Operating Terminal BT 220
Technical Information and Operation
1070 080 037-101 (99.01) GB
Reg. No. 16149-03
E
1999
by Robert Bosch GmbH, Erbach / Germany
All rights reserved, including applications for protective rights.
Reproduction or handing over to third parties are subject to our written permission.
Discretionary charge
20.00 DM
BT220 Technical Information and Operation
Contents
I
1070 080 037-101 (99.01) GB
Contents
Page
1
Safety Instructions
1-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Explanation of pictographs and symbols
1-1
. . . . . . . . . . . . . . . . . . . . . . .
Warning of magnetic fields
1-3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Normal use
1-4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Qualified personnel
1-4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Retrofits and modifications by the user
1-5
. . . . . . . . . . . . . . . . . . . . . . . .
Maintenance, repair
1-5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation and assembly
1-6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Units without Monitoring Contact ÜK
1-7
. . . . . . . . . . . . . . . . . . . . . . . . . .
Start Simulation
1-7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fault Reset
1-7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Working safely
1-8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Overview
2-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
Installation and Assembly
3-1
. . . . . . . . . . . . . . . . . . . . . . . . . .
4
Electrical Connection
4-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1
Power Supply (X1)
4-2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2
Lamp and Ready Outputs (X2)
4-3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3
RS232 Interfaces
4-4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4
RS485 Interface
4-6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
Operation
5-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1
Display and Acknowledge Events, if necessary
5-2
. . . . . . . . . . . . . . . . .
5.2
Display / Change Internal Time Setting of the BT220
5-3
. . . . . . . . . . . .
5.3
Set System Language
5-3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4
Displaying / Changing Welding and Process Data
5-4
. . . . . . . . . . . . . . .
5.4.1 Selection of Program and Weld timer
5-7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.2 F2: Sequence
5-8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.3 F3: Monitoring
5-9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.4 F4: Data of the Last Weld
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
5.4.5 F5: Slope
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
5.4.6 F6: Pressure Profile
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
5.4.7 F7: Stepper Diagnostics
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-14
5.4.8 F8: FPO_1 (freely programmable analog output)
. . . . . . . . . . . . . . . . . . . 5-15
5.4.9 F9: Heat Correction
5-16
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
BT220 Technical Information and Operation
II
1070 080 037-101 (99.01) GB
5.5
Deleting the Message Memory
5-17
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6
Display Diagnostic Memory
5-18
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.7
Printing the Diagnostic Memory
5-20
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.8
Deleting the Diagnostic Memory
5-23
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.9
Adapting the BT220 Display
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-24
5.9.1 Setting the Message Display Mode
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-24
5.9.2 Setting the Flash Rate
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-25
5.9.3 Setting ”Automatic Message Scrolling”
. . . . . . . . . . . . . . . . . . . . . . . . . . . 5-26
5.9.4 Display Parameters
5-27
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.10
Testing the BT220 Keyboard
5-28
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.11
Configuring the Printer Interface (X4)
5-29
. . . . . . . . . . . . . . . . . . . . . . . . . .
5.12
Inhibiting the Control Function
5-30
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.13
Overview: BT220 Specific Functions and Parameters
5-33
. . . . . . . . . . .
6
Maintenance
6-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1
Battery
6-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2
Reset
6-2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3
Software release
6-2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
Appendix
7-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1
Information on the STK multi-contact interface board
7-1
. . . . . . . . . . .
7.2
List of Figures
7-3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.3
Subject index
7-5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
BT220 Technical Information and Operation
Safety Instructions
1070 080 037-101 (99.01) GB
1-1
1
Safety Instructions
The product described hereunde was developed, manufactured and tested
in accordance with the basic safety stipulations of the EC Machine Directive.
You should nevertheless be aware of residual risks!
You should therefore read this manual before mounting, setting up, commis-
sioning or programming the system or working with this control system for
the first time.
Keep the manual in a place where it is easily accessible to all users!
Explanation of pictographs and symbols
The following warnings and notes may be attached to the individual hard-
ware components which are designed to inform the user of certain circum-
stances.
’
Warning of dangerous voltages!
’
Components subject to electrostatic induction!
’
Disconnect mains plug before opening!
’
Bolt for connection of the PE (protective earth)
conductor only!
’
For shield conductor only!
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
1-2
There is a certain hierarchy of warnings in this manual. The warnings are
printed in bold letters and marked by a warning sign at the margin.
The hierarchy of the warnings is as follows:
1. WARNING
2. ATTENTION
3. NOTE
WARNING!
The term WARNING will be used wherever danger is imminent.
The possible consequences may be death or severe injury (personal injury).
ATTENTION!
The term ATTENTION will be used wherever a dangerous situation is
possible.
The possible consequences include death, severe or light injury (personal
injury) damage to property or environmental hazards.
NOTE
The term NOTE will be used for making recommendations on the use.
Non-compliance with these recommendations may result in damage to
property, e.g. to the machine or the workpiece.
!
BT220 Technical Information and Operation
Safety Instructions
1070 080 037-101 (99.01) GB
1-3
Warning of magnetic fields
In the environment of resistance welding systems magnetic field strengths
have to be expected which usually are below the limits specified in VDE 0848
Part 4; in cases of doubt, the field strength must be measured.
WARNING!
When using manual welding guns, the limit values may be exceeded for the
extremities. In this case, additional work protection measures must be
taken.
WARNING for persons with cardiac pacemakers!
Warning signs should be posted for protecting persons with cardiac pace-
makers because the function of these devices may be disturbed (impulse
failure, total failure) and a negative influence on the pacemaker program-
ming or even a total program destruction may occur !!!
We recommend posting a warning of the type shown below at all entrances
to factory halls containing resistance welding equipment:
No entry for persons with cardiac
pacemakers!
Danger!
DIN 40023
!
!
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
1-4
Normal use
In conjunction with the connected PS 5000 weld timer the Operating terminal
serves for the
‘ Display and change of parameters
‘ Display of faults, warnings and signals
It is only suitable for
‘ industrial applications
in accordance with DIN EN 50082-2 of Electromagnetic Compatibility
(EMC).
It is not intended for any other use!
ATTENTION!
The use for purposes other than the intended use may result in personal
damage to the user or third persons or damage to the equipment, the work-
piece to be welded or other hazards.
Therefore, our products should only be used for their intended purpose!
Qualified personnel
This manual is designed for welding technicians and engineers with special
training and specific knowledge of the welding technology. They require pro-
found knowledge of the hardware components, the functions and the pro-
gramming of the welding equipment.
The term qualified personnel refers to
-
engineering personnel familiar with the safety standards of the electrical
and automation technology.
-
commissioning personnel entitled to commission, earth and label electri-
cal circuits and equipment/systems in compliance with the standards of
safety technology.
-
operating personnel who have been instructed in operating installations
in resistance welding technology and who know the contents of the pres-
ent documentation as far as operation is concerned.
WARNING!
An exception are persons with cardiac pacemakers!
Due to the strong magnetic fields arising from resistance welding, the func-
tion of cardiac pacemakers may be disturbed. This may cause the death or
considerable health damages to persons with cardiac pacemakers!
Therefore, these persons should avoid the welding system.
Please note our comprehensive range of training courses. More information
is available from our training center (Phone: ++49 (0)6062 / 78258).
!
BT220 Technical Information and Operation
Safety Instructions
1070 080 037-101 (99.01) GB
1-5
Retrofits and modifications by the user
Our equipment has been designed and manufactured by us as a safe unit.
WARNING!
Retrofits or modifications may have negative effects on the safety of the unit!
The possible consequences include death, severe or light injury (personal
injury) damage to property or environmental hazards.
Therefore, please contact us prior to retrofits or modifications to the welding
system using third-party equipment. This is the only way to determine
whether these parts are suitable for use with our product.
Maintenance, repair
WARNING!
-
Danger of life through electrical voltage!
Prior to any maintenance work - unless described otherwise - the sys-
tem must always be switched off! In the event of necessary measure-
ment or test procedures on the active system, the applicable safety and
accident prevention regulations must be strictly observed. In any case,
suitable insulated tools must be used!
-
Danger of life through inappropriate EMERGENCY-OFF devices!
EMERGENCY-OFF devices must be operative in all modes of the sys-
tem. Releasing the EMERGENCY-OFF facility must by no means result
in an uncontrolled restart of the system!
ATTENTION!
-
The right to perform repair/maintenance work on the timer compenents is
reserved to the BOSCH service department or to repair/maintenance
units authorized by BOSCH!
-
Only use spare parts/replacement parts approved by BOSCH!
− If handled improperly, batteries may cause cauterization or explode!
Therefore:
Batteries must not be opened forcefully, recharged, soldered at the cell
body or thrown into fire!
-
Only use original replacement batteries! Spent batteries or accumulators
must be disposed of as hazardous waste.
!
!
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
1-6
Installation and assembly
ATTENTION!
-
Please observe all applicable safety and accident prevention regula-
tions!
-
Danger of damage to property through short-circuits!
When drilling or sawing out openings, metal burr may get inside modules
or plant sections that have already been installed.
Possible consequences include short-circuits and a destruction of the
equipment.
Therefore, all equipment should be well partitioned prior to any additional
work!
-
The units, and especially the operating elements, must be installed so as
to be sufficiently protected against unintentional operation or contact.
-
Connection and signal leads should be run so as to avoid disturbance of
any equipment functions by capacitive or inductive interference.
-
Equipment designed for installation in housings or switch cabinets must
be installed in such enclosures before they may be used or operated!
BT220 Technical Information and Operation
Safety Instructions
1070 080 037-101 (99.01) GB
1-7
Units without Monitoring Contact ÜK
ATTENTION!
When the ÜK is permanently connected to +24V, the squeeze times are to
be selected long enough so as to ensure that the parts to be welded are opti-
mally pressed together before the weld time starts.
Start Simulation
ATTENTION!
If the equipment is started remotely, there results a program sequence
which can cause hazardous machine movements. So check before remote
start up that no one is in the danger zone of the welding equipment!
Fault Reset
WARNING!
-
Danger of physical injury!
If the start signal is present on fault reset, the weld timer immediately
starts the program sequence! Hazardous machine movements may be
the result!
Therefore, before fault reset, you should make sure that there are no per-
sons in the danger zone of the welding equipment!
-
Danger of bruises through electrode movement!
All users, line designers, welding machine manufacturers and welding
gun producers are obliged to connect the output signal of the Bosch weld
timer which initiates the electrode movement so that the applicable
safety regulations are complied with.
The risk of bruises can be considerably reduced by means of,
e.g.,
‘ two-handed start
‘ guard rails
‘ light barriers etc.
!
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
1-8
Working safely
WARNING!
-
During operation of the welding equipment welding splashes are to be
expected! The consequence may be injuries to the eyes or burns.
Therefore:
‘ wear protective goggles
‘ wear protective gloves
‘ wear flame-retardant clothes
-
Danger of injury at sheet metal edges and danger of getting burnt at the
parts to be welded!
Therefore: ‘ wear protective gloves
NOTE
The strong magnetic fields arising in connection with resistance welding
may cause lasting damages to wrist watches, pocket watches, or cards with
magnetic stripes (e.g. EC cards).
Therefore, you should not carry any such items on you when working in the
direct vicinity of the welding equipment.
!
BT220 Technical Information and Operation
Overview
1070 080 037-101 (99.01) GB
2-1
2
Overview
NOTE
For comfortable programming and setting of parameters of the PS 5000 use
a PC with the welding software ”BOS 5000” installed. In normal operation of
the welding unit the complete function range of this package is not really re-
quired.
Because of this the BT220 is available to you as a stationary control ter-
minal of your PS 5000 (supported control types: PSS 5100.510 and
PSS 5200.510; please ask for other supported types).
It is designed for installation in the machine operating panel of the welding
unit. So faults, warnings and messages of the PS 5000 can be displayed in
clear text and basic welding data may be quickly and easily displayed or
changed.
Fig. 2-1:
Front View BT220
This manual contains information on
‘ the mechanics
‘ the electrical connection and
‘ the functions of the BT220.
ATTENTION!
Danger of malfunctions and damage!
Wrong installation and faulty connection can lead to unexpected or wrong
unit reactions and hence to hazardous situations. So please respect the de-
tails in the present manual.
Follow all the instructions in this manual (instructions are identified by the
sign ”’”). They are for your own safety and for problem-free commissioning.
‘ Display of faults, warnings and messages of the PS 5000.
The BT220 can manage a maximum of 100 events present at the same
time in the message memory.
‘ Display and modification of different welding and process data.
‘ Diagnostic memory for max. 400 events (ring memory).
The contents of the diagnostic memory can be output via the serial
interface to a printer.
Functions
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
2-2
‘ BT220-1:
with 1 RS232 interface for the connection of
1 x
PS 5000
or
1 x
STK multi-contact interface board.
‘ BT220-2:
with 2 RS232 interfaces for the connection of
2 x
PS 5000
or
1 x
STK multi-contact interface board
and
1 x
Report printer.
‘ BT220-3/7:
with 1 RS485 and 1 RS232 interface for the connection
of
1 x
STK multi-contact interface board (RS485)
and
1 x
Report printer (RS232).
‘ STK x:
Multi-contact interface board for the connection of max.
7 PS 5000 via RS232 interfaces. In the basic design the
STK is already prepared for the connection of 3
PS 5000. It can be easily retrofitted with additional
plug-in RS232 interface modules.
For communication with a BT220-x, the multi-contact
interface board is optionally available with a separate
RS485 or RS232 interface.
You can find more information on the multi-contact in-
terface board on page 7-1.
BT220-1
X1
X4
max. 15m
1st PS 5000
RS232
Fig. 2-2:
Connection of a PS 5000
Constructions
Options
Application Examples
BT220 Technical Information and Operation
Overview
1070 080 037-101 (99.01) GB
2-3
BT220-2
X1
X5
max. 15m
X1
X4
max. 15m
1st PS 5000
2nd PS 5000
RS232
RS232
Fig. 2-3:
Connection of 2 PS 5000
BT220-x
1st PS 5000
X1
2nd PS 5000
3rd PS 5000
4th PS 5000
5th PS 5000
6th PS 5000
7th PS 5000
Multi-contact in-
terface board
STK
X1
X1
X1
X1
X1
X1
Cable lengths for
- RS232 connections max.15m
- RS485 connections max.1000m
RS232
RS232
RS232
RS232
RS232
RS232
RS232
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
RS232
or
RS485
Fig. 2-4:
Connection of max. 7 PS 5000 to BT220 via STK multi-contact interface board
BT220 Technical Information and Operation
Installation and Assembly
1070 080 037-101 (99.01) GB
3-1
3
Installation and Assembly
The BT220 is intended for installation in a control panel, a control cabinet or
a front plate.
Weight:
approx. 1.5 kg
Installation position:
0_ to max. 90_ slant
Installation type:
in a desk or hinged frame, sealed as per IP 65
Degree of protection: IP 65 (front face); IP 40 (back face)
Dimensions:
Required assembly cutout:
262 mm x 92 mm
Required installation depth: 110 mm
Front dimensions:
277 mm x 112 mm
Temperature:
Operating temperature range:
0_C to +50_C
Storage temperature range:
-30_C to +70_C
Air humidity:
20% to 80% rel. air humidity
’
Please refer to the information in chapter ”Safety Instructions” relative to
installation and assembly.
’
Install the BT220 so that ergonomic operation is guaranteed. Also the
operator must have a clear view of all moving machine parts at all times!
Remember how quickly the front panel can become dirty with an inclined
or horizontal installation.
’
Avoid installation places which are exposed to direct sunshine (reduction
of display legibility; additional heat).
’
Provide a minimum all-round clearance of 50mm for sufficient ventilation
and cable routing.
’
Run all connection cables in loops, and use strain reliefs for all cables.
’
Keep as far away as possible away from sources of interference, how-
ever at least 25cm. With strong magnetic fields we recommend the in-
stallation of partition plates.
’
Only use silicon-free sealing, adhesive or insulating media.
max. 90°
Minimum all�round
clearance of 50 mm
BT220
Fig. 3-1:
Installation positions and distances
Installation and Assembly
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
3-2
’
Fix the BT220 with the 4 screw terminals. For this purpose, first insert the
BT220 into the assembly cutout and then engage the screw terminals in
the recesses on the top and bottom sides of the BT220 housing.
Then tighten the screw terminals.
BT220 Technical Information and Operation
Electrical Connection
1070 080 037-101 (99.01) GB
4-1
4
Electrical Connection
Supply inputs, outputs and interfaces are isolated from each other.
’
Disconnect the unit from power before wiring the BT220.
’
Make sure that the circuits of relays or contactors, which are installed in
the same installation room as the BT220 include the corresponding free-
wheeling diodes or RC spark-quenching devices.
1
5
6
9
X4
X1
X2
PE/Screening
X1: 24VDC power input
X2: Outputs (indicator lamps, ready state)
X4: RS232 interface for the connection of PS 5000, or STK multi-contact
interface board
Fig. 4-1:
Connections on the BT220-1
1
5
6
9
X4
X5
X1
X2
PE/Screening
1
5
6
9
X1: 24 VDC power input
X2: Outputs (indicator lamps, ready state)
X4: RS232 interface for the connection of PS 5000 or report printer
X5: RS232 interface for the connection of PS 5000, or STK multi-contact
interface board
Fig. 4-2:
Connections on the BT220-2
Remarks
BT220-2: If an STK multi-contact interface board is connected to X5, only a
report printer may be connected to X4.
Position of the Connec-
tions
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
4-2
1
5
6
9
1
13
14
25
X4
X5
X1
X2
PE/Screening
X1: 24 VDC power input
X2: Outputs (indicator lamps, ready state)
X4: RS232 interface for connection of report printer
X5: RS485 interface for connection of STK multi-contact interface board
Fig. 4-3:
Connections on the BT220-3/7
4.1
Power Supply (X1)
Connection:
Screw terminal plugs
MSTB 2.5 / 5-ST-5.08
Supply voltage:
19...33 VDC; typ. 24 VDC
Current consumption:
< 0.35 A
X1
+24 VDC
0 VDC
PE
Fig. 4-4:
Terminal Assignment X1
Remarks
If you wish to use the outputs on X2, you must connect the supply voltage to
X2 as well.
BT220 Technical Information and Operation
Electrical Connection
1070 080 037-101 (99.01) GB
4-3
4.2
Lamp and Ready Outputs (X2)
Connection:
Screw terminal plugs
MSTB 2.5 / 8-ST-5,08
Output current:
(with 24 VDC supply); permanently short-circuit-
proof
Supply voltage:
19...33 VDC; typ. 24 VDC
The outputs for the display of warnings and fault messages are functionally
identical with the warning (red LED) and fault message (yellow LED) on the
front panel of the BT220. The output signals are static (not flashing).
NOTE
Overloading the output drivers possible!
’
Use the outputs only for control of the relays or PLC inputs.
Via the ready output a connected PLC can recognize whether serial com-
munication is functioning properly.
X2
Warning
0 VDC
+24 VDC
Ready
Fault
res.
Fig. 4-5:
Terminal Assignment X2
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
4-4
4.3
RS232 Interfaces
BT220-1:
X4
BT220-2:
X4 and X5
BT220-3/7: X4
Connection:
Sub-D socket, 9-pin.
Type:
RS232
Lead length:
max. 15m
Lead type:
shielded, core cross-section min. 0.14mm2
Transmission rate: adjustable:
300, 600, 1200, 2400, 4800, 9600,
19200, 38400, 76800 bits/s
default:
9600
Parameters:
adjustable:
7 or 8 data bits,
even / odd / no parity,
1 or 2 stop-bits
default:
8N1 (8 data bits, no parity, 1 stop-bit)
Handshake:
adjustable:
without,
Hardware-Handshake (RTS, CTS),
Software-Handshake (XON, XOFF),
Software-Handshake + DTR
default:
Software-Handshake (XON, XOFF)
1
2
3
RX
TX
4
max. 15 m
BT220
Shield continuity via the metal housing of the plug
connection, or via a spade connector on the housing
5
GND
6
7
8
9
PS 5000 (X1; Sub-D, 9-pin)
RX
TX
GND
Socket
Plug
2
3
5
DTR
4
DSR
6
RTS
7
CTS
8
Fig. 4-6:
Connection of PS 5000 to BT220
Connection:
PS 5000 - BT220
BT220 Technical Information and Operation
Electrical Connection
1070 080 037-101 (99.01) GB
4-5
Prerequisite for shown connection: Hardware-Handshake
3
7
READY
RX
11
max. 15 m
BT220
GND
Printer (Sub-D, 25-pin)
CTS
TX
GND
Socket
Socket
8
3
5
Shield continuity via the metal housing of the plug
connection or via a spade connector on the housing
Fig. 4-7:
Connection of a Serial Printer
Remarks
Many printers output the READY signal to Pin 20. In such cases the CTS
input on the BT220 must be connected with Pin 20 on the printer.
1
2
3
TX
RTS�/�DTR
4
max. 15 m
BT220
5
CTS
6
7
8
STK (Channel 4; Sub-HD, 15-pin)
RX
TX
GND
Socket
Socket
2
3
5
DTR
4
DSR
6
RTS
7
CTS
8
RX
GND
Shield continuity via the metal housing of the plug
connection or via a spade connector on the housing
Fig. 4-8:
Connection of the STK multi-contact interface board: Channel 4 fitted with RS232
interface
Connection:
Report Printer - BT220
RS232 Connection:
STK - BT220
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
4-6
4.4
RS485 Interface
BT220-3/7: X5
Connection:
Sub-D socket, 25-pin.
Type:
RS485
Lead length:
max. 1000m
Lead type:
2-wire, twisted and shielded, core cross-section min.
0.14mm2
Transmission rate: adjustable:
38400, 57600, 76800, 115200 bits/s
Parameters:
7 data bits, even parity, 1 stop-bit (7E1)
max. 1000 m
BT220
Shield continuity via the metal housing of the plug connection or via a spade
connector on the housing
Connection on one side: for short data cables or low frequency interference
Connection on both sides: for long data cables or high frequency interference
STK (Channel 4; Sub-HD, 15-pin)
A
B
+5�V
Socket
Socket
14
15
21
A
B
4
11
0�V
7
+5�V
15
0�V
8
provision for
bus termination
provision for
bus termination
Fig. 4-9:
Connection of the STK multi-contact interface board. Channel 4 fitted with RS485
Interface
With high transmission rates or long data cables we recommend the use of a
bus termination.
The necessary resistors can for example be integrated into both plugs of the
transmission lead:
BT220
Rt
approximately equal to the characteristic resistance of the lead (typically 50-120 Ohm)
Ru Pull-up resistor
Rd Pull-down resistor
STK (Channel 4; Sub-D, 15-pin)
Pin 15
Pin 8
Pin 4
Pin 11
A
B
Ru
Rt
Rd
Pin 21
Pin 7
Pin 14
Pin 15
A
B
Ru
Rt
Rd
Fig. 4-10:
Bus Termination for RS485 Connections
RS485 Connection:
STK - BT220
RS485 Connection:
Bus Termination
BT220 Technical Information and Operation
Operation
1070 080 037-101 (99.01) GB
5-1
5
Operation
Numerical keys
Cursor keys
Command keys
Fig. 5-1:
Front View BT220
For the input of numerical values (inc. decimal point and minus sign).
F
calls up the function key mode. In this mode you have access to weld-
ing and process data (see page 5-4).
depends on the current state of the BT220:
-
acknowledges events, parameter changes or queries
-
triggers functions
-
branches into sub-menus.
I,0
switches welding specific functions on or off within the function key
mode.
i
calls up hidden Help texts, depending on the current status.
shows the day, date, time and calendar week (see page 5-3).
MEN depending on the current status of the BT220:
-
calls up the Main Menu of the BT220 (for menu tree see
page 5-33)
-
cancels parameter changes
-
cancels a function awaiting acknowledgment.
VAR
initiates a parameter change.
A " depending on the current state of the BT220:
-
scrolls through the messages present
-
scrolls through the diagnostic memory
-
selects a parameter for modification
Y B depending on the current state of the BT220:
-
scrolls through menus
-
scrolls through setting options
-
scrolls through texts comprising more than 2 lines.
Numerical keys
Command keys
Cursor keys
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
5-2
5.1
Display and Acknowledge Events, if necessary
Display
Fault
Warning
Message
Cursor keys
Acknowledge key
Help key
Fig. 5-2:
Front View BT220
After it is switched on the BT220 is in Message Display Mode. All events
which are transmitted by the connected weld timers can be displayed and
acknowledged, if necessary.
If no event has occurred, the text “No message” is shown in the display (see
Figure).
Whole display text flashes:
An event is present and must be acknowl-
edged with the key .
Call up Help on the event:
Key i
Close Help:
Key i
Display text does not flash:
An event which does not have to be ac-
knowledged or has already been acknowl-
edged (is logically TRUE) is present. As
soon as the event is no longer present, the
corresponding display text is automatically
deleted.
Call up Help on the event:
Key i
Close Help:
Key i
Fault (red LED flashes):
Fault/error message is present.
’
Remedy fault and acknowledge with .
Warning (yellow LED flashes): A warning is present.
’
Remedy the cause and acknowledge
with .
Message (green LED):
There is more than 1 event present.
You can select the event automatically dis-
played by the BT220 (see page 5-24).
Other events present can be found in the
message memory (max. 100) and dis-
played with the cursor keys
A and ".
You can find additional information on the
message memory on page 5-17.
BT220 Technical Information and Operation
Operation
1070 080 037-101 (99.01) GB
5-3
5.2
Display / Change Internal Time Setting of the BT220
The BT220 is fitted with an internal clock.
Whenever an event appears, disappears or is acknowledged, the BT220
stores the current time and date in the diagnostic memory as well as the
corresponding text.
’
Therefore, make sure the clock is set to the right time.
In the following description we assume that the BT220 is in message display
mode (see chapter 5.1, page 5-2).
The function may be called up from several other operating states, but on
completion always returns to the message display mode.
1. Press key .
The first line in the display shows the current value for the day, date, time,
calendar week.
The BT220 calculates the details of the day and calendar week automati-
cally from the date value.
2. Values are incorrect: Proceed to Step 3.
Values are correct:
Press MEN key.
The BT220 returns to the message display mode.
3. Press VAR key.
The currently changeable figure flashes.
4. Move the cursor with the cursor keys A and " to the figure to be changed
and enter the new value
-
via the numerical keys or
-
via the keys Y and B.
In this way set the correct date and time.
5. To store current values:
press .
To cancel changes:
press MEN.
Proceed to Step 2.
5.3
Set System Language
The language for message and menu texts can be set. The BT220 offers
German and English as standard. Other languages can be added as re-
quired (max. 10 in total).
In the following description we assume that the BT220 is in the message dis-
play mode (see chapter 5.1, page 5-2).
1
Press the MEN key.
The menu item ”Diagnostic memory” appears in the second display line.
2. Keep pressing the B key until the text ”Change language” is displayed in
the second display line.
3. First press the key, then the VAR key.
4. Use the keys Y and B to set the new language.
5. To activate the displayed language:
press .
To cancel changing the current language:
press MEN.
6. Press the MEN key twice to return to the message display mode.
Procedure
Procedure
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
5-4
5.4
Displaying / Changing Welding and Process Data
’
Do not change data without instructions. All data is transmitted on-line to
the weld timer. Wrongly entered data can cause damage to the equip-
ment or the part to be welded!
’
Make sure that the required welding program and the required weld timer
have been correctly selected before you change data. For the selection
see page 5-7.
Via the BT220 you have access to the following data:
‘ F1 Help. Options:
-
Display Help text.
‘ F2 Sequence. Options:
-
Display and change the pre-squeeze time, squeeze time, 1. weld
time, 1. heat, 1. cool time, 2. weld time, 2. heat, pulsation, 2. cool time,
3. weld time, 3. cool time, 3. heat, hold time, off time.
‘ F3 Monitoring. Options:
-
Activate/deactivate current monitoring.
-
Display and change +/- tolerance, ”conditional tolerance band”,
conditional welds, reference current.
Depending on the selectable mode (STANDARD or MIXED) you have
access to the above mentioned parameters for WLD, 1.WLD, 2.WLD
or 3.WLD.
‘ F4 Last weld. Options:
-
Display reference and actual current, average phase angle.
‘ F5 Slope. Options:
-
Activate/deactivate the slope.
-
Display and change the start and end slope (time and heat, each).
‘ F6 Pressure Profile. Options:
-
Activate/deactivate control of the pressure regulating valve.
-
Display and change the basic pressure (up to SQZ), welding pressure
(from SQZ).
‘ F7 Stepper Diagnostics. Options:
-
Display the current electrode wear values (for max. 8 electrodes).
-
Acknowledge tip dress, acknowledge electrode change (for one
single electrode or for all electrodes collectively by entering electrode
number ”0”).
‘ F8 FPO_1 (freely programmable output). Options:
-
Activate/deactivate the output.
-
Display and change 3 high and 3 low times.
‘ F9 Heat Correction. Options:
-
Display and change heat correction parameters of all electrodes.
To display or change the welding or process data of all programs of the con-
nected PS 5000, switch the BT220 to the ”Function Key Mode”.
Overview
BT220 Technical Information and Operation
Operation
1070 080 037-101 (99.01) GB
5-5
Remarks
When events are present or occur which have to be acknowledged, the
BT220 automatically switches to the message display mode (see chapter
5.1, page 5-2).
Display and modification of the welding or process data is only possible
when you have acknowledged all events. The BT220 in this case automati-
cally returns to the last active display level of the function key mode.
In the following description of the procedure we assume that the BT220 is in
the message display mode (see chapter 5.1, page 5-2).
The function key mode can also be called up from some other operating
statuses, but on completion always returns to the message display mode.
1. Press key F.
The BT220 now waits for the input of the function number (1 to 9).
In the ”Overview” section on the previous page you will find all the avail-
able functions listed numerically (Fx).
2. Enter
-
the required number using the numerical keys, or
-
press theB key (automatically selects the lowest applicable function
number: here ”1”).
3. Press key .
BT220 is now in the ”Main Menu” of the function key mode. The display
shows the previously selected function.
Remarks
When at the end of the first display line the character ”q” (”0” with a horizontal
line through the middle) is displayed, there is a sub-menu to the function
shown.
In this operating mode the following actions can be selected :
-
Return to the message display mode
-
Step through the Main Menu
-
Select program and/or weld timer for data display/modification
-
Change to the sub-menu of the displayed function (only possible when
the character ”q” appears at the end of the first display line)
-
Switching the displayed function on, off, over.
The following figure shows you the individual options:
Procedure:
Calling up the Function
Key Mode
Operating Options in
the Main Menu of the
Function Key Mode
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
5-6
Message
display
mode
Function Key Mode
(Main Menu)
.
.
MEN
F
B
F
1
9
"
B
Y
I
0
to F1
from F1
to F9
from F9
To the individual
sub-menus:
VAR
A
Select program and weld timer for data display /
modification; see also page 5-7)
(see A)
.
.
0
9
from
the
Main
Menu
Enter pro-
gram or
weld timer
number
Select ”pro-
gram” or
”TIM” (weld
timer)
to the
Main
Menu
(Cancel)
(Ok)
see page
5-8
x
= press corresponding key
Return to
message dis-
play mode
see page
5-9
see page
5-11
see page
5-12
see page
5-13
see page
5-14
see page
5-15
see page
5-16
F1
Help
F2
Sequence
F9
Heat Correction
F3
Monitoring
F4
Last Weld
F5
Slope
F6
Pressure Profile
F7
Stepper Diagnostics
F8
FPO_1
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Standard
Mixed
I
0
I
0
I
0
I
0
B
Y
(see A)
B
Y
(see A)
B
Y
(see A)
B
Y
(see A)
B
Y
(see A)
B
Y
(see A)
B
Y
(see A)
A
"
Fig. 5-3:
Command Options in the Main Menu of the Function Key Mode
BT220 Technical Information and Operation
Operation
1070 080 037-101 (99.01) GB
5-7
5.4.1
Selection of Program and Weld timer
In order to display or change the data of a program stored on a connected
weld timer (TIM) via the BT220, you must select both the relevant timer
number and the relevant program number.
Values between ”0” and ”255” are admissible for input as program numbers.
The possible timer numbers depend on the number of timers actually con-
nected and start with ”1”. Depending on the BT220 version used the follow-
ing assignment applies:
BT220-1 without STK multi-contact
interface board:
TIM1 = Timer at X4
BT220-2 without STK multi-contact
interface board:
TIM1 = Timer at X4
TIM2 = Timer at X5
BT220-x with STK multi-contact
interface board
TIM1 = Timer at Channel 1
TIM2 = Timer at Channel 2
TIM3 = Timer at Channel 3
TIM4 = Timer at Channel 5
TIM5 = Timer at Channel 6
TIM6 = Timer at Channel 7
TIM7 = Timer at Channel 8
Remarks
-
Please note that channel 4 of the multi-contact interface board is always
used for communication with the BT220!
-
Numbers of timers not connected (TIMx) are not recognized on selection
and not accepted.
In the following description of the operating sequence we assume that the
BT220 is in the Main Menu of the function key mode (see page 5-6).
MEN
VAR
.
.
0
9
Enter pro-
gram or
weld timer
number
Select ”Pro-
gram” or
”TIM” (weld
timer)
x
= press corresponding key
Cancel
inputs
Accept inputs
Change pro-
gram or weld
timer number
A
"
Fig. 5-4:
Operating Sequence: Selection of Program and Weld timer
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
5-8
5.4.2
F2: Sequence
Here you have access to basic parameters which determine the sequence of
a welding process; e.g.
pre-squeeze time, squeeze time, 1. weld time, 1. heat, 1. cool time, 2. weld
time, 2. heat, pulsation, 2. cool time, 3. weld time, 3. cool time, 3. heat, hold
time, off time.
In the following description of the operating sequence we assume that the
BT220 is in the Main Menu of the function key mode (see page 5-6) and
displays ”F2: Sequence”.
A
"
MEN
VAR
.
.
0
9
Enter program
or weld timer
number
Select ”pro-
gram” or
”TIM”
x
= press corresponding key
Cancel
inputs
Accept inputs
Call up Sub-
Menu
B
Y
Change value
is ”program” or
”TIM” dis-
played?
yes
.
.
0
9
Enter para-
meter value
no
Back to the Main
Menu
"
Scroll display
backward
Scroll display
forward
F2:
Sequence
Fig. 5-5:
Operating Sequence: F2 Sequence
BT220 Technical Information and Operation
Operation
1070 080 037-101 (99.01) GB
5-9
5.4.3
F3: Monitoring
Current monitoring can be switched on or off by selecting the corresponding
mode (STANDARD or MIXED) selectively for individual sections of the weld-
ing cycle (WLD, 1.WLD, 2.WLD or 3.WLD).
Only when current monitoring is switched on do you have access to the
corresponding set of parameters, consisting of: +tolerance, -tolerance,
”conditional tolerance”, conditional welds, reference current.
STANDARD mode:
Monitoring can be switched on or off for weld time.
Monitoring is deactivated for 1.WLD, 2.WLD and
3.WLD.
MIXED mode:
Monitoring can be switched on or off for 1.WLD,
2.WLD and 3.WLD independently of one another.
Monitoring is deactivated for weld time.
In the following description of the operating sequence we assume that the
BT220 is in the Main Menu of the function key mode (see page 5-6) and
displays ”F3: Monitoring”.
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
5-10
Monitoring
OFF
Change pro-
gram or weld
timer
number
MEN
VAR
.
.
0
9
Enter program
or weld timer
number
Select ”pro-
gram” or
”TIM”
x
= press corresponding key
Cancel
inputs
Accept inputs
Call up Sub-
Menu
B
Y
Change current
parameter
yes
.
.
0
9
Enter para-
meter value
no
Back to the Main
Menu
"
I
0
Monitoring
ON
B
is ”program”
or ”TIM” dis-
played?
VAR
proceed
to A
A
MEN
Cancel
inputs
Accept inputs
Select
MIXED mode
I
0
Select STAN-
DARD mode
B
Y
B
yes
no
A
"
Is STANDARD
mode
selected?
Is the term ”Current
Monitoring” dis-
played in the first
display line?
yes
no
proceed
to A
Back to the Main
Menu
"
proceed to B
Y
B
Scroll display
backward
Scroll display
forward
Scroll display
forward
Scroll display
forward or
backward
Scroll display for-
ward or backward
Back to the Main
Menu
"
F3:
Monitoring
Fig. 5-6:
Operating Sequence: F3 Monitoring
BT220 Technical Information and Operation
Operation
1070 080 037-101 (99.01) GB
5-11
5.4.4
F4: Data of the Last Weld
This function displays (for WLD, 1.WLD, 2.WLD and 3.WLD) the reference
currents, actual currents and average phase angles of the previous welding
cycle.
In the following description of the operating sequence we assume that the
BT220 is in the Main Menu of the function key mode (see page 5-6) and
displays ”F4: Last Weld”.
A
"
MEN
VAR
.
.
0
9
Enter program
or weld timer
number
Select ”pro-
gram” or
”TIM”
x
= press corresponding key
Cancel
inputs
Accept inputs
Call up Sub-
Menu
B
Y
Scroll display
backward
Only when ”pro-
gram” or ”TIM”
are displayed:
Back to the Main
Menu
"
Change pro-
gram or weld
timer number
Scroll display
forward
F4:
Data of last
weld
Fig. 5-7:
Operating Sequence: F4 Last Weld
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
5-12
5.4.5
F5: Slope
Switches the slope on and off. When the slope function is active, the timer
increases (at the start of welding) or decreases (at the end of welding) the
welding heat for a definable time period.
When the slope is active, both the duration and the heat values at the begin-
ning and end of welding can be entered for the startslope and endslope.
In the following description of the operating sequence we assume that the
BT220 is in the Main Menu of the function key mode (see page 5-6) and
displays ”F5: Slope”.
Change pro-
gram or weld
timer
number
MEN
VAR
.
.
0
9
Enter program
or weld timer
number
Select ”pro-
gram” or
”TIM”
x
= press corresponding key
Cancel
inputs
Accept inputs
Call up Sub-
Menu
B
Y
Change current
parameter
yes
.
.
0
9
Enter para-
meter value
no
Back to the Main
Menu
"
is ”program”
or ”TIM” dis-
played?
VAR
proceed
to A
A
MEN
Cancel
inputs
Accept inputs
B
A
"
Scroll display
backward
Scroll display
forward
Scroll display
forward
Slope ON
I
0
Slope OFF
Back to the Main
Menu
"
F5:
Slope
Fig. 5-8:
Operating Sequence: F5 Slope
BT220 Technical Information and Operation
Operation
1070 080 037-101 (99.01) GB
5-13
5.4.6
F6: Pressure Profile
Switches the pressure control on and off.
Only when the pressure control function is active can the individual pressure
parameters be displayed/changed.
In the following description of the operating sequence we assume that the
BT220 is in the Main Menu of the function key mode (see page 5-6) and
displays ”F6: Pressure Profile”.
Change pro-
gram or weld
timer
number
MEN
VAR
.
.
0
9
Enter program
or weld timer
number
Select ”pro-
gram” or
”TIM”
x
= press corresponding key
Cancel
inputs
Accept inputs
Call up Sub-
Menu
B
Y
Change current
parameter
yes
.
.
0
9
Enter para-
meter value
no
Back to the Main
Menu
"
is ”program”
or ”TIM” dis-
played?
VAR
proceed
to A
A
MEN
Cancel
inputs
Accept inputs
B
A
"
Scroll display
backward
Scroll display
forward
Scroll display
forward
Pressure Profile ON
I
0
Pressure Profile OFF
Back to the Main
Menu
"
F6:
Pressure
Profile
Fig. 5-9:
Operating Sequence: F6 Pressure Profile
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
5-14
5.4.7
F7: Stepper Diagnostics
Here you have the following options:
-
to display electrode wear (Wr) (for max. 8 electrodes). Only electrodes
with a wear value > 0% are displayed. The wear display is in integers.
-
to acknowledge ”Tip dress” (individual or all electrodes)
-
to acknowledge ”Electrode Change” (individual or all electrodes)
In the following description of the operating sequence we assume that the
BT220 is in the Main Menu of the function key mode (see page 5-6) and
displays ”F7: Stepper Diagnostics”.
Change weld
timer
number
MEN
VAR
.
.
0
9
Enter weld timer
number
x
= press corresponding key
Cancel
selection
Acknowl-
edge ”Tip
dress” or
”Electrode
change”
Call up Sub-
Menu
B
Y
Select electrode
number
yes
.
.
0
9
Enter electrode
number
(1 to 31:
”0” for all)
no
Back to the Main
Menu
"
is ”TIM” dis-
played?
VAR
proceed
to A
A
MEN
Cancel
inputs
Accept inputs
B
Scroll display
backward
Scroll display
forward
Scroll display
forward
Back to the
Main Menu
"
only when ”Elec-
trode no.” is dis-
played in the sec-
ond display line
Set Electrode
number to ”0”
F7:
Stepper
Diagnostics
Fig. 5-10:
Operating Sequence: F7 Stepper Diagnostics
BT220 Technical Information and Operation
Operation
1070 080 037-101 (99.01) GB
5-15
5.4.8
F8: FPO_1 (freely programmable analog output)
Activation and deactivation of the freely programmable analog output.
Only when the analog output is activated can the individual parameters be
displayed/changed.
In the following description of the operating sequence we assume that the
BT220 is in the Main Menu of the function key mode (see page 5-6) and
displays ”F8: FPO_1”.
Change
parameter
Change pro-
gram or weld
timer
number
MEN
VAR
.
.
0
9
Enter program
or weld timer
number
Select ”pro-
gram” or
”TIM”
x
= press corresponding key
Cancel
inputs
Accept inputs
Call up Sub-
Menu
B
Y
yes
no
Back to the Main
Menu
"
is ”program”
or ”TIM” dis-
played?
VAR
proceed
to A
A
MEN
Cancel
inputs
Accept inputs
B
A
"
Scroll display
backward
Scroll display
forward
Scroll display
forward
FPO_1 ON
I
0
FPO_1 OFF
Back to the Main
Menu
"
.
.
0
9
Enter new
value
Select
parameter
A
"
F8:
FPO_1
Fig. 5-11:
Operating Sequence: F8 FPO_1 (freely programmable analog output)
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
5-16
5.4.9
F9: Heat Correction
Display and change the heat correction values of individual electrodes.
NOTE
The current values are only read out from the connected timers after the
BT220 has been switched on. If data has been changed via an additionally
connected programming unit, the BT220 will not display the modified data
before it has been re-initialized (cycling power) or communication between
BT220 and the weld timer has been re-established.
In the following description of the operating sequence we assume that the
BT220 is in the Main Menu of the function key mode (see page 5-6) and
displays ”F9: Heat Correction”.
x
= press corresponding key
Call up Sub-
Menu
B
Y
yes
no
Back to the Main
Menu
"
proceed
to A
A
B
Scroll display
backward
Scroll display
forward
Scroll display
forward
Back to the
Main Menu
"
F9:
Heat
Correction
is ”Electrode
no.” or ”TIM”
displayed?
Change elec-
trode or weld
timer num-
ber
.
.
0
9
Enter electrode
or weld timer
number
is ”Electrode
no.” or ”TIM”
displayed?
VAR
MEN
Cancel
inputs
Accept inputs
A
"
Change
parameter
MEN
VAR
Cancel in-
puts
Accept inputs
.
.
0
9
Enter new
value
Select
parameter
A
"
Fig. 5-12:
Operating Sequence: F9 Heat Correction
BT220 Technical Information and Operation
Operation
1070 080 037-101 (99.01) GB
5-17
5.5
Deleting the Message Memory
Events are logged in
-
the diagnostic memory (see page 5-18) and entered in
-
the message memory.
The message memory with battery back-up acts as a ”collecting tank” for
maximum 100 events, which are logically TRUE, or have to be acknowl-
edged.
If the message memory contains more than one entry, the green message
LED on the front panel of the BT220 flashes.
Entries in the message memory are only deleted when
-
an event which does not have to be acknowledged changes again into
the state ”logically FALSE” (=Depart message), or
-
an event which has to be acknowledged is acknowledged by you with the
key.
Normally each entry is removed again from the message memory in this
way.
As an exception it can happen that the BT220 may not receive a ”Depart
message” for an event present.
This effect may for example happen when during an event the communica-
tion between BT220 and PS 5000 is interrupted for some reason and during
the interruption the event again changes to logically FALSE; the correspon-
ding entry was never removed from the message memory.
Using the function ”Close all messages” you delete all entries in the mess-
age memory.
ATTENTION!
Events which have to be acknowledged are deleted!
Random deletion of events which must be acknowledged can impair the
safety of the unit or severely disturb or even interrupt the production pro-
cess.
’
Make sure that no negative effects on the safety or the production pro-
cess are to be expected before you delete the message memory!
In the following description we assume that the BT220 is in the message dis-
play mode (see chapter 5.1, page 5-2).
1. Press MEN key.
The menu item ”Diagnostic memory” appears in the second display line.
2. Press key .
3. Press key B . The text ”Close all messages” appears in the second dis-
play line.
4. Press key .
5. To delete the message memory:
first press VAR key then .
To cancel the function
Press MEN.
6. Press MEN key to return to the message display mode.
Procedure
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
5-18
5.6
Display Diagnostic Memory
To log all events the BT220 has a diagnostic memory with a battery back-up.
It is structured as a ring memory and comprises a maximum of 400 entries.
Should the memory be completely full the oldest entry is overwritten by the
new entry.
Each entry consists of 2 information blocks:
-
Max. 2 lines for the event message in clear text
-
2 lines for the event number and time tags (for appearance, disappear-
ance and acknowledgment of the event).
You can have the contents of the diagnostic memory displayed on the moni-
tor step-by-step.
Here the definition of a ”Time for evaluation” is possible. Only entries with
time tags within this time period are then considered for the display.
In the following description we assume that the BT220 is in the message dis-
play mode (see chapter 5.1, page 5-2).
1. Press the MEN key.
The menu item ”Diagnostic memory” appears in the second display line.
2. Press key twice.
The text ”All entries from...” inc. the date and time of the oldest entry ap-
pears in the first display line. The cursor flashes in the input field ”Day”.
Should the diagnostic memory not contain any entries you receive a
corresponding message. Then acknowledge the message with and
press the MEN key. The BT220 returns to the message display mode.
’
If you do not want to limit the evaluation time:
Press key . Proceed to step 6.
3. Move the cursor with the cursor keys A and " to the figure to be changed
and enter the new value via
-
the numerical keys or
-
the keys Y and B.
In this way you define the beginning of the evaluation time.
4. Press key .
The text ”All entries to ...” inc. date and time of the latest entry appears in
the first display line. The cursor flashes in the input field ”Day”.
5. Move the cursor with the cursor keys A and " to the figure to be changed
and enter the new value via
-
the numerical keys or
-
the keys Y and B.
In this way you define the end of the time.
6. Press key .
The display shows the latest entry. The flashing number at the end of the
first display line only serves for your orientation and indicates the position
of the displayed entry within the diagnostic memory.
The higher the value, the older the entry concerned.
Should there not be any entries, the message ”Selected time period ex-
ceeded!” appears on the display.
7. At this point you have several control options:
-
to scroll 1 entry forward or backward:
press A or "
Procedure
BT220 Technical Information and Operation
Operation
1070 080 037-101 (99.01) GB
5-19
Should you reach the beginning or end of the diagnostic memory, the
BT220 displays the message ”Selected time period exceeded!” (see
Figure below).
-
to change between both information blocks
of an entry:
press Y or B
-
to return to the message display mode:
press MEN key twice.
-
to enter a new time period for evaluation:
first press the MEN key
then press the key.
Proceed to step 3.
x
= press corresponding key
Message in clear text 2 lines of 40 char-
acters, each displayable on the monitor
No.: arrive:_________ depart:___ quit:__
xxx DD.MM.YY HH:MM:SS HH:MM:SS HH:MM:SS
Date
Time
(arrive
message)
Time
(depart
message)
Time
(acknowledg-
ment)
Event
number
Message: ”Selected time period exceeded”
Message: ”Selected time period exceeded!”
A
"
A
"
B
Y
Latest
entry
Oldest
entry
max. 400
A
"
A
"
A
"
to the latest entry
to the oldest entry
A
"
Fig. 5-13:
Display Structure of the Diagnostic Memory
Remarks
To
-
print the diagnostic memory:
see page 5-20
-
delete the diagnostic memory:
see page 5-23
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
5-20
5.7
Printing the Diagnostic Memory
Remarks
In principle all BT220 variants are able to control a connected printer. With
the BT220-1, however, only 1 serial interface is available which is required
for the connection of the PS 5000.
’
When switched on, the PS 5000 should not be disconnected from the
BT220-1!
’
For this reason use the BT220-2 or BT220-3/7 if you want to use the
”Print” function.
For printing you need a printer with a serial interface. On page 4-5 you will
find instructions for connecting a printer.
’
Switch off the printer before you connect or separate either unit!
’
If both units are connected you can switch the printer on.
’
Make sure that the interface parameters on the printer are set to the fol-
lowing values :
8 data bits, no parity, 1 stop-bit,
hardware-handshake
’
Make sure that the font size of the printer is set to “12 CPI” (= 96 char-
acters per line) and there is sufficient paper.
Align the paper to start on a new page.
’
Switch the printer On-line, should this be necessary to receive data (see
Printer manual).
You have the option of printing the contents of the diagnostic memory
-
unsorted
(= all entries in chronological order) or
-
sorted
(= according to event numbers, chronologically
within a number).
In both cases the definition of a ”Time for evaluation” is possible. Only entries
with time tags within this time period are then considered for printing.
In the following description we assume that the BT220 is in message display
mode (see chapter 5.1, page 5-2).
1. Press the MEN key.
The menu item ”Diagnostic memory” appears in the second display line.
2. Press the B key. The text ”Print” appears in the second display line.
3. Press the key.
The text ”Diagnostic memory unsorted” appears in the second display
line.
’
If you want to print the unsorted memory:
Proceed to step 4.
If you want to print the sorted memory:
Press the B key.
Proceed to step 4.
4. Press the key.
The text ”All entries from ...” inc. date and time of the oldest entry is dis-
played in the first display line. The cursor flashes in the input field ”Day”.
If the diagnostic memory does not contain any entries you receive a
Procedure
BT220 Technical Information and Operation
Operation
1070 080 037-101 (99.01) GB
5-21
corresponding message. Acknowledge the message with and then
press the MEN key. The BT220 returns to the message display mode.
’
If you do not want to limit the evaluation time:
Press key . Proceed to step 8.
5. Move the cursor with the cursor keys A and " to the figure to be
changed and enter the new value via
-
the numerical keys or
-
the keys Y and B.
In this way you define the beginning of the evaluation time period.
6. Press key .
The text ”All entries to ...” inc. date and time of the latest entry appears in
the first display line. The cursor flashes in the input field ”Day”.
7. Move the cursor with the cursor keys A and " to the figure to be changed
and enter the new value via
-
the numerical keys or
-
the keys Y and B
den neuen Wert ein.
In this way you define the end of the time period.
8. Press key .
If you have selected ”unsorted”:
Proceed to step 10.
If you have selected ”sorted”:
Proceed to step 9.
9. Select the range of event numbers in question. For this purpose, move
the cursor with the cursor keys A and " to the figure to be changed and
enter the new value via
-
the numerical keys or
-
the keys Y and B .
-
to cancel the dialog without printing:
Press the MEN key twice.
The BT220 returns to the message display mode.
-
to acknowledge the displayed values:
Press key .
10.The BT220 initializes its printer interface.
Then it asks you to confirm the printer status:
Press key .
The printing process starts.
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
5-22
__________________________________________ No.: arrive:_________ depart:___ quit:___
TIM 1: Weld without command 81 21.04.98 20:19:44 20:19:50 20:19:49
__________________________________________ No.: arrive:_________ depart:___ quit:___
TIM 1: Sequence inhibited program 2 94 21.04.98 20:20:06 20:20:11 20:20:10
_________________________________________ No.: arrive:_________ depart:___ quit:___
TIM 1: Power unit not ready 83 21.04.98 20:20:46 20:21:26 20:20:53
__________________________________________ No.: arrive:_________ depart:___ quit:___
TIM 1: Emergency stop open / 24V= error 80 21.04.98 20:21:33 20:21:42 20:21:41
__________________________________________ No.: arrive:_________ depart:___ quit:___
TIM 1: External weld off 102 21.04.98 20:21:33 20:21:37 20:21:39
__________________________________________ No.: arrive:_________ depart:___ quit:___
PS5 error: TIM1: coupling error 5 21.04.98 22:40:35 22:40:54
(function key mode) = continue 5 21.04.98 22:47:41 22:53:00
5 21.04.98 22:53:01 22:53:03
5 21.04.98 22:53:27 22:53:38
5 21.04.98 22:54:01 22:56:30
5 21.04.98 23:01:27 23:04:54
5 21.04.98 23:05:22 23:05:54
5 22.04.98 12:09:16 12:11:56
5 22.04.98 12:13:07 12:13:10
Diagnostic memory unsorted print ended_____________22.04.98__12:13:41______Week: 17
All entries from message 1 to 2047
___________________________________________No.: arrive:__________ depart:___ quit:___
PS5 error: TIM1: coupling error 5 21.04.98 22:40:35 22:40:54
(function key mode) = continue 5 21.04.98 22:47:41 22:53:00
5 21.04.98 22:53:01 22:53:03
5 21.04.98 22:53:27 22:53:38
5 21.04.98 22:54:01 22:56:30
5 21.04.98 23:01:27 23:04:54
5 21.04.98 23:05:22 23:05:54
5 22.04.98 12:09:16 12:11:56
5 22.04.98 12:13:07 12:13:10
5 22.04.98 12:13:34 12:14:38
___________________________________________No.: arrive:__________ depart:___ quit:___
TIM 1: Emergency stop open / 24V= error 80 21.04.98 20:21:33 20:21:42 20:21:41
___________________________________________No.: arrive:__________ depart:___ quit:___
TIM 1: Weld without command 81 21.04.98 20:19:44 20:19:50 20:19:49
___________________________________________No.: arrive:__________ depart:___ quit:___
TIM 1: Power unit not ready 83 21.04.98 20:20:46 20:21:26 20:20:53
___________________________________________No.: arrive:__________ depart:___ quit:___
TIM 1: Sequence inhibited program 2 94 21.04.98 20:20:06 20:20:11 20:20:10
___________________________________________No.: arrive:__________ depart:___ quit:___
TIM 1: External weld off 102 21.04.98 20:21:33 20:21:37 20:21:39
Sorted (= according to order of event numbers)
Unsorted (= only in chronological order)
Fig. 5-14:
Examples: Diagnostic Memory Print-Outs
BT220 Technical Information and Operation
Operation
1070 080 037-101 (99.01) GB
5-23
5.8
Deleting the Diagnostic Memory
Normally the diagnostic memory with battery back-up need not be deleted.
Due to its internal ring structure it stores up to 400 entries before the oldest
entry is overwritten by a new incoming one.
Nevertheless, it may be useful to delete the diagnostic memory at certain
times.
NOTE
Loss of important report data!
If you delete the diagnostic memory you will lose the logged data which may
be used for subsequent error diagnostics or quality assurance.
’
Therefore, you should print the diagnostic memory contents before the
deleting if the memory contains important data (for printing see page
5-20).
In the following description we assume that the BT220 is in the message dis-
play mode (see chapter 5.1, page 5-2).
1. Press the MEN key.
The menu item ”Diagnostic memory” appears in the second display line.
2. Press the key.
3. Keep pressing the B key until the text ”Delete diagnostic memory” ap-
pears in the second display line.
4. Press the key.
5. To delete the diagnostic memory:
first press the VAR key then .
The BT220 displays: ”Diagnostic memory will be deleted!”
To cancel the function:
press the MEN key.
6. Press the MEN key to return to the message display mode.
Procedure
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
5-24
5.9
Adapting the BT220 Display
In this section you find all internal display functions of the BT220.
’
Set these functions during commissioning.
5.9.1
Setting the Message Display Mode
In case of several active events, the BT220 automatically shows one event
on the display. The event automatically displayed can be defined in accord-
ance with the following criteria:
Last value with priority:
the latest event with the highest priority is
displayed first (default setting)
Last value without priority:
the latest event is displayed first
First value with priority:
the oldest event with the highest priority is
displayed first
First value without priority:
the oldest event is displayed first.
In the following description we assume that the BT220 is in the message dis-
play mode (see chapter 5.1, page 5-2).
1. Press the MEN key.
The menu item ”Diagnostic memory” appears in the second display line.
2. Keep on pressing the B key until the text ”Special function” is displayed
in the second display line.
3. Press the key.
4. Keep on pressing the B key until the text ”System functions” is displayed
in the second display line.
5. Press the key three times.
6. The current setting is displayed behind the text ”Mode”.
To change the message display mode:
Press the VAR key.
To cancel the function:
Press the MEN key twice.
7. Select the required mode using the keys Y and B.
8. To activate the selected mode:
Press the key.
To keep the current setting:
Press the MEN key.
Proceed to step 6.
Procedure
BT220 Technical Information and Operation
Operation
1070 080 037-101 (99.01) GB
5-25
5.9.2
Setting the Flash Rate
Events which have to be acknowledged are shown in the display as flashing
text.
The times for the on and off phases are adjustable.
In the following description we assume that the BT220 is in the message dis-
play mode (see chapter 5.1, page 5-2).
1. Press the MEN key.
The menu item ”Diagnostic memory” appears in the second display line.
2. Keep on pressing the B key until the text ”Special function” is displayed
in the second display line.
3. Press the key.
4. Keep on pressing the B key until the text ”System functions” is displayed
in the second display line.
5. Press the key twice.
6. Keep on pressing the B key until the text ”Flash rate” is displayed in the
second display line.
7. Press the key.
8. The current setting is displayed behind the text ”Flash rate”.
To change values:
Press the VAR key.
To cancel function:
Press the MEN key twice.
9. Move the cursor with the cursor keys A and " to the figure to be changed
and enter the new value (range: 0.1 to 3.9 sec.) via
-
the numerical keys or
-
the keys Y and B .
Define both times in this way.
10.To activate selected values:
Press the key.
To keep the current setting:
Press the MEN key.
Proceed to step 8.
Procedure
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
5-26
5.9.3
Setting ”Automatic Message Scrolling”
In case of events with a text of more than 2 lines, the BT220 only shows the
first 2 lines initially. The remaining text can then be made visible in the follow-
ing way:
-
manually using the keys Y and B (these call up the previous and the
next two lines) or
-
automatically using the ”Message Scroll” function (display of the next two
lines within a certain time period).
In the following description we assume that the BT220 is in the message dis-
play mode (see chapter 5.1, page 5-2).
1. Press the MEN key.
The menu item ”Diagnostic memory” appears in the second display line.
2. Keep pressing the B key until the text ”Special function” is displayed in
the second display line.
3. Press the key.
4. Keep on pressing the B key until the text ”System functions” is displayed
in the second display line.
5. Press the key twice.
6. Press the B key until the text ”Autom. message scroll” is displayed in the
second display line.
7. Press the key.
8. The current setting is displayed in the first line.
To change values:
Press the VAR key.
To cancel the function:
Press the MEN key twice.
9. Move the cursor with the cursor keys A and " to the entry to be changed
and enter the new value using the keys Y and B (scroll time range: 1 to
99 sec.).
10.To activate selected values:
Press key .
To keep the current setting:
Press the MEN key.
Proceed to step 8.
Procedure
BT220 Technical Information and Operation
Operation
1070 080 037-101 (99.01) GB
5-27
5.9.4
Display Parameters
This function is used to set the display brightness.
’
Set the brightness so that the display can be optimally read at any time of
the day. Please note that a reduced brightness protects the VFD tube of
the display monitor.
In the following description we assume that the BT220 is in the message dis-
play mode (see chapter 5.1, page 5-2).
1. Press the MEN key.
The menu item ”Diagnostic memory” appears in the second display line.
2. Keep pressing the B key until the text ”Special function” is displayed in
the second display line.
3. Press the key.
4. Keep on pressing the B key until the text ”System functions” is displayed
in the second display line.
5. Press the key twice.
6. Press the B key until the text ”Display parameter” is displayed in the sec-
ond display line.
7. Press the key.
8. The current setting is displayed in the first line.
To change values:
Press the VAR key.
To cancel the function:
Press the MEN key twice.
9. Enter the new value using the keys Y and B (30%, 50%, 75% or 100%;
standard: 75%).
10.To activate selected values:
Press key .
To keep the current setting:
Press the MEN key.
Proceed to step 8.
Procedure
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
5-28
5.10
Testing the BT220 Keyboard
If need be you can test the keyboard for proper functioning.
In the following description we assume that the BT220 is in the message dis-
play mode (see chapter 5.1, page 5-2).
1. Press the MEN key.
The menu item ”Diagnostic memory” appears in the second display line.
2. Keep pressing the B key until the text ”Special function” is displayed in
the second line.
3. Press the key.
4. Keep on pressing the B key until the text ”Test functions” is displayed in
the second line.
5. Press the key twice.
The test mode is active.
The code of a pressed key is displayed in the first display line.
Exception: MEN key (reserved for canceling the test).
6. To cancel the keyboard test:
Press the MEN key twice.
Procedure
BT220 Technical Information and Operation
Operation
1070 080 037-101 (99.01) GB
5-29
5.11
Configuring the Printer Interface (X4)
Remarks
With BT220-1:
the settings of the interface described below are only ac-
tive when you print out the diagnostic memory.
The BT220-1 in this case automatically changes the interface parameters.
After the printing process the parameters necessary for communication with
the PS 5000 (19200 bits/s; 8 data bits; even parity; 1 stop-bit) are set again.
Communication with a peripheral unit is only possible when
-
the connection cable is correctly wired (inc. any necessary Handshake
leads),
-
the interface parameter settings of both units are identical.
In the following description we assume that the BT220 is in the message dis-
play mode (see chapter 5.1, page 5-2).
1. Press the MEN key.
The menu item ”Diagnostic memory” appears in the second display line.
2. Keep pressing the B key until the text ”Special function” is displayed in
the second line.
3. Press the key.
4. Keep on pressing the B key until the text ”System functions” is displayed
in the second display line.
5. Press the key.
6. Keep on pressing the B key until the text ”Print parameter” is displayed in
the second display line.
7. Press the key twice.
8. The current parameters are displayed in the first display line.
To change values:
Press the VAR key.
To cancel the function:
Press the MEN key twice.
9. Move the cursor with the cursor keys A and " to the setting to be
changed and enter the new value using the keys Y and B . Value range:
Baud rate:
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 76800
Handshake: without =
no flow control
Hardware = flow control through CTS, RTS leads
Xon/Xoff =
flow control with control symbol Xon/Xoff
Xon/Xoff + DTR = inc. testing of the DSR input
Protocol:
7O1, 7E1, 7N2, 7O2, 7E2, 8N1, 8O1, 8E1, 8N2
1st character:
Number of data bits
2nd character:
O =odd parity
E = even parity
N = no parity
3rd character:
Number of stop-bits
10.To activate selected values:
Press key .
To keep the current setting:
Press the MEN key.
Proceed to step 8.
Procedure
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
5-30
5.12
Inhibiting the Control Function
To protect the BT220 from unauthorized access a 4-digit freely definable
key code can be assigned both to the
-
menu items within the BT220 (see page 5-33) and to the
-
menu items in the function key mode (see page 5-6).
Access to a protected menu level is only possible when the correct key code
is entered.
Here you can decide for the menu items of the function key mode whether
access to a menu item or only changes within a menu items should be pro-
tected by a key code.
Various strategies can be considered for access protection:
-
User group oriented:
Define a specific key code for each user group (e.g. system administra-
tor, master, technician etc.).
Depending on the privileges/tasks of the individual user group you may
then assign the relevant key code to the individual menu items.
Disadvantage: a user with extensive privileges must generally know all
key codes of the lower-level user groups.
-
Function oriented:
Define a specific key code for each ”critical” function area (from a safety
point of view) (e.g. changing welding parameters, deleting diagnostic or
message memory, changing key codes (!!) etc.).
Depending on the function areas you may then assign the relevant key
code to the individual menu items.
Disadvantage: any user with comprehensive machine-related tasks has
to know all - or at least several - key codes of the individual function
areas.
ATTENTION!
Unauthorized alteration of or prying into key codes possible!
’
Use a separate key code for protecting the menu item ”Change key code”
(for menu structure see page 5-33).
’
Only make this key code known to authorized people. People who know
this key code can display all key codes stored and also change them!
NOTE
Deleting or overwriting the BT220 internal data is possible!
Via the menu item ”Text management” (for menu structure see page 5-33)
functions can be called up which delete or overwrite the internal data of the
BT220.
’
Therefore, you should protect the menu item ”Text management” from
unauthorized access.
’
Only make this key code known to authorized people. Unauthorized
people who know this key code could damage the BT220.
BT220 Technical Information and Operation
Operation
1070 080 037-101 (99.01) GB
5-31
In the following description we assume that the BT220 is in the message dis-
play mode (see chapter 5.1, page 5-2).
1. Press the MEN key.
The menu item ”Diagnostic memory” appears in the second display line.
2. Keep pressing the B key until the text ”Special function” is displayed in
the second line.
3. Press the key.
4. Keep on pressing the B key until the text ”System functions” is displayed
in the second display line.
5. Press the key.
6. Press the�B key until the text ”Change key code” is displayed in the
second display line.
7. Press the key.
8. The text ”Menu” appears in the second display line.
-
To cancel the function:
Press the MEN key.
To change key codes of
-
internal menu items of the BT220:
press the key and
proceed to step 9.
-
functions of the function key mode:
proceed to step 14.
9. The currently selected BT220 menu item and the key code assigned to it
appear in the first display line (”Code”).
Code ”0000” means: menu item is not protected.
10.-
To cancel the function:
Press the MEN key twice.
-
To select menu items (for structure see page 5-33): Press Y or B
-
To change the key code:
Press the VAR key.
11.Move the cursor with the cursor keys A and " to the figure to be changed
and enter the the required key code via
-
the numerical keys or
-
the keys Y and B .
12.To activate the displayed key code:
Press the key.
To cancel the changes:
Press the MEN key.
13.-
To process further internal menu items
of the BT220:
proceed to 10.
-
To process menu items of the function key mode:
Press MEN.
14.Press the B key.
The text ”Function keys/Symbols” appears in the second display line.
15.Press the key.
The ”Entry number” flashes.
An entry must contain the following details:
-
function number (F1 - F50) in the function key mode, which should be
protected
-
whether a key code must be entered for access or for a modification
(Query..=> Call up / change)
-
the assigned key code.
Code ”0000” means: function number is not protected.
You can see from the function number displayed directly behind the entry
number (e.g.: ”1: F2”) whether an entry already contains data.
A total of 50 entries can be stored.
Procedure
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
5-32
16.-
To select an entry:
Press Y or B.
-
To change the data of the selected entry:
Press the VAR key.
-
To cancel the function:
Press the MEN key twice.
17.The cursor flashes in the first line.
- To change the function number:
Keep pressing the " key until the
cursor flashes in the first possible
location behind the entry number.
Then select the required function
number with Y or B.
Should
the
selected
function
number already exist in another
entry, it is automatically deleted
there as soon as the changes to the
current entry are activated.
- To delete the function number:
Place the cursor behind the function
number using " .
Then press the A key.
- To change the query type:
Keep pressing the " key until the
text ”Call up” or ”Change” flashes.
Then select the required type with Y
or B.
- To change the key code:
Keep pressing the " key until the
cursor flashes behind the text
”Code”.
Then enter the required key code
with the numerical keys or with
Y
or B .
- To activate changes:
Press the key and proceed to
step 16.
- To cancel the changes:
Press the MEN key and proceed to
step 16.
BT220 Technical Information and Operation
Operation
1070 080 037-101 (99.01) GB
5-33
5.13
Overview: BT220 Specific Functions and Parameters
Diagnostic memory
Print
Special functions
Change language (p. 5-3)
Display diagnostic memory (p. 5-18)
Close all messages (p. 5-17)
Delete diagnostic memory (p. 5-23)
Diagnostic memory unsorted (p. 5-20)
Diagnostic memory sorted (p. 5-20)
Transfer texts
Available text memory
Initialize text memory
Transfer mother text
System functions
Display
Print parameters (p. 5-29)
Change key code (p. 5-30)
Message display mode (p. 5-24)
Flash rate (p. 5-25)
Autom. message scroll (p. 5-26)
Display parameter (p. 5-27)
Test functions
Key test (p. 5-28)
x
= press corresponding key
B
Y
B
Y
B
Y
B
Y
B
Y
B
Y
B
Y
B
Y
B
Y
B
Y
B
Y
B
Y
B
Y
B
Y
B
Y
B
Y
Message
display
mode
A
MEN
to A
MEN
to A
MEN
to A
MEN
to A
MEN
to A
MEN
to A
MEN
to A
MEN
to A
MEN
to A
MEN
to A
MEN
to A
MEN
to A
MEN
to A
MEN
to A
MEN
to A
MEN
to A
MEN
see B
see B
see B
see B
see B
see B
see B
see B
see B
see B
see B
see B
see B
see B
see B
see B
see B
B: with to the function,
back with MEN
Text management
Fig. 5-15:
Menu Tree of the BT220 Specific Functions and Parameters
BT220 Technical Information and Operation
Maintenance
1070 080 037-101 (99.01) GB
6-1
6
Maintenance
6.1
Battery
A battery is necessary to back up the internal memory modules. Depending
on the operating environment, the battery must be changed after certain cy-
cles.
Battery type:
Lithium-Thionychloride (Sonnenschein SL-160)
hermetically sealed
Size:
AA (R6, UM-3)
Capacity:
1.9 Ah
Storage capability: Capacity loss <10% after 10 years at 25_C
Data retention:
> 2.5 years over the whole temperature range (0_C to
+50_C)
> 7.5 years at 40_C
> 15 years at 20_C
Remarks
When the battery is replaced, the contents of the diagnostic memory and
message memory are deleted.
1. Switch the unit off.
2. Remove all connection cables from the BT220.
3. Make sure that the BT220 cannot fall out of the assembly cutout and
loosen the screw terminals on the top and bottom of the BT220 housing.
Take out the screw terminals and draw the unit out of the assembly
cutout.
4. Lay the BT220 front side facing down on a soft, even surface.
Loosen the 4 screws (1) and pull the housing upwards. The battery (3) is
on the underside of the main circuit board.
1
5
6
9
1
1
1
1
2
3
+
Fig. 6-1:
Changing the Battery
5. Unsolder the battery from the solder support points. Ensure correct po-
larity and solder in the new battery.
6. Put the housing carefully back on and screw it tight.
7. Reinstall the BT 220 and plug in all the cables again.
Changing Battery
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
6-2
6.2
Reset
Should a software reset of the BT220 be necessary (e.g. after faults of the
BT220), proceed as follows:
1. Switch off the BT220 power supply.
2. Press and hold down keys ”1” and Y at the same time.
3. Switch the BT220 power supply back on.
Then you can release the keys.
6.3
Software release
To display the current software status of the BT220:
1. Press the MEN key.
2. Press the key i.
(Software status: the last 3 digits in the first display line)
3. To return to the message display mode:
Press key i then
press the MEN key.
BT220 Technical Information and Operation
Appendix
1070 080 037-101 (99.01) GB
7-1
7
Appendix
7.1
Information on the STK multi-contact interface board
Connection:
Screw terminal plug
MSTB 2.5 / 3-ST-5.08
Supply voltage:
24 VDC
Current consumption:
approx. 1 A
X1
+24 VDC
0 VDC
PE
Fig. 7-1:
Terminal Assignment X1
For the setting use DIP switch block S1. The Baud rate setting is only effec-
tive for the interface at channel 4 (connection to the BT220).
Front panel
S1
Fig. 7-2:
Position of S1
On
Off
1
2
3
4
5
6
7
8
S1
res. res. res.
res.
res.:
reserved. Must be OFF.
Baud rate: 19200: ON
9600:
OFF
Number of connected PS 5000
(example setting: 3)
Baud rate
(here: 19200)
No.:
1 PS 5000:
2 PS 5000:
3 PS 5000:
4 PS 5000:
5 PS 5000:
6 PS 5000:
7 PS 5000:
Switch
6 7 8
OFF OFF ON
OFF ON OFF
OFF ON ON
ON OFF OFF
ON OFF ON
ON ON OFF
ON ON ON
Fig. 7-3:
Setting the Baud Rate and Number of Connected PS 5000
’
Make sure that the selected Baud rate is identical with that on the BT220.
Power Supply (to X1)
Setting the ”Baud Rate”
and ”Number of Con-
nected PS 5000”
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
7-2
For the connection of max. 7 PS 5000 the multi-contact interface board can
be fitted with RS232 interface modules.
All interface leads are isolated from the power supply to X1.
Connection:
Sub-HD socket, 15-pin
Type:
RS232
Cable length:
max. 15m
Cable type:
shielded, core cross-section min. 0.14mm2
Transmission rate: 19200 bits/s
Parameters:
8E1 (8 data bits, even parity, 1 stop-bit)
Handshake:
Software handshake (XON, XOFF)
1
2
3
RX
TX
4
max. 15 m
STK (channels 1-3 and
5-8; Sub-HD, 15-pin)
Shield continuity via metal housing of the plug
connection or via a spade connector on the housing
5
GND
6
7
8
9
PS 5000 (X1; Sub-D, 9-pin)
TX
RTS�/�DTR
CTS
Socket
Plug
2
3
5
RX
4
6
7
GND
8
+5V
15
Fig. 7-4:
Connection of PS 5000 to the STK multi-contact interface board
ATTENTION!
Malfunctions and damage are possible!
Pin 15 of the Sub-HD socket is connected to a 5V auxiliary voltage.
’
Make sure that pin 15 is not wired. No external consumer should be con-
nected without consulting us.
Communication between STK and BT220 is established via a separate in-
terface module (RS232 or RS485) on the multi-contact interface board
(channel 4).
Information on the wiring is available in
-
chapter 4.3 from page 4-4 (for RS232 connection) or in
-
chapter 4.4 on page 4-6 (for RS485 connection).
Connection:
STK - PS 5000
Connection:
STK - BT220
BT220 Technical Information and Operation
Appendix
1070 080 037-101 (99.01) GB
7-3
7.2
List of Figures
Fig. 2-1:
Front View BT220
2-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 2-2:
Connection of a PS 5000
2-2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 2-3:
Connection of 2 PS 5000
2-3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 2-4:
Connection of max. 7 PS 5000 to BT220 via STK multi-contact
interface board
2-3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 3-1:
Installation positions and distances
3-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 4-1:
Connections on the BT220-1
4-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 4-2:
Connections on the BT220-2
4-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 4-3:
Connections on the BT220-3/7
4-2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 4-4:
Terminal Assignment X1
4-2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 4-5:
Terminal Assignment X2
4-3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 4-6:
Connection of PS 5000 to BT220
4-4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 4-7:
Connection of a Serial Printer
4-5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 4-8:
Connection of the STK multi-contact interface board:
Channel 4 fitted with RS232 interface
4-5
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 4-9:
Connection of the STK multi-contact interface board.
Channel 4 fitted with RS485 Interface
4-6
. . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 4-10:
Bus Termination for RS485 Connections
4-6
. . . . . . . . . . . . . . . . . . . . . . . .
Fig. 5-1:
Front View BT220
5-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 5-2:
Front View BT220
5-2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 5-3:
Command Options in the Main Menu of the Function Key Mode
5-6
. . . .
Fig. 5-4:
Operating Sequence: Selection of Program and Weld timer
5-7
. . . . . . . .
Fig. 5-5:
Operating Sequence: F2 Sequence
5-8
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 5-6:
Operating Sequence: F3 Monitoring
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
Fig. 5-7:
Operating Sequence: F4 Last Weld
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
Fig. 5-8:
Operating Sequence: F5 Slope
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
Fig. 5-9:
Operating Sequence: F6 Pressure Profile
. . . . . . . . . . . . . . . . . . . . . . . 5-13
Fig. 5-10:
Operating Sequence: F7 Stepper Diagnostics
. . . . . . . . . . . . . . . . . . . 5-14
Fig. 5-11:
Operating Sequence: F8 FPO_1 (freely programmable
analog output)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15
Fig. 5-12:
Operating Sequence: F9 Heat Correction
. . . . . . . . . . . . . . . . . . . . . . . 5-16
Fig. 5-13:
Display Structure of the Diagnostic Memory
. . . . . . . . . . . . . . . . . . . . . 5-19
Fig. 5-14:
Examples: Diagnostic Memory Print-Outs
. . . . . . . . . . . . . . . . . . . . . . . 5-22
Fig. 5-15:
Menu Tree of the BT220 Specific Functions and Parameters
. . . . . . 5-33
Fig. 6-1:
Changing the Battery
6-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 7-1:
Terminal Assignment X1
7-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 7-2:
Position of S1
7-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fig. 7-3:
Setting the Baud Rate and Number of Connected PS 5000
7-1
. . . . . . . .
Fig. 7-4:
Connection of PS 5000 to the STK multi-contact interface board
7-2
. . .
BT220 Technical Information and Operation
Appendix
1070 080 037-101 (99.01) GB
7-5
7.3
Subject index
A
Acknowledge electrode change, 5-14
Acknowledge tip dress, 5-14
Air humidity, 3-1
Analog output, 5-15
Application Examples, 2-2
Assembly, 3-1
B
BT220
Degree of protection, 3-1
Fixation, 3-2
Menu tree, 5-33
Weight, 3-1
BT220-1, 2-2
BT220-2, 2-2
BT220-3/7, 2-2
Bus termination, 4-6
C
Cable routing, 3-1
Changing battery, 6-1
Close all messages, 5-17
Command keys, 5-1
Connection, 4-1
Lamps, 4-3
of PS 5000 to BT220, 4-4
of STK to BT220, 4-5, 4-6
Printer, 4-5
PS 5000 to STK, 7-2
Ready signal, 4-3
Constructions, BT220, 2-2
D
Degree of protection, 3-1
Diagnostic memory
delete, 5-23
display, 5-18
print, 5-20
Dimensions, 3-1
Display, 5-2
Brightness, 5-27
Flash rate, 5-25
Message scrolling, 5-26
Display software release, 6-2
E
Electrical connection, 4-1
EMERGENCY-OFF devices, 1-5
Error message, 5-2
Event
Acknowledge, 5-2
Active, 5-2
Call up Help, 5-2
Explanation of pictographs, 1-1
Explanation of symbols, 1-1
F
Fault message, 5-2
FPO_1, 5-15
Front View BT220, 5-2
Function key mode, 5-4
Main menu, 5-6
H
Heat correction, 5-16
I
Inhibiting the control function, 5-30
Installation, 1-6, 3-1
Interfaces, 4-1
RS232, 4-4
RS485, 4-6
Bus Termination, 4-6
K
Key code, 5-30
Keyboard, test, 5-28
Keys, 5-1
BT220 Technical Information and Operation
1070 080 037-101 (99.01) GB
7-6
L
Lamp outputs, 4-3
Last weld, 5-11
LED’s on front panel, 5-2
List of Figures, 7-3
M
Magnetic fields, 1-3
Maintenance, 6-1
Menu Tree of the BT220 Main Menu, 5-33
Message Display Mode, 5-2
Adjust, 5-24
Message memory, delete, 5-17
Minimum all-round clearance, 3-1
Modifications by the user, 1-5
Monitoring, 5-9
Monitoring contact, 1-7
N
Normal use, 1-4
O
Operation, 5-1
Operation of manual welding guns, 1-3
Options, 2-2
Overview, BT220 menu functions, 5-33
P
Phone no., Training center, 1-4
Power supply connection
BT220, 4-2
STK multi-contact interface board, 7-1
Pressure control, 5-13
Printer, 4-5
Interface parameters, 5-29
Priorities, 5-24
Program number, 5-7
Protection from unauthorized access, 5-30
Q
Qualified personnel, 1-4
R
Ready output, 4-3
Reset of the BT220, 6-2
S
S1, 7-1
Safety instructions
EMERGENCY-OFF devices, 1-5
Fault reset, 1-7
Maintenance/Repair, 1-5
Modifications, 1-5
Retrofits, 1-5
Spare parts, 1-5
Sequence, 5-8
Set System Language, 5-3
Setting the time, 5-3
Slope, 5-12
Squeeze times, 1-7
Start remotely, 1-7
Start Simulation, 1-7
Stepper, 5-14
Stepper Diagnostics, 5-14
STK, 2-2, 7-1
STK multi-contact interface board, 2-2, 7-1
Baud rate for BT220, 7-1
Channel position, 2-3
Connections, 2-3
Connections to PS 5000, 7-2
Power supply, 7-1
S1, 7-1
Setting the number of PS 5000, 7-1
X1, 7-1
BT220 Technical Information and Operation
Appendix
1070 080 037-101 (99.01) GB
7-7
T
Temperature ranges, 3-1
Test procedures, 1-5
TIM, 5-7
Tip wear, 5-14
Training courses, 1-4
V
Ventilation, 3-1
W
Warning, 5-2
Wear display, 5-14
Weld timer number, 5-7
Welding data, 5-4
Actual current, 5-11
Cool time, 5-8
Current monitoring, 5-9
Heat, 5-8
Heat correction, 5-16
Hold time, 5-8
Monitoring
Conditional welds, 5-9
Reference current, 5-9
Tolerance, 5-9
Off time, 5-8
Phase angle, 5-11
Pre-squeeze time, 5-8
Pressure control
Base pressure, 5-13
Welding pressure, 5-13
Program number, 5-7
Pulsation, 5-8
Slope, 5-12
Squeeze time, 5-8
Weld time, 5-8
Welding splashes, 1-8
Working safely, 1-8
X
X1
BT220, 4-2
STK multi-contact interface board, 7-1
X2, BT220, 4-3