Azbil Intelligent Component Series Specifications & Instructions

Specifications

Brand: Azbil
Category: Controller
Model: Intelligent Component Series (Specifications & Instructions)
File Type: PDF
File Size: —
Pages: 20

Read Online

Read the Azbil Intelligent Component Series Specifications & Instructions online using the built-in PDF viewer.

Text of the manual

Intelligent Component Series

ACTIVAL™ Motorized Two-Way Valve with Flanged-End Connection (JIS 10K / FC200, SCS13A) (Spring Return Type Actuator) General ACTIVAL™ Models VY516XK and VY616XH are series of motorized two-way valves with flanged-end connection. Rotary valve and actuator are integrated in a single unit. Valve size ranges from DN15 (1/2”) to DN80 (3”), and valve body rating corresponds to JIS 10K. Actuator has a reversible synchronous motor, which operates at a low voltage of 24 V AC. Since the actuator fully closes the valve in case of power failure, it is suitable for failsafe application. Model VY516XK/VY516XH communicates with a controller via SAnet (Azbil Corporation’s communication protocol). ∗ Note JIS: Japanese Industrial Standards Features • Compact and lightweight: Rotary valve actualizes small body and light weight. • Valve and actuator integrated in a single unit: • SAnet communication: Intelligent Component Series ACTIVAL communicates with a controller via SAnet, and thus position control signal/position feedback signal is input/output from/to the controller. • Valves for chilled/hot water control and for steam control applicable to large Cv value, high rangeability, and low leakage. • Durable actuator with low power consumption. • Equal percentage flow characteristic. • Spring return actuator: Actuator automatically closes the valve in 0 % position in case that the power is down. • Interlock signal input to fully close the valve: Interlock input signal to forcibly close the valve in 0 % position is provided. • Sub-DO for wire saving: Sub-DO (digital output) provided takes a signal, including a humidifying output of a neighboring device, leading to wire saving. • CE Marking certified product: Models VY516XK and VY516XH conform to all the applicable standards of CE Marking.

Please read instructions carefully and use the product as specified in this manual. Be sure to keep this manual near by for ready

reference. Usage Restrictions This product is targeted for general air conditioning. Do not use this product in a situation where human life may be affected. If this product is used in a clean room or a place where reliability or control accuracy is particularly required, please contact Azbil Corporation’s sales representative. Azbil Corporation will not bear any responsibility for the results produced by the operators.  WARNING  • DANGER: To prevent the risk of severe or fatal electrical shock, always disconnect power source and product power supply before performing any wiring.  • Be sure to reattach the terminal cover after wiring and engineering work. Without the terminal cover, electrical shock may occur.  • This product weighs 18 kg or over (depending on the models). To prevent hazardous accident and severe injury, move or carry the product with enough manpower or using a vehicle.  • Do not disassemble the product. Disassembly may result in electrical shock or equipment damage.  • Do not disassemble the spring unit of the actuator. The spring may rotate too fast or jump out of the actuator due to disassembly, resulting in severe injury.  • Do not detach the actuator from the valve in open position. Detaching the actuator in open position may cause severe injury.  CAUTION (1/2)  • This product must be operated under the operating conditions (power, temperature, humidity, vibration, installation position, atmospheric condition, etc) specified in this manual to prevent equipment damage.  • This product must be operated within its rated operating ranges specified in this manual. Failure to comply will cause equipment damage.  • Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.  • Avoid application that keeps the operating cycle of the product excessively frequent. Excessively frequent operation may cause fire or equipment failure. Service life of the actuator spring is 30,000 returns. Do not keep using the product beyond the service life.  • All wiring must comply with local codes of indoor wiring and electric installation rules.  • Install externally the protective device such as fuse or circuit breaker for your safety.  • Do not touch the moving parts of the product to prevent personal injury.  • Install the product in the position as specified in this manual. Excessively tight connection of the valve to a pipe and improper installation position may damage the valve.  • After installation, make sure no fluid leaks from the connecting parts of valve and pipes. Incorrect piping may cause fluid leakage.  • Do not allow any foreign substance inside the piping. Flush the piping so that no foreign substance remains. Attach a strainer in a pipe on the inflow side of the product to prevent equipment damage.  • Avoid using the product in an atmosphere containing oxidizing gas, explosive gas, etc. since it may damage the actuator, valve, or their components.  • Do not leave the controlled fluid frozen to prevent equipment damage or fluid leakage.  • Do not put heavy load on the actuator.  • User full gaskets for the flat-face flange type valve.  • Do not install the product nearby a steam coil or a hot-water (in high temperature) coil. High heat radiation may result in an actuator malfunction.  • Avoid touching the installed product. When being used to control hot water or steam, it may reach high temperature and may cause burn injury.

Use crimp terminal lugs with insulation for electric wires to be connected to the screw terminals.

 • Make sure all the wires are tightly connected to the screw terminals. Loose connection may cause fire or heat generation.  • Do not stack unpacked products. Piled products without package will be polluted or damaged.  • Dispose of this product as an industrial waste in accordance with your local regulations. Do not reuse all or part of this product. Trademark information: ACTIVAL, Infilex, and savic-net are trademarks or registered trademarks of Azbil Corporation in Japan or in other countries. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). KPEV is a registered trademark of Furukawa Electric Co., Ltd. System Configurations Notes: ∗ MIS may be used instead of SMS and DSS for your system. Note that MIS cannot be mixed with SMS or DSS in the same system. ∗ Up to two SAnet I/F (interface) module can be connected to one Infilex GC/Infilex GD. ∗ For detailed specifications of SAnet, refer to Installation Manual of Intelligent Component Series for SAnet Communication (AB-6713). ∗ 1 ACTIVAL or 1 damper actuator requires 1 SAnet address. 1 ACTIVAL PLUS requires 2 SAnet addresses. Figure 1. System configuration example: SAnet connection in savic-net™ FX system MIS DSS: Data Storage Server MIS: Management Integration Server PMX-III: PARAMATRIX™-III SCS: System Core Server SMS: System Management Server SCS SMS Infilex™ AC Model WY5117C Infilex™ GC Model WY5111 Infilex™ GD Model WY5110 PMX-III Model WY2001 Infilex™ FC Model WY5205 Infilex™ VC Model WY5206 Neopanel Model QY7205 (Digital user terminal) Neoplate Model QY7290 (Analog user terminal) NC-bus (Max. 25 units and 500 m, but extendable up to 1000 m with the repeater module.) SC-bus (Max. 50 units and 1000 m) BACnet®/IP DSS SAnet I/F Intelligent Component Series ACTIVAL™ Infilex™ ZM Model WY5122 SAnet (Max. 15 addresses) Intelligent Component Series Damper actuator Display Panel Intelligent Component Series ACTIVAL™ PLUS Temperature sensor for pipe surface

Models VY516XK00XX and VY516XH00XX are the models for the valve and actuator integrated into a single unit.

The model number label is attached to the yoke. Actuator/valve Actuator Valve Base model number Control signal Rating/ material Type ⎯ Nominal size/Cv ⎯ Description VY51 Motorized two-way valve with flanged-end connection 6 SAnet 5 JIS 10K / JIS FC 200 6 JIS 10K / JIS SCS13A K IEC IP54 protected, standard torque, and spring return type actuator with terminal block for standard differential pressure application (Mountable valve sizes: DN15 to DN80) H IEC IP54 protected, standard torque, and spring return type actuator with terminal block for high differential pressure application (Mountable valve sizes: DN65 to DN80) 00 Fixed 11 DN15 (1/2”) / 1.0 in Cv value 12 DN15 (1/2”) / 2.5 in Cv value 13 DN15 (1/2”) / 6.0 in Cv value 14 DN15 (1/2”) / 1.6 in Cv value 15 DN15 (1/2”) / 4.0 in Cv value 21 DN25 (1”) / 10 in Cv value 22 DN25 (1”) / 16 in Cv value 41 DN40 (1 1/2”) / 25 in Cv value 42 DN40 (1 1/2”) / 40 in Cv value 51 DN50 (2”) / 65 in Cv value 61 DN65 (2 1/2”) / 95 in Cv value 81 DN80 (3”) / 125 in Cv value -B Fixed ∗ Note: To use DN65 and DN80 models for chilled/hot water or high temperature water control, high differential pressure type (Model VY516XH) is only applicable.

For weight, refer to the table shown in the section Dimensions.

Valve specifications Item Specification Type Two-way valve with flanged-end connection, proportional control Body pressure rating JIS 10K (Max. working pressure: 1.0 MPa) Close-off ratings Model number Nominal size Cv Steam Chilled/hot water High temperature water VY516XK0011 DN15 (1/2”) 1.0 1.0 MPa 1.0 MPa VY516XK0012 DN15 (1/2”) 2.5 1.0 MPa 1.0 MPa VY516XK0013 DN15 (1/2”) 6.0 1.0 MPa 1.0 MPa VY516XK0014 DN15 (1/2”) 1.6 1.0 MPa 1.0 MPa VY516XK0015 DN15 (1/2”) 4.0 1.0 MPa 1.0 MPa VY516XK0021 DN25 (1”) 10 1.0 MPa 1.0 MPa VY516XK0022 DN25 (1”) 16 1.0 MPa 1.0 MPa VY516XK0041 DN40 (1 1/2”) 25 1.0 MPa 1.0 MPa VY516XK0042 DN40 (1 1/2”) 40 1.0 MPa 1.0 MPa VY516XK0051 DN50 (2”) 65 1.0 MPa 1.0 MPa VY516XK0061 DN65 (2 1/2”) 95 0.3 MPa ⎯ VY516XK0081 DN80 (3”) 125 0.1 MPa ⎯ VY516XH0061 DN65 (2 1/2”) 95 1.0 MPa 0.7 MPa Size, Cv, Close-off rating Note: Close-off ratings of the actuator in combination are shown on the right. Practical close-off rating required for the valve controlling 175 °C steam is 0.8 MPa. VY516XH0081 DN80 (3”) 125 0.7 MPa 0.4 MPa Body Gray cast iron (equivalent to JIS FC200) for Model VY5165 Cast stainless steel (equivalent to JIS SCS13A) for Model VY5166 Plug, stem Stainless steel (equivalent to JIS SCS) Seat ring Heat-resistant PTFE Gland packing Inorganic fiber Materials Gasket Non-asbestos joint sheet End connection JIS 10K flanged-end, flat face flange (FF) for Model VY5165 raised face flange (RF) for Model VY5166 Applicable fluid Chilled/hot water, high temperature water, steam, brine (ethylene glycol solutions, 50 % max.) Allowable fluid temperature 0 °C to 175 °C* (Non-freezing) Flow characteristic Equal percentage Rangeability 100 : 1 Seat leakage 0.01 % of rated Cv value (0.0006 Cv or less for DN15 model) Paint Gray (equivalent to Munsell 5B 4/1): Model VY5165 (Gray cast iron valve body) Unpainted: Model VY5166 (Cast stainless steel valve body) Actuator to be combined Integrated with the valve ∗ Note: To use the stainless steel valve for fluid of temperature below 0 °C, consult with our sales personnel.

24 V AC ± 15 %, 50 Hz/60 Hz

Type Spring return actuator for standard/high differential pressure application Power consumption 15 VA or less in operating state, 10 VA or less in non-operating state Timing 63 ± 5 sec (50 Hz) / 53 ± 5 sec (60 Hz) Return time: 3 to 40 seconds (fully open → fully close operation) Control signal SAnet Input type Potential free (dry) contact input Forced fully-close input (contact input) Voltage, current 20 V DC, 5 mA (∗ This contact input is only for interlock operation.) Output type Potential free (dry) contact output Contact rating 200 V AC/30 V DC, Max. 0.5 A (2 A at startup) Sub-DO (contact output) Min. applicable load 24 V DC, 5 mA LED indication Description Initializing Continuous ON → LED indication corresponding to the operating status (after initializing is complete.) Normal Repetition of 1-second ON → 1-second OFF. Major alarm Continuous ON. Minor alarm Repetition of 1-second ON → 0.25-second OFF → 0.25-second ON → 0.25-second OFF. Communication error (and minor alarm) Repetition of 0.25-second ON → 0.25-second OFF Manual operation Repetition of 0.25-second ON → 0.25-second OFF → 0.25-second ON → 1.25-second OFF. Error during manual operation Repetition of 0.25-second ON → 0.25-second OFF → 0.25-second ON → 0.25-second OFF → 0.25-second ON → 0.75-second OFF. Communication Transmission system Voltage transmission (SAnet) (via SAnet) Transmission speed 1200 bps Transmission distance Transmission distance varies depending on the number of devices and the type of devices to be connected to. For details on the transmission distance, refer to Installation Manual of Intelligent Component Series for SAnet Communication (AB-6713). Case Die cast aluminum Top cover, terminal cover Polycarbonate resin (Color: gray) Yoke Steel plate Case and cover of spring unit Die cast aluminum Materials Spring Stainless steel Case None Surface finishing Yoke Electro-galvanized (Bright chromate finish) Valve position indication Pointer located at the bottom of the actuator shows the position by pointing at the value of the scale (0: close to 100: open) on front, rear, and bottom sides. Manual operation Not available. Terminals connection M3.5 screw terminal connection Enclosure rating IEC IP54 (dust-proof and splash-proof) Insulation resistance Between terminal and case: 5 MΩ or higher at 500 V DC Dielectric strength Between terminal and case: 500 V AC/min with 0.5 mA or less leakage current Service life of spring return operation 30,000 operations 0.25s 0.25s 0.25s 0.25s 0.25s 0.75s ON OFF 0.25s 0.25s 0.25s 1.25s ON OFF 0.25s 0.25s 0.25s 0.25s 0.25s 0.25s ON OFF 0.25s 1s 0.25s 0.25s 0.25s ON OFF 1s 1s ON OFF

Valve and actuator (as a single unit) specifications

Item Specification Environmental conditions Rated operating condition Limit operating condition Transport/storage conditions (packaged* 2) -20 °C to 50 °C (Fluid temperature 0 °C to 150 °C) Ambient temperature* 1 -20 °C to 40 °C (Fluid temperature 150 °C to 175 °C) -20 °C to 60 °C -20 °C to 70 °C Ambient humidity 5 %RH to 95 %RH Vibration 4.9 m/s 2 (10 Hz to 150 Hz) 9.8 m/s 2 (10 Hz to 150 Hz) 19.6 m/s 2 (10 Hz to 150 Hz) Notes: ∗1 Do not allow the fluid to freeze. ∗2 Actuator shall be packed during transport. Installation locations Indoor / outdoor (Keep away from direct sunlight.) Installation orientation Installable in any position ranging from upright to sideways (90° tilted.) * Always install in upright position outdoors. Position for shipment 0 % (fully closed) preset at factory. Function Function Specification Data monitoring Following items can be monitored/operated from the host system (savic-net FX) and Infilex GC/Infilex GD. Valve position setting, valve position measuring, sub-DO output, sub- DI monitoring ∗ Note: Above function is available in combination with Infilex GC/Infilex GD and savic-net FX. Wire specifications For details regarding specifications of SAnet communication line (24 V (∼), GND (⊥), SAnet), refer to the Installation Manual of SAnet for Intelligent Component Series (AB-6713). Item Specification Length Contact input (sub-DI) JIS CVV, JIS VCT, JIS IV, KPEV for low power 0.75 mm 2, 0.9 mm 2, 1.25 mm 2, 2.0 mm 2 30 m Contact output (sub-DO) JIS CVV, JIS VCT, JIS IV, KPEV for low power 0.75 mm 2, 0.9 mm 2, 1.25 mm 2, 2.0 mm 2 30 m Note ∗ KPEV: Wire standard provided by Furukawa Electric Co., Ltd. Ambient temperature (°C) 50 40 -20 100 175 150 0 Fluid temperature (°C)

For options, separate order is required.

Item Specification Note Part No. 83104346-003 Applicable wire size: φ7 mm to φ9 mm Part No. 83104346-004 Applicable wire size: φ9 mm to φ11 mm Seal connector Part No. 83104346-005 Applicable wire size: φ11 mm to φ13 mm Seal connector is necessary for IEC IP54 protection. Part No. 83104346-012 Applicable wire size: φ6 mm to φ8 mm Part No. 83104346-013 Applicable wire size: φ7 mm to φ9 mm Seal connector for SAnet cable gland Part No. 83104346-014 Applicable wire size: φ9 mm to φ11 mm Seal connector for SAnet cable gland with three ports is necessary for IEC IP54 protection. SAnet cable gland with three ports Part No. DY7000A1000 For the specifications of SAnet cable gland with three ports, refer to the Specifications (AS-923E). For the installation of SAnet cable gland with three ports, refer to the Installation Manual of Intelligent Component Series for SAnet Communication (AB-6713). Outdoor cover Part No. DY3001A1017 Required when the product is installed outdoors. Hot-rolled steel (JIS SS4400), electro-galvanized/not electro-galvanized Electro-galvanized Not electro-galvanized Applicable valve size Part No. 83168456-001 Part No. 83168456-101 DN15 Part No. 83168456-002 Part No. 83168456-102 DN25 Part No. 83168456-003 Part No. 83168456-103 DN40 Part No. 83168456-004 Part No. 83168456-104 DN50 Part No. 83168456-005 Part No. 83168456-105 DN65 Valve flange adapter kit (for replacing Model V5063/V5064 with Model VY51XX) Part No. 83168456-006 Part No. 83168456-106 DN80 CE Marking Conformity This product complies with the following Electromagnetic Compatibility (EMC). EMC : EN61000-6-2, EN55011 Class A

Figure 2. Dimensions and maintenance clearance (mm): Models VY5165K00XX

Model VY5165H00XX Model number Valve size (DN) H (mm) H1 (mm) L (mm) L1 (mm) t (mm) φC (mm) φD (mm) φh (mm) N Weight (kg) VY5165H0061 65 314 124 190 90 22 140 175 19 4 18.5 VY5165H0081 80 315 125 203 100 22 150 185 19 8 21.0 Figure 3. Dimensions and maintenance clearance (mm): Models VY5165K00XX Note: Leave enough clearance for maintenance and wire connection after installation. 600 mm or more clearance is recommended. Install the product in a location where address setting inside the cover can visually be checked. 70 70 H H1 190 L t φC φD Flow direction Min. 600 82 85 Min. 300 Min. 300 N × φh Min. 300 Min. 300 L1 Note: Leave enough clearance for maintenance and wire connection after installation. 600 mm or more clearance is recommended. Install the product in a location where address setting inside the cover can visually be checked. 70 70 H H1 190 L t φC φD Flow direction Min. 600 82 85 Min. 300 N × φh Min. 300 Min. 300 L1 Min. 300

φC (mm) φD (mm)

φg (mm) φh (mm) N Weight (kg) VY5166K001X 15 265 75 108 50 12 70 95 51 15 4 6.6 VY5166K002X 25 280 90 127 60 14 90 125 67 19 4 8.6 VY5166K004X 40 293 103 165 82.5 16 105 140 81 19 4 12.0 VY5166K0051 50 297 107 178 89 16 120 155 96 19 4 13.5 VY5166K0061 65 314 124 190 90 18 140 175 116 19 4 18.0 VY5166K0081 80 315 125 203 100 18 150 185 126 19 8 20.5 Figure 4. Dimensions and maintenance clearance (mm): Model VY5166K00XX Model VY5166H00XX Model number Valve size (DN) H (mm) H1 (mm) L (mm) L1 (mm) t (mm) φC (mm) φD (mm) φg (mm) φh (mm) N Weight (kg) VY5166H0061 65 314 124 190 90 18 140 175 116 19 4 18.5 VY5166H0081 80 315 125 203 100 18 150 185 126 19 8 21.0 Figure 5. Dimensions and maintenance clearance (mm): Models VY5166K, VY5166H Note: Leave enough clearance for maintenance and wire connection after installation. 600 mm or more clearance is recommended. Install the product in a location where address setting inside the cover can visually be checked. H L Min. 300 Note: Leave enough clearance for maintenance and wire connection after installation. 600 mm or more clearance is recommended. Install the product in a location where address setting inside the cover can visually be checked. H L t φg φC φD Min. 300 L1 70 70 H1 190 Flow direction Min. 600 82 85 Min. 300 N × φh Min. 300 Min. 300 70 70 H1 190 t φg φC φD Flow direction Min. 600 82 85 N × φh Min. 300 Min. 300 L1 Min. 300

Figure 6. Parts identification

Top cover Terminal cover Knockout hole Yoke Actuator Valve body Pointer Spring unit O-ring Packing Stem Seat ring Spring Plug : Heat insulation Spring unit

Precautions for installation

 CAUTION  • Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.  • Install the product in the position as specified in this manual. Excessively tight connection of piping and improper installation position may damage the valve.  • Do not allow any foreign substance inside the piping. Flush the piping so that no foreign substance remains. Attach a strainer in a pipe on the inflow side of the product to prevent equipment damage. • ACTIVAL Model VY516XK/VY516XH is the valve and actuator integrated into a single unit. Do not combine the valve with any other actuator, or do not combine the actuator with any other valve. • To remove foreign substances inside the pipes, install a strainer with 40 or more meshes (with 80 or more meshes recommended for steam control) on the inflow side of each valve. In case that the strainers cannot be installed on the inflow side of each valve, install it on the pipe diverting sections (sections diverting from main piping system to sub piping system). • Install the valve so that the flow direction of process fluid agrees with the arrow indicated on the valve body. Installation location  CAUTION  • Avoid using the product in an atmosphere containing oxidizing gas, explosive gas, etc. since it may damage the actuator, valve, or their components.  • Do not install the product nearby a steam coil or a hot-water (in high temperature) coil. High heat radiation may result in an actuator malfunction. IMPORTANT: • The top and the terminal covers might be corroded by chemicals and organic solvent or their vapor. Do not expose the ACTIVAL to such substances/vapor. • When the ACTIVAL is used for steam humidifying, install a valve interlocking with air-conditioning unit on the inflow side in case the ACTIVAL gets damaged. • Although the ACTIVAL can be used in high humidity environments (max. 95 %RH), do not immerse the actuator in water. • Although the ACTIVAL can be used outdoors, be sure not to expose the ACTIVAL to direct sunlight. • When the ACTIVAL is used for steam humidifying, set the high limit alarm of supply air temperature in case that the valve fails to properly operate. For critical piping system, in addition to the high limit alarm of supply air temperature, set the high and low limit alarms of humidity for AHU (air handling unit) operation, and install a valve interlocking with the AHU fan on the inflow side. • Install the ACTIVAL in a position allowing easy access for maintenance and inspection. Figs. 2 and 3 show the minimum clearance for maintenance and inspection. When installing the ACTIVAL in a ceiling space, provide an access hole within the 50 cm radius of the ACTIVAL. And, place a drain pan under the valve. • Do not mount the ACTIVAL on a pipe where water hammer occurs, or where solid objects including slug may accumulate. Mounting position The ACTIVAL can be mounted in any position ranging from upright to sideways (90° tilted). The ACTIVAL should be installed with its actuator vertically positioned above the valve body. (See Fig. 7.) However, the ACTIVAL must be installed always in upright position outdoors. Figure 7. Actuator mounting position Correct mounting Incorrect mounting

Check that the model number of the product is what you ordered. The model number is shown on the label attached to the

yoke. • Install a bypass pipe and gate valves on the inflow, outflow, and bypass sides. Also, install a strainer with 40 or more meshes (with 80 or more meshes recommended for steam control) on the inflow side. • When installing the ACTIVAL to the pipes, do not allow any object, such as chips, to get inside a pipe or valve. Valve cannot fully close, or the valve seat may get damaged causing fluid leakage, due to an object jammed inside the valve. • When piping, do not apply too much sealing material, such as solidifying liquid and tape, to the pipe connection sections so that these materials flow into the valve. Valve cannot fully closes, or the valve seat may get damaged causing fluid leakage, due to the sealing material jammed inside the valve. • Before activating the ACTIVAL, fully open the valve (in 100 % position) and flush the pipes (with the ACTIVAL installed) at the maximum flow rate to remove all the foreign substances. (Factory preset position: 0 %) • For steam control, drain retained water (condensate) in piping. Install a trap on a pipe run which may retain condensate. Condensate may cause water hummer or damage the valve and piping. Heat insulation Do not apply heat insulation to the actuator or to the yoke, as shows in Fig. 6. If the yoke and the actuator are covered with insulation material, the pointer cannot be checked and may be distorted. Factory preset position The actuator shaft is positioned at 0 % (in fully closed position) for shipment. The shaft is thus completely turned counterclockwise, and the pointer points at ‘0’. (See Fig. 8.) Figure 8. Pointer position for shipment Pointer

DANGER: To prevent the risk of severe or fatal electrical shock, always disconnect power source and product

power supply before performing any wiring.  CAUTION  • Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards. IMPORTANT: • The ACTIVAL is designed for 24 V AC power supply voltage. Do not apply any other power voltage (e.g., 100 V AC, 200 V AC) to the ACTIVAL. • To prevent damage, cover the terminals except when connecting/disconnecting wires. • Do not leave any refuse including metal chips after cutting a knockout hole and after connecting the wires inside the actuator. Wiring precautions 1) To lead the wires into the terminals, cut out a knockout hole for a wiring port. Two knockout holes (φ22 mm) are provided on the bilateral sides of the actuator terminals. Select a knockout hole according to the conduit mounting direction, and cut it out by lightly knocking the hole using a screwdriver. Figure 9. Knockout hole for wiring port 2) Unscrew the 3 setscrews (M4 × 10) of the terminal cover and remove the terminal cover, as shown in Fig. 10. Figure 10. Terminal cover removal Knockout hole for wiring port 2. Remove terminal cover. Terminal cover 1. Unscrew the setscrews. Setscrews Shorting bar ∗ Shorting bar is connected to the terminals 4 and 5. Do not bend the jumper. Otherwise, it may touch a connected wire or housing causing error.

3) Correctly connect the wires to the terminals with M3.5 screw terminal lugs, referring to Fig. 11.

Figure 11. Basic connection example If 100 V AC or more is output from the sub-DO terminals (6 and 7), be sure to ground with 100 Ω or lower ground resistance. To use the forced shutoff DI, remove the shorting bar connected to the terminals 4 and 5. 4) Separate sub-DO line from SAnet and sub-DI lines. Do not lead the sub-DO line through the wiring port (knockout hole) for SAnet and DI lines to protect sub-DO line from noise. Figure 12. Separation of sub-DO line from other lines If sub-I/O is used, SAnet line cannot be daisy-chained since the number of the wiring ports is limited. In such a case, use SAnet cable gland with three ports to daisy-chain the SAnet line, or branch the SAnet line ahead of connecting to the terminals. Note: For wiring of SAnet line, refer to the Installation Manual of Intelligent Component Series for SAnet Communication (AB-6713) To keep IP54 protection (dust-proof and splash-proof), Use a water-proof connector for the ACTIVAL in a high-humidity environment or outdoor location. Through wiring port with the water-proof connector (Seal connector) attached to, only 1 cable can be lead in. Through wiring port with the SAnet cable gland (with three ports) and the seal connectors attached to, 3 cables can be lead in. • Be sure to completely close the terminal cover and the top cover. • Waterproof the wiring port. - For cable connection, use a water-proof connector. (Seal connector Part Nos. 83104346-003, 83104346-004, 83104346-005 are recommended.) - To daisy-chain the SAnet line, use the SAnet cable gland with three ports and the seal connector Azbil Corporation supplies. SAnet cable gland with three ports: Part No. DY7000A1000 Seal connector: Part Nos. 83104346-012, 83104346-013, 83104346-014 - For conduit connection, use a water-proof plica tube or the like. 1 2 3 4 5 6 7 ∼ ⊥ SAnet 24 V AC DI SAnet Humidifier ∼ DO Cable Thermostat, differential pressure switch, etc. Actuator of Model VY516XK/ Model VY516XH 3-core 2-core Actuator of Model VY5162J SAnet Filter alarm, etc. 5-core ∼ ⊥ SAnet DI DO Joint box

Address Setting (Addressing)

To SAnet interface module, ACTIVAL Model VY516XK/VY516XH and other Intelligent Component Series devices including ACTIVAL PLUS and damper actuators are connected via SAnet. Set address for the terminal devices (Intelligent Component Series devices) so that the SAnet interface module can recognize all the terminal devices connected. Follow the procedure below to set the address. For details regarding address setting (addressing), ask our sales/service personnel. 1) Unscrew the setscrews and remove the terminal cover. See Fig. 10 for removing the terminal cover. 2) Set address. (See Table 1.) Address can be set with rotary switch, with service pin switch, or based on SAnet ID. Rotary switch and service pin switch are provided on this product. To set the address with rotary switch or based on SAnet ID, Data Setter or PC-MMI is required. Set the address in either way according to your availability. Setting with rotary switch: Turn the rotary switch using a precision screwdriver and set. Setting with service pin switch: 1. Set the rotary switch to ‘0’. 2. Start addressing operation* of Data Setter or PC-MMI. Then, press the service pin switch. Do not keep the switch pressed for longer than 5 seconds. 3. Address is set within 5 seconds after pressing the service pin switch. ∗ For the addressing operation of Data Setter or PC-MMI, ask our sales/service personnel. Setting based on SAnet ID: 1. Set the rotary switch to ‘0’. 2. With Data Setter or PC-MMI, enter the SAnet ID (on the product code label) and address number to set. The product code label is attached on the side surface of the actuator, as shown in Fig. 12. ∗ For the addressing operation of Data Setter or PC-MMI, ask our sales/service personnel. 3) Attach the terminal cover after setting the address. IMPORTANT: • While the terminal cover is removed, do not touch the terminal block or allow anything to touch the terminal block. • If the service pin switch is kept pressed for more than 5 seconds, address setting mode will be switched and address will not be set. In such a case, press the service pin switch again and keep it pressed for more than 10 seconds to go back to the normal mode. LED Service pin switch (for Data SEtter/PC-MMI) Rotary switch Terminal block Ground terminal Figure 13. Terminal block, LED, setting switches (without terminal cover) Figure 14. SAnet ID on the product code label SAnet ID

Table 1. Basic address setting of this product and other Intelligent Component Series devices

Add. Device Sub-DO Sub-DI 1 Outdoor air damper 2 Exhaust air damper 3 Return air damper 4 Switch damper of total heat exchanger for outdoor air 5 Switch damper of total heat exchanger for exhaust air 6 Chilled/hot water valve / Chilled water valve Filter alarm 7 Hot water valve (Chilled water valve*) Humidifying ON/OFF 8 Humidifying valve Forced fully-close input D (13) Reserved E (14) Reserved F (15) Reserved Notes: ∗ For ‘chilled/hot water valve + chilled water valve’ application, set address 6 for chilled/hot water valve and 7 for chilled water valve. ∗ Items in bold characters are the basic address to set for this product. ∗ The above table is a basic setting example. Set address and use sub-I/O in response to system configuration, installation location, and wiring best suitable for your application. ∗ Forced shutoff DI is for interlock operation of the spring-return type Model VY516XK, VY516XH. (Not available for the non- spring-return type Model VY516XJ). System Indication Label A part of the product code label can be a system indication label. Clip the part, and write down the name of the system, host controller number of the system, SAnet line number, and address. Then attach the part, as the system indication label, to a location where you can easily check. Figure 15. SAnet system indication label IMPORTANT: • Attach the system indication label to a clean location with no dust, oil, or moisture. • Attach the system indication label by pressing the whole surface of the label to stick on the product surface. Clip and write down the following. • SYSTEM NAME: System name or device number • CON No.: Host controller number (Infilex GC/Infilex GD number) • SAnet No.: SAnet line number • ADDRESS: SAnet address System indication label

Manual Operation Mode

In the manual operation mode, even when this product has not been connected via SAnet yet, the operations shown in Table 2 can be performed. Follow the procedure below for the operation check. For the locations of the service pin switch and the rotary switch, see Fig. 11. 1) Keep the service pin switch pressed for 10 seconds to enter the manual operation mode. 2) Turn the rotary switch to the desired position (See Table 2.), using a precision slotted screwdriver. Operation will start in 3 seconds after setting the rotary switch. Table 2. Operations in the manual operation mode Rotary switch scale Operation 0 Restart (to go back to the normal operation mode) 2 Fully close (in 0 % position) 4 Open in 50 % position 6 Fully open (in 100 % position) 8 Spring return operation check A Cancel of spring return operation check E Automatic adjustment of the potentiometer. Notes: ∗ Rotary switch scales 1, 3, 5, 7, 8, 9, B to D and F are not available in the manual operation mode. ∗ Do not set the rotary switch to ‘E’. (Operation of the rotary switch ‘E’ is required only when potentiometer itself is replaced.) 3) After the operation, press and hold the service pin switch for 10 seconds to go back to the normal operation mode. 4) If the address is set with the rotary switch, be sure to reset the rotary switch at the address after entering the normal operation mode. Interlock Operation This product (Model VY516XK/VY516XH) has the forced shutoff DI (contact input) for interlock operation. Connect the input signal line for start/stop of air-conditioning unit in a critical steam-humidifying system. Operation with the forced shutoff DI is as follows: When the contact opens, the actuator forcibly closes the valve in 0 % position. When the contact closes, the actuator continues normal operation. Jumper is connected to the terminals 4 and 5. Remove the jumper to connect the forced fully-close signal input line. Note that the forced fully-close input is for interlock operation and cannot be used for any other purpose. Interlock operation due to disconnection of SAnet communication When SAnet communication is disconnected for a certain time period, this product recognizes abnormal condition and forcibly starts shutoff operation. Notes: ∗ Forced shutoff DI is applicable only for Model VY516XK/VY516XH ACTIVAL (spring-return type). This is not applicable for ACTIVAL Model VY516XJ ∗ To forcibly shut off the valve, interlock the operation with the forced shutoff DI. Do not interlock with disconnection of SAnet communication. ∗ In the manual operation mode, the product does not forcibly start shutoff operation even when SAnet communication is disconnected for a certain time period. But when the forced shutoff contact opens in the manual operation mode, the products forcibly starts the shutoff operation. Table 3. Interlock operation with the forced shutoff DI Normal operation mode Manual peratoin mode mode Forced fully-close input * (4) and (5) are terminal numbers SAnet communicating SAnet disconnected (for longer than a certain period) SAnet communicating SAnet disconnected (for longer than a certain period) Contact open Forced shutoff Forced shutoff Forced shutoff Forced shutoff Contact closed Normal operation Normal operation Normal operation Normal operation (4) (5) (4) (5)

Inspection and Troubleshooting

 CAUTION  • Avoid touching the installed product (valve body, yoke, joint). When being used to control hot water, it reaches high temperature and may cause burn injury. • Inspect the ACTIVAL according to Table 4. • Visually inspect the fluid leakage of the valve and the actuator operations every six months. If any of the problems described in Table 5 are found, take corresponding actions shown in the table. If your problem is not solved by the corresponding action, please contact Azbil Corporation near you. Table 4. Inspection items and details Inspection item Inspection interval Inspection detail Visual inspection Semiannual • Fluid leakage from the gland and the flange face • Loosened bolts • Valve and actuator damages Operating status Semiannual • Unstable open/close operation • Abnormal noise and vibration • Incomplete spring return operation when power is off • Slow spring return operation (taking longer than the rated time (8 to 60 seconds)) Routine inspection Any time • Fluid leakage to the outside • Abnormal noise and vibration • Unstable open/close operation • Valve hunting Table 5. Troubleshooting Problem Part to check Action Fluid leaks from the flange face. Loosened flange bolts Gasket on the flange face Misaligned piping Tighten the flange bolts. Replace the gasket. Redo piping. Fluid leaks from the gland part. ⎯ Consult with our sales/service personnel. Fluid leaks from the bonnet. Loosened bolts Tighten the bolts. Valve does not operate smoothly / valve stops halfway / valve does not operate at all. Conditions of the power applied and of the input signal applied Loosened terminals Wiring condition / disconnected wires Check the power supply and the controller connected to. Tighten the terminals. Check the wiring. Fluid leaks to the outside of the valve when the ACTIVAL is in fully closed position. Actuator pointer not pointing to fully closed position Fully close the ACTIVAL. The valve vibrates or produces an abnormal noise. Primary pressure condition Differential pressure condition Adjust the mounting position and change the installation location. Valve hunting occurs. Secondary pressure condition Differential pressure condition Control stability Adjust the mounting position and change the installation location. Correct the control parameter setting of controller. Operating time of the spring return is too short. Wiring condition of the brake motor Consult with our sales/service personnel. Operating time of the spring return is too long. The spring return does not operate. Torque of valve operation Consult with our sales/service personnel. The actuator does not fully closes the valve (in 0 % position). ⎯ Consult with our sales/service personnel. SAnet communication error occurs. ⎯ Consult with our sales/service personnel.

Specifications are subject to change without notice.