Bender ISOMETER isoNAV685-D-B Quick Start Manual
Read Online
Read the Bender ISOMETER isoNAV685-D-B Quick Start Manual online using the built-in PDF viewer.
Text of the manual
Insulation monitoring device
This quickstart guide does not replace the operating manual.
Intended use
The ISOMETER® isoNAV685-D-B monitors the insulation resis-
tance of loads that are switched off. These loads, which are tem-
porarily or mostly switched off, are powered by TN, TT or IT
systems.
The internal mains switch has a circuit capacity of AC 0…690 V
and DC 0…1000 V.
Due to the separate supply voltage, de-energised systems can
also be monitored. The maximum permissible system leakage
capacitance is 150 μF.
Functional description
The insulation monitoring device ISOMETER® isoNAV685-D-B
monitors the entire insulation resistance of systems that are swit-
ched off and triggers an alarm when the insulation resistance va-
lue falls below a preset response value.
The insulation resistance of the L1, L2 and L3 coupling paths is
measured sequentially. This means that faults are not only mea-
sured, but they can also be localized or located. The test time may
vary, e.g. it may be longer, depending on the leakage
capacitance.
Isolationsüberwachungsgerät
Diese Kurzanleitung ersetzt nicht das Handbuch.
Bestimmungsgemäße Verwendung
ISOMETER® isoNAV685-D-B überwacht den Isolationswiderstand
von Verbrauchern im abgeschalteten Zustand. Diese zeitweise
oder überwiegend abgeschalteten Verbraucher werden aus TN-,
TT- oder IT-Systemen gespeist.
Die internen Netztrennschalter haben ein Schaltungsvermögen
von AC 0…690 V und DC 0…1000 V.
Durch die separate Versorgungsspannung ist auch die Überwa-
chung eines spannungslosen Systems möglich. Die maximal zu-
lässige Netzableitkapazität beträgt 150 μF.
Funktionsbeschreibung
Das ISOMETER® isoNAV685-D-B überwacht den gesamten Isolati-
onswiderstand eines abgeschalteten Systems und löst einen
Alarm aus, wenn der eingestellte Ansprechwert unterschritten
wird.
Der Isolationswiderstand der L1, L2 und L3 Netzankoppelpunkte
wird sequentiell gemessen. Dadurch können Fehler nicht nur ge-
messen sondern auch lokalisiert werden.
Abhängig von der Netzableitkapazität kann sich die Messzeit ver-
längern.
108 mm
110 mm
m
m
3
9
IT System
3x
230 kΩ
1/4
230 kΩ
ISOMETER® isoNAV685-D-B
isoNAV685-D-B_D00264_02_Q_DEEN/04.2017
DE
EN
Consider a minimum distance to adjacent devices: lateral 0 mm,
top 20 mm, bottom 20 mm!
DIN rail mounting:
Snap all 3 mounting clips delivered with the device (2 of them pa-
cked separately) onto the DIN rail in such a way that a safe and
tight fit is ensured.
Screw mounting
Install the three accompanying mounting clips (2 are packed
separately) manually or by means of a tool in a way that they pro-
trude beyond the enclosure. Fix the device by means of three M4
screws (no counter sunk screw) as shown in the following
pictures.
Risk of electric shock!
The terminals carry high voltage and direct contact with
these terminals will likely result in electrocution. If the
terminals L1/+, L2, L3/- of the device are connected to a
live IT system, the terminals E and KE must not be discon-
nected from the protective conductor (PE).
Risk of damage to property due to incorrect
installation!
There should only be one insulation monitoring device
per conductively connected installation. Damage to the
installation may result if several insulation monitoring
devices are connected. In addition, the device will not
function and will not report an insulation fault if more
than one insulation monitoring device is connected.
Disconnect from the IT system!
The insulation monitoring device must be disconnected
from the IT system before insulation or voltage tests at
the installation and must remain so for the duration of
the test. Otherwise the device may be damaged.
DANGER
CAUTION
CAUTION
Sicherheitshinweise
Montage
Beachten Sie den Mindestabstand zu benachbarten Geräten:
seitlich 0 mm, oben 20 mm, unten 20 mm!
Montage auf Hutschiene
Rasten Sie alle 3 mitgelieferten Montageclips (2 separat verpackt)
des Geräts auf der Hutschiene unten so ein, dass ein sicherer und
fester Sitz gewährleistet ist.
Schraubbefestigung
Bringen Sie die 3 mitgelieferten Montageclips (2 separat ver-
packt) manuell oder mittels Werkzeug in eine über das Gehäuse
hinaus ragende Rastposition. Befestigen Sie das Gerät mit drei
M4-Schrauben (kein Senkkopf), siehe nachfolgende Skizze.
Gefahr eines elektrischen Schlages!
An den Klemmen liegt eine hohe Spannung an, die bei
direkter Berührung lebensgefährlich ist. Ist das Gerät mit
den Klemmen L1/+, L2, L3/- an ein betriebsbedingt span-
nungsführendes IT-System angeschlossen, dürfen die
Klemmen KE und E nicht vom Schutzleiter (PE) getrennt
werden.
Gefahr von Sachschaden durch unsachgemäße
Installation!
Die Anlage kann Schaden nehmen, wenn Sie mehr als
ein Isolationsüberwachungsgerät anschließen. Sind me-
hrere Geräte angeschlossen, funktioniert das Gerät nicht
und meldet keine Isolationsfehler. Schließen Sie in jedem
leitend verbundenen System nur ein ISOMETER® an.
Trennung vom IT-System beachten!
Bei Isolations- und Spannungsprüfungen an der Anlage
muss das Isolationsüberwachungsgerät für die Dauer
der Prüfung vom IT-System getrennt sein. Andernfalls
kann das Gerät Schaden nehmen.
GEFAHR
VORSICHT
VORSICHT
Screw mounting
DIN rail mounting
72 mm
108 mm
54 mm
100 mm
107,3 mm
Wire up the device according to the wiring diagram taking ac-
count of the technical data. After connecting the device, install
the enclosed upper and lower terminal cover!
Risk of electric shock!
A nominal voltage of up to 1000 V may be present at the
terminals L1/+…L3/–. Direct contact with these will
likely result in electrocution. Make sure the terminal co-
vers are properly mounted and clicked in before putting
the device into operation.
Danger of injury, fire and damage to property due to
a short circuit!
When coupling the terminals L1/+, L2, L3/- to the IT sys-
tem ≤690 V to be monitored, devices for protection
against a short-circuit can be omitted according to
IEC 60364-4-43:2008 or DIN VDE 0100430 (German ver-
sion) if the wiring is carried out in such a way as to reduce
the risk of a short-circuit to a minimum. The use of short-
circuit
proof
and
earth-fault
proof
wiring
is
recommended.
Provide line protection!
According to DIN VDE 0100-430, a line protection shall
be provided for the supply voltage.
The ISOMETER® may only be used for monitoring de-
energized systems. The device must be deactivated via
the digital input before the mains voltage is switched on.
Connection to X1:
External Power supply for powering ISOMETER® via ter-
minal X1 must fulfil immunity and emission standards of
the required application. For wiring longer than 1 m the
use of a shielded cable is prescribed.
DANGER
WARNING
CAUTION
Anschluss
Verdrahten Sie das Gerät gemäß Anschlussplan. Beachten Sie da-
bei die technischen Daten. Montieren Sie nach dem Anschluss
die obere und die untere mitgelieferte Klemmenabdeckung!
Gefahr eines elektrischen Schlages!
An den Klemmen L1/+…L3/- können Nennspannungen
bis 1000 V anliegen, die bei direkter Berührung lebensge-
fährlich sein können. Nehmen Sie das Gerät nur mit
montierten und eingerasteten Klemmenabdeckungen
in Betrieb.
Gefahr von Verletzungen, Bränden und Sachschä-
den durch Kurzschluss!
Entsprechend DIN VDE 0100-430 können Sie auf Schut-
zeinrichtungen zum Schutz bei Kurzschluss für die Anko-
pplung der Klemmen L1/+, L2, L3/- an das zu
überwachende IT-System verzichten, wenn die Leitung
oder das Kabel so ausgeführt ist, dass die Gefahr eines
Kurzschlusses auf ein Mindestmaß beschränkt ist.
Achten Sie auf kurz- und erdschlussfeste Verlegung.
Leitungsschutz vorsehen!
Gemäß der DIN VDE 0100-430 ist bei der Versor-
gungsspannung ein Leitungsschutz vorzusehen.
Das ISOMETER® darf nur zur Überwachung von span-
nungslosen Systemen eingesetzt werden. Das Gerät
muss über den Digitaleingang deaktiviert werden, bevor
die Netzspannung zugeschaltet wird.
Anschluss an X1:
Externe Netzteile, zur Spannungsversorgung des
ISOMETER®s über die Klemme X1, müssen den Störfesti-
gkeits- und Emissionsanforderungen der geforderten
Applikationsnorm entsprechen. Für Verbindungsleitun-
gen, die länger als 1 m sind, müssen geschirmte Leitun-
gen verwendet werden.
GEFAHR
WARNUNG
VORSICHT
Legend to terminal diagram
Terminal
Connections
I1…I3
(X1)
Configurable digital inputs (e.g. Test, Reset).
A, B
(X1)
Serial interface RS-485
termination by means of a DIP switch R (OFF, ON).
+
(X1)
Supply voltage of the inputs and outputs I, Q and M.
Electrical overload protection. Automatic shutdown in the
event of a short circuit and transient (resettable).
If the supply is via an external 24 V source, then A1/+, A2/- must
not be connected.
Q1, Q2
(X1)
Configurable digital output
M+
(X1)
Configurable analogue output
(X1)
Reference potential ground
RJ45
(ETH)
Ethernet connection
R
Switchable terminating resistor
Anschlussplan
Legende zum Anschlussplan
Klemme
Anschlüsse
I1…I3
(X1)
Konfigurierbare digitale Eingänge (z. B. Test, Reset).
A, B
(X1)
Serielle Schnittstelle RS-485
Terminierung mittels DIP-Schalter R (OFF, ON).
+
(X1)
Versorgungsspannung der Ein- und Ausgänge I, Q und M.
Elektr. Überlastschutz. Autom. Abschaltung bei Kurzschluss
und Transiente (rücksetzbar).
Bei Versorgung über ein externes 24-V-Netzteil dürfen
A1/+,A2/- nicht angeschlossen werden.
Q1, Q2
(X1)
Konfigurierbarer digitaler Ausgang
M+
(X1)
Konfigurierbarer analoger Ausgang
(X1)
Bezugspotential Masse
RJ45
(ETH)
Ethernet-Anschluss
R
Zuschaltbarer Abschlusswiderstand
Qx
X1
+
Qx
X1
+
I
X1
+
Ix
X1
M+
X1
X1
A
M+
X1
X1
V
Passive
Active
Active high
x
Active low
Current output
Voltage output
X1
X1
X1
X1
Digital outputs
Digital inputs
Analogue output
L1
L2
L3
N
PE
US
A1/+
A2/-
11
R
ETH
X1
12
14
21
22
24
L1/+
L2
L3/-
KE
E
8
7
3(N)AC
I1 I2 I3 A B
Q1
+
Q2 M+
X1
IT System
OK
L1 230 kΩ
L2 250 kΩ
L3 130 kΩ
R(an)
50kΩ
OK
L1 230 kΩ
L2 250 kΩ
L3 130 kΩ
PE
M
DC+
DC-
AC
KE
E
IT System
OK
230 kΩ
R(an) 40kΩ/10kΩ
OK
230 kΩ
L1/+
L2
L3/-
L1/+
L2
L3/-
KE E
3
=
3
=
Anschluss an einen Frequenzumrichter zur Überwachung im abgeschalteten
Zustand (Offline)
Connection to a frequency converter to monitor in the off state (Offline)
Allgemeiner Ablauf der Inbetriebnahme
1. Prüfen Sie den korrekten Anschluss des ISOMETER®s an das
zu überwachende Netz.
2. Schalten Sie die Versorgungsspannung für das ISOMETER® zu.
3. Schalten Sie die Netzspannung zu.
4. Das Gerät führt einen vierstufigen Selbsttest durch, die
Alarmrelais werden dabei nicht geprüft. Danach erscheint im
Display der ermittelte Isolationswiderstand. Liegt er über
den in der untersten Zeile eingeblendeten Ansprechwerten,
wird zusätzlich die Meldung „OK“ angezeigt. Wird während
des Selbsttests ein Fehler erkannt, erscheint im Display eine
Fehlermeldung.
5. Funktion mit einem echten Isolationsfehler prüfen. Das
ISOMETER® ist am überwachten Netz z. B. mit einem dafür
geeigneten Widerstand gegen Erde zu prüfen.
Alarm und seine Wirkung
Ursachen für eine Alarmmeldung
• Isolationsfehler
– Der gemessene Isolationswiderstand an L1 und L2
unterschreitet den Ansprechwert.
– LED ALARM 1 leuchtet.
• Isolationsfehler
– Der gemessene Isolationswiderstand an L3 unterschrei-
tet den Ansprechwert.
– LED ALARM 2 leuchtet.
• Gerätefehler
– Interner Gerätefehler.
– LED SERVICE leuchtet.
Inbetriebnahme ISOMETER®
Ggf. Grundeinstellungen
anpassen
Gerät anschließen gemäß
Anschlussplan
Versorgungsspannung zuschalten
Netzspannung zuschalten
Das ISOMETER® führt einen
Selbsttest durch
Funktionsprüfung mit geeignetem
Widerstand von Netz nach Erde,
Größe: 50% des Ansprechwertes
Alarm2
Widerstand entfernen
Das ISOMETER® ist
funktionstüchtig und richtig
angeschlossen
Commissioning of the device
Commissioning scheme
General commissioning process
1. Check that the ISOMETER® is properly connected to the sys-
tem to be monitored.
2. Connect the supply voltage to the ISOMETER®.
3. Connect the mains voltage.
4. The device carries out a self test in four steps. However, the
alarm relays are not checked during this test. After comple-
tion of the test, the measured insulation resistance is shown
on the display. If the value exceeds the response values
indicated in the lowest line of the display, the message "OK"
will additionally be displayed. If a fault is detected during the
self test, a fault message will appear on the display.
5. Check the function using a genuine insulation fault. Check
the ISOMETER® in the system being monitored, e.g. using a
suitable resistance against earth.
Alarm and its effect
Cause of the alarm
• Insulation fault
– The insulation resistance of the L1 and L2 coupling
paths falls below a preset response value.
– LED ALARM 1 flashes.
• Insulation fault
– The insulation resistance of L3 coupling path falls below
a preset response value.
– LED ALARM 2 flashes.
• Device error
– Internal device error.
– LED SERVICE flashes.
Commissioning the ISOMETER®
Adjust basic settings if
necessary
Install the device according to the
wiring diagram
and documentation
Connect the supply voltage
Connect the system voltage
The ISOMETER® performs a self
test
Function test with a suitable
resistance between system and
earth. Resistance value: 50% of
the response value Alarm 2
Remove the resistance
The ISOMETER® is properly
connected and
functions reliably
Run the commissioning
wizard
Gerät meldet Alarm bzw. Gerätefehler
• Das Display zeigt den Fehler und ggf. den Messwert an.
• Bei einem Isolationsfehler und Gerätefehler leuchten die
zugehörigen LEDs.
• Alarmton ertönt intervallweise, wenn zugeordnet.
• Zugeordnete Alarmrelais schalten.
• Zugeordnete digitale Ausgänge schalten.
Alarmmeldungen zurücksetzen (Reset)
Voraussetzung: Ursache für Alarmmeldung besteht nicht mehr.
Isolationswiderstand muss mindestens 25 % über dem Ansprech-
wert liegen.
Wählen Sie: „RESET“ > „RESET“ > „OK“.
Werkseinstellungen
Ansprechwerte
Ansprechwert Ran
50 kΩ
Anlaufverzögerung TAnlauf
30 s
Schnittstellen
IP-Adresse
manuell 192.168.0.5
Netzmaske
255.255.255.0
BCOM-Adresse
system-1-0
Digitale Eingänge
Arbeitsweise
X1.I1 & X1.I3:
high-aktiv
Funktionen
X1.I1: Reset;
X1.I3: Gerät deaktivieren
Schaltglieder
Arbeitsweise
Ruhestrom
Kontakt 11-12-14
Funktion 1: Alarm L1
Funktion 2: Alarm L2
Kontakt 21-22-24
Funktion 1: Alarm L3
Sonstiges
Netzform
3 AC
Sprache
Deutsch
Ankoppelüberwachung
aus
Fehlerspeicher
aus
Profil
Offline
Device signals alarm or device error
• The display indicates an error and, where applicable, the
measured value.
• In the event of an insulation fault or a device error, the
associated LEDs flash.
• A warning sound beeps at certain intervals, if assigned
accordingly.
• Assigned alarm relays will switch.
• Assigned digital outputs will switch.
Reset alarm messages (Reset)
Requirement: The cause of the alarm is no longer present. The in-
sulation resistance must be at least 25 % higher than the re-
sponse value.
Select: "RESET" > "RESET" > "OK".
Factory settings
Response values
Response value Ran1
50 kΩ
Startup delay Tstartup
30s
Interfaces
IP-Adress
manual 192.168.0.5
Network mask
255.255.255.0
BCOM Address
system-1-0
Digital Inputs
Operating mode
X1.I1 & X1.I3:
active high
Functions
X1.I1: Reset;
X1.I3: deactivate device
Switching elements
Operating principle
NC operation
Contact 11-12-14
Function 1: Alarm L1
Function 2: Alarm L2
Contact 21-22-24
Function 1: Alarm L3
Other
Power supply system
3 AC
Language
German
Coupling monitoring
off
Fault memory
off
Profile
Offline
Bemessungsspannung.............................................................................................................................. 1000 V
Überspannungskategorie....................................................................................................................................III
Bemessungs-Stoßspannung (IEC 60664-1) ................................................................................................ 8 kV
Verschmutzungsgrad (Un < 690 V) .................................................................................................................. 3
Verschmutzungsgrad (Un < 1000 V) ................................................................................................................ 2
Sichere Trennung (≤ 2000 m NN) zwischen ........................................................................ (L1/+,L2,L3/-) –
...............................................................................(A1,A2) – (11,12,14) – (21,22,24) – (E, KE), (X1, ETH, X3)
Spannungsprüfung, Stückprüfung (IEC 61010-1) .............................................................................. AC 2,2 kV
Versorgungsspannung
Versorgung über A1/+,A2/-:
Versorgungsspannungsbereich Us ........................................................................................ AC/DC 24…240 V
Toleranz von US..............................................................................................................................-30…+15 %
Frequenzbereich von Us ........................................................................................................... DC, 50…400 Hz
Versorgung über X1:
Versorgungsspannung Us.........................................................................................................................DC 24 V
Toleranz von Us ........................................................................................................................DC -20…+25 %
Überwachtes IT-System
Netznennspannungsbereich Un ................................................................................................................. offline
Schaltvermögen interne Netztrennschalter........................................................AC 0…690 V, DC 0…1000 V
...........................................................................................................AC/DC 0…600 V (für UL Anwendungen)
Ansprechwerte
Ansprechwert Ran ......................................................................................................................... 1 kΩ…10 MΩ
Ansprechunsicherheit (nach IEC 61557-8)...................................................................... ±15 %, mind. ±1 kΩ
Zeitverhalten
Ansprechzeit tan bei RF = 0,5 x Ran (Ran = 50 kΩ) und Ce = 1 μF nach IEC 61557-8..................................30 s
Schnittstellen
Feldbus: Schnittstelle/Protokoll.........................................................................Webserver/Modbus TCP/BCOM
Feldbus: Funktion.................................................................................................. Kommunikationsschnittstelle
Schaltglieder
Schaltglieder ....................................................................................................................................... 2 Wechsler
Arbeitsweise .......................................................................................... Ruhestrom (N/C) /Arbeitsstrom (N/O)
Kontakt 11-12-14.........................................................Keine, Alarm L1, Alarm L2, Alarm L3, Anschlussfehler,
.....................................................................................................................................Gerätefehler, Gerät inaktiv
Kontakt 21-22-24.........................................................Keine, Alarm L1, Alarm L2, Alarm L3, Anschlussfehler,
.....................................................................................................................................Gerätefehler, Gerät inaktiv
Elektrische Lebensdauer bei Bemessungsbedingungen.......................................................10.000 Schaltspiele
Kontaktdaten nach IEC 60947-5-1
Gebrauchskategorie ............................................................................. AC-13 /AC-14 / DC-12 / DC-12 / DC-12
Bemessungsbetriebsspg. ......................................................................... 230 V / 230 V / 24 V / 110 V / 220 V
Bemessungsbetriebsstrom .................................................................................... 5 A / 3A / 1 A / 0,2 A / 0,1 A
Bemessungsisolationsspannung ≤2000 m NN ......................................................................................... 250 V
Bemessungsisolationsspannung ≤3000 m NN ......................................................................................... 160 V
Minimale Kontaktbelastbarkeit ..................................................................................... 1 mA bei AC/DC ≥10 V
Sonstiges
EMV ........................................................................................................................................... IEC 61326-2-4 (1
Schutzart Einbauten ..................................................................................................................................... IP40
Schutzart Klemmen ....................................................................................................................................... IP20
1) Dies ist eine Einrichtung der Klasse A. Diese Einrichtung kann im Wohnbereich Funkstörungen verursachen.
In diesem Fall kann vom Betreiber verlangt werden, angemessene Maßnahmen durchzuführen.
Technical data
Insulation co-ordination
Rated insulation voltage (IEC 60664-1) ................................................................................................... 1000 V
Rated impulse voltage (IEC 60664-1) .......................................................................................................... 8 kV
Overvoltage category..........................................................................................................................................III
Pollution degree (Un < 690 V) .......................................................................................................................... 3
Pollution degree (Un < 1000 V) ........................................................................................................................ 2
Protective separation (≤ 2000 m NN) between..................................................................... L1/+,L2,L3/-) –
...............................................................................(A1,A2) – (11,12,14) – (21,22,24) – (E, KE), (X1, ETH, X3)
Voltage test, routine test (IEC 61010-1) ............................................................................................. AC 2,2 kV
Supply voltage
Supply via A1/+,A2/-:
Supply voltage range Us ........................................................................................................ AC/DC 24…240 V
Tolerance of Us .............................................................................................................................. -30…+15%
Frequency range of Us ............................................................................................................. DC, 50…400 Hz
Supply via X1:
Supply voltage Us......................................................................................................................................DC 24 V
Tolerance of Us ........................................................................................................................ DC -20…+25 %
IT system being monitored
Nominal system voltage range Un...............................................................................................................offline
Circuit capacity internal mains switch.................................................................AC 0…690 V, DC 0…1000 V
........................................................................................................... AC/DC 0…600 V (für UL Anwendungen)
Response values
Response value Ran ...................................................................................................................... 1 kΩ…10 MΩ
Operating uncertainty (acc. to IEC 61557-8)..................................................................±15 %, at least ±1 kΩ
Time response
Response time tan at RF = 0.5 x Ran (Ran = 50 kΩ) and Ce = 1 μF according to IEC 61557-8..................... 30 s
Interfaces
Field bus: Interface/protocol............................................................................. Webserver/Modbus TCP/BCOM
Field bus: Function....................................................................................................... communication interface
Switching elements
Switching elements......................................................................................................... 2 changeover contacts
Operating principle ................................................................................................N/C operation/N/O operation
Contact 11-12-14 .........................................................none, Alarm L1, Alarm L2, Alarm L3, connection fault,
...................................................................................................................................device fault, device inactive
Contact 21-22-24 .........................................................none, Alarm L1, Alarm L2, Alarm L3, connection fault,
...................................................................................................................................device fault, device inactive
Electrical endurance under rated operating conditions, number of cycles...............................................10,000
Contact data acc. to IEC 60947-5-1:
Utilisation category..............................................................................AC-13 / AC-14 / DC-12 / DC-12 / DC-12
Rated operational voltage..........................................................................230 V / 230 V / 24 V / 110 V / 220 V
Rated operational current...................................................................................... 5 A / 3 A / 1 A / 0.2 A / 0.1 A
Rated insulation voltage ≤ 2000 m NN.......................................................................................................250 V
Rated insulation voltage ≤ 3000 m NN.......................................................................................................160 V
Minimum contact rating...................................................................................................1 mA at AC/DC ≥ 10 V
Other
EMC ........................................................................................................................................... IEC 61326-2-4 (1
Degree of protection internal components .................................................................................................. IP40
Degree of protection terminals ..................................................................................................................... IP20
1) This is a class A product. In a domestic environment this product may cause radio interference in which case
the user may be required to take adequate measures.
Alle Rechte vorbehalten.
Nachdruck und Vervielfältigung
nur mit Genehmigung des Herausgebers.
Änderungen vorbehalten!
© Bender GmbH & Co. KG
All rights reserved.
Reprinting and duplicating
only with permission of the publisher.
Subject to change!
© Bender GmbH & Co. KG
Service
Service hotline: 0700-BenderHelp (Telephone and Fax)
Carl-Benz-Straße 8 • 35305 Gruenberg • Germany
Tel: +49 6401-807-760 • Fax: +49 6401 807-629
E mail: [email protected] • www.bender.de
Bender GmbH & Co. KG
Postfach 1161 • 35301 Gruenberg • Germany
Londorfer Str. 65 • 35305 Gruenberg • Germany
Tel.: +49 6401-807-0 • Fax: +49 6401 807-259
E mail: [email protected] • www.bender.de
Documentation