Azbil BH-101G0W0000 Specifications & Instructions
Read Online
Read the Azbil BH-101G0W0000 Specifications & Instructions online using the built-in PDF viewer.
Text of the manual
© 2017–2020 Azbil Corporation. All Rights Reserved.
Overview
This product (Model BH-101G0_0000) is a Supervisory
Controller that collects information about a primary device
(such as a controller) and provides that information to the
Client PC in savic-net G5, Azbil Corporation's building
management system.
This product receives point information from the primary
device through periodic scan or state change notifi cations
and accumulates and manages various kinds of control-
related data.
In addition, the software that can be downloaded from this
product allows you to monitor its state using graphics and
lists, set up several different kinds of controls including
interlock controls and scheduling, view data such as
charts as well as daily, weekly, monthly and yearly reports,
and perform other operations from the Client PC.
This product can also provide information to a third-party
BACnet device.
Features
Any combination of the following applications is available
as required.
• Equipment status monitoring
This product monitors up to 5000 points of the data
below.
It is possible to connect up to 30 Supervisory Controllers
to monitor up to 150,000 points.
Each Supervisory Controller can also be confi gured
for redundancy. (If a redundancy confi guration is
implemented, up to 60 Supervisory Controllers can be
connected.)
•
Point information in the primary device
•
Direct inputs to ensure immediate detection of
power supply state and fi re alarms from a building
• Comprehensive control
This product comprehensively controls the devices
connected to the system to realize comfort, safety, and
energy effi ciency.
• Data management
This product stores and manages the following data:
•
Data collected from the devices connected to this
product
•
Data transmitted from the devices connected to
this product
•
Data that has been processed for daily, weekly,
monthly, and yearly reports based on the collected
and transmitted data
• Data visualization
By using the software that comes with this product,
you can display graphics, charts, and daily, weekly,
monthly, and yearly reports on the screen of a Client
PC or output them to a fi le.
Please read instructions carefully and use the product
as specified in this manual. Be sure to keep this manual
nearby for quick reference.
Restrictions on Use
This product was developed, designed, and manufac-
tured for general air conditioning use.
Do not use the product in a situation where human life
may be at risk or for nuclear applications in radiation
controlled areas. If you wish to use the product in a radi-
ation controlled area, please contact Azbil Corporation.
Particularly when the product is used in the following
applications where safety is required, implementation of
fail-safe design, redundant design, regular maintenance,
etc., should be considered in order to use the product
safely and reliably.
• Safety devices for protecting the human body
• Start/stop control devices for transportation machines
• Aeronautical/aerospace machines
For system design, application design, instructions
for use, or product applications, please contact Azbil
Corporation.
Azbil Corporation bears no responsibility for any result,
or lack of result, deriving from the customer's use of the
product.
Caution for Instrumentation Design
Considering unexpected failures or contingencies,
be sure to design and check safety of the system and
equipment.
Recommended Design Life
It is recommended that this product be used within the
recommended design life.
The recommended design life is the period during which
you can use the product safely and reliably based on the
design specifications.
If the product is used beyond this period, its failure ratio
may increase due to time-related deterioration of parts,
etc.
The recommended design life during which the product
can operate reliably with the lowest failure ratio and least
deterioration over time is estimated scientifically based
on acceleration tests, endurance tests, etc., taking into
consideration the operating environment, conditions,
and frequency of use as basic parameters.
The recommended design life of this product is 10 years.
The recommended design life assumes that mainte-
nance, such as replacement of the limited life parts, is
carried out properly.
Refer to the section on maintenance in this manual.
Caution for Transporting
Lithium batteries are used in this product.
When this product, which uses lithium batteries, is
transported by air or sea, ship it in accordance with
IATA-DGR/IMDG-Code regulations.
Please inform your shipping company that lithium
batteries are included in the product, and follow the
necessary procedures according to the company's
instructions.
If the product is shipped by air or sea without the
necessary labels, etc., specified by the ordinances, you
may be in violation of aviation or maritime safety laws
and be subject to punishment.
Warnings and Cautions
WARNING
Alerts users that improper handling may
cause death or serious injury.
CAUTION
Alerts users that improper handling may
cause minor injury or material loss.
Signs
Electric shock
Alerts users to possible hazardous condi-
tions caused by erroneous operation or
erroneous use. The symbol inside
indicates the specific type of danger. (For
example, the sign on the left warns of the
risk of electric shock.)
Disassemble
Notifies users that specific actions are
prohibited to prevent possible danger.
The symbol inside graphically indicates
the prohibited action. (For example, the
sign on the left means that disassembly is
prohibited.)
General
Instructs users to carry out a specific oblig-
atory action to prevent possible danger.
The symbol inside d graphically indicates
the actual action to be carried out. (For
example, the sign on the left indicates
general instructions.)
Install this product in a location out of
reach of unauthorized people. (e.g. Inside
of the control panel with a lock)
Failure to do so might cause electric shock.
Ground
Ground this product with ground resistance
of less than 100 Ω.
Improper grounding may cause electric
shock or malfunction.
Electric shock
Before wiring or maintenance, turn off the
power to this product.
Failure to do so may result in electric shock
or device failure.
Prohibition
Do not insert conductive objects through
product ventilation holes.
Doing so may cause electric shock.
Electric shock
Do not touch electrically charged parts.
Doing so may cause electric shock.
CAUTION
General
Take anti-lightning surge measures based
on regional and building characteristics.
Lightning may cause fire or critical damage
to this product if protective measures are
not taken.
General
Keep the products in package for storage.
Failure to do so may damage or stain the
products.
General
Do not drop this product.
Doing so may cause an injury or may
damage the device.
General
Install, wire, and use this product under the
conditions specified by this manual.
Failure to do so may cause fire or device
failure.
General
Take anti-noise measures if this product
is installed in a location near source of
electric noise.
Failure to do so may cause malfunction or
device failure.
General
Installation and wiring must be performed
by personnel qualified to do instrumenta-
tion and electrical work.
Mistakes in installation or wiring may cause
fire or electric shock.
General
All wiring must comply with applicable
codes and ordinances.
Otherwise there is a danger of fire.
CAUTION
General
Strip the insulation from cables as speci-
fied in this manual.
If the length of exposed wire is longer than
specified, it may cause electric shock or
short circuit between adjacent terminals.
If it is too short, it may not make proper
contact.
General
Tighten the terminal screws with the spec-
ified torque.
Insufficient tightening of the terminal
screws may cause fire or overheating.
Prohibition
Do not use unused/spare terminals on this
product as relay terminals.
Doing so may cause device failure.
Prohibition
Do not block the ventilation holes of this
product.
Doing so may cause device failure.
Prohibition
Do not allow wire clippings, metal
shavings, and other refuse to enter into the
product.
Doing so may cause fire or product
damage.
Disassemble
Do not disassemble this product.
Doing so may cause device failure.
General
Before cleaning the product or retorquing
the terminal screws, turn off the power to
the product.
Failure to do so may cause electric shock,
device failure, or malfunction.
General
Before touching this product, remove any
static electrical charge from your body.
Otherwise your static electricity may
damage some components of the product.
Static electrical charge can be removed by
touching the grounded metal.
Prohibition
When removing the fan, do not insert
fingers into the product.
Doing so may damage the internal
components.
General
Dispose of used lithium batteries in accor-
dance with local regulations. Do not throw
them in the fire or dispose of them with
ordinary garbage.
Doing so may cause the batteries to burst
or ignite.
System Configuration
Third-party
BACnet/IP
device
Third-party
BACnet/IP
device
Operator
Interface*7
Model
QJ-1101
Third-party
BACnet/IP
device
ETHERNET*5
Infilex VC
Model
WY5706
Model
MY804_A
Model
FVY516_J00__
Damper
Actuator
SAnet*3
Model WJ-1102
Operator Panel
(Panel Mount
Type)*4
Model
QY5100W0000
Model QY7205
Neopanel*4
Direct Mount
I/O Module
SAnet I/F Module
Setting-Device
Connection Module (SD)
Model RY51_ _
Supervisory
device network
Primary device
network
Secondary device
network
General
Controller
Third-party
Modbus/
TCP device
Third-party
Modbus
device
Compact
Remote
I/O Module
Third-party
BACnet
MS/TP
device
Advanced
Remote
I/O module
Advanced
Remote
I/O module
Advanced
Remote
I/O module
Model
RJ-11_ _
Model
RJ-11_ _
Model
WJ-1111
Remote
I/O network*6
Model
RJ-11_ _
Model RJ-12_ _
Compact
Remote
I/O Module
Model RJ-12_ _
Switching hub*1
Switching hub
Switching hub
Switching hub
Switching hub
Switching hub
RS-485*3 (if BACnet MS/TP is selected)
Third-party
BACnet
MS/TP
device
FCU
Controller
Model
WJ-1202
RS-485*2 (if BACnet MS/TP is selected)
ACTIVAL +
RS-485*2 (if Modbus is selected)
RS-485*2 (if Modbus is selected)
ETHERNET (BACnet/IP, Modbus/TCP, etc.).
The communication distance between each device and the switching hub must be 100 m or less.
Advanced
Controller for
Chiller/Pump Units
Supervisory Controller
Model BH-101G
Client PC
Network Attached
Storage
Third-party
Modbus
device
Supervisory Controller
Model BH-101G
(Active)
Supervisory Controller
Model BH-101G
(Standby)
(Redundancy)
Switching hub*1
Switching hub*1
Network Attached
Storage
Figure 1. Example system configuration
Multiple switching hubs (network components) will be required depending on the actual equipment placement.
*2
The General Controller, Advanced Controller for Chiller Units, and Advanced Controller for Pump Units have two
channels of the RS-485 line.
For each channel, communication protocol can be selected from BACnet MS/TP, Modbus™ RTU, or Modbus™ ASCII.
• The number of devices that can be connected for BACnet MS/TP
If only the Azbil devices are connected:
50 devices/channel (VAV/FCU Controllers, Compact Remote I/O Modules, etc.)
There are restrictions on the General Controller that up to 70 secondary devices or up to 50 of the sum of Azbil’s VAV and
FCU controllers can be connected. There are no restrictions on the Advanced Controller for Chiller Units, and Advanced
Controller for Pump Units.
If only the third-party devices are connected:
31 devices/channel (when transmission speed is 76.8 kbps, 30 objects/device)
• The number of devices that can be connected for Modbus
31 devices/channel (when transmission speed is 76.8 kbps, 30 objects/device)
If the transmission speed and the number of objects are different among the third-party devices, or if the Azbil devices and third-
party devices coexist on the same channel, the number of connected devices will vary. For details, please contact one of Azbil
salespersons.
*3
By connecting the SAnet Interface Module, it is possible to connect the Intelligent Component Series devices.
For restrictions on the SAnet communication line, refer to AB-6713, Intelligent Component Series for SAnet Communication
Installation Manual.
*4
By connecting the Setting-Device Connection Module (SD), you can connect the Operator Panel (Panel Mount Type), and
Neopanel, Neoplate.
By connecting the Operator Panel (Integral Type), you can connect Neopanel, and Neoplate devices.
AB-7530, Operator Panel (Panel Mount Type), Operator Panel (Integral Type) Specifications/Instructions
*5
A network that connects the Advanced Controller for Chiller Units, Advanced Controller for Pump Units and Advanced
Remote I/O Modules under their control is referred to as a local I/O network.
A switching hub is not required for the local I/O network since a jumper wiring using ETHERNET is used between the Advanced
Controller for Chiller Units, and Advanced Controller for Pump Units of the local I/O network and the high speed remote I/O module
under their control and between the Advanced Remote I/O Module and the I/O module.
*6
A network that connects the Advanced Controller for Chiller Units, Advanced Controller for Pump Units, and Advanced
Remote I/O Modules through a host network is referred to as a remote I/O network.
A switching hub is required to connect the Advanced Remote I/O Modules to the remote I/O network.
The number of Advanced Remote I/O Modules that can be connected to this network should be up to three units per Advanced
Controller for Chiller Units, or Advanced Controller for Pump Units.
When using IPv6 for BACnet communication, the Advanced Remote I/O Module cannot be connected via a remote I/O network.
*7
Up to four Controllers (Model WJ-1102) can be managed with one Operator Interface (Model QJ-1101) unit.
Model Numbers
Model number
Description
BH-101G0W0000
Supervisory Controller
BH-101G0N0000
Supervisory Controller without azbil logo
z Items Provided Separately
Model number
Description
83104567-001
DIN rail clamp
z Replacement Parts
Model number
Description
Replacement interval
83173710-001
Fan replacement kit
Only in the case of failure.
83173707-001
Power connector (× 1)
83173883-001
I/O plug (DI connector × 2,
DO connector × 1)
83170639-001
Lithium battery (× 1)
Five years
(For the first time, five years from the date
of manufacture of this product)
83170639-005
Lithium battery (× 5)
83170639-010
Lithium battery (× 10)
z Basic Specifications
Item
Specification
Power supply
specifications
Rated voltage
100–240 V AC, 50 Hz/60 Hz
Operating power supply
voltage
90–264 V AC, 50 Hz/60 Hz ± 3 Hz
Inrush current
50 A max. (240 V AC)
Power consumption
60 VA max. (240 V AC)
Leakage current
1.5 mA max. (240 V AC)
Backup power
For system
Lithium ion capacitor module
For RTC
Lithium battery (non-chargeable)
CPU
Intel Atom E3845
1.9 GHz, 4 cores, 4 threads, 64 bits
Main storage capacity
DDR3L SDRAM
2 GB
Auxiliary storage device
SATA SSD
32 GB
Commu-
nications
ETHERNET
Number of lines
1
Communication speed
100/1000 Mbps
Communication method
Auto negotiation, Auto MDI/MDI-X
Material and color of
main parts
Case, base, cover,
fan cover
Modified PPE, black
Door
Modified PPE, silver
Fan bracket
Hot-dipped steel plate (1 mm thick)
Lens
Polycarbonate, transparent
DIN holder
Polyacetal, black
Key top
Aluminum alloy (Al+Mg)
Panel
Polycarbonate board, 2 mm thick, transparent
Anti-static sheet
Polycarbonate board, 0.1 mm, black
Weight
1.4 kg
Environmental
conditions
Rated operating
conditions
Ambient temperature
5–40 °C
Ambient humidity
30–85 % RH (without condensation)
Altitude
2000 m max.
Vibration
3.2 m/s2 max. (10–150 Hz)
Transport
and storage
conditions
Ambient temperature
-20–60 °C
Ambient humidity
30–85 % RH (without condensation)
Vibration
4.9 m/s2 max. (10–150 Hz)
CPU: central processing unit
DDR3L: double data rate type three low voltage
DIN: Deutsches Institut für Normung (German Institute for Standardization)
MDI: medium dependent interface
MDI-X: medium dependent interface crossover
PPE: polyphenylene ether
RTC: real-time clock
SATA: serial ATA
SDRAM: synchronous dynamic random-access memory
SSD: solid-state drive.
z Specifications for Inputs and Outputs
Item
Specification
Digital
input
Number of input terminals
8
Voltage
12 V DC -10/+15 % (with voltage contact)
Current
10 mA DC typ.
Connected device output method
Dry contact or open collector
Digital
output
Number of output terminals
2
Relay output
Output method
Photo MOS relay
Rated contact voltage
12 V DC, 100 mA DC max.
Specifications for Wiring
Item
Wire type
Maximum
cable length
Remarks
Power supply
600 V PVC-insulated cable (IEC 60227-3)/
CVV equivalent, stranded cable,
1.25–2.0 mm2
Daisy chain supported (only for cables with
the same cross-sectional area of 1.5 mm2)
–
Ground
600 V PVC-insulated cable (IEC 60227-3)/
CVV equivalent, stranded cable,
1.25–2.0 mm2
Daisy chain supported (only for cables with
the same cross-sectional area of 1.5 mm2)
–
Ground the product with
resistance less than 100 Ω.
ETHERNET
Twisted pair cable, category 5e
100 m
1000BASE-T cable as
defined in ISO/IEC8802-3,
or equivalent
Direct input
600 V PVC-insulated cable (IEC 60227-3)/
CVV equivalent, stranded cable,
0.5–1.25 mm2
350 m
Direct output
600 V PVC-insulated cable (IEC 60227-3)/
CVV equivalent, stranded cable,
0.5–1.25 mm2
350 m
CVV: control-use vinyl insulated vinyl sheathed cable
External Dimensions
Figure 2. External dimensions (mm)
Name of Parts
Fan
Communication LEDs
USB 2.0 (not used)
Line output (not used)
Operation state LEDs
USB 3.0 (not used)
DO status LED
ETHERNET LAN1
ETHERNET LAN2
(not used)
Display port (not used)
Power switch
Power supply connector
User operation switch
7-segment LED
Power supply connector
LED (not used)
DI status LED
Connector (not used)
DI connector
DO connector
Connector (not used)
DO connector
DI connector
Figure 3. Name of parts
230
80
140
Install this product in a location out of reach of unauthorized people. (e.g. Inside of the control panel with
a lock)
Failure to do so might cause electric shock.
CAUTION
General
Do not drop this product.
Doing so may cause an injury or may damage the device.
General
Install, wire, and use this product under the conditions specified by this manual.
Failure to do so may cause fire or device failure.
General
Installation and wiring must be performed by personnel qualified to do instrumentation and electrical
work.
Mistakes in installation or wiring may cause fire or electric shock.
z Installation Location
This product must be installed in a control panel cabinet.
Note: A unit that satisfies the following conditions is considered to be equivalent to a control panel.
Flame resistance: V-1 or higher (UL 94 standard)
Strength: Enclosure stiffness test (EN 61010-1:2010 8.2)
The control panel should be installed in a place that satisfies the following:
• An indoor place that is not exposed to direct sunlight
• A place that is not near water
Note: The product is not waterproof.
z Installation Angle
• This product should be installed upright in the control panel.
Installation of this product on a slant or laid on its side is prohibited. Doing so reduces heat radiation performance, which
may cause the internal temperature to rise abnormally.
Figure 4. Installation angle
• Do not block the ventilation holes by putting an object on top of the product, etc.
Install vertically
Front
Side
z Installation Method
Figure 5. Example of installation in control panel cabinet
600 mm
1900 mm
700 mm
215 mm from
the panel cabinet
ceiling (highest
level of the
standard layout)
50 mm
50 mm or
more*1
35 mm or more
50 mm or
more*1
35 mm
Fan (Model 83978069-101)
• Install one unit at the top of the panel cabinet.
30 mm
30 mm
30 mm duct
30 mm duct
30 mm duct
• Install it at the top of the panel
(right under the fan).
• Install it upright.
Note: Do not tilt it.
• Check that there is clearance for maintenance.
30 mm duct
Power strip
Clearance above and under the product
Air inlet
0.0174 m2 (198 long oval holes measuring
3 × 30 mm) or larger under the panel door.
40 mm duct
Clearance in front of the product
• When a device from
which hot air is
exhausted is installed
in the same panel,
install the power strip
underneath the
Supervisory
Controller.
To reduce the effects
of heat radiation,
install high-temperature
devices under the
power strip.
• Install the Supervisory
Controller, Advanced
Controller, and devices
that do not generate
heat (switching hub,
power failure recovery
circuit, terminal block,
etc.) in the panel.
• The depth should be
60 mm max.
*1 To place the wiring ducts above and under
this product, make sure to leave a
clearance of 35 mm or more.
35 mm
Supervisory Controller
Model BH-101G0_0000
60 mm duct
(1)
Pull down the two DIN holders on the bottom of the
device.
(2) Hook the upper part of the DIN holder to the DIN rail
and check that it is hooked securely.
(3) Push up the two DIN holders on the bottom of the
device.
(4) Check that the four DIN holders on the top and
bottom of the device are secured on the DIN rail.
Check that the device is steady.
(5) Secure both ends with the DIN rail clamps (Model
83104567-001).
After installation, keep the connectors that come
with the device because they will be used for wiring
connection.
Pull out
Hook
Push up
Install the product on the wall or panel wall using four M4
L=8 screws or four studs with female threads.
(1)
Make four screw holes in the installation locations.
(2) Pull up the two DIN holders at the top of the device
and then pull down the two DIN holders on the
bottom.
(3) Use the four holes for the DIN holder to secure the
device with the M4 screws.
Check that the device is steady.
150 mm
160 mm
Pull out
Pull up
Secure with
an M4 screw
Be sure to ground the product with ground
resistance of less than 100 Ω.
Improper grounding may cause electric
shock or malfunction.
Electric shock
Before wiring or maintenance, be sure to
turn off the power to this product.
Failure to do so may result in electric shock
or device failure.
CAUTION
General
Installation and wiring must be performed
by personnel qualified to do instrumenta-
tion and electrical work.
Mistakes in installation or wiring may cause
fire or electric shock.
General
All wiring must comply with applicable
codes and ordinances.
Otherwise there is a danger of fire.
General
Take anti-noise measures if this product
is installed in a location near source of
electric noise.
Failure to do so may cause malfunction or
device failure.
General
Strip the insulation from cables as speci-
fied in this manual.
If the length of exposed wire is longer than
specified, it may cause electric shock or
short circuit between adjacent terminals.
If it is too short, it may not make proper
contact.
General
Tighten the terminal screws with the spec-
ified torque.
Insufficient tightening of the terminal
screws may cause fire or overheating.
Prohibition
Do not use unused/spare terminals on this
product as relay terminals.
Doing so may cause device failure.
z Notes on Wiring
• Do
not
use
an
uninterruptible
power
supply
that outputs rectangular waves.
Doing so may cause the device to fail.
• Use cable ties so that cables will not hide the LEDs
and switches.
• Do not let the wiring between the cable duct and the
device hang loose.
z Wiring of Power Supply Terminal Block
Screw connectors are used.
(1)
Strip 7 mm of insulation from the cable core wire.
(2) If the connector is plugged into the device, push in
the release levers on the right and left sides of the
connector to remove it from the device.
(3) Turn the screw above the cable clamp (the hole for
the cable) of the connector to the left with a screw-
driver to open the cable clamp.
Note: Compatible screwdriver blade: 0.6 × 3.5 mm
Power supply
connector
7 mm
Push in
Turn the screw to
the left until it stops
to open the clamp.
Opening
(4) Insert the cable whose wire was exposed in step (1)
into the cable clamp and tighten it by turning the
screw above the cable clamp to the right with a
screwdriver.
The screw tightening torque is 0.5 N·m–0.6 N·m.
Make sure there are no strands of cable wire
protruding from the cable clamp.
Note: Check that the cable is inserted into the cable jack.
(5) Lightly pull the cable to check that it does not come
out.
(6) Insert the connector into the device.
Check that the release levers of the connector are
securely locked.
(7) Lightly pull the cable to check that the power supply
connector does not come out.
Terminal No.
Description
1
AC input
2
AC input
3
Ground
Do not insert
the cable here.
Cable clamp
(opening)
z Wiring of the Direct Input Terminal Blocks and
Direct Output Terminal Block
Terminal Nos.
4 to 11
Terminal Nos.
12 to 19
Direct input
(DI) terminal
block
Terminal block
(not used)
Terminal Nos. 24 to 27
Direct output (DO)
terminal block
Terminal Nos. 20 to 23
(1)
Strip 7 mm of insulation from the cable core wire.
(2) If the connector is plugged into the device, push in
the release levers on the right and left sides of the
connector to remove it from the device.
(3) Turn the screw above the cable clamp (the hole for
the cable) of the connector to the left with a screw-
driver to open the cable clamp.
(4) Insert the cable whose wire was stripped in step
(1) into the cable clamp and tighten it by turning
the screw above the cable clamp to the right with a
screwdriver.
Make sure there are no strands of cable wire
protruding from the cable clamp.
(5) Lightly pull the cable to check that it does not come
out.
(6) Insert the connector into the device.
Check that the release levers of the connector are
securely locked.
(7) Lightly pull the cable to check that the power supply
connector does not come out.
Push in
Terminal
No.
Connector
Pin No.
Description (example usage)
4
1
DI CH1 (fire inputs)
5
2
DI CH1 common
6
3
DI CH2 (generator switching
input)
7
4
DI CH2 common
8
5
DI CH3 (power supply status
input)
9
6
DI CH3 common
10
7
DI CH4 (reset alarm output)
11
8
DI CH4 common
12
9
DI CH5 (reserved)
13
10
DI CH5 common
14
11
DI CH6 (reserved)
15
12
DI CH6 common
16
13
DI CH7 (reserved)
17
14
DI CH7 common
18
15
DI CH8 (reserved)
19
16
DI CH8 common
Terminal
No.
Connector
Pin No.
Description (example usage)
20
1
DO CH1 (point alarm)
21
2
DO CH1 common
22
3
DO CH2 (device alarm)
23
4
DO CH2 common
24
5
Not used
25
6
Not used
26
7
Not used
27
8
Not used
z Wiring for ETHERNET
Figure 6
Handling
Do the following before turning the power on.
(1)
Check again that the wiring is done correctly.
(2) Peel off the protective sheets before powering the
device on.
Notes 1. Check that all protective sheets have been peeled off.
2. If foreign substances might get into the product
through holes during the period after the comple-
tion of installation and wiring but before the unit is
powered on, block the ventilation holes with plastic
sheets, etc., on the surfaces (on the sides and
bottom) that are not covered with protective sheets.
Protective sheet
CAUTION
Prohibition
Do not block the ventilation holes of this
product.
Doing so may cause device failure.
ETHERNET LAN1
ETHERNET LAN2
(not used)
Power On/Off
WARNING
Electric shock
Do not touch electrically charged parts.
Doing so may cause electric shock.
IMPORTANT!! • Do not test the withstand voltage of this product.
Doing so may cause the device to fail.
• If more than the rated power voltage is applied to this product, replace the product with a new one.
Failure to do so may result in a malfunction.
In order to retain the minimum required system data, the product has an on-board lithium ion capacitor module.
When no power is supplied due to power failure or power shutoff, the lithium ion capacitor module supplies power for one
second (by default) to maintain functions excluding direct inputs/outputs as a countermeasure against instantaneous power
failure. It then continues supplying power until the status data stored in the memory is transferred to the secondary storage
medium (SSD) as part of the shutdown process.
When power is supplied from the main power supply due to restoration of power or power-on operation, the module is
charged automatically.
• Charge the lithium ion capacitor module by turning on the power for the product within six months of its delivery.
Turning on the power charges the capacitor automatically.
A continuous charge duration of five minutes or less is required for a full charge.
• If a fully charged lithium ion capacitor module has been off for six months or more, it will have fallen below the discharge
stop voltage (6.9 V). Charging the module in this state significantly reduces the part life.
Therefore, if an excessively discharged state is detected, this product stops charging the lithium ion capacitor module
for the sake of safety. The lithium ion capacitor module will no longer be able to be charged.
If the POWER LED does not stop flashing and stays on for 10 minutes after turning the power on when the controller is
already charged, the controller itself must be replaced.
• Do not turn the power on/off frequently.
After it is turned on, wait at least 5 minutes before turning it off.
• If the SVC will not be turned on again for one month or longer, turn it off in shutdown mode.
z Turning OFF the SVC
(1)
Press the [>] button (one of the user operation switches) three times at intervals of less than 1 second.
The shutdown mode will be activated and “” will be displayed.
Note: If the interval is 1 second or longer, the mode will return to automatic mode.
(2)
Press the [ENTER] button.
When the shutdown process is complete, “” will be displayed.
The LEDs and system indicators will be turned off.
Note:
1. Pressing any button except [ENTER] will return the unit to automatic mode. Also, if no button is pressed for 5
seconds or longer, automatic mode will resume.
2. “” will flash every second while shutdown is in process.
(3)
Turn off the power to the SVC.
Figure 7. Indicator positions
Item
Product indicator
Color
State
Description
Power indicator
POWER
Green
Lit
Power ON
Flashing
Power ON
(Lithium ion capacitor module being
charged)
Not lit
Power OFF
System error indicator
ERROR
Red
Lit
Abnormal
Note: Contact Azbil Corporation.
Flashing
Not lit
Normal
Active indicator for redundant
product configuration
ACT
Green
Lit
The device is operating (active).
Not lit
The device is for backup (standby).
Storage access indicator
STORAGE
Green
Lit
The data storage is being accessed.
Not lit
The data storage is not being accessed.
ETHERNET communication
indicator
LAN1 100
LAN2 100 (not used)
Green
Lit
A link is established at 100 Mbps.
Flashing
Data is being received or transmitted at
100 Mbps.
Not lit
A link has not been established.
LAN1 1000
LAN2 1000
(not used)
Green
Lit
A link is established at 1000 Mbps.
Flashing
Data is being received or transmitted at
1000 Mbps.
Not lit
A link has not been established.
System indicator
Indication using
7-segment LED
Blue
Normal
The four 7-segment LEDs are lit in
sequence at their outer edges at an
interval of two seconds.
Abnormal
Indication other than above.
DI status indicator
DI ch1–ch8
Green
Lit
DI status is ON.
Not lit
DI status is OFF.
DO status indicator
DO ch1 and ch2
Green
Lit
DO status is ON.
Not lit
DO status is OFF.
Indicator (not used)
IN
–
OUT
–
LAN1 100 1000
DI1 DI2 DI3 DI4
POWER
DI5 DI6 DI7 DI8
D01 D02
ERROR
ACT
STORAGE
7-segment LED
LAN2 100 1000 (not used)
REDUNDANT IN OUT (not used)
Do not touch electrically charged parts.
Doing so may cause electric shock.
CAUTION
Disassemble
Do not disassemble this product.
Doing so may cause device failure.
General
Before cleaning the product or retorquing
the terminal screws, be sure to turn off the
power to the product.
Failure to do so may cause electric shock,
device failure, or malfunction.
Azbil Corporation personnel who have been trained on
the product will carry out periodic maintenance and parts
replacement.
Please contact us.
Note: Refer to the "Model Numbers" section for details on
replacement parts.
z Notes for Daily Care
• Keep the temperature and humidity environment within
system specifications.
Otherwise, the product life will be affected.
• Keep the area around the system clean.
Otherwise, the life of the fan and other parts will be
affected.
• Do not put devices or other items that cause vibrations
or impact near this system.
Doing so may result in loose electrical connections.
• Do not eat or drink around the system.
Doing so may result in spilled liquid or other unexpected
accident.
z Inspection
Inspect the device for the following problems.
• The product generates abnormal noise.
• The product gives off an unusual odor.
• The fan is not rotating and air is not coming out of the
exhaust vent.
• Dust has built up on the inlet and exhaust vents around
the device.
• A connector has fallen off of the product.
• The display is hard to read.
• If the product generates abnormal noise, the fan may
have failed.
Clean the fan according to "● How to Clean ."
If this does not solve the problem, contact Azbil
Corporation.
• If the product has an unusual odor, possible causes
are dust buildup and failure of internal parts.
Please contact Azbil Corporation.
• If you do not feel air when you put your hand near the
fan, the fan has failed.
Please contact Azbil Corporation.
• If there is dust buildup, clean the fan according to "●
How to Clean ."
• If connectors have fallen off of the product, reconnect
them.
• If the display is hard to read, clean the device according
to "● How to Clean ."
z Notes on Cleaning
• Clean the device according to this manual.
Do not touch the parts and switches not mentioned in
this manual.
Doing so may cause an electric shock or system
shutdown.
z How to Clean
Dust buildup on the fan may cause it to fail, and as a
result, the product may not function normally.
Therefore, clean around the device every three months.
• Vacuum dust around the device using a small vacuum
cleaner or other tool.
• If the fan generates abnormal noise, remove the fan
assembly and vacuum the dust attached to the blades
using a small vacuum cleaner or other tool.
• Clean the surface of the device with cleaner for office
equipment.
Do not use cleaners that contain alcohol, thinner or
similar substances.
• Use the cleaner according to its specified uses and
notes on handling.
z How to Remove and Attach the Fan Assembly
Remove the fan while this product is operating.
CAUTION
General
Before touching this product, be sure to
remove any static electrical charge from
your body.
Otherwise your static electricity may
damage some components of the product.
Static electrical charge can be removed by
touching the grounded metal.
Prohibition
When removing the fan, be sure not to
insert fingers into the product.
Doing so may damage the internal
components.
(1)
Open the door at the top of the device.
(2) Remove the fan cover.
Pull the fan cover toward you while pressing down
on the two triangles on the top of the fan cover.
Door
Open
Fan cover
Pull out
Pull out
(3) Pull the connector out of the fan assembly.
(4) Check that the fan has stopped.
(5) Lift and remove the fan assembly.
(6) Clean the fan assembly using a small vacuum
cleaner or other tool.
(7) Attach the fan assembly by performing the opera-
tion described in step (5) in reverse.
(8) Connect the fan assembly connector.
(9) Place the fan cover over the fan and push it in until it
is in place.
(10) Close the door at the top front of the device.
(11) After attaching the fan, check that air is vented from
the fan cover and that the fan does not generate
abnormal noise.
Fan assembly
Connector
Lift
z Replacement Procedure
Specifications are subject to change without notice.
https://www.azbil.com/
1-12-2 Kawana, Fujisawa, Kanagawa
251-8522 JAPAN
Building Systems Company
20
AB-7333
Rev. 7.0 Mar. 2020
(J: AI-7424 Rev. 5.0)
AB-7333
* ACTIVAL, ACTIVAL +, Infilex, and savic-net are trademarks of Azbil Corporation.
* BACnet is a trademark of American Society of Heating, Refrigerating, and Air-conditioning Engineers (ASHRAE).
* Modbus is a trademark and the property of Schneider Electric SE, its subsidiaries and affiliated companies.
Install this product in a panel cabinet.
Additionally, always keep the panel cabinet accessible only to people with sufficient knowledge concerning electrical equipment.
This product complies with the following harmonised standards of the Electromagnetic Compatibility Directive (EMCD), the Low Voltage
Directive (LVD) and the Restriction of the use of certain Hazardous Substances in Electrical and Electronic Equipment Directive (RoHSD).
EMCD : EN 61326-1 Class A, Table 2 (for or use in an industrial electromagnetic environment)
LVD
: EN 61010-1 Overvoltage category II
Pollution degree 2
RoHSD : EN 50581
Class A (Broadcasting Communication Equipment for Office Use)
As an electromagnetic wave equipment for office use (Class A), this equipment is intended to use in other than home area. Sellers or users
need to take note of this.