Lenze EMF2191IB Communications Manual

Specifications

Brand: Lenze
Category: Control Unit
Model: EMF2191IB
File Type: PDF
File Size: —
Pages: 56

Read Online

Read the Lenze EMF2191IB Communications Manual online using the built-in PDF viewer.

Text of the manual

EDSMF2191IB .M\} Ä.M\}ä Communication Manual POWERLINK  EMF2191IB Communication module L−force Communication

EDSMF2191IB EN 2.0

1 About this documentation 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 Document history 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2 Conventions used 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3 Terminology used 8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4 Notes used 9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Safety instructions 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1 General safety information 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.2 Device− and application−specific safety instructions 11 . . . . . . . . . . . . . . . . . . . . . . . . 2.3 Residual hazards 11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Product description 12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.1 Application as directed 12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2 Identification 13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.3 Product features 14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.4 Connections and interfaces 15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Technical data 17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1 General data and operating conditions 17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2 Protective insulation 18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3 Data for POWERLINK communication 19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3.1 Cycle time 20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3.2 Processing time in the inverter 20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.4 Dimensions 21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Installation 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1 Mechanical installation 23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2 Electrical installation 24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2.1 Wiring according to EMC (CE−typical drive system) 24 . . . . . . . . . . . . . . . . . 5.2.2 Network topology 25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2.3 POWERLINK 26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2.4 Operation in the standard Ethernet 28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2.5 POWERLINK connection 29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2.6 Specification of the Ethernet cable 30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2.7 Voltage supply 32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

EDSMF2191IB EN 2.0

6 Commissioning 34 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.1 Before switching on 34 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2 Setting the node address 35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.3 Configuration via the "Automation Studio" 36 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.4 Initial switch−on 37 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Diagnostics 38 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Appendix 39 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1 Index table 39 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Index 53 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

About this documentation

1  4 EDSMF2191IB EN 2.0 0Fig. 0Tab. 0 1 About this documentation Contents This documentation exclusively describes the EMF2191IB (POWERLINK) communication module.  Note! This documentation supplements the mounting instructions supplied with the function/communication module and the documentation of the used standard device. The mounting instructions contain safety instructions which must be observed! The features and functions of the communication module are described in detail. Examples illustrate typical applications. Furthermore this documentation contains the following: ƒ Safety instructions that must be observed. ƒ Key technical data relating to the communication module ƒ Information on versions of Lenze standard devices to be used. ƒ Notes on troubleshooting and fault elimination The theoretical correlations are only explained in so far as they are necessary for comprehending the function of the communication module. This documentation does not describe the software of an original equipment manufacturer. No responsibility is taken for corresponding information given in this manual. Information on how to use the software can be obtained from the documents of the host system (master). All brand names mentioned in this manual are trademarks of their respective companies.  Tip! Detailed information about POWERLINK can be found on the website of the "Ethernet POWERLINK Standardisation Group": http://www.ethernet−powerlink.org

About this documentation

1  5 EDSMF2191IB EN 2.0 Target group This documentation is intended for all persons who plan, install, commission and maintain the networking and remote service of a machine.  Tip! Information and auxiliary devices related to the Lenze products can be found in the download area at http://www.Lenze.com Validity information The information in this documentation applies to the following devices: Extension module Type designation From hardware version From software version POWERLINK communication module EMF2191IB VA 1.0

About this documentation

Document history 1  6 EDSMF2191IB EN 2.0 1.1 Document history Version Description 1.0 05/2008 TD00 First edition 2.0 09/2013 TD17  Corrected information on cycle times ( 19)  New chapter structure Your opinion is important to us! These instructions were created to the best of our knowledge and belief to give you the best possible support for handling our product. If you have suggestions for improvement, please e−mail us to: feedback−[email protected] Thank you for your support. Your Lenze documentation team

About this documentation

Conventions used 1  7 EDSMF2191IB EN 2.0 1.2 Conventions used This documentation uses the following conventions to distinguish between different types of information: Type of information Identification Examples/notes Spelling of numbers Decimal separator Point In general, the decimal point is used. For instance: 1234.56 Decimal Standard notation Example: 1234 Hexadecimal 0x[0 ... 9, A ... F] Example: 0x60F4 Binary  Nibble 0b[0, 1] Point Example: ´0b0110´ Example: ´0b0110.0100´ Text Program name » « PC software For example: »Engineer«, »Global Drive Control« (GDC) Icons Page reference  Reference to another page with additional information For instance:  16 = see page 16 Documentation reference  Reference to another documentation with additional information For example:  EDKxxx = see documentation EDKxxx

About this documentation

Terminology used 1  8 EDSMF2191IB EN 2.0 1.3 Terminology used Term Meaning EPSG Ethernet Powerlink Standardisation Group User organisation which defines POWERLINK. Inverter Inverter, the communication module can be used with ( 12). Standard device Slave (CN) Controlled Node POWERLINK node which is a slave in the real−time Ethernet POWERLINK. Master (MN) Managing Node POWERLINK node which has the master function in the real−time Ethernet POWERLINK. Node ID POWERLINK node address MAC address (MAC ID) Media Access Control address The MAC address is unequivocal worldwide. The MAC address is represented by six bytes in hexadecimal form the single bytes being separated by dots. The first three bytes refer to the manufacturer, the other bytes serve to identify the device. HW Hardware SW Software

About this documentation

Notes used 1  9 EDSMF2191IB EN 2.0 1.4 Notes used The following pictographs and signal words are used in this documentation to indicate dangers and important information: Safety instructions Structure of safety instructions:  Danger! (characterises the type and severity of danger) Note (describes the danger and gives information about how to prevent dangerous situations) Pictograph and signal word Meaning  Danger! Danger of personal injury through dangerous electrical voltage. Reference to an imminent danger that may result in death or serious personal injury if the corresponding measures are not taken.  Danger! Danger of personal injury through a general source of danger. Reference to an imminent danger that may result in death or serious personal injury if the corresponding measures are not taken. Stop! Danger of property damage. Reference to a possible danger that may result in property damage if the corresponding measures are not taken. Application notes Pictograph and signal word Meaning  Note! Important note to ensure troublefree operation  Tip! Useful tip for simple handling  Reference to another documentation

General safety information

2  10 EDSMF2191IB EN 2.0 2 Safety instructions  Note! It is absolutely vital that the stated safety measures are implemented in order to prevent serious injury to persons and damage to material assets. Always keep this documentation to hand in the vicinity of the product during operation. 2.1 General safety information  Danger! Disregarding the following basic safety measures may lead to severe personal injury and damage to material assets! ƒ Lenze drive and automation components ... ... must only be used for the intended purpose. ... must never be operated if damaged. ... must never be subjected to technical modifications. ... must never be operated unless completely assembled. ... must never be operated without the covers/guards. ... can − depending on their degree of protection − have live, movable or rotating parts during or after operation. Surfaces can be hot. ƒ For Lenze drive components ... ... only use permitted accessories. ... only use original manufacturer spare parts. ƒ All specifications of the corresponding enclosed documentation must be observed. This is vital for a safe and trouble−free operation and for achieving the specified product features. The procedural notes and circuit details provided in this document are proposals which the user must check for suitability for his application. The manufacturer does not accept any liability for the suitability of the specified procedures and circuit proposals. ƒ Only qualified skilled personnel are permitted to work with or on Lenze drive and automation components. According to IEC 60364 or CENELEC HD 384, these are persons ... ... who are familiar with the installation, assembly, commissioning and operation of the product, ... possess the appropriate qualifications for their work, ... and are acquainted with and can apply all the accident prevent regulations, directives and laws applicable at the place of use.

Device− and application−specific safety instructions

2  11 EDSMF2191IB EN 2.0 2.2 Device− and application−specific safety instructions ƒ During operation, the communication module must be securely connected to the standard device. ƒ With external voltage supply, always use a separate power supply unit, safely separated in accordance with EN 61800−5−1 in every control cabinet (SELV/PELV). ƒ Only use cables that meet the given specifications. ( 30)  Documentation of the standard device, control system, and plant/machine All the other measures prescribed in this documentation must also be implemented. Observe the safety instructions and application notes contained in this manual. 2.3 Residual hazards Protection of persons ƒ If controllers are connected to phase−earthed system with a rated mains voltage  400 V, external measures need to be implemented to provide reliable protection against accidental contact. (see chapter "4.2",  18) Device protection ƒ The communication module contains electronic components that can be damaged or destroyed by electrostatic discharge.

Application as directed

3  12 EDSMF2191IB EN 2.0 3 Product description 3.1 Application as directed The communication module ... ƒ is a device intended for use in industrial power systems; ƒ can only be used in POWERLINK networks; ƒ can be used together with the following standard devices (nameplate data): Device type Design Version Variant Explanation HW SW 1) 82EVxxxxxBxxxXX  Vx  1x 8200 vector 82CVxxxxxBxxxXX  Vx  1x 8200 vector, cold plate 82DVxxxKxBxxxXX  Vx  1x 8200 vector, thermally separated EPL 10200 E  1x  1x Drive PLC 33.93XX xE.  2x  1x Vxxx 9321 − 9332 vector 33.938X xE.  1x  0x 9381 − 9383 vector 33.93XX xC.  2x  1x Vxxx 9321 − 9332, with cold plate version 33.93XX EI / ET  2x  1x Vxxx 9300 Servo PLC 33.93XX CI / CT  2x  1x Vxxx 9300 Servo PLC, cold plate ECSxSxxxx4xxxxXX  1A  6.0 ECSxS "Speed & Torque" ECSxPxxxx4xxxxXX  1A  6.0 ECSxP "Posi & Shaft" ECSxMxxxx4xxxxXX  1A  6.0 ECSxM "Motion" ECSxAxxxx4xxxxXX  1A  2.3 ECSxA "Application" ECSxExxxx4xxxxXX  VA  3.0 ECSxE power supply module 1) operating system software versions of the controllers Any other use shall be deemed inappropriate!

EDSMF2191IB EN 2.0

3.2 Identification E82AF000P0B201XX L Type Id.-No. Prod.-No. MAC-ID  2191EPL013  33.2191IB VA 10 Device series Hardware version Software version

EDSMF2191IB EN 2.0

3.3 Product features ƒ Powerful and real−time capable communication system for motion and general applications. Real time Ethernet with the Ethernet POWERLINK V2 communication profile. ƒ Communication module for the AIF slot of the frequency inverters 8200 vector, 9300 vector and ECS servo system. ƒ Support of the Ethernet POWERLINK slave functionality (controlled node). ƒ Very short slave (Controlled Node) response times for optimal network performance. ƒ Integrated Ethernet hub (double) for easily setting up line topologies without any additional components. ƒ External 24V supply for maintaining the POWERLINK communication in case the device fails. ƒ Use of max. 3 PDO crosslinks for master (managing node) or slave (controlled node) to create systems with "distributed intelligence".

Connections and interfaces

3  15 EDSMF2191IB EN 2.0 3.4 Connections and interfaces 2191EPL001B Connections Pos. Description POWERLINK connection Version: RJ45 socket according to IEC 60603−7  Connection to external supply of the communication module Version: Connector with screw connection, 2−pole Switch Pos. Description  Switches for addressing the nodes  Left switch: Setting with factor 16  Right switch: Setting with factor 1 The addition of both products results in the node address (node ID) Node ID = 254 (the node ID is obtained from a DHCP server)

Connections and interfaces

3  16 EDSMF2191IB EN 2.0 Displays LED Description Pos. Colour Condition  green off The communication module is supplied with voltage, but has no connection to the basic device (basic device is either switched off, in the initialisation phase, or not available). on The communication module is supplied with voltage and is connected to the standard device.  green The NMT state machine triggers the two−colored LED:  Green: Display of status messages  Red: Display of error messages Off NMT_GS_OFF, NMT_GS_INITIALISATION, NMT_CS_NOT_ACTIVE / NMT_MS_NOT_ACTIVE NMT_CS_PREOPERATIONAL_1 / NMT_MS_PREOPERATIONAL_1 (LED flashes once within a second.) NMT_CS_PREOPERATIONAL_2 / NMT_MS_PREOPERATIONAL_2 (LED flashes twice within a second.) NMT_CS_READY_TO_OPERATE / NMT_MS_READY_TO_OPERATE (LED flashes three times within a second.) NMT_CS_BASIC_ETHERNET (LED is blinking with a frequency of 10 Hz or depending on the connection state) NMT_CS_STOPPED (LED is blinking with a frequency of 2.5 Hz.) NMT_CS_OPERATIONAL / NMT_MS_OPERATIONAL (LED is lit permanently.) Red ERROR (LED is lit permanently. An error has occurred.)  Red On The red and green drive LED indicates the operating status of the standard device (see documentation of the standard device).  green blinking Depending on the connection state, the data is transmitted or received (ACTIVITY).  yellow on Ethernet connection is available (LINK).

General data and operating conditions

4  17 EDSMF2191IB EN 2.0 4 Technical data 4.1 General data and operating conditions Field Values Order designation EMF2191IB Communication profile Ethernet POWERLINK V2 Interface RJ45, Fast Ethernet Mode MII (according to IEEE 802.3) Communication medium TP (100BaseTX, Cat5e) Cable length max. 100 m between 2 nodes / hubs Total extension Number of nodes x 100 m Network topology Tree, star, line Transmission mode Half duplex Type of node Slave (CN, Controlled Node) Node address Max. 239 Conformities, approvals  CE  cUL Baud rate 100 Mbps Voltage supply External supply via separate power supply unit + V = I = 24VDC(20.4 V − 0%... 28.8 V+ 0%) 140 mA −Reference potential for external voltage supply  Documentation for Lenze series of devices 8200 vector, 9300 and ECS Here you can find the ambient conditions and the electromagnetic compatibility (EMC) specifications applying to the communication module.

EDSMF2191IB EN 2.0

4.2 Protective insulation  Danger! Dangerous electrical voltage If Lenze controllers are used on a phase earthed mains with a rated mains voltage  400 V, protection against accidental contact is not ensured without implementing external measures. Possible consequences: ƒ Death or serious injury Protective measures: ƒ If protection against accidental contact is required for the control terminals of the controller and the connections of the plugged device modules, ... – a double isolating distance must exist. – the components to be connected must be provided with the second isolating distance. Insulation between bus and ... Type of insulation (in accordance with EN 61800−5−1)  Earth reference / PE Functional insulation  With external supply Functional insulation  Power stage – 8200 vector Reinforced insulation – 9300 servo inverter Reinforced insulation – 93xx servo position controller Reinforced insulation – 93xx servo register control Reinforced insulation – 93xx servo cam profiler Reinforced insulation – 9300 vector / Servo PLC Reinforced insulation – ECS devices Reinforced insulation  Control terminals – 8200 vector Functional insulation – 9300 servo inverter Basic insulation – 93xx servo position controller Basic insulation – 93xx servo register control Basic insulation – 93xx servo cam profiler Basic insulation – 9300 vector / Servo PLC Basic insulation – ECS devices Basic insulation

Data for POWERLINK communication

4  19 EDSMF2191IB EN 2.0 4.3 Data for POWERLINK communication Field Values Jitter synchronisation information approx. 1 s Total cycle times Slave (CN): 1, 2, 3  60 ms  The module can be operated with a minimum cycle of 1 ms.  In multiplex mode, a minimum cycle of 200 sec is supported if the data is accepted on the millisecond. Buffer size Tx−iso: max. 92 bytes (64 bytes of PDO user data) Rx−iso: max. 328 bytes (300 bytes of PDO user data) Frame size Max. asynchronous telegram size (MTU): 1518 bytes SDO communication method UDP/IP Number of RPDOs 3 RPDO user data per application (all RPDOs) max. 32 objects with a total of max 64 bytes Number of TPDOs 1 TPDO user data per application max. 32 objects with a total of max 64 bytes Delay time TPReq − TPRes: 1900 ns TSoA − TASnd: 1900 ns

Data for POWERLINK communication

Cycle time 4  20 EDSMF2191IB EN 2.0 4.3.1 Cycle time The cycle time of the communication system is the time in which all process data between the master (managing node) and the slaves (controlled nodes) are exchanged. It depends on the data of the communication system and can be calculated as follows e. g. for a baud rate of 500 kbps: tzykl  3, 35  103 (n  48  3 BK)  0, 24 L  0, 2 tcycl Cycle time [ms] n Sum of all data bits in the POWERLINK network BK Number of bus terminals L Length of the remote bus cable [km] The following diagram shows the relation between cycle time and number of connected fieldbus nodes. The given values refer to the connection of Lenze inverters (e.g. 82xx) with 48 bits (1 parameter data word + 2 process data words). 12 10 8 6 4 2 10 20 30 40 50 60 Cycle time [ms] Number of nodes 1 Fig. 4−1 Relationship between cycle time and number of nodes 4.3.2 Processing time in the inverter There are no interdependencies between parameter data and process data. Processing times Parameter data Process data Processing time inside the inverter  For controller−internal parameters approx. 30 ms + a tolerance of 20 ms  Some codes may have a longer processing time (see documentation of the inverter)  There is no synchronisation between the communication module and the inverter.  Times of 8200 vector/motec, starttec: Approx 3 ms + a tolerance of 2 ms  Times of 9300 / ECS: Approx. 2 ms + a tolerance of 1 ms (each being independent of the basic cycle time) Additional times outside the inverter  Communication transfer times  Communication processing times of the transmitting node

EDSMF2191IB EN 2.0

4.4 Dimensions 2191EPL001B All dimensions in mm

EDSMF2191IB EN 2.0

5 Installation  Danger! Inappropriate handling of the communication module and the standard device can cause serious personal injury and material damage. Observe the safety instructions and residual hazards described in the documentation for the standard device. Stop! The device contains components that can be destroyed by electrostatic discharge! Before working on the device, the personnel must ensure that they are free of electrostatic charge by using appropriate measures.

EDSMF2191IB EN 2.0

5.1 Mechanical installation 2102LEC014 Fig. 5−1 Attaching the communication module ƒ Plug the communication module onto the standard device (here: 8200 vector). ƒ Tighten the communication module to the standard device using the fixing screw in order to ensure a good PE connection.  Note! For the internal supply of the communication module by the 8200 vector frequency inverter the jumper has to be adjusted within the interface opening (see illustration above). Observe the notes ( 32).

Wiring according to EMC (CE−typical drive system)

5  24 EDSMF2191IB EN 2.0 5.2 Electrical installation 5.2.1 Wiring according to EMC (CE−typical drive system) For wiring according to EMC requirements observe the following points:  Note! ƒ Separate control cables/data lines from motor cables. ƒ Connect the shields of control cables/data lines at both ends in the case of digital signals. ƒ Use an equalizing conductor with a cross−section of at least 16mm2 (reference:PE) to avoid potential differences between the bus nodes. ƒ Observe the other notes concerning EMC−compliant wiring given in the documentation for the standard device. Wiring procedure 1. Comply with bus topology, thus do not use stubs. 2. Observe notes and wiring instructions in the documents for the control system. 3. Only use cables that comply with the given specifications ( 30). 4. Observe notes for the voltage supply of the module ( 32).

EDSMF2191IB EN 2.0

5.2.2 Network topology IP routing IT integration (NAT) Access protection EPL router Hub Hub Protected segment (machine system) Ethernet max. 100 m max. 100 m  Detailed information on this topic can be found in the Ethernet POWERLINK brochure "Real−time Industrial Ethernet is reality"

EDSMF2191IB EN 2.0

5.2.3 POWERLINK POWERLINK network segment  Note! Standard Ethernet nodes are not permitted in the POWERLINK network segment. In order to use the real−time capability of the POWERLINK technology, the POWERLINK nodes must be interconnected in a separate network segment. In accordance with the POWERLINK rules, only the network master (managing node) controls the access of the slaves (controlled nodes) to the network. The network master is the only node that transmits autonomously. All other nodes (controlled nodes) only transmit when they are entitled to transmit by the master. Non−POWERLINK nodes (e.g. PCs) typically violate these rules by sending frames independently of the master. These frames interfere with the cyclic frame exchange of the POWERLINK nodes and prevent the real−time capability of the POWERLINK. Connection to the standard Ethernet network The connection to an external standard Ethernet network is carried out via an Ethernet POWERLINK router. These infrastructure component separates the network traffic in the POWERLINK network segment from the one in the standard Ethernet. The handling of the frames depend on their direction: ƒ Standard Ethernet −−−> POWERLINK network segment Only frames that are addressed to nodes in the POWERLINK network segment are forwarded. The forwarding takes place in the asynchronous area of the POWERLINK cycle. ƒ POWERLINK network segment −−−> Standard Ethernet Only asynchronous frames that are not addressed to nodes in the POWERLINK network segment are forwarded.

EDSMF2191IB EN 2.0

Topologies in the POWERLINK network segment  Note! The use of class 1 hubs and switches inside the POWERLINK network segment is not permitted. Inside the segment only Ethernet hubs may be used as infrastructure elements. The hubs must meet the requirements on class 2 repeaters acc. to IEEE 802.3u. For this purpose, Lenze offers the dual hub integrated into the communication module and the separate eight−fold hub, type E94AZCEH. Class 1 hubs and switches are not permissible since they have considerably longer delay times for the frame forwarding and a bigger jitter. Both sizes reduce the real−time capability and dynamics. The cable length between both nodes is limited to 100 m. The topology rules (IEEE802.3u) required for controlling the collisions may be violated in the POWERLINK network segment since according to the POWERLINK access order, frame collisions are prevented. This enables a structure of lines and any hybrid forms between star and line topology. Recommended topology For an easy configuration and due to many possible topology variants we recommend to create networks according to the following rules: 1. Create slave groups with up to 10 nodes 2. Connect groups in star shape to the master (managing node). 3. For more than 2 groups: Use external 8−port hubs, e.g. Lenze hub E94AZCEH. Exception: For maximally 2 groups, these are directly connected to the two ports of the communication module. Hub Master 1. slave group 2. slave group Fig. 5−2 Star topology for 1 to 2 slave groups 4. Connect slave groups to the master via one external hub each. – For max. 7 slave groups one hub is sufficient. – For more than 7 slave groups, use further hubs. – The groups can be distributed on the hubs just as you like.

Operation in the standard Ethernet

5  28 EDSMF2191IB EN 2.0 5.2.4 Operation in the standard Ethernet  Note! Operation in the standard Ethernet does not permit any real−time communication. The communication module can be operated in the standard Ethernet for a basic parameter setting provided that the following applies: 1. Operation of the module in slave mode: – Network address 239 – IP address: 192.168.100. 2. Real time operation must not be carried out. 3. No integration of a master (EPL address  240) into the standard Ethernet network. More notes on wiring ƒ Do not wire, if possible, more than 9nodes in succession in a network line.

EDSMF2191IB EN 2.0

5.2.5 POWERLINK connection You can use a standard Ethernet patch cable for connecting the communication module to the fieldbus (see "Ethernet cable specifications" ( 30)).  Note! Plug/remove the Ethernet cable plug in a straight manner (at right angles) into/from the socket to make sure that the RJ45 socket will not be damaged. Pin assignment RJ45 socket PIN Signal 1 Tx + 2 Tx − 3 Rx + 4 − 5 − 6 Rx − 7 − E94AYCXX004C 8 −  Tip! The POWERLINK interfaces feature an auto MDIX function. This function adjusts the polarity of the RJ45 interfaces so that a connection is established irrespective of the polarity of the opposite POWERLINK interface, and irrespective of the type of cable used (standard patch cable or crossover cable).

Specification of the Ethernet cable

5  30 EDSMF2191IB EN 2.0 5.2.6 Specification of the Ethernet cable  Note! Only use cables complying with the below specifications. Ethernet cable specifications Ethernet standard Standard Ethernet (according to IEEE 802.3), 100base TX (fast Ethernet) Cable type S/FTP (Screened Foiled Twisted Pair), ISO/IEC 11801 or EN 50173, CAT 5e Damping 23.2 dB (at 100 MHz and per 100 m) Crosstalk damping 24 dB (at 100 MHz and per 100 m) Return loss 10 dB (per 100 m) Surge impedance 100  Design of the Ethernet cable E94YCEP016 Fig. 5−3 Design of the Ethernet cable (S/FTP, CAT 5e) A Cable insulation B Braid C Foil shielding of the core pairs TP1 ... TP4 Twisted core pairs 1 ... 4

Specification of the Ethernet cable

5  31 EDSMF2191IB EN 2.0 Colour code of Ethernet cable  Note! Wiring and colour code are standardised in EIA/TIA 568A/568B. You can use 4−pin Ethernet cables in accordance with the industrial standard. The cable type only connects the assigned pins 1, 2, 3 and 6 with each other. E94YCEI004A Fig. 5−4 Ethernet plug in accordance with EIA/TIA 568A/568B Pair Pin Signal EIA/TIA 568A EIA/TIA 568B 3 1 Tx + White/green White/orange 2 Tx − Green Orange 2 3 Rx + White/orange White/green 1 4 Not assigned Blue Blue 5 Not assigned White/blue Blue/white 2 6 Rx − Orange Green 4 7 Not assigned White/brown White/brown 8 Not assigned Brown Brown

EDSMF2191IB EN 2.0

5.2.7 Voltage supply Internal voltage supply  Note! Internal voltage supply has been selected in the case of standard devices with an extended AIF interface opening (e.g. front of 8200 vector). The area shown on a grey background in the graphic marks the jumper position. ƒ By default, this is not supplied internally in the standard device. ƒ For internal voltage supply place the jumper on the position indicated below. In the case of all other device series (9300, ECS), voltage is always supplied from the standard device. Lenze setting (Only external voltage supply possible.) Internal voltage supply External voltage supply  Note! In the case of an external voltage supply and for greater distances between the control cabinets, always use a separate power supply unit (SELV/PELV) that is safely separated in accordance with EN 61800−5−1 in each control cabinet. The external voltage supply of the communication module ... ƒ is required if communication via the fieldbus is to be continued when the supply of the device fails. ƒ is provided via the 2−pin terminal strip with screw−type connection (24 V DC): Terminal Description + External voltage supply U = 24VDC(20.4 V − 0%... 28.8 V +0%) I = 85 mA − Reference potential for external voltage supply ƒ The parameters of a standard device disconnected from the mains cannot be accessed.

EDSMF2191IB EN 2.0

Terminal data Area Values Electrical connection Plug connector with screw connection Possible connections rigid: 1.5 mm2 (AWG 16) flexible: without wire end ferrule 1.5 mm2 (AWG 16) with wire end ferrule, without plastic sleeve 1.5 mm2 (AWG 16) with wire end ferrule, with plastic sleeve 1.5 mm2 (AWG 16) Tightening torque 0.5 ... 0.6 Nm (4.4 ... 5.3 lb−in) Stripping length 6 mm

Before switching on

6  34 EDSMF2191IB EN 2.0 6 Commissioning During commissioning, system−dependent data as e.g. motor parameters, operating parameters, responses and parameters for fieldbus communication are selected for the controller. In Lenze devices, this is done via codes. The codes are stored in numerically ascending order in the Lenze controllers and in the plugged−in communication/function modules. In addition to these configuration codes, there are codes for diagnosing and monitoring the bus devices. 6.1 Before switching on Stop! Before switching on the standard device with the communication module for the first time, check the entire wiring for completeness, short circuit and earth fault.

Setting the node address

6  35 EDSMF2191IB EN 2.0 6.2 Setting the node address  Note! ƒ Use different node addresses for several networked inverters. The Lenze setting for the node address (node ID) has the value ’4’: – link switch in position ’0’ – right switch in position ’4’ ƒ Switch the voltage supply of the inverter/communication module off and on again to activate changed settings. E94YCEP001D Fig. 6−1 Setting the node address Each node has to be assigned to a unique address (node ID). ƒ Valid address range for slave (controlled node): 1 ... 239 ƒ The corresponding IP address of the communication module results from the setting of the two rotary switches. IP address: 192.168.100. (ValueLeftSwitch  16)(ValueRightSwitch)  NodeAddress Example ƒ Left rotary switch in position ’2’ ƒ Right rotary switch in position ’5’ (2  16)5  37 ==> The node address is ’37’.

Configuration via the "Automation Studio"

6  36 EDSMF2191IB EN 2.0 6.3 Configuration via the "Automation Studio" The upgrade mechanism of the "Automation Studio" of the B & R company serves to esta- blish an internet connection via which the necessary installation files are called. After the upgrade, tick "display customised devices" in the hardware selection list to dis- play the Lenze devices. The following functions are available: ƒ Adding Lenze devices to the hardware configuration ƒ Setting node parameters (e.g. node ID) ƒ I/O configuration (basic configuration settings of the controller) ƒ Defining the I/O mapping (assignment of the process data objects of the controller to the PLC objects) The communication module is configured like a B & R device. The I/O configuration indica- tes the code which are compulsory for commissioning the inverter. If further codes have to be written, library functions from the PLC project can be used. For this purpose, you can find the "AsEPL" library in the "Library Manager". It provides the func- tions "EplSDOWrite" and "EplSDORead" which serve to read and write any parameters of the device. Indexing the Lenze codes The index number is converted to a code as follows: Conversion formula Index (dec) Index (hex) 24575 − Lenze code 0x5FFF − (Lenze code) Example of C0001 (operating mode): Index (dec) Index (hex) 24575 − 1 = 24574 0x5FFF − 1 = 0x5FFE  Further information on the "Automation Studio" functions can be found in the corresponding documentation.

EDSMF2191IB EN 2.0

6.4 Initial switch−on Switch on the inverter and check whether it is ready for operation using the diagnostic LEDs at the front of the communication module. ƒ Red diagnostic LEDs must not be on. ƒ The following signalling should be visible: LED Description Pos. Colour Condition  green on The communication module is supplied with voltage and is connected to the standard device.  green The NMT state machine triggers the two−colored LED:  Green: Display of status messages  Red: Display of error messages NMT_CS_BASIC_ETHERNET (LED is blinking with a frequency of 10 Hz or depending on the connection state) NMT_CS_OPERATIONAL / NMT_MS_OPERATIONAL (LED is lit permanently.)  green blinking Depending on the connection state, the data is transmitted or received (ACTIVITY).  yellow on Ethernet connection is available (LINK).

EDSMF2191IB EN 2.0

7 Diagnostics The LEDs on the front are provided to the communication module for the purpose of fault diagnostics. Displays LED Description Pos. Colour Condition  green off The communication module is supplied with voltage, but has no connection to the basic device (basic device is either switched off, in the initialisation phase, or not available). on The communication module is supplied with voltage and is connected to the standard device.  green The NMT state machine triggers the two−colored LED:  Green: Display of status messages  Red: Display of error messages Off NMT_GS_OFF, NMT_GS_INITIALISATION, NMT_CS_NOT_ACTIVE / NMT_MS_NOT_ACTIVE NMT_CS_PREOPERATIONAL_1 / NMT_MS_PREOPERATIONAL_1 (LED flashes once within a second.) NMT_CS_PREOPERATIONAL_2 / NMT_MS_PREOPERATIONAL_2 (LED flashes twice within a second.) NMT_CS_READY_TO_OPERATE / NMT_MS_READY_TO_OPERATE (LED flashes three times within a second.) NMT_CS_BASIC_ETHERNET (LED is blinking with a frequency of 10 Hz or depending on the connection state) NMT_CS_STOPPED (LED is blinking with a frequency of 2.5 Hz.) NMT_CS_OPERATIONAL / NMT_MS_OPERATIONAL (LED is lit permanently.) Red ERROR (LED is lit permanently. An error has occurred.)  Red On The red and green drive LED indicates the operating status of the standard device (see documentation of the standard device).  green blinking Depending on the connection state, the data is transmitted or received (ACTIVITY).  yellow on Ethernet connection is available (LINK).

EDSMF2191IB EN 2.0

8 Appendix 8.1 Index table Overview The following objects specified by the Ethernet POWERLINK communication profile are supported.  Tip! The Ethernet POWERLINK specification contains details on the POWERLINK communication profile and can be obtained from the Ethernet POWERLINK Standardisation Group (EPSG): http://www.ethernet−powerlink.org EPL index Subindex Index name More information 0x1000 NMT_DeviceType_U32  42 0x1001 ERR_ErrorRegister_U8  42 0x1003 ERR_History_ADOM − 0x1006 NMT_CycleLen_U32  42 0x1008 NMT_ManufactDevName_VS − 0x1009 NMT_ManufactHwVers_VS − 0x100A NMT_ManufactSwVers_VS − 0x1010 NMT_StoreParam_REC − 0x1011 NMT_RestoreDefParam_REC − 0x1018 1 ... 4 NMT_IdentityObject_REC  42 0x1020 CFM_VerifyConfiguration_REC − 0x1030 1 ... 9 NMT_InterfaceGroup_0h_REC  43 0x1101 1 Dia_NMTTelegramCount_REC  43 0x1400 1 ... 2 PDO_RxCommParam_00h_REC  43 0x1401 1 ... 2 PDO_RxCommParam_01h_REC  44 0x1402 1 ... 2 PDO_RxCommParam_02h_REC  44 0x1600 1 ... 20 PDO_RxMappParam_00h_REC  44 0x1601 1 ... 20 PDO_RxMappParam_01h_REC  45 0x1602 1 ... 20 PDO_RxMappParam_02h_REC  45 0x1800 1 ... 2 PDO_TxCommParam_00h_REC − 0x1A00 1 ... 20 PDO_TxMappParam_00h_REC  46 0x1C0A DLL_CNCollision_REC  46 0x1C0B DLL_CNLossSoC_REC  46 0x1C0C DLL_CNLossSoA_REC − 0x1C0D DLL_CNLossPReq_REC − 0x1C0E DLL_CNSoCJitter_REC − 0x1C0F DLL_CNCRCError_REC  47 0x1C10 DLL_CNLossOfLinkCum_U32  47 0x1C13 DLL_CNSoCJitterRange_U32 −

EDSMF2191IB EN 2.0

More information Index name Subindex EPL index 0x1C14 DLL_LossOfFrameTolerance_U32 − 0x1E40 1 ... 5 NWL_IpAddrTable_0h_REC  48 0x1E4A 1 ... 3 NWL_IpGroup_REC − 0x1F50 PDL_DownloadProgData_ADOM − 0x1F51 PDL_ProgCtrl_AU8 − 0x1F52 PDL_LocVerApplSw_REC − 0x1F81 1 ... 64 NMT_NodeAssignment_AU32  49 0x1F82 NMT_FeatureFlags_U32  50 0x1F83 NMT_EPLVers_U8  50 0x1F8C NMT_CurrState_U8  51 0x1F8D 1 ... 64 NMT_MNPResPayloadList_AU32  51 0x1F93 1 ... 2 NMT_EPLNodeID_REC  51 0x1F98 1 ... 9 NMT_CycleTiming_REC − 0x1F99 NMT_CNBasicEthernetTimeout_U32  51 0x1F9A NMT_HostName_VSTR  52 0x1F9E NMT_ResetCmd_U8  52

EDSMF2191IB EN 2.0

How to read the index table Model of an index table Index Name Subcode Lenze Values Data type Access: Meaning Header Meaning Index Number of the Ethernet POWERLINK index I−xxxx Name Display text Leading columns Meaning Subcode Number of the subcode Lenze Lenze setting ("Default" setting) of the code   Display code The code cannot be configured. Values Minimum value [smallest increment/unit] Maximum value In case of a display code the displayed values are specified. Data type  BITFIELD_8  BITFIELD_32  U8 8 bit value without sign  U16 16 bit value without sign  U32 32 bit value without sign  U64 64 bit value without sign  VS Visible String, string with specified length Footer Meaning Access ro: The parameter can only be read (display code) rw: The parameter can be changed

EDSMF2191IB EN 2.0

I−1000: EPL device type Index 0x1000 EPL name NMT_DeviceType_U32 Subcode Lenze Values Data type −  U32 Access: ro The object displays the device type of the node. I−1001: EPL error register Index 0x1001 EPL name ERR_ErrorRegister_U8 Subcode Lenze Values Data type −  U8 Access: ro The object contains currently pending errors arranged according to error classes. The bits of the error register have the following meaning: Bit Description 0 Generic error, signals an existing error message in the CN which can be read out via StatusResponse 1 Amperage 2 Voltage 3 Temperature 4 Communication error 5 Device profile−related error 6 Reserved (0) 7 Manufacturer−specific error I−1006: EPL cycle time Index 0x1006 EPL name NMT_CycleLen_U32 Subcode Lenze Values Data type − 1 1 ... [1 ms] ... 20 U32 Access: rw The object contains the length of the EPL cycle in [s]. I−1018: EPL identity object Index 0x1018 EPL name NMT_IdentityObject_REC Subcode Lenze Values Data type 1: VendorId_U32 0x59 U32 2: ProductCode_U32 2191 3: RevisionNo_U32 0x00000000 4: SerialNo_U32 Access: ro The object contains identification information on the communication module.

EDSMF2191IB EN 2.0

I−1030: EPL MAC address Index 0x1030 EPL name NMT_InterfaceGroup_0h_REC Subcode Lenze Values Data type 1: InterfaceIndex_U16  0 U16 2: InterfaceDescription_VSTR EMF2191IB_1 VSTR 3: InterfaceType_U8 6 U8 4: InterfaceMtu_U32 1500 U32 5: InterfacePhysAddress_OSTR "00:0A:86:84:xx:xx" OSTR 6: InterfaceName_VSTR "IF1" VSTR 7: InterfaceOperStatus_U8 1 U8 Access: ro for subcodes 1, 2, 3, 4, 5 and 7 Access: rw for subcode 6 The object contains information on the Ethernet interface. The subcode 5 contains the MAC address. When the communication module is produced, the MAC address is assigned unequivocally worldwide and provides addressing on the lowest level. I−1101: EPL telegram counter Index 0x1101 EPL name DIA_NMTTelegrCount_REC Subcode Lenze Values Data type 1: IsochrCyc_U32 − − U32 Access: ro Subcode 1 of the object contains a counter for POWERLINK cycles. The counter is started with each power−on of the node at 0. An overflow occurs at 4.294.967.295. I−1400: EPL address : RPDO Index 0x1400 EPL name PDO_RxCommParam_XXh_REC.NodeID_U8 Subcode Lenze Values Data type 1 0 0, 1 ... 240, 253, 254 U8 Access: rw Subcode 1 of the object contains the node address (node ID) of the transmitting node for the PDO channel (n+1). Values > ’0’ describe the origin of a PRes telegram. The value ’0’ is reserved for "PReq" (cannot be used in systems with a Lenze Servo Drive 9400 as managing node). The value is only valid if the corresponding object 0x160x has a value > ’0’.

EDSMF2191IB EN 2.0

I−1401: EPL address : RPDO Index 0x1401 EPL name PDO_RxCommParam_XXh_REC.NodeID_U8 Subcode Lenze Values Data type 1 0 0, 1 ... 240, 253, 254 U8 Access: rw Subcode 1 of the object contains the node address (node ID) of the transmitting node for the PDO channel (n+1). Values > ’0’ describe the origin of a PRes telegram. The value ’0’ is reserved for "PReq" (cannot be used in systems with a Lenze Servo Drive 9400 as managing node). The value is only valid if the corresponding object 0x160x has a value > ’0’. I−1402: EPL address : RPDO Index 0x1402 EPL name PDO_RxCommParam_XXh_REC.NodeID_U8 Subcode Lenze Values Data type 1 0 0, 1 ... 240, 253, 254 U8 Access: rw Subcode 1 of the object contains the node address (node ID) of the transmitting node for the PDO channel (n+1). Values > ’0’ describe the origin of a PRes telegram. The value ’0’ is reserved for "PReq" (cannot be used in systems with a Lenze Servo Drive 9400 as managing node). The value is only valid if the corresponding object 0x160x has a value > ’0’. I−1600: EPL number of RPDO Index 0x1600 EPL name PDO_RxMappParam_xxh_AU64.NumberOfEntries Subcode Lenze Values Data type 0 0 0, 1 ... 32 U64 Access: rw The object describes the number of valid mapping entries for the PDO channel (n+1). The value ’0’ inhibits the PDO channel. The sum of all mapping entries enabled via the objects 0x160x must not exceed the value ’64’.

EDSMF2191IB EN 2.0

I−1601: EPL number of RPDO Index 0x1601 EPL name PDO_RxMappParam_xxh_AU64.NumberOfEntries Subcode Lenze Values Data type 0 0 0, 1 ... 32 U64 Access: rw The object describes the number of valid mapping entries for the PDO channel (n+1). The value ’0’ inhibits the PDO channel. The sum of all mapping entries enabled via the objects 0x160x must not exceed the value ’64’. I−1602: EPL number of RPDO Index 0x1602 EPL name PDO_RxMappParam_xxh_AU64.NumberOfEntries Subcode Lenze Values Data type 0 0 0, 1 ... 32 U64 Access: rw The object describes the number of valid mapping entries for the PDO channel (n+1). The value ’0’ inhibits the PDO channel. The sum of all mapping entries enabled via the objects 0x160x must not exceed the value ’64’.

EDSMF2191IB EN 2.0

I−1A00: EPL TPDO Index 0x1A00 EPL name PDO_TxMappParam_00h_AU64 Subcode Lenze Values Data type 1 ... 32: ObjectMapping − see below U64 Access: rw The object describes the mapping for the TPDO channel. Subcode 0 describes the number of valid mapping object entries. Subcodes 1 to 32 describe the mapping of the individual objects. The entry is structured as follows: Byte Name Description 0, 1 Index EPL index of the mapped object 2 Subindex Subindex 3 Reserved 4, 5 Offset Offset, calculated from the start of the PDO user data [bits] 6, 7 Length Length of the mapped object [bits] I−1C0A: EPL CN: Telegr. collisions Index 0x1C0A EPL name DLL_CNCollision_REC Subcode Lenze Values Data type 1: CumulativeCnt_U32 − − U32 Access: ro The object indicates the number of Ethernet collisions detected by the slave (controlled node). Each event is counted. Every single event is followed by an error message. No threshold value management is implemented. I−1C0B: EPL CN: Loss of synchr. Index 0x1C0B EPL name DLL_CNCollision_REC Subcode Lenze Values Data type 1: CumulativeCnt_U32 − − U32 2: ThresholdCnt_U32 − − 3: Threshold_U32 1 0, 1, 2 etc. Access: see below The slave (controlled node) expects SoC frames in time intervals which correspond to the cycle time. The object indicates the error counters for missing SoC frames.

EDSMF2191IB EN 2.0

I−1C0F: EPL CN: Frame error (CRC) Index 0x1C0F EPL name DLL_CNCRCError_REC Subcode Lenze Values Data type 1: CumulativeCnt_U32 − − U32 2: ThresholdCnt_U32 0 0, 1, 2, 3 ... U32 3: Threshold_U32 0 0, 1, 2, 3 ... U32 Access: Subcode 3: rw , otherwise ro The object indicates the number of frame checksum errors detected by the slave (controlled node). I−1C10: EPL CN: Link interruptions Index 0x1C10 EPL name DLL_CNLossOfLinkCum_U32 Subcode Lenze Values Data type − − − U32 Access: ro The object indicates the counter of the slave (controlled node) for Ethernet connection interruptions. Each event is counted. Every single event is followed by an error message. No threshold value management is implemented.

EDSMF2191IB EN 2.0

I−1E40: EPL IP address Index 0x1E40 EPL name NWL_IpAddrTable_0h_REC.Addr_IPAD Subcode Lenze Values Data type 2  − U32 3  − 5 0xC0A864FE − Access: ro ƒ Subcode 2: The subcode contains the IP address of the communication module. It is derived according to the following rule from the node address (node ID, I−1F93): 192.168.100. ƒ Subcode 3: The subcode contains the IP subnet mask which limits the IP address range that can be addressed directly (i.e. without using a gateway in the EPL segment of the routers). In an EPL segment, the subnet mask is permanently assigned to the value ’255.255.255.0’ (0xFFFFFF00). ƒ Subcode 5: The subcode contains the IP address of the EPL router via which the EPL segment is connected to the higher−level network. The standard entry corresponds to the standard router address of the POWERLINK specification: 192.168.100.254 Permissible entries replace the lowest−order byte of the standard entry with the EPL address of the node which has the function of a router.

EDSMF2191IB EN 2.0

I−1F81: EPL node declaration CN Index 0x1F81 EPL name NMT_NodeAssignment_AU32 Subcode Lenze Values Data type see table U32 Access: rw The object describes the slave (controlled node) and its properties. The describing bit field has the following structure: Bit Relevance Lenze Value Description MN CN 0 (LSB)   0, 1 0 Node with this ID does not exist 1 Node with this ID exists 1   0, 1 0 Node with this ID is no CN 1 Node with this ID is a CN 2   1 0 *) starting CNs are not automatically booted 1 starting CNs are automatically booted 3   1 0 optional CN. 1 obligatory CN. 4   0 0 CN can be reset independently of the current state using the NMTResetCommunication command 1 *) CN must not be reset when being in the NMT_CS_OPERATIONAL state 5   0 0 Application SW version verification is not required 1 *) Application SW version verification is required 6   0, 1 0 Automatic application SW update is not allowed 1 Automatic application SW update is allowed 7 − − 0 − Reserved 8   0, 1 0 Isochronously accessed CN. 1 AsyncOnly CN, bit 9 irrelevant 9   0 0 Continuously accessed CN 1 *) Multiplex CN 10 ... 30 − − 0 − Reserved 31 (MSB)   0, 1 0 Bit 0 .. 30 inhibited 1 Bit 0 .. 30 enabled *) Not permissible for Servo Drives 9400

EDSMF2191IB EN 2.0

I−1F82: EPL feature flags Index 0x1F82 EPL name NMT_FeatureFlags_U32 Subcode Lenze Values Data type −  U32 Access: ro The object indicates the POWERLINK functions implemented by the slave (controlled node). The describing bit field has the following structure: Bit Relevance TRUE FALSE MN CN 0   Isochronous access is allowed Only AsyncOnly access 1   SDO via UDP/IP No SDO by UDP/IP 2   SDO via EPL ASnd (only MN for Servo Drives 9400) No SDO via EPL ASnd (only CN for Servo Drives 9400) 3   SDO integrated in PDO No SDO integrated in PDO 4   Support NMT Info Services No NMT Info Services 5   Support of extended NMT State Commands No extended NMT State Commands 6   Support of dynamic PDO mapping No dynamic PDO mapping 7   NMT services via UDP/IP No NMT services via UDP/IP 8   Configuration manager function No configuration manager function 9   Isochronous multiplex access is possible Only isochronous cyclic access is allowed 10   Address assignment via SW No address assignment via SW 11   Support of basic Ethernet mode of the master No support of basic Ethernet mode of the master 12   Device can be used as Powerlink to standard Ethernet router Device does not support any Powerlink to standard Ethernet function 13   Device can be used as Powerlink to fieldbus router Device does not support any Powerlink to fieldbus router function 14 ... 31 − − Reserved (these bits are assigned to FALSE) − I−1F83: EPL version Index 0x1F83 EPL name NMT_EPLVers_U8 Subcode Lenze Values Data type −  0x20 U8 Access: ro The object describes the version of the Ethernet POWERLINK communication profile implemented by the communication module. The higher−order nibble describes the major version, the lower order nibble describes the minor version. The implemented value corresponds to the EPL version 2.0.

EDSMF2191IB EN 2.0

I−1F8C: EPL communication status Index 0x1F8C EPL name NMT_CurrNMTState_U8 Subcode Lenze Values Data type −  see table Access: ro The object contains the current NMT state. I−1F8D: EPL CN: Max. user data PRes RPDO Index 0x1F8D EPL name NMT_PResPayloadList_AU16 Subcode Lenze Values Data type 1 ... 100 36 bytes see description, unit: Byte U16 Access: rw This object defines the reserved user data length of the PRes frames. Each subcode corresponds to a node with the same node ID. The node must have been enabled via the object 0x1F81. The subcode describes the received PRes frames. The value must be within the range of 36 ... 1490 bytes. The values are limit values for the total sizes of the PDO mappings to be defined for received PRes frames. I−1F93: EPL device address Index 0x1F93 EPL name NMT_EPLNodeID_REC.NodeID_U8 Subcode Lenze Values Data type − − 1 .. 239 U8 Access: ro The object contains the currently valid node address (node ID). I−1F99: EPL CN: Max. MN detection time Index 0x1F99 EPL name NMT_CNBasicEthernetTimeout_U32 Subcode Lenze Values Data type − 5000000 s 0 ... 50000000 s U32 Access: rw The object contains a time interval for a booting slave (controlled node) for detecting a master (managing node). If a booting slave (controlled node) detects a master (managing node) during the interval, it changes to NMT_CS_PREOPERATIONAL_1. If not, it changes to "Basic Ethernet Mode".

EDSMF2191IB EN 2.0

I−1F9A: EPL host name Index 0x1F9A EPL name NMT_Hostname_VSTR Subcode Lenze Values Data type − − see "naming convention" VS15 Access: rw The object contains a DNS−compatible device name. The length is limited to 15 characters. Naming convention: ƒ The device name ... – starts with a letter; – ends with a letter or a digit. ƒ The device name consists of ... – letters (A .. Z), upper or lower case, – digits (0 .. 9), – hyphen (−).  Note! The device name must be unambiguous within the network domain. I−1F9E: EPL reset command Index 0x1F9E EPL name NMT_ResetCmd_U8 Subcode Lenze Values Data type − see table U8 Access: wo The object initiates a reset of the node. The following reset commands are available: Command Value Status transition NMTInvalidService 0xFF (255) no function (default) NMTResetNode 0x28 (40) NMT_GS_RESET_APPLICATION NMTResetCommunication 0x29 (41) NMT_GS_RESET_COMMUNICATION NMTResetConfiguration 0x2A (42) NMT_GS_RESET_CONFIGURATION NMTSwReset 0x2B (43) NMT_GS_INITIALISING When the reset has been executed, the object is automatically set to "NMTInvalidService". Stop! A reset command on a single node in the network can cause cycle and monitoring errors.

EDSMF2191IB EN 2.0

9 Index A Address settings, 35 Application as directed, 12 Automation Studio, configuration, 36 B Baud rate, 17 C Cable specification, 30 CE−typical drive system, 24 Colour code of Ethernet cable, 31 Commissioning, 34 −Initial switch−on, 37 Communication medium, 17 Communication profile, 17 Configuration via the "Automation Studio", 36 Connection to the standard Ethernet, 26 Connections, 15 Cycle time, 20 D Data for POWERLINK communication, 19 Definition of notes used, 9 Definitions, 8 Design of the Ethernet cable, 30 Device protection, 11, 22 Diagnostics, 38 E Electrical installation, 24 EPL index −1C0B, 46 −I−1000, 42 −I−1001, 42 −I−1006, 42 −I−1018, 42 −I−1030, 43 −I−1101, 43 −I−1400, 43 −I−1401, 44 −I−1402, 44 −I−1600, 44 −I−1601, 45 −I−1602, 45 −I−1A00, 46 −I−1C0A, 46 −I−1C0F, 47 −I−1C10, 47 −I−1E40, 48 −I−1F81, 49 −I−1F82, 50 −I−1F83, 50 −I−1F8C, 51 −I−1F8D, 51 −I−1F93, 51 −I−1F99, 51 −I−1F9A, 52 −I−1F9E, 52 Ethernet cable specification, 30 Ethernet cable, colour code , 31 Ethernet cable, design, 30 Ethernet connection, 29 External voltage supply, 32

EDSMF2191IB EN 2.0

H Hardware version, type code, 13 I I−1000: EPL device type, 42 I−1001: EPL error register, 42 I−1006: EPL cycle time, 42 I−1018: EPL identity object, 42 I−1030: EPL MAC address, 43 I−1101: EPL telegram counter, 43 I−1400: EPL address RPDO, 43 I−1401: EPL address RPDO, 44 I−1402: EPL address RPDO, 44 I−1600: EPL number of RPDO, 44 I−1601: EPL number of RPDO, 45 I−1602: EPL number of RPDO, 45 I−1A00: EPL TPDO, 46 I−1C0A: EPL CN: Telegr. collisions, 46 I−1C0B: EPL CN: Loss of synchr., 46 I−1C0F: EPL CN: Frame error (CRC), 47 I−1C10: EPL CN: Link interruptions, 47 I−1E40: EPL IP address, 48 I−1F81: EPL node declaration CN, 49 I−1F82: EPL feature flags, 50 I−1F83: EPL version, 50 I−1F8C: EPL communication status, 51 I−1F8D: EPL CN: Max. user data PRes RPDO, 51 I−1F93: EPL device address, 51 I−1F99: EPL CN: Max. MN detection time, 51 I−1F9A: EPL host name, 52 I−1F9E: EPL reset command, 52 Identification, 13 Indexing the Lenze codes, 36 Initial switch−on, 37 Installation, 22 −electrical, 24 −mechanical, 23 Interface, 17 Interfaces, 15 Internal voltage supply, 32 M Mechanical installation, 23 N Nameplate, 13 Network segment, 26 Network topology, 17 Notes, definition, 9 O Operation in the standard Ethernet, 28 Order designation, 17 P POWERLINK communication (technical data), 19 POWERLINK connection, 29 POWERLINK network segment, 26 Processing time, 20 Product description, 12 −application as directed, 12 Product features, 14 Protection of persons, 11 Protective insulation, 18 R Residual hazards, 11 S Safety instructions, 10 −application as directed, 12 −definition, 9 −device− and application−specific, 11 −layout, 9 Setting the node address, 35 Software version, type code, 13 Specification of the Ethernet cable, 30 Standard Ethernet connection, 26 Standard Ethernet operation, 28 Switch on, initial, 37

EDSMF2191IB EN 2.0

T Technical data, 17 Terminal data, 33 Topologies in the POWERLINK network segment, 27 Transmission mode, 17 Type code, 13 −finding, 13 V Validity of the documentation, 5 Voltage supply, 32 −internal, 32 Voltage supply: external, 32 W Wiring according to EMC, 24

Lenze Automation GmbH

Hans−Lenze−Str. 1 D−31855 Aerzen Germany Service Lenze Service GmbH Breslauer Straße 3 D−32699 Extertal Germany  +49(0)51 54 /82−0  008000/ 2446877 (24 h helpline)  +49(0)51 54 /82 − 28 00  +49(0)5154/ 82−11 12  [email protected]  [email protected]  www.Lenze.com EDSMF2191IB  .M\}  EN  2.0  TD17 10 9 8 7 6 5 4 3 2 1