Controller Installation Guide Application The FAC2611 Advanced Application Field Equipment Controller (FAC) is part of the Metasys® system Field Equipment Controller family. The FAC26 Series controllers run pre-engineered and user-programmed applications and provide the inputs and outputs required to monitor and ...
• Three fasteners appropriate for the mounting surface (M4 screws or #8 screws) • One 20 cm (8 in.) or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount (only) • Small straight-blade screwdriver for securing wires in the terminal blocks FAC2611 physical features Figure 1: FAC2611 physical f ...
vibration, such as duct work. • Do not mount the controller in areas where electromagnetic emissions from other devices or wiring can interfere with controller communication. Observe these additional guidelines when mounting a field controller in a panel or enclosure: • Mount the controller so that the ...
Débrancher l'alimentation avant de réaliser tout rac- cordement électrique afin d'éviter tout risque de décharge électrique. CAUTION Risk of Property Damage Do not apply power to the system before checking all wiring connections. Short circuited or improperly con- nected wires may result in permanent damage t ...
Note: The SA PWR terminal supplies 15 VDC. The SA PWR terminal can be used to connect (daisy chain) the 15 VDC power leads on the SA bus. FC bus port The FC bus port on the front of the controller is an RJ-12, 6-position modular jack that provides a connection for the Mobile Access Portal (MAP) Gateway, the Bluetooth ...
Note: The supply power wire colors may be different on transformers from other manufacturers. Refer to the transformer manufacturer’s instructions and the project installation drawings for wiring details. Important: Connect 24 VAC supply power to the field controller and all other network devices so th ...
Terminal block label Terminal label Function, ratings, requirements Determine wire size and maximum cable length +15 V 15 VDC Power Source for active (3-wire) input devices connected to the Universal INn terminals. Provides 100 mA total current Same as (Universal) INn Note: Use 3 ...
Terminal block label Terminal label Function, ratings, requirements Determine wire size and maximum cable length Analog Output - Voltage Mode (0–10 VDC) 10 VDC maximum output voltage 10 mA maximum output current Requires an external load of 1,000 ohm or more. Note: The Analog O ...
Terminal block label Terminal label Function, ratings, requirements Determine wire size and maximum cable length Analog Output - Voltage Mode (0–10 VDC) 10 VDC maximum output voltage 10 mA maximum output current Required an external load of 1,000 ohm or more. See Guideline A in ...
V) Inputs and Outputs by current and wire size Communications bus and supply power wiring guidelines The Communications bus and power supply terminal block rating and requirements table provides information about the functions, ratings, and requirements for the communication bus and supply power terminals ...