Salda Stouch Technical Manual
Read Online
Read the Salda Stouch Technical Manual online using the built-in PDF viewer.
Text of the manual
Ragainės g. 100, LT-78109 Šiauliai, Lithuania
Tel. (+370 41) 540415
Fax. (+370 41) 540417
offi [email protected]
www.salda.lt
Techninis vadovas
[ lt ]
Psl. 2
Техническое руководство [ ru ] Cтр. 14
Technical manual
[ en ]
Pg. 26
Bedienungsanleitung
[ de ]
S. 38
Notice technique
[ fr ]
P. 50
Sensorinis pultelis
Сенсорный пульт
Sensor controller
Sensorpult
Boîtier de commande tactile
Stouch
all-guides
com
Stouch valdymo pultelis specialiai sukurtas valdyti:
• SALDA vėdinimo įrenginius;
• Kitus įrenginius turinčius PRV ir ECO valdymo plokštes;
• Modbus protokolu valdomus prietaisus.
Valdymo pulteliai garantuoja optimalų eksploatacijos, stebėsenos ir aptarnavimo komfortą bei saugumą. Visos
operacijos atliekamos nuotoliniu būdu naudojant valdymo pultelį, kuriame parodomos gedimų ataskaitos ir aptar-
navimo sąlygos.
Ypatybės:
• Išskirtinis ir ergonomiškas dizainas;
• Paprastas naudojimas;
• Skirtas virštinkiniam montavimui;
• Vieno paspaudimo sensorinis valdymas;
• Lengvai valomas;
• Skaičių atvaizdavimas ekranėlyje;
• Garsinis atsakas į lietimą;
• Gali būti prijungtas prie BMS tinklo;
• Galima tiesiogiai prijungti prie 0-10VDC signalu valdomo ventiliatoriaus;
• Naudojant 0-10VDC įėjimą, galima prijungti CO2 arba slėgio jutiklį;
• 4 nustatomi greičiai;
• Makslimalus ventiliatoriaus greitis, ribotą laiko tarpą (boost);
• Blokavimas (užrakinimas) - apsauga nuo vaikų;
• Vartotojo meniu galite pakeisti garso, pristabdytosios veiksenos (StandBy), CO2 parametrus.
Į pakuotę įeina:
Stouch valdymo pultelis, laidas (13m), tvirtinimo elementai (6 vnt.), techninis vadovas.
Ma
Matmenys
20,5
84
84
1,5
1. Naudojant pateiktą šabloną, pasirinktoje vietoje įsukite savisriegius, palikdami apie 1 mm tarpą nuo
plokštumos.
2. Prie pultelio prijunkite kabelį
2.1- standartinis jungimas;
Montavimas
2.2 - specialus jungimas (žiūrėti: “8 kontaktų jungimas”).
3. Užkabinkite pultelį laikydami jį pasuktą 25O kampu į kairę pusę.
4-5. Sukite pultelį į dešinę, kol pultelis prisispaus prie plokštumos. Pašalinkite panaudotą šabloną.
1
4
1 2 3 4
PIN1 - +24V
PIN2 - B+
PIN3 - A-
PIN4 - COM
PIN1 - +24V
PIN2 - B+
PIN3 - A-
PIN4 - COM
8
8 kontaktų jun
ungimas
1. Maitinimo šaltinis 24V AC/DC, 100mA
2. Maitinimo šaltinis 24V AC/DC
3. GND
4. RS485 B (Modbus)
5. RS485 A (Modbus)
6. GND
7. 0-10VDC įėjimas (naudojamas slėgio arba CO2 jutikliui). Jutiklis maitinamas nuo atskiro maitinimo šaltinio.
8. 0-10VDC išėjimas (naudojamas 0..10 VDC ventiliatorių valdymui.
Elektrinis pajungimas gali būti atliktas tik kvalifi kuoto elektriko pagal, galiojančius tarptautinius ir nacionalinius
elektrosaugos, elektros įrenginių įrengimo, reikalavimus.
Ventiliatoriaus greičio nustatymas
B3
Temperatūros nustatymas
B4
Padidinti
B5
Makslimalus ventiliatoriaus greitis,
ribotą laiko tarpą (boost)
B6
Pamažinti
S1
Segmentinis ekranas
L4-L7 Ventiliatoriaus greičio indikacijos
Informacija va
vartotojui
ui
• Pultelyje sukurtas paprastas vartotojo meniu garso, temperatūros, miego režimo bei CO2 lygio parametrų
nustatymui.
• Spartusis maksimalaus greičio aktyvavimo mygtukas.
• Nustatytos, bei tiekiamo oro temperatūros rodymas skaitmenimis.
• Pasirinkto greičio LED indikacija.
• Aktyvių avarijų rodymas simboliais: A.01, A.02 ir t.t., bei LED indikacija.
• Pultelio miego režimas taupantis energiją.
• Galima vėdinimo sistemos išjungimo blokavimo funkcija.
• „Apsauga nuo vaikų“ - užrakina pultelį.
Elementai
Komanda Veiksmas
Indikacija
B1
L1
Įjungimas 2 sekundes palaikyti B1
Šviečia L1.
B1
L1
Išjungimas 2 sekundes palaikyti B1
Užgęsta L1.
L1
Pažadinimas iš miego
režimo Paliesti bet kurį mygtuką.
Miego režime lėtai mirksi L1.
B2 B4 B6
L2
Nustatyti ventiliatorių
greitį Paliesti B2.
Šviečia L2. Greitis reguliuojamas liečiant
B4 ir B6 elementus
B3 B4 B6
L3
Nustatyti temperatūrą Paliesti B3.
Šviečia L3. Temperatūra reguliuojama
liečiant B4 ir B6 elementus
B4 B6
L4-L7
Keisti pasirinkto nus-
tatymo reikšmę
Didinti palietus B4, mažinti
palietus B6
Segmentiniame ekranėlyje keičiasi
skaitmenys. L4, L5, L6, L7 rodo pasirinktą
ventiliatorių greitį.
B4 B5 B6
L2
Intensyvaus vėdinimo
funkcijos(boost)
įjungimas / išjungimas
2 sekundes palaikyti B5.
Mirksi L2. Segmentiniame ekranėlyje
rodomas likęs laikas sekundėmis (virš
600s laikas rodomas minutėmis). Laikas
reguliuojamas liečiant B4 ir B6.
Maksimalus BOOST veikimo laikas:
180min. (3h)
Mirksintis „Con“ užrašas – jungiamasi.
Šviečiantis „noC“ užrašas – dingo ryšys.
Ryšio indikaci
cija
Ve
Ventiliatorių gr
greičio va
valdym
ymas
• Pagal nustatytus fi ksuotus 4 greičius
• Pagal procentinį greitį (0, 20-100%)
• Vartotojo meniu greičiai valdomi kas 5%
• Serviso meniu greičiai valdomi kas 1%
• Pagal nustatytus fi ksuotus 4 slėgius naudojant slėgio jutiklį
• Maksimalus greitis apsaugotas laikmačiu, kurį galime lengvai keisti paleidus maksimalų ventiliatoriaus greitį
(boost)
• Maksimalus greitis aktyvuojamas sparčiuoju mygtuku. Pasibaigus maksimalaus ventiliatoriaus greičio (boost)
nustatytam laikui, automatiškai grįžtama į ankstesnį greitį.
• Galima pajungti 0..10 VDC CO2 jutiklį, kuris aktyvuotų maksimalų greitį pagal nurodytus CO2 parametrus
Te
Temperatūros v
valdyma
mas
• Pultekyje galima nurodyti norimą temperatūrą nuo 15 - 35°C
• Galimas tiekiamo oro ir nustatytos temperatūros rodymas pakaitomis (5 sekundes rodoma nustatyta
temperatūra, 2 sekundes tiekiamo oro temperatūra )
Nuotolinis valdy
dymas (M
(Modbu
bus)
Pultelis palaiko pilnai konfi gūruojamą Modbus sąsają. Pultelis gali būti ir pagrindiniu ir pagalbiniu įrenginiu
modbus tinkle, be to, galite jį pilnai valdyti, bei konfi gūruoti ne tik per serviso meniu, bet ir per modbus sąsają.
Va
Vartotojo meni
niu
Norint patekti į vartotojo meniu reikia 3 sekundes laikyti palietus B2, B3.
Vartotojo meniu iš eilės rodomi menių punktų (P.01, P.02 ir t.t) nustatymai. Meniu punktas pasirenkamas B4 ir
B6 elementais. Paspaudus B5 parodoma pasirinkto parametro reikšmė, kurią keisti galima B4 ir B6 elementais.
Paspaudus B5 parametras išsaugomas ir grįžtama į meniu.
Dėl ribotų segmentinio ekranėlio galimybių P.04 ir P.05 reikšmės nurodomos 10 kartų mažesnės, t.y. jeigu
ekranėlyje rodoma 20, tai reiškia jog tikroji reikšmė yra 20 x 10 = 200.
P.06 - fi ltrų laikmatis atstatomas į pradinę būseną 5 sekundes palaikius nuspaustą B5 elementą. Filtrų laikma-
tis taip pat atstatomas į pradinę padėtį anuliuojant A.03 avariją.
Norint išeiti iš meniu reikia paliesti B1 elementą.
B4 B6
L4-L7
Avarijų peržiūra ir anul-
iavimas
Anuliuojant 3 sekundes
palaikyti B2 ir B3.
Esant avarijoms mirksi L4, L5, L6, L7, bei
segmentiniame ekranėlyje rodomi avarijos
kodai (A.01, A.02 ir t.t.). Avarijų sąrašą
peržiūrėti galima B4 ir B6 elementų
pagalba. Anuliavus avariją, pultelis grįžta į
pradinę būseną.
L2-L7
Vyksta CO2 prapūtimas
Mirksi L2, L3 ir L7, šviečia L4, L5, L6.
B2 B3 B5
Įjungaima/išjungiama
“apsauga nuo vaikų”
2 sekundes palaikyti B3,
B2 ir B5.
Neaktyvūs elementai B1, B4 ir B6.
Paspaudus neleistiną mygtuką segmenti-
nis ekranėlis rodo „---“
Šis pultelis gali valdyti kitus (MODBUS protokolu valdomus) įrenginius. Tai nustatoma serviso meniu nurodant
reikiamus parametrus F.17, F.18, F.19, F.20, F.21 serviso meniu punktuose. Norint valdyti ne tik standartin-
ius įrenginius, F.20 meniu punkte reikia nurodyti „CUSTOM“ bei įrenginių adresus meniu punktuose nuo Nr.
F.22 iki F.37. Jeigu įrenginiai tokių adresų neturi, nurodytuose meniu punktų laukeliuose reikia įvesti „00:00“.
Standartiškai šis pultelis naudojamas su ECO arba PRV valdymo plokštėmis.
PULTELIS
(master)
MODBUS
AHU
(slave)
1) Modbus master (
r (pagrindinis)
Panaudojant BMS (Building Management System) sistemą vienu pulteliu galima valdyti kelis įrenginius
sinchroniškai, arba su keliais pulteliais valdyti vieną įrenginį. Naudojant MODBUS protokolą galima keisti visus
pultelių parametrus bei stebėti prijungtų jutiklių duomenis.
PULTELIS
(slave)
AHU
(slave)
BMS
AHU
(slave)
PULTELIS
(slave)
MODBUS
RS485
2) Modbus slave (p
(pagalbinis)
Nr.
Pavadinimas Galimos reikšmės
Numatyta
reikšmė
P.01
Miego režimas 0 - Išjungtas
1 - 99 užmigimo laikas sekundėmis
0
P.02
Garsas 0: Išjungtas
1: 1 –9 garso tembras
2
P.03
Tiekiamos temperatūros rodymas 0: Nerodoma
1: Rodoma pakaitomis su nustatyta
0
P.04
CO2 reikalaujama (ppm) 0 – 99 x10ppm
20 x10
P.05
CO2 leistinas skirtumas 0 – 99 x10ppm
5 x 10
P.06
Filtrų laikmatis 0 – 999 dienos
0
all-guides
com
3) Ventiliatoriaus va
valdymas, kai greitis nust
ustatomas
mas pu
pulte
lteliu
ir/arba kompiuteriu p
u per Modbus
Šiuo pulteliu galima valdyti tiek įrenginį tiek 0..10VDC ventiliatorių. Serviso meniu pasirinkite norimą greičio
valdymo būdą (F.01), jeigu pasirinkote valdymą pagal nustatytus greičius, tada nurodykite juos: F.03, F.04, F.05,
F.06 meniu punktuose.
PULTELIS
(slave)
FAN
0...10 VDC
MODBUS
4) Slėgio palaikymas,
as, kuris nurodomas pult
ulteliu ir/a
r/arba
kompiuteriu per Mo
Modbus
Prijungus 0..10VDC ventiliatorių ir 0..10VDC slėgio keitiklį tiesiai prie pultelio galima palaikyti norimą slėgį.
Valdymo bei slėgio jutiklio parametrus galima keisti pulteliu. Naudojant pultelį kaip pagalbinį („Modbus slave“)
įrenginį yra galimybė valdyti visus parametrus bei stebėti slėgio jutiklio rodmenis.
Tam, kad galėtumėme valdyti pagal slėgį, serviso meniu reikia nurodyti šiuos parametrus:
• F.14 - 1
• F.15 ir F.16 - pagal slėgio keitiklio parametrus
• F.11, F.12 ir F.13 - (PID valdymo koefi cientai). Jeigu slėgis palaikomas nekorektiškai, galima šiuos parametrus
koreguoti.
• F.07 - F.10 - nurodome fi ksuotus greičius Pa.
PULTELIS
(slave)
FAN
0...10 VDC
MODBUS
slėgio
jutiklis
0...10 VDC
5) CO2 palaikymas
as
PULTELIS
(master)
FAN
(vietoje AHU)
0...10 VDC
MODBUS
CO2
jutiklis
0...10 VDC
AHU
(slave)
Šio pultelio pagalba galima valdyti patalpoje esančio anglies dvideginio (CO2) lygį. Tiesiog prie pačio pultelio
reikia prijungti 0..10VDC CO2 jutiklį ir sukonfi gūruoti pultelį. Serviso režime F.14 punkte reikia nustatyti 2, o F.15
ir F.16 nurodome pagal jutiklio specifi kaciją.
Prijungus CO2 jutiklį ir serviso meniu nustačius nurodytus parametrus, vartotojo meniu reikia nustatyti
norimą CO2 lygį (P.05) ir leistiną viršyti skirtumą nuo nustatytos (P.05) ribos. Viršijus leistiną skirtumą, pultelis
automatiškai paleis ventiliatorius maksimaliu (4) greičiu, skaitmeniniame ekranėlyje bus rodomas „CO2“
užrašas. CO2 pasiekus nustatytą lygį (P.05), pultelis sugrįš į ankstesnį režimą.
Norint patekti į serviso meniu reikia:
1. Perjungti į būseną „Išjungta“ ( jei pultelis įjungtas, 3 sekundes palaikyti B1 elementą).
2. 3 sekundes palaikyti B1 ir B2.
3. Įvesti apsaugos kodą „022“ su B4, B6 elementais ir patvirtinkite su B5 elementu.
Serviso meniu iš eilės rodomi meniu punktų (F.01, F.02 ir t.t) nustatymai. Meniu punktas pasirenkamas B4 ir B6
elementais. Paspaudus B5 parodoma pasirinkto parametro reikšmė, kurią keisti galima B4 ir B6 elementais.
Paspaudus B5 parametras išsaugomas ir grįžtama į nustatymų meniu.
Norint išeiti iš serviso meniu reikia 3 sekundes palaikyti B1 elementą (pultelis perjungiamas į išjungimo būseną).
Nr.
Pavadinimas Galimos reikšmės
Numatyta
reikšmė
F.01
Ventiliatorių valdymas
0: 0..100%
1: Fiksuotais greičiais
2: Pagal fi ksuotus slėgius
1
F.02
Išjungimo blokavimas
0: Neblokuojama
1: Ventiliatorius visada pučia minimaliai 1
greičiu
1
F.03
1 greitis (%) 0 – 100
20
F.04
2 greitis (%) 0 – 100
40
F.05
3 greitis (%) 0 – 100
70
F.06
4 greitis (boost) (%) 0 – 100
100
F.07
1 greitis (Pa) 0 – 999
5
F.08
2 greitis (Pa) 0 – 999
10
F.09
3 greitis (Pa) 0 – 999
25
F.10
4 greitis (boost) (Pa) 0 – 999
40
F.11
Slėgio PID – P 0 –999
5
F.12
Slėgio PID – I 0 – 999
10
F.13
Slėgio PID – D 0 – 999
0
F.14
Keitiklis
0: Nėra
1: Slėgio
2: CO2
0
F.15
Keitiklio MIN 0-250 x10
0
F.16
Keitiklio MAX 1-250 x10
20
F.17
Pultelio Modbus master/slave adresas 0: Master
1 - 247: Slave
0
F.18
Modbus duomenų perdavimo greitis
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
7: 115200
4
F.19
Modbus parity
0: None
1: Even
2: Odd
0
F.20
Valdomas įrenginys
(Pultelis automatiškai atpažįsta PRV ir ECO
plokštes)
0: None
1: Custom
2: ECO
3: PRV
0
Atkuriant gamyklinius parametrus reikia pakartotinai įvesti serviso slaptažodį „022“.
Dėl riboto segmentinio ekranėlio rodomų simbolių skaičiaus „CUSTOM“ įrenginio modbus adresai įvedami
HIGH ir LOW baitais šešioliktainėje sistemoje (HEX). B2 ir B3 mygtukų pagalba pasirenkame HIGH arba LOW
baitas, atitinkamai ekranėlyje rodoma „H.00“ ir „L.00“.
F.21
Valdomo įrenginio Modbus adresas 1 - 247
1
F.22
SET Temperature address 00:00 - FF:FF
00:00
F.23
SET Fan speed (%) address 00:00 - FF:FF
00:00
F.24
SET Fan speed fi xed address 00:00 - FF:FF
00:00
F.25
SET Pressure address 00:00 - FF:FF
00:00
F.26
SET CO2 address 00:00 - FF:FF
00:00
F.27
Temperature address 00:00 - FF:FF
00:00
F.28
Alarm 1 address 00:00 - FF:FF
00:00
F.29
Alarm 2 address 00:00 - FF:FF
00:00
F.30
Alarm 3 address 00:00 - FF:FF
00:00
F.31
Alarm 4 address 00:00 - FF:FF
00:00
F.32
Alarm 5 address 00:00 - FF:FF
00:00
F.33
Alarm 6 address 00:00 - FF:FF
00:00
F.34
Alarm 7 address 00:00 - FF:FF
00:00
F.35
Alarm 8 address 00:00 - FF:FF
00:00
F.36
Alarm 9 address 00:00 - FF:FF
00:00
F.37
Alarm 10 address 00:00 - FF:FF
00:00
F.38
Atkurti pultelio gamyklinius parametrus 0: Ne
1:Taip
0
Modbus Slave
ve(pagalbi
binio) adre
resų l lentelė
lė
Pavadinimas Galimos reikšmės
Tipas
Adresas
(HEX)
Adresas
(DEC)
Ventiliatorių valdymas
0: 0..100%
1: Fiksuotais greičiais
2: Pagal fi ksuotus slėgius
Holding
register
0x01
1
Išjungimo blokavimas
0: Neblokuojama
1: Ventiliatorius visada pučia
minimaliai 1 greičiu
Holding
register
0x02
2
1 greitis (%) 0 – 100
Holding
register
0x03
3
2 greitis (%) 0 – 100
Holding
register
0x04
4
3 greitis (%) 0 – 100
Holding
register
0x05
5
4 greitis (boost) (%) 0 – 100
Holding
register
0x06
6
1 greitis (Pa) 0 – 999
Holding
register
0x07
7
2 greitis (Pa) 0 – 999
Holding
register
0x08
8
3 greitis (Pa) 0 – 999
Holding
register
0x09
9
4 greitis (boost) (Pa) 0 – 999
Holding
register
0x0A
10
Slėgio PID – P 0 – 999
Holding
register
0x0B
11
Slėgio PID – I 0 – 999
Holding
register
0x0C
12
Slėgio PID – D 0 – 999
Holding
register
0x0D
13
Keitiklio MIN
0: Nėra
1: Slėgio
2: CO2
Holding
register
0x0E
14
Keitiklio MAX 0-250 x10
Holding
register
0x0F
15
Pultelio Modbus master/slave
adresas 1-250 x10
Holding
register
0x10
16
0: Master
1 - 247: Slave
Holding
register
0x11
17
Modbus duomenų perdavimo
greitis
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
7: 115200
Holding
register
0x12
18
Modbus parity
0: None
1: Even
2: Odd
Holding
register
0x13
19
Valdomas įrenginys
0: None
1: Custom
2: ECO
3: PRV
Holding
register
0x14
20
Valdomo įrenginio Modbus adresas 1 - 247
Holding
register
0x15
21
SET Temperature address 00:00 - FF:FF
Holding
register
0x16
22
SET Fan speed (%) address 00:00 - FF:FF
Holding
register
0x17
23
SET Fan speed fi xed address 00:00 - FF:FF
Holding
register
0x18
24
SET Pressure address 00:00 - FF:FF
Holding
register
0x19
25
SET CO2 address 00:00 - FF:FF
Holding
register
0x1A
26
Temperature address 00:00 - FF:FF
Holding
register
0x1B
27
Alarm 1 address 00:00 - FF:FF
Holding
register
0x1E
28
Alarm 2 address 00:00 - FF:FF
Holding
register
0x1F
29
Alarm 3 address 00:00 - FF:FF
Holding
register
0x20
30
Alarm 4 address 00:00 - FF:FF
Holding
register
0x21
31
Alarm 5 address 00:00 - FF:FF
Holding
register
0x22
32
Alarm 6 address 00:00 - FF:FF
Holding
register
0x23
33
Alarm 7 address 00:00 - FF:FF
Holding
register
0x24
34
Alarm 8 address 00:00 - FF:FF
Holding
register
0x25
35
Alarm 9 address 00:00 - FF:FF
Holding
register
0x26
36
Alarm 10 address 00:00 - FF:FF
Holding
register
0x27
37
Atkurti pultelio gamyklinius para-
metrus
0: Ne
1:Taip
Holding
register
0x28
38
Miego režimas
0 - Išjungtas
1 - 99 užmigimo laikas
sekundėmis
Holding
register
0x29
39
Garsas 0: Išjungtas
1: 1 –9 garso tembras
Holding
register
0x2A
40
Tiekiamos temperatūros rodymas
0: Nerodoma
1: Rodoma pakaitomis su
nustatyta
Holding
register
0x2B
41
CO2 reikalaujama (ppm) 0 – 99 x10ppm
Holding
register
0x2C
42
CO2 leistinas skirtumas 0 – 99 x10ppm
Holding
register
0x2D
43
SET Temperature 150 – 350 (/10)
Holding
register
0x2F
44
SET Fan speed (%) 0, 20 - 100
Holding
register
0x30
45
SET Fan speed fi xed 0 - 4
Holding
register
0x31
46
SET Pressure 0 – 999Pa
Holding
register
0x32
47
Display supply temperature -500 – 1000 (/10)
Holding
register
0x34
48
Išsaugoti nustatymus 0: Ne
22:Taip
Holding
register
0x36
49
Current fan speed (%) 0 – 100%
Input register
0x01
1
Current fi xed fan speed 0 – 4
Input register
0x02
2
Temperature Setpoint 150 – 350°C (/10)
Input register
0x03
3
Current Temperature -500– 1000 (/10)
Input register
0x04
4
Pressure Setpoint 0 – 999Pa
Input register
0x05
5
Current pressure 0 – 999Pa
Input register
0x06
6
CO2 Setpoint 0 – 999ppm
Input register
0x07
7
Current CO2 0 – 999ppm
Input register
0x08
8
Alarm 1 address 0/1
Coil
0x01
1
all-guides
com
Alarm 2 address 0/1
Coil
0x02
2
Alarm 3 address 0/1
Coil
0x03
3
Alarm 4 address 0/1
Coil
0x04
4
Alarm 5 address 0/1
Coil
0x05
5
Alarm 6 address 0/1
Coil
0x06
6
Alarm 7 address 0/1
Coil
0x07
7
Alarm 8 address 0/1
Coil
0x08
8
Alarm 9 address 0/1
Coil
0x09
9
Alarm 10 address 0/1
Coil
0x0A
10
Norint išsaugoti konfi gūravimo parametrus būtina į 49 registrą įrašyti 22, tuomet nustatymai įrašomi į
EEPROM atmintį, pultelis persikrauna.
Indikacija
Reikšmė (avarijos aprašymą žiūrėti įrenginio techniniame vadove)
A.01
Šilumokaičio priešužšaliminė apsauga
A.02
Suveikė išorinė apsauga
A.03
Grįžtamo vandens kritinė temperatūra
A.04
„P-mA“ įėjimo gedimas
A.05
Žema įtampa
A.06
Ištraukiamo oro jutiklio gedimas
A.07
Tiekiamo oro jutiklio gedimas
A.08
Grįžtamo vandens temperatūros jutiklio gedimas
A.09
Lauko temperatūros jutiklio gedimas
Av
Avarijos
ECO automatikos av
avarijos
Indikacija
Reikšmė (avarijos aprašymą žiūrėti įrenginio techniniame vadove)
A.01
Šilumokaičio priešužšaliminė apsauga
A.02
Priešgaisrinė apsauga
A.03
Užsiteršę fi ltrai
A.04
Ventiliatoriaus gedimas
A.05
Žema įtampa
A.06
DTJ(100) temperatūros jutiklio gedimas
A.07
Šalinamo oro jutiklio gedimas
A.08
Tiekiamo oro jutiklio gedimas
A.09
DTJ(100) drėgmės jutiklio gedimas
A.10
Grįžtamo vandens temperatūros jutiklio gedimas
A.11
Lauko temperatūros jutiklio gedimas
PRV automatikos av
avarijos
kos avarijos (papildyti po
po CUSTOM
TOM
modbus adresų nust
ustatymo)
Пульт управления Stouch создан специально для управления:
• Вентиляционными устройствами SALDA;
• Другими устройствами с платами управления PRV и ECO;
• Приборами, управляемыми с помощью протокола Modbus.
Пульты управления гарантируют оптимальные комфортные условия эксплуатации, мониторинга и
обслуживания, а также безопасность. Все операции выполняются на расстоянии с помощью пульта
дистанционного управления , на котором отображается информация о неисправностях и условия
обслуживания.
Особенности:
• Эксклюзивный и эргономичный дизайн;
• Простота использования;
• Предназначен для поверхностного монтажа;
• Сенсорное управление одним нажатием;
• Легкая чистка;
• Изображение цифр на дисплее;
• Звуковой ответ на прикосновение;
• Может быть подключен к сети BMS;
• Может быть непосредственно подключен к вентилятору с управляющим сигналом 0-10VDC;
• С помощью ввода 0-10VDC можно подключить сенсор CO2 или давления;
• Возможность установить 4 скорости;
• Максимальная скорость вентилятора в течение ограниченного времени (boost);
• Блокировка (замыкание) – защита от детей;
• Возможность изменения параметров звука, дежурного режима (StandBy), CO2 в меню пользователя.
В комплект входят:
Пульт управления Stouch, провод (13 м), крепежные элементы (6 шт.), техническое руководство.
Размеры
20,5
84
84
1,5
1. Используя представленный шаблон, ввинтите в выбранном месте самонарезающие винты, оставив
зазор около 1 мм от плоскости.
2. Подключите к пульту кабель
2.1- стандартное соединение
Монтаж
2.2 - специальное соединение (смотреть: «8-ми контактное соединение»)).
3. Подвесьте пульт, держа его повернутым влево под углом 25°.
4-5. Поверните пульт вправо, пока он не прижмется к плоскости. Удалите использованный шаблон.
1
4
1 2 3 4
PIN1 - +24V
PIN2 - B+
PIN3 - A-
PIN4 - COM
PIN1 - +24V
PIN2 - B+
PIN3 - A-
PIN4 - COM
8-ми контактно
ное соед
единен
ение
1. Источник питания 24V AC/DC, 100 мA
2. Источник питания 24V AC/DC
3. GND
4. RS485 B (Modbus)
5. RS485 A (Modbus)
6. GND
7. Вход 0-10VDC (используется для датчика давления или CO2) Питание датчика идет от отдельного
источника питания.
8. Выход 0-10VDC (используется для управления вентиляторами 0..10 VDC)
Электрическое подключение может выполнять лишь квалифицированный электрик в соответствии с
действующими международными и национальными требованиями электробезопасности и требованиями
к монтажу электроустановок.
Настройка скорости вентилятора
B3
Настройка температуры
B4
Увеличить
B5
Максимальная скорость вентилятора
в течение ограниченного времени
(boost)
B6
Уменьшить
S1
Сегментный дисплей
L4-L7 Индикации скорости вентилятора
Элементы
Команда Действие
Индикация
B1
L1
Включение Держать 2 секунды В1
Горит L1.
B1
L1
Выключение Держать 2 секунды В1
Гаснет L1.
L1
Пробуждение из
дежурного режима
Прикоснуться к любой
кнопке
В дежурном режиме медленно мигает
L1.
B2 B4 B6
L2
Настройка скорости
вентилятора Прикоснуться к В2
Горит L2. Скорость регулируется
прикосновением к элементам В4 и В6.
B3 B4 B6
L3
Настройка
температуры Прикоснуться к В3
Горит L3. Температура регулируется
прикосновением к элементам В4 и В6.
B4 B6
L4-L7
Изменение значения
выбранной настройки
Увеличение
прикосновением
к В4, уменьшение
прикосновением к В6
На сегментном дисплее меняются
цифры. L4, L5, L6, L7 показывают
выбранную скорость вентилятора.
Информация д
для пол
ользов
овател
еля
• В пульте создано меню пользователя для настройки параметров звука, температуры, дежурного
режима и уровня CO2.
• Кнопка быстрой активации максимальной скорости.
• Численное отображение установленной температуры и температуры приточного воздуха.
• LED индикация выбранной скорости.
• Отображение активных аварий в символах: A.01, A.02 и т.д., а также LED индикация.
• Дежурный режим пульта, экономящий электроэнергию.
• Возможна функция блокировки выключения вентиляционной системы.
• «Защита от детей» – блокирует пульт.
all-guides
com
Мигает „Con“ символ - соединяется
Сияющий „noC“ символ – пропала связь
Индикация св
связи
B4 B5 B6
L2
Включение/
выключение функции
интенсивной
вентиляции (boost)
Держать 2 секунды В5
Мигает L2. На сегментном дисплее
показано оставшееся время в секундах
(время свыше 600 сек. отображается
в минутах). Время регулируется
прикосновением к В4 и В6.
максимальное время BOOST работы:
180m. (3H)
B4 B6
L4-L7
Просмотр и отмена
аварий
Для отмены держать 3
секунды В2 и В3
При аварии мигают L4, L5, L6,
L7, на сегментном дисплее также
отображаются коды аварий (A.01,
A.02 и т.д.). Список аварий можно
просмотреть с помощью элементов
В4 и В6. После отмены аварии пульт
возвращается в исходное состояние.
L2-L7
Выполняется
продувание СО2
Мигают L2, L3 и L7, горят L4, L5, L6.
B2 B3 B5
Включение/
выключение «защиты
от детей»
Держать 2 секунды В3,
В2 и В5
Неактивные элементы В1, В4 и В6.
При нажатии неверной кнопки на
сегментном дисплее появится „---“.
Уп
Управление с
скорост
стью вен
енти
тилято
торо
ров
• По установленным 4 фиксированным скоростям
• По процентной скорости (0, 20-100%)
• Скорости в меню пользователя регулируются через каждые 5%
• Скорости в служебном меню регулируются через каждый 1%
• По установленным 4 фиксированным давлениям с помощью датчика давления
• Максимальная скорость ограничена таймером, параметры которого можно легко менять после
включения максимальной скорости вентилятора (boost)
• Максимальная скорость включается быстрой кнопкой. По истечении установленного времени действия
максимальной скорости вентилятора (boost) происходит автоматический возврат к предыдущей
скорости.
• Можно подключить датчик СО2 0..10 VDC CO2, который будет запускать максимальную скорость в
соответствии с заданными параметрами CO2.
Уп
Управление т тем
емпера
ратурой
• На пульте можно выставить нужную температуру от 15°C до 35°C
• Возможно попеременное отображение температуры приточного воздуха и установленной температуры
(5 секунд отображается установленная температура, 2 секунды отображается температура приточного
воздуха).
Дистанционно
ное упра
равлен
ение (Modb
dbus
us)
Пульт поддерживает полностью конфигурируемый интерфейс Modbus. Пульт может служить как
основным, так и вспомогательным устройством в сети modbus, кроме того, вы можете полностью
управлять им и конфигурировать его не только в служебном меню, но и с помощью интерфейса modbus.
Меню пользов
ователя
Для выхода в меню пользователя нужно 3 секунды держать нажатыми B2, B3.
В меню пользователя по порядку отображаются настройки пунктов меню (P.01, P.02 и т.д.). Пункт меню
можно выбрать с помощью элементов B4 и B6. При нажатии на B5 появляется значение выбранного
параметра, изменить его можно с помощью элементов B4 и B6. При нажатии на B5 происходит
сохранение параметра и возврат в меню.
В связи с ограниченными возможностями сегментного дисплея значения P.04 и P.05 отображаются в 10
раз меньше, т.е. если на дисплее изображено число 20, это значит, что истинное значение составляет 20
x 10 = 200.
С помощью данного пульта можно управлять другими устройствами (управляемыми протоколом
MODBUS). Это устанавливается в служебном меню с указанием необходимых параметров в пунктах
меню F.17, F.18, F.19, F.20, F.21. Для управления не только стандартными устройствами в пункте меню
F.20 нужно выставить «CUSTOM», а также адреса устройств в пунктах меню от № F.22 до F.37. Если у
устройств нет адресов, в окошках указанных пунктов меню необходимо ввести «00:00». В стандартной
версии данный пульт используется с платами управления ECO или PRV.
ПУЛЬТ
(master)
MODBUS
Вентиляционное
устройство
(slave)
1) Modbus master (основной)
Использование системы BMS (Building Management System – Система управления зданием) позволяет
с помощью одного пульта синхронно управлять несколькими устройствами или с помощью нескольких
пультов управлять одним устройством. С помощью протокола MODBUS можно менять параметры всех
пультов и наблюдать за показаниями подключенных датчиков.
ПУЛЬТ
(slave)
вентиляционное
устройство
(slave)
BMS
вентиляционное
устройство
(slave)
ПУЛЬТ
(slave)
MODBUS
RS485
2) Modbus slave (в
(вспомогательный)
№
Название Возможные значения
Предусмотренное
значение
P.01
Дежурный режим 0 – Выключен
1- 99 время засыпания в секундах
0
P.02
Звук 0: Выключен
1: 1–9 тембр звука
2
P.03
Отображение поступающей
температуры
0: Не отображается
1: Отображается попеременно с
установленной
0
P.04
Требуемый СО2 (ppm) 0 – 99 х 10 ppm
20 x10
P.05
Допустимая разница СО2 0 – 99 х 10 ppm
5 x 10
P.06
Таймер фильтров 0 – 999 дни
0
P.06 - Таймер фильтров сбрасывается в исходное состояние если поддержете 5 секунд нажав нажав
пункт В5. Таймер фильтров воcстонавливается и аyнулируя A.03 аварию.
Для выхода из меню нужно прикоснуться к элементу B1.
3) Управление вент
ентилятором, если скорос
рость уст
устанавли
вливае
вается
тся
тся с
с пом
пом
помощь
ощь
ощь
ощью
ю
пульта и/или компь
мпьютера через Modbus
С помощью данного пульта можно управлять как устройством, так и вентилятором 0..10VDC. Выберите
в служебном меню нужный способ управления скоростью (F.01), если вы выбрали управление по
установленным скоростям, укажите их в пунктах меню: F.03, F.04, F.05, F.06.
ПУЛЬТ
(slave)
ВЕНТИЛЯТОР
0...10 VDC
MODBUS
4) Поддержание дав
давления, которое устана
анавливае
вается
тся с пом
пом
помощь
ощью п
ю п
ю пуль
уль
ульта
та
та и/и
и/и
и/и
и/или
ли
ли
компьютера через M
з Modbus
При подключении вентилятора 0..10VDC и преобразователя давления 0..10VDC прямо к пульту можно
поддерживать нужное давление. Параметры управления и преобразователя давления можно менять с
помощью пульта. Использование пульта в качестве вспомогательного устройства („Modbus slave“) дает
возможность управлять всеми параметрами и наблюдать за показаниями датчика давления.
Для того, чтобы можно было управлять по давлению, в служебном меню нужно указать следующие
параметры:
• F.14 - 1
• F.15 и F.16 - по параметрам преобразователя давления
• F.11, F.12 ir F.13 - (PID коэффициенты управления). Если давление поддерживается неправильно, в
данные параметры можно внести исправления.
• F.07 - F.10 - указываем фиксированные скорости в Пa.
ПУЛЬТ
(slave)
ВЕНТИЛЯТОР
0...10 VDC
MODBUS
датчик
давления
0...10 VDC
Поддержание CO2
CO2
ПУЛЬТ
(master)
ВЕНТИЛЯТОР
(вместо вентиляцион-ного устройства)
0...10 VDC
MODBUS
датчик
СО2
0...10 VDC
вентиляционное
устройство
(slave)
С помощью данного пульта можно управлять уровнем углекислого газа (CO2) в помещении. Просто к
самому пульту нужно подключить датчик СО2 0..10VDC и сконфигурировать пульт. В служебном режиме
в пункте F.14 необходимо выставить 2, а F.15 и F.16 настроить в соответствии со спецификацией датчика.
После подключения датчика CO2 и установки указанных параметров в служебном меню необходимо
установить нужный уровень СО2 (P.05) и допустимую для превышения разницу с установленным
пределом (P.05) в меню пользователя. При превышении допустимой разницы пульт автоматически
запустит вентилятор на максимальной (4) скорости, на цифровом дисплее появится надпись «CO2».
Когда CO2 достигнет установленного уровня (P.05), пульт вернется в предыдущий режим.
Для выхода в служебное меню необходимо:
1. Перейти в состояние „Выключен“ (если пульт включен, подержите элемент B1 нажатым 3 секунды).
2. Подержать нажатыми B1 и B2 3 секунды.
3. Ввести защитный код „022“ с помощью элементов B4, B6 и подтвердить элементом B5.
В меню пользователя по порядку отображаются настройки пунктов меню (F.01, F.02 и т.д.). Пункт меню
можно выбрать с помощью элементов B4 и B6. При нажатии на B5 появляется значение выбранного
параметра, изменить его можно с помощью элементов B4 и B6. При нажатии на B5 происходит
сохранение параметра и возврат в меню настроек.
Для выхода из служебного меню нужно 3 секунды подержать нажатым элемент В1 (пульт переключается
в состояние выключения).
№
Название Возможные значения
Предусмотренное
значение
F.01
Управление вентиляторами
0: 0..100%
1: Фиксированными скоростями
2: По фиксированным давлениям
1
F.02
Блокировка выключения
0: Не блокируется
1: Вентилятор всегда работает как
минимум на 1 скорости
1
F.03
1 скорость (%) 0 – 100
20
F.04
2 скорость (%) 0 – 100
40
F.05
3 скорость (%) 0 – 100
70
F.06
4 скорость (boost) (%) 0 – 100
100
F.07
1 скорость (Па) 0 – 999
5
F.08
2 скорость (Па) 0 – 999
10
F.09
3 скорость (Па) 0 – 999
25
F.10
4 скорость (boost) (Па) 0 – 999
40
F.11
PID давления – P 0 –999
5
F.12
PID давления – I 0 – 999
10
F.13
PID давления – D 0 – 999
0
F.14
Преобразователь
0: Отсутствует
1: Давления
2: СО2
0
F.15
Преобразователь МИН. 0-250 x10
0
F.16
Преобразователь МАКС. 1-250 x10
20
F.17
Адрес пульта Modbus основной/
вспомогательный
0: Master
1 - 247: Slave
0
F.18
Скорость передачи данных
Modbus
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
7: 115200
4
F.19
Modbus parity
0: Отсутствует
1: Четный
2: Нечетный
0
Для восстановления заводских параметров нужно повторно ввести служебный пароль «022».
В связи с ограниченным числом отображаемых на сегментном дисплее символов адреса modbus
устройства «CUSTOM» вводятся с помощью старших и младших байтов в шестнадцатеричной системе
(HEX). Кнопками B2 и B3 выбираем старший или младший байт, на экране соответственно появляется
«H.00» и «L.00».
F.20
Управляемое устройство
(Пульт управления
автоматически раcпознает PRV
и ECO платы управления)
0: Отсутствует
1: На выбор
2: ECO
3: PRV
0
F.21
Адрес Modbus управляемого
устройства 1 - 247
1
F.22
Адрес настройки температуры 00:00 - FF:FF
00:00
F.23
Адрес настройки скорости
вентилятора (%) 00:00 - FF:FF
00:00
F.24
Фиксированный адрес настройки
скорости вентилятора 00:00 - FF:FF
00:00
F.25
Адрес настройки давления 00:00 - FF:FF
00:00
F.26
Адрес настройки CO2 00:00 - FF:FF
00:00
F.27
Адрес температуры 00:00 - FF:FF
00:00
F.28
Адрес сигнала опасности 1 00:00 - FF:FF
00:00
F.29
Адрес сигнала опасности 2 00:00 - FF:FF
00:00
F.30
Адрес сигнала опасности 3 00:00 - FF:FF
00:00
F.31
Адрес сигнала опасности 4 00:00 - FF:FF
00:00
F.32
Адрес сигнала опасности 5 00:00 - FF:FF
00:00
F.33
Адрес сигнала опасности 6 00:00 - FF:FF
00:00
F.34
Адрес сигнала опасности 7 00:00 - FF:FF
00:00
F.35
Адрес сигнала опасности 8 00:00 - FF:FF
00:00
F.36
Адрес сигнала опасности 9 00:00 - FF:FF
00:00
F.37
Адрес сигнала опасности 10 00:00 - FF:FF
00:00
F.38
Восстановить заводские
параметры пульта
0: Нет
1: Да
0
Та
Таблица адре
ресов Mo
Modbus
us Slave
ve (вс
вспо
помо
мога
гатель
льно
ного
го)
Название Возможные значения
Тип
Адрес
(HEX)
Адрес
(DEC)
Управление вентиляторами
0: 0..100%
1: Фиксированными скоростями
2: По фиксированным
давлениям
Регистр
удерживания
0x01
1
Блокировка выключения
0: Не блокируется
1: Вентилятор всегда работает
как минимум на 1 скорости
Регистр
удерживания
0x02
2
1 скорость (%) 0 – 100
Регистр
удерживания
0x03
3
2 скорость (%) 0 – 100
Регистр
удерживания
0x04
4
3 скорость (%) 0 – 100
Регистр
удерживания
0x05
5
all-guides
com
4 скорость (boost) (%) 0 – 100
Регистр
удерживания
0x06
6
1 скорость (Па) 0 – 999
Регистр
удерживания
0x07
7
2 скорость (Па) 0 – 999
Регистр
удерживания
0x08
8
3 скорость (Па) 0 – 999
Регистр
удерживания
0x09
9
4 скорость (boost) (Па) 0 – 999
Регистр
удерживания
0x0A
10
PID давления – P 0 – 999
Регистр
удерживания
0x0B
11
PID давления – I 0 – 999
Регистр
удерживания
0x0C
12
PID давления – D 0 – 999
Регистр
удерживания
0x0D
13
Преобразователь МИН.
0: Отсутствует
1: Давления
2: СО2
Регистр
удерживания
0x0E
14
Преобразователь МАКС. 0-250 x10
Регистр
удерживания
0x0F
15
Адрес пульта Modbus основного/
вспомогательного 1-250 x10
Регистр
удерживания
0x10
16
0: Основной
1 - 247: Вспомогательный
Регистр
удерживания
0x11
17
Скорость передачи данных
Modbus
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
7: 115200
Регистр
удерживания
0x12
18
Четность Modbus
0: Отсутствует
1: Четный
2: Нечетный
Регистр
удерживания
0x13
19
Управляемое устройство
0: Отсутствует
1: На выбор
2: ECO
3: PRV
Регистр
удерживания
0x14
20
Адрес Modbus управляемого
устройства 1 - 247
Регистр
удерживания
0x15
21
Адрес настройки температуры 00:00 - FF:FF
Регистр
удерживания
0x16
22
Адрес настройки скорости
вентилятора (%) 00:00 - FF:FF
Регистр
удерживания
0x17
23
Фиксированный адрес настройки
скорости вентилятора 00:00 - FF:FF
Регистр
удерживания
0x18
24
Адрес настройки давления 00:00 - FF:FF
Регистр
удерживания
0x19
25
Адрес настройки СО2 00:00 - FF:FF
Регистр
удерживания
0x1A
26
Адрес температуры 00:00 - FF:FF
Регистр
удерживания
0x1B
27
Адрес сигнала опасности 1 00:00 - FF:FF
Регистр
удерживания
0x1E
28
Адрес сигнала опасности 2 00:00 - FF:FF
Регистр
удерживания
0x1F
29
Адрес сигнала опасности 3 00:00 - FF:FF
Регистр
удерживания
0x20
30
Адрес сигнала опасности 4 00:00 - FF:FF
Регистр
удерживания
0x21
31
Адрес сигнала опасности 5 00:00 - FF:FF
Регистр
удерживания
0x22
32
Адрес сигнала опасности 6 00:00 - FF:FF
Регистр
удерживания
0x23
33
Адрес сигнала опасности 7 00:00 - FF:FF
Регистр
удерживания
0x24
34
Адрес сигнала опасности 8 00:00 - FF:FF
Регистр
удерживания
0x25
35
Адрес сигнала опасности 9 00:00 - FF:FF
Регистр
удерживания
0x26
36
Адрес сигнала опасности 10 00:00 - FF:FF
Регистр
удерживания
0x27
37
Восстановить заводские
параметры пульта
0: Да
1: Нет
Регистр
удерживания
0x28
38
Дежурный режим
0 – Выключен
1- 99 время засыпания в
секундах
Регистр
удерживания
0x29
39
Звук 0: Выключен
1: 1 – 9 тембр звука
Регистр
удерживания
0x2A
40
Отображение поступающей
температуры
0: Не отображается
1: Отображается попеременно с
установленной
Регистр
удерживания
0x2B
41
Требуемый СО2 (ppm) 0 – 99 x10ppm
Регистр
удерживания
0x2C
42
Допустимая разница СО2 0 – 99 x10ppm
Регистр
удерживания
0x2D
43
SET Temperature 150 – 350 (/10)
Регистр
удерживания
0x2F
44
SET Fan speed (%) 0, 20 - 100
Регистр
удерживания
0x30
45
SET Fan speed fi xed 0 - 4
Регистр
удерживания
0x31
46
SET Pressure 0 – 999Pa
Регистр
удерживания
0x32
47
Display supply temperature -500 – 1000 (/10)
Регистр
удерживания
0x34
48
Сохранить настройки 0: Нет
22: Да
Регистр
удерживания
0x36
49
Current fan speed (%) 0 – 100%
Регистр входа
0x01
1
Current fi xed fan speed 0 – 4
Регистр входа
0x02
2
Temperature Setpoint 150 – 350°C (/10)
Регистр входа
0x03
3
Current Temperature -500– 1000 (/10)
Регистр входа
0x04
4
Значение (описание аварии смотреть в техническом руководстве к
устройству)
A.01
Защита теплообменника от замерзания
A.02
Сработала внешняя защита
A.03
Критическая температура возвратной воды
A.04
Неисправность входа «P-mA»
A.05
Низкое напряжение
A.06
Неисправность датчика вытяжного воздуха
A.07
Неисправность датчика приточного воздуха
A.08
Неисправность датчика температуры возвратной воды
A.09
Неисправность датчика наружной температуры
Ав
Аварии
Аварии автоматики
ки ЕСО
Pressure Setpoint 0 – 999Pa
Регистр входа
0x05
5
Current pressure 0 – 999Pa
Регистр входа
0x06
6
CO2 Setpoint 0 – 999ppm
Регистр входа
0x07
7
Current CO2 0 – 999ppm
Регистр входа
0x08
8
Alarm 1 address 0/1
Coil
0x01
1
Alarm 2 address 0/1
Coil
0x02
2
Alarm 3 address 0/1
Coil
0x03
3
Alarm 4 address 0/1
Coil
0x04
4
Alarm 5 address 0/1
Coil
0x05
5
Alarm 6 address 0/1
Coil
0x06
6
Alarm 7 address 0/1
Coil
0x07
7
Alarm 8 address 0/1
Coil
0x08
8
Alarm 9 address 0/1
Coil
0x09
9
Alarm 10 address 0/1
Coil
0x0A
10
Индикация
Значение (описание аварии смотреть в техническом руководстве к
устройству)
A.01
Защита теплообменника от замерзания
A.02
Пожарная защита
A.03
Засорение фильтров
A.04
Неисправность вентилятора
A.05
Низкое напряжение
A.06
Неисправность датчика температуры DTJ(100)
A.07
Неисправность датчика удаляемого воздуха
Аварии автоматики
ки PRV
Для сохранения параметров конфигурации необходимо ввести 22 в регистре 49, таким образом
настройки вносятся в память EEPROM, происходит перезагрузка пульта.
ки CUSTOM (дополнить после опр
опреде
еделен
ления
ия
адресов modbus CUS
CUSTOM)
A.08
Неисправность датчика приточного воздуха
A.09
Неисправность датчика влажности DTJ(100)
A.10
Неисправность датчика температуры возвратной воды
A.11
Неисправность датчика наружной температуры
Stouch controller is specially designed for control of:
• SALDA ventilation equipment;
• Other equipment with PRV and ECO control boards;
• Devices which are controlled using Modbus protocol.
Controller ensures comfortable operation, monitoring, maintenance and safety. All operations are performed
remotely by using controller, which shows fault reports and maintenance conditions.
Features:
• Exceptional and ergonomic design
• Easy operation
• Surface mounted
• One touch control
• Easily controlled
• Numbers displayed at screen
• Acoustic response to touch
• Can be connected to BMS network
• Can be directly connected to fan controlled with 0-10VDC signal
• CO2 or pressure sensor can be connected by using 0-10VDC output
• 4 selectable speeds
• Maximum fan speed for limited time period (boost);
• Blocking (locking) - protection from children;
• In the user menu, parameters of sound, standby menu and CO2 can be changed
Package includes:
Stouch controller, wire (13m), fastening elements (6 pieces), technical manual.
Dimensions
20,5
84
84
1,5
all-guides
com
Using provided template, at the intended location screw the self-threading screws leaving gap of approximately
1 mm from the plane.
2. Connect the cable to the controller
2.1- standard connection
Installation
2.2 - spec connection (see “8 pin connection”).
3. Attach the controller by positioning it rotated to the left at the angle of 25°.
4-5. Turn the controller to the right until the controller contacts the plane. Remove the used template.
1
4
1 2 3 4
PIN1 - +24V
PIN2 - B+
PIN3 - A-
PIN4 - COM
PIN1 - +24V
PIN2 - B+
PIN3 - A-
PIN4 - COM
8
8 pin connectition
1. Power supply 24V AC/DC, 100mA
2. Power supply 24V AC/DC
3. GND
4. RS485 B (Modbus)
5. RS485 A (Modbus)
6. GND
7. 0-10VDC input (used for pressure or CO2 sensor). The sensor is powered from a separate power source.
8. 0-10VDC output (used for control of 0..10 VDC fans.
Only competent electrician is allowed to make electrical connections in accordance with the applicable interna-
tional and national electrical safety and electrical equipment installation requirements.
Description of elements
B1
On/Off
B2
Fan speed selection
B3
Temperature selection
B4
Increase
B5
Maximum fan speed for limited time
(boost)
B6
Decrease
S1
Segment display
L4-L7 Fan speed indications
Elements
Coomand Action
Indication
B1
L1
Switch on Press down for 2 seconds
B1
L1 lights on.
B1
L1
Switch off Press down for 2 seconds
B1
L1 lights off.
L1
Activation from sleep
mode Press any button.
L1 fl ashes slowly in sleep mode.
B2 B4 B6
L2
Set fan speed Touch B2.
L2 lights on. Speed is adjusted by touch-
ing elements B4 and B6
B3 B4 B6
L3
Set temperature Touch B3.
L3 lights on. Temperature is adjusted by
touching elements B4 and B6
B4 B6
L4-L7
Change value of se-
lected setting
Increase by touching B4,
decrease by touching B6
Numbers change in the segment display.
L4, L5, L6, L7 shows selected fan speed.
In
Information fo
for user
• Controller allows easy setting of sound, temperature, sleep mode and CO2 level parameters from the user
menu.
• Fast button for setting maximum speed.
• Numerical display of set and supply air temperature.
• Selected speed LED indication.
• Symbolical display of active alarms: A.01, A.02, etc., and LED indication.
• Controller sleep mode to reduce power consumption.
• Selectable ventilation system switch off locking feature.
• “Child safety feature” - locks the controller.
Flashing „Con“ – connecting.
Shining „noC“ – connection lost.
Connection ind
ndication
B4 B5 B6
L2
Switch on/off the inten-
sive ventilation (boost) 2 sekundes palaikyti B5.
L2 fl ashes. Remaining time in seconds is
shown in the segment display (for values
above 600s, time is shown in minutes).
Time is adjusted by touching B4 and B6.
Maximum BOOST running time: 180m.
(3h)
B4 B6
L4-L7
Review and cancel
alarms
For canceling, press down
B2 and B3 for 3 seconds.
In case of alarms, L4, L5, L6, L7 fl ash
and alarm code is shown in the segment
display (A.01, A.02 etc.). You can review
alarm list by using elements B4 and B6.
After alarm is canceled, controller returns
to initial state.
L2-L7
CO2 blow off
L2, L3 and L7 fl ash, L4, L5, L6 light on.
B2 B3 B5
On/off
“Child safety feature”
Press down B3, B2 and
B5 for 2 seconds.
Non active elements B1, B4 and B6. After
pressing unavailable button, segment
display shows “−−−”
Fan speed cont
ntrol
• Selecting 4 preset speeds
• Selecting percentage value of speed (0, 20-100%)
• User menu speeds are set in intervals of 5%
• Service menu speeds are set in intervals of 1%
• Selecting 4 preset pressure values by using pressure sensor
• Maximum speed is limited by timer which can be easily set when maximum fan speed is activated (boost)
• Maximum speed can be activated using fast button. When preset maximum fan speed (boost) time is over,
previous speed is automatically restored.
• 0..10 VDC CO2 sensor can be connected for activation of maximum speed based on the given CO2 param-
eters
Temperature co
control
• In controller, desired temperature can be set between 15 and 35°C
• Supply air and set temperatures can be displayed interchangeably (set temperature is displayed for 5 sec-
onds, then supply air temperature is displayed for 2 seconds)
Remote control
ol (Modb
dbus)
Controller supports fully confi gurable Modbus interface. Panel can operate as master and slave device in
modbus network and also it can be fully controlled and confi gured not only via service menu but also via mod-
bus interface.
User menu
In order to reach user menu, press down B2 and B3 for 3 seconds.
In user menu, menu items (P.01, P.02 etc.) settings are displayed sequentially. Menu item is selected using
elements B4 and B6. After pressing B5, value of selected parameter is shown and can be changed using ele-
ments B4 and B6. Press B5 to save the parameter and to return to menu.
Due to limitations of segment display, values of P.04 and P.05 are shown divided by 10, i.e. if 20 is displayed, it
means that real value is 20 x 10 = 200.
P.06 - To reset fi lter timer to press and hold for 5 seconds item B5. Also fi lter timer resets by removing A.03
alarm.
Touch element B1 to exit menu.
This controller can control other devices (controlled by MODBUS protocol). This can be set in service menu by
selecting required parameters for service menu items F.17, F.18, F.19, F.20, F.21. To control not only standard
devices, select “CUSTOM” in menu item F.20 and device addresses in menu items from F.22 up to F.37. If
devices have no such addresses, in fi elds of given menu items enter “00:00”. Normally, this controller is used
with ECO or PRV control boards.
CONTROLLER
(master)
MODBUS
AHU
(slave)
1) 1) Modbus maste
ster (main)
Using BMS (Building Management System), several devices can be controlled simultaneously or one device
can be controlled using several controllers. MODBUS protocol allows changing all parameters of controllers and
monitoring data of connected sensors.
CONTROLLER
(slave)
AHU
(slave)
BMS
AHU
(slave)
CONTROLLER
(slave)
MODBUS
RS485
2) Modbus slave
No.
Name Possible values
Default
value
P.01
Sleep mode 0 - Off
1 - 99 sleeping time in seconds
0
P.02
Sound 0: Off
1: 1 –9 sound tone
2
P.03
Supply air temperature display 0: Not shown
1: Shown interchangeably with the set temp
0
P.04
CO2 required (ppm) 0 – 99 x10ppm
20 x10
P.05
CO2 allowed difference 0 – 99 x10ppm
5 x 10
P.06
Filtrer timer 0 – 999 days
0
3) Fan control when s
n speed is set using con
controller a
r and/or
or
computer via Modb
odbus
This controller allows controlling both device and 0..10VDC fan. In service menu, select desired speed control
method (F.01). If control based on preset speeds is selected, then select them in menu items F.03, F.04, F.05,
F.06.
CONTROLLER
(slave)
FAN
0...10 VDC
MODBUS
4) Pressure contro
trol when selected using co
controller
er and/or
/or
computer via Modbu
dbus
Desired pressure can be maintained by connecting 0..10VDC fan and 0..10VDC pressure converter directly to
the controller. Control and pressure sensor parameters can be changed in controller. When controller is used as
Modbus slave device, it allows controlling all parameters and monitoring of pressure sensor readings.
For pressure based control, select the following parameters in the service menu:
• F.14 - 1
• F.15 and F.16 -based on pressure converter parameters
• F.11, F.12 and F.13 - (PID control ratios). If pressure is maintained incorrectly, these parameters can be
adjusted.
F.07 - F.10 - nurodome fi ksuotus greičius Pa.
CONTROLLER
(slave)
FAN
0...10 VDC
MODBUS
pressure
sensor
0...10 VDC
5) CO2 control
CONTROLLER
(master)
FAN
(instead of AHU)
0...10 VDC
MODBUS
CO2
sensor
0...10 VDC
AHU
(slave)
This controller allows controlling level of carbon dioxide (CO2) in a room. Connect 0..10VDC CO2 sensor di-
rectly to the controller and confi gure the controller. In service mode, in item F.14 set 2, and F.15 and F.16 should
be set based on the sensor specifi cation.
After CO2 sensor is connected and required parameters are set in the service menu, select desired CO2
level (P.05) and allowed difference from the set (P.05) limit in the user menu. If allowed difference is exceeded,
controller will automatically start fans at maximum (4) speed and “CO2” will be shown in digital display. After set
CO2 level (P.05) is reached, controller will return to previous mode.
all-guides
com
To enter service menu:
1. Go to “Off” state (if controller is on, press down element B1 for 3 seconds).
2. Press down B1 and B2 for 3 seconds.
3. Using elements B4 and B6, enter security code “022” and confi rm with element B5.
In the service menu, settings of menu items (F.01, F.02 etc.) are shown sequentially. Menu item is selected
using elements B4 and B6. After pressing B5, value of selected parameter is shown and can be changed using
elements B4 and B6. Pressing B5 saves the parameters and returns to the setting menu.
To exit the service menu, press down element B1 for 3 seconds (controller goes to switch off state).
No.
Name Possible values
Default
value
F.01
Fan control
0: 0..100%
1: Fixed speeds
2: Based on fi xed pressures
1
F.02
Switch of locking 0: Not locked
1: Fan always operates at minimum speed 1
1
F.03
Speed 1 (%) 0 – 100
20
F.04
Speed 2 (%) 0 – 100
40
F.05
Speed 3 (%) 0 – 100
70
F.06
Speed 4 (boost) (%) 0 – 100
100
F.07
Speed 1 (Pa) 0 – 999
5
F.08
Speed 2 (Pa) 0 – 999
10
F.09
Speed 3 (Pa) 0 – 999
25
F.10
Speed 4 (boost) (Pa) 0 – 999
40
F.11
Pressure PID – P 0 –999
5
F.12
Pressure PID – I 0 – 999
10
F.13
Pressure PID – D 0 – 999
0
F.14
Converter
0: No
1: Pressure
2: CO2
0
F.15
Converter MIN 0-250 x10
0
F.16
Converter MAX 1-250 x10
20
F.17
Controller Modbus master/slave address 0: Master
1 - 247: Slave
0
F.18
Modbus data transfer rate
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
7: 115200
4
F.19
Modbus parity
0: None
1: Even
2: Odd
0
F.20
Controlled device
(Remote controller will automatically recog-
nize the PRV and ECO plates))
0: None
1: Custom
2: ECO
3: PRV
0
Name Possible values
Type
Address
(HEX)
Address
(DEC)
Fan control
0: 0..100%
1: Fixed speeds
2: Based on fi xed pressures
Holding
register
0x01
1
Switch of locking
0: Not locked
1: Fan always operates at mini-
mum speed 1
Holding
register
0x02
2
Speed 1 (%) 0 – 100
Holding
register
0x03
3
Speed 2 (%) 0 – 100
Holding
register
0x04
4
Speed 3 (%) 0 – 100
Holding
register
0x05
5
Speed 4 (boost) (%) 0 – 100
Holding
register
0x06
6
Speed 1 (Pa) 0 – 999
Holding
register
0x07
7
Speed 2 (Pa) 0 – 999
Holding
register
0x08
8
Speed 3 (Pa) 0 – 999
Holding
register
0x09
9
F.21
Modbus address of controlled device 1 - 247
1
F.22
SET Temperature address 00:00 - FF:FF
00:00
F.23
SET Fan speed (%) address 00:00 - FF:FF
00:00
F.24
SET Fan speed fixed address 00:00 - FF:FF
00:00
F.25
SET Pressure address 00:00 - FF:FF
00:00
F.26
SET CO2 address 00:00 - FF:FF
00:00
F.27
Temperature address 00:00 - FF:FF
00:00
F.28
Alarm 1 address 00:00 - FF:FF
00:00
F.29
Alarm 2 address 00:00 - FF:FF
00:00
F.30
Alarm 3 address 00:00 - FF:FF
00:00
F.31
Alarm 4 address 00:00 - FF:FF
00:00
F.32
Alarm 5 address 00:00 - FF:FF
00:00
F.33
Alarm 6 address 00:00 - FF:FF
00:00
F.34
Alarm 7 address 00:00 - FF:FF
00:00
F.35
Alarm 8 address 00:00 - FF:FF
00:00
F.36
Alarm 9 address 00:00 - FF:FF
00:00
F.37
Alarm 10 address 00:00 - FF:FF
00:00
F.38
Restore controller factory settings 0: No
1:Yes
0
Modbus Slave
ve a
address
ss table
le
To restore factory settings, service password “022” should be reentered.
Due to limited number of symbols in segment display, modbus addresses of “CUSTOM” device are entered
as HIGH and LOW bytes in hexadecimal (HEX) system. Using buttons B2 and B3, select HIGH or LOW bytes,
“H.00” and “L.00” are displayed respectively.
Speed 4 (boost) (Pa 0 – 999
Holding
register
0x0A
10
Pressure PID – P 0 – 999
Holding
register
0x0B
11
Pressure PID – I 0 – 999
Holding
register
0x0C
12
Pressure PID – D 0 – 999
Holding
register
0x0D
13
Converter MIN
0: No
1: Pressure
2: CO2
Holding
register
0x0E
14
Converter MAX 0-250 x10
Holding
register
0x0F
15
Controller Modbus master/slave
address 1-250 x10
Holding
register
0x10
16
0: Master
1 - 247: Slave
Holding
register
0x11
17
Modbus data transfer rate
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
7: 115200
Holding
register
0x12
18
Modbus parity
0: None
1: Even
2: Odd
Holding
register
0x13
19
Controlled device
0: None
1: Custom
2: ECO
3: PRV
Holding
register
0x14
20
Modbus address of controlled
device 1 - 247
Holding
register
0x15
21
SET Temperature address 00:00 - FF:FF
Holding
register
0x16
22
SET Fan speed (%) address 00:00 - FF:FF
Holding
register
0x17
23
SET Fan speed fi xed address 00:00 - FF:FF
Holding
register
0x18
24
SET Pressure address 00:00 - FF:FF
Holding
register
0x19
25
SET CO2 address 00:00 - FF:FF
Holding
register
0x1A
26
Temperature address 00:00 - FF:FF
Holding
register
0x1B
27
Alarm 1 address 00:00 - FF:FF
Holding
register
0x1E
28
Alarm 2 address 00:00 - FF:FF
Holding
register
0x1F
29
Alarm 3 address 00:00 - FF:FF
Holding
register
0x20
30
Alarm 4 address 00:00 - FF:FF
Holding
register
0x21
31
Alarm 5 address 00:00 - FF:FF
Holding
register
0x22
32
Alarm 6 address 00:00 - FF:FF
Holding
register
0x23
33
Alarm 7 address 00:00 - FF:FF
Holding
register
0x24
34
Alarm 8 address 00:00 - FF:FF
Holding
register
0x25
35
Alarm 9 address 00:00 - FF:FF
Holding
register
0x26
36
Alarm 10 address 00:00 - FF:FF
Holding
register
0x27
37
Restore controller factory
parameters
0: No
1:Yes
Holding
register
0x28
38
Sleep mode 0 - Off
1 - 99 sleeping time in seconds
Holding
register
0x29
39
Sound 0: Off
1: 1 –9 sound tone
Holding
register
0x2A
40
Supply temperature display
0: Not shown
1: Shown interchangeably with
the set temperature
Holding
register
0x2B
41
CO2 required (ppm) 0 – 99 x10ppm
Holding
register
0x2C
42
CO2 allowed difference 0 – 99 x10ppm
Holding
register
0x2D
43
SET Temperature 150 – 350 (/10)
Holding
register
0x2F
44
SET Fan speed (%) 0, 20 - 100
Holding
register
0x30
45
SET Fan speed fi xed 0 - 4
Holding
register
0x31
46
SET Pressure 0 – 999Pa
Holding
register
0x32
47
Display supply temperature -500 – 1000 (/10)
Holding
register
0x34
48
Save parameters 0: No
22: Yes
Holding
register
0x36
49
Current fan speed (%) 0 – 100%
Input register
0x01
1
Current fi xed fan speed 0 – 4
Input register
0x02
2
Temperature Setpoint 150 – 350°C (/10)
Input register
0x03
3
Current Temperature -500– 1000 (/10)
Input register
0x04
4
Pressure Setpoint 0 – 999Pa
Input register
0x05
5
Current pressure 0 – 999Pa
Input register
0x06
6
CO2 Setpoint 0 – 999ppm
Input register
0x07
7
Current CO2 0 – 999ppm
Input register
0x08
8
Alarm 1 address 0/1
Coil
0x01
1
Alarm 2 address 0/1
Coil
0x02
2
Alarm 3 address 0/1
Coil
0x03
3
Alarm 4 address 0/1
Coil
0x04
4
Alarm 5 address 0/1
Coil
0x05
5
Alarm 6 address 0/1
Coil
0x06
6
Alarm 7 address 0/1
Coil
0x07
7
Alarm 8 address 0/1
Coil
0x08
8
Alarm 9 address 0/1
Coil
0x09
9
Alarm 10 address 0/1
Coil
0x0A
10
To save confi guration parameters, write 22 to the register 49, then settings are saved to EEPROM
memory, controller reloads.
Indication
Meaning (see device technical manual for alarm description)
A.01
Heat exchanger antifreeze protection
A.02
External protection activated
A.03
Return water critical temperature
A.04
“P-mA” output fault
A.05
Low voltage
A.06
Extracted air sensor fault
A.07
Supply air sensor fault
A.08
Return water temperature sensor fault
A.09
Ambient air temperature sensor fault
Al
Alarms
ECO automation ala
alarms
Indication
Meaning (see device technical manual for alarm description)
A.01
Heat exchanger antifreeze protection
A.02
Fire protection
A.03
Clogged fi lters
A.04
Fan fault
A.05
Low voltage
A.06
DTJ(100) temperature sensor alarm fault
A.07
Exhaust air sensor fault
A.08
Supply air sensor fault
A.09
DTJ(100) humidity sensor fault
A.10
Return water temperature sensor fault
A.11
Ambient air temperature sensor fault
PRV automation ala
alarms
all-guides
com
on alarms (add after settin
ting of C
f CUSTOM
OM mod
modbus
bus
bus ad
ad
addre
dre
dresse
sse
sse
sses)
s)
Das Pult „Stouch“ ist speziell für Bedienung von:
• SALDA-Lüftungsanlagen,
• anderen Anlagen mit PRV- UND ECO-Bedienplatten,
• Geräten, die durch „Modbus“-Protokoll bedient werden,
konzipiert.
Bedienpulte gewährleisten einen optimalen Betriebs-, Überwachungs- und Wartungskomfort und Sicherheit. Alle
Handlungen werden mit einem Fernbedienungspult ausgeführt, in dem Störungsberichte und Bedingungen für
Bedienung gezeigt werden.
Eigenschaften
• Außergewöhnliches und ergonomisches Design
• Einfacher Gebrauch
• Für Überputzmontage bestimmt
• Sensorische Bedienung durch einen Druck
• Leichte Reinigung
• Zahlenabbildung auf dem Bildschirm
• Akustische Antwort auf die Berührung
• Kann an BMS-Netz angeschlossen werden
• Kann direkt an Ventilator, der durch 0-10VDC-Signal bedient wird, angeschlossen werden
• Kann durch einen 0-10VDC-Eingang an CO2- oder Druckfühler angeschlossen werden
• 4 einstellbare Geschwindigkeiten
• Maximale Geschwindigkeit des Ventilators für einen begrenzten Zeitraum (boost)
• Blockierung (Absperrung) als Absicherung gegen Kinder
• Im Benutzermenü können Parameter für Ton, Bereitschaftsmodus (StandBy) bzw. CO2 geändert werden
Die Packung besteht aus:
dem Bedienungspult „Stouch“, dem Leitungsdraht (13m), den Befestigungselementen (6 Stk.), dem technischen
Handbuch
Ab
Abmessungen
20,5
84
84
1,5
1. Laut dem vorgelegten Muster die Selbstschneideschrauben auf einem ausgewählten Platz mit einem 1 mm-
Abstand von der Oberfl äche einschrauben.
2. Einen Kabel an das Pult anschließen
2.1 Standardanschluss
Montage
2.2: spezieller Anschluss, s. 8-Kontakten-Anschluss.
3. Das Pult, der um 25° nach links gedreht ist, anhängen.
4-5. Das Pult nach rechts drehen, bis er sich an die Oberfl äche drückt. Das gebrauchte Muster entfernen.
1
4
1 2 3 4
PIN1 - +24V
PIN2 - B+
PIN3 - A-
PIN4 - COM
PIN1 - +24V
PIN2 - B+
PIN3 - A-
PIN4 - COM
8-
8-Kontakten-An
Anschlus
uss
1. 1. Stromversorgung: 24V AC/DC, 100mA
2. 2. Stromversorgung 24V AC/DC
3. 3. GND
4. 4. RS485 B (Modbus)
5. 5. RS485 A (Modbus)
6. 6. GND
7. 0-10VDC-Eingang (für Druck- oder CO2-Fühler). Die Speisung des Fühlers erfolgt durch separate Stromver-
sorgung
8. 0-10VDC-Ausgang (für Bedienung von 0..10VDC-Ventilatoren).
Elektrischer Anschluss kann nur durch qualifi zierte Elektrofachkraft laut geltenden internationalen und lokalen
Elektroschutzbestimmungen sowie Bestimmungen für Anschluss elektrischer Anlagen ausgeführt werden.
Bedeutungen der Elemente
B1
Ein-/Ausschalten
B2
Geschwindigkeitseinstellung vom
Ventilator
B3
Temperatureinstellung
B4
Vergrößern
B5
Maximale Geschwindigkeit des Ventila-
tors für einen begrenzten Zeitraum
(boost)
B6
Verringern
S1
Segmentbildschirm
L4-L7 Anzeigen der Geschwindigkeiten vom
Ventilator
Information an
an Benutze
zer
• Auf dem Pult einfaches Menü für Ton-, Temperatur-, Ruhezustand- und CO2-Niveau-Einstellung konzipiert
• Schnelltaste für Aktivierung der Höchstgeschwindigkeit
• Anzeige der eingestellten sowie Zulufttemperatur in Zahlen
• LED-Anzeige der ausgewählten Geschwindigkeit
• Anzeige der aktiven Störungen in Symbolen: A.01, A.02 usw, sowie LED-Anzeige
• Ruhezustand des Pults für das Energiesparen
• Ist eine Blockierung der Ausschaltung vom Lüftungssystem möglich
• Absicherung gegen Kinder: verriegelt den Pult
Elemente
Befehl Handlung
Anzeige
B1
L1
Einschalten B1 drücken und für 2
Sekunden halten
L1 leuchtet
B1
L1
Ausschalten B1 drücken und für 2
Sekunden halten
L1 erlischt
L1
Aktivieren aus dem
Ruhezustand Beliebige Taste berühren
L1 blinkt langsam im Ruhezustand
B2 B4 B6
L2
Geschwindigkeit der
Ventilatoren einstellen B2 berühren
L2 leuchtet; die Geschwindigkeit wird
durch Berühren von B4- und B6-Elemente
geregelt
B3 B4 B6
L3
Temperatur einstellen B3 berühren
L3 leuchtet; die Temperatur wird durch
Berühren von B4- und B6-Elemente
geregelt
B4 B6
L4-L7
Gewählte Einstellungs-
bedeutung ändern
Vergrößerung: B4
berühren, Verringerung:
B6 berühren
Im Segmentbildschirm ändern sich
die Zahlen; L4, L5, L6, L7 zeigen die
gewählte Geschwindigkeit der Ventila-
toren
B4 B5 B6
L2
Ein-/Ausschalten der
Funktion für intensive
Lüftung (boost)
B5 drücken und für 2
Sekunden halten
L2 blinkt; im Segmentbildschirm wird die
Restzeit in Sekunden gezeigt (die Zeit von
mehr als 600s wird in Minuten gezeigt);
die Zeit wird durch Berühren von B4 und
B6 geregelt. Maximal BOOST Laufzeit :
180 min. (3h)
Anzeige „Con“ blinkt - verbinden
Anzeige „noC“ leuchtet - keine Verbindung
Ve
Verbindungsanz
nzeige
Ge
Geschwindigk
gkeitssteu
euerun
ung de
der Ve
Ventililator
oren
en
• Laut fi xierten 4 Geschwindigkeitswerten
• Laut prozentueller Geschwindigkeit (0, 20-100%)
• Geschwindigkeiten des Benutzermenüs werden je 5% gesteuert
• Geschwindigkeiten des Servicemenüs werden je 1% gesteuert
• Laut eingestellten fi xierten 4 Druckwerten unter Benutzung eines Druckfühlers
• Maximale Geschwindigkeit wird durch Zeitmesser geschützt, der durch Aktivierung maximaler Geschwindig-
keit des Ventilators (boost) leicht geändert werden kann
• Maximale Geschwindigkeit wird mit der Schnelltaste aktiviert. Nach Ende der eingestellten Zeit für maximale
Geschwindigkeit des Ventilators (boost) kehrt man automatisch in frühere Geschwindigkeit
• Kann 0..10VDC-Fühler für CO2 angeschlossen werden, der eine maximale Geschwindigkeit laut angege-
benen CO2-Parametern aktivieren würde
Te
Temperatursteu
euerung
• Im Pult kann gewünschte Temperatur von 15 bis 35°C angegeben werden
• Mögliche abwechselnde Anzeige der Zuluft- sowie eingestellten Temperatur (für 5 Sekunden wird eingestellte
Temperatur und für 2 Sekunden Zulufttemperatur gezeigt)
Fernbedienung
g (Modbu
bus)
Das Pult unterstützt eine völlig konfi gurierbare Modbus-Schnittstelle. Das Pult kann als Haupt- und Hilfsgerät
im Modbus-Netz funktionieren, es kann nicht nur durch Servicemenü, sondern auch durch Modbus-Schnittstelle
völlig bedient und konfi guriert werden.
Benutzermenü
nü
Fürs Öffnen des Benutzermenüs müssen B2 bzw. B3 berührt und für 3 Sekunden gehalten werden.
Im Benutzermenü werden Einstellungen von Menüpunkten nacheinander (P.01, P.02 usw.) gezeigt.
Menüpunkt wird durch B4- und B6-Elemente gewählt. Nach Drücken von B5 wird die Bedeutung vom aus-
gewählten Menü gezeigt, die durch B4- und B6-Elemente geändert werden kann. Nach Drücken von B5 wird
der Parameter gespeichert und man kehrt ins Menü zurück.
Wegen begrenzter Möglichkeiten des Segmentbildschirms werden die Werte 10 Mal kleiner gezeigt, d. h.
wenn auf dem Bildschirm die Zahl 20 gezeigt wird, bedeutet das, dass echter Wert 20 x 10 = 200 ist.
P.06 - Filtertimer-Rücksetzen: Taste B5 5 Sekunden drücken. Filtertimer-Rücksetzung erfolgt auch beim
Beheben vom Alarm A.03.
Zum Verlassen des Menüs B1-Element berühren.
B4 B6
L4-L7
Übersicht und Annul-
lierung der Störungen
Für Annullierung B2 und
B3 drücken und für 3
Sekunden halten
Im Falle einer Störung blinkt L4, L5, L6,
L7 und im Segmentbildschirm werden die
Kennzahlen der Störungen gezeigt (A.01,
A.02 usw.); Übersicht der Störungsliste
kann mit Hilfe von B4- und B6-Elementen
ausgeführt werden; nach Annullierung der
Störung kehrt der Pult in den Anfangs-
zustand
L2-L7
Läuft CO2-Spülung
L2, L3 und L7 blinken, L4, L5, L6 leuchten
B2 B3 B5
Absicherung gegen
Kinder wird ein-/ ausge-
schaltet
B3, B2 und B5 drücken
und für 2 Sekunden halten
Inaktive Elemente B1, B4 und B6; nach
Drücken einer nicht zugelassenen Taste
zeigt der Segmentbildschirm „---“
all-guides
com
Mit diesem Pult können andere Geräte (die durch MODBUS-Protokoll bedient werden) gesteuert werden. Das
wird im Servicemenü durch Angabe von nötigen Parametern in Punkten F.17, F.18, F.19, F.20, F.21 des Serv-
icemenüs eingestellt werden. Falls man nicht nur Standardgeräte bedienen will, muss man im Menüpunkt F.20
CUSTOM sowie Geräteadressen in Menüpunkten von F.22 bis F.37 angeben. Wenn die Geräte diese Adressen
nicht besitzen, muss in angegebenen Punktfeldern 00:00 eingegeben werden. Üblicherweise wird dieses Pult
mit ECO- oder PRV-Bedienplatten benutzt.
PULT
(master)
MODBUS
AHU
(slave)
1) Modbus slave (u
(untergeordnet)
Unter Benutzung des BMS-Systems (Building Management System) können mehrere Geräte mit einem Pult
synchron oder ein Gerät kann mit mehreren Pulten bedient werden. Unter Benutzung des MODBUS-Protokolls
können alle Pultparameter geändert und die Angaben von angeschlossenen Fühlern überwacht werden.
PULT
(slave)
AHU
(slave)
BMS
AHU
(slave)
PULT
(slave)
MODBUS
RS485
2) Modbus slave (u
(untergeordnet)
Nr.
Bezeichnung Mögliche Bedeutungen
Vorgesehene
Bedeutung
P.01
Ruhezustand 0: ausgeschaltet
1-99: Einschlafzeit in Sekunden
0
P.02
Ton 0: ausgeschaltet
1: 1-9 Tonfarbe
2
P.03
Anzeige der gelieferten Temperatur
0: nicht angezeigt
1: wird abwechselnd mit eingestell-
ter Temperatur gezeigt
0
P.04
CO2 gefordert (ppm) 0 – 99 x10ppm
20 x10
P.05
Zugelassener Unterschied von CO2 0 – 99 x10ppm
5 x 10
P.06
Filtertimer 0 – 999 dienos
0
3) Bedienung des V
s Ventilators, wenn die Ges
Geschwind
indigkeit
eit
mit dem Pult und/o
d/oder Computer durch Mo
Modbus eing
ingest
estellt w
t wird
ird
Mit diesem Pult kann sowohl das Gerät als auch der 0..10VDC-Ventilator bedient werden. Im Servicemenü
gewünschte Bedienart der Geschwindigkeit (F.01) wählen; falls die Bedienung laut eingestellten Geschwindig-
keitswerten gewählt ist, diese angeben: Menüpunkte F.03, F.04, F.05, F.06.
PULT
(slave)
VENTILATOR
0...10 VDC
MODBUS
4) Druckbehalten, das
das mit dem Pult und/ode
oder Comp
omputer r
durch Modbus angeg
gegeben wird
Nach direktem Anschluss des 0..10VDC-Ventilators oder des 0..10VDC-Druckwechslers am Pult kann gewün-
schter Druck behalten werden. Parameter der Bedienung und der Druckfühlers können mit dem Pult geändert
werden. Falls das Pult als Hilfsgerät („Modbus slave“) benutzt wird, ist es möglich, alle Parameter zu bedienen
und Anzeigen des Druckfühlers zu überwachen. Damit die Bedienung laut dem Druck möglich wäre, müssen im
Servicemenü folgende Parameter angegeben werden:
• F.14 - 1
• F.15 und F.16 - laut Parametern des Druckwechslers
• F.11, F.12 und F.13 - (PID-Bedienkoeffi zienten). Wenn der Druck unkorrekt behalten wird, können diese
Parameter korrigiert werden.
• F.07 bis F.10 - werden fi xierte Geschwindigkeiten Pa angegeben.
PULT
(slave)
VENTILATOR
0...10 VDC
MODBUS
Druckfühler
0...10 VDC
5) Beibehaltung vo
von CO2
PULT
(master)
VENTILATOR
(anstelle von AHU)
0...10 VDC
MODBUS
CO2
Fühler
0...10 VDC
AHU
(slave)
Mit Hilfe dieses Pults kann Niveau des Kohlendioxids (CO2) im Raum gesteuert werden. Am selben Pult
muss der 0..10VDC-Fühler für CO2 angeschlossen und das Pult konfi guriert werden. Im Punkt F.14 des Serv-
icebetriebs muss die Zahl 2 eingestellt werden, und in F.15 und F.16 wird sie laut Beschreibung des Fühlers
angegeben.
Nach Anschluss des CO2-Fühlers und der Einstellung von angegebenen Parametern soll im Benutzermenü
das gewünschte CO2-Niveau und der Unterschied von der eingestellten (P.05) Grenze, der überschritten
werden darf, eingestellt werden. Nach Überschreitung des zugelassenen Unterschieds löst das Pult automa-
tisch die Ventilatoren mit einer maximalen Geschwindigkeit (4) aus und im Bildschirm wird die Aufschrift „CO2“
gezeigt. Nachdem CO2 das eingestellte Niveau erreicht (P.05), kehrt das Pult in frühere Betriebsart zurück.
Zum Aufruf des Servicemenüs:
1. in den Zustand Ausgeschaltet umschalten (wenn das Pult eingeschaltet ist, Element B1 für 3 Sekunden
gedrückt halten),
2. B1 und B2 für 3 Sekunden gedrückt halten,
3. Sicherheitscode „022“ mit Elementen B4 und B6 eingeben und mit dem Element B5 bestätigen.
Im Servicemenü werden die Einstellungen von Menüpunkten (F.01, F.02 usw.) nacheinander gezeigt.
Menüpunkt wird mit Elementen B4 und B6 ausgewählt. Nach dem Drücken von B5 wird Parameter gespeichert
und man kehrt ins Menü für Einstellungen zurück.
Zum Verlassen des Servicemenüs muss das Element B1 gedrückt und für 3 Sekunden gehalten werden (das
Pult wird in den Ausschaltungszustand umgeschaltet).
Nr.
Bezeichnung Mögliche Bedeutungen
Vorgesehene
Bedeutung
F.01
Steuerung der Ventilatoren
0: 0..100%
1: Mit fi xierten Geschwindigkeitswerten
2: Laut fi xierten Druckwerten
1
F.02
Blockierung der Ausschaltung
0: Wird nicht blockiert
1: Der Ventilator bläst immer mit einer
minimalen 1. Geschwindigkeit
1
F.03
1. Geschwindigkeit (%) 0 – 100
20
F.04
2. Geschwindigkeit (%) 0 – 100
40
F.05
3. Geschwindigkeit (%) 0 – 100
70
F.06
4. Geschwindigkeit (boost) (%) 0 – 100
100
F.07
1. Geschwindigkeit (Pa) 0 – 999
5
F.08
2. Geschwindigkeit (Pa) 0 – 999
10
F.09
3. Geschwindigkeit (Pa) 0 – 999
25
F.10
4. Geschwindigkeit (boost) (Pa) 0 – 999
40
F.11
PID-P des Drucks 0 –999
5
F.12
PID-I des Drucks 0 – 999
10
F.13
PID-D des Drucks 0 – 999
0
F.14
Tauscher
0: Kein
1: Vom Druck
2: Von CO2
0
F.15
MIN des Tauschers 0-250 x10
0
F.16
MAX des Tauschers 1-250 x10
20
F.17
Adresse von Modbus master/slave (Haupt-/
untergeordnetes Gerät) des Pultes
0: Master
1 - 247: Slave
0
F.18
Übergabegeschwindigkeit der Modbus-
Daten
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
7: 115200
4
F.19
Modbus parity
0: None
1: Even
2: Odd
0
Bei der Herstellung von Werkeinstellungen muss Service-Passwort „022“ wiederholt eingegeben werden.
Wegen der begrenzten Zahl von Symbolen, die auf dem Segmentbildschirm gezeigt werden, werden die
Modbus-Adressen vom CUSTOM-Gerät mit HIGH- und LOW-Bytes im hexadezimalen System (HEX) eingege-
ben werden. Mit Hilfe von B2- und B3-Tasten wird HIGH- oder LOW- Byte gewählt, auf dem Bildschirm werden
dementsprechend „H.00“ und „L.00“ gezeigt.
F.20
Gesteuertes Gerät
(Das Pult identifi ziert die PRV- und EKO-
Platinen automatisch)
0: None
1: Custom
2: ECO
3: PRV
0
F.21
Modbus-Adresse des gesteuerten Gerätes 1 - 247
1
F.22
SET Temperature address 00:00 - FF:FF
00:00
F.23
SET Fan speed (%) address 00:00 - FF:FF
00:00
F.24
SET Fan speed fi xed address 00:00 - FF:FF
00:00
F.25
SET Pressure address 00:00 - FF:FF
00:00
F.26
SET CO2 address 00:00 - FF:FF
00:00
F.27
Temperature address 00:00 - FF:FF
00:00
F.28
Alarm 1 address 00:00 - FF:FF
00:00
F.29
Alarm 2 address 00:00 - FF:FF
00:00
F.30
Alarm 3 address 00:00 - FF:FF
00:00
F.31
Alarm 4 address 00:00 - FF:FF
00:00
F.32
Alarm 5 address 00:00 - FF:FF
00:00
F.33
Alarm 6 address 00:00 - FF:FF
00:00
F.34
Alarm 7 address 00:00 - FF:FF
00:00
F.35
Alarm 8 address 00:00 - FF:FF
00:00
F.36
Alarm 9 address 00:00 - FF:FF
00:00
F.37
Alarm 10 address 00:00 - FF:FF
00:00
F.38
Werkeinstellungen des Pultes herstellen 0: Nein
1: Ja
0
Bezeichnung Mögliche Bedeutungen
Art
Adresse
(HEX)
Adresse
(DEC)
Steuerung der Ventilatoren
0: 0..100%
1: mit fester Drehzahl
2: nach festem Druck
Holding
register
0x01
1
Blockierung der Abschaltung
0: Wird nicht blockiert
1: Der Ventilator bläst immer mini-
mal mit der 1. Geschwindigkeit
Holding
register
0x02
2
1. Geschwindigkeit (%) 0 – 100
Holding
register
0x03
3
2. Geschwindigkeit (%) 0 – 100
Holding
register
0x04
4
3. Geschwindigkeit (%) 0 – 100
Holding
register
0x05
5
4. Geschwindigkeit (boost) (%) 0 – 100
Holding
register
0x06
6
Ad
Adressentabelllle von Modb
dbus s
slave
ve
(untergeordnet
et)
1. Geschwindigkeit (Pa) 0 – 999
Holding
register
0x07
7
2. Geschwindigkeit (Pa) 0 – 999
Holding
register
0x08
8
3. Geschwindigkeit (Pa) 0 – 999
Holding
register
0x09
9
4. Geschwindigkeit (boost) (Pa) 0 – 999
Holding
register
0x0A
10
PID-P des Drucks 0 – 999
Holding
register
0x0B
11
PID-I des Drucks 0 – 999
Holding
register
0x0C
12
PID-D des Drucks 0 – 999
Holding
register
0x0D
13
MIN des Wechslers
0: Kein
1: Vom Druck
2: Von CO2
Holding
register
0x0E
14
MAX des Wechslers 0-250 x10
Holding
register
0x0F
15
Adresse von Modbus-Master/-
Slave des Pults 1-250 x10
Holding
register
0x10
16
0: Master
1 - 247: Slave
Holding
register
0x11
17
Übergabegeschwindigkeit von
Modbus-Daten
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
7: 115200
Holding
register
0x12
18
Modbus parity
0: None
1: Even
2: Odd
Holding
register
0x13
19
Gesteuertes Gerät
0: None
1: Custom
2: ECO
3: PRV
Holding
register
0x14
20
Modbus-Adresse des gesteuerten
Gerätes 1 - 247
Holding
register
0x15
21
SET Temperature address 00:00 - FF:FF
Holding
register
0x16
22
SET Fan speed (%) address 00:00 - FF:FF
Holding
register
0x17
23
SET Fan speed fi xed address 00:00 - FF:FF
Holding
register
0x18
24
SET Pressure address 00:00 - FF:FF
Holding
register
0x19
25
SET CO2 address 00:00 - FF:FF
Holding
register
0x1A
26
Temperature address 00:00 - FF:FF
Holding
register
0x1B
27
Alarm 1 address 00:00 - FF:FF
Holding
register
0x1E
28
all-guides
com
Alarm 2 address 00:00 - FF:FF
Holding
register
0x1F
29
Alarm 3 address 00:00 - FF:FF
Holding
register
0x20
30
Alarm 4 address 00:00 - FF:FF
Holding
register
0x21
31
Alarm 5 address 00:00 - FF:FF
Holding
register
0x22
32
Alarm 6 address 00:00 - FF:FF
Holding
register
0x23
33
Alarm 7 address 00:00 - FF:FF
Holding
register
0x24
34
Alarm 8 address 00:00 - FF:FF
Holding
register
0x25
35
Alarm 9 address 00:00 - FF:FF
Holding
register
0x26
36
Alarm 10 address 00:00 - FF:FF
Holding
register
0x27
37
Werkeinstellungen des Pultes
herstellen
0: Nein
1: Ja
Holding
register
0x28
38
Ruhezustand 0: ausgeschaltet
1-99: Einschlafzeit in Sekunden
Holding
register
0x29
39
Ton 0: ausgeschaltet
1: 1-9 Tonfarbe
Holding
register
0x2A
40
Anzeige der Speisungstemperatur
0: Nicht gezeigt
1: Wird nacheinander gezeigt mit
eingestellte
Holding
register
0x2B
41
Geforderter CO2 (ppm) 0 – 99 x10ppm
Holding
register
0x2C
42
Zugelassener CO2-Unterschied 0 – 99 x10ppm
Holding
register
0x2D
43
SET Temperature 150 – 350 (/10)
Holding
register
0x2F
44
SET Fan speed (%) 0, 20 - 100
Holding
register
0x30
45
SET Fan speed fi xed 0 - 4
Holding
register
0x31
46
SET Pressure 0 – 999Pa
Holding
register
0x32
47
Display supply temperature -500 – 1000 (/10)
Holding
register
0x34
48
Einstellungen speichern 0: Nein
22: Ja
Holding
register
0x36
49
Current fan speed (%) 0 – 100%
Input register
0x01
1
Current fi xed fan speed 0 – 4
Input register
0x02
2
Temperature Setpoint 150 – 350°C (/10)
Input register
0x03
3
Current Temperature -500– 1000 (/10)
Input register
0x04
4
Pressure Setpoint 0 – 999Pa
Input register
0x05
5
Current pressure 0 – 999Pa
Input register
0x06
6
CO2 Setpoint 0 – 999ppm
Input register
0x07
7
Current CO2 0 – 999ppm
Input register
0x08
8
Alarm 1 address 0/1
Coil
0x01
1
Alarm 2 address 0/1
Coil
0x02
2
Alarm 3 address 0/1
Coil
0x03
3
Alarm 4 address 0/1
Coil
0x04
4
Alarm 5 address 0/1
Coil
0x05
5
Alarm 6 address 0/1
Coil
0x06
6
Alarm 7 address 0/1
Coil
0x07
7
Alarm 8 address 0/1
Coil
0x08
8
Alarm 9 address 0/1
Coil
0x09
9
Alarm 10 address 0/1
Coil
0x0A
10
Falls man Parameter der Konfi gurierung speichern will, muss man in den Register 49 die Zahl 22
eingeben, dann werden die Einstellungen im EEPROM-Speicher bleiben und das Pult wird erneut ge-
laden.
Anzeigen
Bedeutung (Beschreibung der Störung s. im technischen Handbuch des
Geräts)
A.01
Frostschutz des Wärmetauschers
A.02
Außenschutz ist angesprochen
A.03
Kritische Temperatur des Rückwassers
A.04
Defekt des Eingangs „P-mA“
A.05
Niedrige Spannung
A.06
Defekt des Fühlers für Auszugsluft
A.07
Defekt des Fühlers für Zuluft
A.08
Defekt des Temperaturfühlers für Rückwasser
A.09
Defekt des Fühlers für Außentemperatur
St
Störungen
Störungen der ECO-
CO-Automatik
Bedeutung (Beschreibung der Störung s. im technischen Handbuch des
Geräts)
A.01
Frostschutz des Wärmetauschers
A.02
Brandschutz
A.03
Verschmutzte Filter
A.04
Defekt des Ventilators
A.05
Niedrige Spannung
A.06
Defekt des Temperaturfühlers für DTJ(100)
A.07
Defekt des Fühlers für Abluft
A.08
Defekt des Fühlers für Zuluft
A.09
Defekt des Feuchtefühlers für DTJ(100)
A.10
Defekt des Temperaturfühlers für Rückwasser
A.11
Defekt des Fühlers für Außenluft
Störungen von PRV-
RV-Automatik
Anzeigen
Bedeutung
A.01
A.02
A.03
A.04
A.05
A.06
A.07
A.08
A.09
A.10
Störung der CUSTOM
TOM-Automatik (nach Eins
instellung d
g der Adr
Adress
ess
essen vom
vom
vom CU
CU
CUSTO
STO
STO
STOM-
M-
M-
Modbus beifügen)
Le boîtier de commande tactile « Stouch » est spécialement conçu pour la commande des :
• Centrales de traitement d’air SALDA ;
• Autres unités équipées des contrôleurs PRV ou ECO ;
• Dispositifs contrôlés à l’aide du protocole MODBUS.
Ces boîtiers de commande assurent le confort et la sécurité optimale de l’exploitation, de la surveillance et de
la maintenance. Toutes les opérations sont réalisées à distance, à l’aide du boîtier de commande, qui fournit les
rapports des pannes et indique les conditions de maintenance.
Particularités
• Design exclusif et ergonome ;
• Facile à utiliser ;
• Destiné pour montage en applique ;
• Commande tactile par un seul appui ;
• Nettoyage facile ;
• Réponse sonore à un appui ;
• Possibilité de brancher sur le réseau GTB ;
• Possibilité du branchement direct au ventilateur commandé à l’aide du signal 0-10VDC ;
• Possibilité de connecter une sonde de CO2 ou un capteur de pression à l’entrée 0-10VDC.
• 4 vitesses prédéfi nies ;
• Vitesse maximale du ventilateur pour un laps de temps déterminé (boost) ;
• Verrouillage de sécurité enfants ;
• Possibilité de modifi er les paramètres du son, du régime de veille (StandBy), du CO2 à partir du menu «
utilisateur ».
Le kit comprend :
Boîtier de commande « Stouch », câble (13 m), éléments de fi xation (6 pcs.), notice technique.
Dimensions
20,5
84
84
1,5
1. À l’aide du modèle fourni visser les vis à l’endroit choisi, en laissant l’écartement du mur de 1 mm.
2. Brancher le câble au boîtier
2.1 – fi che standard
Installation
Installation
2.2 – fi che spécifi que (Cf. « Fiche 8 contacts »)).
3. Accrocher le boîtier en le tenant tourné à 25º vers la gauche.
4-5. Tourner le boîtier à droite jusqu’à ce qu’il se colle contre le mur. Retirer le modèle.
1
4
1 2 3 4
PIN1 - +24V
PIN2 - B+
PIN3 - A-
PIN4 - COM
PIN1 - +24V
PIN2 - B+
PIN3 - A-
PIN4 - COM
Fiche 8 contac
acts
1. Source d’alimentation 24 V AC/DC, 100 mA
2. Source d’alimentation 24 V AC/DC
3. GND
4. RS485 B (Modbus)
5. RS485 A (Modbus)
6. GND
7. Entrée 0-10VDC (pour la sonde de CO2 ou le capteur de pression). La sonde est alimentée depuis une
source d’alimentation distincte.
8. Sortie 0-10VDC (pour la commande 0..10VDC du ventilateur)
Le branchement électrique ne peut être effectué que par un électricien qualifi é conformément aux exigences
internationales et nationales en vigueur en matière de sécurité en milieu électrique et de montage des installa-
tions et des équipements électriques.
all-guides
com
Signifi cations des éléments
B1
Allumer/éteindre
B2
Réglage de la vitesse du ventilateur
B3
Réglage de la température
B4
Augmenter
B5
Vitesse maximale du ventilateur, inter-
valle de temps limité (Boost)
B6
Diminuer
S1
Écran segmentaire
L4-L7 Indications de vitesse du ventilateur
Informations u
utilisateur
ur
• Le menu « utilisateur » du boîtier est conçu pour le réglage facile des paramètres de la température, du
régime de veille et du niveau de CO2.
• Touche rapide d’activation de la vitesse maximale.
• Affi chage des valeurs (en chiffres) de la température de consigne et de celle de l’air souffl é.
• Indication LED de la vitesse choisie.
• Affi chage des pannes actives par symboles A.01, A.02 et indications LED.
• Régime de veille du boîtier (économie de l’énergie).
• Fonction de condamnation de l’arrêt du système de ventilation disponible.
• « Sécurité enfants » - verrouillage du boîtier.
Éléments
Commande Action
Indication
B1
L1
Allumer Maintenir 2 secondes B1
L1 éclaire
B1
L1
Éteindre Maintenir 2 secondes B1
L1 est éteint
L1
Sortir du régime de
veille
Toucher n’importe quel
bouton
L1 clignote lentement en régime de veille
B2 B4 B6
L2
Régler la vitesse des
ventilateurs Toucher B2
L2 éclaire. La vitesse est réglée en
touchant les éléments B4 et B6
B3 B4 B6
L3
Régler la température Toucher B3
L3 éclaire. La température est réglée en
touchant les éléments B4 et B6
B4 B6
L4-L7
Modifi er la valeur de
réglage choisie
Augmenter en touchant
B4, diminuer en touchant
B6
Les chiffres sur l’écran segmentaire. L4,
L5, L6 et L7 indique la vitesse des ventila-
teurs choisie
B4 B5 B6
L2
Allumer/éteindre la
fonction de ventilation
intense
Maintenir 2 secondes B5
L2 clignote. L’écran segmentaire indique
le temps restant en secondes (au-dessus
de 600s, le temps est indiqué en minutes).
Le temps est réglé en touchant B4 et B6.
La période maximale du fonctionnement
de BOOST - 180 min.
„Con“ clignote – en phase de connexion.
„noC“ allumé – pas de connexion.
Indication de co
connexio
ion
Contrôle de la
la v
vitesse
se du ve
ventililateu
eur
• En fonction de 4 vitesses prédéfi nies fi xes
• En fonction du pourcentage choisi (0. 20-100%)
• À partir du menu « utilisateur » la vitesse est réglable à l’intervalle de 5%
• À partir du menu « service » la vitesse est réglable à l’intervalle de 1%
• En fonction de 4 pressions prédéfi nies fi xes à l’aide du capteur de pression
• La vitesse maximale est sécurisée par un chronomètre, dont le temps est facilement modifi able lors de
l’activation de la vitesse de rotation maximale (boost).
• La vitesse de rotation maximale est activée à l’aide de la touche rapide. Le temps réglé de la rotation maxi-
male du ventilateur (boost) écoulé, le ventilateur reprend automatiquement la vitesse précédente.
• Possibilité de connecter la sonde CO2 0..10VDC, qui active la vitesse maximale du ventilateur en fonction des
paramètres CO2 défi nis.
Contrôle de la
la t tempéra
rature
re
• Possibilité de régler sur le boîtier la température souhaitée de 15 à 35ºC.
• Possibilité d’affi cher alternativement la température de l’air souffl é et celle de consigne (5 s d’affi chage de la
température de consigne et 2 s d’affi chage de celle de l’air souffl é).
Communicatio
ion à dist
stance
ce (Mo
Modbus
us)
Le boitier est compatible avec l’interface entièrement paramétrable Modbus. Le boîtier peut être utilisé en tant
qu’un dispositif principal ou auxiliaire dans le réseau GTB en Modbus ; en outre il est entièrement contrôlable et
paramétrable non seulement à partir du menu « service », mais encore par l’interface Modbus.
amétrable non seulement à part
artir du menu «
u « service
ce », mais e
s encore
re par l’ l’interface
ace Mo
Modbu
dbus.
paramé
Menu « utilisate
teur »
Pour accéder au menu « utilisateur », appuyer 3 secondes sur B2, B3.
Le menu « utilisateur » fait défi ler les réglages des points du menu (p.01, P.02 etc.). Le point du menu est
sélectionné à l’aide des éléments B4 et B6. L’appui de B5 affi che la valeur du paramètre choisi, qui peut être
modifi ée à l’aide des éléments B4 et B6. L’appui sur le B5 fait sauvegarder le paramètre choisi et fait retourner
au menu.
Les ressources limitées de l’affi cheur segmentaire ne permettent l’affi chage des valeurs P.04, P.05 que
diminués 10 fois, c’est-à-dire, la valeur réelle de l’affi chage « 20 » est 20 x 10 = 200.
P.06 - le chronomètre des fi ltres est remis en position initiale en maintenant 5 secondes l’élément B5 appuyé.
Le chronomètre des fi ltres est également remis en position initiale en annulant la panne A.03.
Appuyer l’élément B1 pour sortir du menu.
B4 B6
L4-L7
Contrôle et annulation
des pannes
En annulant, maintenir 3
secondes B2 et B3
En cas de pannes, L4, L5, L6 et L7
clignotent et les codes de la panne (A.01,
A.02, etc.) sont indiqués sur l’écran seg-
mentaire. La liste des pannes peut être
contrôlée à l’aide des éléments B4 et B6.
Après annulation de la panne, le boîtier
revient en position initiale
L2-L7
La purge CO2 fonc-
tionne
L2, L3 et L7 clignote, L4, L5 et L6 éclaire
B2 B3 B5
« Sécurité enfants » al-
lumée/éteinte
Maintenir 2 secondes B3,
B2 et B5
Éléments B1, B4 et B6 inactifs.
Après avoir appuyé sur un bouton non au-
torisé, l’écran segmentaire montre « --- »
Nr.
Libellé Valeurs éventuelles
Valeur
prévue
P.01
Régime de veille 0 – arrêté
1-99 temps de mise en veille en secondes
0
P.02
Volume 0 : coupé
1 : 1-9 timbre du son
2
Ce boîtier de commande peut commander les autres unités (commandées à l’aide du protocole MODBUS).
Les réglages se font à partir du menu « service » en indiquant les paramètres requis sur les points du menu
F.17, F.18, F.19, F.20, F.21. Lors du besoin de commander des dispositifs spécifi ques, indiquer « CUSTOM »
dans le point du menu F.20 et les adresses des dispositifs dans les points de F.22 à F.37. Dans le cas où ces
dispositifs ne possèdent pas d’adresses, saisir dans les champs de ces points du menu « 00:00 ». Générale-
ment ce boîtier est utilisé avec des contrôleurs ECO ou PRV.
BOÎTIER
(master)
MODBUS
CTA
(slave)
1) Modbus maître (
e (principal)
Dans le cas d’utilisation du système GTB, un boîtier peut commander plusieurs unités simultanément, ou plu-
sieurs boîtiers peuvent commander une seule unité. À l’aide du protocole MODBUS il est possible de modifi er
tous les paramètres des boîtiers et de contrôler les informations des sondes et capteurs connectés.
BOÎTIER
(slave)
CTA
(slave)
GTB
CTA
(slave)
BOÎTIER
(slave)
MODBUS
RS485
2) Modbus esclave
ve (auxiliaire)
3) Commande du ven
ventilateur lorsque la vite
itesse est r
t réglée
ée à
l’aide du boîtier ou
ou de l’ordinateur au moyen
yen de l’int
interface
ace Mo
Modbu
dbu
dbus
Ce boîtier peut commander tant l’unité, tant le ventilateur 0..10VDC. À partir du menu « service », sélection-
ner le mode de commande de la vitesse souhaité (F.01). Dans le cas du choix de la commande en fonction des
vitesses prédéfi nies, indiquer ces vitesses dans les points du menu : F.03, F.04, F05, F.06.
BOÎTIER
(slave)
VENT.
0...10 VDC
MODBUS
P.03
Affi chage température de l’air souffl é
0 : Non affi chée
1 : Affi chage alternatif avec celle de con-
signe
0
P.04
CO2 requise 0 – 99 x10ppm
20 x10
P.05
Dépassement CO2 toléré 0 – 99 x10ppm
5 x 10
P.06
Chronomètre des fi ltres 0 – 999 dienos
0
4) Maintien de la pre
pression, réglée à l’aide d
e du boîtier
ier ou
de l’ordinateur au mo
moyen de l’interface Modbu
dbus
Dans le cas de la connexion directe du ventilateur 0..10VDC et du variateur de pression 0..10VDC au boîtier
de commande, il est possible de maintenir la pression souhaitée. Les paramètres de commande et ceux du
capteur de pression sont modifi ables à l’aide du boîtier de commande. L’utilisation du boîtier en tant que le
dispositif « esclave » (« Modbus slave ») permet la commande de tous les paramètres et le contrôle des indica-
tions du capteur de pression.
Pour la commande en fonction de la pression, il est nécessaire de déterminer dans le menu « service » les
paramètres suivants :
• F.14 - 1
• F.15 et F.16 - en fonction des paramètres du variateur de pression
• F.11, F.12 et F.13 - (coeffi cients régulateur PID). Si la pression est maintenue de manière impropre, ces
paramètres peuvent être corrigés.
• F.07 - F.10 - indiquer les vitesses prédéfi nies Pa.
BOÎTIER
(slave)
VENT.
0...10 VDC
MODBUS
Capteur de
pression
0...10 VDC
5) Maintien du CO2
CO2
BOÎTIER
(master)
VENT.
(au lieu de la CTA)
0...10 VDC
MODBUS
Capteur de
pression
0...10 VDC
CTA
(slave)
Ce boîtier permet de contrôler le niveau de CO2 de l’ambiance. Il suffi t de connecter au boîtier la sonde de
CO2 0..10VDC et de confi gurer le boîtier. Dans le régime « service » régler le point F.14 sur 2 et défi nir et F.15
et F.16 en fonction de la spécifi cation de la sonde.
Une fois la sonde de CO2 connectée et le paramétrage depuis le menu « service » effectué, il est nécessaire
de régler le niveau CO2 souhaité (P.05) et la différence tolérée au-dessus du seuil réglé (P.05). La différence
tolérée dépassée, le boîtier met automatiquement le ventilateur à la vitesse maximale (4) et l’affi chage « CO2 »
apparait sur l’affi cheur numérique. Lorsque la teneur de CO2 atteint le niveau réglé (P.05), le boîtier reprend le
régime initial.
Menu « service
ce »
Pour accéder au menu « service » il est nécessaire de :
1. Mettre le boîtier au régime « Arrêt » (si le boîtier est allumé, appuyer 3 secondes sur l’élément B1).
2. Appuyer 3 secondes sur B1 et B2.
3. Saisir le code de sécurité « 022 » à l’aide des éléments B4, B6 et valider avec l’élément B5.
Le menu « service » fait défi ler les réglages des points du menu (p.01, P.02 etc.). Le point du menu est sélec-
tionné à l’aide des éléments B4 et B6. L’appui de B5 affi che la valeur du paramètre choisi, qui peut être modifi ée
à l’aide des éléments B4 et B6. L’appui sur le B5 fait sauvegarder le paramètre choisi et fait retourner au menu.
Appuyer l’élément B1 3 secondes pour sortir du menu (le boîtier passe au régime « Arrêt »).
No.
Libellé Valeurs éventuelles
Valeur
prévue
F.01
Commande des ventilateurs
0 : 0..100 %
1 : Vitesses prédéfi nies
2 : En fonction des valeurs de pression
prédéfi nies
1
F.02
Condamnation arrêt
0 : Sans condamnation
1 : Marche continue du ventilateur à vitesse
minimale (1)
1
F.03
Vitesse 1 (%) 0 – 100
20
F.04
Vitesse 2 (%) 0 – 100
40
F.05
Vitesse 3 (%) 0 – 100
70
F.06
Vitesse 4 (boost) (%) 0 – 100
100
F.07
Vitesse 1 (Pa) 0 – 999
5
F.08
Vitesse 2 (Pa) 0 – 999
10
F.09
Vitesse 3 (Pa) 0 – 999
25
F.10
Vitesse 4 (boost) (Pa) 0 – 999
40
F.11
PID de pression – P 0 –999
5
F.12
PID de pression – I 0 – 999
10
F.13
PID de pression – D 0 – 999
0
F.14
Variateur
0 : Néant
1 : Pression
2 : CO2
0
F.15
Variateur MIN 0-250 x10
0
F.16
Variateur MAX 1-250 x10
20
F.17
Adresse maître / esclave du boîtier 0: Master
1 - 247: Slave
0
F.18
Vitesse de transmission de données par
Modbus
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
7: 115200
4
F.19
Parité Modbus
0: None
1: Even
2: Odd
0
all-guides
com
Lors de restitution des réglages usine il est nécessaire de ressaisir le mot de passe service « 022 ».
En raison de nombre de caractères limité dans l’affi cheur segmentaire, les adresses Modbus du dispositif «
CUSTOM » sont saisies en bytes HIGH et LOW, dans le système hexadécimal (HEX). À l’aide des touches B2
et B3 sélectionner les bytes HIGH ou LOW, dont l’affi chage est respectivement « H.00 » et L.00 ».
F.20
Dispositif commandé
(Le boîtier reconnait automatiquement les
régulateurs PRV et ECO)
0 : Néant
1 : Utilisateur
2 : Eco
3 : PRV
0
F.21
Adresse Modbus du dispositif commandé 1 - 247
1
F.22
SET Temperature address 00:00 - FF:FF
00:00
F.23
SET Fan speed (%) address 00:00 - FF:FF
00:00
F.24
SET Fan speed fi xed address 00:00 - FF:FF
00:00
F.25
SET Pressure address 00:00 - FF:FF
00:00
F.26
SET CO2 address 00:00 - FF:FF
00:00
F.27
Temperature address 00:00 - FF:FF
00:00
F.28
Alarm 1 address 00:00 - FF:FF
00:00
F.29
Alarm 2 address 00:00 - FF:FF
00:00
F.30
Alarm 3 address 00:00 - FF:FF
00:00
F.31
Alarm 4 address 00:00 - FF:FF
00:00
F.32
Alarm 5 address 00:00 - FF:FF
00:00
F.33
Alarm 6 address 00:00 - FF:FF
00:00
F.34
Alarm 7 address 00:00 - FF:FF
00:00
F.35
Alarm 8 address 00:00 - FF:FF
00:00
F.36
Alarm 9 address 00:00 - FF:FF
00:00
F.37
Alarm 10 address 00:00 - FF:FF
00:00
F.38
Restituer les réglages usine du boîtier 0: Ne
1:Taip
0
Libellé Valeurs éventuelles
Type
Adresse
(HEX)
Adresse
(DEC)
Commande des ventilateurs
0 : 0..100 %
1 : Vitesses prédéfi nies
2 : En fonction des valeurs de
pression prédéfi nies
Holding
register
0x01
1
Condamnation arrêt
0 : Sans condamnation
1 : Marche continue du ventilateur
à vitesse minimale (1)
Holding
register
0x02
2
Vitesse 1 (%) 0 – 100
Holding
register
0x03
3
Vitesse 2 (%) 0 – 100
Holding
register
0x04
4
Vitesse 3 (%) 0 – 100
Holding
register
0x05
5
Vitesse 4 (boost) (%) 0 – 100
Holding
register
0x06
6
Ta
Tableau d’adre
resses M
Modbu
bus Es
Esclav
ave (a
(aux
uxilia
iaire)
e)
Vitesse 1 (Pa) 0 – 999
Holding
register
0x07
7
Vitesse 2 (Pa) 0 – 999
Holding
register
0x08
8
Vitesse 3 (Pa) 0 – 999
Holding
register
0x09
9
Vitesse 4 (boost) (Pa) 0 – 999
Holding
register
0x0A
10
PID de pression – P 0 – 999
Holding
register
0x0B
11
PID de pression – I 0 – 999
Holding
register
0x0C
12
PID de pression – D 0 – 999
Holding
register
0x0D
13
Variateur MIN
0 : Néant
1 : Pression
2 : CO2
Holding
register
0x0E
14
Variateur MAX 0-250 x10
Holding
register
0x0F
15
Pultelio Modbus master/slave
adresas 1-250 x10
Holding
register
0x10
16
0: Master
1 - 247: Slave
Holding
register
0x11
17
Vitesse de transmission de don-
nées par Modbus
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
7: 115200
Holding
register
0x12
18
Modbus parity
0: None
1: Even
2: Odd
Holding
register
0x13
19
Dispositif commandé
0: None
1: Custom
2: ECO
3: PRV
Holding
register
0x14
20
Adresse Modbus du dispositif
commandé 1 - 247
Holding
register
0x15
21
SET Temperature address 00:00 - FF:FF
Holding
register
0x16
22
SET Fan speed (%) address 00:00 - FF:FF
Holding
register
0x17
23
SET Fan speed fi xed address 00:00 - FF:FF
Holding
register
0x18
24
SET Pressure address 00:00 - FF:FF
Holding
register
0x19
25
SET CO2 address 00:00 - FF:FF
Holding
register
0x1A
26
Temperature address 00:00 - FF:FF
Holding
register
0x1B
27
Alarm 1 address 00:00 - FF:FF
Holding
register
0x1E
28
Alarm 2 address 00:00 - FF:FF
Holding
register
0x1F
29
Alarm 3 address 00:00 - FF:FF
Holding
register
0x20
30
Alarm 4 address 00:00 - FF:FF
Holding
register
0x21
31
Alarm 5 address 00:00 - FF:FF
Holding
register
0x22
32
Alarm 6 address 00:00 - FF:FF
Holding
register
0x23
33
Alarm 7 address 00:00 - FF:FF
Holding
register
0x24
34
Alarm 8 address 00:00 - FF:FF
Holding
register
0x25
35
Alarm 9 address 00:00 - FF:FF
Holding
register
0x26
36
Alarm 10 address 00:00 - FF:FF
Holding
register
0x27
37
Restituer les réglages usine du
boîtier
0 : Non
1 : Oui
Holding
register
0x28
38
Régime de veille 0 – Arrêté
1-99 temps de mise en veille en s
Holding
register
0x29
39
Volume 0 : Coupé
1 : 1-9 timbre du son
Holding
register
0x2A
40
Affi chage température de l’air
souffl é
0 : Non affi chée
1 : Affi chage alternatif avec celle
de consigne
Holding
register
0x2B
41
CO2 requise (ppm) 0 – 99 x10ppm
Holding
register
0x2C
42
Dépassement CO2 toléré 0 – 99 x10ppm
Holding
register
0x2D
43
SET Temperature 150 – 350 (/10)
Holding
register
0x2F
44
SET Fan speed (%) 0, 20 - 100
Holding
register
0x30
45
SET Fan speed fi xed 0 - 4
Holding
register
0x31
46
SET Pressure 0 – 999Pa
Holding
register
0x32
47
Display supply temperature -500 – 1000 (/10)
Holding
register
0x34
48
Sauvegarder les réglages 0 : Non
22 : Oui
Holding
register
0x36
49
Current fan speed (%) 0 – 100%
Input register
0x01
1
Current fi xed fan speed 0 – 4
Input register
0x02
2
Temperature Setpoint 150 – 350°C (/10)
Input register
0x03
3
Current Temperature -500– 1000 (/10)
Input register
0x04
4
Pressure Setpoint 0 – 999Pa
Input register
0x05
5
Current pressure 0 – 999Pa
Input register
0x06
6
CO2 Setpoint 0 – 999ppm
Input register
0x07
7
Current CO2 0 – 999ppm
Input register
0x08
8
Alarm 1 address 0/1
Coil
0x01
1
Alarm 2 address 0/1
Coil
0x02
2
Alarm 3 address 0/1
Coil
0x03
3
Alarm 4 address 0/1
Coil
0x04
4
Alarm 5 address 0/1
Coil
0x05
5
Alarm 6 address 0/1
Coil
0x06
6
Alarm 7 address 0/1
Coil
0x07
7
Alarm 8 address 0/1
Coil
0x08
8
Alarm 9 address 0/1
Coil
0x09
9
Alarm 10 address 0/1
Coil
0x0A
10
Pour sauvegarder les paramètres réglés, il est nécessaire de saisir « 22 » dans le registre 49 : les
réglages sont mémorisés dans le mémoire EEPROM et le boîtier redémarre.
Indication
Valeur (pour la description de l’alarme, voir la notice technique de l’unité)
A.01
Protection antigel de l’échangeur de chaleur
A.02
Déclenchement de la protection extérieure
A.03
Température critique de l’eau de retour
A.04
Panne entrée ‘P-mA »
A.05
Tension basse
A.06
Panne de la sonde de l’air repris
A.07
Panne de la sonde de l’air souffl é
A.08
Panne de la sonde de température de l’eau de retour
A.09
Panne de la sonde de température de l’air extérieur
Al
Alarmes
Alarmes du contrôl
rôleur ECO
Indication
Valeur (pour la description de l’alarme, voir la notice technique de l’unité)
A.01
Protection antigel de l’échangeur de chaleur
A.02
Protection incendie
A.03
Filtres encrassés
A.04
Panne ventilateur
A.05
Tension basse
A.06
Panne de la sonde de température DTJ (100)
A.07
Panne de la sonde de l’air rejeté
A.08
Panne de la sonde de l’air souffl é
A.09
Panne de la sonde d’humidité DTJ (100)
A.10
Panne de la sonde de température de l’eau de retour
A.11
Panne de la sonde de température de l’air extérieur
Alarmes du contrôl
rôleur PRV
Alarmes du contrôl
rôleur CUSTOM (compéter
er après la
la défi
défi ni
nitio
tion d
n des
es adr
adr
adress
ess
esses
es
es Mod
Mod
Mod
Mod
Mod-
bus CUSTOM)
all-guides
com