BRI-TEK BRI0116 Installation

Text of the manual

Product No: BRI0116

Operation Non-Maintained The lamp is normally off and battery on automatic charge {green LED on) when the A.C. supply is healthy. Solid state circuitry automatically switches the lamp on when the A.C. supply is interrupted. Maintained The lamp is normally on when the supply to the switched live is on. The battery is on automatic charge {green LED on). Lamp will switch on or remain on if A.C. supply is interrupted. Monitoring The green LED indicator lamp will be on continuously. It will go out if A.C. supply or charger fails Fault Finding and Corrective Action 1 Green LED indicator not illuminated: A.C. supply is not connected or battery not connected or the charger has failed. 2 Unit is not meeting the required emergency duration: The fitting may need cycling. Discharge then recharge for full 30 hours. Retest. The battery may need replacing it emergency duration is still not achieved. Battery Replacement: (N.B. Replace with BRITEK BRI0116CELL only) 1 Switch off the electricity at the mains 2 Allow batteries to fully discharge then reconnect to supply and allow charging for 30 hours 3 Test again for 3 hours, if light does not remain lit change the battery pack as follows: a Remove the shell from the body by easing each of the 4 lugs off the body using a 5mm flat screwdriver b Unplug the battery lead from the circuit board c Remove the battery lead from the housing d Write current date on the new battery pack e Fit new battery pack into the housing f Plug battery back into circuit board g Refit the shell and press each of the 4 lugs to ensure they are fully located h Restore power and allow charging for 30 hours I Perform full operation check and update test record. Guarantee This product is guaranteed for a period of 3 year from the date of purchase. (N.B. The battery Cell BRI0116CELL is guaranteed for 4 years from assembly date which is denoted by the batch code.) The guarantee is invalid In the case of Improper use, tampering, removal of the Q.C. date label, installation in an improper working environment or installation not according to the current edition of the I.E.E. Wiring Regulations BS7671). Should this product fail during the guarantee period it will be replaced free of charge, subject to correct installation and return of the faulty unit. We do not accept responsibility for any installation costs associated with the replacement of this product Your statutory rights are not affected. We reserve the right to alter specifications without prior notice MAINTAINED NON MAINTAINED Unswitched Supply EMERGENCY BATTERY FOR LED LIGHTING Product No: BRI0116 Installation Note: Some LED Luminaires come with a female connector to the light and a male connector to the driver. If this is the case disconnect the male lead from 5 & 6 and the female lead from 3 & 4 on the terminal block, and connect the male lead to 3 & 4 and the female lead to 5 & 6 on the terminal block. Ensure the mains supply is isolated before attempting installation! Please refer to the diagram above for mains supply, driver and lamp connections. 1 Remove the lid 2 Connect the AC supply to the battery (Connection points 1 and 2) on an externally fused supply 3 Connect the LED Indicator to the green (Connection points 7 and 8) 6 pin terminal block 4 Connect the DC side of the driver (for maintained) to the top adaptor lead (if supplied) N.B. If no connector leads are supplied connect the driver directly to the Connection points 3 & 4 5 Connect the LED Luminaire to the middle lead (if supplied) N.B. If no connector leads are supplied connect the LED and driver directly to the Connection points 5 & 6 6 Once wiring is complete, ensure the lid is fixed in place using the screw on the base. If external plug and socket connectors are used without means to prevent accidental disconnection, the remote box should be sited so that it is protected from unauthorised disconnection. A recessed mount can be found inside the packaging carton to assist installation of the indicator LED. Once installed, the indicator LED will be illuminated and the supply should be left undisturbed for a minimum of 24 hours to charge the batteries before attempting a commissioning test. After a successful test, the date should be noted on the space provided on the battery. Commissioning should be recorded on the commissioning page. EMERGENCY BATTERY FOR LED LIGHTING Dedicate AC mains Required DC Connection to the LED Light Fitting LED Indicator N L + - + +- - Switched Supply N L LED Driver + - + - + - LED Light 3 4 5 6 7 8 L N LED Indicator 1 2 Switched AC In Switched DC Out DC In DC In Dedicated AC Supply N L + - + +- - N L + - + - + - LED Light 5 6 7 8 LED Indicator 1 2 DC In DC In Dedicated AC Supply Optional. DC Connection to LED Driver. For maintained supply where the LED Light can be operated by a light switch or sensor Ta +45°C EL Tc +70°C For use with LED lighting only For use with LED lighting only

Commission & Testing

The emergency light must be tested and inspected regularly in accordance with local codes of preactice. Note: for safety reasons, tests should be carried out during daylight hours The minimum recommended test schedule is as follows: After installation, allow 36 hours to ensure full battery charge, and then interrupt the supply; check after 3 hours that the luminaire is still lighting. 1 Daily - Check that the charge indicator LED is working 2 Monthly - interrupt the power supply for a short period and check the lamp remains illuminated 3 Six Monthly - interrupt the supply and check that the lamp remains illuminated after 1 hr 4 At the end of the 3rd year, and annually thereafter - check 3 hour duration: batteries must be replaced when they can no longer support 3 hour operation 5 Complete record sheet on installation and retain in maintenance file. 6 Update file with on-going test records for inspection by fire officer or other duly authorised person. Installation / Test Record Date: Date: Serial/Luminaire Number: Installed by: Commissioned by: YEAR 4 * * Battery must be replaced YEAR 3 YEAR 2 YEAR 1 Signed Date 1 2 3 4 5 6 7 8 9 10 11 12 Signed Date Signed Date Signed Date Month short short short short short 1 hour short short short short short short Test 3 hour Product Specification Mains Voltage 110 to 240v AC Mains Frequency 50 – 60 Hz Power consumption (Excluding external Driver) 4vA Input Current 1A max Icharge 140 to 260 mA Charge Regime Constant Current Emergency output voltage range 4-42V dc Max O/C 60V: Ballast Cut-off Voltage (for battery cell protection) 3.2V Emergency output current min/max 1A (Operated in constant current mode) Emergency Duration 3 hours Battery NiMH 4.8V 2.5Ah Ambient temperature range 0° to 45°C Min/Max Conductor sizes 0.5 to 4mm² Weight 240g Size 170mm x 60mm x 35mm Charging Time 24 hours Protection Class 2 Degree of Protection IP20 Material Fire Retardant ABS Em module complies with EN61347-1, 61347-2-7, 61347-2-13, 61558 Suitable for installation to EN50172 and BS7671 Compatible with any LED Lunimaires to 3-100W The unit provides reinforced insulation between the mains supply and battery charging circuit and employs self- resetting protection against short-circuit of battery terminals. Normal charging will resume automatically once a fault is removed. 170mm 60mm 35mm EMERGENCY BATTERY FOR LED LIGHTING EMERGENCY BATTERY FOR LED LIGHTING For use with LED lighting only For use with LED lighting only

Other Camera Accessories Manuals