coupling a PROCONTROL station

to the FDDI (Fibre Distributed Data Interface) Publication No. D KWL 6322 95 E, Edition 10/17 Application This module is used for coupling the PROCONTROL station to the PROCONTROL remote bus which uses an FDDI ring (distributed data interface based on optical---fibre technology) acc. to the ISO/IEC 9314 standard. The distance between two s

ABB 88TK50-E/R1210 PROCONTROL remote---bus coupling

Sending from the station For send data communication, the station protocol control offers two modes: • Cyclic mode • Event mode. In cyclic mode, the station protocol control allocates the send permit (activated by cyclic calls) to the station modules, one after the other, allowing them to send their cyclic telegrams which are then stored in the send shared memory by the station---bus interface. At interva

PROCONTROL system parameters

The PROCONTROL system parameters define the data trans- mission from and to the station: System parameters Fixed value Number of cyclic telegrams in the system 24 000 FDDI token rotation time (in msec) 3 Synchronous bandwidth for PROCONTROL (in % TRT) 85 Number of event telegrams per frame 10 Number of PROCONTROL stations 249 Number of events per second • Non-Recurring max. peak load • Basic load 500 350 Statio

Switch S701 is used for setting module addresses (GA) 60 or

61, system address (SYS) 0, 1, 2 or 3, the mode (BA): for ’au- tonomous station’ (AS) or ’remote bus’ (FB) as well as for ac- tivation or deactivation of ’module detection’ (GE, i.e. function detecting which PROCONTROL station modules are plugged---in or removed). Switch S701: Assignments GA BA GE SYS Contacts 1 2 3 4 5 6 7 8 Significance 1 2 Example ON D SYS01 D D D D E

Standard FDDI interface

The standard FDDI interface is located on the module front (connectors X2 and X3). The module is connected directly to the FDDI ring via connec- tors X2 and X3. According to the FDDI standard, this ring has to be designed as a double ring (optical---fibre ring 1 and opti- cal---fibre ring 2) for redundancy reasons. The FDDI interface consists of two disconnectable optical transceivers with integrated connectors, of a

ABB 88TK50-E/R1210 Exchange of 88TK50 modules in case of

dual---channel station---bus coupling In the case of a dual---channel station---bus coupling, bump- less exchange of modules is possible on---line and without any impairment of the ongoing station operation provided that the module is in the PASSIVE state. The PASSIVE state is indicated by the following LED annuncia- tion on the module front: LED designation Operating state LED signal FE FDDI receiving O

ABB 88TK50-E/R1210 Disturbance annunciations on the module

On the module front, the following disturbances are indicated by red LEDs: LED designation --- Disturbance, general ST Types of disturbance 1 ... 3 --- Module disturbance of 88TK50 SG Type of disturbance 1 --- Processor halt HLT --- Disturbance of ring redundancy SR Light---emitting diode ST indicates all disturbances of the module and disturbances of the data communication with the module. After three