Circutor Wibeee Max Instruction Manual
Text of the manual
Warns of a risk, which could result in personal injury or material damage.
ATTENTION
Indicates that special attention should be paid to a specifi c point.
Follow the warnings described in this manual with the symbols shown below.
If you must handle the unit for its installation, start-up or maintenance, the following
should be taken into consideration:
Incorrect handling or installation of the unit may result in injury to personnel as well as damage
to the unit. In particular, handling with voltages applied may result in electric shock, which may
cause death or serious injury to personnel. Defective installation or maintenance may also
lead to the risk of fi re.
Read the manual carefully prior to connecting the unit. Follow all installation and maintenance
instructions throughout the unit’s working life. Pay special attention to the installation stan-
dards of the National Electrical Code.
Refer to the instruction manual before using the unit
In this manual, if the instructions marked with this symbol are not respected or carried out correctly, it can
result in injury or damage to the unit and /or installations.
CIRCUTOR, SA reserves the right to modify features or the product manual without prior notifi cation.
DISCLAIMER
CIRCUTOR, SA reserves the right to make modifi cations to the device or the unit specifi ca-
tions set out in this instruction manual without prior notice.
CIRCUTOR, SA on its web site, supplies its customers with the latest versions of the device
specifi cations and the most updated manuals.
www.circutor.com
CIRCUTOR, recommends using the original cables and accessories that are
supplied with the device.
1.- VERIFICATIONS UPON RECEPTION..............................................................................................................6
2.- DESCRIPTION OF THE PRODUCT..................................................................................................................6
3.- INSTALLING THE DEVICE...............................................................................................................................7
3.1.- PRELIMINARY RECOMMENDATIONS....................................................................................................7
3.2.- INSTALLATION.........................................................................................................................................8
3.3.- SENSORS FOR CURRENT MEASUREMENT.......................................................................................10
3.3.1.- Wibeee Max.......................................................................................................................................10
3.3.2.- Wibeee Max Plus..............................................................................................................................11
3.4.- DEVICE TERMINALS..............................................................................................................................13
3.5.- CONNECTION DIAGRAMS....................................................................................................................13
3.6.- STARTING UP THE DEVICE...................................................................................................................14
3.6.1.- APPLICATION MODE.......................................................................................................................14
3.6.2.- DIRECT SHARE MODE....................................................................................................................15
4.- OPERATION ...................................................................................................................................................16
4.1.- OPERATING PRINCIPLE........................................................................................................................16
4.2.- MEASUREMENT PARAMETERS...........................................................................................................17
4.3.- LED INDICATORS...................................................................................................................................17
4.4.- KEY..........................................................................................................................................................18
4.5.-START-UP.................................................................................................................................................18
5.- DISPLAY AND CONFIGURATION..................................................................................................................20
5.1.-MOBILE APPLICATION...........................................................................................................................20
5.2.- WEB PLATFORM....................................................................................................................................21
5.2.1.-
HOME...........................................................................................................................................22
5.2.2.-
DASHBOARD..............................................................................................................................26
5.2.3.-
DEVICES......................................................................................................................................27
5.2.4.-
NOTIFICATIONS..........................................................................................................................27
5.2.5.-
REPORTS....................................................................................................................................28
5.2.6.-
HELP............................................................................................................................................30
5.3.- INTERNAL WEB SERVER......................................................................................................................30
5.3.1.- INSTANT DATA.................................................................................................................................31
5.3.2.- NETWORK.........................................................................................................................................32
5.3.3.- ADVANCED OPTIONS......................................................................................................................32
5.3.4.- GENERAL OPTIONS........................................................................................................................33
5.4.- CONFIGURATION THROUGH HTTP GET REQUESTS........................................................................34
5.4.1.- PARAMETER QUERY.......................................................................................................................34
5.4.2.- CONFIGURATION.............................................................................................................................36
6.- WIRELESS COMMUNICATIONS....................................................................................................................38
6.1.- USAGE ENVIRONMENT AND HEALTH.................................................................................................38
6.2.- Wi-Fi COMMUNICATIONS......................................................................................................................38
6.3.- MODBUS TCP PROTOCOL....................................................................................................................38
6.4.- MODBUS MEMORY MAP.......................................................................................................................39
7.- TECHNICAL FEATURES................................................................................................................................41
8.- MAINTENANCE AND TECHNICAL SERVICE................................................................................................43
9.- WARRANTY.....................................................................................................................................................43
10.- CE CERTIFICATE..........................................................................................................................................44
Table 1: Revision log.
Date
Revision
Description
12/17
M169B01-03-17A
Initial Version
06/18
M169B01-03-18A
Changes in the following sections:
1.- 3.2. - 3.3.1.
Note: The images of the devices are for illustration purposes only and may differ from the orig-
inal device.
SYMBOLS
Table 2: Symbols.
Symbol
Description
Compliant with the relevant European standards.
Double insulation.
~
AC current.
Device covered by European directive 2002/96/EC. At the end of its useful
life, do not leave the device in a household waste container. Follow local
regulations on electronic equipment recycling.
1.- VERIFICATIONS UPON RECEPTION
The following must be checked upon reception of the device:
a) The device has been supplied according to the specifications in your order.
b) The device has not been damaged during transport.
c) Perform an external visual inspection of the device before connecting it.
d) Check that it has been supplied with the following:
- An installation guide,
- Accessories bag with crocodile clips.
- Wibeee Max model: FLEX Wibeee 25 flexible sensors.
- Wibeee Max Plus model: FLEX Wibeee 54 flexible sensors.
2.- DESCRIPTION OF THE PRODUCT
The Wibeee Max is a device that measures three-phase lines and is connected to the cloud via
the Wibeee platform. The device has been designed to make the installation process as simple
as possible. It also has an internal memory that allows information to be recovered in the event
of a temporary loss of the Wi-Fi connection.
There are 2 models available:
Wibeee Max with two scales for current measurement: 350 A and 700 A.
Wibeee Max Plus with three scales for current measurement: 100 A, 1000 A and 5000 A.
The models have:
- 2 indicator LEDs
- 1 selection key
- Wi-Fi communications
You can access the data measured by the device via the Wibeee Circutor mobile application,
the website http://wibeee.circutor.com, or the device's internal web server.
3.- INSTALLING THE DEVICE
3.1.- PRELIMINARY RECOMMENDATIONS
In order to use the device safely, it is critical that individuals who handle it follow
the safety measures set out in the standards of the country where it is being used,
use the personal protective equipment necessary (rubber gloves, face protection
and approved flame-resistant clothing) to prevent injuries due to electric shock or
electric arc due to exposure to current-carrying conductors and pay attention to
the various warnings indicated in this instruction manual.
The Wibeee Max device must be installed by authorised and qualified staff.
Disconnect the device from the power supply and disconnect the measuring devices before
handling, changing the connections or replacing the device. Handling the device while it is con-
nected is hazardous to people nearby.
It is essential to keep the cables in a perfect condition to avoid accidents, personal injury and
damage to installations.
Limit the operation of the device to measuring the specified current or voltage values.
The manufacturer of the device shall not be held responsible for any damage resulting from the
user or installation company failing to observe the warnings and/or recommendations indicated
in this manual nor for any damage resulting from the use of non-original products or accesso-
ries or those from other brands.
Do not use the device to take measurements if you detect an anomaly or malfunction.
Check the environment in which the device is installed before taking a measurement. Do not
use the device to take measurements in dangerous, explosive, wet or damp environments.
Disconnect the device from the mains and from the power supply (both the device
and its measuring system) before performing any maintenance work, repairs or
handling any of the connections of the device.
Contact the after-sales service if you detect that the device is not working prop-
erly.
Before using the Wibeee Max ensure that the conditions are appropri-
ate for working, and that the protective equipment is adequate.
The flexible current sensor has been designed and tested to ensure that
it complies with the IEC 61010-1:2001/EN61010-1 61010-2-31:2002 safety
standard.
Use of the sensor on uninsulated conductors is limited to 600 V ~ or DC to
frequencies below 1kHz.
Do not expose the device to aggressive or explosive environments.
Do not use the device if you have any reason to believe that it is not working
correctly or it is defective.
For measuring of uninsulated conductors, use the appropriate and necessary
personal protective equipment.
The device should be installed after the circuit breaker.
To install the device, carry out the following steps:
1. Remove the protective panel from the electric panel.
Figure 1: Remove the connection panel.
2. Install the device on the electric panel. The device can be attached in three different ways:
A magnetic attachment.
A DIN rail attachment, Figure 2.
An attachment with screws, Figure 2.
A DIN rail
attachment
An attachment with
screws
Figure 2: Attachment methods.
Note: The attachment with screws is die-cut and if it is not used and it interferes with another
type of installation, it may be broken.
3. Connect the device. See “3.4.- DEVICE TERMINALS” y “3.5.- CONNECTION DIAGRAMS”.
4. Once the Wibeee Max has been connected to the auxiliary power supply, check that the red
LED is on and flashing (see “4.3.- LED INDICATORS”).
5. Select the measurement scale for the current sensors:
The Wibeee Max model, following the steps indicated in section “3.3.1.1.- Scale se-
lection”.
The Wibeee Max Plus model, following the steps indicated in section “3.3.2.1.- Scale
selection”.
3.3.- SENSORS FOR CURRENT MEASUREMENT
3.3.1.- Wibeee Max
In the Wibeee Max model, current measurement is performed using the FLEX Wibeee 25 flex-
ible sensors.
Table 3:Metrological characteristics.
FLEX Wibeee 25
Measurement scales
350
700
Nominal range
350 A
700 A
Output / input ratio
2.86 mV/A
1.43 mV/A
Range of use
3.5 ... 350 A
7 ... 700 A
Specified measurement range
35 ... 350
70 ... 700
Typical phase difference
1st
1st
The measurement uncertainty is for the sensor in its optimal position, with no external electric
or magnetic fields and within the working temperature range, Table 4.
Table 4:Position error
Position
Error
A
B
A
± 1%
B
A ± 3%
Table 5: Variations in range of use.
Variations in range of use
Magnitude of Influence
Range of influence
Typical
Maximum
Temperature
- 10ºC ... +60ºC
-
±0.3 % / ºC
Relative humidity
10% ... 90%
-
0.3 %
Conductor position
-
2 %
3 %
Adjacent conductor
D/4 300 A
-
2 %
Set to 50 Hz
Full scale
0.2 %
0.3 %
Set to 60 Hz
Full scale
0.2 %
0.3 %
Frequency
40 Hz - 5 kHz
< ± 1 dB
< ± 1 dB
Deviation 50 Hz - 60 Hz
-
-
0.3 %
Note : Circutor also has the model of flexible sensors, FLEX Wibeee 14, with the same metro-
logical characteristics of the FLEX Wibeee 25 model, but with a length of 14 cm.
3.3.1.1.- Scale selection
The FLEX Wibeee 25 current sensors indicate the selected scale through the blue LED on
their head.
During the first 20 seconds after being switched on, the Wibeee Max is in the scale selection
period. The blue LED flashes quickly and indicates the selected scale.
Press the RESET key during this period to select the desired scale:
One blink indicates that the 350 A scale has been selected.
Two blinks indicate that the 700 A scale has been selected.
When the scale selection period has ended, the quick blinking light is deactivated and the blue
LED indicates the selected scale at regular intervals.
3.3.2.- Wibeee Max Plus
In the Wibeee Max Plus model, current measurement is performed using the FLEX Wibeee
54 flexible sensors.
Table 6:Metrological characteristics.
FLEX Wibeee 54
Measurement scales
100
1 k
5 k
Nominal range
100 A
1000 A
5000 A
Output / input ratio
10.0 mV/A
1.0 mV/A
0.2 mV/A
Range of use
1 ... 100 A
10 ... 1000 A
50 ... 5000 A
Specified measurement range
10 ... 100
100 ... 1000
500 ... 5000
Typical phase difference
1st
1st
1st
The measurement uncertainty is for the sensor in its optimal position, with no external electric
or magnetic fields and within the working temperature range, Table 7.
Table 7:Position error
Position
Error
A
B
A
± 1%
B
A ± 3%
Table 8: Variations in range of use.
Variations in range of use
Magnitude of Influence
Range of influence
Typical
Maximum
Temperature
- 10ºC ... +60ºC
-
±0.3 % / ºC
Relative humidity
10% ... 90%
-
0.3 %
Conductor position
-
2 %
3 %
Adjacent conductor
D/4 300 A
-
2 %
Set to 50 Hz
Full scale
0.2 %
0.3 %
Set to 60 Hz
Full scale
0.2 %
0.3 %
Frequency
40 Hz - 5 kHz
< ± 1 dB
< ± 1 dB
Deviation 50 Hz - 60 Hz
-
-
0.3 %
3.3.2.1.- Scale selection
The FLEX Wibeee 54 current sensors indicate the selected scale through the blue and red
LEDs on their head.
During the first 20 seconds after being switched on, the Wibeee Max Plus is in the scale selec-
tion period. The blue and red LEDs flash slowly and indicate the selected scale.
Press the RESET key during this period to select the desired scale:
The blue LED indicates that the 100 A scale has been selected.
The red LED indicates that the 1 kA scale has been selected.
The blue and red LEDs indicate that the 5 kA scale has been selected.
When the scale selection period has ended, the quick blinking light is deactivated and the blue
and red LEDs indicate the selected scale.
3.4.- DEVICE TERMINALS
Table 9:List of terminals of the Wibeee Max.
Terminals of the Wibeee Max device
1: Current measurement: Black: L1 , Red: L2, Yellow: L3
2: Voltage measurement and power supply: Black: L1 , Red: L2, Yellow: L3, Blue: Neutral
Green and Brown: Power supply.
1
2
Figure 3: Wibeee Max terminals.
3.5.- CONNECTION DIAGRAMS
LOAD
Power
Supply
Blue
Black
Red
Yellow
Brown
Green
Black
Red
Yellow
L1
L2
L3
N
Figure 4: Wibeee Max connection diagram.
3.6.- STARTING UP THE DEVICE
To start communication with the device it is necessary:
1.- To have access to the Internet through a wireless network.
2.- To check that the following ports are open:
- Port 8080 for Http Get / Post.
- Port 53 for DNS
- Port 80 for Internet
Note: The Orange Livebox Next router is incompatible with Wibeee Max devices when in
“WPA/WPA2” security mode and they do not connect. When in “only WPA2” mode they connect
correctly.
The Wibeee Max's data can be accessed in two ways:
Application mode.
Direct share mode.
3.6.1.- APPLICATION MODE
In application mode, the data measured by the Wibeee Max is uploaded to the cloud and ac-
cessed using the Wibeee CIRCUTOR application. When using this mode, the Wibeee Max and
the user who has configured it are linked, so the user can control the device, view the data that
has been sent and the charts and manage groups of devices.
To start the device in application mode, follow these steps:
1.- Scan the QR code to download the application or download it from:
http://wibeee.circutor.com
2.- Open the Wibeee CIRCUTOR application. And follow the steps that it indicates.
3.6.2.- DIRECT SHARE MODE
In direct share mode the Wibeee Max's data is directly accessed from the device's integrated
web server, so you can view the measurements being captured at that moment in real time and
manually configure the device. This allows you to change parameters, such as the server and
port to which the Wibeee Max will send the data. If you configure a Wibeee Max while using
this mode, there is no link between the user and the device, so the only way to access the de-
vice when it is connected to the network is by knowing its IP address and accessing it using a
search tool.
To start the device in direct share mode, follow these steps:
1.- On a smartphone/tablet, use the Wi-Fi connection's settings to connect to the Wibeee Max.
2.- You can get access to the net configuration and instant measurements through your brows-
er, at the address: http://192.168.1.150
User: user
Password: user
4.1.- OPERATING PRINCIPLE
The Wibeee Max is a power consumption measurement device with a Wi-Fi wireless connec-
tion to display or download the data that is measured, using any smartphone, tablet or PC.
Wibeee MAX
Electrical Panel
Laptop
PC
Smartphone
Tablet
Figure 5: Overview
The device can work in two operating modes:
Application mode
In application mode, the data measured by the Wibeee Max is uploaded to the cloud
and accessed via the Wibeee CIRCUTOR application or the http://wibeee.circutor.
com web platform.
Direct share mode
In direct share mode the Wibeee Max's data is directly accessed from the device's inte-
grated web server.
Note: The device's integrated web server can also be accessed in the application's operating
mode.
If the Wibeee Max loses the connection with the server, a back-up memory with a 30-day
capacity will start up.
This back-up memory will store the values of the most critical variables (voltage, current,
apparent power, active power, reactive power and power factor) every minute for 30 days.
When the connection with the server comes back online the device gradually begins to dump
the stored data. Depending on the quality of the connection, the reading retrieval speed is up
to 100 readings per minute.
Note: The back-up memory will only start up if the device has previously been started and
properly configured, i.e. if it has had an Internet connection at some time.
4.2.- MEASUREMENT PARAMETERS
The device measures, logs and displays the following parameters, Table 10:
Table 10: Measurement parameters of the Wibeee Max
Parameter
Units
Display
Phases
L1 - L2 - L3
Three-phase
Current
A
Numerical
Graphical
Graphical
Voltage
V
Numerical
Graphical
Graphical
Active Power
kW
Numerical
Graphical
Graphical
Reactive Power
kVAr
Numerical
Graphical
Graphical
Active Energy
kWh
Numerical
Graphical
Graphical
Reactive Energy
kVArh
Numerical
Graphical
Graphical
Frequency
Hz
Numerical
Graphical
Graphical
Power Factor
Cos Φ
Numerical
Graphical
Graphical
Energy
kWh
-
Graphical
CO2 Emissions
kgCO2
-
Graphical
Cost
€
-
Graphical
4.3.- LED INDICATORS
The device has 2 status LEDs, Figure 6.
Red LED
Blue LED
Figure 6:LED indicators.
Table 11: Description of the LEDs.
LED
Description
Red
Blinking light: Powered device.
Blue
Indicates the connection status:
Slow blinking light (1s): Generating a Wi-Fi network.
Fast blinking light (<1s) : Connected to a Wi-Fi network.
Steady light: Data being sent over the network.
4.4.- KEY
The device has a RESET key, Figure 7.
Reset
key
Figure 7:Wibeee Max Key.
The RESET key has 2 functions:
During the start-up of the device, it is used to select the scale of the current measuring
sensor, see “3.2.- INSTALLATION”.
Restore the device's factory settings. To do this, hold down the RESET button for 10
seconds, until the device's red and blue LEDs simultaneously flash three times.
4.5.-START-UP
During the start-up of the device, the Wibeee Max goes through different states:
1.- Configuration state
Blue LED → Slow blinking light (1s)
Red LED → Slow blinking light (1s)
In this state, the Wibeee Max generates its own Wi-Fi network called WIBEEE_xx:xx:xx.
It is only used to configure the device and connect it to the user's network.
If you want to return to this state to obtain the initial conditions, you should hold down the Re-
set button for more than 6 seconds. The device deletes any previous settings and restores the
default values.
2.- Connecting... state
Blue LED → Off
Red LED → Slow blinking light (1s)
In this state, the Wibeee Max is managing the connection with the router/access point.
This state should last for 40 seconds, when there is good Wi-Fi coverage. In places where there
is weak Wi-Fi coverage, it may take longer.
If it takes longer than 2 minutes, it is recommended to return to the initial state, check the Wi-Fi
coverage and re-start the process.
If it is unable to connect to the Wi-Fi, the device retries 5 times. If the lack of connection per-
sists, it goes into Configuration mode (so that the configuration can be changed without open-
ing the panel) for 5 minutes; it then tries to reconnect again and, until it manages to reconnect,
it remains in this alternating mode. (5 minutes in the Configuration state and 1 attempt to
connect).
3.- Connecting state
Blue LED → Fast blinking light (<1s)
Red LED → Slow blinking light (1s)
In this state, the device has connected to the Wi-Fi network and is waiting to complete the first
successful transfer of data.
When it first manages to successfully send data, it will enter the “Connected and sending OK”
state.
If the device is not able to successfully send the first set of data, it will retry 3 times. If it does not
manage to send it, the Wi-Fi connection is restarted and it retries sending the package 3 times.
It remains in this state until the first data is successfully sent.
4.- Connected and sending OK state
Blue LED → Steady light.
Red LED → Slow blinking light (1s)
When the device is configured and connected to the network in the user's infrastructure, it
automatically starts sending data on the installation's power consumption to the server (every
minute).
It also allows you to access instant measurements by making requests to its internal XML and
Modbus servers.
5.- DISPLAY AND CONFIGURATION
When the device has been installed and started up, it is possible to access all of its data by
using different methods, depending on the device's operating mode, Figure 8.
Application mode
Direct share mode
Internal Web
server
Web platform
http://wibeee.circutor.com
Mobile application
Wibeee Circutor
Internal Web
server
Data display
Figure 8: Data display based on the operating mode.
5.1.-MOBILE APPLICATION
The Wibeee Circutor mobile application is compatible with iOS and Android, and has a version
for smartphones and tablets.
In it you can view and configure all of the parameters measured by the device.
Figure 9: Wibeee Circutor mobile application.
5.2.- WEB PLATFORM
Figure 10 shows the main screen of the http://wibeee.circutor.com web platform.
Figure 10:Main screen of the web platform.
From this screen you can access the different sections of the platform:
: Home, summary of consumption, displays charts and gives access to the
dashboard configuration options (graphical interface).
: Dashboard, displays all of the dashboards of every active device.
: Devices, access to all of the connected devices.
: Notifications, displays the notifications log.
: Reports, access to regular report generation.
: Help, help screen.
The Home screen is divided into different areas:
The area in Figure 11 displays a summary of consumption and CO2 emissions from the
previous month, the current month and the forecast for the end of the month. It also displays
the set target value.
Figure 11: Summary area.
The area in Figure 12 shows 2 of the possible charts that can be viewed. Table 10 show all
of the parameters that can be graphically displayed.
Use the < > arrows to toggle between charts.
Figure 12: Charts area.
The area in Figure 13 shows the latest measurements sent by the device.
Figure 13: Measurements area.
In the area in Figure 14 you can access the configuration options for the devices and
dashboard, see “5.2.1.1.- Configuration screen for the devices/dashboard”.
Figure 14: Access to the device/dashboard configuration area.
5.2.1.1.- Configuration screen for the devices/dashboard.
On the device/dashboard configuration screen you can configure the following data:
DEVICE
Figure 15: Configuration screen: Device.
The device’s basic data is entered in this section:
Name: The name of the device.
Select Dashboard: Dashboard selection.
Mac: MAC address of the device.
2-4 Quadrants: Measurement selection for 2 quadrants (consumption) or 4 quadrants
(consumption and generation).
LOCATION
Figure 16: Configuration screen: Location.
The device’s location data is entered in this section:
Name: Name of the device’s location.
Time zone: Time zone.
Longitude, Latitude: Location of the device.
COST
Figure 17: Configuration screen: Cost
The costs are entered in this section:
Price kWh : Price of kWh.
Tax (%), Other Tax (%) : Fees and taxes.
Other Costs (Cost/day): Other costs.
Cost kW Day (Cost/kW Day): Cost in kW per day.
Billing date: Billing date.
Contracted power (kW): Contracted power.
TARGET AND NOTIFICATIONS
Figure 18: Configuration screen: Target and Notifications.
In this section you enter the following:
Target Limit (kWh) : The maximum consumption value that you want to reach, in kWh.
And the following notifications are activated or deactivated:
•
Wibeee has been inactive for 1 day.
•
Wibeee has been inactive for 3 days.
•
Overvoltage, overvoltage alarm.
•
Undervoltage, undervoltage alarm.
•
High consumption, alarm for high consumption in the installation.
5.2.2.-
DASHBOARD
The Dashboard screen, Figure 19, shows all of the active dashboards.
Figure 19: Dashboard Screen.
It is also possible to create a chart comparing different dashboards. To do this, simply select
the dashboards that you want to compare by ticking the box, as shown in Figure 20.
Figure 20: Selecting the Factory dashboard.
The Devices screen, Figure 21, displays a list of all of the connected devices.
Figure 21: Devices screen.
5.2.4.-
NOTIFICATIONS
The Notifications screen, Figure 22, shows a log of all of the notifications that have been
generated.
Figure 22: Notifications screen.
The Reports screen, Figure 23, is divided into two areas:
Figure 23: Reports Screen.
REPORTS
This section shows the scheduled reports to be regularly generated.
To create a new regular report, press the
icon. The dialogue box in Figure 24 opens.
Figure 24: New Report.
In this dialogue box, you should enter:
Report name: Name with which the report is going to be saved.
Select Dashboard: Select the Dashboard on which you are going to prepare the report.
Frequency: Select the frequency of the report: Weekly, Monthly, Billing period.
Recipients: Enter the email addresses of the recipients of the report.
You can prepare a simple version of a report by selecting Normal Section (Figure 24), where
everything is pre-configured and you only have to select the quantity.
Or an advanced version, by selecting Advanced Section (Figure 25), where you can configure
a lot more options.
Figure 25: New Report: Advanced Section.
REPORT LOG
In this section you can download all of the reports that have already been created.
The Help screen, Figure 26, tries to answer any questions about the installation, operation, web
platform and application of the Wibeee systems.
Figure 26: Help Screen.
5.3.- INTERNAL WEB SERVER
Figure 27 shows the screen where you access the device's internal web server. The device's
default address is: http://192.168.1.150
User: user
Password: user
Figure 27:Internal web server access screen.
The main screen is shown in Figure 28.
Figure 28:Main screen of the internal web server.
5.3.1.- INSTANT DATA
In this section you can access instant data from each of the measurement phases, Figure 29.
Figure 29:Internal web server: Instant Data.
You can configure the network parameters in the Network section, Figure 30.
Figure 30:Internal web server: Network.
5.3.3.- ADVANCED OPTIONS
You can configure the IP parameters in the Advanced Options section, Figure 31.
Figure 31:Internal web server: Advanced Options.
wibeee.circutor.com
5.3.4.- GENERAL OPTIONS
Figure 32 shows the General Options section.
Figure 32:Internal web server: General Options.
You can configure the following parameters in this section:
Connection Type: Connection type
Measures Refresh Time (s): The measurement refresh time.
Data Refresh Time (min): The data refresh time. If the value is set to -1, the sending of data
is deactivated.
Offline HD Save Time (min): If the device loses its connection, the data measured is stored
in an internal memory. In this section, you set the frequency with which data is stored in the
memory. If the value is set to -1, the saving of data is deactivated.
It is also possible to reset the energy meter, by pressing the
button.
5.4.- CONFIGURATION THROUGH HTTP GET REQUESTS
Wibeee Max accepts HTTP GET requests for parameter and settings queries for the device.
Requests must be made directly to the IP address: 192.168.1.150 after connecting to the Wi-Fi
network created by the device.
All requests made to the Wibeee Max's internal server are GET requests and when they have
been processed by the server it sends an HTTP correct access response:
“HTTP 200 OK”.
5.4.1.- PARAMETER QUERY
5.4.1.1.- DEVICE ID
You should use the following request to view the device's ID:
http://ip_address/services/user/devices.xml
Figure 33: HPPT queries: Device ID.
5.4.1.2.- Values of the device's variables
To view the values of all of the device's variables, use the following request:
http://ip_address/services/user/values.xml?id=device
It is also possible to view specific variables, see Table 12 with the available variables.
http://ip_address/services/user/values.xml?var=device.variable
Figure 34:HPPT queries: Values of the device's variables.
Table 12: Variables table.
Variable
Description
Units
measuresRefresh
Measures refresh time of the internal web
Seconds
appRefresh
Time sending data to the server.
Minutes
softVersion
Firmware version of the device
-
model
Model identifier
-
ipAddr
Type of IP : DHCP or static IP
-
gwAddr
The device's current IP.
-
subnetMask
Gateway.
-
primaryDNS
Primary DNS server.
-
secondaryDNS
Secondary DNS server.
-
macAddr
MAC identifier
-
ssid
Name of the network.
-
keyEnc
Password type.
-
keyType
Password format: Hex or ASCII
-
securKey
Password.
-
serverIp
Name of the server domain.
-
serverIpResolved
IP address of the server.
-
serverPort
Sending port.
-
vrms1
Phase voltage L1
V
vrms2
Phase voltage L2
V
vrms3
Phase voltage L3
V
vrmst
Total voltage (average of L1, L2, L3)
V
irms1
Current L1
A
irms2
Current L2
A
irms3
Current L3
A
irmst
Total current (average of L1, L2, L3)
A
pap1
Apparent Power L1
VA
pap2
Apparent Power L2
VA
pap3
Apparent Power L3
VA
papt
Total Apparent Power
VA
pac1
Active Power L1
W
Table 12 (Cont.): Variables table
Variable
Description
Units
pac2
Active Power L2
W
pac3
Active Power L3
W
pact
Total Active Power
W
preac1
L1 Reactive Power
Var
preac2
L2 Reactive Power
Var
preac3
L3 Reactive Power
Var
preact
Total Reactive Power
Var
freq1
Frequency L1
Hz
freq2
Frequency L2
Hz
freq3
Frequency L3
Hz
freqt
Total frequency (average of L1, L2, L3)
Hz
fpot1
Power Factor L1
-
fpot2
Power Factor L2
-
fpot3
Power Factor L3
-
fpott
Total Power Factor
-
eac1
Active Energy L1
Wh
eac2
Active Energy L2
Wh
eac3
Active Energy L3
Wh
eactt
Total Active Energy
Wh
ereactl1
Inductive Reactive Energy L1
VArLh
ereactl2
Inductive Reactive Energy L2
VArLh
ereactl3
Inductive Reactive Energy L3
VArLh
ereactlt
Total Inductive Reactive Energy
VArLh
ereactc1
Capacitive Reactive Energy L1
VArCh
ereactc2
Capacitive Reactive Energy L2
VArCh
ereactc3
Capacitive Reactive Energy L3
VArCh
ereactct
Total Capacitive Reactive Energy
VArCh
5.4.2.- CONFIGURATION
The minimum requests for configuring the Wibeee Max with HPPT are:
1.- Device Network Configuration:
http://ip_address/config_value?name=WIBEEE&dhcp=false&ip=c0a80196&gw=-
c0a80101&subnet=ffff0000&id=0.5973659041337669
Table 13: Configuration HPPT variables (Request 1)
Variable
Description
name
Name of the Wibeee
dhcp
false: static network
true: dynamic network
ip
IP address in hexadecimal
Table 12 (Cont.): ConFiguretion HPPT variables (Request 1)
Parameter
Symbol
gw
Gateway in hexadecimal
subnet
Subnet mask in hexadecimal
2.- Configuration of the Local Wi-Fi Network:
htt p: // ip_addres s / c onfig_v alue?ssid= Cirprotec-A lmacen& securit y= 5& ty-
pekey=2&id=0.5105853546410799
Table 14: Configuration HPPT variables (Request 2)
Variable
Description
ssid
Name of the Wi-Fi
security
Type of security:
0: OPEN - 1: WEP - 5:WPA - 9: WPA2 - 13: WPA/WPA2
typekey
Password encryption:
1: Hexadecimal - 2: PassPhrase
3.- Password sending:
http://ip_address/config_value?pass=xxxxxxxxx&id=0.9732521877158433
Table 15: Configuration HPPT variables (Request 3)
Variable
Description
pass
Wi-Fi password
4.- Server Configuration:
http://ip_address/conFigure_server?URLServidor=c339a462&portServidor=1f91&
id=0.33531335316222393
Table 16: Configuration HPPT variables (Request 4)
Variable
Description
ServerURL
Name of the server domain
Serverport
Port in hexadecimal
5.- Resetting the device:
http://ip_address/config_value?reset=true&id=0.03616242413409054
6.- WIRELESS COMMUNICATIONS
6.1.- USAGE ENVIRONMENT AND HEALTH
Wireless communications emit radio frequency electromagnetic energy, like other radio devic-
es.
Because wireless communications operate within the guidelines found in radio frequency safe-
ty standards and recommendations, they are safe for users to use.
In certain environments or situations, the use of wireless communications may be restricted by
the owner of the building or the representatives responsible for the organisation.
These situations include:
The use of wireless connections on board aircraft, in hospitals or near to service stations,
blasting areas, medical implants or electronic medical devices implanted in the body (pace-
makers etc.).
In any other environment where the risk of interference with other devices or services is
identified as hazardous.
If you are unsure about the policy implemented regarding the use of wireless devices in a spe-
cific organisation (airport, hospital, etc.), it is advisable to ask for authorisation to use wireless
communications.
6.2.- Wi-Fi COMMUNICATIONS
Wi-Fi is one of the most widely used wireless technologies today, for connecting and exchang-
ing information between electronic devices without having to connect them physically.
The Wibeee Max has Wi-Fi communications in the 2.4 GHz band, compliant with standard
IEEE 802.11
6.3.- MODBUS TCP PROTOCOL
The MODBUS protocol is an industry communication standard that enables the network
connection of multiple devices, where there is a master and multiple slaves.
The MODBUS functions implemented in the device are:
Function 0x03. Reading of multiple registers. This function is used to request the
desired measurement parameters from the Wibeee Max Modbus server.
Function 0x05. Writing of a specific register. This function is used to delete the
Wibeee Max's energy meters.
If the Wibeee max receives a function request other than those above, or for non-specified
memory registers, the device identifies this as an “Illegal error” and responds with the appro-
priate exception code.
As it is a MODBUS TCP server, the device number internally assigned to the Wibeee Max is 1.
By default, once configured, the Wibeee Max starts to send data over the internet to the CIR-
CUTOR server. If you want to stop this data from being sent (for example, because the local
network does not have an Internet connection) you have to set a data refresh time of -1. This
way, the device is only waiting to handle MODBUS requests.
6.4.- MODBUS MEMORY MAP
All MODBUS map addresses are in hexadecimal format.
Table 17: Modbus memory map
Parameter
Symbol
Address
Units
Phase voltage L1
Vrms1x10
0000
V x 10
Phase voltage L2
Vrms2x10
0001
V x 10
Phase voltage L3
Vrms3x10
0002
V x 10
Current L1
Irms1x10
0003
A x 10
Current L2
Irms2x10
0004
A x 10
Current L3
Irms3x10
0005
A x 10
Frequency L1
Freq1x10
0006
Hz x 10
Frequency L2
Freq2x10
0007
Hz x 10
Frequency L3
Freq3x10
0008
Hz x 10
Total Frequency
FreqTx10
0009
Hz x 10
Active Power L1
Wreal1x10
000A
W x 10
Active Power L2
Wreal2x10
000B
W x 10
Active Power L3
Wreal3x10
000C
W x 10
Total Active Power
WrealTx10
000D
W x 10
L1 Reactive Power
Wreact1x10
000E
Var x 10
L2 Reactive Power
Wreact2x10
000F
Var x 10
L3 Reactive Power
Wreact3x10
0010
Var x 10
Total Reactive Power
WreactTx10
0011
Var x 10
Apparent Power L1
Waparent1x10
0012
VA x 10
Apparent Power L2
Waparent2x10
0013
VA x 10
Apparent Power L3
Waparent3x10
0014
VA x 10
Total Apparent Power
WaparentTx10
0015
VA x 10
Power Factor L1
PF1 x 100
0016
x 100
Power Factor L2
PF2 x 100
0017
x 100
Power Factor L3
PF3 x 100
0018
x 100
Total Power Factor
TPF x 100
0019
x 100
Active Energy L1
Eact1
001A - 001B
kWh
Active Energy L2
Eact2
001C - 001D
kWh
Active Energy L3
Eact3
001E - 001F
kWh
Total Active Energy
EactT
0020 - 0021
kWh
Inductive Reactive Energy L1
EreactL1
0022 - 0023
kVarh
Inductive Reactive Energy L2
EreactL2
0024 - 0025
kVarh
Inductive Reactive Energy L3
EreactL3
0026 - 0027
kVarh
Total Inductive Reactive Energy
EreactLT
0028 - 0029
kVarh
Table 17 (Cont.): Modbus memory map.
Parameter
Symbol
Address
Units
Capacitive Reactive Energy L1
EreactC1
002A - 002B
kVarh
Capacitive Reactive Energy L2
EreactC2
002C - 002D
kVarh
Capacitive Reactive Energy L3
EreactC3
002E - 002F
kVarh
Total Capacitive Reactive Energy
EreactCT
0030 - 0031
kVarh
Function 05 is used to delete energy meters.
Table 18:Modbus memory map: Deleting parameters
Deleting parameters
Address
Value to be sent
Deleting energy meters
0000
0xFF00
7.- TECHNICAL FEATURES
Power supply
Rated Voltage
100 ... 400 V ~
Frequency
50 ... 60 Hz
Consumption
4.5 ... 9 VA
Voltage measurement circuit
Voltage measurement margin
100 ... 440 VPh-N
Frequency measurement margin
50 ... 60 Hz
Min. voltage measurement (Vstart)
95 V
Installation category
CAT III
Current measurement circuit
Current measurement through sensors, see “3.3.- SENSORS FOR CURRENT MEASUREMENT”
Measurement accuracy
Voltage measurement
1 % + variations in range of use
Current measurement
1 % + variations in range of use
Active Power measurement
2 % + variations in range of use
Reactive Power measurement
2 % + variations in range of use
Active energy measurement
2 % + variations in range of use
Reactive energy measurement
2 % + variations in range of use
Frequency measurement
1 % + variations in range of use
Power factor measurement
2 % + variations in range of use
Variations in Range of Use
Magnitude of Influence
Range of influence
Typical
Maximum
Temperature
- 10ºC ... +60ºC
-
0.3 %
Relative humidity
10% ... 90%
-
0.3 %
Crosstalk (current)
-
0.9 %
-
External demagnetising field (current)
-
2 %
-
Conductor position
-
2 %
3 %
Adjust
Full Scale
0.2 %
0.4 %
Communications
Type
Wi-Fi (IEEE 802.11)
Protocol
HTTP, Modbus/TCP, XML
Frequency Range
2.405 - 2.48 GHz
Encryption
AES128
Monthly data consumption
300 MB
FCC (USA), IC (CANADA), ETSI (EUROPA) Certified
User interface
LED
2 LEDs
Key
1 key
Mobile application
Wibeee Circutor
Internal memory
Capacity
1 month (offline HD Save Time = 1s)
Download time
Maximum 8 hours
-10ºC ... +45ºC
Storage temperature
-40ºC ... +85ºC
Relative humidity (without condensation)
5 ... 95%
Maximum altitude
2000 m
Protection degree
IP20
Insulation
Double insulation
Mechanical features
Dimensions (mm)
Figure 35
Weight
1700 g
Enclosure
Self-extinguishing VO Plastic (UNE 21031 90ºC)
4,50
4,50
4,50
32
8
105,28
120,96
32
129,70
49,41
54,41
Figure 35: Wibeee Max dimensions.
Standard
Safety requirements for electrical equipment for measurement, control,
and laboratory use -- Part 1: General requirements
IEC 61010-1: 2001
Safety requirements for electrical equipment for measurement, control
and laboratory use -- Part 2-030: Particular requirements for testing and
measuring circuits
UNE-EN 61010-2-030:2011
Electrical equipment for measurement, control and laboratory use - EMC
requirements -- Part 1: General requirements (IEC 61326-1:2005)
UNE-EN 61326-1:2006
Electromagnetic compatibility and Radio spectrum Matters (ERM); Elec-
troMagnetic Compatibility (EMC) standard for radio equipment; Part 17:
Specific conditions for Broadband Data Transmission Systems
EN 301 489-17 V2.2.1.
8.- MAINTENANCE AND TECHNICAL SERVICE
9.- WARRANTY
In the case of any query in relation to device operation or malfunction, please contact the
CIRCUTOR, SA Technical Support Service.
Technical Assistance Service
Vial Sant Jordi, s/n, 08232 - Viladecavalls (Barcelona)
Tel: 902 449 459 ( España) / +34 937 452 919 (outside of Spain)
email: [email protected]
• No returns will be accepted and no unit will be repaired or replaced if it is not ac-
companied by a report indicating the defect detected or the reason for the return.
•The guarantee will be void if the units has been improperly used or the stora-
ge, installation and maintenance instructions listed in this manual have not been
followed. “Improper usage” is defi ned as any operating or storage condition con-
trary to the national electrical code or that surpasses the limits indicated in the
technical and environmental features of this manual.
• CIRCUTOR accepts no liability due to the possible damage to the unit or other
parts of the installation, nor will it cover any possible sanctions derived from a pos-
sible failure, improper installation or “improper usage” of the unit. Consequently,
this guarantee does not apply to failures occurring in the following cases:
- Overvoltages and/or electrical disturbances in the supply;
- Water, if the product does not have the appropriate IP classifi cation;
- Poor ventilation and/or excessive temperatures;
- Improper installation and/or lack of maintenance;
- Buyer repairs or modifi cations without the manufacturer’s authorisation.
CIRCUTOR guarantees its products against any manufacturing defect for two years after the
delivery of the units.
CIRCUTOR will repair or replace any defective factory product returned during the guarantee
period.
Vial Sant Jordi, s/n
08232 - Viladecavalls (Barcelona)
Tel.: (+34) 93 745 29 00 - Fax: (+34) 93 745 29 14
www.circutor.com [email protected]