Daikin ALTHERMA User Reference Manual
Read Online
Read the Daikin ALTHERMA User Reference Manual online using the built-in PDF viewer.
Text of the manual
User reference guide
Daikin Altherma – Low temperature split
English
User reference guide
Daikin Altherma – Low temperature split
EABH16DA6V
EABH16DA9W
EABX16DA6V
EABX16DA9W
EAVH16S18DA6V(G)
EAVH16S23DA6V(G)
EAVH16S18DA9W(G)
EAVH16S23DA9W(G)
EAVX16S18DA6V(G)
EAVX16S23DA6V(G)
EAVX16S18DA9W(G)
EAVX16S23DA9W(G)
Table of contents
User reference guide
2
EABH/X16DA+9W + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556071-1 – 2018.10
Table of contents
1
General safety precautions
2
1.1
About the documentation ..........................................................
2
1.1.1
Meaning of warnings and symbols..............................
2
1.2
For the user ...............................................................................
2
2
About this document
3
3
About the system
3
3.1
Components in a typical system layout.....................................
4
4
Operation
4
4.1
User interface: Overview ...........................................................
4
4.2
Possible screens: Overview ......................................................
4
4.2.1
Home screen...............................................................
5
4.2.2
Main menu screen ......................................................
5
4.2.3
Setpoint screen...........................................................
6
4.2.4
Detailed screen with values ........................................
6
4.3
Basic usage...............................................................................
6
4.3.1
Using the home screen...............................................
6
4.3.2
Using the menu structure............................................
6
4.3.3
Turning operation ON or OFF.....................................
6
4.4
Space heating/cooling control ...................................................
7
4.4.1
About space heating/cooling control...........................
7
4.4.2
Setting the space operation mode ..............................
7
4.4.3
Determining which temperature control you are using
7
4.4.4
To change the desired room temperature...................
8
4.4.5
To change the desired leaving water temperature......
8
4.5
Domestic hot water control........................................................
8
4.5.1
About domestic hot water control................................
8
4.5.2
Reheat mode ..............................................................
8
4.5.3
Scheduled mode.........................................................
9
4.5.4
Scheduled + reheat mode...........................................
9
4.5.5
To change the domestic hot water temperature .........
9
4.5.6
Using DHW powerful operation...................................
9
4.6
Advanced usage........................................................................
9
4.6.1
Using quiet mode........................................................
10
4.6.2
Using holiday mode ....................................................
10
4.6.3
Reading out information..............................................
10
4.6.4
To configure time and date .........................................
11
4.7
Preset values and schedules ....................................................
11
4.7.1
Using preset values ....................................................
11
4.7.2
Setting the energy prices ............................................
11
4.7.3
Using and programming schedules ............................
12
4.7.4
Schedule screen: Example .........................................
12
4.8
Weather dependent operation...................................................
14
4.8.1
Detailed screen with weather-dependent curve..........
14
4.9
Menu structure: Overview user settings ....................................
15
4.10
Installer settings: Tables to be filled in by installer ....................
16
4.10.1
Configuration wizard ...................................................
16
4.10.2
Settings menu.............................................................
16
5
Energy saving tips
16
6
Maintenance and service
16
6.1
Overview: Maintenance and service .........................................
16
6.2
To find the contact/helpdesk number ........................................
17
7
Troubleshooting
17
7.1
To display the help text in case of a malfunction.......................
17
7.2
To check the malfunction history...............................................
17
7.3
Symptom: You are feeling too cold (hot) in your living room.....
17
7.4
Symptom: The water at the tap is too cold................................
17
7.5
Symptom: Heat pump failure.....................................................
17
7.6
Symptom: The system is making gurgling noises after
commissioning...........................................................................
18
8
Relocation
18
8.1
Overview: Relocation ................................................................. 18
9
Disposal
18
10 Glossary
18
1
General safety precautions
1.1
About the documentation
▪The original documentation is written in English. All other
languages are translations.
▪The precautions described in this document cover very important
topics, follow them carefully.
▪The installation of the system, and all activities described in the
installation manual and the installer reference guide MUST be
performed by an authorised installer.
1.1.1
Meaning of warnings and symbols
DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING
Indicates a situation that could result in burning because of
extreme hot or cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious
injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate
injury.
NOTICE
Indicates a situation that could result in equipment or
property damage.
INFORMATION
Indicates useful tips or additional information.
Symbol
Explanation
Before installation, read the installation and
operation manual, and the wiring instruction sheet.
Before performing maintenance and service tasks,
read the service manual.
For more information, see the installer and user
reference guide.
1.2
For the user
▪If you are NOT sure how to operate the unit, contact your installer.
▪This appliance can be used by children aged from 8 years and
above and persons with reduced physical, sensory or mental
capabilities or lack of experience and knowledge if they have been
2 About this document
User reference guide
3
EABH/X16DA+9W + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556071-1 – 2018.10
given supervision or instruction concerning use of the appliance in
a safe way and understand the hazards involved. Children shall
NOT play with the appliance. Cleaning and user maintenance
shall NOT be made by children without supervision.
WARNING
To prevent electric shocks or fire:
▪Do NOT rinse the unit.
▪Do NOT operate the unit with wet hands.
▪Do NOT place any objects containing water on the unit.
NOTICE
▪Do NOT place any objects or equipment on top of the
unit.
▪Do NOT sit, climb or stand on the unit.
▪Units are marked with the following symbol:
This means that electrical and electronic products may NOT be
mixed with unsorted household waste. Do NOT try to dismantle
the system yourself: the dismantling of the system, treatment of
the refrigerant, of oil and of other parts must be done by an
authorized installer and must comply with applicable legislation.
Units must be treated at a specialized treatment facility for reuse,
recycling and recovery. By ensuring this product is disposed of
correctly, you will help to prevent potential negative consequences
for the environment and human health. For more information,
contact your installer or local authority.
▪Batteries are marked with the following symbol:
This means that the batteries may NOT be mixed with unsorted
household waste. If a chemical symbol is printed beneath the
symbol, this chemical symbol means that the battery contains a
heavy metal above a certain concentration.
Possible chemical symbols are: Pb: lead (>0.004%).
Waste batteries must be treated at a specialized treatment facility
for reuse. By ensuring waste batteries are disposed of correctly,
you will help to prevent potential negative consequences for the
environment and human health.
2
About this document
Thank you for purchasing this product. Please:
▪Read the documentation carefully before operating the user
interface to ensure the best possible performance.
▪Request the installer to inform you about the settings that he used
to configure your system. Check if he has filled in the installer
settings tables. If not, request him to do so.
▪Keep the documentation for future reference.
Target audience
End users
Documentation set
This document is part of a documentation set. The complete set
consists of:
▪General safety precautions:
▪Safety instructions that you must read before operating your
system
▪Format: Paper (in the box of the indoor unit)
▪Operation manual:
▪Quick guide for basic usage
▪Format: Paper (in the box of the indoor unit)
▪User reference guide:
▪Detailed step-by-step instructions and background information
for basic and advanced usage
▪Format: Digital files on http://www.daikineurope.com/support-
and-manuals/product-information/
Latest revisions of the supplied documentation may be available on
the regional Daikin website or via your installer.
The original documentation is written in English. All other languages
are translations.
Breadcrumbs
Breadcrumbs (example: [4.3]) help you to locate where you are in
the menu structure of the user interface.
1
To enable the breadcrumbs: In the home screen or
main menu screen, press the help button. The
breadcrumbs will appear in the top left corner of the
screen.
2
To disable the breadcrumbs: Press the help button
again.
This document also mentions these breadcrumbs. Example:
1
Go to [4.3]: Space heating/cooling > Operation
range.
This means:
1
Starting from the home screen, turn the left dial and
go to Space heating/cooling.
4
Space heating/cooling
2
Press the left dial to enter the submenu.
3
Turn the left dial and go to Operation range.
Operation range
4.3
4
Press the left dial to enter the submenu.
3
About the system
Depending on the system layout, the system can:
▪Heat up a space
▪Cool down a space (if a heating/cooling heat pump model is
installed)
▪Produce domestic hot water (if a DHW tank is installed)
User reference guide
4
EABH/X16DA+9W + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556071-1 – 2018.10
3.1
Components in a typical system
layout
d
a
b
c
e
f
g
B
C
A
A
Main zone. Example: Living room.
B
Additional zone. Example: Bedroom.
C
Technical room. Example: Garage.
a
Outdoor unit heat pump
b
Indoor unit heat pump
c
Domestic hot water (DHW) tank
d
User interface at the indoor unit
e
User interface used as room thermostat
f
Underfloor heating
g
Radiators, heat pump convectors, or fan coil units
INFORMATION
The indoor unit and the domestic hot water tank (if
installed) can be separated or integrated depending on the
indoor unit type.
4
Operation
4.1
User interface: Overview
The user interface has the following components:
b
c
a
a
b
c
a
Status indicator
b
LCD screen
c
Dials and buttons
Status indicator
The LEDs of the status indicator light up or blink to show the
operating mode of the unit.
LED
Mode
Description
Blinking blue
Standby
The unit is not in operation.
Continuous blue Operation
The unit is in operation.
Blinking red
Malfunction
A malfunction occurred.
See "7.1 To display the help text
in case of a malfunction" on
page 17 for more information.
LCD screen
The LCD screen has a sleeping function. After a certain time of non-
interaction with the user interface, the screen darkens. Pressing any
button or rotating any dial awakens the display. The time of non-
interaction differs depending on the user permission level:
▪User or Advanced user: 15 min
▪Installer: 1 h
Dials and buttons
You use the dials and buttons:
▪To navigate through the screens, menus and settings of the LCD
screen
▪To set values
a
b
c
d
e
Item
Description
a
Left dial
The LCD shows an arc on the left side of the
display when you can use the left dial.
▪
: Turn, then press the left dial. Navigate
through the menu structure.
▪
: Turn the left dial. Choose a menu item.
▪
: Press the left dial. Confirm your choice
or go to a submenu.
b
Back button
: Press to go back 1 step in the menu structure.
c
Home
button
: Press to go back to the home screen.
d
Help button
: Press to show a help text related to the current
page (if available).
e
Right dial
The LCD shows an arc on the right side of the
display when you can use the right dial.
▪
: Turn, then press the right dial. Change
a value or setting, shown at the right side of the
screen.
▪
: Turn the right dial. Navigate through
the possible values and settings.
▪
: Press the right dial. Confirm your
choice and go to the next menu item.
4.2
Possible screens: Overview
The most common screens are as follows:
User reference guide
5
EABH/X16DA+9W + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556071-1 – 2018.10
+
–
a
b
c
c2
c1
a
Home screen
b
Main menu screen
c
Lower level screens:
c1: Setpoint screen
c2: Detailed screen with values
4.2.1
Home screen
Press the
button to go back to the home screen. You see an
overview of the unit configuration and the room and setpoint
temperatures. Only symbols applicable for your configuration are
visible on the home screen.
6
1.6
bar
18 Feb 2018
22:19
55
18
21
45
f
i
j
h
g
e
d
a
b
c
Possible actions on this screen
Go through the list of the main menu.
Go to the main menu screen.
Enable/disable breadcrumbs.
Item
Description
21 21
The temperatures are shown in circles. If the circle
is grey, the corresponding operation (example:
space heating) is currently not active.
Outdoor
unit
a2 a3
a1
a1
: Outdoor unit
a2
: Quiet mode active
a3 Measured ambient temperature
Indoor unit /
domestic
hot water
tank
b1
b2
b1 Indoor unit:
▪
:
Floor-standing
indoor
unit
with
integrated tank
▪
: Wall-mounted indoor unit with separated
tank
▪
: Wall-mounted indoor unit
b2 Water pressure
Item
Description
Space
operation
mode
c
▪
: Cooling
▪
: Heating
Disinfection
/ Powerful
d
▪
: Disinfection mode active
▪
: Powerful operation active
Date / time
e
Current date and time
Holiday
f
: Holiday mode active
Main zone
g3
g1
g4
g2
g1 Heat emitter type:
▪
: Underfloor heating
▪
: Fancoil unit
▪
: Radiator
g2 Leaving water temperature setpoint
g3 Room thermostat type:
▪
: Daikin user interface used as room
thermostat
▪
: External control
▪Hidden: Leaving water temperature control
g4 Measured room temperature
Additional
zone
h3
h1 h2
h1 Heat emitter type:
▪
: Underfloor heating
▪
: Fancoil unit
▪
: Radiator
h2 Leaving water temperature setpoint
h3 Room thermostat type:
▪
: External control
▪Hidden: Leaving water temperature control
Domestic
hot water
i1
i2
i1
: Domestic hot water
i2 Measured tank temperature
Malfunction
j
or
: A malfunction occurred
See "7.1 To display the help text in case of a
malfunction" on page 17 for more information.
4.2.2
Main menu screen
In the home screen, press
to open the main menu screen.
From the main menu, you can access the different setpoint screens
and submenus.
Possible actions on this screen
Go through the list.
Enter the submenu.
Enable/disable breadcrumbs.
Item
Description
or
Malfunctioning
Restriction: Only displayed if a malfunction
occurs.
See "7.1 To display the help text in case of
a malfunction" on page 17 for more
information.
User reference guide
6
EABH/X16DA+9W + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556071-1 – 2018.10
Item
Description
Room
Restriction: Only displayed if a room
thermostat is connected to the indoor unit.
Set the room temperature.
Main zone
Shows the applicable symbol for your main
zone emitter type.
Set the leaving water temperature for the
main zone.
Additional zone
Restriction: Only displayed if there are two
leaving water temperature zones. Shows
the applicable symbol for your additional
zone emitter type.
Set the leaving water temperature for the
additional zone (if present).
Space heating/
cooling
Shows the applicable symbol for your unit.
Put the unit in heating mode or cooling
mode. You cannot change the mode on
heating only models.
Tank
Restriction: Only displayed if a domestic
hot water tank is present.
Set the domestic hot water tank
temperature.
User settings
Gives access to user settings such as
holiday mode and quiet mode.
Information
Displays data and information about the
indoor unit.
Installer settings
Restriction: Only for the installer.
Gives access to advanced settings.
Commissioning
Restriction: Only for the installer.
Perform tests and maintenance.
User profile
Change the active user profile.
Operation
Turn heating/cooling functionality and
domestic hot water preparation on or off.
4.2.3
Setpoint screen
The setpoint screen is displayed for screens describing system
components that need a setpoint value.
Example:
▪Room temperature screen
▪Main zone screen
▪Additional zone screen
▪Tank temperature screen
a1
d
+
–
d
e
d
e
c
a2
b1
b2
Possible actions on this screen
Go through the list of the submenu.
Go to the submenu.
Adjust and automatically apply the desired
temperature.
Item
Description
Minimum temperature limit
a1
Fixed by the unit
a2
Restricted by the installer
Item
Description
Maximum temperature limit
b1
Fixed by the unit
b2
Restricted by the installer
Current temperature
c
Measured by the unit
Desired temperature
d
Turn the right dial to
increase/decrease.
Submenu
e
Turn or press the left dial to
go to the submenu.
4.2.4
Detailed screen with values
a
b
a
Settings
b
Values
Possible actions on this screen
Go through the list of settings.
Change the value.
Go to the next setting.
Confirm changes and proceed.
4.3
Basic usage
4.3.1
Using the home screen
About the home screen
On the home screen, you can read out the most important settings
that are meant for daily usage. The setup of the unit is displayed in a
schematic way. See "4.2.1 Home screen" on page 5 for more
information.
To go to the home screen
Press the
button to return to the home screen.
4.3.2
Using the menu structure
About the menu structure
Go to the menu structure to change the settings of the unit and read
out values such as the current temperature. For an overview of the
settings available to the user, see "4.9 Menu structure: Overview
user settings" on page 15.
To go to the menu structure
Press
to go to the menu structure.
4.3.3
Turning operation ON or OFF
Certain functionalities of the unit can be enabled of disabled
separately. If a functionality is disabled, the corresponding
temperature icon in the home screen will be greyed out.
To turn room temperature control ON or OFF
1
Go to [C.1]: Operation > Room.
2
Set operation to On or Off.
To turn space heating/cooling operation ON or OFF
1
Go to [C.2]: Operation > Space heating/cooling.
2
Set operation to On or Off.
To turn tank heating operation ON or OFF
User reference guide
7
EABH/X16DA+9W + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556071-1 – 2018.10
1
Go to [C.3]: Operation > Tank.
2
Set operation to On or Off.
4.4
Space heating/cooling control
4.4.1
About space heating/cooling control
Controlling space heating/cooling typically consists of the following
stages:
1
Setting the space operation mode
2
Controlling the temperature
Depending on the system layout and installer configuration, you use
a different temperature control:
▪Room thermostat control (linked or NOT linked to leaving water
temperature)
▪Leaving water temperature control
▪External room thermostat control
4.4.2
Setting the space operation mode
About space operation modes
Depending on your heat pump model, you have to tell the system
which space operation mode to use: heating or cooling.
If a … heat pump
model is installed
Then…
Heating/cooling
The system can heat up and cool down a
space. You have to tell the system which
space operation mode to use.
Heating only
The system can heat up a space, but
NOT cool down a space. You do NOT
have to tell the system which space
operation mode to use.
To determine if a heating/cooling heat pump model is installed
1
Go to [4]: Space heating/cooling.
2
Check if [4.1] Operation mode is listed and editable.
If so, a heating/cooling heat pump model is installed.
To tell the system which space operation to use, you can:
You can…
Location
Check which space operation mode is
currently used.
Home screen
Set the space operation mode permanently. Main menu
Restrict automatic changeover according
to a monthly schedule.
To check which space operation mode is currently used
The space operation mode is displayed on the home screen:
▪When the unit is in heating mode, the
icon is shown.
▪When the unit is in cooling mode, the
icon is shown.
The status indicator shows if the unit is currently in operation:
▪When the unit is not in operation, the status indicator will show a
blue pulsation with an interval of approximately 5 seconds.
▪While the unit is in operation, the status indicator will light up blue
constantly.
To set the space operation mode
1
Go to [4.1]: Space heating/cooling > Operation mode
2
Select one of the following options:
▪Heating: Always heating mode
▪Cooling: Always cooling mode
▪Automatic:
The
operation
mode
changes
automatically based on the outdoor temperature.
Restricted according to the operation mode
schedule.
Automatic heating/cooling changeover is is NOT applicable for
heating only models. When Automatic is selected, the changing of
the operation mode is based on the Operation mode schedule [4.2].
To restrict automatic changeover according to a schedule
Conditions: You set the space operation mode to Automatic.
1
Go to [4.2]: Space heating/cooling > Operation mode
schedule.
2
Select a month.
3
For each month, select an option:
▪Reversible: Not restricted
▪Heating only: Restricted
▪Cooling only: Restricted
4
Confirm the changes.
Example: Changeover restrictions
When
Restriction
During cold season.
Example: October, November,
December, January, February and March.
Heating only
During warm season.
Example: June, July and August.
Cooling only
In-between.
Example: April, May and September.
Heating/Cooling
If both the Operation mode and the Operation mode schedule are
set to Automatic, the operation mode will be determined by the
outdoor temperature.
4.4.3
Determining which temperature control
you are using
To determine which temperature control you are
using (method 1)
Check the installer settings table filled in by the installer.
To determine which temperature control you are
using (method 2)
You can see on the home screen which temperature control you are
using.
6
1.6
bar
18 Feb 2018
22:19
55
18
21
45
a2
a1
b
a1
Heat emitter of the main zone
a2
Heat emitter of the additional zone (if any)
b
Room thermostat type of the main zone
To determine the number of temperature zones
Check the number of heat emitters displayed on the home screen:
If…
Then…
One heat emitter symbol is displayed
There is only one zone.
User reference guide
8
EABH/X16DA+9W + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556071-1 – 2018.10
If…
Then…
Two heat emitter symbols are displayed
There are two zones.
To determine the control type
Check the room thermostat type of the main zone:
If…
Then the main zone temperature control is…
Room thermostat control
External room thermostat control
No icon
Leaving water temperature control
4.4.4
To change the desired room temperature
During room temperature control, you can use the room temperature
setpoint screen to read out and adjust the desired room temperature.
1
Go to [1]: Room.
You can read out the desired and actual room
temperature in the center of the setpoint screen.
2
Adjust the desired room temperature.
If scheduling is on after changing the desired room temperature
▪The temperature will stay the same as long as there is no
scheduled action.
▪The desired room temperature will return to its scheduled value
whenever a scheduled action occurs.
You can avoid scheduled behaviour by (temporarily) turning off
scheduling.
To turn off room temperature scheduling
1
Go to [1.1]: Room > Schedule.
2
Select No.
4.4.5
To change the desired leaving water
temperature
INFORMATION
The leaving water is the water that is sent to the heat
emitters. The desired leaving water temperature is set by
your installer in accordance with the heat emitter type.
Only adjust the leaving water temperature settings in case
of problems.
You can use the leaving water temperature setpoint screen to read
out and adjust the desired leaving water temperature.
1
Go to [2]: Main zone or [3]: Additional zone.
You can read out the desired and actual leaving
water temperature in the center of the setpoint
screen.
2
Adjust the desired leaving water temperature.
If scheduling is on after changing the desired leaving water
temperature
▪The temperature will stay the same as long as there is no
scheduled action.
▪The desired leaving water temperature will return to its scheduled
value whenever a scheduled action occurs.
You can avoid scheduled behaviour by (temporarily) turning off
scheduling.
To turn off leaving water temperature scheduling
1
Go to one of the following:
▪[2.1]: Main zone > Schedule
▪[3.1]: Additional zone > Schedule
2
Select No.
To enable weather dependent operation for the leaving water
temperature
See "4.8 Weather dependent operation" on page 14.
4.5
Domestic hot water control
4.5.1
About domestic hot water control
Depending on the DHW tank mode (installer setting), you use a
different domestic hot water control:
▪Reheat only
▪Schedule + reheat
▪Schedule only
CAUTION
The booster heater permission schedule is used to restrict
or allow booster heater operation based on a weekly
program.
Advice:
In
order
to
avoid
unsuccessful
disinfection function, at least allow the booster heater (by
the weekly program) for minimum 4 hours starting from the
scheduled start-up of disinfection. If the booster heater is
restricted during disinfection, this function will NOT be
successful and the applicable warning AH will be
generated.
INFORMATION
In case of error code AH and no interruption of the
disinfection function occurred due to domestic hot water
tapping, following actions are recommended:
▪When the Reheat only or Schedule + reheat mode is
selected, it is recommended to program the start-up of
the disinfection function at least 4 hours later than the
last expected large hot water tapping. This start-up can
be set by installer settings (disinfection function).
▪When the Schedule only mode is selected, it is
recommended to program a Eco action 3 hours before
the scheduled start-up of the disinfection function to
preheat the tank.
To determine which domestic hot water mode you are using
(method 1)
Check the installer settings table filled in by the installer.
To determine which domestic hot water mode you are using
(method 2)
1
Go to [5]: Tank.
2
Check which items are displayed:
If… is displayed
Then the DHW tank mode =…
Only [5.1] Powerful
operation
Reheat only
All items except [5.4]
Reheat setpoint are
displayed
Schedule only
All items including [5.4]
Reheat setpoint are
displayed
Schedule + reheat
4.5.2
Reheat mode
In reheat mode the DHW tank continuously heats up to the
temperature shown on the home screen (example: 50°C).
User reference guide
9
EABH/X16DA+9W + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556071-1 – 2018.10
t
60°C
00:00
07:00
50°C
15°C
40°C
14:00
21:00
1
2
3
4
Tt
Tt
DHW tank temperature
t
Time
INFORMATION
Risk of space heating capacity shortage for domestic hot
water tank without internal booster heater: In case of
frequent domestic hot water operation, frequent and long
space heating/cooling interruption will happen when
selecting the following:
Tank > Heat up mode > Reheat only.
INFORMATION
When the DHW tank mode is reheat, the risk for capacity
shortage and comfort problem is significant. In case of
frequent reheat operation, space heating/cooling function
is regularly interrupted.
4.5.3
Scheduled mode
In scheduled mode the DHW tank produces hot water corresponding
to a schedule. The best time to allow the tank to produce hot water is
at night, because the space heating demand is lower.
Example:
t
60°C
00:00
07:00
50°C
15°C
40°C
14:00
21:00
1
2
3
4
5
Tt
Tt
DHW tank temperature
t
Time
▪Initially, the DHW tank temperature is the same as the
temperature of the domestic water entering the DHW tank
(example: 15°C).
▪At 00:00 the DHW tank is programmed to heat up the water to a
preset value (example: Comfort = 60°C).
▪During the morning, you consume hot water and the DHW tank
temperature decreases.
▪At 14:00 the DHW tank is programmed to heat up the water to a
preset value (example: Eco = 50°C). Hot water is available again.
▪During the afternoon and evening, you consume hot water again
and the DHW tank temperature decreases again.
▪At 00:00 the next day, the cycle repeats.
4.5.4
Scheduled + reheat mode
In scheduled + reheat mode, the domestic hot water control is the
same as in scheduled mode. However, when the DHW tank
temperature drops below a preset value (=reheat tank temperature –
hysteresis value; example: 35°C), the DHW tank heats up until it
reaches the reheat set point (example: 45°C). This ensures that a
minimum amount of hot water is available at all times.
Example:
t
Tt
60°C
00:00
07:00
50°C
45°C
15°C
14:00
21:00
35°C
1
2
4
5
3
Tt
DHW tank temperature
t
Time
4.5.5
To change the domestic hot water
temperature
In Reheat only mode, you can use the room temperature setpoint
screen to read out and adjust the domestic hot water temperature.
1
Go to [5]: Tank.
You can read out the desired and actual room
temperature in the center of the setpoint screen.
2
Turn the right dial to adjust the domestic hot water
temperature.
In other modes, you can only view the setpoint screen but not modify
it. Instead, you can modify the settings for the Comfort setpoint [5.2],
Eco setpoint [5.3] and Reheat setpoint [5.4].
4.5.6
Using DHW powerful operation
About powerful operation
Powerful operation allows the domestic hot water to be heated by
the backup heater or booster heater. Use this mode on days when
there is more hot water usage than usual.
To check if powerful operation is active
If
is displayed on the home screen, powerful operation is active.
Activate or deactivate Powerful operation as follows:
1
Go to [5.1]: Tank > Powerful operation
2
Turn powerful operation Off or On.
Usage example: You immediately need more hot water
You are in the following situation:
▪You already consumed most of your domestic hot water.
▪You cannot wait for the next scheduled action to heat up the
domestic hot water tank.
Then you can activate powerful operation. The domestic hot water
tank will start heating up the water to the Comfort temperature.
INFORMATION
When powerful operation is active, the risk of space
heating/cooling and capacity shortage comfort problems is
significant. In case of frequent domestic hot water
operation, frequent and long space heating/cooling
interruptions will happen.
4.6
Advanced usage
The amount of information you can read out in the menu structure
depends on your user permission level:
▪User: Standard mode
▪Advanced user: You can read out more information
To change the user permission level
You can change the user permission level as follows:
User reference guide
10
EABH/X16DA+9W + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556071-1 – 2018.10
1
Go to [B]: User profile.
2
Enter the applicable code for the user permission.
—
▪Move the cursor from left to right.
▪Browse through the list of digits and change the
selected digit.
▪Confirm the pincode and proceed.
Advanced user pin code
The Advanced user pin code is 1234. Additional menu items for the
user are now visible.
User pin code
The User pin code is 0000.
4.6.1
Using quiet mode
About quiet mode
You can use quiet mode to decrease the sound of the outdoor unit.
However, this also decreases the heating/cooling capacity of the
system. There are multiple quiet mode levels.
You can:
▪Completely deactivate quiet mode
▪Manually activate a quiet mode level until the next scheduled
action
▪Use and program a quiet mode schedule
INFORMATION
If the outdoor temperature is below zero, we recommend to
NOT use the most quiet level.
To check if quiet mode is active
If
is displayed on the home screen, quiet mode is active.
To use quiet mode
1
Go to [7.4.1]: User settings > Quiet > Activation.
2
Do one of the following:
—
If you want to…
Then…
Completely deactivate
quiet mode
Select Off.
Manually activate a quiet
mode level
Select the applicable quiet
mode level. Example: Most
quiet.
Use and program a quiet
mode schedule
Select Automatic.
Go to [7.4.2] Schedule and
program the schedule. For
more information about
scheduling, see
"4.7.4 Schedule screen:
Example" on page 12.
Usage example: Baby is sleeping in the afternoon
If you are in the following situation:
▪You have programmed a quiet mode schedule:
▪During the night: Most quiet.
▪During the day: Off to ensure the heating/cooling capacity of the
system.
▪However, during the afternoon the baby is sleeping and you want
it to be quiet.
Then you can do the following:
1
Go to [7.4.1]: User settings > Quiet > Activation.
2
Select Most quiet.
Advantage:
The outdoor unit runs in its most quiet level.
4.6.2
Using holiday mode
About holiday mode
During your holiday, you can use the holiday mode to deviate from
your normal schedules without having to change them. While holiday
mode is active, space heating/cooling operation and domestic hot
water operation will be turned off. Room frost protection and anti-
legionella operation will remain active.
Typical workflow
Using holiday mode typically consists of the following stages:
1
Setting the starting date and ending date of your holiday.
2
Activating the holiday mode.
To check if holiday mode is activated and/or running
If
is activated on the home screen, holiday mode is active.
To configure the holiday
1
Activate the holiday mode.
—
▪Go to [7.3.1]: User settings > Holiday > Activation.
▪Select On.
2
Set the first day of your holiday.
—
▪Go to [7.3.2]: From.
▪Select a date.
▪Confirm the changes.
3
Set the last day of your holiday.
—
▪Go to [7.3.3]: Till.
▪Select a date.
▪Confirm the changes.
4.6.3
Reading out information
To read out information
1
Go to [8]: Information.
Possible read-out information
In menu…
You can read out…
[8.1] Energy data
Produced energy, consumed
electricity, and consumed gas
[8.2] Malfunction history
Malfunction history
[8.3] Dealer information
Contact/helpdesk number
[8.4] Sensors
Room, tank or domestic hot
water, outside, and leaving water
temperature (if applicable)
[8.5] Actuators
Status/mode of each actuator
Example: Domestic hot water
pump ON/OFF
[8.6] Operation modes
Current operation mode
Example: Defrost/oil return
mode
[8.7] About
Version information about the
system
[8.8] Connection status
Information about the connection
status of the unit, the room
thermostat and the LAN adapter.
User reference guide
11
EABH/X16DA+9W + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556071-1 – 2018.10
4.6.4
To configure time and date
1
Go to [7.2] User settings > Time/date.
4.7
Preset values and schedules
4.7.1
Using preset values
About preset values
For some settings in the system, you can define preset values. You
only need to set these values one time, then reuse the values in
other screens such as the scheduling screen. If you later want to
change the value, you only have to do it in one place.
To define tank temperature preset values
For EABH/X: Only if a domestic hot water tank is installed
The domestic hot water schedule makes use of different preset
values:
Preset value
Where used
Comfort setpoint
In schedule if domestic hot water tank
mode is
▪Schedule only
▪Schedule + reheat
Eco setpoint
Reheat setpoint
If domestic hot water tank mode is
▪Schedule + reheat
To define energy prices
Only possible if Bivalent is enabled by the installer.
Preset value
Where used
Electricity price >
▪High
▪Medium
▪Low
Used in the weekly schedule screen
when setting the energy prices.
Gas price
4.7.2
Setting the energy prices
In the system, you can set the following energy prices:
▪a fixed gas price
▪3 electricity price levels
▪a weekly schedule timer for electricity prices.
Refer to the installation manual for more information.
Example: How to set the energy prices on the user interface?
Price
Value in breadcrumb
Fuel: 5.3 euro cents/kWh
[7.6]=5.3
Electricity: 12 euro cents/kWh
[7.5.1]=12
To set the gas price
1
Go to [7.6]: User settings > Gas price.
2
Select the correct gas price.
3
Confirm the changes.
INFORMATION
Price value ranging from 0.00~990 valuta/kWh (with 2
significant values).
To set the electricity price
1
Go to [7.5.1]/[7.5.2]/[7.5.3]: User settings > Electricity
price > High/Medium/Low.
2
Select the correct electricity price.
3
Confirm the changes.
4
Repeat this for all three electricity prices.
—
INFORMATION
Price value ranging from 0.00~990 valuta/kWh (with 2
significant values).
INFORMATION
If no schedule is set, the Electricity price for High is taken
into account.
To set the electricity price schedule timer
1
Go to [7.5.4]: User settings > Electricity price >
Schedule.
2
Program the selection using the scheduling screen.
You can set the High, Medium and Low electricity
prices according to your electricity supplier.
—
3
Confirm the changes.
INFORMATION
The values correspond with the electricity price values for
High, Medium and Low previously set. If no schedule is
set, the electricity price for High is taken into account.
About energy prices in case of an incentive per
kWh renewable energy
An incentive can be taken into account when setting the energy
prices. Although the running cost can increase, the total operation
cost, taking into account the reimbursement will be optimized.
NOTICE
Make sure to modify the setting of the energy prices at the
end of the incentive period.
To set the gas price in case of an incentive per kWh renewable
energy
Calculate the value for the gas price with the following formula:
▪Actual gas price+(Incentive/kWh×0.9)
For the procedure to set the gas price, see "To set the gas price" on
page 11.
To set the electricity price in case of an incentive per kWh
renewable energy
Calculate the value for the electricity price with following formula:
▪Actual electricity price+Incentive/kWh
For the procedure to set the electricity price, see "To set the
electricity price" on page 11.
Example
This is an example and the prices and/or values used in this
example are NOT accurate.
Data
Price/kWh
Gas price
4.08
Electricity price
12.49
Renewable heat incentive per
kWh
5
Calculation of the gas price:
Gas price=Actual gas price+(Incentive/kWh×0.9)
Gas price=4.08+(5×0.9)
Gas price=8.58
User reference guide
12
EABH/X16DA+9W + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556071-1 – 2018.10
Calculation of the electricity price:
Electricity price=Actual electricity price+Incentive/kWh
Electricity price=12.49+5
Electricity price=17.49
Price
Value in breadcrumb
Gas: 4.08 /kWh
[7.6]=8.6
Electricity: 12.49 /kWh
[7.5.1]=17
4.7.3
Using and programming schedules
About schedules
Depending on your system layout and installer configuration,
schedules for multiple controls may be available.
You can:
▪Select which schedules you currently want to use.
▪Program your own schedules if the predefined schedules are not
satisfactory. The actions you can program are control specific.
Possible scheduling screens
Name and location
Usage
[1.2] Room > Heating
schedule
Program the desired room temperature
in heating mode.
[1.3] Room > Cooling
schedule
Program the desired room temperature
in cooling mode.
[2.2] Main zone > Heating
schedule
Program the desired leaving water
temperature for the main zone in
heating mode.
[2.3] Main zone > Cooling
schedule
Program the desired leaving water
temperature for the main zone in
cooling mode.
[3.2] Additional zone >
Heating schedule
Program the desired leaving water
temperature for the additional zone in
heating mode.
[3.3] Additional zone >
Cooling schedule
Program the desired leaving water
temperature for the additional zone in
cooling mode.
[4.2] Space heating/
cooling > Operation mode
schedule
See "4.4.2 Setting the space operation
mode" on page 7.
[5.5] Tank > Schedule
Program the domestic hot water tank
temperature for your normal domestic
hot water needs:
▪Comfort
▪Eco
▪Stop
[7.4.2] User settings >
Quiet > Schedule
Program when the unit has to use which
quiet mode level:
▪Off
▪Quiet
▪More quiet
▪Most quiet
[7.5.4] User settings >
Electricity price >
Schedule
Program when a certain electricity tariff
is valid.
Example of programming a schedule
See "4.7.4 Schedule screen: Example" on page 12.
4.7.4
Schedule screen: Example
This example shows how to set a room temperature schedule in
heating mode for the main zone.
INFORMATION
The procedures to program other schedules are similar.
To program the schedule
Example: You want to program the following schedule:
Mon
Sat
Wed
Fri
Thu
Tue
Sun
User defined 1
Prerequisite: The room temperature schedule is only available if
room thermostat control is active. If leaving water temperature
control is active, you can program the main zone schedule instead.
1
Go to the schedule.
2
Clear the contents of the schedule (optional).
3
Program the schedule for Monday.
4
Copy the schedule to the other weekdays.
5
Program the schedule for Saturday and copy it to Sunday.
6
Give the schedule a name.
To go to the schedule:
1
Go to [1.1]: Room > Schedule.
2
Set scheduling to Yes.
3
Go to [1.2]: Room > Heating schedule.
To clear the contents of the schedule:
1
Select the name of the current schedule.
Mon
Sat
Wed
Fri
Thu
Tue
Sun
User defined 1
2
Select Delete.
Edit
Delete
3
Select OK to confirm.
To program the schedule for Monday:
1
Select Monday.
Mon
Sat
Wed
Fri
Thu
Tue
Sun
User defined 1
User reference guide
13
EABH/X16DA+9W + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556071-1 – 2018.10
2
Select Edit.
Delete
Copy
Edit
3
Use the left dial to select an entry and edit the entry
with the right dial. You can program up to 6 actions
each day.
0
6:00
8:30
17:30
20°C
18°C
22:00
--:--
18°C
--
21°C
12
24
Mon
4
Confirm the changes.
To copy the schedule to the other weekdays:
1
Select Monday.
Mon
Sat
Wed
Fri
Thu
Tue
Sun
User defined 1
2
Select Copy.
Edit
Copy
Result: "C" is displayed next to the copied day.
3
Select Tuesday.
Mon
Sat
Wed
Fri
Thu
Tue
Sun
User defined 1
C
4
Select Paste.
Copy
Paste
C
Result:
Mon
Sat
Wed
Fri
Thu
Tue
Sun
User defined 1
C
5
Repeat this action for all other weekdays.
Mon
Sat
Wed
Fri
Thu
Tue
Sun
User defined 1
C
—
To program the schedule for Saturday and copy it to Sunday:
1
Select Saturday.
2
Select Edit.
3
Use the left dial to select an entry and edit the entry
with the right dial.
0
8:00
23:00
--:--
21°C
18°C
--
12
24
Sat
4
Confirm the changes.
5
Select Saturday.
6
Select Copy.
7
Select Sunday.
8
Select Paste.
Result:
Mon
Sat
Wed
Fri
Thu
Tue
Sun
User defined 1
C
To rename the schedule:
INFORMATION
Not all schedules can be renamed.
1
Select the name of the current schedule.
Mon
Sat
Wed
Fri
Thu
Tue
Sun
User defined 1
2
Select the Rename option.
Delete
Rename
3
Browse through the character list and confirm the
selected character.
4
Confirm the new name.
Usage example: You work in a 3-shift system
If you work in a 3-shift system, you can do the following:
1
Program 3 room temperature schedules in heating mode and
give them appropriate names. Example: EarlyShift, DayShift
and LateShift
2
Select the schedule that you currently want to use.
User reference guide
14
EABH/X16DA+9W + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556071-1 – 2018.10
4.8
Weather dependent operation
In space heating/cooling control, the leaving water temperature
setpoint mode can be:
▪Fixed
▪WD heating, fixed cooling (in heating mode, the leaving water
temperature is determined automatically depending on the
outdoor temperature)
▪Weather dependent (the leaving water temperature is determined
automatically depending on the outdoor temperature)
You can change the setpoint mode for the:
▪Main zone [2.4]
▪Additional zone (if available) [3.4]
To modify the parameters for the weather-dependent curve ([2.5]
and [2.6] for the main zone and [3.5] and [3.6] for the additional
zone, see below.
4.8.1
Detailed screen with weather-dependent
curve
When weather dependent operation is active the desired tank
temperature is determined automatically depending on the averaged
outdoor temperature. When the outdoor temperature is lower the
tank temperature will need to be higher as the water pipes will be
colder and vice versa.
The weather-dependent curves are defined by two setpoints:
▪Setpoint (X1, Y2)
▪Setpoint (X2, Y1)
Weather-dependent curve:
X1
Y1
Y2
X2
Y
a
X
Possible actions on this screen
Go through the temperatures.
Change the temperature.
Go to the next temperature.
Confirm changes and proceed.
Item
Description
a
Possible weather dependent zones:
▪
: Main zone or additional zone heating
▪
: Main zone or additional zone cooling
▪
: Domestic hot water
X, X1, X2 Outdoor ambient temperature
Y, Y1, Y2 Desired tank temperature or leaving water temperature.
The symbol shown here corresponds to the heat emitter
for that zone:
▪
: Underfloor heating
▪
: Fan coil unit
▪
: Radiator
▪
: Domestic hot water tank
User reference guide
15
EABH/X16DA+9W + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556071-1 – 2018.10
4.9
Menu structure: Overview user settings
[4] Space heating/cooling
Operation mode
Operation mode schedule
[2] Main zone
Schedule
Heating schedule
Setpoint mode
Cooling schedule
Heating WD curve
Cooling WD curve
[3] Additional zone
Schedule
Heating schedule
Setpoint mode
Cooling schedule
Heating WD curve
Cooling WD curve
[1.4] Antifrost
Activation
Room setpoint
[1.5] Setpoint range
Heating minimum
Heating maximum
Cooling minimum
Cooling maximum
[7] User settings
Language
Time/date
Holiday
Quiet
Electricity price
Gas price
[C]Operation
Room
Space heating/cooling
Tank
[B]User profile
[7.3]
Holiday
Activation
From
Till
[7.4] Quiet
Activation
Schedule
[7.5]
Electricity price
High
Medium
Low
Schedule
[7.2]
Time/date
Hours
Minutes
Year
Month
Day
Daylight savings time
Format
[8.1]
Energy data
Electricity input
Produced heat
[1] Room
Room sensor offset
Setpoint range
Antifrost
Cooling schedule
Heating schedule
Schedule
[5] Tank
Powerful operation
Comfort setpoint
Eco setpoint
Reheat setpoint
Schedule
[8] Information
Energy data
Malfunction history
Dealer information
Sensors
Actuators
Operation modes
About
Connection status
Setpoint screen
INFORMATION
Depending on the selected installer settings and unit type,
settings will be visible/invisible.
5 Energy saving tips
User reference guide
16
EABH/X16DA+9W + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556071-1 – 2018.10
4.10
Installer settings: Tables to be
filled in by installer
4.10.1
Configuration wizard
Setting
Fill in…
System
Indoor unit type (read only)
Backup heater type [9.3.1]
Domestic hot water [9.2.1]
Emergency [9.5]
Number of zones [4.4]
Backup heater
Voltage [9.3.2]
Configuration [9.3.3]
Capacity step 1 [9.3.4]
Additional capacity step 2 [9.3.5]
(if applicable)
Main zone
Emitter type [2.7]
Control [2.9]
Setpoint mode [2.4]
Schedule [2.1]
Additional zone (only if [4.4] = 1)
Emitter type [3.7]
Control (read only) [3.9]
Setpoint mode [3.4]
Schedule [3.1]
Tank
Heat up mode [5.6]
Comfort setpoint [5.2]
Eco setpoint [5.3]
Reheat setpoint [5.4]
4.10.2
Settings menu
Setting
Fill in…
Main zone
Thermostat type [2.A]
Additional zone (if applicable)
Thermostat type [3.A]
Information
Dealer information [8.3]
5
Energy saving tips
Tips about room temperature
▪Make sure the desired room temperature is NEVER too high (in
heating mode) or too low (in cooling mode), but ALWAYS
according to your actual needs. Each saved degree can save up
to 6% of heating/cooling costs.
▪Do NOT increase the desired room temperature to speed up
space heating. The space will NOT heat up faster.
▪When your system layout contains slow heat emitters (example:
under floor heating), avoid large fluctuation of the desired room
temperature and do NOT let the room temperature drop too low. It
will take more time and energy to heat up the room again.
▪Use a weekly schedule for your normal space heating or cooling
needs. If necessary, you can easily deviate from the schedule:
▪For shorter periods: You can overrule the scheduled room
temperature until the next scheduled action. Example: When
you have a party, or when you are leaving for a couple of hours.
▪For longer periods: You can use the holiday mode.
Tips about leaving water temperature
▪In heating mode, a lower desired leaving water temperature
results in lower energy consumption and better performance. In
cooling, the opposite is valid.
▪Set the desired leaving water temperature in accordance with the
heat emitter type. Example: Underfloor heating is designed for
lower leaving water temperature than radiators and heat pump
convectors.
Tips about DHW tank temperature
▪Use a weekly schedule for your normal domestic hot water needs
(only in scheduled mode).
▪Program to heat up the DHW tank to a preset value (Comfort =
higher DHW tank temperature) during the night, because then
space heating demand is lower.
▪If heating up the DHW tank once at night is not sufficient,
program to additionally heat up the DHW tank to a preset value
(Eco = lower DHW tank temperature) during the day.
▪Make sure the desired DHW tank temperature is NOT too high.
Example: After installation, lower the DHW tank temperature daily
by 1°C and check if you still have enough hot water.
▪Program to turn ON the domestic hot water pump only during
periods of the day when instant hot water is necessary. Example:
In the morning and evening.
6
Maintenance and service
6.1
Overview: Maintenance and
service
The installer has to perform a yearly maintenance. You can find the
contact/helpdesk number via the user interface.
As end user, you have to:
▪Keep the area around the unit clean.
▪Keep the user interface clean with a soft damp cloth. Do NOT use
any detergents.
▪Regularly check if the water pressure is above 1 bar.
Refrigerant
This product contains fluorinated greenhouse gases. Do NOT vent
gases into the atmosphere.
Refrigerant type: R32
Global warming potential (GWP) value: 675
NOTICE
Applicable legislation on fluorinated greenhouse gases
requires that the refrigerant charge of the unit is indicated
both in weight and CO2 equivalent.
Formula to calculate the quantity in CO2 equivalent
tonnes: GWP value of the refrigerant × total refrigerant
charge [in kg] / 1000
Please contact your installer for more information.
WARNING: FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
User reference guide
17
EABH/X16DA+9W + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556071-1 – 2018.10
WARNING
The appliance shall be stored in a room without
continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric
heater).
WARNING
▪Do NOT pierce or burn refrigerant cycle parts.
▪Do NOT use cleaning materials or means to accelerate
the defrosting process other than those recommended
by the manufacturer.
▪Be aware that the refrigerant inside the system is
odourless.
WARNING
The refrigerant inside the unit is mildly flammable, but
normally does NOT leak. If the refrigerant leaks in the
room and comes in contact with fire from a burner, a
heater, or a cooker, this may result in fire, or the formation
of a harmful gas.
Turn off any combustible heating devices, ventilate the
room, and contact the dealer where you purchased the
unit.
Do NOT use the unit until a service person confirms that
the part from which the refrigerant leaked has been
repaired.
6.2
To find the contact/helpdesk
number
1
Go to [8.3]: Information > Dealer information.
7
Troubleshooting
7.1
To display the help text in case of
a malfunction
In case of a malfunction, the following will appear on the home
screen depending on the severity:
▪
: Error
▪
: Malfunction
You can get a short and a long description of the malfunction as
follows:
1
Press the left dial to open the main menu and go to
Malfunctioning.
Result: A short description of the error and the error
code is displayed on the screen.
2
Press in the error screen.
Result: A long description of the error is displayed
on the screen.
7.2
To check the malfunction history
Conditions: The user permission level is set to advanced end user.
1
Go to [8.2]: Information > Malfunction history.
You see a list of the most recent malfunctions.
7.3
Symptom: You are feeling too cold
(hot) in your living room
Possible cause
Corrective action
The desired room temperature is
too low (high).
Increase (decrease) the desired
room temperature.
If the problem recurs daily, do
one of the following:
▪Increase (decrease) the room
temperature preset value.
▪Adjust the room temperature
schedule.
The desired room temperature
cannot be reached.
Increase the desired leaving
water temperature in accordance
with the heat emitter type.
7.4
Symptom: The water at the tap is
too cold
Possible cause
Corrective action
You ran out of domestic hot
water because of unusual high
consumption.
If you immediately need domestic
hot water, activate the DHW tank
Powerful operation. However,
this consumes extra energy.
If you can wait, overrule
(increase) the active or next
scheduled desired temperature
so that more hot water will be
produced exceptionally.
If the problems recurs daily, do
one of the following:
▪Increase
the
DHW
tank
temperature preset value.
▪Adjust
the
DHW
tank
temperature
schedule.
Example:
Program
to
additionally
heat
up
the
DHW tank to a preset value
(Eco setpoint = lower tank
temperature) during the day.
The desired DHW tank
temperature is too low.
7.5
Symptom: Heat pump failure
When the heat pump fails to operate, the backup heater and/or
booster heater can serve as an emergency heater and either
automatically or non-automatically take over the heat load.
▪When auto emergency is set to Automatic and a heat pump failure
occurs:
▪For EHVH/X: The backup heater will automatically take over the
heat load and domestic hot water production
▪For EHBH/X: The backup heater will automatically take over the
heat load, and the booster heater in the optional tank will
automatically take over the domestic hot water production.
▪When auto emergency is set to Manual and a heat pump failure
occurs, the domestic hot water and space heating operation will
stop and need to be recovered manually via the user interface. To
recover operation manually, go to the Malfunctioning main menu
screen, where the user interface will then ask you to confirm
whether the backup heater and/or booster heater can take over
the heat load or not.
When the heat pump fails,
or
will appear on the user
interface.
User reference guide
18
EABH/X16DA+9W + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556071-1 – 2018.10
Possible cause
Corrective action
Heat pump is damaged.
See "7.1 To display the help text
in case of a malfunction" on
page 17.
INFORMATION
When the backup heater or booster heater takes over the
heat load, electricity consumption will be considerably
higher.
7.6
Symptom: The system is making
gurgling noises after
commissioning
Possible cause
Corrective action
There is air in the system.
Purge air from the system.(a)
Various malfunctions.
Check if
or
is displayed
on the home screen of the user
interface. See "7.1 To display the
help text in case of a
malfunction" on page 17 for more
information about the
malfunction.
(a)
We recommend to purge air with the unit's air purge
function (to be performed by the installer). If you purge air
from the heat emitters or collectors, mind the following:
WARNING
Air purging heat emitters or collectors. Before you
purge air from heat emitters or collectors, check if
or
is displayed on the home screen of the user interface.
▪If not, you can purge air immediately.
▪If yes, make sure that the room where you want to
purge air is sufficiently ventilated. Reason: Refrigerant
might leak into the water circuit, and subsequently into
the room when you purge air from the heat emitters or
collectors.
8
Relocation
8.1
Overview: Relocation
If you want to relocate parts of your system (user interface, indoor
unit, outdoor unit, DHW tank…), contact your installer. You can find
the contact/helpdesk number via the user interface.
9
Disposal
NOTICE
Do NOT try to dismantle the system yourself: dismantling
of the system, treatment of the refrigerant, oil and other
parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for
reuse, recycling and recovery.
10
Glossary
DHW = Domestic hot water
Hot water used, in any type of building, for domestic
purposes.
LWT = Leaving water temperature
Water temperature at the water outlet of the heat pump.
Dealer
Sales distributor for the product.
Authorized installer
Technical skilled person who is qualified to install the
product.
User
Person who is owner of the product and/or operates the
product.
Applicable legislation
All international, European, national and local directives,
laws, regulations and/or codes that are relevant and
applicable for a certain product or domain.
Service company
Qualified company which can perform or coordinate the
required service to the product.
Installation manual
Instruction manual specified for a certain product or
application, explaining how to install, configure and maintain
it.
Operation manual
Instruction manual specified for a certain product or
application, explaining how to operate it.
Accessories
Labels, manuals, information sheets and equipment that are
delivered with the product and that need to be installed
according to the instructions in the accompanying
documentation.
Optional equipment
Equipment made or approved by Daikin that can be
combined with the product according to the instructions in
the accompanying documentation.
Field supply
Equipment NOT made by Daikin that can be combined with
the
product
according
to
the
instructions
in
the
accompanying documentation.