TOPTEK TOPVERT E1 Series Quick Start Manual
Read Online
Read the TOPTEK TOPVERT E1 Series Quick Start Manual online using the built-in PDF viewer.
Text of the manual
High performance Vector Control AC drive
TOPTEK ELECTRONICS CORPORATION
QUICK START
快速安裝手冊
TOPVERT G1/H1/P1 Series
E-1
PREFACE
Thank you for choosing TOPTEK’S TOPVERT G1, H1 and P1 Series Drive. TOPVERT G1, H1 and
P1 Series are Sensorless current vector control high-performance drive. They were manufactured by
adopting high-quality components, material and incorporating the latest microprocessor technology
available.
Copyright statement
All information in this Quick start manual are Toptek’s intellectual property. Even we had done our best
to make this manual but is unable to guarantee 100% correct.Based on " Never Stop for better but
perfect accomplished " quality policy, our product permanently in the journey which perfectly strives for
perfection to the pursue,Therefore we reserve the right to change the information in this manual
without prior notice.But we will continue the latest edition document in our website, for free download.
http://www.toptek.biz
Getting Started
This manual will be helpful in the installation, parameter setting, troubleshooting, and daily
maintenance of the drives. To guarantee safe operation of the equipment, read the following safety
guidelines before connecting power to the drives. Keep this operating manual handy and distribute to
all users for reference.
Always read this manual thoroughly before using TOPVERT G1,H1 and P1 Series drives.
DANGER!
1- AC input power must be disconnected before any maintenance. Do not connect or disconnect
wires and connectors while power is applied to the circuit. Maintenance must be performed by
qualified technicians.
2- A charge may still remain in the DC-link capacitor with voltages even if the power has been turned
off. To avoid personal injury, please ensure that power has turned off before operating drive and
wait ten minutes for capacitors to discharge to safe voltage levels.
3- The drive may be destroyed beyond repair if incorrect cables are connected to the input/output
terminals. Never connect the drive output terminals U/T1, V/T2, and W/T3 directly to the AC main
circuit power supply
CAUTION!
1- There are highly sensitive MOS components on the printed circuit boards. These components are
especially sensitive to static electricity. To avoid damage to these components, do not touch
these components or the circuit boards with metal objects or your bare hands.
2- Ground the drive using the ground terminal. The grounding method must comply with the laws of
the country where the drive is to be installed. Refer to Basic Wiring Diagram.
3- The final enclosures of the drive must comply with EN50178. (Live parts shall be arranged in
enclosures or located behind barriers that meet at least the requirements of the Protective Type
IP20.The top surface of the enclosures or barrier that is easily accessible shall meet at least the
requirements of the Protective Type IP40). (TOPVERT G1, H1 and P1 Series correspond with
this regulation.)
4- Heat sink may heat up over 70℃ (158℉), during the operation. Do not touch the heat sink.
5- The rated voltage for the drive must be ≤ 240V (≤ 480V for 460V models, ≤ 600VFor 575V models)
and the mains supply current capacity must be ≤ 5000A RMS (≤10000A RMS for the ≥ 40hp
(30kW) models).
6- The leakage current between chassis and earth could be up to 22mA.
7- The load motor should meet IEC:60034-1 standard.
W A R N IN G
TOPVERT G1/H1/P1 Series
E-2
Nameplate Information
Example for G1 series, 3HP/2.2kW 230V 3-Phase,a speed feedback PG card equipped.
Model Explanation
Explanation of Production control data
Please contact the dealers immediately if any discrepancy occurred.
Firmware version : 3.08
Input Specifications
Output Specifications
Barcode
Production control data
Output Frequency Range
Model number
CE certification
G1-232P2-D101-08 T0509001
Model:TOPVERT G1-232P2-D101
(FRN:3.08)
Production Month: 1~9 = Jan. to Sep.
O=Oct. N=Nov. D=Dec.
Production Year: 0~9=2010~2019
Production Factory: T = Taiwan factory
Option Code or custom-made code
Model: G1 series, 230V 3 Phase 2.2kW / 3Hp
Motor V/F selecting Preset (Pr0-02)
Production Number
G1-232P2-xxxx-08 T 0 5 09001
Applicable Motor (4 Pole)
(Base on 230V,380V,575V)
0P4= 0.4kW 0P7= 0.75kW
2P2= 2.2kW 5P5= 5.5kW
7P5= 7.5kW 011= 11kW
022= 22kW 075= 75kW
160= 160kW 630= 630kW
Toptek’ s AC drive family
AC Power source
21= 230V 1 Phase
23= 230V 3 Phase
43= 460V 3 Phase
63= 575V 3 Phase
G1 series
Hardware version
Blank: original version
A: version A
B: version B
Z: version Z
Brake chopper option
Blank or N : Brake chopper not include
D: Brake chopper built-in
**Brake chopper as standard equipped in
Fram e code A & B
Extension, Interface cards & other option
Blank or N : no option
01 :TEK-PG-01 speed feedback card equipped
02 :PU-02 equipped
03 :PU-03 equipped
Enclosure Protection
Blank or N : Standard
0 : IP 00 ( NEMA 0)
1 : IP 20 ( NEMA 1)
2 : IP 21 ( NEMA 4)
**IP 20 (NEMA 1) as standard In
Fram e code A , B & C
TOPVERT G1-23 2P2 x-x x xx
TOPVERT G1/H1/P1 Series
E-3
STANDARD SPECIFICATIONS
Series
TOPVERT G1 series
High performance general
purpose multi-function drive
TOPVERT H1 series
High performance high speed drive
TOPVERT P1 series
High performance variable torque drive
for Fan & Pump
Control Characteristics
Output frequency range
0.1 - 600Hz, Programmable
0.1 - 6000Hz, Programmable
0.1 - 600Hz, Programmable
Overload endurance
150% of rated current for 1 minute/10 minutes, Ta <=40, 200% of
rated current for 2 seconds
125% of rated current for 1 minute/10
minutes,
Ta <=40,165% of rated current for 2 seconds
Maximum output voltage
Proportional to Input Voltage, 3-Phase output
Power factor/Efficiency
Power factor no lower than 0.95. Efficiency no lower than 95% at full load
Control system
SPWM (Sinusoidal Pulse Width Modulation) vector control, 4 control modes :V/F, V/F + PG, SVC & VC + PG
Speed control range
V/F mode 20:1; V/F+PG mode 120:1; SVC mode 120:1; VC+PG mode 600:1
Output frequency resolution
Analog input: 10Bit(1/1024), Digital input: 0.01Hz, Fly-Shuttle dial input: 0.01Hz
Output frequency accuracy
Analog input: Within ±0.2% of max. output frequency (25℃ ±10℃ ).
Digital input: Within 0.01% of set output frequency
PWM carrier Frequency
0.7 -18kHz, Adjustable (Some models are limited), H1: 1.4kHz ~ 36kHz, Adjustable
Torque characteristics
auto-torque boost, auto-slip compensation; starting torque can be 150% at 1.0Hz
Skip frequency
Setting range 0.00 -600Hz (H1series: 0.00 ~ 6000 Hz), Max. 6 points, skip width are adjustable
Accel/Decel time
0.1-60000 seconds ( 2 Independent settings for Accel/Decel Time)
Stall prevention
0 to 250% of Rated Current, independent adjustable both in acceleration and constant speed operation.
DC Braking
DC Braking both when start up and stop , Braking Current Level: 0 to 125% of rated output current. Braking time: 0
to 60 seconds. Braking Start-Point when stop: 0.1-600Hz (H1series: 0.00 ~ 6000 Hz)
Dynamic braking
Braking torque Approx. 20%(10%E.D.). Dynamic Brake chopper built-in in Frame code: xx-A and xx-B.
Others can be built-in as an option. All models can connect to external Dynamic Brake Unit (TDBU-xxxx series).
V/F Pattern
2 of adjustable Random V/F curve. Constant Torque curve & Reduced Torque curve are available.
OPERATING Characteristics
Frequency Setting
Keypad
By an Encoder style Fly-Shuttle dial. (setting resolution 0.01Hz/0.1Hz/1Hz/10Hz adjustable)
External
Signal
0 ~ +10VDC((Input impedance 20kΩ), -10 ~ +10VDC((Input impedance 10kΩ),4 ~20mA DC ((Input impedance
250Ω),Multi-Function Inputs 1 ~ 6 (15 Steps Jog, up/down), PLC run, RS-485 port MODBUS protocol
Operation Setting
Keypad
Set by RUN, STOP and JOG. Switch-able between Keypad and External signal
External
Signal
2 wire control(FWD/STOP、REV/STOP、RUN/STOP、FWD/REV), 3 wire control, FWD, REV, MI1 to MI6 can be
combined to offer various modes of operation, RS-485 serial interface MODBUS protocol
Multi-Function Digital Input
(DI)
(6 terminals)
Multi-step selection 0 to 15, first to second accel/decel switches, accel/decel inhibit, Input the counter, Pause Stop,
EF Input, Emergency Stop, auxiliary motor control is invalid, ACI/AVI/AUI speed command selection, Reset, PLC
Run, Jog, Up/Down command, Sink/Source selection, Parameter team selection…etc, up to 43 functions.
Multi-Function Output Indication
(DO)
(4 indications )
Include a form C relay contact, a form A relay contact and 2 Open collector output. They can be programmed to
below indications: Drive Operating, Frequency Attained, zero speed, Base Block, Over torque,
Fault Indication, Local/Remote indication, PLC Operation indication, and Auxiliary Motor Output, Drive ready for
use, IGBT over-heat indication …etc, up to 63 functions.
Multi-Function Analog Input
(AI)
AVI: 0 ~ +10VDC((Input impedance 20kΩ), AUI: -10 ~ +10VDC((Input impedance 10kΩ), ACI: 4 ~20mA DC ((Input
impedance 250Ω). 3 different Input terminals can be programmed to 15 functions
Multi-Function Analog Output
(AO)
Include ACO and AVO, They can be programmed to Proportional to output frequency, output current, voltage,
frequency command or motor's speed …etc, up to 15 functions.
Fault Indication
The output will be activated when faults occur (User may get 1 or up to 4 indications from below terminals:2 Relay
contact point RA, RB, RC. or 2 Open-collector
Communication function
RS-485 serial port, MODBUS protocol, ASCII & RTU. (Baud rate up to 125 k bps)
Other Functions
PID feedback control, Flying start, Automatic voltage regulation (AVR), 2 accel./decel time selection , Auto-optimum
accel./decel. Time, S-curves, External fault interlock, External fault reset, Auto Restart after fault, 16 Fault records,
Automatic energy–saving, Upper/Lower limit, Programmable pulse output, Password protection, Pump and Fan
process control, Sleep/Wakeup function , Auto-Tuning, By-Pass, Y-Delta control,. Bi-Directional Speed search,
Reverse inhibit, Automatic torque boost & slip compensation, 16-step PLC run, 16 step preset speed, Coast or ramp
to stop, Random V/F curve, Mechanical brake release control, IGBT/ Heatsink temperature display & Pre-warning,
Quiet operation mode (No noise), User define Multi-function display, Over torque detection, Over current/voltage t
stall prevention, Sink/Source (NPN/PNP) mode, Electronic Thermal Relay, Internal Counter, DC injection brake both
in start and stop, Dynamic brake, Controlled cooling Fan, Removable keypad operator, Programmable
Multi-Function DI,DO,AI,AO and Ry terminals.
Intelligent Protection Functions
Self-testing, AC source Over Voltage, Phase loss, Over Voltage, Over Current, Under Voltage, Over Torque,
External Fault, Motor over-load, IGBT Over-temperature, Heat-sink Over-temperature, Electronic thermal, Ground
Fault, Output short circuit, Stall Prevention, Fuse protection, IGBT short circuit , Drive Over Load , DC bus capacitor
life monitoring, Auto carrier frequency adjust according temperature, 16 Trip records, Run information of latest Fault
such like DC-BUS voltage, Output voltage/Frequency/Current, Command frequency, IGBT temperature, Heat-sink
temperature….etc.
Digital Keypad
(PU-02 Digital Keypad with copy
function and PU-03 Digital Keypad
with LCD display are available as an
option)
Eight Function keys: Access R un, Stop, Reset/ Digit Shift, Forward/ Reverse run, Display mode, Keypad Enable,
Programming data and Jog operation…etc.
One Encoder style Fly-Shuttle dial: Sets the parameter number and changes the numerical data
One 6 digits 7 segment display: Display the Setting frequency/actual operation frequency, Output
current/Voltage, motor speed, Fault trip User defined unit(up to 88 type)…etc.
Six LED Display for status indication: Display the Drive run/stop status, Forward/Reverse run status, Keypad
enable, and Frequency command source.
One RJ-45 connector: Removable Keypad, remote control distance up to 150 meters.
Environment
Certificate
Complies with CE (EN61800-3) standard
Temperature
Ambient: -10
~ +40
/(
℃
℃-10
~ + 50
) (
℃
℃
Non-Condensing and not frozen). Storage: -20
~ +60
℃
℃
Humidity
Below 98% R.H. (Non-Condensing)
Vibration
Below 20Hz: 1G, above 20Hz: 0.6G
Installation Location
Altitude 1,000 m or lower, keep away from corrosive gasses, liquid and dust
* All series in TOPVERT family are designed and manufactured base on CNS and IEC, IEEE, CE & UL standard.
TOPVERT G1/H1/P1 Series
E-4
TOPVERT G1, H1 Series: 1-Phase,200/-15% ~ 240/+10%Vac, 47 ~ 63Hz /[400Hz]
Model
Applicable Motor
(230V 4 P)
Rated Output
Source
Enclosure structure
TOPVERT
G1-xxxxx
H1-xxxxx
Power
(kW)
Horse
Power
(Hp)
Capacity
(kVA)
Current
(A)
Voltage
(V)
Frequency
(Hz)
Current
(Amax.)
Cooling
Method
(Noise
level)
Degree of
protection
Net
Weight
(kg)
Frame
Code
210P4
0.4
0.5
1.2
3
3- Phase,
0-100%
of supply
voltage
G1 series
0 ~ 600
H1 series
0 ~ 6000
5.7
Fan-
cooled
(<70
dB/1M)
IP 20
NEMA 1
[IP
21/40/42
/50/52
Optional]
2.6
G1-A
H1-A
210P7
0.75
1
2
5
9.5
2.7
211P5
1.5
2
3
7.5
14
2.7
212P2
2.2
3
4.4
11
21
3.0
TOPVERT G1, H1 Series: 3-Phase, 200/-15% ~ 240/+10%Vac, 47 ~ 63Hz /[400Hz]
Model
Applicable Motor
(230V 4 P)
Rated Output
Source
Enclosure structure
TOPVERT
G1-xxxxx
H1-xxxxx
Power
(kW)
Horse
Power
(Hp)
Capacity
(kVA)
Current
(A)
Voltage
(V)
Frequency
(Hz)
Current
(Amax.)
Cooling
Method
(Noise
level)
Degree of
protection
Net
Weight
(kg)
Frame
Code
230P4
0.4
0.5
1.2
3
3- Phase,0-100% of supply voltage
G1 series
:
0 ~ 600
H1 series
:
0 ~ 6000
3.3
Fan-
cooled
(<70
dB/1M)
IP 20
NEMA 1
[IP 21/40/
42/50/52
Optional]
2.6
G1-A
H1-A
230P7
0.75
1
2
5
5.5
2.8
231P5
1.5
2
3
7.5
8.3
2.8
232P2
2.2
3
4.4
11
12
2.8
233P7
3.7
5
6.8
17
19
3.0
235P5
5.5
7.5
10
25
28
3.2
237P5
7.5
10
13
33
36
4.0
G1-B
H1-B
23011
11
15
20
49
54
11.9
G1-C
H1-C
23015
15
20
26
65
72
12.3
23018
18.5
25
30
75
83
13.0
23022
22
30
36
90
99
13.5
23030
30
40
48
120
132
IP 00
NEMA 0
[IP 20/21
/40/42/
50/52
NEMA 1
Optional]
32.7
G1-D
H1-D
23037
37
50
58
145
160
33.8
23045
45
60
73
182
200
34.6
G1-E
23055
55
75
92
232
255
58.0
G1-F
H1-F
23075
75
100
120
300
330
59.4
23090
90
125
143
360
396
Fan-
cooled
(<80
dB/1M)
192
G1-G
23110
110
150
175
440
484
192
23132
132
175
207
520
572
198
23132S
132
175
207
520
572
302
G1-H
Free-st
anding
[ ]: Optional
TOPVERT G1/H1/P1 Series
E-5
TOPVERT G1, H1 Series: 3-Phase 380/-15% ~ 480/+10%Vac, 47 ~ 63Hz /[400Hz]
Model
Applicable Motor
(4 pole)
Rated Output
Source
Enclosure structure
TOPVERT
G1-xxxxx
H1-xxxxx
380/415 V
(kW/Hp )
440/460 V
(kW/Hp )
Capacity
(kVA)
Current
(A)
Voltage
(V)
Frequency
(Hz)
Current
(A)
Cooling
Method
(Noise
level)
Degree of
protection
Net
Weight
(kg)
Frame
Code
430P7
0.75/1
2.4
3
3- Phase,0-100% of supply voltage
G1 series
:
0 ~ 600
H1 series
:
0 ~ 6000
3.3
Fan-
cooled
(<70
dB/1M)
IP 20
NEMA 1
[IP 21
/40/42/
50/52
Optional]
2.8
G1-A
H1-A
431P5
1.5/2
3.3
4.2
4.6
2.9
432P2
2.2/3
4.8
6
6.6
2.9
433P7
3.7/5
6.8
8.5
9.4
2.9
435P5
5.5/7.5
10
13
14
3.0
437P5
7.5/10
14
18
20
3.3
43011
11/15
19
24
26
4.3
G1-B
H1-B
43015
15/20
25
32
35
5.0
43018
18.5/25
32
40
44
13.0
G1-C
H1-C
43022
22/30
38
48
53
13.0
43030
30/40
48
60
66
13.9
43037
37/50
64
80
88
13.9
43045
45/60
77
97
107
13.9
43055
55/75
75/100
94
118
130
IP 00
NEMA 0
[IP 20/21
/40/42/
50/52
NEMA 1
Optional]
33.5
G1-D
H1-D
43075
75/100
90/125
121
152
167
37.1
43090
90/125
110/150
143
180
198
42.4
G1-E
H1-E
43110
110/150
132/175
191
240
264
63.0
G1-F
H1-F
43132
132/175
160/215
215
270
297
64.5
43160
160/215
185/250
242
304
334
64.5
43185
185/250
220/300
295
370
407
Fan-
cooled
(<80
dB/1M)
192
G1-G
43220
220/300
280/375
359
450
495
192
43280
280/375
315/422
414
520
572
198
43315
315/422
375/500
486
610
671
198
43280S
280/375
315/422
414
520
572
IP 20
NEMA 1
[IP 21
/40/42/
50/52
Optional]
302
G1-H
Free-st
anding
43315S
315/422
375/500
486
610
671
312
43400S
400/535
450/600
583
732
805
333
43450S
450/600
500/670
690
866
953
341
43500S
500/670
560/750
766
962
1058
348
43560S
560/750
630/850
872
1094
1203
355
43630S
630/850
750/1000
966
1212
1333
360
[ ]: Optional
TOPVERT G1/H1/P1 Series
E-6
TOPVERT P1 Series : 3-Phase,
,
,
,200/-15% ~ 240/+10%Vac, 47 ~ 63Hz /[400Hz]
Model
Applicable Motor
(230V 4 P )
Rated Output
Source
Enclosure structure
TOPVERT
P1-xxxxx
Power
(kW)
Horse
Power
(Hp)
Capacity
(kVA)
Current
(A)
Voltage
(V)
Frequency
(Hz)
Current
(Amax.)
Cooling
Method
(Noise
level)
Degree of
protection
Net
Weight
(kg)
Frame
Code
230P7
0.75
1
1.4
3.6
3- Phase,0-100% of supply voltage
0 ~ 600
4
Fan-
cooled
(<70
dB/1M)
IP 20
NEMA 1
[IP 21
/40/42/
50/52
Optional]
2.6
P1-A
231P5
1.5
2
2.4
6
6.6
2.8
232P2
2.2
3
3.6
9
9.9
2.8
233P7
3.7
5
5.3
13.2
15
2.8
235P5
5.5
7.5
8.1
20.4
22
3.0
237P5
7.5
10
12
30
33
3.2
23011
11
15
16
39.6
44
4.0
P1-B
23015
15
20
23
58.8
65
11.9
P1-C
23018
18.5
25
31
75
86
12.3
23022
22
30
36
90
99
13.0
23030
30
40
43
108
119
13.5
23037
37
50
57
144
158
IP 00
NEMA 0
[IP 20/21
/40/42/
50/52
NEMA 1
Optional]
32.7
P1-D
23045
45
60
69
174
191
33.8
23055
55
75
87
218.4
240
34.6
23075
75
100
111
278.4
306
58.0
P1-F
23090
90
125
143
360
396
59.4
23110
110
150
172
432
475
Fan-
cooled
(<80
dB/1M)
192
P1-G
23132
132
175
210
520
581
192
[ ]: Optional
TOPVERT G1/H1/P1 Series
E-7
TOPVERT P1 Series : 3-Phase,380/-15% ~ 480/+10%Vac, 47 ~ 63Hz /[400Hz]
Model
Applicable Motor
(4 pole)
Rated Output
Source
Enclosure structure
TOPVERT
P1-xxxxx
380/415 V
(kW/Hp)
440/460 V
(kW/Hp)
Capacity
(kVA)
Current
(A)
Voltage
(V)
Frequency
(Hz)
Current
(Amax.)
Cooling
Method
(Noise
level)
Enclosure
Net
Weight
(kg)
Frame
Code
431P5
1.5/2
2.9
3.6
3-Phase,0-100% of supply voltage
0 ~ 600
4
Fan-
cooled
(<70
dB/1M)
IP 20
NEMA 1
[IP 21
/40/42/
50/52
Optional]
2.8
P1-A
432P2
2.2/3
4
5.04
5.5
2.9
433P7
3.7/5
5.7
7.2
7.9
2.9
435P5
5.5/7.5
8.1
10.2
11
2.9
437P5
7.5/10
12
15.6
17
3.0
43011
11/15
17
21.6
24
3.3
43015
15/20
23
28.8
32
4.3
P1-B
43018
18.5/25
31
38.4
42
5.0
43022
22/30
38
48
53
13.0
P1-C
43030
30/40
46
57.6
63
13.0
43037
37/50
57
72
79
13.9
43045
45/60
76
96
106
13.9
43055
55/75
93
116.4
128
13.9
43075
75/100
90/125
113
141.6
156
IP 00
NEMA 0
[IP 20/21
/40/42/
50/52
NEMA 1
Optional]
33.5
P1-D
43090
90/125
110/150
145
180
201
37.1
43110
110/150
132/175
172
216
238
42.4
P1-E
43132
132/175
160/215
229
270
317
63.0
P1-F
43160
160/215
185/250
258
304
356
64.5
43185
185/250
220/300
291
365
401
64.5
43220
220/300
280/375
354
444
488
Fan-
cooled
(<80
dB/1M)
192
P1-G
43280
280/375
315/422
430
520
594
192
43315
315/422
375/500
497
610
671
198
43400
400/535
450/600
583
732
805
198
43315S
315/422
375/500
497
610
671
IP 20
NEMA 1
[IP 21
/40/42/
50/52
Optional]
312
P1-H
Free-
standing
43400S
400/535
450/600
583
732
805
333
43450S
450/600
500/670
700
866
953
341
43500S
500/670
560/750
828
962
1058
348
43560S
560/750
630/850
920
1094
1203
355
43630S
630/850
750/1000 1046
1212
1333
360
[ ]: Optional
TOPVERT G1/H1/P1 Series
E-8
Basic Wiring Diagram
M.C.
B2
B1
+12V/10V,20mA
0~10V/4~20mA
-12V
-12V,20mA
ACM
4~20mA/0~10V
VR : 5~10 KΩ
AI3
-10~+10V (10KΩ )
M
3~
U(T1)
W(T3)
V(T2)
R1A
R1B
R1C
R2B
R2C
AO2
AO1
ACM
+
P1
R(L1)
M.C.
T(L3)
S(L2)
-
E
B2
B1
+
TDBR
-
(AO)
(DI)
(AI)
MI1
MI2
MI3
MI4
MI5
MI6
DCM
24V
FWD
REV
60
60
0
Hz
FWD
REV
-12V
+12V
1
2
3
1
2
3
(Ry)
24V
MI7
MI8
MI9
DCM
E
(DI)
24V
+
-
MI9
DCM
24V
MI7
MI8
E
TMCA-IO-10
Extension
card (Option)
MO3
MO4
MC4
(DO)
MC3
MO1
MO2
MCM
(DO)
DCM
VP
B
A
A
B
+12V
GND
PG
E
A
B
E
A/O
B/O
COM
+VX
10
12
AI1
A
V
AI2
V
A
SG+
SG-
V
A
+VX
AI1
AI2
AO2
R2A
AO3
ACM
(AO)
Digital signal from
external
Analog signal from external
Digital signal
from external
24V
+
-
Source (PNP) mode
Sink (NPN) mode
MI1
MI2
MI3
MI4
MI5
MI6
DCM
24V
FWD
REV
SW1
Source
Sink
OC
TP
12V
5V
SW2
SW1
R30
S30
T30
Stand
alone
power
card for
control
(optional)
R1
S1
12 pulse rectifier
(optional)
Source (PNP) Mode
Sink (NPN) Mode
SW1
Source
Sink
Phase
difference 30°
Power source
M.C.
Single phase
auxiliary
power supply
E
TOPVERT
Main circuit
** B2 terminal is Optional
B2
B1
+
TDBU
-
P1
TD
BR
Jumper
TDBR
DC Choke (Option)
Models with Frame code:
C,D,E,F,G & H
Brake Resistor
(Option)
Models with
Frame code:
A & B
MCCB or Fuse
3-Phase
Power source
50/60Hz
[400Hz Option]
[ Use R(L1), S(L2) for 1-phase models]
Control circuit
Use external power source
Use internal power source
Reference of
external power
(Reset)
(E.F.)
FWD / STOP
(Multi-Step2)
(Multi-Step3)
(Multi-Step4)
(Multi-Step1)
REV / STOP
Digital Signal Common
*Don´t apply any voltage
directly to those terminals
Multi-function
Digital input
Multi-
function
Analog
input
(Frequency Command)
Multi-
function
Digital input
Digital Signal Common
Reference of
external power
Use externalpower source
Use internal
power source
Motor
Speed
feedback
PG card
(Option)
Factory Default
*Pulse Generator power source +5VDC
RPM Meter
Contact output 1
(indicates malfunction)
240VAC/2.5A, 120VAC/5A, 24VDC/5A
Contact output 2
(indicates drive running)
240VAC/2.5A, 120VAC/5A, 24VDC/5A
Photo-coupler output common terminal
Open collector output 1
(pre-set speed attained 1 (forward only))
48VDC/50mA
Open collector output 2
(indicates drive ready for use)
48VDC/50mA
Analog output 2 (output frequency)
4(0)~20mA/0~10V, 2mA
Analog output 1 (output frequency)
0~10VDC,2mA
Analog outputs Common
RS-485 serial port
(Modbus)
Multi-
function
Relay
output
Multi-
function
Digital
output
Serial
port
Multi-
function
Analog
output
Multi-
function
Digital
output
Multi-
function
Analog
output
Open collector output 3 +
( 48VDC/50mA )
Open collector output 3 -
Open collector output 4 +
( 48VDC/50mA )
Open collector output 4 -
Analog output 3 (output frequency)
4(0)~20mA
Analog outputs Common
Magnetic
contactor
◎
◎
◎
◎ →
→
→
→ Main circuit ○
○
○
○ →
→
→
→ Control circuit →
→
→
→ Shielded & twisted leads & Cable ( ) →
→
→
→ Factory default →
→
→
→ option
Wiring Diagram
TOPVERT G1/H1/P1 Series
E-9
Main circuit terminal explanations
Terminal Symbol
Content Explanation
R(L1),S(L2),T(L3)
AC source input terminals, to be connected to commercial power.
Ensuring the power voltage and the maximum current possible supplied
is meet the driver nameplate.
R30,S30,T30 (option)
The phase difference 30° AC source input terminals (When using
12-pulse input, a transformer with a Dual Star-delta Secondary is
necessary.)
Ensuring the power voltage and the maximum current possible supplied
is meet the driver nameplate.
R1,S1 (option)
Extra 1-phase AC source input terminals for main control card, to be
connected to commercial power. The voltage rating is same as
R(L1),S(L2),T(L3).These terminals can be powered both independent
and simultaneously with the main inputs. When These terminals
powered only, the drive cannot run, it can precede check signals and
management parameter setting and troubleshooting only.
U(T1),V(T2),W(T3)
Drive output terminals for motor connections
⊕/B1, B2
Connections for Brake Resistor (optional) . Refer to Chapter 9
⊕/B1, Θ
Connecting terminals of the external Dynamic Brake Unit.
(DC Bus, power source terminals)
P1, ⊕/B1
Connections for DC choke (option) .
Disconnect the short-circuit piece when the device is installed
Ground terminals, please have these terminals grounded following the
third-type grounding of 230V models and the special grounding of
460/575V models within the electrician regulations. There are two
ground terminals, one for AC source grounding on the input side.
The other one is for motor grounding on the output side.
TOPVERT G1/H1/P1 Series
E-10
Control Terminal Explanations
Symbol
Explanation
Ratings/Relative
parameters/Factory Default
Digital inputs
(Use the shielded twisted-pair cables to prevent operating faults)
MI1
Multi-function digital input MI1
(3-wire STOP-designated terminal)
Pr2-01/
(multi-step speed command 1)
MI2
Multi-function digital input MI2
Pr2-02/
(multi-step speed command 2)
MI3
Multi-function digital input MI3
Pr2-03/
(multi-step speed command 3)
MI4
Multi-function digital input MI4
Pr2-04/
(multi-step speed command 4)
MI5
Multi-function digital input MI5
Pr2-05/( Abnormal reset command)
MI6
Multi-function digital input MI6
(TRG-designated terminal)
Pr2-06/ (EF input)
AI2 Analog input selector
AI1 Analog input selector
AO2 Analog output selector
+VX Reference source selector
Socket for extension card
Logic control card
Mode of digital
Input terminals
Fault indication
Power indication
Fault
Power
+VX
AO2
AI2
AI1
10V
12V
A
V
A
V
V
A
Sink
Source
Port for keypad connection
Factory use only
Connector to power
supply & driver card
DI
AI/AO
Ry
DO
JP3
JP4
JP7
JP6
Setting of analog signal input/output
(Pull-up the female DI socket before setting)
SW1
JP2
Pluggable terminals
Ground & 24V output
E 24V DCM
Multi-function analog input/output (AI/AO)
+VX -12V AI1 AI2 AI3 ACM AO1 AO2
Multi-function digital output (DO)
& serial port
MO1 MO2 MCM SG+ SG-
Multi-function relay output (Ry)
R1A R1B R1C R2A R2B R2C
Multi-function digital input (DI)
MI1 MI2 MI3 MI4 MI5 MI6 FWD REV DCM
TP1
Field ground pin
TEK-G1-01-xx
Ver:
Date Code:
Fix hole for
extension card
Fix hole for
extension card
Socket for
extension card
+VX
AO2
AI2
AI1
10V
12V
A
V
A
V
V
A
JP7
TOPVERT G1/H1/P1 Series
E-11
FWD
FWD RUN/STOP command
Pr2-00/( FWD RUN/STOP)
REV
REV RUN/STOP command
Pr2-00/( REV RUN/STOP)
DCM
The reference point of digital signal inputs.
The reference of +24V control power supply.
These terminals are isolated from ACM terminal
Totally 2 DCM terminals with same
function.
[MI7]
[Multi-function digital input MI7]
Pr2-26
[MI8]
[Multi-function digital input MI8]
Pr2-27
[MI9]
[Multi-function digital input MI9]
Pr2-28
Relay contact outputs
Separate these control circuit wiring from wiring for other control terminals
R1A
Multi-Function digital output 1
Relay 1 (Relay dry contact output)
R1A-R1C :Relay 1 Normal open (a contact)
R1B-R1C :Relay 1 Normal close (b contact)
Pr2-20,Pr2-21
Resistive Load
5A(N.O.)/3A(N.C.) 240VAC
5A(N.O.)/3A(N.C.) 24VDC
Inductive Load
1.5A(N.O.)/0.5A(N.C.) 240VAC
1.5A(N.O.)/0.5A(N.C.) 24VDC
R1B
R1C
R2A
Multi-Function digital output 2
Relay 2 (Relay dry contact output)
R2A-R2C :Relay 2 Normal open (a contact)
R2B-R2C :Relay 2 Normal close (b contact)
R2B
R2C
Voltage source for digital signal and Frame Ground
(Use the shielded twisted-pair cables to prevent operating faults)
E
Connect to the shield net of shielded twisted-pair
cables (Frame Ground)
24V
Digital control voltage source.
Reference point is DCM
Max. 50mA
DCM
The reference point of digital signal inputs.
The reference of +24V control power supply.
These terminals are isolated from ACM terminal
Totally 2 DCM terminals with same
function.
Analog Inputs and outputs
(Use the shielded twisted-pair cables to prevent operating faults)
+VX
+12V/+10V selectable reference voltage source.
Reference point is ACM.
Max.20mA/(+12V)
-12V
-12V reference voltage source.
Reference point is ACM
Max. 20mA
AI1
Multi-Function analog input 1 (voltage command
or current command selectable)
(when AI1 analog input selector switch to “V” can
accept DC 0~10V voltage signal. when switch to
“I” can accept DC 4(0)~20mA current signal.
Pr3-02/
(DC 0~10V corresponding to the
maximum operation frequency)
AI2
Multi-Function analog input 2 (current command
or voltage command selectable)
(when AI2 analog input selector switch to “V” can
accept DC 0~10V voltage signal. when switch to
“I” can accept DC 4(0)~20mA current signal.
Pr3-06/(4~20mA)
AI3
Multi-Function analog input 3 (accept DC
-10~+10 0~10V voltage signal.)
Pr3-11
ACM
The reference point of analog inputs and outputs
signal.
The reference of reference voltage source.
These terminals are isolated from DCM terminals
TOPVERT G1/H1/P1 Series
E-12
AO1
Multi-Function analog output 1
(can output DC 0~10V voltage signal)
Max.2mA/Pr3-15/
(Output frequency)
AO2
Multi-Function analog output 2 (current signal or
voltage signal selectable)
(when AO2 analog output selector switch to “V”
can output DC 0~10V voltage signal. when
switch to “I” can output DC 4(0)~20mA current
signal.
Pr3-16/(4~20mA )
(Output frequency)
[AO3]
[Multi-Function analog output 3]
(can output DC 4(0)~20mA current signal)
Pr3-15/(4~20mA )
(Output frequency)
Digital outputs and serial port
(Use the shielded twisted-pair cables to prevent operating faults)
MO1
Multi-Function Digital output 3 - MO1
Max.48VDC,50mA/( Pre-set speed
attained 1 (Forward only) )
MO2
Multi-Function Digital output 4 – MO2
Max.48VDC,50mA/
( Drive ready for use)
MCM
Multi-function output terminal – the common end
SG+
RS-485 serial port +
SG-
RS-485 serial port -
[MO3]
[Multi-Function Digital output 5 MO3+]
Pr2-24
[MC3]
[Multi-Function Digital output 5 MO3-]
[MO4]
[Multi-Function Digital output 6 MO4+]
Pr2-25
[MC4]
[Multi-Function Digital output 6 MO4-]
[ ]:Option
Description of the Digital Keypad
Digital Keypad PU-01 function descriptions
FWD
REV
EXT
PU
Part number
Status Display……
……
……
…… Display the driver's current status
When "PU" lights, RUN/STOP is controlled by PU-01.
When "PU" is dark, RUN/STOP is set by Pr0-19.
When "EXT" lights, frequency command is set by Pr0-18.
When "EXT" is dark,frequency command is controlled by PU-01
When "REV" lights, Drive is in reverse operation.
When "FWD" lights, Drive is in forward operation.
Left /Reset key
Moves cursor to the left.
Reset errors.
FWD/REV Direction key
Display Selection key
Changes between different display mode.
STOP key
Programming Unit key
Enable the keypad.
It can determine the source of RUNSTOP
RUN key
PU-01
PU
JOG
DISP
F/R
RUN
STOP
RUN indication
STOP indication
RESET
Main Display
Display the drive status such as frequency,
current, voltage, parameter setting valueand
alarm contents.
Data modification/Program Dial
Rotate to modification for settings, parameters
and output frequency adjustment.
Press to Read or Enter datas
Jog Operation key
Press this key to execute JOG frequency opeation
TOPVERT G1/H1/P1 Series
E-13
Digital Keypad PU-02 function descriptions
It keeped all function in PU-01 and add on Parameter Read/Write/Storage/Copy
function. (Valid for Firmware version 2.xx and after only)
Digital Keypad PU-03 function descriptions
It is an user programmable LCD graphical and text display.
FWD
REV
EXT
PU
PU-02
PU
JOG
DISP
F/R
RUN
STOP
RESET
Read/Save
Press PU and RESET
together to operate
Read and Save functions
100%
FWD
REV
EXT
PU
RESET
Main Display
Display the drive status such as frequency,
current, voltage, parameter setting value
and alarm contents.
Part number
Shift /Reset key
Moves cursor to shift the digit. Reset errors.
FWD/REV Direction key
Display selection key
Changes between different display mode.
STOP key
Jog Operation key
Press this key to execute JOG frequency opeation
RUN key
PU-03
Data modification/Program Dial
Rotate to modification for settings, parameters
and output frequency adjustment.
Press to read or enter data
PU
JOG
DISP
F/R
RUN
STOP
RUN indication
STOP indication
6000.00Hz 9999.99A
6000.00Hz
Status Display……
……
……
…… Display the driver's current status
When "PU" lights, RUN/STOP is controlled by PU-03.
When "PU" is dark, RUN/STOP is set by Pr0-19.
When "EXT" lights, frequency command is set by Pr0-18.
When "EXT" is dark,frequency command Is controlled by PU-03
When " " Is lights:Timer run function is proceeding
When "REV" lights, Drive is in reverse operation.
When "FWD" lights, Drive is in forward operation.
JProgramming Unit key
Enable the keypad.
It can determine the source of Run/Stop
TOPVERT G1/H1/P1 Series
E-14
Explanations of Display Messages
Operation Steps
Selecting display mode
Messages Displayed
Descriptions
Display master frequency command of the drive
(Press the DISP key to read)
Display actual operation frequency output to the motor from the drive
(Press the DISP key to read)
Display output current to motor
(Press the DISP key to read)
Display User-selected content on Pr0-07
(Press the DISP key to read)
Display Read/Save selected content (For PU-02 only)
(Press the DISP key to read)
The specified parameter item
(Rotate and press the dial to modification, read and Enter)
(Press to display those parameters which data are different from
factory default)
Value of the parameter content
(Rotate the dial to modify for setting parameters)
If the “End” message is displayed , for about 1 second, it is an
indication that the data has been accepted and saved to the internal
memory.
RESET
F W D
R E V
E X T
P U
F W D
R E V
E X T
P U
F W D
R E V
E X T
P U
F W D
R E V
E X T
P U
F W D
R E V
E X T
P U
F W D
R E V
E X T
P U
To scrolling between F page, H page, A page and U page by pressing the DISP key
User defined Multi-
Function Display
DISP
Output current to motor
Press
DISP
Actual operation
frequency output to the
motor from the drive
Press
DISP
Master frequency
command of the drive
Press
FWD
REV
EXT
PU
FWD
REV
EXT
PU
FWD
REV
EXT
PU
DISP
Press
FWD
REV
EXT
PU
FW D
RE V
EXT
PU
FW D
R EV
E X T
P U
FW D
R E V
E X T
PU
TOPVERT G1/H1/P1 Series
E-15
Setting parameters (For example, to set Pr0-07 = 2)
To run (For example, to run 50 Hz from PU)
Parameters READ/SAVE Operation (For PU-02 only)
(Parameter copy can execute between same drive model only)
T o ru n se tte d 5 0 .0 0 H z
S e t m a ste r fre q u e n cy
to 5 0 .0 0 H z
(U se le ft ke y fo r q u ick
d a ta e n try)
R U N
P re ss
F W D
R E V
E X T
P U
F W D
R E V
E X T
P U
RESET
T o sh ift d a ta
R o ta te
T o se ttin g d ire ctio n ,
F W D /R E V
F /R
P re ss
F W D
R E V
E X T
P U
T o e n a b le P U
P U
P re ss
F W D
R E V
E X T
P U
T o d isp la y a ctu a lo u tp u t fre q u e n cy
to th e m o to r
D IS P
P re ss
F W D
R E V
E X T
P U
T o settin g p a ram e te r
P o w er-up D ispla y
P ress th en
rotate
F W D
R E V
E X T
P U
M o d ify d ata to 2
P ress th en
rotate
F W D
R E V
E X T
P U
S uccess to se t p a ram e ter.
F W D
R E V
E X T
P U
P ress
P re ss 0.5sec
F W D
R E V
E X T
P U
T o se ttin g pa ra m ete r
F W D
R E V
E X T
P U
D ISP
P re ss tw ice
P ress
F W D
R E V
E X T
P U
S e lect P r 0 -0 7
to b e m od ifie d
Selections:
Read1
Save1
Read2
Save2
Rotate
PU
Press 2 key
simultaneously
RESET
To read parameter
FWD
REV
EXT
PU
To save parameter
PU
Press 2 key
simultaneously
RESET
FWD
REV
EXT
PU
Parameter Save
accomplished
FWD
REV
EXT
PU
Parameter Read
accomplished
FWD
REV
EXT
PU
FWD
REV
EXT
PU
TOPVERT G1/H1/P1 Series
E-16
FUNCTIONS AND PARAMETER SUMMARY
★=This parameter cannot be set
during operation.
◎: Available in Firmware Version
2.xx and after only.
☉: Available in Firmware Version
3.xx and after only.
{ }Parameter no. in
Firmware Version 1.xx
[ ] :optional
Group 0: System parameters
Parame
ters
Functions
Settings
Factory
Setting
User
★
Pr0-00
Model display
Display according to the model number
Read
Only
★
Pr0-01
Rated output current to
motor
Display according to the model number
Read
Only
★
Pr0-02
Parameter Reset (Motor
V/F selecting)
10: Parameter reset for 60Hz - 230/460/575V motor
application
8
9: Parameter reset for 50Hz - 220/380/575V motor
application
8: Parameter reset for 60Hz - 220/380/575V motor
application
7: Parameter reset for 50Hz - 230/460/575V motor
application
6: Parameter reset for 60Hz - 240/415/575V motor
application
◎
5: Parameter reset for 50Hz - 240/415/575V motor
application
◎
Pr0-03
Password Input (The Key)
0~9999
0
Pr0-04
Password set (The Lock)
0~9999
0
Pr0-05
Parameter Locking Level
Bit0
(bxxxx0)
0 All parameters are readable,
b00000
1
Parameters after Pr0-05 cannot
read ”Err” message will displayed
when try to read.
Bit1
(bxxx0x)
0 Enable Frequency Command.
1 Disable frequency command
Bit2
(bxxx0x)
0 Enable run command from PU
1 Disable run command from PU
Pr0-06
Power on display
selection
0: Frequency command value
0
1: Actual output frequency (Hz)
2: Output current
3: User defined contents on Pr0-07
Pr0-07
Versatile display
0: Motor speed (RPM)
0
1: DC-Bus Voltage (Vdc)
2: Actual output voltage (Vac)
3: Output voltage command value (Vac)
4: PID feedback frequency value (Hz)
5: Running step no. of MSS run
6: Sleep time (Pr8-07)
7: Auto-Restart after Fault (Pr6-10)
8: PID frequency command value (Hz)
9: (Factory Reserved)
10: Output power factor angle ( º )
11: Counter value
12: Over-Torque detection time 1 (Pr5-17)
13: (Factory Reserved)
14: Dwell Time at Accel. (Pr6-14)
15: Dwell Time at Decel. (Pr6-16)
16: DC Braking time in Start-up (Pr6-01)
17: DC Braking Time during stop (Pr6-02)
18: Remain time of the executing MSS Run
19: (Factory Reserved)
20: (Factory Reserved)
TOPVERT G1/H1/P1 Series
E-17
21: Accumulated power-up Day (day)
22: Accumulated power-up time (hh:mm)
23: (Factory Reserved)
24: (Factory Reserved)
25: (Factory Reserved)
26: The signal of AI1 analog input (Vdc)
27: The signal of AI2 analog input (mAdc)
28: The signal of AI3 analog input (Vdc)
29: (Factory Reserved)
30~33: (Factory Reserved)
34: Over-Torque detection level 1 (Pr5-16)
35: Motor 1 Auto torque boost (Pr5-01)
36~37: (Factory Reserved)
38: Stall level while run in constant torque area
(Pr5-12)
39〜52: (Factory Reserved)
53: Output power (kW)
54: Output capacity (kVA)
55:(Factory Reserved)
56: The temperature of IGBT module--TH1 ( °C)
57: The temperature of environment or fin (TH2) (°C )
58: (Factory Reserved)
59: (Factory Reserved)
60: Drive overload accumulated time (OL)
61~63:(Factory Reserved)
64: DC Bus voltage upon a fault (Vdc)
65: Output voltage upon a fault (Vac)
66: Output frequency upon a fault (Hz)
67: IGBT module temperature upon a fault ( °C)
◎
68: Output current value upon a fault (Aac)
69︰Temperature of Fin or environment
upon a fault ( °C)
◎
70~86︰(Factory Reserved)
87: DC Bus ripple voltage (Vdc)
◎
88: PG frequency (Hz)
◎
Pr0-08
User-Defined coefficient K
0~39 (no use)
0
40~60000 (the corresponding value for Pr1-00-- the
max. frequency).
Pr0-09
The decimal places
0~3 (0=Without d.p., 1= 1 digit d.p., 2=2 digit d.p.,
3=3 digit d.p.)
0
Pr0-10
Firmware version
Read-only
x.xx
Pr0-11
EPROM store set
Bit0
(bxxxx0)
0
FWD/REV direction command will
be store
b00000
1
FWD/REV direction command not
store
Bit1
(bxxx0x)
0
Frequency command from PU will
be store
1
Frequency command from PU not
store
Bit2
(bxx0xx)
0
RS-485 frequency command will
be store
1
RS-485 frequency command not
store
Bit3
(bx0xxx)
0
Up/Down frequency command will
be store
1
Up/Down frequency command not
store
Bit4
(b0xxxx)
0
Changed parameter will be store
1
Changed parameter not store
TOPVERT G1/H1/P1 Series
E-18
Pr0-12
Auto Accelerate/
Decelerate
0: Linear Acc, linear Dec.
0
1: Auto Acc, linear Dec.
2: Linear Acc, auto Dec.
3: Auto Acc, auto Dec.
4: Linear Acc,/Dec., auto to prevent stall.
★
Pr0-13
Accelerate/ Decelerate
time unit
0: 0.01 Second
0
1: 0.1 Second
2: 1 Second
Pr0-14
PWM Carrier frequency
upper bound
0=0.7kHz
10
1~18kHz
Pr0-15
PWM Carrier frequency
lower bound
0=0.7kHz
10
1~18kHz
Pr0-16
Automatic Voltage
Regulation (AVR)
0: Enable Automatic Voltage Regulation
0
1: Disable Automatic Voltage Regulation
2: Disable Automatic Voltage Regulation while in
decele
Pr0-17
Automatic Energy-Saving
Operation (AESO)
and others
Bit0
(bxxxx0)
0
Disable Automatic Energy-Saving
Operate
b00000
1
Enable Automatic Energy-Saving
Operate
Bit1
(bxxx0x)
0
Allow output voltage over source
voltage
1
Maximum output voltage equals to
source voltage
Bit2
(bxx0xx)
0
For constant torque load application.
1
For variable torque load application.
Bit3
(bx0xxx)
0
Regen-torque no slip compensation
1
Regen-torque with slip compensation
Bit4
(b0xxxx)
0
Low noise mode operation
1
Quiet mode operation
Pr0-18
Source of the frequency
command
0: From PU
0
1: From RS485 communication port
2: From external analog signal
3: From external Up/Down terminals
4: From Pulse input via PG Feedback Card
◎
Pr0-19
Source of the operation
command
0: From RS485 communication port or PU
0
1: From external terminals or PU
2: From PU
3: From external terminals
Pr0-20
Stop/ Run/safety lockout
Bit0
(bxxxx0)
0
Ramp to stop
b00000
1
Coast to stop
Bit1
(bxxx0x)
0
Terminal command not run after
reset
1
Terminal command restart after reset
Bit2
(bxx0xx)
0
Line start Lockout is enabled
1
Line start Lockout is disabled
Bit3
(bx0xxx)
0
FWD/REV go through zero point
1
FWD/REV go not through zero point
Bit4
(b0xxxx)
0
Linear Accel/Decel at high speed
zone
1
S-curve Accel/Decel at high speed
zone
Pr0-21
Direction limit
0: Enable Forward/Reverse operation
0
1: Disable Reverse operation
2: Disabled Forward operation
Pr0-22
Waiting time to restart
after stop
0.00~60.00sec
0.00
TOPVERT G1/H1/P1 Series
E-19
Pr0-23
Cooling fan control & PID
direction
Bit0
(bxxxx0)
0
Fan on while power on
b00000
1
Fan on while run command effect
Bit1
(bxxx0x)
0
(Factory Reserved)
1
Bit2
(bxx0xx)
0
(Factory Reserved)
1
Bit3
(bx0xxx)
0
PID reverse operation allow
1
PID reverse operation not allow
Bit4
(b0xxxx)
0
(Factory Reserved)
1
Pr0-24
Resolution of dial
0=0.01 Hz
1
1=0.10Hz
2=1.00Hz
3=10.00 Hz
★
◎
Pr0-25
Parameter select
0: Team A
0
1: Team B
2: Select Team A or Team B by MI3
Group 1: Basic parameters
Paramet
ers
Functions
Settings
Factory
Setting
User
★
Pr1-00
Maximum operation frequency
3.00~600.00Hz (H1:100. 0 ~6000.0Hz)
60.00/
50.00
★
Pr1-01
1st Frequency 1
(Base frequency 1 ) (Fbase 1)
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
60.00/
50.00
Pr1-02
1st Voltage 1
(Motor rated voltage 1) (Vbase 1)
230V models: 0.0~255.0V
230.0
460V models: 0.0~510.0V
460.0
◎ 575V models: 0.0~637.5V
575.0
★
Pr1-03
2nd Frequency 1
(Middle frequency 1) (Fmid 1)
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
0.50
Pr1-04
2nd Voltage 1
(Middle voltage 1) (Vmid 1)
230V models: 0.0~255.0V
5.0
460V models: 0.0~510.0V
10.0
◎ 575V models:0.0~637.5V
12.5
★
Pr1-05
3rd Frequency 1
(Low-point frequency 1) (Flow 1)
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
0.50
Pr1-06
3rd Voltage 1
(Low-point voltage 1) (Vlow 1)
230V models: 0.0~255.0
5.0
460V models: 0.0~510.0V
10.0
◎ 575V models: 0.0~637.5V
12.5
Pr1-07
0Hz Voltage 1
(Output voltage at 0Hz) (V0Hz 1)
230V models: 0.0~25.5
0.0
460V models: 0.0~51.0V
◎ 575V models: 0.0~63.7V
Pr1-08
Start-up frequency
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
0.50
Pr1-09
Output frequency Upper limit
0.0~150.0% of Maximum operation
frequency (Pr1-00)
110.0
Pr1-10
Output Frequency Lowerl limit
0.0~100.0% of Maximum operation
frequency (Pr1-00)
0.0
Pr1-11
1st Acceleration time
0.00~60000 Sec
##.##
Pr1-12
1st Deceleration time
0.00~60000 Sec
Pr1-13
2nd Acceleration time
0.00~60000 Sec
Pr1-14
2nd Deceleration time
0.00~60000 Sec
Pr1-15
JOG Acceleration time
0.00~60000 Sec
Pr1-16
JOG Deceleration time
0.00~60000 Sec
Pr1-17
JOG frequency
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
6.00
Pr1-18
1st/2nd Acceleration/Deceleration
Switching frequency
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
0.000
TOPVERT G1/H1/P1 Series
E-20
Pr1-19
S-Acc. departure time when
accelerate
0.00~12000 Sec
0.00
Pr1-20
S-Acc. arrival time when
accelerate
0.00~12000 Sec
0.00
Pr1-21
S-Dec. departure time when
decelerate
0.00~12000 Sec
0.00
Pr1-22
S-Dec. arrival time when
decelerate
0.00~12000 Sec
0.00
Pr1-23
{Pr1-29}
Offset voltage while decelerate
230V models: -50.0~50.0 V
0.00
460V models: -100.0~100.0 V
◎575V models: -125.0~125.0 V
★
Pr1-24
{Pr1-23}
Skip Frequency 1 upper limit
0.00~600.00Hz (H1:00.0~6000.0Hz)
0.00
★
Pr1-25
{Pr1-24}
Skip Frequency 1 lower limit
0.00~600.00Hz (H1:00.0~6000.0Hz)
0.00
★
Pr1-26
{Pr1-25}
Skip Frequency 2 upper limit
0.00~600.00Hz (H1:00.0~6000.0Hz)
0.00
★
Pr1-27
{Pr1-26}
Skip Frequency 2 lower limit
0.00~600.00Hz (H1:00.0~6000.0Hz)
0.00
★
Pr1-28
{Pr1-27}
Skip Frequency 3 upper limit
0.00~600.00Hz (H1:00.0~6000.0Hz)
0.00
★
Pr1-29
{Pr1-28}
Skip Frequency 3 lower limit
0.00~600.00Hz (H1:00.0~6000.0Hz)
0.00
★
◎
◎
◎
◎
Pr1-30
Skip Frequency 4 upper limit
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
0.00
★
◎
◎
◎
◎
Pr1-31
Skip Frequency 4 lower limit
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
0.00
★
◎
◎
◎
◎
Pr1-32
Skip Frequency 5 upper limit
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
0.00
★
◎
◎
◎
◎
Pr1-33
Skip Frequency 5 lower limit
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
0.00
★
◎
◎
◎
◎
Pr1-34
Skip Frequency 6 upper limit
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
0.00
★
◎
◎
◎
◎
Pr1-35
Skip Frequency 6 lower limit
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
0.00
★
◎
◎
◎
◎
Pr1-36
1st Frequency 2
(Base frequency 2 ) (Fbase 2)
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
60.00/
50.00
◎
◎
◎
◎
Pr1-37
1st Voltage 2
(Motor rated voltage 2) (Vbase 2)
230V models: 0.0~255.0V
230
460V models: 0.0~510.0V
460
◎575V models:0.0~637.5V
575
★
◎
◎
◎
◎
Pr1-38
2nd Frequency 2
(Middle frequency 2) (Fmid 2)
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
0.50
★
◎
◎
◎
◎
Pr1-39
2nd Voltage 2
(Middle voltage 2) (Vmid 2)
230V models: 0.0~255.0V
5.0
460V models: 0.0~510.0V
10.0
◎ 575V models:0.0~637.5V
12.5
★
◎
◎
◎
◎
Pr1-40
3rd Frequency 2
(Low-point frequency 2) (Flow 2)
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
0.50
★
◎
◎
◎
◎
Pr1-41
3rd Voltage 2
(Low-point voltage 2) (Vlow 2)
230V model: 0.0~255.0V
5.0
460V model: 0.0~510.0V
10.0
◎575V models: 0.0~637.5V
12.5
★
◎
◎
◎
◎
Pr1-42
0Hz Voltage 2
(Output voltage at 0Hz) (V0Hz 2)
230V models: 0.0~25.5
0.0
460V models: 0.0~51.0V
◎ 575V models: 0.0~63.7V
TOPVERT G1/H1/P1 Series
E-21
Group 2: Digital Input/Output parameters
Parame
ters
Functions
Settings
Factory
Setting
User
★ Pr2-00
External operation
0: 2-wire mode 1- FWD/STOP, REV/STOP
0
1: 2-wire mode 2- RUN/STOP, REV/FWD
2: 3-wire mode -RUN,STOP, FWD/REV
★ Pr2-01
Multi-Function Digital input MI1
0: No definition
1
★ Pr2-02
Multi-Function Digital input MI2
1: Multi-step speed command 1
2
★ Pr2-03
Multi-Function Digital input MI3
2: Multi-step speed command 2
3
★ Pr2-04
Multi-Function Digital input MI4
3: Multi-step speed command 3
4
★ Pr2-05
Multi-Function Digital input MI5
4: Multi-step speed command 4
5
★
Pr2-06
[Pr2-26]
[Pr2-27]
[Pr2-28]
Multi-Function Digital input MI6
5: External Reset
14
6: Clear counter
7: 1st and 2nd acceleration/ deceleration time
select
8: Acceleration/deceleration inhibit
9: Force the frequency command from AI1
10: Force the frequency command from AI2
11: Force the frequency command from AI3
12: Emergency stop
13: Disable PID function
14: External fault input (EF)
15: B.B. traces from the bottom upward
16: B.B. traces from the top downward
17: Force operation command to external
18: Cancel the auto acceleration/ deceleration
function
19: FWD JOG command
20: REV JOG command
21: JOG command
22: Cancel PLC Run
23: Pause PLC Run
24: Up command
25: Down command
26: Zero speed is replaced by DC braking
27: Pause
28: Disable dwell function
29: Disable traverse function
30: Disable Speed search during start-up
31: Disable EEPROM write function
32: Counter Trigger input (MI2 only)
33~41: (Factory Reserved)
42: Motor Select
◎
43: Confirm signal of Motor selection
◎
44: Disable reverse operation
◎
45: Disabled forward operation
◎
Pr2-07
Up/Down command mode
Bit 0
(bxxxx0)
0 Up command-Accel by the Acc.
time
b00000
1 Up command-Accel by Pr2-08
setting
Bit 1
(bxxx0x)
0 Down Command-Decel by the Dec.
time
1 Down Command-Decel by Pr2-08
setting
Bit 2
(bxx0xx)
(Factory Reserved)
Bit 3
(bx0xxx)
0 FWD/REV terminals act by edge
trigger
1 FWD/REV terminals act by level
trigger
TOPVERT G1/H1/P1 Series
E-22
Bit 4
(b0xxxx)
0 Allow PG feed-back over
compensation while Accel.
1 Refuse PG feed-back over
compensation while Accel.
Pr2-08
Up/Down command rate
0.01~1.00Hz/msec (10~1000Hz/sec)
0.01
Pr2-09
Digital Input terminal debounce
time
0.001~30.000 Sec
0.005
Pr2-10
Polarity of Digital Input terminals
00000~007FF
h00000
(0=Close circuit enable 1=Open circuit enable)
Pr2-11
Target count value
0~65500
0
Pr2-12
Pre warn count value
0~65500
0
Pr2-13
Digital pulse output gain
1~20
1
Pr2-14
Pre-set arrival frequency 1
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
60.00/
50.00
Pr2-15
Pre-set arrival frequency 1
bandwidth
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
2.00
Pr2-16
Pre-set arrival frequency 2
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
60.00/
50.00
Pr2-17
Pre-set arrival frequency 2
bandwidth
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
2.00
Pr2-18
Polarity of Digital output
terminals
00000~0003F
h00000
◎ Pr2-19
Delay time of Digital output
terminals
0.000~60.000 Sec
0.003
Pr2-20
{Pr2-19}
Multi-Function Digital output 1-
Relay 1
0: No definition
11
Pr2-21
{Pr2-20}
Multi-Function Digital output 2 -
Relay 2
1: Drive in run
1
Pr2-22
{Pr2-21}
Multi-Function Digital output 3 -
MO1
2: Master frequency attained 1
(Both Forward and Reverse)
5
Pr2-23
{Pr2-22}
Multi-Function Digital output 4 -
MO2
3: Master frequency attained 2
(Both Forward and Reverse)
9
◎
◎
◎
◎ Pr2-24
[Multi-Function Digital output 5 -
MO3]
4: Pre-set speed attained 1
(Both Forward and Reverse)
0
◎
◎
◎
◎ Pr2-25
[Multi-Function Digital output 6 -
MO4]
5: Pre-set speed attained 1 (Forward only)
0
6: Pre-set speed attained 2
(Both Forward and Reverse)
0
7 : Pre-set speed attained 2 (Forward only)
8: Drive in decel
9: Drive ready for operate
10: Low voltage alarm (LU, LUr)
11: Fault Indication
12: Base block (B.B.) Indication
13: Zero Speed (including shutdown)
14: Zero speed (while in run)
15: Terminal count value attained
16: Pre warn count value attained
17: PLC Run running
18: PLC Run paused
19: A step of PLC Run completed
20: PLC Run completed
21: OH1 pre–warning indication
22: Dwell Accel/Decel in execution
23: External operation mode indication
24: Over-torque 1 (ot1)
25: Digital frequency output (MO2 only)
26: Software brake output (MO1 only)
27: Auxiliary Motor no. 1
28: Auxiliary Motor no. 2
29: Auxiliary Motor no. 3
TOPVERT G1/H1/P1 Series
E-23
30: Over-torque 2 (ot2)
◎
31: OH2 pre–warning indication
◎
32: Motor selection output (Pr5-49)
◎
33~47: (Factory Reserved)
48: Master speed executing
49: PLC Run step 1 executing
50: PLC Run step 2 executing
51: PLC Run step 3 executing
52: PLC Run step 4 executing
53: PLC Run step 5 executing
54: PLC Run step 6 executing
55: PLC Run step 7 executing
56: PLC Run step 8 executing
57: PLC Run step 9 executing
58: PLC Run step 10 executing
59: PLC Run step 11 executing
60: PLC Run step 12 executing
61: PLC Run step 13 executing
62: PLC Run step 14 executing
63: PLC Run step 15 executing
64~79: (Factory Reserved)
◎
◎
◎
◎ Pr2-26
[Multi-Function Digital input MI7]
Same as Pr2-01~Pr2-06
0
◎
◎
◎
◎ Pr2-27
[Multi-Function Digital input MI8]
◎
◎
◎
◎ Pr2-28
[Multi-Function Digital input MI9]
Group 3: Analog Input/Output parameters
Parame
ters
Functions
Settings
Factory
Setting
User
Pr3-00
Addition Function of the Analog
Inputs
0: Enable addition function
0
1: Disable addition function
Pr3-01
Analog input noise filter time
0.00~2.00 sec
0.10
Pr3-02
Valid
for
AI2
(Pr3-0
6)
and
AI3
(Pr3-1
1)
AI1 Analog Input
0: No functions
1
1: Frequency command
2: To adjust 1st Acceleration/deceleration time)
(same as Pr1-11, Pr1-12)
3: Over Current stall prevention level during
constant speed run on the constant torque region
(same as Pr5-12)
4: Over Current stall prevention level during accel
on the constant torque region (same as Pr5-10)
5: Over-Torque detection level 1 (ot1)
(same as Pr5-16)
6: Motor 1 Torque boost level (same as Pr5-01)
7: Auxiliary command when main frequency
command is AI1 only
8: Auxiliary command when main frequency
command is AI2 only
9: Auxiliary command when main frequency
command is AI3 only
10: Auxiliary command of master frequency
command
11: PID feedback signal
12: PID offset signal (same as Pr7-05)
13: DC Braking current level (same as Pr6-00)
14: Voltage adjusts during run. (AI1 Pr3-02 only)
15: External temperatures signal
Pr3-03
AI1 analog Input bias
-10.00~10.00V
0.00
Pr3-04
AI1 analog Input gain
-500.0~+500.0%
100.0
TOPVERT G1/H1/P1 Series
E-24
Pr3-05
AI1 analog Input bias mode
0: Zero bias
0
1: Value lower than bias = bias
2: Value higher than bias = bias
3: The absolute value of the bias voltage while
serving as the center
Pr3-06
AI2 Analog Input (see Pr3-02)
Same as Pr3-02
0.00
Pr3-07
AI2 analog Input bias
0.00~20.00mA
4.00
Pr3-08
AI2 analog Input gain
-500.0~+500.0%
100.0
Pr3-09
AI2 analog Input bias mode
0:Zero bias
1
1: Value lower than bias = bias
2: Value higher than bias = bias
3: The absolute value of the bias voltage while
serving as the center
Pr3-10
Loss of the AI2 signal
0: Disabled
0
1: Continue operation by the last frequency command
2: Decelerate to stop
3: Coast to stop and display AcI.
Pr3-11
AI3 Analog Input (see Pr3-02)
(Same as Pr3-02)
0.00
Pr3-12
AI3 analog Input bias
-10.00~10.00V
0.00
Pr3-13
AI3 analog Input gain
-500.0~+500.0%
100
Pr3-14
AI3 analog Input bias mode
0: Zero bias
0
1: Value lower than bias = bias
2: Value higher than bias = bias
3: The absolute value of the bias voltage while
serving as the center
Pr3-15
Analog output 1 function (AO1)
0: Output frequency (Hz)
0
Pr3-16
Analog output 2 function (AO2)
1: Command frequency (Hz)
0
2: Motor Speed
3: Output current (A rms)
4: Output voltage (VAC)
5: DC BUS voltage (VDC)
6: Power factor
7: Power
8: AI1 (V)
9: AI2 (mA)
10: AI3 (V)
11~12: (Factory Resewrved)
13: Output voltage command
14: Counter Value
15: User defined value on Pr3-21
16~23: (Factory Reserved)
24: Define to digital output (MOx)
◎
◎
◎
◎
Pr3-17
AO1 Analog output gain
-900.0~900.0%
100.0
Pr3-18
AO2 Analog output gain
-900.0~900.0%
80.0
Pr3-19
AO1 Analog output bias
-10.00~10.00V
0.00
Pr3-20
AO2 Analog output bias
0.00~20.00mA
4.00
Pr3-21
User defined analog output
value
0.0~100.0%
0.0
Group 4: Multi-Step Speed and Process Logic Control operation parameters
Parame
ters
Functions
Settings
Factory
Setting
User
Pr4-00
The 1st step speed of PLC Run or MSS Run
0.00~600.00 Hz
(H1:00.0 ~6000.0Hz)
0.00
Pr4-01
The 2nd step speed of PLC Run or MSS Run
0.00~600.00 Hz
(H1:00.0 ~6000.0Hz)
0.00
Pr4-02
The 3rd step speed of PLC Run or MSS Run
0.00~600.00 Hz
(H1:00.0 ~6000.0Hz)
0.00
TOPVERT G1/H1/P1 Series
E-25
Pr4-03
The 4th step speed of PLC Run or MSS Run
0.00~600.00 Hz
(H1:00.0 ~6000.0Hz)
0.00
Pr4-04
The 5th step speed of PLC Run or MSS Run
0.00~600.00 Hz
(H1:00.0 ~6000.0Hz)
0.00
Pr4-05
The 6th step speed of PLC Run or MSS Run
0.00~600.00 Hz
(H1:00.0 ~6000.0Hz)
0.00
Pr4-06
The 7th step speed of PLC Run or MSS Run
0.00~600.00 Hz
(H1:00.0 ~6000.0Hz)
0.00
Pr4-07
The 8th step speed of PLC Run or MSS Run
0.00~600.00 Hz
(H1:00.0 ~6000.0Hz)
0.00
Pr4-08
The 9th step speed of PLC Run or MSS Run
0.00~600.00 Hz
(H1:00.0 ~6000.0Hz)
0.00
Pr4-09
The 10th step speed of PLC Run or MSS Run
0.00~600.00 Hz
(H1:00.0 ~6000.0Hz)
0.00
Pr4-10
The 11th step speed of PLC Run or MSS Run
0.00~600.00 Hz
(H1:00.0 ~6000.0Hz)
0.00
Pr4-11
The 12th step speed of PLC Run or MSS Run
0.00~600.00 Hz
(H1:00.0 ~6000.0Hz)
0.00
Pr4-12
The 13th step speed of PLC Run or MSS Run
0.00~600.00 Hz
(H1:00.0 ~6000.0Hz)
0.00
Pr4-13
The 14th step speed of PLC Run or MSS Run
0.00~600.00 Hz
(H1:00.0 ~6000.0Hz)
0.00
Pr4-14
The 15th step speed of PLC Run or MSS Run
0.00~600.00 Hz
(H1:00.0 ~6000.0Hz)
0.00
Pr4-15
The duration of master speed
0.0~65500 Sec
0.0
Pr4-16
The 1st step duration of PLC Run or MSS Run
0.0~65500 Sec
0.0
Pr4-17
The 2nd step duration of PLC Run or MSS Run
0.0~65500 Sec
0.0
Pr4-18
The 3rd Step duration of PLC Run or MSS Run
0.0~65500 Sec
0.0
Pr4-19
The 4th Step duration of PLC Run or MSS Run
0.0~65500 Sec
0.0
Pr4-20
The 5th Step duration of PLC Run or MSS Run
0.0~65500 Sec
0.0
Pr4-21
The 6th Step duration of PLC Run or MSS Run
0.0~65500 Sec
0.0
Pr4-22
The 7th Step duration of PLC Run or MSS Run
0.0~65500 Sec
0.0
Pr4-23
The 8th Step duration of PLC Run or MSS Run
0.0~65500 Sec
0.0
Pr4-24
The 9th Step duration of PLC Run or MSS Run
0.0~65500 Sec
0.0
Pr4-25
The 10th Step duration of PLC Run or MSS Run
0.0~65500 Sec
0.0
Pr4-26
The 11th Step duration of PLC Run or MSS Run
0.0~65500 Sec
0.0
Pr4-27
The 12th Step duration of PLC Run or MSS Run
0.0~65500 Sec
0.0
Pr4-28
The 13th Step duration of PLC Run or MSS Run
0.0~65500 Sec
0.0
Pr4-29
The 14th Step duration of PLC Run or MSS Run
0.0~65500 Sec
0.0
Pr4-30
The 15th Step duration of PLC Run or MSS Run
0.0~65500 Sec
0.0
Pr4-31
The PLC Run or MSS Run time multiplier
1~10
1
Pr4-32
The PLC Run or MSS Run operation direction of
each step
00000~07FFF
(0:forward;1:reverse)
h00000
Pr4-33
PLC Run operation mode
Bit 0
(bxxxx0)
0
Direction
determined by
Pr4-32
b01000
1
Direction
determined by the
master speed
Bit 1
(bxxx0x)
0
Without zero
intervals
(Continue mode)
1
With zero
intervals (Stop
mode)
Bit 2
(bxx0xx)
0
Run zero speed
when PLC Run
Paused
1
Run original
TOPVERT G1/H1/P1 Series
E-26
programmed step
speed when PLC
Run Paused
Bit 3
(bx0xxx)
0
Re-Execute PLC
Run from step 0
after recover from
power interruption
1
Continue Execute
PLC Run from the
point which power
interrupted after
recover from
power interruption
Pr4-34
PLC Run operation cycle
0~60000 : 0~60000 cycle
0
0= PLC Run disabled
60001: Continuously execute
recurring cycles
Pr4-35
What to do after PLC Run completed
0~15:step speed
(0=master speed)
16
16:stop
Pr4-36
Multi-Step Speed Run (MSS RUN) operation
mode
Bit 0
(bxxxx0)
0
Direction
determined by
Pr4-32
b00001
1
Direction
determined by the
master speed
Bit 1
(bxxx0x)
0
Duration of MSS
Run determined
by Mix terminals.
1
Duration of MSS
Run determined
by Pr4-15~Pr4-30
setting.
Bit 2
(bxx0xx)
0
Without zero
intervals
(Continue mode)
1
With zero
intervals (Stop
mode)
Bit 3
(bx0xxx)
0
Jog command
ineffective during
Run
1
Jog command
effective during
Run
Group 5: Motor parameters and protection parameters
Paramet
ers
Functions
Settings
Factory
Setting
User
★
Pr5-00
Full-Load Current of Motor 1
Amp (10~120% of drive’s rated current)
##.##
Pr5-01
Auto Torque Compensation of Motor 1
0.0~25.0%
0.0
Pr5-02
Slip Compensation of Motor 1
0~20 RPM
0
Pr5-03
Number of Motor Poles 1
2~20
4
Pr5-04
Rotor Resistance R1 of Motor 1
0.000~65.535 Ω
0
★
Pr5-05
Auto-tuning & control mode selection
0: No function
0
1: To execute auto-tuning and switch to
Sensorless vector control mode
2: Reset to V/F control mode
★
Pr5-06
Low Voltage Level l
230V models: 160~220VAC
180
460V models: 320~440VAC
360
◎ 575V models: 400~550VAC
450
TOPVERT G1/H1/P1 Series
E-27
★
Pr5-07
Over-Voltage Stall Prevention Level
230V models: 320~500VDC
380
460V models: 640~1000VDC
760
◎ 575V models: 800~1250VDC
950
Pr5-08
Software Braking Level
230V models: 320~500VDC
373
460V models: 640~1000VDC
746
◎ 575V models: 800~1250VDC
932
Pr5-09
Phase-Loss Protection
0: Warn and keep operation (below 50%)
0
1: Warn and ramp to stop
2: Warn and coast to stop
Pr5-10
Over- Current Stall Prevention level
during accel on the constant torque
region
Amp (10~250% of drive’s rated current)
##.##
Pr5-11
Over- Current Stall Prevention low-limit
level during accel on the constant
power region
Amp (0~250% of drive’s rated current)
##.##
Pr5-12
Over-Current Stall Prevention level
during constantant speed on the
constant torque region Operation
Amp (10~250% of drive’s rated current)
##.##
Pr5-13
Over- Current Stall Prevention low-limit
level during constant speed run on the
constant power region
Amp (0~250% of drive’s rated current)
##.##
Pr5-14
Over-Current Deceleration Time during
Operation
0.050~600.00 Sec
3.00
Pr5-15
Over-Torque Detection Selection 1
(ot1)
0:Disabled
0
1:Over-torque detection during constant
speed operation, stop operation after
detection.
2:Over-torque detection during constant
speed operation, continue to operate
after detection.
3:Over-torque detection during operation,
stop operation after detection
4:Over-torque detection during operation,
continue operation after detection.
Pr5-16
Over-Torque Detection Level 1 (ot1)
Amp(10~250% of drive’s rated current)
##.##
Pr5-17
Over-Torque Detection Time 1 (ot1)
0.0~60.0 Sec
0.1
Pr 5-18
Motor 1- Electronic Thermal Relay
Selection (oL1)
0:Electronic thermal relay function
disabled
0
1:Inverter duty motor
(with independent cooling fan)
2:Standard motor
(with shaft mounted cooling fan)
Pr5-19
Motor 1- Electronic Thermal Relay
Characteristic
30~600 Sec
60
Pr5-20
IGBT Over-Heat pre–warning setting
(oH2)
0.0~110.0
85.0
Pr5-21
Over-Torque Detection Selection 2
(ot2)
0: Disabled
0
1: Over-torque detection during constant
speed operation, stop operation after
detection.
2: Over-torque detection during constant
speed operation, continue to operate
after detection.
3: Over-torque detection during entire
(acceleration, steady state,deceleration)
operation, stop operation after detection
4: Over-torque detection during entire
(acceleration, steady state,deceleration)
operation, continue operation after
detection.
Pr5-22
Over-Torque Detection Level 2 (ot2)
Amp(10~250% of drive’s rated current)
##.##
TOPVERT G1/H1/P1 Series
E-28
Pr5-23
Over-Torque Detection Time 2 (ot2)
0.0~60.0 Sec
0.1
Pr5-24
{Pr5-21}
Most Recent Fault Record
0: no fault
0
Pr5-25
{Pr5-22}
2nd Most Recent Fault Record
1: oC (over-current)
Pr5-26
{Pr5-23}
3rd Most Recent Fault Record
2: oU (over-voltage)
Pr5-27
{Pr5-24}
4th Most Recent Fault Record
3: GF (ground fault)
◎
Pr5-28
5th Most Recent Fault Record
4: SC (IGBT failure)
◎
Pr5-29
6th Most Recent Fault Record
5: oL (drive overload)
◎
Pr5-30
7th Most Recent Fault Record
6: oL1 (electronic thermal relay 1)
◎
Pr5-31
8th Most Recent Fault Record
7: ot1 (Over-Torque1)
◎
Pr5-32
9th Most Recent Fault Record
8: oCn
(over-current during constant speed)
◎
Pr5-33
10th Most Recent Fault Record
9: oCA (over-current during accel.)
◎
Pr5-34
11th Most Recent Fault Record
10: oCd (over-current during decel.)
◎
Pr5-35
12th Most Recent Fault Record
11: EP1 (EPROM error 1)
◎
Pr5-36
13th Most Recent Fault Record
12: EP2 (EPROM error 2)
◎
Pr5-37
14th Most Recent Fault Record
13: EF (external fault)
◎
Pr5-38
15th Most Recent Fault Record
14: Ct1 (current sensor 1)
◎
Pr5-39
16th Most Recent Fault Record
15: Ct2 (current sensor 2)
16: HPF (protection circuit fault)
17: oH1 (IGBT overheat)
18: oH2 (Heatsink overheat)
19: SoFt (Pre-charge circuit error)
20: ACI. (AI2 error)
21: ASC (RS-485 error)
22: PI.d (PID error)
23: Pu(Keypad communication overtime)
24: tunE (Auto tuning failure)
25: bF (braking chopper failure)
26: PG (PG error)
27: PHL
(Phase-Loss protect or capacitor aged)
28: CC (current signal error during stop)
29: CPu (CPU error)
30: FAn (Fan failure)
31: AnI fault (Analog input error)
32: ot2 (Over-Torque2)
◎
33: oL2 (electronic thermal relay 2)
◎
34: rnot (Motor selection error)
◎
36: LUr (Low Voltage during Run)
◎
37: oUd (over-voltage during decel)
38: `x CoPY (Parameter copy error)
◎
39: LU (Low Voltage)
40: bb (External Base Block )
★
◎
Pr5-40
Full-Load Current of Motor 2
Amp (10~120% of drive’s rated current)
##.##
◎
Pr5-41
Auto Torque Compensation of Motor 2
0.0~25.0%
0.0
◎
Pr5-42
Slip Compensation of Motor 2
0~20 RPM
0
◎
Pr5-43
Number of Motor Poles 2
2~20
4
◎
Pr5-44
Rotor Resistance R1 of Motor 2
0.000~65.535 Ω
0
◎
Pr5-45
Motor 2- Electronic Thermal Relay
Selection (oL2)
0: Electronic thermal relay function
disabled
0
1: Inverter duty motor
(with independent cooling fan)
2: Standard motor
(with shaft mounted cooling fan)
TOPVERT G1/H1/P1 Series
E-29
◎
Pr5-46
Motor 2- Electronic Thermal Relay
Characteristic
30~600 Sec
60
◎
Pr5-47
Heatsink Over-Heat pre–warning
setting (oH2)
0.0~110.0 ℃
85.0
◎
Pr5-48
Delay Time for Motor Selection
0.00~60.00 Sec
0.05
◎
Pr5-49
Motor selection mode
Bit 0
(bxxxx0)
0
Cannot be switch during
operation.
b00000
1
Can be switch during
operation.
Bit 1
(bxxxx0)
0
No need to waiting for
confirm signal when
switching
1
Need to waiting for
confirm signal when
switching
Group 6: Special Parameters
Parame
ters
Functions
Settings
Factory
Setting
User
Pr6-00 DC Braking Current Level
Amp (0~125% of drive’s rated current)
##.##
Pr6-01
DC Braking Time during
Start-up
0.00~60.00 Sec
0.00
Pr6-02
DC Braking Time during
stopping
0.00~60.00 Sec
0.00
Pr6-03
Start-point for DC Braking
during stopping
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
0.00
Pr6-04 Increasing Rate of the DC
Braking Voltage
0.01~300.00%
20.00
Pr6-05
Momentary Power Loss
Operation Selection
0:Operation stops after momentary power loss.
0
1:Operation continues after momentary power loss,
speed search Speed Search starts with Last
Output Frequency Downward
2:Operation continues after momentary power loss,
speed search starts with the Start-up frequency
Upward
Pr6-06
Maximum Allowable Power
Loss Time
0.1~5.0 Sec
2.0
Pr6-07
Base-Block Time for Speed
Search (BB)
0.1~5.0 Sec
0.5
Pr6-08
Maximum Current Level for
Speed Search
Amp(20~200% of drive’s rated current)
##.##
Pr6-09
Deceleration Time for Speed
Search
0.50~120.00 Sec
3.00
Pr6-10
Auto Restart after Fault
0~30 times
0
Pr6-11
Speed Search during Start-up
0:speed search disabled
0
1:speed search through the frequency command
2:FWD-speed search only
(motor only runs in FWD direction)
3:REV-speed search only
(motor only runs in REV direction)
4:FWD/REV speed search enabled in both directions
(FWD first)
5:REV/FWD speed search enabled in both directions
(REV first)
Pr6-12
Speed Search Frequency
(FWD direction)
0.00~600.00 Hz (H1:00.0~6000.0Hz)
60.00/
50.00
Pr6-13
Speed Search Frequency
(REV direction)
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
60.00/
50.00
Pr6-14
Dwell Time at Accel.
0.00~60.00 Sec
0.00
TOPVERT G1/H1/P1 Series
E-30
Pr6-15
Dwell Frequency at Accel.
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
6.00
Pr6-16
Dwell Time at Decel.
0.00~60.00 Sec
0.00
Pr6-17
Dwell Frequency at Decel.
0.00~600.00 Hz (H1:00.0~6000.0Hz)
6.00
Pr6-18
Dwell Frequency current
Amp (0~150% of rated current)
##.##
Pr6-19
Traverse Skip Frequency
0.00~100.00Hz
0.00
Pr6-20
The Amplitude of traverse
0.00~200.00Hz
0.00
Group 7: High-function Parameters (PID and Communication)
Parame
ters
Functions
Settings
Factory
Setting
User
Pr7-00
Proportional Gain (P)
0.0~500.0%
80.0
Pr7-01
Integral Time (I)
0.00~100.00 Sec
1.00
0.00:no integral
Pr7-02
Derivative Control (D)
0.00~5.00 Sec
0.00
Pr7-03
Upper limit for Integral Control
0.0~100.0%
100.0
Pr7-04
PID Output Frequency Limit
0.0~100.0%
100.0
Pr7-05
PID Offset
-100.0~+100.0%
0.0
Pr7-06
Primary Delay Filter Time
0.000~0.100 Sec
0.000
Pr7-07
PID Feedback Signal Detection Time
0.0~6000.0 Sec
0.0
Pr7-08
Treatment of the Erroneous PID
Feedback Signals
0: warn and keep operating
0
1: warn and RAMP to stop
2: warn and COAST to stop
Pr7-9
Treatment of Keypad Transmission
Fault
0: Warn and RAMP to stop
0
1: Warn and COAST to stop
Pr7-10
Keypad Transmission Fault detection
0.0: Disable and keep operating
0.0
0.1~60.0 Sec
Pr7-11
Communication Address
1~254
1
Pr7-12
Transmission Speed (Baud rate)
1.2~125 Kbps
9.6
Pr7-13
Transmission Fault Treatment
0: warn and keep operating
3
1: warn and RAMP to stop
2: warn and COAST to stop
3: No warning and keep operating
Pr7-14
Time-out Detection
0.0: disabled
0.0
0.1~60.0 Sec
Pr7-15
Communication Protocol
0:7,N,2 ASCII
0
1:7,E,1 ASCII
2:7,O,1 ASCII
3:7,E,2 ASCII
4:7,O,2 ASCII
5:8,N,1 ASCII
6:8, N,2 ASCII
7:8,E,1 ASCII
8:8,O,1 ASCII
9:8,E,2 ASCII
10:8,O,2 ASCII
11:8,N,1 RTU
12:8,N,2 RTU
13:8,E,1 RTU
14:8,O,1 RTU
15:8,E,2 RTU
16:8,O,2 RTU
TOPVERT G1/H1/P1 Series
E-31
Group 8: Fan & Pump Control Parameters
Paramet
ers
Functions
Settings
Factory
Setting
User
★
Pr8-00
V/F Curve Selection
0: V/F Curve determined by Parameter Group 1
0
1: 1.5 Power Curve
2: Square Power Curve
Pr8-01
Start-Up Frequency of the
Auxiliary Motor
0.00~600.00 Hz (H1:00.0 ~6000.0Hz)
0.00
Pr8-02
Stop Frequency of the Auxiliary
Motor
5.00~600.00 Hz (H1:50.0 ~6000.0Hz)
5.00
Pr8-03
Time Delay before Stopping the
Auxiliary Motor
0.0~6000.0 Sec
0.00
Pr8-04
Time Delay before Stopping the
Auxiliary Motor
0.0~6000.0 Sec
0.00
Pr8-05
Sleep Frequency
0.00~600.00 Hz (H1:00.0~6000.0Hz)
0.00
Pr8-06
Wake-up Frequency
0.00~600.00 Hz (H1:00.0~6000.0Hz)
0.00
Pr8-07
Sleep Time
0.0~6000.0 Sec
0.0
Group 9: Speed Feedback Control Parameters
(A PG Feedback Card (optional) is necessary for setting those parameters)
Parameters
Functions
Settings
Factory
Setting
User
★
Pr9-00
PG Pulses
1~5000 PPR
1024
★
Pr9-01
PG Type and Function setting
0 : Disable PG
0
1: Bidirection, Phase A leads in a forward
run command and phase B leads in a
reverse run command
2: Bidirection, Phase B leads in a forward
run command and phase A leads in a
reverse run command
4: As PID feedback (REV)
5: As PID feedback (FWD)
8: Frequency command (REV) ( Pr0-18=4 )
9: Frequency command (FWD) ( Pr0-18=4 )
★
Pr9-02
PG Speed Feedback Display
Filter
0.000~1.000sec
0.03
Pr9-03
PG feedback speed control
Proportional Gain (P)
0.0~500.0%
20.0
Pr9-04
PG feedback speed control
Integral Time (I)
0.00~10.00 Sec
0.50
0.00 : no integral
Pr9-05
PG feedback speed control
Differential (D) Time
0.00~5.00 Sec
0.00
Pr9-06
PG Speed Control Output
Frequency Limit
0.00~150.00Hz
20.00
Pr9-07
Treatment of PG Feedback Fault
0: warn and keep operating
0
1: warn and RAMP to stop
2: warn and COAST to stop
Pr9-08
PG Feedback Fault Detection
Time
0.00~10.00 Sec
0.10
Pr9-09
PG Feedback compensation limit
0~900 RPM
90
TOPVERT G1/H1/P1 Series
E-32
ERROR MESSAGE AND TROUBLESHOOTING
The drive has a comprehensive fault diagnostic system that includes various alarms and fault
messages such as over-voltage, low-voltage and over-current….etc. Once a fault is detected, the
corresponding protective functions will be activated, and the drive will stop the output and the motor
will then coast to stop. The following faults are displayed as shown on the drive digital keypad panel.
Once the fault occurred, eliminate it first, and wait for 5 seconds (oC,GF,SC are 60 seconds) then
execute RESET action to reactivate the operation.
User may either by depress RESET key on the keypad or apply a external reset signal from Mix to
execute RESET action.
Problems and Solutions
Fault symbol
Fault descriptions
(Name) {Error code}
Treatments
Over- current
(oC) {01}
The drive detects an
abnormal increase in output
current.
Check the wiring connections between the drive and
motor for possible short circuits.
Increase the Acceleration time (Pr1-11, Pr1-12)
Check for possible excessive loading conditions at the
motor.
Replace the drive with the next higher power model
Wait for 60 seconds then execute RESET action to
reactivate the operation.
Over-voltage on DC-Bus
(oU) {02}
The drive detects that the DC
bus voltage has exceeded its
maximum allowable value.
115/230 V class: about 400V
460 V class: about 800V
575 V class: about 1040V
Check whether the input voltage falls within the rated
drive input voltage range.
Check for possible voltage transients.
If DC Bus over-voltage due to regenerative voltage,
please increase the Deceleration time or add an brake
unit and brake resistor (optional)
Over-voltage on DC-Bus
during deceleration
(oUd) {37}
The drive detects that the DC
bus voltage has exceeded its
maximum allowable value
while in deceleration.
115/230 V class: about 400V
460 V class: about 800V
575 V class: about 1040V
Check whether the input voltage falls within the rated
drive input voltage range.
If DC Bus over-voltage due to regenerative voltage,
please increase the Deceleration time or add an brake
unit and brake resistor (optional)
Check whether the required braking power is within
the specified limits.
Ground fault (GF) {03}:
When (one of) the output
terminal(s) is grounded, short
circuit current is more than
50% of drive rated current,
the drive power module may
be damaged.
NOTE: The Ground fault
protection is provided for
drive protection, not for
protection of the user..
Check the wiring connections between the drive and
motor for possible short circuits, also to ground
Check whether the IGBT power module is damaged.
Check for possible poor insulation at the output line
Wait for 60 seconds then execute RESET action to
reactivate the operation.
TOPVERT G1/H1/P1 Series
E-33
IGBT fault (SC) {04}
IGBT module switching failure
is detected.
Check whether the motor’s resistance and insulation
are functioning right
Check whether the connection to the motor is short
circuited
Disconnect the cable between the drive and
motor,then run again, If the fault code is still displayed
then IGBT module should be failure---please return to
the factory
Wait for 60 seconds then execute RESET action to
reactivate the operation.
Drive overload (Ol) {05}
The drive detects excessive
drive output current.
G1, H1 Series: The drive can
withstand up to 150 % of the
rated current for a maximum
of 60 seconds.
P1 Series: The drive can
withstand up to 125% of the
rated current for a maximum
of 60 seconds.
Check whether the motor is overloaded
Reduce torque compensation setting as set in Pr5-01
Increase the acceleration time
Replace the drive with the next higher power model
Motor overload
-Thermal relay 1
(oL1) {06}
(Electronic thermal relay 1
protection.)
Check whether the motor 1 V/F setting proper
Check whether the motor 1 running low speed for
long period
Check for possible motor 1 overload
Check motor 1 full load current (Pr5-00)
Check electronic thermal overload 1 setting (Pr5-18 to
Pr5-19)
Reduce the load so that the drive output current does
not exceed the value set on Pr5-00
Increase motor capacity
Over-Torque1 detected
(ot1) {07}
Check whether the motor 1 is overloaded
Check whether motor 1 rated current setting (Pr5-00)
is suitable
Check whether the Over-Torque1 detect parameter
are suitable (Pr5-15~Pr5-17)
Check whether the mechanical system is normal
Increase motor 1 capacity and replace the drive with
the next higher power model
Over-current during constant
speed
(oCn) {08}
Check for possible poor insulation at the output wires
Check for possible motor stall
Replace the drive with the next higher power model.
Over-current during
acceleration
(oCA) {09}
Check for possible poor insulation at the output wires
Decrease the torque boost setting in Pr5-01
Increase the acceleration time
Replace the drive with the next higher power model.
Over-current during
deceleration
(oCd) {10}
Check for possible poor insulation at the output wires
Increase the deceleration time
Replace the drive with the next higher power model
EPROM read error
(EP1) {11}
Check whether the power voltage falls within the rated
voltage
TOPVERT G1/H1/P1 Series
E-34
EPROM write error
(EP2) {12}
Switch off power supply wait until display off then on
again.
Reset drive to factory defaults, return to the factory if
not working
External fault (EF) {13}
(one of Pr2-01~Pr2-06 or
Pr2-26~Pr2-28 =14 and act)
Give RESET command after fault has been cleared
Input
U phase current sensor A/D
fault
(Ct1) {14}
Switch off power supply wait until display off then on
again ,If fault code is still displayed please return to
the factory.
Eplace a control board or U phase current sensor
W phase current sensor A/D
fault
(Ct2) {15}
Switch off power supply wait until display off then on
again ,If fault code is still displayed please return to
the factory.
Eplace a control board or W phase current sensor
Hardware protection loop fault
(HPF) {16}
Switch off power supply wait until display off then on
again ,If fault code is still displayed please return to
the factory.
IGBT overheat
(oH1) {17}
IGBT temperature exceeds
protection level
Check the cooling fan and clean it
Ensure that the ambient temperature falls within the
specified
Remove any foreign objects on the heat sinks and
check for possible dirty heat sink fins.
Make sure that the ventilation path is not obstructed.
Provide enough spacing for adequate ventilation.
Environment overheat
(oH2) {18}
The drive temperature sensor
detects excessive heat on
environment.
Ensure that the ambient temperature falls within the
specified
Provide enough spacing for adequate ventilation.
Ensure that the cabinet ventilation path is not
obstructed where the drive is installed.
Inrush limit circuit fault
(SoFt) {19}
Switch off power supply wait until display off then on
again, If fault code is still displayed please return to
the factory.
Analog input signal lost
(ACI.) {20}
Check if the ACI signal is less than 4mA
Check the AI2 wiring
RS-485 serial port time-out
(ASC) {21}
Check the RS-485 wiring
PID feedback error
(PI.d) {22}
Check the PID feedback wiring
Check the PID parameters settings
Check if parameters are properset when it is PG
feedback control.
PU communication error
(Pu) {23}
Check whether the keypad communication circuit is
well-conducted
Auto tuning failure
(tunE) {24}
Check cabling between drive and motor.
Check whether the motors horsepower corresponds to
the drive output power.
Retry again
TOPVERT G1/H1/P1 Series
E-35
Braking chopper fault
(bF) {25}
Switch off power supply wait until display off then on
again, If fault code is still displayed please return to
the factory.
PG error
(PG) {26}
Check the wiring of the PG feedback.
Check whether the motor is blocked
Phase-Loss protect or
capacitor aged
(PHL) {27}
Three phase imbalanced at
the input voltage or the drive
detects excessive ripple
voltage on DC-Bus
Caused of power source:
Check whether the power voltage is normal
Check whether the screw at the input power terminal
is tightened
Check whether the power source phase-lacking
Caused of smoothing capacitor:
Check whether the smoothing capacitors life is ended.
Current signal error during
stop
(CC) {28}
Reset the drive, if okay, then might be interference
noise come into the drive.
Return to the factory if previous method is not effect.
CPU error
(CPu) {29}
Electronics Circuit Fault
Switch off power supply wait until display off then on
again, If fault code is still displayed please return to
the factory.
Fan fault
(FAn) {30}
Check whether the cooling fan is blocked
Replace the fan
Analog input error
(AnI.) {31}
Check if the analog input signal is out of range
Over-Torque2 detected
(ot2) {32}
Check whether the motor 2 is overloaded
Check whether motor 2 rated current setting (Pr5-40)
is suitable
Check whether the Over-Torque2 detect parameter
are suitable (Pr5-21~Pr5-23)
Check whether the mechanical system is normal
Increase motor 2 capacity and replace the drive with
the next higher power model
Motor overload
-Thermal relay 2
(oL2) {33}
(Electronic thermal relay 2
protection.)
Check whether the motor 2 V/F setting proprer
Check whether the motor 2 running low speed for long
period
Check for possible motor 2 overload
Check motor 1 full load current (Pr5-40)
Check electronic thermal overload 1 setting (Pr5-45 to
Pr5-46)
Reduce the load so that the drive output current does
not exceed the value set on Pr5-40
Increase motor capacity
Motor select error
(rnot) {34}
Check the motor wiring connection
Check the parameters settings
Low voltage on DC-Bus
during run
(LUr) {36}
The drive detects that the DC
bus voltage has fallen below
its minimum value during run
Check whether the input power voltage is normal
Check whether the power supply capacity is enough
Check for possible sudden load
Whether the 3-phase model is of the single-phase
power input or the phase-lacking
Check whether the Inrush limit by-pass circuit fault
Check whether the input power was interrupted
Check whether the input side magnetic contactor is
normal
Low voltage on DC-Bus
(LU) {39}
The drive detects that the DC
bus voltage has fallen below
its minimum value
TOPVERT G1/H1/P1 Series
E-36
External Base Block
(bb) {40}
(one of Pr2-01~Pr2-06 or
Pr2-26~Pr2-28 =15 or 16 and
act)
When the external input terminal (B.B) is active, the
drive output will be turned off.
Deactivate the external input terminal (B.B) to operate
the drive again.
EEPROM of PU-02 failure
(1 CoPy)
Replace a PU-02
Nothing to save due to PU-02
is empty (2 CoPy)
Make sure PU-02 had read data then try again
Cannot Save due to drive
model is not the same
(3 CoPy)
Recheck the drive models
Parameter error in PU-02
(4 CoPy)
Parameter is out of range, recheck the Parameter in
PU-02
Cannot Save due to drive is
running (7 CoPy)
Stop the drive then try again
Cannot Save or Read due to
drive was password locked
(8 CoPy)
Unlock the drive then try again
TOPVERT G1/H1/P1 Series
E-37
Dimension:
Unit: mm (inch)
Frame
W
H
D
W1
W3
H1
G1-A,H1-A,P1-A
160.0
(6.30)
250.0
(9.84)
186.0
(7.32)
140.0
(5.51)
6.0
(0.24)
230.0
(9.06)
G1-B,H1-B,P1-B
200.0
(7.87)
275.0
(10.83)
206.0
(8.11)
180.0
(7.87)
6.0
(0.24)
255.0
(10.83)
G1-C,H1-C,P1-C
260.0
(10.24)
460.0
(18.11)
245.0
(9.65)
236.0
(9.29)
9.0
(0.35)
440.0
(17.32)
Front View
Side View
Bottom View
Top View
D
W
W1
H1
H
W3
TOPVERT G1/H1/P1 Series
E-38
Unit: mm (inch)
Frame
W
H
D
W1
W2
W3
H1
H2
D1
D2
Φ1
G1-D
H1-D
P1-D
386.0
(15.20)
617.0
(24.29)
298.3
(11.74)
230.0
(9.06)
376.0
(14.80)
13.0
(0.51)
591.5
(23.29)
566.5
(22.30)
290.5
(11.44)
131.5
(5.18)
13
(0.51)
G1-E
H1-E
P1-E
386.0
(15.20)
683.0
(26.89)
324.3
(12.77)
230.0
(9.06)
376.0
(14.80)
13.0
(0.51)
657.5
(25.89)
632.5
(24.90)
316.5
(12.46)
157.5
(6.20)
13
(0.51)
G1-F
H1-F
P1-F
496.0
(19.53)
810.0
(31.89)
352.1
(13.86)
260.0
(10.24)
484.0
(19.06)
13.0
(0.51)
784.0
(30.87)
764.0
(30.08)
344.0
(13.54)
180.5
(7.11)
13
(0.51)
G1-G
H1-G
P1-G
732
(28.82)
1196
(47.09)
413
(16.26)
410
(16.14)
720.0
(28.35)
13.0
(0.51)
1156
(45.51)
1133
(44.61)
404.9
(15.94)
177.30
(6.98)
13
(0.51)
G1-H
H1-H
P1-H
W1
H1
H
W 3
D
Ø1
D2
Front View
Side View
Bottom View
Top View
W
D1
W2
H2
TOPVERT G1/H1/P1 系列
C-1
序言
序言
序言
序言
感謝您採用陽岡科技所製造的 高性能,電流向量變頻器 TOPVERT G1/H1/P1等系列產品。
TOPVERT G1/H1/P1系列產品採用了高品質之元件、材料及融合最新的微電腦控制技術製造而成。
本手冊提供給使用者安裝、參數設定、異常診斷、異常排除及日常維護相關注意事項。為了確保能夠
正確地安裝及操作變頻器,請在裝機之前,詳細閱讀本使用手冊,並請交由該機器的使用者。
此次使用說明書的更新,除了修改了前8701 版本的錯別字及不適合的用詞以外,我們也儘量加註了更
多解譯字詞,期望使用者能一閱即明暸,我們也在多個參數位置有相關連的地方加註了指引,期望使
用者能容易上手。然而最重大的不同在於韌體版本升級至3.xx 版本所造成的差異。
茲表列二者之主要差異如下:
2.xx 版本韌體及硬體新增加的部份(在參數位置會以 ◎ 標示之)
3.xx 版本韌體及硬體新增加的部份(在參數位置會以 ☉ 標示之)
修改或新增功能內容
相關參數位置
1 原+12V 輸出電壓源更名為+VX,並改成+12V/+10V 可切換的電壓源,参考點為
ACM。
2 原多功能類比輸入AVI 更名為AI1,並可在電壓/電流信號間切換。
Pr3-02 ~ Pr3-05
3 原多功能類比輸入ACI 更名為AI2,並可在電壓/電流信號間切換。
Pr3-06 ~ Pr3-10
4 原多功能類比輸入AUI 更名為AI3,可接入DC -10~+10V 電壓信號。
Pr3-11 ~ Pr3-14
5 原多功能類比輸出AVO 更名為AO1,可輸出DC 0~10V 電壓信號。
Pr3-15,Pr3-17,
Pr3-19,Pr3-21
6 原多功能類比輸出ACO 更名為AO2, 並可在電壓/電流信號間切換。
Pr3-16,Pr3-18,
Pr3-20,Pr3-21
7 原RS-485 串列通訊埠的RJ-45 插座修改為可插拔式歐式端子。
(SG+,SG-)
8 修改了散熱風扇控制出廠預設模式為”運轉命令執行後風扇才運轉”。
Pr0-23
9 所有控制端子改成可插拔式,並依類別群聚及防呆,方便配線及維修。
10 增加了運轉中JOG 命令有效或無效之選擇。
Pr4-36 bit 4
11 增加了一個DCM 端子,方便配線。
12 增加了R2B 端子。
Pr2-21
13 增加了PU-03 的介面,與PU-01 及 PU-02 同接口,並且自動辨識。
14
增加了8個可選配的端子如下: [需加配擴充卡TMCA-IO-10才有此功能]
[MI7] [多功能數位輸入端子 7]
Pr2-26
[MI8] [多功能數位輸入端子 8]
Pr2-27
[MI9] [多功能數位輸入端子 9]
Pr2-28
[AO3] [多功能類比輸出 3] (可輸出4(0)~20mA 電流信號)
Pr3-15
[MO3] [多功能數位輸出 5 –開集極輸出端子MO 3+]]]]
Pr2-24
[MC3] [多功能數位輸出 5 –開集極輸出端子MO 3-]]]]
[MO4] [多功能數位輸出 6 –開集極輸出端子MO 4+]]]]
Pr2-25
[MC4] [多功能數位輸出 6 –開集極輸出端子MO 4-]]]]
TOPVERT G1/H1/P1 系列
C-2
版權聲明
版權聲明
版權聲明
版權聲明
本文件中的資料係陽岡科技的智慧財產,我們雖然盡了最大的努力製作此文件,但無法對內容的正確性
提供百分之百保證,基於”還能更好”的品質政策,我們的產品恆於追求完美精益求精的路途中,因此我
們保留了不告知變動的權利,但我們持續將最新版本的文件擺在陽岡科技的公司網站上,供自由下載。
http://www.toptek.biz
本使用說明書
本使用說明書
本使用說明書
本使用說明書,,,,煩請您確實交給本
煩請您確實交給本
煩請您確實交給本
煩請您確實交給本變頻器
變頻器
變頻器
變頻器之最
之最
之最
之最終
終
終
終使用者
使用者
使用者
使用者,,,,以便發揮最大功能
以便發揮最大功能
以便發揮最大功能
以便發揮最大功能....謝謝
謝謝
謝謝
謝謝!
!
!
!
變頻器乃精密的電力電子產品,為了操作者及機械設備的安全,請務必交由專業的電機工程人員安裝
試車及調整參數,本手冊中有"危險"、"注意"等符號說明的地方請務必仔細研讀,若有任何疑慮的地方
請連絡本公司各地的代理商洽詢,我們的專業人員會樂於為您服務。
以下為特別需要注意的事項:
危險
危險
危險
危險!!!!
1. 實施配線,務必關閉電源。
2. 切斷交流電源後,充電指示燈(CHARGE)未熄滅前,表示變頻器內部仍有高壓,十分危險,請勿觸摸內部
電路及零組件。
3. 絕對不可以自行改裝變頻器內部的零件或線路。
4. 絕不可將變頻器輸出端子U/T1、V/T2、W/T3 連接至AC 電源。
5. 變頻器接地端子 務必正確的接地,230V 機種採第三種接地;460V /575V 機種採特種接地。
1. 切勿對變頻器內部的零組件進行耐壓測試,因內有半導體易受高壓擊穿而損壞。
2. 變頻器的電路板有cmos IC 極易受靜電的破壞,故在未做好防靜電措施前請勿用手觸摸電路板。
3. 即使電動機是停止的,變頻器的主回路端子仍然可能有危險的高壓。
4. 只有合格的電機專業人員才可以安裝、配線及修理保養變頻器。
5. 當變頻器某些功能被設定後,可能在電源輸入後會立即啟動電動機開始運轉。
6. 請選擇安全的區域來安裝變頻器,防止高溫及日光直接照射,避免溼氣和水滴的潑濺。
7. 請防止小孩或一般無關人員接近變頻器。
8. 變頻器只能用在本公司所認可的場合,未經認可的使用環境可能導致火災、氣爆、感電等事件。
9. 當變頻器與電動機之間的配線過長時,對電動機的層間絕緣可能產生破壞,請改用變頻器專用的交流
電動機,或在變頻器及電動機之間加裝電抗器或濾波器,避免造成交流電動機因絕緣破壞而燒毀。
(電抗器或濾波器之選用請參閱使用手冊 3-5章節)。
10. 變頻器所安裝之電源系統額定:(230V級機種不可高於240V),(460V級機種不可高於480V),(575V
級機種不可高於640V),供應容量電流不可超大於5000A RMS(30kW 以上機種不可大於10000A RMS)
11. 變頻器機殼對大地的漏電流 ( High leakage current ) 為22 mA。
12. 變頻器所控制的電動機應符合 IEC:60034-1。
13. 變頻器在開機瞬間充電電阻會有微量煙霧發生,屬正常現象。
警告
警告
警告
警告!!!!
TOPVERT G1/H1/P1 系列
C-3
交貨檢查
交貨檢查
交貨檢查
交貨檢查
機型銘牌
機型銘牌
機型銘牌
機型銘牌說明
說明
說明
說明
以 G1系列 2.2kW/3Hp 230V 3 Phase 選配 動態煞車器及速度迴授PG卡 為例:
型號說明
型號說明
型號說明
型號說明
生產管制
生產管制
生產管制
生產管制之資訊
之資訊
之資訊
之資訊說明
說明
說明
說明
● 拆裝後如有任何登錄資料與您訂貨資料不符或有任何瑕疵,請您與接洽之代理商或經銷商聯絡.
G1-232P2-D101-08 T0509001
Model:TOPVERT G1-232P2-D101
輸入電源規格
生產管制之詳細資訊
輸出頻率範圍
型號
輸出規格
生產管制條碼
軔體版本:3.08
CE認證
(FRN:3.08)
製造月份:1~9=1~9月,
O=10月,N=11月,D=12月
生產序號
製造年份:0~9=2010~2019年
製造廠代碼: T=台灣 桃園廠
選配代碼 或 客戶委製品代碼
機型: G1系列 230V 3 Phase 2.2kW/3Hp
電動機V/F規格預設碼(參數Pr0-02)
G1-232P2-xxxx-08 T 0 5 09001
最大適用電動機功率
(4 Pole)
(230V,380V,575V為標準.440/460V時
可適用較大功率之電動機)
0P4= 0.4kW 0P7= 0.75kW
2P2= 2.2kW 5P5= 5.5kW
7P5= 7.5kW 011= 11kW
022= 22kW 075= 75kW
160= 160kW 630= 630kW
陽岡
變頻器族譜代碼
電源規格
21= 230V 1 Phase
23= 230V 3 Phase
43= 460V 3 Phase
63= 575V 3 Phase
系列代碼: G1系列
硬體版本更新代碼
空白: 原始版本
A: A版本
B: B版本
Z: Z版本
動態煞車器選配代碼
空白或
” N ” : 無選配
D : 附加動態煞車器
(A、B 框號之機種已內建動態煞車器)
擴充卡,介面卡,及其它選配代碼
空白或
” N ” : 無選配
01 :TEK-PG-01 速度迴授PG卡
02 :選配PU-02
03 :選配PU-03
箱體保護構造選配代碼
空白: 標準品--無選配
0 : IP 00 (NEMA 0)
1 : IP 20 (NEMA 1)
2 : IP 21 (NEMA 4)
A、B及C框號機種
IP 20(NEMA 1)已是標準配備
TOPVERT G1-23 2P2 x-x x xx
TOPVERT G1/H1/P1 系列
C-4
標準規格
標準規格
標準規格
標準規格
系列名稱
TOPVERT G1 系列
全功能泛用標準型
TOPVERT H1 系列
全功能高速專用型
TOPVERT P1 系列
全功能風機水泵專用型
輸出
及控
制
輸出頻率範圍 □1
0- 600Hz,可規劃, 0.01Hz/step
0 - 6000Hz,可規劃, 0.01Hz/step
0 - 600Hz,可規劃, 0.01Hz/step
過負載承受能力 □2
額定輸出電流的150%(P1 為125%),運轉60 秒/10 分鐘,Ta≦50 ℃,200%(P1 為160%)運轉3 秒,適用連續性負載。
輸出電壓 □3
對應輸入電源0~100%的電壓,三相輸出,內建自動穩壓器(AVR),電源變動仍俱滿載額壓輸出驅動能力。
功因 及 效率 □4
裝置之功率因數不低於0.95,裝置全載時之效率不低於95%,22kW 以上之機種可達97%。
控制方式 □5
正弦波Soft PWM 調變磁通電壓/電流向量控制,俱電動機參數自動調適(Auto-tuning)及高速IGBT 六橋輸出架構。
控制模式與控速範圍 □6
四種模式可切換,V/F 模式20:1;V/F+PG 閉迴路模式120:1;無感向量模式120:1;磁束向量+PG(閉迴路模式600:1)
頻率設定解析度 □7
類比輸入: 10Bit(1/1024),0.03Hz/60Hz,0.024Hz/50Hz,數位輸入:0.01Hz(±0.01%),飛梭旋鈕輸入: 0.01Hz。
頻率設定精準度 □8
類比輸入:最大輸出頻率之±0.03%以內(25℃ ±10℃); 數位輸入:最大輸出頻率之0.01%以內(-10℃ ~ + 50℃)
PWM 載波頻率 □9
0.7kHz ~ 18kHz 運轉中可連續調整
1.4kHz ~ 36kHz 運轉中可連續調整
0.7kHz ~ 18kHz 運轉中可連續調整
轉矩提升 □
10
內建可調式及自動轉矩提升(Torque boost)及自動滑差補償,1Hz 時可達額定轉矩的150%,起動轉矩可達200%。
共振迴避(跳躍)頻率 □
11
自0.00 ~ 600Hz (H1 系列: 0.00 ~ 6000 Hz)可任意設定6 組,各組之寬度皆獨立可調。
加速/減速時間 □
12
0.01 ~ 60000 秒 (2 段 加速/減速 時間可分別獨立設定,另俱S 曲線加/減速及自動最佳化加/減速時間功能)
失速防止 □
13
過電流失速防止:10 ~ 250%可調,加速中及定速運轉中可分別獨立設定, 過電壓失速防止:100 ~ 160%可調。
直流煞車 □
14 啟動時及停止時,都可直流煞車,制動電流:額定電流的0 ~ 125%,制動時間: 0 ~ 60 秒獨立設定,制動起始頻率0 ~ 600Hz
動態煞車 □
15
動態煞車轉矩大約20%(10% E.D.), A 及 B 框號之機型,煞車迴路已內建,其餘機型之煞車迴路可選配內建
全系列都可外接動態煞車器(TDBU-XXXX) (外接動態煞車器時煞車轉矩可達125%)
V/F 曲線 □
16
可由使用者自定的二組任意V/F 曲線,可設成定轉矩特性曲線或遞減轉矩特性曲線。
運轉
操作
及
輸入
/
輸出
界面
頻率設
定方式/
信號 源
由數位操作器□
17
以360 度編碼器式飛梭旋鈕設定(分解度0.01Hz/0.1Hz/1Hz/10Hz 可規劃),寸動鍵運轉設定,[定時運轉/停止]
由類比信號 □
18
可任意規劃為:0~10/10~0V,4~20/20~4mA,-10~+10V(可逆運轉),1~5/5~1V,0~20/20~0mA,或由外部可變電阻。
由數位信號 □
19
端子MI1~MI6 (15 段速,寸動,Up/Down 指令),可程式運轉(PLC Run),通訊設定(RS-485),信號間並可任意切換。
運轉操
作信號
由數位操作器□
20
可由RUN,STOP,JOG 鍵執行,也可與外部端子切換/並用。
由外部信號 □
21
FWD/REV/STOP (2 線式運轉,3 線式運轉),寸動運轉,可程式運轉(PLC Run),通訊設定(RS-485) 。
可規劃
的智慧
型多功
能輸入
端子
8 組數位輸入
(DI) [可擴充至
11 組] □
22
接點皆可規劃為a 或b 接點,並可規劃成下列功能: 16 段可預設速度切換,第1/2 加減速時間切換,禁止加減速,計數輸入,
暫時停機,外部輸出遮斷,輔助電動機控制失效,AI2/AI1 選擇,變頻器重置,15 段可程式運轉,寸動運轉,遞增/遞減頻率
端子設定,Sink/Source 選擇,馬達過熱保護,參數群選擇…等多達43 種功能。
3 組類比輸入
(AI) □
23
AI1
AI1
AI1
AI1:0~10V/4~20mA (輸入阻抗20kΩ/250Ω), AI2
AI2
AI2
AI2:4~20mA/0~10V (輸入阻抗20kΩ/250Ω),AI3
AI3
AI3
AI3: -10~+10V(輸入阻抗10k
Ω) (也可規劃成4~20mA), 俱斷線偵測,都可規劃成對應16 種不同功能。
可規劃
的智慧
型多功
能輸出
端子
4 組數位輸出
(DO)
[可擴充至6 組]
□
24
接點皆可規劃為a 或b 接點.由2 個"C"接點的繼電器,及 2 個開集極輸出端子(可擴充至4 組)所組成.
並可規劃成下列功能: 運轉中,停止中,頻率到達輸出,零速指示,可程式運轉,計數到達指示,過轉矩,外部輸出中斷,多組
輔助電動機控制, 輸出低電壓報警,操作模式,故障指示,變頻器準備完成,過熱預警,緊急停止,可規劃的數位脈衝信號輸
出…等多達63 種功能及配合監控功能提供信號輸出。
2 組類比輸出端
子(AO) □
25
AO1
AO1
AO1
AO1:0~10V, AO2
AO2
AO2
AO2:4~20mA/0~10V,AO
AO
AO
AO3333:4~20mA,可規劃成對應設定/實際輸出頻率/輸出電流/輸出電壓,頻率指令或電動
機轉速…等計15 種功能,增益及偏壓可由使用者任意自定及配合監控功能提供信號輸出。[可擴充至3 組]
異常/故障信號輸出 □
26
可規劃至2 個"C"接點的繼電器(電氣壽命30 萬次)或2[4]個開集極輸出。
通訊功能 □
27 RS-485 通訊埠,Modbus ASCII & RTU,傳輸速率可達125 kbps。[RS-232,RS-488,CANopen,Device Net,Profibus,USB]
系統
內建
功能
□
28
可調的PID回授控制,P/PI切換功能,回授信號異常偵測,電源瞬停再啟動,自動穩壓輸出-AVR,S曲線及自動最佳化加/減速時間,外部異常聯鎖/重
置,30次異常自動復歸/手動復歸再啟動,自動高效率節能運轉,可設定減額運轉,輸出頻率上/下限,偏置頻率,密碼鎖定,多風機/水泵程序交替/睡眠/
甦醒控制/自動定壓運轉功能,兩組電動機參數且自動調適,By-Pass商用電源切換,Y-Δ運轉中切換,RS-485斷線偵測,雙向自動速度追蹤,飛輪啟動,
轉向限制,16段速運轉,減速/滑行停止,機械煞車聯鎖控制,預警功能,靜音運轉模式,遠方/現場/自動/手動/通訊無縫切換,使用者自定多功能顯示內
容,啟動/運轉電流的高低限制,轉矩控制/限制,Sink/Source(NPN/PNP)模式選擇,內部計數器,齒隙暫停,擺頻功能,減速時電壓偏移,可控式散熱風扇
(連續/節能),16段PLC Run,兩套參數可切換,五種多重參數群組設定功能。[定時運轉/停止,內置EMC/零相濾波器,AC/DC電抗器,12/18脈波整流, 控
制系統之獨立電源板,可由外加電池組供電及並接DC BUS,PG回授閉迴路速度控制]
保護
功能
□
29
電源及訊號之
電源及訊號之
電源及訊號之
電源及訊號之::::Soft Start/突波/雷擊,過電壓/低電壓/瞬間停電/欠相/不平衡/相對地過電流,相位指示,DC-Bus 之:過電壓/低電壓/短路
加速
加速
加速
加速中
中
中
中////定
定
定
定速
速
速
速中
中
中
中////減
減
減
減速
速
速
速中之
中之
中之
中之::::過電壓/過電流,過負載,過轉矩,過電流及過電壓失速防止,IGBT 模組之短路/過熱,散熱器過熱,散熱風扇異常,電子式熱動
電驛,輸出側短路/接地,保險絲熔斷保護,可調的過電流跳脫,輸出dv/dt 電壓抑制功能。
電
電
電
電動
動
動
動機
機
機
機之
之
之
之::::過電流/欠相/欠載/過載/過熱/失速/低速/超速/短路,溫昇預警
系統之
系統之
系統之
系統之::::自我診斷, PWM 切換錯誤,軔體錯誤,外部異常中斷, Dry Pump, Broken Belt 及Bump-less 功能,濾波電容及冷卻風扇老化監視及預警功能,
可依IGBT 模組溫度自動調節PWM 載波頻率,可顯示及無電永久保存 程式/參數/16/[48]次異常記錄及每筆異常時的運轉資訊如:異常原因,DC-Bus
電壓,輸出電壓/頻率/電流/,頻率指令,IGBT 溫度及散熱器溫度[日期,時間,功率,轉矩,運轉狀態,濾波電容過熱]等。
操作
及顯
示
□
30
8888 個
個
個
個薄膜按
薄膜按
薄膜按
薄膜按鍵
鍵
鍵
鍵::::可執行 運轉,停止,重置,正轉/反轉,顯示頁面切換,數位左移,參數資料設定,快捷功能,鍵盤/外部運轉及寸動運轉...等
1111 個
個
個
個360
360
360
360 度編碼器
度編碼器
度編碼器
度編碼器式飛梭旋鈕
式飛梭旋鈕
式飛梭旋鈕
式飛梭旋鈕::::可設定頻率,瀏覽,修改,比較,設定參數及作參數值輸入限定亦可配合智慧型多功能輸出端子動作…等
1111 個
個
個
個6666 位數的
位數的
位數的
位數的7777 節
節
節
節LED
LED
LED
LED 顯示器
顯示器
顯示器
顯示器::::可顯示設定頻率,實際輸出頻率,電壓,輸出電流,電動機轉向,電動機轉速,各種異常故障顯示,使用者自定義多功能顯
示內容(如輸入/輸出之電流,電壓,功率,容量,溫度,時間…計88 種)
6666 個狀態指示
個狀態指示
個狀態指示
個狀態指示LED
LED
LED
LED 燈
燈
燈
燈::::可分別顯示變頻器的運轉狀態,運轉/停止,正轉/反轉,鍵盤運轉指令/外部運轉指令等
1111 個
個
個
個RJ
RJ
RJ
RJ----45
45
45
45 插座
插座
插座
插座::::操作器可分離,可熱插拔,遠程遙控距離可達150 公尺以上,已配置PU-01 操作器如上功能。[PU-02 俱複製,儲存,比對功能]
[PU-03 俱複製,儲存,比對功能及LCD 中英文及圖形可同時顯示7 種運轉資訊,如電壓,電流,頻率,轉速,轉向,命令值,輸出值,溫度…等]
機構
與環
境
安規認證及抗干擾等級 □
31 符合CE,cUL 及UL508C 之規範;符合歐盟 RoHS 指令,內置基本型射頻干擾(RFI)雜訊抑制濾波器已符合EMC:EN61800-3
(EN61800-4-2 ~ EN61800-4-6)之規範,加配本公司特定濾波器時符合EN 55011,Class A/B 規範,
箱體構造 □
32 A,B及C框號機種--壁掛式低阻炭強化塑膠及金屬包覆EMC防護殼體。D, E, F 及 G 框號機種--壁掛式鍍鋅鋼板烤漆金屬
屏蔽包覆EMC防護殼體,全部控制配線與動力配線均實行電氣隔離保護及獨立接線區塊設計。
溫度及濕度 □
33
操作環境: -10℃ ~ + 40℃ [-10℃ ~ + 50℃]; 儲存環境: -20℃ ~ +65℃, 濕度:98% R.H.以下,無結露。
安裝場所及高度 □
34
室內適用,無腐蝕性氣體,液體及粉塵,海拔1000m 以下.振動:0.5G 以下,符合IEC60068-2/6/27 及-2-34/35/36
*TOPVERT 全系列產品均依CNS,IEC,IEEE,NEMA,ANSI,NEC,JIS,DIN,CE,CSA, UL 及cUL 之規範設計製造,台灣地區販售之產品均在台灣製造.[ ]: 選配功能
TOPVERT G1/H1/P1 系列
C-5
機種規格
機種規格
機種規格
機種規格
TOPVERT
TOPVERT
TOPVERT
TOPVERT G1
G1
G1
G1 及
及
及
及H1
H1
H1
H1 系列
系列
系列
系列::::單相電源
單相電源
單相電源
單相電源,,,,200
200
200
200////----15%
15%
15%
15% ~~~~ 240
240
240
240/+10%
/+10%
/+10%
/+10% VAC
VAC
VAC
VAC,
,
,
, 47
47
47
47 ~~~~ 63Hz
63Hz
63Hz
63Hz /[400
/[400
/[400
/[400Hz
Hz
Hz
Hz]]]]
型號
適用電動機(230V 4P)
額定輸出
電源
箱體結構
TOPVERT
G1-xxxxx
H1-xxxxx
功率
(kW)
馬力
(Hp)
容量
(kVA)
電流
(A)
電壓
(V)
頻率
(Hz)
電流
(Amax.)
冷卻方式
運轉噪音 保護等級
淨重
(kg)
外型框號
210P4
0.4
0.5
1.2
3
3 相,0
~ 額定
電源電
壓
G1 系列:
0 ~ 600
H1 系列:
0 ~ 6000
5.7
強制風冷
<70 dB/1M
IP 20
NEMA 1
[IP
21/40/42
/50/52
可加裝]
2.6
G1-A
H1-A
210P7
0.75
1
2
5
9.5
2.7
211P5
1.5
2
3
7.5
14
2.7
212P2
2.2
3
4.4
11
21
3.0
TOPVE
TOPVE
TOPVE
TOPVERT
RT
RT
RT G1
G1
G1
G1 及
及
及
及H1
H1
H1
H1 系列
系列
系列
系列::::三相電源
三相電源
三相電源
三相電源,,,, 200
200
200
200////----15%
15%
15%
15% ~~~~ 240
240
240
240/+10%
/+10%
/+10%
/+10% VAC
VAC
VAC
VAC,
,
,
, 47
47
47
47 ~~~~ 63Hz
63Hz
63Hz
63Hz /[400
/[400
/[400
/[400Hz
Hz
Hz
Hz]]]]
型號
適用電動機(230V 4P)
額定輸出
電源
箱體結構
TOPVERT
G1-xxxxx
H1-xxxxx
功率
(kW)
馬力
(Hp)
容量
(kVA)
電流
(A)
電壓
(V)
頻率
(Hz)
電流
(Amax.)
冷卻方式
運轉噪音 保護等級
淨重
(kg)
外型框號
230P4
0.4
0.5
1.2
3
3 相,0 ~ 額定電源電壓
G1 系列:
0 ~ 600
H1 系列:
0 ~ 6000
3.3
強制風冷
<70 dB/1M
IP 20
NEMA 1
[IP
21/40/42
/50/52
可加裝]
2.6
G1-A
H1-A
230P7
0.75
1
2
5
5.5
2.8
231P5
1.5
2
3
7.5
8.3
2.8
232P2
2.2
3
4.4
11
12
2.8
233P7
3.7
5
6.8
17
19
3.0
235P5
5.5
7.5
10
25
28
3.2
237P5
7.5
10
13
33
36
4.0
G1-B,H1-B
23011
11
15
20
49
54
11.9
G1-C
H1-C
23015
15
20
26
65
72
12.3
23018
18.5
25
30
75
83
13.0
23022
22
30
36
90
99
13.5
23030
30
40
48
120
132
IP 00
NEMA 0
[IP
21/40/42
/50/52
NEMA 1
可加裝]
32.7
G1-D
H1-D
23037
37
50
58
145
160
33.8
23045
45
60
73
182
200
34.6
G1-E
23055
55
75
92
232
255
58.0
G1-F
H1-F
23075
75
100
120
300
330
59.4
23090
90
125
143
360
396
強制風冷
<80 dB/1M
192
G1-G
23110
110
150
175
440
484
192
23132
132
175
207
520
572
198
23132S
132
175
207
520
572
302
G1-H
立櫃型
[ ]: 選配之功能
TOPVERT
TOPVERT
TOPVERT
TOPVERT G1
G1
G1
G1 及
及
及
及H1
H1
H1
H1 系列
系列
系列
系列::::三相電源
三相電源
三相電源
三相電源38
38
38
380000////----15%
15%
15%
15% ~~~~ 48
48
48
480000/+10%
/+10%
/+10%
/+10% VAC
VAC
VAC
VAC,
,
,
, 47
47
47
47 ~~~~ 63Hz
63Hz
63Hz
63Hz /[400
/[400
/[400
/[400Hz
Hz
Hz
Hz]]]]
型號
適用電動機 (4 pole)
額定輸出
電源
箱體結構
TOPVERT
G1-xxxxx
H1-xxxxx
380/415 V
(kW/Hp)
440/460 V
(kW/Hp)
容量
(kVA)
電流
(A)
電壓
(V)
頻率
(Hz)
電流
(Amax.)
冷卻方式
運轉噪音 保護等級
淨重
(kg)
外型框號
430P7
0.75/1
2.4
3
3 相,0 ~ 額定
電源電壓
G1 系列:
0 ~ 600
H1 系列:
3.3
強制風冷
<70 dB/1M
IP 20
NEMA 1
[IP
21/40/42
/50/52
2.8
G1-A
H1-A
431P5
1.5/2
3.3
4.2
4.6
2.9
432P2
2.2/3
4.8
6
6.6
2.9
433P7
3.7/5
6.8
8.5
9.4
2.9
435P5
5.5/7.5
10
13
14
3.0
437P5
7.5/10
14
18
20
3.3
TOPVERT G1/H1/P1 系列
C-6
43011
11/15
19
24
0 ~ 6000
26
可加裝]
4.3
G1-B
H1-B
43015
15/20
25
32
35
5.0
43018
18.5/25
32
40
44
13.0
G1-C
H1-C
43022
22/30
38
48
53
13.0
43030
30/40
48
60
66
13.9
43037
37/50
64
80
88
13.9
43045
45/60
77
97
107
13.9
43055
55/75
75/100
94
118
130
IP 00
NEMA 0
[IP
21/40/42
/50/52
NEMA 1
可加裝]
33.5
G1-D
H1-D
43075
75/100
90/125
121
152
167
37.1
43090
90/125
110/150
143
180
198
42.4
G1-E
H1-E
43110
110/150
132/175
191
240
264
63.0
G1-F
H1-E
43132
132/175
160/215
215
270
297
64.5
43160
160/215
185/250
242
304
334
64.5
43185
185/250
220/300
295
370
407
強制風冷
<80 dB/1M
192
G1-G
43220
220/300
280/375
359
450
495
192
43280
280/375
315/422
414
520
572
198
43315
315/422
375/500
486
610
671
198
43280S
280/375
315/422
414
520
572
IP 20
NEMA 1
[IP
21/40/42
/50/52
可加裝]
302
G1-H
立櫃型
43315S
315/422
375/500
486
610
671
312
43400S
400/535
450/600
583
732
805
333
43450S
450/600
500/670
690
866
953
341
43500S
500/670
560/750
766
962
1058
348
43560S
560/750
630/850
872
1094
1203
355
43630S
630/850 750/1000
966
1212
1333
360
TOPVERT
TOPVERT
TOPVERT
TOPVERT PPPP1111 系列
系列
系列
系列 ::::三相電源
三相電源
三相電源
三相電源,,,,200
200
200
200////----15%
15%
15%
15% ~~~~ 240
240
240
240/+10%
/+10%
/+10%
/+10% VAC
VAC
VAC
VAC,
,
,
, 47
47
47
47 ~~~~ 63Hz
63Hz
63Hz
63Hz /[400
/[400
/[400
/[400Hz
Hz
Hz
Hz]]]]
型號
適用電動機(230V 4 P )
額定輸出
電源
箱體結構
TOPVERT
P1-xxxxx
功率
(kW)
馬力
(Hp)
容量
(kVA)
電流
(A)
電壓
(V)
頻率
(Hz)
電流
(Amax.)
冷卻方式
運轉噪音 保護等級
淨重
(kg)
外型框號
230P7
0.75
1
1.4
3.6
3 相,0 ~ 額定電源電壓
0 ~ 600
4
強制風冷
<70 dB/1 M
IP 20
NEMA 1
[IP
21/40/42
/50/52
可加裝]
2.6
P1-A
231P5
1.5
2
2.4
6
6.6
2.8
232P2
2.2
3
3.6
9
9.9
2.8
233P7
3.7
5
5.3 13.2
15
2.8
235P5
5.5
7.5
8.1 20.4
22
3.0
237P5
7.5
10
12
30
33
3.2
23011
11
15
16
39.6
44
4.0
P1-B
23015
15
20
23
58.8
65
11.9
P1-C
23018
18.5
25
31
75
86
12.3
23022
22
30
36
90
99
13.0
23030
30
40
43
108
119
13.5
23037
37
50
57
144
158
IP 00
NEMA 0
[IP
21/40/42
/50/52
NEMA 1
可加裝]
32.7
P1-D
23045
45
60
69
174
191
33.8
23055
55
75
87 218.4
240
34.6
23075
75
100
111 278.4
306
58.0
P1-F
23090
90
125
143
360
396
59.4
23110
110
150
172
432
475
強制風冷
<80 dB/1 M
192
P1-G
23132
132
175
210
520
581
192
[ ]: 選配之功能
TOPVERT G1/H1/P1 系列
C-7
TOPVERT
TOPVERT
TOPVERT
TOPVERT PPPP1111 系列
系列
系列
系列 ::::三相電源
三相電源
三相電源
三相電源,,,, 三相電源
三相電源
三相電源
三相電源38
38
38
380000////----15%
15%
15%
15% ~~~~ 48
48
48
480000/+10%
/+10%
/+10%
/+10% VAC
VAC
VAC
VAC,
,
,
, 47
47
47
47 ~~~~ 63Hz
63Hz
63Hz
63Hz /[400
/[400
/[400
/[400Hz
Hz
Hz
Hz]]]]
型號
適用電動機 (4 pole)
額定輸出
電源
箱體結構
TOPVERT
P1-xxxxx
380/415 V
(kW/Hp)
440/460 V
(kW/Hp)
容量
(kVA)
電流
(A)
電壓
(V)
頻率
(Hz)
電流
(Amax.)
冷卻方式
運轉噪音
保護構造
(IP/NEMA)
淨重
(kg)
外型框號
431P5
1.5/2
2.9
3.6
3 相,0 ~ 額定電源電壓
0 ~ 600
4
強制風冷
<70 dB/1 M
IP 20
NEMA 1
[IP
21/40/42
/50/52
可加裝]
2.8
P1-A
432P2
2.2/3
4
5.04
5.5
2.9
433P7
3.7/5
5.7
7.2
7.9
2.9
435P5
5.5/7.5
8.1
10.2
11
2.9
437P5
7.5/10
12
15.6
17
3.0
43011
11/15
17
21.6
24
3.3
43015
15/20
23
28.8
32
4.3
P1-B
43018
18.5/25
31
38.4
42
5.0
43022
22/30
38
48
53
13.0
P1-C
43030
30/40
46
57.6
63
13.0
43037
37/50
57
72
79
13.9
43045
45/60
76
96
106
13.9
43055
55/75
93
116.4
128
13.9
43075
75/100
90/125
113
141.6
156
IP 00
NEMA 0
[IP
21/40/42
/50/52
NEMA 1
可加裝]
33.5
P1-D
43090
90/125
110/150
145
180
201
37.1
43110
110/150
132/175
172
216
238
42.4
P1-E
43132
132/175
160/215
229
270
317
63.0
P1-F
43160
160/215
185/250
258
304
356
64.5
43185
185/250
220/300
291
365
401
64.5
43220
220/300
280/375
354
444
488
強制風冷
<80 dB/1 M
192
P1-G
43280
280/375
315/422
430
520
594
192
43315
315/422
375/500
497
610
671
198
43400
400/535
450/600
583
732
805
198
43315S
315/422
375/500
497
610
671
IP 20
NEMA 1
[IP
21/40/42
/50/52
可加裝]
312
P1-H
立櫃型
43400S
400/535
450/600
583
732
805
333
43450S
450/600
500/670
700
866
953
341
43500S
500/670
560/750
828
962
1058
348
43560S
560/750
630/850
920
1094
1203
355
43630S
630/850 750/1000 1046
1212
1333
360
[ ]: 選配之功能
TOPVERT G1/H1/P1 系列
C-8
基本配線圖
基本配線圖
基本配線圖
基本配線圖
M.C.
C,D,E,F,G及H 框號之機種
((((BBBB2222端子選配
端子選配
端子選配
端子選配))))
B2
B1
+12V/10V,20m A
0~10V/4~20mA
-12V
-12V,20mA
ACM
三相電源輸入
50/60Hz
[400Hz 選配]
4~20m A/0~10V
VR : 5~10 KΩ
AI3
-10~+10V (10KΩ )
主迴路
控制迴路
電動機
M
3~
U(T1)
W (T3)
V(T2)
R1A
R1B
R1C
R2B
R2C
接點輸出 1 (故障指示)
240VAC 2.5A,120VAC 5A,24VDC 5A
接點輸出 2 (運轉中指示)
240VAC 2.5A,120VAC 5A,24VDC 5A
類比輸出 2 (輸出頻率)
4(0)~20m A/0~10V, 2m A
類比輸出 1 (輸出頻率)
0~10V, 2m A
類比信號共同端子
AO2
AO1
ACM
+
P1
(頻率命令)
多
多
多
多功
功
功
功能
能
能
能類
類
類
類比
比
比
比信
信
信
信號
號
號
號輸
輸
輸
輸入
入
入
入
R(L1)
M.C.
T(L3)
若為單相電源機種時請接R(L1), S(L2)
S(L2)
-
多
多
多
多功
功
功
功能
能
能
能數
數
數
數位
位
位
位信
信
信
信號
號
號
號輸
輸
輸
輸入
入
入
入
E
數位信號共同端子
端子不可直接加入電壓
多
多
多
多功
功
功
功能
能
能
能接
接
接
接點
點
點
點輸
輸
輸
輸出
出
出
出
多
多
多
多功
功
功
功能
能
能
能類
類
類
類比
比
比
比輸
輸
輸
輸出
出
出
出
通
通
通
通訊
訊
訊
訊接
接
接
接口
口
口
口
A 及 B
框號之機種
B2
B1
+
煞車電阻(選配)
TDBR
-
B2
B1
+
TDBU
-
P1
TD
BR
短路片
TDBR
直流電抗器(選配)
(AO)
(DI)
(AI)
MI1
MI2
MI3
M I4
MI5
M I6
(異常重置)
(外部異常輸入EF)
正轉/停止
(多段速指令2)
(多段速指令3)
(多段速指令4)
(多段速指令1)
反轉/停止
DCM
24V
FW D
REV
1
2
3
1
2
3
(Ry)
多
多
多
多功
功
功
功能
能
能
能數
數
數
數位
位
位
位信
信
信
信號
號
號
號輸
輸
輸
輸入
入
入
入
24V
MI7
MI8
MI9
數位信號共同端子
DCM
E
(DI)
24V
+
-
使用內部電源
使
用
外
部
電
源
MI9
DCM
24V
MI7
MI8
外部電源零電位端子
E
擴充卡
擴充卡
擴充卡
擴充卡
TMCA
TMCA
TMCA
TMCA----IO
IO
IO
IO----10
10
10
10
((((選配
選配
選配
選配))))
共同端子
開集極輸出 1 (任意頻率到達 1)
開集極輸出 2 (變頻器準備完成指示)
M O1
M O2
MCM
多
多
多
多功
功
功
功能
能
能
能數
數
數
數位
位
位
位輸
輸
輸
輸出
出
出
出
(DO)
DCM
VP
B
A
A
B
+12V
GND
PG
E
A
B
E
A/O
B/O
COM
轉速計
*轉速計的電源由使用者自行提供
+VX
10
12
AI1
A
V
AI2
V
A
SG+
SG-
V
A
+VX
AI1
AI2
AO2
R2A
外部輸入數位信號
外部輸入類比信號
外部輸入數位信號
24V
+
-
使
用
外
部
電
源
Source (PNP) 模式
Sink (NPN)模式
使用內部電源
MI1
MI2
MI3
MI4
MI5
MI6
DCM
24V
FW D
REV
外部電源零電位端子
SW 1
Source
Sink
速度迴授
PG卡
(選配)
出廠預設
OC
TP
12V
5V
SW 2
SW 1
R30
S30
T30
控制系統
之獨立電
源板
(選配)
R1
S1
12脈波整流器
(選配)
Source (PNP) 模式
Sink (NPN)模式
SW 1
Source
Sink
30度相移
三相電源輸入
M.C.
單相電源輸入
E
TOPVERT
類比輸出 3 (輸出頻率)
4(0)~20m A
類比信號共同端子
AO3
ACM
多
多
多
多功
功
功
功能
能
能
能類
類
類
類比
比
比
比輸
輸
輸
輸出
出
出
出
(AO)
開集極輸出 4 -
開集極輸出 3 +
開集極輸出 4 +
MO3
M O4
M C4
多
多
多
多功
功
功
功能
能
能
能數
數
數
數位
位
位
位輸
輸
輸
輸出
出
出
出
(DO)
M C3
開集極輸出 3 -
Max.48VDC/50mA
Max.48VDC/50mA
Max.48VDC/50mA
Max.48VDC/50mA
RS-485 串列通訊埠
(Modbus)
無熔絲斷路器
或
保險絲
電磁開關
附註
附註
附註
附註:
:
:
: ◎
◎
◎
◎ →
→
→
→ 主迴路
主迴路
主迴路
主迴路
○
○
○
○ →
→
→
→ 控制迴路
控制迴路
控制迴路
控制迴路
→
→
→
→ 具有
具有
具有
具有被覆隔離網之
被覆隔離網之
被覆隔離網之
被覆隔離網之隔離絞線
隔離絞線
隔離絞線
隔離絞線
( )
( )
( )
( ) →
→
→
→ 出廠預設功能
出廠預設功能
出廠預設功能
出廠預設功能
→
→
→
→ 選配
選配
選配
選配
60
60
0
Hz
FWD
REV
-12V
+12V
TOPVERT G1/H1/P1 系列
C-9
主迴路端子說明
主迴路端子說明
主迴路端子說明
主迴路端子說明
端子符號
內容說明
R(L1)
R(L1)
R(L1)
R(L1),,,,S(L2)
S(L2)
S(L2)
S(L2),,,,T(L3)
T(L3)
T(L3)
T(L3)
主電源輸入端子,接至商用電源。
供應電源之電壓及容量應符合所安裝之變頻器所需。
RRRR30,
30,
30,
30,SSSS30,
30,
30,
30,TTTT30
30
30
30
(選配)
30度相移三相電源輸入端子,接至二次繞組俱雙Star-Delta之三相電源變
壓器.供應電源之電壓及容量應符合所安裝之變頻器所需。
RRRR1,
1,
1,
1,SSSS1
1
1
1
(選配)
控制系統之獨立電源輸入端子,電壓規格同主電源;此端子可單獨供電或
與主電源輸入端子同時供電,但若僅此端子單獨供電時變頻器不能運轉,
僅能查詢記錄,檢查控制信號,參數設定,或故障排除等動作。
U(T1)
U(T1)
U(T1)
U(T1),,,,V(T2)
V(T2)
V(T2)
V(T2),,,,W(T3)
W(T3)
W(T3)
W(T3)
變頻器輸出端子,接至三相感應電動機。
⊕
⊕
⊕
⊕/B1, B2
/B1, B2
/B1, B2
/B1, B2
外接煞車電阻連接端子,請依使用手冊第九章選用安裝。
⊕
⊕
⊕
⊕/B1,
/B1,
/B1,
/B1, Θ
Θ
Θ
Θ
外接動態煞車器連接端子。 (直流電源輸入接續端子)
P1,
P1,
P1,
P1, ⊕
⊕
⊕
⊕/B1
/B1
/B1
/B1
直流電抗器連接端子,安裝時請將短路片拆除。
接地端子,共有二個,必需依電工法規:G1-430V機種採第三種接
地,460V/575V機種採特種接地。靠近電源端子的一個用於接至電源系統的
真大地;靠近輸出端子的一個用於接至電動機的外殼。
控制迴路端子標示說明
控制迴路端子標示說明
控制迴路端子標示說明
控制迴路端子標示說明
AI2 類比輸入選擇開關
AI1 類比輸入選擇開關
AO2 類比輸出選擇開關
+VX 類比電壓源選擇開關
擴充卡插座
邏輯控制板
DI端子動作模式
擴充卡插槽
異常指示燈
電源指示燈
Fault
Power
+VX
AO2
AI2
AI1
10V
12V
A
V
A
V
V
A
Sink
Source
操作器插槽
廠內製程專用
與驅動板之連接插座
DI
AI/AO
Ry
DO
JP3
JP4
JP7
JP6
類比信號相關之選擇
(必須先將可插拔式DI端子群母座拔出才可切換)
SW1
JP2
可插拔式端子群
接地及24V電源輸出
E 24V DCM
多功能類比信號輸入/輸出(AI/AO)
+VX -12V AI1 AI2 AI3 ACM AO1 AO2
多功能光耦合開集極輸出(DO)
及通訊埠
MO1 MO2 MCM SG+ SG-
多功能繼電器接點輸出(Ry)
R1A R1B R1C R2A R2B R2C
多功能數位信號輸入(DI)
MI1 MI2 MI3 MI4 MI5 MI6 FWD REV DCM
+VX
AO2
AI2
AI1
10V
12V
A
V
A
V
V
A
JP7
TP1
接地針
TEK-G1-01-xx
Ver:
Date Code:
擴充卡固定孔
擴充卡固定孔
TOPVERT G1/H1/P1 系列
C-10
控制迴路端子說明
控制迴路端子說明
控制迴路端子說明
控制迴路端子說明
端子
符號
端子功能說明
額定限制/對應参數位址
(出廠預設定功能)
數位信號輸入相關
數位信號輸入相關
數位信號輸入相關
數位信號輸入相關(建議採用18 AWG (0.75 mm
2) 有遮蔽對絞線配線)
MI1 多功能數位輸入端子 1 (三線式STOP指定端子)
Pr2-01/(多段速一命令)
MI2 多功能數位輸入端子 2
Pr2-02/(多段速二命令)
MI3 多功能數位輸入端子 3
Pr2-03/(多段速三命令)
MI4 多功能數位輸入端子 4
Pr2-04/(多段速四命令)
MI5 多功能數位輸入端子 5
Pr2-05/(異常重置命令)
MI6 多功能數位輸入端子 6 (TRG指定端子)
Pr2-06/ (EF)
FWD 正轉運轉/停止 命令
Pr2-00/(正轉運轉/停止)
REV 反轉運轉/停止 命令
Pr2-00/(反轉運轉/停止)
DCM 數位輸入信號的的参考點,24V電源端子的参考點,
此端子與ACM端子成絕緣關係。
共有2個, 功能相同
[MI7] [多功能數位輸入端子 7]
Pr2-26
[MI8] [多功能數位輸入端子 8]
Pr2-27
[MI9] [多功能數位輸入端子 9]
Pr2-28
繼電器接點輸出
繼電器接點輸出
繼電器接點輸出
繼電器接點輸出相關
相關
相關
相關(必須與其它所有的控制迴路端子分離配線)
R1A 多功能輸出 1 (繼電器乾接點輸出)
R1A-R1C :Relay 1 常開 (a接點)
R1B-R1C :Relay 1 常閉 (b接點)
Pr2-20,Pr2-21
電阻性負載
電阻性負載
電阻性負載
電阻性負載
5A(N.O.)/3A(N.C.) 240VAC/24VDC
電感性負載
電感性負載
電感性負載
電感性負載
1.5A(N.O.)/0.5A(N.C.)
240VAC/24VDC
R1B
R1C
R2A 多功能輸出 2 (繼電器乾接點輸出)
R2A-R1C :Relay 2 常開 (a接點)
R2B-R1C :Relay 2 常閉 (b接點)
R2B
R2C
數位信號控制電源
數位信號控制電源
數位信號控制電源
數位信號控制電源 及
及
及
及 接地端子
接地端子
接地端子
接地端子(建議採用18 AWG (0.75 mm
2有遮蔽對絞線配線)
E
數位及類比訊號隔離線,外層披覆隔離網連接用的接
地端子。
24V 數位信號共用電源端子,参考點為 DCM。
Max. 50mA
DCM 數位輸入信號的的参考點. 24V電源端子的参考點,
此端子與ACM端子成絕緣關係。
共有2個, 功能相同
類比信號
類比信號
類比信號
類比信號輸入
輸入
輸入
輸入輸出相關
輸出相關
輸出相關
輸出相關(建議採用18 AWG (0.75 mm
2有遮蔽對絞線配線)
微弱的類比信號,特別容易受外部雜訊干擾影響,所以配線應盡可能短(小於20m),遮蔽對絞線的外
圍網線基本上應接地 (E 端子),但若現場的誘導雜訊大時,連接到ACM端子的效果反而會較好。
如需在此電路中使用接點,則應使用能處理弱信號的雙叉接點,但ACM端子不要使用接點控制。
+VX +12V/+10V可切換的類比電壓源,参考點為ACM。
Max.20mA/(+12V)
-12V -12V 類比電壓源,参考點為ACM。
Max. 20mA
AI1
多功能類比輸入 1 (可選擇輸入電壓或電流信號)
(當AI1 類比信號輸入選擇開關選擇”V”時,可接入
DC 0~10V 電壓信號;選擇”A” 時, 可接入DC
4(0)~20mA 電流信號)
Pr3-02/(DC 0~10V對應頻率命令)
AI2
多功能類比輸入 2 (可選擇輸入電流或電壓信號)
(當AI2 類比信號輸入選擇開關選擇”V”時,可接入
DC 0~10V 電壓信號;選擇”A”, 可接入DC
4(0)~20mA 電流信號)
Pr3-06/(4~20mA對應頻率命令)
AI3 多功能類比輸入 3 (可輸入DC -10~+10V 電壓信號) Pr3-11/(DC -10~+10V對應頻率命令)
TOPVERT G1/H1/P1 系列
C-11
ACM 類比輸入與輸出信號的参考點,此端子與DCM端子成
絕緣關係。
AO1 多功能類比輸出 1 (可輸出DC 0~10V 電壓信號)
Max.2mA/Pr3-15/(對應輸出頻率)
AO2
多功能類比輸出 2 (可選擇輸出電流或電壓信號)
(當AO2 類比信號輸出選擇開關選擇”V”時,可輸出
DC 0~10V 電壓信號;選擇”A” 時, 可輸出DC
4(0)~20mA 電流信號)
Pr3-16/(4~20mA 對應 輸出頻率)
[AO3] [多功能類比輸出 3] (可輸出4(0)~20mA 電流信號) Pr3-15/( 4~20mA 對應 輸出頻率)
數位信號輸出及
數位信號輸出及
數位信號輸出及
數位信號輸出及通訊埠
通訊埠
通訊埠
通訊埠 相關
相關
相關
相關(建議採用18 AWG (0.75 mm
2有遮蔽對絞線配線)
MO1 多功能輸出 3 (光耦合開集極輸出端子 1)
Max.48VDC,50mA/(速度到達 1 )
MO2 多功能輸出 4 (光耦合開集極輸出端子 2)
Max.48VDC,50mA/(變頻器準備完成)
MCM 多功能數位輸出3及4 光耦合開集極輸出端子共同端
SG+ RS-485 串列通訊埠的連接端子 +
應選用有遮蔽對絞線連接
SG- RS-485 串列通訊埠的連接端子 -
[MO3] [多功能數位輸出 5 –開集極輸出端子MO 3+]]]]
Pr2-24
[MC3] [多功能數位輸出 5 –開集極輸出端子MO 3-]]]]
[MO4] [多功能數位輸出 6 –開集極輸出端子MO 4+]]]]
Pr2-25
[MC4] [多功能數位輸出 6 –開集極輸出端子MO 4-]]]]
[ ] :需選配擴充卡才有此功能
數位操作器
數位操作器
數位操作器
數位操作器各部位功能說明
各部位功能說明
各部位功能說明
各部位功能說明
陽岡科技率先採用了360度編碼器式飛梭旋鈕,使得參數的設定變的快速方便,也突破了傳統可變電
阻(VR)式旋鈕解析度低的缺點,從數位操作器以飛梭旋鈕設定輸出頻率解析度可高達0.01Hz.
PU
PU
PU
PU----01
01
01
01 數位操作器
數位操作器
數位操作器
數位操作器各部位功能說明
各部位功能說明
各部位功能說明
各部位功能說明
FWD
REV
EXT
PU
主顯示區
可顯示器驅動器各項資訊狀態
如頻率,電流,電壓,轉向,使用
者定義單位,異常及參數群等
操作器型號
狀態顯示區
PU :燈亮表示運轉指令來自PU-01
燈滅表示運轉指令來自外部(Pr0-19)
EXT :燈亮表示頻率指令來自外部(Pr0-18)
燈滅表示頻率指令來自PU-01
REV :燈亮表示反轉運轉中
FWD︰燈亮表示正轉運轉中
數字左移/重置鍵
正轉/反轉控制鍵
顯示畫面選擇鍵
停止鍵
鍵盤運轉操作/
外部運轉操作切換鍵
寸動運轉鍵
運轉鍵
PU-01
參數資料設定鍵
數值變更旋鈕
輸出頻率調整旋鈕
PU
JOG
DISP
F/R
RUN
STOP
運轉中指示
停止中指示
RESET
TOPVERT G1/H1/P1 系列
C-12
PU
PU
PU
PU----02
02
02
02 數位操作器
數位操作器
數位操作器
數位操作器各部位功能說明
各部位功能說明
各部位功能說明
各部位功能說明((((選配
選配
選配
選配)
)
)
)
保有 PU-01 全部功能,還俱備了參數 讀出/寫入/儲存/複製功能,並可儲存二組用戶參數組
PU
PU
PU
PU----00003333 數位操作器
數位操作器
數位操作器
數位操作器各部位功能說明
各部位功能說明
各部位功能說明
各部位功能說明((((選配
選配
選配
選配))))
保有 PU-01 全部功能,還俱可由使用者規劃的LCD中英文顯示
FWD
REV
EXT
PU
PU-02
PU
JOG
DISP
F/R
RUN
STOP
RESET
Read/Save
同時按下PU及RESET鍵
可執行Read(讀出)及
Save(寫入)的功能
狀態顯示
PU :顯示時表示運轉指令來自PU-03
不顯示時表示運轉指令來自外部(Pr0-19)
EXT :顯示時表示頻率指令來自外部(Pr0-18)
不顯示時表示頻率指令來自PU-03
:顯示時表示時段運轉執行功能已開啟
REV :顯示時表示反向運轉
FWD :顯示時表示正向運轉
100%
FWD
REV
EXT
PU
RESET
主顯示區
可同時顯示變頻器多項資訊狀態
如頻率,電流,電壓,轉向,使用者
定義單位,異常信號及參數群等
操作器型號
數字移位/重置鍵
正轉/反轉控制鍵
顯示區之顯示資訊選擇鍵
進入自體參數設定模式鍵
停止鍵
鍵盤運轉/外部運轉切換鍵
寸動運轉鍵
運轉鍵
PU-03
360度編碼器式飛梭旋鈕
輸出頻率調整,參數資料讀出
寫入,數值變更設定鍵
PU
JOG
DISP
F/R
RUN
STOP
運轉中指示
停止中指示
6000.00Hz 9999.99A
6000.00Hz
TOPVERT G1/H1/P1 系列
C-13
顯示功能說明
顯示功能說明
顯示功能說明
顯示功能說明
顯示項目
說明
‘F’ 顯示變頻器目前的設定頻率
(可按 DISP 鍵觀看)
‘H’顯示變頻器實際輸出到電動機的頻率
(可按 DISP 鍵觀看)
‘A’顯示負載電流
(可按 DISP 鍵觀看)
‘u’顯示用戶在多功能顯示選擇(Pr0-07)所選擇的內容
(可按 DISP 鍵觀看)
顯示Read/Save的選擇內容 (只適用於PU-02)
(可按 DISP 鍵觀看)
選擇參數位址
(可“按下”與“旋轉” 飛梭旋鈕來選擇參數位址)
(按下 鍵可依序顯示已更改過的參數位址)
顯示參數內容值
(可”按下”與“旋轉” 飛梭旋鈕來設定參數內容值)
表示資料已被接受並存入內部記憶體
(參數設定完成後按一下 旋鈕來完成資料存入內部記憶體並顯示End)
操作功能說明
操作功能說明
操作功能說明
操作功能說明
1.
1.
1.
1. 顯示訊息的操
顯示訊息的操
顯示訊息的操
顯示訊息的操作
作
作
作
RESET
F W D
R E V
E X T
P U
F W D
R E V
E X T
P U
F W D
R E V
E X T
P U
F W D
R E V
E X T
P U
F W D
R E V
E X T
P U
F W D
R E V
E X T
P U
F W D
R E V
E X T
P U
F W D
R E V
E X T
P U
F W D
R E V
E X T
P U
每按一下”DISP”鍵,顯示器可在F頁面、H頁面、A頁面及U面切換
顯示用戶選擇的
多功能顯示內容
DISP
顯示負載電流
按一下
DISP
顯示驅動器實際輸
出到電動機的頻率
按一下
DISP
顯示驅動器
的設定頻率
按一下
FWD
REV
EXT
PU
FWD
REV
EXT
PU
FWD
REV
EXT
PU
DISP
按一下
FWD
REV
EXT
PU
TOPVERT G1/H1/P1 系列
C-14
2.
2.
2.
2. 參數設定
參數設定
參數設定
參數設定的
的
的
的操作
操作
操作
操作 (以將Pr0-07設定成2 為例)
3.
3.
3.
3.運轉的操作
運轉的操作
運轉的操作
運轉的操作 (以從PU執行以50Hz運轉為例)
4.
4.
4.
4. 參數讀出
參數讀出
參數讀出
參數讀出////寫入
寫入
寫入
寫入(Read/Save)
(Read/Save)
(Read/Save)
(Read/Save)的操作
的操作
的操作
的操作 (只適用於 PU-02)(參數複製僅限於在同樣機型間執行)
選定參數Pr0-07
按一下
與旋轉
FW D
REV
EXT
PU
選取參數值 2
按一下
與旋轉
FW D
REV
EXT
PU
完成參數設定
FW D
REV
EXT
PU
按一下
開機顯示畫面
按住此鍵
2 秒後
FW D
REV
EXT
PU
跳回顯示訊息畫面
FW D
REV
EXT
PU
DISP
按兩下
進入參數0群
按一下
FW D
REV
EXT
PU
R U N
執行以5 0 H z 運轉
按一下
調整想要的頻率, 搭配
數值左移鍵會更方便
P U
選擇運轉命令來自P U
按一下
D IS P
顯示實際輸出頻率
按一下
F /R
改變電動機轉向
F W D 為正轉, R E V 為反轉
按一下
F W D
R E V
E X T
P U
F W D
R E V
E X T
P U
F W D
R E V
E X T
P U
F W D
R E V
E X T
P U
F W D
R E V
E X T
P U
R E S E T
數值左移
旋轉
可選擇:
Read1
Save1
Read2
Save2
旋轉
PU
同時按下
RESET
執行
讀出(Read)參數
FW D
R EV
EX T
P U
執行
寫入(Save)參數
PU
同時按下
RESET
FW D
RE V
E X T
PU
完成
寫入(Save)參數
FW D
RE V
E X T
PU
完成
讀出(Read)參數
FW D
RE V
E X T
PU
FW D
R EV
EX T
P U
TOPVERT G1/H1/P1 系列
C-15
功能
功能
功能
功能‧
‧
‧
‧參數一覽表
參數一覽表
參數一覽表
參數一覽表
0000 參數群
參數群
參數群
參數群:::: 系統參數
系統參數
系統參數
系統參數
★=運轉中不可設定 ◎:僅適用於軔體版本:2.xx以後之產品 [ ]內為1.xx 軔體版本原參數編號
參數
參數功能
設定範圍
出廠值
客戶
★ Pr0-00
機型顯示
依機型顯示,僅能讀取
唯讀
★ Pr0-01
額定輸出電流
依機型顯示,僅能讀取
唯讀
★ Pr0-02
參數重置 (電動機規格選擇)
10: 參數重置成為符合 60Hz - 230/460/575V 之電動
機的環境
8
9: 參數重置成為符合 50Hz - 220/380/575V 之電動機
的環境
8: 參數重置成為符合 60Hz - 220/380/575V 之電動機
的環境
7: 參數重置成為符合 50Hz - 230/460/575V 之電動機
的環境
6: 參數重置成為符合 60Hz - 240/415/575V 之電動機
的環境
◎
5: 參數重置成為符合 50Hz - 240/415/575V 之電動機
的環境
◎
Pr0-03
參數保護密碼輸入 (鑰匙)
0~9999
0
Pr0-04
參數保護密碼設定 (鎖頭)
0~9999
0
Pr0-05
參數保護等級
Bit 0
Bit 0
Bit 0
Bit 0
(bxxxx0)
0: 所有參數皆可讀取
b00000
1: Pr0-05 之後的參數不可讀取.
(嘗試讀取會顯示”Err”)
Bit
Bit
Bit
Bit 1111
(bxxx0x)
0:頻率命令可改
1:頻率命令不可改
Bit
Bit
Bit
Bit 2222
(bxx0xx)
0:數位操作器可執行運轉操作
1:數位操作器不可執行運轉操作
Pr0-06
開機預設顯示頁面
0:顯示 頻率命令值 (F)
0
1:顯示 實際輸出頻率(H)
2:顯示 輸出電流(A)
3:顯示 使用者於Pr0-07 所定義的顯示內容
Pr0-07
定義多功能顯示內容
0:電動機轉速 (RPM)
0
1:DC-Bus 電壓 (Vdc)
2:實際輸出電壓 (Vac)
3:輸出電壓命令值(Vac)
4:PID 回授頻率值 (Hz)
5:多段速運轉執行中之段數
6:睡眠時間 (Pr8-07)
7:異常再啟動次數(Pr6-10)
8:PID 命令值 (Hz)
9:(廠內保留)
10:輸出功率因數 ( ゚ )
11:計數器計數值
12:過轉矩檢出時間 1 (Pr5-17)
13:(廠內保留)
14:加速時齒隙暫停時間(Pr6-14)
15:減速時齒隙暫停時間 (Pr6-16)
16:啟動時直流制動時間(Pr6-01)
17:停車時直流制動時間(Pr6-02)
18:多段速運轉執行中未完時間
19:(廠內保留)
20:(廠內保留)
21:累積上電的天數 (Day)
22:累積上電的時間 (hh:mm)
23:(廠內保留)
24:(廠內保留)
25:(廠內保留)
26:AI1輸入端對應的比例值 出廠值範圍: 0~10
TOPVERT G1/H1/P1 系列
C-16
27:AI2輸入端對應的比例值 出廠值範圍: 0~10
28:AI3輸入端對應的比例值
REV<~-10V~ 0 ~10V~>FWD 出廠值範圍: 0~10
29:(廠內保留)
30:(廠內保留)
31:(廠內保留)
32:(廠內保留)
33:(廠內保留)
34:過轉矩檢出準位 1 (Pr5-16)
35:電動機1 轉矩補償(Pr5-01)
36:(廠內保留)
37:(廠內保留)
38:恆定轉矩輸出區恆速運轉中過電流失速防止準位
(Pr5-12)
39~ 52:(廠內保留)
53:輸出功率 (kW)
54:輸出容量 (kVA)
55:(廠內保留)
56:IGBT 模組或散熱器溫度-TH1(℃)
57:變頻器週溫—TH2 (℃)
58~59 (廠內保留)
60:變頻器過載累積時間 (Sec)
61~63:(廠內保留)
64:跳脫時DC-Bus 電壓(Vdc)
65:跳脫時輸出電壓值(Vac)
66:跳脫時輸出頻率 (Hz)
67:跳脫時IGBT 模組的溫度 (℃)
◎
68:跳脫時輸出電流值 (A)
69: 跳脫時變頻器週溫(℃)
◎
70~86:(廠內保留)
87: DC-Bus 漣波電(Vdc)
◎
88: PG 頻率 (Hz)
◎
89~132: (廠內保留)
Pr0-08
使用者定義比例係數
0~39(不使用)
0
40~60000(對應於Pr1-00 參數之含意)
Pr0-09
使用者定義比例之小數點位數
0~3 (0=無小數點,1=小數點1 位,
2=小數點2 位,3=小數點3 位)
0
Pr0-10
韌體版本
僅能讀取
x.xx
Pr0-11
EPROM 儲存設定
Bit 0
Bit 0
Bit 0
Bit 0
(bxxxx0)
0 FWD/REV轉向命令會儲存
b00000
1111 FWD/REV轉向命令不儲存,關電後再通
電會回復舊值
Bit
Bit
Bit
Bit 1111
(bxxx0x)
0 由PU來的頻率命令會儲存
1 由PU來的頻率命令不儲存,關電後再通
電會回復舊值
Bit
Bit
Bit
Bit 2222
(bxx0xx)
0 由RS-485通訊埠來的頻率命令會記憶
1111 由RS-485通訊埠來的頻率命令不記憶,
關電後再通電會回復舊值
Bit 3
Bit 3
Bit 3
Bit 3
(bx0xxx)
0 由Up/Down來的頻率命令會記憶
1 由Up/Down來的頻率命令不記憶,關電
後再通電會回復舊值
Bit 4
Bit 4
Bit 4
Bit 4
(b0xxxx)
0 所異動的參數會記憶.
1 所異動的參數不記憶,關電後再通電會
回復舊值
TOPVERT G1/H1/P1 系列
C-17
Pr0-12
最佳化自動加/減速設定
0:直線加速,直線減速(無自動加速/減速)
0
1:自動加速,直線減速
2:直線加速,自動減速
3:自動加速,自動減速
4:直線加/減速,但以自動加/減速做失速防止
★
★
★
★
Pr0-13
加/減速時間單位
0:0.01 秒
0
1:0.1 秒
2:1 秒
Pr0-14
PWM 載波頻率上限
0=0.7kHz
##
1~18kHz (H1 系列:2~36 kHz)
Pr0-15
PWM 載波頻率下限
0=0.7kHz
##
1~18kHz (H1 系列:2~36 kHz)
Pr0-16
自動穩壓功能(AVR)
0:開啟自動穩壓功能
0
1:取消自動穩壓功能
2:減速時取消自動穩壓功能
Pr0-17
自動節能運轉(AESO
AESO
AESO
AESO)及其它
Bit 0
Bit 0
Bit 0
Bit 0
(bxxxx0)
0 取消自動節能運轉
b00000
1 開啟自動節能運轉
Bit
Bit
Bit
Bit 1111
(bxxx0x)
0 最大輸出電壓可大於電源電壓
可過調變)
1 最大輸出電壓等於電源電壓
Bit
Bit
Bit
Bit 2222
(bxx0xx)
0 適用於:定轉矩通用負載
1 適用於:風機/水泵變轉矩負載
Bit 3
Bit 3
Bit 3
Bit 3
(bx0xxx)
0 負轉矩無滑差補償
1 負轉矩有滑差補償
Bit 4
Bit 4
Bit 4
Bit 4
(b0xxxx)
0 低噪音模式運轉
1 靜音模式運轉
Pr0-18
頻率命令來源設定
0: 由數位操作器(PU)
0
1: 由RS485通訊埠
2: 由外部類比信號端子
3: 由外部Up/Down 端子(多功能輸入端子 MIx)
4: 由PG 卡脈波輸入 (使用此功能需選購PG 回授卡)
◎
Pr0-19
運轉命令來源設定
0:由RS-485 通訊埠或數位操作器(PU)
0
1:由外部端子或數位操作器(PU)
2:由數位操作器(PU)
3:由外部端子
Pr0-20
停車/運轉/安全模式
Bit 0
Bit 0
Bit 0
Bit 0
(bxxxx0)
0 以減速煞車方式停止
b00000
1 以自由滑行方式停止
Bit
Bit
Bit
Bit 1111
(bxxx0x)
0 外部端子運轉命令Reset後不可重新
運轉
1 外部端子運轉命令Reset後可重新運
轉
Bit
Bit
Bit
Bit 2222
(bxx0xx)
0 外部端子不可電源通電運轉
1 外部端子可電源通電運轉
Bit 3
Bit 3
Bit 3
Bit 3
(bx0xxx)
0 正/反轉經過零點
1 正/反轉不經過零點
Bit 4
Bit 4
Bit 4
Bit 4
(b0xxxx)
0 高速區直線加/減速
1 高速區曲線加/減速
Pr0-21
轉向限制
0000
允許正反轉
0
1111
禁止反轉
2222
禁止正轉
Pr0-22
停機後等待時間
0.00~60.00 Sec
0.00
TOPVERT G1/H1/P1 系列
C-18
Pr0-23
散熱風扇控制及PID 方向
Bit 0
Bit 0
Bit 0
Bit 0
(bxxxx0)
0
通電後風扇即運轉
b00001
1
運轉命令執行後風扇才運轉
Bit
Bit
Bit
Bit 1111
(bxxx0x)
0 廠內保留
1
Bit
Bit
Bit
Bit 2222
(bxx0xx)
0 廠內保留
1
Bit 3
Bit 3
Bit 3
Bit 3
(bx0xxx)
0
PID可反方向運轉
1
PID禁止反方向運轉
Pr0-24
PU 飛梭旋鈕頻率解析度
0
0.01 Hz
1
1
0.10Hz
2
1.00Hz
3
10.00 Hz
◎
◎
◎
◎
Pr0-25
參數組別選擇
0
A 組參數
0
1
B 組參數
2
由MI3 選擇A 組或B 組參數
1
1
1
1 參數群
參數群
參數群
參數群:::: 基本參數
基本參數
基本參數
基本參數
參數
參數功能
設定範圍
出廠值
客戶
★
Pr1-00
最高操作頻率
10.00~600.00Hz
(H1 系列:100.0 ~6000.0Hz)
60.00/
50.00
★
Pr1-01
第一點頻率 1
(電動機1 額定頻率) (Fbase 1)
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
60.00/
50.00
Pr1-02
第一點電壓 1
(電動機1 額定電壓) (Vbase 1)
230V 機種:0.0~255.0V
230.0
460V 機種:0.0~510.0V
460.0
◎ 575V 機種:0.0~637.5V
575.0
★
Pr1-03
第二點頻率 1
(電動機1 中間頻率) (Fmid 1)
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
0.50
Pr1-04
第二點電壓 1
(電動機1 中間點電壓) (Fmid 1)
230V 機種:0.0~255.0V
5.0
460V 機種:0.0~510.0V
10.0
◎ 575V 機種:0.0~637.5V
12.5
★
★
★
★
Pr1-05
第三點頻率 1
(電動機 1 低點頻率) (Flow 1)
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
0.50
Pr1-06
第三點電壓1
(電動機 1 低點電壓) (Vlow 1)
230V 機種:0.0~255.0V
5.0
460V 機種:0.0~510.0V
10.0
◎ 575V 機種:0.0~637.5V
12.5
Pr1-07
0Hz 輸出電壓1
(電動機 1 0Hz 輸出電壓) (V0Hz 1)
230V 機種:0.0~25.5V
0.0
460V 機種:0.0~51.0V
◎ 575V 機種:0.0~63.7V
Pr1-08
啟動頻率
0.00~600.00Hz (H1 系列:00.0 ~6000.0Hz)
0.50
Pr1-09
輸出頻率上限
0.0~150.0%
(最高操作頻率Pr1-00 之設定值=100%)
110.0
Pr1-10
輸出頻率下限
0.0~100.0%
(最高操作頻率Pr1-00 之設定值=100%)
0.0
Pr1-11
第一加速時間
0.00~60000 Sec
##.##
Pr1-12
第一減速時間
0.00~60000 Sec
Pr1-13
第二加速時間
0.00~60000 Sec
Pr1-14
第二減速時間
0.00~60000 Sec
Pr1-15
寸動加速時間
0.00~60000 Sec
Pr1-16
寸動減速時間
0.00~60000 Sec
Pr1-17
寸動頻率
0.00~600.00Hz (H1 系列:00.0 ~6000.0Hz)
6.00
Pr1-18
第一/第二 - 加減速時間切換點的
頻率
0.00~600.00Hz (H1 系列:00.0 ~6000.0Hz)
0.00
Pr1-19
SSSS 曲線加速起始時間
0.00~12000 Sec
0.00
Pr1-20
SSSS 曲線加速到達時間
0.00~12000 Sec
0.00
Pr1-21
SSSS 曲線減速起始時間
0.00~12000 Sec
0.00
TOPVERT G1/H1/P1 系列
C-19
Pr1-22
SSSS 曲線減速到達時間
0.00~12000 Sec
0.00
Pr1-23
[Pr1-29] 減速時電壓偏移量
230 機種:-50.0~50.0 V
0.0
460V 機種:-100.0~100.0V
◎575V 機種:-125.0~125.0V
★
Pr1-24
[Pr1-23] 禁止設定頻率1 上限
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
0.00
★
Pr1-25
[Pr1-24] 禁止設定頻率1 下限
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
0.00
★
Pr1-26
[Pr1-25] 禁止設定頻率2 上限
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
0.00
★
Pr1-27
[Pr1-26] 禁止設定頻率2 下限
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
0.00
★
Pr1-28
[Pr1-27] 禁止設定頻率3 上限
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
0.00
★
Pr1-29
[Pr1-28] 禁止設定頻率3 下限
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
0.00
★
◎
Pr1-30
禁止設定頻率4 上限
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
0.00
★
◎
Pr1-31
禁止設定頻率4 下限
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
0.00
★
◎
Pr1-32
禁止設定頻率5 上限
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
0.00
★
◎
Pr1-33
禁止設定頻率5 下限
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
0.00
★
◎
Pr1-34
禁止設定頻率6 上限
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
0.00
★
◎
Pr1-35
禁止設定頻率6 下限
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
0.00
★
◎
Pr1-36
第一點頻率 2
(電動機2 額定頻率) (Fbase 2)
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
60.00/
50.00
◎
Pr1-37
第一點電壓 2
(電動機2 額定電壓) (Vbase 2)
230V 機種:0.0~255.0V
230.0
460V 機種:0.0~510.0V
460.0
575V 機種:0.0~637.5V
575.0
★
◎
Pr1-38
第二點頻率 2
(電動機2 中間頻率) (Fmid 2)
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
0.50
◎
Pr1-39
第二點電壓 2
(電動機2 中間電壓) (Vmid 2)
230V 機種:0.0~255.0V
5.0
460V 機種:0.0~510.0V
10.0
575V 機種:0.0~637.5V
12.5
★
◎
Pr1-40
第三點頻率 2
(電動機2 低點頻率) (Flow 2)
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
0.50
◎
Pr1-41
第三點電壓 2
(電動機2 低點電壓) (Vlow 2)
230V 機種:0.0~255.0V
5.0
460V 機種:0.0~510.0V
10.0
575V 機種:0.0~637.5V
12.5
◎
Pr1-42
0Hz 電壓 2
(電動機2 0Hz 輸出電壓) (V0Hz 2)
230V 機種:0.0~25.5V
0.0
460V 機種:0.0~51.0V
575V 機種:0.0~63.7V
2222 參數群
參數群
參數群
參數群:::: 數位
數位
數位
數位 輸入
輸入
輸入
輸入////輸出
輸出
輸出
輸出 相關參數
相關參數
相關參數
相關參數
參數
參數功能
設定範圍
出廠值
客戶
★
Pr2-00
外部運轉控制的組態
0:二線式(1):正轉/停止, 反轉/停止
0
1:二線式(2):運轉/停止, 反轉/正轉
2:三線式(MI1) 運轉,停止, 正轉/反轉
★
Pr2-01
多功能數位輸入 MI1
(三線式運轉時,STOP指定端子) 0:無定義
1
★
Pr2-02
多功能數位輸入 MI2
(計數輸入指定端子)
1:多段速命令一
2
TOPVERT G1/H1/P1 系列
C-20
★
Pr2-03
多功能數位輸入 MI3
(參數組別選擇指定端子)
2:多段速命令二
3
★
Pr2-04
多功能數位輸入 MI4
3:多段速命令三
4
★
Pr2-05
多功能數位輸入 MI5
4:多段速命令四
5
★
Pr2-06
(Pr2-26
Pr2-27
Pr2-28
也適用此
表)
多功能數位輸入 MI6
5:異常復歸命令(Reset)
14
6:計數器清除命令
7:第一,二加減速時間切換
8:禁止加/減速命令
9:強制頻率命令為AI1
10:強制頻率命令為AI2
11:強制頻率命令為AI3
12:強制停止
13:PID 功能取消
14:EF 外部異常輸入
15:外部中斷(B.B.)由下往上追蹤
16:外部中斷(B.B.)由上往下追蹤
17:強制運轉命令由外部端子
18:取消最佳化自動加速/減速
19:正轉寸動命令
20:反轉寸動命令
21:寸動命令
22:取消可編程自動程序運轉(PLC Run)
23:暫停可編程自動程序運轉(PLC Run)
24:頻率遞增命令(Up Command)
25:頻率遞減命令(Down Command)
26:零速以直流制動模式取代
27:暫時停機
28:取消 加/減速時齒隙暫停
29:取消擺頻功能
30:取消啟動時速度追蹤
31:EEPROM 不寫入
32: 計數器觸發信號輸入(指定MI2)
33~41:廠內保留
42: 電動機切換命令
◎
43: 電動機切換完成確認信號
◎
44: 禁止反轉
◎
45: 禁止正轉
◎
Pr2-07
頻率遞增/遞減之加/減速模式
Bit 0
Bit 0
Bit 0
Bit 0
(bxxxx0)
0 頻率遞增(Up)時依加速時間遞增
b00000
1 頻率遞增(Up)時依 Pr2-08 所指定
速率遞增
Bit
Bit
Bit
Bit 1111
(bxxx0x)
0 頻率遞減(Down)時依減速時間遞
減
1 頻率遞減(Down)時依 Pr2-08
所指定速率遞減
Bit 2
Bit 2
Bit 2
Bit 2
(bxx0xx)
廠內保留
Bit 3
Bit 3
Bit 3
Bit 3
(bx0xxx)
0 FWD/REV 端子依邊緣觸發動作
(Edge trigger)
◎
1 FWD/REV 端子依準位觸發動作
(Level trigger)
Bit 4
Bit 4
Bit 4
Bit 4
(b0xxxx)
0 加減速中PG 回授允許過補償
◎
1 加減速中PG 回授不允許過補償
Pr2-08
頻率遞增/遞減 (Up/Down) 命
令之指定速率
0.01~1.00 Hz/mSec (也等於:10~1000Hz/Sec)
0.01
Pr2-09
數位輸入端子濾波時間
0.000~30.000 Sec
0.005
◎
Pr2-10
數位輸入端子極性
00000~007FF (外部端子閉合定義為”0 ”)
h00000
Pr2-11
目標計數值
0~65500
0
TOPVERT G1/H1/P1 系列
C-21
Pr2-12
指定預警到達計數值
0~65500
0
Pr2-13
數位頻率輸出增益
1~20
1
Pr2-14
任意頻率到達1
0.00~600.00Hz (H1 系列:00.0 ~6000.0Hz)
60.00/
50.00
Pr2-15
任意頻率到達1 檢出輻度
0.00~600.00Hz (H1 系列:00.0 ~6000.0Hz)
2.00
Pr2-16
任意頻率到達2
0.00~600.00Hz (H1 系列:00.0 ~6000.0Hz)
60.00/
50.00
Pr2-17
任意頻率到達2 檢出輻度
0.00~600.00Hz (H1 系列:00.0 ~6000.0Hz)
2.00
Pr2-18
多功能數位輸出端子極性
00000~0003F
h00000
◎
Pr2-19
多功能數位輸出端子(DO)動作
延遲時間
0.000~60.000 mSec
0.003
Pr2-20
[Pr2-19]
多功能數位輸出 1 –
Relay 1
0: 無定義
11
Pr2-21
[Pr2-20]
多功能數位輸出 2 –
Relay 2
1:運轉中
1
Pr2-22
[Pr2-21]
多功能數位輸出 3 –
MO 1
2:運轉頻率到達1 (正轉及反轉均有效)
5
Pr2-23
[Pr2-22]
多功能數位輸出 4 –
MO 2
3:運轉頻率到達2 (正轉及反轉均有效)
9
◎
Pr2-24
[多功能數位輸出 5 –
MO 3]]]]
4:任意頻率到達 1 (正轉及反轉均有效)
0
◎
Pr2-25
[多功能數位輸出 6 – MO 4]
5:任意頻率到達 1 (只有正轉有效)
0
6: 任意頻率到達 2 (正轉及反轉均有效)
7:任意頻率到達 2 (只有正轉有效)
8:減速中
9:變頻器準備完成
10:低電壓警報(LU)(LUr)
11:變頻器故障
12:外部中斷中(B.B.)
13:零速(含停機)
14:零速 (必須在RUN 命令執行中)
15:目標計數值到達
16:指定預警計數值到達
17:可編程自動程序運轉 (PLC Run) 執行中
18:可編程自動程序運轉 (PLC Run)暫停
19:可編程自動程序運轉(PLC Run)
一階段運轉完成
20:可編程自動程序運轉 (PLC Run)完成
21:OH1 過熱預警告
22:加/減速時齒隙暫停中
23:變頻器設定為外部端子運轉控制模式
24:過轉矩檢出1(ot1)
25:脈波頻率輸出(僅適用於 MO2,Pr2-23)
26:軟體煞車輸出(僅適用MO1, Pr2-22)
27: 輔助電動機1
28: 輔助電動機2
29: 輔助電動機3
30:過轉矩檢出2 (ot2)
◎
31:OH2 過熱預警告
◎
32:電動機切換輸出
◎
33~47:廠內保留
48:主速頻率命令執行中
49: 自動程序運轉(PLC Run)第1 段執行中
50: 自動程序運轉(PLC Run)第2 段執行中
51: 自動程序運轉(PLC Run)第3 段執行中
52: 自動程序運轉(PLC Run)第4 段執行中
53: 自動程序運轉(PLC Run)第5 段執行中
54: 自動程序運轉(PLC Run)第6 段執行中
TOPVERT G1/H1/P1 系列
C-22
55: 自動程序運轉(PLC Run)第7 段執行中
56: 自動程序運轉(PLC Run)第8 段執行中
57: 自動程序運轉(PLC Run)第9 段執行中
58: 自動程序運轉(PLC Run)第10 段執行中
59: 自動程序運轉(PLC Run)第11 段執行中
60: 自動程序運轉(PLC Run)第12 段執行中
61: 自動程序運轉(PLC Run)第13 段執行中
62: 自動程序運轉(PLC Run)第14 段執行中
63: 自動程序運轉(PLC Run)第15 段執行中
64~79: 廠內保留
◎
Pr2-26
[多功能數位輸入 MI7]
如同Pr2-01~Pr2-06
0
◎
Pr2-27
[多功能數位輸入 MI8]
◎
Pr2-28
[多功能數位輸入 MI9]
3333 參數群
參數群
參數群
參數群:::: 類比
類比
類比
類比 輸入
輸入
輸入
輸入////輸出
輸出
輸出
輸出 相關參數
相關參數
相關參數
相關參數
參數
參數功能
設定範圍
出廠值
客戶
Pr3-00
類比輸入相加減功能
0
可相加減
0
1
不可相加減
Pr3-01
類比輸入濾波時間
0.00~2.00 Sec
0.10
Pr3-02
AI2
(Pr3-06
)
及
AI3
(Pr3-11
)
也適用
此表
AI1 類比輸入功能
0:無功能
1
1:頻率命令(Pr1-00=100%)
2:調整第一加/減速時間(如同Pr1-11,Pr1-12)
3:恆速中過電流失速防止準位調整=Pr5-12
(如同Pr5-12)
4:加速中過電流失速防止準位 (如同Pr5-10)
5:過轉矩檢出準位 1 調整(如同Pr5-16)
6:電動機1 自動轉矩補償調整(如同Pr5-01)
7:頻率命令來源單一為AI1 時的輔助頻率信號
8:頻率命令來源單一為AI2 時的輔助頻率信號
9:頻率命令來源單一為AI3 時的輔助頻率信號
10:主頻的輔助頻率信號
11:PID 回授信號
12:PID 偏移信號 (如同Pr7-05)
13:直流制動電流準位調整(如同Pr6-00)
14:運轉中輸出電壓調整
(僅適用於AI1: Pr3-02)
15:外部溫度信號顯示及保護
Pr3-03
AI1 類比輸入偏壓
-10.00~10.00V
0.00
Pr3-04
AI1 類比輸入增益
-500.0~+500.0%
100.0
Pr3-05
AI1 偏壓模式
0
以偏壓為中心
0
1
低於偏壓=偏壓
2
高於偏壓=偏壓
3
以偏壓為中心取絕對值
Pr3-06
AI2 類比輸入功能
如同Pr3-02
0
Pr3-07
AI2 類比輸入偏壓
0.00~20.00mA
4.00
Pr3-08
AI2 類比輸入增益
-500.0~+500.0%
100.0
Pr3-09
AI2 類比輸入偏壓模式
0
以偏壓為中心
1
1
低於偏壓=偏壓
2
高於偏壓=偏壓
3
以偏壓為中心取絕對值
Pr3-10
AI2 斷線處置選擇
0
不處理
0
1
以斷線前頻率繼續運轉
2
立即依減速停車方式停止
3
立即依滑行方式停止並顯示AcI.
Pr3-11
AI3 類比輸入功能
如同Pr3-02
0
Pr3-12
AI3 類比輸入偏壓
-10.00~10.00V
0.00
Pr3-13
AI3 類比輸入增益
-500.0~+500.0%
100.0
TOPVERT G1/H1/P1 系列
C-23
Pr3-14
AI3 類比輸入偏壓模式
0
以偏壓為中心
0
1
低於偏壓=偏壓
2
高於偏壓=偏壓
3
以偏壓為中心取絕對值
Pr3-15
類比輸出 1 功能選擇(AO1)
0:輸出頻率
0
Pr3-16
類比輸出 2 功能選擇(AO2)
1:命令頻率
0
2:電動機速度
3:輸出電流
4:輸出電壓
5:DC BUS 電壓
6:功率因數
7:輸出功率
8: AI1 值
9:AI2 值
10:AI3 值
11~12:廠內保留
13:輸出電壓命令
14:計數值
15:依Pr3-21 之設定值
16~23:廠內保留
24: 定義成多功能數位輸出(MOx)
Pr3-17
AO1 類比輸出增益
-900.0~900.0%
100.0
Pr3-18
AO2 類比輸出增益
-900.0~900.0%
80.0
Pr3-19
AO1 類比輸出偏壓
-10.00~10.00V
0.00
Pr3-20
AO2 類比輸出偏壓
0.00~20.00mA
4.00
Pr3-21
使用者定義的類比輸出特定值
0.0~100.0%
0.0
4444 參數群
參數群
參數群
參數群:::: 多段速運轉
多段速運轉
多段速運轉
多段速運轉(MSS Run)
(MSS Run)
(MSS Run)
(MSS Run)與可編程自動程序運轉
與可編程自動程序運轉
與可編程自動程序運轉
與可編程自動程序運轉( PLC Run )
( PLC Run )
( PLC Run )
( PLC Run )相關參
相關參
相關參
相關參數
數
數
數
參數
參數功能
設定範圍
出廠值
客戶
Pr4-00 PLC Run 或 MSS Run 第一段速度
0.00~600.00Hz (H1 系列:00.0~6000.0Hz)
0.00
Pr4-01 PLC Run 或 MSS Run 第二段速度
0.00~600.00Hz (H1 系列:00.0~6000.0Hz)
0.00
Pr4-02 PLC Run 或 MSS Run 第三段速度
0.00~600.00Hz (H1 系列:00.0~6000.0Hz)
0.00
Pr4-03 PLC Run 或 MSS Run 第四段速度
0.00~600.00Hz (H1 系列:00.0~6000.0Hz)
0.00
Pr4-04 PLC Run 或 MSS Run 第五段速度
0.00~600.00Hz (H1 系列:00.0~6000.0Hz)
0.00
Pr4-05 PLC Run 或 MSS Run 第六段速度
0.00~600.00Hz (H1 系列:00.0~6000.0Hz)
0.00
Pr4-06 PLC Run 或 MSS Run 第七段速度
0.00~600.00Hz (H1 系列:00.0~6000.0Hz)
0.00
Pr4-07 PLC Run 或 MSS Run 第八段速度
0.00~600.00Hz (H1 系列:00.0~6000.0Hz)
0.00
Pr4-08 PLC Run 或 MSS Run 第九段速度
0.00~600.00Hz (H1 系列:00.0~6000.0Hz)
0.00
Pr4-09 PLC Run 或 MSS Run 第十段速度
0.00~600.00Hz (H1 系列:00.0~6000.0Hz)
0.00
Pr4-10 PLC Run 或 MSS Run 第十一段速度
0.00~600.00Hz (H1 系列:00.0~6000.0Hz)
0.00
Pr4-11 PLC Run 或 MSS Run 第十二段速度
0.00~600.00Hz (H1 系列:00.0~6000.0Hz)
0.00
Pr4-12 PLC Run 或 MSS Run 第十三段速度
0.00~600.00Hz (H1 系列:00.0~6000.0Hz)
0.00
Pr4-13 PLC Run 或 MSS Run 第十四段速度
0.00~600.00Hz (H1 系列:00.0~6000.0Hz)
0.00
Pr4-14 PLC Run 或 MSS Run 第十五段速度
0.00~600.00Hz (H1 系列:00.0~6000.0Hz)
0.00
Pr4-15 PLC Run 或 MSS Run 主速時間
0.0~6550.0 Sec
0.0
Pr4-16 PLC Run 或 MSS Run 第一段時間
0.0~6550.0 Sec
0.0
Pr4-17 PLC Run 或 MSS Run 第二段時間
0.0~6550.0 Sec
0.0
Pr4-18 PLC Run 或 MSS Run 第三段時間
0.0~6550.0 Sec
0.0
Pr4-19 PLC Run 或 MSS Run 第四段時間
0.0~6550.0 Sec
0.0
Pr4-20 PLC Run 或 MSS Run 第五段時間
0.0~6550.0 Sec
0.0
Pr4-21 PLC Run 或 MSS Run 第六段時間
0.0~6550.0 Sec
0.0
Pr4-22 PLC Run 或 MSS Run 第七段時間
0.0~6550.0 Sec
0.0
Pr4-23 PLC Run 或 MSS Run 第八段時間
0.0~6550.0 Sec
0.0
Pr4-24 PLC Run 或 MSS Run 第九段時間
0.0~6550.0 Sec
0.0
Pr4-25 PLC Run 或 MSS Run 第十段時間
0.0~6550.0 Sec
0.0
TOPVERT G1/H1/P1 系列
C-24
Pr4-26 PLC Run 或 MSS Run 第十一段時間
0.0~6550.0 Sec
0.0
Pr4-27 PLC Run 或 MSS Run 第十二段時間
0.0~6550.0 Sec
0.0
Pr4-28 PLC Run 或 MSS Run 第十三段時間
0.0~6550.0 Sec
0.0
Pr4-29 PLC Run 或 MSS Run 第十四段時間
0.0~6550.0 Sec
0.0
Pr4-30 PLC Run 或 MSS Run 第十五段時間
0.0~6550.0 Sec
0.0
Pr4-31 PLC Run 或 MSS Run 時間倍數
1~10
1
◎ Pr4-32 PLC Run 或 MSS Run 各段速之旋轉
方向
00000~07FFF(0:正轉;1:反轉)
h00000
Pr4-33 (PLC Run)可編程自動程序
運轉模式
Bit 0
Bit 0
Bit 0
Bit 0
(bxxxx0)
0 旋轉方向由Pr4-32 決定
b01000
1 旋轉方向由主速決定
Bit
Bit
Bit
Bit 1111
(bxxx0x)
0 無零速間隔運轉(連續模式)
1 有零速間隔運轉(STOP 模式)
Bit
Bit
Bit
Bit 2222
(bxx0xx)
0 暫停時以零速運轉
1 暫停時以該段原定速度運轉
Bit
Bit
Bit
Bit 3333
(bx0xxx)
0 電源中斷復電後,再啟動時從
頭執行
◎
1 電源中斷復電後,再啟動時從中
斷處繼續執行
Pr4-34 (PLC Run)可編程自動程序
運轉執行週期
0:可編程自動程序運轉無效
0
1~60000: 執行 1~60000 次週期
60001:持續循環運轉
Pr4-35 (PLC Run)可編程自動程序
運轉完成後之動作
0~15:依主速或多段速之一運轉(0=主速)
16
16:停止運轉
Pr4-36 (MSS Run)多段速運轉模式
Bit 0
Bit 0
Bit 0
Bit 0
(bxxxx0)
0 旋轉方向由Pr4-32 決定
b00001
1 旋轉方向由主速決定
Bit
Bit
Bit
Bit 1111
(bxxx0x)
0 各段速的運轉時間由依MIx之多
段速端子控制
1 各段速的運轉時間由
Pr4-15~Pr4-30 的設定值決定
Bit
Bit
Bit
Bit 2222
(bxx0xx)
0 無零速間隔運轉(連續模式)
1 有零速間隔運轉(STOP 模式)
Bit
Bit
Bit
Bit 3333
(bx0xxx)
0 PID偏移無效
1 多段速 + PID 偏移有效
Bit
Bit
Bit
Bit 4444
(b0xxxx)
0 運轉中JOG命令無效
◎
1 運轉中JOG 命令有效
◎
5
5
5
5 參數群
參數群
參數群
參數群:
:
:
: 電動機調適及保護參數
電動機調適及保護參數
電動機調適及保護參數
電動機調適及保護參數
參數
參數功能
設定範圍
出廠值
客戶
★
Pr5-00
電動機1 滿載電流
安培 (變頻器額定輸出電流之10~120%)
##.##
Pr5-01
電動機1 轉矩補償
0.0~25.0 %
0.0
◎
Pr5-02
電動機1 滑差補償
0~20% RPM (依Pr1-01 設定頻率對應之2 極至20 極電動
機的同步轉速*20%)
0
Pr5-03
電動機1 極數
2~20
4
Pr5-04
電動機1 R1 值
0.000~65.535 Ω
0.0
★
Pr5-05
電動機參數自動調適及控
制模式切換
0
不自動調適
0
1
依Pr5-00 所設定的電流值執行電動機參數自動調
適並切換成無感測向量控制模式
2
重置已調適的參數並恢復成 V/F 模式
★
Pr5-06
低電壓保護恢復準位
230V 機種:160~220Vac
180
460V 機種:320~440Vac
360
◎575V 機種:400~550Vac
450
Pr5-07
過電壓失速防止準位
230V 機種:320~500VDC
380
460V 機種:640~1000VDC
760
◎575V 機種:800~1250VDC
950
Pr5-08
回升動態煞車準位設定
230V 機種:320~500VDC
373
460V 機種:640~1000VDC
746
◎575V 機種:800~1250VDC
932
TOPVERT G1/H1/P1 系列
C-25
Pr5-09
電源欠相保護
0 提出警告但繼續運轉 (若輸出電流在額定的50%以下)
0
1 提出警告並且減速停止
2 提出警告並且滑行停止
Pr5-10
恆定轉矩輸出區加速時過
電流失速防止準位
安培 (變頻器額定輸出電流之10~250%)
##.##
Pr5-11
恆定馬力輸出區加速時過
電流失速防止下限準位
安培 (變頻器額定輸出電流之0~250%)
##.##
Pr5-12
恆定轉矩輸出區恆速運轉
中過電流失速防止準位
安培 (變頻器額定輸出電流之10~250%)
##.##
Pr5-13
恆定馬力輸出區恆速運轉
中過電流失速防止下限準
位
安培 (變頻器額定輸出電流之0~250%)
##.##
Pr5-14
失速防止動作時之減速時
間
0.50~120.00 Sec
3.00
Pr5-15
過轉矩檢出功能1 選擇
(ot1)
0
不檢測
0
1
恒速運轉中過轉矩檢出時停止運轉
2
恒速運轉中過轉矩檢出時繼續運轉
3
運轉中過轉矩檢出時停止運轉
4
運轉中過轉矩檢出時繼續運轉
Pr5-16
過轉矩檢出準位 1
安培 (變頻器額定輸出電流之10~250%)
##.##
Pr5-17
過轉矩檢出時間 1
0.0~60.0 Sec
0.1
Pr5-18
電動機1 電子熱動電驛選
擇 (oL1)
0
電子熱動電驛功能關閉
0
1
使用變頻專用電動機
(獨立散熱,不需考量變頻器的輸出頻率 )
2
使用標準電動機
(同軸散熱,需考量變頻器的輸出頻率)
Pr5-19
電動機1 電子熱動電驛動
作時間
30~600 Sec
60
Pr5-20
IGBT 過熱預警告溫度設定
1 (OH1)
0.0~110.0℃
85.0
◎
Pr5-21
過轉矩檢出功能2 選擇
(ot2)
0
不檢測
0
1
恒速運轉中過轉矩檢出時停止運轉
2
恒速運轉中過轉矩檢出時繼續運轉
3
運轉中過轉矩檢出時停止運轉
4
運轉中過轉矩檢出時繼續運轉
◎
Pr5-22
過轉矩檢出準位 2
安培 (變頻器額定輸出電流之10~250%)
##.##
◎
Pr5-23
過轉矩檢出時間 2
0.0~60.0 Sec
0.1
Pr5-24
[Pr5
[Pr5
[Pr5
[Pr5----21]
21]
21]
21] 最後一次異常記錄 0: 無異常記錄
16: HPF (硬體保護
迴路異常)
32: ot2(過轉矩2
檢出動作)
0
Pr5-25
[Pr5
[Pr5
[Pr5
[Pr5----22]
22]
22]
22] 前一次異常記錄
1: Oc
(輸出側過電流)
17: oH1 (IGBT 模組
內部或散熱器溫度
過高)
33: oL2(電動機2
過負載)
0
Pr5-26
[Pr5
[Pr5
[Pr5
[Pr5----23]
23]
23]
23] 前二次異常記錄
2: oU
(DC-bus 過電壓)
18: oH2 (變頻器箱
體週溫過高)
(或其它特定監測點
溫度超過容許值)
34: rnot
(電動機切換異常)
0
Pr5-27
[Pr5
[Pr5
[Pr5
[Pr5----24]
24]
24]
24] 前三次異常記錄
3: GF
(輸出側對地漏電)
19: SoFt (預充電限
流迴路異常)
0
◎
Pr5-28
前四次異常記錄
4: SC
(IGBT 模組異常)
20: ACI. (AI2 類比
輸入迴路斷線)
36: LUr (運轉中
DC-bus 低電壓)
0
◎
Pr5-29
前五次異常記錄
5: oL(變頻器過載) 21: ASC (RS485 串
列埠通訊傳輸逾時)
37: oUd (減速時
DC-bus 過電壓)
0
◎
Pr5-30
前六次異常記錄
6: oL1(電動機1 過
負載)
22: PI.d (PID 回授
訊號異常)
38: x CoPY
(參數複製錯誤)
0
◎
Pr5-31
前七次異常記錄
7: ot1(過轉矩1
檢出動作)
23: Pu (操作器(PU)
斷線逾時)
39: LU
(DC-bus 低電壓)
0
TOPVERT G1/H1/P1 系列
C-26
◎
Pr5-32
前八次異常記錄
8: oCn (恆速運轉中
輸出側過電流)
24:tunE (電動機參
數調適失敗)
40: bb (外部中斷)
0
◎
Pr5-33
前九次異常記錄
9: oCA (加速時輸出
側過電流)
25:bF (動能煞車迴
路異常)
0
◎
Pr5-34
前十次異常記錄
10: oCd (減速時輸
出側過電流)
26:PG
(PG 斷線/異常)
0
◎
Pr5-35
前十一次異常記錄
11: EP1
(EEPROM 記憶體資
料讀出異常)
27:PHL DC-Bus連波
電壓過高
(電源欠相)
0
◎
Pr5-36
前十二次異常記錄
12: EP2
(EEPROM 記憶體資
料寫入異常)
28:CC (停機中電流
訊號異常)
0
◎
Pr5-37
前十三次異常記錄 13: EF(外部異常輸
入動作)
29:CPu (變頻器偵
測線路異常)
0
◎
Pr5-38
前十四次異常記錄
14: Ct1 (U 相電流
傳感迴路或A/D 轉
換迴路異常)
30:FAn
(散熱風扇異常)
0
◎
Pr5-39
前十五次異常記錄
15: Ct2 (W 相電流
傳感迴路或A/D 轉
換迴路異常)
31: Anl (類比輸入
信號異常)
0
★
Pr5-40
電動機2 滿載電流
安培 (變頻器額定輸出電流之10~120%)
##.##
◎
Pr5-41
電動機2 自動轉矩補償
0.0~25.0%
0.0
◎
Pr5-42
電動機2 滑差補償
0~20% RPM (依Pr1-36 設定頻率對應之2 極
至20 極電動機的同步轉速*20%)
0
◎
Pr5-43
電動機2 極數
2~20
4
◎
Pr5-44
電動機2 R1 值
0.000~65.535Ω
0.0
◎
Pr5-45
電動機2 電子熱動電驛選擇(oL2)
0 電子熱動電驛功能關閉
0
1 使用變頻專用電動機
(獨立散熱,不需考量變頻器的輸出頻率 )
2 使用標準電動機
(同軸散熱,需考量變頻器的輸出頻率)
◎
Pr5-46
電動機2 電子熱動電驛動作時間
30~600 Sec
60
◎
Pr5-47
變頻器過熱預警告溫度設定2 (OH2)
0.0~110.0℃
75.0
◎
Pr5-48
電動機切換完成確認信號之允許等待
時間
0.00~60.00 Sec
0.05
◎
Pr5-49
電動機切換模式
Bit 0
Bit 0
Bit 0
Bit 0
(bxxxx0)
0 運轉中不可切換
b00000
1 運轉中可切換
Bit
Bit
Bit
Bit 1111
(bxxx0x)
0 切換時不需等待確認信號
1 切換時必需等待確認信號
6
6
6
6 參數群
參數群
參數群
參數群:::: 特殊參數
特殊參數
特殊參數
特殊參數
參數
參數功能
設定範圍
出廠值
客戶
Pr6-00 直流制動電流準位
安培 (變頻器額定輸出電流之0~125%)
##.##
Pr6-01 啟動時直流制動時間
0.00~60.00 Sec
0.00
Pr6-02 停車時直流制動時間
0.00~60.00 Sec
0.00
Pr6-03 停車時直流制動起始頻率
0.00~600.00Hz (H1 系列:00.0 ~6000.0Hz)
0.00
Pr6-04 直流制動電壓的增加速率
0.01~300.00%
20.00
Pr6-05 瞬時停電後再運轉選擇
0 瞬時停電後不繼續運轉
0
1 瞬時停電後由停電前速度往下追蹤繼續運轉
2 瞬時停電後由啟動頻率往上追蹤繼續運轉
Pr6-06 允許瞬時停電之最長時間設定
0.1~5.0 Sec
2.0
Pr6-07 速度追蹤之延遲時間設定(B.B.時間) 0.1~5.0 Sec
0.5
Pr6-08 速度追蹤動作電流準位
安培(變頻器額定輸出電流之20~200%)
##.##
Pr6-09 速度追蹤減速時間
0.50~120.00 Sec
3.00
TOPVERT G1/H1/P1 系列
C-27
Pr6-10
異常自動再啟動次數
0~30
0
Pr6-11
啟動時速度追蹤
0
不執行啟動時速度追蹤
0
1
依頻率命令做速度追蹤
2
只執行正向速度追蹤
3
只執行反向速度追蹤
4
執行正/反向速度追蹤 (正向優先)
5
執行反/正向速度追蹤 (反向優先)
Pr6-12
正向啟動時速度追蹤頻率
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
60.00/
50.00
Pr6-13
反向啟動時速度追蹤頻率
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
60.00/
50.00
Pr6-14
加速時齒隙暫停時間
0.00~60.00 Sec
0.00
Pr6-15
加速時齒隙暫停頻率
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
6.00
Pr6-16
減速時齒隙暫停時間
0.00~60.00 Sec
0.00
Pr6-17
減速時齒隙減速暫停頻率
0.00~600.00Hz
(H1 系列:00.0 ~6000.0Hz)
6.00
Pr6-18
齒隙暫停中之電流限制
安培 (變頻器額定輸出電流之0~150%)
##.##
Pr6-19
擺頻功能跳躍頻率
0.00~100.00Hz
0.00
Pr6-20
擺頻功能頻率寬度
0.00~200.00Hz
0.00
7
7
7
7 參數群
參數群
參數群
參數群:
:
:
: PID
PID
PID
PID 及
及
及
及 通訊傳輸相關參數
通訊傳輸相關參數
通訊傳輸相關參數
通訊傳輸相關參數
參數
參數功能
設定範圍
出廠值
客戶
Pr7-00
PID 比例值增益(P)
0~500%
80
Pr7-01
PID 積分時間 (I)
0.00~100.00 Sec
1.00
0.00:無積分
Pr7-02
PID 微分時間 (D)
0.00~5.00 Sec
0.00
Pr7-03
PID 積分上限值
0.0~100.0%
100.0
Pr7-04
PID 輸出頻率限制
0.0~100.0%
100.0
Pr7-05
PID 偏移量
-100.0~+100.0%
0.0
Pr7-06
PID 濾波延遲時間
0.000~0.100 Sec
0.000
Pr7-07
PID 回授訊號異常檢出時間
0.0~6000.0 Sec
0.0
Pr7-08
PID 回授訊號錯誤處置方式
0
警告但繼續運轉
0
1
警告且減速停止
2
警告且滑行停止
Pr7-09
操作器 (PU) 斷線處置方式
0
警告且減速停止
0
1
警告且滑行停止
Pr7-10
操作器 (PU) 斷線逾時檢出
0.0:不檢出且繼續運轉
0.0
0.1~60.0 Sec
Pr7-11
RS-485 串列通訊埠位址
1~254
1
Pr7-12
RS-485 串列通訊埠傳輸速率
1.2~125 k bps(位元∕秒)
9.6
Pr7-13
RS-485 串列通訊埠傳輸錯誤處置
0
警告但繼續運轉
3
1
警告且減速停止
2
警告且滑行停止
3
不警告且繼續運轉
Pr7-14
RS-485 串列通訊埠傳輸逾時檢出
0.0: 無傳輸逾時檢出
0.0
0.1~60.0 Sec
Pr7-15
RS-485 通訊協定
0:7,N,2 ASCII
0
1:7,E,1 ASCII
2:7,O,1 ASCII
3:7,E,2 ASCII
4:7,O,2 ASCII
5:8,N,1 ASCII
6:8,N,2 ASCII
7:8,E,1 ASCII
8:8,O,1 ASCII
TOPVERT G1/H1/P1 系列
C-28
9:8,E,2 ASCII
10:8,O,2 ASCII
11:8,N,1 RTU
12:8,N,2 RTU
13:8,E,1 RTU
14:8,O,1 RTU
15:8,E,2 RTU
16:8,O,2 RTU
8
8
8
8 參數群
參數群
參數群
參數群:
:
:
: 風機
風機
風機
風機,,,,水泵控制相關參數
水泵控制相關參數
水泵控制相關參數
水泵控制相關參數
參數
參數功能
設定範圍
出廠值
客戶
★
Pr8-00
V/F 曲線選擇
0
V/F 曲線由參數群 1 設定
0
1
1.5次方曲線
2
2次方曲線
Pr8-01
輔助電動機啟動頻率
0.00~600.00Hz (H1 系列:00.0 ~6000.0Hz)
0.00
Pr8-02
輔助電動機停止頻率
5.00~600.00Hz (H1 系列:50.0 ~6000.0Hz)
5.00
Pr8-03
輔助電動機啟動延時
0.0~6000.0Sec
0.0
Pr8-04
輔助電動機停止延時
0.0~6000.0Sec
0.0
Pr8-05
睡眠頻率
0.00~600.00Hz (H1 系列:00.0 ~6000.0Hz)
0.00
Pr8-06
甦醒頻率
0.00~600.00Hz (H1 系列:00.0 ~6000.0Hz)
0.00
Pr8-07
睡眠時間
0.0~6000.0 Sec
0.0
9
9
9
9 參數群
參數群
參數群
參數群:::: 速度
速度
速度
速度回授控制相關參數
回授控制相關參數
回授控制相關參數
回授控制相關參數 (使用此參數群需選購PG 回授卡)
參數
參數功能
設定範圍
出廠值
客戶
★
Pr9-00
PG 旋轉一圈的脈波數
1~5000 PPR
1024
★
Pr9-01
PG 功能及型式設定
0
無使用PG 功能
0
1
雙向使用,A/B 相脈波列,A 相超前B 相90
度視為正轉
2
雙向使用,A/B 相脈波列,B 相超前A 相90 度
視為正轉
3
(廠內保留)
4
PID 回授反向
◎
5
PID 回授正向
◎
6
(廠內保留)
7
(廠內保留)
8
反轉頻率命令 (Pr0-18=4)
◎
9
正轉頻率命令 (Pr0-18=4)
◎
10 (廠內保留)
Pr9-02
PG 速度顯示濾波時間
0.000~1.000 秒
0.03
Pr9-03
PG 回授速度控制比例增益值(P)
0.0~500.0%
20.0
Pr9-04
PG 回授速度控制積分時間(I)
0.00:
:
:
: 無積分
0.50
0.00 ~10.00 Sec
Pr9-05
PG 回授速度控制微分時間(D)
0.00~5.00 秒
0.00
Pr9-06
PG 回授速度控制滑差補償限制
0.00~150.00Hz
20.00
Pr9-07
PG 回授速度控制訊號錯誤處理方式
0
警告但繼續運轉
0
1
警告且減速停止
2
警告且滑行停止
Pr9-08
PG 回授速度控制異常偵測時間
0.00~10.00 秒
0.10
◎
Pr9-09
PG 回授速度控制補償限制
0~900 RPM
90
TOPVERT G1/H1/P1 系列
C-29
錯誤訊息指示與故障排除
錯誤訊息指示與故障排除
錯誤訊息指示與故障排除
錯誤訊息指示與故障排除
變頻器本身有過電壓,低電壓及過電流等多項警示訊息及保護功能,一旦異常故障發生,保護功能
動作,變頻器停止輸出,電動機滑行停止。異常原因會顯示於數位操作器,同時異常接點輸出端子動
作,請依變頻器之異常顯示符號對照其異常原因及處置方法。異常記錄會儲存在變頻器內部記憶體
(可記錄最近16 次異常訊息),可由數位操作器讀出也可經通信方式讀取。而當發生警告機能動作時,
僅數位操作器上閃爍顯示警告內容 (有些例外),異常接點輸出端子不動作。
變頻器由IC,電阻,電容,電晶體等電子零件及冷卻風扇,電驛等為數眾多的零件組成,這些零件不
是能夠永久不壞,不是可以永久使用,即使在正常環境運用,若超過其耐用年限,則容易發生故障。
因此要實施預防性定期檢查,把不符合規格要求或已有品質不良品發掘出來,及早摒除會造成變頻
器不良之潛在原因,同時也把逾期耐用年限的各部品趁機會換掉,以確保良好可安全地運轉。平常就
需要從外部目視檢查變頻器的運轉,確認沒有異常狀況發生,並檢查是否有下列警示訊息發生。
異常跳脫
異常跳脫
異常跳脫
異常跳脫復歸
復歸
復歸
復歸::::
當異常發生後
當異常發生後
當異常發生後
當異常發生後,,,,需等待
需等待
需等待
需等待5555秒後
秒後
秒後
秒後(oC
(oC
(oC
(oC、
、
、
、GF
GF
GF
GF、
、
、
、SC
SC
SC
SC異常需等待
異常需等待
異常需等待
異常需等待60
60
60
60秒後
秒後
秒後
秒後)))),待消除警報原因後,才能有效執行異常復
歸。執行異常復歸方式有三: 1. 由PU操作器上的RESET鍵
2. 將外部端子設定為”異常復歸指令”並導通此端子
3. 以通訊方式傳送異常復歸指令
任何異常警報解除前,應使運轉信號為斷路(OFF)狀態,以防止異常訊號復歸後立即重新運轉而導致機械
損害或人員傷亡。
異常
異常
異常
異常訊息
訊息
訊息
訊息及排除方法
及排除方法
及排除方法
及排除方法
顯示符號 異常現象說明 (符號字元) {異常碼}
排除方法
輸出側過電流
(oC) {01}
檢查與電動機連接線是否有短路現象或接地
延長加速時間(Pr1-11, Pr1-12)
檢查電動機額定與變頻器額定是否相匹配
檢查變頻器與電動機的螺絲有無鬆動
檢查電動機是否有超額負載
是否驅動特殊馬達(高速馬達或脈衝馬達)
異常排除需等待
異常排除需等待
異常排除需等待
異常排除需等待60
60
60
60秒後
秒後
秒後
秒後,
,
,
,才能有效復歸
才能有效復歸
才能有效復歸
才能有效復歸(RESET)
(RESET)
(RESET)
(RESET)
DC-bus過電壓
(oU) {02}
檢查電源電壓是否在變頻器額定輸入電壓範圍
內,並監測是否有突波電壓產生
若是由於電動機慣量回升電壓,造成變頻器內
部直流高壓側電壓過高,可加長減速時間或加
裝煞車器及煞車電阻。(選配)
減速時DC-bus過電壓
(oUd) {37}
檢查電源電壓是否在變頻器額定輸入電壓範圍
內,並監測是否有突波電壓產生
電動機慣量回升電壓,造成變頻器內部直流高
壓側電壓過高,可加長減速時間或加裝煞車器
及煞車電阻。(選用)
輸出側對地漏電
(GF) {03}
變頻器偵測到輸出端對地漏電且接地電
流高於變頻器額定電流的50%以上。
注意
注意
注意
注意::::此保護係針對變頻器而
此保護係針對變頻器而
此保護係針對變頻器而
此保護係針對變頻器而非人體
非人體
非人體
非人體。
。
。
。
檢查與電動機連線是否有短路現象或接地
確定IGBT功率模組是否損壞
檢查輸出側接線是否絕緣不良
異常排除需等待
異常排除需等待
異常排除需等待
異常排除需等待60
60
60
60秒後
秒後
秒後
秒後,
,
,
,才能有效復歸
才能有效復歸
才能有效復歸
才能有效復歸(RESET)
(RESET)
(RESET)
(RESET)
TOPVERT G1/H1/P1 系列
C-30
IGBT模組異常
(SC){04}
變頻器偵測到 IGBT 模組轉態異常
檢查電動機的阻抗及絕緣是否正常
檢查與電動機連接線是否有短路現象
將變頻器的電動機連接線切斷後,若仍發生則
確定IGBT功率模組異常--送廠維修
異常排除需等待
異常排除需等待
異常排除需等待
異常排除需等待60
60
60
60秒後
秒後
秒後
秒後,
,
,
,才能有效復歸
才能有效復歸
才能有效復歸
才能有效復歸(RESET)
(RESET)
(RESET)
(RESET)
變頻器過載
(oL){05}
輸出電流長時間超過可承受的電流
G1系列:額定電流的150%可承受60秒
H1系列:額定電流的150%可承受60秒
P1系列:額定電流的125%可承受60秒
減輕負載及延長加速時間
檢查電動機是否過負載
減低(Pr5-01) 轉矩提升設定值
選用較大輸出容量變頻器
電動機1 過負載
(oL1) {06}
(電子熱動電驛1保護動作)
V/F 1曲線設定是否適當
是否長時間低速運轉
檢查電動機1是否過載
檢查(Pr5-00) 電動機1額定電流值是否適當
檢查電子熱動電驛1功能設定(Pr5-18~ Pr5-19)
增加電動機1容量
過轉矩1檢出動作
(ot1) {07}
檢查電動機1負載是否過大
檢查(Pr5-00) 電動機1額定電流值是否適當
檢查過轉矩檢出位準1設定值(Pr5-15~Pr5-17)
機械負載是否異常
增加電動機1容量, 選用較大輸出容量變頻器
恆速運轉中輸出側過電流
(oCn) {08}
輸出連接線是否絕緣不良
檢查電動機是否堵死
更換較大輸出容量的變頻器
加速時輸出側過電流
(oCA) {09}
檢查變頻器與電動機的螺絲有無鬆動
檢查輸出連接線是否絕緣不良
延長加速時間
減低(Pr5-01) 轉矩提升設定值
更換較大輸出容量的變頻器
減速時輸出側過電流
(oCd) {10}
輸出連接線是否絕緣不良
延長減速時間
更換較大輸出容量的變頻器
EEPROM記憶體資料讀出異常
(EP1) {11}
檢查變頻器的電源雹壓是否在容許範圍內
待顯示幕熄滅後再重新上電
將參數復歸為出廠設定,若無效則送廠維修
EEPROM記憶體資料寫入異常
(EP2) {12}
外部異常輸入動作
(EF) {13}
(Pr2-01~Pr2-06或Pr2-26~Pr2-28 之一
=14 且作動 )
清除外部故障來源後執行RESET命令即可復歸
U 相電流傳感迴路或CPU板A/D轉換迴路
異常
(Ct1) {14}
將變頻器的電源切斷後,待顯示幕熄滅後再重
新上電後,若再次出現異常則送廠維修。
更換控制板或U 相電流傳感器
TOPVERT G1/H1/P1 系列
C-31
W 相電流傳感迴路或CPU板A/D轉換迴路
異常
(Ct2) {15}
將變頻器的電源切斷後,待顯示幕熄滅後再重
新上電後,若再次出現異常則送廠維修。
更換控制板或W 相電流傳感器
硬體保護迴路異常
(HPF) {16}
將變頻器的電源切斷後,待顯示幕熄滅後再重
新上電後,若再次出現異常則送廠維修。
IGBT模組內部或散熱器溫度過高
(oH1) {17}
檢查風扇動作是否正常
檢查環境溫度是否過高
檢查散熱器是否有異物或油污覆蓋
檢查散熱風道是否暢通
檢查是否有足夠散熱空間及足夠冷空氣對流
變頻器箱體週溫過高
(oH2) {18}
(或其它特定監測點溫度超過容許值)
檢查風扇動作是否正常
檢查環境溫度是否過高
檢查是否有足夠散熱空間及足夠冷空氣對流
檢查是否按裝變頻器的箱體內部積熱
預充電限流迴路異常
(SoFt) {19}
將變頻器的電源切斷後,待顯示幕熄滅後再重
新上電後,若再次出現異常則送廠維修。
AI2 類比輸入迴路斷線
(ACI.) {20}
檢查AI2 信號是否小於4mA
檢查AI2 配線
RS485串列埠通訊傳輸逾時
(ASC) {21}
檢查RS-485配線
PID回授訊號異常
(PI.d) {22}
檢查PID回授配線
檢查PID參數是否設定恰當
設定為有PG 回授控制時,Encoder 設定參數是
否正確。
操作器(PU)斷線逾時
(Pu) {23}
檢查Keypad連接線
電動機參數調適失敗
(tunE) {24}
檢查電動機接線是否正確
變頻器的輸出容量與電動機容量是否懸殊
重新檢查配線及參數後再執行
動能煞車迴路異常
(bF) {25}
將變頻器的電源切斷後,待顯示幕熄滅後再重
新上電後,若再次出現異常則送廠維修。
PG斷線/異常
(PG) {26}
檢查PG連接線
檢查電動機有無堵死
變頻器內部DC-Bus連波電壓過高
(電源欠相)
(PHL) {27}
電源輸入異常所引起
電源輸入異常所引起
電源輸入異常所引起
電源輸入異常所引起::::
檢查電源電壓是否正常
檢查電源三相雹壓是否平衡
檢查電源輸入端點螺絲是否鎖緊
是否三相電源機種只接單相電源或欠相
直流濾波電容異常所
直流濾波電容異常所
直流濾波電容異常所
直流濾波電容異常所引起
引起
引起
引起::::
檢查直流濾波電容是否已老化
停機中電流訊號異常,電流偵測硬體電
路異常
(CC) {28}
偶爾發生且復歸後即恢復正常,為雜訊干擾。
復歸無效則送廠維修
變頻器偵測線路異常
(CPu) {29}
將變頻器的電源切斷後,待顯示字幕熄滅後再
重新上電,若再次出現異常則送廠維修。
散熱風扇異常
(FAn) {30}
檢查風扇是否被堵住
更換風扇
TOPVERT G1/H1/P1 系列
C-32
類比輸入信號異常
(AnI.) {31}
檢查類比輸入信號是否超出範圍
過轉矩2檢出動作
(ot2) {32}
檢查電動機2負載是否過大
檢查(Pr5-40) 電動機2額定電流值是否適當
檢查過轉矩檢出位準1設定值(Pr5-21~Pr5-23)
機械負載是否異常
增加電動機2容量, 選用較大輸出容量變頻器
電動機2 過負載
(oL2) {33}
(電子熱動電驛2保護)
V/F 2曲線設定是否適當
是否長時間低速運轉
檢查電動機2是否過載
檢查(Pr5-40) 電動機1額定電流值是否適當
檢查電子熱動電驛1功能設定(Pr5-45~ Pr5-46)
增加電動機2容量
電動機切換異常
(rnot) {34}
檢查電動機接線是否正確
檢查參數設定是否正確
運轉中DC-bus低電壓
(LUr) {36}
檢查輸入電源電壓及配線是否正常
檢查電源容量及電源系統是否不足
檢查負載是否有突然的重載
是否三相電源機種只接單相電源或欠相
檢查輸入充電限流迴路是否正常
檢查運轉中輸入電源是否中斷
電源側電磁接觸器是否不良或故障
同一電源系統中是否有大容量馬達起動
DC-bus低電壓
(LU) {39}
外部中斷
(bb) {40}
當外部多功能輸入端子(MI1~MI6=15或16)有設
定此外部中斷功能動作時,變頻器停止輸出,
清除外部中斷信號後”bb”立刻消失。
操作器PU-02的 EEPROM 故障
(1 CoPy)
更換新品
操作器PU-02內沒有資料,無法存入
(2 CoPy )
請確認操作器PU-02資料存入後,再執行COPY動
作。
機種型號不同不能存入
(3 CoPy)
再確認變頻器機種型號
操作器PU-02的參數錯誤
(4 CoPy)
參數內容超出範圍,再確認PU-02參數內容的正
確性。
RUN狀態下不能做存入
(7 CoPy)
請在STOP狀況下再執行COPY動作
參數或密碼鎖定不能讀出或存入
(8 CoPy)
請先解除參數或密碼鎖定後再執行COPY動作
TOPVERT G1/H1/P1 系列
C-33
外觀尺寸:
Unit: mm (inch)
框號
W
H
D
W1
W3
H1
G1-A,H1-A,P1-A
160.0
(6.30)
250.0
(9.84)
186.0
(7.32)
140.0
(5.51)
6.0
(0.24)
230.0
(9.06)
G1-B,H1-B,P1-B
200.0
(7.87)
275.0
(10.83)
206.0
(8.11)
180.0
(7.87)
6.0
(0.24)
255.0
(10.83)
G1-C,H1-C,P1-C
260.0
(10.24)
460.0
(18.11)
245.0
(9.65)
236.0
(9.29)
9.0
(0.35)
440.0
(17.32)
Front View
Side View
Bottom View
Top View
D
W
W1
H1
H
W3
TOPVERT G1/H1/P1 系列
C-34
Unit: mm (inch)
框號
W
H
D
W1
W2
W3
H1
H2
D1
D2
Φ1
G1-D
H1-D
P1-D
386.0
(15.20)
617.0
(24.29)
298.3
(11.74)
230.0
(9.06)
376.0
(14.80)
13.0
(0.51)
591.5
(23.29)
566.5
(22.30)
290.5
(11.44)
131.5
(5.18)
13
(0.51)
G1-E
H1-E
P1-E
386.0
(15.20)
683.0
(26.89)
324.3
(12.77)
230.0
(9.06)
376.0
(14.80)
13.0
(0.51)
657.5
(25.89)
632.5
(24.90)
316.5
(12.46)
157.5
(6.20)
13
(0.51)
G1-F
H1-F
P1-F
496.0
(19.53)
810.0
(31.89)
352.1
(13.86)
260.0
(10.24)
484.0
(19.06)
13.0
(0.51)
784.0
(30.87)
764.0
(30.08)
344.0
(13.54)
180.5
(7.11)
13
(0.51)
G1-G
H1-G
P1-G
732
(28.82)
1196
(47.09)
413
(16.26)
410
(16.14)
720.0
(28.35)
13.0
(0.51)
1156
(45.51)
1133
(44.61)
404.9
(15.94)
177.30
(6.98)
13
(0.51)
G1-H
H1-H
P1-H
W1
H1
H
W 3
D
Ø1
D2
Front View
Side View
Bottom View
Top View
W
D1
W2
H2
TOPTEK ELECTRONICS CORPORATION
台灣省桃園縣中壢市自強六路1號(中壢工業區)
No.1, Tzu-Chiang 6 Road,
Chung-Li City, Taoyuan Hsien
Taiwan
Tel: +886-3-462-9199 Fax: +886-3-462-8829
http://www.toptek.biz E-mail: [email protected]
Date Code: 3603
ML-QSG1/H1/P102