All safety related regulations, local codes and instructions that appear in the

manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. SPECIFICATIONS 1. POWER: 12 to 42 VDC *(Loop powered). The power supply must have a 30 mA min. capacity. [* Min. voltage must be increased to include the drop across any current display indicator] 2. INPUT: RTD 2, 3, or 4 wire, 100 ohm platinum, alpha=0.00385 (DIN 43760), alpha=0.00392, or resistance [selectable via DIP switch] Excitation: 0.170 mA nominal Lead resistance: Less than 0.5°C with 15 ohms max. per lead Note: There is no lead compensation for 2 wire input. Field calibration should be accomplished with equivalent series resistance. 3. OUTPUT: 4 to 20 mA Linear output with Temperature or resistance input. Ripple: Less than 15 mV peak-to-peak max., across 250 load resistor (up to 120 Hz frequencies). 4. RANGE & ACCURACY: (12 Bit resolution) Accuracy: ± ( 0.075% Range + 0.1°C [Conformity]) at 23°C after 20 min. warm-up, conforming to ITS-90. Note: RTD conformity does not apply to resistance input. Relative Humidity: Less than 85% RH (non-condensing) Span: The input span can be set to a min. of 1/8 of the full scale range, anywhere within that range. Range Accuracy: INPUT RANGE DIP SWITCH TYPE RANGE 4 6 7 8 TEMPERATURE & OHMS RANGE RANGE ACCURACY RTD alpha = 0.00385 0 0 0 0 0 -160 to 654°C  0.61°C 1 0 0 0 1 -108 to 207°C  0.24°C 2 0 0 1 0 -5 to 414°C  0.31°C 3 0 0 1 1 194 to 608°C  0.31°C RTD alpha = 0.00392 0 1 0 0 0 -157 to 640°C  0.60°C 1 1 0 0 1 -106 to 203°C  0.23°C 2 1 0 1 0 -5 to 406°C  0.31°C 3 1 0 1 1 190 to 596°C  0.30°C OHMS 0 0 1 0 0 35.5 to 331.0   0.222  1 0 1 0 1 57.0 to 178.5   0.091  2 0 1 1 0 98.0 to 252.0   0.116  3 0 1 1 1 173.5 to 316.5   0.107  Note: DIP switch settings ON = 1 OFF = 0 USER PROGRAMMABLE INPUT (RTD alpha=0.00385 (DIN 43760), alpha=0.00392, or resistance) 12 to 42 VDC LOOP POWERED (4 to 20 mA Output) MICROPROCESSOR CONTROLLED SIMPLE ADJUSTABLE RANGE SETTING (Using Input Signal) RTD BREAK DETECTION MOUNTS ON “T” AND “G” STYLE DIN RAILS 2-WAY ELECTRICAL ISOLATION (INPUT/OUTPUT & POWER) HIGH-DENSITY PACKAGING (22.5 mm wide) WIDE OPERATING TEMPERATURE RANGE DESCRIPTION The IRMA accepts a 2, 3, or 4 wire RTD or resistance input and converts it into a 4 to 20 mA current output. The 4 to 20 mA output is linearly proportional to the temperature or the resistance input. This output is ideal for interfacing to indicators, chart recorders, controllers, or other instrumentation equipment. The IRMA is loop-powered which means that the same two wires are carrying both the power and the output signal. The unit controls the output current draw from 4 to 20 mA in direct proportion to the input while consuming less than 4 mA for operation. The conversion to a current output signal makes the IRMA less susceptible to noise interference and allows accurate transmission over long distances. Two-Way isolation allows the use of grounded RTD’s which can provide additional noise reduction benefits. The IRMA uses an eight position DIP switch to accomplish the input sensor configuration, range selection, and unit calibration. A simple range setting technique (Field Calibration) is used so the actual input signal adjusts the output current for scaling. This technique eliminates the need for potentiometers which are vulnerable to changes due to vibration. The unit is equipped with a universal mounting foot for attachment to standard DIN style mounting rails, including top hat rail (T) according to EN 50 022 - 35 X 7.5 and 35 X 15, and G profile according to EN 50 035 - G 32. MODEL IRMA - INTELLIGENT RTD MODULE WITH ANALOG OUTPUT POWER/ OUTPUT + - 1 2 3 4 5 6 3.11 (79.0) (83.8) 3.30 .886 (22.5) M2160B RTD S + - SWITCH OFF = 0 DIP SWITCH SETTINGS: RANGE RANGE RTD/OHMS OPEN SEN DN/UP 385/392 BASIC CAL FIELD CAL OUTPUT CAL RANGE 8 7 SENSOR DOWN OPEN SEN 392 385 RTD TYPE UP OHMS RTD 0 4 1 0 5 1 1 0 6 0 2 1 3 0 1 0 0 0 1 1 1 ON = 1 TEST 2 1 4 3 7 6 5 8 M2161A ON SWITCH SWITCH SWITCH IRMA RED LION CONTROLS MODEL IRMA YORK, PA. MADE IN U.S.A. DIMENSIONS In inches (mm) CAUTION: Risk of Danger. Read complete instructions prior to installation and operation of the unit. MODEL NO. DESCRIPTION PART NUMBER IRMA Intelligent RTD Module IRMA2003 ORDERING INFORMATION Bulletin No. IRMA-F Drawing No. LP0393 Released 12/09 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839 www.redlion.net 1 AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

Open Sensor Detection

The output can be set to go Upscale or Downscale for the detection of an open sensor. The Upscale setting makes the output go to 22.5 mA (nominal). The Downscale setting makes the output go to 3.5 mA (nominal). This setting is always active, so changes in the setting are effective immediately. Calibration Malfunction If the unit has scaling problems (current remains at 3.5 mA nominal), check the voltage between the RTD- Input (-) and TEST pad (+) [located next to the DIP switches on the side of the unit]. For normal operation the voltage is 0 V (nominal). If the voltage is +3 V(nominal), a problem occurred storing information in the E2PROM. When this happens, perform a Basic Calibration and then a Field Calibration. Turn off power for 5 seconds. Turn on power and check the voltage between the TEST pad (+) and RTD- Input (-). If the voltage is still +3 V(nominal), contact the factory. EMC INSTALLATION GUIDELINES Although this unit is designed with a high degree of immunity to ElectroMagnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of electrical noise, source or coupling method into the unit may be different for various installations. In extremely high EMI environments, additional measures may be needed. For the purpose of EMC testing, both input and output lines on the unit were connected with 25 feet (8 m) of cable. Cable length, routing and shield termination are very important and can mean the difference between a successful or a troublesome installation. Listed below are some EMC guidelines for successful installation in an industrial environment. 1. Use shielded (screened) cables for all Signal and Control inputs. The shield (screen) pigtail connection should be made as short as possible. The connection point for the shield depends somewhat upon the application. Listed below are the recommended methods of connecting the shield, in order of their effectiveness. a. Connect the shield only at the rail where the unit is mounted to earth ground (protective earth). b. Connect the shield to earth ground at both ends of the cable, usually when the noise source frequency is above 1 MHz. c. Connect the shield to common of the unit and leave the other end of the shield unconnected and insulated from earth ground. 2. Never run Signal or Control cables in the same conduit or raceway with AC power lines, conductors feeding motors, solenoids, SCR controls, and heaters, etc. The cables should be run in metal conduit that is properly grounded. This is especially useful in applications where cable runs are long and portable two-way radios are used in close proximity or if the installation is near a commercial radio transmitter. 3. Signal or Control cables within an enclosure should be routed as far away as possible from contactors, control relays, transformers, and other noisy components. 4. In extremely high EMI environments, the use of external EMI suppression devices, such as ferrite suppression cores, is effective. Install them on Signal and Control cables as close to the unit as possible. Loop the cable through the core several times or use multiple cores on each cable for additional protection. Install line filters on the power input cable to the unit to suppress power line interference. Install them near the power entry point of the enclosure. The following EMI suppression devices (or equivalent) are recommended: Ferrite Suppression Cores for signal and control cables: Fair-Rite # 0443167251 (RLC #FCOR0000) TDK # ZCAT3035-1330A Steward #28B2029-0A0 Line Filters for input power cables: Schaffner # FN610-1/07 (RLC #LFIL0000) Schaffner # FN670-1.8/07 Corcom #1VR3 Note: Reference manufacturer’s instructions when installing a line filter. 5. Long cable runs are more susceptible to EMI pickup than short cable runs. Therefore, keep cable runs as short as possible. 2 SPECIFICATIONS (Cont’d) 5. SENSOR BREAK DETECTION: Upscale to 22.5 mA (nominal) or Downscale to 3.6 mA (nominal) [selectable via DIP switch] 6. RESPONSE TIME: 400 msec (to within 99% of final value w/step input; typically, response is limited to response time of probe.) 7. DIELECTRIC WITHSTAND VOLTAGE: 1500 VAC for 1 minute Working Voltage: 50 VAC from input to output. 8. CERTIFICATIONS AND COMPLIANCES: SAFETY IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment for measurement, control, and laboratory use, Part 1. ELECTROMAGNETIC COMPATIBILITY Notes: 1. This device was designed for installation in an enclosure. To avoid electrostatic discharge, precautions should be taken when the device is mounted outside an enclosure. When working in an enclosure, (ex. making adjustments, setting switches etc.) typical anti-static precautions should be observed before touching the device. 2. Self-recoverable loss of performance during EMI disturbance at 10 V/m: Analog output signal may deviate during EMI disturbance. For operation without loss of performance: Unit is mounted in a metal enclosure (Buckeye SM7013-0 or equivalent). I/O and power cables are routed in metal conduit connected to earth ground. 9. ENVIRONMENTAL CONDITIONS: Operating Temperature Range: -25°C to 75°C (-13°F to 167°F) Storage Temperature Range: -40°C to 85°C (-40°F to 185°F) Vibration according to IEC 68-2-6: Operational 5 to 150 Hz in X, Y, Z direction for 1.5 hours, 2 g’s. Shock according to IEC 68-2-27: Operational 30 g’s, 11 msec in 3 directions Temperature Coefficient: ± 0.01% of input range per °C Altitude: Up to 2000 meters. 10. MOUNTING: Universal mounting foot for attachment to standard DIN style mounting rails, including top hat (T) profile rail according to EN50022 - 35 x 7.5 and 35 x 15, and G profile rail according to EN50035 - G32. 11. CONNECTION: Compression type terminal block 12. CONSTRUCTION: High impact green plastic case 13. WEIGHT: 2.7 oz (76.54 g) Immunity to EN 50082-2 Power frequency magnetic fields EN 61000-4-8 Level 4; 30 A/m Electrostatic discharge EN 61000-4-2 Level 2; 4 Kv contact 1 Level 3; 8 Kv air Electromagnetic RF fields EN 61000-4-3 Level 3; 10 V/m 2 80 MHz - 1 GHz Fast transients (burst) EN 61000-4-4 Level 4; 2 Kv I/O Level 3; 2 Kv power RF conducted interference EN 61000-4-6 Level 3; 10 V/rms 150 KHz - 80 MHz Emissions to EN 50081-2 RF interference EN 55011 Enclosure class A LOOP POWER CIRCUITRY 4 5 CIRCUITRY CONTROL PWM POWER SUPPLY 4V 3V 1.7V CIRCUITRY PROCESS CONVERTER A/D 2 1 3V 0.170mA POWER/ OUTPUT 3 RTD BLOCK DIAGRAM AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

All conductors should meet

voltage and current ratings for each terminal. Also, cabling should conform to appropriate standards of good installation, local codes and regulations. It is recommended that power supplied to the unit be protected by a fuse or circuit breaker. When wiring the unit, use the numbers on the label to identify the position number with the proper function. Strip the wire, leaving approximately 1/4" (6 mm) of bare wire exposed (stranded wire should be tinned with solder). Insert the wire into the terminal, and tighten the screw until the wire is clamped tightly. INPUT AND POWER/OUTPUT CONNECTIONS INPUT When connecting the RTD or resistance device, be certain that the connections are clean and tight. Attach the device to terminals #2 and #3. Install a copper sense lead of the same gauge as those used to connect the device. Attach one end of the wire at the probe where the lead connected to terminal #2 is attached and the other end to terminal #1. This configuration will provide complete lead wire compensation. If a sense wire is not utilized, then Terminal #1 should be shorted to terminal #2. To avoid errors due to lead wire resistance, field calibration should be performed with a series resistance equal to the total lead resistance in the system. Always refer to the probe manufacturer’s recommendations for mounting, temperature range, shielding, etc. POWER/OUTPUT The unit has the power and current output sharing the same two wires (loop- powered). Connect DC power to terminals #4 and #5, observing the correct polarity, with a current meter/indicator connected in between so that the output current can be monitored. Be certain that the DC power is relatively “clean” and within the 12 to 42 VDC range at the terminals. The current meter voltage drop must be included in the power supply considerations. DIP SWITCH SETTING DESCRIPTIONS Range switch settings (ON = 1 OFF = 0) FACTORY SETTINGS The unit is shipped from the factory calibrated for a 4 to 20 mA output using a type 385 RTD in range 0. The IRMA should be calibrated by the operator for the application environment it will be used in. If the unit is not recalibrated by the operator, the following table lists the temperature ranges for each RTD type. SWITCH DESCRIPTION 1 OUTPUT CAL Output Calibration 2 FIELD CAL Field Calibration 3 BASIC CAL Basic Calibration 4 385/392 Select RTD alpha - 0.00392 (ON) / 0.00385 (OFF) 5 OPEN SEN DN/UP Open Sensor Detection - Upscale (ON) / Downscale (OFF) 6 RTD/OHMS Select Input Type - Ohms (ON) / RTD (OFF) 7 8 RANGE Sensor Range - 2 switch combination setting DIP SWITCH RANGE 7 8 0 0 0 1 0 1 2 1 0 3 1 1 2 1 3 RTD S - + - RTD + 1 S 2 3 RTD 1 S 2 + 3 - 3-WIRE RTD 4-WIRE RTD N.C. 2-WIRE RTD 150C to 595C 0 392 150C to 606C 0 385 TEMPERATURE RANGE RANGE TYPE Current Display Indicator or Power Supply 12 to 42 VDC 4 to 20 mA ± A OUTPUT POWER/ + 4 5 - 6 1 2 3 Monitoring Instrument RTD S + - M2160B IRMA 3 AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

Field Calibration with an Accurate Adjustable Resistance Source

1.1 Connect an Adjustable Resistance Source with an accuracy of 0.03% to the RTD input terminals using a third sense wire. For 2 wire sensors short terminal #1 to terminal #2. 1.2 Set the Type and Range for the RTD or resistance used in your application (DIP switches #4, #6, #7 and #8). (RTD alpha=0.00385, Range 0 shown) 1.3 Set the FIELD CAL switch (#2) ON. [Current goes to 3.6 mA (nominal)] 1.4 Set the resistance source to the desired resistance for the 4 mA output. For 2 wire sensors add the system lead resistance to the desired value. 1.5 Set the OUTPUT CAL switch (#1) ON. [Current stays at 3.6 mA (nominal)] 1.6 Adjust the input resistance up until the output equals 4 mA. 1.7 Set the OUTPUT CAL switch (#1) OFF. [Current increases to 22.3 mA (nominal)] 1.8 Set the resistance source to the desired resistance for the 20 mA output. For 2 wire sensors add the system lead resistance to the desired value. 1.9 Set the OUTPUT CAL switch (#1) ON. [Current decreases to 20.5 mA (nominal)] 1.10 Adjust the input resistance down until the output equals 20 mA. 1.11 Set the OUTPUT CAL switch (#1) OFF. 1.12 Set the FIELD CAL switch (#2) OFF. 1.13 Disconnect the resistance source from the IRMA and connect the actual sensor to be used in the application. 1 6 5 4 3 2 8 7 ON 1 6 5 4 3 2 8 7 ON 1 6 5 4 3 2 8 7 ON 1 6 5 4 3 2 8 7 ON 1 6 5 4 3 2 8 7 ON 1 6 5 4 3 2 8 7 ON 1 6 5 4 3 2 8 7 ON Step 1.11 Step 1.12 Step 1.2 Step 1.3 Step 1.5 Step 1.7 Step 1.9 Power Supply 12 to 42 VDC Current Display 4 to 20 mA ± A POWER/ 6 OUTPUT + 4 5 - Indicator Adjustable 3 1 2 Resistance Source RTD S - + MC2160X IRMA TEST OUTPUT CAL FIELD CAL BASIC CAL 385/392 OPEN SEN DN/UP RTD/OHMS RANGE RANGE DIP SWITCH SETTINGS: ON = 1 OFF = 0 M2161A 1 2 4 5 6 7 8 ON Test Pad RED LION CONTROLS MADE IN U.S.A. MODEL IRMA YORK, PA. Field Calibration Wiring Allow a 30 minute warm-up period before starting Field Calibration. Field Calibration scales the 4 to 20 mA output to a temperature or resistance input. This procedure assigns an input value to 4 mA and an input value to 20 mA. The microprocessor handles configuring the output so it is linear to the temperature or resistance input. The Field Calibration procedure is described below. Note: The unit needs to have the Field Calibration completed by the operator before normal operation. To abort this calibration and reset to the previous settings, set the FIELD CAL switch OFF prior to the final OFF setting of the OUTPUT CAL switch (Step 1.11) and turn off power. Wait 5 seconds and then turn on power and the previous settings will be loaded. RTD temperature to resistance conversion table CALIBRATION PROCEDURES 1.0 Field Calibration Temperature C alpha 0.00385 ohms Temperature °C alpha 0.00385 ohms alpha 0.00392 ohms -160 alpha 0.00392 ohms 35.53 300 212.03 214.08 -150 34.38 39.71 350 229.69 232.07 -100 60.25 38.64 400 247.05 249.77 -50 80.30 59.55 410 250.49 253.28 0 79.96 100.00 450 264.13 267.18 50 119.40 100.00 500 280.92 119.75 284.30 100 138.5 139.20 550 297.42 301.13 150 157.33 158.36 590 310.41 314.38 190 172.17 173.48 600 313.63 317.66 200 175.85 177.23 640 326.38 330.68 250 194.09 195.80 650 329.54 333.90 4 AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

12 to 42 VDC

Current Display 4 to 20 mA ± A POWER/ 6 OUTPUT + 4 5 - Indicator Adjustable 3 1 2 Resistance Source RTD S - + MC2160X IRMA 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 7 8 ON ON 3 1 2 5 4 6 7 8 Step 2.1 Steps 2.3 to 2.15 Step 2.16 2.0 Basic Calibration (Factory Calibration) Basic Calibration Wiring The Basic Calibration should only be performed with an ambient temperature between 21°C and 29°C. The Basic Calibration was performed on the unit at the factory and generally does not need to be done again. This procedure initializes the unit by calibrating the input circuitry. The Basic Calibration should be performed only if a condition exists as described in the “Calibration Malfunction” section. After completion of this calibration, the unit needs to be scaled in Field Calibration. The Basic Calibration procedure is described below. Note: To abort this calibration and reset to the previous settings, set the BASIC CAL switch OFF prior to the final setting of the OUTPUT CAL switch (Step 2.15) and turn off power for 5 seconds. Then turn on power and the previous settings will be loaded. 2.1 Connect an Adjustable Resistance Source with an accuracy of 0.03% to the RTD input terminals using a third sense wire. Set the RANGE (#7), TYPE (#4), OUTPUT CAL (#1), and FIELD CAL (#2) switches OFF. Set the BASIC CAL switch (#3) ON. 2.2 Apply power and allow a 30 minute warm-up period. [Current goes to 3.5 mA (nominal)] 2.3 Set the OUTPUT CAL switch (#1) ON and then OFF. 2.4 Set the resistance source to 40 ohms and wait 5 seconds. 2.5 Set the OUTPUT CAL switch (#1) ON and then OFF. 2.6 Set the resistance source to 60 ohms and wait 5 seconds. 2.7 Set the OUTPUT CAL switch (#1) ON and then OFF. 2.8 Set the resistance source to 100 ohms wait 5 seconds. 2.9 Set the OUTPUT CAL switch (#1) ON and then OFF. 2.10 Set the resistance source to 175 ohms and wait 5 seconds. 2.11 Set the OUTPUT CAL switch (#1) ON and then OFF. 2.12 Set the resistance source to 250 ohms and wait 5 seconds. 2.13 Set the OUTPUT CAL switch (#1) ON and then OFF. 2.14 Set the resistance source to 315 ohms and wait 5 seconds. 2.15 Set the OUTPUT CAL switch (#1) ON and then OFF. 2.16 Set the BASIC CAL switch (#3) OFF. [Current increases to 3.6 mA (nominal) or more] 2.17 Perform a Field Calibration. (See Section 1.0) TEST OUTPUT CAL FIELD CAL BASIC CAL 385/392 OPEN SEN DN/UP RTD/OHMS RANGE RANGE DIP SWITCH SETTINGS: ON = 1 OFF = 0 M2161A 1 2 4 5 6 7 8 ON Test Pad RED LION CONTROLS MADE IN U.S.A. MODEL IRMA YORK, PA. 5 AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

An aluminum manufacturer had the

requirement to heat soak aluminum ingots before they were to advance into their hot roll mill. The system is being controlled by a PLC that allows the material to move to the next of twelve zones as soon as the aluminum ingot reaches the soak temperature. An IRMA, RTD Loop powered signal conditioner was used to transmit each zone temperature, measured by an RTD sensor, to the PLC. Because the heat soak procedure was accomplished in an eighty foot furnace tunnel, a relatively long wire run was required to connect each RTD with the PLC. The IRMA transmitter converts and linearizes the RTD signal into a 4 to 20 mA signal that can be run long distances to connect to the PLC. TROUBLESHOOTING For further technical assistance, contact technical support at the appropriate company numbers listed. G Rail Installation To install the IRMA on a “G” style DIN rail, angle the module so that the upper groove of the “foot” catches under the lip of the top rail. Push the module toward the rail until it snaps into place. To remove a module from the rail, push up on the bottom of the module while pulling out away from the rail. T Rail Installation To install the IRMA on a “T” style rail, angle the module so that the top groove of the “foot” is located over the lip of the top rail. Push the module toward the rail until it snaps into place. To remove a module from the rail, insert a screwdriver into the slot on the bottom of the “foot”, and pry upwards on the module until it releases from the rail. INSTALLATION The unit is equipped with a universal mounting foot for attachment to standard DIN style mounting rails, including G profile rail according to EN50035 - G32 , and top hat (T) profile rail according to EN50022 - 35 x 7.5 and 35 x 15. The unit should be installed in a location that does not exceed the maximum operating temperature and provides good air circulation. Placing the unit near devices that generate excessive heat should be avoided. 6 3-WIRE RTD TO PLC ZONE 1 MC2160X POWER/ OUTPUT + - IRMA RTD S + 1 2 3 4 5 6 - PLC AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

This Page Intentionally Left Blank

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

The Company warrants the products it manufactures against defects in materials and workmanship

for a period limited to two years from the date of shipment, provided the products have been stored, handled, installed, and used under proper conditions. The Company’s liability under this limited warranty shall extend only to the repair or replacement of a defective product, at The Company’s option. The Company disclaims all liability for any affirmation, promise or representation with respect to the products. The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries, deaths, property damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be to any extent liable, including without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty Act (P.L. 93-637), as now in effect or as amended hereafter. No warranties expressed or implied are created with respect to The Company’s products except those expressly contained herein. The Customer acknowledges the disclaimers and limitations contained herein and relies on no other warranties or affirmations. Red Lion Controls Headquarters 20 Willow Springs Circle York PA 17406 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839 Red Lion Controls China Unit 101, XinAn Plaza Building 13, No.99 Tianzhou Road ShangHai, P.R. China 200223 Tel +86 21 6113-3688 Fax +86 21 6113-3683 Red Lion Controls Europe Printerweg 10 NL - 3821 AD Amersfoort Tel +31 (0) 334 723 225 Fax +31 (0) 334 893 793 Red Lion Controls India 54, Vishvas Tenement GST Road, New Ranip, Ahmedabad-382480 Gujarat, India Tel +91 987 954 0503 Fax +91 79 275 31 350 AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]