Mark* VIe and Mark VIeS Control Systems

Volume I: System Guide June 2020 Public Information

These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible

contingency to be met during installation, operation, and maintenance. The information is supplied for informational purposes only, and GE makes no warranty as to the accuracy of the information included herein. Changes, modifications, and/or improvements to equipment and specifications are made periodically and these changes may or may not be reflected herein. It is understood that GE may make changes, modifications, or improvements to the equipment referenced herein or to the document itself at any time. This document is intended for trained personnel familiar with the GE products referenced herein. GE may have patents or pending patent applications covering subject matter in this document. The furnishing of this document does not provide any license whatsoever to any of these patents. Public Information – This document contains non-sensitive information approved for public disclosure. GE provides the following document and the information included therein as is and without warranty of any kind, expressed or implied, including but not limited to any implied statutory warranty of merchantability or fitness for particular purpose. For further assistance or technical information, contact the nearest GE Sales or Service Office, or an authorized GE Sales Representative. Revised: June 2020 Issued: Jan 2004 © 2004 - 2020 General Electric Company. ___________________________________ * Indicates a trademark of General Electric Company and/or its subsidiaries. All other trademarks are the property of their respective owners. We would appreciate your feedback about our documentation. Please send comments or suggestions to [email protected] Public Information

Corrected the GE industrial Ethernet 10/100 IONet switch operating

temperature BPPC-based I/O Pack Migration Removed “although this is not recommended” from table entry on mixing BPPB and BPPC I/O packs Intrinsic Variables and Totalizers Updated totalizer support by ControlST version BN Turbine I/O Types Added the compatible terminal boards TVBAH1B and TVBAH2B for the PVIBH1 I/O pack Mark VIeS Safety I/O Types Added the compatible terminal board TVBAS2B for the YVIBS1 I/O pack BM Signal Reference Structure Updated the last paragraph for clarification Terminal Board Fuse Details Updated IS200TRLYH1C and 2C to include 5 X 20MM TIME-LAG in the table Power Distribution, Terminal Board Fuses BL Terminal Board Fuse Details Corrected IS200JPDDG2A to 3A in the table Power Distribution, Terminal Board Fuses IONet Switches Incorporated content from the removed section Approved IONet Switches section into this section and added Approved IONet Switches as the table heading for the list of approved IONet switches BK Serial Number/Barcode Convention New section that provides the logic of the GE serial number/barcode convention Terminal Board Fuse Details Added the following terminal boards to the table Power Distribution, Terminal Board Fuses: IS200JPDDG2A, IS200JPDDG3A, and IS200JPDDG4A; remove +FU# from GE Part # column BJ Introduction Added Attention statement that users application may not be licensed to access full system capability and I/O types described in this document Modbus Protocol Changes made for clarification, including: • Removed the note referencing GSM 3.0 documentation, which is not related to Modbus • Added a note below the Mark VIe Controller Modbus Communication Protocols diagrams in the section Controller Modbus to state that the diagram is not meant to show how to connect Modbus to an application; it is to give the reader a point of reference as to how Modbus is implemented. • Controller was removed from the Mark VIe Controller Modbus Communication Protocols diagram to limit confusion because it does not add value; it was only a point of reference BH Introduction Added content for the Universal I/O (UIO) Mark VIe control cabinet BG IONet Switches Corrected the redundant input voltage range from 10–30 to 18–36 v dc Approved IONet Switches Updated the list of approved IONet ESWx switches Modbus Protocol Added Modbus Slave support for Mark VIeS Safety controller Electromagnetic Compatibility Directive (EMC) 2014/30/EU Updated the EU directive number from 2004/108/EC to 2014/30/EU Added the Code and Description details in the table of fulfilled requirements for EU directive EN/IEC 61326-1 Low Voltage Directive 2014/35/EU Updated the EU directive number from 2006/95/EC to 2014/35/EU Humidity Removed EN50178 statement System Guide GEH-6721_Vol_I_BP 3 Public Information

Shipping and Storage Temperature

Added a table providing equipment shipping and storage temperature range Alarm Types Added content providing the alarm system requirements for maximum number of new alarms that can be processed BE Mark VIe BPPC I/O Migration Guidelines Removed mention of BPPC I/O Upgrade V05.01.xx or Later DVD and added note about Auto-Reconfiguration not available with the Mark VIeS Safety controller. Mean Time Between Failure (MTBF) Added procedure for accessing Exida Applications in Harsh Environments New section Software Tools Moved this content to ControlST Software Suite Installation, Upgrade, and Compatibility Guide (GEI-100694) BD BPPC-based I/O Packs Migration Updates to installation guideslines I/O Module Types Added PVIBH1B, YVIBH1B Diagnostic Alarms Reset New section Unit-specific Grounding Examples New section I/O Types New PUAAH1A Universal Analog I/O Module BC I/O Module Types Added SDIIH2A, YDIAS1B, and YAICS1B Power and I/O Field Wiring New table for wire limitations BPPC-based I/O Pack Migration New sections BPPC-based Mark VIeS Safety I/O Packs Available Mark VIe BPPC-based I/O Packs Mark VIe BPPC I/O Migration Guidelines Equip Mark VIe System for Migration BB Communication Protocols Added PROFINET to the list of Fieldbus Network Protocols Component Part Numbers New section Troubleshooting Added some helpful tables and notes Dual Controllers Updated description to better explain differences between dual controllers and dual I/O pack functions. Functional Safety Updated table to include YSIL, SRSA, YDOAS1B, and STAIS3A Localization - Translation to Native Languages New section Environment Updated information to include components with expanded ambient temperature ratings Controller Alarm Subsystem New section Ethernet Networks Removed subsection on Wind Plant Architecture Less specific switch definitions used, with reference to related document for details Added the ESWA to the section Approved IONet Switches I/O Packs Fixed the accuracy rating for temperature sensor Terminal Board Fuse Details New section 4 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Acronyms and Abbreviations

Acronym Definition Acronym Definition AWG American Wire Gauge PDM Power Distribution Module BoP Balance of Plant PE Protective Earth CDH Control Data Highway PLC Programmable Logic Controller CMOS Complementary Metal-Oxide Semiconductor RLD Relay Ladder Diagram CRC Cyclic Redundancy Code/Check RTD Resistance Temperature Device DAC Digital-to-Analog Converter RTU Remote Terminal Unit DCE Data Communication Equipment SDI System Data Interface Protocol DCS Distributed Control System SIFT Software Implemented Fault Tolerance DHCP Dynamic Host Configuration Protocol TMR Triple Modular Redundancy DMZ Demilitarized Zone TTL Transistor-transistor Logic EGD Ethernet Global Data UDH Unit Data Highway EMC Electromagnetic Capability UDP User Datagram Protocol EMI Electromagnetic Interference UTC Coordinated Universal Time ERA Electrical Riser Angle UTP Unshielded Twisted Pair (cabling) FE Functional Earth VLAN Virtual Local Area Network GPS Global Position System WAN Wide Area Network GSM GE Standard Messaging GTS Global Time Source HMI Human-machine Interface HRSG Heat Recovery Steam Generator IEC International Electrotechnical Commission IEEE Institute of Electrical and Electronics Engineers KP Keyphasor* LAN Local Area Network MPU Magnetic Pickup MDH Monitoring Data Highway MTBF Mean Time Between Failures MTBFO Mean Time Between Forced Outage MTTR Mean Time To Repair NEMA® National Electrical Manufacturer’s Association NFPA National Fire Protection Association NTP Network Time Protocol PDH Plant Data Highway System Guide GEH-6721_Vol_I_BP 5 Public Information

Mark VIeS Control Functional Safety Manual

GEH-6725 Mark VIe and Mark VIeS Control Systems Equipment in Hazardous Locations (HazLoc) Instruction Guide GEH-6700 or GEH-6703 ToolboxST User Guide for Mark Controls Platform GEH-6721_Vol_II Mark VIe and Mark VIeS Control Systems Volume II: System Guide for General-purpose Applications GEH-6855_Vol_I Mark VIeS Functional Safety Systems for General Market Volume I: System Guide GEH-6855_Vol_II Mark VIeS Functional Safety Systems for General Market Volume I: System Guide for General-purpose Applications GEH-6860 Mark VIeS Control General Market Functional Safety Manual GEH-6861 Mark VIeS Functional Safety System Equipment in Hazardous Locations (HazLoc) Instruction Guide GEH-6741 Sequential Function Chart Application Guide GEH-6742 Mark VIe and Mark VIeS Virtual Controller User Guide GEH-6757 WorkstationST GSM 3.0 User Guide GEH-6760 WorkstationST GSM 3.0 Application Guide GEH-6761 Mark VIe Control FOUNDATION Fieldbus™Interface Application Guide GEH-6812 Mark Controllers Shared IONet User Guide GEI-100679 Mark VIe Distributed Control System (DCS) Block Library GEI-100682 Mark VIe Control Standard Block Library GEI-100681 Mark VIe Control Legacy Block Library GEI-100694 ControlST Software Suite Installation, Upgrade, and Compatibility Guide GEI-100795 Trender Instruction Guide GEI-100620 WorkstationST Alarm Viewer Instruction Guide 6 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Safety Symbol Legend

Warning Indicates a procedure or condition that, if not strictly observed, could result in personal injury or death. Caution Indicates a procedure or condition that, if not strictly observed, could result in damage to or destruction of equipment. Attention Indicates a procedure or condition that should be strictly followed to improve these applications. GEH-6721_Vol_I_BP System Guide 7 Public Information

Control System Warnings

Warning To prevent personal injury or damage to equipment, follow all equipment safety procedures, Lockout Tagout (LOTO), and site safety procedures as indicated by Employee Health and Safety (EHS) guidelines. Warning This equipment contains a potential hazard of electric shock, burn, or death. Only personnel who are adequately trained and thoroughly familiar with the equipment and the instructions should install, operate, or maintain this equipment. Warning Isolation of test equipment from the equipment under test presents potential electrical hazards. If the test equipment cannot be grounded to the equipment under test, the test equipment’s case must be shielded to prevent contact by personnel. To minimize hazard of electrical shock or burn, approved grounding practices and procedures must be strictly followed. Warning To prevent personal injury or equipment damage caused by equipment malfunction, only adequately trained personnel should modify any programmable machine. Warning Always ensure that applicable standards and regulations are followed and only properly certified equipment is used as a critical component of a safety system. Never assume that the Human-machine Interface (HMI) or the operator will close a safety critical control loop. 8 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Control System Overview............................................................................................................. 11

1.1 Introduction.......................................................................................................................................... 11 1.2 Controllers ........................................................................................................................................... 15 1.3 IONet Switches ..................................................................................................................................... 16 1.4 Distributed I/O Modules.......................................................................................................................... 16 1.5 Power Distribution................................................................................................................................. 36 1.6 Redundancy Options .............................................................................................................................. 37 1.7 Reliability and Availability ...................................................................................................................... 49 1.8 Component Part Numbers and Serial Numbers/Barcodes............................................................................... 57 2 Functional Safety............................................................................................................................67 2.1 Safety Instrumented System (SIF)............................................................................................................. 68 2.2 Risk Reduction...................................................................................................................................... 69 2.3 Safety System Redundancy Options .......................................................................................................... 70 3 Ethernet Networks..........................................................................................................................75 3.1 Introduction.......................................................................................................................................... 75 3.2 IONet Layer ......................................................................................................................................... 80 3.3 Unit Control Layer................................................................................................................................. 86 3.4 Supervisory Layer.................................................................................................................................. 91 3.5 Monitoring Layer................................................................................................................................... 92 3.6 Enterprise Layer.................................................................................................................................... 93 3.7 Ethernet Cabling for Monitoring, Supervisory, and Unit Control Layers ........................................................... 94 3.8 Third-party Communication Links ............................................................................................................ 98 4 Communication Protocols ...........................................................................................................99 4.1 OPC Protocols .....................................................................................................................................101 4.2 WorkstationST GSM Protocol.................................................................................................................104 4.3 Modbus Protocol ..................................................................................................................................106 4.4 Ethernet Global Data (EGD) ...................................................................................................................109 4.5 System Data Interface (SDI) Protocol .......................................................................................................111 4.6 Network Time Protocol (NTP) ................................................................................................................112 4.7 Fieldbus Communications ......................................................................................................................115 5 Technical Regulations, Standards, and Environment ........................................................ 117 5.1 Safety Standards...................................................................................................................................117 5.2 Conditions for Compliance .....................................................................................................................118 5.3 Electrical.............................................................................................................................................119 5.4 Environment........................................................................................................................................121 6 Installation Guidelines ................................................................................................................127 6.1 Installation Support...............................................................................................................................127 6.2 Equipment Receiving and Handling .........................................................................................................130 6.3 Power Requirements .............................................................................................................................132 6.4 Installation Support Drawings .................................................................................................................134 6.5 Grounding...........................................................................................................................................134 6.6 Cable Separation and Routing .................................................................................................................143 6.7 Power and I/O Field Wiring....................................................................................................................149 GEH-6721_Vol_I_BP System Guide 9 Public Information

6.8 System Power Connection......................................................................................................................152

6.9 Startup Checks .....................................................................................................................................153 6.10 BPPC-based I/O Pack Migration..............................................................................................................158 6.11 Available Mark VIe BPPC-based I/O Packs ...............................................................................................160 6.12 Mark VIe BPPC I/O Migration Guidelines.................................................................................................161 6.13 Equip Mark VIe System for Migration......................................................................................................163 7 Alarm Overview.............................................................................................................................165 7.1 Alarm System Architecture.....................................................................................................................165 7.2 Alarm Types ........................................................................................................................................168 7.3 Controller Alarm Subsystem...................................................................................................................168 7.4 Diagnostic Alarms ................................................................................................................................169 7.5 Process Alarms ....................................................................................................................................172 7.6 Alarm Communication Flow...................................................................................................................174 8 Troubleshooting ...........................................................................................................................175 8.1 Controller, I/O Pack, IONet Switch Not Powering On..................................................................................175 8.2 Unable to Download to Controller............................................................................................................178 8.3 Controller Not in Controlling State...........................................................................................................179 8.4 Unable to Download to I/O Modules ........................................................................................................184 8.5 Unable to Communicate with I/O Module .................................................................................................185 8.6 Unable to Download to Controller or I/O Module .......................................................................................186 8.7 Communication Loss Between Controller and I/O Module............................................................................187 8.8 Boot Log Collection..............................................................................................................................188 8.9 I/O Module Replacement or Upgrade Issues...............................................................................................189 8.10 LED Indicators.....................................................................................................................................194 Glossary of Terms ..............................................................................................................................195 Index.......................................................................................................................................................199 10 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Control System Overview

1.1 Introduction The Mark* VIe control system is a flexible platform used in multiple applications. Its architecture enables unique engineered solutions for a variety of large industrial applications. It features high-speed, networked input/output (I/O) for Simplex, Dual, and Triple Modular Redundant (TMR) systems. Industry-standard Ethernet communications are used for I/O, controllers, and supervisory interface to operator and maintenance stations, as well as third-party systems. The Mark VIeS Safety controller and I/O can operate independently or integrated with the rest of the Mark VIe controllers for safety-critical applications that conform to IEC® 61508. The ControlST* Software Suite, which contains the ToolboxST* application software, is used or programming, configuration, trending, and analyzing diagnostics for Mark controls and related systems. It provides quality, time-coherent data at controller and plant level for effectively managing control system equipment. ControlST simplifies maintenance while retaining a unique set of certified hardware and software blocks. ToolboxST provides a means to lock or unlock the Mark VIeS Safety controller for configuration and Safety Instrumented Function (SIF) programming The Universal I/O (UIO) control cabinet provides a platform for an independent, miniature version of the Mark VIe or Mark VIeS Safety control. The PUAA module is the standard Mark VIe compatible module, while the YUAA module is the companion module that is used in the Mark VIeS Safety control system. The UIO control cabinet is a lower cost, smaller footprint alternative to the standard Mark control cabinet. The control cabinet is installed at sites when there are I/O, power, and/or space limitations in the existing Mark VI, Mark VIe, or Mark VIeS control cabinet. This is especially required for upgrades when there are space restrictions. This unit may also be used as an independent Mark VIe or Mark VIeS control system, communicating directly with the Unit Data Highway (UDH) or Plant Data Highway (PDH), regardless of the existing controller at the site. The UIO control system supports specific I/O. For a list of supported I/O, refer to the Mark VIe and Mark VIeS Control Systems Volume II: System Guide for General-purpose Applications (GEH-6721_Vol_II). ToolboxST is used to set up, configure, and download to the UIO Mark VIe controller. Attention The information in this document applies to the overall Mark* VIe control system or Mark VIeS Functional Safety System control products; however, your application may not be licensed to access full system capability and I/O packs as described in this document. For example, the Mark VIeS Functional Safety System for General Markets only utilizes the following I/O packs: •• Analog I/O (YAIC) •• Universal Analog (YUAA) •• Vibration Input Monitor (YVIB) •• Relay Output (YDOA) •• Discrete Contact Input (YDIA) •• Power Distribution System Diagnostics (PPDA) •• Serial Modbus Communication (PSCA) •• Mark VIeS Safety Controller (UCSCS2x) •• Mark VIe Controller for Gateway (UCSCH1x) Control System Overview GEH-6721_Vol_I_BP System Guide 11 Public Information

Note All instructions in this manual also apply to the UIO control cabinet.

Typical Architecture for Large Industrial Control Systems 12 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

The Mark VIe and Mark VIeS control systems are used in a wide range of process control and protection applications, including steam, gas, and wind turbines, power

generation balance of plant (BoP), deep sea drilling, desalinization, gas compression, and other facility-wide equipment management systems. The control system primarily consists of three hardware components: controller(s), I/O network (IONet) switches, and I/O modules. The control system provides more options for redundancy, better maintainability, and greater capability for locating I/O modules closer to the controlled equipment. It provides quality, time-coherent data at controller and plant level for effectively managing control system equipment. ControlST, which include the ToolboxST and WorkstationST applications, is used for programming, configuration, trending, and troubleshooting the Mark control product line. The following are two commonly used ToolboxST configuration screens. Software Block Editor Control System Overview GEH-6721_Vol_I_BP System Guide 13 Public Information

Component Hardware Editor

14 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

The Mark VIe controller is a stand-alone, single-board controller with scalable

processing power. It includes built-in power supplies and requires no batteries or jumper settings. Controllers run the ControlST* Software Suite, providing a common software environment for turbine and generator excitation controls in the power island and balance of plant equipment to simplify operations and maintenance. The Mark VIeS Safety controller is IEC 61508 certified to SIL 3. Controllers are loaded with software specific to its application, such as steam, gas, land-marine (LM), Balance of Plant (BoP), offshore drilling, desalination, CS, and Wind Power Conversion. It can run Relay Ladder Diagrams (RLD) or blocks. The IEEE® 1588 protocol is used through the R, S, and T I/O networks (IONet) to synchronize the clock of the I/O modules and controllers to within ±100 microseconds. Data is transferred to and from the control system database in the controller over the I/O networks (IONet). IONet data includes process inputs/outputs to the I/O packs. In a dual system, IONet data also includes: • Internal state values and initialization information from the designated controller • Status and synchronization information from both controllers In a triple module redundant (TMR) system, IONet data also includes: • Internal state values for voting and status and synchronization information from all three controllers • Initialization information from the designated controller Note For more information on the Mark VIe controller, refer to the Mark VIe and Mark VIeS Control Systems Volume II: System Guide for General-purpose Applications (GEH-6721_Vol_II), the chapter Controllers. More more information on the Mark VIeS Safety controller, refer to the Mark VIeS Control Functional Safety Manual (GEH-6723). For a list of controllers that are available for each control system, including the supported and unsupported features the controllers offer for that control system, refer to the ToolboxST User Guide for Mark Controls Platform (GEH-6700 or GEH-6703). Control System Overview GEH-6721_Vol_I_BP System Guide 15 Public Information

GE’s Industrial Ethernet 10/100 switches (ESWA and ESWB) provide the performance and features needed in today’s

real-time industrial control systems. Use 8-port ESWA or 16-port ESWB Ethernet switches in all control system I/O networks to maintain the reliability needed for I/O module reception of controller outputs. Note For more information on the IONet switches, refer to the Mark VIe and Mark VIeS Control Systems Volume II: System Guide for General-purpose Applications (GEH-6721_Vol_II), the chapter Unmanaged Ethetnet Swtiches. 1.4 Distributed I/O Modules TMR I/O Module The I/O modules contain three basic parts: terminal board, terminal block, and I/O pack. The terminal board mounts to the cabinet and comes in two basic types: S and T. The I/O pack mounts to the terminal board J-port connector. Both terminal board types provide the following features: • Terminal blocks for I/O wiring • Mounting hardware • Input isolation and protection • I/O pack connectors • Unique electronic ID Simplex I/O Module 16 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

I/O packs have a common processor board and a data acquisition board that is unique

to the type of connected device. I/O packs on each terminal board digitize the I/O variables, perform algorithms, and communicate with the controller. The I/O pack provides fault detection through a combination of special circuitry in the data acquisition board and software running in the Central Processing Unit (CPU) board. The fault status is transmitted to and used by the controllers. The I/O pack transmits inputs and receives outputs on both network interfaces if connected. Each I/O pack also sends an identification message (ID packet) to the main controller when requested. The packet contains, the hardware catalog number of the I/O board, the hardware revision, the board barcode serial number, the firmware catalog number, and the firmware version. The I/O packs have a temperature sensor that is accurate to within ±2°C (±3.6 °F). Every I/O pack temperature is available in the database and can be used to generate an alarm. 1.4.2 Terminal Boards Signal flow begins with a sensor connected to a terminal block on a board. Wide and narrow terminal boards are arranged in vertical columns of high and low-level wiring. An example of a wide board is a board that contains magnetic relays with fused circuits for solenoid drivers. A shield strip is provided to the left of each terminal block. It can be connected to a metal base for immediate grounding or floated to allow individual ground wires from each board to be wired to a centralized, cabinet ground strip. Input Screws I/O Pack Connector Output Screws Simplex Terminal Board Input Screws I/O Pack Connector I/O Pack Connector I/O Pack Connector Output Screws Vote / Select TMR Terminal Board Control System Overview GEH-6721_Vol_I_BP System Guide 17 Public Information

T-type terminal boards typically fan the sensor inputs to three separate I/O packs. Usually, the TMR board hardware votes the

outputs from the three I/O packs. T-type boards contain two, 24-point, barrier-type, removable, terminal blocks. Each point can accept two 3.0 mm (0.12 in) (#12AWG) wires with 300 V insulation per point with either spade or ring-type lugs. In addition, captive clamps are provided for terminating bare wires. Screw spacing is 9.53 mm (0.375 in) minimum and center-to-center. Note Some application-specific TMR terminal boards do not fan inputs or vote the outputs. Barrier-type Terminal Blocks These terminal blocks have the following features: • Black in color with white number labels • Terminal rating is 300 V, 10 A • UL recognized • Recommended screw tightening torque is 7 lb-in (0.8 Nm). 18 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

S-type boards provide a single set of screws for each I/O point and allow a single I/O pack to condition and digitize the I/O.

They are half the size of T-type boards and are standard base mounted but can also be DIN-rail mounted. These boards can be used for simplex, dual, or dedicated triple redundant sensors by using one, two, or three modules. S-type boards have Euro-style, box type terminal blocks. Some boards are available as either removable or fixed terminal block versions. S-type board terminal blocks accept one 2.05 mm (0.08 in) (#12 AWG) wire or two 1.63 mm (0.06 in) (#14 AWG) wires, each with 300 V insulation per point. Screw spacing is 5.08 mm (0.2 in) minimum and center-to-center. Box-type Terminal Blocks These terminal blocks have the following features: • Green in color with number labels. • Terminal rating is 300 V, 10 A • UL and CSA recognized • Recommended screw tightening torque is 5 lb-in (0.5 - 0.6 Nm) Control System Overview GEH-6721_Vol_I_BP System Guide 19 Public Information

I/O Module Types

1.4.3.1 General Purpose I/O Types Discrete I/O Types I/O Pack/ # per Board Board Discrete I/O Types Type Removable PDIAH1A/1, 2, 3 PDIAH1B/1, 2, 3 TBCIH1C 24 discrete inputs (DI) (125 V dc, group isolated) sequence of events (SOE) Barrier Yes PDIAH1A/1, 2, 3 PDIAH1B/1, 2, 3 TBCIH2C 24 DI (24 V dc, group isolated) SOE Barrier Yes PDIAH1A/1, 2, 3 PDIAH1B/1, 2, 3 TBCIH3C 24 DI (48 V dc, group isolated) SOE Barrier Yes PDIAH1A/1, 2, 3 PDIAH1B/1, 2, 3 TBCIH4C 24 DI (24 V dc, group isolated) SOE Barrier Yes PDIAH1A/, 2, 3 PDIAH1B/1, 2, 3 TICIH1A 24 DI (115/230 V ac, 125 V dc point isolated) SOE Barrier Yes PDIAH1A/1, 2, 3 PDIAH1B/1, 2, 3 TICIH2A 24 DI (24 V dc, point isolated) SOE Barrier Yes PDIAH1A/1 PDIAH1B/1 STCIH1A 24 DI (24 V dc, group isolated) SOE Box No PDIAH1A/1 PDIAH1B/1 STCIH2A 24 DI (24 V dc, group isolated) SOE Box Yes PDIAH1A/1 PDIAH1B/1 STCIH4A 24 DI (48 V dc, group isolated) SOE Box Yes PDIAH1A/1 PDIAH1B/1 STCIH6A 24 DI (125 V dc, group isolated) SOE Box Yes PDIAH1A/1 PDIAH1B/1 STCIH8A 24 DI (24 V dc, group isolated) SOE Box Yes PDIIH1A/1 PDIIH1B/1 SDIIH1A 16 DI (24, 48, 125, 250 V dc, 115, 230 V ac point isolated, line-break detection) SOE Box Yes SDIIH2A Same as H1A but is also enhanced to provide more vibration protection for use in some GE Drilling applications. The purchase price is higher for this version, which includes RTV and stabilizer bar. WDIIH1A WDIIH2A WDIIH3A Add 24 V dc, 115/230 V ac wetting voltage Add 48 V dc wetting voltage Add 125 V dc wetting voltage (group isolation) Daughter boards PDIOH1A/1 PDIOH1B/1 TDBSH2A 24 DI and 12 type C mechanical relays (24 V dc group isolated) SOE (Refer to Option Boards Note 1, 2, and 3), SOE for relay outputs Box Yes 20 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Discrete I/O Types (continued)

I/O Pack/ # per Board Board Discrete I/O Types Type Removable PDIOH1A/1 PDIOH1B/1 TDBSH4A 24 DI and 12 type C mechanical relays (48 V dc group isolated) SOE (Refer to Option Boards Note 1, 2, and 3), SOE for relay outputs Box Yes PDIOH1A/1 PDIOH1B/1 TDBSH6A 24 DI and 12 type C mechanical relays (125 V dc group isolated) SOE (Refer to Option Boards Note 1, 2, and 3), SOE for relay outputs Box Yes PDIOH1A/3 PDIOH1B/3 TDBTH2A 24 DI and 12 type C mechanical relays (24 V dc group isolated) SOE (Refer to Option Boards Note 1), SOE for relay outputs Box Yes PDIOH1A/3 PDIOH1B/3 TDBTH4A 24 DI and 12 type C mechanical relays (48 V dc group isolated) SOE (Refer to Option Boards Note 1), SOE for relay outputs Box Yes PDIOH1A/3 PDIOH1B/3 TDBTH6A 24 DI and 12 type C mechanical relays (125 V dc group isolated) SOE (Refer to Option Boards Note 1), SOE for relay outputs Box Yes PDOAH1A/1, 3 PDOAH1B/1, 3 TRLYH1B 12 type C mechanical relays with 6 solenoids, coil diagnostics (115/230 V ac, 24/48/125 V dc), SOE for relay outputs Barrier Yes PDOAH1A/1, 3 PDOAH1B/1, 3 TRLYH1C 12 type C mechanical relays with 6 solenoids, voltage diagnostics (115/230 V ac, 125 V dc), SOE for relay outputs Barrier Yes PDOAH1A/1, 3 PDOAH1B/1, 3 TRLYH2C 12 type C mechanical relays with 6 solenoids, voltage diagnostics (24 V dc), SOE for relay outputs Barrier Yes PDOAH1A/1, 3 PDOAH1B/1, 3 TRLYH1D 6 type A mechanical relays for solenoids, solenoid impedance diagnostics (24/125 V dc), SOE for relay outputs Barrier Yes PDOAH1A/1 PDOAH1B/1 SRLYH1A 12 type C mechanical relays (115/230 V ac, 24/48/125 V dc), SOE for relay outputs Box No PDOAH1A/1 PDOAH1B/1 SRLYH2A 12 type C mechanical relays (115/230 V ac, 24/48/125 V dc) (Refer to Option Boards Note1, 2, and 3), SOE for relay outputs Box Yes PDOAH1A/1, 3 PDOAH1B/1, 3 TRLYH1E 12 type A solid-state relays (115/230 V ac), voltage diagnostics, SOE for relay outputs Barrier Yes PDOAH1A/1, 3 PDOAH1B/1, 3 TRLYH2E 12 type A solid-state relays (125 V dc), voltage diagnostics, SOE for relay outputs Barrier Yes PDOAH1A/1, 3 PDOAH1B/1, 3 TRLYH3E 12 type A solid-state relays (24 V dc), voltage diagnostics, SOE for relay outputs Barrier Yes PDOAH1A/3 PDOAH1B/3 TRLYH1F 36 mechanical relays, 12 voted type A normally open (NO) outputs (115 V ac, 24/48/125 V dc) (Refer to Option Boards Note 4 and 5), SOE for relay outputs Barrier Yes PDOAH1A/3 PDOAH1B/3 TRLYH2F 36 mechanical relays, 12 voted type B normally closed (NC) outputs (115 V ac, 24/48/125 V dc) (Refer to Option Boards Note 4 and 5), SOE for relay outputs Barrier Yes Control System Overview GEH-6721_Vol_I_BP System Guide 21 Public Information

Note 1: Add solenoid interface to first 6 relay circuits

WROFH1A Note 2: Add fuse in COM leg of all 12 relay circuits WROGH1A Note 3: Add fuse power distribution in COM leg of all 12 relay circuits WPDFH1A Note 4: Fuses for solenoid power in (+) and (-) legs WPDFH2A Note 5: Fuses for field solenoid power in top side only for common neutral AC solenoids Analog I/O Types I/O Pack/ # per Board Board Analog I/O Types Type Removable PAICH1A/1, 3 PAICH1B/1, 3 TBAIH1C 10 analog inputs (AI) voltage over current (V/I) inputs, group isolated and 2 analog outputs (AO) (0-20 mA outputs, group isolated) Barrier Yes PAICH2A/1, 3 PAICH2B/1, 3 TBAIH1C 10 AI (V/I inputs, group isolated) and 2 AO (0-20/0-200 mA outputs, group isolated) Barrier Yes PAICH1A/1 PAICH1B/1 STAIH1A 10 AI (V/I inputs, group isolated) and 2 AO (0-20 mA outputs, group isolated) Box No PAICH2A/1 PAICH2B/1 STAIH1A 10 AI (V/I inputs, group isolated) and 2 AO (0-20/0-200 mA outputs, group isolated) Box No PAICH1A/1 PAICH1B/1 STAIH2A 10 AI (V/I inputs, group isolated) and 2 AO (0-20 mA outputs, group isolated) Box Yes PAICH2A/1 PAICH2B /1 STAIH2A 10 AI (V/I inputs, group isolated) and 2 AO (0-20/0-200 mA outputs, group isolated) Box Yes PAICH1A/1 PAICH1B/1 SAIIH1A 10 AI (V/I inputs, point isolated) and 2 AO (0-20 mA outputs, group isolated) Box No PAICH2A/1 PAICH2B/1 SAIIH1A 10 AI (V/I inputs, point isolated) and 2 AO (0-20/0-200 mA outputs, group isolated) Box No PAICH1A/1 PAICH1B/1 SAIIH2A 10 AI (V/I inputs, point isolated) and 2 AO (0-20 mA outputs, group isolated) Box Yes PAICH2A/1 PAICH2B/1 SAIIH2A 10 AI (V/I inputs, point isolated) and 2 AO (0-20/0-200 mA outputs, group isolated) Box Yes PAOCH1A/1, 2 PAOCH1B/1, 2 TBAOH1C 16 AO (0-20 mA outputs) 8 per I/O pack Barrier Yes PAOCH1A/1 PAOCH1B/1 STAOH1A 8 AO (0-20 mA outputs) Box No PAOCH1A/1 PAOCH1B/1 STAOH2A 8 AO (0-20 mA outputs) Box Yes PHRAH1A/1 PHRAH1B/1 SHRAH1A 10 AI (V/I inputs) and 2 AO (0-20 mA outputs) with HARTcommunications Box No PHRAH1A/1 PHRAH1B/1 SHRAH2A 10 AI (V/I inputs) and 2 AO (0-20 mA outputs) with HARTcommunications Box Yes 22 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Analog I/O Types (continued)

I/O Pack/ # per Board Board Analog I/O Types Type Removable PPDAH1A/1 PPDAH1B/1 JPDS JPDM JPDG JPDC Power Distribution System Feedback N/A NA PTCCH1A/1, 2, 3 PTCCH1B/1, 2, 3 TBTCH1B 12 Thermocouples Barrier Yes PTCCH2A/1, 2, 3 PTCCH2B/1, 2, 3 TBTCH1B 12 Thermocouples with extended range for EPRI compliance Barrier Yes PTCCH1A/1, 2 PTCCH1B/1, 2 TBTCH1C 24 Thermocouples (12 per I/O pack) Barrier Yes PTCCH2A/1, 2 PTCCH2B/1, 2 TBTCH1C 24 Thermocouples (12 per I/O pack) with extended range for EPRI compliance Barrier Yes PTCCH1A/1 PTCCH1B/1 STTCH1A 12 Thermocouples Box No PTCCH2A/1 PTCCH2B/1 STTCH1A 12 Thermocouples with extended range for EPRI compliance Box No PTCCH1A/1 PTCCH1B/1 STTCH2A 12 Thermocouples Box Yes PTCCH2A/1 PTCCH2B/1 STTCH2A 12 Thermocouples with extended range for EPRI compliance Box Yes PRTDH1A/1, 2 PRTDH1B/1, 2 TRTDH1D 16 RTDs 3 wires /RTD (8 per I/O pack) Barrier Yes PRTDH1A/1, 2 PRTDH1B/1, 2 TRTDH2D 16 RTDs 3 wires /RTD (8 per I/O pack) supports fast scan rate Barrier Yes PUAAH1A / 1 SUAAH1A The Universal Analog I/O Pack supports a variety of I/O types. Refer to GEH-6721_Vol_II for details. Box Yes Control System Overview GEH-6721_Vol_I_BP System Guide 23 Public Information

Fieldbus I/O Types

I/O Pack/ Qty per Board Board Communications Types Type Removable PSCHHIA/1, 2 SSCAH1A SSCAH2A 6 serial 6 serial Box Box No Yes PSCAH1A/1 PSCAH1B/1 SSCAH1A 6 MODBUS Master serial or 1 Modbus Ethernet Box No PSCAH1A/1 PSCAH1B/1 SSCAH2A 6 MODBUS Master serial or 1 Modbus Ethernet Box Yes PCNOH1A/1 PCNOH1B/1 SPIDG1A CANopen Master Gateway N/A N/A PPRFH1A/1 PPRFH1B/1 PROFIBUS - DP-V0, Class 1 Master Communications PROFIBUS - DP-V1 Class 1 Master Communications (PPRFH1B only) N/A N/A PPNGH1A N/A PROFINET RT Version 2.2 I/O gateway module maps I/O from PROFINETslave devices to the Mark VIe controller on the IONet N/A N/A PFFAH1A/1 N/A FOUNDATION Fieldbus H1 TO HSE Linking Device N/A N/A 24 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Turbine I/O Types

Turbine specific I/O modules provide direct interface to unique turbine field devices, which reduces or eliminates a substantial amount of interposing instrumentation. As a result, many potential single-point failures are eliminated for improved running reliability and reduced long-term maintenance. Direct interface also enables the diagnostics to directly monitor field devices. This provides more precise messages to minimize maintenance time. Pack # packs Terminal Board Turbine Applications Terminal Block Type PAMCH1A 1 or 2 SAMBH1A Acoustic Monitor for MS 6, 7, 9 gas turbines: 18 inputs and buffered outputs UCSA used as I/O pack to interface with BAPA for acoustic monitoring function Removable, Box PCLAH1A PCLAH1B 1 SCLSH2A Core Analog I/O for aero-derivative turbines Removable, Box 3 SCLTH2A PCAAH1A PCAAH1B 1 TCASH2A Core Analog I/O for heavy duty gas turbines Removable, Box 3 TCATH2A PEFVH1A 1, 2, or 3 TEFVH1A Electric Fuel Valve Gateway to Woodward™DVP N/A PGENH1A 1 or 3 TGNAH1A Used for Power Load Unbalance (PLU) and has three 1-phase PTs, three V/I inputs. Analog inputs are box-type and removable. Current transformer (CT) inputs are barrier-type and not removable. PVIBH1A PVIBH1B 1 or 3 TVBAH1A TVBAH2A TVBAH1B TVBAH2B Refer to GEH-6721_Vol_II for a complete listing of supported inputs. TVBAH2A and TBVAH2B include buffered outputs and BNC connectors. Removable, Barrier PSVOH1A PSVOH1B 1 or 3 TSVCH1 TSVCH2A Servos: 2 channels, 2-coil outputs, 8 LVDTs and excitation, 2 pulse rate inputs (heavy duty & Aero-derivative gas & steam) Removable, Barrier PSVPH1A 1 SSVPH1A SSVPH2A Steam servo applications: 2 channels, 2-coil outputs, 6 LVDTs and 2 excitation, 1 pulse rate input for speed feedback Removable, Barrier Removable, Box PTURH1B PTURH1A 1, 3 TTURH#C Turbine Specific Primary Trip, 48 points Removable, Barrier 1 STURH#A Removable, Box 3 TRPAH#A Aeroderivative Turbine Primary Trip, 48 points Removable, Barrier Control System Overview GEH-6721_Vol_I_BP System Guide 25 Public Information

Terminal Block Type

PPRAS1B†† PPRAS1A†† 3 TREAS#A + WREAS1A Aero-derivative Turbine Emergency Trip, 48 points TREA_1A: Removable, Barrier TREA_3A: Removable, Box PPRAH1A 3 TREAH#A + WREAH1A PPROS1B†† 3 TPROS#C Backup Turbine Protection, 48 points TPRO_1A: Removable, Barrier TPRO_2A: Removable, Box PPROS1B PPROH1A 3 TPROH#C 1 SPROH#A Backup Turbine Protection, 24 points SPROH1A: Removable, Barrier SPROH2A: Removable, Box 3 TREAH#A Aero-derivative Turbine Emergency Trip, 48 points H1A, H2A: Removable, Barrier H3A, H4A: Removable, Box ††These modules have IEC 61508 safety-certified functions 26 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Migration I/O Types

The following table provides a list of I/O modules approved for use with Mark V, Mark V LM, and Mark VI migration to the Mark VIe control Mark V, Mark V LM, and Mark VI Migration to Mark VIe Control I/O Pack/Qty per Board Terminal Board Interface Board Migration I/O Types Type Removable PIOAH1A/1 N/A JPDV Mark V ARCNET I/O (for excitation control) N/A N/A PMVE/1, 3 QTBA TBQA TBQB TBQC TBQF TBQD TBQG CTBA TBCA TBCB TCQC MVRA MVRB MVRC MVRF UCSA used as I/O pack controller to interface with dedicated Mark V turbine I/O application boards. Box No – H1A, Yes - H2A, No - G1A, No - G1B PMVD/1, 3 DTBA DTBB DTBC DTBD TCRA 96 contact inputs, 60 relay contact outputs Box No – H1A, Yes – H2A, No –G1A, No – G1B PMVP/3 PTBAG1A PTBAG2A Expansion board TCEB and trip boards TCTE, TCTG, TCTL, TCTS, 2 magnetic p.u. speed inputs, 8 flame detector pulse inputs, Trip solenoid interface relays, Generator breaker synchronizing circuits E-Stop Barrier No PCMI VRID Any existing Mark VI VME board except VPYR, VSCA, VPRO, or VAMB Migration from Mark VI Master Interface N/A N/A Control System Overview GEH-6721_Vol_I_BP System Guide 27 Public Information

Mark VIeS Safety I/O Types

The following table lists the Mark VIeS Safety specific I/O modules. I/O Pack # of packs Terminal Board Mark VIeS Safety I/O Types Connector Type Removable YAICS1A YAICS1B 1, 3 1 1 1 TBAIS1C STAIS1A STAIS2A STAIS3A 10 analog inputs (voltage, 0-20 mA) 2 analog outputs (0-20 mA) Box Box Box None Yes No Yes No YDIAS1A YDIAS1B 1, 2, 3 1, 2, 3 1, 2, 3 1 1 1 1 TBCIS1 TBCIS2 TBCIS3 STCIS1A STCIS2A STCIS4A STCIS6A 24 discrete inputs w/ group isolation (24 V dc, 48 V dc, or 125 V dc) Box Yes Yes Yes No Yes Yes Yes YHRAS1A 1 SHRAS1A SHRAS2A 10 analog inputs (0-20 mA), 2 analog outputs (0-20 mA) (All I/O HARTenabled) Box No Yes YTCCS1A 1 , 2 1 , 2 1 1 TBTCS1B TBTCS1C STTCS1A STTCS2A 12 thermocouple inputs Box Yes Yes No Yes YVIBS1A YVIBS1B 1, 3 TVBAS1A TVBAS2A TVBAS2B Refer to GEH-6721_Vol_II for a complete listing of supported inputs. TVBAS2A and TVBAS2B include buffered outputs and BNC connectors. Box Yes YPROS1A 3 3 3 3 3 3 1 TREAS1A TREAS2A TREAS3A TREAS4A TREGS1B TREGS2B SPROS1A Backup/emergency protection 3 speed inputs 7 contact inputs 3 monitored trip relay outputs 1 E-Stop Barrier Barrier Box Box Box Box Barrier Yes YTURS1A 3 TTURS1C TRPAS1A TRPAS2A TRPGS1B TRPGS2B Primary turbine protection 4 speed inputs 8 flame inputs 3 monitored trip relay outputs 1 E-Stop Box Yes 28 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Mark VIeS Safety I/O Types

Connector Type Removable YSILS1B 3 one TCSAS1A and three SCSAS1A I/O types are detailed in GEH-6721_Vol_III for GE Industrial Applications (if available) Box Yes YDOAS1A YDOAS1B 1, 3 TRLYS1B 12 type C mechanical relays with 6 solenoids, coil diagnostics (115/230 V ac, 24/48/125 V dc), SOE for relay outputs Barrier Yes YDOAS1A YDOAS1B 1, 3 TRLYS1D 6 type A mechanical relays for solenoids, solenoid impedance diagnostics (24/125 V dc), SOE for relay outputs Barrier Yes YDOAS1A YDOAS1B 1, 3 SRLYS1A 12 type C mechanical relays (115/230 V ac, 24/48/125 V dc), SOE for relay outputs Box No YDOAS1A YDOAS1B 1 SRLYS2A 12 type C mechanical relays (115/230 V ac, 24/48/125 V dc) (Refer to Option Boards Note1, 2, and 3), SOE for relay outputs Box Yes YDOAS1A YDOAS1B 1 SRSAS1A SRSAS3A 10 relay outputs Box None Yes No YDOAS1A YDOAS1B 3 TRLYS1F 36 mechanical relays, 12 voted type A normally open (NO) outputs (115 V ac, 24/48/125 V dc) (Refer to Option Boards Note 4 and 5), SOE for relay outputs Barrier Yes YDOAS1A YDOAS1B 3 TRLYS2F 36 mechanical relays, 12 voted type B normally closed (NC) outputs (115 V ac, 24/48/125 V dc) (Refer to Option Boards Note 4 and 5), SOE for relay outputs Barrier Yes Control System Overview GEH-6721_Vol_I_BP System Guide 29 Public Information

Renewable Energy I/O Types

The following table lists the Renewable Energy I/O types. Assembly Individual Boards Renewable I/O Types AEPAH1A AEPAH1A BPPB Alternative Energy Pitch Axis, special-purpose in 1.5 MW wind pitch control: 8 analog inputs, 1 incremental encoder input, 1 absolute encoder input, 1 analog output, 20 discrete inputs, 1 discrete output, 8 relay outputs, 2 RS-485 interfaces, 1 brake control output AEPAH1C AEPAH1A BPPC AEPCH1A AEPCH1A BPPB Alternative Energy Pitch Center module in 20, 30, and 40 Newton Meters (Nm) wind pitch control: 1 24 V dc, 8 A power input, 1 RS-422 interface AEPCH1B AEPCH1B BPPB AEPCH1C AEPCH1C BPPB AEPCH1D AEPCH1A BPPC WEMDH4 AEPCH1E AEPCH1B BPPC WEMDH5 AEPCH1F AEPCH1C BPPC WEPAH1A AEPAH1B BPPB WPCI Wind Energy Pitch Axis special-purpose in 30 and 40 Nm wind pitch control: 8 analog inputs, 1 incremental encoder input, 1 analog output, 20 discrete inputs, 2 discrete outputs, 9 relay outputs, 2 RS-485 interfaces, 2 PWM control outputs WEPAH1B AEPAH1B BPPC WPCI WEPAH2A AEPAH1B BPPB WEPAH2B AEPAH1B BPPC WETAH1A WETAH1A BPPB Wind Energy Top Box board A, special-purpose in 1.5 MW ESS turbine: 69 digital inputs; 8 are pulse-rate counter inputs, 18 analog PT100 temperature sensor inputs, 2 analog thermistor temperature sensor inputs, 12 analog 4 to 20 mA current inputs, 25 relay contact outputs 19 solid-state relay outputs, 1 RS-485 interface WETAH1B WETAH1B BPPC WCBMH1A WCBMH1A Wind Condition Top Box Monitor condition-based monitoring for wind turbines, measures vibration on main bearing, gearbox, and generator bearings WEMAH1A WEMA BPPB Wind Energy Main converter control for ESS wind turbine: 27 digital inputs, 2 analog thermistor temperature sensor inputs, 9 relay contact outputs, 3 solid-state relay outputs WEMAH1B WEMA BPPC 30 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Renewable I/O Types

WEMAH2A WEMA BPPB Wind Energy Main converter control for Brilliance Solar PV inverter: 27 digital inputs, 2 analog thermistor temperature sensor inputs, 9 relay contact outputs, 3 solid-state relay outputs WEMAH2B WEMA BPPC WECAH1A MACC BPPB Wind power converter interface for the power converter: 27 digital inputs, 9 relay contact outputs, 3 solid-state relay outputs SECAH1A MACC BPPB Solar power converter interface for the solar inverter: 27 digital inputs, 9 relay contact outputs, 3 solid-state relay outputs Control System Overview GEH-6721_Vol_I_BP System Guide 31 Public Information

Terminal Board Fuse Details

The following tables are provided to assist in inventory management of the replaceable fuses used on some terminal boards. Discrete I/O, Terminal Board Fuses Board Fuse Designator GE Part # Fuse Rating MFR # IS200TRLYH1B FU1, FU2, FU3, FU4, FU5, FU6, FU7, FU8, FU9, FU10, FU11, FU12 64G5005-011 FUSE, 3.15A, 500VAC/400VDC LITTELFUSE 04773.15MXP IS200TRLYS1B FU1, FU2, FU3, FU4, FU5, FU6, FU7, FU8, FU9, FU10, FU11, FU12 64G5005-011 FUSE, 3.15A, 500VAC/400VDC LITTELFUSE 04773.15MXP IS200TRLYH1C FU1, FU2, FU3, FU4, FU5, FU6, FU7, FU8, FU9, FU10, FU11, FU12 64G5005-011 FUSE, 3.15A, 500VAC/400VDC, 5 X 20MM TIME-LAG LITTELFUSE 04773.15MXP IS200TRLYH2C FU1, FU2, FU3, FU4, FU5, FU6, FU7, FU8, FU9, FU10, FU11, FU12 64G5005-011 FUSE, 3.15A, 500VAC/400VDC, 5 X 20MM TIME-LAG LITTELFUSE 04773.15MXP IS200TRLYH1D FU1, FU2, FU3, FU4, FU5, FU6, FU7, FU8, FU9, FU10, FU11, FU12 64G5005-011 FUSE, 3.15A, 500VAC/400VDC LITTELFUSE 04773.15MXP IS200TRLYS1D FU1, FU2, FU3, FU4, FU5, FU6, FU7, FU8, FU9, FU10, FU11, FU12 64G5005-011 FUSE, 3.15A, 500VAC/400VDC LITTELFUSE 04773.15MXP IS200WROBH1A FU1, FU2, FU3, FU4, FU5, FU6, FU7, FU8, FU9, FU10, FU11, FU12 64G5005-011 FUSE, 3.15A, 500VAC/400VDC LITTELFUSE 04773.15MXP IS200WROFH1A FU1, FU2, FU3, FU4, FU5, FU6, FU7, FU8, FU9, FU10, FU11, FU12 64G5005-011 FUSE, 3.15A, 500VAC/400VDC LITTELFUSE 04773.15MXP IS200WROGH1A FU1, FU2, FU3, FU4, FU5, FU6, FU7, FU8, FU9, FU10, FU11, FU12 64G5005-011 FUSE, 3.15A, 500VAC/400VDC LITTELFUSE 04773.15MXP IS200WDIIH1A FU1, FU2, FU3, FU4, FU5, FU6, FU7, FU8, FU9, FU10, FU11, FU12, FU13, FU14, FU15, FU16 342A4908AFP1 FUSE 0.2A 250V TM LAG TR5 LITTELFUSE 3720200041, 37202000411 IS200WDIIH2A FU1, FU2, FU3, FU4, FU5, FU6, FU7, FU8, FU9, FU10, FU11, FU12, FU13, FU14, FU15, FU16 342A4908AFP1 FUSE 0.2A 250V TM LAG TR5 LITTELFUSE 3720200041, 37202000411 32 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Discrete I/O, Terminal Board Fuses (continued)

Board Fuse Designator GE Part # Fuse Rating MFR # IS200WPDFH1A FU1, FU2, FU3, FU4, FU5, FU6, FU7, FU8, FU9, FU10, FU11, FU12, FU13, FU14, FU15, FU16, FU17, FU18, FU19, FU20, FU21, FU22, FU23, FU24 259A9266P16 FUSE(SLO-B) 3.15A 250V LITTELFUSE 218 3.15 COOPER BUSSMANN GDC-3.15A IS200WPDFH2A FU1, FU2, FU3, FU4, FU5, FU6, FU7, FU8, FU9, FU10, FU11, FU12, FU13, FU14, FU15, FU16, FU17, FU18, FU19, FU20, FU21, FU22, FU23, FU24 259A9266P16 FUSE(SLO-B) 3.15A 250V LITTELFUSE 218 3.15 COOPER BUSSMANN GDC-3.15A Power Distribution, Terminal Board Fuses Board Fuse Designator GE Part # Fuse Rating MFR # IS200JPDAG1A FU1, FU2, FU3, FU4 323A2396P96 FUSE 15A LITTELFUSE 314015P COOPER BUSSMANN ABC-15 IS200JPDBG1A FU1, FU2, FU3, FU4, FU5, FU6, FU7, FU8 323A2396P250 FUSE 10A 250V SLOW BLOW LITTELFUSE 326010 COOPER BUSSMANN MDA-10 IS200JPDBG2A FU1, FU2, FU3, FU4, FU5, FU6, FU7, FU8 323A2396P250 FUSE 10A 250V SLOW BLOW LITTELFUSE 326010 COOPER BUSSMANN MDA-10 IS200JPDCG1A FU71, FU72, FU73, FU74, FU75, FU76,FU1R,FU1S, FU1T,FU2R,FU2S,FU2T 64G5005-010 FUSE, 10A, 500VAC/400VDC, TIME-LAG (SLO-BLOW) LITTELFUSE 0477010.MXP FU81, FU82, FU83, FU84, FU85, FU86 44A725207-011 FUSE, 3.15A,250V, FAST ACTING LITTELFUSE 217 3.15 FUAC1, FUAC2 342A4908ABP21 FUSE, 10A, 250V, TIME-LAG (SLO-BLOW) LITTELFUSE 218 010, 218010. HXP, 218010H IS200JPDDG1A FU1N, FU1P, FU2N, FU2P, FU3N, FU3P, FU4N, FU4P, FU5N, FU5P, FU6N, FU6P 323A2396P96 FUSE 15A LITTELFUSE 314015P COOPER BUSSMANN ABC-15 IS200JPDDG2A N/A FUSE 15A, 250VAC/125VDC, FAST ACTING N/A IS200JPDDG3A N/A FUSE 15A N/A IS200JPDDG4A 323A2396P68 FUSE 0.5A, 250VAC/125VDC, FAST ACTING LITTELFUSE 0314.500MXP COOPER BUSSMANN ABC-1/2 IS200JPDEG1A FU11, FU12, FU21, FU22, FU31, FU32 323A2396P20 FUSE 7 A LITTELFUSE 312007P COOPER BUSSMANN AGC-7 FUA1, FUA2, FUB1, FUB2, FUC1, FUC2 323A2396P96 FUSE 15A LITTELFUSE 314015P COOPER BUSSMANN ABC-15 Control System Overview GEH-6721_Vol_I_BP System Guide 33 Public Information

Power Distribution, Terminal Board Fuses (continued)

Board Fuse Designator GE Part # Fuse Rating MFR # IS200JPDFG1A FU1R, FU1S, FU1T, FU2R, FU2S, FU2T 323A2396P250 FUSE 10A 250V SLOW BLOW LITTELFUSE 326010 COOPER BUSSMANN MDA-10 FU71, FU72, FU73, FU74, FU75, FU76 323A2396P94 FUSE 5A LITTELFUSE 314005 COOPER BUSSMANN ABC-5 FU12, FU13 323A2396P98 FUSE 3A 250V ABC LITTELFUSE 314003 COOPER BUSSMANN ABC-3 FU81, FU82, FU83, FU84 323A2396P91 FUSE 12A 250V ABC LITTELFUSE 314012 COOPER BUSSMANN ABC-12 IS200JPDFG2A FU71, FU72, FU73, FU74, FU75, FU76, FU1R, FU1S, FU1T, FU2R, FU2S, FU2T 323A2396P250 FUSE 10A 250V SLOW BLOW LITTELFUSE 326010 COOPER BUSSMANN MDA-10 FU81, FU82, FU83, FU84 323A2396P91 FUSE 12A 250V ABC LITTELFUSE 314012 COOPER BUSSMANN ABC-12 FU12, FU13 323A2396P98 FUSE 3A 250V ABC LITTELFUSE 314003 COOPER BUSSMANN ABC-3 IS200JPDGH1A FU1, FU2, FU3, FU4, FU5, FU6, FU7, FU8 323A2396P250 FUSE 10A 250V SLOW BLOW LITTELFUSE 326010 COOPER BUSSMANN MDA-10 FU10, FU11, FU12, FU13, FU14, FU15, FU16, FU17, FU18, FU19, FU20, FU21, FU22, FU23 323A2396P96 FUSE 15A 3AB ABC FAST ACTING LITTELFUSE 314015P COOPER BUSSMANN ABC-15 IS200JPDGH2A FU1, FU2, FU3, FU4, FU5, FU6, FU7, FU8 323A2396P250 FUSE 10A 250V SLOW BLOW LITTELFUSE 326010 COOPER BUSSMANN MDA-10 FU10, FU11, FU12, FU13, FU14, FU15, FU16, FU17, FU18, FU19, FU20, FU21, FU22, FU23 323A2396P96 FUSE 15A 3AB ABC FAST ACTING LITTELFUSE 314015P COOPER BUSSMANN ABC-15 IS200JPDMG1A FU1, FU2, FU3, FU4, FU5, FU6, FU7, FU8, FU9, FU10, FU11, FU12 323A2396P250 FUSE 10A 250V SLOW BLOW LITTELFUSE 326010 COOPER BUSSMANN MDA-10 IS400JPDMG1A FU1, FU2, FU3, FU4, FU5, FU6, FU7, FU8, FU9, FU10, FU11, FU12 64G5002-001 FUSE 10A 250V SLOW BLOW LITTELFUSE 0326010.MXP, 326010HP COOPER BUSSMANN MDA-10-R, MDA-10BK-R IS200JPDAG2A FU1, FU2, FU3, FU4 EMPTY FUSE HOLDERS WITH BLACK CAPS ACCEPTING 5 X 20 mm (0.20 X 0.79 in) FUSES IS200JPDAG3A FU1, FU2, FU3, FU4 EMPTY FUSE HOLDERS WITH GREY CAPS ACCEPTING 31.75 X 6.35 mm (1.25 X 0.25 in) FUSES IS200JPDDG2A FU1N, FU1P, FU2N, FU2P, FU3N, FU3P, FU4N, FU4P, FU5N, FU5P, FU6N, FU6P EMPTY FUSE HOLDERS WITH BLACK CAPS ACCEPTING 5 X 20 mm (0.20 X 0.79 in) FUSES IS200JPDDG3A FU1N, FU1P, FU2N, FU2P, FU3N, FU3P, FU4N, FU4P, FU5N, FU5P, FU6N, FU6P EMPTY FUSE HOLDERS WITH GREY CAPS ACCEPTING 31.75 X 6.35 mm (1.25 X 0.25 in) FUSES 34 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Renewable Energy I/O, Terminal Board Fuses

Board Fuse Designator GE Part # Fuse Rating MFR # AEPCH1A FU1, FU2, FU3 323A2396P59 FUSE 4A 250V SLOW BLOW COOPER BUSSMANN MDL-4A LITTELFUSE 313004P AEPCH1B FU1, FU2, FU3 323A2396P59 FUSE 4A 250V SLOW BLOW COOPER BUSSMANN MDL-4A LITTELFUSE 313004P WETAH1A FU2 259A9266P16 FUSE(SLO-B) 3.15A 5X20MM 250V COOPER BUSSMANN GDC-3.15A LITTELFUSE 218 3.15 FU3, FU4,FU7, FU8 342A4908ABP21 FUSE 10.0A 250V 5X20MM LITTELFUSE 218 010, 218010.HXP, 218010H FU5 64G5005-009 FUSE, 6.3A, 250V, 5 X 20MM TIME-LAG (SLO-BLOW) COOPER BUSSMANN S506-6.3-R LITTELFUSE 021806.3MXP FU6 342A4908ABP24 FUSE 1.0A 250V 5X20MM COOPER BUSSMANN BK/S506-1-R LITTELFUSE 218001, 218001MXP, 218001P WEMAH1A FU1 342A4908ABP22 FUSE0.315A 250V 5X20MM LITTELFUSE 218.315, 218.315H, 218.315HXP FU2, FU3 259A9266P16 FUSE(SLO-B) 3.15A 5X20MM 250V COOPER BUSSMANN GDC-3.15A, LITTELFUSE 218 3.15 FU6 342A4908ABP24 FUSE 1.0A 250V 5X20MM COOPER BUSSMANN BK/S506-1-R LITTELFUSE 218001, 218001MXP, 218001P WEMAH2A FU1 342A4908ABP22 FUSE0.315A 250V 5X20MM LITTELFUSE 218.315, 218.315H, 218.315HXP FU2, FU3 259A9266P16 FUSE(SLO-B) 3.15A 5X20MM 250V COOPER BUSSMANN GDC-3.15A, 218 3.15 FU6 342A4908ABP24 FUSE 1.0A 250V 5X20MM COOPER BUSSMANN BK/S506-1-R LITTELFUSE 218001, 218001MXP, 218001P Control System Overview GEH-6721_Vol_I_BP System Guide 35 Public Information

The Mark VIe and Mark VIeS control systems are designed to operate on a flexible, modular selection of power sources. The

power distribution modules (PDM) support 115/230 Vac, 24 and 125 V dc power sources in many redundant combinations. The power applied is converted to 28 V dc for operation of the I/O packs, controllers, and switches. Note Refer to For more information on the IONet switches, refer to the Mark VIe and Mark VIeS Control Systems Volume II: System Guide for General-purpose Applications (GEH-6721_Vol_II), the chapter PDM Power Distribution Modules. The JPDS, JPDM, JPDG, or JPDC core power distribution board allows for the optional attachment of a PPDA I/O pack for system feedback. The PDM can be divided into two substantially different categories, the core distribution system, and the branch circuit elements. They serve as the primary power management for a cabinet or series of cabinets. The branch circuit elements take the core output and fan it into individual circuits for consumption in the cabinets. Branch circuits provide their own feedback mechanisms, which are not part of the feedback provided by the PPDA I/O pack. The wide variety of power distribution components available for use with the Mark VIe and Mark VIeS control systems allow for a flexible and scalable power distribution solution. 36 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

The Mark control platform provides scaleable levels of redundancy. The basic system is a single (simplex) controller with

simplex I/O and one network. The dual system has two controllers, singular or fanned TMR I/O and dual networks, which provides added reliability and online repair options. The TMR system has three controllers, singular or fanned TMR I/O, three networks, and state voting between controllers providing the maximum fault detection and availability. 1.6.1 Controller Redundancy Controller redundancy consists of the following: • Simplex controller • Dual controllers • Triple redundant controllers (TMR) 1.6.1.1 Simplex Controller The simplex control architecture contains one controller connected to an Ethernet interface through the Ethernet network (IONet). No redundancy is provided and no online repair of critical functions is available. Online replacement of non-critical I/O (that where the loss of the I/O does not stop the process) is possible. Each I/O pack delivers an input packet at the beginning of the frame on its primary network. The controller sees the inputs from the I/O modules, performs application code, and then delivers an output packet(s) for all I/O modules. The following diagram displays typical simplex controller architecture. Switch Controller R UDH I/O Modules IONet Simplex Mark VIe Control System Control System Overview GEH-6721_Vol_I_BP System Guide 37 Public Information

The dual control architecture contains two controllers, two IONets, and singular or fanned TMR I/O modules. The following

diagram displays a Mark VIe control system with a Dual redundancy configuration. Switches Controllers R S I/O Modules IONet IONet Legend UDH Dual Mark VIe Control System The dual control Mark VIe architecture reliability can be significantly better than the single controller. The network and controller components are redundant and can be repaired online. The I/O reliability can be mixed and matched to meet varying requirements. In a dual Mark VIe control system, both controllers receive inputs from the I/O modules on both networks and transmit outputs on their respective IONet continuously. When a controller or network component fails, the system continues operating. I/O packs receive inputs from both controllers, but prefer the designated controller. If the only packet received is from a non-designated controller, then the I/O pack will use that packet. Note With dual controllers, the level of I/O reliability can be varied to meet the application needs because not all I/O has to be dual redundant. The Mark VIe controllers listen for the data on both networks at power on. The channel that delivers the first valid packet becomes the preferred network. As long as the data arrives on that channel the controller uses this data. When the preferred channel does not deliver the data in a frame, the other channel becomes the preferred channel as long as valid data is supplied. This prevents a given controller from bouncing back and forth between two sources of data. This does mean that different controllers may have separate preferred sources of data but this can also happen if any component fails. The I/O modules listen for the data on both networks at power on. If the packet from the designated controller is received, that one is the preferred network. When the designated controller packet does not arrive in a given frame, the other channel is used as long as valid data is supplied. 38 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

In a dual control system, the application logic in each controller tries to produce the same results. After many iterations of

running the application, it is possible for the internal data values to differ due to mathematical round off, and different past history (power-up). To converge this data, the internal data (state) variables are taken from the designated controller and transmitted to the non-designated controller for its use. This is known as state exchange. State variables are any internal variables not immediately derived from input or control constants. Any variable that is used prior to being re-calculated is an internal state variable. This principle can be displayed in the following two equations: A = B+C C = 3 x D Assume B and D are inputs and A and C are intermediate values. Since C is used prior to being calculated, the value of C during the previous scan retains some state information. Therefore, C is a state variable that must be updated in the non-designated controller if both controllers are to remain synchronized. In the Mark VIe controller, Boolean state variables are updated on every control frame. The analog state variable updates are multiplexed. A subset of analog state variables is updated every control frame. The controller rolls through each subset until all state variables are transmitted. Control System Overview GEH-6721_Vol_I_BP System Guide 39 Public Information

Triple Modular Redundant (TMR) Controllers

The TMR control architecture contains three controllers, three IONets, and singular or fanned TMR I/O Modules. Reliability and availability are much better with TMR controllers than with dual controllers due to increased fault detection capability. In addition to all of the dual redundant features, the TMR controller provides three independent outputs to all TMR I/O modules and the state variables between controllers are voted. I/O Modules Switches Controllers R S T IONet IONet IONet Legend UDH TMR Mark VIe Control System Note The level of I/O reliability can be varied to meet the application needs because I/O redundancy can be simplex, dual, or TMR. In a TMR control system, all three controllers receive inputs from the I/O modules on all networks and transmit outputs on their respective IONet continuously. If a controller or network component fails, the system does not require fault detection or failover time to continue operating. All controllers transmit their copy of the state variables after the output packet has been transmitted. Each controller takes the three sets of state variables and votes the data to get the values for the next run cycle. 40 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

There are various options available for single and multiple packs and single and dual networks for I/O redundancy. The

following are options for TMR I/O modules: • Single Pack Dual Network I/O Module (SPDN) • Two Single Pack, Single Network (2SPSN) I/O Modules • Dual Pack, Dual Network (DPDN) I/O Module • Triple Pack, Dual Network (TPDN) I/O Module • Hot Backup I/O Module 1.6.2.1 Single Pack Dual Network I/O Module (SPDN) This configuration is typically used for non-critical single sensor I/O. A single sensor connects to a single set of acquisition electronics which is then connected to two networks. • Single data acquisition • Redundant network The I/O pack delivers input data on both networks at the beginning of the frame and receives output data from both controllers at the end of the frame. 1.6.2.2 Two Single Pack, Single Network (2SPSN) I/O Modules This configuration is typically used for inputs where there are multiple sensors monitoring the same process points. Two sensors are connected to two independent I/O modules. • Redundant sensors • Redundant data acquisition • Redundant network • Online repair Each I/O pack delivers input data on a separate network at the beginning of the frame and receives output data from separate controllers at the end of the frame. 1.6.2.3 Dual Pack, Dual Network (DPDN) I/O Module This is a special case for inputs only, using a dual pack, dual network module. A fanned input terminal board can be populated with two packs providing redundant data acquisition for a set of inputs. • Redundant data acquisition • Redundant network • Online repair Each I/O pack delivers input data on a separate network at the beginning of the frame. Control System Overview GEH-6721_Vol_I_BP System Guide 41 Public Information

Triple Pack, Dual Network (TPDN) I/O Module

This is a special case mainly intended for outputs, but also applies to inputs. The special output voting/driving features of the TMR I/O modules can be used in a dual control system. The inputs from these modules are voted in the controller. • Redundant data acquisition • Output voting in hardware • Redundant network • Online repair Two of the I/O packs are connected to separate networks delivering input data and receiving output data from separate controllers. The third I/O pack is connected to both networks. This pack delivers inputs on both networks and receives outputs from both controllers. 1.6.2.5 Hot Backup I/O Module This is a special case mainly intended for a small set of I/O packs used as a gateway to another network. In this configuration, there are dual I/O packs, dual network but only one I/O pack is communicating to the gateway network at one time, the other I/O pack operates in a backup mode. The inputs from active module are used in the controller. • Redundant data acquisition • Redundant network • Online repair The two I/O packs are both connected to both networks, but only communicates to the controller and the gateway network. If a failure occurs on the active I/O pack, the backup I/O pack becomes the active I/O pack, thus maintaining communication with the connected devices. 1.6.2.6 Triple Pack, Triple Network (TPTN) I/O Module For medium integrity applications with medium to high reliability sensors, one sensor can be fanned to three I/O packs. The special output voting/driving features of the TMR I/O modules can be used in a TMR control system. The inputs from these modules are voted in the controllers. A fanned input terminal board can be populated with three packs providing redundant data acquisition for a set of inputs. • Redundant data acquisition • Output voting in hardware • Redundant networks, packs, and controllers • Online repair Each of the I/O packs are connected to separate networks delivering input data and receiving output data from separate controllers. 42 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

All inputs are available to all three controllers, but there are several ways that the input data is handled. For inputs existing in

only one I/O module, all three controllers use the same value as common input without voting, as displayed in the table below. Inputs that appear in all three I/O channels may be voted to create a single input value. The triple inputs may come from three independent sensors. They can also be created from a single sensor by hardware fanning at the terminal board. Mark VIe Controller Redundancy Available IONet Topology Simplex One I/O pack with one IONet The number of IONets in a system equals the number of controllers. Dual One I/O pack with two IONets Two I/O packs with one IONet per pack Three I/O packs with one IONet to controller , one IONet to controller , and two IONets with one to controller and one to controller TMR Fanned – three packs, one IONet/pack with one terminal board Dedicated – three packs, one IONet/pack with three separate S-type terminal boards Simplex – One I/O pack, One IONet Dual – One I/O pack, Two IONets Dual – Two I/O Packs, One IONet Dual – Three I/O Packs with 1, 1, 2 IONets Control System Overview GEH-6721_Vol_I_BP System Guide 43 Public Information

TMR Fanned – Three I/O Packs with One IONet per I/O Pack

TMR Dedicated – Three simplex I/O modules with One IONet per I/O Pack For any of the above input configurations, multiple inputs can be used to provide application redundancy. For example, three Simplex inputs can be used and selected in application code to provide sensor redundancy. The Mark VIe control provides configuration capability for input selection and voting using a simple, highly reliable and efficient selection/voting/fault detection algorithm to reduce application configuration effort. This maximizes the reliability options for a given set of sensor inputs and provides output voting hardware compatibility. All applicable subsets of reliability options are available on a per terminal board basis for any given Mark VIe topology. For example, in a TMR controller, all simplex and dual option capabilities are also provided. While each IONet is associated with a specific controller that is responsible for transmitting outputs, all controllers see all IONets. The result is that for a simplex input the data is not only seen by the output owner of the IONet, it is seen in parallel by any other controllers. The benefit of this is that loss of a controller associated with a simplex input does NOT result in the loss of that data. The simplex data continues to arrive at other controllers in the system. A single input can be brought to the three controllers without any voting. This is used for non-critical, generic I/O, such as monitoring 0-20 mA inputs, contacts, thermocouples, and resistance temperature devices (RTD). This interconnection can also include the following gateway devices: CANbus, FOUNDATION Fieldbus®, Profibus, and Modbus. Single Input to Three Controllers, Not Voted One sensor can be fanned to three I/O boards as above for medium-integrity applications. This is used for sensors with medium-to-high reliability. Three such circuits are needed for three sensors. Typical inputs are 0-20 mA inputs, contacts, thermocouples, and RTDs. 44 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

One Sensor with Fanned Input and Software Voting

Three independent sensors can be brought into the controllers without voting to provide the individual sensor values to the application. Median values can be selected in the controller if required. This configuration, displayed in the following figure, is used for special applications only. Three Independent Sensors with Common Input, Not Voted Control System Overview GEH-6721_Vol_I_BP System Guide 45 Public Information

The following figure displays three sensors, each one fanned and then software implemented fault tolerance (SIFT) voted.

This provides a high reliability system for current and contact inputs, and temperature sensors. Three Sensors, Each One Fanned and Voted, for Medium-to-High Reliability Applications Highly reliable speed input applications are brought in as dedicated inputs and SIFT voted. The following figure displays this configuration. Inputs such as speed control and overspeed are not fanned so there is a complete separation of inputs with no hardware cross coupling which could propagate a failure. RTDs, thermocouples, contact inputs, and 0-20 mA inputs can also be configured this way. Three Sensors with Dedicated Inputs, Software Voted for High Reliability Applications 46 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

The system outputs are the portion of the calculated data transferred to the external hardware interfaces and then to the

various actuators controlling the process. TMR outputs are voted in the output voting hardware. Any system can output individual data through simplex hardware. The three voting controllers calculate TMR system outputs independently. Each controller sends the output to its associated I/O hardware (for example, the R controller sends output to the R I/O). The three independent outputs are then combined into a single output by a voting mechanism. Different data types require different methods of establishing the voted value. The outputs from the three controllers fall into three groups: • Outputs are driven as single ended non-redundant outputs from individual I/O networks • Outputs exist on all three I/O networks and are merged into a single output by the hardware • Outputs exist on all three I/O networks and are output separately to the controlled process. This process may contain external voting hardware. For normal relays, the three outputs feed a voting relay driver, which operates a single relay per channel. For critical protective signals, the three outputs drive three independent relays, with the relay contacts connected in the typical six-contact voting configuration. Relay Output Circuits for Protection For servo outputs, the three independent currents drive a three-coil servo actuator, which adds them by magnetic flux summation, as displayed in the following figure. Failure of a servo driver is sensed and a deactivating relay contact is closed to short the servo coil. Control System Overview GEH-6721_Vol_I_BP System Guide 47 Public Information

TMR Circuit to Combine Three Analog Currents into a Single Output

The following figure displays 0-20 mA outputs combined through a 2/3 current sharing circuit that allows the three outputs to be voted to one. Failure of a 0-20 mA output is sensed and a deactivating relay contact is opened. TMR Circuits for Voted 0-20 mA Outputs 48 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Reliability and Availability

1.7.1 Mean Time Between Failure (MTBF) MTBF is a basic measure of reliability for systems. It is the average failure free operating time, during a particular measurement period under stated conditions. A failure may or may not result in a problem with the overall system depending on any redundancy employed. MTBF is usually specified for each replaceable system component. MTBF roll up of the system components gives the equipment owner the knowledge needed to determine how long the equipment can be expected to operate without failure under given conditions. If it is essential that the equipment does not fail during operation, the owner can use this data to schedule maintenance/replacement of the equipment prior to failure. Alternately, redundant applications could be used preventing system problems when a failure occurs. MTBF data is also used to determine the weak links in a system. The system engineer provides contingency options for those weak links to obtain higher reliability. Users can access the MTBF ratings for their Mark VIeS Safety control system from the Exida, exSilentia tool. ➢➢ To access Mark VIeS Safety Controls IEC 61508 certificates and assessment reports 1. Go to the Exida website at http://www.exida.com/ and select Safety Automation Equipment List from the top tool bar. 2. Type vies in the Search field, and click Submit. 3. Select the company name, General Electric. 4. At the bottom of the page the user may select to view the following: • IEC 61508 certificate • Assessment Report Note A customer can contact Exida to order a copy of the exSILentia Integrated Safety Lifecycle Tool – Standard version. All versions of the Exida tool include the SILver module, Safety Integrity Level Verification, IEC 61508 compliant calculation engine. The SIL verification phase tool, SILver, is an analysis tool that uses Markov model calculation technique during all analyses. Purchasing the Exida tool gives the user access to the Exida Safety Equipment Reliability Handbook database. Control System Overview GEH-6721_Vol_I_BP System Guide 49 Public Information

Mean Time Between Forced Outage (MTBFO)

MTBFO is a measure of system availability, which includes the effects of any fault tolerance that may exist. This average time between failures causes the loss of system functions. The engineer must be very aware of MTBF and MTBFO when designing a reliable continuous system. To maximize the MTBFO, Mark VIe control systems undergo evaluation of all system component MTBF values. The effects of failures and contingency operation are then analyzed to maximizing MTBFO. To continue operation after a critical system component has failed, a control must have one or more backups in place (redundancy) to improve the MTBFO significantly above that of a simplex control. The simplest method is adding a second component that takes over the critical function when a fault is detected. The redundancy in the system can be either active or standby. The Mark VIe control uses active redundancy and has all components operating simultaneously. Standby redundancy activates backup systems after a failure is detected. Realizing the full benefits of redundancy, a system failure must be detectable for the control to bypass it. In a dual control, gross failures are readily detectable while subtle failures are more difficult to detect. TMR controls, using two out of three voting, are always able to select a valid value when presented with any single failure. Depending on the equipment, the time required to detect the fault and switch to the new component may be hours/minutes/seconds/milliseconds. In the case of fuel-flow control to a turbine, this is required to be done in milliseconds. When a redundant control bypasses a failure, it is required that the system annunciate the presence of the failure and that repairs be completed in a timely fashion. The term, mean time to repair (MTTR), refers to the time it takes to identify and repair a given failure. The Mark VIe control is designed to support a MTTR of four hours. This preserves the MTBFO benefits of redundancy resulting in unequaled system reliability. A control is used to run the system as well as detect system failures. In a dual control, configured for one out of two to run, it is often necessary to add dedicated tripping controls for each critical trip system. This is done to yield running reliability while maintaining required tripping reliability. ATMR control normally configures the control for two out of three selection. This yields high running and tripping reliability from the primary control. Additional dedicated tripping controls can be used to achieve even higher tripping reliability, but they must also be TMR to preserve running reliability. 50 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

A system offering redundancy can be less reliable than a non-redundant system. The system must be able to detect and

annunciate faults so it can be repaired before a forced outage occurs. Fault detection is needed to ensure a component or group of components are operating properly. Fault detection is achieved through one or more of the following methods. • Operator inspection of the process • Operator inspection of the equipment. • Special hardware circuits to monitor operation • Hardware and software watchdogs • Software logic • Software heartbeats Complex control systems have many potential failure points. This can be very costly and time consuming to create foolproof fault detection. Failure to control the outputs of a system is the most damaging. Fault detection must be determined as close to the output as possible to achieve the highest level of reliability. With the Mark VIe control configured using triple redundant controllers and I/O modules, a high level of detection and fault masking is provided by voting the outputs of all three controllers and monitoring discrepancies. All Mark VIe control systems benefit from the fault detection design of the I/O packs. Every pack includes function-specific fault detection methods attempting to confirm correct operation. This is made possible by the powerful local processing that is present in each input and output pack. Some examples of this include: • Analog to digital (A/D) converters are compared to a reference standard each conversion cycle. If the converted calibration input falls outside of acceptable ranges, the pack declares bad health. • Analog output 0-20 mA use a small current-sense resistor on the output terminal board. This output is read back through a separate A/D converter and compared to the commanded value. A difference between the commanded and actual value exceeding an acceptable level results in the output being declared in bad health. • Discrete input opto-isolators are periodically forced to an on condition, then forced off. This is done independently of the actual input and is fast enough not to interfere with the sequence of events (SOE) time capture. If any signal path is stuck and does not respond to the test command, the signal is declared in bad health. 1.7.4 Online Repair When a component failure is detected and healed in the control system on a critical path, a potential failure has been avoided. Subsequent actions can include: Option 1- Continue running until the backup component fails. Option 2 - Continue running until the system is brought down in a controlled manner to replace the failed component. Option 3 - Replace the component online. Option 1 is not recommended. A redundant system, where the MTTR is infinite can have a lower total reliability than a simplex system. Option 2 is a valid procedure for some processes needing predictable mission times. Many controlled processes cannot be easily scheduled for a shut down. Note As MTTR increases from the expected four hours to infinite, the system reliability can decline from significantly greater down to less than a simplex system reliability. Repair should be accomplished as soon as possible. Option 3 is required to get the maximum benefit from redundant systems with long mission times. In dual or triple redundant Mark VIe controller applications, the controllers and redundant I/O packs can be replaced online. Control System Overview GEH-6721_Vol_I_BP System Guide 51 Public Information

To ensure online repair capability, control systems must have their redundancy tested after installation and after any system

modifications. Refer to the requisition specific system application documentation/control specification (if available) for redundancy testing procedures. Forced Outage Probability versus Time (Conventional TMR) Forced Outage Probability versus Time (Mark VIe TMR) 52 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Although three controllers, R, S, and T, contain identical hardware and software, some of the functions performed are unique.

A single designated controller can perform the following functions: • Supply initialization data to the other two controllers at start-up • Keep the master time clock • Supply variable state information to the other controllers if one fails For the purposes of deciding which controller is to be the designated controller, each controller nominates itself on a weighting algorithm. The nominating values are voted among the controllers and the majority value is used. If there is a tie, or no majority, the priority is R, then S, and then T. If a designated controller is powered down and later powered up, the designated controller will move and not come back if all controllers are equal. This ensures that a toggling designated controller is not automatically reselected. Designated controller selection is based on: • Control state • UDH connectivity • IONet connectivity • NVRAM health 1.7.6 Communication Loss Each output pack monitors the IONet for valid commands from one or two controllers. In the event that a valid command is not received within an expected time the pack declares the communication as being lost. Upon loss of communication the pack action is configurable. The pack can continue to hold the last commanded value indefinitely or it can be commanded to go to a specified output state. The default action is to go to a power-down state, the same as if the power were removed from the pack. Note Refer to specific I/O pack documentation in Mark VIe and Mark VIeS Control Systems Volume II: System Guide for General-purpose Applications (GEH-6721_Vol_II). For critical loops, the default action is the only acceptable choice. The other options are provided for non-critical loops, where running liability may be enhanced by an alternate output. 1.7.7 State Exchange To keep multiple controllers in synchronization, the Mark VIe control efficiently exchanges the necessary state information through the IONet. State information includes calculated values such as timers, counters, integrators, and logic signals such as bi-stable relays, momentary logic with seal-in, and cross-linked relay circuits. State information is voted in TMR controllers and follows the designated controller in dual or faulted TMR systems. 1.7.8 Voting Voting in the Mark VIe control is separated into analog and logic voting. Additionally, fault detection mechanisms directly choose owned inputs and designated states. Control System Overview GEH-6721_Vol_I_BP System Guide 53 Public Information

Median Value Analog Voting

The analog signals are converted to a floating-point format by the I/O pack. The voting operation occurs in each of the three controller modules (R, S, and T). Each controller receives a copy of the data from the other two channels. For each voted data point, the controller has three values including its own. The median value voter selects the middle value of the three as the voter output. This is the most likely of the three values to be closest to the true value. Median Value Voting Examples with Normal and Bad Inputs 1.7.8.2 Two Out of Three Logic Voter Each of the controllers has three copies of the data for the logic voter. Voting is a simple logic process, inputting the three values and finding the two values that agree. 1.7.8.3 Disagreement Detector A disagreement detector continuously scans the input prevote input data sets and produces an alarm bit if a disagreement is detected between the three values. Any disagreement between the prevote logical signals generates an alarm. Failure of one of the three voted input circuits has no effect on the controlled process since the fault is masked by SIFT. Without a disagreement detector, a failure could go unnoticed until a second failure occurs. For analog signals, comparisons are made between the voted value and each of the three prevote values. The delta for each value is compared with a user programmable limit value. The limit can be set as required to avoid nuisance alarms, but give indication that one of the prevote values has moved out of normal range. Each controller is required to compare only its prevote value with the voted value; for example, R compares only the R prevote value with the voted value. Nominal, analog voting limits are set at a 5% adjustment range, but can be configured to any number for each analog input. 1.7.9 UDH Fault Tolerance — Command Action Using IONet connectivity, the controller copies command traffic from the UDH across all controllers. This provides fault tolerance for dual UDH networks. 54 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

The controller has a feature called Forced Variables. This allows the maintenance technician using application software to set

analog or logical variables to forced values. Variables remain at the forced value until unforced. Both compute and input processing respect forcing. Any applied forcing is preserved through power down or restart of the controller. Warning Logic Forcing is for offline software checkout and troubleshooting and should only be used in conjunction with proper lockout/tag out procedures. Forcing of protective functions is never permissible for an operating unit. 1.7.11 Peer I/O In addition to the data from the I/O modules, there is a class of data coming from other controllers in other cabinets connected through the UDH network. For integrated systems, this network provides a data path between multiple turbine controllers and possibly the controls for the generator, the exciter, or the HRSG/boiler. Selected signals from the controller database can be mapped into pages of peer outputs that are broadcast periodically on the UDH I/O to peer controllers. For TMR systems, the UDH communicator performs this action using the data from its internal database. In the event of a redundant UDH network failure, the controller will request data over the remaining network, the IONet. Control System Overview GEH-6721_Vol_I_BP System Guide 55 Public Information

Rate of Response

Mark VIe and Mark VIeS controllers can run at a variety of frame rates to meet the application needs of the industrial control solution. Control systems are tuned accordingly, based on a variety of factors including: complexity of controller application logic, processor type, and number of I/O and other interfaces used. The following diagram provides an example of typical processes that occur during a single controller frame in sequence. Time TMR set of Mark VIe Controllers Notes Assumes a Triple Modular Redundant (TMR) configuration, versus dual, or simplex Subsystem activities identified with a gray rectangle Activities that span multiple subsystems identified with a dashed TMR IONet TMR Mark VIe Control I/O Start of frame Transmission of outputs from controllers to I/O packs Input and state variables copied into variable space in prep for execution of control logic (application code) Control Logic Time to execute based on quantity and complexity of control blocks Synchronization of data between R, S, and T controllers using IONet Fresh state of outputs applied to terminal block screws, latency is dependent on circuit type I/O packs sample inputs, latency is dependent on circuit type Transmission of inputs from I/O packs to controllers End of frame Mark VIe Subsystem brown rectangle 56 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Component Part Numbers and Serial

Numbers/Barcodes 1.8.1 Common Terminology The following terms are used to identify Mark controls components: Backward Compatible A part is backward compatible when it can directly replace an earlier version of the part in all specified end-use applications without requiring any changes to the host system. Base Part Number The part number that is used to uniquely identify a part as a component in a higher-level assembly or to order a backward compatible replacement part. The base part number remains unchanged for all backward-compatible versions of the part. An example of a base part number is IS220PDIAH1B. Hardware Form The three characters following the module or board type in the part number that together with the Type uniquely defines a module or board in the ToolboxST* configuration tool. An example hardware form is H1B. Module or Board Type The four letter mnemonic taken from characters 6 – 9 of the full part number that is used to identify the function of the part. An example of a board type is Pack Discrete Input A (PDIA). Part Number The Part Number is the ANSI/EIA-649-A National Consensus Standard for Configuration Management, Product Identifier, that represents a specific version of a printed wiring assembly (PWA) and consists of all applicable fields specified in the table Product Identifier Fields Example. The Part Number identifies the baseline design of a product and is changed each time the design is changed. An example part number is IS220PDIAH1BA. Printed Circuit Board Assembly (PCBA) Indicates a single board. Printed Wiring Assembly (PWA) The ANSI/EIA-649-A National Consensus Standard for Configuration Management, Product Identifier, that indicates one or more PCBAs. Printed Wiring Board (PWB) The PC-T-50 Terms and Definitions for Interconnecting and Packaging Electronic Circuits that indicates a circuit board without any parts added. Serial Number/Barcode A unique number assigned to a component that indicates the date of manufacture and the supply vendor. Control System Overview GEH-6721_Vol_I_BP System Guide 57 Public Information

Part Number Convention

A part number consists of up to nine fields of information defined in the following tables. Product Identifier Fields Example Part Number Part Number Fields I II III IV V VI VII VIII IX IS200ABCDG1AAA IS 2 00 ABCD G 1 A A A Part Number Field Definitions Field Field Name Code Definition I Issuing organization code IS GE Energy Connections, Salem, Virginia, USA DS GE Drive Systems, Salem, Virginia, USA II Hazardous substance code 2 Not RoHS [3] compliant 4 RoHS [3] Compliant III Assembly level code [4] 00 PCBA 01 Coated PCBA [5] 05 PCBA designed as a component to be soldered into another PCBA 10 PCBA with an added manufacturing or assembly process step [6] 11 Coated PCBA with an added manufacturing or assembly process step [6] 15 PCBA with added application firmware and/or daughter-board(s) 20 1 or more PCBAs in an enclosure 21 1 or more PCBAs in an enclosure and all PCBAs are coated [5] 30 One or more PWAs on a base 31 One or more PWAs on a base and all PCBAs are coated [5] IV Board or Module Type 4 letter mnemonic that describes the function of the PWA V Technology code G Lead-through hole components only, no surface-mount technology H Contains surface-mount technology components S Functional safety system component [7] VI Assembly variant 1 numeric character, excluding 0 VII Backward compatibility version 1 alpha character, excluding: I, O, Q VIII PWA version Breadboard: BR + 1 numeric character, excluding 0 Prototype: PR + 1 numeric character, excluding 0 Production: 1 alpha character, excluding: I, O, Q IX Optional character Breadboard: Not used Prototype: Not used Production PWB version (assembly levels 00, 05 only): 1 alpha character, excluding: I, O, Q Marked for use in hazardous (classified) locations [8]: X 58 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Part Number Field Definitions (continued)

Field Field Name Code Definition Notes [3] Directive 2011/65/EU Restriction of Hazardous Substances in Electrical and Electronic Equipment [4] There are some legacy part numbers with assembly level code “020”. These identify assemblies of one or more PCBAs, and may not follow the current version rules. [5] Coated PWAs with assembly level codes 01, 21, and 31 are approved for use in environments where the overall corrosion potential due to airborne contaminants does not exceed severity level G3, as defined in ANSI/ISA-71.04-2013 Environmental Conditions for Process Measurement and Control Systems: Airborne Contaminants. [6] Certain legacy boards: IS210AEAAH*B, IS210AEABH*A, IS210AEACH1A, IS210AEBIH*B, IS210AEDBH*A, IS210AEPSG1A, IS210AEPSG*B were originally released as un-coated IS200 and coated IS210 parts, but the un-coated parts were never used in the host product. As these designs evolve, the IS200 level parts are being abandoned and the IS210 level parts are being maintained using the level 00 rules. [7] Each functional safety system PWA is certified to meet IEC 61508 and is equivalent in form, fit, and function to any PWA with a part number that differs only in the Technology Code (field 5). For example: IS400UCSBS1ABB is equivalent in form, fit, and function to IS400UCSBH1ABB, but is also certified to meet IEC 61508 Functional Safety of Electrical/Electronic/Programmable Electronic Safety-Related Systems. [8] NFPA 70 National Electrical Code, Article 500 Hazardous (Classified) Locations The following figures are examples of component labels identifying the part number. Example IONet Switch Label Control System Overview GEH-6721_Vol_I_BP System Guide 59 Public Information

UCPA part number

Example UCPA Controller Label 60 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Example UCSx Controller Label

Control System Overview GEH-6721_Vol_I_BP System Guide 61 Public Information

On the replacement, the revision letter

will be the same or a higher letter. Part number Example I/O Pack Label Internal GE employees and certain third-party parts suppliers can use the ENOVIA PLM tool to search for parts. The following Power Generation PLM web portal is available to assist with account registration and training on how to use the tool to search for parts: http://colab.ge.com/dashboard/canvas/v/518d03b3bf1d408e570001c9/home 62 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Serial Number/Barcode Convention

The serial number/barcode consists of seven characters composed from the following 31 permitted characters: 0 1 2 3 4 5 6 7 9 A C D E F G H J K L M N P R S T U V W X Y Z. It is composed of five coded groups that represent the component’s supply vendor, date of manufacture, and component count in the following format: VYMDS2S1S0. The following table describes what these group codes represent. Group Code Description V Vendor code (one-character) Contact your GE representative or GE Technical Support for further information on vendors and manufacturing locations. Y Year code (one character) Refer to the table Year Codes for permitted values. M Month code (one character) Refer to the table Month Codes for permitted values. D Day-of-month code (one character) Refer to the table Day-of-Month Codes for permitted values. S2S1S0 Serial number count code (three characters) The total count of unique serial numbers generated for a component is reset to zero each day at 12:00 AM, and then incremented by one for each unique serial number generated thereafter. This code limits the number of unique serial numbers to 313 (29,791) per day. Contact your GE representative or GE Technical Support for more information on this code. Serial Number Example Serial Number/Barcode Control System Overview GEH-6721_Vol_I_BP System Guide 63 Public Information

The following tables define the groups and characters in a serial number/barcode.

Year Codes Year Code 2005 0 2006 1 2007 2 2008 3 2009 4 2010 5 2011 6 2012 7 2013 9 2014 A 2015 C 2016 D 2017 E 2018 F 2019 G 2020 H 2021 J 2022 K 2023 L 2024 M 2025 N 2026 P 2027 R 2028 S 2029 T 2030 U 2031 V 2032 W 2033 X 2034 Y 2035 Z Month Codes Month Code January 0 February 1 March 2 April 3 May 4 June 5 July 6 August 7 September 9 October A November C December D 64 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Control System Overview

GEH-6721_Vol_I_BP System Guide 65 Public Information

GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I

Public Information

This chapter provides an introduction to the Mark VIeS Safety control, which is used

for functional safety loops to achieve SIL 2 and 3 capabilities. The Mark VIeS Safety control is used by operators knowledgeable in safety-instrumented system (SIS) applications to reduce risk in critical safety functions. Safety controllers and distributed I/O modules are programmed specifically for safety control use, and this specific control hardware has been IEC 61508 certified. Functional safety is concerned about the speed of the control system’s reaction to trip the system (energize to trip) or to provide an emergency shut-down (de-energize to trip) when a safety-critical event occurs. With this in mind, safety equipment is rated to meet safety integrity levels (SIL), which are achieved by analyzing probability of failure on demand. The Mark VIeS Safety control is a differentiator in the market because of its significant flexibility, easy of control logic development, and redundancy capabilities. Its safety I/O is very flexible in application, for example both analog inputs and outputs are available. The Mark VIeS Safety control is an engineered solution designed for the customers that work on our systems to help simplify and reduce maintenance costs. GE has engineered specific solutions for their internal turbine power plant applications, meeting high standards for reliability of function, and continues to invest in new SIL capabilities, for example GE Oil & Gas YSIL applications. The Mark VIeS control has just recently been made available for integration into other safety-critical applications outside of GE, for example emergency shutdown, burner management, and fire and gas-critical control applications. This solution reflects the experience of three plus decades, four generations, and over ten thousand installed triple-redundant digital turbine controls. Functional Safety GEH-6721_Vol_I_BP System Guide 67 Public Information

Safety Instrumented System (SIF)

While the Safety controller performs the logic solving tasks for the system, it also interfaces with the ToolboxST application for configuration, diagnostics, and changes to controller application logic (blocks). The ToolboxST application provides a means to lock or unlock the Safety controller for configuration and safety-instrumented function (SIF) programming. This allows the user to install a safety function, test it, and place the controller in Locked mode to perform safety control. Sensors Safety Controller Logic Solver Final Elements Safety Instrumented System Third-party devices WorkstationST OPC Server Locked/Unlocked mode Interfaces to Mark VIeS Safety controller must be strictly regulated to avoid interference with the operation of the system. Data exchange to the safety control must be restricted and only used when validated by the SIL application logic. The Mark VIeS Safety control was designed and certified to meet functional safety standards according to IEC 61508 Parts 1 through 3. It is certified for use in both high-and low-demand applications, uses redundant architecture configurations, and a hardware fault tolerance (HFT) of 1 to achieve safety integrity level (SIL) 3. The highest achievable SIL with an HFT of 0 is SIL 2. IEC 61508-4 definitions are as follows: Safety Freedom from unacceptable risk. Risk Combination of the probability of occurrence of harm and the severity of that harm. Functional Safety Part of the overall safety relating to the equipment under control (EUC) and the EUC control system that depends on the correct functioning of the Electrical/electronic/programmable electronic (E/E/PE) safety-related systems, other technology safety-related systems, and external risk reduction facilities. 68 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Functional safety relates to proper equipment operation, as well as other risk reduction facilities. Layers of protection (LOP)

concepts are as follows: Control and Monitoring Prevention Mitigation Plant Emergency Response BPCS Process Alarms Operator Supervision Mechanical Protection Alarms with Operator Action Safety Instrumented Systems Plant Evacuation Procedures Relief Valve Barrier Process The LOP around a process can be used to introduce risk reduction. Failure to carefully analyze the available LOP and the likelihood-consequence relationship of the risks involved with process control failure can lead to an expensive over-design of the system. The goal is to reduce the risk to a level that is as low as reasonably practicable (ALARP). Residual Risk Tolerable Risk Inherent Process Risk Necessary Risk Reduction Actual Risk Reduction Increasing Risk Residual Risk Tolerable Risk Inherent Process Risk Necessary Risk Reduction Actual Risk Reduction To achieve functional safety, it is necessary to analyze the potential hazards to personnel and property, including any environmental impact, that could occur when the control of equipment is lost. Requirements for safety function and integrity must be met to achieve functional safety. Safety function requirements describe what the safety function does and is derived from the hazard analysis. The safety integrity requirement is a quantitative measure of the likelihood that a safety function will perform its assigned task adequately. For safety functions to be effectively identified and implemented, the system as a whole must be considered. A primary parameter used in determining the risk reduction in a safety controller is the Average Probability of Failure on Demand (PFDavg). The inverse of the PFDavg is the Risk Reduction Factor (RRF). RR- F = 1 PFDavg Functional Safety GEH-6721_Vol_I_BP System Guide 69 Public Information

Modes of Operation

A demand mode is a mode of operation in which the safety function is called upon only on demand. IEC 61508-4 clause 3.5.12 defines two demand modes of operation: • Low demand mode • High demand or continuous mode Low demand describes the mode in which safety function demand occurs no greater than once per year. In high demand mode, the frequency of demand is greater than once per year. Continuous mode is regarded as very high demand and is associated with the safety function operating to keep the EUC within its normal safe state. The mode of operation is relevant when determining the target failure measure of a safety function. Low demand mode relates to the PFDavg whereas high demand or continuous demand mode relates to measuring the probability of failure per hour (PFH) (there are approximately 104 hours in a year). IEC 61508 defines a scale of four distinct levels of risk reduction referred to as the Safety Integrity Level (SIL). SIL PFDavg Low Demand Mode PFH High Demand Mode RRF 1 ≥10-2 to < 10-1 ≥10-6 to < 10-5 > 10 to ≤100 2 ≥10-3 to < 10-2 ≥10-7 to < 10-6 > 100 to ≤1,000 3 ≥10-4 to < 10-3 ≥10-8 to < 10-7 > 1,000 to ≤10,000 The SIL applies to all elements in the safety loop (sensors, logic solver, and final element) and their architecture. The loop must be considered in its entirety. 2.3 Safety System Redundancy Options Redundancy is a key feature in safety control system design that can enable on-line repair without interrupting the process. The unique Ethernet back-bone of the Mark VIeS Safety system enables several options for redundancy to achieve required SIL. This provides the safety control engineer unparalleled flexibility to meet the safety SIL requirements for each application in the most cost effective manner. 70 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Triple Modular Redundant (TMR)

The Mark VIeS Triple Modular Redundant (TMR) Control Modes can provide: • Two out of three (2oo3) voting − SIL 3 high/low demand for de-energize-to-trip or − SIL 2 low demand for energize-to-trip • Hardware fault tolerance (HFT): 1 • Degradation sequence: [2oo3] > [1oo2] > [Fail Safe] TMR Fanned Input Single discrete/ analog sensor is fanned through a common terminal board to three independent input packs, 2oo3 voting is done in the controller set. TMR Dedicated Input Three redundant discrete/analog sensors are wired to three independent input modules, 2oo3 voting is done in the controller set. Sensor A Sensor A1 Sensor A2 Sensor A3 Actuator TMR Outputs Voted on Terminal Board The three packs receive output commands from their associated controller, the common terminal board then performs 2oo3 voting on the outputs and controls the discrete actuator. 2oo3 Voting in Actuator TMR Outputs Voted in Actuator Three independent output modules receive the output command from their associated controller, then command the actuator, 2oo3 voting performed in the actuator. TMR Controllers Three Mark VIeS controllers work as a set synchronizing data every frame (sweep). Each controller receives inputs on all 3 I/O networks, and sends output commands on designated I/O network. TMR I/O Network Ethernet based TMR I/O network supports both centralized and distributed I/O modules. R S T Embedded Controller Gateway Embedded controller for communication interface, options: - OPC-UA server - Modbus slave Third Party Control System PC Based Gateway PC based communication interface, options : - OPC-DA server - OPC-UA server - Modbus master Functional Safety GEH-6721_Vol_I_BP System Guide 71 Public Information

The Mark VIeS Dual Control Modes can provide:

• One out of two (1oo2) voting, SIL 3 high/low demand for de-energize-to-trip • Two out of two (2oo2) voting, SIL 2 low demand for energize and de-energize-to-trip • Hardware fault tolerance (HFT): 1 TMR Fanned Input Single sensor is fanned through a common terminal board to three independent input packs, 2oo3 voting done in the controller set. Single Sensor Single sensor wired to a single input module with dual I/O network to controller set. Sensor A Sensor A Sensor A1 Sensor A2 Actuator TMR Outputs Voted on Terminal Board The three output packs receive an output command from designated controller, the common terminal board then performs 2oo3 voting and controls the actuator. Acutator 1oo2 De-energize to Trip in Output Modules Two independent output modules receive the output command from designated controller, combination of two creates 1oo2 de- energize to trip function across the two modules. Dual Controllers Dual Mark VIeS controllers work as a controller set synchronizing data every frame (sweep). Each controller receives inputs on both I/O networks, and sends output commands on designated I/O network. Dual I/O Network Ethernet based dual I/O network supports both centralized and distributed I/O modules. Dual Sensor Dual sensors wired to independent input modules with independent I/O networks to controller set. Third Party Control System R S PC Based Gateway PC based communication interface, options: - OPC-DA server - OPC-UA server - Modbus master Embedded Controller Gateway Embedded controller for communication interface, options: - OPC-UA server - Modbus slave 72 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

The Mark VIeS Simplex Control Mode is used for one out of one (1oo1), SIL 2 low demand for de-energize to trip

applications. R Simplex Controller Simplex Mark VIeS controller receives inputs and sends outputs on the one I/O network. I/O Network Ethernet based I/O network supports both centralized and distributed I/O modules. PC Based Gateway PC based communication interface, options: - OPC-DA server - OPC-UA server - Modbus master Third Party Control System Embedded Controller Gateway Embedded controller for communication interface, options: - OPC-UA server - Modbus slave Single Sensor Single sensor wired to a single input module with a simplex I/ O network to controller. Sensor A Sensor A1 Sensor A2 Dual Sensor Dual sensors wired to independent input modules with a simplex I/O network to controller. Actuator Simplex Output One output pack receives an output command from the controller. Functional Safety GEH-6721_Vol_I_BP System Guide 73 Public Information

GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I

Public Information

The integrated control system is based on a hierarchy of Ethernet networks, used to interconnect individual nodes or zones.

These networks separate the different communication traffic into layers according to their individual functions. This hierarchy extends from the I/O modules and controllers (providing real-time control of the process) to the HMIs, and out to facility-wide monitoring and external networks (industrial internet). Each network layer uses industry standard components and protocols to simplify integration between different platforms and improve overall reliability and maintenance. These layers are designated as IONet, Unit Control, Supervisory, and Enterprise in the following figure, which displays a simplified network hierarchy and is not representative of any specific installation. Ethernet Networks GEH-6721_Vol_I_BP System Guide 75 Public Information

Unit Control Layer

Supervisory Layer Mark VIeS Controller IONet Layer EX2100e Excitation Control LS2100e Static Starter Control Mark VIe Controller Mark VIe Controller Plant Data Highway (PDH) Unit Data Highway (UDH) Enterprise Layer GE Demilitarized Zone (DMZ) Electronic Security Perimeter (ESP) Mark Stat Wind Power Converter Mark VIe Controller R S T TMR I /O Modules Simplex I/O Modules SIL 3 Functional Safety Monitoring Data Highway Monitoring Layer On-Site Monitor (OSM) Remote Services Gateway (RSG) Mark VIe HMI Mark VIe Historian SecurityST Cyber Security Management System Printer Customer Network Simplified Network Hierarchy (switches not shown) 76 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

GE Large Industrial Plant Network Architecture

The current networking architecture for GE large industrial plants uses a mesh architecture design (also known as hub and spoke) with redundant network switches. This design enables flexibility for implementation of cyber security offerings, allowing secure access to unit control data from external customer and monitoring networks. Trunks from the root or hub switches to the edge or spoke switches shall be single-mode fiber for all new site installations. These trunks are configured to provide the UDH, PDH, Monitoring Data Highway (MDH), and can also provide other optional networks to further partition network access to specified unit control equipment and data. Network security can be implemented by adding an additional layer 3 security hardware infrastructure. Network traffic is then regulated by an additional series of routers, switches, and firewalls. The SecurityST* appliance can be installed to allow for tighter network security with or without the additional layer 3 security hardware by providing white listing and restricted access to network devices. Various options for existing sites are available to improve network security without having to relocate equipment or cable runs. In the following figure, both cyber security offerings (the layer 3 hardware and the SecurityST server) are displayed as a simplified example that is not representative of any specific installation. This industrial plant network architecture provides flexibility to cost for sites with various security compliance requirements. A qualified GE networking engineer can determine best fit options for particular customer facilities. Ethernet Networks GEH-6721_Vol_I_BP System Guide 77 Public Information

Catalyst 2960-S Series

25 26 27 28 M G MT B AS E T CONSOLE STCK SPED DPLX STAT MSTR RPS SYST MODE 13X 14X 23X 24X 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 1X 2X 11X 12X Catalyst 2960-S Series 25 26 27 28 M G M T B AS ET CONSOLE STCK SPED DPLX STAT MSTR RPS SYST MODE 13X 14X 23X 24X 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 1X 2X 11X 12X Root Switch MODE Catalyst 3750 -X Series BLAN K MODULE F N SYST CONS OLE XPS STAT SPEED DUPLX S-PWR M AST STACK Catalyst 3750-X Series 1 2 3 4 5 6 7 8 9 10 11 12 MODE Catalyst 3750 -X Series BLAN K MODULE F N SYST CONS OLE XPS STAT SPEED DUPLX S-PWR M AST STACK Catalyst 3750-X Series 1 2 3 4 5 6 7 8 9 10 11 12 ControlST Software Mark VIe TMR Controller Set Catalyst 2960-S Series 25 26 27 28 M G M T B A S E T CONSOLE STCK SPED DPLX STAT MSTR RPS SYST MODE 13 X 14 X 23X 24X 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 1X 2X 1 1X 1 2X XDH Switch Customer Enterprise Network GE Wide Area Network (WAN) Firewall Outside Plant Facility GE Demilitarized Zone (DMZ) To Remote Services Gateway (RSG), Onsite Monitor (OSM), Bently, etc. Layer 3 Security Video Terminal KVM DC2 VH1 DC1 AP1 AP2 AP3 Catalyst 2960-S Series 25 26 27 28 M G M T B AS E T CONSOLE STCK SPED DPLX STAT MSTR RPS SYST MODE 13X 14X 23X 24X 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 1X 2X 11X 12X Catalyst 2960-S Series 25 26 27 28 M G M T B AS ET CONSOLE STCK SPED DPLX STAT MSTR RPS SYST MODE 13X 14X 23X 24X 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 1X 2X 11X 12X Edge Switch Edge Switch Router Router Switch Connector Cable Plant Data Highway (PDH) Cable: Cat 5e Legend Unit Data Highway (UDH) Cable: Cat 5e Trunk Cable: Single Mode Fiber To additional security HW Cable: Cat 6 WorkstationST Historian HMI (hardened) NIDS SecurityST monitoring Cable: Cat 5e Monitoring Data Highway (MDH) Cable: Cat 5e Printer Remote Services Gateway (RSG) On-Site Monitor (OSM) HMI (hardened) Simplified Industrial Plant Network Architecture Note 1. Considerations for network upgrades are discussed the section, Network Retrofit Guidelines. 2. GE Wind Farms use a different network architecture. 3. GE M&C supplies the SecurityST appliance. 78 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

Mesh Architecture for UDH, PDH, MDH

The large industrial plant network architecture involves the use of root switches that communicate the Integrated Control System (ICS) virtual local area networks (VLANs) over Single Mode Fiber (SMF) trunks to edge switches. For redundancy, two or more identical switches are cabled together, enabling them to act as one switch with the port capacity of the combined switches. These cables are connected through special ports or plug sockets in the rear of the switches. Note Refer to NetworkST for Mark VIe Controls Application Guide (GEH-6840). Redundant switch cabling offers the following advantages: • Built-in failover and recovery (failback) in the event one of the switches fails. • An unconfigured switch can be used to replace a failed switch in pair. It will automatically upload the running configuration from the other switch in the group. • Enhanced network storm control protection • Network redundancy • Gigabyte uplink speeds (with SMF) • Enhanced Quality of Service (QoS) – ensures UDH (controller traffic) always has priority over PDH network traffic. • Cisco switches are 802.1x compliant. The current large industrial plant network topology uses pairs of edge switches and pairs of root switches to achieve redundancy. Devices with redundant communications (HMIs, controllers) have a network connection to each of the two switches in the pair. For Triple Modular Redundant (TMR) controllers, the R controller is connected to the first switch, and the S and T controllers are connected to the second switch. MODE Catalyst 3750 -X Ser ies BLANK MODULE FNSYST CONSOLEXPSSTATSPEED DUPLX S-PWR MASTSTACK Catalyst 3750 -X Ser ies 1 2 3 4 5 6 7 8 9 10 11 12 MODE Catalyst 3750 -X Ser ies BLANK MODULE FNSYST CONSOLEXPSSTATSPEED DUPLX S-PWR MASTSTACK Catalyst 3750 -X Ser ies 1 2 3 4 5 6 7 8 9 10 11 12 Root Switches Edge Switches Switch connector cable located rear Mark VIe HMIs, Historians Legend Catalyst 2960 -S Ser ies 25 26 27 28 M GM TBASET CONSOLE STCK SPED DPLX STAT MSTR RPS SYST MODE 13 X 14 X 23X 24X 13 14 15 16 17 1819 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 1X 2X 11 X 12 X Catalyst 2960 -S Ser ies 25 26 27 28 M GM TBASET CONSOLE STCK SPED DPLX STAT MSTR RPS SYST MODE 13 X 14 X 23X 24X 13 14 15 16 17 1819 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 1X 2X 11 X 12 X Catalyst 2960-S Series 25 26 27 28 M G M T B AS E T CONSOLE STCK SPED DPLX STAT MSTR RPS SYST MODE 13X 14X 23X 24X 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 1X 2X 11X 12X Catalyst 2960-S Series 25 26 27 28 M G M T B A SE T CONSOLE STCK SPED DPLX STAT MSTR RPS SYST MODE 13X 14X 23X 24X 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 1X 2X 11X 12X Edge Switches Mark VIe Controller Set Cat alyst 2960 -S Series 25 26 27 28 M GMT BASET CONSOLE STCK SPED DPLX STAT MSTR RPS SYST MODE 13 X 14 X 23 X 24 X 13 1415 16 17 18 19 2021 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 1X 2X 11 X 12 X Cat alyst 2960 -S Series 25 26 27 28 M GMT BASET CONSOLE STCK SPED DPLX STAT MSTR RPS SYST MODE 13 X 14 X 23 X 24 X 13 1415 16 17 18 19 2021 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 1X 2X 11 X 12 X Edge Switches Trunk provides all VLANs Cable: Single Mode Fiber Plant Data Highway (PDH) Cable: Cat5e Unit Data Highway (UDH) Cable: Cat5e Monitoring Data Highway (MDH) connects to an OSM or RSG Cable: Cat5e R S T Mesh Root and Edges The Root bridge switch is at the top of the network spanning tree. The edge switches (Ethernet connections) are then connected below the root switch. The most important element to this spanning tree is the root bridge placement. It should be the most centralized switch on the network (typically located in the control room). All data flow across the network is from the perspective of this switch. Root switches are configured to provide the control system VLANs and other optional networks over trunks to the edge switches. Ethernet Networks GEH-6721_Vol_I_BP System Guide 79 Public Information

Note Root and edge switches are not interchangeable.

Each edge switch connects back to a corresponding root bridge switch through the trunks. There is only one root bridge switch group in the system. Special configuration files define which switch acts as the root or edge. In addition, the edge switch ports are specially configured to provide the PDH, UDH, or MDH. Typically, ports 1–10 are PDH, ports 11–22 are UDH, and 23–24 are MDH (refer to the label on the switch itself for specific port details). Depending on specific site network requirements, the Cisco 2960S can be supplied as a root bridge switch on jobs with up to four units. Cisco 3750X switches serve as the root bridge at sites with more than four units. 3.2 IONet Layer IONet communication is internal between the controller(s) and the I/O modules through an unmanaged IONet switch. IONet redundancy can be one, two, or three networks, and is equal to the controller redundancy. The following cable color-coding for RJ-45 hoods is used to reduce the chance for cross connecting: Note On the UCSx controller from top to bottom, the networks are T, S, R. • Blue for IONet 3 (T network) • Black for IONet 2 (S network) • Red for IONet 1 (R network) Note Refer to the section Controller Redundancy for more information. The IONet provides direct communication between controllers and I/O modules. IONet EGD protocol (which is different than UDH EDG protocol) is used. The I/O modules send their inputs to the controllers and the controllers send their outputs to the I/O modules each frame, as displayed in the section Rate of Response. Examples of IONet traffic are as follows: • Status of control system input data from the I/O packs to the controller set • Status of control system output data from the controller set to the I/O packs • I/O pack configuration data from the ToolboxST application to the controller to the I/O packs • I/O pack health status data from the packs to the controller • Field device input data from the I/O pack to the controller Note The ESWx switch is used for IONet communication. The sharing of input data between two control sets (Shared IONet) on a single IONet is available for the following controllers: • One Mark VIeS Safety controller set and one Mark VIe controller set • One Mark Stat controller set and one Mark VIe controller set • Two Mark VIe controller sets Note A control set is the group of controllers (based on redundancy) with the set of owned I/O modules. From the ToolboxST System Editor Summary View, a control set displays as a single controller. 80 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

IONets are IEEE 802.3 100 Megabits full duplex Ethernet networks. All traffic on each IONet is deterministic UDP/IP based

packets. Each network (red, blue, black) is an independent IP subnet. The IEEE 1588 standard for precision clock synchronization protocol is used to synchronize frame and time between the controllers, and the I/O modules on the IONet. This synchronization provides a high level of traffic flow control on the networks. The following figure display maximum IONet cable lengths. 100FX Fiber Multi mode (MMF): 2000 m (6600 ft) Single mode (SMF): 15km (9.32 miles) Controller Cat 5e (copper) 100m (328 ft) Cat 5e (copper ) 100m (328 ft) Copper or Fiber depending on distance required field wiring Field device Cat 5e (copper) 100m (328 ft) IONet Maximum Distances Item IONet Specification IEEE specification 802.3u Wire speed 100 Mbps Cable types 100Base-TX: UTP Cat 5e 100Base-FX: MMF or SMF Maximum taps per segment 2 Maximum packets per network 199 Maximum number of switches 5 Topology Star For the control system IONet topologies, the following rules apply for deploying SMF systems: • No more than five switches can be placed in series between controller and remote I/O module. • The topology should be kept as flat and balanced as possible (star topology). • Use the GE ESWA or ESWB switch with additional IR SFP single-mode transceiver for SFP1 and SFP2. − GE part # 65G2100-009 for single-mode fiber distances up to 2 km − GE part # 65G2100-008 for single-mode fiber distances up to 15 km Caution Use of any other switch in this application may cause miss operation and/or damage to the associated equipment. Ethernet Networks GEH-6721_Vol_I_BP System Guide 81 Public Information

IONet switches are unmanaged, fully switched, and full-duplex to prevent collisions. They provide data buffering and flow

control during the critical input scan. Only industrial grade switches that meet the codes, standards, performance, and environmental criteria for industrial applications are used for the IONet. GE industrial Ethernet 10/100 IONet switches (ESWA and ESWB) have an operating temperature of -40 to 70 °C (-40 to 158 °F), have provisions for redundant 18 to 36 V dc power sources (200/400 mA), and can be DIN-rail mounted. The switches also provide LEDs to indicate the status of the IONet link, speed, activity, and duplex. 16-port ESWB IONet Switch Caution Use only GE-approved Ethernet switches in all control system I/O networks. Unsupported switches can prevent I/O modules from receiving controller outputs. Approved IONet Switches Part # Description IS420ESWAH1A 8 ports 10/100BASE-TX + 1 port 100BASE-FX LC-type connection IS420ESWAH2A 8 ports 10/100BASE-TX + 2 ports 100BASE-FX LC-type connection IS420ESWAH3A 8 ports 10/100BASE-TX IS420ESWAH4A 8 ports 10/100BASE-TX + 1 port 100BASE-LX10 LC-type connection IS420ESWAH5A 8 ports 10/100BASE-TX + 2 ports 100BASE-LX10 LC-type connection IS420ESWBH1A 16 ports 10/100BASE-TX + 1 port 100BASE-FX LC-type connection IS420ESWBH2A 16 ports 10/100BASE-TX + 2 ports 100BASE-FX LC-type connection IS420ESWBH3A 16 ports 10/100BASE-TX IS420ESWBH4A 16 ports 10/100BASE-TX + 1 port 100BASE-LX10 LC-type connection IS420ESWBH5A 16 ports 10/100BASE-TX + 2 ports 100BASE-LX10 LC-type connection Part # Description 336A4940DNP508TX 8 copper ports 336A4940DNP516TX 16 copper ports 336A4940DNP509FX 8 copper ports and 1 fiber port 336A4940DNP517FX 16 copper ports and 1 fiber port 336A4940DNP508FXE2 6 copper ports and 2 fiber ports (single mode) 336A4940JEP001 Installed within the 1.x ESS wind turbine hub 336A4940JEP002 Installed within the 1.x wind turbine top box 336A4940JEP003 Installed within the 1.x wind turbine Down Tower Assembly (DTA) 336A4940JEP004 Installed within the 2.x and 1.x non-ESS wind turbine hub 82 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

IONet Switch Guidelines

IONet is presently recommended to pass through a maximum of five switches in series when traveling from an I/O pack to a main controller for the following reasons: • IONet switches are not managed switches. • Every Ethernet switch introduces latency into the transmission of Ethernet packets. • Each controller frame allocates a period of time to service I/O data. Mark VIe Controller IONet Switch Communication path between I /O packs and controller, IONet switches A-B A B C D E Communication path between I /O packs and controller, IONet switches A-B-C Communication path between I /O packs and controller, IONet switches A-B-C-D Communication path between I /O packs and controller, IONet switches A-B-C-D-E Note: Maximum of 5 IONet switches that Ethernet packets pass through between I/O pack and controller Five Maximum IONet Switches in Series Between Controller and I/O Pack Ethernet Networks GEH-6721_Vol_I_BP System Guide 83 Public Information

I/O Pack Ethernet Addressing

On the IONet, I/O packs are assigned IP addresses through the DHCP servers in the controllers. The Host ID presented to the DHCP server is based on the board type and serial number information stored on a serial EEPROM located on the terminal board. Since the Host ID is part of the terminal board, the I/O pack can be replaced without having to update the ToolboxST application or controller communication IDs. Note When a terminal board is replaced, the user must associate the new Host ID to the configured device. The ToolboxST application presents a list of unrecognized devices that have requested IP addresses to simplify this process. IONets are Class C networks. Each is an independent network with different subnet addresses. The IONet IP host addresses for the controllers are fixed. The IP addresses of the I/O packs are assigned by the ToolboxST application, and the controller automatically distributes the addresses to the I/O packs through a standard Dynamic Host Configuration Protocol (DHCP) server in the controllers. 84 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

The Shared IONet function (with ControlST* V04.06 or higher) enables the sharing of Mark VIeS Safety inputs or Mark Stat

Wind Converter inputs with another basic process Mark VIe controller set, saving the cost of redundant sensors and I/O. Specific configurations supported include: • One Mark VIeS Safety controller set and one Mark VIe controller set • Two Mark VIe controller sets • One Mark Stat Wind power conversion controller set and one Mark VIe controller set Note The Mark VIe UCPA controller platform does not support Shared IONet. R S T R S T Safety Inputs Field devices for functional safety loop Mark VIeS controller set owns the safety I/O modules (for SIL rating, configuration, and diagnostic reporting). Safety I/O modules Basic process I/O modules Mark VIe controller set receives the inputs from safety I/O modules (data from safety loop field devices). One TMR redundant IONet Shared IONet Example The owner controller allows for the configuration of the owned I/O modules, writes outputs, reads SOEs, and provides diagnostic information. Owned I/O modules are attached to their owner controller that can configure and write to them, and obtain their IP addresses from their owner controller. Outputs from controllers are received by their owned I/O modules (not shared I/O modules). Note Refer to Mark Controllers Shared IONet User Guide (GEH-6812) for more information. A shared I/O module sends field device inputs to both its owner controller and to the consumer controller. The consumer controller receives the field device inputs from the shared I/O modules that are owned by the other owner controller. Configuration of the control sets is managed with the ToolboxST application. The computer with the ToolboxST application communicates with the I/O devices through a software gateway function residing in the controllers. Ethernet Networks GEH-6721_Vol_I_BP System Guide 85 Public Information

Unit Control Layer

The Unit Control layer or Unit Data Highway (UDH) provides the network connections that support continuous operation of the process equipment, including controller sets (general-purpose, safety loops, turbine-specific, static starter, exciter) and HMIs. The UDH is an Ethernet-based network that provides direct or broadcast peer-to-peer communications between a controller set and an operator/maintenance interface. The controllers operate at a fundamental rate called the frame rate, which is configurable, and is dependant on the controller processor type, the amount of application code being run, and other loads. Mark VIe controllers and HMIs use the EGD protocol to exchange real-time data, which on the UDH is based on UDP/IP (for data exchange) and HTTP (for configuration of pages). In addition, SDI protocol is used by the ToolboxST application to download to the controller over the UDH. Alarms and capture buffer uploads (that feed trip logs) are also through the SDI protocol. Note Current controls systems network architecture has UDH, PDH, and MDH connections on a common set of network switches and media trunks. The UDH connections to the controllers and HMIs are unshielded twisted pair (UTP) Cat 5e from edge switches. This redundant mesh architecture allows network connectivity even if one cable or switch is faulty. Redundant networks still comprise one logical network. The following figure displays the UDH network with connections to the controllers and HMIs. Mark VIe Controller Set Mark VIeS Controller EX2100e Excitation Control LS2100e Static Starter Control Mark VIe Controller Mark VIe Controller Unit Data Highway (UDH) Mark Stat Wind Power Converter Mark VIe Controller R S T SIL 3 Functional Safety SecurityST Cyber Security Management System PDH PDH PDH Mark VIe HMI Mark VIe Historian Unit Data Highway Example 86 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

UDH Communicator in a Redundant Controller Set

In dual or TMR Mark VIe controller sets, a single controller is designated to transmit real-time and alarm data for the set; this is the UDH Communicator. This data includes both control signals (EGD) and alarms (SDI). Since each controller has an independent, physical connection to the UDH, if a UDH network fault occurs where one controller becomes isolated from its companion controllers, the isolated controllers assumes the role of UDH communicator for that network fragment. For this reason, a controller set has only one designated controller, while there could be multiple UDH communicators. The designated controller is always a UDH communicator. Note UDH command data is replicated to redundant controllers by the UDH Communicator, allowing for synchronization across the redundant controller set. When a controller does not receive external EGD data from its UDH connection, it may request that the data be forwarded across the IONet from another UDH communicator. One or more communicators supply the data, and the requesting controller uses the last data set received. Only the external EGD data used in sequencing by the controllers is forwarded in this manner. 3.3.2 UDH Network Specifications Item Description Type of Network Ethernet, full duplex, in a single or redundant star configuration Media and Distance Ethernet 100Base-TX for switch to controller/device connections. The cable is 22 to 26 AWG unshielded twisted pair; category 5e EIA/TIA 568 A/B. Distance is up to 100 m. Ethernet 100Base-FX with fiber-optic cable optional for distances up to 2 km (1.24 mi). Number of Nodes At least 25 nodes, given a 25 Hz data rate. Other configurations may be available. Type of Nodes Supported Controllers, PLCs, operator interfaces, and engineering workstations Protocol EGD, based on UDP/IP Message Integrity 32-bit CRC appended to each Ethernet packet plus integrity checks built into UDP and EGD Time Sync. Methods Network time protocol (NTP), accuracy ±1 ms. 3.3.3 Control System Devices on the UDH 3.3.3.1 Mark VIe Controllers The Mark VIe controllers are applied in a wide variety of industrial control applications. The Mark VIeS Safety controller is used for safety-critical SIL applications. The Mark VIe UCPA platform is a lower cost, smaller footprint controller with integral I/O and limited expansion I/O capability. The same ToolboxST application is used for configuration of the Mark VIe controller product line. For more information, refer to Mark VIe and Mark VIeS Control Systems Volume II: System Guide for General-purpose Applications (GEH-6721_Vol_II), the chapter Controllers. The EX2100e excitation controller supplies dc power to the field of the synchronous generator, and controls the generator ac terminal voltage and/or the reactive volt-amperes by means of the field current. The excitation control system is supplied in NEMA 1 freestanding floor-mounted indoor type metal cabinets. The cabinet lineup consists of several cabinets bolted together. Note Refer to EX2100e Excitation Control User Guide (GEH-6781) for further details. Ethernet Networks GEH-6721_Vol_I_BP System Guide 87 Public Information

The LS2100e Static Starter controller is used to start a gas turbine by running the generator as a starting motor. The Static

Starter control, the Mark VIe control, and the excitation control system form an integrated static start system. The Mark VIe control supplies the run, torque, and speed setpoint signals to the Static Starter control, which operates in a closed loop control mode to supply variable frequency power to the generator stator. The excitation control system is controlled by the Static Starter control to regulate the field current during startup. Note The Static Starter control cabinet is a ventilated NEMA 1 freestanding enclosure made of 12-gauge sheet steel on a rigid steel frame designed for indoor mounting. The LS2100e Static Starter control is an adjustable speed ac drive system specifically designed to start a gas turbine generator set. By operating the generator as a synchronous motor, the static starter accelerates the turbine set according to a specific speed profile that provides optimum starting conditions for the gas turbine. The LS2100e control eliminates the need for separate starting hardware, such as an electric motor or diesel engine, torque converters, and associated auxiliary equipment, thus opening up critical space around the turbine base. Note Refer to LS2100e Static Starter Control User Guide (GEH-6798). The Mark Stat controller contains specialized firmware and application to control a GE multi-megawatt wind turbine power conversion system. 3.3.3.2 Human-machine Interface The Human-machine Interface (HMI) is the main operator interface to the Mark VIe control system. Current Mark VIe HMIs are desktop computers running the Windows® 7 operating system with multiple communication drivers for the redundant data highways, WorkstationST* and ToolboxST applications, and the CIMPLICITYAdvanced Viewer for the Graphical User Interface (GUI). The operator initiates commands from the real-time graphic displays, and views real-time process data and alarms. Detailed I/O diagnostics and system configuration is accomplished from the ToolboxST applications. Note HMIs typically connect to both PDH and UDH networks. The WorkstationST server is the hub of the system, channeling data between the UDH and the PDH, and providing data support and system management. The server also has the responsibility for device communication for both internal and external data interchanges. WorkstationST servers collect data on the UDH, and use the PDH to communicate with HMI viewers. Configuration servers, Historian servers, and Alarm servers are used for large system scaling. Multiple servers can be used to provide redundancy so that communication with the viewers continues even if one server fails. Note The HMI can be configured as a server or viewer, containing tools and utility programs. 88 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

The Mark VIe Historian computer runs ControlST software including Historian reports, the WorkstationST application, and

Trender, and can be configured for PI or Proficy data exchange to an external database server. The Historian is a data archival system based on client-server technology, used for data collection, storage, and display of process data. Flexible tools enable the operator to quickly generate custom trends and reports from the archived process data. The Historian combines high-resolution digital event data from the Mark VIe controllers with process analog data, creating a sophisticated tool for investigating cause-effect relationships. The Historian receives data from the controllers over the UDH. The HMIs and other operator interface devices communicate to the Historian through the PDH. Network technology provided by the Windows operating system allows interaction from network computers, including query and view capabilities, using the Historian Client Tool Set. The interface options include the ability to export data into spreadsheet applications. 3.3.3.4 Power Conversion Controllers GE Brilliance* solar inverter and legacy wind power conversion controllers can reside on the integrated control system UDH, and are configured with a common ToolboxST application. 3.3.4 Control Data Highway (CDH) A second UDH or redundant Ethernet Communication known as the Control Data Highway (CDH) allows two separate controllers to communicate with each other. The second CDH Ethernet can be added to a control system currently using the other UDH Ethernet port. The following table displays requirements for hardware setup. Note To configure a CDH, refer to ToolboxST User Guide for Mark Controls Platform (GEH-6700 or GEH-6703), the section Networks. CDH Hardware Setup First Controller Second Controller Ethernet Connection Simplex Simplex Each controller connects though the second Ethernet port using a single cross-over category 5 network cable. Simplex Dual The simplex controller connects to the second Ethernet ports of both the and controllers of the dual system using a category 5 network cable through a network switch. Simplex TMR The simplex controller connects to the second Ethernet ports of , , and controllers of the TMR system using a category 5 network cable through a network switch. Dual Dual The and controllers of each system connect using a category 5 network cable through a network switch. Dual TMR The and controllers of the dual system connect to the , , and controllers of the TMR system using a category 5 network cable through a network switch. TMR TMR The , , and controllers of each system connect using a category 5 network cable through a network switch. With the TMR and TMR configuration, the customer does not have to use the network if all EGD exchanges run at frame rate. Ethernet Networks GEH-6721_Vol_I_BP System Guide 89 Public Information

Catalyst 2960-S Series

25 26 27 28 M G M T B A S ET CONSOLE S TCK S PE D D PLX S TAT MSTR R PS S YS T MODE 13X 14X 23X 24X 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 1X 2X 11X 12X Catalyst 2960-S Series 25 26 27 28 M G M T BA S E T CONSOLE S TCK S PE D D PLX S TAT MSTR R PS S YS T MODE 13X 14X 23X 24X 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 1X 2X 11X 12X Controller R Controller S Controller T 2960S Switch Control Panel 1 Control Panel 2 PAIC PSVO ENET2    GE Unmanaged Switch Field Device Output Catalyst 2960-S Series 25 26 27 28 M G M T B A S ET CONSOLE STCK SPE D DPLX STAT MSTR R PS SYS T MODE 13X 14X 23X 24X 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 1X 2X 11X 12X Catalyst 2960-S Series 25 26 27 28 M G M T BA S E T CONSOLE STCK SPE D DPLX STAT MSTR R PS SYS T MODE 13X 14X 23X 24X 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 1X 2X 11X 12X Controller R Controller S Controller T Input 2960S Switch CDH Application Example Control Data Highway (CDH) Cable: Cat 5e UTP Legend Unit Data Highway (UDH) Cable: Cat 5e UTP IONet Cables: Cat 5e UTP IONet Cable: SMF or MMF Field Device GE Unmanaged Switch 90 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

The Supervisory layer contains the Plant Data Highway (PDH), which connects to WorkstationST servers, Alarm Viewers,

printers, historians, and other HMIs. Additional cyber security management equipment can also reside on the PDH. The PDH has no direct connection to the Mark VIe controllers, which communicate over the UDH. The PDH network is used to further partition equipment and to restrict access or prevent disruptions to the Mark VIe controllers (which are busy broadcasting data across the UDH). The PDH should be used to copy or transfer large files from HMI to HMI (for example, CIMPLICITY projects). PDH uses redundant cables to form one single logical network, and the mesh architecture is identical to the UDH. The hardware consists of edge Ethernet switches with single-mode fiber-optic trunks connected to root switches, then standard Cat 5e outputs to HMIs and other devices. Redundant Ethernet switches and cables prevent complete network failure if a single component fails. The PDH and the UDH are physically the same network of switches, but use different ports for the particular data highway. Plant Data Highway (PDH) UDH UDH UDH SecurityST Cyber Security Management System Printer Mark VIe HMI Mark VIe Historian Supervisory Layer Example Ethernet Networks GEH-6721_Vol_I_BP System Guide 91 Public Information

PDH Network Features

Feature Description Type of Network IEEE 802.3 Ethernet in a mesh topology Speed 100 megabit per second or with 1000 megabit per second trunks interconnecting switches Media and Distance Ethernet 100Base-TX is used for switch to controller/device connections. Cable is CAT 5e compliant. Distance is up to 100 m (328 ft). * Fiber-optic connections, Ethernet 100FX, 1000SX, 1000 LX are used for distances of 2 km (1.24 mi), 550 m (1804.46 ft), and 5 km (3.11 mi), respectively. Number of Nodes Up to 1024 nodes supported Protocols Ethernet-compatible protocol, typically TCP/IP-based. Use GSM, OPC UA, or Modbus over Ethernet for external communications. Message Integrity 32-bit cyclic redundancy code (CRC) appended to each Ethernet packet plus additional checks in protocol used. External Interfaces Various third-party interfaces are available; GSM, OPC UA, and Modbus are the most common. * Fiber-optic cable provides the best signal quality, completely free of electromagnetic interference (EMI) and radio frequency interference (RFI). Large point-to-point distances are possible, and since the cable does not carry electrical charges, ground potential problems are eliminated. 3.5 Monitoring Layer The monitoring data highway (MDH) is used to further partition the flow of data to individual assets, and can include connection to GE Monitoring and Diagnostic (M&D) equipment: the On-Site Monitor (OSM) or Remote Services Gateway (RSG). The data that is allowed to travel over the MDH is managed by two specially configured Cisco 2901 routers. The same mesh architecture and trunks provide the MDH from the root to edge switches, then from special configured ports on the edge switches to the OSM or RSG. Other devices may also be included on the MDH to meet customer requirements. Connectivity to the RSG and OSM is designed during the plant requisition phase, so the MDH is not the only available implementation of GE M&D equipment. Note Refer to the figure Simplified Network Hierarchy. 92 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

The Enterprise layer allows access to specific control system data or communication sources for facility-wide or group asset

management systems. The Enterprise layer can include the following features: • Additional firewalls, routers, and security features • Interface to customer network • GE Demilitarized Zone (DMZ) for hosting GE assets to be accessed external from customer site facility • Interface to other GE Wide Area Network (WAN), Atlanta Data Higway (ADH) for GE Monitoring and Diagnostics (M&D) services The Industrial Internet Gateway (IIG) option consists of a firewall appliance that is inserted as a barrier between the ICS VLAN and any other external devices. The firewall establishes security regions, or zones, as defined in the IEC standard 62443 or ISA 99. Equipment is allocated to each zone based on their function and relative security risk to the Mark VIe control system. For diagnostic or analysis purposes, access to specifically tagged control system data or communications can be allowed from outside the plant. Since any outside communications represent a significant risk to the integrity and security of the control system, establishing a DMZ that terminates the outside networks and then only allows specific authenticated traffic to flow from the DMZ to specific hosts behind the DMZ is recommended. GE demilitarized zone (DMZ) Customer Enterprise Network GE Wide Area Network (WAN) to ADH Firewall Outside Plant Facility Virtual local area networks (VLANs) Mark VIe Integrated Control System (ICS) Enterprise Layer Example (does not represent an actual installation) The IIG establishes four interfaces to connect from the firewall: Customer, ADH, DMZ, and ICS VLAN. The Customer interface typically connects to an additional upstream router or firewall provided by the customer. The ADH is used by GE M&D to provide remote services for the customer, for example analytics or troubleshooting. The DMZ has a rule set or policy that is implemented by GE to enable remote access to key resources. These resources are able to collect specifically configured control system data or perform specifically configured control system functions. The ICS VLAN connects from the IIG firewall to a switch that terminates at two routers and then into the root switch and on to the edge switch. Refer to the section Mesh Architecture for more information. Ethernet Networks GEH-6721_Vol_I_BP System Guide 93 Public Information

Ethernet Cabling for Monitoring, Supervisory, and

Unit Control Layers 3.7.1 Single-mode Fiber Note Trunks tie edge switches to the root switch. For new sites, single-mode fiber-optic (SMF) cables are installed for all trunks. The main advantages of fiber-optic transmission are as follows: Note For more information, refer to Fiber-optic Cable and Patch Panel Selection (GHT-200001). • Fiber segments can be longer than copper because the signal attenuation per foot is less. • In high-lightning areas, copper cable can pick up currents, which can damage the communications electronics. Since the glass fiber does not conduct electricity, the use of fiber-optic segments avoids pickup and reduces lightning-caused outages. • Grounding problems are avoided with optical cable. The ground potential can rise when there is a ground fault on transmission lines, caused by currents coming back to the generator neutral point, or lightning. • Optical cable can be routed through a switchyard or other electrically noisy area and not pick up any interference. This can shorten the required runs and simplify the installation. • Fiber-optic connections normally have higher signal levels and decreased chances of packet discard from noise corruption. Typical differences in error rate is 10000 lower for fiber-optic cables. • The cost per connection for fiber may now be less than copper cables. Large, multifiber trunk cables contain many fibers, so cost per foot for each connection may actually cost less than multiple copper cables. • Fiber-optic cable with proper jacket materials can be run buried in trays or in conduit. • High-quality fiber-cable is light, tough, and easily pulled. With careful installation, it can last the life of the plant. 3.7.1.1 SMF Specifications • Single-mode fiber-optic cables are connected from the root switch group to the edge switch group, providing redundancy. Refer to the figure, Mesh Root and Edges. • SMF cable lengths are less than or equal to 15 km (9.32 mi). • SMF cables must be terminated and/or spliced by a certified fiber-optic cable installer. SMF cables cannot be terminated and/or spliced by requisition or field engineers. • SMF cables are 8.3/125 µm Core/Cladding diameter with a numeric aperture of 0.13. 94 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

SMF and Trunks

Use the following rules for installing SMF cables: • SMF cable lengths cannot exceed 15 km (9.32 mi). • SMF cables must be terminated and/or spliced by a certified fiber-optic cable installer, not by installation engineers. • SMF is used for new unit installations because the new network switches used have Gbit speeds. SMF has greater distance capability than multi-mode fiber (MMF) in Gbit applications. Note Refer to the section Mesh Architecture for more information. The small form-factor pluggable (SFP) or Mini-GBIC is a compact, hot-pluggable transceiver used in network switch applications. It interfaces the network switch to a fiber optic or copper networking cable. It is a popular industry format supported by many network component vendors. The switches used in the current Mark VIe control system networking design use SFPs with LC Connectors to connect to single mode fiber-optic cable for new installations. LC Connectors SFP Ethernet Networks GEH-6721_Vol_I_BP System Guide 95 Public Information

SMF Component Sources

The following are typical sources for single-mode fiber-optic cables and connectors. Fiber-optic Cable: Optical Cable Corporation 5290 Concourse Drive Roanoke, VA 24019 Phone: +1-540-265-0690 Part Numbers (from OCC) Each of these cables are SMF 8.3/125 um Core/Cladding diameter with a numeric aperture of 0.13. OC041214-01 4 Fiber Zero Halogen Riser Rated Cable. OC041214-02 4 Fiber Zero Halogen with CST Armor. OC041214-03 4 Fiber with Flame Retardant Polyurethane. OC041214-04 4 Fiber with Flame Retardant Polyurethane with CST Armor Corning Cable Systems PO Box 489 Hickory, NC 28603-0489 Phone: +1-800-743-2671 Fiber-optic Connectors: 3M® - Connectors and Installation kit Thomas and Betts - Connectors and Assembly polishing kit Amphenol - Connectors and Termination kit 3.7.2 Un-shielded Twisted Pair (UTP) Copper Cables 3.7.2.1 Cat 5e Cables for PDH, UDH, MDH These copper cables are used for data highways connections from edge switches to HMIs and controllers. • High-quality, category 5e UTP cable, for 10/100Base-TX Ethernet • Four pairs of twisted 22 AWG or 24 AWG wire • Protective plastic jacket • Impedance: 75 – 165 Ω • Connector: RJ-45 UTP connector for solid wire 3.7.2.2 Cat 6 Cables for Layer 3 Security Hardware These copper cables are used for the additional layer 3 security offering, and provide connections from root switches to an additional series of routers, switches, and firewalls. • High-quality, category 6 UTP cable, for 10/100Base-TX Ethernet • Four pairs of twisted 22 AWG or 24 AWG wire • More stringent specifications for crosstalk and system noise • Protective plastic jacket • Connector: RJ-45 UTP connector for solid wire • Backward compatible with the Category 5/5e cable standards 96 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

The data highways use a number of 100Base-TX segments and some fiber-optic segments. These guidelines comply with

IEEE 802.3 standards for Ethernet. For details on individual Ethernet LAN component installation, refer to the instructions supplied by the manufacturer of that equipment. For more information, refer to the section Cable Separation and Routing. Note If the connection within a building and the sites share a common ground, it is acceptable to use 100Base-TX connections. If connecting between buildings, or there are differences in ground potential within a building, or distances exceed 100 m (328 ft), then 100Base-FX fiber is required. 3.7.4 Network Retrofit Guidelines Existing sites should upgrade from Allied Telesis to Cisco switches, and use single-mode fiber (SMF) for all ICS VLAN trunks. These required Cisco network switches can use SFPs with LC connectors to connect to multi-mode fiber (MMF), however this is not recommended because it downgrades them to only 100 Mb speed (with SMF, the switches function at Gb speeds). Note GE recommends replacing MMF with SMF. If not, the network is downgraded to only run at 100 MB speed. The GE requisition engineer needs to understand the ramifications if existing sites have MMF runs and the options for retermination of Ethernet cables, changes to junction boxes, and so forth. Only a certified cable installer (not the GE field engineer) can do any changes to MMF sites. Also, it is not recommended to use a converter from MMF SC connector to single SMF LC connector as this can cause network latency or introduce an additional failure point. Note Refer to the figure in the section SMF and Trunks that displays the LC connector and SFP. The options for supporting the new network switch architecture are as follows: • Re-terminate existing MMF with LC connectors to connect to the SFPs. This downgrades to 100 Mb speed, and requires a certified cable technician. • Use SC to LC conversion part (323A4747CSP1G). This is not recommended as it can introduce network latency and another possible point of failure. In addition, it still downgrades network to 100 Mb speed. • Run new SMF cables and use new Cisco switches to full capabilities of Gbit speeds (preferred solution). 3.7.4.1 MMF Cable, Outdoor Use (Data Highways) Warning Never look directly into a fiber because some longer links use lasers, which can cause permanent eye damage. Most fiber links use LEDs, which cannot damage the eyes. The following MMF cables are approved for use: • Multi-mode fiber, 62.5/125 µ core/cladding, 850 nm infrared light • Four sub-cables with elastomeric jackets and aramid strength members, and plastic outer jacket • Cable construction: flame retardant pressure extruded polyurethane. Cable diameter: 8.0 mm (0.31 in). Cable weight: 65 Kg/km • Optical Cable Corporation part number: RK920929-A The following sections provide more details on existing site MMF cabling specifications. Ethernet Networks GEH-6721_Vol_I_BP System Guide 97 Public Information

MMF Cable, Heavy Duty Outdoor Use

• Multi-mode fiber, 62.5/125 µ core/cladding, 850 nm infrared light • Four sub-cables with elastomeric jackets and aramid strength members, and armored outer jacket • Cable construction: flame retardant pressure extruded polyurethane. Armored with 0.155 mm (0.01 in) steel tape, wound with 2 mm (0.08 in) overlap, and covered with polyethylene outer jacket, 1 to 1.5 mm (0.04 to 0.06 in) thick. Cable diameter: 13 mm (0.51 in). Cable weight: 174 Kg/km • Optical Cable Corporation part number: RK920929-A-CST 3.7.4.3 MMF Cable, Indoor Use (Data Highways) • Multi-mode fiber, 62.5/125 µ core/cladding, 850 nm infrared light • Twin plastic jacketed cables (Zipcord) for indoor use • Cable construction: tight-buffered fibers surrounded by aramid strength members with a flexible flame retardant jacket. Cable dimensions: 2.9 mm (0.11 in) diameter x 5.8 mm (0.23 in) width. Cable weight: 15 Kg/km • Corning Cable Systems part number: 002K58-31141–24 3.8 Third-party Communication Links External communication links are available to interface with third-party plant controls or devices. This allows operators to have access to real-time data, and provides for discrete and analog commands to be passed to the Mark VIe controller. The Mark VIe control system can be linked to third-parties in several different ways: • OPC UA direct from the Mark VIe controller (UCSC) • OPC UA, DA, AE from the WorkstationST server • Serial or Ethernet Modbus® Slave link from the WorkstationST server • Ethernet Modbus Slave direct from the Mark VIe controller to the third-party device (Ethernet to serial converter device may be used) • GSM from the WorkstationST server to the DCS. GEDS Standard Messages (GSM) is a proprietary 100 mbps Ethernet link using TCP/IP. It supports turbine control commands, Mark VIe control data and alarms, the alarm silence function, logical events, and contact input sequence of events records with 1 ms resolution. Ethernet GSM has the advantage of tighter system integration. Attention When connecting to third-party devices, the security of the networks and the overall network architecture need to be considered and engineered accordingly. Third-party links are best connected through a firewall where one is available. Consideration must be given to redundancy and availability of communication paths. 98 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information

The Mark VIe control system uses a variety of communication protocols to interface both internally between control system

equipment and out to specialized field devices and other third-party equipment. This allows some protocols to be sent directly to the Mark VIe controllers, while others must first communicate with the I/O module that then interfaces with the controller. Other protocols use an HMI with WorkstationST application as a gateway. Communication Protocol Across Mark VIe Controls Networks Communication Protocols GEH-6721_Vol_I_BP System Guide 99 Public Information

External Interface Protocols

External interface protocols support transmitting and receiving data with third-party control, monitoring, and supervisory systems through the Plant Data Highway (PDH). Communication is important but normally not critical to control and equipment protection. The protocol types include: • Variable feedback and commands to and from a third-party Distributed Control System (DCS) • Alarm annunciation and management interface with third-party systems • Interface with third-party industrial protocol gateways Equipment Control and Configuration Protocols The Unit Data Highway (UDH) and IONet networks use several different protocols for equipment control and configuration, as described in the following table. Equipment Control and Configuration Protocols Functions Ethernet Global Data (EGD) • Feedback and commands between HMI and Mark VIe controllers on UDH • Control data between Mark VIe controllers on UDH • Real time data between I/O modules and Mark VIe controllers on IONet • Redundant controller data synchronization Network Time Protocol (NTP) Clock synchronization between Mark VIe controllers, I/O packs, WorkstationST PCs, and a master time source. NTP operates on both the UDH and IONet networks. System Data Interface (SDI) • ToolboxSTconfiguration and monitoring with controllers, I/O packs, and WorkstationST PCs • Real time alarm annunciation and management between controllers and WorkstationST Alarm Server • Transmission of trip log data from controllers to WorkstationST Alarm Server OPC-UA Server Mark VIe controller interfaces with OPC-UA client functions on UDH network Precision Time Protocol IEEE 1588 IEEE 1588 is designed for local systems requiring high precision that cannot afford the a GPS receiver at each node. The standards describe a hierarchical master-slave architecture for clock distribution. FOUNDATION Fieldbus HSE Mark VIe implementation of HSE is used to couple the controller with the linking device (gateway between IONet and H1). Fieldbus Network Protocols Fieldbus protocols network field devices (sensor and actuators) with the control system, enabling diagnostic and configuration functions along with traditional real time control. The Mark VIe system supports the following protocols: • FOUNDATION Fieldbus • PROFIBUS -DP • HART communications • CANopen communications • Modbus Master RS-232, 422, 485 • Modbus Master Ethernet • PROFINET 100 GEH-6721_Vol_I_BP GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information