]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
1 3/4”
[45]
Ø 1/4”
[6,6]
17 3/4”
[451]
1/8”
[3]
1 3/4”
[44]
When CPD lever is used, about 1 3/16” [30]
must be deducted from the actual reveal
depth when the parameter is set.
Reveal depth maximum 2 3/8” [60]
7 11/16”
[195]
dormakaba ED900 Installation Instructions – Double egress door
Chapter 13
Axle extension
ED900
A
B
C
D
Inches
mm
Inches
mm
Inches
mm
Inches
mm
Standard
●
9/16
14
1 15/16
49
3/16
5
1 9/16
40
3/4"
[20]
●
1 11/32
34
2 23/32
69
1
25
2 3/8
60
1 3/16"
[30]
●
1 3/4
44
3 1/8
79
1 3/8
35
2 3/4
70
2 3/8"
[60]
●
2 29/32
74
4 5/16
109
2 9/16
65
3 15/16
100
Fig. 13.3.1
Assembly on opposite hinge side, push version with slide channel and short pivot pin
B
D
A
C
Lower edge frame
Lower edge frame
Space for cable feed
Reveal depth maximum 2 3/8” [60]
The maximum opening width is 95°.
5 7/8”
[150]
4 3/16”
[106]
1 3/4”
[45]
1 1/4”
[32]
3 15/16”
[100]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
Ø 1/4”
[6,6]
17 3/4”
[451]
5 11/16”
[145]
1 3/8”
[35]
2 1/2”
[63]
1 3/4”
[45]
13.3 Installation templates – pull as push
dormakaba ED900 Installation Instructions – Double egress door
Chapter 13
Axle extension
ED900
A
B
C
D
Inches
mm
Inches
mm
Inches
mm
Inches
mm
Standard
●
11/16
18
2
51
11/32
9
1 21/32
42
3/4"
[20]
●
1 1/2
38
2 13/16
71
1 1/8
29
2 7/16
62
1 3/16"
[30]
●
1 7/8
48
3 3/16
81
1 13/32
39
2 13/16
72
2 3/8"
[60]
●
3 1/16
78
4 3/8
111
2 23/32
69
4
102
Fig. 12.4.1 Assembly on opposite hinge side, push version with J/arm assembly
B
D
C
A
Lower edge frame
Lower edge frame
Space for cable feed
5 7/8”
[150]
4 3/16”
[106]
1 3/4”
[45]
1 1/4”
[32]
3 15/16”
[100]
9 5/8”
[245]
Ø 1/4”
[6,6]
1 5/16
[33]
1 31/32
[50]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
1 3/4”
[45]
2 1/2”
[63]
ED100 = 0 – 11 13/16” [0 – 300]
ED250 = 0 – 19 11/16” [0 – 500]
13.4 Installation templates – push arm
dormakaba ED900 Installation Instructions – Double egress door
Chapter 13
Axle extension
ED900
A
B
C
D
Inches
mm
Inches
mm
Inches
mm
Inches
mm
Standard
●
11/16
18
2
51
11/32
9
1 21/32
42
3/4"
[20]
●
1 1/2
38
2 13/16
71
1 1/8
29
2 7/16
62
1 3/16"
[30]
●
1 7/8
48
3 3/16
81
1 13/32
39
2 13/16
72
2 3/8"
[60]
●
3 1/16
78
4 3/8
111
2 23/32
69
4
102
B
D
C
A
Lower edge frame
Lower edge frame
ED 100 = 0 mm – 300 mm
ED 250 = 0 mm – 500 mm
Space for cable feed
Note lever
position!
1 1/4”
[32]
9 7/8”
[250]
8 1/8”
[206]
3 15/16”
[100]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
2 1/2”
[63]
1 3/4”
[45]
Ø 1/4”
[6,6]
1 5/16
[33]
1 31/32
[50]
12 13/16”
[325]
5 11/16”
[145]
Fig. 13.4.2 Assembly on opposite hinge side, push version with J8/arm assembly
dormakaba ED900 Installation Instructions – Double egress door
Chapter 13
13.3 Installation templates, double doors
Fig. 13.3.1
Pull version, mounting on hinge side, Professional cover, standard axle extension
Inches
mm
Inches
mm
Inches
mm
Inches
mm
Axle extension
Standard
3/4
20
1 3/16
30
2 3/8
60
A
7/8
22
1 5/8
42
2
52
3 1/4
82
Inches
mm
Inches
mm
Pivot pin
1/2
12.5
1
25
B
3/4
19
1 1/4
32
Reveal depth
maximum:
5/8”
[15]
5 7/8”
[150]
± 1 1/16” [30]
2 3/8” [61]
5 1/8” [130]
2 3/4” [70]
5 7/8”
[150]
5/8”
[15]
Minimum 55 1/8” [1400], 57 1/16” [1450] with ESR
Drilling template: short pivot pin 1/2” [12.5]
Center of
operator axle
1 3/4” [45]
5 7/8” [150]
4 3/16” [106]
1 1/4” [31.5]
2 1/2” [63]
3 15/16”
[100]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
17 3/4”
[451]
Minimum 55 1/8” [1400], 57 1/16” [1450] with ESR
Upper edge of door panel
Cable entry location on either the left or right side.
17 3/4”
[451]
5 7/8” [150]
6 1/8”
[155]
4 3/16” [106]
3/8” [9]
1 3/4” [45]
6 1/8”
[155]
Drilling template: long pivot pin 1” [25]
Center of
operator axle
1 3/4” [45]
5 7/8” [150]
4 3/16” [106]
1 1/4” [31.5]
2 1/2” [63]
3 15/16”
[100]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
Ø 1/4”
[6,6]
17 3/4”
[451]
Minimum 55 1/8” [1400], 57 1/16” [1450] with ESR
Upper edge of door panel
Cable entry location on either the left or right side.
17 3/4”
[451]
5 7/8” [150]
6 1/8”
[155]
4 3/16” [106]
3/8” [9]
1 3/4” [45]
6 1/8”
[155]
1 1/4”
[32]
11/16”
[19]
3 15/16”
[100]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
Ø1/4”
[6,6]
3 15/16”
[100]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
Ø1/4”
[6,6]
A+B+10
Ø1/4”
[6,6]
dormakaba ED900 Installation Instructions – Double egress door
Chapter 13
Fig. 13.3.2 Pull version with CPD lever, mounting on hinge side, Professional cover, standard axle extension
Reveal depth
maximum:
2 3/8” [60]
Minimum 55 1/8” [1400], 57 1/16” [1450] with ESR
A+B+10
5 7/8”
[150]
5 7/8”
[150]
5/8”
[15]
5/8”
[15]
A B
2 3/8” [61]
5 1/8” [130]
2 3/4” [70]
Upper edge of door leaf
Drilling template: pivot pin short 12.5 mm
Center of
operator axle
3 15/16”
[100]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
1 3/4” [45]
1 1/4” [31.5]
2 1/2” [63]
17 3/4”
[451]
1 1/4”
[31]
A
Minimum 55 1/8” [1400], 57 1/16” [1450] with ESR
3 3/4”
[95]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 15/16”
[100]
17 3/4”
[451]
5 7/8” [150]
4 3/16” [106]
7 11/16”
[195]
3/8” [9]
1 3/4” [45]
Ø1/4”
[6,6]
Drilling template: pivot pin long 25 mm
Center of
operator axle
3 15/16”
[100]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
1 3/4” [45]
5 7/8” [150]
4 3/16” [106]
1 1/4” [31.5]
2 1/2” [63]
7 11/16”
[195]
17 3/4”
[451]
1 3/4”
[44]
A
Minimum 55 1/8” [1400], 57 1/16” [1450] with ESR
3 3/4”
[95]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 15/16”
[100]
17 3/4”
[451]
5 7/8” [150]
4 3/16” [106]
7 11/16”
[195]
3/8” [9]
1 3/4” [45]
Ø1/4”
[6,6]
Upper edge of door leaf
Ø1/4”
[6,6]
Ø1/4”
[6,6]
Inches
mm
Inches
mm
Inches
mm
Inches
mm
Axle extension
Standard
3/4
20
1 3/16
30
2 3/8
60
A
7/8
22
1 5/8
42
2
52
3 1/4
82
Inches
mm
Inches
mm
Pivot pin
1/2
12.5
1
25
B
1 7/32
31
1 3/4
44
dormakaba ED900 Installation Instructions – Double egress door
Chapter 13
Fig. 13.3.3 Push version with track, mounting on opposite hinge side, Professional cover, standard axle extension
Drilling template: pivot pin short 12.5 mm
Drilling template: pivot pin long 25 mm
Minimum 55 1/8” [1400], 57 1/16” [1450] with ESR
5/8”
[15]
5/8”
[15]
5 7/8”
[150]
5 7/8”
[150]
A+B+10
A
B
5 1/8” [130]
2 3/4” [70]
Reveal depth
maximum:
± 1 1/16” [30]
1 3/4” [45]
1 1/4” [31.5]
2 1/2” [63]
4 3/16” [106]
5 7/8” [150]
17 3/4”
[451]
6 1/8”
[155]
Ø1/4”
[6,6]
3 15/16”
[100]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
1 3/8
[35]
A
3 15/16”
[100]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
Ø1/4”
[6,6]
17 3/4”
[451]
6 1/8”
[155]
5 7/8” [150]
4 3/16” [106]
Bottom edge of reveal
1 3/4” [45]
1 1/4” [31.5]
2 1/2” [63]
5 7/8” [150]
4 3/16” [106]
6 1/8”
[155]
Center of
operator axle
17 3/4”
[451]
1 7/8”
[48]
A
Ø1/4”
[6,6]
3 15/16”
[100]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
3 15/16”
[100]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
Ø1/4”
[6,6]
3/8” [9]
1 3/4” [45]
5 7/8” [150]
6 1/8”
[155]
4 3/16” [106]
17 3/4”
[451]
Minimum 55 1/8” [1400], 57 1/16” [1450] with ESR
Bottom edge of reveal
Minimum 55 1/8” [1400], 57 1/16” [1450] with ESR
Center of
operator axle
3/8” [9]
1 3/4” [45]
Inches
mm
Inches
mm
Inches
mm
Inches
mm
Axle extension
Standard
3/4
20
1 3/16
30
2 3/8
60
A
3/16
5
1
25
1 3/8
35
2 9/16
65
Inches
mm
Inches
mm
Pivot pin
1/2
12.5
1
25
B
1 3/8
35
1 7/8
48
dormakaba ED900 Installation Instructions – Double egress door
Chapter 13
Fig. 13.3.4 Push version with arm, mounting on opposite hinge side, Professional cover, standard axle extension
Inches
mm
Inches
mm
Inches
mm
Inches
mm
Axle extension
Standard
3/4
20
1 3/16
30
2 3/8
60
A
3/8
9
1 1/8
29
1 17/32
39
2 23/32
69
ED 100 =
ED 250 =
5/8”
[15]
5/8”
[15]
5 7/8”
[150]
9 5/8”
[245]
1 31/32”
[50]
A + 1 5/16”
[33]
EN 7 =
9 7/8”
[250]
EN 7 =
12 13/16”
[325]
1 31/32”
[50]
9 5/8”
[245]
5 7/8”
[150]
EN 7 =
9 7/8”
[250]
EN 7 =
12 13/16”
[325]
5 1/8” [130]
2 3/4” [70]
A
1 5/16”
[33]
0 – 11 13/16”
[0 – 300]
0 – 19 11/16”
[0 – 500]
Drilling template: arm EN 7
Center of
operator axle
3 15/16”
[100]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
3/8” [9]
1 3/4” [45]
8 1/8” [206]
9 7/8” [250]
12 13/16” [325]
1 31/32
[50]
12 13/16” [325]
1 31/32
[50]
5 11/16”
[145]
2 1/2” [63]
1 1/4” [31.5]
8 1/8” [206]
9 7/8” [250]
Minimum 55 1/8” [1400], 57 1/16” [1450] with ESR
1 5/16”
[33]
3 15/16”
[100]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
Ø1/4”
[6,6]
Ø1/4”
[6,6]
Bottom edge of reveal
Cable entry location on either the left or right side.
Drilling template: arm EN 3-6
1 3/4” [45]
Center of
operator axle
2 1/2” [63]
1 1/4” [31.5]
4 3/16” [106]
5 7/8” [150]
9 5/8”
[245]
Ø1/4”
[6,6]
3 15/16”
[100]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
1 31/32
[50]
1 5/16”
[33]
Minimum 55 1/8” [1400], 57 1/16” [1450] with ESR
Ø1/4”
[6,6]
3 15/16”
[100]
4 3/4”
[120]
4 3/4”
[120]
4 3/4”
[120]
3 3/4”
[95]
1 31/32
[50]
9 5/8”
[245]
4 3/16” [106]
5 7/8” [150]
3/8” [9]
1 3/4” [45]
Bottom edge of reveal
Cable entry location on either the left or right side.
Minimum 55 1/8” [1400], 57 1/16” [1450] with ESR
dormakaba ED900 Installation Instructions – Double egress door
Chapter 14
14.1 Remove mounting plate from each ED900 operator
Fig. 14.1.2 Mounting plate removed from ED900 operator
14.1.1 Remove 115 Vac plug from
receptacle.
1. Remove 115 Vac plug (5) from its
receptacle (6).
14.1.2 Remove mounting plate from
ED900 operator.
1. Loosen all eight captive ED900 M6 socket
head cap screws (SHCS) using a
5 mm hex T-handle.
TIPS AND RECOMMENDATIONS
Insure all eight fasteners are free
of the mounting plate.
2. Remove operator from mounting plate.
TIPS AND RECOMMENDATIONS
Guide pin resistance may require
screwdriver to start operator
removal from end of mounting
plate (Fig. 14.1.3).
Fig. 14.1.1
115 Vac plug removal
1
ED900 operator
2
Mounting base
3
M6 x 20 SHCS
4
M6 x 10 SHCS
5
Guide pin
6
115 Vac plug
2
3
3
4
4
1
5
6
5
115 Vac plug
6
115 Vac socket
5
6
5
6
14 ED900 operator and mounting plate
preparation
dormakaba ED900 Installation Instructions – Double egress door
Chapter 14
Fig. 14.1.3 Mounting plate removal
Fig. 14.1.4 5 mm T-handle
hex key
4
Guide pin
4
14.2 Mounting plate 115 Vac terminal blocks
1
M3 x 5 screw
2
115 Vac terminal
block
3
Spacer
Fig. 14.2.2 115 Vac terminal block assembly
1
2
3
14.2.1 ED900 installation with standard
covers (Fig. 14.2.1)
1. Customer 115 Vac is connected to
terminal block and ground stud on each
ED900 mounting plate.
Fig. 14.2.1 ED900 mounting plates – installation with standard covers
1
3
2
3
4
4
5
5
5
5
5
5
1
Inactive door
mounting plate
2
Active door
mounting plate
14.2.2 ED900 installation with full width
cover option (Fig. 14.2.2)
1. Customer 115 Vac is connected to
inactive door terminal block and ground
stud.
14.2.2 Remove 115 Vac terminal block on
inactive door mounting plate.
1. Remove M3 x 5 screw securing 115 Vac
terminal block assembly to mounting
plate.
2. Remove 115 Vac terminal block assembly.
TIPS AND RECOMMENDATIONS
Removing 115 Vac terminal block
on inactive door mounting plate is
optional.
• Wiring between mounting
plates is facilitated by
removing terminal block.
Fig. 14.2.3 ED900 mounting plates – installation with optional full width cover example
1
Inactive door
mounting plate
2
Active door
mounting plate
1
2
3
4
4
5
5
5
5
5
5
6
3
115 VAC terminal
block
4
Ground terminal
3
115 VAC terminal
block
4
Ground terminal
5
Guide pin
5
Guide pin
6
Mounting plate
extension
dormakaba ED900 Installation Instructions – Double egress door
Chapter 14
14.3 Options – Customer 115 Vac connection to terminal blocks
TIGHTEN MAINS TERMINAL TO 5-7 in-lb
Use Copper Conductors ONLY
WARNING
Work on electrical equipment and
115 Vac wiring installation must
be performed only by qualified
personnel!
14.3.1 Conduit box.
1. Conduit box (Fig. 14.3.3).
• U/L approved conduit box accessory;
provides 115 Vac surface wiring to
ED900.
• Reference Para. 14.3.3 for conduit box
installation.
14.3.2 Power cord wiring kit.
1. Power cord wiring kit (Fig. 14.3.4).
• Eliminates need for hard wiring. Permits
ED900 to plug directly into 115 Vac
receptacle.
• Power cord length: 15" from end of
conduit box to center of plug.
CAUTION
Insure power cord installation
conforms to local and national
electrical codes.
1
115 VAC terminal
block
2
Ground terminal
3
Mains terminal
torque and wire label
5
M3.5 screw
6
115 Vac plug to
operator
L
115 Vac
N
Neutral
G
Ground
Fig. 14.3.1 115 Vac terminal block
Fig. 14.3.2 Mains terminal torque and wire
label
Use Copper Conductors ONLY
1
2
3
6
L
N
G
Fig. 14.3.4 Power cord wiring kit 08121110
1
Power cord
2
Wire nut
3
Cord grip
4
Conduit box
5
120 Vac label
Fig. 14.3.3 Conduit box 08120730
4
Conduit box
4 11/16”
[119]
2 3/4”
[70]
4
1
2
3
4
5
dormakaba ED900 Installation Instructions – Double egress door
Chapter 14
14.3.3 Install conduit box (option).
TIPS AND RECOMMENDATIONS
115 Vac terminal block is secured
to mounting plate by M3 x 25
Phillips head screw.
• Screw must be loosened to
allow conduit box tabs to slide
into mounting plate slots.
• Screw is then threaded into
conduit box mounting hole and
tightened.
1. Loosen M3 x 25 Phillips head screw.
2. Slide conduit box tabs into slots in
bottom of mounting plate until hole in
conduit box lines up with hole in
mounting plate.
3. Thread M3 Phillips head screw into
conduit box mounting hole and tighten
screw.
CAUTION
Terminal block M3 screw torque.
Tighten M3 screw to a torque of
5 - 7 in-lb.
• Insure screw is threaded into
conduit box mounting hole.
4. Mounting plate assembly is ready for
installation.
Fig. 14.3.5 115 Vac terminal block mounting
Fig. 14.3.6 Conduit box installed on
mounting plate
1
115 VAC terminal
block
2
Ground terminal
5
M3.5 screw
6
115 Vac plug to
operator
L
115 Vac
N
Neutral
G
Ground
1
115 VAC terminal
block
2
Ground terminal
5
M3.5 screw
6
115 Vac plug to
operator
7
Conduit box
7.1
Conduit box
mounting hole
1
2
5
6
L
N
G
5
6
2
7
7.1
1
2
6
7
1
3
4
5
Fig. 14.3.7 Power cord wiring kit assembly (option)
1
Power cord
3
Cord grip
4
Conduit box
5
120 Vac label
dormakaba ED900 Installation Instructions – Double egress door
Chapter 14
14.4 Full width cover option –
ED900 operator preparation and mounting plate assembly
Fig. 14.4.1 ED900 active door operator
TIPS AND RECOMMENDATIONS
Reference Chapter 12 for active /inactive door
assignments.
TIPS AND RECOMMENDATIONS
Power switch on active door operator will be
replaced with single program switch
(Para. 15.8).
14.4.1 Remove terminal board from active door ED900.
1. Press in 3 tabs (2) that secure terminal board (1) to
ED900, lift up terminal board and swing away from
end of housing.
14.4.2 Remove ED900 115 Vac plug.
1. Swing open upper bracket (3).
2. Remove ED900 115 Vac plug (5) from power supply
circuit board socket (6).
14.4.3 Remove power supply circuit board.
1. Remove power supply circuit board (4) from its slot in
ED900.
Fig. 14.4.2 ED900 active door power switch removal
1
Terminal board
2
Tabs
3
Upper bracket
4
Power supply circuit
board
5
ED900 115 Vac plug
1
2
3
3
5
4
6
1
2
2
3
ED900 – Active door
Power switch
Spindle
Program switches
dormakaba ED900 Installation Instructions – Double egress door
Chapter 14
Fig. 14.4.4 Mounting plate assembly
5
5
6
5
Mounting plate,
operator
14.4.5 Drill two holes in pair mounting plate for M6
fastener.
1. Drill hole in each end of pair mounting plate for M6 x
10 mm PFHS (Fig. 14.4.5).
14.4.6 Assemble mounting plates.
1. Place the three mounting plates on a flat surface
(Fig. 14.4.4).
CAUTION
Verify mounting plate assembly dimensions with
installation template (Chapter 13).
2. Secure the operator mounting plates to the pair
mounting plate (6) using:
• (2) mounting plate connectors (4)
• (2) M6 x 10 mm SHS with washer (8)
• (2) M6 x 10 mm PFHS (9)
Do not tighten screws.
14.4.7 Check cover fit over ED operators.
1. Place the ED operators onto their mounting plates.
2. Place end caps (2) at end of each operator.
3. Place cover over end caps and ED operator.
4. Adjust mounting plates as necessary for cover fit
over end caps.
5. Remove end caps and operators.
6. Tighten mounting plate connector fasteners.
14.4.8 Mounting plate installation.
1. Reference Chapter 15.
6
Mounting plate,
pair
Fig. 14.4.5 Pair mounting plate hole for M6 fastener
2.5 mm tap drill
6
5
5
Mounting plate,
operator
6
Mounting plate,
pair
Fig. 14.4.6 Mounting plate connectors and fasteners
4
4
8
8
9
9
6
5
5
4
8
9
4
Mounting plate
connectors
6
Front cover
extension
08121870
7
dormakaba logo
plate
08125241
8
M6 x 10 mm SHS
with washer
9
M6 x 10 mm
PFHS
dormakaba ED900 Installation Instructions – Double egress door
Chapter 15
15.1 ED900 mounting plate attachment to jamb and/or wall examples
Fig. 15.1.3 Mounting plate installation with conduit box
3
1
(12) 2
4
1
ED900 mounting
plate
2
Mounting hole
3
Guide pin
4
Conduit box (option)
15 ED900 mounting plate and operator
installation
Fig. 15.1.1
Double egress door mounting plate installation – standard covers example
1
1
2
2
3
3
1
ED900 mounting
plate
2
115 Vac terminal
block
Fig. 15.1.2 Double egress door mounting plate installation – optional full width cover example
1
ED900 mounting
plate - inactive door
2
ED900 mounting
plate - active door
3
Mounting plate
extension
4
115 Vac terminal
block
5
Conduit box (option)
6
Third guide pin
1
2
4
3
5
6
6
3
Third guide pin
dormakaba ED900 Installation Instructions – Double egress door
Chapter 15
15.2.1 Select installation template.
1. Select applicable installation template.
NOTICE
Installation templates: Reference Chapter 13.
15.2.2 Fasten mounting plates to jamb and/or wall.
CAUTION
Install shims between mounting plates and wall
as required.
CAUTION
ED900 conduit box (if used):
• Insure ED900 conduit box
(Para. 14.3) is prepared with applicable
conduit fitting or cord grip.
• Insure jamb or wall is prepared for wiring
to each ED900 conduit fitting or cord grip.
1. Using template as a guide, prepare
twelve mounting holes at first mounting plate
location for mounting plate fasteners (Fig. 15.2.1).
2. Install first plate.
3. Full width cover option: Using mounting plate
extension as a guide, mark four mounting holes for
extension.
4. Using template as a guide, prepare
twelve mounting holes at second mounting plate
location for mounting plate fasteners (Fig. 15.2.1).
5. Install second mounting plate.
6. Full width cover option: Install mounting plate
extension.
15.2.4 Mounting plate installation checks.
CAUTION
•
Check level.
•
Check spindle to hinge centerline distance.
•
Check mounting plate alignment.
15.2.5 Install third guide pin.
1. Install third guide pin (Fig. 15.2.2) in each mounting
plate (Fig. 15.1.1).
• Use 3 mm hex T-handle or hex key.
13
Fig. 15.2.2 Guide pin
13
Guide pin
15.2 Install ED900 mounting plate to jamb and/or wall
CAUTION
Select fasteners based on door frame and wall
material.
CAUTION
Use fasteners provided with ED900 (Fig. 15.2.1).
Fig. 15.2.1 Mounting plate fasteners
15
1/4-20 x 1" FH
machine screw
16
No. 14 x 1 "FH wood
screw
(12) 15
(12) 16
dormakaba ED900 Installation Instructions – Double egress door
Chapter 15
15.3 Full width cover option – Install cables between mounting plates
Fig. 15.3.3 ED900 cables at active door
Fig. 15.3.2 ED900 cables at inactive door
1
Mounting plate,
active door
2
Mounting plate,
inactive door
3
115 Vac terminal block
3.1
M3 x 5 screw
4
115 Vac plug
5
Ground stud
6
Wire retainer
7
Program switch and
cable
8
115 Vac power cable
TIPS AND RECOMMENDATIONS
Active/inactive door orientation.
May be reversed from Fig. 15.3.1
orientation.
NOTICE
Installer responsibilities.
Installer responsible for routing
and securing all wiring between
ED900 operators.
TIPS AND RECOMMENDATIONS
Cable length options.
Reference Para. 4.12 for cable
length options for:
•
Program switch cable
•
115 Vac power cable
15.3.1 Install program switch cable.
1. Locate single program switch (Fig. 15.3.5)
at end of active door mounting plate
(Fig.15.3.3).
2. Route program switch cable to active
door 115 Vac terminal block end of
mounting plate (Fig. 15.3.4).
15.3.2 Install 115 Vac power cable in
mounting plate channels.
1. Route 115 Vac power cable (Fig. 15.3.6)
between mounting plates using mounting
plate channels.
15.3.3 Install wire retainers to secure
cables.
1. Install wire retainers (Fig. 15.3.7) to
secure cables.
Fig. 15.3.1 Double door mounting plate installation – optional full width cover
1
3
4
5
7
8
6
3.1
Fig. 15.3.4 ED900 housing and terminals,
active door
1
Mounting plate,
inactive door
2
Mounting plate,
active door
3
Mounting plate
extension
4
115 Vac terminal block
1
2
4
3
5
2
5
7
8
6
5
Conduit box (option)
dormakaba ED900 Installation Instructions – Double egress door
Chapter 15
15.3.4 Fasten 115 Vac cable ground wires
to mounting plate ground studs.
1. Inactive door mounting plate – fasten
ground wire ring lug to mounting plate
ground stud (Fig. 15.3.8).
2. Active door mounting plate – fasten
ground wire ring lug to mounting plate
ground stud (Fig. 15.3.9).
TIPS AND RECOMMENDATIONS
Reference Fig. 15.3.10 for ground
stud wiring detail.
• Ground wire ring lug placed
between external tooth
lockwasher and flat washer.
Fig. 15.3.8 Inactive door – 115 Vac cable
ground wire
1
5
8
8.1
1
Active door mounting
plate
5
Ground stud
8
115 Vac power cable
8.1
Ground wire
Fig. 15.3.9 Active door – 115 Vac cable
ground wire
5
Ground stud
6
M5 nut
7
Flat washer
8.1
115 Vac power cable
ground wire
8.2
Ground wire ring lug
9
External tooth lock
washer
5
8.1
6
8.2
7
9
Fig. 15.3.10 Ground stud wiring
2
8
5
8.1
2
Inactive door
mounting plate
5
Ground stud
8
115 Vac power cable
DX3484
8.1
Ground wire
Fig. 15.3.6 115 Vac power cable
Fig. 15.3.5 Single program switch
1
3 conductor cable
3
Ring lug
5
Connector
3
3
5
5
1
3
Fig. 15.3.7 Wire retainer
3
Wire retainer
1
3 position program
switch
2
3 conductor cable
1
2
dormakaba ED900 Installation Instructions – Double egress door
Chapter 15
15.4 Connect customer 115 Vac to ED900 mounting plate terminal block
Fig. 15.4.1 Double door mounting plate installation with standard covers
1
ED900 mounting
plate
3
115 Vac terminal
block
15.4.1 ED900 115 Vac electrical
installation.
WARNING
Work on electrical equipment and
115 Vac wiring installation must
be performed only by qualified
personnel!
WARNING
Electrical shock hazard! 115 Vac
branch circuit disconnect for
ED900's must be Off prior to
start of electrical installation.
WARNING
115 Vac wiring to ED900 operators
must conform to local and national
electrical codes.
Fig. 15.4.2 Double door mounting plate installation – optional full width cover
1
1
3
3
1
ED900 mounting
plate, inactive door
4
115 Vac terminal
block
2
ED900 mounting
plate, aactive door
15.4.2 ED900 installation with standard
covers.
• Customer 115 Vac power wiring required
to terminal block (3) on each mounting
plate (Fig. 15.4.1).
15.4.3 ED900 installation with full width
cover option.
• Customer 115 Vac power wiring required
at terminal block (3) on inactive door
mounting plate (Fig. 15.4.2).
• Active and inactive door assignments
may be reversed from Fig. 15.4.2).
1
2
4
3
5
3
ED900 mounting
plate extension
5
Conduit box (option)
dormakaba ED900 Installation Instructions – Double egress door
Chapter 15
4
115 Vac terminal block
5
Ground post
Fig. 15.4.3 115 Vac wiring example
4
5
Fig. 15.4.4 Conduit box installation
15.5.1 Route accessory wiring (Chapter 9)
to active door mounting plate.
1. Route wiring to active door 115 Vac
terminal block side of mounting plate
(Fig. 14.2.1).
TIPS AND RECOMMENDATIONS
Active/inactive door assignments.
Reference Chapter 12, Para. 12.1
for active/inactive door assignments.
15.5 Route accessory wiring to active door mounting plate
2. Accessory wiring, inactive door hinge
side: route wiring to active door 115 Vac
terminal block side of mounting plate.
TIPS AND RECOMMENDATIONS
Accessory wiring will terminate at
ED900 terminal board (Chapter 9).
NOTICE
Installer responsibilities.
Installer responsible for routing
and securing all wiring between
ED900 operators.
15.4.4 Connect customer 115 Vac wiring.
WARNING
Routing and connection of 115 Vac
wiring to ED900 must be
performed by a qualified person!
WARNING
115 Vac branch circuit disconnect or
circuit breaker must be OFF!
1. Route customer wiring to mounting
plate 115 Vac terminal block.
• Standard cover installation; two 115 Vac
connections required.
• Full width cover installation (optional);
one 115 Vac connection required.
CAUTION
115 Vac wiring.
Use copper conductors only!
1. Connect 115 Vac wiring to each terminal
block.
• Terminal block screw tightening torque.
2. Connect earth ground to mounting plate
ground post (s).
Fig. 15.4.5 PC power cord, conduit box
installation
Fig. 15.5.1 Mounting plate slots for
accessory wiring
TIGHTEN MAINS TERMINAL TO 5-7 in-lb
Use Copper Conductors ONLY
dormakaba ED900 Installation Instructions – Double egress door
Chapter 15
Fig. 15.7.2 Installation of ED900 on mounting plate
1
ED900 mounting
plate
2
ED900 operator
3
Guide pin
4
115 Vac plug
5
Accessory wiring
terminal connectors
Fig. 15.7.3 ED900 115Vac plug and socket
4
115 Vac plug
6
115 Vac socket
7
Power off/on switch
15.7.1 Active door – Install ED900
operator onto its mounting plate.
CAUTION
Protective film strip removal.
Insure two protective film strips
have been removed from operator
heat conductive pads (Para. 15.6).
1. Slide ED900 operator over the three
mounting plate guide pins and onto
mounting plate.
• Guide 115 Vac plug (4) into ED900
housing adjacent to socket (6).
2. Thread the eight captive ED900
M6 SHCS (7) into their mounting plate
holes using 5 mm hex T-handle.
3. Tighten the eight M5 SHCS.
15.7.2 Insert 115 Vac plug into socket.
1. Insert 115 Vac plug from mounting plate
115 Vac terminal block into ED900
socket (Fig. 15.7.2).
15.7.3 Inactive door.
1. Repeat steps in 15.7.1 and 15.7.2.
CAUTION
Full width cover option, single
program switch and cable.
As ED900 operator is lowered
onto mounting plate, route
program switch and cable into
ED900 housing.
Reference Para. 15.8.
6
115 Vac socket
7
M6 x 10 SHCS
15.7 Install each ED900 operator onto its mounting plate
15.6 Remove protective film strips from each ED900 operator
1
Heat conductive
pads
Fig. 15.6.1 Operator protective film strips
15.6.1 Remove protective film strips.
1. Remove two protective film strips from
each operator's heat conductive pads.
CAUTION
Heat conductive pads.
Heat conductive pads must
remain clean once protective film
strips are removed!
1
1
4
6
7
2
5
4
6
3
3
7
7
7
7
1
2
Active door
Inactive door
Fig. 15.7.1 ED900 installation
1
Single program
switch
2
Power switch
dormakaba ED900 Installation Instructions – Double egress door
Chapter 15
15.8 Full width cover option – Install program switch, active door ED900
TIPS AND RECOMMENDATIONS
Active/inactive door orientation.
May be reversed from Fig. 15.8.1
orientation.
14.8.1 Install program switch.
1. Route program switch and cable into
active door ED900 housing.
2. Slide switch into slots in ED900 housing.
• Note orientation of switch in housing
(Fig. 15.8.3).
15.8.2 Connect program switch cable
wires to active door ED900
operator.
1. Connect program switch cable wires to
X1 terminal connector (Fig. 14.7.4)
Fig. 15.8.2 Program switch and cable
7
Program switch and
cable
10
Program switch
terminals
6
Slots for switch
7
Program switch and
cable
Fig. 15.8.3 Program switch installation
7
6
Fig. 15.8.4 Program switch cable
installation, active door ED900
7
Program switch
cable
Terminal
Wire color
Function
31
Brown
Automatic
34
Black
Permanent open
3
Red
0V
Fig. 15.8.5 Program switch functions
7
9
10
15.8.3 Program switch wiring.
Fig. 15.8.1 Program switch installation on active door
1
Single program
switch
2
Power switch
30 31 32
33
34
3 35 3
Brown
Black
Red
X1
7
Automatic
Close
Permanent open
1
2
Inactive door
Active door
dormakaba ED900 Installation Instructions – Double egress door
Chapter 15
15.9 Full width cover option – 115 Vac pair power cable connections
Fig. 15.9.2 ED900 115 Vac pair power cable – inactive door
1
ED900 115 Vac plug
from 115 Vac socket,
female connection
2
ED900 power
supply circuit board
socket, male
connection
3
ED900 power
supply 115 Vac plug,
male connection
4
ED900 power
printed circuit board
socket, female
connection.
5
115 Vac pair power
cable plug, male
connection
15.9.1 Inactive door
1. Insert 115 Vac interconnecting cable plug
(5) into ED900 power supply circuit board
socket (4) (Fig.15.9.2).
1
3
Fig. 15.9.1
Inactive door cables
3
115 Vac interconnect
cable plug, male
connection
Fig. 15.9.4 ED900 115Vac pair power cable
– active door
6
7
6
ED900 power cord,
male connection
7
115 Vac pair power
cable plug, female
connection
7
Fig. 15.9.3 Active door cables
7
115 Vac pair power
cable plug, female
connection
1
2
3
4
5
4
5
4
15.9.2 Active door.
1. Insert 115 Vac interconnecting cable plug
(7) into ED900 power cord socket (6)
(Fig.15.9.4).
dormakaba ED900 Installation Instructions – Double egress door
Chapter 16
16 J/Push arm installation
NOTICE
Reference Chapter 13 for push arm installation
templates.
Fig. 16.1.1 Push arm assemblies
1
J8/Standard push
arm, reveal depths
0 - 8" maximum
2
J12/Deep push arm
reveal depths
8 - 12" maximum
16.2 Push arm installation
Fig. 16.2.1 J8/Splined push arm assembly, 8 7/8" [225]
1
Splined drive arm
2
Socket
4
Adjustment arm
11 1/4"[285]
5
Adjustment arm
tube 12 1/4" [311]
6
Shoe
7
M6 x 10 mm flanged
button head screw
8
Ball head
11
Shoe screw cover
12
M8 x ___ SHCS
13
Cap
Fig. 16.2.2 J12/Splined push arm assembly, 19 11/16" [500]
1
Splined drive arm
2
Socket
6
Shoe
7
M6 x 10 mm flanged
button head screw
8
Ball head
9
Adjustment arm,
17 3/4" [450]
10
Adjustment arm
tube, 17 3/4" [450]
11
Shoe screw cover
12
M8 x ___ SHCS
13
Cap
16.1 Push arm installation templates
2
1
4
5
7
6
8
11
1
12
2
13
1
2
8
10
9
7
6
11
12
13
dormakaba ED900 Installation Instructions – Double egress door
Chapter 16
Fig. 16.2.5 Push arm assemblies for installation
16.2.2 Attach drive arm to operator.
CAUTION
Door must be fully closed!
WARNING
Use caution when working in
proximity of door and push arm!.
CAUTION
ED operator axle zero position.
In order to mount the drive arm in
the correct position, the axle must
be brought to the zero position.
1. Set ED operator spring preload to
approximately ten clockwise rotations.
• Axle rotates to the zero position.
TIPS AND RECOMMENDATIONS
Reference Chapter 19, Operator
spring tension.
2. Insert axle extension into drive arm.
3. Move arm to ED900, inserting arm into
operator spindle at a 90⁰ angle
(Fig. 16.2.5).
4. Insert M8 SHCS through drive arm and
axle extension. Thread SHCS into
ED900 spindle and tighten.
CAUTION
Use torque wrench with hex key
socket to tighten SHCS to
17 ft-lb [23 Nm]
16.2.3 Drill two holes in door for
adjustment arm shoe.
Installation templates (Chapter 13)
document location of shoe on door.
1. Drill two holes in door for adjustment
arm shoe.
• Fastener type based on door material.
TIPS AND RECOMMENDATIONS
Reference Chapter 5, Accessory
kits, for arm fasteners.
16.2.4 Secure adjustment arm assembly
to door.
1. Fasten adjustment arm assembly to
door (Fig. 16.2.6).
1
Drive arm
4
Adjustment arm
11 1/4"[285]
5
Adjustment arm
tube 12 1/4" [311]
6
Shoe
7
M6 x 10 mm flanged
button head screw
8
Ball head
9
Adjustment arm,
17 3/4" [450]
10
Adjustment arm
tube, 17 3/4" [450]
11
ED900 spindle
12
Axle extension sleeve
1
5,10
11
12
6
4,9
Fig. 16.2.6 Arm assemblies attached to
door and ED900
1
Drive arm
6
Shoe
9
Adjustment arm,
17 3/4" [450]
10
Adjustment arm
tube, 17 3/4" [450]
Fig. 16.2.3 Drive arm
1
Drive arm
2
Socket
3
Arm axle sleeve
1
9,10
6
1
2
3
Fig. 16.2.4 Drive arm axle extension installation
1
Drive arm
12
Axle extension sleeve
13
Axle extension
14
M8 x ___ SHCS
1
12
13
14
dormakaba ED900 Installation Instructions – Double egress door
Chapter 16
16.2.5 Connect adjustment arm to drive
arm.
1. Loosen the two adjustment M6 x 10 mm
flanged button head screws (Fig. 16.2.9).
1. Using square, position adjustment arm
assembly at 90⁰ angle to door
(Fig. 16.2.10).
2. Rotate drive arm and adjust length of
adjustment arm until drive arm ball head
(8) is aligned with adjustment arm socket (2).
CAUTION
Maintain adjustment arm
assembly at a 90⁰ angle to door.
3. Insert adjustment arm ball head (8) into
drive arm socket (2).
• Spring in socket will retain ball head in
socket.
4. Secure adjustment arm position by
tightening the two M6 x 10 mm flanged
button head screws.
CAUTION
Recheck that adjustment arm is
at 90⁰ angle to door.
5. Install shoe screw covers.
1
Drive Arm
2
Socket
4
Adjustment arm
11 1/4"[285]
5
Adjustment arm
tube 12 1/4" [311]
6
Shoe
7
M6 x 10 mm flanged
button head screw
90˚ angle
1
5,10
1
8
5, 10
4,9
6
7
2
Fig. 16.2.7 Arm assemblies attached to door and ED900
8
Ball head
9
Adjustment arm,
17 3/4" [450]
Fig. 16.2.10 Adjustment arm at 900 angle to door
1
Drive Arm
5
Adjustment arm
tube 12 1/4" [311]
Fig. 16.2.9 Adjustment arm M6 x 10 screws
7
M6 x 10 mm flanged
button head screw
Fig. 16.2.8 Drive arm, adjustment arm connection
1
Drive arm
2
Socket
3
Spring
5
Adjustment arm
tube 12 1/4" [311]
10
Adjustment arm
tube, 17 3/4" [450]
8
Ball head
2
1
3
5,10
8
7
10
Adjustment arm
tube, 17 3/4" [450]
11
11
Fig. 16.2.11
Shoe screw covers
11
Shoe screw covers
dormakaba ED900 Installation Instructions – Double egress door
Chapter 17
17 Arm with track mount installation
17.1 Arm with track installation
17.2 Splined arm and track assemblies
17.3 Splined arm and track hardware
1
Track
2
End cap
3
Fixing piece
3.1
M5 x 15 Phillips
FHS
4
Pull arm
5
20 mm axle
extension
5.1
Splined sleeve
6
CPD lever
6.1
M6 x 10 SHCS
7
Slotted spring pin
8
Pull arm cap
9
Slide shoe
10
Pivot pin
11
Retaining ring
12
Bumper
13
M8 x 1.25 x 40
SHCS
14
Wood screws
15
Machine screws
16
Bumper stop
17
M5 x 13 FHMS
cross recessed
Fig. 17.3.1
Track assembly
Fig. 17.2.1
T275/Splined arm with CPD
lever and track assembly, LH
1
Drive arm
2
CPD
3
Track
Fig. 17.2.2 T275/Splined arm with CPD
lever and track assembly, RH
Fig. 17.2.3 T/Splined arm and track assembly
1
Drive arm
2
CPD
3
Track
NOTICE
Reference Chapter 13 for pull arm and pull arm
as push installation templates.
1
2
3
1
2
3
1
3
1
2
3
3.1
4
2
3
3.1
5
5.1
6
7
8
9
10
11
12
13
14
16
17
6.1
dormakaba ED900 Installation Instructions – Double egress door
Chapter 17
17.4 Slide shoe assembly
Fig. 17.4.1
Slide shoe and pivot pin
9
Slide shoe
10
Pivot pin
11
Retaining ring
17.4.1 Install pivot pin into slide shoe.
1. Insert pivot pin into slide shoe.
2. Install spring clip into pivot pin slot.
9
10
11
17.5 Install hardware into track
17.5.1 Track assembly.
CAUTION
Assemble track hardware based
on RH or LH installation.
1. Remove both end caps (2) and one fixing
piece (3) from track.
1. Slide bumper stop (16), bumper (12) and
slide shoe assembly (9) into track.
•
Do not tighten bumper stop M5 screw (17).
2. Secure fixing piece to end of track with
M5 x 15 screw (3.1).
• Use No. 2 Phillips, do not over-tighten.
Fig. 17.5.1
RH track assembly
1
Track
3
Fixing piece
9
Slide shoe
12
Bumper
Fig. 17.5.2 LH track assembly
1
Track
3
Fixing piece
9
Slide shoe
12
Bumper
16
Bumper stop
17
M5 x 13 FHMS
cross recessed
3
3
12
9
1
2
2
16
17
16
Bumper stop
17
M5 x 13 FHMS
cross recessed
1
9
12
3
3
1
2
2
16
17
dormakaba ED900 Installation Instructions – Double egress door
Chapter 17
17.6 Fasten track assembly to door
Fig. 17.6.2 Track installation
17.6.1 Mount track assembly on door.
CAUTION
Insure track hardware is
assembled for hand of door.
1. Use applicable template (Chapter 13) to
locate two track mounting holes on door.
CAUTION
Fastener type:
Fig. 17.6.1 shows wood screws.
• Select fastener based on door
material.
2. Drill holes in door, hole size based on
selected screw or fastener
(Ref. Chapter 5, Accessory kits).
3. Mount track to door; thread fasteners
through fixing pieces (2) into door and
tighten.
CAUTION
Check track for level when
tightening fasteners.
1
2
2
15
15
2
Fixing piece
3
Track
15
Fastener
1
2
2
12
9
14
14
16
Fig. 17.6.1
Track assembly
1
Track
2
Fixing piece
9
Slide shoe
12
Bumper
14
Wood screw
Fig. 17.6.3
End cap
17.6.2
Install track end caps.
1. Install track end caps over fixing pieces.
2
End cap
1
Track
2
End cap
2
Fig. 17.6.4 End cap installation
1
2
2
dormakaba ED900 Installation Instructions – Double egress door
Chapter 17
17.8 Arm assembly with CPD lever
17.8.1 Arm with CPD lever assembly.
CAUTION
Assemble arm and CPD lever
based on RH or LH pull or push.
1. Press CPD lever slotted spring pins into
corresponding holes in arm.
2. Secure CPD lever to arm with M6 x 10
SHCS.
Fig. 17.8.5 Arm assembly, LH pull, RH push
Fig. 17.8.4 Arm assembly, RH pull, LH push
6
CPD lever
6.1
M6 x 10 SHCS
7
Slotted spring pin
16
Arm
7
6.1
M6 x 10 SHCS
11
Slotted spring pin
Fig. 17.8.1
Slotted
spring
pin
Fig. 17.8.3 CPD lever and slotted spring pins
6
CPD lever
7
Slotted spring pin
1
17.7 Arm assembly
Fig. 17.7.1 Arm assembly
1
Arm
7
6
6
CPD lever
6.1
M6 x 10 SHCS
7
Slotted spring pin
16
Arm
Fig. 17.8.2 M6 x 10
SHCS
for CPD
6.1
7
7
16
16
6
6.1
7
7
16
16
6.1
6
6
dormakaba ED900 Installation Instructions – Double egress door
Chapter 17
17.9 Fasten arm to ED900 operator
Fig. 17.9.1
Mount drive arm to operator at 12 degrees
Fig. 17.9.6 Torque wrench, 5 mm hex key
17.9.1 Mount drive arm to operator.
WARNING
Use caution when working in proximity of door
and pull arm!.
CAUTION
ED operator axle zero position.
In order to mount the drive arm in the correct
position, the spindle must be brought to the
zero position.
1. Set ED operator spring preload to approximately ten
clockwise rotations.
• Axle rotates to the zero position.
TIPS AND RECOMMENDATIONS
Reference Chapter 19, Operator spring tension.
2. Turn the spring preload back to zero rotations
(fully CCW).
3. Push the drive arm onto the spindle at an angle of
approximately 12⁰ to the ED operator (Fig. 17.9.1).
4. Rotate the drive arm/spindle approximately 10⁰ in
the door's opening direction (Fig. 17.9.2).
5. Remove the drive arm from the spindle (Fig. 17.9.3).
6. Position the drive arm one tooth in the door's closing
direction (Fig. 17.9.4).
7. Push the drive arm / axle extension onto the spindle
(Fig. 17.9.4).
8. Thread the M8 x ___ mm SHCS (length determined
by axle extension) into the spindle and tighten SHCS
(Fig. 17.9.5).
CAUTION
Use torque wrench with hex key socket to
tighten M8 screw to 17 ft-lb [23 Nm].
9. Install cap over M8 SHCS (Fig. 17.9.5).
Fig. 17.9.2 Rotate drive arm 10 degrees in door opening
direction
Fig. 17.9.3 Remove drive arm
Fig. 17.9.4 Install drive arm and axle extension
Fig. 17.9.5 InstallM8 x __ mm SHCS into spindle
2
1
M8 x __ SHCS
2
Cap
1
12˚
10˚
dormakaba ED900 Installation Instructions – Double egress door
Chapter 17
17.9.2 Attach drive arm to pivot pin.
1. Open door as required to access pivot pin M8 socket
head.
2. Use 6 mm T handle hex key to rotate pivot pin
M8 socket head into drive arm and tighten.
CAUTION
Use torque wrench with hex key socket to
tighten M8 screw to 5.9 - 7.4 ft-lb [8 - 10 Nm].
17.9.3 Set operator spring tension.
CAUTION
A minimum of ten spring tension revolutions
are required to operate system.
• Reference Chapter 19 for spring tension
adjustment procedure.
Fig. 17.9.9
Drive arm fastened to track
Fig. 17.9.7
Fastening drive arm to pivot pin
Fig. 17.9.8 Fastening drive arm with CPD to pivot pin
dormakaba ED900 Installation Instructions – Double egress door
Chapter 18
18 Measure door width, reveal depth
Parameter
Description
Reference
paragraph,
parameters
2
Tb
Door width
Para. 18.1.8
Parameter Tb value
Door width
measurement
18.2 Record door width
measurement, Tb value
18.1.1 Door width parameter
Door width is set in increments of 100 mm (4").
Example:
Measured width of 40" [1016] = Tb value of "10".
18.1 Door width parameter Tb
18.3 Tb parameter values
Door width measurement
Inches
[mm]
Tb
Width
Inches [mm]
28 - 31 15/16
[711] - [811]
7
28 [711]
32 - 35 15/16
[813] - [912]
8
32 [813]
36 - 39 15/16
[914] - [1014]
9
36 [914]
40 - 43 15/16"
[1016] - [1116]
10*
40 [1016]
44 - 47 15/16
[1118] - [1218]
11
44 [1118]
48 - 51 15/16
[1219] - [1319]
12
48 [1219]
15.3.1 ED900 door width
*Factory setting
Fig. 18.2.1 Measure door width
Door width
dormakaba ED900 Installation Instructions – Double egress door
Chapter 18
18.3 Reveal depth parameter rd
Parameter
Description
Reference paragraph
2
rd
Reveal depth
18.5 rd parameter values
Reveal measurement
Inches
[mm]
rd
-2 3/8"
-60
-6
-1 3/16
-30
-3
-3/4
-20
-2
-3/8
-10
-1
0
0*
0
3/8
10
1
3/4
20
2
1 1/8
30
3
1 9/16
40
4
18.5.1 ED900 reveal depths, rd parameter
Reveal measurement
Inches
[mm]
rd
1 15/16
50
5
2 3/8
60
6
2 3/4
70
7
3 1/8
80
8
3 1/2
90
9
3 15/16
100
10
4 5/16
110
11
4 3/4
120
12
5 1/8
130
13
Parameter rd value
Reveal measurement
18.3.1 Reveal depth parameter.
1. Reveal depth is set in increments of 10 mm
(approximately 3/8").
Example: Measured reveal depth of 30 mm
(approximately 1 3/16") equals rd parameter value of 3.
18.4.1 Measure reveal depth parameter.
Reveal depth measurement required for each ED900
operator.
Reveal measurement
Inches
[mm]
rd
5 1/2
140
14
5 7/8
150
15
6 5/16
160
16
6 11/16
170
17
7
180
18
7 1/2
190
19
7 7/8
200
20
8 1/4
210
21
8 5/8
220
22
Reveal measurement
Inches
[mm]
rd
9
230
23
9 7/16
240
24
9 13/16
250
25
10 1/4
260
26
10 5/8
270
27
11
280
28
11 7/16
290
29
18.4 Measure and record reveal
depth
Fig. 18.4.1 T275 track and pull arm
Fig. 18.3.1 Positive reveal
Fig. 18.3.2 Negative reveal
Mounting surface
Negative reveal
depth
Door face
Door frame
Positive reveal depth
Door
frame
Mounting surface
Door face
*Factory setting
18.4.2 Use of T275 track and pull arm (Fig. 18.4.1).
Value of parameter rd must be reduced by 3/16" [30].
• Example: ED900 with T275 track in pull installation
with reveal of 30 mm (1 1/8").
Parameter rd setting = 0. (Reveal of 30 mm - 30
mm).
dormakaba ED900 Installation Instructions – Double egress door
Chapter 19
19.1 Set ED900 operator spring tension
19.1.2 Operator spring tension function.
1. Spring tension sets closing force on door.
2. Required spring tension is based on door width.
19.1.3 Spring tension adjustment.
Spring tension adjustment required for both ED900
operators.
1. Spring tension adjustment is factory set fully CCW,
no spring tension.
2. Spring must be pretensioned per Para. 19.1.1.
• Use 5 mm T-handle hex key (Fig. 19.1.2).
Clockwise - increases spring tension.
Counterclockwise - decreases spring tension.
CAUTION
A minimum of ten spring tension revolutions
are required to operate system.
CAUTION
Any change to spring tension setting requires a
new learning cycle (Chapter 23)!
Fig. 19.1.1 Spring tension adjustment
Door width
Inches
32
36
42
48
mm
813
914
1067
1219
Spring setting
revolutions
ED900
10
14
16
18
19.1.1 Spring tension setting revolutions.
TIPS AND RECOMMENDATIONS
System checks spring tension during learning
cycle (Chapter 23).
Learning cycle will be canceled if spring is
insufficiently tensioned; door will stop and
display will show a rotating "0" and an "F".
19.1.4 Check door closing force.
1. Para. 19.1.1 lists approximate spring tension settings.
2. Use pressure gauge to check door closing force at 2°
and adjust tension setting if necessary.
Fig. 19.1.3
Door pressure gauge
TIPS AND RECOMMENDATIONS
Reference Chapter 30, ANSI/BHMA standards
for door closing forces.
1
Spring tension
adjustment
Fig. 19.1.2
5 mm T-handle hex key
19 Operator spring tension
+
-
dormakaba ED900 Installation Instructions – Double egress door
Chapter 20
1
2
20.1 Braking circuit plug position
20 Braking circuit plug
Fig. 20.1.1 Braking circuit socket and plug; plug factory installed in pull arm location
1
Braking circuit plug
2
Braking circuit 3
pin socket
3
User interface
Fig. 20.1.2 Plug position, pull arm
Fig. 20.1.4 Plug position, push arm
1
Braking circuit plug
2
Braking circuit
3 pin socket
1
Braking circuit plug
2
Braking circuit
3 pin socket
Fig. 20.1.3 Power switch
4
Power switch
(shown ON)
3
1
2
1
2
4
20.1.1 Braking circuit plug.
Braking circuit plug positioning required for
both ED900 operators.
Operator braking circuit plug is positioned in
its 3 pin socket for a push or pull installation.
WARNING
Braking circuit will not work correctly
if braking circuit plug is improperly
positioned, or if an incorrect plug is
used!
Door may close at high speed
and/or be difficult to open!
17.1.2 Factory-installed plug position.
Braking circuit plug is factory installed in the
left two pins, the pull installation position
(Fig. 20.1.1 and Fig. 20.1.2).
17.1.3 Change braking circuit plug position
to push installation.
To change plug position for push installation,
install plug in right two pins, toward user
interface (Fig. 20.1.4).
WARNING
Insure power switch is OFF before
changing plug position!
Fig. 20.1.5 Standard push arm
Fig. 20.1.6 Arm and CPD lever and track,
pull or push installation
dormakaba ED900 Installation Instructions – Double egress door
Chapter 21
21.1 Set power fail closing speed
21 Power fail closing speed
1
Power fail closing
speed
potentiometer
2
Control board
Fig. 21.1.1 Power fail closing speed potentiometer
1
2
o
1
2
Fig. 21.1.2 Power on switch
1
Power on switch
2
Terminal board
21.1.1 Power fail closing speed
potentiometer.
• Single turn
• Factory setting: fully CCW
• CCW increases closing speed.
• CW decreases closing speed.
• 3/32" [2-3 mm] flat blade screwdriver
required for adjustment.
21.1.2 Setting door closing speed upon
power failure.
1. Turn ED900 power switch OFF.
2. Manually open door to 90° angle and let
it close.
3. If door closes in less than 5 seconds, turn
potentiometer 1/4 turn CW and retry
test.
4. Continue retrying test after
potentiometer adjustment until the door
closing time is a minimum of 5 seconds
21.1.3 Repeat setting closing speed for
second door.
NOTICE
Error message E73:
If door closes in less than three
seconds, error message E 73
(System error 3, braking circuit) will
be displayed.
Reference: Appendix B,
Troubleshooting.
TIPS AND RECOMMENDATIONS
Minimum 5 second closing time is
required to meet requirements of:
• A117.1, Accessible and Usable
Buildings and Facilities,
Section 404.2.7.
•
2010 ADA Standards for
Accessible Design,
Section 404.2.8.
dormakaba ED900 Installation Instructions – Double egress door
Chapter 22
71
22.1 Parameters
Step 1
Press right button greater than 3 s to
enter program mode.
Step 2
Press up or down button to scroll through
parameters until desired parameter is
displayed.
Step 3
Press right button to display current
parameter value.
Step 4
Press right button again to enable
editing of value, display will start
flashing.
Step 4
Press up or down button to select
desired parameter value.
Step 5
Press right button to save selected
value. Display stops flashing.
Step 6
Press left button to return to selected
parameter.
Step 7
Press up or down button to scroll
through parameters until next desired
parameter is displayed.
Step 8
Press left button for a minimum of 3 s
to exit program mode.
Fig. 22.1.1
dormakaba handheld terminal
22.1.2 Configuration parameters.
Configuration parameters (Para. 22.1.5) are set during
first commissioning (Chapter 23).
• Reference Para. 22.1.7 for configuration parameter
detail.
22.1.3 Driving parameters.
Driving parameters can be set once first commissioning
has been completed.
•
Reference Para. 22.1.6 for a list of driving parameters.
• Reference Appendix A for driving parameter detail.
1
Program switch,es,
close position
22.1.4 Changing parameter values.
1. Set program switches to the CLOSE position
2. Use 4 button keypad as outlined in Steps 1 through 8
to view or change parameter values.
Fig. 22.1.2 Program switches
Fig. 22.1.3 4 button keypad,
2 digit display
2
2 digit display
5
4 button keypad
22 Parameters
22.1.1 Firmware version and updates.
• Operator firmware version is displayed during first
commissioning. Reference Chapter 23.
• dormakaba handheld can be used to check operator
firmware version and to perform firmware updates.
Reference Appendix C, dormakaba handheld, or
dormakaba handheld manual.
> 3s Reset
< 3s Quit
> 3s
PRG
< 3s
LEARN
Fact-Setup
> 3s
> 8s
2
5
dormakaba ED900 Installation Instructions – Double egress door
Chapter 22
Parameter
Description
1
AS
Installation type
2
rd
Reveal depth
3
Tb
Door width
4
dL
Door type
22.1.5 Configuration parameters
Driving parameter
Description
5
So
Opening speed, automatic mode
6
Sc
Closing speed, automatic mode
7
dd
Hold open time, automatic mode
8
dn
Hold open time, night/bank
9
do
Hold open time, manual opening of door
10
Sb
Wall masking on door swing (hinge) side
11
ST
Safety sensor test
12
SA
Activation by safety sensor on approach
(opposite hinge) side
13
SP
Suppression of safety sensor on swing
hinge) side during initial movement
14
Ud
Locking mechanism delayed opening time
15
Pu
Door preload prior to unlocking
16
TS
PR (Power reserve) module test
17
Fo
Static force on door closing edge in
opening direction (wind load control)
18
Fc
Static force on door closing edge in
closing direction (wind load control)
19
EP
Motor driven latching action, automatic
mode
20
EA
Door opening angle at which motor
driven latching action is activated
21
Left intentionally blank
22
PG
Push and Go
23
PS
Program switch type
24
S1
DCW EPS, electronic program switch
behavior following a power reset
25
S2
Internal program switch;
switch function on delay
26
du
Door unlocking during business hours
27
Sr
Status relay function, terminal block X7
22.1.6 Driving parameters
Driving parameter
Description
28
bE
Input 4/4a and X3, 1G 24V locking
device output configuration
29
CC
Cycle counter, number displayed * 10000
30
EC
Delete error log
31
CS
Reset service interval display (yellow LED)
32
SL
Factory setting level (Fact Setup button)
33
OA
Opening angle, set during learning cycle
34
hd
Door closer mode, automatic or manual
35
hA
Power assist function activation angle
36
hF
Power assist function force adjustment
37
hS
Power assist function support for
manual mode in door closed position
38
F1
Upgrade card, fire protection
39
F2
Not used
40
F3
Not used
41
F4
Not used
42
F5
Not used
43
F7
Upgrade card, barrier free toilet
44
F8
Not used
45
C1
Configuration of COM 1 interface
46
bc
Back check angle when door opened
manually
47
Td
Door thickness (mm)
48
d1
Deactivation of drive, emergency
pushbutton at X4, 4 and 4a, trigger type
49
d2
Night/bank function, trigger type
50
FC
Hold open system release by manually
closing door, trigger type
51
Ad
Active door with astragal, caster angle;
angle door must reach before passive
door starts to open
52
HS
Hinge clearance
TIPS AND RECOMMENDATIONS
Driving parameter details can be found in Appendix A.
dormakaba ED900 Installation Instructions – Double egress door
Chapter 22
Fig. 22.1.5 T275/Arm with CPD lever and track
22.1.7 Configuration parameters, detail.
Fig. 22.1.4 T/Arm with track
Fig. 22.1.6 J/Push arm
Fig. 22.1.7 J8/Deep reveal push arm
Parameter and value
range, factory setting
= bold.
Parameter description
1
0 - 2
0
Installation type
0
Pull
•
Arm with track (Fig. 22.1.4).
•
Arm and CPD lever with track
(Fig. 22.1.5).
Wall mounting on swing (hinge)
side.
1
Push
•
Standard push arm
(Fig. 22.1.6)
Wall mounting on approach
(non-hinge) side.
2
Push
•
Arm with track (Fig. 22.1.4).
•
Arm and CPD lever with track
(Fig. 22.1.5).
Wall mounting on approach
(non-hinge) side.
2
ED900
-3 to 29
0
Reveal depth
0
Reveal is set in increments of
10 mm (3/8"), "3" = 30 mm (1 1/8")
•
ED900: [-30 to 290 mm]
-1 3/16" to 11 13/32"
If using arm with CPD lever
(Fig. 22.1.5), approximately
1 3/16" [30 mm] must be
deducted from actual reveal.
3
Tb
ED900
7 to 12
12
Door width
10
Door width is set in increments of
100 mm (4"),;"9" = 900 mm (35.4").
•
ED900: [700 - 1219] 28" - 48"
22.1.9 Arm with track – push installation
[Application specific].
1. For doors without fire or smoke detection
requirements.
2. Maximum reveal depth of 2 3/8" [60].
3. Maximum opening width at a reveal depth of
2 3/8"[60] is reduced to 95 degrees.
22.1.8 CPD arm and lever; rd parameter adjustment.
• Value of parameter rd must be reduced by 3/16" [30]
when using the arm with CPD lever in a pull
installation.
• Example: ED900 with arm and CPD lever in pull
installation with reveal of 30 mm (1 1/8").
Parameter rd setting = 0 (Reveal of 30 mm - 30 mm).
4
0 to 4
0
Door type
0
Single door
1
Double door
•
Overlapping door (with
astragal)
•
Active door operator.
2
Double door
•
Overlapping door (with
astragal)
•
Passive door operator.
3
Double door
•
Edgeless door (no astragal)
•
Active door operator.
4
Double door
•
Edgeless door (no astragal)
•
Passive door operator.
dormakaba ED900 Installation Instructions – Double egress door
Chapter 23
23.1 First commissioning
Fig. 23.1.2 Power switch
Fig. 23.1.1
Program switch
2
Power switch
Fig. 22.1.3 4 button keypad,
2 digit display
3
Four button
keypad
4
Two digit display
23 Single door first commissioning
1
Program switch,
3 position
o
2
4
3
> 3s Reset
< 3s Quit
> 3s
PRG
< 3s
LEARN
Fact-Setup
> 3s
> 8s
Conditions prior to commissioning.
1. ED900 operators are installed.
2. Standard push arms or arm with tracks are
installed.
3. 115 Vac branch circuit to operators is energized.
4. Operator motors are cold.
CAUTION
Motors must be cold for commissioning!
Step 1
Program switch to CLOSE position.
Step 2
Power switch to ON position.
System check.
• Series of letters and numbers
rapidly displayed.
Control unit self check.
• Two segments jumping back
and forth.
Horizontal dashes move up and
down.
Step 3
Press 4 button keypad
down button
.
While 2 digit display segments
move up and down, letters and
numbers will change if required
to display correct orientation.
Display scrolls:
•
Device ID (Ed 900)
•
Firmware version
(format F x x x x)
Program mode display.
Program mode will be displayed
indicating system requires further
parameter settings.
TIPS AND RECOMMENDATIONS
If pressing down button (Step 3) does not
result in desired display orientation,
return to Step 2, turn power button off, then
on to repeat commissioning steps.
23.1.1 First commissioning.
Steps in Para. 23.1 through Para. 23.4 must be
completed for each ED900 operator.
TIPS AND RECOMMENDATIONS
Accessory wiring.
Termination of accessory wiring to the ED900
active door operator should be done only after
operator commissioning is completed and
learning cycle is performed for each door.
Reference Chapter 25 for accessory wiring.
dormakaba ED900 Installation Instructions – Double egress door
Chapter 23
Step 1
Press
Press PRG greater than 3 s to enter
program mode, AS parameter
displayed.
If no change required, go to step 7.
Step 2
Press
Displays "00" , factory setting.
Step 3
Press
"00" starts flashing.
Step 4
Press
Scroll to select parameter value.
"1" shown as example.
Step 5
Press
Saves value entered. Display stops
flashing.
Step 6
Press
Returns to Installation type parameter.
23.2.1 Set parameter AS, installation type.
Installation type
Parameter
value
Parameter description
0*
Pull arm with track, wall mounting on swing
(hinge) side.
1
Push arm, wall mounting on approach (opposite
hinge) side.
2
Push arm with track, wall mounting on approach
(opposite hinge) side.[Application specific]
*
Factory setting
23.2 Set configuration parameters
Fig. 23.2.1 4 button keypad,
2 digit display
3
Four button
keypad
4
Two digit display
Step 7
Press
Scroll to rd parameter.
Step 8
Press
Displays "00" , factory setting.
Step 9
Press
"00" starts flashing.
Step 10
Press
Scroll to select parameter value.
"6" shown as example.
Step 11
Press
Saves value entered.
Display stops flashing.
Step 12
Press
Returns to reveal depth parameter.
23.2.2 Set parameter rd, reveal depth.
Configuration parameter settings continue on next
page.
TIPS AND RECOMMENDATIONS
Reference Chapter 18 for reveal depth
parameter values.
4
3
> 3s Reset
< 3s Quit
> 3s
PRG
< 3s
LEARN
Fact-Setup
> 3s
> 8s
dormakaba ED900 Installation Instructions – Double egress door
Chapter 23
Step 13
Press
Scroll to Tb parameter.
Step 14
Press
Displays "10" , factory setting.
Step 15
Press
"10" starts flashing.
Step 16
Press
Scroll to select parameter value.
"7" is example, for door widths of
28" to 31 15/16"
Step 17
Press
Saves value entered.
Display stops flashing.
Step 18
Press
Returns to door width parameter.
If single door, exit program mode
(Step 19).
Step 19
Press
Exits program mode. Display indicates
"ready for learning cycle".
23.2.3 Set parameter Tb, door width.
20.2.4 Parameter dL, door type.
Fig. 23.2.2 4 button keypad,
2 digit display
3
Four button
keypad
4
Two digit display
TIPS AND RECOMMENDATIONS
Reference Chapter 18 for door width
parameter values.
TIPS AND RECOMMENDATIONS
Parameter dL factory setting is 0, single door.
4
3
> 3s Reset
< 3s Quit
> 3s
PRG
< 3s
LEARN
Fact-Setup
> 3s
> 8s
23.3 Set parameter PS, program switch type
23.3.1 Full width cover or Key switch panel option –
set parameter PS to 1.
Step 1
Press
Press and hold PRG > 3 s to enter
program mode, AS parameter
displayed.
Step 2
Press
Scroll to PS (Program switch type)
parameter.
Step 3
Press
Displays "00" , factory setting.
Step 4
Press
"00" starts flashing.
Step 5
Press
Scroll to select parameter value "1",
External mechanical program switch
connected to operator terminal board.
CAUTION
Key switch panel options – program switch
wired to ED900 terminal board.
Reference Appendix D.
Parameter PS (Program switch type) must be
set to 1.
Step 6
Press
Saves value entered. Display stops
flashing.
Step 7
Press
Returns to program switch parameter.
Step 8
Press
Exits program mode.
dormakaba ED900 Installation Instructions – Double egress door
Chapter 23
23.4 Perform learning cycle
CAUTION
Learning cycle must be performed while
motor is cold!
CAUTION
Door must not be manually moved or held in
position during the learning cycle!
CAUTION
Verify that the following parameters have
been set (Para. 23.2):
•
AS, Installation type
•
rd, Reveal depth
•
Tb, Door width
Full width cover option or Key switch panel option, set
PS parameter to 1.
•
PS, Program switch type (Para. 23.3).
TIPS AND RECOMMENDATIONS
During learning cycle:
•
Operator functions are deactivated.
Step 2
Set program switch to CLOSE position,
Fig. 20.4.1.
Rotating "o" and a "0" indicates
operator learning cycle is required.
Step 3
Press
Press and hold down button until display
changes.
•
Door performs several movements
and display shows a sequence of
symbols.
•
Movements of door must not be
interrupted!
Display indicates door is at 70° position
and is waiting for door opening angle to
be set.
Step 1
Secure motion range of door.
Step 4
•
Manually move door to desired
opening angle.
Maximum door angle is 110°.
Step 5
Press
Momentarily press down button to
continue learning cycle.
•
Door performs several movements
and display shows a sequence of
symbols.
•
Movements of door must not be
interrupted!
Operator spring tension too low.
•
Display with small rotating "o" and
an "F" during learn cycle indicates
spring tension is too low.
•
Door will close.
1. Increase spring tension
(Chapter 19).
2. Restart learning cycle (Step 3).
Door completes learning cycle.
•
Display with two horizontal bars
indicate operator is ready for
operation.
Step 6
Press
Momentarily press down button to cycle
door.
Step 7
Following automatic learning cycle,
actual forces on door, and door
opening and closing times must be
measured and changed if necessary
to insure compliance with
ANSI/BHMA standards, reference
Chapter 30.
Step 9
Set program switch to Auto, Fig. 20.4.2.
WARNING
No personnel or objects must be in range of
door motion during learn cycle!
Fig. 23.4.1 Program switches,
CLOSE position
Fig. 23.4.2 Program switches,
Auto position
dormakaba ED900 Installation Instructions – Double egress door
Chapter 24
24.1 Separately commission active and inactive doors
24 Double door first commissioning
24.1.1 Commission active door first.
1. Refer to Chapter 23 and commission active door.
24.1.2 Commission inactive door.
1. Refer to Chapter 23 and commission inactive door.
24.2 Set operator parameters for double door operation
24.2.1 Full width cover option –
Active door, set parameter PS to 1.
1. Set program switch to CLOSE
Step 1
Press
Press and hold PRG > 3 s to enter
program mode, AS parameter
displayed.
Step 2
Press
Scroll to PS (Program switch type)
parameter.
Step 3
Press
Displays "00" , factory setting.
Step 4
Press
"00" starts flashing.
Step 5
Press
Scroll to select parameter value "1",
External mechanical program switch
connected to operator terminal board.
Fig. 24.2.1 Single program switch located on active door.
CAUTION
Full width cover option – single program
switch.
Parameter PS on active door must be set to 1.
Reference Para. 23.2.1.
Automatic
Close
Permanent open
Step 6
Press
Saves value entered. Display stops
flashing.
Step 7
Press
Returns to program switch parameter.
Step 8
Press
Exits program mode.
dormakaba ED900 Installation Instructions – Double egress door
Chapter 24
24.2.2 Active door, set parameters dL and Ad.
1. Set active door program switches to CLOSE.
2. Set parameters dL (door type) and Ad (caster angle )
for active door.
• Castor angle sets opening angle of active door
before inactive door starts to open.
Factory setting is 30°.
Step 1
Press
Press and hold PRG > 3 s to enter
program mode, AS parameter
displayed.
Step 2
Press
Scroll to dL parameter.
Step 3
Press
Displays "00" , factory setting.
Step 4
Press
"00" starts flashing.
Step 5
Press
Scroll to select parameter value
("1" as an example).
Step 6
Press
Saves value entered. Display stops
flashing.
Step 7
Press
Returns to door type parameter.
Step 8
Press
Scroll to Ad parameter.
Step 9
Press
Displays "30", factory setting.
Step 10
Press
Scroll to select parameter value
(10° as an example).
Step 11
Press
Saves value entered. Display stops
flashing.
Step 12
Press
Returns to caster angle parameter.
Step 13
Press
Exits program mode. Operator is ready
for operation.
Fig. 24.2.2 Program switches in
CLOSE position
Door type
Parameter
value
Parameter description
0*
Single door
1
Double door, with astragal.
Active door operator, door opens first.
2
Double door, with astragal.
Inactive door operator.
3
Double door, without astragal.
Active door operator. Both doors open
simultaneously.
4
Double door, without astragal.
Inactive door operator. Both doors open
simultaneously.
*
Factory setting
CAUTION
Full width cover option
Single program switch located on inactive
door.
dormakaba ED900 Installation Instructions – Double egress door
Chapter 24
Step 1
Press
Press and hold PRG > 3 s to enter
program mode, AS parameter
displayed.
Step 2
Press
Scroll to dL parameter.
Step 3
Press
Displays "00" , factory setting.
Step 4
Press
"00" starts flashing.
24.2.3 Inactive door, set parameter dL.
1. Set program switch to CLOSE.
2. Set parameter dL (door type) for inactive door.
Step 5
Press
Scroll to select parameter value
("3" as an example).
Step 6
Press
Saves value entered. Display stops
flashing.
Step 7
Press
Returns to door type parameter.
Step 25
Press
Exits program mode. Operator is ready
for operation.
24.3 Connect communication cable between operators
Fig. 24.3.1 Double door operators, communication cable
1
RJ45 jack
(horizontal) for
communication
cable
2
Communication
cable
2
Communication
cable 08125243
Fig. 24.3.3 Communication cable
24.3.1 Install communication cable.
1. Set program switch to CLOSE.
2. Connect communication cable to active
and inactive operator RJ45 jacks.
3. Secure cable to header
23.3.2 Test door operation
1. Set program switch to AUTO.
2. Test double door operation.
• Use knowing act device
Fig. 24.3.4 Program switch
1
Program switch,
3 position
1
1
4
Fig. 24.3.2 RJ45 jack
1
RJ45 jack
4
Program switch
cable
1
1
2
2
dormakaba ED900 Installation Instructions – Double egress door
Chapter 25
11
12
12
Fig. 25.1.1
ED900 terminal connectors
11
Connectors
12
Jumpers
25.1 Install accessory wiring
25.1.1 Connect accessory wiring.
• All accessory wiring terminates at active
door ED900 terminals.
Reference Chapter 9, System Accessories.
1. Use applicable terminal connectors
(Fig. 25.1.1) to terminate accessory
wiring.
TIPS AND RECOMMENDATIONS
• Use documentation provided
with each device for electrical
installation.
• Do not connect system
accessories to board until
operator has been
commissioned and learning
cycle performed
(Chapter 23, 24).
2. Use diagram in Chapter 9 to locate
connector to its socket.
CAUTION
Terminal jumpers.
Jumpers (Fig. 25.1.1/12) must be
in place on monitoring circuits.
25 Connect accessory wiring and test
25.2 Test all accessories
25.2.1 Test all accessories.
1. Test functions of all accessories.
TIPS AND RECOMMENDATIONS
ED900 115 Vac branch circuit
disconnect should be Off while
making accessory connections!
dormakaba ED900 Installation Instructions – Double egress door
Chapter 26
26 Set track bumper stop
26.1.1 Set bumper stop position.
1. Set program switch to OPEN.
2. Door moves to set opening angle.
WARNING
Use caution when working in
proximity of door and track.
3. Slide bumper and bumper stop toward
slide shoe until bumper is 3/16" from
edge of slide shoe (Fig. 26.1.3).
4. Tighten bumper stop M5 screw. Do not
overtighten.
CAUTION
Using program switch, close then
open door to verify gap between
bumper and slide shoe with door
at full open position.
26.1 Set track bumper stop position
Fig. 26.1.2 Door at set opening angle
Fig. 26.1.3 Setting bumper stop location
Fig. 26.1.1
Program switch OPEN position
9
Slide shoe
12
Bumper
17
Bumper stop
13
MM5 x 13 FHMS
cross recessed
17
16
12
9
3/16” gap
dormakaba ED900 Installation Instructions – Double egress door
Chapter 27
27 Install push arm door stop
27.1 Install push arm door stop (optional assembly)
27.1.1 Assemble bumper stop.
1. Attach bumper to bumper mounting
plate with 1/2" shoulder screw.
• Use 5 mm hex key.
27.1.2 Open door.
1. Set program switch to OPEN position.
2. Door moves to set opening angle.
WARNING
Use caution when working in
proximity of door and push arm!.
Fig. 27.1.2 Program switch, OPEN position
Fig. 27.1.1
Door stop assembly
4
Bumper stop
assembly
27.1.3 Bumper stop installation.
1. With door at its full open position locate
door stop assembly bumper on door
frame 1/8" beyond arm.
2. Mark mounting plate hole locations on
frame.
• Plate hole diameter is 1/4".
3. Select fasteners based on door frame
material.
4. Attach door stop assembly to frame.
CAUTION
Using program switch, close then
open door to verify arm does not
contact door stop with door at
full open position.
5.1
5.2
1
3
4
2
Fig. 27.1.4 Door stop installation
6
Door stop assembly
1/4" thick plate
08121320
Door stop assembly
1/2" thick plate
08121330
1
Plate, bumper
mounting,
1/4" thick
08120774
2
Plate, bumper
mounting,
1/2" thick
08120770
3
Rubber bumper
08120750
4
Shoulder bolt
08104231
5.1
1/4-20 x 1 1/4"
Phillips FHS, black
oxide, SS
5.2 No. 14 x 1 1/4"
Phillips FHMS for
sheet metal, zinc
plated steel
dormakaba ED900 Installation Instructions – Double egress door
Chapter 28
28 Install ED900 cover, end caps and
spindle caps
28.1 Install cover and end caps
28.1.1 Install covers.
1. Align cover with operator, press inward
until cover snaps into place.
CAUTION
Insure that all cables are in place
and secured as necessary.
TIPS AND RECOMMENDATIONS
Optional full width cover.
28.1.2 Install end caps.
1. Install ED900 operator end caps.
TIPS AND RECOMMENDATIONS
Program switch end cap; insertion
depth is adjustable to compensate
for minor tolerances is length of
operator cover.
Fig. 28.1.1 ED900 standard cover
Fig. 28.1.3 Cover and end cap installation
3
2
Fig. 28.1.2 ED900 operator end caps
2
End cap, program
switches
1
Standard cover
3
End cap, power
switch
3
2
1
2
End cap, program
switches
3
End cap, power
switch
1
ED900 standard
cover
dormakaba ED900 Installation Instructions – Double egress door
Chapter 28
Fig. 28.2.1 Spindle caps
4
5
4
Spindle cap
5
Spindle cap
28.2.1 Install spindle caps.
1. Install spindle caps on ED900 cover.
Fig. 28.2.2 Spindle cap installation, ED900 cover top
Fig. 28.2.3 Spindle cap installation, ED900 cover bottom
28.2 Install spindle caps
4
5
4
Spindle cap
4
4
Spindle cap
5
Spindle cap
dormakaba ED900 Installation Instructions – Double egress door
Chapter 28
28.3 Full width cover option – Install cover and end caps
1
2
3
4
1
2
3
4
Fig. 28.3.3 End cap installation
Fig. 28.3.2 ED900 full width cover option
Fig. 27.3.4 Full cover installation
28.3.1 Install end caps.
1. Install power switch and program switch end caps.
TIPS AND RECOMMENDATIONS
Active door and inactive door may be reversed
from Fig. 28.3.3 orientation.
28.3.2 Install full length cover.
2
End cap, program
switches
1
End cap, power
switch
Fig. 28.3.1 ED900 end caps
1
2
dormakaba ED900 Installation Instructions – Double egress door
Chapter 29
29 Install door signage
29.1 Install door signage
29.1.1 Install door signage based on type of door
operation.
Install applicable door signage as outlined in Chapter 10,
ED900 door signage.
dormakaba ED900 Installation Instructions – Double egress door
Chapter 30
30 ANSI/BHMA standards
ED900 Parameter
A156.19 standard
Parameter
Function
Factory
setting
Adjustment range
Para. Requirement
So
Opening speed
Swing door opening speed.
17°/s
Note 1
8°/s - 27°/s
27°/s max.
L.E. mode
4.2
Opening
Doors shall open from closed to back check or
80°, whichever occurs first, in 3 seconds or
longer as required in Table I.
Total opening time to 90° shall be as in Table II.
If door opens at more than 90°, iit shall
continue at the same rate as back check
speed.
bc
Back check
Checking or slowing down of
door speed before door being
fully opened.
10°
5° - 40°
4.2
Back check shall not occur before 60° opening.
Sc
Closing speed
Swing door closing speed,
automatic mode.
17°/s
Note 1
8°/s - 27°/s
27°/s max.
L.E. mode
4.4
Closing:
Doors shall close from 90° to 10° in 3 seconds
or longer as required in Table I.
Doors shall close from 10° to fully closed in not
less than 1.5 seconds.
dd
Hold open
time
Hold open time.
5 s
5 s - 30 s
4.3
Time delay:
When powered open, the door shall remain
open at the fully opened position for not less
than 5 seconds.
Exception: when push-pull activation is used,
the door shall remain at the fully opened
position for not less than 3 seconds.
hS
Reference
Appendix A for
parameter
detail.
Support for manual mode in
door closed position.
4.5
Doors shall open with a manual force:
•
Not to exceed 15 lbf [67 N]to
release a latch if equipped with a
latch.
•
To set a door in motion 30 lbf [133
N].
•
To fully open the door 15 lbf [67 N].
Forces shall be measured 1" [25.5] from
latch edge of door.
hA
Adjustment, door activation
angle.
hF
Power assist function.
Fo
Static force
in opening
direction
Static force on door closing
edge in opening direction.
13.5 lb f
[60 N]
4.5 lb f [20 N] -
15 lb f [67 N]
4.5
Force required to prevent a stopped
door from opening or closing shall not
exceed 15 lb f [67 N] measured 1"
[25.4] from latch edge of door at any
point during opening or closing.
Fc
Static force
in closing
direction
Static force on door closing
edge in closing direction.
13.5 lb f
[60 N]
4.5 lb f [20 N] -
15 lb f [67 N]
4.5
30.1 A156.19 Low energy power operated doors
The following table references portions of content from ANSI/BHMA A156.19. Refer to the standard, available
through ANSI or BHMA for additional information. Standard material reprinted with BHMA permission.
30.1.1 Door measurements, low energy power operated door
Note 1: Speed may be slower after learning cycle
completed.
dormakaba ED900 Installation Instructions – Double egress door
Chapter 30
"D" door width,
inches [mm]
"W" door weight, pounds [kg]
100 [45.4]
125 [56.7]
150 [68]
175 [79.4]
200 [90.7]
30 [762]
3.0
3.0
3.0
3.0
3.5
36 [914]
3.0 s
3.5 s
3.5 s
3.0 s
3.0 s
Minimum opening time to back check or 80 degrees (whichever occurs first).
Minimum closing time from 90 degrees to latch check or 10 degrees (whichever occurs
first).
30.1.2 A156.19, Table I: Minimum opening and closing times.
30.1.3 A156.19, Table II: Total opening time to 90 degrees.
Back check at 60°
Back check at 70°
Back check at 80°
Table I plus 2 s
Table I plus 1.5 s
Table I plus 1 s
If door opens more than 90°, it shall continue at the same rate as backcheck speed.
Back check occurring at a point between positions shall use lowest setting.
30.1.4 Other door weights and widths
Closing time T = (D W )/188
D = Width of door in inches.
W = Weight of door in pounds.
T = Closing time to latch check in seconds.
SI (metric) units
Closing time T = (D W )/2260
D = Width of door in mm.
W = Weight of door in kg.
T = Closing time to latch check in seconds.
dormakaba ED900 Installation Instructions – Double egress door
Chapter 31
31.1 Upgrade cards
1
Upgrade card slot
2
Upgrade card
socket
Status LEDs
3
Green LED
4
Yellow LED
5
Red LED
6
Upgrade card
Fig. 31.1.1 Upgrade card slot
31.1.1 Upgrade card installation.
dormakaba upgrade cards can be used to expand the range of
functions of ED900 operators.
When upgrade cards are installed, information is exchanged
between and permanently allocated to both the operator control
unit and the upgrade card.
31.2 Container module
31.2.1 Container module
• The first upgrade card installed becomes
the container module.
• Every operator control unit has only one
container module.
• Functions of upgrade cards installed
after the first upgrade card are saved in
the container module.
31.2.2 Container module removal.
• If the container module is removed, all
previously enabled functions will be
deactivated after a certain time.
31.2.3 Operator control unit replacement.
• If the control unit is replaced, the
container module is removed from the
old control unit and inserted into the new
control unit.
• The new control unit synchronizes with
the container module and all upgrade
card functions are available.
31.2.4 Inserting an upgrade card that has
already been activated.
• Rapidly flashing yellow LED on upgrade
card indicates card is rejected.
• Card's functions in operator control unit
are still valid.
31.2.5 Inserted a container module from
third party control unit.
• Rapidly flashing yellow and green LEDs
on container module indicates module is
rejected.
• Container module can only be
synchronized with one control unit.
31.2.6 Container module defective.
• Upgrade cards that were installed after
the container module must be
reinstalled.
Upgrade card
Upgrade card color
Parameter
Fire protection
Red
F1
Barrier free toilet
F7
31.1.2 Upgrade cards
31 Upgrade cards
1
2
6
3
4
5
6
dormakaba ED900 Installation Instructions – Double egress door
Chapter 31
1. Insert first upgrade
card into upgrade
card slot.
2. This card will become
container module.
3. Yellow LED flashes
on and off once
during card insertion.
4. Green LED slowly
flashes on and off
indicating
communication
between card and
control module.
5. Upgrade card
becomes container
module, green LED
continues to slowly
flash on and off.
•
Upgrade card function
is now available.
31.3 Installing upgrade cards
31.3.2 Installing first upgrade card.
31.3.1 Set program switch to CLOSE.
1
Set program switch to Close.
9
Horizontal bars indicate
controller in stand by
mode.
1
Upgrade card slot
3
Green LED
7
Container module
TIPS AND RECOMMENDATIONS
Container module can be configured
using applicable parameter (F1 - F8) for
card. Reference Chapter 22, Parameters.
1. Remove container
module from upgrade
card slot.
6
1
2. Insert next upgrade
card into upgrade
card slot.
4
6
•
Card function is copied
to control module;
upgrade card is then
invalidated.
•
Yellow LED indicates
procedure is complete.
6
1
3. Remove upgrade card
from upgrade card
slot.
4. Reinsert container
module into upgrade
card slot.
•
Control unit recognizes
container module;
container module
stores new functions.
•
Green LED slowly
flashes on and off
indicating successful
operation.
•
New card functions
are now available.
31.3.3 Installing additional upgrade cards.
3
Green LED
7
Container module
TIPS AND RECOMMENDATIONS
New upgrade card can be configured
using applicable parameter (F1 - F8) for
card. Reference Chapter 22, Parameters.
1
Upgrade card slot
6
Next upgrade card
7
Container module
8
Program switch
9
2 digit display with
horizontal bars
8
1
2
4
Yellow LED
7
Container module
1
Upgrade card slot
2
First upgrade card
7
3
7
3
1
7
1
7
7
4
dormakaba ED900 Installation Instructions – Double egress door
Chapter 32
32 Maintenance
SAFETY INFORMATION
Low Energy Swinging
Doors
1. Activate the door. Door
should open at a slow
smooth pace (4 or more
seconds), and stop without
impact.
2. Door must remain fully open
for a minimum of 5 seconds
before beginning to close.
3. Door should close at a slow,
smooth pace (4 or more
seconds), and stop without
impact.
4. Inspect the floor area. It
should be clean with no
loose parts that might cause
user to trip or fall. Keep
traffic path clear.
5. Inspect door‘s overall
condition. The appropriate
signage should be present
and the hardware should
be in good condition.
6. Have door inspected by an
AAADM certified inspector
at least annually.
AAADM
American Association of Automatic
Door Manufacturers
ANNUAL COMPLIANCE
INSPECTION
INSPECT FOR AND
COMPLIES WITH ANSI
A156.19 ON:
DATE:______________
by AAADM Certified
Inspector
Number:___________
AAADM-3044
DO NOT USE DOOR if it fails
any of these safety checks of if
it malfunctions in any way. Call
a qualified automatic door
service company to have door
repaired or serviced.
See Owner’s manual or
instructions for details on
each of these and other
safety items. If you need
a copy of the manual,
contact the manufacturer.
These minimum safety checks,
in addition to those in the
Owner’s Manual, should be
made each day and after any
loss of electrical power.
Fig. 32.1.1
Safety
information
label
32.1 Safety label, low energy swing
doors
32.1.1 Low energy swinging door safety information
label
This AAADM label outlines safety checks that should be
performed daily on low energy swinging door controlled
by an ED900 operator.
32.1.2 Safety information label location
Place label in a protected, visible location on door frame,
near program switch panel if possible.
32.1.3 Annual compliance section of label
This section of label is only completed on low energy
swing doors that comply with ANSI/BHMA A156.19
standard and pass inspection by an AAADM certified
dormakaba USA, Inc. technician.
32.1.4 Additional annual compliance inspection labels
Place additional labels over annual compliance
inspection section of safety information label.
ANNUAL COMPLIANCE
INSPECTION
INSPECT FOR AND
COMPLIES WITH ANSI
A156.19 ON:
DATE: ______________
by AAADM Certified
Inspector
Number: ___________
Fig. 32.1.2 Annual
compliance
inspection label
dormakaba ED900 Installation Instructions – Double egress door
Chapter 32
32.2 ED900 environment and cleaning
32.2.1 ED900 environmental requirements.
ED900 assembly is designed to operate on an interior
application only under the specifications shown in
Table 32.2.1.
32.2.2 Areas around door(s) and door swing radius.
Areas around doors and door swing radius must be kept
clear of all obstacles.
32.2.3 Cleaning
WARNING
Cleaning of ED900 cover surfaces should be
done with program switches in Close position!
ED900 cover can be cleaned with a damp cloth and
commercial cleaning agents.
TIPS AND RECOMMENDATIONS
Abrasive (scouring) agents should not be used
as they may damage cover surface.
32.2.4 Water and other liquids.
WARNING
No water or other liquids must be sprayed or
spilled on ED900!
Table 32.2.1 Operator environmental requirements.
Fig. 32.2.1 ED900 low energy installation
32.3 Yellow LED, service level
Fig. 32.3.1 Service level indicator
32.3.1 Service level indicator
Yellow LED on operator power switch side is service level
indicator. Operator system should be scheduled for
service when yellow LED is first illuminated, or annually,
whichever comes first.
TIPS AND RECOMMENDATIONS
Reference Appendix A, Parameter detail, for
information on:
•
Parameter CS, reset service interval display.
•
Parameter CC, cycle counter.
Ambient temperature
5 to 122 °F
[-15 to 50⁰ C]
1
2
3
4
1
Red LED
2
Yellow LED
3
Green LED
4
Power switch
CAUTION
DOOR
AUTOMATIC
DD0586-010
ACTIVATE SWITCH
TO OPERATE
CAUTION
DOOR
AUTOMATIC
DD0586-01
ACTIVATE SWITCH
TO OPERATE
dormakaba ED900 Installation Instructions – Double egress door
Chapter 32
32.4 Pull arm maintenance
Fig. 32.4.1 Arm and track assembly
1
Track
2
Slide shoe
3
Pivot pin
6
Arm
Fig. 32.4.3 Track, slide shoe, pivot pin
7
7
7
End cap
2
3
6
1
32.4.1 Track mounting screws.
1. Set program switch to CLOSE.
2. Remove track end caps
3. Check tightness of track mounting
screws.
4. Replace end caps.
32.4.2 Track maintenance.
1. Set program switch to OPEN.
2. Track.
• Check for wear or damage.
3. Slide shoe and pivot pin.
• Check for wear or damage.
4. Bumper stop M6 screw.
• Check bumper stop position (bumper
location approximately 1/8" from slide
shoe)
• Check tightness of screw.
32.4.3 CPD lever.
1. Check tightness of M6 SHCS.
Fig. 32.4.5 Program switch
1
Track
2
Bumper stop
2.1
M6 FHMS
3
Bumper
4
Slide shoe, pivot pin
1
2
2.1
3
4
Fig. 32.4.2 Arm and track assembly
Fig. 32.4.4 CPD lever M6 socket head screw
3
M6 socket head
cap screw
5
3
5
CPD lever
dormakaba ED900 Installation Instructions – Double egress door
Chapter 32
Fig. 32.5.1 Arm M8 SHCS cap
8
Cap
Fig. 32.5.2 M8 SHCS
8
5
32.5 Arm fasteners – torque requirements
32.5.1 Check drive arm M8 SHCS torque.
1. Set program switch to CLOSE.
2. Remove cap over M8 SHCS.
3. Check torque.
4. Replace cap.
CAUTION
Using torque wrench with 5 mm
hex key socket, check M8 SHCS
torque.17 ft-lb [23 Nm].
32.5.2 Check pivot pin M8 socket head
torque.
1. Check torque.
CAUTION
Use torque wrench with hex key
socket. M8 screw torque:
5.9 - 7.4 ft-lb [8 - 10 Nm].
Fig. 32.5.3 Pivot pin M8 socket head
3
Pivot pin M8
socket head
3
5
M8 x __ SHCS
dormakaba ED900 Installation Instructions – Double egress door
Chapter 32
32.6 Push arm maintenance
1
Drive arm
2
Adjustment arm
3
Adjustment arm
tube
32.6.1 Push arm maintenance.
WARNING
Set program switch to CLOSE
before performing maintenance!
1. Adjustment arm.
• Check for wear or damage.
• Check tightness of M6 x 10 flanged
button head screws (Fig. 32.6.2).
2. Shoe and adjustment arm assembly:
• Check for wear or damage at shoe
bearing (Fig. 32.6.3).
3. Adjustment arm socket and ball head
(Fig. 32.6.4).
• Check for wear or damage.
27.6.2 Shoe door mounting screws .
1. Remove screw cover caps (Fig. 32.6.1).
2. Check for tightness of mounting screws
(Fig. 32.6.3).
3. Replace screw cover caps.
27.6.3 Drive arm to ED50 spindle.
1. Remove spindle cap.
2. Check tightness of M8 SHCS.
CAUTION
Using torque wrench with 5 mm
hex key socket, torque M8 SHCS to
17 ft-lb [23 Nm].
Fig. 32.6.1 Push arm assembly
Fig. 32.6.4 Arm socket and ball head
10
4
M6 x 10 button
head screws
5
Drive arm socket
7
2
9
4
Fig. 32.6.3 Shoe bearing
2
Adjustment arm
3
Adjustment arm
tube
4
M6 x 10 mm flanged
button head screw
7
Shoe
9
Articulated
bearing
11
M8 SHCS
6
Adjustment arm
ball head
7
Shoe
8
Shoe mounting
screws (2)
5
6
5
Socket
6
Ball head
Fig. 32.6.5 Spindle M8 SHCS
1
6
5
8
8
7
3
2
4
Fig. 32.6.2 Push arm assembly hardware
11
10
Screw cover caps
dormakaba ED900 Installation Instructions – Double egress door
Chapter 32
32.7 ED900 brake maintenance
Fig. 32.7.1
ED900 operator
Fig. 32.7.3 Brake assembly
1
Brake assembly
2
Brake disc
assembly
3
M3 x 3 set screw
4
Brake motor
flange
6
M3 x 5 SHCS
1
Brake assembly
32.7.1 Adjustment of air gap:
brake to brake disc (Fig. 32.7.2).
TIPS AND RECOMMENDATIONS
Reference drawing:
254197-01-50
WARNING
Set program switch to CLOSE
before performing maintenance!
CAUTION
Air gap setting between brake and
brake disc:
0.1 mm to 0.3 mm
(0.004" to 0.012")
1. Using 2.5 mm hex key, loosen three
M3 x 3 set screws securing brake disc to
motor shaft.
2. Insert feeler gauge [air gap setting for
sizing] between brake disc and brake.
3. Move brake disc against shim(s).
4. Screw M3 x 3 set screws against motor
shaft but do not tighten.
5. Remove feeler gauge.
6. Tighten M3 x 3 set screws.
CAUTION
M3 x3 SHCS torque setting:
5.3 in-lb + 0.9 in-lb [0.6 Nm +0.1 Nm].
TIPS AND RECOMMENDATIONS
Paper stock thickness:
approximately 0.003"
1
2
3
4
6
6
3
Y
Y
Air gap
3
2
1
Fig. 32.7.2 Brake to brake disc air gap
1
Brake assembly
2
Brake disc
assembly
Fig. 32.7.4 Feeler gauge set
3
M3 x 3 SHCS
1
dormakaba ED900 Installation Instructions – Double egress door
Chapter 32
Fig. 32.7.7 Brake and brake disc assemblies
Fig. 32.7.6 Brake disc assembly removed
from brake
2
5
1
1
Brake assembly
2
Brake disc
assembly
5
Motor shaft
1
2
6
6
Fig. 32.7.5 M3 x 5 SHCS
1
Brake assembly
2
Brake disc
assembly
6
M3 x 5 SHCS
32.7.2 Torque setting of M3 x 5 SHCS.
• 5.3 in-lb + 0.9 in-lb [0.6 Nm +0.1 Nm]
2
6
6
1
1
Brake assembly
2
Brake disc
assembly
6
M3 x 5 SHCS
Fig. 32.7.8 Brake coil wiring
43 3 64 63 62 1G 3
1G
Red
3
Blk
dormakaba ED900 Installation Instructions – Double egress door
Appendix A
A.1
Driving parameters detail
Parameter
Value
range
Units
Factory
setting
Description
Opening speed, automatic mode
1. Opening speed refers to automatic mode. Speed can be adjusted using this parameter.
2. Internal monitoring system checks if parameter setting is admissible If setting exceeds
value, the setting is alternately displayed with the permissible value.
3. After parameter set, verify setting meets ANSI/BHMA standard A156.19 (low energy)
See Chapter 30.
5
ED900
8 - 27
°/s
25
Closing speed, automatic mode
1. Closing speed refers to automatic mode. Speed can be adjusted using this parameter.
2. Internal monitoring system checks if parameter setting is admissible. If setting exceeds
admissible value, the setting is alternately displayed with the permissible value.
3. After parameter set, verify setting meets ANSI/BHMA standard A156.19 (low energy)
See Chapter 30.
*ED900: maximum closing speed 27⁰/s in low energy mode.
6
ED900
2 - 27*
°/s
25
Hold open time, automatic mode
1. Hold open time starts once all internal, external, safety and push and go inputs have
been opened or dropped, and door is in an open position.
2. Hold open time values from 5 to 30 s are set in increments of 1 second.
3. In low energy mode, a minimum hold open time of 5 seconds is required.
4. Hold open time can be re-triggered.
7
0 - 30
s
5
Night-bank hold open time
1. Night-bank (key switch) hold open time is set using this parameter.
2. Night-bank Hold open time starts once contact on night-bank activator input is
opened and door is in an open position.
3. Night-bank hold open time can be re-triggered.
8
0 - 30
s
10
Hold open time, manual opening
1. Default hold open time of 1 second that follows every manual opening of door can be
adjusted using parameter do.
2. Hold open time starts when door is released.
9
0 - 30
s
1
Wall masking on door hinge side
1. Wall masking required if door opens against an obstacle.
2. When door reaches set wall masking angle, system will ignore signal from safety
sensor on door swing (hinge) side.
3. The wider the detection range of safety sensor used, the greater the area must be in
which system has to ignore sensor's emitted signal. To insure personnel safety, it is
advised to keep this range as small as possible.
4. If set wall masking angle is exceeded when door is being opened, a rapidly flashing dot
appears in top left hand corner of 2 digit display.
5. Rapidly flashing dot disappears when door angle drops below set wall masking angle.
10
60 - 99
°
80
A.1.1 Driving parameters detail.
Appendix A – Driving parameters – detail
dormakaba ED900 Installation Instructions – Double egress door
Appendix A
Parameter
Value
range
Units
Factory
setting
Description
Safety sensor test
11
0 - 8
0
Safety sensor parameter ST must be set to sensors used and if they are active-high
or active-low. See E 04 safety sensor test error, Appendix B.
0
Sensor test off.
1
Sensor test on swing (hinge) side. Active-high
2
Sensor test on swing and approach sides. Active-high
3
Sensor test on swing and approach sides. Active-high
4
Sensor test on swing side. Active-low
ST
5
Sensor test on approach side. Active-low
6
Sensor test on swing and approach sides. Active-low
7
Wall mounted sensor with data line. Lock monitoring not available.
8
Sensor test overhead sensor type Bodyguard III or Premier T with monitoring input.
Activation by safety sensor on approach
(opposite hinge) side
12
0 - 1
0
0
Safety sensor's input is disregarded as soon as door is closed.
1
Safety sensor can trigger an opening pulse while door is closed.
Suppression of safety sensor on swing
(hinge) side during initialization drive
13
0 - 1
0
0
Safety sensor on swing side is active during an initialization drive after a power on
reset.
1
1. With SP set to 1, operator will disregard swing side safety sensor during
initialization drive. After a power on reset, operator starts an initialization drive
at slow speed. The initialization drive cannot be completed if safety sensor on
hinge side is, or has been triggered.
Delayed opening time for locking
mechanism
1. Delayed opening time delay starts as soon as door opening pulse has been generated.
2. Door opens on expiration of time delay.
3. If parameter is set to "0" and input for locking feedback contact is closed, door will not
perform a preload Pu before door unlocks.
4. Since various motor locks do not have feedback contacts, a delay of up to 4 seconds is
possible
14
0 - 40
* 100
ms
3
*100
A.1.1 Driving parameters detail.