IInnssttaallllaattiioonn aanndd SSttaarrtt--uupp GGuuiiddee
CARRIER CORPORATION ©2019
A member of the United Technologies Corporation family · Stock symbol UTX · Catalog No. 11-808-477-01 · 1/23/2019
Verify that you have the most current version of this document from www.hvacpartners.com or your local Carrier
office.
Important changes are listed in Document revision history at the end of this document.
CARRIER CORPORATION ©2019. All rights reserved throughout the world. i-Vu is a registered trademark of Carrier
Corporation. All other trademarks are the property of their respective owners.
AppController overview and specifications ............................................................................................................... 1
What is the AppController? ................................................................................................................................. 1
Specifications ........................................................................................................................................................ 2
Safety considerations........................................................................................................................................... 3
Installing the AppController ........................................................................................................................................ 4
Mounting the AppController ................................................................................................................................ 4
Wiring the AppController for power ................................................................................................................... 5
To wire for power ................................................................................................................................... 5
Addressing the AppController ............................................................................................................................. 5
Wiring for communications ................................................................................................................................. 6
Wiring specifications for BACnet MS/TP and ARC156 ........................................................................ 6
To wire the controller to the BACnet network ...................................................................................... 6
Wiring inputs and outputs ................................................................................................................................... 7
Input wiring specifications .................................................................................................................... 7
Inputs ..................................................................................................................................................... 8
Binary outputs ....................................................................................................................................... 8
Analog outputs ...................................................................................................................................... 8
To wire inputs and outputs ................................................................................................................... 9
Wiring devices to the AppController's Rnet port ........................................................................................... 11
Rnet wiring specifications ................................................................................................................... 11
To wire ZS sensors to the controller ................................................................................................... 12
To wire the Wireless Adapter for wireless sensors ............................................................................ 13
To wire an Equipment Touch to the AppController ............................................................................ 15
To wire the TruVu™ ET Display ........................................................................................................... 16
Installing the AppController into an i-Vu® Control System ......................................................................... 17
Local access to the AppController .................................................................................................................. 18
Troubleshooting ......................................................................................................................................................... 19
LED's .................................................................................................................................................................... 19
Serial number ..................................................................................................................................................... 20
To restore defaults ............................................................................................................................................. 20
To replace the AppController's battery ........................................................................................................... 21
Compliance ................................................................................................................................................................ 22
FCC Compliance ................................................................................................................................................. 22
CE Compliance ................................................................................................................................................... 22
BACnet Compliance........................................................................................................................................... 22
Appendix A: AppController wire list .......................................................................................................................... 23
Appendix B: AHU CV (small) inputs and outputs points list .................................................................................... 24
Document revision history ........................................................................................................................................ 25
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
1
What is the AppController?
The AppController provides the communications circuitry, non-volatile memory, and removable screw terminals for
I/O connections. It has 5 binary outputs, 6 universal inputs, and 3 analog outputs. The AppController runs single
purpose applications such as Fan Coil, Unit Vent, Air Source Interface, Water Source Heat Pump, and basic AHU
CV.
AppController overview and specifications
AppController overview and specifications
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
2
Specifications
Driver
drv_acopen_std
Maximum number of control
programs*
2
Maximum number of
BACnet objects*
1050
* Depends on available memory
Power
24 Vac ±10%, 50–60 Hz
20 VA power consumption
26 Vdc (25 V min, 30 V max)
Single Class 2 source only, 100 VA or less
BACnet Port
For communication with the controller network using BACnet ARC156 (156 kbps)
or BACnet MS/TP (9600 bps – 76.8 kbps)
Rnet port
Supports up to 10 wireless and/or ZS sensors, and one Equipment Touch or
TruVu™ ET Display
Supplies 12 Vdc/210 mA power to the Rnet at an ambient temperature of
77°F (25°C) with a 24 Vac nominal power source.
NOTE Ambient temperature and power source fluctuations may reduce the
power supplied by the Rnet port.
NOTE If the total power required by the sensors on the Rnet exceeds the power
supplied by the Rnet port, use an external power source. The Wireless Adapter,
Equipment Touch, or TruVu™ ET Display must be powered by an external power
source. See the specifications in each device's Installation and Start-up Guide to
determine the power required.
Local Access port
For system start-up and troubleshooting using Field Assistant
Inputs
6 inputs configurable for thermistor or dry contact.
1 and 2 are also configurable for 0–5 Vdc sensors.
NOTES
Inputs 7 and 8 are unused.
Input 5 has a maximum temperature of 140°F (60°C).
Input resolution
10 bit A/D
Analog outputs
3 analog outputs, 0–10 Vdc (5 mA max)
Binary outputs
5 binary outputs, dry relay contacts rated at 1 A max. @ 24 Vac/Vdc. Configured
normally open
Output resolution
8 bit A/D, using filtered PWM
Real time clock
Battery-backed real time clock keeps track of time in the event of a power failure
Battery
10-year Lithium CR2032 battery retains the following data for a maximum of
10,000 hours during power outages: control programs, graphics, editable
properties, schedules, and trends.
AppController overview and specifications
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
3
Protection
Built-in surge and transient protection for power and communications in
compliance with EN61000-6-1.
Incoming power and network connections are protected by non-replaceable
internal solid-state polyswitches that reset themselves when the condition that
causes a fault returns to normal.
The power, network, input, and output connections are also protected against
transient excess voltage/surge events lasting no more than 10 msec.
CAUTION To protect against large electrical surges on serial EIA-485
networks, place a PROT485 at each place wire enters or exits the building.
Status indicators
LEDs indicate status of communications, running, errors, and power.
Environmental operating
range
0 to 130°F (-18 to 54°C), 0 to 90% relative humidity, non-condensing
Storage temperature range
-24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
Physical
Rugged GE C2950HF Cycoloy plastic
Overall dimensions
A:
B:
5-5/8 in. (14.3 cm)
5-1/8 in. (13 cm)
Mounting dimensions
C:
D:
E:
5-1/4 in. (13.3 cm)
2-9/16 in. (6.5 cm)
3/16 in. (.5 cm)
Panel depth
2 in. (5.1 cm)
Weight
0.44 lbs. (0.20 kg)
BACnet support
Conforms to the BACnet Advanced Application Controller (B-AAC) Standard Device
Profile as defined in ANSI/ASHRAE Standard 135-2012 (BACnet) Annex L,
Protocol Revision 9
Listed by
UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-Class A, CE
Safety considerations
WARNING Disconnect electrical power to the AppController before wiring it. Failure to follow this warning
could cause electrical shock, personal injury, or damage to the controller.
Installing the AppController
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
4
1
Mount the controller (page 4).
2
Wire the controller for power (page 5).
3
Set the controller's address (page 5).
4
Wire the controller to the BACnet MS/TP or BACnet ARC156 network (page 6).
5
Wire inputs and outputs. (page 7)
6
Wire devices to the controller's Rnet port (page 12, page 11).
Mounting the AppController
WARNING
When you handle the AppController:
• Do not contaminate the printed circuit board with fingerprints, moisture, or any foreign material.
• Do not touch components or leads.
• Handle the board by its edges.
• Isolate from high voltage or electrostatic discharge.
• Ensure that you are properly grounded.
Screw the AppController into an enclosed panel using the mounting slots on the coverplate. Leave about 2 in. (5
cm) on each side of the controller for wiring. Mounting hole dimensions 5 9/16" (14.1 cm) between mounting slot
center lines.
Installing the AppController
Installing the AppController
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
5
Wiring the AppController for power
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.
CAUTIONS
The AppController is powered by a Class 2 power source. Take appropriate isolation measures when
mounting it in a control panel where non-Class 2 circuits are present.
Carrier controllers can share a power supply as long as you:
Maintain the same polarity.
Use the power supply only for Carrier controllers.
To wire for power
1
Remove power from the power supply.
2
Pull the screw terminal connector from the controller's power terminals labeled Gnd and Hot.
3
Connect the transformer wires to the screw terminal connector.
NOTE If using a grounded transformer, connect the ungrounded lead to the Hot terminal to avoid damaging
the transformer.
4
Apply power to the power supply.
5
Measure the voltage at the AppController’s power input terminals to verify that the voltage is within the
operating range of 21.6–26.4 Vac.
6
Insert the screw terminal connector into the AppController's power terminals.
7
Verify that the Power LED is on and the Run LED is blinking.
Addressing the AppController
You must give the AppController an address that is unique on the network. You can address the AppController
before or after you wire it for power.
1
If the AppController has been wired for power, pull the screw terminal connector from the controller power
terminals labeled Gnd and Hot. The controller reads the address each time you apply power to it.
Installing the AppController
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
6
2
Using the rotary switches, set the controller address. Set the Tens (10's) switch to the tens digit of the
address, and set the Ones (1's) switch to the ones digit.
EXAMPLE If the controller’s address is 25, point the arrow on the Tens (10's) switch to 2 and the arrow on
the Ones (1's) switch to 5.
10's
1's
1
3
4
5
2
7
8
9
6
0
1
3
4
5
2
7
8
9
6
0
CAUTION The factory default setting is 00 and must be changed to successfully install your
AppController.
Wiring for communications
The AppController communicates using BACnet on the following types of network segments:
MS/TP communicating at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps
ARC156 communicating at 156 kbps
NOTE For more networking details, see the Open Controller Network Wiring Installation Guide.
Wiring specifications for BACnet MS/TP and ARC156
Cable:
22 AWG or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire
Maximum length:
2000 feet (610 meters)
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.
To wire the controller to the BACnet network
1
Pull the screw terminal connector from the AppController's power terminals labeled 24 Vac and Gnd (Return).
2
Check the communications wiring for shorts and grounds.
3
Connect the communications wiring to the controller’s screw terminals labeled Net +, Net -, and Shield.
NOTE Use the same polarity throughout the network segment.
Installing the AppController
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
7
4
Set the communication type and baud rate.
For...
Set Communications
Selection jumper to...
Set DIP switches 1 and 2 to...
Set DIP switches 3 and 4 to...
MS/TP
BACnet MS/TP
The appropriate baud rate. See the
MS/TP Baud diagram on the
controller.
Off/Off
ARC156
BACnet ARC156
N/A. Baud rate will be 156 kbps
regardless of the DIP switch
settings.
Off/Off
NOTE Use the same baud rate for all controllers on the network segment.
5
Wire the controllers on a BACnet MS/TP or BACnet ARC156 network segment in a daisy-chain configuration.
6
If the AppController is at either end of a network segment, connect a BT485 to the AppController.
7
Insert the power screw terminal connector into the AppController's power terminals.
8
Verify communication with the network by viewing a Module Status report in the i-Vu® interface.
Wiring inputs and outputs
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.
See Appendix A (page 23) to print a blank wire list.
Input wiring specifications
Input
Maximum length
Minimum gauge
Shielding
0–5 Vdc
500 feet
(152 meters)
22 AWG
100 feet
(30.4 meters) unshielded
100 - 500 feet shielded
Thermistor
Dry contact
Pulse counter TLO
500 feet
(152 meters)
22 AWG
100 feet
(30.4 meters) unshielded
100 - 500 feet shielded
ZS sensors
Wireless Adapter for
wireless sensors
Equipment Touch
TruVu™ ET Display
See Wiring devices to the AppController's Rnet port (page 11).
Installing the AppController
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
8
Inputs
The AppController has 6 inputs that accept the following signal types.
These
inputs...
Support this signal
type...
Description
All
Thermistor
Precon type 2 (10 kOhm at 77°F/25°C)
Input voltage for IN-5: 1 to 2.52 Vdc
Input voltage for all other inputs: 0.33 to 2.52 Vdc
All
Dry contact
A 3.3 Vdc wetting voltage detects contact position, resulting in a 0.3 mA
maximum sense current when the contacts are closed.
IN-1, IN-2
0–5 Vdc
The input impedance of the AppController is approximately 30 kOhm.
All
Pulse counter
Pulse counting up to 10 pulses per second.
Minimum pulse width (on or off time) required for each pulse is 50
msec.
Binary outputs
The AppController has 5 binary outputs. You can connect each output to a maximum of 24 Vac/26 Vdc. Each
output is a dry contact rated at 1 A, 24 V maximum and is normally open.
To size output wiring, consider the following:
Total loop distance from the power supply to the controller, and then to the controlled device
NOTE Include the total distance of actual wire. For 2-conductor wires, this is twice the cable length.
Acceptable voltage drop in the wire from the controller to the controlled device
Resistance (Ohms) of the chosen wire gauge
Maximum current (Amps) the controlled device requires to operate
Analog outputs
The AppController has 3 analog outputs that support voltage. The controlled device must share the same ground
as the controller and have the following input impedance:
0–10 Vdc
Minimum impedance 2000 Ohms, max 5 mA
NOTE Ohm's law: -10V/.005a = 2000 Ohms
Installing the AppController
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
9
To wire inputs and outputs
Pull the screw terminal connector from the controller's power terminals labeled Gnd and Hot.
1
Connect the input wiring to the screw terminals on the AppController.
NOTES
○
Connect the shield wire to the GND terminal with the ground wire.
○
IN-5 and IN-6 share the GND terminal above IN-5.
Installing the AppController
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
10
2
Set the appropriate jumpers on the AppController.
To use...
For...
IN-1
Thermistor
Set jumpers IN-1 to the Therm position.
IN-1
0–5 Vdc
Set jumpers IN-1 to the 0-5 Vdc position.
IN-2
Thermistor/
Dry contact
Set jumpers IN-2 to the Thermistor/Dry contact position.
All
Thermistor
Dry contact
Verify the IN-5 jumper is on.
Rnet Port
ZS sensors
Wireless Adapter for
wireless sensors
Equipment Touch
TruVu™ ET Display
Set the Rnet jumper to Rnet.
3
Connect the analog output wiring to the screw terminals on the AppController and to the controlled device.
Installing the AppController
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
11
4
Connect the binary output wiring to the screw terminals on the AppController and to the controlled device.
5
Insert the power screw terminal connector into the AppController's power terminals.
Wiring devices to the AppController's Rnet port
The Rnet communicates at a rate of 115 kbps and should be wired in a daisy-chain or hybrid configuration.
Supports up to
10 wireless and/or ZS sensors (5 per control program)
One Equipment Touch
One TruVu™ ET Display
NOTE ZS sensors, a Wireless Adapter, and an Equipment Touch can share the Rnet, but not SPT sensors.
Rnet wiring specifications
NOTE Use the specified type of wire and cable for maximum signal integrity.
Description
4 conductor, shielded or unshielded, CMP, plenum rated cable
Conductor
22 AWG (7x0096) bare copper if Rnet has only sensors
Maximum length
500 feet (152 meters)
Insulation
Low-smoke PVC (or equivalent)
Color Code
Black, white, green, red
Shielding
If shielded, Aluminum/Mylar shield (100% coverage) with TC drain wire, terminated
at controller
UL temperature rating
32–167°F (0–75°C)
Voltage
300 Vac, power limited
Listing
UL: NEC CL2P, or better
Installing the AppController
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
12
To wire ZS sensors to the controller
ZS Sensors are thermistor-based temperature sensors that may optionally sense humidity, CO2, or VOC. ZS
Sensors are wired to the Rnet port on i-Vu® Open controllers. You can use the following ZS sensors:
ZS Standard
ZS Plus
ZS Pro
ZS Pro-F
NOTES
The ZS CO2 model uses 190 mA during sample period. Use auxiliary 12 Vdc, unless it is the only device on
the Rnet port.
A control program can use no more than 5 ZS Sensors
SPT sensors cannot share the Rnet with other devices.
For detailed instructions, see the ZS Sensor Installation Guide.
1
Remove power from the AppController.
2
Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick the inner insulation.
Strip about .25 inch (.6 cm) of the inner insulation from each wire.
Outer Jacket
Inner insulation
.25 in.
(.6 cm)
3
Wire each terminal on the sensor to the same terminal on the controller. See diagram below.
NOTE Carrier recommends that you use the following Rnet wiring scheme:
Connect this wire...
To this terminal...
Red
Black
White
Green
+12V
Rnet-
Rnet+
Gnd
4
Apply power to the AppController.
Installing the AppController
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
13
To wire the Wireless Adapter for wireless sensors
WARNING Do not apply line voltage (mains voltage) to the Wireless Adapter.
The Carrier wireless sensors are available in 868, 902, and 928 MHz radio frequency. The sensors are thermistor-
based temperature sensors that may optionally sense humidity.
Wireless sensors communicate through a Wireless Adapter, which is wired to the Rnet port of the controller.
REQUIREMENTS
A v6.5 or later i-Vu® system
v6-xx-xxx or later controller drivers
To configure the control program for the desired user interaction with the sensor, see the Wireless Sensors
Application Guide. For detailed instructions, see the Wireless Sensors Installation Guide.
To wire, power, and mount the Wireless Adapter
NOTES
The Wireless Adapter requires a 24 Vac power supply. It is not powered by the Rnet.
If the Wireless Adapter will be:
○
Daisy-chained on the Rnet with ZS sensors, an Equipment Touch, or TruVu™ ET Displayuse the standard
4-conductor Rnet wiring.
○
The only device on the Rnet, you can use a 3-conductor cable instead of the standard 4-conductor Rnet
cable.
1
Turn off the power to the controller that the Wireless Adapter will be wired to.
2
Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick the inner insulation.
Inner insulation
Outer jacket
Foil shield
.25 in.
(.6 cm)
Shield wire
3
Strip about 0.25 inch (0.6 cm) of the inner insulation from each wire.
Installing the AppController
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
14
4
Wire the Rnet +, Rnet -, and Gnd terminals on the controller's Rnet port to the terminals of the same name on
the Wireless Adapter's Rnet connector.
NOTE If using shielded wire, connect the shield wire and the ground wire to the Gnd terminal.
5
Wire the 24 Vac external power supply to the Wireless Adapter's power connector.
6
Mount the Wireless Adapter by inserting 2 screws through the mounting tabs on each end of the Wireless
Adapter.
7
Apply power to the external power supply.
8
Verify that the LED on top of the Wireless Adapter is blinking. See "LED" below.
9
Turn on the controller's power.
LED
The blue LED on the top of the Wireless Adapter indicates the following:
If the LED is...
Then the device...
Off
Is not powered or there is a problem.
Blinking
Is working properly.
Steadily on
Has a problem. Do one of the following:
Cycle power to the device.
Insert a small screwdriver or paper clip into the hole next to the LED to reboot the
device.
Installing the AppController
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
15
To wire an Equipment Touch to the AppController
NOTES
The Equipment Touch requires a 24 Vac power supply. It is not powered by the Rnet.
If the Equipment Touch will be:
○
Daisy-chained on the Rnet with ZS sensors or a Wireless Adapter, use the standard 4-conductor Rnet
wiring and follow the wiring instructions To wire ZS sensors to the AppController (page 12).
○
The only device on the Rnet, you can use a 2-conductor cable instead of the standard 4-conductor Rnet
cable and follow the instructions below.
For complete Equipment Touch installation instructions including wiring diagrams, see the Equipment Touch
Installation and Setup Guide.
CAUTION The AppController can share a power supply with the Carrier controller as long as:
The power supply is AC power.
You maintain the same polarity.
You use the power source only for Carrier controllers.
1
Turn off the AppController's power.
2
Partially cut, then bend and pull off the outer jacket of the cable. Do not nick the inner insulation.
3
Strip about 0.25 inch (0.6 cm) of the inner insulation from each wire.
4
Wire the AppController's Rnet+ and Rnet- terminals to the terminals of the same name on the Equipment
Touch's connector.
NOTE If using shielded wire, connect the shield wire and the ground wire to the Gnd terminal.
5
Turn on the AppController's power.
6
Turn on the Equipment Touch.
Installing the AppController
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
16
To wire the TruVu™ ET Display
WARNING Do not apply line voltage (main) - 24 Vdc power only.
Wiring power
Wire the TruVu™ ET Display 24V DC connector to the 24 Vdc power supply using 2-conductor 18 AWG wire.
Maximum distance 100 feet (30 meters).
CAUTION The TruVu™ ET Display can share a power supply with the Carrier controller as long as:
The power supply is DC power.
You maintain the same polarity.
You use the power source only for Carrier controllers.
Wiring communication
1
Turn off the AppController's power.
2
Wire the TruVu™ ET Display's RS485 connector to the 's Rnet port, Gnd to Gnd, + to Rnet +, - to
Rnet - using 2-conductor 22 AWG wire with a maximum distance of 500 feet (152 meters).
3
Turn on the AppController's power.
For complete TruVu™ ET Display installation instructions, see the TruVu™ ET Display Installation and Start-up
Guide.
Installing the AppController
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
17
Installing the AppController into an i-Vu® Control System
You must complete the following procedures to successfully install your AppController into an i-Vu® Control
System. Use the Help in the referenced software for detailed descriptions of these procedures.
EquipmentBuilder or Snap
1
Use EquipmentBuilder or Snap to create control program(s) for your AppController.
2
If applicable, print the Sequence of Operation, which includes the points list.
NOTE You can create a points list under Reports in the i-Vu® application or Field Assistant after installing
your control program.
This Installation Guide
1
Prepare a wire list using the points list. Refer to Appendix A.
2
Use the wire list and the following installation procedures to install and wire I/O points to your AppController.
The i-Vu® or Field Assistant application
1
Upload the controller to the database by selecting the router in the navigation tree.
2
Select Devices > Manage tab.
3
Select the controller in the list on the page and click Upload.
4
If you are adding a new control program, click
. A dialog window appears.
5
Enter a name for your control program in Display Name and select your controller in the Controller drop-down
list.
NOTES
○
If you already have the maximum number of control programs for a controller, it will not appear in the
list.
○
Optional: You can change the control program's Reference Name if needed.
6
Do one of the following:
If the control program is...
In the Control Program drop-down list
Select the control program.
Not in the Control Program drop-down list a. Click Add New.
b. Browse to select the control program.
c. Click Open.
d. Click Continue.
e. Click Close.
7
To upload a graphic, click Add New under Views and browse to your .view file.
8
Click Continue. When message appears File added successfully, click Close.
9
Click Close again.
Installing the AppController
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
18
10 Right-click on the programmable controller in the controller list and select Check Status from the list. The
status of the controller should say File Mismatch.
11 Click the Download All Content button.
12 Assign channel numbers to the physical points by selecting the controller in the navigation tree and going to
Properties page > I/O Points tab.
NOTE 39m CV Small AHU Equipment has pre-assigned IO channels. See Appendix B (page 24). Fan Coil, Unit
Ventilator, and Water Source Heat Pump are created with pre-assigned, non-editable IO channel
assignments. You must assign IO channels in all other applications by:
○
Entering your channel numbers under Num, using your wire list
○
Entering your expander address under Exp, if applicable
○
Selecting the appropriate value under Sensor/Actuator Type, if applicable
13 Configure the controller on the Properties page > Control Program tab.
14 Check out and commission the equipment.
Local access to the AppController
You can use the following items as a local user interface to an Open controller. These items let you access the
controller information, read sensor values, and test the controller.
Connect...
To the controller's...
For...
Field Assistant1
application
Local Access port
Temporary user interface for start-up
Equipment Touch2 touchscreen
device
Rnet port
Temporary or permanent user interface
for start-up
1 Requires a USB Link (Part #USB-L)
2 See the Equipment Touch Installation and Setup Guide for detailed instructions.
CAUTION If multiple controllers share power but polarity was not maintained when they were wired, the
difference between the controller's ground and the computer's AC power ground could damage the USB Link and
the controller. If you are not sure of the wiring polarity, use a USB isolator between the computer and the USB
Link. Purchase a USB isolator online from a third-party manufacturer.
These are accessory items that do not come with the controller.
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
19
If you have problems mounting, wiring, or addressing the AppController, contact Carrier Control Systems Support.
NOTE To help you troubleshoot, obtain a Module Status (Modstat) from the controller and review the System Error
and Warning details.
LED's
The LED’s indicate if the controller is speaking to the devices on the network. The LED’s should reflect
communication traffic based on the baud rate set. The higher the baud rate the more solid the LED’s become.
Verify the LED patterns by cycling power to the controller and noting the lights and flashes.
LEDs
Status
Power
Lights when power is being supplied to the controller.
NOTE The AppController is protected by internal solid state Polyswitches on the incoming power
and network connections. These Polyswitches are not replaceable, but they will reset themselves if
the condition that caused the fault returns to normal.
Rx
Lights when the controller receives data from the network segment; there is an Rx LED for Ports 1
and 2.
Tx
Lights when the controller transmits data from the network segment; there is an Rx LED for Ports 1
and 2.
Run
Lights based on controller health.
Error
Lights based on controller health.
The Run and Error LED's indicate controller and network status.
If Run LED shows...
And Error LED shows...
Status is...
1 flash per second
1 flash per second, alternating
with the Run LED
The controller files are archiving. Archive is
complete when Error LED stops flashing.
2 flashes per second
Off
Normal
2 flashes per second
2 flashes,
alternating with Run LED
Five minute auto-restart delay after system error
2 flashes per second
3 flashes,
then off
The controller has just been formatted
2 flashes per second
4 flashes, then pause
Two or more devices on this network have the
same network address
2 flashes per second
1 flash per second
The controller is alone on the network
Troubleshooting
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
20
If Run LED shows...
And Error LED shows...
Status is...
2 flashes per second
On
Exec halted after frequent system errors, due to:
Controller halted
Program memory corrupted
One or more programs stopped
5 flashes per second
On
Exec start-up aborted, Boot is running
5 flashes per second
Off
Firmware transfer in progress, Boot is running
7 flashes per second
7 flashes per second,
alternating with Run LED
Ten second recovery period after brownout
14 flashes per second
14 flashes per second,
alternating with Run LED
Brownout
On
On
Failure. Try the following solutions:
Turn the AppController off, then on.
Download memory to the AppController.
Replace the AppController.
NOTE If you resolve the issue but the Error LED does not turn off, cycle power to the controller.
Serial number
If you need the AppController's serial number when troubleshooting, the number is on a sticker on the back of the
main controller board.
To restore defaults
CAUTION This erases all archived information and user-configuration settings. You will have to reconfigure
all custom settings. It is recommended to restore the factory defaults only under the guidance of Carrier Control
Systems Support.
To erase volatile memory data and restore factory default configuration settings:
1
Turn off the AppController's power switch.
2
Put the Factory Defaults jumper on.
3
Turn on the AppController's power switch.
4
Remove the Factory Defaults jumper.
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
21
To replace the AppController's battery
To determine when to replace the battery, remove power and measure the voltage. If the voltage is below 2.9
volts, you need to replace the battery.
CAUTION Power must be ON to the AppController when replacing the battery, or your date, time, and trend
data will be lost.
1
Remove the battery from the controller, making note of the battery's polarity.
2
Insert the new battery, matching the battery's polarity with the polarity indicated on the AppController.
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
22
FCC Compliance
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference in which case the user will be required to correct the interference at his own expense.
CAUTION Changes or modifications not expressly approved by the responsible party for compliance could
void the user’s authority to operate the equipment.
CE Compliance
WARNING This is a Class A product. In a domestic environment, this product may cause radio interference
in which case the user may be required to take adequate measures.
BACnet Compliance
Compliance of listed products to requirements of ASHRAE Standard 135 is the responsibility of BACnet
International. BTL® is a registered trademark of BACnet International.
Compliance
Appendix A: AppController wire list
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
23
Open System Network - AppController
Project Name:
Location:
Network Number:
MAC Address:
Point#
Cable
number
(G)
Input
Type
Jumper
Position
of Pins
I/O
Channel
Number
Sensor
code
Equipment
Name
Point
Name
IN-1
Gnd
Therm/
Dry Contact
Upper
IN-1
Gnd
0-5Vdc
Lower
IN - 2
Gnd
Therm/
Dry Contact
Upper
Gnd
0-5Vdc
Lower
IN-3
Gnd
Therm/
Dry Contact
N/A
IN - 3
IN-4
Gnd
Therm/
Dry Contact
N/A
IN - 4
IN-5*
Gnd
Therm/
Dry Contact
N/A
IN - 5
IN-6
Gnd
Therm/
Dry Contact
N/A
IN - 6
IN-7
Unused
IN-8
Unused
*Input 5 has a maximum temperature of 140°F (60°C).
Point#
Outputs
(+)
COM
B-Output
Type
Jumper
Position
of Pins
I/O
Channel
Number
Sensor
code
Equipment
Name
Point
Name
AO-1
N/A
AO-1
AO-2
N/A
AO-1
AO-3
N/A
AO-1
BO-1
Bus
N.O.
N/A
BO-1
BO-2
Bus
N.O.
N/A
BO-2
BO-3
Bus
N.O.
N/A
BO-3
BO-4
Bus
N.O.
N/A
BO-4
BO-5
Bus
N.O.
N/A
BO-5
Appendix A: AppController wire list
Appendix B: AHU CV (small) inputs and outputs points list
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
24
This wire list represents all the possible points for this application. The points that are actually used in your application
depend on the equipment options you select in EquipmentBuilder or Snap.
I/O
Type
I/O
Terminal
Gnd
Terminal
Point Name/
Function
Hardware/
Signal
Jumper Position of
Pins
IN-1
BI
1
2 - Gnd
Filter Status
Dry Contact
Middle
IN-2
AI
2
4 - Gnd
Supply Air Temp
10K Thermistor
Middle
IN-3
AI
3
6 - Gnd
Mixed Air Temp
10K Thermistor
Middle
IN-4
AI
4
8 - Gnd
Outdoor Air Temp
5K Thermistor
Middle
IN-5
BI
5
1 - Gnd
Freezestat
Dry Contact
Middle
IN-6
BI
6
1 - Gnd
Fan Status
Dry Contact
Middle
IN-7
Unused
IN-8
Unused
BO-1
BO
1
1 - Bus
Fan S/S
Relay
N/A
BO-2
BO
2
1 - Bus
Electric Heat stage 1
Relay
N/A
BO-3
BO
3
1 - Bus
Electric Heat stage 2
Relay
N/A
BO-4
BO
4
1 - Bus
DX stage 1
Relay
N/A
BO-5
BO
5
1 - Bus
DX Stage 2
Relay
N/A
AO-1
AO
1
2 - Gnd
Modulating OA Damper
0-10 Volt
N/A
AO-2
AO
3
4 - Gnd
Modulating HW Valve
0-10 Volt
N/A
AO-3
AO
5
6 - Gnd
Modulating CW Valve
0-10 Volt
N/A
Legend
AI - Analog Input
AO - Analog Output
BI - Binary Input
BO - Binary Output
Appendix B: AHU CV (small) inputs and outputs points list
Document revision history
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
25
Important changes to this document are listed below. Minor changes such as typographical or formatting errors are not
listed.
Date
Topic
Change description
Code*
1/23/19
Wiring devices to the AppController's
Rnet port
Removed star configuration from the first paragraph.
X-TS-TS-O
New look, no content changes
Added surge CAUTION to Protection specification.
X-TS-AK-E-CC
12/14/17
Analog outputs
Corrected impedance from 500 Ohms to 2000 Ohms
C-AE-ZL-E-WB
2/15/17
Changed name of sensors from WS to wireless
C-D
1/16/17
Specifications
Wiring devices to the 's
Rnet port
Number of SPT and ZS sensors clarified to 10 (5 per control
program)
C-TS-JN-BR
ZS sensor overview
SPT sensor overview
Simplified. Detailed descriptions are available in specified
manuals. Corrected total number of ZS sensors.
C-D-RD
Wireless sensor overview
To install the Wireless Adapter for
wireless sensors
New Topics
C-D
Wiring devices to the AppController's
Rnet port
Added Wireless Adapter for wireless sensors
C-D
Input wiring specifications
Added Wireless Adapter for wireless sensors
C-D
To wire the controller to the network
Added BACnet ARC156 connection information
C-D-OC
Wiring for communications
Changed from Wiring the AppController to the MS/TP network
C-D-OC
Specifications
Added BACnet ARC156 connection and Wireless Adapter for
Carrier wireless sensors. Corrected SPT information.
C-D-OC
Cover
What is the AppController?
Changed to latest controller image.
C-D
6/2/16
Specifications
Corrected error. Max number of third party integration points
removed.
C-TS-RD-E
2/19/16
Local access to the AppController
Added USB Link wiring caution.
C-TS-RD-E-JH
12/2/15
Inputs
Corrected error - changed 8 inputs to 6 inputs.
C-TS-RR-E
8/14/14
Restore factory defaults
Added information on using the Factory Defaults jumper
C-D-LJ-E-RD
To wire the Equipment Touch to the
AppController
Added Caution to maintain polarity and use the power supply
only for Carrier controllers
C-TS-RD-E
Specifications
Maximum number of BACnet third-party integration points using
Snap - changed to unlimited, depending on memory
Power - removed references to BACview
Rnet port - added a note that number of possible ZS sensors you
can have with an Equipment Touch is 15
Added Equipment Touch and removed BACview
Local Access port - removed BACview, added Equipment Touch
C-D-LJ-O
Wiring devices to the Rnet port
Changed from "Wiring a communicating zone sensor to the
AppController"
Removed references to BACview
Connecting an SPT sensor
Removed BACview and added Equipment Touch
To wire an Equipment Touch to the
AppController
New topic
BACview devices
Removed references and topics
Local Access to the AppController
Removed BACview and added Equipment Touch