ABB CM 16 Manual
| Brand: | ABB |
| Category: | Temperature Controller |
| Model: | CM 16 (Manual ) |
| File Type: | |
| File Size: | — |
| Pages: | 20 |
Text of ABB CM 16 Manual
Table of contents
Page
Remarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Installation and commissioning
1.
Identifying the instrument . . . . . . . . . . . . . . . . . . . . .
3
2.
Selecting installation site and
mounting the instrument . . . . . . . . . . . . . . . . . . . . . .
3
3.
Connecting signals . . . . . . . . . . . . . . . . . . . . . . . . . .
4
4.
Connecting the power supply . . . . . . . . . . . . . . . . . .
4
5.
C
Installation and commissioning
1.
Identifying the instrument
The unit is identified by its rating plate. The rating plate is located
on the side of the case. It contains the following information:
−
voltage range of the built-in power supply unit
−
type of sensor input for which the controller has been adap-
ted to at the factory: thermocouple (“T/C”), Pt100 resistance
thermometer (“RTD”) or mA input
−
type of output: 0/4...20 mA or relay ou
Connecting the signals
Fig. 2
Wiring diagram
Z-18800
1, 2
Alarm
3, 4, 5
Sensor input (RTD, TC, mA)
6, 7
Power supply
8, 9, 10 Control output (relay, mA)
Caution
When selecting the lead material as well as when installing
and connecting the power leads, the local specifications for
installation of power current systems are to be observed.
The controller is ex works either equipped with a measuring input
for thermocouple, Pt100-resistance thermometer or
ABB CM 16 Status LED for alarm relay
4
Status LED for output relay
5
Status display „manual mode“
6
Status display „selftune active“
7
Key „increase“
8
Key „menü“
9
Key „start selftune“ or „back to main operator level“
10
Key „decrease“
Key
Function description
switches to the next parameter within a menu
level.
if pressed for at least 6 s, switches to the n
Parameter definition
Parameter-definition principle
Fig. 4
Flow diagram
Z-18796
6
Parameter definition
Display the first parameter accessible at the main operator
level:
Remarks
At the main operator level, only those parameters are accessi-
ble, which were defined in parameter
(see page 9). The fac-
tory setting for
is 0, i.e. no additional parameters can be se-
lected at the main operator level.
If parameter
has the value 1, parameters can only be dis-
played but not changed (see page 9).
2.
Change parameter:
,
3.
Display the next parameter:
4.
Change
ABB CM 16 In order to parameter-define the controller completely, the steps
provided below must be processed consecutively.
Key
Display
Parameter
Parameter values
underlined or FS = Factory Setting
change
Main operator level
for at
least 6 s
defines the alarm setpoint value for the alarm con-
figured under
. Depending on the type of alarm
defined for the parameter
, this can be either an
absolute alarm value or a deviation alarm va
ABB CM 16 underlined or FS = Factory Setting
change
defines integral (reset) time. This action component
prevents stationary control deviations.
Notice
Changing this parameter has decisive effects on the
control action. A big integral action time in a slow
control, whereas a too small value can lead to over-
shooting and even to a destabilisation of the entire
control process.
0...120...3600 s
,
defines the derivative (rate)