ABB 88TK50-E/R1210 Module And Application Description
| Brand: | ABB |
| Category: | Control Unit |
| Model: | 88TK50-E/R1210 (Module And Application Description) |
| File Type: | |
| File Size: | — |
| Pages: | 20 |
Text of ABB 88TK50-E/R1210 Module And Application Description
coupling a PROCONTROL station
to the FDDI (Fibre Distributed Data Interface)
Publication No.
D KWL 6322 95 E, Edition 10/17
Application
This module is used for coupling the PROCONTROL station to
the PROCONTROL remote bus which uses an FDDI ring
(distributed data interface based on optical---fibre technology)
acc. to the ISO/IEC 9314 standard.
The distance between two s
ABB 88TK50-E/R1210 PROCONTROL remote---bus coupling
Sending from the station
For send data communication, the station protocol control
offers two modes:
• Cyclic mode
• Event mode.
In cyclic mode, the station protocol control allocates the send
permit (activated by cyclic calls) to the station modules, one
after the other, allowing them to send their cyclic telegrams
which are then stored in the send shared memory by the
station---bus interface.
At interva
PROCONTROL system parameters
The PROCONTROL system parameters define the data trans-
mission from and to the station:
System parameters
Fixed
value
Number of cyclic telegrams in the system
24 000
FDDI token rotation time (in msec)
3
Synchronous bandwidth for PROCONTROL
(in % TRT)
85
Number of event telegrams per frame
10
Number of PROCONTROL stations
249
Number of events per second
•
Non-Recurring max. peak load
•
Basic load
500
350
Statio
Switch S701 is used for setting module addresses (GA) 60 or
61, system address (SYS) 0, 1, 2 or 3, the mode (BA): for ’au-
tonomous station’ (AS) or ’remote bus’ (FB) as well as for ac-
tivation or deactivation of ’module detection’ (GE, i.e. function
detecting
which
PROCONTROL
station
modules
are
plugged---in or removed).
Switch S701:
Assignments
GA
BA
GE
SYS
Contacts
1
2
3
4
5
6
7
8
Significance
1
2
Example
ON
D
SYS01
D
D
D
D
E
Standard FDDI interface
The standard FDDI interface is located on the module front
(connectors X2 and X3).
The module is connected directly to the FDDI ring via connec-
tors X2 and X3. According to the FDDI standard, this ring has
to be designed as a double ring (optical---fibre ring 1 and opti-
cal---fibre ring 2) for redundancy reasons.
The FDDI interface consists of two disconnectable optical
transceivers with integrated connectors, of a
ABB 88TK50-E/R1210 Exchange of 88TK50 modules in case of
dual---channel station---bus coupling
In the case of a dual---channel station---bus coupling, bump-
less exchange of modules is possible on---line and without any
impairment of the ongoing station operation provided that the
module is in the PASSIVE state.
The PASSIVE state is indicated by the following LED annuncia-
tion on the module front:
LED designation
Operating state
LED signal
FE
FDDI receiving
O
ABB 88TK50-E/R1210 Disturbance annunciations on the module
On the module front, the following disturbances are indicated
by red LEDs:
LED designation
--- Disturbance, general
ST
Types of disturbance 1 ... 3
--- Module disturbance of 88TK50
SG
Type of disturbance 1
--- Processor halt
HLT
--- Disturbance of ring redundancy
SR
Light---emitting diode ST indicates all disturbances of the
module and disturbances of the data communication with the
module.
After three