Bard W24G4 Installation Instructions Manual
Read Online
Read the Bard W24G4 Installation Instructions Manual online using the built-in PDF viewer.
Text of the manual
1 of 54
INSTALLATION INSTRUCTIONS
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
www.bardhvac.com
Manual No.:
2100-721B
Supersedes:
2100-721A
Date:
5-7-20
WARNING
READ ALL INSTRUCTIONS CAREFULLY BEFORE
BEGINNING THE INSTALLATION.
THE INSTALLATION MUST COMPLY WITH THESE
INSTRUCTIONS AND THE REQUIREMENTS OF
ALL GOVERNING CODES AND ORDINANCES FOR
THE INSTALLATION LOCATION.
IT IS THE RESPONSIBILITY OF INSTALLER
TO KNOW AND UNDERSTAND ALL OF THESE
REQUIREMENTS.
FAILURE TO DO SO COULD CREATE A HAZARD
RESULTING IN PROPERTY DAMAGE, BODILY
INJURY, OR DEATH.
WALL MOUNTED GAS/ELECTRIC
Models:
W24G4
W24G4D
W30G4
W30G4D
W36G4
W36G4D
W42G4
W42G4D
W48G4
W48G4D
W60G4
W60G4D
2 of 54
CONTENTS
Getting Other Information and Publications....4
Wall Mount Gas/Electric General Information...5
W**G Series Model Nomenclature...................... 5
Ventilation Options........................................... 5
Air Conditioning Module Options........................ 6
1. Transportation Damage.................................... 10
2. Important...................................................... 10
3. General Information........................................ 10
4. Application.................................................... 10
5. Duct Work...................................................... 10
6. High Altitude Applications............................... 11
7. Wall Mounting Information.............................. 11
8. Mounting the Unit.......................................... 11
9. Clearances..................................................... 18
10. Vent Terminal and Combustion Inlet Hood......... 19
11. Optional Vertical Venting................................. 19
12. Vent Resizing Instructions............................... 20
13. Fresh Air Intake.............................................. 20
14. Condensate Drain........................................... 20
15. Wiring – Main Power....................................... 20
16. Wiring – Low Voltage Wiring............................. 21
17. Thermostats................................................... 23
18. Gas Supply and Piping.................................... 28
19. Manifold Pressure Adjustment......................... 29
20. Checking Gas Input Rate................................. 29
21. Standard Orifice Sizing and High
Altitude Derate............................................... 31
22. Conversion of Gas Input BTUH from High
to Low Rating................................................. 34
23. Measuring Air Temperature Rise....................... 34
24. Filters........................................................... 34
25. Compressor Control Module............................. 35
26. Phase Monitor................................................ 37
27. Lighting and Shutdown Instructions................. 37
28. Service Agency Procedures.............................. 38
29. Maintaining Unit in Good Working Order........... 38
30. Troubleshooting NIDEC SELECTECH Series
ECM Motors................................................... 39
31. Replacement Parts......................................... 41
32. Sequence of Operation – Heating..................... 42
33. Sequence of Operation – Cooling..................... 42
34. Setting Unit Airflow........................................ 43
35. Pressure Service Ports.................................... 52
36. R-410A Refrigerant Charge............................. 53
37. Fan Blade Setting Dimensions......................... 53
38. Low NOx Burner Assembly "N" Suffix
Models Only – U.S. Installations Only............... 53
INDEX – Wiring Diagrams...................................... 54
Page
Page
3 of 54
FIGURES
Figure 1
Unit Dimensions...................................9
Figure 2A
Mounting Instructions – W24-36G........13
Figure 2B
Mounting Instructions – W42-60G........14
Figure 3A
Combustible Clearance – W24-36G ......15
Figure 3B
Combustible Clearance – W42-60G.......15
Figure 4
Wall Mounting Instructions...................16
Figure 5
Wall Mounting Instructions...................16
Figure 6
Common Wall Mounting Installations.....17
Figure 7
Location of Vent Terminal in Shipping...18
Figure 8
Vent Terminal and Combustion
Air Inlet Hood.....................................19
Figure 9
Fresh Air Damper................................20
Figure 10
Installation of Flexible Conduit.............21
Figure 11
Low Voltage Wiring – All Units Except
Units with Economizers........................24
Figure 12
Low Voltage Wiring – Thermostat Using
Separate Temperature and Humidity
Controllers..........................................25
Figure 13
Low Voltage Wiring –
JIFM Economizer.................................26
Figure 14
Gas Pipe Connection............................27
Figure 15
Proper Piping Practice.........................28
Figure 16
Access Internal Filter through
Upper Service Door..............................35
Figure 17
8201-169 Compressor Control Module.... 36
Figure 18
Lighting and Shutdown
Instruction Label.................................37
Figure 19
Top View of Gas Control.......................38
Figure 20
Motor Connections...............................40
Figure 21
Motor Connections...............................41
Figure 22
Sequence of Operation –
Electronic Blower Control.....................42
Figure 23
Increasing Heating Speed....................43
Figure 24
Increasing Cooling Speed.....................44
Figure 25
Speed Taps.........................................44
Figure 26
Fan Blade...........................................53
Figure 27
Low NOx Insert...................................53
TABLES
Table 1A
Specifications – W24-36G Models............7
Table 1B
Specifications – W42-60G Models............8
Table 2
Minimum Installation Clearances............18
Table 3
Low Voltage Connections for
DDC Control.........................................22
Table 4
CO2 Controllers.....................................23
Table 5
Thermostat Wire Size.............................23
Table 6
Wall Thermostats..................................23
Table 7
Humidity Controls.................................23
Table 8
Length of Standard Pipe Threads............28
Table 9
Gas Pipe Sizes – Natural Gas.................28
Table 10
Natural Gas Derate Capacities
for All Models.......................................31
Table 11A Natural Gas Orifice Tables – W24-36G....32
Table 11B Natural Gas Orifice Tables – W42-60G....33
Table 12
W24G4 Indoor Blower Performance........45
Table 13
W30G4 Indoor Blower Performance........46
Table 14
W36G4 Indoor Blower Performance........47
Table 15
W42G4 Indoor Blower Performance .......48
Table 16
W48G4 Indoor Blower Performance........49
Table 17
W60G4 Indoor Blower Performance........50
Table 18
Integrated Furnace and Blower
Control Operation..................................51
Table 19 Cooling Pressure Table...........................52
Table 20
Fan Blade Dimension............................53
Page
Page
4 of 54
Getting Other Information and Publications
For more information, contact these publishers:
ACCA
Air Conditioning Contractors of America
1712 New Hampshire Avenue, NW
Washington, DC 20009
Telephone: (202) 483-9370
ANSI
American National Standards Institute
11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900
Fax: (212) 302-1286
ASHRAE
American Society of Heating Refrigerating,
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, NE.
Atlanta, GA 30329-2305
Telephone: (404) 636-8400
Fax: (404) 321-5478
NFPA
National Fire Protection Association
Batterymarch Park
P.O. Box 9101
Quincy, MA 02269-9901
Telephone: (800) 344-3555
Fax: (617) 984-7057
CSA
Canadian Standards Association
178 Rexdale Boulevard
Rexdale, Ontario
Canada. M9W 1R3
Telephone: (416) 447-4044
BARD MANUFACTURING COMPANY, INC.
BRYAN, OHIO 43506 USA
These publications can help when installing the
furnace. They can usually be found at the local library
or purchased directly from the publisher. Be sure to
consult the current edition of each standard.
National Fuel Gas Code.....ANSI Z223.1 / NFPA 54
National Electrical Code............... ANSI / NFPA 70
Standard for the Installation ...... ANSI / NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ............... ANSI / NFPA 90B
Heating and Air Conditioning Systems
Standard for Chimneys, ........................NFPA 211
Fireplaces, Vents, and Solid Fuel Burning
Appliances
Load Calculation for ......................ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential .........ACCA Manual D
Winter and Winter Air Conditioning and Equipment
Selection
Canadian Electrical Code......................CSA C22.1
Canadian Installation Code…………CAN/CGA B149
5 of 54
W
42
G 4 –
A
X
C
X
X
X
X
X
X
WALL MOUNT GAS/ELECTRIC GENERAL INFORMATION
MODEL NUMBER NOMENCLATURE
Low ambient control is required with economizer for low temperature compressor operation.
Ventilation Options
Models
W24G, W30G, W36G
W42G, W48G, W60G
Description
Factory Installed
Code No.
Field Installed
Part No.
Field Installed
Part No.
Barometric Fresh Air Damper
X
WGBFAD-3
WGBFAD-5
Blank-Off Plate
B
WGBOP-3
WGBOP-5
Motorized Fresh Air Damper
M
WGMFAD-3A
WGMFAD-5A
Commercial Ventilator – Spring Return
V
WGCRVS-3A
WGCRVS-5A
Commercial Ventilator – Power Return
P
WGCRVP-3A
WGCRVP-5A
Economizer - Fully Modulating
E
WGJIFM-3
WGJIFM-5
Energy Recovery Ventilator – 230 Volt
R
WGERV-A3B
WGERV-A5B
Energy Recovery Ventilator – 460 Volt
R
WGERV-C3C
WGERV-C5C
1 Reference Supplemental Instructions 7960-867 for dehumidification unit information.
MODEL
Wall Mount
CONTROL OPTIONS
(See table page 6)
VENT
(See table
below)
COOLING
CAPACITY
24 – 2 ton
30 – 2½ ton
36 – 3 ton
42 – 3½ ton
48 – 4 ton
60 – 5 ton
OUTLET
X – Front Outlet
T – Top Outlet
COIL OPTIONS
X – Standard
1 – Phenolic coated evaporator
2 – Phenolic coated condenser
3 – Phenolic coated both coils
COLOR
X – Beige
1 – White
4 – Gray
8 – Bronze
FILTER
X – 2" Pleated (Standard)
W – 1" Washable
VOLTAGE
A – 230/208-60-1
B – 230/208-60-3
C – 460-60-3
REVISION
FEATURE
C – Canadian Approval
D – Dehumidification1
EMISSIONS
X = Standard
N = NOx Certified
*125,000 BTU input model is not NOx certified.
HEATING INPUT
2 - 3 Ton
3.5 - 5 Ton
A – 45,000
B – 75,000
B – 67,500
C – 100,000
C – 90,000
D – 125,000*
GAS/ELECTRIC
6 of 54
Air Conditioning Module Options
STD – Standard equipment.
CCM Compressor control module has adjustable 30 second to 5 minute delay-on-break timer. On initial power up, or any
time the power is interrupted, the delay-on-make will be 2 minutes plus 10% of the delay-on-break setting. There is no
delay-on-make during routine operation of the unit. The module also provides the lockout feature (with 1 retry) for high
and/or low pressure controls, and a 2-minute timed bypass for low pressure control.
HPC High pressure control is auto reset. Always used with compressor control module (CCM) which is included. See Note
.
LPC Low pressure control is auto reset. Always used with compressor control module (CCM) which is included. See Note .
LAC Low ambient control permits cooling operation down to 0°F. (Includes fan cycling control + Freeze Stat)
SK
CMC-15 is PTCR Start Kit can be used with all -A single phase models. Increases starting torque 2-3X. Not used for -B
or -C 3-phase models. Do not use if SK111 is used.
SK
SK111 Start Capacitor and Potential Relay Start Kit can be used with all -A single phase models. Increases starting
torque 9x. Not used for -B or -C 3-phase models. Do not use if CMC-15 is used.
CCM
HPC
LPC
LAC
SK
Factory Installed
Code
Field Installed
Part
STD
STD
STD
•
H
CMA-45 (WG4D Units)
CMA-46 (WG4 Units)
•
Field Only
SK111 or CMC-15
7 of 54
TABLE 1A
Specifications
W24G4, W30G4 and W36G4 Models
* 75° C Copper wire size
** Maximum time delay fuse or circuit breaker
Models
W24G4-A
W24G4-B
W24G4-C
W30G4-A
W30G4-B
W30G4-C
W36G4-A
W36G4-B
W36G4-C
Electrical Rating – 60 Hz
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
Operating Voltage Range
197-253
187-253
414-506
197-253
187-253
414-506
197-253
187-253
414-506
Minimum Circuit Ampacity
20.6
12.6
8
22.6
16.1
8.6
26.4
19
10.6
* Field Wire Size
10
14
14
10
12
14
8
10
14
Ground Wire Size
10
14
14
10
12
14
10
10
14
** Delay Fuse or Circuit Breaker Max.
30
15
10
30
20
10
35
25
15
Compressor
Voltage
230/208
230/208
460
230/208
230/208
460
230/208
230/208
460
Rated Load Amps
7.6/8.7
4.6/5.3
2.5
9.4/10.7
6/6.9
3.2
12/13.5
7.8/8.7
4.8
Branch Circuit Selection Current
12.9
6.5
3.6
14.2
9
4.2
16.7
10.5
5.8
Lock Rotor Amps
58.3
55.4
28
73
58
28
79
73
38
Compressor Type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Fan Motor and Condenser
Fan Motor – HP/RPM/SPD
1/5-1100-1
1/5-1100-1
1/5-1100-1
1/5-1100-1
1/5-1100-1
1/5-1100-1
1/5-1100-1
1/5-1100-1
1/5-1100-1
Fan Motor – Amps
1.4
1.4
0.8
1.4
1.4
0.8
1.4
1.4
0.8
Fan – DIA/CFM
20” - 2100
20” - 2100
20” - 2100
20” - 2100
20” - 2100
20” - 2100
20” - 2000
20” - 2000
20” - 2000
Blower Motor and Evaporator
Blower Motor – HP/RPM/SPD
1/2-670-5
1/2-670-5
1/2-670-5
1/2-750-5
1/2-750-5
1/2-750-5
1/2-870-5
1/2-870-5
1/2-870-5
Blower Motor – Amps
0.9
0.9
1.2
1.2
1.2
1.2
1.9
1.9
1.2
CFM Cooling and E.S.P.
800 - 0.15
800 - 0.15
800 - 0.15
900 - 0.15
900 - 0.15
900 - 0.15
1100 -
0.15
1100 -
0.15
1100 -
0.15
Filter Size
20 x 25 x 2
20 x 25 x 2
20 x 25 x 2
20 x 25 x 2
20 x 25 x 2
20 x 25 x 2
20 x 25 x 2
20 x 25 x 2
20 x 25 x 2
Shipping Weight – LBS.
500
500
500
530
530
530
540
540
540
Unit Charge (R-410A lb.)
5.750
5.750
5.750
5.750
5.750
5.750
6.625
6.625
6.625
8 of 54
* 75° C Copper wire size
** Maximum time delay fuse or circuit breaker
TABLE 1B
Specifications
W42G, W48G and W60G Models
Models
W42G4-A
W42G4-B
W42G4-C
W48G4-A
W48G4-B
W48G4-C
W60G4-A
W60G4-B
W60G4-C
Electrical Rating – 60 Hz
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
Operating Voltage Range
197-253
187-253
414-506
197-253
187-253
414-506
197-253
187-253
414-506
Minimum Circuit Ampacity
29
23.4
11.5
34.4
24.4
12
40.2
29.7
13.6
* Field Wire Size
8
10
14
8
10
14
8
8
12
Ground Wire Size
10
10
14
10
10
14
10
10
12
** Delay Fuse or Circuit Breaker Max.
40
30
15
50
30
15
50
40
20
Compressor
Voltage
230/208
230/208
460
230/208
230/208
460
230/208
230/208
460
Rated Load Amps
15.5/17.4
11.7/13.2
5.9
16.7/19.5
10.6/12.3
6.5
19.5/21.9
12.9/14.4
7
Branch Circuit Selection Current
18
13.6
6
21.8
13.8
6.5
24.4
16
7.8
Lock Rotor Amps
112
88
44
117
83.1
41
144.2
110
52
Compressor Type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Fan Motor and Condenser
Fan Motor – HP/RPM/SPD
1/3-850-1
1/3-850-1
1/3-850-1
1/3-830-1
1/3-830-1
1/3-830-1
1/2-1000-1
1/2-1000-1
1/2-1000-1
Fan Motor – Amps
1.8
1.8
1
1.8
1.8
1
3.8
3.8
2.5
Fan – DIA/CFM
24” - 2900
24” - 2900
24” - 2900
24” - 2700
24” - 2700
24” - 2700
24” - 3400
24” - 3400
24” - 3400
Blower Motor and Evaporator
Blower Motor – HP/RPM/SPD
3/4-850-5
3/4-850-5
3/4-850-5
3/4-940-5
3/4-940-5
3/4-940-5
3/4-1040-5
3/4-1040-5
3/4-1040-5
Blower Motor – Amps
2.4
2.4
1.7
3.1
3.1
1.7
3.7
3.7
1.7
CFM Cooling and E.S.P.
1300 -
0.15
1300 -
0.15
1300 -
0.15
1450 -
0.20
1450 -
0.20
1450 -
0.20
1650 -
0.20
1650 -
0.20
1650 -
0.20
Filter Size
20 x 30 x 2
20 x 30 x 2
20 x 30 x 2
20 x 30 x 2
20 x 30 x 2
20 x 30 x 2
20 x 30 x 2
20 x 30 x 2
20 x 30 x 2
Shipping Weight – LBS.
500
500
500
530
530
530
550
550
550
Unit Charge (R-410A lb.)
6.500
6.500
6.500
7.125
7.125
7.125
9.625
9.625
9.625
9 of 54
F
G
N
P
D
DD
FF
GG
HH
A
M
I
C
K
J
L
H
R
S
S
S
S
S
T
V
Y
AA
X
U
Z
CC
BB
B
EE
O
E
B
II
Q
W
COMBUSTION
AIR INTAKE
CONTROL
RIGHT SIDE
ENTRANCES
GAS
RETURN OPENING
4 DEG. PITCH IN TOP
PANEL DOOR
DOOR
LOW VOLTAGE
SUPPLY OPENING
PANEL
BACK
DISCONNECT ACCESS
VESTIBULE
PANEL (LOCKABLE)
CONDENSER
AIR INLETS
CONDENSER
VENT OPTION
AIR OUTLET
AIR EXHAUST
COMBUSTION
ENTRANCES
FRONT
CIRCUIT BREAKER/
MIS-3239
HIGH VOLTAGE
ENTRANCES
FRONT DOOR
FILTER
SERVICE
DOOR
UNIT
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
W24G-W30G-W36G
7.88
27.88
13.88
24.25
40
25.63
81.63
27.38
27.5
39.25
5.88
W42G-W48G-W60G
9.88
29.88
15.88
27.25
43.81
31.63
87.5
33.38
28.75
42.88
3.75
UNIT
S
T
U
V
W
X
Y
Z
AA
BB
CC
DD
EE
FF
GG
HH
II
W24G-W30G-W36G
12 - 7 HOLES
2.88
22.9
38
17.84
4.44
11.44
9
36.25
2
0.38
W42G-W48G-W60G
16 - 6 HOLES
3.88
24.9
42
17.34
8.44
12.19
10
40.25
2.75
0.44
1.25
7.25
1.13
3.75
2.25
3.25
15.31
4.5
2.5
14.88
30
14.12
15.44
FIGURE 1
Unit Dimensions
10 of 54
1. TRANSPORTATION DAMAGE
All units are packed securely in shipping containers.
All units should be carefully inspected upon arrival for
damage. In the event of damage, the consignee should:
1. Note on delivery receipt of any damage to container.
2. Notify carrier promptly, and request an inspection.
3. In case of concealed damage, the carrier must be
notified as soon as possible within 15 days after
delivery.
4. Claims for any damage, apparent or concealed,
should be filed with the carrier, using the following
supporting documents:
A. Original Bill of Lading, certified copy or
indemnity bond.
B. Original paid freight bill of indemnity in lieu
thereof.
C. Original invoice or certified copy thereof showing
trade and other discounts or deductions.
D. Copy of the inspection report issued by
carrier’s representative at the time damage is
reported to carrier.
2. IMPORTANT
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians. All duct work or portions thereof not in the
conditioned space should be properly insulated in order
to both conserve energy and prevent condensation or
moisture damage.
3. GENERAL INFORMATION
This appliance is not intended for use by persons
(including children) with reduced physical, sensory
or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or
instruction concerning use of the appliance by a person
responsible for their safety.
Children should be supervised to ensure that they do
not play with the appliance.
These instructions explain the recommended method
to install the air cooled self-contained electric air
conditioning and gas heating unit and the electrical
wiring connections and gas piping to the unit. The
refrigerant system is completely assembled and
charged. All internal wiring is complete.
These instructions and any instructions packaged with any
separate equipment required to make up the entire heating/
cooling system should be carefully read before beginning
the installation.
While these instructions are intended as a general
recommended guide, they do not supersede any
national and/or local codes in any way. Authorities
having jurisdiction should be consulted before the
installation is made. See page 4 for information on
codes and standards.
Size of unit for proposed installation should be based
on heat loss/heat gain calculations made according to
methods of Air Conditioning Contractors of America
(ACCA). The air duct should be installed in accordance
with the Standards of the National Fire Protection
Association for the Installation of Air Conditioning and
Ventilating Systems of Other Than Residence Type,
NFPA No. 90A, and Residence Type Warm Air Heating
and Air Conditioning Systems, NFPA No. 90B. Where
local regulations are at a variance with instructions,
installer should adhere to local codes.
4. APPLICATION
This is a fan-assisted forced air gas furnace with electric
air conditioning for outdoor installation. A fan-assisted
furnace is equipped with an integral mechanical means
to draw products of combustion through the combustion
chamber and heat exchanger. The furnace installation
must conform with local building codes and ordinances
or, in their absence, with the National Fuel Gas Code
ANSI Z223.1 or CAN/CGA-B149.1, latest edition,
and the National Electrical Code ANSI/NFPA-7 or CSA
C22.1, latest edition. It is the personal responsibility
and obligation of the purchaser to contact a qualified
installer to assure that installation is adequate and is in
conformance with governing codes and ordinances.
5. DUCT WORK
The unit is designed for use with or without duct work
(see WARNING). Flanges are provided for attaching
CAUTION
During the initial firing of the burners there will probably be some amount of smoke issued to the
circulating air stream as the result of residual oil burning off of the heat exchanger tubes. This oil
is required during the forming process of the stainless steel heat exchanger tubes to facilitate the
bending. OSHA or the National Toxicology Program does not list the oil as a carcinogen. In vapor
form this may be irritating to the eyes or could cause headaches. This is a one-time occurrence, and
ventilation of the space may be required depending upon the space being conditioned.
11 of 54
6. HIGH ALTITUDE APPLICATIONS
Ratings of gas utilization equipment are based on
sea level operation and need not be changed for
operation at elevations up to 6,000'. For operation at
elevations above 6,000' and in the absence of specific
recommendations from the local authority having
jurisdiction, equipment ratings shall be reduced as
specified in Section 21.
7. WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings
must be cut through the wall as detailed in Figure 4.
2. On wood-frame walls, the wall construction must
be strong and rigid enough to carry the weight of
the unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected
to ensure that they are capable of carrying the
weight of the installed unit.
8. MOUNTING THE UNIT
1. These units are secured by wall mounting brackets
which secure the unit to the outside wall surface at
both sides. A bottom mounting bracket is provided
for ease of installation but is not required.
2. The W42G, W48G and W60G models are suitable
for 0 clearance on the installation mounting wall and
to the top. For all models the supply air duct flange
and the first 3' of supply air duct require a minimum
of 1" clearance to combustible material. The W24G,
W30G and W36G models are suitable for 0 clearance
on the installation mounting wall, but require 1"
clearance to the top if combustible material overhang
projects above the unit (see Figures 3A and 3B). If
a combustible wall, use a minimum of Figure 1 “A”
dimension plus 2" and “B” dimension plus 2". See
Figures 4 and 5 for details.
the supply and return ducts. All duct work, supply
and return, must be properly sized for the design
airflow requirement of the equipment. Air Conditioning
Contractors of America (ACCA) is an excellent guide to
proper sizing.
Refer to Tables 12, 13, 14, 15, 16 and 17 for maximum
static pressure available for duct design.
See Figures 3A and 3B and clearance information in
Section 9 and Table 2 for additional information.
Design the duct work according to methods given by
the Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one-inch of insulation.
Use insulation with a vapor barrier on the outside of the
insulation. Flexible joints should be used to connect
the duct work to the equipment in order to keep the
noise transmission to a minimum.
A 1" clearance to combustible material for the first 3'
of duct attached to the outlet air frame is required.
See wall mounting instructions and Figures 2A, 2B, 3A
and 3B for further details.
Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the wall
cavity.
Some installations may not require any return air duct.
A metallic return air grille is required with installations
not requiring a return air duct. The spacing between
louvers on the grille shall not be larger than 5/8".
Any grille that meets with the 5/8" louver criteria may
be used. It is recommended that Bard Return Air Grille
or Return Filter Grille be installed when no return duct
is used. Contact distributor or factory for ordering
information. If using a return air filter grille, filters must be
of sufficient size to allow a maximum velocity of 400 fpm.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to
installation only in a single story structure.
CAUTION
If the bottom bracket is used, be certain the
bracket is secured to the outside wall surface
in a way sufficient to support the entire
weight of the unit during installation until side
mounting brackets are secured.
WARNING
Failure to provide the 1" clearance between
the supply duct and a combustible surface
for the first 3' of duct can result in fire causing
damage, injury or death.
WARNING
In all cases, there must be a metal duct
connection made to the supply air flange, and a 1"
clearance to combustibles must be maintained to
this duct connection.
For free blow applications, a metal sleeve must be
used in the wall opening itself, again maintaining
a 1" clearance to combustibles.
Failure to use the sheet metal can cause fire
resulting in property damage, injury, or death.
12 of 54
3. Locate and mark lag bolt locations and bottom
mounting bracket location.
4. Mount bottom mounting bracket.
5. Hook top rain flashing under back bend of top.
Top rain flashing is shipped secured to the right
side of the back.
6. Position unit in opening and secure with 5/16"
lag bolts; use 7/8" diameter flat washers on the
lag bolts. Use lag bolts long enough to support
the unit’s weight when mounted to the structure.
This length may be dependent on the type of
construction.
7. Secure rain flashing to wall and caulk across entire
length of top (see Figures 2A and 2B).
8. On side-by-side installations, maintain a minimum of
20" clearance on right side to allow access to control
panel and burner compartment, and to allow proper
airflow to the outdoor coil. Additional clearance may
be required to meet local or national codes.
13 of 54
FIGURE 2A
Mounting Instructions
for W24G, W30G and W36G
39 3/16"
29 3/4"
4 11/16"
12"
12"
12"
12"
12"
12"
2"
2 1/4"
10"
28 5/16"
15"
27"
17 15/16"
11 5/16"
8 5/8"
2 15/16"
2 1/4"
30"
29"
5 1/16"
7/16"
5 9/16"
4 9/16"
4 1/2"
2 15/16"
18 15/16"
4 9/16"
SUPPLY
AIR DUCT
RETURN
AIR DUCT
Ø2 3/4" GAS
OPENING
(OPTIONAL)
Ø2 3/4" HIGH
VOLTAGE
(OPTIONAL)
Ø2" LOW VOLTAGE
(OPTIONAL)
(12) FLANGE
SCREWS
UNIT SUPPORT
1" MIN.
NECCESSARY
NO CLEARANCE
SUPPLY
AIR DUCT
RETURN
AIR DUCT
CONTROL
PANEL
VESTIBULE
DOOR
WALL
STRUCTURE
(OUTSIDE)
1" CLEARANCE ON ALL
FOUR SIDES OF SUPPLY
AIR DUCT IS REQUIRED FROM
COMBUSTABLE MATERIALS
NOTE: IT IS RECOMMENDED THAT A BEAD
OF SILICONE CAULKING BE PLACED BEHIND
THE SIDE MOUNTING FLANGES AND UNDER
TOP FLASHING AT TIME OF INSTALLATION
RIGHT SIDE
VIEW WITH UNIT
OUTSIDE WALL WITH
UNIT REMOVED
RAIN FLASHING
SUPPLIED
SEAL WITH BEAD OF CAULKING
ALONG ENTIRE LENGTH OF TOP
TOP
FOAM AIR SEAL
WALL
MIS-1681
15 of 54
FIGURE 3A
Combustible Clearance
for W24G, W30G and W36G Models
FIGURE 3B
Combustible Clearance
for W42G, W48G and W60G Models
WARNING
A minimum of 1" clearance must be maintained between the supply air duct and combustible materials. This is
required for the first 3' of ducting.
It is important to insure that the one 1" minimum spacing is maintained at all points.
Failure to do this could result in overheating the combustible material and may result in a fire causing damage,
injury or death.
16 of 54
FIGURE 4
Wall Mounting Instructions
FIGURE 5
Wall Mounting Instructions
18 of 54
9. CLEARANCES
Minimum clearances, as specified in Table 2, must
be maintained from adjacent structures to provide
adequate fire protection, adequate combustion air and
room for service personnel.
While minimum clearances are acceptable for safety
reasons, they may not allow adequate air circulation
around the unit for proper operation in the cooling
mode. Whenever possible, it is desirable to allow
additional clearance, especially around the condenser
inlet and discharge openings. DO NOT install the unit
in a location that will permit discharged air from the
condenser to recirculate to the condenser inlet.
TABLE 2
Minimum Installation Clearances
Outlet Duct
(from combustible materials)
1" first 3'
Vent Terminal
(from combustible materials)
17"*
Condenser Inlet
20"
Top
See Figures 3A
and 3B
Burner Service
20"
Combustible Base (Wood or Class A,
B or C roof covering material)
0
* See Figures 3A and 3B
FIGURE 7
Location of Vent Terminal in Shipping
WARNING
Clearances from combustible materials must
be maintained as specified. Failure to maintain
clearances could cause fire resulting in
property damage, injury or death.
19 of 54
10. VENT TERMINAL AND
COMBUSTION AIR INLET HOOD
The vent terminal is shipped in the burner
compartment (see Figure 7). Remove the two shipping
screws and separate the two-piece assembly. Install
the vent terminal by using the four screws provided.
Do not cut or trim gasket. Make sure gasket is in
place. See Figure 8. The combustion air intake vent
hood is factory installed.
11. OPTIONAL VERTICAL VENTING
With the optional vertical venting kit (VVK-5), this unit
may be vented vertically through a roof or overhang.
The kit includes a stainless steel transition drain tee,
silicone sealant and drain tubing.
If unit is installed with vertical vent kit, annually
inspect the vent system and drain. Replace any portion
of the vent system that shows signs of deterioration.
Make sure drain is open and free of obstruction.
FIGURE 8
Vent Terminal and Combustion Air Intake
CAUTION
Vent terminal must be installed as shown in Figure 8 for proper operation of the heating system.
NOTE: The inner vent hood gasket is designed to stretch over and seal around the combustion air
blower outlet. This is a very critical seal to prevent water and flue products from entering the unit.
Care must be taken to insure this gasket is in place and sealing properly.
MIS-2057
MIS-2126
20 of 54
12. VENT RESIZING INSTRUCTIONS
When an existing furnace is removed from a venting
system servicing other appliances, the venting system
is likely to be too large to properly vent the remaining
attached appliances.
The following steps shall be followed with each of
the appliances remaining connected to the common
venting system, placed in operation one at a time
while the other appliances remaining connected to the
common venting system are not in operation.
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National
Fuel Gas code, ANSI Z223.1 or the CAN/CGA
B149 Installation Codes and these instructions.
Determine that there is no blockage or restriction,
leakage, corrosion and other deficiencies which
could cause an unsafe condition.
3. In so far as is practical, close all building doors and
windows and all doors between the space in which
the appliance(s) connected to the venting system
are located and other spaces of the building. Turn
on clothes dryers and any appliances not connected
to the venting system. Turn on any exhaust fans,
such as range hoods and bathroom exhausts, so they
will operate at maximum speed. Do not operate a
summer exhaust fan. Close fireplace dampers.
4. Follow the lighting instructions. Place the
appliance being inspected in operation. Adjust
thermostat so appliance shall operate continuously.
5. Test for draft hood equipped appliance spillage at
the draft hood relief opening after 5 minutes of
main burner operation. Use the flame of a match
or candle.
6. After it has been determined that each appliance
connected to the venting system properly vents
when tested as outlined above, return doors,
windows, exhaust fans, fireplace dampers and
any other gas-burning appliances to their previous
conditions of use.
7. If improper venting is observed during any of the
above tests, the venting system must be corrected.
13. FRESH AIR INTAKE
All units are built with fresh air inlet slots punched in
the service panel.
If the unit is equipped with a fresh air damper
assembly, the assembly is shipped already attached
to the unit. The damper blade is locked in the
closed position. To allow the damper to operate, the
maximum and minimum blade position stops must be
installed (see Figure 9).
All capacity, efficiency and cost of operation
information as required for Department of Energy
“Energyguide” Fact Sheets is based upon the fresh
air blank-off plate in place and is recommended for
maximum energy efficiency.
The blank-off plate is available upon request from the
factory and is installed in place of the fresh air damper
shipped with each unit.
One of several other ventilation options may be
installed. Refer to model number and/or supplemental
installation instructions.
14. CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at
the top of the unit down to the unit base. There are
openings in the unit base for the drain hose to pass
through. In the event the drain hose is connected to
a drain system of some type, it must be an open or
vented type system to assure proper drainage.
15. WIRING – MAIN POWER
FIGURE 9
Fresh Air Damper
Refer to unit rating plate for wire sizing information and
maximum fuse or circuit breaker size. Each outdoor
unit is marked with a “Minimum Circuit Ampacity”.
This means that the field wiring used must be sized to
carry that amount of current. All models are suitable
only for connection with copper wire. Each unit and/or
WARNING
For personal safety, turn off electric power
at service entrance panel before making any
electrical connections. Failure to do so could
result in electric shock or fire.
21 of 54
FIGURE 10
Installation of Flexible Conduit
Electrical Grounding
When installed, the furnace must be electrically
grounded in accordance with local codes, or in the
absence of local codes, with the National Electrical
Code, ANSI/NFPA 70 or Canadian Electrical Code,
CSA22.1, latest edition. Use a copper wire from green
ground wire on the furnace to a grounded connection
in the service panel or a properly driven and electrically
grounded ground rod. See Tables 1A and 1B for proper
ground wire size.
Field-Installed Equipment
Wiring to be done in the field between the furnace
and devices not attached to the furnace, or between
separate devices which are field installed and located,
shall conform with the temperature limitation for
Type T wire {63° F rise (36° C)} when installed in
accordance with the manufacturer’s instructions.
WARNING
Failure to provide a proper electrical ground
could result in electric shock or fire.
Installation of Flexible Conduit Through Return Air
Opening
NOTE: To allow proper clearance between the control
panel and any vent options, 90° conduit
fittings must be used on the back of the
control panel.
Installing Conduit (See Figure 10)
1. Remove conduit access panel if required to gain
access to area behind control panel.
2. Remove low voltage and high voltage knockouts
located in rear of control panel.
3. Run low voltage conduit through 7/8 bushing
located in conduit entrance plate and secure to low
voltage opening in rear of control panel.
4. Run high voltage conduit through 1-3/4 bushing
located in conduit entrance plate and secure to
high voltage opening in rear of control panel.
5. Replace conduit access panel if required to
complete installation.
6. Seal around conduit in conduit entrance plate.
16. WIRING – LOW VOLTAGE WIRING
230/208 Volt Units
All 230/208V 1 phase and 3 phase equipment have
dual primary voltage transformers. All equipment leaves
the factory wired on 240V tap. For 208V operation,
reconnect from 240V to 208V tap. The acceptable
operating voltage range for the 240 and 208V taps are:
Tap: 240
Range: 253 – 216
Tap: 208
Range: 220 – 187
NOTE: The voltage should be measured at the field
power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).
WARNING
Failure to provide an electrical power supply
shut off means could result in electric shock or
fire.
wiring diagram will be marked “Use Copper Conductors
Only”. These instructions must be adhered to. Refer
to the National Electrical Code (NEC) for complete
current carrying capacity data on the various insulation
grades of wiring material. All wiring must conform to
NEC and all local codes.
The electrical data lists fuse and wire sizes (75° C
copper) for all models.
The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or circuit breaker that is to be used with
the equipment. The correct size must be used for
proper circuit protection and also to assure that there
will be no nuisance tripping due to the momentary high
starting current of the compressor motor.
The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect. To
convert for the locking capability bend the tab located
in the bottom left hand corner of the disconnect
opening under the disconnect access panel straight
out. This tab will now line up with the slot in the door.
When shut, a padlock may be placed through the hole
in the tab preventing entry.
22 of 54
Low Voltage (24VAC) Connections
These units use a 24-volt AC low voltage circuit.
C terminal is the 24VAC common and is grounded.
G terminal is the indoor blower input.
Y1 terminal is the 1st Stage cooling input. Economizer
stage when used. Balanced Climate stage when used.
Y2 terminal is the 2nd Stage cooling input. Compressor
cooling stage when economizer or Balanced Climate is
used.
B/W1 terminal is the gas heat.
A terminal is the ventilation option input. This
terminal energizes any factory-installed ventilation
option and indoor blower.
D terminal is the dehumidification input. If installed, this
terminal energizes any factory-installed dehumidification
option.
L terminal is 24 volt alarm active output.
Unit Shutdown Feature (Standard on All Models)
The RT terminal is the 24VAC transformer output,
and the R terminal is the 24VAC hot terminal for the
operation of the equipment. RT and R are connected
with a brass jumper bar which can be removed and RT
and R connected to an external NC (normally closed)
contact such as a fire/smoke detector that will cause
shutdown of the equipment upon activation.
Balanced Climate™ Feature (Standard on All Models)
All units are equipped with the capability of running
in Balanced Climate mode. This mode is designed to
enhance the comfort level by reducing the indoor airflow
amount and extending the run time to help extract more
humidity during cooling operation. The Y1 terminal
is the 24VAC input for Balanced Climate compressor
cooling operation. The Y2 terminal is the 24VAC input
for compressor cooling standard operation. Y1 and Y2
are connected with a brass jumper bar which can be
removed to enable Balanced Climate mode. Units with
an economizer will not have the brass jumper installed.
Refer to vent manuals for instructions on how Balanced
Climate works with each vent.
To operate in Balanced Climate mode, a 2-stage cooling
thermostat is required. The lower indoor airflow operation
is overridden by utilizing a 2-stage thermostat. If the call
for cooling is not satisfied within a given time frame or
temperature differential (specified by the thermostat), the
thermostat will send a signal to Y2 which then increases
the blower speed back to the selected speed. See pages
43 – 44 for blower speed selection options.
In units with an economizer vent installed, Balanced
Climate mode should not be used. The Y1 and Y2
jumper must remain installed.
Dehumidification Feature (Optional)
The D terminal is the 24VAC input for dehumidification
operation on dehumidification hot gas reheat equipped
units. When 24VAC is applied to the D terminal, a
3-way valve solenoid is energized. The reheat coil
located behind the evaporator coil is then active to
reheat the supply air during cooling mode. This allows
humidity to be removed from the air entering the unit
without a large amount of sensible cooling capacity.
During dehumidification, the indoor blower speed is
reduced to help with the humidity removal. A humidity
sensing thermostat or humidistat is required to
control dehumidification operation. See Supplemental
Instructions 7960-867 for additional information on
dehumidification unit operation.
Ventilation Features (Optional)
See ventilation instructions provided with unit for low
voltage wiring.
Low Ambient Control (LAC)
The low ambient control is a pressure switch that is
attached to the liquid line of the system and monitors
Standard Units
Units w/
Economizers
Fan Only
Energize G
Energize G
1st Stage
Cooling Mode/Bal-
anced Climate
Energize Y1, G
Energize Y1, G
2nd Stage
Cooling Mode
Energize Y2 to
overide Bal-
anced Climate
mode when
Y1-Y2 jumper is
removed
Energize Y1, Y2, G
Gas Heating
Energize B/W1
Energize B/W1
Ventilation
Energize A
Energize A
Dehumidification
(if employed)
Energize D
Energize D
For low voltage wiring, an 18 gauge copper, color-
coded cable is recommended. See Table 5 for more
information.
460 Volt Units
All models are equipped with single primary voltage
transformers and no rewiring is required.
Direct Digital Controls (DDC)
For total and proper control using DDC, a total of six
controlled outputs are required (five if no ventilation is
installed).
TABLE 3
Low Voltage Connections for DDC Control
23 of 54
TABLE 6
Wall Thermostats
Thermostat
Predominant Features
8403-060
1120-445
3 Stage Cool; 3 Stage Heat
Programmable/Non-Programmable
Electronic
HP or Conventional
Auto or Manual changeover
8403-082
(VT8600U5500B)
2 stage Cool; 2 stage Heat
Programmable/Non-Programmable
Electronic
HP or Conventional, Auto or Manual
changeover with Occupancy Sensor,
BACnet
8403-084
(VT8600U5000B)
2 stage Cool; 2 stage Heat
Programmable/Non-Programmable
Electronic
HP or Conventional, Auto or Manual
changeover with BACnet
8403-089
(T4 Pro)
1 stage Cool; 1 stage Heat – Heat Pump
1 stage Cool; 1 stage Heat – Conventional
Programmable/Non-Programmable
Electronic
Auto or Manual changeover
8403-090
(T6 Pro)
2 stage Cool; 3 stage Heat – Heat Pump
2 stage Cool; 2 stage Heat – Conventional
Programmable/Non-Programmable
Electronic
Auto or Manual changeover
8403-091
(T701-FEMA)
1 stage Cool, 1 stage Heat
Non-Programmable
FEMA use
8403-092
(T6 Pro Wi-Fi)
2 stage Cool, 3 stage Heat – Heat Pump
2 stage Cool, 2 stage Heat – Conventional
Programmable/Non-Programmable
Electronic
Auto or Manual changeover
Wi-Fi
high side pressure. Operation of the LAC occurs as
outdoor temperatures drop below 60°F. On/Off and
modulating controls are used which operate based
on pressure changes caused by outdoor temperature
changes. On/Off LAC operation cycles the condenser
fan on/off to maintain desired liquid pressure while
modulating LAC operation is factory adjusted and slows
the condenser fan speed (rpm).
Outdoor Temperature Switch and Freeze Protection
Thermostat
An outdoor temperature switch and an evaporator
freeze protection thermostat is supplied with all units
that have a low ambient control. The outdoor switch
disables Balanced Climate mode (if enabled) when the
temperature drops below 50°F. This prevents potential
evaporator coil freeze up issues. The freeze thermostat
cuts out compressor operation if the evaporator begins
to freeze up.
Balanced Climate Mode
If the application is likely to require air conditioning
operation below 60°F outdoor conditions, a low ambient
control (LAC) kit must be installed.
If the unit is being installed with any ventilation
package, a Bard LAC kit must be installed. Failure to
utilize an LAC with any air conditioner can cause coil
freeze up. Balanced Climate can readily be applied to
duct-free (supply and return air grille) applications. It
may also be applied to ducted applications with limited
rated static (total including both supply and return
statics). Consult Bard Application Engineering for
details prior to implementation.
CAUTION: Balanced Climate is not a replacement for
a dehumidification (hot gas reheat) unit for extreme
applications, but rather an enhancement feature for
limited climates and applications.
17. THERMOSTATS
TABLE 7
Humidity Controls
Part Number
Predominate Features
8403-038
(H600A1014)
SPDT switching, pilot duty 50VA @ 24V;
Humidity range 20-80% RH
8403-047
(H200-10-21-10)
Electronic dehumidstat SPST closes-
on-rise; Humidity range 10-90% with
adjustable stops
TABLE 4
CO2 Controllers
Part Number
Predominate Features
8403-056
CO2 ventilation control with digital display.
Normally Open SPST (Default: Close at
800ppm)
8403-067
Normally Open SPST relay closes-on-rise
24V dual wave length sensor. Default setting
950ppm, adjustable to 0-2000ppm
Default off setting 1000ppm, adjustable to
0-200 ppm can be calibrated
TABLE 5
Thermostat Wire Size
Transformer
VA
FLA
Wire Gauge
Maximum
Distance
in Feet
55
2.3
20 gauge
18 gauge
16 gauge
14 gauge
12 gauge
45
60
100
160
250
24 of 54
6
5
4
3
2
1
TEMP-OUT
C02 OUT
24VAC
Optional CO2 Controller
Bard Part #8403-067
B/W1 W2
Y1
6
C
A
4
1
RT
L
G
Y2
2
D
W3
5
3
R
4
Y
W2
Y2
8
4
W
R
1
W1/E
5
C
Y1
17
L
R
RC
O/B
G
6
A
B
O
3
R
G
7
C
JUMPER
2
or #8403-084
Thermostat
(1120-445)
Part #8403-060
Thermostat
HAVE OCCUPANCY OUTPUT.
2
FOR HEAT/COOL)
BLUE
(MUST BE CONFIGURED
THERMOSTAT SUBBASE
1
INSTALL IF YOU REQUIRE VENTILATION ANYTIME BLOWER IS ON.
3
RED
4
CONFIGURE THERMOSTAT FOR HEAT/COOL
1
RED/WHITE
5
SET SWITCH ON THERMOSTAT TO "GAS-OIL"
MODE.
Part #8403-057
or T4 Pro 8403-089
MODE.
(TH311DD1040)
A 2-STAGE THERMOSTAT IS RECOMMENDED FOR
BALANCED CLIMATE™
UNIT CONTROL PANEL
TERM. STRIP
VOLTAGE
UNIT LOW
MUST INSTALL JUMPER FOR 8403-057 OR OTHER THERMOSTAT THAT DOES NOT
BLACK/WHITE
INSTALLED
BROWN/WHITE
BLUE
ORANGE
3
Thermostat
Part #8403-082
D/YO
BALANCED CLIMATE™
5
FACTORY INSTALLED JUMPER. REMOVE TO ACTIVATE
FACTORY
VENT
PACKAGE
WIRING
PLUG
RED
MIS-2775 H
12
2
FIGURE 11
Low Voltage Wiring
All Units Except Units with Economizers
25 of 54
B
C
Y
RC
G
O
R
W
Y
W
C
G
R
W2
L
RC
Y2
O/B
A
6
4
3
C
Y1
Y2
G
RT
R
L
D
5
W3
2
W2
1
B/W1
4
6
3
4
6
5
INSTALLED
(TH522OD1151)
or T6 Pro 8403-090
3
1
MUST INSTALL JUMPER FOR 8407-057, 8403-058 OR OTHER THERMOSTAT THAT DOES NOT
HAVE OCCUPANCY OUTPUT.
2
MIS-2788 D
7
(H200-10-21-10)
Bard part #
5
TERM. STRIP
VOLTAGE
Thermostat
JUMPER
FACTORY INSTALLED JUMPER.
8403-047
4
IF THIS "A" TO "G" JUMPER IS INSTALLED, YOU MUST INSURE TO REMOVE VENTILATION
PACKAGE ORANGE WIRE FROM TERMINAL "G".
YELLOW
UNIT CONTROL PANEL
(TH311DD1040)
Part #8403-057
Thermostat
CHANGE "SYSTEM TYPE", SET UP FUNCTION 1, FROM 5 (2 HEAT/ 1 COOL HEAT PUMP)
Mechanical Humidistat
TO 6 (2 HEAT/ 2 COOL CONVENTIONAL).
2
1
8403-038
or T4 Pro 8403-089
2
(H600A 1014)
UNIT LOW
Part #8403-058
Electronic Humidistat
Bard part #
RED
THERMOSTAT SUBBASE
INSTALL IF YOU REQUIRE VENTILATION ANYTIME BLOWER IS ON.
SET SWITCH ON THERMOSTAT TO "GAS-OIL"
3
5
FACTORY
FACTORY INSTALLED JUMPER. REMOVE TO ACTIVATE BALANCED CLIMATE™ MODE.
A 2-STAGE THERMOSTAT IS RECOMMENDED FOR BALANCED CLIMATE™ MODE.
5
6
7
MIS-2788D
FIGURE 12
Low Voltage Wiring
Thermostat Using Separate Temperature and Humidity Controllers
26 of 54
Must be energized to enable minimum position. NOTE: Economizer Control Default Setting
is 10V (100%). Depending upon application may require setting to lower value.
BLACK/WHITE
to 6 (2 heat/ 2 cool conventional).
O/B
FROM
BLUE
Change model configuration from heat pump to heat/cool, and must be configured for
economizer for YO/D output to be active as first stage cooling.
JUMPER
4
W2
5
(TH5220D1151)
R
W2
Change "system type", set up function 1, from 5 (2 heat/ 1 cool heat pump)
Y2
RC
3
L
B/W1
8403-058
C
Y
UNIT CONTROL PANEL
W
L
G
Low Voltage Wiring Diagram
W1/E
RT
A
G
RED/WHITE
1
Thermostat
3
part #8403-060
4
WIRES
YO/D
C
G
VOLTAGE
UNIT LOW
YELLOW
5
5
YELLOW/RED
PINK
R
4
W3
2
W2
Factory installed jumper.
1
move blue wire to "A" terminal.
PURPLE
3
6
C
Y1
2
PLUG
R
For demand ventilation and/or to disable ventilation on call for heat,
D
Y2
2
1
A
FACTORY
INSTALLED
1
Y1
Y2
MIS-3349 C
6
Balance Climate is unavailable with economizer.
Leave the jumper installed.
6
FIGURE 13
Low Voltage Wiring
JIFM Economizer
28 of 54
18. GAS SUPPLY AND PIPING
General Recommendations
1. Be sure the gas line complies with the local codes
and ordinances, or in their absence with the
National Fuel Gas Code, ANSI Z223.1, or Natural
Gas Installation Code, CAN/CGA B149.1, or
Propane Installation Code B149.2, latest edition.
2. A sediment trap or drip leg must be installed in the
supply line to the furnace.
3. A ground joint union shall be installed in the gas
line adjacent to and upstream from the gas valve
and downstream from the manual shut-off valve.
4. An 1/8" NPT plugged tapping accessible for test
gauge connection shall be installed immediately
upstream of the gas supply connection to the
furnace for the purpose of determining the supply
gas pressure. This can be omitted if local codes
permit use of plugged tapping in gas valve inlet.
5. Install listed manual shut-off valve in the supply
gas line external to and immediately upstream of
the furnace (see Figure 14).
6. Use steel or wrought iron pipe and fittings.
7. DO NOT thread pipe too far. Valve distortion or
malfunction may result from excess pipe within
the control. Use pipe joint compound resistant to
the action of liquefied petroleum gases on male
threads only. DO NOT use Teflon tape. See Table
8 and Figure 15.
TABLE 8
Length of Standard Pipe Threads (Inches)
TABLE 9
Gas Pipe Sizes – Natural Gas
Checking the Gas Piping
Before turning gas under pressure into piping, all
openings from which gas can escape should be closed.
Immediately after turning on gas, the system should be
checked for leaks. This can be done by watching the
1/2 cubic foot test dial, allowing 4 minutes to show any
movement, soaping each pipe connection and watching
for bubbles. If a leak is found, make the necessary
repairs immediately and repeat the above test. The
furnace must be isolated from the gas supply piping
system by closing the manual shut-off valve on the
combination gas control valve during pressure testing
of the gas supply piping system at pressures up to 1/2
PSIG. The furnace and its individual shut-off valve must
be disconnected from supply piping and supply piping
capped during any pressure testing of supply piping
system at test pressures in excess of 1/2 PSIG.
Defective pipes or fittings should be replaced and
not repaired. Never use a flame or fire in any form to
locate gas leaks; use a soap solution.
After the piping and meter have been checked
completely, purge the system of air. DO NOT bleed air
inside the furnace. Be sure to check and relight all
the gas pilots on other appliances that may have been
extinguished because of interrupted gas supply.
FIGURE 15
Proper Piping Practice
8. Refer to Table 9 for gas pipe sizes for natural gas.
If more than one appliance is supplied from a
single line size, capacity must equal or exceed the
combined input to all appliances, and the branch
lines feeding the individual appliances properly
sized for each input.
Pipe Size
Effective Length
of Thread
Overall Length of
Thread
3/8
1/2
9/16
3/4
1/2 – 9/16
13/16
1
9/16
1
Length
of Pipe -
Feet
Pipe Capacity -
BTU per Hour Input Pipe Size
1/2"
3/4"
1"
1-1/4"
10
132,000
278,000
520,000
1,050,000
20
92,000
190,000
350,000
730,000
30
73,000
152,000
285,000
590,000
40
63,000
130,000
245,000
500,000
50
56,000
115,000
215,000
440,000
60
50,000
105,000
195,000
400,000
70
46,000
96,000
180,000
370,000
80
43,000
90,000
170,000
350,000
100
38,000
79,000
150,000
305,000
MIS-897
THIS PRODUCT MUST BE GAS PIPED
BY A LICENSED PLUMBER OR GAS
FITTER IN THE COMMONWEALTH OF
MASSACHUSETTS.
29 of 54
19. MANIFOLD PRESSURE
ADJUSTMENT
A 0 to 15" water manometer with 0.1" resolution and a
1/8" NPT manual shut-off valve is needed to measure
actual manifold pressure.
Depending on local gas heating value and elevation,
the manifold pressure may need to be adjusted or the
orifices changed to get proper gas input rate. Check
with the local gas supplier to determine heating value
(BTU/cu. ft.) of natural gas in the area.
NOTE: If furnace is being installed at an altitude of
more than 6,000' above sea level, you must
derate the furnace. See Section 21 “Standard
Orifice Sizing and High Altitude Derate”.
1. Turn off gas at equipment shut-off valve in gas
supply line just ahead of furnace.
2. Remove plug from outlet pressure tap in gas
control or gas manifold.
3. Install 1/8" NPT manual shut-off valve in hole
vacated by plug. Make sure shut-off valve is in
OFF position.
4. Attach manometer to 1/8" NPT manual shut-off
valve just installed.
PROPANE (LP) GAS CONVERSION
This unit may be converted in the field for
use with propane (LP) gas. Propane gas
conversion kit number WGCK-1 is designed
for conversions of units installed from
0 – 6,000' elevations. Propane gas
conversion kit number WGCK-2 is designed
for conversions of units installed from
6,001' – 10,000' elevations. These kits
may be purchased from the ocal distributor.
5. Slowly open equipment shut-off valve in gas supply
line just ahead of furnace. Start furnace following
“Operating Instructions” on front door.
6. Slowly open 1/8" NPT manual shut-off valve
leading to manometer.
7. Read manifold pressure on manometer.
8. Adjust manifold pressure by turning gas control
regulator adjusting screw clockwise to increase
pressure or turning counterclockwise to decrease
pressure. Manifold pressure must be within
allowable range as follows:
•
Natural gas manifold pressure must be
between 3.2" and 3.8" W.C. Rated pressure is
3.5" W.C.
•
Propane gas (LP) manifold pressure must be
between 9.7" and 10.3" W.C. Rated pressure
is 10" W.C.
NOTE: For natural gas, if gas flow rate can’t be
properly set within these pressure ranges,
the main burner orifices must be changed to
obtain proper gas flow rate.
9. Shut off furnace. Turn off gas at equipment shut-off
valve in gas supply line just ahead of furnace. Install
outlet pressure tap plug in gas control. Turn on gas.
10. Check regulator adjustment cover screw and gas
control plug for gas leaks. Use a commercial soap
solution made for leak detection.
20. CHECKING GAS INPUT RATE
It is the installer’s responsibility to see that the
BTU input rate of the furnace is properly adjusted.
Under-firing could cause inadequate heat, excessive
condensation or ignition problems. Overfiring could
cause sooting, flame impingement or overheating of
heat exchanger.
WARNING
Failure to adjust furnace to the proper firing
rate could cause heat exchanger failure.
WARNING
When converting from propane (LP) gas to
natural gas, the gas orifice spuds and gas
valve spring must be replaced and the gas
valve regulator pressure must be adjusted
correctly. Failure to do so can result in fire,
injury or death. Refer to Tables 11A and 11B
for proper orifice sizing.
Natural gas spring kit, part number 5603-007,
can be purchased through the local distributor.
WARNING
Correct manifold pressure is necessary for
proper ignition and burner operation. Failure
to accurately adjust pressure could cause heat
exchanger failure.
30 of 54
Natural Gas Input Rate
Natural gas heating value (BTU/cu. ft.) can vary
significantly. Before starting natural gas input check,
obtain gas heating value at the location from local
supplier. A stopwatch will be needed to measure
actual gas input.
1. Gas supply pressure must be between 5" and 7"
W.C. for natural gas.
2. Turn off all other gas appliances. The pilots may
be left on.
3. Start furnace following “Operating Instructions” on
front door.
4. Let furnace warm up for 6 minutes.
5. Locate gas meter. Determine which dial has the
least cubic feet of gas and how many cubic feet
per revolution it represents. This is usually one-
half, one or two cubic feet per revolution.
6. With stopwatch, measure time it takes to consume
two cubic feet of gas.
•
If dial is one-half cubic foot per revolution,
measure time for four revolutions.
•
If dial is one cubic foot per revolution,
measure time for two revolutions.
•
If dial is two cubic feet per revolution,
measure time for one revolution.
7. Divide this time by two. This gives average time
for one cubic foot of gas to flow through meter.
Example: If it took 58 seconds for two cubic feet
to flow, it would take 29 seconds for one cubic foot
to flow.
8. Calculate gas input using this formula:
Gas Heating Value (BTU/cu. ft.)
x 3,600 sec/hr
Gas input =
= BTU/hour
Time (Seconds for one
cubic foot of gas)
Example:
Assume it took 29 seconds for one cubic foot of
gas to flow and heating value of 1,000 BTU/cu. ft.
1,000 x 3,600
Gas input =
= 124,138 BTU
29
If no other pilots were left on, this is the furnace
gas input.
9. If the water heater, dryer or range pilots were left
on, allow for them in calculating correct furnace
gas input. A quick way is to allow 1,000 BTU per
hour for a water heater, 500 BTU per hour for dryer
and 500 BTU per hour for each range burner pilot.
1. Make the main burner orifices are correct.
2. Gas supply pressure must be between 11" and 13"
W.C. for propane (LP) gas.
3. Start furnace following “Operating Instructions” on
front door.
4. Let furnace warm up for 6 minutes.
5. Adjust manifold pressure to 10.0" W.C. ± 0.3".
See Section 19, “Manifold Pressure Adjustment”.
WARNING
Propane (LP) gas installations do not have gas
meters to double check input rate. Measure
manifold pressure adjustment with an accurate
manometer. Failure to accurately adjust
pressure could cause heat exchanger failure,
asphyxiation, fire or explosion, resulting in
damage, injury or death.
WARNING
Do not set propane (LP) manifold pressure
at 11.0" W.C. It could cause heat exchanger
failure.
Example:
If the gas water heater, dryer, two range burner
pilots and one oven pilot were left on, allow:
Water heater pilot
1,000 BTU per hour
Dryer pilot
500 BTU per hour
2 range burner pilots
1,000 BTU per hour
1 range oven pilot
500 BTU per hour
3,000 BTU per hour
Subtracting 3,000 BTU per hour from 124,138
BTU per hour measured above equals 121,138
BTU per hour. This would be the correct furnace
gas input after allowing for pilots left on.
10. Manifold pressure may be adjusted within the
range of 3.2" W.C. to 3.8" W.C. to get rated input
± 2 percent. See Section 19, “Manifold Pressure
Adjustment.” If rated input with manifold pressure
cannot be gotten within the allowable range,
orifices must be changed.
Propane (LP) Gas Input Rate
31 of 54
21. STANDARD ORIFICE SIZING AND
HIGH ALTITUDE DERATE
This furnace is shipped with fixed gas orifices for use
with natural gas and sized for 1000 BTU/cubic foot
gas. Make sure actual gas input does not exceed rating
plate input. The orifices may need to changed to get
the correct gas input. Whether they need changed
or not depends on input and the gas heat value at
standard conditions and elevation. Consult the local
gas supplier for gas heat value and any special derating
requirements. See Section 20 for more information.
At higher altitudes, the density of the air is reduced.
Therefore, for proper combustion, the quantity of gas
burned in the furnace must also be reduced. This
is called derating. This unit must be derated when
installed at altitudes greater than 6,000' above sea
level. A high altitude pressure switch must also be
installed for operation above 6,000'. High Altitude
Pressure Switch Kit number 8620-189 is designed for
this application.
TABLE 10
Natural Gas Derate Capacities
for All Models
W**G Rated
Input
Sea Level
1000
2000
3000
4000
5000
6000
7000
8000
9000
10,000
41,000
45,000
40,500
45,000
39,204
43,560
37,908
42,120
36,612
40,680
35,640
39,600
34,992
38,880
34,182
37,980
33,696
37,440
33,048
36,720
32,643
36,270
32,076
35,640
61,000
68,000
60,750
67,500
58,806
65,340
56,862
63,180
54,918
61,020
53,460
59,400
52,488
58,320
51,273
56,970
50,544
56,160
49,572
55,080
48,965
54,405
48,114
53,460
75,000
81,000
75,000
81,000
72,600
78,408
70,200
75,816
67,800
73,224
66,000
71,280
64,800
69,984
63,300
68,364
62,400
67,392
61,200
66,096
60,450
65,286
59,400
64,152
90,000
100,000
90,000
100,000
87,120
96,800
84,240
93,600
81,360
90,400
79,200
88,000
77,760
86,400
75,960
84,400
74,880
83,200
73,440
81,600
72,540
80,600
71,280
79,200
113,000
125,000
112,500
125,000
108,900
121,000
105,300
117,000
101,700
113,000
99,000
110,000
97,200
108,000
94,950
105,500
93,600
104,000
91,800
102,000
90,675
100,750
89,100
99,000
It is the installer’s responsibility to see that the
furnace input rate is adjusted properly. Derating
must be achieved by reducing the size of the main
burner orifices. Derating the furnace by adjusting the
manifold pressure lower than the range specified in
the Section 19, “Manifold Pressure Adjustment” is
considered to be an improper procedure.
Above 6,000' elevation orifice changes are required,
and capacity reductions are a function of altitude
impact and orifice change. Pressure switch change is
required above 6,000' elevation. For natural gas, see
Altitude Table 10 below and Orifice Tables 11A and
11B on following pages.
32 of 54
TABLE 11A
Natural Gas Orifice Tables for Models W24G, W30G and W36G
All other orifice sizes shown are available as individual field-supplied items. See orifice tables below for specifications and number
required.
Factory Standard
Input
Gas Heat* Value
BTU/Cu. Ft.
Up to 6,000' No
Changes Except
for BTU Content
6,001' to 8,000'
Requires Pressure Switch
Change and Orifice
Change Based on BTU
Content
8,001' to 10,000'
Requires Pressure Switch
Change and Orifice Change
Based on BTU Content
25000 BTU
Per Burner
700-749
2.75
2.70
2.60
750-799
2.70
2.60
2.50
800-849
2.60
2.50
2.45
850-899
2.50
2.45
2.35
900-949
2.45
2.35
(2.30)
950-999
2.35
(2.30)
2.25
1000-1049**
(2.30)
2.25
[2.20]
1050-1100
2.25
[2.20]
2.15
Pressure Switch
Standard (.55)
Order 8620-189 High Altitude Pressure Switch Kit (.42)
(2.30) is the standard factory-installed orifice size
[2.20] orifices are shipped with the unit for field-installed
optional 10% derate
Optional
10% Field-
Converted Derate
Gas Heat* Value
BTU/Cu. Ft.
Up to 6,000’ No
Changes Except
for BTU Content
6,001’ to 8,000’
Requires Pressure Switch
Change and Orifice
Change Based on BTU
Content
8,001’ to 10,000’
Requires Pressure Switch
Change and Orifice Change
Based on BTU Content
22250 BTU
Per Burner
700-749
2.60
2.50
2.45
750-799
2.50
2.45
2.40
800-849
2.45
2.40
(2.30)
850-899
2.40
(2.30)
2.25
900-949
(2.30)
2.25
[2.20]
950-999
2.25
[2.20]
2.15
1000-1049**
[2.20]
2.15
2.10
1050-1100
2.15
2.15
2.10
Pressure Switch
Standard (.55)
Order 8620-189 High Altitude Pressure Switch Kit (.42)
[2.20] orifices are shipped with the unit for field-installed optional
10% input rate
(2.30) is the factory-installed orifice size for full rated
input
At standard conditions: 30.00 inches Mercury, 60F, saturated, .60 specific gravity.
All Natural Gas factory orifice sizing and standard input ratings based on nominal 1025 BTU/cu. ft. gas and sea level conditions
*
**
Orifice Size (mm)
Orifice Diameter
2.10
0.0826
2.15
0.0846
2.20
0.0866
2.25
0.0885
2.30
0.0905
2.35
0.0925
2.40
0.0945
No. of Orifices Required Based
on Unit Input Rating
41,000 (2)
45,000 (2)
61,000 (3)
68,000 (3)
75,000 (3)
81,000 (4)
90,000 (4)
100,000 (4)
113,000 (5)
125,000 (5)
Orifice Size (mm)
Orifice Diameter
2.45
0.0964
2.50
0.0984
2.60
0.1024
2.70
0.1063
2.75
0.1082
2.80
0.1102
2.90
0.1142
33 of 54
All other orifice sizes shown are available as individual items. See orifice tables on page 32 for part numbers and number required.
TABLE 11B
Natural Gas Orifice Tables for Models W42G, W48G and W60G
Factory Standard
Input
Gas Heat* Value
BTU/Cu. Ft.
Up to 6,000’ No
Changes Except
for BTU Content
6,001’ to 8,000’
Requires Pressure Switch
Change and Orifice
Change Based on BTU
Content
8,001’ to 10,000’
Requires Pressure Switch
Change and Orifice Change
Based on BTU Content
25000 BTU
Per Burner
700-749
2.90
2.80
2.70
750-799
2.80
2.70
2.60
800-849
2.70
2.60
2.50
850-899
2.60
2.50
2.45
900-949
2.50
2.45
(2.40)
950-999
2.45
(2.40)
2.35
1000-1049**
(2.40)
2.35
[2.30]
1050-1100
[2.30]
2.25
2.20
Pressure Switch
Standard (.55)
Order 8620-189 High Altitude Pressure Switch Kit (.42)
(2.40) is the standard factory-installed orifice size
[2.30] orifices are shipped with the unit for field-installed
optional 10% derate
Optional
10% Field
Converted Derate
Gas Heat* Value
BTU/Cu. Ft.
Up to 6,000’ No
Changes Except
for BTU Content
6,001’ to 8,000’
Requires Pressure Switch
Change and Orifice
Change Based on BTU
Content
8,001’ to 10,000’
Requires Pressure Switch
Change and Orifice Change
Based on BTU Content
22250 BTU
Per Burner
700-749
2.75
2.70
2.60
750-799
2.70
2.60
2.50
800-849
2.60
2.50
850-899
2.50
2.45
(2.40)
900-949
(2.40)
2.35
[2.30]
950-999
2.35
[2.30]
2.25
1000-1049**
[2.30]
2.25
2.20
1050-1100
2.25
2.25
2.20
Pressure Switch
Standard (.55)
Order 8620-189 High Altitude Pressure Switch Kit (.42)
[2.30] orifices are shipped with the unit for field-installed optional
10% input rate
(2.40) is the factory-installed orifice size for full rated
input
At standard conditions: 30.00 inches Mercury, 60F, saturated, .60 specific gravity.
All Natural Gas factory orifice sizing and standard input ratings based on nominal 1025 BTU/cu. ft. gas and sea level conditions
*
**
34 of 54
23. MEASURING AIR TEMPERATURE
RISE
Air temperature rise (supply air temperature minus
return air temperature) must be within allowable air
temperature rise range specified on furnace rating
plate.
Two thermometers with 1° resolution capable of reading
up to 200° F will be needed. Check thermometers to
make sure they agree, or compensate accordingly.
Follow this procedure:
1. Open supply air registers and return air grilles.
Make sure the registers and grilles are free of
obstruction from rugs, carpets, drapes or furniture.
2. Set balancing dampers in supply duct system.
3. Check duct work for obstructions or leaks.
22. CONVERSION OF GAS INPUT BTUH
FROM HIGH TO LOW RATING
All the derated WG series units are produced with
maximum BTUH input orifices installed. To field
convert input, a change to main burner orifices is
required.
NOTE: No change to air orifices is necessary. A set
of low input orifices is shipped with every
unit. They will be found packaged in a bag
behind the burner door. Refer to the unit
rating plate to confirm the proper orifice size.
Proper installation of the orifices is detailed as
follows:
1. Shut off electrical supply to the unit.
2. Shut off gas supply to the unit.
3. Remove burner access panel.
4. Disconnect gas valve from gas supply piping.
5. Disconnect the two wires from the gas valve.
6. Remove the manifold assembly so that orifices are
now accessible and remove orifices.
7. Apply a modest amount of pipe compound to the
new orifices and screw them into the manifold.
8. To assemble burner, reverse Steps 1 through 7.
4. Make sure filters are clean and in place.
5. Place one thermometer in supply air plenum
approximately 2' from furnace. Locate
thermometer tip in center of plenum to ensure
proper temperature measurement.
6. Place second thermometer in return air
duct approximately 2' from furnace. Locate
thermometer tip in center of duct to ensure proper
temperature measurement.
7. Set room thermostat on highest temperature
setting. Operate furnace 10 minutes. Record
supply air and return air temperatures.
8. Calculate air temperature rise by subtracting return
air temperature from supply air temperature.
•
If air temperature rise is above the
temperature rise range on rating plate,
furnace is overfired or has insufficient airflow.
Check gas input following the instructions in
Section 20, “Checking Gas Input Rate”. If
air temperature rise is still above temperature
rise range specified, more heating airflow is
needed. Check duct work and grilles to make
sure all are properly sized.
•
If air temperature rise is below the
temperature rise range on rating plate,
furnace is underfired or has too much airflow.
Check gas input following the instructions in
Section 20, “Checking Gas Input Rate”. If air
temperature rise is still below temperature rise
range specified, less heating airflow is needed.
Adjust dampers or grilles as needed.
•
After making adjustments, check air
temperature rise to verify that resulting air
temperature rise is within allowable range.
If air temperature rise is still outside the
temperature rise range specified on rating
plate, check duct system design with a
qualified heating engineer. It may be
necessary to re-size the duct work. Recheck
air temperature rise after revising duct
systems.
9. Set room thermostat to desired setting.
10. Remove thermometers and seal duct work holes.
NOTE: Failure to seal holes could result in reduced
system performance.
24. FILTERS
A 2" thick throwaway filter is supplied with each unit.
This filter is installed by opening the filter service door
(see Figure 16).
Replacement filters are available through the dealer.
WARNING
Failure to follow these instructions could
create a hazard resulting in property damage,
bodily injury, or death.
35 of 54
25. COMPRESSOR CONTROL MODULE
The compressor control module is standard on models
covered by this manual.
Features
Delay-on-Make Timer
Short Cycle Protection/Delay-on-Break
High Pressure Detection
HPC Status LED
Test Mode
Brownout Protection with Adjustment
Delay-on-Make Timer
A delay-on-make timer is included to be able to delay
startup of the compressor. This is desired when more
than one unit is on a structure so that all of the units
do not start at the same time which could happen
after a power loss or building shutdown. The delay-
on-make time period is 2 minutes plus 10% of the
delay-on-break time period. To ensure that all of the
units do not start at the same time, adjust the delay-
on-break timer on each unit to a slightly different
delay time.
Short Cycle Protection/Delay-on-Break
An anti-short cycle timer is included to prevent short
cycling the compressor. This is adjustable from 30
seconds to 5 minutes via the adjustment knob. Once
FIGURE 16
Access Internal Filter Through Upper Service Door
a compressor call is lost, the time period must expire
before a new call will be initiated.
High Pressure Detection
High pressure switch monitoring allows for a lockout
condition in a situation where the switch is open. If
the high pressure switch opens, the CCM will de-
energize the compressor. If the switch closes again,
it will then restart the compressor after the delay-
on-break setting has expired on the device. If the
switch trips again during the same thermostat call,
the compressor will be de-energized and the alarm
terminal will be energized indicating an alarm. The
red LED will light and stay on until power is cycled
to the control or a loss of voltage is present at Y
terminal for more than ½ second.
Test Mode
By rapidly rotating the potentiometer (POT) clockwise
(see Figure 17 on page 36), all timing functions will
be removed for testing.
The conditions needed for the unit to enter test mode
are as follows: POT must start at a time less than or
equal to the 40 second mark. The POT must then be
rapidly rotated to a position greater than or equal to
the 280 second mark in less than ¼ second. Normal
operation will resume after power is reset or after the
unit has been in test mode for at least 5 minutes.
MIS-3237
FILTER
FILTER
SERVICE
DOOR
36 of 54
Brownout Protection with Adjustment
Brownout protection may be necessary if the utility
power or generator power has inadequate power to
prevent the voltage from dropping when the compressor
starts. This is rare but can happen if the generator
is undersized at the site or if the site is in a remote
location far from the main power grid. Under normal
circumstances, allowing the brownout to be ignored for
a time period should not be needed. The 8201-169 is
shipped in “0” do not ignore position, with all the DIP
switches off (see Figure 17).
If ignoring the brownout is needed because of the
above conditions, three preset timers can be set by DIP
switches in order to delay signaling a power brownout
for a specific length of time after compressor contactor
is energized. This allows the compressor a time period
to start even if the voltage has dropped and allows the
voltage to recover. This delay only happens when the
CC terminal energizes. The delay can be set to 1 second
(A DIP switch), 5 seconds (B DIP switch) or 10 seconds
(C DIP switch); time is not cumulative—only the longest
setting will apply. If the voltage recovers during the
brownout delay period, the compressor will start.
If a brownout condition is detected by the 8201-169,
the troubleshooting light will flash blue. The light will
continue to flash until the cooling call is satisfied or
power is removed from the Y terminal. This condition
does not prevent operation, it only indicates that a
brownout condition was present at some point during
the cooling call. If a brownout condition is detected,
CC will be de-energized and will retry after the delay-
on-make timer is satisfied; this process will continue
until call is satisfied.
If user chooses the “0” do not ignore position when the
site has inadequate utility or generator power, this could
lead to the compressor never starting. The control will
see the brownout immediately and not start.
A common scenario and one that has been seen in the
field is when a unit or units switches from utility power
to generator power. With slower transfer switches, the
time delay between the utility power and generator
power didn’t cause a problem. The units lost power,
shut off and came back on line normally. With the
introduction of almost instantaneous transfer switches,
the millisecond long power glitch can be enough that the
compressor will start to run backwards. In this scenario,
the CCM will catch this and restart the units normally.
FIGURE 17
8201-169 COMPRESSOR CONTROL MODULE
High Pressure Switch
Compressor Contactor Output
Alarm Output
Common
Delay-on-Break Time
Adjustment Potentiometer
Brownout Ignore Time DIP Switches*
18-30 VAC Input
Y Input from Thermostat
and High Pressure Switch
Troubleshooting Light
* Turn on only one switch for that specific ignore time setting.
10 seconds is the maximum brownout ignore time.
Jumper
37 of 54
27. LIGHTING AND SHUTDOWN INSTRUCTIONS
FIGURE 18
Lighting and Shutdown Instruction Label
BEND & PEEL “HERE” TO REMOVE LABEL LINER
A. This appliance does not have a pilot. It is equipped with
an ignition device which automatically lights the burner.
Do NOT try to light the burner by hand.
B. BEFORE OPERATING smell all around the appliance
area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
* Do not try to light any appliance.
* Do not touch any electric switch; do not use any
phone in your building.
* Immediately call your supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
* If you cannot reach your gas supplier; call the fire
department.
C. Use only your hand to push in or move the gas control
lever. Never use tools. If the lever will not push in or
turn by hand, don’t try to repair it, call a qualified ser-
vice technician. Force or attempted repair may result
in a fire or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect
the appliance and to replace any part of the control sys-
tem and any gas control which has been under water.
WARNING: If you do not follow these instructions exactly, a fire or
explosion may result causing property damage, personal injury or loss of life.
1.
Set the thermostat to lowest setting.
2.
Turn off all electric power to the appliance if service
is to be performed.
3.
Remove control access panel.
4.
Push in gas control lever slightly and move to “OFF”.
Do not force.
5.
Replace control access panel.
7961-509
TO TURN OFF GAS TO APPLIANCE
FOR YOUR SAFETY READ BEFORE OPERATING
OPERATING INSTRUCTIONS
1.
STOP! Read the safety information above on this label.
2.
Set the thermostat to lowest setting
3.
Turn off all electric power to the appliance.
4.
This appliance is equipped with an ignition device which
automatically lights the burner. Do NOT try to light
the burner by hand.
5. Remove control access panel.
6. Push
in
gas
control
knob
slightly
and
turn
clockwise to “OFF”.
NOTE: Knob cannot be turned to “OFF” unless knob is
pushed in slightly. Do not force.
7. Wait five (5) minutes to clear out any gas. Then smell
for gas, including near the floor. If you smell gas, STOP!
Follow “B” in the safety information above on this label.
If you don’t smell gas, go to the next step.
8. Turn gas control knob counterclockwise to “ON”.
9. Replace control access panel.
10. Turn on all electric power to the appliance.
11. Set thermostat to desired setting.
12. If the appliance will not operate, follow the instructions
“To Turn Off Gas To Appliance” and call your service
technician or gas supplier.
GAS CONTROL
KNOB SHOWN
IN “OFF” POSITION
GAS
INLET
26. PHASE MONITOR
All units with three phase scroll compressors are
equipped with a three phase line monitor to prevent
compressor damage due to phase reversal.
The phase monitor in this unit is equipped with two
LEDs. If the “Y” signal is present at the phase monitor
and phases are correct, the green LED will light.
If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.
If a fault condition occurs, reverse two of the supply
leads to the unit. Do not reverse any of the unit factory
wires as damage may occur.
38 of 54
28. SERVICE AGENCY PROCEDURES
Main Burner
Observe the main burners in operation. The flame
should be mostly “blue” with possibly a little orange
(not yellow) at the tips of the flame. The flames should
be in the center of the heat exchanger tubes and not
impinging on the heat exchanger surfaces themselves.
Observe the fire until the blower starts (there is a
normal delay period until the heat exchanger warms
up). There should be no change in the size or shape
of the flame. If there is any wavering or blowing of
the flame on blower start-up, it is an indication of a
possible leak in the heat exchanger.
Burners/Heat Exchanger/Flue Gas Passage Ways
The burners, heat exchanger and interior flue gas
passages may be inspected using a light on small
mirror or an extension handle. Remove the screws
securing the inducer and collector box. Now inspect
the upper tubes of the heat exchanger.
Check the exterior of the heat exchanger and
the interior flue gas passages for any evidence of
deterioration due to corrosion, cracking or other
causes. If signs of sooting exist, remove the burners
and clean the heat exchanger, as required.
29. MAINTAINING UNIT IN GOOD
WORKING ORDER
The unit should be inspected annually by a qualified
service agency.
MIS-165
FIGURE 19
Top View of Gas Control
CAUTION
Label all wires prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation. Verify
proper operation after servicing.
WARNING
Follow these procedures before inspecting
furnace.
• Turn room thermostat to its lowest or off
setting.
• Turn off manual gas shut-off valve.
• Wait at least 5 minutes for furnace to cool
if it was recently operating.
• Turn off furnace electrical power; failure
to do so could result in injury or death.
WARNING
Use replacement parts listed in the
Replacement Parts list only. The use of
incorrect parts could cause improper unit
operation, resulting in damage, injury or death.
39 of 54
Routine Maintenance
1. Air Filters – Check the condition at least monthly
when the unit is in use, and replace as necessary.
2. Lubrication Requirements – The indoor circulating
air blower motor and outdoor circulating air fan
motor are permanently lubricated and requires
no re-oiling. The combustion air blower motor
requires no re-oiling.
Routine Inspection
1. Inspect the physical support of the unit annually to
make sure it is securely fastened to the building.
Also look for any obvious signs of deterioration.
2. Inspect the main burners at the beginning of each
heating season and clean as necessary.
3. Inspect the vent terminal and combustion air
intake hood for any obvious deterioration, to make
sure it is free and clear of any obstructions.
30. TROUBLESHOOTING NIDEC
SELECTECH SERIES ECM MOTORS
If the Motor Is Running
1. It is normal for the motor to rock back and forth
on start up. Do not replace the motor if this is the
only problem identified.
2. If the system is excessively noisy, does not appear
to change speeds in response to a demand (Heat,
Cool, Other) or is having symptoms during the
cycle such as tripping limit or freezing coil, check
the following:
A. Wait for programmed delays to time out.
B. Ensure that the motors control inputs are
wired as shown in the factory-supplied wiring
diagram to ensure motor is getting proper
control signals and sequencing.
C. Remove the filter and check that all dampers,
registers and grilles are open and free flowing.
If removing the filters corrects the problem,
clean or replace with a less restrictive filter.
Also check and clean the blower wheel or coil
as necessary.
Annual Maintenance
Routine inspection and maintenance procedures are
the responsibility of the user and are outlined below.
1. Before inspecting unit:
A. Turn room thermostat to lowest or off setting.
B. Turn off equipment gas shut-off valve.
C. Wait for unit to cool if it was recently
operating.
D. Turn off electrical power to unit.
2. Inspect the following:
A. Vent terminal and combustion air intake
terminal. Make sure both are free from
obstructions.
B. Vertical vent applications – Inspect venting
system. Make sure system has no holes, is
physically sound and free from obstructions.
C. Make sure the supply and return air flange
sleeves or duct work are securely fastened to
unit and physically sound.
D. Supply and return grilles must be open and
free from obstructions.
E. Inspect to make sure the unit is securely
fastened to the wall. Seal any possible leaks
between unit and wall with appropriate exterior
sealing material.
F.
Inspect burners, heat exchanger, induced draft
blower and induced draft blower collector
box. There must be no obvious signs of
deterioration.
G. Inspect all electrical connections and wiring.
H. Check all gas piping for leaks with soap
solution used to detect leaks.
I.
Inspect, clean and repair as needed the entire
blower assembly, air filters, draft inducer,
cooling coils and vent options (if installed).
WARNING
Disconnect electrical power before servicing
unit. Failure to do so could result in electrical
shock or death.
WARNING
Turn off electrical power supply to prevent injury
from moving parts or electric shock.
40 of 54
D. Check the external static pressure (total of
both supply and return) to ensure it is within
the range as listed on the unit serial plate. If
higher than allowed, additional duct work is
needed.
E. If the motor does not shut off at the end of the
cycle, wait for any programmed delays to time
out (no more than 90 seconds). Also make
sure that there is no call for “Continuous Fan”
on the G terminal.
F.
If the above diagnostics do not solve the
problem, confirm the voltage checks in the
next section below, then continue with the
Model SelecTech Communication Diagnostics.
If the Motor Is Not Running
1. Check for proper high voltage and ground at the L/
L1, G, N/L2 connections at the motor (see Figure
20). Correct any voltage issues before proceeding
to the next step. The SelecTech motor is voltage
specific. Only the correct voltage should be
applied to the proper motor. Input voltage within
plus or minus 10% of the nominal line power VAC
is acceptable.
2. If the motor has proper high voltage and ground at
the L/L1, G, N/L2 connections, then continue with
the Model SelecTech Communication Diagnostics.
Model SelecTech Communication Diagnostics
The SelecTech motor is communicated through 24 VAC
low voltage (thermostat control circuit wiring).
1. Start with unit wiring diagram to confirm proper
connections and voltage (see Figure 21).
2. Initiate a demand from the thermostat and
check the voltage between the common and the
appropriate motor terminal (1-5). (G input is
typically on terminal #1, but always refer to wiring
diagram.)
A. If the low voltage communication is not
present, check the demand from the
thermostat. Also check the output terminal
and wire(s) from the terminal strip or control
relay(s) to the motor.
B. If the motor has proper high voltage (verified
in Step 1 of If the Motor Is Not Running),
proper low voltage to a programmed terminal
and is not operating, the motor is failed and
will require replacement.
FIGURE 20
Motor Connections
Manual
2100-467H
Page
22 of 23
FIGURE 10
↓
↓
NOTE: Bard Models PA13242; PA13302; PA13362-A, -B; PA13422-A, -B, -C; PA13482-A, -B, -C; PA13602-A, -B, -C
contain the X13-Series Motors.
TROUBLESHOOTING GE X13-SERIES ECM2.3™ MOTORS
If the Motor is Running
1. It is normal for the motor to rock back and forth on start up.
Do not replace the motor if this is the only problem identified.
2. If the system is excessively noisy, does not appear to change
speeds in response to a demand (Heat, Cool, Other), or is having
symptoms during the cycle such as tripping limit or freezing coil,
check the following:
a.Wait for programmed delays to time out.
b.Ensure that the motors control inputs are wired to the factory
supplied wiring diagram to insure motor is getting proper
control signals and sequencing.
c.Remove the filter and check that all dampers, registers, and
grilles are open and free flowing. If removing the filters
corrects the problem, clean or replace with a less restrictive
filter. Also check and clean the blower wheel or coil as
necessary.
d.Check the external static pressure (total of both supply and
return) to insure that you are within the ranges as listed on the
unit serial plate. If higher than allowed, additional duct work
is needed.
e.If the motor does not shut off at the end of the cycle, wait for
any programmed delays to time out (no more than 90
seconds). Also make sure that there is no call for
“Continuous Fan” on the "G" terminal.
f. If the above diagnostics do not solve the problem, confirm the
voltage checks in the next section below, then continue with
the “Model X13 Communication Diagnostics”.
If the Motor is Not Running
1. Check for proper high voltage and ground at the (L/L1) (G) (N/
L2) connections at the motor (see Figure 10). Correct any voltage
issues before proceeding to the next step. The X13 Motor is voltage
specific. Only the correct voltage should be applied to the proper
motor. Input voltage within plus or minus 10% of the nominal 230
VAC is acceptable.
2. If the motor has proper high voltage and ground at the (L/L1)
(G) (N/L2) connections, then continue with the “Model X13
Communication Diagnostics”.
L2 LINE
POWER
EARTH
GROUND
L1 LINE
POWER
NOTE: MOTOR IS CONSTANTLY
POWERED BY LINE VOLTAGE
LINE
POWER
LINE
POWER
GROUND
41 of 54
31. REPLACEMENT PARTS
Replacement parts for the gas/electric units are
available through local distributors.
A replacement parts list manual is supplied with
each unit. When ordering parts or making inquires
pertaining to any of the units covered by these
WARNING
Use replacement parts listed in Replacement
Parts list. Failure to do so could cause
improper furnace operation, resulting in
property damage, personal injury or death.
FIGURE 21
Motor Connections
Manual
2100-467H
Page
23 of 23
FIGURE 11
24VAC "R" Signal through
thermostat output.
24VAC Common
24VAC Common
24VAC "R" Signal through
thermostat output.
Speed Tap 1: Balanced Climate Speed
Speed Tap 2: Cool Speed
Speed Tap 3: Cool High Speed
Speed Tap 4: Heat Speed
Speed Tap 5: Heat High Speed
instructions, it is very important to always supply the
complete model number and serial number of the unit.
This is necessary to assure that the correct parts (or
an approved alternate part) are issued to the service
agency.
42 of 54
32. SEQUENCE OF OPERATION –
HEATING
On a call for heat from the thermostat, the induced
draft blower is energized. Once sufficient draft is
established, the pressure switch contacts close and
the ignition system is energized. The direct spark
igniter will be energized allowing gas to flow. At the
same time the main valve is energized, a 30-second
blower delay timer is activated.
After this delay, the heating speed blower relay
energizes. The blower will begin operating and remain
in operation until the set delay time after the call
for heat has been satisfied. This timing sequence
guarantees blower on, blower off operation.
This unit is equipped with a flame roll-out switch,
which is wired in series with the control circuit. This
is a manual reset switch and is used for the purpose
of preventing possible fire hazard in the event of a
system malfunction. If this switch has opened the
control circuit, there could be a possible system
malfunction. Some of the conditions that might cause
a roll-out to occur are blockage or sooting of primary
heat exchanger, overfiring of furnace due to improper
main burner orifices or incorrect manifold pressure,
insufficient combustion air or installation deficiencies
with respect to return air duct design or sizing.
FIGURE 22
Sequence of Operation
Electronic Blower Control
Action
System Response
Thermostat calls for heat
(W terminal is energized).
• Combustion air blower is energized.
• Air proving switch makes. Airflow is established.
• Ignition system is energized.
• Gas valve opens and main burner lights.
• Heat fan on delay timing begins. When timing is complete, the circulating fan is
energized at heat speed.
Thermostat ends call for heat.
• Ignition system is de-energized and gas valve closes.
• Combustion air blower is de-energized after postpurge timing.
• Heat fan off delay timing begins. When timing is complete, the circulating fan is
de-energized.
Thermostat begins call for cool
(G and Y terminals re-energized).
• Cooling contactor is energized.
• Circulating fan is energized on cool speed after cool fan on delay timing.
Thermostat begins call for fan
(G terminal is de-energized).
• Circulating fan is de-energized
Limit (flame rollout) opens.
• Thermostat and ignition system are de-energized and gas valve closes.
• Combustion air blower and circulating fan heat speed are energized.
Limit (auto reset) or flame rollout
(manual reset) circuit closed.
• Combustion air blower remains energized for postpurge timing.
• The circulation fan remains energized for the selected delay off timing.
• Normal operation resumes.
Once the problem has been resolved, reset the switch
by pressing down on the reset button on top of the
switch. See Figure 22 for additional information.
33. SEQUENCE OF OPERATION –
COOLING
On a call for cooling from the room thermostat, the
blower relay will be energized as well as the compressor
contactor. Following termination of the cooling cycle,
the blower motor will continue to run for one minute.
See Figure 22 for additional information.
The unit may be equipped with a low ambient control
for lower outdoor temperature operation in the cooling
mode. If equipped with this optional control, the
condenser fan will not operate immediately upon
compressor start-up, and will cycle on and off until the
condensing pressure remains above 180 PSIG. Low
ambient control energizes the fan motor at 280 PSIG,
de-energizes at 180 PSIG.
43 of 54
34. SETTING UNIT AIRFLOW
All models have multiple speed direct drive blower
motors. If supply and return ducts are connected to
the unit, the ducts must be of adequate size. Refer
to the appropriate blower tables. See Tables 12, 13,
14, 15, 16 and 17 for maximum static pressures
acceptable. Note the minimum CFM for Heating and
Cooling operation.
The unit is set from the factory at the default speed.
W**G units have three (3) selectable speeds for cooling
and two (2) selectable speeds for heating. First set
the airflow for heating. For high static applications
the speed should be set to high. When in doubt,
note the allowable air temperature rise listed on the
name plate and using the procedure listed in Section
23, "Measuring Air Temperature Rise", measure the
air temperature rise. If the temperature rise is above
allowable range, the heating airflow must be increased.
To increase the heating airflow speed:
•
First disconnect power to the unit.
•
Open the control panel and find the furnace control
board (see Figure 23).
•
Remove the black wire from the unused terminal
and then remove the red wire from the heat
terminal.
•
Install the red wire on the unused terminal and the
black wire on the heat terminal.
•
Close the control panel and repeat the air
temperature rise test.
•
To reduce the heating airflow speed from high
to standard, move the black wire from the heat
terminal to the unused terminal and the red wire
from the unused terminal to the heat terminal.
The default speed for cooling is the rated cooling speed
that is listed in Tables 12, 13, 14, 15, 16 and 17.
The higher cooling speed tap can be used for higher
duct static applications or to increase the sensible
cooling capacity. The higher speeds can also be used
when higher sensible cooling is desired.
To increase the cooling airflow speed:
•
First disconnect power to the unit.
•
Open the control panel and find the terminal block
above the blower relay (see Figure 24 on page 44).
MIS-4138
RED
BLACK
FURNACE CONTROL BOARD
BLACK
RED
STANDARD TO HIGH
BLACK
RED
STANDARD HEATING AIRFLOW
RED
BLACK
HIGH HEATING AIRFLOW
MIS-4138
FIGURE 23
Increasing Heating Speed
44 of 54
•
Locate the orange and blue wires on the terminal
block below the furnace control board.
•
Switch the terminal landings on the terminal block.
•
Close the control panel.
•
To reduce the cooling airflow speed from high to
rated, reverse the blue and orange wires on the
terminal block below the furnace control board.
NOTE: Be sure to adjust the system static or blower
speed to maintain airflows above the minimum
recommendations to prevent freeze up conditions
if Balanced Climate mode is activated.
Do not operate the unit in Balanced Climate mode
if running high static applications as indicated in
the blower performance table. If Balanced Climate
mode is activated as described on page 22, the unit
will run in this mode at all times unless there is a
call for ventilation, electric heat or 2nd stage cooling
from a 2-stage thermostat. At that time, the unit will
automatically activate a higher speed tap.
Blower Speeds
Five factory programmed speed taps (torque settings)
are available for the motor, and are selected through
different unit modes of operation. These modes are
energized by 24VAC signals from the low voltage
terminal block located inside the control panel by a
thermostat or other controlling device. Each speed tap
is programmed by Bard at the factory to different motor
torque settings (see Figure 25).
Multiple motor speed taps may be energized
simultaneously by 24VAC power during different modes
of operation. The highest number speed tap energized
takes priority with 5 being the highest and 1 being the
lowest.
FIGURE 25
Speed Taps
Speed Tap 1: Balanced Climate Speed
Speed Tap 2: Cool Speed
Speed Tap 3: Cool High Speed
Speed Tap 4: Heat Speed
Speed Tap 5: Heat High Speed
Manual
2100-467H
Page
23 of 23
FIGURE 11
TROUBLESHOOTING GE X13-SERIES ECM2.3™ MOTORS CONT’D.
Model X13 Communication Diagnostics
The X13 motor is communicated through 24 VAC low voltage
(Thermostat Control Circuit Wiring).
1. Start with unit wiring diagram to confirm proper
connections and voltage (see Figure 11).
2. Initiate a demand from the thermostat and check the
voltage between the common and the appropriate motor
terminal (1-5). ("G" input is typically on terminal #1, but
refer to wiring diagram!)
a. If the low voltage communication is not present, check
the demand from the thermostat. Also check the
output terminal and wire(s) from the terminal strip or
control relay(s) to the motor.
b. If the motor has proper high voltage as identified
above (Motor not Running #1), and proper low voltage
to a programmed terminal, and is not operating, the
motor is failed, and will require replacement.
24VAC "R" Signal through
thermostat output.
24VAC Common
24VAC Common
24VAC "R" Signal through
thermostat output.
24VAC Common
24VAC "R"
signal through
thermostat output
FIGURE 24
Increasing Cooling Speed
TERMINAL
BLOCK
TERMINAL
BLOCK
BLUE
ORANGE/BLACK
ORANGE
TERMINAL
BLOCK
BLUE
ORANGE
ORANGE/BLACK
TERMINAL
BLOCK
BLUE
ORANGE
ORANGE/BLACK
MIS-4139
PURPLE
BLOWER
RELAY
BLACK/WHITE
BLUE
YELLOW/WHITE
ORANGE/BLACK
BLACK/WHITE
WIRE
ORANGE/BLACK
TERMINAL BLOCK IN REFERENCE TO LOCATION OF
BLUE
:
WIRE LOCATIONS ON
ORANGE
&
PLEASE NOTE
.
HIGH AIRFLOW
BLUE
ORANGE
B
ORANGE/BLACK
STANDARD RATED COOLING AIRFLOW
TO CHANGE FROM RATED TO HIGH
A
PINK
OPTIONAL
NOTE
A
RATED AIRFLOW
B HIGH COOLING AIRFLOW
45 of 54
TABLE 12
W24G4 Indoor Blower Performance @ 230 and 460 VOLTS
Recommended W24G cooling airflow range at rated 800 CFM @ 0.10 ESP (WC) is 700 - 910 CFM
Factory set on Rated speed for cooling and Medium speed for heating.
SG-3, RG-3, non-ducted application adjustment – Reduce airflow by 100 CFM for SG-3 and RG-3 installations
ESP
Inches
H2O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
90,000 BTU Input
81,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
670
928
1213
0.1
598
851
1141
1361
0.2
511
760
1055
1288
1373
1288
0.3
417
662
962
1214
1324
1214
0.4
323
564
870
1143
1278
1143
0.5
235
473
784
1077
1237
1077
1237
ESP
Inches
H2O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
68,000 BTU Input
61,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
670
928
1213
0.1
598
851
1141
0.2
511
760
1055
1288
0.3
417
662
962
1214
0.4
323
564
870
1143
1278
1143
0.5
235
473
784
1077
1237
1077
ESP
Inches
H2O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
45,000 BTU Input
41,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
670
928
1213
0.1
598
851
1141
1361
0.2
511
760
1055
1288
0.3
417
662
962
1214
1324
0.4
323
564
870
1143
1278
1143
0.5
235
473
784
1077
1237
1077
46 of 54
TABLE 13
W30G4 Indoor Blower Performance @ 230 AND 460 VOLTS
Recommended W30G cooling airflow range at rated 900 CFM @ 0.15 ESP (WC) is 750 - 1150 CFM
Factory set on Rated speed for cooling and Medium speed for heating.
Dehumidification coil adjustment – Reduce airflow by 35 CFM for dehumidification coil installed
SG-3, RG-3, non-ducted application adjustment – Reduce airflow by 100 CFM for SG-3 and RG-3 installations
ESP
Inches
H2O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
90,000 BTU Input
81,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
850
1022
1157
1281
0.1
769
953
1098
1237
1375
1237
0.2
688
883
1038
1188
1329
1188
0.3
606
812
975
1134
1279
1134
0.4
523
739
910
1075
1225
1075
1225
0.5
439
664
843
1011
1168
1011
1168
ESP
Inches
H2O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
68,000 BTU Input
61,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
850
1022
1157
1281
0.1
769
953
1098
1237
0.2
688
883
1038
1188
0.3
606
812
975
1134
1279
1134
0.4
523
739
910
1075
1225
1075
0.5
439
664
843
1011
1168
1011
ESP
Inches
H2O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
45,000 BTU Input
41,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
850
1022
1157
1281
0.1
769
953
1098
1237
0.2
688
883
1038
1188
1329
1188
0.3
606
812
975
1134
1279
1134
0.4
523
739
910
1075
1225
1075
0.5
439
664
843
1011
1168
1011
1168
47 of 54
TABLE 14
W36G4 Indoor Blower Performance @ 230 AND 460 VOLTS
Recommended W36G cooling airflow range at rated 1100 CFM @ 0.10 ESP (WC) is 940 - 1250 CFM
Factory set on Rated speed for cooling and Medium speed for heating.
SG-3, RG-3, non-ducted application adjustment – Reduce airflow by 100 CFM for SG-3 and RG-3 installations
ESP
Inches
H2O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
90,000 BTU Input
81,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
932
1202
1281
1281
0.1
855
1148
1238
1237
1375
1237
0.2
776
1091
1190
1188
1329
1188
0.3
695
1030
1139
1134
1279
1134
0.4
614
966
1083
1075
1225
1075
1225
0.5
530
898
1022
1011
1168
1011
1168
ESP
Inches
H2O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
68,000 BTU Input
61,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
932
1202
1281
1281
0.1
855
1148
1238
1237
0.2
776
1091
1190
1188
0.3
695
1030
1139
1134
1279
1134
0.4
614
966
1083
1075
1225
1075
0.5
530
898
1022
1011
1168
1011
ESP
Inches
H2O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
45,000 BTU Input
41,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
932
1202
1281
1281
0.1
855
1148
1238
1237
0.2
776
1091
1190
1188
1329
1188
0.3
695
1030
1139
1134
1279
1134
0.4
614
966
1083
1075
1225
1075
0.5
530
898
1022
1011
1168
1011
1168
48 of 54
TABLE 15
W42G4 Indoor Blower Performance @ 230 AND 460 VOLTS
Recommended W42G cooling airflow range at rated 1300 CFM @ .15 ESP (WC) is 1030 - 1480 CFM
Factory set on Rated speed for cooling and Medium speed for heating.
SG-5, RG-5, non-ducted application adjustment – Reduce airflow by 170 CFM for SG-5 and RG-5 installations
ESP
Inches
H2O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
125,000 BTU Input
113,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
1084
1394
1552
1788
0.1
1011
1335
1498
1734
0.2
930
1270
1439
1678
1678
0.3
840
1198
1374
1618
1618
0.4
741
1119
1305
1557
1811
1557
0.5
633
1034
1230
1492
1754
1492
ESP
Inches
H2O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
100,000 BTU Input
90,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
1084
1394
1552
1788
0.1
1011
1335
1498
1734
1734
0.2
930
1270
1439
1678
1678
0.3
840
1198
1374
1618
1870
1618
0.4
741
1119
1305
1557
1811
1557
0.5
633
1034
1230
1492
1754
1492
ESP
Inches
H2O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
75,000 BTU Input
68,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
1084
1394
1552
1788
0.1
1011
1335
1498
1734
0.2
930
1270
1439
1678
1678
0.3
840
1198
1374
1618
1870
1618
0.4
741
1119
1305
1557
1811
1557
0.5
633
1034
1230
1492
1754
1492
49 of 54
TABLE 16
W48G4 Indoor Blower Performance @ 230 AND 460 VOLTS
Recommended W48G cooling airflow range at rated 1450 CFM @ .20 ESP (WC) is 1150 - 1680 CFM
Factory set on Rated speed for cooling and Medium speed for heating.
SG-5, RG-5, non-ducted application adjustment – Reduce airflow by 170 CFM for SG-5 and RG-5 installations
ESP
Inches
H2O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
125,000 BTU Input
113,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
1185
1501
1668
1788
0.1
1118
1445
1616
1734
0.2
1042
1384
1560
1678
1678
0.3
958
1317
1500
1618
1618
0.4
866
1245
1436
1557
1811
1557
0.5
766
1167
1368
1492
1754
1492
ESP
Inches
H2O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
100,000 BTU Input
90,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
1185
1501
1668
1788
0.1
1118
1445
1616
1734
1734
0.2
1042
1384
1560
1678
1678
0.3
958
1317
1500
1618
1870
1618
0.4
866
1245
1436
1557
1811
1557
0.5
766
1167
1368
1492
1754
1492
ESP
Inches
H2O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
75,000 BTU Input
68,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
1185
1501
1668
1788
0.1
1118
1445
1616
1734
0.2
1042
1384
1560
1678
1678
0.3
958
1317
1500
1618
1870
1618
0.4
866
1245
1436
1557
1811
1557
0.5
766
1167
1368
1492
1754
1492
50 of 54
TABLE 17
W60G4 Indoor Blower Performance @ 230 AND 460 VOLTS
Recommended W60G cooling airflow range at rated 1650 CFM @ .20 ESP (WC) is 1360 - 1850 CFM
Factory set on Rated speed for cooling and Medium speed for heating.
SG-5, RG-5, non-ducted application adjustment – Reduce airflow by 170 CFM for SG-5 and RG-5 installations
ESP
Inches
H2O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
125,000 BTU Input
113,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
1347
1771
1881
1743
0.1
1272
1708
1823
1682
0.2
1199
1646
1766
1619
1843
1619
0.3
1128
1584
1709
1554
1783
1554
0.4
1060
1523
1652
1486
1721
1486
0.5
994
1462
1596
1417
1657
1417
1657
ESP
Inches
H2O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
100,000 BTU Input
90,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
1347
1771
1881
1743
0.1
1272
1708
1823
1682
1682
0.2
1199
1646
1766
1619
1843
1619
0.3
1128
1584
1709
1554
1783
1554
0.4
1060
1523
1652
1486
1721
1486
1721
0.5
994
1462
1596
1417
1657
1417
1657
ESP
Inches
H2O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
75,000 BTU Input
68,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
1347
1771
1881
1743
0.1
1272
1708
1823
1682
1682
0.2
1199
1646
1766
1619
1843
1619
0.3
1128
1584
1709
1554
1783
1554
0.4
1060
1523
1652
1486
1721
1486
1721
0.5
994
1462
1596
1417
1657
1417
1657
51 of 54
TABLE 18
Integrated Furnace and Blower Control Operation
IGNITION SEQUENCE CONTROL
Ignition Source
24 VAC DSI
Flame Sensing
Remote
Timings
- Prepurge
- Postpurge
- Inter-trial purge
- Pressure switch proving period
- Trials for ignition
- Trial for ignition
- Ignition sequence lockout
- Heat blower on - delay
- Heat blower off - delay
- Cool blower on - delay
- Cool blower off - delay
- Manual fan operations
- High limit control operation
- Flame rollout switch operation
15 seconds
30 seconds (0 if cycle terminated before valve “on”)
15 seconds
60 seconds
3 per ignition sequence
7 seconds total time to prove flame
60 minutes (after 3 trials for ignition), auto reset
- can be reset during the 60-minute lockout period by opening thermostat
circuit for 3 seconds or more
30 seconds (timing starts when ignitor cycles off)
90, 120, 150 seconds selectable; factory set at 120
7 seconds
60 seconds
Operates on selected heating speed and cycles off during ignition or burner
start-up sequence.
Automatic reset, ignition sequence restart. See Note 1.
Manual reset, igniton sequence initiated after switch is manually reset.
See Note 1.
NOTE 1: After the fourth limit trip on a given call for heat, there will be a 1-hour delay before the ignition sequence will restart.
After either high limit switch or flame rollout switch actuation, the inducer will operate for the 30-second postpurge and the
comfort air blower will operate for the selected off delay. If on Manual Fan operation, the comfort air blower will continue to
operate.
SAFETY UNITS
High limit/Rollout
Pressure switch
SPST in 24 Volt
SPST, safe start check
COMFORT FAN CONTROL
Heating Speed Fan
Normal operation
- ON delay
- OFF delay
Limit Operation
Flame Sense
30 seconds fixed. Timing starts when igniter de-energized.
3 selectable timings – 120 seconds standard can be changed to 90 or 150
seconds.
ON when limit OPEN
OFF after OFF delay when limit CLOSES
ON if flame is sensed and there is no call for heat.
Cooling Speed Fan
- ON delay
- OFF delay
7 seconds
60 seconds
Manual Fan
ON continuously on HEATING speed. When call for cool, the fan switches
to COOLING speed. Then when thermostat satisfied, the fan switches back
to HEATING speed after COOLING OFF delay.
DIAGNOSTIC INDICATOR
A red LED is provided to indicate system faults as follows:
Steady ON - Control okay in standby, call for heat, cool or fan modes
Steady OFF - Internal control fault or no power. Also check 3A fuse on control.
1 flash - Lockout due to failed ignition or flame dropouts
2 flashes - Pressure switch open with inducer on
3 flashes - Pressure switch is closed with inducer off
4 flashes - Limit switch is open
5 flashes - Flame detected with gas valve closed
6 flashes - Compressor output delayed from short cycle/staging timer
The flash rate is 0.25 seconds on, 0.25 seconds off with 2.0 seconds pause between flash codes.
52 of 54
35. PRESSURE SERVICE PORTS
High and low pressure service ports are installed on
all units so that the system operating pressures can
be observed. Table 19 outlines expected pressures at
various indoor and outdoor temperatures.
This unit employs high-flow Coremax valves instead of
the typical Shrader type valves.
TABLE 19
Cooling Pressure Table
Model
Return Air
Temperature
Pressure
75°
80°
85°
90°
95°
100°
105°
110°
115°
120°
125°
W24G4
75° DB
62° WB
Low Side
High Side
119.7
298.0
122.6
318.5
125.3
340.2
127.9
363.0
130.3
386.9
132.8
411.8
135.0
438.0
137.2
465.3
139.1
493.6
141.0
523.2
142.8
553.8
80° DB
67° WB
Low Side
High Side
128.0
305.6
131.1
326.7
134.0
348.9
136.8
372.3
139.4
396.8
142.0
422.4
144.4
449.2
146.7
477.2
148.8
506.3
150.8
536.6
152.7
568.0
85° DB
72° WB
Low Side
High Side
132.5
316.3
135.7
338.1
138.7
361.1
141.6
385.3
144.3
410.7
147.0
437.2
149.5
464.9
151.8
493.9
154.0
524.0
156.1
555.4
158.0
587.9
W30G4
75° DB
62° WB
Low Side
High Side
120.1
297.7
122.7
318.0
125.2
339.5
127.6
362.0
130.0
385.5
132.3
410.0
134.5
435.5
136.8
462.2
138.9
489.7
141.0
518.4
143.1
548.1
80° DB
67° WB
Low Side
High Side
128.5
305.3
131.2
326.2
133.9
348.2
136.5
371.3
139.0
395.4
141.5
420.5
143.9
446.7
146.3
474.0
148.6
502.3
150.8
531.7
153.0
562.2
85° DB
72° WB
Low Side
High Side
133.0
316.0
135.8
337.6
138.6
360.4
141.3
384.3
143.9
409.2
146.5
435.2
148.9
462.3
151.4
490.6
153.8
519.9
156.1
550.3
158.4
581.9
W36G4
75° DB
62° WB
Low Side
High Side
124.4
312.6
126.8
334.9
129.1
357.9
131.3
381.6
133.4
405.9
135.4
431.0
137.4
456.7
139.1
483.1
140.9
510.2
142.6
538.0
144.2
566.5
80° DB
67° WB
Low Side
High Side
133.1
320.6
135.6
343.5
138.1
367.1
140.4
391.4
142.7
416.3
144.8
442.0
146.9
468.4
148.8
495.5
150.7
523.3
152.5
551.8
154.2
581.0
85° DB
72° WB
Low Side
High Side
137.8
331.8
140.3
355.5
142.9
379.9
145.3
405.1
147.7
430.9
149.9
457.5
152.0
484.9
154.0
512.8
156.0
541.6
157.8
571.1
159.6
601.3
W42G4
75° DB
62° WB
Low Side
High Side
124.7
328.7
127.4
350.3
130.0
373.0
132.3
396.7
134.6
421.4
136.7
447.1
138.8
473.8
140.6
501.4
142.3
530.1
143.9
559.7
145.4
590.4
80° DB
67° WB
Low Side
High Side
133.4
337.1
136.3
359.3
139.0
382.6
141.5
406.9
144.0
432.2
146.2
458.6
148.4
485.9
150.4
514.3
152.2
543.7
153.9
574.1
155.5
605.5
85° DB
72° WB
Low Side
High Side
138.1
348.9
141.1
371.9
143.9
396.0
146.5
421.1
149.0
447.3
151.3
474.7
153.6
502.9
155.7
532.3
157.5
562.7
159.3
594.2
W48G4
75° DB
62° WB
Low Side
High Side
124.9
325.9
126.8
347.5
128.7
369.8
130.4
392.9
132.2
416.9
134.0
441.7
135.8
467.2
137.5
493.6
139.3
520.8
141.0
548.9
142.7
577.8
80° DB
67° WB
Low Side
High Side
133.6
334.3
135.6
356.4
137.6
379.3
139.5
403.0
141.4
427.6
143.3
453.0
145.2
479.2
147.1
506.3
149.0
534.2
150.8
563.0
152.6
592.6
85° DB
72° WB
Low Side
High Side
138.3
346.0
140.3
368.9
142.4
392.6
144.4
417.1
146.3
442.6
148.3
468.9
150.3
496.0
152.2
524.0
154.2
552.9
156.1
582.7
157.9
613.3
W60G4
75° DB
62° WB
Low Side
High Side
123.3
309.0
125.1
329.6
127.0
351.4
128.8
374.2
130.6
398.2
132.5
423.3
134.3
449.6
136.1
477.0
137.9
505.5
139.8
535.2
141.6
566.0
80° DB
67° WB
Low Side
High Side
131.9
316.9
133.8
338.1
135.8
360.4
137.8
383.8
139.7
408.4
141.7
434.2
143.6
461.1
145.6
489.2
147.5
518.5
149.5
548.9
151.4
580.5
85° DB
72° WB
Low Side
High Side
136.5
328.0
138.5
349.9
140.6
373.0
142.6
397.2
144.6
422.7
146.7
449.4
148.6
477.2
150.7
506.3
152.7
536.6
154.7
568.1
156.7
600.8
WARNING! Do NOT use a Schrader valve core removal
tool with these valves. Use of such a tool could result
in eye injuries or refrigerant burns!
To change a Coremax valve without first removing the
refrigerant, a special tool is required which can be
obtained at www.fastestinc.com/en/SCCA07H. See the
replacement parts manual for replacement core part
numbers.
Low side pressure ± 4 PSIG High side pressure ±10 PSIG
Tables based upon rated CFM (airflow) across the evaporator coil.
If there is any doubt as to correct operating charge being in the system, the charge should be reclaimed, and the system
evacuated and recharged to serial plate instruction.
53 of 54
"A"
AIRFLOW
MIS-1724
TABLE 20
Fan Blade Dimension
FIGURE 26
Fan Blade
38. LOW-NOX BURNER ASSEMBLY “N”
SUFFIX MODELS ONLY –
U.S. INSTALLATIONS ONLY
Natural Gas Models Only
Model numbers designated with an “N” are designed
for low NOx emissions which comply with all California
Air Quality Management District regulations for
nitrogen oxide emission levels. Refer to Figure 27 for
NOx insert information.
* * IMPORTANT * *
For propane (LP) conversions, the NOx
reduction screen inserts shown below must be
removed. This is accomplished by removing
the burner box assembly and removing the
NOx screens. Reassemble unit properly before
firing. Failure to remove the NOx screens can
result in improper operation and malfunction of
the burner system.
FIGURE 27
Low NOx Insert
36. R-410A REFRIGERANT CHARGE
This unit was charged at the factory with the quantity
of refrigerant listed on the serial plate. AHRI capacity
and efficiency ratings were determined by testing with
this refrigerant charge quantity.
Table 19 shows nominal pressures for the units. Since
many installation specific situations can affect the
pressure readings, this information should only be used
by certified technicians as a guide for evaluating proper
system performance. They shall not be used to adjust
charge. If charge is in doubt, reclaim, evacuate and
recharge the unit to the serial plate charge.
37. FAN BLADE SETTING DIMENSIONS
The correct fan blade setting dimension for proper air
delivery across the outdoor coil is shown in Figure 26.
Model
Dimension A
W24G
1.25
W30G
1.25
W36G
1.25
W42G
1.75
W48G
1.75
W60G
1.75
54 of 54
INDEX
Wiring Diagrams
Unit
Model No.
Basic
Wiring Diagram
W24G4-A
4085-177
W24G4-B
4085-277
W24G4-C
4085-400
W30G4-A
4085-177
W30G4-B
4085-277
W30G4-C
4085-400
W36G4-A
4085-177
W36G4-B
4085-277
W36G4-C
4085-400
W42G4-A
4085-177
W42G4-B
4085-277
W42G4-C
4085-400
W48G4-A
4085-177
W48G4-B
4085-277
W48G4-C
4085-400
W60G4-A
4085-175
W60G4-B
4085-275
W60G4-C
4085-398