RAYPAK REPLACEMENT INSTRUCTIONS
PC BOARD & TEMPERATURE CONTROL (KIT #013464F)
FOR GAS POOL HEATERS WITH ELECTRONIC IGNITION (SEE “SCOPE” FOR MODELS)
IMPORTANT NOTICE
These instructions are intended for use by qualified personnel specifically trained and experienced in the installation of this
type of heating equipment and related system components. Installation and service personnel may be required to be li-
censed in some states. Installation or repairs performed by unqualified persons may void the warranty.
DANGER - SHOCK HAZARD
Make sure electrical power to the heater is disconnected to avoid potential serious injury or damage to components.
DANGER - PROPANE HAZARD
Make sure to determine if unit is propane and see special instructions on page 6.
SCOPE:
This version of the temperature control board has an integrated ignition module plus 3-wire temperature sensor. It is a di-
rect replacement for the following models: 185B, 206A, 207A, 265B, 266A, 267A, 268, 335B, 336A, 337A, 405B, 406A,
407A, 408.
P/N 241417 Rev 4
Effective:
12-04-12
Replaces: 10-07-11
MODELS
185B, 265B, 335B, 405B
PRODUCED NOV. 2003
THROUGH OCT. 2004
SERIAL # 0311 TO # 0410
MODELS
206A, 266A, 336A, 406A
207A, 267A, 337A, 407A
268, 408
PRODUCED NOV. 2004
THROUGH CURRENT
SERIAL # 0411 TO CURRENT
This Kit Includes:
(1) PC Control Board
(1) LCD Gasket
(5) Screws #6 x 3/8”
(1) Remote Mode Label
(1) Instructions
P/N 241417 Rev 4
Effective:
12-04-12
Replaces: 10-07-11
Page 2
ACCESSING THE CONTROL BOARD
1.
Turn off the power to the heater.
2.
Turn off the gas to the heater.
3.
B-Series: Remove front door by removing
the 4 door panel screws shown in Fig. 1 and
Fig. 2.
4.
A-Series: Remove front door by removing
the large door screw in front of unit as
shown in Fig. 1.
5.
Remove the four screws on the side of con-
trol panel. See Fig. 3 and Fig. 4.
6.
Lay control panel forward toward you to ac-
cess the back of the temperature control
board.
REMOVE THESE
SCREWS FOR B - SERIES
LARGE
DOOR
SCREW
FOR A-SERIES
Close-up
REMOVE THESE SCREWS
Fig. 1
Fig. 2
Fig. 3
Fig. 4
P/N 241417 Rev 4
Effective:
12-04-12
Replaces: 10-07-11
Page 3
REMOVING THE CIRCUIT BOARD
Make sure the power and gas are off.
1.
Unplug all connectors from old circuit board. See
Fig. 5.
2.
Unplug keypad ribbon from old circuit board.
3.
Remove screws as shown in Fig. 6.
4.
Remove old circuit board.
UNPLUG
ALL CONNECTORS
REMOVE KEYBOARD
RIBBON
REMOVE MOUNTING SCREWS
Fig. 5
Fig. 6
P/N 241417 Rev 4
Effective:
12-04-12
Replaces: 10-07-11
Page 4
PROPANE HEATERS ONLY:
PREPARE NEW REPLACEMENT CONTROL PCB FOR INSTALLATION
1.
Locate the proper propane tab on the board as shown in Fig. 7.
2.
Break off tab with pliers as shown in Fig. 8 & Fig. 9.
Note:
Requirements for Propane safety time vary by
area. Check your local and state code regula-
tions to determine whether your required
Propane safety time is 15 seconds or 90 sec-
onds.
PROPANE
TABS
15-Second
Safety Time
90-Second
Safety Time
BROKEN TAB
Fig. 7
Fig. 8
90-second
safety time
shown
Fig. 9
90-second
safety time
shown
P/N 241417 Rev 4
Effective:
12-04-12
Replaces: 10-07-11
Page 5
MODELS 185B, 265B, 335B & 405B, Lo NOx ONLY:
PREPARE NEW REPLACEMENT CONTROL PCB FOR INSTALLATION
1. DO NOT break tab See Fig. 10 and Fig. 11.
2. No additional wiring or connections are necessary for Lo NOx operation.
DO NOT
break
tab.
DO NOT
break tab.
After control PCB is
installed, remove and
discard flag label.
Fig. 10
Fig. 11
P/N 241417 Rev 4
Effective:
12-04-12
Replaces: 10-07-11
Page 6
Lo NOx MODELS 207A, 267A, 337A & 407A ONLY:
PREPARE NEW REPLACEMENT CONTROL PCB FOR INSTALLATION
1.
Locate Lo NOx tab and P-10 air switch terminal on the board as shown
in Fig. 12 and Fig. 13.
2.
Use pliers to break off the tab shown in Fig. 14.
3.
Attach the wire from the air switch to the P-10 location shown in Fig. 14.
P-10
Terminal
Lo NOx
Tab
Break
tab
Wire Air
Switch
to P-10
here.
Break and
remove tab
P10
Fig. 12
Fig. 13
Fig. 14
P/N 241417 Rev 4
Effective:
12-04-12
Replaces: 10-07-11
Page 7
GASKET INSTALLATION - ALL MODELS
1.
If the existing bezel gasket is shorter than the new gasket included with this
kit (see Fig. 15), remove the gasket completely from the bezel (Fig. 16).
2.
Before removing the backing on the new gasket, verify the installation place-
ment as per Fig. 17. The gasket is flexible and MUST be installed with all
edges straight. Verify the fit before peeling the adhesive backing.
Old Gasket
(Shorter)
NEW Gasket
(Longer)
Remove
shorter
gasket.
Line gasket up along this edge.
Touch gasket against these two stand-offs.
Fig. 15
Fig. 16
Fig. 17
P/N 241417 Rev 4
Effective:
12-04-12
Replaces: 10-07-11
Page 8
GASKET INSTALLATION - ALL MODELS (Continued)
3.
Remove the backing on the new gasket (Fig. 18) and
install as per Fig. 19.
Peel
adhesive
backing.
Fig. 18
When the gasket is installed correctly,there will be
a small part of the bezel showing within the display
window area. The other side of the gasket will be
even with the bezel display window edge.
Fig. 19
P/N 241417 Rev 4
Effective:
12-04-12
Replaces: 10-07-11
Page 9
REPLACEMENT CONTROL BOARD - ALL MODELS
1.
Mount the replacement control board to plastic bezel using (5) five mounting screws as
shown in Fig. 20.
2.
Reconnect all cable connections. WARNING: See page 10 for specific directions on
connecting P2 and P4.
3.
When installation is complete, attach the new Remote Mode Label as shown in Fig. 21.
Mount
Screws
Mount
Screws
Fig. 20
Fig. 21
P/N 241417 Rev 4
Effective:
12-04-12
Replaces: 10-07-11
Page 10
IMPORTANT
INSTALLING THE SAFETY AND GAS VALVE HARNESS ONTO P2 AND P4
Care must be taken when reinstalling the harness connections to P2 and P4.
The mating connections on the Advanced Flame Technology (AFT) board are rotated 180 degrees
compared to the connections on the previous Digital board. See Fig. 22 and Fig. 23.
Be sure the locking edge of the harness connector (Fig. 24) is oriented towards the board connector
locking tabs when installing all Control PCB wire connectors.
P2
P4
Digital Board
locking tabs
face out.
P2
P4
AFT Board
locking tabs
face in.
Harness Connector
Locking Edge
Fig. 22
Fig. 23
Fig. 24
P/N 241417 Rev 4
Effective:
12-04-12
Replaces: 10-07-11
Page 11
THERMOSTAT OPERATION - ADVANCED FLAME TECHNOLOGY (AFT) BOARD
PROGRAM BUTTON
LCD Display
Temp Buttons
Mode Button
The pool heater touchpad, located on the upper front panel
of the heater, allows the user to select either POOL or SPA
operation, and to adjust the setpoint temperature. The LCD
display window indicates the mode (OFF, SPA, POOL) and
the actual water temperature. A manual power switch pro-
vided below the touchpad turns the control power ON or
OFF.
Mode Button
The MODE button is used to select either POOL or SPA op-
eration. It also allows the user to turn the heater off elec-
tronically, allowing the LCD display to remain energized and
to continue showing the actual water temperature.
Temp Buttons
If the heater is in POOL or SPA mode, the desired water tem-
perature (SETPOINT) will also be displayed and may be ad-
justed using the UP or DOWN buttons.
Operation
In the POOL or SPA modes, the actual water temperature is
displayed along with the desired water temperature (SET-
POINT). When the water temperature is above the setpoint,
“Water Temp” will alternate with “No Demand.” When the
water temperature is below the setpoint and the heater is fir-
ing, “Water Temp” will alternate with “Heating.”
To adjust the setpoint temperature, make sure the control is
in the appropriate mode (POOL or SPA) and push the UP or
DOWN buttons.
Service Menu and Fault History
To access the Service Menu and fault history, press the
MODE and UP buttons simultaneously for 3 to 5 seconds.
The heater will continue to operate normally while in the
Service Menu. The first screen displayed is the Flame
Strength indicator, which indicates the pilot flame current
ALTERNATING DISPLAYS DURING HEATING
FLAME STRENGTH INDICATOR
SUPPLY VOLTAGE INDICATOR
RUN TIME INDICATOR
Press the DOWN button. The Supply Voltage screen indi-
cates the voltage supplied to the control board. Normal read-
ings range from 24 to 29 volts.
Press the DOWN button. The Run Time indicates the total
hours of operation for the pool heater, as measured by the
amount of time that the main gas valve has been powered.
The Cycle count indicates the number of on/off cycles of the
heater, as measured by the number of times the pilot valve
has been powered.
using a bar graph and numerical display. A signal of less
than 4 indicates a weak flame signal and may require serv-
ice. Refer to Section 5 – Troubleshooting for possible
causes and corrections.
FAULT HISTORY
Press the DOWN button. The Fault History can display up
to ten faults in memory. The order of the faults begins with
“Fault Last,” which is the most recent fault, and proceeds
through ten most recent messages in chronological order.
The second line of the display shows the fault message. If
there are no faults in the history buffer, the second line reads
“All Faults Clear.”
P/N 241417 Rev 4
Effective:
12-04-12
Replaces: 10-07-11
Page 12
Resets board to factory default
settings.
Resets faults in the History File.
Change from Fahrenheit to Celsius.
SPA setpoint maximum adjustment.
POOL setpoint maximum adjustment.
Set Factory Defaults
Refer to step one above to access the program screen. Set
Factory Defaults should appear on the screen. If it does not,
press the Mode button until Set Factory Defaults appears
on the digital display. Press and hold both UP and DOWN
buttons for 5-7 seconds until Defaults Set appears. This op-
eration resets the operating program to its factory default val-
ues. Both the POOL and SPA setpoints will revert to 65°F
(18.5°C) and both POOL and SPA maximum temperature
settings will be 104°F (40.0°C). The Control Lockout PIN will
be cleared and the control will resume normal operation.
Clear Faults
Refer to step one above to access the program screen.
Press the Mode button until Clear Faults appears on the
digital display. Press and hold both UP and DOWN buttons
for 5-7 seconds until Faults Cleared appears. This operation
resets the Fault History file to “0” and clears all the stored
faults.
Program Button
1)
Remove the four screws holding the control cover, and
swing the panel down so the back side of the board is
visible (see page 2). Locate the Program Mode button
(marked as SW1) as shown on page 15. Press and hold
the button (5-7 seconds) until Set Factory Defaults ap-
pears on the display. Release the program button.
2) Press the Mode button sequentially until the desired pro-
gram event is reached. There are 5 different events that
can be programmed. They appear in the sequence listed
below:
Fahrenheit or Celsius
Refer to step one above to access the program screen.
Press the Mode button until Fahrenheit or Celsius appears
on the digital display. The digital display is capable of dis-
playing Celsius as well as Fahrenheit temperatures. The UP
or DOWN buttons will select Fahrenheit or Celsius on the
temperature display. Choose the desired temperature scale.
Spa Max Temp – Spa Set Point Maximum Adjustment
Refer to step one above to access the program screen.
Press the Mode button until Spa Max Temp appears on the
digital display. Using the UP and DOWN buttons will change
the Maximum Temperature Setting to your desired value.
The control can be set for a maximum of 107°F.
Pool Max Temp – Pool Set Point Maximum Adjustment
Refer to step one above access into the program screen.
Press the Mode button until Pool Max Temp appears on the
digital display. Using the UP and DOWN buttons will change
the Maximum Temperature Setting to your desired value.
The control can be set for a maximum of 107°F.
Control Lockout
The heater is equipped with a Control Lockout feature to pre-
vent unauthorized tampering or adjustment of the control set-
tings. To lock out the controls, press the DOWN button and
Mode button for 5 seconds. Choose a three digit PIN, using
the UP and DOWN buttons to select the digits and the Mode
button to lock in selections. Confirm your selection and
record your PIN.
To unlock the controls, press any button to bring up the Enter
PIN menu. Enter the PIN that was used to lock the control.
Note that power cycling will not clear the lockout. Success-
fully unlocking the control will display “Lockout Cleared.”
Failure to enter the correct PIN will display “Invalid PIN.”
In the event that the user-selected PIN is lost or does not
clear the Control Lockout, use the Program Button to Set
Factory Defaults. This will clear the PIN and allow normal
operation and selection of a new PIN if desired. See the
Program Button directions on this page for details.
NOTE: Both the POOL and SPA setpoints will revert back
to 65°F (18.5°C) and the POOL and SPA maximum tem-
perature settings will be 104°F (40.0°C). These setpoints
will need to be readjusted to desired settings.
P/N 241417 Rev 4
Effective:
12-04-12
Replaces: 10-07-11
Page 13
STATUS AND DIAGNOSTICS
The digital thermostat models are programmed to display a variety of status and diagnostic messages, depending on the
operating conditions.
NOTE: The LCD temperature display may not agree with the temperature reading of your pool or spa thermometer. The
heater reads the water temperature at the inlet. Due to the circulation characteristics of any pool or spa, the water tem-
perature at the inlet to the heater may differ from that observed at a given location in the pool or spa.
Display
Condition
Heating
Call for heat established, flame present
Spark
Spark operating
No Demand
Heat demand is satisfied
The following conditions are displayed in Pool, Spa and Re-
mote modes.
Display
Condition
Sensor Failure Thermistor temperatures disagree by
more than 2°F
Sensor Open
Thermistor sensor failed open.
(Below -20°F)
Sensor Short
Thermistor sensor failed short.
(Above 217°F)
Flame w/o
CFH
Board is sensing flame when both main
and pilot valves are commanded shut.
PV Output
Fault
Pilot gas valve output is not in com-
manded state.
MV Output
Fault
Main gas valve output is not in com-
manded state.
LoNox Tab
Fault
Voltage is sensed at the Lo NOx termi-
nal on a non-Lo NOx heater (Lo NOx
tab is intact).
Internal Fault
Board fault, replace board.
EEPROM Fault Memory fault, reset set points, replace
board if fault does not clear.
Clock/ Fire-
man Sw
Time clock/fireman switch circuit is
open.
Low Temp
Lockout
Water temperature below 36°F.
The following heat status messages are displayed in Pool,
Spa, and Remote modes when there are no active fault con-
ditions.
The following conditions are displayed only while there is a
demand for heat present.
Display
Condition
Water Sw Open
Water pressure switch open.
Vent/Field
Sw #1
Vent spill switch/field switch #1 open.
Hi Limit 1 Fault
High limit 1 open.
Hi Limit 2 Fault
High limit 2 open.
Rollout Sw Open Rollout switch open.
Flow/Field SW #2 Flow switch/field switch #2 open.
Fan Lockout
3 fan switch faults within same heat
demand cycle, power must be cycled
to clear the fault.
Fan 5 Min Delay
Heater shut down for 5 minutes be-
cause LoNox fan switch didn't close.
Ignition Lockout
(Propane Tab
Broken)
Alternating with “No pilot sensed” -
Pilot flame not established within the
required time (15 sec or 90 sec).
Alternating with “Main Ign Failure” -
Pilot flame lost during the 8 second
trial to ignite the main burner.
Ignition Failure
(Propane Tab
Not Broken)
Alternating with “No pilot sensed” -
Pilot flame not established within 90
seconds.
Ign 6min Delay
(Propane Tab
Not Broken)
Alternating with “Main Ign Failure” -
Pilot flame lost 4 times within the 8
second trial to ignite the main burner.
Heater will lockout for 6 minutes be-
fore retrying.
P/N 241417 Rev 4
Effective:
12-04-12
Replaces: 10-07-11
Page 14
Pool Common
(BLK/ORN)
Spa Common
(ORN/BLK)
24VAC HOT
(BLU)
7-PIN Remote
Wiring Connector
REMOTE CONTROL INSTALLATION AND OPERATION
CAUTION: Before installing remote controls to the AFT thermostat model heaters, read the following:
The digital thermostat model is remote-ready in most cases. The digital liquid crystal display (LCD) shows the actual pool
temperature, operating status, and service codes (See examples below). The touch pad on the control panel allows you
to select the desired pool or spa temperature. It also indicates when a remote system is controlling the heater by display-
ing Remote in the display. When connecting the heater to a remote system, identify whether it is a two- or three-wire re-
mote system. Select the appropriate instruction listed below to properly install the remote to the heater.
OFF Mode
Heating in the POOL Mode
Heating in the SPA Mode
Remote Mode
REMOTE OPERATION
The AFT model heaters are equipped with the ability to work
with external remote controls. The supplied 7-pin remote
wiring connector supplies power out to either a toggle switch
or the switch contacts of a third party remote. The remote
works by either making or breaking the circuit created by the
remote wiring. Typically, a remote does not supply power to
the heater, it only provides a switching function to turn the
heater On or Off. If your remote is supplying its own volt-
age to the heater, it will not work with this heater and
may damage the digital circuit board.
For operation of the heater using the onboard thermostatic
controls with a time clock, see the “Time Clock / Fireman’s
Switch” section.
ACTIVATING THE REMOTE
To activate or deactivate the remote function, follow these
steps:
Note: Electrostatic Discharge (ESD) damage can be caused by direct or in-
direct contact with the wiring or circuit board. When one walks to the heater
area, an electrostatic charge accumulates on the body. Contact of a finger
allows the body to discharge, possibly causing device damage. This dam-
age can be limited if the service person discharges himself, following ESD
preventive/removal practices, and holds on to the heater enclosure for 5 sec-
onds before proceeding.
Press and hold the UP and DOWN arrow buttons for 3 to 5
seconds.
NOTE: When in remote operation, the keypad mode and
temp buttons are disabled.
The second line of the display will alternate even when the
unit is off (“No Demand”).
P/N 241417 Rev 4
Effective:
12-04-12
Replaces: 10-07-11
Page 15
REMOTE CONTROL WIRING
Important Installation Notes for Remote or External Wiring Configuration
•
Remote wiring must be run in a separate conduit.
•
Remote wiring must not be run parallel to high voltage lines.
•
For runs of under 30 feet, remote wiring should have stranded conductors with a minimum of 22 AWG, 600V, cable
twisting 1.5 to 2.5 in. lay and jacketed.
•
For runs over 30 feet, the conductors should be a minimum of 20 AWG, 600V, cable twisting 1.5 to 2.5 inch lay that is
shielded and jacketed.
•
Maximum cable length is 200 feet.
•
For both two- and three-wire remote systems, the provided 7-pin wiring connector must be utilized. Please refer to the
wiring instructions.
NOTE: The remote wires must be connected to the 7-pin connector before the connector
is plugged into the board.
2-Wire Remote Control (On-Off)
This application assumes that only one heating function (pool or spa) is required.
1.
Turn on power to the heater.
2.
For a 2-Wire Remote Control from a remote without its own sen-
sor, push the mode button to the “POOL” or “SPA” mode and set
the desired setpoint (eg. 102 °F for spa).
3.
For a 2-Wire Remote Control from a remote with its own sensor,
push the mode button “POOL” or “SPA” mode and set the tem-
perature to the highest setting available on the control. The actual
setpoint will be controlled by the remote control.
4.
Turn the mode button to "OFF" and remove power from the heater.
5.
On the "Remote Interface Harness", connect the BLUE wire to one
side of the "REMOTE" switch and connect the other side to either
the ORANGE/BLACK wire for "SPA" operation or the BLACK/OR-
ANGE wire for "POOL" operation.
6.
Attach wire nut on unused wire to the "Remote Interface Harness."
7.
Install the "7-Pin Remote Interface Harness" to the P8 connector
and turn power “On” to the heater.
See instructions on previous page to activate the remote control.
3-Wire Remote Control Using Three-Position Switch (Pool-Off-Spa, or Low-Off-High)
This application assumes that both heating functions (pool and spa) are required.
1.
Turn on power to the heater.
2.
Push the mode button to the "POOL" or "SPA" mode and set the
desired temperature for each (eg. 80°F for Pool and 102°F for
Spa).
3.
Turn the mode button to "OFF" and remove power from the heater.
4.
On the "Remote Interface Harness" connect the BLUE wire to one
side of the "REMOTE" switch and connect the ORANGE/BLACK
wire for "SPA" operation and the BLACK/ORANGE wire for the
"POOL" operation.
5.
Install the "Remote Interface Harness" to the P8 connector and
turn power "ON" to the heater.
See instructions on previous page to activate the remote control.
P8 Connector
Wire Nut - BLK/ORN
To Pool (COMM)
ORN/BLK - To Spa (COMM)
BLU - 24VAC
P8 Connector
ORN/BLK - To Spa (COMM)
BLU - 24VAC
BLK/ORN - To Pool (COMM)