ABB Relion 630 Series Communication Protocol Manual
Read Online
Read the ABB Relion 630 Series Communication Protocol Manual online using the built-in PDF viewer.
Text of the manual
Document ID: 1MRS757203
Issued: 2011-02-23
Revision: A
Product version: 1.1
© Copyright 2011 ABB. All rights reserved
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third
party, nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license
and may be used, copied, or disclosed only in accordance with the terms of such
license.
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 Vaasa, Finland
Telephone: +358 10 2211
Facsimile: +358 10 22 41094
http://www.abb.com/substationautomation
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The IED is designed in accordance with the international
standards of the IEC 60255 series.
Table of contents
Section 1
Introduction.......................................................................5
This manual........................................................................................5
Intended audience..............................................................................5
Product documentation.......................................................................6
Product documentation set............................................................6
Document revision history.............................................................7
Related documentation..................................................................8
Symbols and conventions...................................................................8
Safety indication symbols..............................................................8
Manual conventions.......................................................................8
Section 2
IEC 60870-5-103 overview.............................................11
IEC 60870-5-103 standard...............................................................11
Communication system principle.................................................12
Section 3
IEC 60870-5-103 communication engineering...............13
IEC 60870-5-103 engineering in PCM600........................................13
Specific IEC 60870-5-103 settings...................................................13
Settings........................................................................................14
IEC 60870-5-103 time synchronization............................................14
Section 4
IEC 60870-5-103 vendor specific implementation.........17
Signals in monitoring direction..........................................................17
Measurands for IEC 60870-5-103 I103MEAS.............................17
Functionality...........................................................................17
Function block........................................................................18
Signals....................................................................................18
Settings..................................................................................18
Supported information types..................................................19
Measurands user defined signals for IEC 60870-5-103
I103MEASUSR............................................................................20
Functionality...........................................................................20
Function block........................................................................20
Signals....................................................................................20
Settings..................................................................................21
Supported information types..................................................21
Function status auto-recloser for IEC 60870-5-103 I103AR........22
Functionality...........................................................................22
Function block........................................................................22
Signals....................................................................................22
Table of contents
630 series
1
Communication Protocol Manual
Supported information types..................................................22
Function status earth-fault for IEC 60870-5-103 I103EF.............23
Functionality...........................................................................23
Function block........................................................................23
Signals....................................................................................23
Settings..................................................................................23
Supported information types..................................................24
Function status fault protection for IEC 60870-5-103
I103FLTPROT.............................................................................24
Functionality...........................................................................24
Function block........................................................................25
Signals....................................................................................25
Settings..................................................................................26
Supported information types..................................................26
IED status for IEC 60870-5-103 I103IED....................................27
Functionality...........................................................................27
Function block........................................................................28
Signals....................................................................................28
Settings..................................................................................28
Supported information types..................................................28
Supervison status for IEC 60870-5-103 I103SUPERV................29
Functionality...........................................................................29
Function block........................................................................29
Signals....................................................................................29
Settings..................................................................................30
Supported information types..................................................30
Status for user defined signals for IEC 60870-5-103
I103USRDEF...............................................................................30
Functionality...........................................................................30
Function block........................................................................31
Signals....................................................................................31
Settings..................................................................................32
Supported information types..................................................32
Commands in control direction.........................................................33
Function commands for IEC 60870-5-103 I103CMD..................33
Functionality...........................................................................33
Function block........................................................................33
Signals....................................................................................33
Settings..................................................................................33
Supported information types..................................................34
IED commands for IEC 60870-5-103 I103IEDCMD....................34
Functionality...........................................................................34
Function block........................................................................34
Table of contents
2
630 series
Communication Protocol Manual
Supported information types..................................................35
Function commands user defined for IEC 60870-5-103
I103USRCMD..............................................................................35
Functionality...........................................................................35
Function block........................................................................35
Signals....................................................................................36
Settings..................................................................................36
Supported information types..................................................36
Function commands generic for IEC 60870-5-103
I103GENCMD..............................................................................37
Functionality...........................................................................37
Function block........................................................................37
Signals....................................................................................37
Settings..................................................................................38
Supported information types..................................................38
IED commands with position and select for IEC
60870-5-103 I103POSCMD........................................................38
Functionality...........................................................................38
Function block........................................................................38
Signals....................................................................................39
Settings..................................................................................39
Supported information types..................................................39
Disturbance recorder file transfer.....................................................39
Disturbance upload......................................................................39
Deviations from the standard.......................................................40
Section 5
Interoperability................................................................43
Physical layer...................................................................................43
Optical interface...........................................................................43
Transmission speed....................................................................43
Application layer...............................................................................43
Transmission mode for application data......................................43
Common address of ASDU.........................................................44
Selection of standard information numbers in monitor
direction.......................................................................................44
System functions in monitor direction.....................................44
Status indications in monitor direction....................................44
Supervision indications in monitor direction...........................45
Earth fault indications in monitor direction..............................45
Fault indications in monitor direction......................................45
Auto-reclosure indications in monitor direction.......................46
Measurands in monitor direction............................................46
Table of contents
630 series
3
Communication Protocol Manual
Generic functions in monitor direction....................................46
Selection of standard information numbers in control
direction.......................................................................................47
System functions in control direction......................................47
General commands in control direction..................................47
Generic functions in control direction.....................................47
Basic application functions..........................................................48
Miscellaneous..............................................................................48
Section 6
Glossary.........................................................................51
Table of contents
4
630 series
Communication Protocol Manual
The communication protocol manual describes a communication protocol
supported by the IED. The manual concentrates on vendor-specific implementations.
1.2
Intended audience
This manual addresses the communication system engineer or system integrator
responsible for pre-engineering and engineering for communication setup in a
substation from an IED perspective.
The system engineer or system integrator must have a basic knowledge of
communication in protection and control systems and thorough knowledge of the
specific communication protocol.
1MRS757203 A
Section 1
Introduction
630 series
5
Communication Protocol Manual
Product documentation set
Planning & purchase
Engineering
Installing
Commissioning
Operation
Maintenance
Decommissioning
deinstalling & disposal
Application manual
Operation manual
Installation manual
Service manual
Engineering manual
Commissioning manual
Communication protocol
manual
Technical manual
Planning & purchase
Engineering
Installing
Commissioning
Operation
Maintenance
Decommissioning
deinstalling & disposal
Planning & purchase
Engineering
Installing
Commissioning
Operation
Maintenance
Decommissioning
deinstalling & disposal
Application manual
Application manual
Operation manual
Operation manual
Installation manual
Installation manual
Service manual
Service manual
Engineering manual
Engineering manual
Commissioning manual
Commissioning manual
Communication protocol
manual
Communication protocol
manual
Technical manual
Technical manual
en07000220.vsd
IEC07000220 V1 EN
Figure 1:
The intended use of manuals in different lifecycles
The engineering manual contains instructions on how to engineer the IEDs using
the different tools in PCM600. The manual provides instructions on how to set up a
PCM600 project and insert IEDs to the project structure. The manual also
recommends a sequence for engineering of protection and control functions, LHMI
functions as well as communication engineering for IEC 60870-5-103, IEC 61850
and DNP3.
The installation manual contains instructions on how to install the IED. The
manual provides procedures for mechanical and electrical installation. The chapters
are organized in chronological order in which the IED should be installed.
The commissioning manual contains instructions on how to commission the IED.
The manual can also be used by system engineers and maintenance personnel for
assistance during the testing phase. The manual provides procedures for checking
of external circuitry and energizing the IED, parameter setting and configuration as
Section 1
1MRS757203 A
Introduction
6
630 series
Communication Protocol Manual
well as verifying settings by secondary injection. The manual describes the process
of testing an IED in a substation which is not in service. The chapters are organized
in chronological order in which the IED should be commissioned.
The operation manual contains instructions on how to operate the IED once it has
been commissioned. The manual provides instructions for monitoring, controlling
and setting the IED. The manual also describes how to identify disturbances and
how to view calculated and measured power grid data to determine the cause of a
fault.
The service manual contains instructions on how to service and maintain the IED.
The manual also provides procedures for de-energizing, de-commissioning and
disposal of the IED.
The application manual contains descriptions of preconfigurations. The manual can
be used as a reference for configuring control, protection, measurement, recording
and LED functions. The manual can also be used when creating configurations
according to specific application requirements.
The technical manual contains application and functionality descriptions and lists
function blocks, logic diagrams, input and output signals, setting parameters and
technical data sorted per function. The manual can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during
normal service.
The communication protocol manual describes a communication protocol
supported by the IED. The manual concentrates on vendor-specific implementations.
The point list manual describes the outlook and properties of the data points
specific to the IED. The manual should be used in conjunction with the
corresponding communication protocol manual.
The service manual is not available yet.
1.3.2
Document revision history
Document revision/date
Product series version
History
A/2011-02-23
1.1
First release
Download the latest documents from the ABB web site http://
www.abb.com/substationautomation.
1MRS757203 A
Section 1
Introduction
630 series
7
Communication Protocol Manual
Product-specific point list manuals and other product series- and product-specific
manuals can be downloaded from the ABB web site http://www.abb.com/
substationautomation .
1.4
Symbols and conventions
1.4.1
Safety indication symbols
The caution icon indicates important information or warning related
to the concept discussed in the text. It might indicate the presence
of a hazard which could result in corruption of software or damage
to equipment or property.
The information icon alerts the reader of important facts and
conditions.
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
Although warning hazards are related to personal injury, it is necessary to
understand that under certain operational conditions, operation of damaged
equipment may result in degraded process performance leading to personal injury
or death. Therefore, comply fully with all warning and caution notices.
1.4.2
Manual conventions
Conventions used in IED manuals. A particular convention may not be used in this
manual.
•
Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
•
Push button navigation in the LHMI menu structure is presented by using the
push button icons, for example:
To navigate between the options, use
and
.
•
HMI menu paths are presented in bold, for example:
Select Main menu/Settings.
•
LHMI messages are shown in Courier font, for example:
To save the changes in non-volatile memory, select Yes and press
.
•
Parameter names are shown in italics, for example:
Section 1
1MRS757203 A
Introduction
8
630 series
Communication Protocol Manual
The function can be enabled and disabled with the Operation setting.
•
The ^ character in front of an input or output signal name in the function block
symbol given for a function, indicates that the user can set an own signal name
in PCM600.
•
The * character after an input or output signal name in the function block
symbol given for a function, indicates that the signal must be connected to
another function block in the application configuration to achieve a valid
application configuration.
1MRS757203 A
Section 1
Introduction
630 series
9
Communication Protocol Manual
IEC 60870-5-103 overview
2.1
IEC 60870-5-103 standard
IEC 60870-5-103 is defined as a companion standard for the informative element
of protection equipment. While the official IEC 60870-5-103 standard dates back
to 1997, the protocol has its roots in the VDEW6 communication protocol from the
late 1980’s. A VDEW6 device can be seen as a subset of an IEC 60870-5-103
device but not the opposite.
IEC 60870-5-103 defines communication for a serial, unbalanced link only.
Communication speeds are defined as either 9600 or 19200 baud.
Standard documentation
This manual assumes that the reader has some basic knowledge of the IEC
60870-5-103 protocol and the standard IEC 60870 documents relating to the protocol.
Table 1:
Standard IEC 60870 documents relating to IEC 60870-5-103
IEC 60870
document part
Description
5-1
Transmission frame formats
5-2
Link transmission procedures
5-3
General structure of application data
5-4
Definition and coding of application information elements
5-5
Basic application functions
5-6
Conformance testing guidelines
5-103
Companion standard for the informative interface of protection equipment.
The IEC 60870-5-1…6 parts are also used in communication protocols like IEC
60870-5-101 and IEC 60870-5-104.
Interoperability and interchangeability
An IEC 60870-5-103 device can be interoperable and interchangeable, or only
interoperable. Interoperability means that any required application data in the
device, which can be coded into an IEC 60870-5-103 data type, can be mapped into
the IEC 60870-5-103 address space. This data is recognized by any IEC
60870-5-103 master.
Interchangeability means supporting the application data (informative elements)
whose semantics are pre-defined by the IEC 60870-5-103 standard. However, only
a very limited set of application data informative elements has been defined by the
1MRS757203 A
Section 2
IEC 60870-5-103 overview
630 series
11
Communication Protocol Manual
standard. It should also be noticed that these sets of data are mainly defined for a
single function protection IED. 630 series IEDs in turn are multifunctional
protection and control IEDs whose internal data model is based on the IEC 61850
standard.
Interoperability list
The standard requires the IEC 60870-5-103 device to provide an interoperability
list, which actually is more an interchangeability list. See the vendor specific
implementation section in this manual for the interoperability list.
2.1.1
Communication system principle
TCP/IP
Control Center
IED
IED
IED
Gateway
Star coupler
RER 125
Station HSI
en05000660.vsd
IEC05000660 V3 EN
Figure 2:
Example of IEC 60870-5-103 communication structure for a
substation automation system
IEC 60870-5-103 communication protocol is mainly used when a protection IED
communicates with a third party control or monitoring system. This system must
have software that can interpret the IEC 60870-5-103 communication messages.
Table 2:
Max distances between IED/nodes
Connector
Distance
glass (ST
connector)
< 1000 m according to optical budget
Section 2
1MRS757203 A
IEC 60870-5-103 overview
12
630 series
Communication Protocol Manual
IEC 60870-5-103 communication
engineering
3.1
IEC 60870-5-103 engineering in PCM600
The Application Configuration tool (ACT) and the Parameter Setting tool (PST) in
PCM600 are used to configure the communication for IEC 60870-5-103 protocol.
1.
Add the desired IEC 60870-5-103 function blocks to the application
configuration in the Application Configuration tool.
2.
Connect the outputs of desired protection and monitoring function in the
application configuration to the inputs of the corresponding IEC 60870-5-103
function block.
3.
Set the function type and desired information number, where an information
number must be supplied, for each IEC 60870-5-103 function block instance
in the Parameter Setting tool.
3.2
Specific IEC 60870-5-103 settings
Set parameter Operation to On either in Parameter Setting tool or from the local HMI.
Parameter Operation is found under IED Configuration/Station communication/
IEC60870-5-103:1 in PST. The IED is automatically restarted when any general
parameter is changed.
The general settings for IEC 60870-5-103 communication are the following:
•
SlaveAddress and BaudRate: Settings for slave number and communication
speed (baud rate).
The slave number can be set to any value between 1 and 31. The
communication speed, can be set either to 9600 bits/s or 19200 bits/s.
•
RevPolarity: Setting for connection idle state (light on or light off).
•
CycMeasRepTime: Setting for CycMeasRepTime must be coordinated with the
xDbRepInt and xAngDbRepInt reporting setting on the MMXU measurement
function blocks. See I103MEAS function block for more information.
•
EventRepMode: Defines the mode for how events are reported.
The event buffer size is 1000 events.
1MRS757203 A
Section 3
IEC 60870-5-103 communication engineering
630 series
13
Communication Protocol Manual
Event reporting mode
If SeqOfEvent is selected, all GI and spontaneous events will be delivered in the
order they were generated by BSW. The most recent value is the latest value
delivered. All GI data from a single block will come from the same cycle.
If HiPriSpont is selected, spontaneous events will be delivered prior to GI event.
To prevent old GI data from being delivered after a new spontaneous event, the
pending GI event is modified to contain the same value as the spontaneous event.
As a result the GI dataset is not time-correlated.
3.2.1
Settings
Table 3:
IEC60870-5-103 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation
SlaveAddress
1 - 31
-
1
1
Slave address
BaudRate
9600 Bd
19200 Bd
-
-
9600 Bd
Baudrate on serial line
RevPolarity
Off
On
-
-
On
Invert polarity
CycMeasRepTime
1.0 - 1800.0
s
0.1
5.0
Cyclic reporting time of measurments
MasterTimeDomain
UTC
Local
Local with DST
-
-
UTC
Master time domain
TimeSyncMode
IEDTime
LinMastTime
IEDTimeSkew
-
-
IEDTime
Time synchronization mode
EvalTimeAccuracy
5ms
10ms
20ms
40ms
Off
-
-
5ms
Evaluate time accuracy for invalid time
EventRepMode
SeqOfEvent
HiPriSpont
-
-
SeqOfEvent
Event reporting mode
3.3
IEC 60870-5-103 time synchronization
An IED with IEC 60870-5-103 protocol can be used for time synchronization, but
for accuracy reasons, it is not recommended. In some cases, however, this kind of
synchronization is needed, for example, when no other synchronization is available.
First, set the IED to be synchronized via IEC 60870-5-103 from IED
Configuration/Time/Synchronization/TIMESYNCHGEN:1 in PST.
Section 3
1MRS757203 A
IEC 60870-5-103 communication engineering
14
630 series
Communication Protocol Manual
GUID-68284E7B-A24D-4E78-B5BA-736B29F50E9A V1 EN
Figure 3:
Settings under TIMESYNCHGEN:1 in PST
Only CoarseSyncSrc can be set to IEC 60870-5-103, not FineSyncSource.
After setting up the time synchronization source, the user must check and modify
the IEC 60870-5-103 time synchronization specific settings, under: IED
Configuration/Communication/Station communication/IEC60870-5-103:1.
•
MasterTimeDomain specifies the format of the time sent by the master. Format
can be:
•
Coordinated Universal Time (UTC)
•
Local time set in the master (Local)
•
Local time set in the master adjusted according to daylight saving time
(Local with DST)
•
TimeSyncMode specifies the time sent by the IED. The time synchronisation is
done using the following ways:
•
IEDTime: The IED sends the messages with its own time.
•
LinMasTime: The IED measures the offset between its own time and the
master time, and applies the same offset for the messages sent as in the
IEDTimeSkew. But in LinMasTime it applies the time changes occurred
between two synchronised messages.
•
IEDTimeSkew: The IED measures the offset in between its own time and
the master time and applies the same offset for the messages sent.
•
EvalTimeAccuracy evaluates time accuracy for invalid time. Specifies the
accuracy of the synchronization (5, 10, 20 or 40 ms). If the accuracy is worse
than the specified value, the “Bad Time” flag is raised. To accommodate those
masters that are really bad in time sync, the EvalTimeAccuracy can be set to
Off.
According to the standard, the “Bad Time” flag is reported when synchronization
has been omitted in the protection for >23 h.
1MRS757203 A
Section 3
IEC 60870-5-103 communication engineering
630 series
15
Communication Protocol Manual
IEC 60870-5-103 vendor specific
implementation
The signal and setting tables specify the information types supported by the IEDs
with the communication protocol IEC 60870-5-103 implemented.
The information types are supported when corresponding functions are included in
the protection and control IED.
4.1
Signals in monitoring direction
4.1.1
Measurands for IEC 60870-5-103 I103MEAS
4.1.1.1
Functionality
103MEAS is a function block that reports all valid measuring types depending on
connected signals.
The measured values come from the corresponding MMXU function block and are
depending on the function block settings. The event reporting interval is set by the
CycMeasRepTime parameter of the IEC 60870-5-103 communication settings.
Input signals of the IEC 60870-5-103 I103MEAS block should be connected to the
corresponding outputs of the MMXU application functions. Depending on the
connected input signals, the IEC 60870-5-103 protocol automatically selects the
proper ASDU Meas 3 or Meas 9 to be used as Class 2 data.
1MRS757203 A
Section 4
IEC 60870-5-103 vendor specific implementation
630 series
17
Communication Protocol Manual
IEC10000287 V1 EN
Figure 4:
I103MEAS function block
4.1.1.3
Signals
Table 4:
I103MEAS Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of service value reporting
IL1
REAL
0.0
Service value for current phase L1
IL2
REAL
0.0
Service value for current phase L2
IL3
REAL
0.0
Service value for current phase L3
IN
REAL
0.0
Service value for residual current IN
UL1
REAL
0.0
Service value for voltage phase L1
UL2
REAL
0.0
Service value for voltage phase L2
UL3
REAL
0.0
Service value for voltage phase L3
UL1L2
REAL
0.0
Service value for voltage phase-phase L1-L2
UN
REAL
0.0
Service value for residual voltage UN
P
REAL
0.0
Service value for active power
Q
REAL
0.0
Service value for reactive power
F
REAL
0.0
Service value for system frequency
4.1.1.4
Settings
Table 5:
I103MEAS Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
MaxIL1
1 - 99999
A
1
3000
Maximum current phase L1
MaxIL2
1 - 99999
A
1
3000
Maximum current phase L2
MaxIL3
1 - 99999
A
1
3000
Maximum current phase L3
MaxIN
1 - 99999
A
1
3000
Maximum residual current IN
Table continues on next page
Section 4
1MRS757203 A
IEC 60870-5-103 vendor specific implementation
18
630 series
Communication Protocol Manual
0.05 - 2000.00
kV
0.05
230.00
Maximum voltage for phase L1
MaxUL2
0.05 - 2000.00
kV
0.05
230.00
Maximum voltage for phase L2
MaxUL3
0.05 - 2000.00
kV
0.05
230.00
Maximum voltage for phase L3
MaxUL1-UL2
0.05 - 2000.00
kV
0.05
400.00
Maximum voltage for phase-phase L1-L2
MaxUN
0.05 - 2000.00
kV
0.05
230.00
Maximum residual voltage UN
MaxP
0.00 - 2000.00
MW
0.05
1200.00
Maximum value for active power
MaxQ
0.00 - 2000.00
MVA
0.05
1200.00
Maximum value for reactive power
MaxF
50.0 - 60.0
Hz
10.0
50.0
Maximum system frequency
Maximum value corresponds to the value 4096 on the master side.
4.1.1.5
Supported information types
Measurands in public range, I103MEAS
Number of instances: 1
The IED reports all valid measuring types depending on connected signals.
According to standard the upper limit for measured currents, active/reactive-power
is 2.4 times rated value.
According to standard the upper limit for measured voltages and frequency is 1.2
times rated value.
Upper limit for measured voltages and frequency is 1.2 times rated value.
Only the measurand standard frames defined in IEC 60870-5-103 are supported.
See the Table I103MEASUSR Input signals .
Table 6:
Interchangeable Class 2 measurand frames
Frame No
ASDU
FUN1)
INF
Number of data
Data in the Class 2 frame
1
3
0
144
1
IL2
2
3
0
145
2
IL2, U12
3
3
0
146
4
IL2, U12, P3, Q3
4
3
0
147
2
Io, Uo
5
9
0
148
9
IL1, IL2, IL3, UL1, UL2,
UL3, P3, Q3, f
1.
FUN= 0 means that the Function type is coded as the Device function type
which in turn is defined by the setting parameter Main menu/Configuration/
System/IEDMainFunType.
1MRS757203 A
Section 4
IEC 60870-5-103 vendor specific implementation
630 series
19
Communication Protocol Manual
Measurands user defined signals for IEC 60870-5-103
I103MEASUSR
4.1.2.1
Functionality
I103MEASUSR is a function block with user defined input measurands in monitor
direction. These function blocks include the FunctionType parameter for each
block in the private range, and the Information number parameter for each block.
4.1.2.2
Function block
IEC10000288-1-en.vsd
I103MEASUSR
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
IEC10000288 V1 EN
Figure 5:
I103MEASUSR function block
4.1.2.3
Signals
Table 7:
I103MEASUSR Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of service value reporting
INPUT1
REAL
0.0
Service value for measurement on input 1
INPUT2
REAL
0.0
Service value for measurement on input 2
INPUT3
REAL
0.0
Service value for measurement on input 3
INPUT4
REAL
0.0
Service value for measurement on input 4
INPUT5
REAL
0.0
Service value for measurement on input 5
INPUT6
REAL
0.0
Service value for measurement on input 6
INPUT7
REAL
0.0
Service value for measurement on input 7
INPUT8
REAL
0.0
Service value for measurement on input 8
INPUT9
REAL
0.0
Service value for measurement on input 9
Section 4
1MRS757203 A
IEC 60870-5-103 vendor specific implementation
20
630 series
Communication Protocol Manual
I103MEASUSR Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
25
Function type (1-255)
InfNo
1 - 255
-
1
1
Information number for measurands
(1-255)
MaxMeasur1
0.05 -
10000000000.00
-
0.05
1000.00
Maximum value for measurement on
input 1
MaxMeasur2
0.05 -
10000000000.00
-
0.05
1000.00
Maximum value for measurement on
input 2
MaxMeasur3
0.05 -
10000000000.00
-
0.05
1000.00
Maximum value for measurement on
input 3
MaxMeasur4
0.05 -
10000000000.00
-
0.05
1000.00
Maximum value for measurement on
input 4
MaxMeasur5
0.05 -
10000000000.00
-
0.05
1000.00
Maximum value for measurement on
input 5
MaxMeasur6
0.05 -
10000000000.00
-
0.05
1000.00
Maximum value for measurement on
input 6
MaxMeasur7
0.05 -
10000000000.00
-
0.05
1000.00
Maximum value for measurement on
input 7
MaxMeasur8
0.05 -
10000000000.00
-
0.05
1000.00
Maximum value for measurement on
input 8
MaxMeasur9
0.05 -
10000000000.00
-
0.05
1000.00
Maximum value for measurement on
input 9
4.1.2.5
Supported information types
Measurands in private range, I103MEASUSR
Number of instances: 3
Function type parameter for each block in private range. Default values are defined
in private range 25 – 27. One for each instance.
Information number must be selected for measurands.
Info.
Message
Supported
*1)
Meas1
Yes
*
Meas2
Yes
*
Meas3
Yes
*
Meas4
Yes
*
Meas5
Yes
*
Meas6
Yes
*
Meas7
Yes
*
Meas8
Yes
*
Meas9
Yes
1)
* User defined information number
1MRS757203 A
Section 4
IEC 60870-5-103 vendor specific implementation
630 series
21
Communication Protocol Manual
Function status auto-recloser for IEC 60870-5-103 I103AR
4.1.3.1
Functionality
I103AR is a function block with defined functions for autorecloser indications in
monitor direction. This block includes the FunctionType parameter, and the
information number parameter is defined for each output signal.
4.1.3.2
Function block
IEC10000289-1-en.vsd
I103AR
BLOCK
16_ARACT
128_CBON
130_UNSU
IEC10000289 V1 EN
Figure 6:
I103AR function block
4.1.3.3
Signals
Table 9:
I103AR Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting
16_ARACT
BOOLEAN
0
Information number 16, auto-recloser active
128_CBON
BOOLEAN
0
Information number 128, circuit breaker on by auto-
recloser
130_UNSU
BOOLEAN
0
Information number 130, auto-recloser blocked
4.1.3.4
Settings
Table 10:
I103AR Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
4.1.3.5
Supported information types
Autorecloser indications in monitor direction, I103AR
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signal.
Section 4
1MRS757203 A
IEC 60870-5-103 vendor specific implementation
22
630 series
Communication Protocol Manual
I103AR supported indications
Info. no.
Message
Supported
16
Autorecloser active
Yes
17
Teleprotection active
No
18
Protection active
No
128
CB on by Autorecloser
Yes
129
CB ‘on’ by long-time AR
No
130
Autorecloser blocked
Yes
4.1.4
Function status earth-fault for IEC 60870-5-103 I103EF
4.1.4.1
Functionality
I103EF is a function block with defined functions for earth fault indications in
monitor direction. This block includes the FunctionType parameter, and the
information number parameter is defined for each output signal.
4.1.4.2
Function block
IEC10000290-1-en.vsd
I103EF
BLOCK
51_EFFW
52_EFREV
IEC10000290 V1 EN
Figure 7:
I103EF function block
4.1.4.3
Signals
Table 12:
I103EF Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting
51_EFFW
BOOLEAN
0
Information number 51, earth-fault forward
52_EFREV
BOOLEAN
0
Information number 52, earth-fault reverse
4.1.4.4
Settings
Table 13:
I103EF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
160
Function type (1-255)
1MRS757203 A
Section 4
IEC 60870-5-103 vendor specific implementation
630 series
23
Communication Protocol Manual
Supported information types
Earth fault indications in monitor direction, I103EF
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signal.
Table 14:
I103EF supported indications
Info. no.
Message
Supported
48
Earth fault L1
No
49
Earth fault L2
No
50
Earth fault L3
No
51
Earth fault forward
Yes
52
Earth fault reverse
Yes
4.1.5
Function status fault protection for IEC 60870-5-103
I103FLTPROT
4.1.5.1
Functionality
I103FLTPROT is used for fault indications in monitor direction. Each input on the
function block is specific for a certain fault type and therefore must be connected to
a correspondent signal present in the configuration. For example: 68_TRGEN
represents the General Trip of the device, and therefore must be connected to the
general trip signal SMPPTRC_TRIP or equivalent.
The delay observed in the protocol is the time difference in between the signal that
is triggering the Disturbance Recorder and the respective configured signal to the
IEC 60870-5-103 I103FLTPROT.
Section 4
1MRS757203 A
IEC 60870-5-103 vendor specific implementation
24
630 series
Communication Protocol Manual
IEC10000291 V1 EN
Figure 8:
I103FLTPROT function block
4.1.5.3
Signals
Table 15:
I103FLTPROT Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting.
64_STL1
BOOLEAN
0
Information number 64, start phase L1
65_STL2
BOOLEAN
0
Information number 65, start phase L2
66_STL3
BOOLEAN
0
Information number 66, start phase L3
67_STIN
BOOLEAN
0
Information number 67, start residual current IN
68_TRGEN
BOOLEAN
0
Information number 68, trip general
69_TRL1
BOOLEAN
0
Information number 69, trip phase L1
70_TRL2
BOOLEAN
0
Information number 70, trip phase L2
71_TRL3
BOOLEAN
0
Information number 71, trip phase L3
72_TRBKUP
BOOLEAN
0
Information number 72, back up trip I>>
73_SCL
REAL
0
Information number 73, fault location in ohm
74_FW
BOOLEAN
0
Information number 74, forward/line
75_REV
BOOLEAN
0
Information number 75, reverse/busbar
Table continues on next page
1MRS757203 A
Section 4
IEC 60870-5-103 vendor specific implementation
630 series
25
Communication Protocol Manual
Information number 76, signal transmitted
77_RECEV
BOOLEAN
0
Information number 77, signal received
78_ZONE1
BOOLEAN
0
Information number 78, zone 1
79_ZONE2
BOOLEAN
0
Information number 79, zone 2
80_ZONE3
BOOLEAN
0
Information number 80, zone 3
81_ZONE4
BOOLEAN
0
Information number 81, zone 4
82_ZONE5
BOOLEAN
0
Information number 82, zone 5
84_STGEN
BOOLEAN
0
Information number 84, start general
85_BFP
BOOLEAN
0
Information number 85, breaker failure
86_MTRL1
BOOLEAN
0
Information number 86, trip measuring system
phase L1
87_MTRL2
BOOLEAN
0
Information number 87, trip measuring system
phase L2
88_MTRL3
BOOLEAN
0
Information number 88, trip measuring system
phase L3
89_MTRN
BOOLEAN
0
Information number 89, trip measuring system
neutral N
90_IOC
BOOLEAN
0
Information number 90, over current trip, stage low
91_IOC
BOOLEAN
0
Information number 91, over current trip, stage high
92_IEF
BOOLEAN
0
Information number 92, earth-fault trip, stage low
93_IEF
BOOLEAN
0
Information number 93, earth-fault trip, stage high
ARINPROG
BOOLEAN
0
Autorecloser in progress (SMBRREC- INPROGR)
FLTLOC
BOOLEAN
0
Faultlocator faultlocation valid (LMBRFLO-
CALCMADE)
4.1.5.4
Settings
Table 16:
I103FLTPROT Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
128
Function type (1-255)
4.1.5.5
Supported information types
Function status fault protection for IEC60870-5-103, I103FLTPROT
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each input signals.
Section 4
1MRS757203 A
IEC 60870-5-103 vendor specific implementation
26
630 series
Communication Protocol Manual
I103FLTPROT supported indications
Info. no.
Message
Supported
TYPE
GI
COT
64
Start phase L1
Yes
2
Y
1,7,9
65
Start phase L2
Yes
2
Y
1,7,9
66
Start phase L3
Yes
2
Y
1,7,9
67
Start residual current IN
Yes
2
Y
1,7,9
68
Trip general
Yes
2
N
1,7
69
Trip phase L1
Yes
2
N
1,7
70
Trip phase L2
Yes
2
N
1,7
71
Trip phase L3
Yes
2
N
1,7
72
Back up trip I>>
Yes
2
N
1,7
73
Fault location in ohm
Yes
4
N
1,7
74
Forward/line
Yes
2
N
1,7
75
Reverse/busbar
Yes
2
N
1,7
76
Signal transmitted
Yes
2
N
1,7
77
Signal received
Yes
2
N
1,7
78
Zone 1
Yes
2
N
1,7
79
Zone 2
Yes
2
N
1,7
80
Zone 3
Yes
2
N
1,7
81
Zone 4
Yes
2
N
1,7
82
Zone 5
Yes
2
N
1,7
83
Zone 6
No
2
N
1,7
84
Start general
Yes
2
Y
1,7,9
85
Breaker failure
Yes
2
N
1,7
86
Trip measuring system phase L1
Yes
2
N
1,7
87
Trip measuring system phase L2
Yes
2
N
1,7
88
Trip measuring system phase L3
Yes
2
N
1,7
89
Trip measuring system neutral N
Yes
2
N
1,7
90
Over current trip, stage low
Yes
2
N
1,7
91
Over current trip, stage high
Yes
2
N
1,7
92
Earth-fault trip, stage low
Yes
2
N
1,7
93
Earth-fault trip, stage high
Yes
2
N
1,7
4.1.6
IED status for IEC 60870-5-103 I103IED
4.1.6.1
Functionality
I103IED is a function block with defined IED functions in monitor direction. This
block uses parameter as FunctionType, and information number parameter is
defined for each input signal.
1MRS757203 A
Section 4
IEC 60870-5-103 vendor specific implementation
630 series
27
Communication Protocol Manual
IEC10000292 V1 EN
Figure 9:
I103IED function block
4.1.6.3
Signals
Table 18:
I103IED Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting
19_LEDRS
BOOLEAN
0
Information number 19, reset LEDs
21_TESTM
BOOLEAN
0
Information number 21, test mode is active
23_GRP1
BOOLEAN
0
Information number 23, setting group 1 is active
24_GRP2
BOOLEAN
0
Information number 24, setting group 2 is active
25_GRP3
BOOLEAN
0
Information number 25, setting group 3 is active
26_GRP4
BOOLEAN
0
Information number 26, setting group 4 is active
4.1.6.4
Settings
Table 19:
I103IED Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
4.1.6.5
Supported information types
Terminal status indications in monitor direction, I103IED
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each input signals.
Table 20:
I103IED supported indications
Info. no.
Message
Supported
19
LED reset
Yes
20
Monitor direction blocked
No
21
TestMode
Yes
Table continues on next page
Section 4
1MRS757203 A
IEC 60870-5-103 vendor specific implementation
28
630 series
Communication Protocol Manual
Local Parameter setting
No
23
Setting group 1 active
Yes
24
Setting group 2 active
Yes
25
Setting group 3 active
Yes
26
Setting group 4 active
Yes
4.1.7
Supervison status for IEC 60870-5-103 I103SUPERV
4.1.7.1
Functionality
I103SUPERV is a function block with defined functions for supervision indications
in monitor direction. This block includes the FunctionType parameter, and the
information number parameter is defined for each output signal.
4.1.7.2
Function block
IEC10000293-1-en.vsd
I103SUPERV
BLOCK
32_MEASI
33_MEASU
37_IBKUP
38_VTFF
46_GRWA
47_GRAL
IEC10000293 V1 EN
Figure 10:
I103SUPERV function block
4.1.7.3
Signals
Table 21:
I103SUPERV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting
32_MEASI
BOOLEAN
0
Information number 32, measurand supervision of
I
33_MEASU
BOOLEAN
0
Information number 33, measurand supervision of
U
37_IBKUP
BOOLEAN
0
Information number 37, I high-high back-up
protection
38_VTFF
BOOLEAN
0
Information number 38, fuse failure VT
46_GRWA
BOOLEAN
0
Information number 46, group warning
47_GRAL
BOOLEAN
0
Information number 47, group alarm
1MRS757203 A
Section 4
IEC 60870-5-103 vendor specific implementation
630 series
29
Communication Protocol Manual
I103SUPERV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
4.1.7.5
Supported information types
Supervision indications in monitor direction, I103SUPERV
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for output signals.
Table 23:
I103SUPERV supported indications
Info. no.
Message
Supported
Type
GI
COT
32
Measurand supervision I
Yes
1
Y
1,7,9
33
Measurand supervision U
Yes
1
Y
1,7,9
35
Phase sequence supervision
No
1
Y
1,7,9
36
Trip circuit supervision
No
1
Y
1,7,9
37
I>>back-up operation
Yes
1
Y
1,7,9
38
VT fuse failure
Yes
1
Y
1,7,9
39
Teleprotection disturbed
No
1
Y
1,7,9
46
Group warning
Yes
1
Y
1,7,9
47
Group alarm
Yes
1
Y
1,7,9
4.1.8
Status for user defined signals for IEC 60870-5-103
I103USRDEF
4.1.8.1
Functionality
I103USRDEF is a function blocks with user defined input signals in monitor
direction. These function blocks include the FunctionType parameter for each
block in the private range, and the information number parameter for each input
signal.
I103USRDEF can be mapped to the INF that are not supported directly by specific
function blocks, for example: INF17, INF18, INF20 or INF35. After connecting
the appropriate signals to the I103USRDEF inputs, the user must also set the
InfNo_x values in the settings
Section 4
1MRS757203 A
IEC 60870-5-103 vendor specific implementation
30
630 series
Communication Protocol Manual
GUID-391D4145-B7E6-4174-B3F7-753ADDA4D06F V1 EN
Figure 11:
I103USRDEF example settings
4.1.8.2
Function block
IEC10000294-1-en.vsd
I103USRDEF
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
IEC10000294 V1 EN
Figure 12:
I103USRDEF function block
4.1.8.3
Signals
Table 24:
I103USRDEF Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting
INPUT1
BOOLEAN
0
Binary signal Input 1
INPUT2
BOOLEAN
0
Binary signal input 2
INPUT3
BOOLEAN
0
Binary signal input 3
INPUT4
BOOLEAN
0
Binary signal input 4
INPUT5
BOOLEAN
0
Binary signal input 5
INPUT6
BOOLEAN
0
Binary signal input 6
INPUT7
BOOLEAN
0
Binary signal input 7
INPUT8
BOOLEAN
0
Binary signal input 8
1MRS757203 A
Section 4
IEC 60870-5-103 vendor specific implementation
630 series
31
Communication Protocol Manual
I103USRDEF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
5
Function type (1-255)
InfNo_1
1 - 255
-
1
1
Information number for binary input 1
(1-255)
InfNo_2
1 - 255
-
1
2
Information number for binary input 2
(1-255)
InfNo_3
1 - 255
-
1
3
Information number for binary input 3
(1-255)
InfNo_4
1 - 255
-
1
4
Information number for binary input 4
(1-255)
InfNo_5
1 - 255
-
1
5
Information number for binary input 5
(1-255)
InfNo_6
1 - 255
-
1
6
Information number for binary input 6
(1-255)
InfNo_7
1 - 255
-
1
7
Information number for binary input 7
(1-255)
InfNo_8
1 - 255
-
1
8
Information number for binary input 8
(1-255)
4.1.8.5
Supported information types
Function status indications in monitor direction, user-defined,
I103USRDEF
Number of instances: 20
Function type is selected with parameter FunctionType for each function block
instance in private range. Default values are defined in private range 5 - 24. One
for each instance.
Information number is required for each input signal. Default values are defined in
range 1 - 8.
Info. no.
Message
Supported
1
Binary signal input
Yes
2
Binary signal input
Yes
3
Binary signal input
Yes
4
Binary signal input
Yes
5
Binary signal input
Yes
6
Binary signal input
Yes
7
Binary signal input
Yes
8
Binary signal input
Yes
Section 4
1MRS757203 A
IEC 60870-5-103 vendor specific implementation
32
630 series
Communication Protocol Manual
Commands in control direction
4.2.1
Function commands for IEC 60870-5-103 I103CMD
4.2.1.1
Functionality
I103CMD is a command function block in control direction with pre-defined
output signals.
4.2.1.2
Function block
IEC10000282-1-en.vsd
I103CMD
BLOCK
16-AR
17-DIFF
18-PROT
IEC10000282 V1 EN
Figure 13:
I103CMD function block
4.2.1.3
Signals
Table 26:
I103CMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of commands
Table 27:
I103CMD Output signals
Name
Type
Description
16-AR
BOOLEAN
Information number 16, block of autorecloser
17-DIFF
BOOLEAN
Information number 17, block of differential
protection
18-PROT
BOOLEAN
Information number 18, block of protection
4.2.1.4
Settings
Table 28:
I103CMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
1MRS757203 A
Section 4
IEC 60870-5-103 vendor specific implementation
630 series
33
Communication Protocol Manual
Supported information types
Function commands in control direction, pre-defined I103CMD
Number of instances: 1
Function type is selected with parameter FunctionType .
Information number is defined for each output signals.
Info. no.
Message
Supported
16
Auto-recloser on/off
Yes
17
Teleprotection on/off
Yes
18
Protection on/off
Yes
4.2.2
IED commands for IEC 60870-5-103 I103IEDCMD
4.2.2.1
Functionality
I103IEDCMD is a command block in control direction with defined IED functions.
4.2.2.2
Function block
IEC10000283-1-en.vsd
I103IEDCMD
BLOCK
19-LEDRS
23-GRP1
24-GRP2
25-GRP3
26-GRP4
IEC10000283 V1 EN
Figure 14:
I103IEDCMD function block
4.2.2.3
Signals
Table 29:
I103IEDCMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of commands
Table 30:
I103IEDCMD Output signals
Name
Type
Description
19-LEDRS
BOOLEAN
Information number 19, reset LEDs
23-GRP1
BOOLEAN
Information number 23, activate setting group 1
24-GRP2
BOOLEAN
Information number 24, activate setting group 2
25-GRP3
BOOLEAN
Information number 25, activate setting group 3
26-GRP4
BOOLEAN
Information number 26, activate setting group 4
Section 4
1MRS757203 A
IEC 60870-5-103 vendor specific implementation
34
630 series
Communication Protocol Manual
I103IEDCMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
255
Function type (1-255)
4.2.2.5
Supported information types
Commands in control direction, I103IEDCMD
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signals.
Info. no
Message
Supported
19
LED Reset
Yes
23
Activate setting group 1
Yes
24
Activate setting group 2
Yes
25
Activate setting group 3
Yes
26
Activate setting group 4
Yes
4.2.3
Function commands user defined for IEC 60870-5-103
I103USRCMD
4.2.3.1
Functionality
I103USRCMD is a command block in control direction with user defined output
signals. These function blocks include the FunctionType parameter for each block
in the private range, and the Information number parameter for each output signal.
4.2.3.2
Function block
IEC10000284-1-en.vsd
I103USRCMD
BLOCK
^OUTPUT1
^OUTPUT2
^OUTPUT3
^OUTPUT4
^OUTPUT5
^OUTPUT6
^OUTPUT7
^OUTPUT8
IEC10000284 V1 EN
Figure 15:
I103USRCMD function block
1MRS757203 A
Section 4
IEC 60870-5-103 vendor specific implementation
630 series
35
Communication Protocol Manual
I103USRCMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of commands
Table 33:
I103USRCMD Output signals
Name
Type
Description
OUTPUT1
BOOLEAN
Command output 1
OUTPUT2
BOOLEAN
Command output 2
OUTPUT3
BOOLEAN
Command output 3
OUTPUT4
BOOLEAN
Command output 4
OUTPUT5
BOOLEAN
Command output 5
OUTPUT6
BOOLEAN
Command output 6
OUTPUT7
BOOLEAN
Command output 7
OUTPUT8
BOOLEAN
Command output 8
4.2.3.4
Settings
Table 34:
I103USRCMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
PulseMode
Steady
Pulsed
-
-
Pulsed
Pulse mode
PulseLength
0.200 - 60.000
s
0.001
0.400
Pulse length
InfNo_1
1 - 255
-
1
1
Information number for output 1 (1-255)
InfNo_2
1 - 255
-
1
2
Information number for output 2 (1-255)
InfNo_3
1 - 255
-
1
3
Information number for output 3 (1-255)
InfNo_4
1 - 255
-
1
4
Information number for output 4 (1-255)
InfNo_5
1 - 255
-
1
5
Information number for output 5 (1-255)
InfNo_6
1 - 255
-
1
6
Information number for output 6 (1-255)
InfNo_7
1 - 255
-
1
7
Information number for output 7 (1-255)
InfNo_8
1 - 255
-
1
8
Information number for output 8 (1-255)
4.2.3.5
Supported information types
Function commands in control direction, user-defined, I103USRCMD
Number of instances: 4
Section 4
1MRS757203 A
IEC 60870-5-103 vendor specific implementation
36
630 series
Communication Protocol Manual
Function type for each function block instance in private range is selected with
parameter FunctionType. Default values are defined in private range 1 - 4. One for
each instance.
Information number must be selected for each output signal. Default values are 1 - 8.
Info. no.
Message
Supported
1
Output signal 01
Yes
2
Output signal 02
Yes
3
Output signal 03
Yes
4
Output signal 04
Yes
5
Output signal 05
Yes
6
Output signal 06
Yes
7
Output signal 07
Yes
8
Output signal 08
Yes
4.2.4
Function commands generic for IEC 60870-5-103
I103GENCMD
4.2.4.1
Functionality
I103GENCMD is used for transmitting generic commands over IEC 60870-5-103.
The function has two outputs signals CMD_OFF and CMD_ON that can be used to
implement double-point command schemes.
4.2.4.2
Function block
IEC10000285-1-en.vsd
I103GENCMD
BLOCK
^CMD_OFF
^CMD_ON
IEC10000285 V1 EN
Figure 16:
I103GENCMD function block
4.2.4.3
Signals
Table 35:
I103GENCMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of command
Table 36:
I103GENCMD Output signals
Name
Type
Description
CMD_OFF
BOOLEAN
Command output OFF
CMD_ON
BOOLEAN
Command output ON
1MRS757203 A
Section 4
IEC 60870-5-103 vendor specific implementation
630 series
37
Communication Protocol Manual
I103GENCMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 127
-
1
1
Function type (1-255)
PulseLength
0.000 - 60.000
s
0.001
0.400
Pulse length
InfNo
32 - 239
-
1
32
Information number for command output
(1-255)
4.2.4.5
Supported information types
Function commands generic for IEC60870-5-103, I103GENCMD
Number of instances: 50
Function type for each function block instance is selected with parameter
FunctionType.
Information number must be selected for command output.
4.2.5
IED commands with position and select for IEC
60870-5-103 I103POSCMD
4.2.5.1
Functionality
I103POSCMD is used for controllable switching devices. It has double-point
position indicators that are getting the position value as an integer (POSITION
output of the GNRLCSWI function block) and sending it over IEC 60870-5-103
(1=OPEN; 2=CLOSE); .The standard does not define the use of values 0 and 3 .
However, when connected to a switching device, these values are transmitted.
The BLOCK input will block only the signals in monitoring direction (the position
information), not the commands via IEC 60870-5-103. The SELECT input is used
to indicate that the monitored apparatus has been selected (in a select-before-
operate type of control)
4.2.5.2
Function block
IEC10000286-1-en.vsd
I103POSCMD
BLOCK
POSITION
SELECT
IEC10000286 V1 EN
Figure 17:
I103POSCMD function block
Section 4
1MRS757203 A
IEC 60870-5-103 vendor specific implementation
38
630 series
Communication Protocol Manual
I103POSCMD Input signals
Name
Type
Description
BLOCK
BOOLEAN
Block of indications
POSITION
INTEGER
Position indication of controllable object
SELECT
BOOLEAN
Select indication of controllable object
4.2.5.4
Settings
Table 39:
I103POSCMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
InfNo
160 - 196
-
4
160
Information number for position
indication and command output
(160-196.)
4.2.5.5
Supported information types
IED commands with position and select for IEC60870-5-103,
I103POSCMD
Number of instances: 50
Function type for each function block instance is selected with parameter
FunctionType.
Information number must be selected for command output.
The current implementation of the IEC 60870-5-103 commands
will reject any new command if a previously issued command has
not yet been completed.
The value of the control model parameter of the switching device
has no effect on operation.
4.3
Disturbance recorder file transfer
4.3.1
Disturbance upload
•
The transfer functionality is based on the Disturbance recorder function. The
analog and binary signals recorded will be reported to the master by file
transfer. The eight last disturbances that are recorded are available for transfer
1MRS757203 A
Section 4
IEC 60870-5-103 vendor specific implementation
630 series
39
Communication Protocol Manual
to the master. A file that has been transferred and acknowledged by the master
cannot be transferred again.
•
The binary signals that are reported by polling are those that are connected to
the disturbance function blocks B1RBDR to B6RBDR. These function blocks
include the function type and the information number for each signal. For
more information on the description of the Disturbance report in the Technical
reference manual. The analog channels, that are reported, are those connected
to the disturbance function blocks A1RADR to A4RADR. The eight first ones
belong to the public range and the remaining ones to the private range.
The following elements are used in the ASDUs (Application Service Data Units)
defined in the standard.
Analog signals, 40-channels: the channel number for each channel has to be
specified. Channels used in the public range are 1 to 8 and with:
•
IL1 connected to channel 1 on disturbance function block A1RADR
•
IL2 connected to channel 2 on disturbance function block A1RADR
•
IL3 connected to channel 3 on disturbance function block A1RADR
•
IN connected to channel 4 on disturbance function block A1RADR
•
VL1E connected to channel 5 on disturbance function block A1RADR
•
VL2E connected to channel 6 on disturbance function block A1RADR
•
VL3E connected to channel 7 on disturbance function block A1RADR
•
VEN connected to channel 8 on disturbance function block A1RADR
Channel number used for the remaining 32 analog signals are numbers in the
private range 64 to 95.
Binary signals, 96-channels: for each channel the user can specify a FUNCTION
TYPE and an INFORMATION NUMBER.
4.3.2
Deviations from the standard
For each input of the Disturbance recorder function there is a setting for the
information number of the connected signal. The information number can be set to
any value between 0 and 255. Default value is 0.
Furthermore, there is a setting on each input of the Disturbance recorder function
for the function type.
Disturbance upload
All analog and binary signals that are recorded with disturbance recorder can be
reported to the master. The last eight disturbances that are recorded are available
for transfer to the master. A successfully transferred disturbance (acknowledged by
the master) will not be reported to the master again.
Section 4
1MRS757203 A
IEC 60870-5-103 vendor specific implementation
40
630 series
Communication Protocol Manual
When a new disturbance is recorded by the IED a list of available recorded
disturbances (ASDU 23) will be sent to the master, an updated list of available
disturbances will also be sent whenever something has happened to disturbances in
this list. For example, when a disturbance is deleted (by other client, for example,
PCM600) or when a new disturbance has been recorded or when the master has
uploaded a recording.
Deviations from the standard
This section describes all data that is not exactly as specified in the standard.
ASDU23
In ‘list of recorded disturbances’ (ASDU23) an information element named SOF
(status of fault) exists. This information element consists of 4 bits and indicates
whether:
•
Bit TP: the protection equipment has tripped during the fault
•
Bit TM: the disturbance data are currently being transmitted
•
Bit TEST: the disturbance data have been recorded during normal operation or
test mode.
•
Bit OTEV: the disturbance data recording has been initiated by another event
than start
The only information that is easily available is test-mode status. The other
information is always set (hard coded) to:
TP
Recorded fault with trip. [1]
TM
Disturbance data waiting for transmission [0]
OTEV
Disturbance data initiated by other events [1]
Another information element in ASDU23 is the FAN (fault number). According to
the standard this is a number that is incremented when a protection function takes
action.
ASDU26
When a disturbance has been selected by the master; (by sending ASDU24), the
protection equipment answers by sending ASDU26, which contains an information
element named NOF (number of grid faults). This number must indicate fault
number in the power system,that is, a fault in the power system with several trip
and auto-reclosing has the same NOF (while the FAN must be incremented).
To get INF and FUN for the recorded binary signals there are parameters on the
disturbance recorder for each input. The user must set these parameters to identify
the corresponding inputs.
1MRS757203 A
Section 4
IEC 60870-5-103 vendor specific implementation
630 series
41
Communication Protocol Manual
number of loads
No
5.1.1
Optical interface
Table 41:
Optical interface
Supported
Glass fibre
Yes
Plastic fibre
No
F-SMA type connector
No
BFOC/2,5 type connector
Yes
5.1.2
Transmission speed
Table 42:
Transmission speed
Supported
9 600 bit/s
Yes
19 200 bit/s
Yes
5.2
Application layer
5.2.1
Transmission mode for application data
Mode 1 (least significant octet first), as defined in 4.10 of IEC 60870-5-4, is used
exclusively in this companion standard.
1MRS757203 A
Section 5
Interoperability
630 series
43
Communication Protocol Manual
Common address of ASDU
Table 43:
Common address of ASDU
Supported
One COMMON ADDRESS OF ASDU (identical
with station address)
Yes
More than one COMMON ADDRESS OF ASDU
No
5.2.3
Selection of standard information numbers in monitor
direction
5.2.3.1
System functions in monitor direction
Table 44:
System functions in monitor direction
INF
Semantics
Supported
0
End of general interrogation
Yes
0
Time synchronization
Yes
2
Reset FCB
Yes
3
Reset CU
Yes
4
Start/restart
Yes
5
Power on
No
5.2.3.2
Status indications in monitor direction
Table 45:
Status indications in monitor direction
INF
Semantics
Supported
16
Auto-recloser active
Yes
17
Teleprotection active
No
18
Protection active
No
19
LED reset
Yes
20
Monitor direction blocked
No
21
Test mode
Yes
22
Local parameter setting
No
23 to
26
Characteristic 1 to Characteristic 4
Yes
27 to
30
Auxiliary input 1 to Auxiliary input 4
No
Section 5
1MRS757203 A
Interoperability
44
630 series
Communication Protocol Manual
Supervision indications in monitor direction
Table 46:
Supervision indications in monitor direction
INF
Semantics
Supported
32
Measurand supervision I
Yes
33
Measurand supervision V
Yes
35
Phase sequence supervision
No
36
Trip circuit supervision
No
37
I>> back-up operation
Yes
38
VT fuse failure
Yes
39
Teleprotection disturbed
No
46
Group warning
Yes
47
Group alarm
Yes
5.2.3.4
Earth fault indications in monitor direction
Table 47:
Earth fault indications in monitor direction
INF
Semantics
Supported
48 to
50
Earth fault L1 to Earth fault L3
No
51
Earth fault forward, i.e. Line
Yes
52
Earth fault reverse, i.e. Busbar
Yes
5.2.3.5
Fault indications in monitor direction
Table 48:
Fault indications in monitor direction
INF
Semantics
Supported
64 to
66
Start /pick-up L1 to Start /pick-up L3
Yes
67
Start /pick-up N
Yes
68
General trip
Yes
69 to
71
Trip L1 to Trip L3
Yes
72
Trip I>> (back-up operation)
Yes
73
Fault location X in ohms
Yes
74
Fault forward/line
Yes
75
Fault reverse/busbar
Yes
76
Teleprotection signal transmitted
Yes
77
Teleprotection signal received
Yes
78 to
82
Zone 1 to Zone 5
Yes
83
Zone 6
No
Table continues on next page
1MRS757203 A
Section 5
Interoperability
630 series
45
Communication Protocol Manual
Trip measuring system L1 to Trip measuring
system L3
Yes
89
Trip measuring system E
Yes
90
Trip I>
Yes
91
Trip I>>
Yes
92
Trip IN>
Yes
93
Trip IN>>
Yes
5.2.3.6
Auto-reclosure indications in monitor direction
Table 49:
Auto-reclosure indications in monitor direction
INF
Semantics
Supported
128
CB ‘on’ by AR
Yes
129
CB ‘on’ by long-time AR
No
130
AR blocked
Yes
5.2.3.7
Measurands in monitor direction
Table 50:
Measurands in monitor direction
INF
Semantics
Supported
144
Measurand I
Yes
145
Measurands I, V
Yes
146
Measurands I, V, P, Q
Yes
147
Measurands IN, VEN
Yes
148
Measurands IL1,2,3, VL1,2,3, P, Q, f
Yes
5.2.3.8
Generic functions in monitor direction
Table 51:
Generic functions in monitor direction
INF
Semantics
Supported
240
Read headings of all defined groups
No
241
Read values or attributes of all entries of one group
No
243
Read directory of a single entry
No
244
Read value or attribute of a single entry
No
245
End of general interrogation of generic data
No
249
Write entry with confirmation
No
250
Write entry with execution
No
251
Write entry aborted
No
Section 5
1MRS757203 A
Interoperability
46
630 series
Communication Protocol Manual
Selection of standard information numbers in control
direction
5.2.4.1
System functions in control direction
Table 52:
System functions in control direction
INF
Semantics
Supported
0
Initiation of general interrogation
Yes
0
Time synchronization
Yes
5.2.4.2
General commands in control direction
Table 53:
General commands in control direction
INF
Semantics
Supported
16
Auto-recloser on/off
Yes
17
Teleprotection on/off
Yes
18
Protection on/off
Yes
19
LED reset
Yes
23 to
26
Activate characteristic 1 to Activate characteristic 4
Yes
5.2.4.3
Generic functions in control direction
Table 54:
Generic functions in control direction
INF
Semantics
Supported
240
Read headings of all defined groups
No
241
Read values or attributes of all entries of one group
No
243
Read directory of a single entry
No
244
Read value or attribute of a single entry
No
245
General interrogation of generic data
No
248
Write entry
No
249
Write entry with confirmation
No
250
Write entry with execution
No
251
Write entry abort
No
1MRS757203 A
Section 5
Interoperability
630 series
47
Communication Protocol Manual
Basic application functions
Table 55:
Basic application functions
Supported
Yes
Test mode
No
Blocking of monitor direction
Yes
Disturbance data
No
Generic services
Yes
Private data
5.2.6
Miscellaneous
Measurands are transmitted with ASDU 3 as well as with ASDU 9. As defined in
7.2.6.8, the maximum MVAL can either be 1,2 or 2,4 times the rated value. No
different rating shall be used in ASDU 3 and ASDU 9, i.e. for each measurand
there is only one choice.
Table 56:
Miscellaneous
Measurand
Max. MVAL = rated value times
1,2
2,4
Current L1
Yes
Yes
Current L2
Yes
Yes
Current L3
Yes
Yes
Voltage L1-E
Yes
Yes
Voltage L2-E
Yes
Yes
Voltage L3-E
Yes
Yes
Active power P
Yes
Yes
Reactive power Q
Yes
Yes
Frequency f
Yes
Yes
Voltage L1 - L2
Yes
Yes
Recorded analog channels are sent with ASDU26 and ASDU31. One information
element in these ASDUs is called ACC and indicates the actual channel to be
processed. The channels on disturbance recorder will be sent with an ACC
according to the following table:
DRA#-Input
ACC
IEC103 meaning
1
1
IL1
2
2
IL2
3
3
IL3
4
4
IN
Table continues on next page
Section 5
1MRS757203 A
Interoperability
48
630 series
Communication Protocol Manual
Communication Protocol Manual
Application-layer service data unit
DNP3
A distributed network protocol originally developed by
Westronic. The DNP3 Users Group has the ownership
of the protocol and assumes responsibility for its evolution.
EMC
Electromagnetic compatibility
FAN
Fault number
FUN
Default function type
GI
General interrogation
HMI
Human-machine interface
IEC
International Electrotechnical Commission
IEC 60870-5-101 Companion standard for basic telecontrol tasks
IEC 60870-5-103 Communication standard for protective equipment; A
serial master/slave protocol for point-to-point
communication
IEC 60870-5-104 Network access for IEC 60870-5-101
IEC 61850
International standard for substation communication and
modeling
IED
Intelligent electronic device
INF
Default information number
LED
Light-emitting diode
LHMI
Local human-machine interface
NOF
Number of grid faults
OTEV
Disturbance recording triggered from start bit
PCM600
Protection and Control IED Manager
SOF
Status of fault
TEST
Disturbance data recorded in test mode bit
TM
Disturbance data transmission in progress bit
TP
Disturbance data recorded with or without trip bit
VDEW6
Communication protocol standard for protection devices
1MRS757203 A
Section 6
Glossary
630 series
51
Communication Protocol Manual
P.O. Box 699
FI-65101 VAASA, Finland
Phone
+358 10 22 11
Fax
+358 10 22 41094
www.abb.com/substationautomation
1MRS757203 A
© Copyright 2011 ABB. All rights reserved.