Code : 180120008Ga - NDU : NOT120008Ha
Edition : 0320
NOTICE D'UTILISATION
P 1
OPERATING INSTRUCTIONS
P 15
BEDIENUNGSANLEITUNG
S 29
NOTICE D’UTILISATION
AXS3
grade 3 - 3rd grade
EN 50131-6
50W - 75W
Table des matières
1
NOTICE D’UTILISATION ............................................................................................................ 3
2
Informations générales ............................................................................................................. 4
2.1
Tableau des correspondances ................................................................................................................................ 4
2.2
Spécifications environnementales ........................................................................................................................... 4
2.3
Spécifications électriques d’entrée et de sortie ....................................................................................................... 4
2.4
Modèles ................................................................................................................................................................... 5
2.5
Caractéristiques mécaniques .................................................................................................................................. 5
2.6
Surveillance du sabotage ........................................................................................................................................ 5
2.7
Protections ............................................................................................................................................................... 5
2.8
Coupure Tension Basse .......................................................................................................................................... 5
2.9
Limitation courant batterie ....................................................................................................................................... 6
2.10 Compensation température (selon VdS2122) ......................................................................................................... 6
2.11 Capacités batteries .................................................................................................................................................. 6
3
Installation de votre équipement .............................................................................................. 7
3.1
Fixation .................................................................................................................................................................... 7
3.2
Switchs de détection ouverture capot et arrachement mural .................................................................................. 7
3.3
Batteries................................................................................................................................................................... 7
3.4
Raccordement ......................................................................................................................................................... 8
3.5
Plombage............................................................................................................................................................... 10
4
Fonctionnement de l’AXS3 ..................................................................................................... 11
4.1
Surveillances et signalisations ............................................................................................................................. 11
4.2
Communication ...................................................................................................................................................... 12
5
Maintenance ............................................................................................................................. 12
6
Protections et fusibles ............................................................................................................ 12
6.1
Versions 12V ......................................................................................................................................................... 12
6.2
Versions 24V ......................................................................................................................................................... 12
7
Procédure de dépannage ........................................................................................................ 13
ANNEXE / APPENDIX / ANHANG .................................................................................................... 42
1 NOTICE D’UTILISATION
Félicitations,
Vous venez d’acquérir une alimentation électrique sécurisée AXS3 de la marque SLAT et nous vous en remercions.
Vous trouverez dans cette notice toutes les indications à suivre pour l’installation, la mise en service et la maintenance de
cet équipement.
Pour la bonne marche de l’appareil, nous vous conseillons de les suivre très attentivement.
BONNE INSTALLATION
Consignes de sécurité
Ce matériel est destiné à être raccordé au réseau 230V et 110V de distribution publique.
Afin d’éviter tout risque de choc électrique, toute INTERVENTION doit être réalisée HORS TENSION
Un dispositif de sectionnement accessible doit être installé à cet effet à l’extérieur du matériel.
La borne de terre doit être raccordée à la terre électrique de sécurité avant tout autre connexion
Les travaux sous tension ne sont autorisés que pour les exploitations où la mise hors tension est impossible. Dans ce
cas, l’intervention doit être réalisée uniquement par du personnel habilité.
Normes, directives et protection de l’environnement et de la santé publique
Tous nos produits de la gamme AXS3 suivent les directives BT et CEM (immunité et émission). Ils sont conformes aux
normes :
•
EN 60950-1 (2006) + A11 (2009) + A1 (2010) + A12 (2011) + A2 (2013) (Classe TBTS)
•
EN 62368 -1 (2014)
•
EN 61000-6-1(2007), EN 61000-6-2 (2005), EN 61000-6-3 (2007), EN 61000-6-4 (2007) + A1 (2011)
•
EN 50130-4 (2011)
•
EN 55022 (2006) + A1 (2007) classe B
•
UL1950 pour les composants.
Ils sont également certifiés conformes aux normes métiers :
•
EN 50131-6 (2017) grade 3: Systèmes d’alarme contre l’intrusion et les hold-up, partie 6 : alimentation
•
VdS 2115 (2015) : Energieversorgungsgeräte für Gefahrenmeldeanlagen, Anforderungen
SLAT est certifiée ISO 14001 depuis 2008.
SLAT fabrique tous ses produits dans le respect des directives environnementales RoHS et DEEE.
SLAT assure le recyclage des produits en fin de vie à travers sa filière de recyclage.
Garantie
Notre garantie est de trois ans départ usine. Elle est strictement limitée au remboursement ou au remplacement (à notre
choix et sans indemnité d’aucune sorte) des pièces reconnues défectueuses par nos services, après retour dans nos
ateliers aux frais de l’acheteur. Nous ne saurions accepter de remplacements ou de réparations de matériels ailleurs que
dans nos ateliers. Dans le but de faire bénéficier à notre clientèle de nos dernières améliorations techniques, SLAT se
réserve le droit de procéder sur ses produits à toutes les modifications nécessaires. La batterie n’est pas incluse dans la
garantie.
2 Informations générales
2.1 Tableau des correspondances
50W
75W
12V
4A
6A
24V
2A
3A
Les courants indiqués sont les courants (In) à puissance nominale de sortie
2.2 Spécifications environnementales
Température de fonctionnement :
- 10°C à + 55°C en coffret @ 100 % de charge
- 10°C à + 60°C en coffret @ 75% de charge
Altitude maximum de fonctionnement :
2000m
Température de stockage :
-25 à + 85°C.
Humidité relative en fonctionnement :
20 à 95%.
Durée de vie : 200 000 h @ 25°C
(ambiance externe, en coffret, secteur nominal @ 75% de charge)
Degré de pollution :
II (selon EN 60950-1 et EN 62368-1)
Surtension de catégorie :
II (selon EN 60950-1 et EN 62368-1)
Classe d’environnement :
II (selon EN 50131-1)
2.3 Spécifications électriques d’entrée et de sortie
2.3.1
Entrée réseau
tension monophasée: 110V - 240V
fréquence: 50 - 60Hz
classe I
régimes de neutre : TT, TN, IT
disjoncteur bipolaire courbe C de calibre situé entre 2A et 10A à prévoir en amont
12V
50W
75W
Courant primaire @ 99V
1A
1.52A
Courant primaire @ 195V
0.51A
0.76A
24V
50W
75W
Courant primaire @ 99V
0.98A
1.50A
Courant primaire @ 195V
0.52A
0.78A
2.3.2 Sortie
Tension nominale
12V
24V
Courant de sortie In
4A
6A
2A
3A
Tension de floating (Un) réglée à
mi-charge et 25°C
13.6V
27.2V
Limitation courant - courant de
court-circuit
De In à In+15% pour tension de sortie > 50% de Un.
Courant de décharge batterie en
l’absence de secteur et de charge
17,5mA @ 12V
29,5mA @ 24V
Ondulation résiduelle HF cac
(20MHz-50)
< 4% de Un
Ondulation résiduelle BF efficace
< 0.2% de Un
Caractéristiques de régulation
statique et dynamique
< 5% de Un pour des variations cumulées du secteur et de la charge
(de 10 à 90%)
η @ 20% de charge
84,5 %
84,5 %
81,3 %
84,6 %
η @ 75% de charge
88,3 %
88,3 %
89,1 %
90,4 %
η @ 100% de charge
88,6 %
87,8 %
90,1 %
90,9 %
2.4 Modèles
Fixer le coffret tel que décrit ci-dessous :
Modèle 12V
4A
6A
C24
12V 4A C24
12V 6A C24
C38
12V4A C38
12V 6A C38
C85
-
12V 6A C85
Modèle 24V
2A
3A
C24
24V 2A C24
24V 3A C24
C38
24V 2A C38
24V 3A C38
C85
-
24V 3A C85
2.5 Caractéristiques mécaniques
Modèle
Longueur
Hauteur
Profondeur
Poids
IP
C24
322mm
248mm
126mm
2.5kg
30
C38
350mm
289mm
189mm
5.8kg
31
C85
408mm
408mm
224mm
9.2kg
31
* Voir plans mécaniques détaillés en annexe
2.6 Surveillance du sabotage
L’ouverture du coffret est détectée.
L’arrachement du coffret de plus de 5mm du mur est détecté.
Les 2 détections sont signalées par un même contact sec.
2.7 Protections
Contre les inversions polarités batterie avant et après mise sous tension.
Contre les surtensions au secondaire par transil (dérégulation ou erreur de branchement) et par coupure avec
redémarrage cyclique si tension de sortie >2.4V/élt+/-3%.
Contre les erreurs de branchement batterie :
•
si à la mise sous-tension, la tension batterie est >2.5V/élt+/-3%, la batterie n’est pas connectée.
•
si à la mise sous-tension, la tension batterie est < 1.17V/élt+/-3%, la batterie n’est pas connectée.
Contre les surintensités et court-circuits au secondaire.
Contre les court-circuits internes produit par fusible primaire.
Contre les surtensions au primaire (d’origine atmosphérique ou industriel).
2.8 Coupure Tension Basse
Le seuil de coupure est de 1.7V/élt+/-3%.
L’élément effectuant la coupure est positionné dans le +.
C24
*Photos non
contractuelles
C38 – C85
*Photos non
contractuelles
2.9 Limitation courant batterie
La limitation courant batterie est ajustable par le client en fonction de la capacité batterie afin de garantir une recharge
entre 0.1 et 0.3C préconisée par les constructeur. Les seuils sont de 25, 50 et 75% du courant nominal. La sélection se
fait par 2 microswitches. Par défaut, le courant de charge vaut 75% du courant nominal.
Figure 1 : position des microswitches 1 et 2 pour limitation du courant batterie
2.10 Compensation température (selon VdS2122)
Un système de compensation de la tension batterie permet de maintenir les caractéristiques de charge dans les limites
de spécifications du constructeur batteries sur toute la plage de température d’utilisation.
Une sonde placée au plus près des batteries permet la mesure de la température de celles-ci.
Les valeurs de tension en fonction de la température sont :
Temperature (°C)
-20
-10
0
10
20
25
30
40
50
60
12V
14.13
14.13
14.13
13.87
13.69
13.60
13.49
13.33
13.20
13.08
24V
28.27
28.27
28.27
27.74
27.38
27.20
26.98
26.66
26.40
26.17
2.11 Capacités batteries
Tension chargeur (V)
24
24
12
12
Calibre chargeur (A)
2
3
4
6
Courant maximum de charge batterie (A)
1,5
2,25
3
4,5
Capacité maximum (Ah) - C20 - 1.75V
26
40
50
86
Capacité minimum (Ah) - C20 – 1.75V
7
7
7
7
3 Installation de votre équipement
3.1 Fixation
Fixer le coffret doit être fixé au mur tel que décrit ci-dessous :
3.2 Switchs de détection ouverture capot et arrachement mural
En coffret C24, un switch avec boucle filaire permet la détection de l’ouverture du capot et de l’arrachement mur.
En coffret C38 et C85, deux switches avec boucle filaire permettent la détection de l’ouverture du capot et de
l’arrachement mural.
Une vis de détection d’arrachement coffret est à
installer dans le mur au niveau du trou dans le
fond du coffret indiqué en ANNEXE
Cette vis doit dépasser du mur de 55mm +/-1mm
Une vis de détection d’arrachement coffret est à
installer dans le mur au niveau du trou dans le fond
du coffret indiqué en ANNEXE
Cette vis doit dépasser du mur de 24mm +/-1mm
3.3 Batteries
Le plan d’intégration et de câblage des batteries est disponible en ANNEXE.
Les capacités des batteries à associer sont listées dans le tableau Capacité batterie §2.11
Switch
C24 : 1 switch pour
ouverture et arrachement
(la vis de contact est fournie)
En version C38 – C85 :
1 switch pour arrachement et
1 switch pour ouverture
C38
(4 vis de fixation)
C85
(4 vis de fixation)
C24
(3 vis de fixation)
3.4.1 Plan de raccordement
3.4.2 Borniers
Tous les borniers sont débrochables avec sérigraphie sur la fiche mobile.
Secteur
1x3pts / 0.5 - 2.5 mm² / 15A
Sortie utilisation
1x2pts / 0.5 – 2.5 mm² / 15A
Sortie batterie
1x2pts / 0.5 – 2.5 mm² / 15A
Reports
1x9pts / 0.5 – 1.5 mm² / 14.5A
Détail des fiches mobiles :
Secteur
Sorties
Communication
Attention, les ouvertures prévues dans le coffret doivent être utilisées. Ne pas créer d’ouvertures
supplémentaires sous peine de dysfonctionnement de l’appareil et de non reprise sous garantie.
Procédure de raccordement
1. Ouvrir le disjoncteur secteur avant tout raccordement.
2. Pour le câble secteur utiliser un câble conforme CEI 60227 ou CEI 60245.
Raccorder le secteur sur le connecteur SECTEUR en commençant impérativement par le fil
de terre sur le connecteur.
3. Raccorder les fils batteries sur le bornier mais ne pas raccorder les bornes de la batterie.
4. Après avoir effectué les raccordements électriques (secteur, utilisations et batteries), fermer le
disjoncteur secteur en amont.
5. Vérifier la tension de sortie utilisation. La LED de la carte mère devient rouge.
6. Raccorder les bornes de la batterie.
7. Vérifier que le voyant de bon fonctionnement sur la carte mère passe au vert ( vert = tout OK, rouge = défaut).
8. Fixer le câble secteur au coffret à l’aide du collier fourni en utilisant les trous suivant.
9. Raccorder le fil de terre du capot si nécessaire.
10. Fermer le capot.
Votre appareil est en état de marche lorsque les 3 LED vertes en face avant sont allumées (voyants secteur,
batterie et chargeur).
Fixation du câble entrée secteur
C38
C85
C24
Les parties qui ne doivent pas être accessibles à l’utilisateur peuvent être scellées par un plombage en coffret C38 et
C85 et par autocollant spécifique fournie en coffret C24.
L’autocollant spécifique est à placer sur
l’une des 2 vis en coffret C24
Le plomb est à placer dans ces deux
trous en coffret C38 et C85
4 Fonctionnement de l’AXS3
4.1 Surveillances et signalisations
Surveillances :
Défaut secteur :
-
si secteur absent.
Défaut chargeur :
-
si absence de tension sur Sortie 1.
-
si absence de tension sur Sortie 2.
-
si tension de sorties basse (produit en surcharge).
-
si fusible secteur HS ou absent.
-
si produit HS.
Défaut batterie :
-
si batterie absente (test toutes les 30s pendant les 20 premières minutes après la mise en service puis test
toutes les 15 minutes maximum. Si un défaut est détecté, le test repasse toutes les 30s jusqu’à 20 minutes
après la disparition du défaut).
-
si tension batterie < 1.75V/élt+/-3%.
-
si impédance interne trop élevée (test toutes les 4h maximum sur une batterie chargée). Les valeurs limites
de l’impédance sont :
2A
3A
4A
6A
12V
-
-
0.16Ω
0.16Ω
24V
0.65Ω
0.65Ω
-
-
Signalisations en face avant :
3 voyants permettent l’indication des 3 défauts.
Signalisation par LED jaune si défaut, verte sinon.
Figure 2 : Leds en situation de défaut secteur
Signalisations sur carte mère :
Un voyant sur la carte mère permet d’indiquer l’état de fonctionnement avant la fermeture du coffret (carte visu
non connectée) ou lorsqu’il n’y a pas de carte visu. La signalisation est :
o
Tout ok : vert,
o
Défauts : rouge
Défaut secteur
Défaut batterie
Défaut chargeur
Les 3 défauts (secteur, batterie, chargeur) sont reporté sur 3 contacts sec dont les positions normalement ouvert (NO) et
normalement fermé (NC) sont accessible sur le bornier « Alarms reports ».
Contacts sec: 1A @ 24Vdc, 0.3A @125Vac
5 Maintenance
Pour que votre produit vous rende un service maximal et durable, il est vivement conseillé de le maintenir dans un état de
propreté et de veiller à avoir une installation dans un endroit sec et ventilé. Nous ne serions en aucun cas responsables
des dommages liés à une mauvaise utilisation ou à un défaut d’entretien de ce matériel.
AVERTISSEMENT
Le remplacement de la batterie par une batterie de type incorrect peut engendrer un risque d’explosion.
Les batteries usagées doivent être mises au rebut conformément aux obligations de recyclage des matériaux.
6 Protections et fusibles
6.1 Versions 12V
Désignation
4A
6A
Fusible primaire
F1
5x20 T3,15A 250Vac
5x20 T3,15A 250Vac
Fusible Util 1
F8
5x20 F6.3A
5x20 F6.3A
Fusible Util 2
F7
5x20 F6.3A
5x20 F6.3A
Fusible batterie
FBat
7A, 16V
Réarmable automatiquement
7A, 16V
Réarmable automatiquement
6.2 Versions 24V
Désignation
2A
3A
Fusible primaire
F1
5x20 T3,15A 250Vac
5x20 T3,15A 250Vac
Fusible Util 1
F8
5x20 T3.15A
5x20 T3.15A
Fusible Util 2
F7
5x20 T3.15A
5x20 T3.15A
Fusible batterie
FBat
4A, 30V
Réarmable automatiquement
4A, 30V
Réarmable automatiquement
7 Procédure de dépannage
Si l’AXS3 ne délivre pas de tension
•
Vérifier la présence secteur sur le bornier secteur
•
Vérifier les fusibles
•
Vérifier la valeur de la tension sur les bornes util 1 et/ou util 2
•
La tension sur les câbles batterie doit être identique à celle de l’utilisation
•
Vérifier que chaque batterie de 12Vcc présente une tension égale voir supérieure à 11,5Vcc
•
Répéter la mesure après avoir débranché l’utilisation et la batterie.
•
Recontrôler la signalisation des voyants (cf chapitre 5)
•
Si toutes les étapes sont validées vérifier la compatibilité de votre utilisation
Si la batterie ne prend pas le relais après un défaut secteur
•
Contrôler la tension aux bornes de la batterie
•
Contrôler le fusible batterie
•
Contrôler la tension sur les bornes util 1 et/ou util 2
Si les voyants ne sont pas allumés
•
Contrôler la présence secteur sur le bornier secteur
•
Contrôler le raccordement batterie (et le fusible batterie)
•
Contrôler la bonne connection de la nappe
•
Contrôler la tension sur les bornes util 1 et/ou util 2
Pour une assistance technique complémentaire, contactez la hot line SLAT
+ 33 (0) 4 78 66 63 70
Pour vos demandes de retour, connectez vous sur notre site internet :
http://www.slat.fr/support/rma/demandez-votre-numero-rma/
ou contactez le SAV SLAT afin d ‘obtenir un numéro RMA (retour de marchandise autorisé).
Sans numéro RMA votre retour ne sera pas accepté.
grade 3 - 3rd grade
EN 50131-6
50W - 75W
Table of contents
8
OPERATING INSTRUCTIONS .................................................................................................. 17
9
General information ................................................................................................................. 18
9.1
Correspondance table ........................................................................................................................................... 18
9.2
Environmental specifications ................................................................................................................................. 18
9.3
Electrical Characteristics ....................................................................................................................................... 18
9.4
Models ................................................................................................................................................................... 19
9.5
Mechanical characteristics .................................................................................................................................... 19
9.6
Tamper monitoring: ............................................................................................................................................... 19
9.7
Protections ............................................................................................................................................................. 19
9.8
Battery low voltage disconnection ......................................................................................................................... 19
9.9
Battery current limitation ........................................................................................................................................ 20
9.10 Temperature compensation (according VdS2122) ............................................................................................... 20
9.11 Battery capacity ..................................................................................................................................................... 20
10
Installation of your equipment ................................................................................................ 21
10.1 Mounting ................................................................................................................................................................ 21
10.2 Wall remover detection switches ........................................................................................................................... 21
10.3 Battery ................................................................................................................................................................... 21
11
Cabling ...................................................................................................................................... 22
11.1 Connection diagram .............................................................................................................................................. 22
11.2 Connectors ............................................................................................................................................................ 22
11.3 Lead Sealing: ......................................................................................................................................................... 24
12
AXS3 operation ........................................................................................................................ 25
12.1 Monitorings and warnings...................................................................................................................................... 25
12.2 Communication ...................................................................................................................................................... 26
13
Maintenance ............................................................................................................................. 26
14
Fuses ........................................................................................................................................ 26
14.1 12V versions .......................................................................................................................................................... 26
14.2 24V versions .......................................................................................................................................................... 26
15
Troubleshooting procedure .................................................................................................... 27
ANNEXE / APPENDIX / ANHANG .................................................................................................... 42
8 OPERATING INSTRUCTIONS
Congratulations,
You have just acquired an AXS3 emergency power supply by SLAT, and we thank you for your choice.
This manual includes instructions for the installation, commissioning and maintenance of this equipment.
In order for the equipment to work properly, we recommend that these instructions be followed very carefully.
Safety precautions
This equipment is designed to be connected to the 230V or 110V public distribution network.
To avoid any risk of electric shock, all INTERVENTIONS must be carried out with the equipment SWITCHED OFF
One easily accessible disconnect must be installed for this purpose outside the material.
The protective earth terminal must be connected to the safety electrical ground before another connection is made
Interventions with the equipment switched on are authorized only when it is impossible to switch the equipment off.
The operation must only be performed by qualified personnel.
Standards, directives and protection of the environment and public health
All products of the AXS3 range are compliant with LV and EMC directives (immunity and emission). They are compliant
with standards:
•
EN 60950-1 (2006) + A11 (2009) + A1 (2010) + A12 (2011) + A2 (2013) (TBTS class)
•
EN 62368-1 (2014)
•
EN 61000-6-1(2007), EN 61000-6-2 (2005), EN 61000-6-3 (2007), EN 61000-6-4 (2007) + A1 (2011)
•
EN 50130-4 (2011)
•
EN 55022 (2006)+ A1 (2007) class B
•
UL1950 for components.
They are also certified compliant with the following trade standards:
•
EN 50131-6 (2017) 3rd grade: Alarm systems – Intrusion systems. Part 6: Power supplies
•
VdS 2115 (2015) : Energieversorgungsgeräte für Gefahrenmeldeanlagen, Anforderungen
SLAT is ISO 14001 certified since 2008.
SLAT manufactures all its products in accordance with RoHS and WEEE environmental directives.
SLAT recycles its products at the end of their service life through its recycling programme.
Warranty
Our warranty is three years from the date of delivery (ex-works). It is strictly limited to reimbursement or replacement (at
our discretion and without compensation of any sort) of parts recognised as faulty by our services, following return of the
product to our premises at the buyer's expense. The replacement or repair of equipment is possible only on our premises.
In order to allow our customers to benefit from the latest technical improvements, SLAT reserves the right to make all
necessary modifications to its products. The battery is not included in the warranty.
9 General information
9.1 Correspondance table
The currents (In) shown are at rated output power.
9.2 Environmental specifications
Operating temperature:
- 10°C à + 55°C housed @ 100 % load
- 10°C à + 60°C housed @ 75% load
Operating maximum altitude:
2000m
Storage temperature:
-25 à + 85°C.
Operating relative humidity:
from 20 to 95%.
Life time: 200 000 h @ 25°C
(ambient T, external to the housing, mains nominal @ 75% load housed)
Pollution degree:
II (according EN 60950-1 and EN 62368-1)
Overvoltage category:
II (according EN 60950-1 and EN 62368-1)
Environmental class:
II (according EN 50131-1)
9.3 Electrical Characteristics
9.3.1
Mains input
Single AC voltage: 110V - 240V
Frequency: 50 - 60Hz.
Class I.
Groundings: TT, TN, IT.
Double pole breaker C curve rated current between 2A and 10A to provide upstream.
12V
50W
75W
Primary current @ 98V
1A
1.52A
Primary current @ 195V
0.51A
0.76A
24V
50W
75W
Primary current @ 98V
0.98A
1.50A
Primary current @ 195V
0.52A
0.78A
9.3.2
Output
Nominal voltage
12V
24V
Output current In
4A
6A
2A
3A
Floating voltage (Un) at half load
and 25°C
13.6V
27.2V
Current limitation – short circuit
current
From In to In+15% for an output voltage > 50% Un.
Battery discharge current with no
mains and no load
17,5mA @ 12V
29,5mA @ 24V
HF p-t-p ripple (20MHz-50)
< 4% Un
BF rms ripple
< 0.2% Un
Static and dynamic regulation
characteristics
< 5% Un for total added mains and load variations (from 10 to 90%)
50W
75W
12V
4A
6A
24V
2A
3A
η @ 20% load
84,5 %
84,5 %
81,3 %
84,6 %
η @ 75% load
88,3 %
88,3 %
89,1 %
90,4 %
η @ 100% load
88,6 %
87,8 %
90,1 %
90,9 %
9.4 Models
Modèle 12V
4A
6A
C24
12V 4A C24
12V 6A C24
C38
12V4A C38
12V 6A C38
C85
-
12V 6A C85
Modèle 24V
2A
3A
C24
24V 2A C24
24V 3A C24
C38
24V 2A C38
24V 3A C38
C85
-
24V 3A C85
9.5 Mechanical characteristics
Modèle
Longueur
Hauteur
Profondeur
Poids
IP
C24
322mm
248mm
126mm
2.5kg
30
C38
350mm
289mm
189mm
5.8kg
31
C85
408mm
408mm
224mm
9.2kg
31
* See mechanical drawing in annex
9.6 Tamper monitoring:
Any housing tamper must be detected.
Any snatch pulling the housing more than 5mm away from the wall must be detected
Both detections are reported via a dry contact.
9.7 Protections
Against battery polarity inversion before and after switch on.
Against secondary overvoltages thanks to transil diode (regulation troubles or connections mistakes) and auto-recovery
when output voltage > 2.4V/elt
Against battery wiring error
o
If battery voltage > 2.5V/elt +/-3%, the battery is not connected
o
If battery voltage < 1.17V/elt +/-3%, the battery is not connected
Against secondary overcurrent and short-circuits.
Against internal short-circuits thanks to primary fuse.
Against primary overvoltages (due to atmospheric or industrial causes).
9.8 Battery low voltage disconnection
Battery get disconnect when is voltage reach the threshold of 1.7V/cells +/-3%.
The disconnection is made by a static switch located on positive battery output.
C24
*Photos not
contractual
C38 – C85
*Photos not
contractual
9.9 Battery current limitation
The battery current limitation is user adjustable according to the battery capacity, in order to ensure a battery reloading
between 0.1C and 0.3C as advised by the manufacturer. The thresholds are 25%, 50% and 75% of the nominal current.
Selection is made by 2 microswitches. The charging current default value is set at 75% of the nominal current.
Figure 3: configurating battery current limitation using microswitches 1 & 2
9.10 Temperature compensation (according VdS2122)
Thanks to a battery voltage compensation system, the battery charge characteristics can be maintained within the
specifications limits provided by the battery manufacturer under the whole range of temperature.
The temperature is measured by a sensor placed as close as possible to the battery.
Voltage values versus temperature values are:
Temperature (°C)
-20
-10
0
10
20
25
30
40
50
60
12V
14.13
14.13
14.13
13.87
13.69
13.60
13.49
13.33
13.20
13.08
24V
28.27
28.27
28.27
27.74
27.38
27.20
26.98
26.66
26.40
26.17
9.11 Battery capacity
Charger voltage (V)
24
24
12
12
Charger current (A)
2
3
4
6
Maximum battery charging current (A)
1,5
2,25
3
4,5
Specified capacity (Ah) - C20 - 1.75V
26
40
50
86
Minimum capacity (Ah) - C20 –1.75V
7
7
7
7
10 Installation of your equipment
10.1 Mounting
The housing has to be mount on a wall as represented below ::
10.2 Wall remover detection switches
A screw on the wall have to be install in the
housing hole indicate in ANNEX to detect a tear
down.
This screw must extend out of the wall by 55mm
+/-1mm
A screw on the wall have to be install in the
housing hole indicate in ANNEX to detect a tear
down.
This screw must extend out of the wall by 24mm +/-
1mm
10.3 Battery
Batteries integration drawing and wiring schematics are available in APPENDIX.
*Capacities of batteries to be associated are listed in Table Capacity Battery §9.11.
C38
(4 screws)
C85
(4 screws)
C24
(3 screws)
C24 switch – C38 – C85 switch
C24: 1 switch for both
housing tamper and
housing snatch
C38 – C 85: 1 switch for
housing tamper and a
switch for housing snatch
11.1 Connection diagram
11.2 Connectors
Every connectors are pluggable. Marking is located on the moving plug.
Mains
1x3pts / 0.5 - 2.5 mm² / 15A
User output
1x2pts / 0.5 – 2.5 mm² / 15A
Battery output
1x2pts / 0.5 – 2.5 mm² / 15A
Alarm reports
1x9pts / 0.5 – 1.5 mm² / 14.5A
Moving plugs :
Mains
Output
Communication
Important: the openings provided in the cabinet must be used. Do not create additional openings as doing so
may cause the device to malfunction and voids the warranty.
1. Open the mains breaker before any connections.
2. Use a AC power mains cabble conform to CEI 60227 or CEI 60245.
Connect first the safety electrical ground to the MAINS connector ground terminal and then
the line and neutral according the picture on the left side.
3. Connect the battery wires to the battery output terminal, but do not connect wires to the
battery.
4. After the electrical connections are made (mains, loads and batteries), close the mains circuit
breaker.
5. Check the load output voltage. The motherboard LED turns red.
6. Connect the battery
7. Check that the motherboard LED turns green (green = everything is ok, red = fault).
8. The mains cable have to be tight to the housing with the tie wrap provided using the hole indicate below
9. Connect the ground wire to the cover if equiped.
10. Close the protective cover.
Your equipment is operational when the 3 LEDs on the front panel are green (mains, battery and charger).
Fixing of AC mains power cable
C38
C85
C24
11.3 Lead Sealing:
Parts whose access is restricted must be-sealed by lead sealing in C38 and C85 housing and by a seal sticker in C24
housing
The security seal sticker has to be stick
on one of the 2 screw hole in C24
The lead sealing has to be place in
these holes in C38 or C85 housing
12 AXS3 operation
12.1 Monitorings and warnings
Monitorings
Mains fault (main supply):
1. If there is no mains.
Charger fault:
-
If there is no voltage on user output 1.
-
If there is no voltage on user output 2.
-
If output voltages are low (overloaded product).
-
If mains fuse is blown / there is no mains fuse.
-
If the product is out of order.
Battery fault (auxiliary supply):
-
If there is no battery (a test will performed every 30s during the first 20min after switch on and every 15min
(maximum time interval) then after. In case a fault is detected, another test will be performed every 30s until
20min have passed from fault end.
-
If battery voltage < 1.75V/elt+/-3%.
-
If internal impedance is too high (a tests will be performed every 4h (maximum time interval) on a loaded
battery). Limit values are:
2A
3A
4A
6A
12V
-
-
0.16Ω
0.16Ω
24V
0.65Ω
0.65Ω
-
-
Front panel LED indicator:
3 LED indicate these 3 faults.
Yellow led warning if fault, green if not.
Figure 1: Leds in case of mains fault
Motherboard LED indicator:
A led let the user check the product state before the housing is closed (leds board unplugged) or when there is no leds
board. Leds warnings are as followed:
o
Everything OK: green
o
Any Faults: red.
AC power mains fault
Battery fault
Charger fault
The 3 faults (mains, battery, output) are reported on 3 dry contacts NC and NO (use positive security).
Dry contact: 1A @ 24Vdc, 0.3A @ 125 Vac
13 Maintenance
In order to ensure maximal and durable service, we strongly recommend that your product be maintained clean and
ensure that it is installed in a dry and ventilated location. We shall in no case be liable for damages associated with
improper use or incorrect maintenance of the equipment.
WARNING
Replacing the battery with a battery of incorrect type may result in an explosion hazard.
Used batteries must be disposed of in compliance with recycling requirements.
14 Fuses
14.1 12V versions
Ref.
4A or 6A
Primary fuse
F1
5x20 T3,15A 250Vac
User 1 fuse
F8
5x20 F6.3A
User 2 fuse
F7
5x20 F6.3A
Battery fuse
FBat
7A, 16V
Automatically resettable
14.2 24V versions
Ref.
2A or 3A
Primary fuse
F1
5x20 T3,15A 250Vac
User 1 fuse
F8
5x20 T3.15A
User 2 fuse
F7
5x20 T3.15A
Battery fuse
FBat
4A, 30V
Automatically resettable
15 Troubleshooting procedure
If the AXS3 does not deliver voltage
•
Check mains presence on the mains terminal strip
•
Check the fuses
•
Check the voltage value on terminals load1 and/or load2
•
The voltage on the battery cables must be identical to that of the load
•
Check that each 12 Vdc battery has a voltage greater than or equal to 11.5 Vdc
•
Repeat the measurement after having disconnected the load and the battery
•
Recheck the signalling of the indicator lights (see chapter 5)
•
If all the steps are validated, check the compatibility of your load
If the battery does not take over after a mains fault
•
Check the voltage on the battery terminals
•
Check the battery fuse
•
Check the voltage on terminals load1 and/or load2
If the indicator lights are not illuminated
•
Check mains presence on the mains terminal strip
•
Check the battery connection (and the battery fuse)
•
Check that the wire ribbon is properly connected
•
Check the voltage on terminals load1 and/or load2
For additional technical assistance, contact the SLAT hotline
+ 33 (0) 4 78 66 63 70
For return requests, visit our website:
http://en.slat.fr/support-2/rma-customer-service/request-an-rma-number/
or contact SLAT After-Sales Service to obtain an RMA (Return Material Authorisation) number.
Returns are not accepted without an RMA number.
grade 3 - 3rd grade
EN 50131-6
50W - 75W
BEDIENUNGSANLEITUNG ...................................................................................................... 31
17
Allgemeine Informationen ....................................................................................................... 32
17.1 Übereinstimmungstabelle ...................................................................................................................................... 32
17.2 Umweltspezifikationen ........................................................................................................................................... 32
17.3 Elektrische Spezifikationen für Ein- und Ausgänge .............................................................................................. 32
17.4 Modelle .................................................................................................................................................................. 33
17.5 Mechanische Eigenschaften.................................................................................................................................. 33
17.6 Sabotageüberwachung: ......................................................................................................................................... 33
17.7 Schutz .................................................................................................................................................................... 33
Abschalten bei Niederspannung ...................................................................................................................................... 33
17.8 Batteriestrombegrenzung ...................................................................................................................................... 34
17.9 Temperaturausgleich ............................................................................................................................................. 34
17.10 Batteriekapazitäten ................................................................................................................................................ 34
18
Installation Ihres Geräts .......................................................................................................... 35
18.1 Montage ................................................................................................................................................................. 35
18.2 Erkennungsschalter Öffnen der Abdeckung und Abreißen von der Wand ........................................................... 35
18.3 Batterien ................................................................................................................................................................ 35
19
Anschluss ................................................................................................................................. 36
19.1 Anschlussplan ....................................................................................................................................................... 36
19.2 Anschluss und Größe der Klemmleisten ............................................................................................................... 36
19.3 Plombierung .......................................................................................................................................................... 38
20
Funktionsweise des AXS3 ...................................................................................................... 39
20.1 Überwachung und Meldungen .............................................................................................................................. 39
20.2 Verbindung ............................................................................................................................................................ 40
21
Wartung .................................................................................................................................... 40
22
Schutz und Sicherungen ......................................................................................................... 40
22.1 12V-Versionen ....................................................................................................................................................... 40
22.2 24V-Versionen ....................................................................................................................................................... 40
23
Verfahren zur Fehlerbehebung ............................................................................................... 41
ANNEXE / APPENDIX / ANHANG .................................................................................................... 42
Sie haben sich für die gesicherte Stromversorgung AXS3 der Marke SLAT entschieden und dafür danken wir Ihnen.
Sie finden in dieser Bedienungsanleitung alle notwendigen Angaben zu Installation, Inbetriebnahme und Wartung dieses
Geräts.
Für eine reibungslose Funktionsweise des Geräts empfehlen wir Ihnen, diesen Angaben genau zu folgen.
ODNUNGSGEMÄSSE INSTALLATION
Sicherheitshinweise
Dieses Gerät ist zum Anschluss an das öffentliche 230V – 110V -Stromversorgungsnetz vorgesehen.
Um die Gefahr eines Stromschlags auszuschließen, muss jeder EINGRIFF SPANNUNGSFREI erfolgen.
Zu diesem Zweck muss eine zugängliche Trenneinrichtung außen am Gerät angebracht sein.
Arbeiten unter Spannung sind nur in Betrieben zulässig, in denen das Trennen nicht möglich ist. Der Eingriff hat
ausschließlich durch berechtigte Personen zu erfolgen.
Normen, Richtlinien und Umwelt- und Gesundheitsschutz
Alle Produkte aus der Baureihe AXS3 halten die NS-Richtlinien und EMV-Normen (bzgl. Störfestigkeit und Emission) ein.
Sie entsprechen den Normen:
•
EN 60950-1 (2006) + A11 (2009) + A1 (2010) + A12 (2011) + A2 (2013) (Klasse TBTS)
•
EN 62368-1 (2014)
•
EN 61000-6-1(2007), EN 61000-6-2 (2005), EN 61000-6-3 (2007), EN 61000-6-4 (2007) + A1 (2011)
•
EN 50130-4 (2011)
•
EN 55022 (2006) + A1 (2007) Klasse B
•
UL1950 bei den Komponenten
Sie sind ebenfalls nach den Normen für den jeweiligen Einsatzbereich zertifiziert:
•
EN 50131-6 (2017) 3rd grade: Einbruch- und Diebstahlsicherungssysteme, Teil 6: Stromversorgung
•
VdS 2115 (2015) : Energieversorgungsgeräte für Gefahrenmeldeanlagen, Anforderungen
SLAT ist seit 2008 ISO 14001 zertifiziert.
SLAT stellt alle seine Produkte unter Einhaltung der Umweltrichtlinien RoHS und DEEE her.
SLAT sorgt über seinen Rückführungsservice für die Wiederverwertung der Produkte am Ende ihres Lebenszyklus.
Garantie
Unsere Garantie beträgt drei Jahre ab Werk. Sie beschränkt sich ausschließlich auf die Erstattung oder den Austausch
(unserer Wahl und ohne jegliche Entschädigung) der von unseren Abteilungen als schadhaft anerkannten Teile nach
Rücksendung in unsere Werkstätten auf Kosten des Käufers. Wir akzeptieren weder den Austausch noch die Reparatur
von Geräten außerhalb unserer Werkstätten. Mit dem Ziel, seinen Kunden die neuesten technischen Verbesserungen zu
bieten, behält sich SLAT das Recht vor, sämtliche erforderliche Änderungen an seinen Produkten vorzunehmen. Die
Batterie ist nicht Teil der Garantieleistung.
17 Allgemeine Informationen
17.1 Übereinstimmungstabelle
50W
75W
12V
4A
6A
24V
2A
3A
Bei den genannten Stromstärken handelt es sich um die Ausgangsnennleistung (In)
17.2 Umweltspezifikationen
Betriebstemperatur:
- 10°C bis + 55°C im Gehäuse bei 100 % Ladung
- 10°C bis + 60°C im Gehäuse bei 75% Ladung
Maximale Betriebshöhe:
2000m
Lagertemperatur:
-25 bis + 85°C.
Relative Luftfeuchtigkeit bei Betrieb: 20 bis 95%.
Lebensdauer: 200.000 h bei 25°C
(Umgebungstemperatur, im Gehäuse, Nennstromanschluss bei 75%
Ladung)
Verschmutzungsgrad:
II (nach EN 60950-1 und EN 62368-1)
Überspannungsgrad:
II (nach EN 60950-1 und EN 62368-1)
Umweltklasse:
II (nach EN 50131-1)
17.3 Elektrische Spezifikationen für Ein- und Ausgänge
20.3.1 Eingang Netz
-
Einphasige Spannung: 110V - 240V
-
Frequenz: 50 - 60Hz.
-
Klasse I.
-
Sternschaltungen: TT, TN, IT.
-
Vorgeschalteten bipolaren 2A bis 10A Nennwert Trennschalter zu vorsehen
12V
50W
75W
Primärstrom bei 99V
1A
1.52A
Primärstrom bei 195V
0,51A
0,76A
24V
50W
75W
Primärstrom bei 99V
0,98A
1,50A
Primärstrom bei 195V
0,52A
0,78A
20.3.2 Ausgang
Nennspannung
12V
24V
Ausgangsstrom In
4A
6A
2A
3A
Schwebeladungsspannung (Un), auf
halbe Ladung und 25°C eingestellt
13,6V
27,2V
Strombegrenzung -
Kurzschlussstrom
Von In bis In +15% für Ausgangsspannung > 50% von Un.
Batterieentladungsstrom bei
fehlender Netz- und Ladungspräsenz
17,5mA bei 12V
29,5mA bei 24V
Restwelligkeit HF cac (20MHz-50)
< 4% von Un
Restwelligkeit BF wirksam
< 0,2% von Un
Merkmale der statischen und
dynamischen Steuerung
< 5% von Un für kumulierte Schwankungen von Netz und Ladung (10 bis
90%)
η bei 20% Ladung
84,5 %
84,5 %
81,3 %
84,6 %
η bei 75% Ladung
88,3 %
88,3 %
89,1 %
90,4 %
η bei 100% Ladung
88,6 %
87,8 %
90,1 %
90,9 %
17.4 Modelle
Modell
4A
6A
C24
12V4A C24
12V6A C24
C38
12V4A C38
12V6A C38
C85
-
12V6A C85
Modell
2A
3A
C24
24V2A C24
24V3A C24
C38
24V2A C38
24V3A C38
C85
-
24V3A C85
*unverbindliche Abbildungen
17.5 Mechanische Eigenschaften
Modell
Länge
Höhe
Tiefe
Gewicht
IP
C24
322mm
248mm
126mm
2,5kg
30
C38
350mm
289mm
189mm
5,8kg
31
C85
408mm
408mm
224mm
9,2kg
31
* See mechanical drawing in annex
17.6 Sabotageüberwachung:
Das Öffnen des Gehäuses wird erkannt.
Das Abreißen des Gehäuses in über 5mm Entfernung von der Wand wird erkannt.
Die beiden Erkennungssignale wird über ein und den gleichen trockenen Kontakt übermittelt.
17.7 Schutz
Vor Polaritätsinversion der Batterie vor und nach dem Spannung zuschalten.
Vor sekundärseitiger Überspannung entstehen durch Suppressordiode (Verstellen oder fehlerhafte Anschlüsse) und
durch Abschalten mit zyklischem Neustart, falls Ausgangsspannung >2,4V/Zelle+/-3%.
Vor Batterieanschlussfehlern:
- falls die Batteriespannung beim Spannung zuschalten >2,5V/Zelle+/-3% beträgt, ist die Batterie nicht angeschlossen.
- falls die Batteriespannung beim Spannung zuschalten <1,17V/Zelle+/-3% beträgt, ist die Batterie nicht angeschlossen.
Vor Überstrom und sekundärseitigen Kurzschlüssen.
Vor internen durch die Primärsicherung verursachten Kurzschlüssen.
Gegen primärseitige Überspannungen (aus atmosphärischen oder industriellen Gründen).
Abschalten bei Niederspannung
Die Abschaltgrenze liegt bei 1,7V/Zelle+/-3%.
Das Bauteil, das die Abschaltung auslöst, liegt im +.
C24
C38 - C85
Die Batteriestrombegrenzung kann durch den Kunden in Abhängigkeit entsprechend der Batteriekapazität eingestellt
werden, um die vom Hersteller empfohlene Aufladung von 0,1 bis 0,3C zu gewährleisten. Die Schwellenwerte betragen
25, 50 und 75% des Nennstroms. Die Auswahl erfolgt durch 2 Mikroschalter. Der voreingestellte Ladestrom beträgt 75%
des Nennstroms.
Abbildung 3: Position der Mikroschalter 1 und 2 zur Batteriestrombegrenzung
17.9 Temperaturausgleich
Ein System zum Ausgleich der Batteriespannung ermöglicht die Beibehaltung der Ladungseigenschaften im Rahmen der
Spezifikationen des Batterieherstellers über die gesamte Spannbreite der Nutzungstemperatur.
Durch eine nahe an den Batterien angebrachte Sonde kann die Batterietemperatur gemessen werden.
Die Spannungswerte in Abhängigkeit von der Temperatur betragen:
T (°C)
-20
-10
0
10
20
25
30
40
50
60
12V
14,13
14,13
14,13
13,87
13,69
13,60
13,49
13,33
13,20
13,08
24V
28,27
28,27
28,27
27,74
27,38
27,20
26,98
26,66
26,40
26,17
17.10 Batteriekapazitäten
Spannung Ladegerät (V)
24
24
12
12
Kaliber Ladegerät (A)
2
3
4
6
Maximaler Ladestrom Batterie (A)
1,5
2,25
3
4,5
Maximale Kapazität (Ah) - C20 - 1,75V
26
40
50
86
Minimale Kapazität (Ah) - C20 - 1,75V
7
7
7
7
18 Installation Ihres Geräts
18.1 Montage
Wie unten dargestellt das Gehäuse soll an einer Wand montiert werden:
18.2 Erkennungsschalter Öffnen der Abdeckung und Abreißen von der Wand
Im C24-Gehäuse ermöglicht ein Schalter mit Kabelschleife die Erkennung des Öffnens der Abdeckung und des
Abreißens von der Wand
Im C38- und C85-Gehäuse ermöglichen zwei Schalter mit Kabelschleife die Erkennung des Öffnens der Abdeckung und
des Abreißens von der Wand.
Eine abreißen Erkennungsschraube ist dem im
Anhang
gezeichneten
Gehäusebohrung
gegenüber an der Wand zu befestigen.
Diese Schraube muß über die Wand 55mm +/-
1mm hinausragen.
Eine abreißen Erkennungsschraube ist dem im
Anhang gezeichneten Gehäusebohrung gegenüber
an der Wand zu befestigen.
Diese Schraube muß über die Wand 24mm +/-
1mm hinausragen.
18.3 Batterien
Der Einbau- und Verkabelungsplan der Batterien befindet sich in dem finden Sie in ANHANG.
*Kapazität Batterien Gesellschafter sind in der Tabelle aufgeführt Akku-Kapazität §17.10.
C38
(4 Schrauben)
C85
(4 Schrauben)
C24
(3 Schrauben)
Schalter
C24: 1 Schalter zur Erkennung
des Ausreißens und Öffnens (die
Kontaktschraube ist mitgeliefert)
Bei den C38 – C85-Modellen:
1 Schalter zur Erkennung des
Ausreißens 1 Schalter zur
Erkennung des Öffnens
19.2 Anschluss und Größe der Klemmleisten
Alle Klemmleisten sind abnehmbar und mit einem Siebdruck auf dem mobilen Steckverbinder versehen.
Stromnetz
1x3pts / 0,5 - 2,5 mm² / 15A
Ausgang Verbraucher
1x2pts / 0,5 – 2,5 mm² / 15A
Ausgang Batterie
1x2pts / 0,5 – 2,5 mm² / 15A
Berichte
1x2pts / 0,5 – 1,5 mm² / 14,5A
Einzelheiten zu den mobilen Steckverbindern:
Stromnetz
Ausgänge
Verbindung
Achtung, es müssen die dafür vorgesehenen Öffnungen im Gehäuse verwendet werden. Keine zusätzlichen
Öffnungen schaffen, ansonsten Gefahr von Betriebsstörungen des Gerätes und keine Rücknahme während der
Garantielaufzeit.
1. Vor jedem Anschließen Netzschalter öffnen.
2. Verwenden Sie ein Netzanschlusskabel CEI 60227 oder 60245 CEI entsprechen.
Schließen Sie zunächst die Masse an und dann Schließen Sie den Netz am Netz -
Anschluss an, Siehe Bild auf der rechten Seite.
1. Batteriekabel an der Klemmleiste anschließen, jedoch nicht die Batterieklemmen.
2. Nach Durchführung der elektrischen Anschlüsse (Stromnetz, Verbraucher und Batterie) den
vorgeschalteten Netzschalter schließen.
3. Ausgangsspannung auf Verwendungsseite prüfen. Die LED-Anzeige der Grundplatine wird
rot.
4. Batterieklemmen anschließen
5. Betriebsleuchte auf der Grundplatine prüfen:
•
alles ok: grün,
•
Fehler: rot.
6. Der Netzkabel muß an dem Gehäuse mit dem mitgelieferten Verbinder durch die unten bezeichneten Öffnungen
befestigt werden.
7. Erdkabel und Flachbandkabel (falls vorhanden) anschließen.
8. Abdeckung schließen.
Ihr Gerät ist betriebsbereit, sobald die 3 grünen LED-Anzeigen (Netz-, Batterie- und Ladegerätanzeigen) leuchten.
Befestigung des Netzkabels
C38
C85
C24
Die Abdeckung der Modelle C38 und C85 werden mit einer Plombe (siehe Abbildung rechts) und die Abdeckung des
Modells C24 mit einem Sticker (siehe Abbildung links) versiegelt. Die Sticker sind im Lieferumfang enthalten.
Der Sticker muss über einen der beiden
Verschraubungen des Modells C24 platziert
werden
Die Plombe muss durch die zwei Löcher
des Modells C38 und C85 geführt und
anschließend versiegelt werden
20 Funktionsweise des AXS3
20.1 Überwachung und Meldungen
Überwachung:
Fehler Stromnetz:
-
falls kein Netz vorhanden.
Fehler Ladegerät:
-
falls keine Spannung an Ausgang 1.
-
falls keine Spannung an Ausgang 2.
-
falls Ausgangsspannung niedrig (Gerät überlastet).
-
falls Netzsicherung außer Betrieb oder nicht vorhanden.
-
falls Gerät außer Betrieb.
Fehler Batterie:
-
falls keine Batterie vorhanden (Test alle 30s während der ersten 20 Minuten nach Inbetriebnahme, danach
Test mindestens alle 15 Minuten. Wenn ein Fehler entdeckt wurde, wird der Test alle 30s bis zu 20 Minuten
nach Behebung des Fehlers durchgeführt).
-
falls Batteriespannung < 1,75V/Zelle+/-3%.
-
falls innere Impedanz zu hoch (Test mindestens alle 4h an geladener Batterie). Die Grenzwerte der
Impedanz lauten:
2A
3A
4A
6A
12V
-
-
0,16Ω
0,16Ω
24V
0,65Ω
0,65Ω
-
-
Frontseite LED-Anzeige
3 Kontrollleuchten zeigen 3 Fehler an.
Abwesenheitsmeldung durch gelbe LED-Leuchte, ansonsten grüne Anzeige.
Abbildung 1: LED-Anzeigen bei fehlendem Netz
Auf Grundplatine
Eine Kontrollleuchte auf der Grundplatine zeigt den Betriebszustand vor dem Schließen des Gehäuses an
(Anzeigeplatine nicht angeschlossen) oder falls keine Anzeigeplatine vorhanden ist. Die Meldung lautet:
•
Alles ok: grün,
•
Fehler: rot
Fehlermeldung Stromnetz
Fehlermeldung Batterie
Fehlermeldung Ladegerät:
Die 3 Fehler (Netz, Batterie, Verbraucher) sind in 3 Echtzeituhr-Trockenkontakte (eigensicher) zusammengefasst.
Trockenkontakt: 1A bei 24Vdc, 0,3A bei125Vac
21 Wartung
Damit Ihnen Ihr Produkt maximal und dauerhaft gute Dienste leistet, empfiehlt es sich dringend, dieses in sauberen
Zustand zu halten und die Installation an einem trockenen und gut belüfteten Ort vorzunehmen. Wir übernehmen in
keinem Fall die Haftung für Schäden durch eine unsachgemäße Verwendung oder eine fehlerhafte Instandhaltung dieses
Geräts.
WARNUNG
Das Austauschen der Batterie durch einen falschen Batterietyp kann zu Explosionsgefahr führen.
Verbrauchte Batterien müssen gemäß den Materialrückführungsverpflichtungen entsorgt werden.
22 Schutz und Sicherungen
22.1 12V-Versionen
Bezeichnung
4A
6A
Primärsicherung
F1
5x20 T3,15A 250Vac
5x20 T3,15A 250Vac
Sicherung Verbraucher 1
F8
5x20 F6,3A
5x20 F6,3A
Sicherung Verbraucher 2
F7
5x20 F6,3A
5x20 F6,3A
Sicherung Batterie
FBat
7A, 16V
Automatisch rückstellbar
7A, 16V
Automatisch rückstellbar
22.2 24V-Versionen
Bezeichnung
2A
3A
Primärsicherung
F1
5x20 T3,15A 250Vac
5x20 T3,15A 250Vac
Sicherung Verbraucher 1
F8
5x20 T3,15A 250Vac
5x20 T3,15A 250Vac
Sicherung Verbraucher 2
F7
5x20 T3,15A 250Vac
5x20 T3,15A 250Vac
Sicherung Batterie
FBat
4A, 30V
Automatisch rückstellbar
4A, 30V
Automatisch rückstellbar
23 Verfahren zur Fehlerbehebung
Falls AXS3 keine Spannung liefert
•
Netzpräsenz auf der Netzklemmleiste prüfen
•
Sicherungen prüfen
•
Spannungswert an den Klemmen Verbr1 und/oder Verbr2 prüfen
•
Die Spannung in den Batteriekabeln muss der Verbraucherspannung entsprechen.
•
Prüfen, ob jede 12Vcc-Batterie eine Spannung von 11,5Vcc oder mehr aufweist
•
Wiederholen Sie die Messung, nachdem Sie Verbraucher und Batterie abgetrennt haben..
•
Meldung der Kontrollleuchten erneut kontrollieren (siehe Kapitel 5)
•
Nachdem Sie alle Schritte ausgeführt haben, prüfen Sie die Kompatibilität Ihrer Verbraucher.
Falls die Batterie nach einer Netzstörung die Versorgung nicht übernimmt
•
Spannung an den Batterieklemmen prüfen
•
Batteriesicherung prüfen
•
Spannung an den Klemmen Verbr1 und/oder Verbr2 prüfen
Falls die Kontrollleuchten nicht aufleuchten
•
Netzpräsenz auf der Netzklemmleiste prüfen
•
Batterieanschluss (und Batteriesicherung) prüfen
•
Prüfen, ob das Flachbandkabel korrekt angeschlossen ist
•
Spannung an den Klemmen Verbr1 und/oder Verbr2 prüfen
Für weitere technische Unterstützung wenden Sie sich bitte an die SLAT Hotline
+ 33 (0) 4 78 66 63 70
Bei Rücksendeanfragen melden Sie sich bitte auf unserer Website an:
http://www.slat.fr/support/rma/demandez-votre-numero-rma/
oder wenden Sie sich an den SLAT Kundendienst, um eine Rücksendenummer (RMA) zur
erhalten (genehmigte Warenrücksendung).
Ohne RMA-Nummer kann ihre Rückware nicht angenommen werden.
ANNEXE / APPENDIX / ANHANG
IMPLANTATION BATTERIES AUTORISEES
AUTORISED BATTERY IMPLANTATION
GENEHMIGTE BATTERIENANORDNUNG
COFFRET / CABINET / GEHÄUSE : C24
COFFRET / CABINET / Gehäuse : C38
12V 7Ah/12Ah
12V 17Ah
24V 7Ah/12Ah
PLAN DE MONTAGE
MOUNTING DRAWING
MONTAGEZEICHNUNG
COFFRET / CABINET / GEHÄUSE : C24
Trou pour vis de détection d’arrachement mural
Hole of the screw use to detect housing tear down
Bohrung für die abreißen Erkennung
COFFRET / CABINET / GEHÄUSE : C38
Trou pour vis de détection d’arrachement mural
Hole of the screw use to detect housing tear down
Bohrung für die abreißen Erkennung
COFFRET / CABINET / GEHÄUSE : C85
Trou pour vis de détection d’arrachement mural
Hole of the screw use to detect housing tear down
Bohrung für die abreißen Erkennung