Single-Door and Double-Door

Access Control Unit Hardware Installation Manual Models: AC-215 AC-215U all-guides com

Copyright © 2017 by Rosslare. All rights reserved.

This manual and the information contained herein are proprietary to ROSSLARE ENTERPRISES LIMITED and/or its related companies and/or subsidiaries’ (hereafter: "ROSSLARE"). Only ROSSLARE and its customers have the right to use the information. No part of this manual may be re-produced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of ROSSLARE. ROSSLARE owns patents and patent applications, trademarks, copyrights, or other intellectual property rights covering the subject matter in this manual. TEXTS, IMAGES, AND ILLUSTRATIONS INCLUDING THEIR ARRANGEMENT IN THIS DOCUMENT ARE SUBJECT TO THE PROTECTION OF COPYRIGHT LAWS AND OTHER LEGAL RIGHTS WORLDWIDE. THEIR USE, REPRODUCTION, AND TRANSMITTAL TO THIRD PARTIES WITHOUT EXPRESS WRITTEN PERMISSION MAY RESULT IN LEGAL PROCEEDINGS. The furnishing of this manual to any party does not give that party or any third party any license to these patents, trademarks, copyrights or other intellectual property rights, except as expressly provided in any written agreement of ROSSLARE. ROSSLARE reserves the right to revise and change this document at any time, without being obliged to announce such revisions or changes beforehand or after the fact.

Table of Contents

AC-215 Installation Manual iii Table of Contents 1. Introduction ....................................................................... 8 1.1 Control Panel Components ............................................................... 10 1.2 Software ........................................................................................... 10 2. Technical Specifications ................................................. 11 2.1 Panel ................................................................................................ 11 2.2 Transformer ...................................................................................... 11 2.3 PS-14 Power Supply Specifications .................................................... 12 3. Inputs and Outputs ......................................................... 13 3.1 Inputs ............................................................................................... 13 3.1.1 Release to Exit Button (REX) ....................................................................... 13 3.1.2 Door Monitor ............................................................................................ 13 3.1.3 Tamper ..................................................................................................... 14 3.1.4 General ..................................................................................................... 14 3.1.5 Outputs .................................................................................................... 14 3.1.6 Door Lock ................................................................................................. 14 3.1.7 Door Alarm ............................................................................................... 15 3.1.8 Auxiliary .................................................................................................... 15 3.1.9 General ..................................................................................................... 15 3.1.10 Card Readers ............................................................................................. 16 3.1.11 Keypad ..................................................................................................... 16 4. DIP Switch Settings Configuration ............................... 17 4.1 ACU Baud Rate ................................................................................. 17 4.2 ACU Type ......................................................................................... 18 4.2.1 Single Door Controller ............................................................................... 18 4.2.2 Double Door Controller ............................................................................. 18 4.3 ACU Addressing ............................................................................... 19 5. Communications ............................................................. 21 5.1 Serial Connection ............................................................................. 21 5.1.1 RS-232 Connection ................................................................................... 21

Table of Contents

iv AC-215 Installation Manual 5.1.2 RS-485 Connection to the PC .................................................................... 21 5.1.3 Daisy Chain ............................................................................................... 22 5.2 Modem ............................................................................................ 22 5.3 Communication through the Local Area Network (LAN) .................... 23 6. Wiring ............................................................................... 24 6.1 General Wiring Diagram ................................................................... 24 6.2 Inputs ............................................................................................... 25 6.3 Outputs ............................................................................................ 25 6.3.1 Power Supply ............................................................................................ 28 6.4 AC-215 Access Control Panel Diagram .............................................. 29 6.5 Reader .............................................................................................. 30 A. Connecting between MD-N32 and AC-215 ................... 31 A.1 Hardware Requirements.................................................................... 31 A.2 Topics ............................................................................................... 31 A.3 Connections – PC Side ...................................................................... 31 A.4 Connections – AC-215 Panel Side ..................................................... 31 A.5 MD-N32 Configuration with AxTraxNG ............................................. 32 B. Connecting between MD-N33 and AC-215 ................... 35 B.1 Hardware Requirements.................................................................... 35 B.2 Topics ............................................................................................... 35 B.3 Connections – PC Side ...................................................................... 35 B.4 Connections – AC-215 Panel Side ..................................................... 35 B.5 MD-N33 Configuration with AxTraxNG ............................................. 36 B.6 PC Modem – Configuration and Initialization .................................... 37 B.7 Remote Modem – Configuration and Initialization ............................. 38 B.8 Remote Modem Status ..................................................................... 39 B.9 Restoring Factory Default Configuration ............................................ 40 C. Limited Warranty ............................................................ 41

List of Figures

AC-215 Installation Manual v List of Figures Figure 1: AxTraxNG™ and AC-215 System ..................................................... 9 Figure 2: Remote Site Modem Configuration ................................................ 22 Figure 3: MD-N32 Configuration Connecting a Single Panel ......................... 23 Figure 4: Connecting Multiple Access Control Panels with MD-N32 .............. 23 Figure 5: Wiring ........................................................................................... 24 Figure 6: Wiring Four AC-215 Inputs ............................................................ 25 Figure 7: Door Lock – Fail Closed .................................................................. 26 Figure 8: Door Lock – Fail Open .................................................................... 27 Figure 9: AC-215 Wiring to Power Supply ..................................................... 28 Figure 10: AC-215 Wiring Communications .................................................. 29 Figure 11: Reader Cable Coloring ................................................................. 30

List of Tables

vi AC-215 Installation Manual List of Tables Table 1: Description of AC-215 Panels ............................................................ 8 Table 2: DIP Switches and their Functions ..................................................... 17 Table 3: Switch Baud Rates ........................................................................... 17 Table 4: Available Panel Addresses ............................................................... 19 Table 5: RS-232 Connection ......................................................................... 21 all-guides com

Notice and Disclaimer

AC-215 Installation Manual vii Notice and Disclaimer This manual’s sole purpose is to assist installers and/or users in the safe and efficient installation and usage of the system and/or product, and/or software described herein. BEFORE ATTEMPTING TO INSTALL AND/OR USE THE SYSTEM, THE INSTALLER AND THE USER MUST READ THIS MANUAL AND BECOME FAMILIAR WITH ALL SAFETY REQUIREMENTS AND OPERATING PROCEDURES.  The system must not be used for purposes other than those for which it was designed.  The use of the software associated with the system and/or product, if applicable, is subject to the terms of the license provided as part of the purchase documents.  ROSSLARE exclusive warranty and liability is limited to the warranty and liability statement provided in an appendix at the end of this document.  This manual describes the maximum configuration of the system with the maximum number of functions, including future options. Therefore, not all functions described in this manual may be available in the specific system and/or product configuration you purchased.  Incorrect operation or installation, or failure of the user to effectively maintain the system, relieves the manufacturer (and seller) from all or any responsibility for consequent noncompliance, damage, or injury.  The text, images and graphics contained in the manual are for the purpose of illustration and reference only.  All data contained herein subject to change without prior notice.  In no event shall manufacturer be liable for any special, direct, indirect, incidental, consequential, exemplary or punitive damages (including, without limitation, any and all damages from business interruption, loss of profits or revenue, cost of capital or loss of use of any property or capital or injury).  All graphics in this manual are for reference only, some deviation between the image(s) and the actual product may occur.  All wiring diagrams are intended for reference only, the photograph or graphic of the PCB(s) are intended for clearer illustration and understanding of the product and may differ from the actual PCB(s).

AC-215 Installation Manual

1. Introduction In this manual, unless otherwise stated, “AC-215” refers to both the regular AC-215 and the UL-listed AC-215U models. The AC-215 series of access control panels and the AxTraxNG™ PC software are a combination that gives full control over the entrances of your premises. The AxTraxNG software supports control for both single and double door entrances, with which up to 1000 AC-215 access control units (ACUs) can be monitored. The AC-215 panels employ the latest technology to meet the requirements of the market. They control one or two doors when used as a standalone controller, and up to 64 doors per 32 controllers in a network and 5000 users when used as a networked controller with the AxTraxNG software. Table 1 summarizes the two AC-215 and AC-215U models and their respective descriptions. Table 1: Description of AC-215 Panels Model Name Description AC-215 No onboard IP, supplied with 230 VAC transformer AC-215U No onboard IP, FCC approved and UL-294 listed. Use a Class 2 plug-in power supply (sold separately). The AxTraxNG software, which is user-friendly and intuitive, defines settings and event logs. A single server, communicating to and from the ACU, can serve unlimited network clients. The system’s database is saved in the server. The database can be set to back up, and can import/export previous configurations. Clients are able to modify the database; for example, define new employees and/or their access permissions. AxTraxNG can run under Windows 98, 2000, NT or XP operating systems. The AxTraxNG software and associated computer monitoring equipment has not been evaluated by UL. Figure 1 is an example of how the AxTraxNG and AC-215 system can be set up.

AC-215 Installation Manual

9 Figure 1: AxTraxNG™ and AC-215 System AxTraxNG Software RS-485/232 Converter AC-215 Single Door Up to 32 ACUs AC-215 AC-215 Single Door AC-215 Double Door RS-485 RS-232 RS-485 RS-485 Door Monitor Door 2 Maglock Exit Button Reader Door 4 Exit Button Reader, Keypad, and Door Release 2 readers for Reader In and Reader Out Door 3 Door 1 Reader, Keypad, and Door Release

AC-215 Installation Manual

1.1 Control Panel Components The AC-215 control panel consists of the following components:  AC-215 controller board  Enclosure  PS-14 power supply 1.2 Software The AxTraxNG software is user-friendly and intuitive. Its graphic interface is used to define settings, which are downloaded to the ACU and event logs which are uploaded to the PC to generate reports. A single server, which communicates to and from the ACU, can serve unlimited network clients. The system’s database is saved in the server. The database can be set to backup and can import/export previous configurations. Clients are able to modify the database, for example, define new employees and their access permissions. The software enables features to be added as and when they are required. The modular software enables the user interface to be as powerful and strong as required and yet remains simple to use. The software can be set for automatic backup on a periodic basis. AxTraxNG can be run on Windows 98, 2000, NT and XP. For UL installations, the installer must configure the system as fail-safe to comply with NFPA (National Fire Protection Association) regulations.

AC-215 Installation Manual

11 2. Technical Specifications This chapter discusses the technical specification required for the system. 2.1 Panel Electrical Characteristics Operating Voltage 12 VDC 0.5 A (from PS-14) Maximum Input Current (not including attached devices) Standby: 125 mA Maximum: 325 mA Relay Outputs 5 A Relay N.O. and N.C. options General Inputs High impedance active low inputs. Maximum voltage: 5 VDC Reader's Electrical Requirements Voltage: 12 VDC Max current: 300 mA Visual 8 onboard LEDs as well as three PS LEDs (power, low battery, output (V) Fail) Audio Built-in sounder (bell, chime and siren) Speaker's Electrical Characteristics 8 Ohm, 250 mW Environmental Characteristics Operating Temperature Range 0°C to 49°C (32°F to 120.2°F) Operating Humidity Range 0 to 85% (non-condensing) Dimensions Enclosure (L x W x D) 264 x 334 x 84.5 mm (10.4 x 13.2 x 3.4 in.) Weight 3.8 kg (8.3 lb) 2.2 Transformer AC-215 Input: 120/220 VAC Output: 16 VAC 2.5 A (40 VA) supplied, internal to unit AC-215U Input: 120 VAC Output: 16.5 VAC 2.42 A (40 VA) Class 2 (not included). Use wall plug-in unit such as Universal Power Group Part No. UB1640W. all-guides com

AC-215 Installation Manual

2.3 PS-14 Power Supply Specifications Input Voltage 16.5 VAC, 2.42 A Output Voltage 1 13.8 V / 300 mA for 12 V lead acid battery up to 7 Ah. Note: For UL installations, use a 7 Ah battery for a 4-hour minimum backup time. Output Voltage 2 12 VDC, 0.5 A Output Voltage 3 12 VDC, 1.5 A Power Supply Indication Tamper Output (open collector) Indicates faulty power Power LEDs Power In (AC) – Green LED1 Main power Power Out (DC) – Red LED2 Low voltage Charger (BAT) – Red LED3 Backup battery low voltage

Inputs and Outputs

AC-215 Installation Manual 13 3. Inputs and Outputs This chapter discusses the AC-215 ACU input and output requirements. 3.1 Inputs 3.1.1 Release to Exit Button (REX) REX enables quick exit from a premises. The following should be defined: Single door controller Door 1 – IN1 Double door controller Door 1 – IN 1 Door 2 – IN 2 Usually the REX input is connected to a push button that is located inside the premises. The push button opens a door without reading a proximity card or PIN code. Generally, the REX is located in a convenient position such as near the reception area, and is always set as enabled in the AxTraxNG software. 3.1.2 Door Monitor The Door Monitor connects to a door’s micro switch for door status monitoring. The following should be defined: Single door controller Door 1 – IN1A Double door controller Door 1 – IN 1A Door 2 – IN 2A Two alarm states can be generated:  Forced alarm – When the door is forcibly opened by unauthorized persons  Door held open alarm – When the door is open for a period exceeding the lock strike programmed open time A door held open alert can be generated by activating chime on speaker to remind that the door should be close. After the ACU enables access, the lock is activated according to its programmed time until one of the following occurs:  The ACU stops lock activation immediately after the door opens  The ACU waits for the door to close. (This can help to reduce tailgating) When the door open time period expires, the ACU ends lock activation.

Inputs and Outputs

14 AC-215 Installation Manual 3.1.3 Tamper The internal tamper switch must be connected to a UL Listed burglary unit. Refer to the selected UL Listed burglary unit for connection instructions The tamper input connects to a tamper micro switch assembled within the ACU panel. The following should be defined: Single door controller Door 1 – IN2 Tamper input is activated when the panel is opened through vandalism. The system has two additional tamper inputs on the reader terminals. 3.1.4 General The General input connects to any general-purpose dry contact input. Single door controller Door 1 – IN2A This function can be used when activating the general purpose output connections, such as alarm sensors and monitoring power supply failure. The ACU reports activation if this input changes status. The system has four output relays. Their contacts are voltage free and rated 5 A at 12 VAC or VDC. This indicates that output is very versatile and can operate virtually any electrical equipment including Fail Open and Fail Close locks, electric gates and so on. 3.1.5 Outputs We recommend using a suppression diode for all outputs. 3.1.6 Door Lock There are two types of door locking devices:  Fail open (fail secure)  Fail close (fail safe) The user can select either normally open or normally closed output contacts. The following should be defined: Single door controller Door 1 – OUT1 Double door controller Door 1 – OUT1 Door 2 – OUT2 The output can sink current from any power supply (see Section 2.2). In a time zone door locking is activated in the following modes:  Grant Access  Automatic Relock

Inputs and Outputs

AC-215 Installation Manual 15 The output can provide 12 VDC power up to 1.5 A for external door locks. For higher rated door locks an external UL 294 Listed power supply must be used to provide power to the door lock. For UL installations, the installer must configure the system as fail-safe to comply with NFPA (National Fire Protection Association) regulations 3.1.7 Door Alarm This output is activated when either an alarm occurs in the system, or automatically by a time zone. The following should be defined: Single door controller Door 1 – OUT1A Double door controller Door 1 – OUT1A Door 2 – OUT2A The output can be activated for a specified time and closes when the timer ends. 3.1.8 Auxiliary This output is activated when a transaction occurs in the readers that are either associated with auxiliary, or automatically by a time zone. The following should be defined: Single door controller Door 1 – OUT2 The output has two activations modes:  Time – active for a specified time and closes when the timer ends  Toggle – active for every change in the output trigger – the trigger changes state 3.1.9 General This output is usually related to the general input or automatically by a time zone. The following should be defined: Single door controller Door 1 – OUT2A The output has three activation modes:  Follow input – output follows the input state  Toggle – active for every change in the output trigger – the trigger changes state  Time – active for a specified time and closes when the timer ends

Inputs and Outputs

16 AC-215 Installation Manual 3.1.10 Card Readers Two card readers can be connected to the ACU. The following should be defined: Single door controller Door 1 – Reader 1 IN/OUT/Auxiliary Reader 2 – IN/OUT/Auxiliary Double door controller Door 1 – Reader 1 IN/OUT Door 2 – Reader 2 IN/OUT The readers can be assigned to a single or double door controller’s door as an IN or OUT reader and can activate the auxiliary output in a single door configuration. The reader’s tamper connects to the ACU and can generate an alarm. The reader’s green LED input is activated by the ACU when in the Card and PIN secure mode to inform the user to enter his personal PIN number after entering his card. 3.1.11 Keypad Two keypads can be alternatively connected to the ACU on Reader1 and Reader2 terminals. The following should be defined: Single door controller Door 1 – Keypad – Reader 1 IN/OUT Keypad – Reader 2 IN/OUT Double door controller Door 1 – Keypad – Reader 1 IN/OUT Door 2 – Keypad – Reader 2 IN/OUT The keypad type must be a Rosslare format keypad. A keypad has to be connected for any reader mode that requires PIN code entries, such as Card or PIN, PIN only or Card and PIN (Secured mode). all-guides com

DIP Switch Settings Configuration

AC-215 Installation Manual 17 4. DIP Switch Settings Configuration The ACU DIP switch controls a number of operating parameters including the device address and baud rates for serial communication. Power down the ACU before making changes in the dipswitch settings. Restart the ACU after modifications are made. The new settings are automatically defined after power up. The following is a list of DIP switch numbers and their functions: Table 2: DIP Switches and their Functions DIP Switch Function 1–2 Set ACU baud rate 3 Sets ACU type (single door or double door controller) 4–8 Set ACU address 4.1 ACU Baud Rate The ACU serial port baud rate, set in DIP switches one and two, defines the communication speed for connecting with a PC in a network connection. The following lists switch 1 and 2 status and baud rate: Table 3: Switch Baud Rates Switch 1 Switch 2 Baud Rate Off Off 9600 Off On 19200 On Off 38400 On On 57600 The ACU baud rate must be identical to the host PC’s serial port baud rate. 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

DIP Switch Settings Configuration

18 AC-215 Installation Manual 4.2 ACU Type The ACU type is defined using the third DIP switch. Both the single and double can be set.  Off – defines single door controls  On – defines a double door controls 4.2.1 Single Door Controller This access type has two readers, IN and OUT, as follows:  Outputs:  Door lock strike  Auxiliary output  Alarm output  General purpose output  Inputs:  Release to exit  Door monitor input  Tamper input  General purpose input For more information, see Chapter 3. 4.2.2 Double Door Controller This access type has two readers, IN and OUT, as follows:  Outputs  Door 1 lock strike  Door 1 alarm output  Door 2 lock strike  Door 2 alarm output  Inputs  REX Door1  Door 1 monitor input  REX Door 2  Door 2 monitor input 1 2 3 4 5 6 7 8

DIP Switch Settings Configuration

AC-215 Installation Manual 19 4.3 ACU Addressing The DIP switch is used to select the binary coded ACU address. The ACU address is defined in the AxTraxNG software. For successful communications, the dipswitch must be defined with the same address. Table 4 displays the 32 address settings available: Table 4: Available Panel Addresses Address Switch 4 Switch 5 Switch 6 Switch 7 Switch 8 1 Off Off Off Off Off 2 Off Off Off Off On 3 Off Off Off On Off 4 Off Off Off On On 5 Off Off On Off Off 6 Off Off On Off On 7 Off Off On On Off 8 Off Off On On On 9 Off On Off Off Off 10 Off On Off Off On 11 Off On Off On Off 12 Off On Off On On 13 Off On On Off Off 14 Off On On Off On 15 Off On On On Off 16 Off On On On On 17 On Off Off Off Off 18 On Off Off Off On 19 On Off Off On Off 20 On Off Off On On 21 On Off On Off Off 22 On Off On Off On 23 On Off On On Off 24 On Off On On On 25 On On Off Off Off 1 2 3 4 5 6 7 8

DIP Switch Settings Configuration

20 AC-215 Installation Manual Address Switch 4 Switch 5 Switch 6 Switch 7 Switch 8 26 On On Off Off On 27 On On Off On Off 28 On On Off On On 29 On On On Off Off 30 On On On Off On 31 On On On On Off 32 On On On On On

AC-215 Installation Manual

21 5. Communications Communication lines are used to upload and download information between the ACU and the AxTraxNG software. Communication between the ACU and PC is displayed by the system’s two LEDs.  The RX LED flashes when the controller receives data  The TX LED flashes when the controller transmits data The ACU address is defined in the AxTraxNG software. For successful communications, the dipswitch must be defined with the same address. There are three connection modes:  Serial  RS-232  RS-485  Modem  LAN 5.1 Serial Connection The PC Serial Port controlling the ACU is assigned in the Network Properties in the AxTraxNG software. By default the default is set to 9600 for direct connection to the PC using the standard RS-232 interface. 5.1.1 RS-232 Connection Table 5: RS-232 Connection ACU DB9 Connector DB25 Connector GND Pin 5 Pin 7 Tx Pin 2 Pin 3 Rx Pin 3 Pin 2 DTR Pin 4 Pin 20 The RS-232 connection can only be used for one ACU. The distance between the PC and ACU can be no more than 50 m (150 ft). If the baud rate is increased to 57600 the distance can be up to 10 m (30 ft). J1 must be in the RS-232 position to select the RS-232 communication. 5.1.2 RS-485 Connection to the PC Up to 32 ACUs can be linked together and connected to a single communication port on the PC. The RS-485 interface must be used when multiple controllers are connected. The serial port used to control the ACU is assigned in the AxTraxNG software Network Properties dialog box. all-guides com

AC-215 Installation Manual

ACU supports the 2-wire RS-485 interface. RS-485 interface enables the distance between the ACU and PC to be extended up to 1300 m (4000 ft). The data line wiring must be in daisy chain formatting with one control unit following another. The first ACU connecting to the PC must use the MD-14, RS-485 to RS-232 adaptor. The recommended cable type to be used is STP cat5 (shielded twisted pair category 5). We recommend using a 20-24-AWG cable. 5.1.3 Daisy Chain Communication lines must be wired in a daisy chain format with one ACU following another. J1 must be in the RS-485 position. J1 must be in the RS-485 position. At each end of the data line a termination resistor of 100–120 Ω is required across the L1 and L2 connections. 5.2 Modem The PC modem connection, used to control the ACU, is assigned in the AxTraxNG software’s Network Properties dialog box. The modem is used when the distance between the ACU and the PC is greater than the recommended serial connection distance or in an application where an alternative RS-232/RS-485 network is unavailable. Figure 2 illustrates remote site modem configuration with AC-215. Figure 2: Remote Site Modem Configuration For more information, see Appendix B.

AC-215 Installation Manual

23 5.3 Communication through the Local Area Network (LAN) The TCP/IP connection, used to control the ACU, is assigned in the AxTraxNG software’s Network Properties dialog box. The PC running the AxTraxNG software can communicate with the ACU through the LAN card inside the PC. The ACU connects to the LAN using Rosslare MD-N32, TCP/IP to RS-232 gateway converter. MD-N32 can be connected in any legal network address in the Local Area Network. The following type of connection is used when a LAN network already exists and therefore the long RS-485 network is not required. This schematic illustrates the connection of a single AC-215 to the PC using the LAN network. MD-N32 must be first configured by Rosslare's Netconfig software. The setting is stored in a non-volatile memory in the MD-N32. Figure 3: MD-N32 Configuration Connecting a Single Panel Multiple ACUs can be connected by adding an RS-485 converter (MD-14) between the RS-485 ACUs network and MD-N32 converter. Figure 4: Connecting Multiple Access Control Panels with MD-N32 For more information, see Appendix A.

AC-215 Installation Manual

6. Wiring 6.1 General Wiring Diagram Figure 5 illustrates the general wiring layout of the AC-215. Figure 5: Wiring For UL installations, the following signal lines are not allowed to be run outside of the protected area: • 12 VDC 1.5 A + and (-) • 12 VDC 0.5 A + and (-) • Relay contacts OUT1: COM., N.O., and N.C.

AC-215 Installation Manual

25 6.2 Inputs Figure 6 illustrates wiring for four AC-215 inputs. For further details, see Chapter 3. Figure 6: Wiring Four AC-215 Inputs 6.3 Outputs Figure 7 and Figure 8 illustrate wiring for two main types of 12 VDC electric release mechanisms. Other electrical devices can be switched using the voltage free relay contacts. The output can provide 12 VDC power up to 1.5 A for external door locks. For higher rated door locks an external UL 294 Listed power supply must be used to provide power to the door lock. For UL installations, the installer must configure the system as fail-safe to comply with NFPA (National Fire Protection Association) regulations.

AC-215 Installation Manual

6.3.1 Power Supply Figure 9 illustrates wiring between the PS-14 power supply and the AC-215. It is recommended to add a 12 VDC lead acid backup battery to backup power if the main fails. If the main output is 12 VDC, wire it to the (PS-14); otherwise support your power supply according to output requirements. Figure 9: AC-215 Wiring to Power Supply

AC-215 Installation Manual

29 6.4 AC-215 Access Control Panel Diagram Figure 10 presents a complete view of the AC-215 control panel’s PCB, including all connector buttons and LED schematics (not to scale). Figure 10: AC-215 Wiring Communications

AC-215 Installation Manual

6.5 Reader Proximity and keypad readers are supplied with a limited cable. The color of the cable covering represents the cable’s function. When extending cable distance be careful with the color of the cable cover. The distance is limited by the Wiegand standard. Figure 11: Reader Cable Coloring Key: +V Red (-) Black D0 Green D1 White G.LED Brown Tamper Purple

Connecting between MD-N32 and AC-215

AC-215 Installation Manual 31 A. Connecting between MD-N32 and AC-215 This instruction is written as step by step instruction. It is very important to follow the right order. A.1 Hardware Requirements  Standard LAN cable – RJ45 plugs in both sides  Rosslare's MD-14 (RS-232 to RS-485 converter)  Rosslare's MD-N32 (TCP/IP to serial gateway)  Rosslare's AC-215 panel A.2 Topics  Before setting, ask your network administrator for one, free IP address and subnet mask, which has to be used here.  The IP addresses shown in the examples below are for illustration purpose only. A.3 Connections – PC Side Connect the PC using the internal network card (mostly in the rear side of the PC) to the LAN network with regular network cable. (If the PC is already identified and known in the local network, it is already connected and you do not need any further installation). A.4 Connections – AC-215 Panel Side To connect to the panel: 1. Connect a 9 VDC adapter to the MD-N32. Check that the power LED (Red) is on. 2. Connect the MD-N32 to the LAN by using a regular network cable through the MD-N32's RJ-45 connector. Check that the link LED (Green) is on. 3. Connect MD-N32's DB9 male jack to MD-14's DB9 female jack with cross serial cable. 4. Connect the AC-215's RS-485 outlet to MD-14 4 wires cable. 5. Make sure that J1 (on the AC-215) is set to RS-485 Mode. 6. If the jumper was not set properly, make the change, turn the power of AC-215 off, wait few seconds and turn it on. all-guides com

Connecting between MD-N32 and AC-215

32 AC-215 Installation Manual A.5 MD-N32 Configuration with AxTraxNG To configure the MD-N32: 1. Add a new network using the AxTraxNG software (for more details, see the AxTrax user manuals.) The network type should be selected as TCP/IP. 2. Click the Configuration tab and wait until "searching" is complete. 3. Click OK. 4. Select the suitable MAC address from the MD-N32 list. The MD-N32's MAC address should be labeled on the MD-N32's box.

Connecting between MD-N32 and AC-215

AC-215 Installation Manual 33 5. In the Configuration area, type the IP Address and Subnet that the network administrator supplied you. 6. In the Port field, enter 1000. 7. In the Speed area, select the speed of your serial connection (9600/19200/ 38400/57600). 8. Click Apply to send the configuration to the unit and wait for following message: 9. Click OK to start verification process and wait for the following message:

Connecting between MD-N32 and AC-215

34 AC-215 Installation Manual 10. Click OK twice and verify that the configuration was accepted by the AxTraxNG software. The MD-N32 and AxTraxNG software are now configured ready for testing. From this stage, you can continue working per the procedure for adding a new panel to the AxTraxNG.

Connecting between MD-N33 and AC-215

AC-215 Installation Manual 35 B. Connecting between MD-N33 and AC-215 This manual is written as step by step instruction. It is very important to follow the right order. B.1 Hardware Requirements  2 Standard Telephone cables – RJ11 plugs in both sides  Standard Serial cable D-type 9 pin (Female connectors at both sides)  Rosslare's MD-14 (RS-232 to RS-485 converter)  2 Rosslare's MD-N33 (Modem to serial gateway)  Rosslare's AC-215 panel B.2 Topics  The telephone numbers shown at the examples below are for illustration purpose only.  Before permanent modem installations, the modem that has to be connected to the panel must initialize at PC running the AxTraxNG software. B.3 Connections – PC Side To connect to the PC: 1. Connect a 9 VDC adapter to the first MD-N33. 2. Make sure that the power LED (Red) is on. 3. Connect the PC, using a free COM port, to the MD-N33 with cross serial cable. 4. Connect the MD-N33's RJ11 jack to telephone line using the telephone cable. B.4 Connections – AC-215 Panel Side To connect to the panel: 1. Connect a 9 VDC adapter to the second MD-N33. 2. Make sure that the power LED (Red) is on. 3. Connect the MD-N33's DB11 jack to telephone wall mount using the telephone cable. 4. Connect MD-N33's DB9 female jack to MD-14's DB9 female jack. 5. Connect the AC-215's RS-485 outlet to the MD-14 4-wire cable.

Connecting between MD-N33 and AC-215

36 AC-215 Installation Manual 6. Make sure that J1 (on the AC-215) is set to RS-485 Mode. 7. If the jumper was not set properly, make the change, turn the power of AC-215 off, wait few seconds and turn it on. B.5 MD-N33 Configuration with AxTraxNG To configure the MD-N33: 1. Add a new network using the AxTraxNG software (for more details see the AxTrax user manuals). The network type should be selected as Modem. all-guides com

Connecting between MD-N33 and AC-215

AC-215 Installation Manual 37 B.6 PC Modem – Configuration and Initialization 1. Click the Configuration tab to get the Modem configuration screen. 2. In the Dialing section: a. In the "Remote modem phone number" field, enter the destination telephone number to call. b. Change the "number of dial attempts" as needed. c. In the Additional dialing string options field, for most applications, the default dialing string of AS-525 is enough. The dialing string is displayed in the window. Adding or editing dialing string is allowed by clearing the "Use default" checkbox and typing the AT command in the dialing string window. d. In the “Dialing schedule” dropdown, select the proper time zone. The disconnecting condition can be chosen: "Disconnect by schedule end" or "Disconnect on upload complete". (It is allowed when the selected time zone is different than the default time zones (Always & Never). 3. In the Settings section: For most applications, the default initialization string of AS-525 is enough. The initialization string is displayed in the window. Adding or editing initialization string is allowed by clearing "Use default" and type the AT command in the "Initialization string" window. 4. Connect the PC modem to the PC via the selected com port and click Apply to initialize the PC modem. 5. Click OK for the successful initialization.

Connecting between MD-N33 and AC-215

38 AC-215 Installation Manual If a failure message appeared, check the modem connections and repeat the last steps. B.7 Remote Modem – Configuration and Initialization To configure a remote modem: 1. Click the Remote modem tab to configure the remote modem. 2. In the Settings section: For most applications, the default initialization string of AS-525 is enough. The initialization string is displayed in the window. Adding or editing initialization string is allowed by uncheck "Use default" and type the AT command in the "Initialization string" window.

Connecting between MD-N33 and AC-215

AC-215 Installation Manual 39 3. Set the number of rings before the PC modems will answer. 4. Connect the remote modem to the PC via the selected com port and click Apply to initialize the PC modem. 5. Click OK for the successful initialization. If a failure message appeared, check the modem connections and repeat the last steps. The MD-N33 and AxTraxNG software are now configured ready for testing. From this stage, you can continue working per the AxTraxNG adding new panel procedure. B.8 Remote Modem Status When a panel is connected to a modem network, you can see the status of the modem by clicking the phone icon in the toolbar. There is a manual option to dial or disconnect the modem.

Connecting between MD-N33 and AC-215

40 AC-215 Installation Manual To prevent access to AxTraxNG data from non-authorized users, the AC-215 contains a password that can be changed only when the modem is connected and there is a link with AC-215. The default password is AxTrax. You may be asked to enter the password during first data configuration like adding a new panel or downloading a new firmware. B.9 Restoring Factory Default Configuration If you forgot the existing password, there is an option to return AC-215 to factory default (with password: AxTrax) Returning to factory default changes also all the doors and readers configuration to factory default and clears all the users' properties. To restore factory default configuration: 1. Turn off the supply power. 2. It is recommended to disconnect the doors and readers wiring. 3. Connect Data 0, Data 1 and Tamper inputs to GND (-) in both Reader 1 and 2 (totally 6 wires!) 4. Power up the supply power for few seconds and wait for the control LEDs to flash. 5. Turn off the supply power. 6. Connect the doors and readers wiring again. 7. Delete the panel by clearing the Enable panel checkbox in the panel screen and clicking OK. 8. Check Enable panel in the panel screen and click OK. This action causes a full setting of the AC-215 with the pervious configuration. 9. Dial the proper AC-215 ACU and click password in the modem status screen. You may enter the "current password" as AxTrax and change the password to a new one.

AC-215 Installation Manual

41 C. Limited Warranty The full ROSSLARE Limited Warranty Statement is available in the Quick Links section on the ROSSLARE website at www.rosslaresecurity.com. Rosslare considers any use of this product as agreement to the Warranty Terms even if you do not review them. all-guides com

Asia Pacific, Middle East,

Africa Rosslare Enterprises Ltd. Kowloon Bay, Hong Kong Tel: +852 2795-5630 Fax: +852 2795-1508 [email protected] United States and Canada Rosslare Security Products, Inc. Southlake, TX, USA Toll Free: +1-866-632-1101 Local: +1-817-305-0006 Fax: +1-817-305-0069 [email protected] Europe Rosslare Israel Ltd. Rosh HaAyin, Israel Tel: +972 3 938-6838 Fax: +972 3 938-6830 [email protected] Latin America Rosslare Latin America Buenos Aires, Argentina Tel: +54-11-4001-3104 [email protected] China Rosslare Electronics (Shenzhen) Ltd. Shenzhen, China Tel: +86 755 8610 6842 Fax: +86 755 8610 6101 [email protected] India Rosslare Electronics India Pvt Ltd. Tel/Fax: +91 20 40147830 Mobile: +91 9975768824 [email protected] CERT ISO 9001 ISO 14001