Pressure Leak Detector DLR-GS
Please read instructions prior to commencing any work
As of: 08/2020
Item no.: 604302
PRESSURE LEAK DETECTOR DLR-GS .. 06/08/2020
- 2 -
Overview of the design variants
DLR pressure leak detectors are available in different versions that are described more precisely
by the suffix characters. The levels of availability and the possible combinations depend on the de-
vice. Please contact our sales team. Phone +49 271 48964-0, email [email protected]
DLR- … .. P M N LE/LG Si
„Service indication”: integrated service
indicator (LED) with an adjustable service
period
Equipped with data transfer module (DTM)
for the LOD-Service.
Data transfer via Leak detection-Online-Di-
agnostic with Ethernet-module (LE) or GSM-
module (LG)
„N/ Feed required“: The leak detector indicates
by means of a diode that the pressure in the in-
terstitial space has decreased and that the
pressure must be built up again
„Manometer/ Pressure gauge“: The leak detector
is equipped with a digital pressure display in the
housing cover
„Protected“: Construction of the leak detector in a
weatherproof housing
„..“ = „Numerical value“ for the alarm-vacuum of the leak
detector.
„G = Gas (bottle)“: A pressure gas bottle is used for pressure
generation, usually nitrogen
„P = Pump“: A pump integrated in the leak detector is used for
pressure generation
„GS = Gas (bottle) static“: A static pressure generator must
be brought to the site since the leak detector does not have a
pump or automatic feed mechanism
„DLR/ Pressure Leak Detector Pipe“: The leak detector operates
with overpressures towards the atmosphere and is designed for ap-
plication on double-walled pipes
Design variations
PRESSURE LEAK DETECTOR DLR-GS ..
- 3 -
Table of Contents
1.
General ................................................................................. 5
1.1
Information ................................................................... 5
1.2
Explanation of Symbols ............................................... 5
1.3
Limitation of Liability .................................................... 5
1.4
Copyright ..................................................................... 5
1.5
Warranty Conditions .................................................... 6
1.6
Customer Service ........................................................ 6
2.
Safety ................................................................................... 7
2.1
Intended Use ............................................................... 7
2.2
Obligation of the Operating Company ......................... 7
2.3
Qualification ................................................................. 8
2.4
Personal Protective Equipment (PPE) ......................... 8
2.5
Fundamental Hazards ................................................. 9
3.
Technical Data of the Leak Detector ................................. 10
3.1
General Data ............................................................... 10
3.2
Electrical Data .............................................................. 10
3.3
Switching Values ......................................................... 11
3.4
Field of Application ...................................................... 12
4.
Design and Function........................................................... 14
4.1
Design .......................................................................... 14
4.2
Normal Operating Condition ........................................ 16
4.3
Function in Case of Leaks ........................................... 16
4.4
Overpressure Valve ..................................................... 16
4.5
Displays and Controls .................................................. 17
5.
Mounting the System .......................................................... 18
5.1
Basic Instructions ......................................................... 18
5.2
Leak Detector .............................................................. 18
5.3
Selecting the Pressure Gas Bottle and the Pressure
Reducer ....................................................................... 19
5.4
Setting up the Pressure Gas Bottle and Mounting
the Pressure Reducer .................................................. 19
5.5
Pneumatic Connection Lines, Requirements ............... 19
5.6
Completing Pneumatic Connections ............................ 19
5.7
Electrical Cables .......................................................... 20
5.8
Electrical Wiring Diagram ............................................ 21
5.9
Installation Examples ................................................... 23
6.
Commissioning ................................................................... 26
6.1
Commissioning the Pressure Gas Bottle ..................... 26
6.2
Commissioning the Leak Detector ............................... 26
6.3
Changing the Pressure Level ...................................... 27
7.
Functional Check and Maintenance .................................. 28
7.1
General ........................................................................ 28
7.2
Maintenance ................................................................ 28
7.3
Functional Check ......................................................... 28
Table of Contents
PRESSURE LEAK DETECTOR DLR-GS .. 06/08/2020
- 4 -
8.
Alarm (Malfunction) ............................................................. 31
8.1
Alarm ............................................................................ 31
8.2
Malfunction ................................................................... 31
8.3
How to Behave ............................................................. 31
9.
Spare Parts .......................................................................... 32
10. Accessories ......................................................................... 33
11. Disassembly and Disposal ................................................. 34
11.1 Disassembly ................................................................. 34
11.2 Disposal ....................................................................... 34
12. Appendix .............................................................................. 35
12.1 Dimensions and Drilling Pattern, Plastic Housing ........ 35
12.2 Dimensions and Drilling Pattern, Stainless Steel
Housing for Installation Outdoors (IP 54) ..................... 36
12.3 Declaration of Conformity ............................................. 37
12.4 Declaration of Performance ......................................... 38
12.5 Manufacturer’s declaration of compliance .................... 38
12.6 Certification TÜV Nord ................................................. 39
Table of Contents
PRESSURE LEAK DETECTOR DLR-GS ..
- 5 -
1.
General
1.1
Information
These instructions provide important notes on using the leak detector
DLR-GS. Complying with all safety instructions and guidelines is a
prerequisite for safe working.
Furthermore, any local regulations for prevention of accidents appli-
cable at the site of use of the leak detector and general safety instruc-
tions must be complied with.
1.2
Explanation of Symbols
In these instructions, warnings are marked with the adjacent symbol.
The signal word expresses the level of hazard.
DANGER:
Imminently hazardous situation which, if not avoided, will result in
death or serious injury
WARNING:
Potentially hazardous situation which, if not avoided, could result in
death or serious injury
CAUTION:
Potentially hazardous situation which, if not avoided, could result in
minor or moderate injury
INFORMATION:
Highlights useful tips, recommendations and information
1.3
Limitation of Liability
All information and instructions in this documentation have been com-
piled considering the applicable norms and regulations, the state of
the art and our longstanding experience.
SGB does not assume any liability in case of:
Noncompliance with these instructions
Unintended use
Use of unqualified personnel
Unauthorized modifications
Connection to systems not approved by SGB
1.4
Copyright
The contents, texts, drawings, images and other representations are
copyrighted and subject to industrial property rights. Any misuse is
punishable.
General
PRESSURE LEAK DETECTOR DLR-GS .. 06/08/2020
- 6 -
1.5
Warranty Conditions
We provide warranty for the leak detector DLR-GS for a period of 24
months from the day of installation on site in accordance with the
General Terms & Conditions.
The maximum warranty period is 27 months from our date of sale.
Warranty is subject to submission of the functional/test report on ini-
tial commissioning by qualified personnel.
Stating the serial number of the leak detector is required.
The obligation of warranty shall cease to exist in case of
- inadequate or improper installation
- unintended use
- modifications/repairs without the manufacturer's consent.
Our warranty does not include parts, which may be perished prema-
ture due to their consistence or category of usage (e.g. pumps,
valves, gaskets, etc.). Furthermore, we are not liable for defects or
corrosion damages caused by humid or inappropriate installation en-
vironments.
1.6
Customer Service
Our customer service is available for any inquiries.
For information on contacts please refer to our website sgb.de/en or
the label of the leak detector.
General
PRESSURE LEAK DETECTOR DLR-GS ..
- 7 -
2.
Safety
2.1
Intended Use
For double-walled pipes/fittings installed underground or indoors
only.
The leak detector alarm pressure must be at least 1 bar higher
than the maximum feed pressure in the product-transporting pipe.
Grounding in accordance with valid regulations1.
Tightness of the leak detection system according to section 7.3.4.
Leak detector installed outside of the explosive area.
Lead-throughs for connection lines into and out of the manhole
chamber must be sealed gas-tight.
Leak detector (electric) cannot be turned off.
Use of the leak detection medium compressed air only with con-
veyed media with flash point > 60°C (> 55°C for Germany accord-
ing to TRGS 509 and 751).
Use of the leak detection medium nitrogen with conveyed media
with flash point > 60°C and ≤ 60°C if the interstitial space is zone 2
(> 55°C and ≤ 55°C for Germany according to TRGS 509 and
751).
Section 3.4.5 must be complied with.
Any claims arising from misuse are excluded.
2.2
Obligation of the Operating Company
The leak detector DLR-GS is used in a commercial environment. The
operating company is therefore subject to statutory occupational
safety obligations.
In addition to the safety instructions in this documentation, all applica-
ble safety, accident prevention and environmental regulations must
be adhered to. In particular:
- Compiling a risk assessment and implementing its results in a di-
rective
- Performing regular checks as to whether the directive is in compli-
ance with the current standards
- The directive includes, among others, how to react to an alarm that
might arise
- Arranging for an annual functional check
1 For Germany: e.g. EN 1127
WARNING!
Danger from
misuse
WARNING!
Danger in case
of incomplete
documentation
Safety
PRESSURE LEAK DETECTOR DLR-GS .. 06/08/2020
- 8 -
2.3
Qualification
The personnel must be capable of independently recognizing and
avoiding potential risks based on their qualifications.
Companies commissioning leak detectors should have completed re-
spective training with SGB, through SGB or its authorized representa-
tive.
National guidelines must be adhered to.
For Germany:
Technical service qualification for installation, commissioning and
maintenance of leak detection systems
2.4
Personal Protective Equipment (PPE)
Personal protective equipment must be worn during work.
- Wear necessary protective equipment for the relevant work
- Note and comply with existing PPE signs
Entry in the "Safety Book"
Wear HV vest
Wear safety footwear
Wear hard hat
Wear gloves – where necessary
Wear safety goggles – where necessary
2.4.1 Personal Protective Equipment working with systems that may be subject to risk of explo-
sion
The parts listed here refer in particular to safety when working with
systems that may be subject to risk of explosion.
WARNING!
Danger to hu-
mans and the en-
vironment in case
of inadequate
qualification
Safety
PRESSURE LEAK DETECTOR DLR-GS ..
- 9 -
If work is performed in areas in which an explosive atmosphere must
be expected, the minimum required equipment is as follows:
Suitable clothing (risk of electrostatic charge)
Suitable tools (in accordance with EN 1127)
Suitable combustible gas indicator calibrated to the existing vapor-
air mixture (work should be performed only at a concentration of
50 % below the lower explosion limit)2
Measuring equipment to determine the oxygen content in the air
(Ex/O-meter)
2.5
Fundamental Hazards
DANGER
From electric current
When working on the leak detector, it must be disconnected from the
power supply unless stated otherwise in the documentation.
Comply with relevant regulations regarding electric installation,
explosion protection (e.g. EN 60 079-17), if necessary, and accident
prevention.
DANGER
From explosive vapor-air mixtures
Ensure there is no gas present prior to performing work
Comply with explosion regulations, e.g. BetrSichV (and/or directive
1999/92/EC and the laws of the respective member states resulting
therefrom) and/or others.
DANGER
From working in shafts
The leak detectors are mounted outside the manhole chambers.
Pneumatic connection is usually performed inside the manhole cham-
ber. Therefore, the chamber must be entered for mounting.
Before entering, the corresponding protective measures must be
taken and it must be ensured that no gas and sufficient oxygen are
present.
2 Other manufacturers' or countries' regulations may provide different percentages.
Safety
PRESSURE LEAK DETECTOR DLR-GS .. 06/08/2020
- 10 -
3.
Technical Data of the Leak Detector
3.1
General Data
Dimensions and drilling pattern:
see sections 12.1 and 12.2
Weight:
2.1 kg (plastic housing)
6.3 kg (stainless steel housing)
Storage temperature range:
-40°C to +70°C
Operating temperature range:
0°C to +40°C (plastic housing)
-40°C to +60°C (stainless steel
housing incl. heating)
Housing protection class:
IP 30 (plastic housing)
IP 54 (stainless steel housing)
3.2
Electrical Data
Power supply
100 … 240 V AC
optional:
24 V DC
Power input:
10 W (without heating)
28 W (incl. heating at 20°C)
Terminals 5, 6 (external signal):
max. 24 V DC; max. 300 mA*
Terminals 11…13 (voltage-free):
DC ≤ 25 W or AC ≤ 50 VA
Terminals 17…19 (voltage-free):
DC ≤ 25 W or AC ≤ 50 VA
Fuse protection:
max. 10 A
Overvoltage category:
2
* With Ethernet board max. 150 mA
Technical Data
PRESSURE LEAK DETECTOR DLR-GS ..
- 11 -
3.3
Switching Values
The following abbreviations are used in the table:
pO
Maximum operating pressure in the inner pipe (feed pressure + dynamic
pressure + pressure due to geodetic height differences)
pAON
Switching value "Alarm ON"; the alarm will be triggered at this pressure level
at the latest
pSETPT
Pressure setpoint which should be built up according to the manufacturer’s
recommendation. Note: there is no display indication when this pressure is
reached.
This setting can be varied, in which case the following must be noted:
- Upwards: the test pressure must be at least 1.3 times higher
- Downwards: the alarm pressure is reached considerably more quickly
pTEST
Minimum test pressure of the interstitial space
pPR
Set pressure on the pressure reducer (must be adjusted in some cases, ac-
cording to the pressure setpoint)
With the function “Feed required” display, this pressure value is about 1 bar
higher than the alarm pressure.
Further switching values:
pAOFF
Switching value "Alarm OFF"; the alarm will be deactivated if this value is
exceeded
type 1 to 8 approx. 250 mbar
type 10 to 16 approx. 500 mbar
3 Switches 1 to 9 for determining the pressure level
Type DLR-GS
pO
[bar]
pAON
[bar]
pSETPT
[bar]
Switch position of
dip switch
pTEST
[bar]
pPR
[bar]
1
pressureless
> 1
5
3
> 6,5
5
2
< 1
> 2
6
> 8
6
3
< 2
> 3
7
> 9
7
4
< 3
> 4
8
> 10
8
6
< 5
> 6
10
> 13
10
8
< 7
> 8
12
> 16
12
10
< 9
> 10
14
> 18
14
13
< 12
> 13
17
> 22
17
16
< 15
> 16
20
> 26
20
Special values agreed between
SGB and customer
Technical Data
PRESSURE LEAK DETECTOR DLR-GS .. 06/08/2020
- 12 -
3.4
Field of Application
3.4.1 Interstitial space requirements
Proof of pressure resistance of the interstitial space (see section
3.3, column "pTEST" minimum test pressure of the interstitial space)
Proof of suitability of the interstitial space (for Germany: proof of
usability from construction authority).
Sufficient passage in the interstitial space for the leak detection
medium (air/nitrogen)
Tightness of the interstitial space according to this documentation.
The number of interstitial spaces to be monitored depends on the
total interstitial space volume. According to EN 13160, 10 m3 may
not be exceeded. To be able to test the tightness of the interstitial
space, it is recommended not to exceed 4 m3.
The pipeline length (per duct) to be monitored should not exceed
2500 m and must correspond with the specifications for the pipe
permit.
3.4.2 Pipes
Double-walled pipes made of metal or plastic, in factory or on-site
construction.
For Germany: Additional requirements may result from the respec-
tive permits.
ONLY for applications without temperature variations of more than
10°C (e.g. double-walled pipes installed underground or indoors
– no hot media).
3.4.3 Fittings
Double-walled fittings made of metal or plastic in factory or on-site
construction.
For Germany: with proof of usability from construction authority,
unless it is part of the pipe permit.
ONLY for applications without temperature variations of more than
10°C (e.g. double-walled pipes installed underground or indoors
– no hot media).
3.4.4 Conveyed product
Liquids hazardous to water, even with a flash point of ≤ 60°C (for
Germany ≤ 55°C according to TRGS 509 and TRGS 751). Chapter
3.4.5 is to be observed.
The conveyed product may not react with the leak detection me-
dium.
Technical Data
PRESSURE LEAK DETECTOR DLR-GS ..
- 13 -
3.4.5 Interaction between interstitial space, leak detection medium and operating mode
Regardless whether there is permeation in the interstitial space or
not, the leak detection medium nitrogen is to be used for all applica-
tions if the goods to be conveyed have a flash point ≤ 60°C (≤ 55°C
for Germany according to TRGS 509 and TRGS 751).
This specification is based on a risk evaluation according to the di-
rective 2014/34/EU (explosion directive). The risk evaluation was per-
formed based on the table in section 3.3 (informative) for EN 13160.
If the evaluation of the device categories has different results due to
operational regulations or for any other reasons, the use of the leak
detector must be checked separately.
Technical Data
PRESSURE LEAK DETECTOR DLR-GS .. 06/08/2020
- 14 -
4.
Design and Function
4.1
Design
Interior view of plastic housing with:
01
Signal lamp "Alarm", red
09
Signal lamp "Operation", green
23
Signal lamp "Refilling required", yellow
29
Button "Commissioning" (filling)
69
Buzzer
71
“Mute” Button
75
Display board
76
Main board
102
Pressure sensor
140
Contact for serial data transfer
75
102
09
01
71
69
23
76
140
Design and Function
PRESSURE LEAK DETECTOR DLR-GS ..
- 15 -
Interior view of stainless-steel housing, weather-protected, with:
44
Solenoid valve
69
Buzzer
70-1
Overpressure valve (interstitial space)
70-2
Overpressure valve (supply)
75
Display board
76
Main board
102
Pressure sensor
140
Contact for serial data transfer
141
Keypad terminal strip
144
Temperature switch, frost protection
75
102
69
76
140
141
144
Design and Function
PRESSURE LEAK DETECTOR DLR-GS .. 06/08/2020
- 16 -
The pressure leak detector DLR-GS monitors both walls of the dou-
ble-walled system for leaks. The monitoring pressure during operation
is higher than any pressure on the inner or outer wall, so that leaks
will be indicated by a pressure drop.
Inert gas, air from a pressure gas bottle or from a pressure gas sys-
tem can be used as leak detection media. If air is used, it must be
dried to a relative humidity of less than 10%.
The current pressure is shown on the display in mbar/bar or PSI4:
Values of less than 150 mbar or less than 2.18 PSI will not be dis-
played.
Values of up to 990 mbar will be displayed in mbar and without
decimal.
Values from 1 bar are displayed in bar with two decimals and from
10 bar with one decimal.
Values in PSI are displayed with one or two decimals.
4.2
Normal Operating Condition
The normal operating condition is achieved during the initial operation
through pressure buildup to the operating pressure, generally with a
mobile pressure tank.
The existing pressure in the interstitial space is monitored with a pres-
sure sensor in the leak detector. Any minor leaks will lead to a fall in
pressure. The result of this is that the requirements for the impermea-
bility of the interstitial space(s) and the connection(s) must be set very
high to assure trouble free operation for one year.
4.3
Function in Case of Leaks
If there is a leak in the inner or outer wall, gas will leak from the inter-
stitial space. The pressure drops.
An optical and audible alarm will be triggered when the alarm pres-
sure is reached, which will open the voltage-free contacts.
Optionally, an additional relay can be used to establish voltage-free
contacts when the specified “Refilling required” pressure is not
reached. The pressure value for “Refilling required” is approx. 1 bar
above the "Alarm ON” switching value.
4.4
Overpressure Valve
An overpressure valve is not provided in the leak detector, but it can
be installed if the application requires it. (Please consult with the man-
ufacturer).
4 The change of the bar and PSI settings is performed at the factory. This change can also be performed on
site following coordination with the manufacturer.
Design and Function
PRESSURE LEAK DETECTOR DLR-GS ..
- 17 -
4.5
Displays and Controls
4.5.1 Display
Signal lamps
Operating Con-
dition
Refilling acti-
vated or re-
quired
Alarm condition
Alarm, audible
alarm acknow-
ledged
Device malfunc-
tion
OPERATION:
green
ON
ON
ON
ON
ON
ALARM: red
OFF
OFF
ON
BLINK-
ING
ON
REFILLING:
yellow
OFF
ON
ON
ON
OFF
4.5.2 Function "Turn off audible alarm signal"
Shortly press "Mute" button once, audible signal turns off, the red
LED blinks.
Pressing the button again will turn the audible signal on.
This function is not available during normal operating conditions and
malfunctions.
4.5.3 Function "Testing the optical and audible alarm signal"
Press and hold the "Mute" button (about 10 seconds). The alarm will
be triggered until the button is released.
This inquiry is only possible if the pressure in the system has ex-
ceeded the "Alarm OFF" pressure.
Design and Function
PRESSURE LEAK DETECTOR DLR-GS .. 06/08/2020
- 18 -
5.
Mounting the System
5.1
Basic Instructions
Prior to commencing work, the documentation must be read and
understood. In case of ambiguities, please refer to the manufac-
turer.
The safety instructions in this documentation must be adhered to.
Only qualified service companies may be used for installation.
Comply with relevant regulations for prevention of accidents.
Lead-throughs for pneumatic and electric connection lines, through
which the explosion atmosphere can carry over, must be sealed
gas-tight.
Comply with explosion regulations (if required), e.g. BetrSichV
(and/or directive 1999/92/EC and the laws of the respective mem-
ber states resulting therefrom) and/or others.
Compliance with the relevant traffic regulations is required when
transporting pressure gas bottles to and from the construction site.
The pressure gas bottle must be protected from falling over at the
construction site.
If nitrogen is used, sufficient ventilation must be provided if com-
missioning/operation is performed in enclosed spaces. Attach in-
formation sign.
Provide a test valve at the end facing away from the leak detector
at the end of the pipe(s)/fitting(s).
Before entering inspection chambers, the oxygen content must be
tested and the inspection chamber flushed if necessary.
If metallic connection lines are used, it must be ensured that the
power supply grounding is on the same potential as the pipe to be
monitored.
Notes on personal protective equipment are provided in chapter
2.4.
5.2
Leak Detector
(1) Generally mounted on walls with plugs and screws.
(2) In a dry room, or outdoors in a suitable housing.
(3) If mounted in a protective box: additional external signal or alarm
forwarding via voltage-free contacts to a switchboard or similar
device.
(4) NOT in potentially explosive areas.
(5) Dimensions of housings and drilling patterns are illustrated in Ap-
pendix 12.1 and 12.2, respectively.
Mounting
PRESSURE LEAK DETECTOR DLR-GS ..
- 19 -
5.3
Selecting the Pressure Gas Bottle and the Pressure Reducer
(1) The pressure reducer must have an integrated overpressure
valve.
(2) The range of settings for the pressure reducer to be used must
be selected in correspondence with the application or the pres-
sure to be set. (see section 3.3).
(3) The maximum pressure setting on the pressure reducer should
not exceed the test pressure for the interstitial space
(SGB recommendation).
5.4
Setting up the Pressure Gas Bottle and Mounting the Pressure Reducer
(1) Set up and secure pressure gas bottle, e.g. using a bracket and
safety chain intended for this purpose.
(2) Close safety chain.
(3) Remove protective cover and mount pressure reducer to bottle.
(4) Close shut-off valve on the pressure reducer.
5.5
Pneumatic Connection Lines, Requirements
Pressure resistance of the metal (generally Cu) or plastic pipes
must at least correspond with the test pressure in the interstitial
space. Also applies to fittings and screwed connections. Note tem-
perature range, especially when using plastic.
Inside clearance
at least 4 mm with inert gas as leak detection medium
at least 6 mm with air as leak detection medium
50 m should not be significantly exceeded, but if this happens: In-
stall pipe with greater inside clearance using transition pieces.
The full cross section must be maintained. Do not push in or bend5.
Install metal or plastic pipes underground or plastic pipes above-
ground outdoors in protective pipes.
Seal the protective pipe gas-tight and protect from moisture.
Avoid build-up of electrostatic charges (e.g. during pulling of lines).
5.6
Completing Pneumatic Connections
5.6.1 Between pressure reducer and leak detector
(1) Select suitable test equipment to connect the pressure re-
ducer to the leak detector. Recommendation: Use the test
equipment SGB item no.: 115520
(2) Mount the test equipment with pressure reducer at the pres-
sure gas bottle.
(3) Connect the test equipment to the leak detector.
5 If necessary, install commercial fittings for plastic pipes (specified bending radii).
Mounting
PRESSURE LEAK DETECTOR DLR-GS .. 06/08/2020
- 20 -
5.6.2 Between leak detector and interstitial space, test valves
(1) Select and install suitable pipe.
(2) During installation of the tube/pipe, ensure again that the tubes
are protected against damage when the manhole chamber is en-
tered.
(3) Complete the relevant connection (according to the illustrations in
the following images)
(4) According to the specifications of the manufacturer of the pipe/in-
terstitial space
5.6.2.1 Flanged screw connections (for flanged pipes)
(1) Lubricate O-rings
(2) Insert spacer ring loosely into the screw socket
(3) Slide union nut and pressure ring over the pipe
(4) Hand-tighten union nut
(5) Tighten union nut until need for increased force is clearly noticeable
(6) Final assembly: Tighten by another ¼ turn
5.6.2.2 Clamping ring screw connection for metal and plastic pipes
(1) Insert support sleeve (only plastic pipe) into the pipe end
(2) Insert the pipe (with support sleeve) as far as it will go
(3) Tighten nut of screw connection by hand to the resistance; then
turn further 1¾ turns with the wrench
(4) Release nut
(5) Tighten nut by hand until stronger resistance
(6) Final assembly of the screw connection by tightening ¼ turn
5.6.2.3 Quick screw connections for PA tubing
(1) Cut PA tube to length at a right angle
(2) Unfasten union nut and slide over the end of the pipe
(3) Slide pipe onto nipple up to the beginning of the thread
(4) Hand-tighten union nut
(5) Wrench-tighten union nut until need for increased force is notice-
able (approx. 1 to 2 turns)
5.7
Electrical Cables
Power connection:
-
2.5 mm2 without ferrule
-
1.5 mm2 with ferrule and plastic collar
Voltage-free contacts and external signal:
-
1.5 mm2 without ferrule
-
0.75 mm2 with ferrule and plastic collar
Mounting
PRESSURE LEAK DETECTOR DLR-GS ..
- 21 -
5.8
Electrical Wiring Diagram
(1) Power supply: according to label imprint
(2) Fixed wiring, i.e. no plug or switch connections
(3) Regulations of power supply companies must be adhered to6.
(4) Terminal layout: (see also section 5.9.3)
1 / 2
Power connection (100…240 V AC)
CAUTION: both terminals exist in duplicate!
3 / 4
not used, internal assignment
5 / 6
External signal (24 V in case of alarm, can be turned
off by activating the "Audible alarm signal" button)
11 / 12
Voltage-free contacts (opened in case of alarm or loss
of power)
12 / 13
As above, but contacts closed
17 / 18 /19
Voltage-free contacts at “Refilling on”:
17/18 opened
18/19 closed;
Voltage-free contacts at “Refilling off” or in currentless
condition:
17/18 closed
18/19 opened
21 / 22
Occupied (with internal sensor)
40 / 41
24 V DC as permanent power supply to power other
assemblies or, for a device with a supply voltage of 24
V DC, the power supply is connected here
6 For Germany: also VDE regulations
Mounting
PRESSURE LEAK DETECTOR DLR-GS .. 06/08/2020
- 22 -
5.8.1 Connecting the wires
(1) Press down the orange point with a screwdriver. This opens the
tension spring of the terminal.
(2) Insert cable into the open terminal.
(3) Hold cable and remove screwdriver.
(4) Check cable for a tight fit and install more cables to the terminals
using the same process.
Mounting
PRESSURE LEAK DETECTOR DLR-GS ..
- 23 -
5.9
Installation Examples
5.9.1 Leak detector DLR-GS .. (single, underground pipeline and/or above-ground riser in the
building
01
Signal lamp "Alarm", red
51
Test coupling
02
Shut-off cock
57
Test valve
05
Shut-off valve (on pressure reducer)
69
Buzzer
06.2
Coupling, on the leak detector side
71
“Mute” Button
09
Signal lamp "Operation", green
77
Pressure regulating valve
14
Pressure reducer
88
Double-walled pipe
19
Pressure accumulator
99
Control shaft
25
Canister shut-off valve
103
Display
29
Button "Filling"
104
On-site compressed air system
45
Signal lamp "Refilling", yellow
(e.g. air/nitrogen)
88
88
57
57
45
71
69
01
09
06.2
14
05
77
25
19
bar
0
16
10
bar
0
100
200
300
02
99
Mounting
PRESSURE LEAK DETECTOR DLR-GS .. 06/08/2020
- 24 -
5.9.2 Leak detector DLR-GS .. (underground pipeline, series connection)
01
Signal lamp "Alarm", red
51
Test coupling
02
Shut-off cock
57
Test valve
05
Shut-off valve
69
Buzzer
06.2
Coupling, on the leak detector side
71
“Mute” Button
09
Signal lamp "Operation", green
76
Main circuit board
14
Pressure reducer
77
Pressure regulator
19
Pressure cylinder
88
Double-walled pipe
25
Cylinder shut-off valve
99
Inspection chamber
29
Button "Filling"
102
Pressure sensor
30
Housing
103
Display
45
Signal lamp "Refilling", yellow
99
99
57
57
88
88
88
76
30
02
14
05
77
25
19
bar
0
16
10
bar
0
100
200
300
06.2
Mounting
PRESSURE LEAK DETECTOR DLR-GS ..
- 25 -
5.9.3
Block diagram
01
Signal lamp "Alarm", red
59.4
Relay "Refilling"
09
Signal lamp "Operation", green
69
Buzzer
24.1
Fuse "Power supply", 2 A
71
“Mute” Button
24.2
Fuse "Solenoid valve", 0.5 A
76
Main board
24.3
Fuse "External signal", 1 A
102
Pressure sensor
29
Button "Filling"
103
Display
44
Solenoid valve
105
Control unit
45
Signal lamp "Refilling", yellow
116
Power supply unit 24 V DC
59.2
Relay "External signal"
140
Contacts for serial data transfer
59.3
Relay "Alarm"
141
Keypad terminal strip
Mounting
PRESSURE LEAK DETECTOR DLR-GS .. 06/08/2020
- 26 -
6.
Commissioning
(1) Only perform commissioning once the steps in section
5 "Mounting" have been fulfilled.
(2) Flush the interstitial space with inert gas if walls of storage me-
dium are not impermeable.7
(3) If a leak detector is commissioned on a pipe (fitting) that is al-
ready in operation, special protective measures must be taken
(e.g. testing that the leak detector and/or the interstitial space is
free of gas). Additional measures may be necessary depending
on the local conditions and must be assessed by qualified per-
sonnel.
6.1
Commissioning the Pressure Gas Bottle
(1) Turn pressure regulator all the way back.
(2) Insert a suitable manometer (indicating range) into the coupling
51 of the test equipment and insert the test equipment into the
coupling (6.2) of the leak detector.
(3) Open cylinder shut-off valve (if necessary, test tightness between
pressure reducer and bottle)
(4) Set pressure on the pressure reducer using the pressure regula-
tor on the pressure reducer according to section 3.3 (adjust dur-
ing pressure build-up, if necessary).
(5) After completion of the functional check:
- Close shut-off valve on the pressure reducer.
- Close cylinder shut-off valve.
- Remove pressure reducer from the bottle (Caution: Gas will
escape until the pressure reducer has no pressure).
- Install protective cover on bottle.
6.2
Commissioning the Leak Detector
(1) Tightness of the interstitial space prior to commissioning is as-
sumed
(2) Switch on line voltage
(3) Ascertain lighting of "Operation" and "Alarm" signal lamps and
sounding of the audible alarm. If necessary, turn off audible
alarm signal.
(4) Pressure build-up the interstitial space:
Open the shut-off cock 2.2 at the test equipment to build up the
pressure in the leak detector and the interstitial space.
With very large interstitial spaces it may be necessary to switch
bottles (see section 5.3 in conjunction with sections 5.4 and 6.1)
Note: If no pressure build-up is achieved with the pressure gas
bottle connected, the leak must be located and corrected (check
the settings for the pressure reducer as well, if necessary).
7 For Germany: Additional DIBT requirements must be considered for such double-walled pipes.
Commissioning
PRESSURE LEAK DETECTOR DLR-GS ..
- 27 -
CAUTION: Display on the leak detector (display) begins with a
pressure from 150 mbar.
(5) Check all connections for leaks with a foaming agent.
(6) Perform a functional check according to section 7.3.
6.3
Changing the Pressure Level
(1) Switch positions 1-9 are designed to select the pressure level.
(2) The assignment of the switch position to the relevant pressure
level is shown in chapter 3.3.
(3) If the switch positions 1-9 are changed at the construction site, it
must be assured that the operating pressure to be built up does
not exceed the test pressure of the interstitial space.
Commissioning
PRESSURE LEAK DETECTOR DLR-GS .. 06/08/2020
- 28 -
7.
Functional Check and Maintenance
7.1
General
(1) If the leak detection system has been properly installed and is
free of leaks, trouble-free operation can be assumed.
(2) Even very minor leaks will trigger an alarm.
(3) In the event of an alarm, determine the cause and fix it quickly.
(4) The leak detector must be disconnected from power for any re-
pairs to be performed on the leak detector.
(5) A loss of power is indicated by the "Operation" signal lamp going
off. Alarm signals are triggered via the voltage-free relay contacts
(if used for alarm transmission) if contacts 11 and 12 were used.
After the power loss, the green signal lamp lights up again and
the voltage-free contacts no longer generate an alarm (unless the
power loss has caused the pressure to drop below the alarm
pressure).
7.2
Maintenance
Maintenance work and functional checks must be performed by
trained personnel only8.
Once a year to ensure functional and operational safety.
Test scope according to section 7.3.
Compliance with the conditions according to sections 5 and 6 must
also be tested.
Comply with explosion regulations (if required), e.g. BetrSichV
(and/or directive 1999/92/EC and the laws of the respective mem-
ber states resulting therefrom) and/or others.
7.3
Functional Check
The functional and operational safety tests must be performed:
after each commissioning
in accordance with the time intervals listed in section 7.29
each time a malfunction has been corrected
7.3.1 Test scope
(1) Coordinate the work to be performed with those responsible for
operation on site, if necessary
(2) Observe the safety instructions for working with the product to be
conveyed.
8 For Germany: Technical service according to water law with expertise in leak detection systems. For Eu-
rope: Authorization by the manufacturer
9 For Germany: In addition, national laws apply (e.g. AwSV)
Functional Check and Maintenance
PRESSURE LEAK DETECTOR DLR-GS ..
- 29 -
(3) Check the test valve at the end of the interstitial space pointing
away from the leak detector for tightness and contamination, and
clean it, if necessary
(4) Checking the free passage of air in the interstitial space (section
7.3.2)
(5) Testing the switching values (section 7.3.3)
(6) Tightness test following commissioning or correction of malfunc-
tions (section 7.3.4)
(7) Creating the operating condition (section 7.3.5)
(8) A qualified person must complete a test report, confirming func-
tional and operational safety.
7.3.2 Checking the free passage of air in the interstitial space
If several interstitial spaces are connected in parallel, each one of
them must be checked for passage.
(1) Insert measuring gauge into the test coupling 6.2. The current
pressure in the interstitial space will be displayed.
(2) Open the test valve for the first connected interstitial space.
(3) Check whether the measuring gauge registers a pressure drop.
(4) Close the test valve.
(5) Repeat process from paragraph (2) to (4) for each additional test
valve of the interstitial space(s) connected to this leak detector.
(6) The pressure drop generated by the test can be compensated as
follows:
a) Remove the measuring gauge from the coupling and insert it
into the test coupling 51 of the test equipment.
b) Insert the test equipment into coupling 6.2.
c)
Connect the pressure cylinder to the test equipment acc. To
chapter 5.3 (5.4 and 6.1)
d) Open the shut-off cock 2.2.
e) Pressure build-up until pressure setpoint; during filling, moni-
tor the pressure on the pressure reducer (test pressure must
not be exceeded) and re-adjust if necessary
f)
Once the filling process has been completed, close the shut-
off valve on the pressure reducer, and disconnect the meas-
uring gauge and pressure cylinder.
7.3.3 Testing the switching values
(1) If several interstitial spaces are connected through a distribution
system, close all shut-off cocks on the distributor.
(2) Insert the test equipment into the coupling 6.2
(3) Insert the manometer into the test coupling 51 of the test equip-
ment.
Functional Check and Maintenance
PRESSURE LEAK DETECTOR DLR-GS .. 06/08/2020
- 30 -
(4) Connect the pressure cylinder to the test equipment acc. To
chapter 5.3 (5.4 and 6.1).
(5) Bleed the shut-off cock 2.1 to determine the switching values
“Refilling required” (the yellow signal lamp, if available, lights up)
and for “Alarm ON”. Record the values.
(6) Close the shut-off cock.
(7) (Slowly) open the shut-off cock 2.2. During the pressure build-up,
check the switching values for “Alarm OFF” and “Refilling (here:
Filling) OFF” (if available). Record the values.
(8) Close the shut-off cocks. Remove the pressure cylinder properly
and decouple the test equipment.
(9) The test is considered passed if the values specified in section
3.3 have been satisfied.
(10) Open all shut-off cocks in the connection line(s).
7.3.4 Tightness test following commissioning or correction of malfunctions10
(1) Insert measuring gauge into the coupling 6.2. The measuring
gauge will display the current pressure.
(2) The tightness test is approved for one year of trouble-free opera-
tion if the following conditions have been met:
Determine the difference between the measured values for “Re-
filling (Filling) OFF” and “Alarm ON” and convert into mbar
(x 1000). Divide the calculated value by 8760. This results in a
maximum tolerated pressure drop (per hour) to prevent triggering
an alarm before one year has passed. If the determined value
cannot be measured, multiplication of the pressure drop will re-
sult in the same multiplication of the test time.
Example: Difference between the above-named switching values:
1.75 bar (value measured on site)
1.75 x 1000 = 1750
1750 / 8760 = 0.2 mbar/h (admissible pressure drop)
The measuring gauge available on site “only” shows a value of
5 mbar. This means the readability is 25 times (5 / 0.2). This ex-
tends the test time to 25 hours.
(3) Disconnect the measuring gauge after the tightness test has
been completed.
7.3.5 Creating the operating condition
(1) Seal the housing and the test valve(s) at the end of the interstitial
space pointing away from the leak detector.
(2) If shut-off cocks have been installed in the connection lines, they
must be sealed in an opened position (if connected to an intersti-
tial space).
10 This section assumes that the operating pressure has been built up in the interstitial space and the pres-
sure has been compensated.
Functional Check and Maintenance
PRESSURE LEAK DETECTOR DLR-GS ..
- 31 -
8.
Alarm (Malfunction)
8.1
Alarm
(1) The red signal lamp lights up (yellow also lights up if existing),
the audible signal sounds.
(2) Turn the audible signal off.
8.2
Malfunction
(1) In case of a malfunction, only the red signal lamp will light up
(yellow is off), and at the same time the audible signal cannot be
acknowledged.
8.3
How to Behave
(1) Inform the installation company immediately and state the display
from the preceding paragraph.
(2) Determine the cause for the alarm, fix it, and then perform a func-
tional check for the leak detection system according to section
7.3.
Alarm
PRESSURE LEAK DETECTOR DLR-GS .. 06/08/2020
- 32 -
9.
Spare Parts
See also online shop shop.sgb.de
Switchboard (for plastic housing):
331670
Switchboard VD SMD L with LED and
transformer 630 mA (please indicate pressure level)
331725
Display board for electronic leak indicator, VL, VLR, DL,
DLG, DLR-G, DLR-P
Manifold:
412690
Manifold DLR-GS with sensor 20 bar and flange plate in-
cluding test coupling (please indicate screw connection)
412691
Manifold DLR-GS with sensor 40 bar and flange plate in-
cluding test coupling (please indicate screw connection)
Pressure sensors:
344520
Sensor 20 bar for DLR-GS
344540
Sensor 40 bar for DLR-GS
Housing:
220220
Housing lower part, "ABS" RAL 7033 (dark gray)
220210
Upper housing part, "ABS", RAL 7171 (light gray)
220214
Upper housing part, light gray, only mounted display
Spare Parts
PRESSURE LEAK DETECTOR DLR-GS ..
- 33 -
10. Accessories
For accessories please refer to our online shop shop.sgb.de, e.g.
-
Installation kits
-
Electrical isolators
-
Manifolds
-
Pressure reducers
-
Remote data transmission (LOD)
-
P version, housing with IP 54
Accessories
PRESSURE LEAK DETECTOR DLR-GS .. 06/08/2020
- 34 -
11. Disassembly and Disposal
11.1 Disassembly
Prior to and during works, make sure the unit is free of gas and the
breathing air contains sufficient oxygen levels.
Seal any openings gas-tight through which an explosion atmosphere
can carry over.
Avoid using spark-producing tools (saws, parting grinders, etc.) for
disassembly whenever possible. Should this be unavoidable, how-
ever, comply with EN 1127 or the area must be free of explosive at-
mosphere.
Avoid the build-up of electrostatic charges (e.g. through friction).
11.2 Disposal
Properly dispose of contaminated components (possibly through out-
gassing).
Properly dispose of electronic components.
Disassembly and Disposal
PRESSURE LEAK DETECTOR DLR-GS ..
- 35 -
12. Appendix
12.1 Dimensions and Drilling Pattern, Plastic Housing
D = 110
170
230
30
100
210
265
~ 250
Space needed
to remove the
housing lid
Space needed
to open the
housing lid
Appendix
PRESSURE LEAK DETECTOR DLR-GS .. 06/08/2020
- 36 -
12.2 Dimensions and Drilling Pattern, Stainless Steel Housing for Installation Outdoors
(IP 54)
D = 80
Ø8,5
220
243
268
250
280
320
Appendix
PRESSURE LEAK DETECTOR DLR-GS ..
- 37 -
12.3 Declaration of Conformity
We,
SGB GmbH
Hofstraße 10
57076 Siegen, Germany,
hereby declare in sole responsibility that the leak detectors
DLR-GS
are in conformity with the essential requirements of the EU directives
listed below.
In case the device is modified or used in a way that has not been
agreed with us, this declaration shall lose its validity.
Number/short title
Satisfied regulations
2014/30/EU
EMC Directive
EN 61 000-6-3: 2011
EN 61 000-6-2: 2006
EN 61 000-3-2: 2015
EN 61 000-3-3: 2014
2014/35/EU
Low Voltage Directive
EN 60 335-1: 2012
EN 61 010-1: 2010
EN 60 730-1: 2011
2014/34/EU
Equipment for Explo-
sive Atmospheres
The pneumatic components of the leak detector may be connected
to spaces (interstitial spaces of containers/pipes/fittings) that require
category 3 devices. The following documents have been consulted:
EN 1127-1: 2011
The ignition hazard assessment did not result in any additional haz-
ards.
Conformity is declared by:
ppa. Martin Hücking
(Technical Director)
As of: 02/2019
Appendix
PRESSURE LEAK DETECTOR DLR-GS .. 06/08/2020
- 38 -
12.4 Declaration of Performance
Number: 008 EU-BauPVO 2015
1.
Unique identification code of the product type:
Pressure leak detector type DLR-GS
2.
Usage purpose:
Class I pressure leak detector for monitoring double-walled
pipes
3.
Manufacturer:
SGB GmbH, Hofstr. 10, 57076 Siegen, Germany
Phone: +49 271 48964-0, E-Mail: [email protected]
4.
Authorized representative:
n/a
5.
System of assessment and verification of constancy of performance:
System 3
6.
In the case of the declaration of performance concerning a construction product that is cov-
ered by a harmonized standard:
Harmonized standard: EN 13160-1-2:2003
Notified body: TÜV Nord Systems GmbH & Co.KG, CC Tankanla-
gen, Große Bahnstraße 31, 22525 Hamburg, Germany
Identification number of the notified testing laboratory: 0045
7.
Declared performance:
Essential characteristics
Performance
Harmonized norm
Pressure switch points
Passed
EN 13160-2: 2003
Reliability
10,000 cycles
Pressure test
Passed
Volume flow rate test in the
alarm switch point
Passed
Function and tightness of
the leak detection system
Passed
Temperature resistance
depending on housing type
0°C .. +40°C
-40°C .. +60°C
8.
Signed for and on behalf of the manufacturer by:
Dipl.-Ing. M. Hücking, Technical Director
Siegen, 31-10-2015
12.5 Manufacturer’s declaration of compliance
Compliance of the leak detector with the “Muster-Verwaltungs-
vorschrift Technische Baubestimmungen“ (sample administrative reg-
ulation technical building regulations) is hereby declared.