ABB INDUSTRIAL DRIVES
ATEX-certified motor thermal protection
functions for cabinet-built ACS880 drives
(options +L513+Q971 and +L514+Q971)
User's manual
ATEX-certified motor thermal
protection functions for cabinet-built
ACS880 drives (options +L513+Q971
and +L514+Q971)
User's manual
Table of contents
1. Safety instructions
© 2020 ABB Oy. All Rights Reserved.
3AXD50000014979 Rev D
EN
EFFECTIVE: 2020-02-24
Table of contents
1
Safety instructions
9
Contents of this chapter ...........................................................................
9
Use of warnings and notes .......................................................................
9
ATEX-certified motor thermal protection functions ............................................
11
Electrical safety precautions .....................................................................
2
Introduction to the manual
13
Contents of this chapter ...........................................................................
13
Applicability .........................................................................................
13
Target audience ....................................................................................
14
Exclusion of liability ................................................................................
14
Terms and abbreviations ..........................................................................
15
Related manuals ...................................................................................
3
ATEX-certified motor thermal protection function with PTC thermistor relays
(+L513+Q971)
17
Contents of this chapter ...........................................................................
17
Option description ..................................................................................
19
Operation principle .............................................................................
19
Without an FSO module ...................................................................
20
With an FSO module .......................................................................
21
Implementation of the manual reset .........................................................
21
Indications of the motor thermal protection function ......................................
21
Commissioning the drive for a motor in a hazardous area ..................................
22
PTC thermistor relays .............................................................................
22
ABB CM-MSS.41 thermistor motor protection relay .......................................
22
Layout ........................................................................................
23
Operation diagram ..........................................................................
23
DOLD MK 9163N.12/110-ATEX thermistor relay ..........................................
23
Layout ........................................................................................
24
Operation diagram ..........................................................................
24
Wiring ................................................................................................
24
Insulation of the sensor circuit ................................................................
25
General wiring instructions ....................................................................
25
Wiring example .................................................................................
26
Start-up and acceptance test .....................................................................
27
Maintenance ........................................................................................
27
Fault tracing .........................................................................................
27
Safety data and block diagrams .................................................................
27
Without an FSO module .......................................................................
28
With an FSO module ...........................................................................
4
ATEX-certified motor thermal protection function with Pt100 relays
(+L514+Q971)
29
Contents of this chapter ...........................................................................
Table of contents 5
Option description ..................................................................................
30
Pt100 relays .....................................................................................
31
Operation principle .............................................................................
31
Without an FSO module ...................................................................
32
With an FSO module .......................................................................
33
Implementation of the manual reset .........................................................
33
Indications of the motor thermal protection function ......................................
33
Commissioning the drive for a motor in a hazardous area ..................................
34
Pt100 relays ........................................................................................
34
GM International D1073S relay (programmable) ..........................................
34
Layout ........................................................................................
35
PR electronics 9116B1 universal converter relay (programmable) .....................
35
Layout ........................................................................................
35
Pt100 relay programming .....................................................................
35
Wiring ................................................................................................
35
Insulation of the sensor circuit ................................................................
36
General wiring instructions ....................................................................
37
Wiring example .................................................................................
37
Start-up and acceptance test .....................................................................
38
Maintenance ........................................................................................
38
Fault tracing .........................................................................................
39
Safety data and block diagrams .................................................................
39
Without an FSO module .......................................................................
40
With an FSO module ...........................................................................
5
Parameter settings
41
Contents of this chapter ...........................................................................
41
Drive / inverter ......................................................................................
41
Switching frequency limitation ................................................................
41
Reset method and status indications ........................................................
41
31.22 STO indication run/stop ............................................................
42
Motor overtemperature indication ........................................................
42
31.11 Fault reset selection .................................................................
42
Other recommended settings .................................................................
43
FSO module ........................................................................................
44
General parameters ............................................................................
46
Parameters for the STO function .............................................................
47
Parameters for the SSE function .............................................................
48
Parameters for the SS1 function .............................................................
50
SS1 ramp parameters in the drive/inverter unit ........................................
50
FSE module and safety pulse encoder parameters .......................................
51
Notes .............................................................................................
51
Mechanical brake control .........................................................................
6
Technical data
53
Contents of this chapter ...........................................................................
53
The ATEX-certified motor thermal protection functions ......................................
53
PTC thermistor relays .............................................................................
53
ABB CM-MSS.41 ...............................................................................
57
DOLD MK 9163N.12/110-ATEX ..............................................................
6 Table of contents
Pt100 relays ........................................................................................
59
GM International D1073S .....................................................................
60
PR electronics 9116B1 universal converter ................................................
62
General rules, notes and definitions ............................................................
62
Validation of the safety functions .............................................................
62
Competence .................................................................................
62
Validation procedure ........................................................................
63
Acceptance test reports ....................................................................
63
Ambient conditions .............................................................................
63
Reporting problems and failures related to safety functions .............................
63
Related standards and directives ................................................................
64
Markings of the drive ..............................................................................
65
ATEX certificate ....................................................................................
68
Declaration of Conformity .........................................................................
7
Circuit diagrams
70
Contents of this chapter ...........................................................................
71
PTC monitoring with two relays (+2L513+Q971) ..............................................
71
PTC monitoring with two relays and an FSO-12 module (+2L513+Q971+Q973) ........
74
Pt100 monitoring with three relays (+3L514+Q971) ..........................................
76
Pt100 monitoring with five relays and an FSO-12 module (+5L514+Q971+Q973) ......
Further information
Table of contents 7
Contents of this chapter
This chapter contains the safety instructions which you must obey when you install, operate
and do maintenance on the safety functions of a drive.
Use of warnings and notes
Warnings tell you about conditions which can cause injury or death, or damage to the
equipment. They also tell you how to prevent the danger. Notes draw attention to a particular
condition or fact, or give information on a subject.
The manual uses these warning symbols:
WARNING!
Electricity warning tells about hazards from electricity which can cause injury or
death, or damage to the equipment.
WARNING!
General warning tells about conditions, other than those caused by electricity,
which can cause injury or death, or damage to the equipment.
WARNING!
Electrostatic sensitive devices warning tells you about the risk of electrostatic
discharge which can cause damage to the equipment.
ATEX-certified motor thermal protection functions
Only qualified specialists are permitted to install, control and maintain the ATEX-certified
motor thermal protection functions (see EN/IEC 60079-14). Obey all safety regulations
1
Safety instructions 9
required with application of Ex motors in Zone 1/21 (equipment category 2) or Zone 2/22
(equipment category 2 or 3).
WARNING!
Obey the safety instructions of the drive. If you ignore them, injury or death,
or damage to the equipment can occur.
This manual does not contain the complete safety instructions of the drive. It only includes
the instructions related to the scope of this manual. The general instructions are given in
this section and the option-specific instructions in the applicable chapter.
In addition to this manual:
•
For ACS880 single drives, see the drive hardware manual
•
For ACS880 air-cooled multidrives, see ACS880 multidrive cabinets and modules safety
instructions (3AUA0000102301 [English])
•
For ACS880 liquid-cooled multidrives, see ACS880 liquid-cooled multidrive cabinets
and modules safety instructions (3AXD50000048633 [English]).
WARNING!
The functions described in this manual do not disconnect the voltage of the main
and auxiliary circuits from the drive. Do not do work on the drive, motor cable or
motor when they are energized. Before you start the work, do the steps in section
Electrical safety precautions (page 11).
WARNING!
If a short-circuit occurs in the output stage of the drive, the STO function does not
prevent the intermediate DC current from flowing through and heating up the motor.
The system integrator must take this into account when planning the protection of
the installation.
10 Safety instructions
Electrical safety precautions
These electrical safety precautions are for all personnel who do work on the drive, motor
cable or motor.
WARNING!
Obey these instructions. If you ignore them, injury or death, or damage to the
equipment can occur.
If you are not a qualified electrical professional, do not do installation or
maintenance work.
Go through these steps before you begin any installation or maintenance work.
1.
Clearly identify the work location and equipment.
2.
Disconnect all possible voltage sources. Make sure that re-connection is not possible.
Lock out and tag out.
•
Open the main disconnecting device of the drive.
•
Open the charging switch if present.
•
Open the disconnector of the supply transformer. (The main disconnecting device
in the drive cabinet does not disconnect the voltage from the AC input power busbars
of the drive cabinet.)
•
Close the grounding switch or switches ([Q9], option +F259) if present. Do not use
excessive force as the switch has electromagnetic interlocking.
•
If the drive is equipped with a DC/DC converter unit (optional): Open the DC
switch-disconnector ([Q11], option +F286) of the DC/DC converter. Open the
disconnecting device of the energy storage connected to the DC/DC converter unit
(outside the drive cabinet).
•
Open the auxiliary voltage switch-disconnector (if present), and all other possible
disconnecting devices that isolate the drive from dangerous voltage sources.
•
In the liquid cooling unit (if present), open the motor protective circuit breaker(s) of
the cooling pumps.
•
If you have a permanent magnet motor connected to the drive, disconnect the motor
from the drive with a safety switch or by other means.
•
Disconnect any dangerous external voltages from the control circuits.
•
After you disconnect power from the drive, always wait 5 minutes to let the
intermediate circuit capacitors discharge before you continue.
3.
Protect any other energized parts in the work location against contact.
4.
Take special precautions when close to bare conductors.
Safety instructions 11
Measure that the installation is de-energized. If the measurement requires removal or
disassembly of shrouding or other cabinet structures, obey the local laws and regulations
applicable to live working (including – but not limited to – electric shock and arc
protection).
•
Use a multimeter with an impedance greater than 1 Mohm.
•
Make sure that the voltage between the drive input power terminals (L1, L2, L3)
and the grounding (PE) busbar is close to 0 V.
•
Make sure that the voltage between the drive output terminals (T1/U, T2/V, T3/W)
and the grounding (PE) busbar is close to 0 V.
•
Make sure that the voltage between the drive DC busbars (+ and -) and the
grounding (PE) busbar is close to 0 V.
WARNING!
The busbars inside the cabinet of liquid-cooled drives are partially coated.
Measurements made through the coating are potentially unreliable, so only
measure at uncoated portions. Note that the coating does not constitute a safe
or touch-proof insulation.
6.
If the drive is not equipped with a grounding switch, install temporary grounding as
required by the local regulations.
7.
Ask the person in control of the electrical installation work for a permit to work.
12 Safety instructions
Introduction to the manual
Contents of this chapter
This chapter contains information on the manual.
Applicability
The manual is applicable to cabinet-built ACS880 single drives and multidrives with the
options:
•
+L513+Q971 and +2L513+Q971 (+3L513+Q971 is available as an order-based
engineered option)
•
+3L514+Q971, +5L514+Q971 and +8L514+Q971 (other configurations with a maximum
of 8 relays are available as an order-based engineered option).
The motor thermal protection functions described in this manual are certified, with an EU-type
examination certificate, as protective systems in accordance with the ATEX Product Directive
2014/34/EU.
Target audience
The manual is intended for people who install, start-up, use and service the ATEX-certified
motor thermal protection functions of the drive. Read the manual before working on the
drive. You are expected to know the fundamentals of electricity, wiring, electrical components,
electrical schematic symbols and ATEX/Ex regulations.
2
Introduction to the manual 13
Exclusion of liability
ABB is not responsible for the implementation, verification and validation of the overall safety
system. It is the responsibility of the system integrator (or other party) who is responsible
for the overall system and system safety.
The system integrator (or other responsible party) must make sure that the entire
implementation complies with the instructions in this manual, all relevant standards, directives
and local electrical code, and that the system is tested, verified and validated correctly.
Terms and abbreviations
Description
Term
Directives 2014/34/EU and 1999/92/EC are commonly referred to as the ATEX direct-
ives (from "Atmosphères Explosibles")
ATEX
Type of control unit
BCU
An IEC term used in the context of explosive atmospheres (IEC 60079)
Ex
Type of protection, flameproof enclosures (EN/IEC 60079-1)
Ex d
Types of protection, increased safety (EN/IEC 60079-7)
Ex eb, Ex ec
Type of protection, intrinsic safety (EN/IEC 60079-11)
Ex i
Motors used in explosive atmospheres
Ex motors
Failure in time: 1E-9 hours (IEC 61508)
FIT
Physical size of the drive or power module
Frame, frame size
Optional pulse encoder interface module for safety encoder
FSE-31
Safety functions module which supports the FSE-31 module and the use of safety
encoders
FSO-21
Safety functions module which does not support the use of encoders
FSO-12
Hardware fault tolerance (IEC 61508)
HFT
Average probability of dangerous failure on demand (IEC 61508)
PFDavg
Programmable logic controller
PLC
Resistance temperature detector
RTD
Safe acceleration range
SAR
Safe brake control
SBC
Safety integrity level (1...3) (IEC 61508)
SIL
Safe stop 1 (IEC/EN 61800-5-2)
SS1
Safe stop emergency
SSE
Safe torque off (IEC/EN 61800-5-2)
STO
There are three categories of stop functions:
• stop category 0: an uncontrolled stop where power to the machine actuators is re-
moved immediately (STO)
• stop category 1: a controlled stop where the machine actuators have power for
stopping, after which the power is removed (SS1)
• stop category 2: a controlled stop where the machine actuators continue to have
power SS2).
Stop category
Proof test interval. Defines the probabilistic failure rate (PFH or PFDavg) for the safety
function or subsystem. Performing a proof test at a maximum interval of T1 is required
to keep the SIL capability valid. The same interval must be followed to keep the PL
capability (EN ISO 13849) valid. Note that any T1 values given cannot be regarded
as a guarantee or warranty.
T1
Type of control unit
ZCU
Potentially explosive atmosphere. Hazardous areas are divided into zones, based on
the frequency and duration of the occurrence of an explosive atmosphere. (EN/IEC
60079)
Zone
14 Introduction to the manual
ACS880-07 drives (560 to 2800 kW) hardware manual
3AUA0000105718
ACS880-07 drives (45 to 710 kW, 50 to 700 hp) hardware manual
3AXD50000020436
ACS880-17 drives (160 to 3200 kW) hardware manual
3AXD50000035158
ACS880-17 drives (45 to 400 kW) hardware manual
3AXD50000250295
ACS880-17LC hardware manual
3AXD50000020437
ACS880-37 drives (160 to 3200 kW) hardware manual
3AXD50000035159
ACS880-37 drives (45 to 400 kW) hardware manual
3AXD50000251407
ACS880-37LC hardware manual
3AUA0000101764
ACS880 multidrive cabinets mechanical installation instructions
3AXD50000048635
ACS880 liquid-cooled multidrive cabinets mechanical installation instructions
3AUA0000102324
ACS880 multidrive cabinets and modules electrical planning instructions
3AXD50000048634
ACS880 liquid-cooled multidrive cabinets and modules electrical planning
Inverter units
3AUA0000102519
ACS880-107 inverter units hardware manual
3AXD50000196111
ACS880-107LC inverter units hardware manual
Drive firmware
3AUA0000085967
ACS880 primary control program firmware manual
3AUA0000098062
ACS880 primary control program quick start-up guide
PC tools
3AUA0000094606
Drive composer start-up and maintenance PC tool user's manual
3AXD10000102417
Functional safety design tool user’s manual
Safety
3AUA0000102301
ACS880 multidrive cabinets and modules safety instructions
3AXD50000048633
ACS880 liquid-cooled multidrive cabinets and modules safety instructions
3AUA0000048753
Functional safety; Technical guide No. 10
1SFC001008B0201
Safety and functional safety; A general guide
www.abb.com/safety
ABB Safety information and solutions
3AUA0000037223
Motors and drives in potentially explosive atmospheres - What you need to know
Options
3AUA0000085685
ACX-AP-x assistant control panels user’s manual
3AXD50000014979
ATEX-certified motor thermal protection functions for cabinet-built ACS880 drives
(options +L513+Q971 and +L514+Q971)
3AXD50000015612
FSO-12 safety functions module user’s manual
3AXD50000015614
FSO-21 safety functions module user’s manual
3AXD50000016597
FSE-31 pulse encoder interface module user’s manual
3AXD50000027782
FPTC-02 ATEX-certified thermistor protection module, Ex II (2) GD (option
+L537+Q971) for ACS880 drives user's manual
Manuals and quick guides for I/O extension modules, fieldbus adapters, etc.
Other documents
Delivered with the drive
Circuit diagrams
Introduction to the manual 15
Delivered with the drive
Part lists
You can find manuals and other product documents in PDF format on the Internet. See
Document Library. For manuals not available in the Document library, contact your local
ABB representative.
For additional ABB safety information and solutions visit http://www.abb.com/safety.
16 Introduction to the manual
ATEX-certified motor thermal protection
function with PTC thermistor relays
(+L513+Q971)
Contents of this chapter
This chapter describes the ATEX-certified motor thermal protection function (option
+L513+Q971) and gives instructions on how to wire, install and start up the function. It also
describes the PTC thermistor relays available for the option and gives fault tracing and
maintenance instructions. The safety data is also given.
Option description
This protection function monitors the temperature of a motor with PTC resistor sensors (PTC
thermistors) in a potentially explosive atmosphere. The function is activated when the PTC
sensor resistance exceeds the overtemperature limit. It is possible to:
•
monitor the motor bearings or stator windings (+L513+Q971)
•
monitor the motor bearings and stator windings (+2L513+Q971 or +3L513+Q971).
The safety function described in this manual activates the Safe torque off (STO) function of
the drive when it detects motor overtemperature. The STO function of the ACS880 drives
is certified (SIL 3 according to EN/IEC 61800-5-2 and IEC 61508). When activated, the STO
function disables the control voltage of the power semiconductors of the drive output stage.
This prevents the inverter from generating the torque required to rotate the motor. The motor
coasts to a stop. For a detailed description of the STO function, see the hardware manual
of your drive/inverter unit.
ACS880-07/17/37 and ACS880-17LC/37LC drives with option +Q978: Also the main
contactor/breaker is opened.
3
ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971) 17
ACS880-07 drives (frames n×DxT + n×R8i) with a main contactor/breaker (option
+F250/+F255), ACS880-17/37 drives (frames n×R8i + n×R8i) and ACS880-17LC/37LC
drives (frames n×R8i + n×R8i): When the STO function is activated in the inverter unit, the
main contactor/breaker is opened after user-defined delay (defined with parameter 94.11,
the default value is 600 s). See hardware and firmware manuals for more information.
Other safety functions in the drive can also use the STO function. Also, an FSO module can
be included in the ATEX-certified motor thermal protection function. See the circuit diagrams
delivered with the drive for the actual safety circuitry.
The FSO safety functions module (FSO-12 or FSO-21) is an optional device used with the
ACS880 drives to implement safety functions. When installed, it reserves the standard STO
connection of the drive.
The motor thermal protection function is implemented as follows:
•
without an FSO module, the opening contacts of the relay(s) open the STO circuit of
the drive.
•
with an FSO module, the opening contacts of the relay(s) activate the STO or Safe stop
1 (SS1) function of the FSO module, and the FSO module opens the STO circuit of the
drive.
Select the stop category according to the system risk assessment.
The protection function circuit is motor-specific. The function stops only the motor where
overtemperature is detected.
It is possible to get information on the status of the protection function through a
normally-open contact of the relay. The information can be obtained separately from the
bearing and stator sensors. The contact can be wired to a digital input on the drive control
unit or to an external control system. See the wiring instructions.
18 ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971)
Without an FSO module
1.
When the motor temperature rises to the thermistor wake-up level, the resistance of
the thermistor increases sharply.
2.
The PTC thermistor relay detects the change and indicates motor overtemperature
through its output contacts.
3.
The opening contacts of the PTC relay(s) open the STO circuit of the drive. This prevents
the drive from generating the torque required to rotate the motor.
4.
The drive generates an STO indication (parameter 31.22).
5.
If the auxiliary contacts of the PTC relays are wired to a digital input of the drive (or
inverter unit), the loss of the signal triggers a motor overtemperature indication in the
drive.
6.
After the motor temperature has decreased to normal, the user resets the PTC relay(s)
using remote reset buttons (or the buttons on the PTC relays themselves). See the
circuit diagrams of the delivery.
7.
Optional: The user resets the drive faults either from the reset source defined by the
user (parameter 31.11) or locally with the drive control panel:
•
the STO fault in the drive (if configured with drive parameter 31.22)
•
the motor overtemperature fault in the drive (if configured).
Note: ABB recommends that you do not use the autoreset setting (that is, short-circuit the
reset switch terminals of the PTC relay) with a safety device protecting an Ex motor.
ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971) 19
With an FSO module
1.
When the motor temperature rises to the thermistor wake-up level, the resistance of
the thermistor increases sharply.
2.
The PTC thermistor relay detects the change and indicates motor overtemperature
through its output contacts.
3.
The opening contacts of the PTC relay(s) switch off the voltage to terminal X113:4 of
the FSO module (this is configured as the input of the STO [or SS1] function in the FSO
module).
4.
The FSO module opens the STO circuit of the drive either immediately (STO function)
or after a deceleration ramp (SS1 function). This prevents the drive from generating the
torque required to rotate the motor.
5.
The drive generates an STO indication (parameter 31.22).
6.
The FSO module generates an STO indication (parameter FSOGEN.61).
7.
If the auxiliary contacts of the PTC relay(s) are wired to a digital input, the loss of the
signal triggers a motor overtemperature indication.
8.
After the motor temperature has decreased to normal, the user resets the PTC relay(s)
using remote reset buttons (or the buttons on the PTC relays themselves). See the
circuit diagrams of the delivery.
9.
Optional: The user resets the drive faults either from the reset source defined by the
user (parameter 31.11) or locally with the drive control panel:
•
the STO fault in the drive (if configured with drive parameter 31.22)
•
the motor overtemperature fault in the drive (if configured).
10. Optional: The user resets the safety function in the FSO module with the reset button
(if a reset circuit is wired and configured).
20 ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971)
Note: ABB recommends that you do not use the autoreset setting (that is, short-circuit the
reset switch terminals of the PTC relay) with a safety device protecting an Ex motor.
■Implementation of the manual reset
After the ATEX-certified motor thermal protection function activates, the motor must not
restart before a manual reset command is given.
The manual reset is set in the ATEX-certified PTC thermistor relay at the factory. This
complies with the ATEX requirement on manual reset, which means that you do not have
to configure any faults in the drive or FSO parameters. If you change the manual reset
setting in the PTC thermistor relay, make sure that the user cannot restart the drive without
a manual reset.
You can configure the manual reset either in:
•
the drive with the motor overtemperature or STO indication parameters
•
the FSO module by connecting a reset circuit to the FSO module.
ACS880-07/17/37 and ACS880-17LC/37LC drives with the option +Q978 or +Q979
(Emergency stop): In these safety functions, a reset circuit is connected to the FSO module
and the user must reset the safety function with the emergency stop reset button. The user
must also reset the ATEX-certified motor thermal protection function with the emergency
stop reset button. Do not change this setting.
■Indications of the motor thermal protection function
An indication of the safety function can come from several sources:
•
the motor overtemperature indication in the drive
•
the STO indication in the drive
•
the STO or SS1 indication in the FSO module.
If you want to avoid parallel indications in overtemperature situations, you can set one or
several of the indication parameters value to No indication (or None) or Event:
•
the motor overtemperature indication with drive parameters 31.01…31.02 or
35.11…35.12
•
the STO indication in the drive with drive parameter 31.22 STO indication run/stop
•
the STO or SS1 indication in the FSO module with FSO parameter FSOGEN.61 STO
indication ext request.
If the PTC thermistor relay is not in the manual reset mode, make sure that at least one of
these indications generates a fault.
Commissioning the drive for a motor in a hazardous area
Commission the drive according to the requirements and limitations set by the application,
the motor manufacturer’s instructions, drive firmware manual, local laws and regulations
and this manual.
The certificate of the Ex motor typically requires that you set a minimum limit for the output
switching frequency of the drive. Make sure that the Ex motor is operated above the minimum
output switching frequency specified by the motor manufacturer.
ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971) 21
PTC thermistor relays
The ATEX-certified motor thermal protection function contains one (+L513) or two (+2L513)
ABB CM-MSS.41 thermistor relay(s) by default. Three ABB CM-MSS.41 thermistor relays
(+3L513) are available as an order-based engineered option.
DOLD MK 9163N.12/110-ATEX thermistor relay(s) are available as an order-based
engineered option.
■ABB CM-MSS.41 thermistor motor protection relay
Layout
Power supply
A1-A2
Measuring circuit with 1…3 sensors
T1-T2
Remote reset push button switch
Note: Although autoreset of the relay can be implemented
by connecting these terminals together, this is not recommen-
ded when used in the protection function of an Ex motor.
S1-T2
Output contacts (1)
• 11: Common
• 12: Normally-closed
• 14: Normally-open
11-12/14
Output contacts (2)
• 21: Common
• 22: Normally-closed
• 24: Normally-open
21-22/24
Fault reset button
Reset: only possible if the measured value is less than switch-
on resistance.
Test: only possible when there is no fault.
Test / Reset
Indication of operational states
LEDs
Supply voltage present
“U” LED (green)
Fault message (overtemperature, broken wire, or short-circuit in the measurement circuit)
“F” LED (red)
Output relay status
“R” LED (yellow)
DIP switches
4
3
2
1
Position
Non-volatile fault
storage de-activated
Short-circuit detec-
tion de-activated
Not in use
Not in use
ON
Non-volatile fault
storage activated
Short-circuit detec-
tion activated
Not in use
Not in use
OFF (default)
22 ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971)
Test / Reset
S1-T2
11-14 / 21-24
11-12 / 21-22
1
5
1
5
5
5
3
4
2
Tripping caused by overtemperature
1
Control supply voltage interrupted
2
Test (outputs are switched off)
3
Short-circuit in sensor circuit
4
Reset (resets fault)
5
• Manually with a front-face Test / Reset button
• Externally by a remote reset between terminal S1-T2
■DOLD MK 9163N.12/110-ATEX thermistor relay
Layout
Power supply
A1-A2
A1 (+)
11
21
P1
P2
X1
R
Test /
Reset
22
24
X2
12
14
A2
Measuring circuit with 1…6 sensors
P1-P2
Remote reset push button switch
X1-X2
Output contacts (1)
• 11: Common
• 12: Normally-closed
• 14: Normally-open
11-12/14
Output contacts (2)
• 21: Common
• 22: Normally-closed
• 24: Normally-open
21-22/24
Test and internal reset button
Test / Reset
Supply voltage present
Upper LED
(green)
Fault (overtemperature, broken wire, or short-circuit in the
sensor circuit)
"R" LED (red)
ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971) 23
≥ 3800 Ω
A1/A2
≤ 1500 Ω
≤ 20 Ω
P1/P2
R [Ω]
X1/X2
Test/Reset
11-14/21-24
11-12/21-22
1
2
3
4
5
Tests
1
Overtemperature/broken wire detection
2
Voltage failure/reset
3
Sensor short-circuit
4
Test/Reset
5
Wiring
■Insulation of the sensor circuit
When you connect the temperature sensor(s) of the Ex motor to the drive STO terminals
through a relay, make sure that there is reinforced (double) insulation between the main
circuit (motor) and the drive control unit as required by IEC 61800-5-1. The insulation of the
temperature sensor in the Ex motor and the insulation of the protection relay form the
insulation of the whole circuit. All Ex motors manufactured by ABB have basic insulation
between the main circuit and the temperature sensor. The thermistor relays shown in this
manual have basic insulation between the sensor circuit and relay output. This ensures that
there is double insulation between the main circuit and the drive control unit.
24 ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971)
■General wiring instructions
1.
Install only the sensor circuit into the potentially explosive atmosphere.
The sensor circuit in the Ex Zone must comply with the requirements for the applicable
type of protection, such as:
•
Ex d (EN/IEC 60079-1)
•
Ex eb (EN/IEC 60079-7, Ex e in EN 60079-7:2007 and IEC 60079-7:2006)
•
Ex ec (EN/IEC 60079-7, Ex nA in EN/IEC 60079-15:2010).
2.
Install the drive or inverter unit, including the components of the ATEX-certified motor
thermal protection function, outside the potentially explosive atmosphere.
3.
For the sensor connection, ABB recommends to use shielded twisted-pair cable. This
type of cable decreases electromagnetic interference in the sensor circuit.
4.
Route the sensor cables away from the motor cable. Power cables can cause
electromagnetic interference in the sensor circuit.
5.
Ground all sensor cable shields to a single grounding point outside the potentially
explosive atmosphere. 360-degree grounding of the cable shields is recommended. Do
not connect the cable shields to ground at the sensor end of the cable.
■Wiring example
1.
Connect the PTC sensor(s) of the motor to the PTC thermistor relay(s) [K74] (and [K75],
[K76] if included) to terminal block [X506].
2.
Indication to the drive via DI6 (shown below): Connect a +24 V DC source via contacts
11 and 14 of the PTC thermistor relay(s) (pre-wired to terminal block [X506] at the
factory) to digital input DI6 on the drive control unit.
3.
Connect a reset button for the PTC relay(s) via terminal block [X506] (recommended).
4.
With an FSO module (not shown in the figure): If necessary, connect a reset circuit to
an input of the FSO module (for example, DI X113:2).
ZCU/BCU
14
K74
(K75)
11
14
11
X506:32
X506:41
X506:42
X506:31
XD24:7
X504
XD24:7
+24VD
(K76)
14
11
X506:51
X506:52
XDI:6
XDI:6
DI6
Thermistor relay, stator windings
K74
Thermistor relay, bearings
K75
Thermistor relay, stator windings
K76
Additional I/O terminal block (option +L504)
X504
ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971) 25
Drive control unit
ZCU/BCU
See the circuit diagrams delivered with the drive for the actual wiring and terminals. For
wiring diagram examples, see chapter Circuit diagrams.
Start-up and acceptance test
Use the Drive composer PC tool or a control panel to do the start-up and acceptance test.
To set FSO module parameters, you must use the Drive composer pro PC tool.
Action
Initial status
Make sure that the drive is ready for use, that is, you have done the tasks of the drive start-up procedure.
See the drive hardware manual.
WARNING!
Obey the Safety instructions (page 9). If you ignore them, injury or death, or damage to the
equipment can occur.
Checks and settings with no voltage connected
Stop the drive and do the steps in section Electrical safety precautions (page 11) before you start the
work.
Make sure that the classification of the motor thermal protection function corresponds to the Ex classi-
fication of the environment and the Ex motor.
The motor manufacturer selects the PTC sensors for the motor temperature measurement. Make sure
that the temperature on-off resistances match those of the PTC thermistor relay. Also make sure that
there is basic or reinforced insulation between the sensor and the motor main circuit.
Make sure that the installation of PTC sensors complies with the requirements for the applicable type
of protection. See section Wiring (page 24).
Make sure that the wires are connected to the correct terminals and that the terminal connections are
tightened.
Settings with voltage connected
If necessary, set the applicable parameters. See chapter Parameter settings (page 41).
If necessary, configure the motor overtemperature and STO indication. See section Reset method and
status indications (page 41).
Acceptance test procedure
To test short-circuit detection, short-circuit the sensor input with a 20 ohm resistance (you do not have
to disconnect the sensor circuit).
Expected outcome: Relay fault trip (the applicable LED lights). Drive STO is activated.
Make sure that the correct indications are activated.
To test wire break monitoring, disconnect the sensor circuit.
Expected outcome: Relay fault trip (the applicable LED lights). Drive STO is activated.
Make sure that the correct indications are activated.
To test excess temperature detection, increase the resistance of the sensor circuit from 50 … 1500 ohm
to 4 kohm.
Expected outcome: Relay fault trip (the applicable LED lights). Drive STO is activated.
Make sure that the correct indications are activated.
With the relay(s) in tripped state, try to start the drive. The drive must not start before the PTC relay(s)
and/or any drive (and FSO) faults are reset.
Fill in and sign the acceptance test report which verifies that the safety function is safe and accepted
to operation.
26 ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971)
After the operation of the safety circuit has been verified at start-up, the circuit requires a
periodic proof test at least every two years.
If you change any wirings or components related to the motor thermal protection function
after the start-up, repeat the procedure given in section Start-up and acceptance
test (page 26).
Fault tracing
For the warning and fault messages generated by the drive, see the drive firmware manual.
For the fault indication LEDs of the PTC relays, see section PTC thermistor relays (page 22).
For the status LEDs of the FSO module, see the FSO module user’s manual.
Safety data and block diagrams
The safety block diagrams show the components that are included in the safety data
calculations.
■Without an FSO module
1
2
3
Customer motor PTC sensor(s)
1
Thermistor relay(s)
2
• K74
• (K75)
• (K76)
Drive STO
3
PFDavg (1…3 relays)
T1
HFT
SIL
5.00E-2
2 years
0
1
3AXD10000331763 E
ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971) 27
■With an FSO module
1
2
3
4
Customer motor PTC sensor(s)
1
Thermistor relay(s)
2
• K74
• (K75)
• (K76)
FSO module
FSE module (optional)1)
3
Drive STO
4
1) The FSE module is included in the calculations only if:
• a safety encoder is used in the application, and
• the FSO-21 module is configured to activate the SS1 function (stop category 1) in overtemperature situations, and
• the ramp monitoring method is used in the SS1 function.
PFDavg (1…3 relays)
T1
HFT
SIL
5.02E-2
2 years
0
1
3AXD10000331763 E
28 ATEX-certified motor thermal protection function with PTC thermistor relays (+L513+Q971)
ATEX-certified motor thermal protection
function with Pt100 relays
(+L514+Q971)
Contents of this chapter
This chapter describes the ATEX-certified motor thermal protection function (option
+L514+Q971) and gives instructions on how to wire, install and start up the function. It also
describes the Pt100 relays available for the option and gives fault tracing and maintenance
instructions. The safety data is also given.
Option description
This protection function monitors the temperature of a motor with Pt100 sensors in a
potentially explosive atmosphere. The function is activated when the motor temperature
exceeds the set operating temperature limit of the Pt100 relay. It is possible to:
•
monitor the motor stator windings (+3L514+Q971)
•
monitor the motor bearings and stator windings (+5L514+Q971)
•
monitor the motor bearings and double-monitor the stator windings (+8L514+Q971).
Other configurations are available as an order-based engineered option. The maximum
number of Pt100 relays is 8.
The safety function described in this manual activates the Safe torque off (STO) function of
the drive when it detects motor overtemperature. The STO function of the ACS880 drives
is certified (SIL 3 according to EN/IEC 61800-5-2 and IEC 61508). When activated, the STO
function disables the control voltage of the power semiconductors of the drive output stage.
This prevents the inverter from generating the torque required to rotate the motor. The motor
coasts to a stop. For a detailed description of the STO function, see the hardware manual
of your drive/inverter unit.
4
ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971) 29
ACS880-07/17/37 and ACS880-17LC/37LC drives with option +Q978: Also the main
contactor/breaker is opened.
ACS880-07 drives (frames n×DxT + n×R8i) with a main contactor/breaker (option
+F250/+F255), ACS880-17/37 drives (frames n×R8i + n×R8i) and ACS880-17LC/37LC
drives (frames n×R8i + n×R8i): When the STO function is activated in the inverter unit, the
main contactor/breaker is opened after user-defined delay (defined with parameter 94.11,
the default value is 600 s). See hardware and firmware manuals for more information.
Other safety functions in the drive can also use the STO function. Also, an FSO module can
be included in the ATEX-certified motor thermal protection function. See the circuit diagrams
delivered with the drive for the actual safety circuitry.
The FSO safety functions module (FSO-12 or FSO-21) is an optional device used with the
ACS880 drives to implement safety functions. When installed, it reserves the standard STO
connection of the drive.
The motor thermal protection function is implemented as follows:
•
without an FSO module, the opening contacts of the relay(s) open the STO circuit of
the drive.
•
with an FSO module, the opening contacts of the relay(s) activate the STO or Safe stop
1 (SS1) function of the FSO module, and the FSO module opens the STO circuit of the
drive.
Select the stop category according to the system risk assessment.
The protection function circuit is motor-specific. The function stops only the motor where
overtemperature is detected.
It is possible to get information on the status of the protection function through a
normally-open contact of the relay. The information can be obtained separately from the
bearing and stator sensors. The contact can be wired to a digital input on the drive control
unit or to an external control system. See the wiring instructions.
■Pt100 relays
The Pt100 relays are configurable PLCs. In addition to the actuation of the motor thermal
protection function, it is possible to get, for example, a 4 … 20 mA analog temperature signal
from each Pt100 sensor.
The used Pt100 relays are [Ex i] (intrinsically safe) approved associated apparatus (Ex i
barrier). The installation and cabling of the protection circuit in the ACS880 cabinet is done
as intrinsically safe according to EN/IEC 60079-14 ed. 5 clause 16.
If Pt100 sensors in the Ex Zone are not protected by an Ex type of protection (eg, Ex eb,
Ex ec or Ex d), the cabling from sensors to the terminal blocks in the drive must be done
as intrinsically safe [Ex i] installation. To comply with the [Ex i] requirements, use shielded
or shielded twisted pair cable.
If Pt100 sensors in the Ex Zone are protected by an Ex type of protection (eg, Ex eb, Ex ec
or Ex d), the intrinsically safe [Ex i] installation and cabling are not required. If the final
installation does not need [Ex i] installation, the Ex i markings must be removed or covered
from the cabinet.
The drive delivery contains a notification label, stating: Note! This sensor circuit is not
executed as intrinsically safe [Ex i] installation.
If [Ex i] installation is not required, you must attach the label to the drive cabinet.
30 ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971)
The temperature measurement circuit of ABB motors has basic insulation. For information
on the insulation of the Pt100 relay, see the applicable relay data sheet.
■Operation principle
Without an FSO module
1.
When the motor temperature rises, the sensor resistance increases linearly.
2.
When the motor temperature exceeds the set operating temperature limit of the Pt100
relay, the relay indicates motor overtemperature through its output contacts.
3.
The opening contacts of the extension relay(s) [-A81] ([-A82] and [-A83]) open the STO
circuit of the drive. This prevents the drive from generating the torque required to rotate
the motor.
4.
The drive generates an STO indication (parameter 31.22).
5.
If the extension relay(s) [-A81] ([-A82] and [-A83]) are wired to a digital input, the loss
of the signal triggers a motor overtemperature fault in the drive.
6.
After the motor temperature has decreased to normal, the Pt100 relays reset
automatically.
7.
The user must reset the drive faults either from the reset source defined by the user
(parameter 31.11) or locally with the drive control panel:
•
the STO fault in the drive (if configured with drive parameter 31.22)
•
the motor overtemperature fault in the drive (if configured).
ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971) 31
With an FSO module
1.
When the motor temperature rises, the sensor resistance increases linearly.
2.
When the motor temperature exceeds the set operating temperature limit of the Pt100
relay, the relay indicates motor overtemperature through its output contacts.
3.
The opening contacts of the extension relay(s) [-A81] ([-A82] and [-A83]) switch off the
voltage to terminal X113:4 of the FSO module (this is configured as the input of the
STO [or SS1] function in the FSO module).
4.
The FSO module opens the STO circuit of the drive either immediately (STO function)
or after a deceleration ramp (SS1 function). This prevents the drive from generating the
torque required to rotate the motor.
5.
The drive generates an STO indication (parameter 31.22).
6.
The FSO module generates an STO indication (parameter FSOGEN.61).
7.
If the extension relay(s) [-A81] ([-A82] and [-A83]) are wired to a digital input, the loss
of the signal triggers a motor temperature fault in the drive.
8.
After the motor temperature has decreased to normal, the Pt100 relays reset
automatically.
32 ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971)
The user must reset the faults either from the reset source defined by the user (parameter
31.11) or locally with the drive control panel:
•
the STO fault in the drive (if configured with drive parameter 31.22)
•
the motor overtemperature fault in the drive (if configured).
10. Optional: The user must reset the safety function in the FSO module with the reset
button (if a reset circuit is wired and configured).
■Implementation of the manual reset
After the ATEX-certified motor thermal protection function activates, the motor must not
restart before a manual reset command is given.
The Pt100 relay is reset automatically. To comply with the ATEX requirement on manual
reset, make sure that the user cannot restart the drive without a manual reset.
You must configure the manual reset either in:
•
the drive with the motor overtemperature or STO indication parameters
•
the FSO module by connecting a reset circuit to the FSO module.
ACS880-07/17/37 and ACS880-17LC/37LC drives with the option +Q978 or +Q979
(Emergency stop): In these safety functions, a reset circuit is connected to the FSO module
and the user must reset the safety function with the emergency stop reset button. The user
must also reset the ATEX-certified motor thermal protection function with the emergency
stop reset button. Do not change this setting.
■Indications of the motor thermal protection function
An indication of the safety function can come from several sources:
•
the motor overtemperature indication in the drive
•
the STO indication in the drive
•
the STO or SS1 indication in the FSO module.
If you want to avoid parallel indications in overtemperature situations, you can set one or
several of the indication parameters value to No indication (or None) or Event:
•
the motor overtemperature indication with drive parameters 31.01…31.02 or
35.11…35.12
•
the STO indication in the drive with drive parameter 31.22 STO indication run/stop
•
the STO or SS1 indication in the FSO module with FSO parameter FSOGEN.61 STO
indication ext request.
Make sure that at least one of these indications generates a fault to ensure that the required
manual reset is implemented.
Commissioning the drive for a motor in a hazardous area
Commission the drive according to the requirements and limitations set by the application,
the motor manufacturer’s instructions, drive firmware manual, local laws and regulations
and this manual.
The certificate of the Ex motor typically requires that you set a minimum limit for the output
switching frequency of the drive. Make sure that the Ex motor is operated above the minimum
output switching frequency specified by the motor manufacturer.
ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971) 33
The option contains 3, 5, or 8 GM International D1073S relays by default. Other configurations
are available as an order-based engineered option. The maximum number of relays is 8.
PRelectronics 9116B1 relays are available as an order-based engineered option.
The option also contains one, two or three DOLD LG5925.48 extension relays in the Safe
torque off and diagnostic circuits.
■GM International D1073S relay (programmable)
Layout
Current output
1-2
1
2
3
4
16
15
14
13
5
6
7
8
C
O
N
F
PWR BURN
ALARM
A
B
• 1: + Output channel 1 for Current Source Mode or
Voltage Source Mode1)
• 2: - Output channel 1 for Current Source Mode or
Voltage Source Mode 1)
This output has been pre-wired to terminal block X506.
See chapter Circuit diagrams.
Power supply
• 3: + 24 V DC
• 4: - 24 V DC
3-4
Output contacts (Alarm A)
5-6
Output contacts (Alarm B)
7-8
Measuring circuit
• 13: Input channel 1 for 3-4 wire RTD, Reference
Junction Compensator Option 91 or potentiometer 1)
• 14: Input channel 1 for 3-4 wire RTD
• 15: + Input channel 1 for 4 wire RTD, thermocouple
TC or potentiometer 1)
• 16: Input channel 1 for 3-4 wire RTD, thermocouple
TC or potentiometer 1)
13-16
Programming channel
CONF
Supply voltage present
"PWR" LED (green)
Burnout detected
"BURN" LED (red)
Alarm A2)
"A" LED (red)
Alarm B 2)
"B" LED (red)
1) Voltage Source Mode, Reference Junction Compensator Option 91, potentiometer and thermocouple TC are not used in
the particular application described by this manual.
2) Note: For SIL applications, alarm contacts must be used in series with equal configuration. Relay contact shown in
de-energized position.
34 ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971)
■PR electronics 9116B1 universal converter relay (programmable)
Layout
Power supply
32-31
31
32
33
34
11
12
13
14
41
42
43
44
51
52
53
54
relay
error
• 32: +24 V DC
• 31: 0 V DC
Status relay in safe area (Not used in the particular
application described by this manual)
33-34
Current output
• 12: +
• 11: -
12-11
Relay output
13-14
Measuring circuit/inputs for RTD, TC, linear resistance,
or potentiometer1)
• 41-43: 3-wire
• 41-44: 4-wire
41-44
Inputs for mA and V (Not used in the particular applica-
tion described by this manual)
51-54
Operation status
Upper LED (green)
Relay status
"relay" LED (yellow)
Malfunction
"error" LED (red)
1) TC, linear resistance and potentiometer are not used in the particular application described by this manual.
■Pt100 relay programming
The Pt100 relays are programmable. You need a dedicated programming tool for the relay.
The programming tools are not included in the delivery. See the technical data for the
ordering information.
Wiring
■Insulation of the sensor circuit
When you connect the temperature sensor(s) of the Ex motor to the drive STO terminals
through a relay, make sure that there is reinforced (double) insulation between the main
circuit (motor) and the drive control unit as required by IEC 61800-5-1. The insulation of the
temperature sensor in the Ex motor and the insulation of the protection relay form the
insulation of the whole circuit. All Ex motors manufactured by ABB have basic insulation
between the main circuit and the temperature sensor. The thermistor relays shown in this
manual have basic insulation between the sensor circuit and relay output. This ensures that
there is double insulation between the main circuit and the drive control unit.
ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971) 35
■General wiring instructions
1.
Install only the sensor circuit into the potentially explosive atmosphere.
The sensor circuit in the Ex Zone must comply with the requirements for the applicable
type of protection, such as:
•
Ex d (EN/IEC 60079-1)
•
Ex eb (EN/IEC 60079-7, Ex e in EN 60079-7:2007 and IEC 60079-7:2006)
•
Ex ec (EN/IEC 60079-7, Ex nA in EN/IEC 60079-15:2010).
2.
Install the drive or inverter unit, including the components of the ATEX-certified motor
thermal protection function, outside the potentially explosive atmosphere.
3.
For the sensor connection, ABB recommends to use shielded twisted-pair cable. This
type of cable decreases electromagnetic interference in the sensor circuit.
4.
Route the sensor cables away from the motor cable. Power cables can cause
electromagnetic interference in the sensor circuit.
5.
Ground all sensor cable shields to a single grounding point outside the potentially
explosive atmosphere. 360-degree grounding of the cable shields is recommended. Do
not connect the cable shields to ground at the sensor end of the cable.
Note: For the motor thermal protection function with Pt100 relays, also the following types
of protection for the sensor circuit are applicable:
•
Ex ib (EN/IEC 60079-11)
•
Ex ic (EN/IEC 60079-11).
If the installation of the sensor circuit does not comply with an applicable type of protection,
obey the installation and wiring requirements for intrinsically safe (Ex i) circuits, as given in
EN/IEC 60079-14 ed. 5, clause 16.
36 ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971)
In this example, contacts of the Pt100 relay(s) are wired to digital input DI6 of the drive
control unit.
1.
Connect the Pt100 sensor(s) of the motor to the relay(s) K71.x (and K72.x, K73.x if
included) to terminal block [X506].
2.
Connect a +24 V DC source via contacts 14 and 13 of the extension relay(s) [A81] (and
[A82], [A83] if included) to digital input DI6 on the drive control unit. The contacts are
wired in series.
3.
With an FSO module (not shown in the figure): If necessary, connect a reset circuit to
an input of the FSO module (for example, DI X113:2).
ZCU/BCU
13
14
13
14
X506
XD24:7
X504
XD24:7
+24VD
13
14
XDI:6
XDI:6
DI6
A81
(A82)
(A83)
Extension relay, stator windings
A81
Extension relay, bearings
A82
Extension relay, stator windings
A83
Additional I/O terminal block (option +L504)
X504
Drive control unit
ZCU/BCU
See the circuit diagrams delivered with the drive for the actual wiring and terminals. For
wiring diagram examples, see chapter Circuit diagrams.
Start-up and acceptance test
Use the Drive composer PC tool or a control panel to do the start-up and acceptance test.
To set FSO module parameters, you must use the Drive composer pro PC tool.
Action
Initial status
Make sure that the drive is ready for use, that is, you have done the tasks of the drive start-up procedure.
See the drive hardware manual.
WARNING!
Obey the Safety instructions (page 9). If you ignore them, injury or death, or damage to the
equipment can occur.
ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971) 37
Checks and settings with no voltage connected
Stop the drive and do the steps in section Electrical safety precautions (page 11) before you start the
work.
Make sure that the classification of the motor thermal protection function corresponds to the Ex classi-
fication of the environment and the Ex motor.
The motor manufacturer selects the Pt100 sensors for the motor temperature measurement. Make
sure that the temperature trip levels match those of the Pt100 relay and set the relay accordingly.
Make sure that the installation of Pt100 sensors complies with the requirements for the applicable type
of protection. See section Wiring (page 35).
Make sure that the wires are connected to the correct terminals and that the terminal connections are
tightened.
Set the trip level of the Pt100 relay. For example, for temperature class T3 the values are:
• 120 … 140 °C when only tripping is used
• alarm 120 … 140 °C and trip 130 … 150 °C when both alarm and trip are used.
Set the temperatures according to the temperature class of the motor.
To modify the settings of the relay, you need a programming tool. See the technical data for ordering
information.
Make sure that the other settings of the relay are correct.
Settings with voltage connected
If necessary, set the applicable parameters. See chapter Parameter settings (page 41).
If necessary, configure the motor overtemperature indication message. See section Motor overtemper-
ature indication (page 42).
Acceptance test procedure
To do a test of the wire break monitoring, disconnect the sensor circuit.
Expected outcome: Fault trip (the applicable LED lights). Drive STO is activated.
Make sure that the correct indications are activated.
With the relay(s) both in tripped and in reset state, try to start the drive.
The drive must not start before the drive (and FSO) faults are reset.
Fill in and sign the acceptance test report which verifies that the safety function is safe and accepted
to operation.
Maintenance
After the operation of the safety circuit has been verified at start-up, the circuit requires a
periodic proof test at least every two years.
If you change any wirings or components related to the motor thermal protection function
after the start-up, repeat the procedure given in section Start-up and acceptance
test (page 37).
Fault tracing
For the warning and fault messages generated by the drive, see the drive firmware manual.
For the fault indication LEDs of the relays, see section Pt100 relays (page 34).
For the status LEDs of the FSO module, see the FSO module user’s manual.
38 ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971)
Safety data and block diagrams
The safety block diagrams show the components that are included in the safety data
calculations.
■Without an FSO module
1
2
3
4
Customer motor Pt100 sensor(s)
1
Pt100 relay(s)
2
• K71.1…3
• (K72.1…2)
• (K73.1…3)
Extension relay(s)
3
• A81
• (A82)
• (A83)
Drive STO
4
PFDavg (3, 5, or 8 relays)
T1
HFT
SIL
9.74E-4
2 years
0
1
3AXD10000331763 E
ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971) 39
■With an FSO module
1
2
3
4
5
Customer motor Pt100 sensor(s)
1
Pt100 relay(s)
2
• K71.1…3
• (K72.1…2)
• (K73.1…3)
Extension relay(s)
3
• A81
• (A82)
• (A83)
FSO module
FSE module (optional)1)
4
Drive STO
5
1) The FSE module is included in the calculations only if
• a safety encoder is used in the application, and
• the FSO-21 module is configured to activate the SS1 function (stop category 1) in overtemperature situations, and
• the ramp monitoring method is used in the SS1 function.
PFDavg (3, 5, or 8 relays)
T1
HFT
SIL
1.16E-3
2 years
0
1
3AXD10000331763 E
40 ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971)
Contents of this chapter
This chapter lists the parameters that you have to set for the ATEX-certified motor thermal
protection functions in this manual.
WARNING!
If there is missing or inaccurate information, do not operate the motor before you
have made sure that the parameter settings are correct.
Drive / inverter
■Switching frequency limitation
The certificate of the Ex motor typically requires that you set a minimum limit for the switching
frequency of the drive.
For ABB Ex motors, use parameter 95.15 to set the required minimum switching frequency.
For more information, see the drive firmware manual.
For Ex motors supplied by other motor manufacturers, contact the motor manufacturer for
the correct value and your local ABB representative for instructions on how to make the
parameter setting in the drive.
■Reset method and status indications
To configure a manual reset for the temperature protection function in the drive, you can
set either the STO indication (parameter 31.22 STO indication run/stop) or the motor
temperature indication so that it generates a fault.
31.22 STO indication run/stop
Set this parameter to value Fault/Fault or Fault/Warning.
5
Parameter settings 41
Fault/Fault: This generates a fault in the drive/inverter unit when STO is activated.
•
Fault/Warning: This generates a fault in the drive/inverter unit when the drive is running
and warning when the drive is stopped.
When the drive/inverter unit generates a fault indication because of STO activation, you
must reset the drive/inverter unit before you can restart the drive.
Note: You can also configure the FSO module so that it sends a fault to the drive each time
it activates the drive STO function. See parameter FSOGEN.61.
The default values set for the options at the factory:
•
option +L513+Q971 (PTC relays, with or without an FSO module): Warning/Warning
•
option +L514+Q971 (Pt100 relays, with or without an FSO module): Fault/Fault.
Motor overtemperature indication
There are two ways to configure the motor overtemperature indication.
Example 1
The ACS880 primary control program has two separate temperature monitoring functions.
In this example, one of these functions (External event 1) is configured to monitor digital
input DI6. When off (0), the function triggers the user-selected indication and shows the
user-defined message. To configure the motor overtemperature indication in the drive:
1.
Select the digital input which shows the status of the external event: set parameter
31.01 External event 1 source to DI6. You can also use another digital input.
2.
Select the type of the External event 1: set parameter 31.02 External event 1 type to
Fault, Warning or Warning/Fault. If you set this parameter to Fault, the drive trips due
to overtemperature and you must reset the drive with a manual reset command before
you can restart the drive.
3.
If necessary, edit the indication message. You can use the control panel or Drive
composer PC tool to edit messages.
Example 2
In this example, the motor temperature is read from digital input DI6.
1.
Select PTC DI6 as the source of the temperature with parameter 35.11 Temperature 1
source. Use the same setting also with Pt100 sensors.
2.
By default, an excessive temperature will generate a warning. If you want a fault instead,
set parameter 35.12 Temperature 1 fault limit to 4000 ohm.
3.
If necessary, edit the indication message. You can use the control panel or Drive
composer PC tool to edit messages.
For more information, see ACS880 primary control program firmware manual
(3AUA0000085967 [English]).
31.11 Fault reset selection
Select the correct source of an external fault reset signal with parameter 31.11 Fault reset
selection.
■Other recommended settings
ABB recommends that you also set these parameters to improve the safety of the application:
•
minimum and maximum speeds (parameter group 30)
•
maximum current, power and torque (group 30)
•
acceleration and deceleration times
42 Parameter settings
stall protection (parameters 31.24…31.28)
•
motor load curve (parameters 35.50…35.55)
•
motor cable protection (parameters 35.60…35.62)
For more information, see the drive firmware manual.
FSO module
If you use an FSO module (option +Q972 or +Q973) in the safety system configuration, set
the parameters according to the system requirements. Example values are shown in this
section.
You need the Drive composer pro PC tool to set the FSO module parameters. You also
need a password to be able to download the configuration to the FSO module from Drive
composer pro. For the default password of the FSO module, see the applicable FSO module
user’s manual. For more information on the Drive composer pro PC tool, see Drive composer
start-up and maintenance PC tool user's manual (3AUA0000094606 [English]).
Follow the configuration steps described in the applicable FSO module user’s manual,
chapter Configuration.
There are parameters that you must always set when you use the FSO module, and
parameters that are related only to some safety functions. These tables list the parameters
that are relevant to the options +L513+Q971+Q973/Q972 and +L514+Q971+Q973/Q972.
The example values are applicable only to these options.
You can use the FSO-21 module (+Q972) also with a safety pulse encoder and the FSE-31
pulse encoder interface module (+L521). If you do, set the parameters listed in section FSE
module and safety pulse encoder parameters (page 50).
You can configure the FSO module so that it opens the drive or inverter STO circuit
immediately (STO function in the FSO module, stop category 0) or after a deceleration ramp
(SS1 function in the FSO module, stop category 1). For the options described in this manual,
ABB has configured the FSO module so that it activates the STO function (stop category
0). Select the stop category according to the system risk assessment. Do not configure the
STO function and the SS1 function to the same input at the same time.
Note: Setting parameters related to STO and SS1 can also have an effect on other safety
functions. You must take all safety functions into consideration when you configure the FSO
module. See the applicable FSO module user’s manual and safety option user's manual.
Note: The factory reset of the FSO module clears the configuration and sets the parameters
to the factory default values. These values are not the same as the pre-set values in an
FSO module that was ordered as an option (with a plus code). You cannot restart the drive
with the factory default values. If you do a factory reset of the FSO module, you must
reconfigure the FSO module and set the applicable parameters. See the applicable FSO
module user's manual.
Parameter settings 43
These parameters are common to all safety functions in the FSO module.
Description
Example value
Name
Index
Sets the digital output that indicates the completion of
any stop function. Active when the FSO module has
completed the STO, SSE or SS1 function.
None
Stop completed out-
put
FSOGEN.11
ACS880-07/17/37 and ACS880-17LC/37LC drives with
the option +Q978 or +Q979: ABB has configured the
emergency stop indication lamp to this digital output at
the factory. Make sure that this value corresponds to
the actual wiring. See the circuit diagrams of the deliv-
ery. Do not change this setting.
Sets the nominal motor speed. Adjust the default value
to meet the ratings of the motor in use.
1500.0 rpm
Motor nominal speed
FSOGEN.21
Sets the nominal motor frequency. Adjust the default
value to meet the ratings of the motor in use.
50.00 Hz
Motor nominal fre-
quency
FSOGEN.22
Sets the power-up acknowledgement method of the
FSO module.
Automatic
Power-up acknow-
ledgement
FSOGEN.41
Automatic: You do not need to push a reset button after
switching on the FSO module. The FSO module gener-
ates the acknowledgement signal automatically after
the power-up.
Manual: The FSO module reads the external acknow-
ledgement signal through the digital input defined by
parameter FSOGEN.42.
Make sure that the value is Automatic.
Sets the digital input for the acknowledgement signal
when parameter STO.02 has value Manual.
None
Acknowledgement
button input
FSOGEN.42
None: In the safety functions described in this manual,
parameter STO.02 has value Automatic and this para-
meter has value None (no acknowledgement signal
connected).
In the safety functions described in this manual, you
can use this parameter to implement manual reset in
the FSO module. Set the digital input which the reset
circuit is connected to with this parameter.
ACS880-07/17/37 and ACS880-17LC/37LC drives with
the option +Q978 or +Q979: The value of this parameter
is DI X113:2. A reset circuit is connected to the FSO
module and the user must reset the safety function with
the emergency stop reset button also when motor
overtemperature is reached. Do not change this setting.
Sets the general zero speed limit for safety functions
when no safety encoder is in use.
90.0 rpm
Zero speed without
encoder
FSOGEN.51
STO function: The value has no effect.
SS1 function: The FSO module activates the drive STO
function when the drive has decelerated the motor
speed below this value. Adjust the default value accord-
ing to application requirements.
ACS880-07/17/37 and ACS880-17LC/37LC drives with
the option +Q978: Also the main contactor/breaker is
opened.
44 Parameter settings
Sets the general zero speed limit for safety functions
when a safety encoder is in use.
0.0 rpm
Zero speed with en-
coder
FSOGEN.52
STO function: The drive STO function is active (cannot
be reset) until the motor speed is less than or equal to
this value.
SS1 function: The FSO module activates the drive STO
function when the drive has decelerated the motor
speed to less than this value. Adjust the default value
according to application requirements.
ACS880-07/17/37 and ACS880-17LC/37LC drives with
the option +Q978: Also the main contactor/breaker is
opened.
Note: This parameter is used only with FSO-21 and
when a safety encoder is used in the application.
Sets the type of the event that the FSO module gener-
ates and sends to the drive after external requests that
end to a successful activation of the drive STO function
(STO, SSE or SS1).
Warning
STO indication ext
request
FSOGEN.61
None, Warning, Event: You do not have to reset the
drive/inverter unit.
Fault: You have to reset the drive/inverter unit.
In the safety functions described in this manual, you
can use this indication as the motor overtemperature
indication message and to implement a manual reset.
Adjust the default value when necessary.
Sets the type of the event that the FSO module gener-
ates and sends to the drive for limit hits during ramp
and time monitoring of safety ramps SAR0 and SAR1.
Fault
STO indication safety
limit
FSOGEN.62
STO function: The value has no effect.
SS1 function: When the motor speed does not follow
the stop ramp or the time limit is exceeded, the FSO
module activates the STO function and generates this
user-defined indication. Adjust the default setting if ne-
cessary. If you select Fault, you must reset the drive
before you can restart it.
Parameter settings 45
■Parameters for the STO function
These parameters are related to the STO function of the FSO module. With stop category
0, the FSO module activates the STO function in overtemperature situations. Also, the FSO
module can activate the STO function in fault situations.
Description
Example value
Name
Index
Sets the acknowledgement method used in the STO,
SSE and SS1 functions.
Automatic
STO acknowledge-
ment
STO.02
Automatic: The FSO module resets the STO function
automatically after the STO request is removed.
Manual: The FSO module reads the external acknow-
ledgement signal through the digital input defined by
parameter FSOGEN.42. In the safety functions de-
scribed in this manual, you can use this setting to im-
plement a manual reset for the motor temperature
protection function in the FSO module.
ACS880-07/17/37 and ACS880-17LC/37LC drives with
the option +Q978 or +Q979: The FSO module is con-
figured so that after the safety function activation, the
user must reset the FSO manually with the emergency
stop reset button (this parameter is set to Manual). In
this case, the user must reset the FSO module with the
emergency stop reset button also when motor overtem-
perature is reached. Do not change this setting.
Sets the digital input that is connected to the primary
input of the STO function.
None
STO input A
STO.11
In the safety functions described in this manual, this
parameter has value None.
ACS880-07/17/37 and ACS880-17LC/37LC drives with
the option +Q978 or +Q979: ABB has connected the
emergency stop button to this digital input at the factory.
Make sure that the setting corresponds to the circuit
diagrams of the delivery.
ACS880 multidrives with the option +Q979: ABB has
connected the emergency stop safety relay to this digital
input at the factory. Make sure that the setting corres-
ponds to the circuit diagrams of the delivery.
Sets the digital input that is connected to the secondary
input of the STO function.
STO: DI X113:4
SS1: None
STO input B
STO.12
For the safety functions described in this manual, ABB
has configured the contacts of the PTC/Pt100 relay to
this digital input at the factory. Make sure that the set-
ting corresponds to the circuit diagrams of the delivery.
If you set this parameter to DI X113:4, set parameter
SS1.12 to None.
Sets the time after which the drive can restart when the
FSO module has activated the STO function and
opened the drive STO circuit. With this parameter, you
can let the drive restart before the motor has stopped
(fly-start). This parameter is applicable only if the STO
function is requested from STO input A (STO.11) or
STO input B (STO.12).
2000 ms
Restart delay after
STO
STO.13
STO function: Adjust the value when necessary. If you
do not want to use the fly-start feature, set this paramet-
er to the same value as parameter STO.14.
SS1 function: This value has no effect.
46 Parameter settings
Sets the time that is needed to coast the motor to a
standstill from maximum process speed. If this time is
not known, it can be measured with Drive composer
pro PC tool when an encoder is used for motor control
(otherwise you have to make sure that the motor shaft
has stopped rotating by other means, eg, visually).
2000 ms
Time to zero speed
with STO and modoff
STO.14
Acknowledgement is allowed after coast stop in the
STO, SSE and SS1 functions (when SBC is not used).
If the drive STO is activated or modulation stopped
while a monitoring safety function is indicating “unsafe”,
after this time acknowledgement is allowed. For ex-
ample, if the drive modulation is lost during SLS decel-
eration ramp, SLS OK will be indicated after this time
has elapsed.
STO function: This parameter sets the time after which
the STO function is completed and the STO completed
indication goes on. Parameter STO.13 defines the time
after which the acknowledgement is allowed. Adjust
the value according to application requirements.
SS1 function: This parameter is used only when the
motor speed does not follow the ramp settings or the
time monitoring limit is exceeded and the FSO module
activates the STO function. Adjust the value according
to application requirements.
When an encoder is used: This parameter is relevant
only if there is an encoder failure and the FSO module
activates the STO function.
SBC usage
Sets how the mechanical brake is used together with
the STO function.
None
STO SBC usage
SBC.11
In the safety functions described in this manual, this
feature is not used and this parameter has value None.
ACS880-07/17/37 and ACS880-17LC/37LC drives with
the option +Q978: The SBC function is used in the
emergency stop implementation to control the auxiliary
safety relay(s) which is connected to the main contact-
or/breaker. Make sure that the value is Delayed brake.
■Parameters for the SSE function
These parameters are related to the Safe stop emergency (SSE) function of the FSO module.
The safety functions described in this manual do not use this function, but the FSO module
can activate the SSE function in internal fault situations.
Description
Example value
Name
Index
Sets the type of the SSE function.
Immediate STO
SSE function
SSE.13
Immediate STO: The FSO module activates the drive
STO function immediately after the SSE request (stop
category 0).
Emergency ramp: The FSO module first ramps down
the motor speed and when the speed is below the zero
speed limit (parameter FSOGEN.51 or FSOGEN.52) it
activates the STO function (stop category 1). SAR0
parameters define the deceleration ramp (for more
information, see the FSO module user’s manual).
For the safety functions described in this manual, ABB
has set this parameter to value Immediate STO at the
factory. Adjust the default value when necessary.
Parameter settings 47
Sets the absolute speed below which the FSO module
activates the brake (SBC) while ramping.
0.0 rpm
SSE/SS1 SBC speed
SBC.15
0.0 rpm: The feature is not in use.
In the safety functions described in this manual, this
feature is not used. Make sure that the value is 0.0 rpm.
■Parameters for the SS1 function
Set these parameters only if you want that the FSO module activates the SS1 function in
overtemperature situations (stop category 1).
Description
Example value
Name
Index
Activates or deactivates the SS1 function and shows
the version of the SS1 function.
Version 1
SS1 activity and ver-
sion
SS1.01
Version 1: Activates version 1 of the SS1 function. For
more information, see the FSO module user’s manual.
Sets the digital input that is connected to the primary
input of the SS1 function.
None
SS1 input A
SS1.11
Sets the digital input that is connected to the secondary
input of the SS1 function.
STO: None
SS1: DI X113:4
SS1 input B
SS1.12
If you set this parameter to DI X113:4, set parameter
STO.12 to None.
Sets the method used for the SS1 monitoring. Adjust
the default value when necessary.
SS1-r
SS1 type
SS1.13
Time monitoring (SS1-t): The FSO module monitors
that a user-defined deceleration time limit is not ex-
ceeded. (See parameter SS1.14.)
Ramp monitoring (SS1-r): The FSO module monitors
that the motor decelerates along a user-defined stop
ramp. (See SAR1 ramp parameters 200.112, SARx.21,
SARx.22 and SARx.02.)
Sets the monitoring delay after which the FSO module
activates the drive STO and SBC at the latest, if the
motor speed has not gone below the zero speed limit
(parameter FSOGEN.51 or FSOGEN.52) yet.
20000 ms
SS1-t delay for STO
SS1.14
Time monitoring: This value sets the security delay that
the FSO module monitors. Adjust the default value
when necessary.
Ramp monitoring: This value has no effect in the oper-
ation.
SAR1 ramp settings
Sets the target time for the stop ramp SAR1 that is used
in the SS1 and function. Adjust the default value when
necessary.
2000 ms
SAR1 ramp time to
zero
200.112
The target time is the time in which the drive deceler-
ates the motor from the speed defined by parameter
200.202 to zero.
Note: With value 0 ms, the drive uses the emergency
stop ramp set by drive parameter 23.23 (see section
SS1 ramp parameters in the drive/inverter
unit (page 50)). Also in this case, the FSO module only
monitors the actual ramp (ramp monitoring or time
monitoring).
48 Parameter settings
Sets a speed value that the FSO module uses as a
reference point in ramp parameter calculations (see
SAR1 ramp parameters 200.112, SARx.21, SARx.22
and SARx.02.). Adjust the default value when neces-
sary.
1500 rpm
SAR speed scaling
200.202
Sets the initial allowed range for the SAR0/SAR1 ramp.
This parameter moves the location of the maximum
monitoring ramp forward on the time axis, when monit-
oring is started. The slope of the ramp stays the same
as defined with parameters 200.202 and SARx.22. For
more information, see the FSO module user’s manual.
100 ms
SAR initial allowed
range
SARx.02
Time monitoring: This value has no effect in the opera-
tion.
Ramp monitoring: Adjust the default value when neces-
sary.
Sets the minimum ramp time for the SAR1 ramp monit-
oring.
1000 ms
SAR1 min ramp time
to zero
SARx.21
Time monitoring: This value has no effect in the opera-
tion.
Ramp monitoring: Sets the minimum stop ramp time
for the emergency stop. Adjust the default value when
necessary.
Note: With value 0 ms, the minimum ramp is not mon-
itored.
Sets the maximum ramp time for the SAR1 ramp
monitoring.
3000 ms
SAR1 max ramp time
to zero
SARx.22
Time monitoring: This value has no effect in the opera-
tion.
Ramp monitoring: Sets the maximum stop ramp time
for the emergency stop. Adjust the default value when
necessary.
SBC usage
Sets the absolute speed below which the FSO module
activates the brake (SBC) while ramping.
0.0 rpm
SSE/SS1 SBC speed
SBC.15
0.0 rpm: The feature is not in use.
In the safety functions described in this manual, this
feature is not used. Make sure that the value is 0.0 rpm.
In addition to the parameters related to the SS1 function, set these parameters.
Value with the SS1 function
Pre-set value
(STO function)
Name
Index
None
DI X113:4
STO input B
STO.12
If you do not use a safety encoder, adjust the default
value to meet the motor in use.
90.0 rpm
Zero speed without
encoder
FSOGEN.51
If you use a safety encoder, adjust the default value to
meet the motor in use.
0.0 rpm
Zero speed with
encoder
FSOGEN.52
Adjust the default value when necessary.
Fault
STO indication safety
limit
FSOGEN.62
Parameter settings 49
SS1 ramp parameters in the drive/inverter unit
Set these parameters only for the SS1 function.
If FSO parameter 200.112 is set to 0 ms, drive parameters define the stop ramp that is used
in the SS1 function:
•
21.04 Emergency stop mode is set to value Eme ramp stop (Off3)
•
23.23 Emergency stop time is set to a suitable value.
Also in this case, the FSO module monitors the actual stop ramp (ramp monitoring or time
monitoring). For more information, see the drive firmware manual and FSO module user's
manual.
■FSE module and safety pulse encoder parameters
Set these parameters only when you use a safety pulse encoder and the FSE-31 pulse
encoder interface module with the FSO-21 module.
Description
Example value
Name
Index
Activates the FSE-31 encoder interface and shows the
version of the encoder parameter groups (91 and 92).
Version 1
FSE 3X act and par
version
200.231
Shows the number of safety pulse encoders connected
to the FSE module.
Single encoder
CH1
Number of encoders
200.232
Activates the safety pulse encoder and shows the ver-
sion parameter group S_ENCGEN.
Version 1
Safe pulse encoder
version
S_ENCGEN.01
Sets the action taken when there is a problem with the
FSE module.
STO
FSE diagnostic fail-
ure reaction
S_ENCGEN.11
STO: The FSO module goes into the Fail-safe mode
and activates the drive STO function.
Note: This parameter is relevant only when there are
no active safety functions.
Sets the encoder speed cross comparison tolerance.
This defines how much the axle speed of the motor can
change within 1 ms.
1.0 rpm
Enc speed cross
comp tolerance
S_ENCGEN.14
Adjust the default value to meet the motor in use.
This parameter is used for the encoder diagnostic. It
defines the maximum difference between the speed
information from channel A and B of the encoder. If the
difference of these two values is more than defined by
this parameter, FSO will safely stop the system (STO).
The suitable value depends on the configuration (motor
and load). Typically this value is between 2 … 10 rpm.
A value that is too small will cause an encoder fault
(A7D8). A value that is too big will prevent the encoder
diagnostic related to this parameter.
Sets the rotation direction for the safety pulse encoder.
1
Gear numerator en-
coder 1
S_ENCGEN.41
With this parameter, you can change the rotation direc-
tion of the motor. Adjust the default value if necessary.
Sets the type of the safety pulse encoder interface
module 1.
FSE-31
Module 1 type
91.11
Sets the slot in which the safety pulse encoder interface
module 1 is located.
2
Module 1 location
91.12
Activates or deactivates the communication with the
safety pulse encoder interface module 1 and sets the
type for the safety pulse encoder.
HTL1
Encoder 1 type
92.01
50 Parameter settings
Sets the safety pulse encoder interface module that
the safety pulse encoder 1 is connected to.
Module 1
Encoder 1 source
92.02
Sets the number of HTL pulses per revolution for safety
pulse encoder 1.
2048
Pulses/revolution
92.10
Adjust the default value to meet the safety pulse en-
coder in use. Make sure that the value is according to
the encoder nameplate.
Sets the maximum pulse frequency range of encoder
1. Adjust the default value to meet the motor and safety
pulse encoder in use. You can use this formula to define
the value: r_max · ppr_enc + 10%, where
300 kHz
Accepted pulse freq
of encoder 1
92.17
• r_max: the maximum motor speed (rpm) used in the
application (or the motor nominal speed)
• ppr_enc: pulses/revolution of the safety pulse en-
coder (parameter 92.10).
■Notes
ACS880-07/17/37 and ACS880-17LC/37LC drives with option +Q978: In motor
overtemperature situations, the FSO module also opens the main contactor/circuit breaker.
ACS880-07/17/37 and ACS880-17LC/37LC drives with option +Q978 or +Q979: The FSO
module is configured so that after the safety function activation, the user must reset the
FSO module manually with the emergency stop reset button. The user must also reset the
FSO module with the emergency stop reset button after motor overtemperature situations.
The indication lamp on the reset button is on. Do not change this setting.
Mechanical brake control
If you use a mechanical brake with the motor thermal protection circuit, pay special attention
to the control of the mechanical brake.
If the motor deceleration by the mechanical brake causes extra heat generation in the Ex
zone, make sure that the use of the brake does not increase the temperature too much. In
this case, make sure that the mechanical brake is activated only at zero speed (see
parameters SBC.11, SBC.15 and FSOGEN.51 or FSOGEN.52).
In some cases you cannot use the brake for the motor deceleration when the motor thermal
protection circuit has tripped and the motor temperature is too high.
For more information, see the drive firmware manual (or the FSO module user’s manual if
you use the Safe brake control (SBC) function of the FSO module).
Parameter settings 51
Contents of this chapter
This chapter contains the technical specifications of the protection functions. It also gives
general rules, notes and definitions related to safety functions and lists related standards.
The ATEX compliance markings and certificates are also included.
The ATEX-certified motor thermal protection functions
Response time: < 200 ms
PTC thermistor relays
■ABB CM-MSS.41
Ordering information
1SVR740712R1200
CM-MSS.41P (Push-in
terminals)
Part number
1SVR730712R1200
CM-MSS.41S (Screw
terminals)
Power supply A1-A2
24 … 240 V AC/DC
Rated control supply voltage Us
-15 … +10%
Rated control supply voltage Us tolerance
15 … 400 Hz
Rated frequency
33 mA / 0.55 VA
24 V AC/DC
Typical current / power
consumption
11 mA / 1.6 VA
220 … 240 V AC
yes
Electrical insulation between supply circuit and
measuring circuit
20 ms
Power failure buffering time
6
Technical data 53
Measuring circuit / Sensor circuit T1-T2
PTC type A (DIN/EN 44081, DIN/EN 44082)
Sensor type
1
Number of sensor circuits
< 750 ohm
Max. total resistance of sensors connected in series,
cold state
2.83 kohm ± 1%
Switch-off resistance
(relays de-energize)
Overtemperature
monitoring
1.1 kohm ± 1%
Switch-on resistance
(relays energize)
< 12 ohm
Switch-off resistance
(relays de-energize)
Short-circuit detection
> 19 ohm
Switch-on resistance
(relays energize)
dynamic
Switch-off resistance
(relays de-energize)
Interrupted wire detection
not available
Switch-on resistance
(relays energize)
configurable
Non-volatile fault storage
yes
Test function
2.5 V
1.33 kohm
Maximum voltage in sensor
circuit
3.7 V
4 kohm
5.5 V
∞kohm
3.7 mA
Maximum current in sensor circuit
2 × 100 m at 0.75 mm2
Maximum sensor cable length
2 × 400 m at 2.5 mm2
0.50%
Accuracy within the rated control supply voltage
tolerance
0.01%/K
Accuracy within the temperature range
on request
Repeat accuracy (constant parameters)
< 100 ms
Reaction time of the safety function
0
Hardware fault tolerance (HFT)
Control circuit S1-T2
yes
Manual reset
Control function
adjustable
Auto reset
adjustable
Remote reset
5.5 V
Maximum no-load voltage (S1-T2 open)
0.6 mA
Max. current (S1-T2 jumpered)
2 × 100 m at 0.75 mm2
Maximum cable length
2 × 400 m at 2.5 mm2
Indication of operational states
"U" LED (green)
Control supply voltage
"R" LED (yellow)
Relay status
"F" LED (red)
Fault message
Operating controls
front-face button
Test / Reset
54 Technical data
non-volatile fault storage
DIP switch 1
Configuration of
short-circuit detection
DIP switch 2
disabled
DIP switch 3
Remote Test/Reset
DIP switch 4
Output circuit
Relay, 1st c/o (SPDT) contact
11-12/14
Kind of output
Relay, 2nd c/o (SPDT) contact
21-22/24
closed-circuit principle
Operating principle
AgNi alloy, Cd free
Contact material
24 V / 10 mA
Minimum switching voltage / Minimum switching current
See the relay data sheet.
Maximum switching voltage / Maximum switching
current
4 A
AC-12 (resistive) at 230 V
Rated operational voltage
Ue and rated operational
current Ie
3 A
AC-15 (inductive) at 230 V
4 A
DC-12 (resistive) at 24 V
2 A
DC-13 (inductive) at 24 V
B 300
Utilization category
(Control Circuit Rating
Code)
AC Rating (UL 508)
300 V AC
Maximum rated operational
voltage
5 A
Maximum continuous
thermal current at B 300
3600/360 VA
Maximum making/breaking
apparent power at B 300
250 V AC - 4 A
General purpose rating
30 x 106 switching cycles
Mechanical lifetime
0.1 x 106 switching cycles
Electrical lifetime at AC-12, 230 V AC, 4 A
10 A fast-acting
N/C contact
Maximum fuse rating to
achieve short-circuit
protection
10 A fast-acting
N/O contact
General data
100%
Duty cycle
85.6 × 22.5 × 103.7 mm (3.37 × 0.89 × 4.08 in)
Dimensions (Height × Width × Depth)
0.141 kg
Screw connection
technology
Weight, net
0.130 kg
Easy Connect Technology
(push-in)
DIN rail (IEC/EN 60715), snap-on mounting without any
tool
Mounting
10 mm (0.39 in) if switching current > 2 A
Vertical
Minimum distance to other
units
10 mm (0.39 in) if switching current > 2 A
Horizontal
UL 94 V-0
Material of housing
IP50
Housing
Degree of protection
IP20
Terminals
Technical data 55
Fine-strand with(out) wire
end ferrule
Connecting capacity
• 1 × 0.5 … 2.5 mm2 (1 × 18 … 14 AWG)
• 2 × 0.5 … 1.5 mm2 (2 × 18 … 16 AWG)
Easy Connect Technology (push-in):
• 2 × 0.5 … 1.5 mm2 (2 × 18 … 16 AWG)
Screw connection:
Rigid
• 1 × 0.5 … 4.0 mm2 (1 × 20 … 12 AWG)
• 2 × 0.5 … 2.5 mm2 (2 × 20 … 14 AWG)
Easy Connect Technology (push-in):
• 2 × 0.5 … 1.5 mm2 (2 × 20 … 16 AWG)
8 mm (0.32 in)
Stripping length
0.6 … 0.8 Nm (7.08 lbf·in)
Tightening torque
Environmental data
-25 °C … +60 °C (-13 °F … +140 °F)
Operation
Ambient temperature
ranges
-40 °C … +85 °C (-40 °F … +185 °F)
Storage
6 x 24 h cycle, 55 °C, 95 % RH
Damp heat, cyclic (IEC/EN 60068-2-30)
3K5 (no condensation, no ice formation)
Climatic class (IEC/EN 60721-3-3)
5-13.2 Hz: w1 mm; 13.2-100 Hz: 0.7 g
Vibration, sinusoidal
10 g / 11 ms
Shock
Approvals
ATEX Ex II (2) G D
Isolation data
300 V AC
Supply circuit / Measuring
circuit1)
Rated insulation voltage Ui
300 V AC
Supply circuit / Output
circuits
300 V AC
Measuring circuit1) /
Output circuits
300 V AC
Output circuit 1 / Output
circuit 2
4 kV
Supply circuit / Measuring
circuit1)
Rated impulse withstand
voltage Uimp
4 kV
Supply circuit / Output
circuits
4 kV
Measuring circuit1) /
Output circuits
4 kV
Output circuit 1 / Output
circuit 2
600 V AC
Supply circuit / Measuring
circuit1)
Basic insulation
600 V AC
Supply circuit / Output
circuits
600 V AC
Measuring circuit1) /
Output circuits
300 V AC
Output circuit 1 / Output
circuit 2
56 Technical data
yes, up to 300 V AC
Supply circuit / Measuring
circuit1)
Protective separation
(IEC/EN 61140, EN 50178)
yes
Supply circuit / Output
circuits
yes
Measuring circuit1) /
Output circuits
no
Output circuit 1 / Output
circuit 2
3
Pollution degree
III
Overvoltage category
1) Potential of measuring circuit = Potential of control circuit
For the complete relay technical data, see the CM-MSS.41 data sheet (2CDC112216D0201
[English]), available at library.abb.com.
■DOLD MK 9163N.12/110-ATEX
Ordering information
0056901
Part number
Power supply A1-A2
24 V AC/DC
Rated voltage
AC 0.8 … 1.1 U
Voltage range
DC 0.9 … 1.25 UH
at 10% residual ripple
DC 0.8 … 1.1 UH
at 48% residual ripple
1.5 VA
AC
Nominal consumption
0.85 W
DC
50 / 60 Hz
Nominal frequency
45 … 65 Hz
Frequency range
20 ms
Max. bridging time on failure of aux. supply
< 40 ms
Operate delay
< 100 ms
Release delay
Measuring circuit P1-P2
3.2 … 3.8 kohm
Response value
1.5 … 1.8 kohm
Release value
> 3.8 kohm
Broken wire detection
< 20 ohm
Short-circuit on measuring circuit
< 5 mW (R = 1.5 kohm)
Loading of measuring circuit
≤2 V (R = 1.5 kohm)
Measuring voltage
2 × 550 m
4 mm2
Maximum wire length
2 × 250 m
2.5 mm2
2 × 150 m
1.5 mm2
2 × 50 m
0.5 mm2
Reset circuit X1-X2
External remote reset X1-X2 with NO contact (voltage
free)
Function
Technical data 57
This input is not galvanic separated from measuring
input P1-P2
Remark
Output contacts
2 changeover contacts
Contacts
5 A
Thermal current Ith
3 A / AC 230 V
to AC 15
Switching capacity
(IEC/EN 60947-5-1)
2 A / DC 24 V
to DC 13
1.5 × 106 switching cycles
Electrical life at 4 A, 230 V AC, cos phi = 0.6
max. fuse rating: 6 A gG / gL
NC contact
Short-circuit strength
(IEC/EN 60947-5-1)
max. fuse rating: 10 A gG / gL
NO contact
≥30 × 106 switching cycles
Mechanical life
Terminals
1 × 0.5 … 2.5 mm2 (2 × 20 … 14 AWG)
Stranded ferruled
Wire size
2 × 0.5 … 1.5 mm2 (2 × 20 … 16 AWG)
1 × 0.5 … 4 mm2 (1 × 20 … 12 AWG)
Solid
2 × 0.5 … 2.5 mm2 (2 × 20 … 14 AWG)
Max. 0.8 Nm (7 lbf·in)
Tightening torque
Indicators
on, when auxiliary supply connected
Green LED
on, when overtemperature or broken wire, short circuit
is detected
Red LED
General data
Continuous operation
Operating mode
-20 °C … +60 °C (-4 °F … +140 °F)
Operation
Temperature range
-20 °C … +60 °C (-4 °F … +140 °F)
Storage
< 2000 m
Altitude
Limit value class B
Interference suppressions
EMC (EN 55011)
IP40
Housing
Degree of protection
(IEC/EN 60529)
IP20
Terminals
Thermoplastic with V0-behavior according to UL subject
94
Housing
20 / 060 / 04
Climate resistance (IEC/EN 60068-1)
Amplitude 0.2 mm, frequency 10 … 55 Hz
Vibration resistance (IEC/EN 60068-2-6)
DIN rail
Mounting (IEC/EN 60715)
160 g
Weight
22.5 × 90 × 102 mm
Dimensions
Approvals
ATEX Ex II (2) G D
Isolation data
Note: The supply and measurement circuits are not electrically isolated. Use a dedicated power supply for the
PTC relay(s).
4 kV
Rated impulse withstand voltage between all isolated
circuits
2
Pollution degree
58 Technical data
For the complete relay technical data, see www.dold.com.
Pt100 relays
■GM International D1073S
Ordering information
D1073S
Model
GM Pocket Portable Configurator PPC1090, or RS-232
serial line with PPC1092 Adapter and SWC1090
Configurator software (recommended).
Programming tool (not included in the ABB delivery)
Power supply (terminals 3-4)
24 V DC reverse polarity protected
Rated voltage
20 … 30 V DC
Voltage range
2.1 W at 30 V supply voltage, overload condition, relays
energized and PPC1090 connected
Maximum power consumption
Measuring circuit (terminals 13-16)
3-4 wire RTD Pt100 (for other alternatives, see the relay
data sheet)
Sensor type
500 ms
Integration time
5 μV on mV, 20 mohm on RTD, 0.05% on transmitting
potentiometer
Resolution
0.1 °C on temperature, 10 μV on mV, 0.1% on
potentiometer
Visualization
within rated limits of sensor (-10 mV … +80 mV).
Input range
≤0.5 mA
Measuring RTD current
≤10 ohm
RTD line resistance compensation
-5 ohm … +20 ohm, programmable
RTD line resistance error compensation
Current output (terminals 1-2)
0/4 … 20 mA, on max. 600 ohm load source mode,
current limited at 22 mA
Signal range (span)
2 μA current output or 1 mV voltage output
Resolution
linear or reverse
Transfer characteristic
≤50 ms (10…90% step change)
Response time
≤20 mVrms on 250 ohm load
Output ripple
Output contacts (terminals 5-8)
Two SPST relay contacts
Number of contacts
0 … 5 °C for temperature sensor input, 0 … 50 mV for
mV input, 0 … 50% for potentiometer input (see input
for step resolution).
Hysteresis
0 … 1000 s, 100 ms step, separate setting
ON-OFF delay time
2 A / 250 V AC / 500 VA
Contact rating
2 A / 250 V DC / 80 W (resistive load)
Performance
Ref. Conditions 24 V supply, 250 ohm load, 23 ±1 °C surrounding air temperature
Technical data 59
≤± 40 μV on mV or thermocouple, 200 mohm on RTD,
0.2% on potentiometer or ± 0.05% of input value
Calibration and linearity
accuracy
Input
≤± 2 μV, 20 mohm, 0.02% or ± 0.01% of input value
for a 1 °C change.
Temperature influence
≤± 0.1% of full scale
Calibration accuracy
Analog Output
≤± 0.05% of full scale
Linearity error
≤± 0.05% of full scale for a min to max supply change
Supply voltage influence
≤± 0.05% of full scale for a 0…100% load resistance
change
Load influence
≤± 0.01% on zero and span for a 1 °C change
Temperature influence
Power supply indication (green)
PWR
Signalling LEDs
Burnout (red)
BURN
Alarm A (red)
A
Alarm B (red)
B
Environmental conditions
Temperature limits -20 °C … +60 °C (-4 °F … +140 °F),
relative humidity max. 90% non condensing, up to 35 °C
(95 °F).
Operating
Temperature limits -45 °C … +80 °C (-49 °F … +176 °F)
Storage
General
T35 DIN Rail according to EN 50022
Mounting
114.5 × 22.5 × 99 mm
Dimensions (Height × Width × Depth)
approximately 160 g
Weight
Screw terminal blocks, max. 2.5 mm2
Terminal connection
IP20
Protection class
Approvals
• ATEX Ex II (1) G D
• IECEx
• TUV Certificate No. C-IS-236198-02, SIL 2 according to IEC 61511
• DNV A-13778 and KR MIL20769-EL001 Certificates for maritime applications
For the complete list of approvals, see the relay data sheet.
Isolation data
1.5 kV
In/Outs
Isolation voltage (Test
voltage)
1.5 kV
In/Supply
500 V
Analog Out/Supply
1.5 kV
Analog Out/Alarm Outs
1.5 kV
Alarm Outs/Supply
1.5 kV
Alarm Out/Alarm Out
For the complete relay technical data, see www.gminternational.com.
■PR electronics 9116B1 universal converter
Ordering information
9116B1
Universal converter - Uo 28 V DC (max. loop voltage)
4501
Display / Programming front (not included in the ABB
delivery)
60 Technical data
Power supply (terminals 32-31)
19.2 … 31.2 V DC
Supply voltage
1.25 A SB / 250 V AC
Fuse
≤2.1 W
Maximum required power
≤1.7 W
Maximum power dissipation
Measuring circuit/RTD input (terminals 41-44)
3-4 wire RTD Pt100 (for other alternatives, see the relay
data sheet)
Sensor type
< 0.002 ohm / ohm
Effect of sensor cable resistance (3-/4-wire)
Programmable ON / OFF
Sensor error detection
Yes
Short circuit detection
50 ohm
Cable resistance per wire (max)
0.2 mA
Sensor current (nominal)
Current output (terminals 12-11)
0 … 23 mA
Signal range (span)
0/4 … 20 mA
Programmable signal ranges
≤600 ohm
Load (at current output)
≤0.01% of span / 100 ohm
Load stability
0 / 3.5 / 23 mA / none
Sensor error indication
23 mA / 3.5 mA
NAMUR NE43 Upscale/Downscale
3.8 … 20.5 mA
on 4…20 and 20…4 mA
signals
Output limitation
0 … 20.5 mA
on 0…20 and 20…0 mA
signals
≤28 mA
Current limit
Relay output (terminals 13-14)
Setpoint, Window, Sensor error, Power and Off
Relay functions
0.1…25 / 1…25
Hysteresis, in % of span/display range
0 … 3600 s
ON-OFF delay time
Break / Make / Hold
Sensor error reaction
250 V AC/DC
Max. voltage
2 A
Max. current
500 VA
Max. AC power
2 A DC
resistive load ≤30 V DC
Max. DC current
See the relay manual
resistive load > 30 V DC
Indication of operating states
LED (green)
Operation status
“relay” LED (yellow)
Relay status
“error” LED (red)
Malfunction
Environmental conditions
-20 °C … +60 °C (-4 °F … +140 °F)
Operating temperature
-20 °C … +85 °C (-4 °F … +185 °F)
Storage temperature
20 … 28 °C (68 °F … 82 °F)
Calibration temperature
< 95% RH (non-cond.)
Relative humidity
Technical data 61
Pollution degree 2 & meas. / overvoltage cat. II
Installation in
Mechanical specifications
109 × 23.5 × 104 mm
Without 4501
Dimensions (Height ×
Width × Depth)
109 × 23.5 × 116 mm
With 4501
approximately 185 g
Weight
approximately 200 g
Weight including 4501
0.13 … 2.08 mm2 (AWG 26 … 14) stranded wire
Wire size
Terminals
0.5 N·m (4.4 lbf·in)
Tightening torque
±1 mm
2 … 13.2 Hz
Vibration
±0.7 g
13.2 … 100 Hz
Approvals
• ATEX Ex II (1) G D
• IECEx
• EAC Ex
• SIL 2 certified according to IEC 61508
For the complete list of approvals, see the relay data sheet.
Isolation data
2.6 kV AC / 300 V AC reinforced isolation
Test/working: Input to any
Isolation voltage
2.6 kV AC / 300 V AC reinforced isolation
Analog output to supply
1.5 kV AC / 150 V AC reinforced isolation
Status relay to supply
For the complete relay technical data, see www.prelectronics.com.
General rules, notes and definitions
■Validation of the safety functions
You must do an acceptance test (validation) to validate the correct operation of safety
functions.
Competence
The acceptance test of the safety function must be carried out by a competent person with
expertise and knowledge of the safety function as well as functional safety, as required by
IEC 61508-1 clause 6, and ATEX/Ex regulations. The test procedures and report must be
documented and signed by this person.
Validation procedure
You must do the acceptance test using the checklist given in section Start-up and acceptance
test:
•
at initial start-up of the safety function
•
after any changes related to the safety function (wiring, components,
safety-function-related parameter settings, etc.)
•
after any maintenance work related to the safety function.
The acceptance test must include at least the following steps:
•
you must have an acceptance test plan
•
you must test all commissioned functions for proper operation, from each operation
location
62 Technical data
you must document all acceptance tests
•
you must sign and store the acceptance test report for further reference.
Acceptance test reports
You must store the signed acceptance test reports in the logbook of the machine and in the
explosion protection document under the scope of the ATEX User Directive 1999/92/EC.
The report must include, as required by the referred standards:
•
a description of the safety application (including a figure)
•
a description and revisions of safety components that are used in the safety application
•
a list of all safety functions that are used in the safety application
•
a list of all safety-related parameters and their values
•
documentation of start-up activities, references to failure reports and resolution of failures
•
the test results for each safety function, checksums, date of the tests, and confirmation
by the test personnel.
You must store any new acceptance test reports performed due to changes or maintenance
in the logbook of the machine and in the explosion protection document under the scope
of the ATEX User Directive 1999/92/EC.
■Ambient conditions
For the environmental limits for the safety functions and the drive, refer to the hardware
manual.
■Reporting problems and failures related to safety functions
Contact ABB.
Related standards and directives
Safety devices required for the safe functioning of equipment with respect to explo-
sion risks
EN 50495:2010
Functional safety of electrical/electronic/programmable electronic safety-related
systems.
IEC 61508:2010
Part 1 – General Requirements
Part 2 – Requirements for electrical/electronic/programmable electronic safety-re-
lated systems
Adjustable speed electrical power drive systems – Part 5-2: Safety requirements
– Functional
EN 61800-5-2:2007
IEC 61800-5-2:2016
Functional safety – Safety instrumented systems for the process industry sector –
Part 1:Framework, definitions, system, hardware and application programming re-
quirements
IEC 61511-1:2016
European ATEX Product Directive
2014/34/EU
Technical data 63
Markings of the drive
1
2
3
6
4
5
7
CE marking with Notified Body identification: The manufacturer declares that the product conforms with
ATEX Product Directive 2014/34/EU.
1
Notified Body: Eurofins Expert Services (Formerly VTT Expert Services, now part of the Eurofins Group).
Specific marking of explosion protection
2
Equipment group II: Product for surface industry (other than mining applications)
3
Equipment category 2. Parentheses show that the drive (or inverter unit) must be installed outside the
potentially explosive atmosphere.
4
Certified for use in explosive atmospheres caused by:
5
G = gases, vapors or mists, D = dust.
Certificate reference
6
QR code (with the factory code and tracing information)
7
64 Technical data
If the Declaration of Conformity is needed in any other official language of the European
Union than in English, contact ABB.
Technical data 69
7. Circuit diagrams
Contents of this chapter
This chapter contains circuit diagram examples. The purpose of the example circuit diagrams
is to help in understanding the operation of the ATEX-certified motor thermal protection
functions. The diagrams do not cover all possible details and variants of the drives. The
component designations do not necessarily match each drive. For the actual configuration,
see the circuit diagrams delivered with the drive.
WARNING!
Do not connect, test or measure a drive based on the diagrams of this manual.
Each delivery is unique. Before you start the work on the electric circuits of a drive,
always refer to the delivery-specific circuit diagrams.
For the sensor connection, ABB recommends to use shielded twisted-pair cable. This type
of cable decreases electromagnetic interference in the sensor circuit.
70 Circuit diagrams
PTC monitoring with two relays (+2L513+Q971)
A
1
2
3
4
5
6
7
8
B
C
D
E
F
ACS880-07-0145A-3
SINGLE DRIVE
020
ATEX PTC temperature monitoring
070a
Cont.
.1
Rev.
01
=
SAP Doc. No.
EPLAN Doc. No.
ABB Ref. No.
Resp. Dept.
Item Des.
Sheet
Title
Prep.
App.
Project
Cust. Doc. No.
Cust. Ref. No.
Customer
1
2
3
4
5
6
7
8
A
B
C
D
E
F
+
Circuit diagram
EFS2
P193018
14.01.2020
01.1.3
SAFETY CIRCUIT
Changes to this document shall be reviewed by design
manager and approved by ATEX manager.
Also notified body must approve the change.
( See instruction 3AFE002084 and 3AFE003559)
1)
-
On
-
1
2
3
-
4
-
-K74
THERMISTOR RELAY
CM-MSS.41S
12
11
14
//2C
22
21
24
//8C
A1
A2
T1
T2
Reset
S1
NOTE! THESE WIRES ARE ON
ELECTRICAL INSULATION SLEEVE
WINDINGS
OVERHEAT
2A/230VAC
STO TERMINAL FOR CUSTOMER
ACTIVATION SIGNAL TO ZCU
MODULE 2
REMOTE
RESET
PTC 2
TEMPERATURE
SENSOR 1-3 PCS
ATEX CERTIFIED PTC
BEARINGS TEMPERATURE
MONITORING
BEARINGS
OVERHEAT
2A/230VAC
NOTE! THESE WIRES
ARE ON SLEEVE
1) ALL PARTS AND CONNECTIONS DRAWN
WITH A DASHED LINE - - ARE INSTALLATIONS
MADE BY THE USER
1)
-
On
-
1
2
3
-
4
-
-K75
THERMISTOR RELAY
CM-MSS.41S
12
11
14
//5C
22
21
24
//7D
A1
A2
T1
T2
Reset
S1
MODULE 1
REMOTE
RESET
PTC 1
TEMPERATURE
SENSOR 1-3 PCS
ATEX CERTIFIED PTC
WINDINGS TEMPERATURE
MONITORING
25A
-X506
26A
1A
-X506
2A
3A
4A
5A
6A
2B
3B
1B
25B
26B
5B
6B
4B
=01
+01.1
FRAME
27A
-X506
28A
7A
-X506
8A
9A
10A
11A
12A
27B
28B
11B
12B
10B
9B
8B
7B
12
11
14
-K74
//3C
°t
A
B
-X32
9
A
B
-X32
10
A
B
-X31
3
A
B
2
A
B
-X31
1
A
B
-X32
6
A
B
5
WX31-X9
H05V2-K
1 BK
WX31-X9
H05V2-K
1 BK
WX32-X9
H05V2-K
1 BK
WX32-X9
H05V2-K
1 BK
WX31-X9
H05V2-K
1 BK
WK74
H05V2-K
1 BK
WK74
H05V2-K
1 BK
WK74_2
H05V2-K
1 BK
WK74_2
H05V2-K
1 BK
WK74_2
H05V2-K
1 BK
1)
A
B
-X33
9
1B
1A
-X969
2B
2A
3B
3A
4B
4A
A
B
-X33
10
=01
+01.1
FRAME
22
21
24
-K74
//3C
WX33-A41
H05V2-K
1 BK
WX33-A41
H05V2-K
1 BK
WX33-K74
H05V2-K
1 BK
WX33-K74
H05V2-K
1 BK
12
11
14
-K75
//6C
°t
WK75_2
H05V2-K
1 BK
WK75
H05V2-K
1 BK
WK75_2
H05V2-K
1 BK
WK75
H05V2-K
1 BK
1)
A
B
-X34
6
A
B
5
A
B
-X33
3
A
B
2
A
B
-X33
1
WX33-X9
WX34-X9
WX33-X9
22
21
24
-K75
//6C
WX33-K74
H05V2-K
1 BK
/021a/7E
-X9A:12A:4
/021a/6E
-X9A:2A:3
/040b/6D
-A41-XSTO:3
/040b/6D
-A41-XSTO:1
/040b/6D
-A41-XSTO:4
Circuit diagrams 71
PTC monitoring with two relays and an FSO-12 module (+2L513+Q971+Q973)
A
1
2
3
4
5
6
7
8
B
C
D
E
F
ACS880-07-0145A-3
SINGLE DRIVE
010
FSO connections
060a
Cont.
060b
.1
Rev.
01
=
SAP Doc. No.
EPLAN Doc. No.
ABB Ref. No.
Resp. Dept.
Item Des.
Sheet
Title
Prep.
App.
Project
Cust. Doc. No.
Cust. Ref. No.
Customer
1
2
3
4
5
6
7
8
A
B
C
D
E
F
+
Circuit diagram
EFS2
P193018
14.01.2020
01.1
SAFETY CIRCUIT
GENERATED FROM SOLUTION REVISION
RULES CONVERTED 25.10.2018
-A68
-X112
1
2
1
2
3
4
-A68
-X111
-A68
OPTION BOARD KIT
FSO-12 MODULE
1
POWER
2
POWER
1
STO
2
STO
3
STO
4
STO
CHASSIS
WQ973
H05V2-K
1 BK
H05Z-K
0.5 YE
/021a/6E
-X9A:11A:4
/021a/5E
-X9A:1A:3
/040b/6D
-A41-XSTO:3
/040b/6D
-A41-XSTO:1
/040b/6D
-A41-XSTO:4
/040b/7D
-A41-XSTO:2
72 Circuit diagrams
SAP Doc. No.
EPLAN Doc. No.
ABB Ref. No.
Resp. Dept.
Item Des.
Sheet
Title
Prep.
App.
Project
Cust. Doc. No.
Cust. Ref. No.
Customer
1
2
3
4
5
6
7
8
A
B
C
D
E
F
+
Circuit diagram
EFS2
P193018
14.01.2020
01.1
Control and status signals
Terminal Pin
-X113
7
-X113
8
-X113
9
-X113
10
-X114
7
-X114
8
-X114
9
-X114
10
Control and status signals
Terminal Pin
-X113
1
-X113
2
-X113
3
-X113
4
STO B1 REQUEST FROM ATEX RELAY
-X114
1
-X114
2
-X114
3
-X114
4
SAFETY CIRCUIT
GENERATED FROM SOLUTION REVISION
RULES CONVERTED 25.10.2018
Changes to this document shall
be reviewed by design
manager and approved by Ex manager.
Also notified body
must approve the change.
( See instructions 3AFE002084
and 3AFE003559)
-A68
-X113
-A68
-X114
-A68
OPTION BOARD KIT
FSO-12 MODULE
A
B
-X68
3
A
B
17
A
B
4
A
B
18
A
B
5
A
B
19
A
B
6
A
B
20
A
B
7
A
B
21
A
B
9
A
B
8
A
B
22
A
B
23
A
B
10
A
B
24
A
B
11
A
B
25
A
B
12
A
B
26
A
B
13
A
B
14
A
B
15
A
B
16
A
B
27
A
B
28
A
B
29
A
B
30
5
6
5
6
-A68
OPTION BOARD KIT
FSO-12 MODULE
5
GND
5
GND
6
GND
6
GND
4
DI114.4
4
3
DI114.3
3
1
DI114.1
2
2
DI114.2
1
-A68
-X114
4
DI113.4
4
3
DI113.3
3
2
DI113.2
2
1
DI113.1
-A68
-X113
1
10
TP2
10
10
TP1
10
9
DO114.9
9
9
DO113.9
9
8
DO114.8
8
8
DO113.8
8
7
DO114.7
7
7
DO113.7
7
/070a/8B
-X33:10:A
Circuit diagrams 73
ATEX PTC temperature monitoring
070a
Cont.
.1
Rev.
01
=
SAP Doc. No.
EPLAN Doc. No.
ABB Ref. No.
Resp. Dept.
Item Des.
Sheet
Title
Prep.
App.
Project
Cust. Doc. No.
Cust. Ref. No.
Customer
1
2
3
4
5
6
7
8
A
B
C
D
E
F
+
Circuit diagram
EFS2
P193018
14.01.2020
01.1.3
SAFETY CIRCUIT
Changes to this document shall be reviewed by design
manager and approved by ATEX manager.
Also notified body must approve the change.
( See instruction 3AFE002084 and 3AFE003559)
NOTE! THESE WIRES ARE ON
ELECTRICAL INSULATION SLEEVE
WINDINGS
OVERHEAT
2A/230VAC
ACTIVATION SIGNAL TO FSO
MODULE 2
REMOTE
RESET
PTC 2
TEMPERATURE
SENSOR 1-3 PCS
ATEX CERTIFIED PTC
BEARINGS TEMPERATURE
MONITORING
1)
-
On
-
1
2
3
-
4
-
-K75
THERMISTOR RELAY
CM-MSS.41S
12
11
14
//5C
22
21
24
//8D
A1
A2
T1
T2
Reset
S1
BEARINGS
OVERHEAT
2A/230VAC
NOTE! THESE WIRES
ARE ON SLEEVE
1) ALL PARTS AND CONNECTIONS DRAWN
WITH A DASHED LINE - - ARE INSTALLATIONS
MADE BY THE USER
1)
-
On
-
1
2
3
-
4
-
-K74
THERMISTOR RELAY
CM-MSS.41S
12
11
14
//2C
22
21
24
//8D
A1
A2
T1
T2
Reset
S1
MODULE 1
REMOTE
RESET
PTC 1
TEMPERATURE
SENSOR 1-3 PCS
ATEX CERTIFIED PTC
WINDINGS TEMPERATURE
MONITORING
A
B
-X33
9
A
B
10
22
21
24
-K74
//3C
WX33-X68
H05V2-K
1 BK
WX33-X68
H05V2-K
1 BK
12
11
14
-K75
//6C
°t
WK75_2
H05V2-K
1 BK
WK75
H05V2-K
1 BK
WK75_2
H05V2-K
1 BK
WK75
H05V2-K
1 BK
1)
A
B
-X34
6
A
B
5
A
B
-X33
3
A
B
2
A
B
-X33
1
WX33-X9
WX34-X9
WX33-X9
22
21
24
-K75
//6C
25A
-X506
26A
1A
-X506
2A
3A
4A
5A
6A
2B
3B
1B
25B
26B
5B
6B
4B
=01
+01.1
FRAME
27A
-X506
28A
7A
-X506
8A
9A
10A
11A
12A
27B
28B
11B
12B
10B
9B
8B
7B
12
11
14
-K74
//3C
°t
A
B
-X32
9
A
B
-X32
10
A
B
-X31
3
A
B
2
A
B
-X31
1
A
B
-X32
6
A
B
5
WX31-X9
H05V2-K
1 BK
WX31-X9
H05V2-K
1 BK
WX32-X9
H05V2-K
1 BK
WX32-X9
H05V2-K
1 BK
WX31-X9
H05V2-K
1 BK
WK74
H05V2-K
1 BK
WK74
H05V2-K
1 BK
WK74_2
H05V2-K
1 BK
WK74_2
H05V2-K
1 BK
WK74_2
H05V2-K
1 BK
1)
/021a/6D
-X9A:12A:1
/060b/2B
-X68:6:A
/021a/7E
-X9A:12A:4
/021a/6E
-X9A:2A:3
74 Circuit diagrams
Pt100 monitoring with three relays (+3L514+Q971)
A
1
2
3
4
5
6
7
8
B
C
D
E
F
ACS880-07-0145A-3
SINGLE DRIVE
010
ATEX PT100 temperature monitoring
070a
Cont.
071a
.1
Rev.
01
=
SAP Doc. No.
EPLAN Doc. No.
ABB Ref. No.
Resp. Dept.
Item Des.
Sheet
Title
Prep.
App.
Project
Cust. Doc. No.
Cust. Ref. No.
Customer
1
2
3
4
5
6
7
8
A
B
C
D
E
F
+
Circuit diagram
EFS2
P193023
14.01.2020
01.1.3
Changes to this document shall be reviewed by
design manager and approved by Ex manager.
Also notified body must approve the change.
( See instructions 3AFE002084 and 3AFE003559)
SAFETY CIRCUIT
NOTE*
NOTE*
NOTE*
NOTE*= THESE EARTHINGS ARE ON SAME BUSBAR
-K71.1
PT100 RELAY
D1073S
5
6
//3B
7
8
//3B
13
14
15
16
3
4
1
mA+
2
mA-
-K71.2
PT100 RELAY
D1073S
5
6
//5B
7
8
//5B
13
14
15
16
3
4
1
mA+
2
mA-
-K71.3
PT100 RELAY
D1073S
5
6
//7B
7
8
//7B
13
14
15
16
3
4
1
mA+
2
mA+
ATEX CERTIFIED PT-100 WINDINGS TEMPERATURE MONITORING
NOTE!
IF CONNECTED
WITH WIRES
WIRES ARE
ON SLEEVE
NOTE!
IF CONNECTED
WITH WIRES
WIRES ARE
ON SLEEVE
NOTE!
IF CONNECTED
WITH WIRES
WIRES ARE
ON SLEEVE
NOTE*
NOTE*
NOTE*
NOTE*= THESE EARTHINGS ARE ON SAME BUSBAR
WK71-A81
H05V2-K
1 BK
WK71-A81
H05V2-K
1 BK
WK71-A81
H05V2-K
1 BK
WK71-X32
H05V2-K
1 BK
WK71-X32
H05V2-K
1 BK
WK71-X34
H05V2-K
1 BK
WK71-X32
H07V2-K
4 GNYE
WX31-X506
H05V2-K
1 BK
=01
+01.1
FRAME
1
-X506
2
3
4
31
-X506
32
6
-X506
7
8
9
33
-X506
34
5
10
BK
BK
BK
BK
BK
BK
BK
BK
PT-100
°t
PT-100
°t
5
6
-K71.1
//1B
7
8
5
6
-K71.2
//3B
7
8
5
6
-K71.3
//6B
7
8
11
-X506
12
13
14
35
-X506
36
15
PT-100
°t
BK
BK
BK
BK
A
B
3
-X31
A
B
4
-X32
1
A
B
2
A
B
3
A
B
4
A
B
5
A
B
-XFE
FE1
BK
BK
BK
BK
WK71-X32
H05V2-K
1 BU
-X32
7
A
B
8
A
B
9
A
B
10
A
B
6
A
B
-XFE
FE2
BK
BK
BK
BK
-X31
1
A
B
2
A
B
-X31
6
A
B
7
A
B
WK71-X32
H05V2-K
1 BU
WK71-X34
H05V2-K
1 BU
-X34
1
A
B
2
A
B
3
A
B
4
A
B
5
A
B
-XFE
FE3
BK
BK
BK
BK
-X33
1
A
B
2
A
B
WX31-X9
WK71-X31
H05V2-K
1 BK
WX31-X506
H05V2-K
1 BK
WX33-X506
H05V2-K
1 BK
4x1
BETAFLAM c-flex
-WX32-X506
BK
BK
BK
BK
4x1
BETAFLAM c-flex
-WX32-X506
BK
BK
BK
BK
4x1
BETAFLAM c-flex
-WX34-X506
BK
BK
BK
BK
WK71-X31
H05V2-K
1 BK
WK71-X31
H05V2-K
1 BK
WK71-X31
H05V2-K
1 BK
WK71-X31
H05V2-K
1 BK
WK71-X31
H05V2-K
1 BK
WK71-X31
H05V2-K
1 BK
WK71-X31
H05V2-K
1 BK
WK71-X31
H05V2-K
1 BK
WK71-A81
H05V2-K
1 BK
WK71-A81
H05V2-K
1 BK
WK71-X33
H05V2-K
1 BK
FRAME
/021a/7E
-X9A:12A:4
/021a/6E
-X9A:2A:3
/071a/1A
-A81:A1
/071a/1A
-A81:A2
Circuit diagrams 75
ATEX PT100 temperature monitoring
071a
Cont.
.1
Rev.
01
=
SAP Doc. No.
EPLAN Doc. No.
ABB Ref. No.
Resp. Dept.
Item Des.
Sheet
Title
Prep.
App.
Project
Cust. Doc. No.
Cust. Ref. No.
Customer
1
2
3
4
5
6
7
8
A
B
C
D
E
F
+
Circuit diagram
EFS2
P193023
14.01.2020
01.1.3
Changes to this document shall be reviewed by
design manager and approved by Ex manager.
Also notified body must approve the change.
( See instructions 3AFE002084
and 3AFE003559)
SAFETY CIRCUIT
1) ALL PARTS AND CONNECTIONS DRAWN
WITH A DASHED LINE - - ARE INSTALLATIONS
MADE BY THE USER
A1
S11
S12
S21
S22
S33
S34
A2
-A81
SAFETY RELAY
LG5925.48/60
13
14
//1D
23
24
//6D
33
34
41
42
33
34
24
23
13
14
-K1
-K2
42
41
Cross fault detection
Without
With
Start mode
Automatic
Manual
S1
S2
WINDINGS
OVERHEAT
MONITORING
STO TERMINAL FOR CUSTOMER
STO ACTIVATION
13
14
-A81
//1B
=01
+01.1
FRAME
37
-X506
38
39
40
WX33-X506
H05V2-K
1 BK
WK71-A81
H05V2-K
1 BK
WK71-A81
H05V2-K
1 BK
WK71-A81
H05V2-K
1 BK
A
B
3
A
B
4
-X33
A
B
-X33
9
23
24
-A81
//1B
1A
-X969
2A
3A
4A
A
B
-X33
10
WX33-X506
H05V2-K
1 BK
WX33-X506
H05V2-K
1 BK
/070a/8B
-K71.3:4
/070a/8B
-K71.3:7
/040b/6D
-A41-XSTO:3
/040b/6D
-A41-XSTO:1
/040b/6D
-A41-XSTO:4
76 Circuit diagrams
Pt100 monitoring with five relays and an FSO-12 module (+5L514+Q971+Q973)
A
1
2
3
4
5
6
7
8
B
C
D
E
F
ACS880-07-0145A-3
SINGLE DRIVE
010
FSO connections
060a
Cont.
060b
.1
Rev.
01
=
SAP Doc. No.
EPLAN Doc. No.
ABB Ref. No.
Resp. Dept.
Item Des.
Sheet
Title
Prep.
App.
Project
Cust. Doc. No.
Cust. Ref. No.
Customer
1
2
3
4
5
6
7
8
A
B
C
D
E
F
+
Circuit diagram
EFS2
P193007
14.01.2020
01.1
SAFETY CIRCUIT
GENERATED FROM SOLUTION REVISION
RULES CONVERTED 25.10.2018
-A68
-X112
1
2
1
2
3
4
-A68
-X111
-A68
OPTION BOARD KIT
FSO-12 MODULE
1
POWER
2
POWER
1
STO
2
STO
3
STO
4
STO
CHASSIS
WQ973
H05V2-K
1 BK
H05Z-K
0.5 YE
/021a/6E
-X9A:11A:4
/021a/5E
-X9A:1A:3
/040b/6D
-A41-XSTO:3
/040b/6D
-A41-XSTO:1
/040b/6D
-A41-XSTO:4
/040b/7D
-A41-XSTO:2
Circuit diagrams 77
SAP Doc. No.
EPLAN Doc. No.
ABB Ref. No.
Resp. Dept.
Item Des.
Sheet
Title
Prep.
App.
Project
Cust. Doc. No.
Cust. Ref. No.
Customer
1
2
3
4
5
6
7
8
A
B
C
D
E
F
+
Circuit diagram
EFS2
P193007
14.01.2020
01.1
Control and status signals
Terminal Pin
-X113
7
-X113
8
-X113
9
-X113
10
-X114
7
-X114
8
-X114
9
-X114
10
Control and status signals
Terminal Pin
-X113
1
-X113
2
-X113
3
-X113
4
STO B1 REQUEST FROM ATEX RELAY
-X114
1
-X114
2
-X114
3
-X114
4
SAFETY CIRCUIT
GENERATED FROM SOLUTION REVISION
RULES CONVERTED 25.10.2018
Changes to this document shall
be reviewed by design
manager and approved by Ex manager.
Also notified body
must approve the change.
( See instructions 3AFE002084
and 3AFE003559)
-A68
-X113
-A68
-X114
-A68
OPTION BOARD KIT
FSO-12 MODULE
A
B
-X68
3
A
B
17
A
B
4
A
B
18
A
B
5
A
B
19
A
B
6
A
B
20
A
B
7
A
B
21
A
B
9
A
B
8
A
B
22
A
B
23
A
B
10
A
B
24
A
B
11
A
B
25
A
B
12
A
B
26
A
B
13
A
B
14
A
B
15
A
B
16
A
B
27
A
B
28
A
B
29
A
B
30
5
6
5
6
-A68
OPTION BOARD KIT
FSO-12 MODULE
5
GND
5
GND
6
GND
6
GND
4
DI114.4
4
3
DI114.3
3
1
DI114.1
2
2
DI114.2
1
-A68
-X114
4
DI113.4
4
3
DI113.3
3
2
DI113.2
2
1
DI113.1
-A68
-X113
1
10
TP2
10
10
TP1
10
9
DO114.9
9
9
DO113.9
9
8
DO114.8
8
8
DO113.8
8
7
DO114.7
7
7
DO113.7
7
/071a/6A
-X33:10:A
78 Circuit diagrams
ATEX PT100 temperature monitoring
070a
Cont.
070b
.1
Rev.
01
=
SAP Doc. No.
EPLAN Doc. No.
ABB Ref. No.
Resp. Dept.
Item Des.
Sheet
Title
Prep.
App.
Project
Cust. Doc. No.
Cust. Ref. No.
Customer
1
2
3
4
5
6
7
8
A
B
C
D
E
F
+
Circuit diagram
EFS2
P193007
14.01.2020
01.1.3
Changes to this document shall be reviewed by
design manager and approved by Ex manager.
Also notified body must approve the change.
( See instructions 3AFE002084 and 3AFE003559)
SAFETY CIRCUIT
NOTE*
NOTE*
NOTE*
NOTE*= THESE EARTHINGS ARE ON SAME BUSBAR
-K71.1
PT100 RELAY
D1073S
5
6
//3B
7
8
//3B
13
14
15
16
3
4
1
mA+
2
mA-
-K71.2
PT100 RELAY
D1073S
5
6
//5B
7
8
//5B
13
14
15
16
3
4
1
mA+
2
mA-
-K71.3
PT100 RELAY
D1073S
5
6
//7B
7
8
//7B
13
14
15
16
3
4
1
mA+
2
mA+
ATEX CERTIFIED PT-100 WINDINGS TEMPERATURE MONITORING
NOTE!
IF CONNECTED
WITH WIRES
WIRES ARE
ON SLEEVE
NOTE!
IF CONNECTED
WITH WIRES
WIRES ARE
ON SLEEVE
NOTE!
IF CONNECTED
WITH WIRES
WIRES ARE
ON SLEEVE
NOTE*
NOTE*
NOTE*
NOTE*= THESE EARTHINGS ARE ON SAME BUSBAR
WK71-A81
H05V2-K
1 BK
WK71-A81
H05V2-K
1 BK
WK71-A81
H05V2-K
1 BK
WK71-X32
H05V2-K
1 BK
WK71-X32
H05V2-K
1 BK
WK71-X34
H05V2-K
1 BK
WK71-X32
H07V2-K
4 GNYE
WX31-X506
H05V2-K
1 BK
=01
+01.1
FRAME
1
-X506
2
3
4
31
-X506
32
6
-X506
7
8
9
33
-X506
34
5
10
BK
BK
BK
BK
BK
BK
BK
BK
PT-100
°t
PT-100
°t
5
6
-K71.1
//1B
7
8
5
6
-K71.2
//3B
7
8
5
6
-K71.3
//6B
7
8
11
-X506
12
13
14
35
-X506
36
15
PT-100
°t
BK
BK
BK
BK
A
B
3
-X31
A
B
4
-X32
1
A
B
2
A
B
3
A
B
4
A
B
5
A
B
-XFE
FE1
BK
BK
BK
BK
WK71-X32
H05V2-K
1 BU
-X32
7
A
B
8
A
B
9
A
B
10
A
B
6
A
B
-XFE
FE2
BK
BK
BK
BK
-X31
1
A
B
2
A
B
-X31
6
A
B
7
A
B
WK71-X32
H05V2-K
1 BU
WK71-X34
H05V2-K
1 BU
-X34
1
A
B
2
A
B
3
A
B
4
A
B
5
A
B
-XFE
FE3
BK
BK
BK
BK
-X33
1
A
B
2
A
B
WX31-X9
WK71-X31
H05V2-K
1 BK
WX31-X506
H05V2-K
1 BK
WX33-X506
H05V2-K
1 BK
4x1
BETAFLAM c-flex
-WX32-X506
BK
BK
BK
BK
4x1
BETAFLAM c-flex
-WX32-X506
BK
BK
BK
BK
4x1
BETAFLAM c-flex
-WX34-X506
BK
BK
BK
BK
WK71-X31
H05V2-K
1 BK
WK71-X31
H05V2-K
1 BK
WK71-X31
H05V2-K
1 BK
WK71-X31
H05V2-K
1 BK
WK71-X31
H05V2-K
1 BK
WK71-X31
H05V2-K
1 BK
WK71-X31
H05V2-K
1 BK
WK71-X31
H05V2-K
1 BK
WK71-A81
H05V2-K
1 BK
WK71-A81
H05V2-K
1 BK
WK71-X33
H05V2-K
1 BK
FRAME
/021a/7E
-X9A:12A:4
/021a/6E
-X9A:2A:3
/071a/1A
-A81:A1
/071a/1A
-A81:A2
/070b/1A
-K72.1:3
Circuit diagrams 79
ATEX PT100 temperature monitoring
070b
Cont.
071a
.1
Rev.
01
=
SAP Doc. No.
EPLAN Doc. No.
ABB Ref. No.
Resp. Dept.
Item Des.
Sheet
Title
Prep.
App.
Project
Cust. Doc. No.
Cust. Ref. No.
Customer
1
2
3
4
5
6
7
8
A
B
C
D
E
F
+
Circuit diagram
EFS2
P193007
14.01.2020
01.1.3
Changes to this document shall be reviewed by
design manager and approved by Ex manager.
Also notified body must approve the change.
( See instructions 3AFE002084 and 3AFE003559)
SAFETY CIRCUIT
NOTE*
NOTE*
NOTE*= THESE EARTHINGS ARE ON SAME BUSBAR
-K72.1
PT100 RELAY
D1073S
5
6
//3B
7
8
//3B
13
14
15
16
3
4
1
mA+
2
mA-
-K72.2
PT100 RELAY
D1073S
5
6
//5B
7
8
//5B
13
14
15
16
3
4
1
mA+
2
mA-
ATEX CERTIFIED PT100 BEARINGS TEMPERATURE MONITORING
NOTE!
IF CONNECTED
WITH WIRES
WIRES ARE
ON SLEEVE
NOTE!
IF CONNECTED
WITH WIRES
WIRES ARE
ON SLEEVE
NOTE*
NOTE*
NOTE*= THESE EARTHINGS ARE ON SAME BUSBAR
WK72-A82
H05V2-K
1 BK
WK72-A82
H05V2-K
1 BK
WK72-X35
H05V2-K
1 BK
WK72-X35
H05V2-K
1 BK
WK72-X36
H05V2-K
1 BK
WK72-X36
H05V2-K
1 BK
=01
+01.1
FRAME
16
-X506
17
18
19
41
-X506
42
21
-X506
22
23
24
43
-X506
44
20
25
BK
BK
BK
BK
BK
BK
BK
BK
26
-X506
PT-100
°t
PT-100
°t
5
6
-K72.1
//1B
7
8
5
6
-K72.2
//3B
7
8
WK72-X36
H05V2-K
1 BU
BK
BK
BK
BK
WK72-X36
H05V2-K
1 BU
BK
BK
BK
BK
-X36
1
A
B
2
A
B
3
A
B
4
A
B
5
A
B
-X35
1
A
B
2
A
B
-XFE
FE4
-X36
7
A
B
8
A
B
9
A
B
10
A
B
6
A
B
-X35
6
A
B
7
A
B
-XFE
FE5
WX35-X506
H05V2-K
1 BK
WX35-X506
H05V2-K
1 BK
4x1
BETAFLAM c-flex
-WX36-X506
BK
BK
BK
BK
4x1
BETAFLAM c-flex
-WX36-X506
BK
BK
BK
BK
WK72-A82
H05V2-K
1 BK
WK71-X31
H05V2-K
1 BK
WK71-X31
H05V2-K
1 BK
WK71-X31
H05V2-K
1 BK
WK71-X31
H05V2-K
1 BK
WK71-X31
H05V2-K
1 BK
/071a/3A
-A82:A1
/071a/4A
-A82:A2
/070a/8B
-K71.3:3
/071a/2A
-A81:S21
80 Circuit diagrams
ATEX PT100 temperature monitoring
071a
Cont.
.1
Rev.
01
=
SAP Doc. No.
EPLAN Doc. No.
ABB Ref. No.
Resp. Dept.
Item Des.
Sheet
Title
Prep.
App.
Project
Cust. Doc. No.
Cust. Ref. No.
Customer
1
2
3
4
5
6
7
8
A
B
C
D
E
F
+
Circuit diagram
EFS2
P193007
14.01.2020
01.1.3
Changes to this document shall be reviewed by
design manager and approved by Ex manager.
Also notified body must approve the change.
( See instructions 3AFE002084
and 3AFE003559)
SAFETY CIRCUIT
1) ALL PARTS AND CONNECTIONS DRAWN
WITH A DASHED LINE - - ARE INSTALLATIONS
MADE BY THE USER
A1
S11
S12
S21
S22
S33
S34
A2
-A81
SAFETY RELAY
LG5925.48/60
13
14
//1D
23
24
//6D
33
34
41
42
33
34
24
23
13
14
-K1
-K2
42
41
Cross fault detection
Without
With
Start mode
Automatic
Manual
S1
S2
ACTIVATION SIGNAL TO FSO
A1
S11
S12
S21
S22
S33
S34
A2
-A82
SAFETY RELAY
LG5925.48/60
13
14
//3D
23
24
//6D
33
34
41
42
33
34
24
23
13
14
-K1
-K2
42
41
Cross fault detection
Without
With
Start mode
Automatic
Manual
S1
S2
WINDINGS
OVERHEAT
MONITORING
BEARINGS
OVERHEAT
MONITORING
13
14
-A81
//1B
=01
+01.1
FRAME
37
-X506
38
39
40
WX33-X506
H05V2-K
1 BK
WK71-A81
H05V2-K
1 BK
WK71-A81
H05V2-K
1 BK
WK71-A81
H05V2-K
1 BK
A
B
3
A
B
4
-X33
A
B
9
-X33
23
24
-A81
//1B
A
B
10
-X33
WX33-X506
H05V2-K
1 BK
45
-X506
46
47
48
13
14
-A82
//3B
A
B
4
-X37
A
B
3
WX37-X506
H05V2-K
1 BK
WK71-A81
H05V2-K
1 BK
WK71-A81
H05V2-K
1 BK
WK71-A81
H05V2-K
1 BK
23
24
-A82
//3B
/070a/8B
-K71.3:4
/070a/8B
-K71.3:7
/060b/2B
-X68:6:A
/021a/6D
-X9A:12A:1
/070b/6B
-K72.2:7
/070b/6B
-K72.2:4
/070b/1A
-K72.1:4
Circuit diagrams 81
Product and service inquiries
Address any inquiries about the product to your local ABB representative, quoting the type
designation and serial number of the unit in question. A listing of ABB sales, support and service
contacts can be found by navigating to www.abb.com/searchchannels.
Product training
For information on ABB product training, navigate to new.abb.com/service/training.
Providing feedback on ABB manuals
Your comments on our manuals are welcome. Navigate to
new.abb.com/drives/manuals-feedback-form.
Document library on the Internet
You can find manuals and other product documents in PDF format on the Internet at