DPS Telecom NetGuardian 216F Operation & User’s Manual
Read Online
Read the DPS Telecom NetGuardian 216F Operation & User’s Manual online using the built-in PDF viewer.
Text of the manual
March 19, 2019
D-UM-NETGF
Visit our website at www.dpstelecom.com for the latest PDF manual and FAQs.
© 2019 DPS Telecom
This document contains proprietary information which is protected by copyright. All rights are reserved. No part of this
document may be photocopied without prior written consent of DPS Telecom.
All software and manuals are copyrighted by DPS Telecom. Said software and manuals may not be reproduced, copied,
transmitted or used to make a derivative work, by either mechanical, electronic or any other means in whole or in part, without
prior written consent from DPS Telecom, except as required by United States copyright laws.
The material in this manual is for information purposes and is subject to change without notice. DPS Telecom shall not be
liable for errors contained herein or consequential damages in connection with the furnishing, performance, or use of this
manual.
Notice
Revision History
Minor updates
General Updates
Updated Data ports section
Added monitoring SFP Ports and Fiber Fault Deteciton
Revisions to Data Ports
Revisions for BAS Optional Accessory
NetGuardian 216F User Manual (D-OC-UM08C.11100) released.
March 19, 2019
March 22, 2018
September 28, 2017
August 17, 2017
June 4, 2009
June 3, 2009
December 11, 2008
Visit our website at www.dpstelecom.com for the latest PDF manual and FAQs
NetGuardian 216F Overview
1
1
About This Manual
2
2
Shipping List
3
2
Optional Shipping Items - Available by Request
3.1
4
Optional Accessories
4
5
Specifications
5
5
Hardware Installation
6
8
Tools Needed
6.1
8
Mounting
6.2
8
Power Connection
6.3
9
LAN Connection
6.4
10
Alarm and Control Relay Connections
6.5
11
Alarm and Control Relay Connector Pinout Table
6.5.1
11
Discretes 1–16 Connector Pinout Diagram
6.5.2
12
Optional 66 Block Connector
6.5.3
13
Integrated Temperature and Battery Sensor
6.5.4
14
Analog Dipswitches
6.5.5
15
Data Port
6.5.6
16
6.5.6.1
Connecting NetGuardian Accessories
16
Optional Wire-Wrap Back Panel
6.6
17
Integrated 10/100/1000BaseT Ethernet Switch
6.7
17
Front Panel LEDs
7
18
Back Panel LEDs
8
19
Configuring the NetGuardian
9
19
Connecting to the NetGuardian
10
20
... via Craft Port
10.1
20
... via LAN
10.2
20
TTY Interface
11
22
Menu Shortcut Keys
11.1
22
Unit Configuration
11.2
23
Ethernet Port Setup
11.2.1
23
Monitoring
11.3
24
Monitoring the NetGuardian
11.3.1
24
11.3.1.1 Monitoring Base Alarms
25
11.3.1.2 Monitoring Ping Targets
26
11.3.1.3 Monitoring and Operating Relays (Controls)
26
11.3.1.4 Monitoring Analogs
27
11.3.1.5 Monitoring System Alarms
28
11.3.1.6 Monitoring Data Port Activity
28
11.3.1.7 Monitoring SFP Ports and Fiber Fault Detection
29
Viewing Live Target Pings
11.3.2
31
Event Logging
11.3.3
31
Backing Up NetGuardian Configuration Data via FTP
11.3.4
32
11.3.4.1 Reloading NetGuardian Configuration Data
32
Debug Input and Filter Options
11.3.5
33
Reference Section
12
34
Display Mapping
12.1
34
System Alarms Display Map
12.1.1
37
SNMP Manager Functions
12.2
39
SNMP Granular Trap Packets
12.3
42
ASCII Conversion
12.4
43
Frequently Asked Questions
13
44
General FAQs
13.1
44
SNMP FAQs
13.2
46
Technical Support
14
48
RMA Policy
15
49
End User License Agreement
16
49
NetGuardian 216F Overview
1
The NetGuardian 216F has all the tools you need to manage your remote site
The NetGuardian 216F — The Intelligent RTU for Complete Site Management
The NetGuardian 216F is a wide temperature range, SFP Fiber Interface, and Ethernet-based, SNMP/DCPx remote
telemetry unit. The NetGuardian has all the tools you need to manage your remote sites, including a 7 port
10/100/1000BaseT Ethernet switch, built-in alarm monitoring, paging, and e-mail capabilities that can eliminate the
need for an alarm master.
The NetGuardian is the ideal solution for collecting equipment and environmental alarms from your outdoor
enclosures and reporting these alarm conditions. The 7 port Ethernet switch can also be utilized to provide
connectivity to other far-end devices from the SFP Fiber Interface.
Benefits of the NetGuardian 216F include:
·
Integrated 7 port switch - Saves space, provides Ethernet connectivity for other equipment
·
Web Browser support for monitoring and configuring the units–Convenient access
·
Remote Firmware download ability–Easy initial deployment, and avoids costly trips to the sites for routine
upgrades. Firmware upgradable via Ethernet or SFP Fiber Interface.
·
Unique wire-wrap termination–Quick and easy installation and enables the unit to be removed without
rewiring.
·
Multiple master support–Disaster recovery scenarios.
·
Alarm qualification times–Reduce nuisance alarm, avoids alarm desensitization.
·
Extreme temperature rating– -22°F to 158°F (-30°C to 70°C)–A must in harsh environments.
·
Multi-level password access–Control who accesses your units and to what level.
·
Ping IP network devices and verify that they're online and operating.
·
Optional build would include 4 additional data ports. Contact DPS Sales for more information at (800) 622-
3314
·
Expandable up to 160 discrete alarm inputs and 26 control outputs with the NetGuardian DX chassis.
·
The NetGuardian 216F is a 1 rack unit alarm remote that supports 16 discrete alarms that are "software reversible"
to support both N/O and N/C alarm wiring, 8 analog inputs (4 general purpose, 1 for monitoring internal temperature,
and 2 for monitoring battery feeds). The sensor probe has 10-ft long leads, so once connected to the NetGuardian
216F, it may be placed in the most appropriate location within the cabinet. The NetGuardian 216F also allows you
to remotely control external devices via its 2 internal relays. These controls are a convenient and time efficient way
of remotely switching equipment in the field. The Web browser interface allows you to have quick and convenient
access for programming or simply to spot-check the alarm status for any given site.
The NetGuardian 216F's operational temperature range of -22°F to 158°F (-30°C to 70°C) makes it ideal for
deployment in very harsh environments. It's hardened design means it will continue to deliver real time telemetry
when the weather is at its worst.
The NetGuardian can be configured many different ways including TTY for the initial IP settings through the front craft
port, standard Web browser software, and a Windows-based utility called Edit216F, included at no additional cost.
This software will allow you to create a NetGuardian 216F configuration file without being connected to the
NetGuardian 216F, then download that database remotely from the SFP Fiber Interface, Ethernet, or serial
connection.
About This Manual
2
There are three separate user manuals for the NetGuardian 216F: the Hardware Manual (which you're reading now),
the Edit216F User Manual, and the NetGuardian 216F Web Interface User Manual.
This Hardware Manual provides instructions for hardware installation and using the TTY interface. The Edit216F and
Web Interface User Manuals, included on the NetGuardian Resource CD, provide instructions for configuring the
NetGuardian using the Windows-based Edit216F utility software or the Web Interface.
Shipping List
3
Please make sure all of the following items are included with your NetGuardian 216F. If parts are missing, or if you
ever need to order new parts, please refer to the part numbers listed and call DPS Telecom at 1-800-622-3314.
NetGaurdian 216F
D-PK-NETGF-12001
NetGuardian BSM Resource CD
x1
NetGuardian 216F Hardware Manual
D-UM-NETGF
DB9M-DB9F Download Cable 6 ft.
D-PR-045-10-A-04
x2
x4
WAGO Connectors (Main Power)
3/4-Amp GMT Fuses
2-741-00250-00
x2
19" Rack Ear
D-CS-325-10A-00
4 Pin Analog Connector
14ft. Ethernet Cable
D-PR-932-10B-14
3/8" Ear Screws
2-000-60375-05
x4
x4
Standard Rack Screws
1-000-12500-06
Metric Rack Screws
2-000-80750-03
x4
x4
Pads
2-015-00030-00
Zip Ties
1-012-00106-00
Optional Shipping Items - Available by Request
3.1
Wire-Wrap Back Panel
D-PA-00242-10A
The NetGuardian 216F's Wire-Wrap back panel allows for wire-
wrap connections for the discrete alarms, analog alarms, and
control relays.
Temperature Sensor
D-PR-998-10A-07
The NetGuardian 216F's external
temperature sensor cable for manual hook-
up.
Note: The NetGuadian 216F also has an
internal temperature sensor.
x2
Pluggable Back Panel
D-PK-16PAN
The NetGuardian 216's pluggable back panel allows for screw-in
barrier plug connections for the
NetGuardian's alarms and control relays.
23" Rack Ear
D-CS-325-10A-01
The NetGuardian may also come with 23"
rack ears, available on request.
You can extend the capabilities of the NetGuardian through accessory units that provide greater discrete alarm
capacity, remote audiovisual alarm notification, visual surveillance of remote sites, and other options. If you would
like to order any of these accessories, or if you would like more information about them, call DPS Telecom at (800)
622-3314.
NetGuardian Expansion (NetGuardian DX)
D-PK-NETDX-12001
The NetGuardian Expansion provides an additional 48 discrete alarm points. Up to three NetGuardian Expansions
can be daisy-chained off one NetGuardian, providing a total of 160 alarm points.
NetGuardian 864 DX Expansion
D-PK-DX864-12001
The NetGuardian 864 DX G5 is another option to achieve both discrete and analog expansion. Each chassis adds 64
alarm points, providing a total of 208 when 3 DX Expansion units are daisy-chained from the NetGuardian 216F.
Entry Control Unit G2
D-PK-ECUG2
The Building Access System (BAS) is a comprehensive building entry management system that can provide
centralized door access control to your NetGuardian. The four part system consists of the NetGuardian 216F, the
Entry Control Unit (ECU), and optional keypad and/or proximity card reader. With the system in place, the
NetGuardian can maintain a database of all personnel access as well as the time of day and location that access
was granted. It can also receive a control from the T/Mon master to remotely open a door. However, should the
NetGuardian lose connection with the T/Mon, the unit is still able to make local entry decisions. Front panel LEDs
indicate communication activity between the NetGuardian and the ECU.
Specifications
5
Key Specifications:
· 1 RU, 19" Mountable
· 16 Discrete alarms, 8 analog alarms (4 general purpose, 2 for temperature monitoring, 2 for battery
monitoring), 2 controls
· 2 SFP Fiber Interfaces
· 7 ports of 10/100/1000BaseT Ethernet available for client use. Internally, an 8 port switch.
· Dual -48VDC power feed
· Front Craft port and LEDs
· Extended temp range, -22°F to 158°F (-30°C to 70°C)
· Firmware downloadable via LAN or SFP Fiber Interface
· Web browser with multi-level security access
· SNMP–Traps to at least 2 masters natively
· Special amphenol to Wire Wrap termination module
· Includes our new digital temperature probe on 10-ft lead, connects to rear of unit via pluggable screw
lug connector.
· Windows-based configuration utility (Serial/LAN/SFP Fiber Interface)
Analog Input Range:
(–94 to 94 VDC or 4 to 20 mA)
Control Relays:
Form A or Form C
Maximum Voltage:
60 VDC/120 VAC
Maximum Current:
3/4 Amp, AC/DC
Discrete Alarms:
16
Ping Alarms:
16
Protocols:
SNMPv1, v2c and v3
DCPx, DCPf, TRIP, SMTP, TAP
Interfaces:
2 SFP Fiber Interfaces (1000Base-X)
7 RJ45 10/100/1000BaseT Ethernet ports
1 DB9 RS-232 Craft port
1 RJ45 Yost RS-232 port
4 RJ45 Yost RS-232 ports (optional build)
1 50-pin amphenol connectors (discretes, controls, and analogs)
1 4-pin screw connector (external temp sensor)
1 stereo input jack (for external temp sensor)
Dimensions:
1.75"H x 17"W x 12"D (4.5 cm x 43.2 cm x 30.5 cm)
Weight:
4 lbs. 3 oz. (1.9 kg)
Mounting:
19" or 23" rack
Power Input:
+/- 24 – 48VDC (–40 to –70 VDC)
Current Draw:
375 mA max (at -48V)
Fuse:
3/4 amp GMT for power inputs
Visual Interface: 12 bicolor LEDs
11 unicolor LEDs
Operating Temperature:
-22°–158° F (-30°–70° C)
Operating Humidity:
0%–95% noncondensing
To install the NetGuardian, you'll need the following tools:
PC with Edit216F software
Wire Strippers/Cutter
Phillips No. 2 Screwdriver
Punch Down Tool (if 66 blocks are used)
Small Standard No. 2 Screwdriver
Mounting
6.2
The NetGuardian can be flush or rear-mounted
The NetGuardian mounts in a 19" rack or a 23" rack using the provided rack ears for each size. Two rack ear
locations are provided. Attach the appropriate rack ears in the flush-mount or rear-mount locations shown in above.
Note: Rack ears can be rotated 90° for wall mounting or 180º for other mounting options (not shown).
Power connectors and fuses
The NetGuardian has two screw terminal barrier plug power connectors, located on the left side of the back panel.
(See Figure 6.3.1.)
Before you connect a power supply to the NetGuardian, test the voltage of your power supply:
·
Connect the black common lead of a voltmeter to the ground terminal of the battery, and connect the red
lead of the voltmeter to the battery's –48 VDC terminal. The voltmeter should read between –43 and –53
VDC. If the reading is outside this range, test the power supply.
To connect the NetGuardian to a power supply, follow these steps:
1.
Remove Fuse A and Fuse B from the back panel of the NetGuardian. Do not reinsert the fuse until all
connections to the unit have been made.
2.
Remove the power connector plug from Power Connector A. Note that the plug can be inserted into the
power connector only one way — this ensures that the barrier plug can only be reinserted with the correct
polarity. Note that the –48V terminal is on the left and the GND terminal is on the right.
3.
Use the grounding lug to properly ground the unit.
4.
Insert a battery ground into the power connector plug's right terminal and tighten the screw; then insert
a –48 VDC line to the plug's left terminal and tighten its screw.
5.
Push the power connector plug firmly back into the power connector. If the power feed is connected
correctly, the LED by the connector will light GREEN. The LED by the power connector will be off if the
power feed is reversed.
6.
Repeat Steps 2–5 for Power Connector B.
7.
Reinsert Fuse A and Fuse B to power the NetGuardian. The front panel LEDs will flash RED and GREEN.
Chart of Ethernet and SFP Fiber Interface Connections
The NetGuardian 216F has a 10-BaseT Ethernet switch for connecting through LAN. To connect the NetGuardian
216F to the LAN, insert a standard RJ45 Ethernet cable into one of the Ethernet ports.
From the NetGuardian 216F, the connection can be routed via Ethernet to a local subnet of up to 7 devices.
Yost RS-232 RJ45 Connector
Ethernet port pinout
The pinout diagram for the Ethernet switch port is shown above.
Alarm and Control Relay Connections
6.5
Alarm and control relay connectors
The NetGuardian's discrete alarm inputs, control relay outputs, and analog alarm inputs are connected through the
50-pin connectors labeled "Discretes 1–16, Analogs 1-4, and Relays 1-2" on the back panel.
6.5.1
Alarm and Control Relay Connector Pinout Table
Discretes 1–16
RTN
ALM
RTN
ALM
ALM 1
1
26
ALM 9
9
34
ALM 2
2
27
ALM 10
10
35
ALM 3
3
28
ALM 11
11
36
ALM 4
4
29
ALM 12
12
37
ALM 5
5
30
ALM 13
13
38
ALM 6
6
31
ALM 14
14
39
ALM 7
7
32
ALM 15
15
40
ALM 8
8
33
ALM 16
16
41
Alarm, amphenol connector, and control relay pinout (continued on next page)
Analogs 1–4
+
–
ANA 1
21
46
ANA 2
22
47
ANA 3
23
48
ANA 4
24
49
GND
25
50
Control Relatys 1–2
NO/NC
CO
CTRL 1
17/42
43
CTRL 2
19/44
18
FUSE
20/NA
45
Alarm, amphenol connector, and control relay pinout
The table shows the pinouts for the 50-pin connectors "Discretes 1-16," and "Analogs 1-4" and "Control Relays 1-2."
Optional 66 Block Connector
Both of the 50-pin connectors on the back panel of the NetGuardian can be connected to the optional 25-pair 66
Block Connector (part number D-PR-966-10A-00). For 66 block pinout and color code information, see diagram
below for Discretes 1–16.
Note: If connecting to a 50-pair split block, all connections should be made on the two pin columns closest to the
right-hand side of the block or bridge clips should be installed.
Optional 66 block pinout for Discretes 1–16
Integrated Temperature and Battery Sensor
The integrated temperature and battery sensor monitors the ambient temperature and the NetGuardian's power
feeds. This option is available only if it was ordered with your NetGuardian. The integrated temperature sensor
measures a range of -22° F to 158° F (-30° C to 70° C) within an accuracy of ± 1°.
Analog Function
Location
Channel Mapping
User Channel 1
Amphenol or 4-pin
connector
Reported as analog
channel 1
User Channel 2
Amphenol or 4-pin
connector
Reported as analog
channel 2
User Channel 3
Amphenol only
Reported as analog
channel 3
User Channel 4
Amphenol only
Reported as analog
channel 4
Monitor Power Feed A
Internal
Reported as analog
channel 5
Monitor Power Feed B
Internal
Reported as analog
channel 6
Monitor Internal
Temperature
Internal
Reported as analog
channel 7
Monitor External
Temperature
1/4 inch stereo jack
Reported as analog
channel 8
Integrated sensor connection options
Between the Amphenol connector and Fuse B resides the 1/4 inch stereo jack for the external temperature sensor,
as well as the 4-pin connection for Analogs 1-2, as shown below.
Temperature Sensor and Analog Connectors
Dipswitch and layout
The analogs are controlled by the dipswitches to the left of the Amphenol connector (located at the back of the unit).
For milliamp sensor operation, turn the dipswitch on by placing it in the on position. For normal operation, place the
dipswitch in the off position. Note that the dipswitch is internal, and requires the case to be opened in order to
change the setting.
!
Hot Tip!
WARNING
WARNING: Do not put the dipswitches in the on position unless you are sure of the analog setting. Having the
dipswitches on will put a 250 ohm resistor across the input lines. Any voltage beyond 5V or 20 mA will damage
components.
The port can function as a DPC or ECU port.
Data ports on the NetGuardian 216F
1 TX+ (Transmit +)
2 N/C (Not Connected)
3 RX+ (Receive +)
4 GND (Ground)
5 GND (Ground)
6 RX- (Receive -)
7 N/C (Not Connected)
8 TX- (Transmit -)
Yost RS-485 RJ45 Connector
1 CTS (Clear to Send)
2 DSR (Data Set Ready)
3 RXD (Receive Data)
4 GND (Ground)
5 GND (Ground)
6 TXD (Transmit Data)
7 DTR (Data Terminal Ready)
8 RTS (Request to Send)
Yost RS-232 RJ45 Connector
Data Port Pinout
6.5.6.1
Connecting NetGuardian Accessories
If you are using a NetGuardian Expansion, connect it to the Serial port. Additional configuration requires using Edit216F for
Windows configuration software.
Optional Wire-Wrap Back Panel
6.6
The wire-wrap back panel (arrows indicate screw locations for mounting)
The optional wire-wrap back panel provides wire-wrap connections for the NetGuardian's alarms (discrete and analog) and
control relays. Screw the board into the holes on either side of the "Discretes 1-16/Analogs 1-4/Relays 1-2 connector" (as
shown in Figure 6.7.1). To connect discrete alarms, analog alarms, and control relays to the wire-wrap panel, connect them to
the pin block on the front of the panel.
Integrated 10/100/1000BaseT Ethernet Switch
6.7
NetGuardian integrated Ethernet switch
The NetGuardian 216F comes equipped with an integrated 10/100/1000BaseT Ethernet switch, which provides seven
regular Ethernet ports as shown above. The integrated Ethernet switch is powered by the same –48 VDC power as
the NetGuardian, which provides more secure, more robust operation than switches that run off commercial power.
The integrated switch also frees valuable rack space by eliminated an unnecessary extra unit.
Front Panel LEDs
7
Front panel LEDs
The NetGuardian's front panel LEDs indicate communication and alarm reporting status. LED status messages are
described below.
LED
Status
Description
Link
Solid Green
Ethernet link detected
Activity
Blink Green
Activity detected on Ethernet link
SFP
Off
No link detected
Solid Green
Link detected
LAN
Blink Red
Receive traffic on LAN interface
Blink Green
Transmit traffic on LAN interface
Serial
Blink Red
Receive traffic on Serial interface
Blink Green
Transmit traffic on Serial interface
Loop
Solid Red
Loopback detected on SFP interface
Alarm *
Blink Red
Unacknowledged COS alarm exists
Solid Red
Acknowledged alarm exists
Config
Blink Red
Configuration is invalid
Blink Green
Configuration is valid
Craft
Blink Red
Receive traffic on craft interface
Blink Green
Transmit traffic on craft interface
*NOTE: Alarm must be configured for notification to be reflected in LED
Front panel LED Status message descriptions
Back Panel LEDs
8
Back panel LEDs for Power and Ethernet connections
The back panel LEDs indicate the status of power and Ethernet connections. LED status messages are described
below.
LED
Status
Description
Power
Pwr A
Off
Power not applied or polarity incorrect
Green
Power applied
Pwr B
Off
Power not applied or polarity incorrent
Green
Power applied
Fuse
Alarm
---
Red
Fuse A or B is blown
10/100/1000
BaseT Switch
Green
Flashing
Activity on port detected
Orange
Solid
Link detected
SFP Fiber
Interface
Port 1
Red
SFP detected, no link
Green
SFP detected, link is up
Port 2
Red
SFP detected, no link
Green
SFP detected, link is up
Back panel LED Status message descriptions
Configuring the NetGuardian
9
The NetGuardian must be provisioned with log-on passwords, alarm descriptions, port parameters, ping targets,
control descriptions, and other system information. You can provision the NetGuardian using either the Edit216F
software or the Web interface. The NetGuardian also supports a limited TTY interface for configuring some basic
options. (For full instructions on configuring the NetGuardian, see the software configuration guides on the
NetGuardian Resource CD.)
You can provision the NetGuardian either locally through the craft port or remotely through a LAN connection.
However, to access the NetGuardian via LAN you must first make a temporary connection to the NetGuardian and
assign it an IP address on your network. For more information, see Section 10, "Connecting to the NetGuardian."
Connecting to the NetGuardian
10
... via Craft Port
10.1
NetGuardian Craft Port
The simplest way to connect to the NetGuardian is over a physical cable connection between your PC's COM port
and the NetGuardian's craft port.
Note: You must be connected via craft port to use the TTY interface, but you don't have to be connected to a
NetGuardian unit to use Edit216F. You only need a connection to the unit to read or write configuration files to its
NVRAM. You can use Edit216F on an unconnected PC to create and store NetGuardian configuration files.
Use the DB9M-DB9F download cable provided with your NetGuardian to make a craft port connection.
You can perform all configuration tasks via the craft port with Edit216F — but if you like, you can connect via the
craft port just to configure the NetGuardian's Private LAN IP address, and then do the rest of your configuration via a
LAN connection.
... via LAN
10.2
NetGuardian LAN Link
Once LAN settings are provisioned, you can connect to the NetGuardian over a LAN connection by connecting to
one of the seven 10/100/1000BaseT Ethernet switch ports. This is a very convenient way to provision multiple
NetGuardian units at multiple locations. Note: You don't have to be connected to a NetGuardian unit to use
Edit216F. You only need a connection to the unit to read or write configuration files to its NVRAM. You can use
Edit216F on an unconnected PC to create and store NetGuardian configuration files.
To connect to the NetGuardian via LAN, all you need is the unit's IP address (Default IP address is
192.168.1.100).
If you have physical access to the NetGuardian, the easiest thing to do is connect to the unit through the craft
port and then assign it an IP address. Then you can complete the rest of the unit configuration over a remote LAN
connection, if you want. For instructions, see section: "Connecting to the NetGuardian via Craft Port."
If you DON'T have physical access to the NetGuardian, you can make a LAN connection to the unit by
temporarily changing your PC's IP address and subnet mask to match the NetGuardian's factory default IP settings.
Follow these steps:
1.
Look up your PC's current IP address and subnet mask, and write this information down.
2.
Reset your PC's IP address to 192.168.1.200.
3.
Reset your PC's subnet mask to 255.255.0.0. You may have to reboot your PC to apply your changes.
4.
Once the IP address and subnet mask of your computer coincide with the NetGuardian's, you can access
the NetGuardian via a Telnet session or via Web browser by using the NetGuardian's default IP address of
192.168.1.100.
5.
Provision the NetGuardian with the appropriate information, then change your computer's IP address and
subnet mask back to their original settings.
Note: You can ping the NetGuardian to confirm connectivity through the Ethernet switch ports.
The TTY interface initial configuration screen
The TTY interface is the NetGuardian's built-in provision controls for basic configuration of the NetGuardian. Configure
the NetGuardian's Ethernet port settings, monitor the status of base and system alarms, operate control relays, view
live ping targets , view debug or create proxy connections to other ports. For more advanced configuration tools,
please use the Web browser interface or the Edit216F utility.
To use the TTY interface with the NetGuardian, all you need is any PC with terminal emulation software and a
connection to the NetGuardian. This connection can be a direct connection to the NetGuardian's front panel craft
port or a remote connection via Telnet. Some initial software configuration must be performed before you can use a
remote connection to the NetGuardian.
The TTY interface is primarily used for configuring and provisioning the NetGuardian, but you can also use it to ping
IP targets, view system statistics, and data port activity.
NOTE: The TTY default username and password is "dpstelecom".
Menu Shortcut Keys
11.1
The letters before or enclosed in parentheses ( ) are menu shortcut keys. Press the shortcut key to access that
option. Pressing the ESC key will always bring you back to the previous level. Entries are not case sensitive.
11.2.1 Ethernet Port Setup
The NetGuardian must be assigned an IP address before you will be able to connect via LAN using a Telnet client or
a Web browser. To connect via LAN, the minimum configuration requires setup of the IP address and subnet mask.
Follow the instructions below to configure the NetGuardian's IP address, subnet mask, and default gateway for
Ethernet connectivity.
Configure the Ethernet port parameters
1.
Once a connection is established, the NetGuardian will respond with "Password."
2.
Type the default password, "dpstelecom," then press Enter.
Note: DPS strongly recommends changing the default password.
3.
The NetGuardian's main menu will appear.
4.
Type C for the C)onfig menu.
5. Type E for E)dit menu.
6. Type E for port settings.
7.
Configure the unit address, subnet mask, and default gateway.
8.
ESC to the main menu.
9.
When asked if you would like to save changes, type Y (yes).
10. Reboot to save the new configuration to the NetGuardian.
11. Now you can connect to the NetGuardian via LAN and complete the configuration.
11.3.1 Monitoring the NetGuardian
Connect a PC running terminal emulation software to the craft port or connect via LAN using a Telnet client with
emulation to port 2002 to reach the monitor menu selection. This section allows you to do full system monitoring of
the NetGuardian including: all alarms, ping information, relays, analogs, and system status.
The monitor menu allows status checking on all elements
11.3.1.1 Monitoring Base Alarms
View the status of the device connected to the discrete alarms from the M)onitor menu > A)larms option. Under
Status, the word Alarm will appear if an alarm has been activated and Clear will appear if an alarm condition is not
present. If groups are used the user defined status will be displayed.
This example shows page two of the discrete alarms
11.3.1.2 Monitoring Ping Targets
View the status of all your ping targets from the M)onitor menu > P)ing targets option. This screen displays the ping
target ID, description, and IP address. Under Status the word Alarm will appear if an alarm has been activated and
Clear will appear if an alarm condition is not present.
The Ping info submenu allows you to change ping targets
11.3.1.3 Monitoring and Operating Relays (Controls)
The NetGuardian comes equipped with 2 relays that can be used to control external devices. Monitor the status of
your relays from the M)onitor menu > R)elays option.
Relays are set to normally open (N/O) as the factory default, but each or all of them can be changed to normally
closed (N/C) by changing their respective jumper.
The relays can be operated from this screen
11.3.1.4 Monitoring Analogs
View the current reading and the alarm status of your analog devices from the M)onitor menu > a(N)logs option. The
value shown is a snapshot of the channels measurement, not a real-time reading. Refresh the readings by re-
selecting the analogs option. Alarm status indicates that a preset threshold has been crossed and is designated by
an x.
The four analog measuring inputs are set to measure voltage as the factory default. If your sensors output is current,
change the appropriate analog dipswitch, to the current measuring position. The scaling worksheet in the
provisioning section converts all readings shown here into native units, such as degrees Celsius.
Note that channels 5 and 6 are reserved for Power Feed A and Power Feed B, respectively; and that channel 7 is
reserved for internal temperature monitoring ("iF"=internal Fahrenheit) while channel 8 is for external temperature
monitoring ("eF"=external Fahrenheit).
This display allows you to monitor your eight analog inputs
11.3.1.5 Monitoring System Alarms
View the status of the NetGuardian's system alarms from the M)onitor menu > S)ystem option. Under Status, the
word Alarm will appear if an alarm has been activated and Clear will appear if an alarm condition is not present. See
section: "System Alarms Display Map," for more information. If groups are used, the user defined status will be
displayed.
System Alarms can be viewed from the M)onitor menu > S)ystem option
11.3.1.6 Monitoring Data Port Activity
View the status of the NetGuardian's data port from the M)onitor menu > p(O)rts option.
The NetGuardian provides an ASCII description under Transmit and Receive. Choose a) Transmit to view
data transmitted to another device. Choose b) Receive to view data received from another device. See Section
12.4, "ASCII Conversion," for specific ASCII symbol conversion.
Data port activity can be viewed from the M)onitor menu > p(O)rts option
11.3.1.7 Monitoring SFP Ports and Fiber Fault Detection
The NG216F can support 2 SPF connections.
When using a compatible OpticalZonu SFP transceiver, the contents of their registers can be read and the fiber
connection status and parameters are displayed in the TTY interface.
The TTY interface displays information about the transceiver such as its Type, Vendor, Part No., and Wavelength, as
well as diagnostic information on the connection status such as TX Power, RX Power, Voltage, Bias, and
Temperature.
You can monitor SFP port 1 and port 2 individually by entering in the following commands, depending on which port
you wish to monitor:
Port 1:
Port 2:
Fiber Fault Detection and Micro OTDR
If the SFP transceivers are Micro OTDR capable, the distance to the fiber fault will be displayed in this TTY interface
when a fault is detected.
It will take 15 - 30 seconds after power up for the micro OTDR to run.
Once micro OTDR runs, the vendor name field will change from OpticalZonu,Corp to OZC followed by OTDR data:
1. The first number after OZC indicates the number of reflections (02 in the example below).
2. The second number x2 indicates distance to the farthest fault (00128 in the example below means fault is 256m
away [128 x 2]).
11.3.2 Viewing Live Target Pings
Choose P)ing to ping any of the NetGuardian's user defined IP addresses. Then enter the ID number (1-32) of the IP
address or enter any IP address to ping.
Continuously ping an IP address that has been defined in the NetGuardian's ping table
11.3.3 Event Logging
Choose E)vent log to view the up to 100 events posted to the NetGuardian; including unit reset, base and system
alarms, ping alarms, analog alarms, and controls. Posted events for the various alarms include both alarm and clear
status. Refer to the table for event log field descriptions.
Note: All information in the event log will be erased upon reboot or a power failure.
Monitor the last 100 events recorded by the NetGuardian from the M)onitor menu > E)vent log option
Event Log Field
Description
Evt
Event number (1–100)
Date
Date the event occurred
Time
Time the event occurred
Grp
Alarm Group
State
State of the event (A=alarm, C=clear)
PRef
Point reference (See Appendix A for display descriptions).
Description
User defined description of the event as entered in the alarm point and
relay description fields.
Event Log field descriptions
11.3.4 Backing Up NetGuardian Configuration Data via FTP
1.
From the Start menu on your PC, select RUN.
2.
Type "ftp" followed by the IP address of the NetGuardian you are backing up (example: ftp 126.10.120.199).
3.
After the connection is made press Enter.
4.
Enter the password of the NetGuardian (default password is dpstelecom), then press Enter.
5.
Type "binary" and press Enter (necessary for NetGuardian file transfer).
6.
Type "lcd" and press Enter (this allows you to change the directory of your local machine).
7.
Type "get" followed by the name you wish to define for the NetGuardian backup file. Add the extension ".ngd" to
the file name (example: get ngdbkup.ngd) and press Enter.
8.
After reloading, type "bye" and press Enter to exit.
Note: The backup file name can have a maximum of eight characters before the file extension.
11.3.4.1 Reloading NetGuardian Configuration Data
1.
From the Start menu on your PC, select RUN.
2.
Type "ftp" followed by the IP address of the NetGuardian you are backing up (example: ftp 126.10.120.199).
3.
After the connection is made press Enter.
4.
Enter the password of the NetGuardian (default password is dpstelecom), then press ENTER.
5.
Type "binary" and press Enter (necessary for NetGuardian file transfer).
6.
Type "lcd" and press Enter (this allows you to change the directory of your local machine).
7.
Type "put" followed by the name you defined for the NetGuardian backup file and press Enter (example: put
ngdbkup.ngd).
8.
Type "literal REBT" to reboot the NetGuardian.
9.
After reloading, type "bye" and press Enter to exit.
11.3.5 Debug Input and Filter Options
Debug Input Options
ESC
Exit Debug
T
Show task status
U
Show DUART information
R
Show network routing table
X
Clear debug enable bitmap. Turn all debug filters OFF
?
Display Options
Debug Filter Options:
a
Alarm toggle switch. Shows posting of alarm data
A
Analog toggle switch. Shows TTY interface debug
c
Config toggle switch. Shows TTY interface debug
C
Control relay toggle switch. Shows relay operation
d
DCP responder toggle switch. Shows DCP protocol
D
Device toggle switch. Shows telnet and proxy information and NGEdit4 serial
communication.
e
Expansion poller toggle switch. Shows NGDdx polling
f
FTP Command toggle switch. Shows command string parsing
F
FTP Data toggle switch. Shows FTP Read / Write
G
GLD poller toggle switch. Shows GLD polling
h
HTML debug switch. Shows Web Browser processing
H
HDLC debug switch. Shows SFP Fiber Interface channel protocol activity
i
PING toggle switch
k
Socket toggle switch. Shows current dcu resources
o
Osstart toggle switch. Miscellaneous application debug, including NVRAM read
and write operation, and event posting
b
IP broadcasting block. Shows IPA
p
SPORT toggle switch. Port init debug and channeled port debug
q
QAccess toggle switch. Reserved for future use
r
Report toggle switch. Shows reporting event activity, including SNMP, pagers,
email, etc. Also shows PPP negotiation for NG client PPP mode.
s
(SNMP toggle switch. Reserved for future use
S
STAK toggle switch. Shows network processing and IPA of arp requests. Also
shows packets discarded by Filter IPA.
t
TERM toggle switch. Shows UDP/TCP port handling. The camera and network
time (NTP) jobs also use the TERM toggle switch
w
HTTP toggle switch. Shows handling of web browser packets
W
WEB toggle switch 2. Dump HTML text from web browser
Debug Input and Filter Options (previous page)
Discrete Alarms 1-16
8001-8016
9001-9016
99
1
2
Ping Table
8065-8096
9065-9096
99
1
3
Analog Channel 1**
8129-8132
9129-9132
99
1
4
Analog Channel 2**
8193-8196
9193-9196
99
1
5
Analog Channel 3**
8257-8260
9257-9260
99
1
6
Analog Channel 4**
8321-8324
9321-9324
99
1
7
Analog Channel 5–Pow er Feed A**
8385-8388
9385-9388
99
1
8
Analog Channel 6–Pow er Feed B**
8449-8452
9449-9452
99
1
9
Analog Channel 7–Internal Temp Sensor**
8513-8516
9513-9516
99
1
10
Analog Channel 8–External Temp Sensor**
8577-8580
9577-9580
99
1
11
Relays/System Alarms (See table below )
8641-8674
9641-9674
99
1
12
NetGuardian Expansion 1 Alarms 1-48
6001-6064
7001-7064
99
1
13
NetGuardian Expansion 1 Relays 1-8
6065-6072
7065-7072
99
1
14
NetGuardian Expansion 2 Alarms 1-48
6129-6177
7129-7177
99
1
15
NetGuardian Expansion 2 Relays 1-8
6193-6200
7193-7200
99
1
16
NetGuardian Expansion 3 Alarms 1-48
6257-6305
7257-7305
99
1
17
NetGuardian Expansion 3 Relays 1-8
6321-6328
7321-7328
Display descriptions and SNMP Trap numbers for the NetGuardian
* The TRAP number ranges show n correspond to the point range of each display. For example, the SNMP Trap "Set" number for alarm 1
(in Display 1) is 8001, "Set" for alarm 2 is 8002, "Set" for alarm 3 is 8003, etc.
** The TRAP number descriptions for the Analog channels (1-8) are in the follow ing order: minor under, minor over, major under, and major
over. For example, for Analog channel 1, the "Set" number for minor under is 8129, minor over is 8130, major under is 8131, and major over
is 8132.
SNMP Trap #s
Points
Description
Set
Clear
1
Relays
8641
9641
2
Relays
8642
9642
3
Relays
8643
9643
4
Relays
8644
9644
5
Relays
8645
9645
6
Relays
8646
9646
7
Relays
8647
9647
8
Relays
8648
9648
9
Undefined**
8649
9649
10
Undefined**
8650
9650
11
Undefined**
8651
9651
12
Undefined**
8652
9652
Display 11 System Alarms point descriptions (continues on next page)
SNMP Trap #s
Points
Description
Set
Clear
13
Undefined**
8653
9653
14
Undefined**
8654
9654
15
Undefined**
8655
9655
16
Undefined**
8656
9656
17
Timed Tick
8657
9657
18
Exp. Module Callout
8658
9658
19
Netw ork Time Server
8659
9659
20
Accumulation Event
8660
9660
21
Duplicate IP Address
8661
9661
22
Undefined**
8662
9662
23
Undefined**
8663
9663
24
Undefined**
8664
9664
25
Undefined**
8665
9665
26
Undefined**
8666
9666
27
Undefined**
8667
9667
28
Undefined**
8668
9668
29
Undefined**
8669
9669
30
Undefined**
8670
9670
31
Undefined**
8671
9671
32
Undefined**
8672
9672
33
Unit Reset
8673
9673
34
Undefined**
8674
9674
35
Undefined**
8675
9675
36
Lost Provisioning
8676
9676
37
DCP Poller Inactive
8677
9677
38
NET1 not active
8678
9678
40
NET Link Dow n
8680
9680
41
Modem not
8681
9681
42
No dial-tone
8682
9682
43
SNMP Trap not Sent
8683
9683
44
Pager Que Overflow
8684
9684
45
Notification failed
8685
9685
46
Craft RcvQ full
8686
9686
47
Modem RcvQ full
8687
9687
48
Data 1 RcvQ full
8688
9688
49
Data 2 RcvQ full
8689
9689
50
Data 3 RcvQ full
8690
9690
51
Data 4 RcvQ full
8691
9691
52
Data 5 RcvQ full
8692
9692
53
Data 6 RcvQ full
8693
9693
54
Data 7 RcvQ full
9694
9694
Display 11 System Alarms point descriptions (continues on next page)
SNMP Trap #s
Points
Description
Set
Clear
55
Data 8 RcvQ full
8695
9695
56
NetGuardian DX 1 fail
8696
9696
57
NetGuardian DX 2 fail
8697
9697
58
NetGuardian DX 3 fail
8698
9698
59
GLD/BSU 1 Fail
8699
9699
60
GLD/BSU 2 Fail
8700
9700
61
GLD/BSU 3 Fail
8701
9701
62
CHAN timeout
8702
9702
63
Craft Timeout
8703
9703
64
Event Que Full
8704
9704
Display 11 System Alarms point descriptions (continued)
* Data Ports 2-5 are included on optional expansion card.
Note: See section: "System Alarms Display Map," for detailed descriptions of the NetGuardian's system alarms.
12.1.1 System Alarms Display Map
Display
Points
Alarm Point
Description
Solution
11
17
Timed Tick
Toggles state at constant rate as
configured by the Timed Tick timer variable.
Useful in testing integrity of SNMP trap
alarm reporting.
To turn the feature off, set the Timed Tick timer
to 0.
19
Netw ork Time Server Communication w ith Netw ork Time Server
has failed.
Try pinging the Netw ork Time Server’s IP
Address as it is configured. If the ping test is
successful, then check the port setting and
verify the port is not being blocked on your
netw ork.
21
Duplicate IP Address The unit has detected another node w ith
the same IP Address.
Unplug the LAN cable and contact your
netw ork administrator. Your netw ork and the
unit w ill most likely behave incorrectly. After
assigning a correct IP Address, reboot the unit
to clear the System alarm.
33
Pow er Up
The unit has just come-online. The set
alarm condition is follow ed immediately by a
clear alarm condition.
Seeing this alarm is normal if the unit is
pow ering up.
36
Lost Provisioning
The internal NVRAM may be damaged. The
unit is using default configuration settings.
Use Web or latest version of NGEditG5 to
configure unit. Pow er cycle to see if alarm
goes aw ay. May require RMA.
37
DCP Poller Inactive
The unit has not seen a poll from the Master
for the time specified by the DCP Timer
setting.
If DCP responder is not being used, then set the
DCP Unit ID to 0. Otherw ise, try increasing the
DCP timer setting under timers, or check how
long it takes to cycle through the current polling
chain on the Master system.
38
Ethernet not active
The Net1 LAN port is dow n.
Check LAN cable. Ping to and from the unit. (If
not using Net1 or Net2, set IP, Subnet and
Gatew ay to 255's)
40
LNK Alarm
No netw ork connection detected
41
Modem not
responding
An error has been detected during modem
initialization. The modem did not respond to
the initialization string.
Remove configured modem initialization string,
then pow er cycle the unit. If alarm persists, try
resetting the Modem port from the TTY
interface, or contact DPS for possible RMA.
43
SNMP Trap not Sent
SNMP trap address is not defined and an
SNMP trap event occurred.
Define the IP Address w here you w ould like to
send SNMP trap events, or configure the event
not to trap.
44
Pager Queue
Overflow
Over 250 events are currently queued in
the pager queued and are still trying to
report.
Check for failed notification events that may be
filling up the pager queue. There may be a
configuration or communication problem w ith
the notification events.
45
Notification failed
A notification event, like a page or email,
w as unsuccessful.
Use RPT filter debug to help diagnose
notification problems.
46
Craft RcvQ full
The Craft port received more data than it
w as able to process.
Disconnect w hatever device is connected to
the craft serial port. This alarm should not
occur.
47
Modem RcvQ full
The modem port received more data than it
w as able to process.
Check w hat is connecting to the NetGuardian.
This alarm should not occur.
System Alarms Descriptions (continues on next page)
Serial 1 RcvQ full
Serial port 1 (or appropriate serial port
number) receiver filled w ith 8 K of data (4 K
if BAC active).
Check proxy connection. The serial port data
may not be getting collected as expected.
49
Serial 2 RcvQ full
50
Serial 3 RcvQ full
51
Serial 4 RcvQ full
52
Serial 5 RcvQ full
53
Serial 6 RcvQ full
54
Serial 7 RcvQ full
55
Serial 8 RcvQ full
System Alarms Descriptions (continued)
*Data Ports 2-5 are included on optional expansion card.
SNMP Manager Functions
12.2
The SNMP Manager allows the user to view alarm status, set date/time, issue controls, and perform a resync. The
display and tables below outline the MIB object identifiers. Table B.1 begins with dpsRTU; however, the MIB object
identifier tree has several levels above it. The full English name is as follows:
root.iso.org.dod.internet.private.enterprises.dps-Inc.dpsAlarmControl.dpsRTU. Therefore, dpsRTU's full object
identifier is 1.3.6.1.4.1.2682.1.2. Each level beyond dpsRTU adds another object identifying number. For example,
the object identifier of the Display portion of the Control Grid is 1.3.6.1.4.1.2682.1.2.3.3 because the object identifier
of dpsRTU is 1.3.6.1.4.1.2682.1.2 + the Control Grid (.3) + the Display (.3).
Tbl. B1 (O.)_OV_Traps
points
_OV_vTraps
(1.3.6.1.4.1.2682.1.2.0)
PointSet (.20)
PointClr (.21)
SumPSet (.101)
SumPClr (.102)
ComFailed (.103)
ComRestored (.014)
P0001Set (.10001) through
P0064Set (.10064)
P0001Clr (.20001) through
P0064Clr (.20064)
Tbl. B3 (.3) ControlGrid
points
ControlGrid
(1.3.6.1.4.1.2682.1.2.3)
Port (.1)
Address (.2)
Display (.3)
Point (.4)
Action (.5)
Tbl. B2 (.1) Identity points
Ident
(1.3.6.1.4.1.2682.1.2.1)
Manufacturer (.1)
Model (.2)
Firmware Version (.3)
DateTime (.4)
ResyncReq (.5)*
* Must be set to "1" to perform the
resync request which will resend TRAPs
for any standing alarm.
Tbl. B3 (.2) DisplayGrid
points
DisplayEntry
(1.3.6.1.4.1.2682.1.2.2.1)
Port (.1)
Address (.2)
Display (.3)
DispDesc (.4)*
PntMap (.5)*
Tbl. B5 (.5) AlarmEntry points
AlarmEntry (1.3.6.4.1.2682.1.2.5.1)
Aport (.1)
AAddress (.2)
ADisplay (.3)
APoint (.4)
APntDesc (.5)*
AState (.6)
* For specific alarm points, see Table
B6
!
Hot Tip!
The NetGuardian 216F OID has changed from 1.3.6.1.4.1.2682.1.4 to 1.3.6.1.4.1.2682.1.2
Updated MIB files are available on the Resource CD or upon request.
Exp. Module Callout
99
1
11
18
Netw ork Time Server
99
1
11
19
Accumulation Event
99
1
11
20
Duplicate IP Address
99
1
11
21
Undefined**
99
1
11
22-32
Unit Reset
99
1
11
33
Undefined**
99
1
11
34-35
Lost Provisioning
99
1
11
36
DCP poll inactive
99
1
11
37
NET 1 not active
99
1
11
38
NET 2 not active
99
1
11
39
NET link dow n
99
1
11
40
Modem not responding
99
1
11
41
No dial-tone
99
1
11
42
SNMP trap not sent
99
1
11
43
Pager Queue Overflow
99
1
11
44
Notification failed
99
1
11
45
Craft RCVQ full
99
1
11
46
Modem RCVQ
99
1
11
47
Data 1-8 RCVQ
99
1
11
48-55
Alarm point descriptions (continues on next page)
NGDdx 1-3 fail
99
1
11
56-58
GLD/BSU 1-3 fail
99
1
11
59-61
CHAN timeout
99
1
11
62
CRFT timeout
99
1
11
63
Event Que Full
99
1
11
64
Alarm point descriptions (continued)
* "No data" indicates that the alarm point is defined but there is no description entered.
** "Undefined" indicates that the alarm point is not used.
^ Data Ports 2-5 are included on optional expansion card.
SNMP Granular Trap Packets
12.3
Tables 12.3.A and 12.3.B provide a list of the information contained in the SNMP Trap packets sent by the
NetGuardian.
SNMP Trap managers can access alarm information via either:
·
Granular traps (not necessary to define point descriptions for the NetGuardian)
Or
·
The SNMP manager reads the description from the Trap.
UDP Header
Description
1238
Source port
162
Destination port
303
Length
0xBAB0
Checksum
UDP Headers and descriptions
SNMP Header
Description
0
Version
Public
Request
Trap
Request
1.3.6.1.4.1.2682.1.2
Enterprise
126.10.230.181
Agent address
Enterprise Specific
Generic Trap
8001
Specific Trap
617077
Time stamp
1.3.7.1.2.1.1.1.0
Object
NetGuardian 216F v1.0B
Value
1.3.6.1.2.1.1.6.0
Object
1-800-622-3314
Value
1.3.6.1.4.1.2682.1.2.4.1.0
Object
01-02-1995 05:08:27.760
Value
1.3.6.1.4.1.2682.1.2.5.1.1.99.1.1.1
Object
99
Value
1.3.6.1.4.1.2682.1.2.5.1.4.99.1.1.1
Object
1
Value
1.3.6.1.4.1.2682.1.2.5.1.3.99.1.1.1
Object
1
Value
1.3.6.1.4.1.2682.1.2.5.1.2.99.1.1.1
Object
1
Value
1.3.6.1.4.1.2682.1.2.5.1.5.99.1.1.1
Object
Rectifier Failure
Value
1.3.6.1.4.1.2682.1.2.5.1.6.99.1.1.1
Object
Alarm
Value
SNMP Headers and descriptions
The information contained in Table 12.4.A is a list of ASCII symbols and their meanings. Refer to the bulleted list
below to interpret the ASCII data transmitted or received through the data port. Port transmit and receive activity can
be viewed from the Web browser interface.
•
Printable ASCII characters will appear as ASCII.
•
Non-printable ASCII characters will appear as labels surrounded by { } brackets (e.g. {NUL}).
•
Non-ASCII characters will appear as hexadecimal surrounded by [ ] brackets (e.g. [IF]).
•
A received BREAK will appear as .
Abbreviation
Description
Abbreviation
Description
NUL
Null
DLE
Data Link Escape
SOH
Start of Heading
DC
Device Control
STX
Start of Text
NAK
Negative Acknowledge
ETX
End of Text
SYN
Synchronous Idle
EOT
End of Transmission
ETB
End of Transmission Block
ENQ
Enquiry
CAN
Cancel
ACK
Acknowledge
EM
End of Medium
BEL
Bell
SUB
Substitute
BS
Backspace
ESC
Escape
HT
Horizontal Tabulation
FS
File Separator
LF
Line Feed
GS
Group Separator
VT
Vertical Tabulation
RS
Record Separator
FF
Form Feed
US
Unit Separator
CR
Carriage Return
SP
Space (blank)
SO
Shift Out
DEL
Delete
SI
Shift In
BRK
Break Received
ASCII symbols
Frequently Asked Questions
13
Here are answers to some common questions from NetGuardian users. The latest FAQs can be found on the
NetGuardian support web page, http://www.dpstele.com .
If you have a question about the NetGuardian, please call us at (559) 454-1600 or e-mail us at
[email protected]
General FAQs
13.1
Q. How do I telnet to the NetGuardian?
A.
You must use Port 2002 to connect to the NetGuardian. Configure your Telnet client to connect using TCP/IP
(not "Telnet," or any other port options). For connection information, enter the IP address of the NetGuardian
and Port 2002. For example, to connect to the NetGuardian using the standard Windows Telnet client, click
Start, click Run, and type "telnet 2002."
Q. How do I connect my NetGuardian to the LAN?
A. To connect your NetGuardian to your LAN, you need to configure the unit IP address, the subnet mask and the
default gateway. A sample configuration could look like this:
Unit Address: 192.168.1.100
subnet mask: 255.255.255.0
Default Gateway: 192.168.1.1
Save your changes by writing to NVRAM and reboot. Any change to the NetGuardian's IP configuration requires
a reboot.
Q. When I connect to the NetGuardian through the craft port on the front panel it either doesn't work right
or it doesn't work at all. What's going on?
A.
Make sure your using the right COM port settings. Your COM port settings should read:
Bits per second: 9600 (9600 baud)
Data bits: 8
Parity: None
Stop bits: 1
Flow control: None
Important! Flow control must be set to none. Flow control normally defaults to hardware in most terminal
programs, and this will not work correctly with the NetGuardian.
Q. I can't change the craft port baud rate.
A.
If you select a higher baud rate, you must set your terminal emulator program to the new baud rate and press
Enter. If your terminal emulator is set to a slower baud rate than the craft port, normal keys can appear as a
break key — and the craft port interprets a break key as an override that resets the baud rate to the standard
9600 baud.
Q. How do I use the NetGuardian to access TTY interfaces on remote site equipment?
A.
If your remote site device supports RS-232, you can connect it to one of the eight data ports located on the
NetGuardian back panel. To make the data port accessible via LAN, configure the port for TCP/IP operation. You
now have a LAN-based proxy port connection that lets you access your device's TTY interface through a Telnet
session.
Q. How do I telnet to the NetGuardian?
A.
Configure your Telnet client with these options:
·
Connect using TCP/IP (not "Telnet," or any other port options)
·
Enter the IP address of the NetGuardian
·
Enter Port 2002
Example:
To connect using the Windows Telnet client, click Start, click Run, and type telnet 126.12.220.8 2002.
Telnet is connected through the 10BaseT switch. Make sure you're connected to one of the switch's 7
connectors.
Q. I just changed the port settings for one of my data ports, but the changes did not seem to take effect
even after I wrote the NVRAM.
A.
In order for data port and craft port changes (including changes to the baud rate and word format) to take effect,
the NetGuardian must be rebooted. Whenever you make changes, remember to write them to the NetGuardian's
NVRAM so they will be saved when the unit is rebooted.
Q. The LAN link LED is green on my NetGuardian, but I can't poll it from my T/Mon.
A.
Some routers will not forward packets to an IP address until the MAC address of the destination device has
been registered on the router's Address Resolution Protocol (ARP) table. Enter the IP address of your gateway
and your T/Mon system to the ARP table.
Q. What do the terms "port," "address," "display" and "alarm point" mean?
A.
These terms refer to numbers that designate the location of a network alarm, from the most general (a port to
which several devices are connected) to the most specific (an individual alarm sensor).
Port: A number designating a serial port through which a monitoring device collects data.
Address: A number designating a device connected to a port.
Display: A number designating a logical group of 64 alarm points.
Alarm Point: A number designating a contact closure that is activated when an alarm condition occurs. For
example, an alarm point might represent a low oil sensor in a generator or an open/close sensor in a door.
These terms originally referred only to physical things: actual ports, devices, and contact closures. For the sake
of consistency, port-address-display-alarm point terminology has been extended to include purely logical
elements: for example, the NetGuardian reports internal alarms on Port 99, Address 1.
Q. What characteristics of an alarm point can be configured through software? For instance, can point 4
be used to sense an active-low signal, or point 5 to sense a level or a edge?
A.
The NetGuardian's standard configuration is for all alarm points to be level-sensed. You cannot use
configuration software to convert alarm points to TTL (edge-sensed) operation. TTL alarm points are a hardware
option that must be specified when you order your NetGuardian. Ordering TTL points for your NetGuardian does
not add to the cost of the unit What you can do with the configuration software is change any alarm point from
"Normal" to "Reversed" operation. Switching to Reversed operation has different effects, depending on the kind of
input connected to the alarm point:
·
If the alarm input generates an active-high signal, switching to Reversed operation means the
NetGuardian will declare an alarm in the absence of the active-high signal, creating the practical equivalent of an
active-low alarm.
·
If the alarm input generates an active-low signal, switching to Reversed operation means the
NetGuardian will declare an alarm in the absence of the active-low signal, creating the practical equivalent of an
active-high alarm.
·
If the alarm input is normally open, switching to Reversed operation converts it to a normally closed
alarm point.
·
If the alarm input is normally closed, switching to Reversed operation converts it to a normally open
alarm point.
Q. Every time my NetGuardian starts up, I have to reenter the date and time. How can I get the
NetGuardian to automatically maintain the date and time setting?
A.
You have three options for keeping the correct time on your NetGuardian:
Real Time Clock Option: You can order your NetGuardian with the Real Time Clock hardware option. Once it's
set, the Real Time Clock will keep the correct date and time, regardless of reboots.
Network Time Protocol Synchronization: If your NetGuardian has Firmware Version 2.9F or later, you can
configure the unit to automatically synchronize to a Network Time Protocol (NTP) server.
·
To get the latest NetGuardian firmware, sign in to MyDPS at www.dpstelecom.com/mydps.
·
For instructions on configuring your NetGuardian to use NTP synchronization, see your Edit216F or
NetGuardian Web Browser Interface user manual.
T/Mon RTU Time Sync Signal: You can configure your T/Mon NOC to send an RTU Time Sync signal at a
regular interval, which you can set to any time period between 10 and 10,080 minutes. The Time Sync will
automatically synchronize the NetGuardian's clock to the T/Mon's clock. And if you set your T/Mon to NTP
synchronization, you'll make sure you have consistent, accurate time stamps throughout your monitoring
network.
Q. How do I back up my NetGuardian configuration?
A.
There are two ways to back up NetGuardian configuration files:
Use Edit216F
NGEdit4 can read the configuration of a NetGuardian unit connected to your PC via LAN, modem or COM port.
You can then use NGEdit4 to save a NetGuardian configuration file on your PC's hard disk or on a floppy disk.
With Edit216F you can also make changes to the configuration file and write the changed configuration to the
NetGuardian's NVRAM.
Use FTP
You can use File Transfer Protocol (FTP) to read and write configuration files to the NetGuardian's NVRAM, but
you can't use FTP to edit configuration files.
SNMP FAQs
13.2
Q. Which version of SNMP is supported by the SNMP agent on the NetGuardian?
A.
SNMP v1 and v2.0c.
Q. How do I configure the NetGuardian to send traps to an SNMP manager? Is there a separate MIB for
the NetGuardian? How many SNMP managers can the agent send traps to? And how do I set the IP
address of the SNMP manager and the community string to be used when sending traps?
A.
The NetGuardian begins sending traps as soon as the SNMP managers are defined. The NetGuardian MIB is
included on the NetGuardian Resource CD. The MIB should be compiled on your SNMP manager. (Note: MIB
versions may change in the future.) The unit supports a main SNMP manager, which is configured by entering
its IP address in the Trap Address field of Ethernet Port Setup. You can also configure up to eight secondary
SNMP managers, which is configured by selecting the secondary SNMP managers as pager recipients.
Community strings are configured globally for all SNMP managers. To configure the community strings, choose
System from the Edit menu, and enter appropriate values in the Get, Set, and Trap fields.
Q. Does the NetGuardian support MIB-2 and/or any other standard MIBs?
A.
The NetGuardian supports the bulk of MIB-2.
Q. Does the NetGuardian SNMP agent support both NetGuardian and T/MonXM variables?
A.
The NetGuardian SNMP agent manages an embedded MIB that supports only the NetGuardian's RTU variables.
The T/MonXM variables are included in the distributed MIB only to provide SNMP managers with a single MIB for
all DPS Telecom products.
Q. How many traps are triggered when a single point is set or cleared? The MIB defines traps like "major
alarm set/cleared," "RTU point set," and a lot of granular traps, which could imply that more than one
trap is sent when a change of state occurs on one point.
A.
Generally, a single change of state generates a single trap, but there are two exception to this rule. Exception
1: the first alarm in an "all clear" condition generates an additional "summary point set" trap. Exception 2: the
final clear alarm that triggers an "all clear" condition generates an additional "summary point clear" trap.
Q. What does "point map" mean?
A.
A point map is a single MIB leaf that presents the current status of a 64-alarm-point display in an ASCII-readable
form, where a "." represents a clear and an "x" represents an alarm.
Q. The NetGuardian manual talks about two control relay outputs. How do I control these from my SNMP
manager?
A.
The control relays are operated by issuing the appropriate set commands, which are contained in the DPS
Telecom MIB. For more information about the set commands, see Appendix, "Display Mapping," in any of the
NetGuardian software configuration guides.
Q. How can I associate descriptive information with a point for the RTU granular traps?
A.
The NetGuardian alarm point descriptions are individually defined using the Web Browser, TTY, or Edit216F
configuration interfaces.
Q. My SNMP traps aren't getting through. What should I try?
A.
Try these three steps:
1.
Make sure that the Trap Address (IP address of the SNMP manager) is defined. (If you changed the
Trap Address, make sure you saved the change to NVRAM and rebooted.)
2.
Make sure all alarm points are configured to send SNMP traps.
3.
Make sure the NetGuardian and the SNMP manager are both on the network. Use the NetGuardian's
ping command to ping the SNMP manager.
DPS Telecom products are backed by our courteous, friendly Technical Support representatives, who will give you
the best in fast and accurate customer service. To help us help you better, please take the following steps before
calling Technical Support:
1. Check the DPS Telecom website.
You will find answers to many common questions on the DPS Telecom website, at http://
www.dpstelecom.com/support/. Look here first for a fast solution to your problem.
2. Prepare relevant information.
Having important information about your DPS Telecom product in hand when you call will greatly reduce the time it
takes to answer your questions. If you do not have all of the information when you call, our Technical Support
representatives can assist you in gathering it. Please write the information down for easy access. Please have
your user manual and hardware serial number ready.
3. Have access to troubled equipment.
Please be at or near your equipment when you call DPS Telecom Technical Support. This will help us solve your
problem more efficiently.
4. Call during Customer Support hours.
Customer support hours are Monday through Friday, from 7 A.M. to 6 P.M., Pacific time. The DPS Telecom
Technical Support phone number is (559) 454-1600.
Emergency Assistance: Emergency assistance is available 24 hours a day, 7 days a week. For emergency
assistance after hours, allow the phone to ring until it is answered with a voicemail message(the only time DPS
allows voicemail!!). You will be asked to enter your phone number. An on-call technical support representative will
return your call as soon as possible. If the on-call staff is unable to resolve the problem, they will be able to
escalate the call to the appropriate DPS personnel.
Technical support features have been built into many of our products. In many cases, our technicians, in
conjunction with customer permission, can dial directly into our units to correct problems first-hand.
DPS Telecom guarantees all products for two years. We will repair any deficiency in workmanship during this
warranty period free of charge. DPS Telecom products not under warranty can still be repaired with a service
charge.
In the event that a DPS Telecom product needs repaired, contact Technical Support and a technician can help
solidify the field diagnosis, and issue and RMA number if needed. An RMA will be issued if the product has a failed
feature or component, if the technicians are unable to resolve the issue remotely, or if the wrong product is ordered
or shipped.
DPA Telecom, on average, returns RMA units within 4 weeks and will email the RMA submitter on the return
shipment with a tracking number.
Under urgent circumstances, DPS Telecom will issue an advanced replacement. DPS Telecom will send a
replacement unit in advance if the problem affects service or if technicians can better troubleshoot an issue. In both
cases the advance replacement depends on DPS Telecom stock on hand.
End User License Agreement
16
All Software and firmware used in, for, or in connection with the Product, parts, subsystems, or derivatives thereof, in
whatever form, including, without limitation, source code, object code and microcode, including any computer
programs and any documentation relating to or describing such Software is furnished to the End User only under a
non-exclusive perpetual license solely for End User's use with the Product.
The Software may not be copied or modified, in whole or in part, for any purpose whatsoever. The Software may not
be reverse engineered, compiled, or disassembled. No title to or ownership of the Software or any of its parts is
transferred to the End User. Title to all patents, copyrights, trade secrets, and any other applicable rights shall
remain with the DPS Telecom.
DPS Telecom's warranty and limitation on its liability for the Software is as described in the warranty information
provided to End User in the Product Manual.
End User shall indemnify DPS Telecom and hold it harmless for and against any and all claims, damages, losses,
costs, expenses, obligations, liabilities, fees and costs and all amounts paid in settlement of any claim, action or
suit which may be asserted against DPS Telecom which arise out of or are related to the non-fulfillment of any
covenant or obligation of End User in connection with this Agreement.
This Agreement shall be construed and enforced in accordance with the laws of the State of California, without
regard to choice of law principles and excluding the provisions of the UN Convention on Contracts for the
International Sale of Goods. Any dispute arising out of the Agreement shall be commenced and maintained only in
Fresno County, California. In the event suit is brought or an attorney is retained by any party to this Agreement to
seek interpretation or construction of any term or provision of this Agreement, to enforce the terms of this
Agreement, to collect any money due, or to obtain any money damages or equitable relief for breach, the prevailing
party shall be entitled to recover, in addition to any other available remedy, reimbursement for reasonable attorneys'
fees, court costs, costs of investigation, and other related expenses.
alarm detection speed, 5
analog alarm inputs, 5
current range, 5
voltage range, 5
ASCII Conversion, 43
backup NetGuardian Configuration, 32
cables, 2
download cable, 2
Ethernet cable, 2
telephone cable, 2
control relays, 1, 5
maximum current, 5
maximum voltage, 5
operating from SNMP manager, 46
craft port,
making a craft port connection, 20
serial format, 44
current draw, 5
debug filter, 33
debug input, 33
dimensions, 5
discrete alarm inputs,
capacity, 5
display mapping, 34
Edit216F,
connecting to the NetGuardian 216F, 20, 20
Ethernet port, 10
event logging, 31
firmware updates, 1
frequently asked questions (FAQs), 44
general, 44
SNMP, 46
fuse, 2
installation,
LAN connection, 10
mounting, 8
power connection, 9
tools needed, 8
LAN, 1, 10
LAN connections,
making a LAN connection, 20
MIB object identifiers, 39
NetGuardian 216F,
accessories, 5
accessory part numbers, 5
configuration interfaces, 2
connecting via craft port, 20
connecting via LAN, 20
MIB, 46
provisioning, 2
resource CD, 2
software configuration, 2
software configuration guides, 2
specifications, 5
TTY interface, 1, 2
user manual, 2
Web Browser interface, 1, 2
NetGuardian Expansion, 5
NVRAM, 44
parts, 2
numbers, 2
ordering, 2
power input, 5, 9
rack ears, 2, 8
reach-through ports, 1
reload NetGaurdian configurations, 32
serial ports, 1
SFP Interface, 16, 18, 19
shipping list, 2
SNMP, 1, 46
Granualr Trap Packets, 42
SNMP manager functions, 39
SNMP traps, 46
specifications, 5
system alarm descriptions, 37
system alarm point descriptions, 34
target pings, 31
technical support, 44, 48
e-mail address, 44
phone number, 44, 48
web page, 48
Telnet, 44
temperature,
external temperature sensor, 14
integrated temperature and battery sensor, 1, 14
specifications, 5
TTY,
Analogs, 27
Base Alarms, 25
Controls, 26
Data Port Activity, 28
Ethernet Port, 23
menu keys, 22
Monitoring, 24
Ping Targets, 26
System Alarms, 28
TTY interface, 22
wire-wrap back panel, 5, 17
“Your Partners in Network Alarm Management ”