Mark* VIeS Functional Safety Systems

for General Market Volume II: System Guide for General-purpose Applications July 2019 Public Information

These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible

contingency to be met during installation, operation, and maintenance. The information is supplied for informational purposes only, and GE makes no warranty as to the accuracy of the information included herein. Changes, modifications, and/or improvements to equipment and specifications are made periodically and these changes may or may not be reflected herein. It is understood that GE may make changes, modifications, or improvements to the equipment referenced herein or to the document itself at any time. This document is intended for trained personnel familiar with the GE products referenced herein. GE may have patents or pending patent applications covering subject matter in this document. The furnishing of this document does not provide any license whatsoever to any of these patents. Public Information – This document contains non-sensitive information approved for public disclosure. GE provides the following document and the information included therein as is and without warranty of any kind, expressed or implied, including but not limited to any implied statutory warranty of merchantability or fitness for particular purpose. For further assistance or technical information, contact the nearest GE Sales or Service Office, or an authorized GE Sales Representative. Issued: July 2019 © 2019 General Electric Company. ___________________________________ * Indicates a trademark of General Electric Company and/or its subsidiaries. All other trademarks are the property of their respective owners. We would appreciate your feedback about our documentation. Please send comments or suggestions to [email protected] Public Information

Mark VIeS Functional Safety Systems for General Market Volume I: System Guide

GEH-6860 Mark VIeS Control General Market Functional Safety Manual GEH-6861 Mark VIeS Functional Safety System Equipment in Hazardous Locations (HazLoc) Instruction Guide GEH-6862 ToolboxST User Guide for Mark VIeS Functional Safety Systems GEI-100846 Mark VIeS Functional Safety System Release Notes GEI-100861 Mark VIeS Functional Safety Control Systems Power Distribution Modules (PDM) Application Guide for General Market GEI-100862 Mark VIeS Functional Safety Contact Input Module Summary Sheet GEI-100863 Mark VIeS Functional Safety Relay Contact Output Module Summary Sheet GEI-100864 Mark VIeS Functional Safety Vibration Input Module Summary Sheet GEI-100865 Mark VIeS Functional Safety Universal Analog I/O Module Summary Sheet GEI-100866 Mark VIeS Functional Safety Analog I/O Module Summary Sheet GEI-100867 Mark VIe and Mark VIeS Functional Safety UCSC Controller Summary Sheet GEI-100868 Mark VIe Modbus Master Communication Module Summary Sheet GEI-100869 Mark VIe Industrial Ethernet / IONet Switches Summary Sheet GEI-100870 Mark VIe Power Distribution Module Summary Sheet GFK-3006 UCSC/UCEC Installation and Maintenance Requirements (IMR) GFT-870 Mark VIeS Functional Safety System Technical Specifications Mark VIeS DoC EU Declaration of Conformity - Mark VIeS System Guide GEH-6855_Vol_II 3 Public Information

Safety Symbol Legend

Warning Indicates a procedure or condition that, if not strictly observed, could result in personal injury or death. Caution Indicates a procedure or condition that, if not strictly observed, could result in damage to or destruction of equipment. Attention Indicates a procedure or condition that should be strictly followed to improve these applications. 4 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Control System Warnings

Warning To prevent personal injury or damage to equipment, follow all equipment safety procedures, Lockout Tagout (LOTO), and site safety procedures as indicated by Employee Health and Safety (EHS) guidelines. Warning This equipment contains a potential hazard of electric shock, burn, or death. Only personnel who are adequately trained and thoroughly familiar with the equipment and the instructions should install, operate, or maintain this equipment. Warning Isolation of test equipment from the equipment under test presents potential electrical hazards. If the test equipment cannot be grounded to the equipment under test, the test equipment’s case must be shielded to prevent contact by personnel. To minimize hazard of electrical shock or burn, approved grounding practices and procedures must be strictly followed. Warning To prevent personal injury or equipment damage caused by equipment malfunction, only adequately trained personnel should modify any programmable machine. Warning Always ensure that applicable standards and regulations are followed and only properly certified equipment is used as a critical component of a safety system. Never assume that the Human-machine Interface (HMI) or the operator will close a safety critical control loop. GEH-6855_Vol_II System Guide 5 Public Information

Orderable Part Numbers................................................................................................................. 9

2 Controllers .......................................................................................................................................17 2.1 UCSC Controllers.................................................................................................................................. 17 2.2 Controller Password Protection ................................................................................................................ 37 2.3 Shared IONet........................................................................................................................................ 37 2.4 Black Channel Safety Communication....................................................................................................... 37 2.5 Controller Setup and Download................................................................................................................ 37 2.6 Initial Download to I/O Modules .............................................................................................................. 38 2.7 Controller Diagnostic Alarms................................................................................................................... 40 3 Unmanaged Ethernet Switches ..................................................................................................85 3.1 Available Form Factors........................................................................................................................... 86 3.2 Installation ........................................................................................................................................... 86 3.3 Configuration........................................................................................................................................ 87 3.4 IONet Switch Specifications .................................................................................................................... 87 3.5 Operation............................................................................................................................................. 88 3.6 Third-party Switch Replacement............................................................................................................... 90 4 YAIC Analog I/O Modules .............................................................................................................91 4.1 Mark VIeS YAIC Analog I/O Pack............................................................................................................ 91 4.2 YAIC Specific Alarms ...........................................................................................................................101 4.3 TBAIS1C Analog Input/Output ...............................................................................................................106 4.4 STAIS2A Simplex Analog Input..............................................................................................................113 5 YDIA Discrete Input Modules .................................................................................................... 115 5.1 Mark VIeS YDIA Discrete Input Pack ......................................................................................................115 5.2 Configuration.......................................................................................................................................119 5.3 YDIA Specific Alarms...........................................................................................................................120 5.4 TBCIS#C Contact Input with Group Isolation ............................................................................................121 5.5 STCIS#A Simplex Contact Input .............................................................................................................127 6 YDOA Discrete Output Modules ...............................................................................................131 6.1 Mark VIeS YDOA Discrete Output Pack...................................................................................................131 6.2 YDOA Configuration ............................................................................................................................137 6.3 YDOA Specific Alarms .........................................................................................................................138 6.4 TRLY Discrete Output Terminal Boards....................................................................................................142 6.5 TRLYS1B Relay Output with Coil Sensing................................................................................................143 6.6 TRLYS1D Relay Output with Solenoid Integrity Sensing .............................................................................150 6.7 TRLYS#F Relay Output – TMR Contact Voting .........................................................................................155 6.8 SRLYS2A Simplex Relay Output.............................................................................................................161 7 YUAA Universal I/O Modules.....................................................................................................171 7.1 Mark VIeS YUAA Universal I/O Pack......................................................................................................171 7.2 Specifications ......................................................................................................................................172 7.3 Module Installation and Mounting ...........................................................................................................176 7.4 Operation............................................................................................................................................186 7.5 Analog Inputs (Voltage or mA Current).....................................................................................................188 7.6 Current Outputs....................................................................................................................................189 6 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

7.7 HART-Enabled mA Inputs and Outputs.....................................................................................................190

7.8 RTD Inputs..........................................................................................................................................191 7.9 Thermocouple Inputs.............................................................................................................................192 7.10 Digital Inputs and Outputs......................................................................................................................194 7.11 Pulse Accumulator................................................................................................................................200 7.12 Configuration.......................................................................................................................................200 7.13 Diagnostics..........................................................................................................................................213 7.14 Replacement........................................................................................................................................214 7.15 YUAA Diagnostic Alarms......................................................................................................................216 7.16 SUAA Universal Analog Terminal Board..................................................................................................225 8 YVIB Vibration Monitor Modules ..............................................................................................227 8.1 Mechanical Vibration Standards ..............................................................................................................227 8.2 Mark VIeS YVIB Vibration Monitor I/O Pack............................................................................................228 8.3 YVIB Functions ...................................................................................................................................234 8.4 YVIB Specific Diagnostic Alarms ...........................................................................................................271 8.5 TVBAVibration Input ...........................................................................................................................276 9 PSCA Modbus Master (Serial Communication) Module.....................................................285 9.1 PSCA Serial Communication I/O Pack .....................................................................................................285 9.2 PSCA Specific Alarms...........................................................................................................................291 9.3 SSCA Simplex Serial Communication Input/Output ....................................................................................293 10 PDM Power Distribution Modules..........................................................................................301 10.1 Power Distribution Overview..................................................................................................................301 10.2 PPDA Power Distribution System Feedback ..............................................................................................306 10.3 PPDA Specific Alarms ..........................................................................................................................319 10.4 JPDD DC Power Distribution..................................................................................................................362 10.5 JPDE DC Battery Power Distribution .......................................................................................................366 10.6 JPDG Core Power Distribution ...............................................................................................................373 10.7 JPDH High Density Power Distribution ....................................................................................................384 10.8 JPDS Core 28 V DC Power Distribution ...................................................................................................388 10.9 JGND Shield Ground ............................................................................................................................395 10.10Phoenix Power Supplies (GE Part Number Series 342A3648) ......................................................................398 11 Common I/O Module Functionality ........................................................................................441 11.1 BPPx Processor....................................................................................................................................441 11.2 I/O Module Common Diagnostic Alarms ..................................................................................................443 12 Maintenance and Replacement ..............................................................................................477 12.1 Maintenance ........................................................................................................................................477 12.2 Replacement........................................................................................................................................478 12.3 Ordering Parts......................................................................................................................................484 GEH-6855_Vol_II System Guide 7 Public Information

GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II

Public Information

Orderable Part Numbers

The following tables provide the orderable part numbers for the Mark VIeS Functional Safety System product components, including I/O packs, modules, Terminal Boards (TB), and daughterboards. Note For replacement and ordering instructions, refer to the sections Replacement and Ordering Parts. Attention The information in this document applies to the Mark VIeS Functional Safety System general market products; however, your application may not be licensed to access full system capability and I/O packs as described in this document. For example, the Mark VIeS Functional Safety System for General Markets only utilizes the following I/O packs: •• Analog I/O (YAIC) •• Universal Analog (YUAA) •• Vibration Input Monitor (YVIB) •• Relay Output (YDOA) •• Discrete Contact Input (YDIA) •• Power Distribution System Diagnostics (PPDA) •• Serial Modbus Communication (PSCA) •• Mark VIeS Safety Controller (UCSCS2x) •• Mark VIe Controller for Gateway (UCSCH1x) Orderable Part Numbers GEH-6855_Vol_II System Guide 9 Public Information

Module Part Numbers

I/O Pack/Part Number Associated Base Assembly/Accessory Description Replacement Part within Module Notes IS420YDIAS1B N/A Contact Input Safety I/O pack Board: IS400BPPCS1A Board: IS200BPDIS1A IS410STCIS2A Simplex, 24 pt - 24 V dc Contact In, 4" S-type TB, with cover and TB plugs, WROx posts Board: IS400STCIS2A Cover: 151X1202YE04PP01BL 52 pt TB: 64G6940-226L IS410STCIS4A Simplex, 24 pt - 48 V dc Contact In, 4" S-type TB, with cover and TB plugs, WROx posts Board: IS400STCIS4A Cover: 151X1202YE04PP01BL 52 pt TB: 64G6940-226L IS410STCIS6A Simplex, 24 pt - 125 V dc Contact In, 4" S-type TB, with cover and TB plugs, WROx posts Board: IS400STCIS6A Cover: 151X1202YE04PP01BL 52 pt TB: 64G6940-226L UL Pending IS410TBCIS1C TMR, 24 pt - 125 V dc Contact In, 4" T-type TB, with cover and TB blocks Board: IS400TBCIS1C Cover: 151X1202YE08PP16BL 24 pt TB (1-24): 173C9123BB 003 24 pt TB (25-48): 173C9123BB 004 UL Pending IS410TBCIS2C TMR, 24 pt - 24 V dc Contact In, 4" T-type TB, with cover and TB blocks Board: IS400TBCIS2C Cover: 151X1202YE08PP16BL 24 pt TB (1-24): 173C9123BB 003 24 pt TB (25-48): 173C9123BB 004 IS410TBCIS3C TMR, 24 pt - 48 V dc Contact In, 4" T-type TB, with cover and TB blocks Board: IS400TBCIS3C Cover: 151X1202YE08PP16BL 24 pt TB (1-24): 173C9123BB 003 24 pt TB (25-48): 173C9123BB 004 10 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Module Part Numbers (continued)

I/O Pack/Part Number Associated Base Assembly/Accessory Description Replacement Part within Module Notes IS420YDOAS1B N/A Contact Output Safety I/O pack Board: IS400BPPCS1A Board: IS200BPDOS1 IS410SRLYS2A Simplex, 12 Form C Contact Out, 7" S-type TB, with cover and TB plugs Board: IS400SRLYS2A Cover: 151X1202YE04PP05BL 48 pt TB: 64G6940-224L IS410TRLYS1B Simplex or TMR, 12 pt - Form C Relay, 1st 6 pts wetted, with cover and TB blocks Board: IS400TRLYS1B Cover: 151X1202YE08PP18BL 24 pt TB (1-24): 173C9123BB 003 24 pt TB (25-48): 173C9123BB 004 3.15 A fuse: 64G5005-011 10 A 2PDT Relay: 64G5600-003 Relay Clip: 65G2101-011 IS410TRLYS1D Simplex or TMR, 6 pt - Solenoid Out, ohm monitor, 7" T-type TB, with cover and TB block Board: IS400TRLYS1D Cover: 151X1202YE08PP18BL 24 pt TB: 173C9123BB 003 3.15 A fuse: 64G5005-011 10 A 2PDT Relay: 64G5600-003 Relay Clip: 65G2101-011 IS410TRLYS1F TMR, 12 pt NO Voted Contacts, 7" T-type TB, with cover and TB blocks, WPDF post Board: IS400TRLYS1F Cover: 151X1202YE08PP14BL 24 pt TB (1-24): 173C9123BB 003 24 pt TB (25-48): 173C9123BB 004 IS410TRLYS2F TMR, 12 pt NC Voted Contacts, 7" T-type TB, with cover and TB blocks, WPDF post Board: IS400TRLYS2F Cover: 151X1202YE08PP14BL 24 pt TB (1-24): 173C9123BB 003 24 pt TB (25-48): 173C9123BB 004 IS420YAICS1B N/A Analog In / Out Safety I/O pack Board: IS400BPPCS1A Board: IS400BPAIS1A IS410STAIS2A Simplex, 10 Analog in / 2 Analog out, 4" S-type TB, with cover and TB plugs Board: IS400STAIS2A Cover: 151X1202YE04PP01BL 48 pt TB: 64G6940-224L IS410TBAIS1C TMR, 10 Analog in / 2 Analog out, 4" S-type TB, with cover and TB blocks Board: IS400TBAIS1C Cover: 151X1202YE08PP16BL 24 pt TB (1-24): 173C9123BB 003 24 pt TB (25-48): 173C9123BB 004 IS420YUAAS1A N/A Universal Analog Safety I/O pack N/A IS410SUAAS1A Universal Analog Simplex, 16 Channel Volt/Current/TC/DI/Cntr, 3" S-type TB 52 pt TB: 64G6946-226L Orderable Part Numbers GEH-6855_Vol_II System Guide 11 Public Information

Module Part Numbers (continued)

I/O Pack/Part Number Associated Base Assembly/Accessory Description Replacement Part within Module Notes IS420YVIBS1B N/A Vibration I/O pack Board: IS400BPPCS1A Board: IS400BBAAS1A IS410TVBAS2B Simplex or TMR, 8 Vib/Prox, 3 Pos, 2 Key/Pos, 7" T-type TB, with cover and TB blocks Board: IS400TVBAS2B Cover: 151X1202YE08PP14BL 24 pt TB (1-24): 173C9123BB 003 24 pt TB (25-48): 173C9123BB 004 IS420PSCAH1B N/A Serial Communication / Modbus Master I/O pack Board: IS400BPPCS1A Board: IS400BSCAH3A IS410SSCAH2A Simplex, 6 channel Serial Comm Termination Board , 4" S-type TB, with cover and TB plugs Board: IS400SSCAH2A Cover: 151X1202YE04PP01BL 48 pt TB: 64G6940-224L Power Distribution Module and Daughterboard Part Numbers I/O Pack/Part Number Associated Base Assembly/Accessory Description Replacement Part within Module Notes IS420PPDAH1B N/A JPDG / JPDS Power Supply Diagnostics I/O pack Board: IS400BPPCH1A Board: IS400BPDAH1A IS410JPDSG1A 28 V Control Power Distribution, with diagnostics I/O pack, with cover Board: IS400JPDSG1A Cover: 151X1202YE12PP02BL IS410JPDGH1A 28 V Dual Control and 24 V (or 48 V) Wetting Power Distribution, with diagnostics, with cover Board: IS400JPDGH1A Cover: 151X1202YE12PP02BL 10 A fuse: 64G5002-001 15 A fuse: 64G5003-001 N/A IS410JPDDG2A 24 or 48 V dc wetting distribution via 6 switch branches, 5 x 20 mm fuse holder, with cover Board: IS400JPDDG2A Cover: 151X1202YE12PP04BL Fuse: any 20.0 × 5.0 mm (0.79 × 0.20 in) IS410JPDDG3A 24 or 48 V dc wetting distribution via 6 switch branches, 1.25 x 0.2 5in fuse holder, with cover Board: IS400JPDDG3A Cover: 151X1202YE12PP04BL Fuse: any 31.75 × 6.35 mm (1.25 × 0.25 in) IS410JPDEG1A TMR Wetting Power System / Distribution module (24 or 48 V dc), with cover Board: IS400JPDEG1A Cover: 151X1202YE12PP01BL 7 A fuse: 64G5001-001 15 A fuse: 64G5003-001 IS410JPDHG1A Control Power Fanout Distribution, with cover Board: IS400JPDHG1A Cover: 151X1202YE12PP03BL 12 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Power Distribution Module and Daughterboard Part Numbers (continued)

I/O Pack/Part Number Associated Base Assembly/Accessory Description Replacement Part within Module Notes N/A IS400WROBH1A Optional daughterboard IS400SRLYS2A wetting and fusing, adds hi/lo fusing to 1st 6 relays 3.15 A fuse: 64G5005-011 IS400WROFH1A Optional daughterboard IS400SRLYS2A wetting and fusing, adds form-C COM fuses to all 12 relays 3.15 A fuse: 64G5005-011 IS400WROGH1A Optional daughterboard IS400SRLYS2A wetting and fusing, adds hi-side fusing to all 12 relays 3.15 A fuse: 64G5005-011 IS400WPDFH1A Optional daughterboard IS400TRLYS#F wetting and fusing, Adds hi/lo fusing and sensed power to 2 groups of 6 relays 3.15 A fuse: 64G5005-005 UL Pending IS400WPDFH2A Optional daughterboard IS400TRLYS#F wetting and fusing, Add hi side fusing and sensed power to 2 groups of 6 relays 3.15 A fuse: 64G5005-005 UL Pending Mark VIe and Mark VIeS Controllers Part Numbers I/O Pack/Part Number Associated Base Assembly/Accessory Description Replacement Part within Module Notes IS420UCSCS2A N/A Mark VIeS Safety Controller N/A IS420UCSCH1B N/A Mark VIe Gateway Controller N/A Orderable Part Numbers GEH-6855_Vol_II System Guide 13 Public Information

IONet Switch and DIN-rail Mounting Clip Part Numbers

I/O Pack/Part Number Associated Base Assembly/Accessory Description Replacement Part within Module Notes IS420ESWAH1A N/A IONet Switch - 8 copper, 1 FX Multimode Fiber (LC-type) N/A IS420ESWAH2A N/A IONet Switch - 8 copper, 2 FX Multimode Fiber (LC-type) N/A IS420ESWAH3A N/A IONet Switch - 8 copper N/A IS420ESWAH4A N/A IONet Switch - 8 copper, 1 FX Singlemode Fiber (LC-type) N/A IS420ESWAH5A N/A IONet Switch - 8 copper, 2 FX Singlemode Fiber (LC-type) N/A IS420ESWBH1A N/A IONet Switch -16 copper, 1 FX Multimode Fiber (LC-type) N/A IS420ESWBH2A N/A IONet Switch - 16 copper, 2 FX Multimode Fiber (LC-type) N/A IS420ESWBH3A N/A IONet Switch - 16 copper N/A IS420ESWBH4A N/A IONet Switch - 16 copper, 1 FX Singlemode Fiber (LC-type) N/A IS420ESWBH5A N/A IONet Switch - 16 copper, 2 FX Singlemode Fiber (LC-type) N/A 259B2451BVP1 N/A Option DIN-rail base for ESWA and ESWB, long edge of switch body parallel to DIN-rail N/A 259B2451BVP2 N/A Option DIN-rail base for ESWA, long edge of switch body perpendiculr to DIN-rail N/A 259B2451BVP4 N/A Option DIN-rail base for ESWB, long edge of switch body perpendicular to DIN-rail N/A 14 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Mark VIe Power Supplies and OR-ing Module Part Numbers

I/O Pack/Part Number Associated Base Assembly/Accessory Description Replacement Part within Module Notes 342A3648P120W24 N/A 120W Power Supply 120/240AC//125/250DC > 24DC N/A 342A3648P120W24C N/A 120W Power Supply 120/240AC//125/250DC > 24DC, Coated N/A 342A3648P120W28 N/A 120W Power Supply 120/240AC//125/250DC > 28DC N/A 342A3648P120W28C N/A 120W Power Supply 120/240AC//125/250DC > 28DC, Coated N/A 342A3648P240W24 N/A 240W Power Supply 120/240AC//125/250DC > 24DC N/A 342A3648P240W24C N/A 240W Power Supply 120/240AC//125/250DC > 24DC, Coated N/A 342A3648P240W28 N/A 240W Power Supply 120/240AC//125/250DC > 28DC N/A 342A3648P240W28C N/A 240W Power Supply 120/240AC//125/250DC > 28DC, Coated N/A 342A3648P240W48 N/A 240W Power Supply 120/240AC//125/250DC > 48DC N/A 342A3648P480W24 N/A 480W Power Supply 120/240AC//125/250DC > 24DC N/A 342A3648P480W24C N/A 480W Power Supply 120/240AC//125/250DC > 24DC, Coated N/A 342A3648P480W28 N/A 480W Power Supply 120/240AC//125/250DC > 28DC N/A 342A3648P480W28C N/A 480W Power Supply 120/240AC//125/250DC> 28DC, Coated N/A 342A3648P480W48 N/A 480W Power Supply 120/240AC//125/250DC > 48DC N/A 342A3648P960W24 N/A 960W Power Supply 120/240AC//125/250DC > 24DC N/A 342A3648P960W28 N/A 960W Power Supply 120/240AC//125/250DC > 28DC N/A 342A3647P960W48 N/A 960W Power Supply 120/240AC//125/250DC > 48DC N/A 342A3648PF20A28C N/A FET-ORing Module - 28VDC 2X10ADC, Coated N/A 342A3648PF40A28C N/A FET-ORing Module - 28VDC 2X20ADC, Coated N/A 342A3648PF80A28C N/A FET-ORing Module - 28VDC 2X40ADC, Coated N/A 342A3647PD40A48 N/A Diode-ORing Module - 48VDC 2x20ADC N/A Orderable Part Numbers GEH-6855_Vol_II System Guide 15 Public Information

GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II

Public Information

UCSC controllers are compact, stand-alone controllers that run application-specific control system logic used in a diverse

range of applications, such as wind turbines, gas and steam turbines, and combined-cycle power plants. The UCSC controller offers the following advantages: • Single module • No battery • No fan • No jumper settings required • Flash memory can be conveniently updated • Can be expanded to include seven additional I/O ports The UCSC controller mounts in a panel and communicates with I/O modules through on-board I/O network (IONet), PROFINET, High-speed Serial Link (HSSL), and/or other interfaces. UCSC Controller Data Name Plate Note For additional information, refer to the following documents: • Mark* VIe and Mark VIeS Functional Safety UCSC Controller Summary Sheet (GEI-100867) • Mark VIeS Functional Safety Systems for General Market Volume I: System Guide (GEH-6855_Vol_I) • ToolboxST *User Guide for Mark VIeS Functional Safety Systems (GEH-6862) • Mark VIeS Functional Safety System Release Notes (GEI-100846) • UCSC/UCEC Installation and Maintenance Requirements (IMR) (GFK-3006) Controllers GEH-6855_Vol_II System Guide 17 Public Information

Mark VIe UCSCH1B Controllers

The Mark VIe IS420UCSCH1B quad core controller uses real-time hypervisor technology and QNX® Neutrino, a real-time, multi-tasking operating system (OS) to run high-speed, high-reliability industrial applications. Embedded Field Agent (EFA) technology is used to apply Predix™cloud-based applications and/or locally hosted web applications over a secure connection and deliver real-time data. The UCSCH1x controller is loaded with software specific to its application. As a turbine or balance of plant (BoP) controller, it runs the Mark VIe firmware and applications and utilizes IONet interfaces. IONet is a private special-purpose Ethernet that only supports Mark controls I/O packs and controllers. IEEE 1588 protocol is used through the IONet interfaces to synchronize the clock of the I/O modules and controllers to within ±100 microseconds. External data is transferred to and from the control system database in the controller over the IONet interfaces. This includes process inputs/outputs to the I/O modules. Unlike traditional controllers where I/O is on a backplane, the UCSC controller does not host any application I/O. In a redundant set, all I/O networks are attached to each controller, providing them with all input data. This hardware and software architecture guarantees that no single point of application input is lost if a controller is powered down for maintenance or repair. The UCSCH1B is available beginning with ControlST* V07.01, and supports Simplex, Dual, and Triple Modular Redundant (TMR) redundancy. UCSCH1 Platform Configuration Supported Features Platform Embedded PPNG Embedded EtherCAT EFA UCSCH1B X X ✓ Mark VIe UCSCH1B Controller 18 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Mark VIeS UCSCS2A Controllers

The IS420UCSCS2A dual core controller runs the Mark VIeS Safety control applications used for functional safety loops to achieve SIL 2 and 3 capabilities. Mark VIeS Safety equipment is used by operators that are knowledgeable in safety-instrumented system (SIS) applications to reduce risk in critical safety functions. Safety controllers and distributed I/O modules are specifically programmed for safety control use, and this specific control hardware and software is compliant with the IEC 61508 certification. The Mark VIeS Safety controller runs on QNX Neutrino, a real-time, multi-tasking operating system (OS). The UCSCS2A is available beginning with ControlST V07.02, and supports Simplex, Dual, and TMR redundancy. Mark VIeS Safety UCSCS2A Controller Controllers GEH-6855_Vol_II System Guide 19 Public Information

IS420UCSCH1: quad core, 1.2 GHz AMD G-Series

IS420UCSCS2: dual core, 1.6 GHz AMD G-Series Memory IS420UCSCH1: 4 GB DDR3-1333 SDRAM IS420UCSCS2: 2 GB DDR3-1066 SDRAM NVSRAM Supports 3067 nonvolatile program variable, 338 forces, and 64 totalizers Not supported by the Mark VIeS Safety control Ports • 5 Ethernet ports on front panel (Refer to the section Interface Details.) • 1 Ethernet port on bottom used for connectivity to Predix • 2 USB ports only used to initially set up UDH network IP address or for restore function • 1 COM port is 115200 bit/s, 8N1, RJ-45 connector, no Flow-Control, serial redirection of UEFI-setup, and typically used by GE for troubleshooting in field • 1 Display Port (disabled after startup) • 1 microSD (not currently supported) LEDs Refer to the section LEDs. Input Power Refer to the section Power Requirements. HMI ControlST V07.00.00C or later Programming Control block language with analog and discrete blocks; Boolean logic represented in relay ladder diagram format. Supported data types include: • Boolean • 16-bit signed integer • 16-bit unsigned integer • 32-bit signed integer • 32-bit unsigned integer • 32-bit floating point • 64-bit long floating point Dimensions UCSC: 168 x 150 x 55 mm (6.61 x 5.90 x 2.17 in) (H x D x W) UCSC with mounting: 204 x 152 x 55 mm (8.03 x 5.99 x 2.17 in) (H x D x W) Weight 1,327 g (46.8 oz) Mounting Refer to the section Mounting Requirements. Cooling Convection Operating temperature -40 to 70°C (-40 to 158 °F), ambient 25 mm (0.98 in) from any point on UCSC Storage Temperature -40 to 85°C (-40 to 185 °F) Humidity 95% non-condensing Altitude Normal Operation: 0 to 1,000 m (0 to 3281 ft) at 101.3 to 89.8 kPa Extended Operation: 1,000 to 3,000 m (3281 to 9,843 ft) at 89.8 to 69.7 kPa; requires temperature derating up to 3000 m (9,843 ft) = 65°C (149 °F) max Reliability MTBF at 30°C (86 °F) IS420UCSCH1: 414,248 hours IS420UCSCS2: 417,821 hours ECCN US Classification Can be supplied upon request Certifications Refer to the section Agency Certifications and Standards. 20 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

UCSC Mounting and Installation Requirements

2.1.4.1 UCSC Mounting Requirements The following are requirements for mounting the UCSC controller: • Directly mount the UCSC to the mounting base using the two mounting screws. • Vertical mount with unobstructed air flow through fins. • Leave a minimal 100 mm (3.94 in) air gap above and below the UCSC. • Parallel mount UCSC to UCSC requires a minimal 50 mm (1.97 in) spacing to achieve full temperature rating. • The operating temperature envelope is 25 mm (0.98 in) from any point on UCSC. Controllers GEH-6855_Vol_II System Guide 21 Public Information

UCSC Mounting Requirements to Achieve 70ºC Operating Temperature

22 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

UCSC Mounting Requirements to Achieve 65ºC Operating Temperature

Controllers GEH-6855_Vol_II System Guide 23 Public Information

UCSC Controller Mounting Dimensions

24 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

UCSC Controller Input Power

— 18 30.8 Watts Voltage 18 24/28 30 V dc Input Capacitance — 25 — uF Surge Protection Non-replaceable 4 A 125 V dc rated fuse Nominal melting: 26 A squared seconds (A2 sec) Reverse Polarity Protection Provided Reversing the + and - input will not damage the UCSC, nor will it power up. 3-pin Power Plug Item Description Pin 1 Ground Pin 2 Negative The UCSC case is bonded to power supply negative. Pin 3 Positive Wire Sizes 28 to 16 AWG Screw Torque 0.23 Nm (2 in-Ib) Part Number Phoenix Contact MC 1,5/ 3-STF-3,81 - 1827716 Controllers GEH-6855_Vol_II System Guide 25 Public Information

UCSC Connection Ports (Front View)

Note For further information, refer to the ToolboxST User Guide for Mark VIeS Functional Safety Systems (GEH-6862), the section System Controller Platforms. 26 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

UCSC Connection Ports (Bottom View)

Note † For instructions to set up the controller Internet Protocol (IP) address using the COM port, refer to the ToolboxST User Guide for Mark VIeS Functional Safety Systems (GEH-6862), the section Configure and Transfer IPAddress to UCSC Controller. Controllers GEH-6855_Vol_II System Guide 27 Public Information

Mark VIe UCSCH1B Ethernet Ports

Ethernet Port Description IONet Ethernet Interface (3 Ports) UCSCH1B: T/SL3 is network for TMR (using all three ports). S/SL2 is network for Dual redundancy (used with R/SL1). R/SL1 is network for Simplex redundancy. Twisted pair 10Base-TX/100Base-TX, RJ-45 connector is used. TCP/IP protocols is used to communicate between controllers and I/O modules. For TMR and Dual configurations, IONet redundancy is equal to controller redundancy. For Simplex configurations, both Simplex and TMR IONet redundancy are supported. ENET 1 Primary Ethernet Interface to LAN UDH Twisted pair 10Base-T/100Base-TX, RJ-45 connector is used. TCP/IP protocol is used for communication between controller and ToolboxST application. TCP/IP protocol is used for alarm communication to HMIs. Modbus TCP Slave and/or OPC UA EGD protocol is used for application variable communication to HMIs. ENET 2 UCSCH1B: Secondary plant network Twisted pair 10Base-T/100Base-TX, RJ-45 connector is used. Modbus TCP Slave, OPC UA, and/or EGD Mark VIeS UCSCS2A Ethernet Ports Ethernet Port Description IONet Ethernet Interface (3 Ports) T/SL3 is network for TMR (using all three ports). S/SL2 is network for Dual redundancy (used with R/SL1). R/SL1 is network for Simplex redundancy. Twisted pair 10Base-TX/100Base-TX, RJ-45 connector is used. TCP/IP protocols is used to communicate between controllers and I/O modules. For TMR and Dual configurations, IONet redundancy is equal to controller redundancy. For Simplex configurations, both Simplex and TMR IONet redundancy are supported. ENET 1 Primary Ethernet Interface to LAN UDH Twisted pair 10Base-T/100Base-TX, RJ-45 connector is used. TCP/IP protocol is used for communication between controller and the ToolboxST application. TCP/IP protocol is used for alarm communication to HMIs. Modbus TCP Slave EGD protocol is used for application variable communication to HMIs. ENET 2 Not supported 28 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

UDH Network Configuration

The UCSC is typically set up for communications on the UDH network using an unencrypted minimum 4 GB flash drive that is configured with the ToolboxST application. The factory default IP address is 192.168.101.111. The correct UDH IP address must be properly set up so that the controller can communicate to the site HMIs. Note The UCSC, as shipped from the factory, does not include the software on the controller to support communication from the PHY PRES button to the EFA. The user needs to download to the controller at least once (using ToolboxST) to enable this. ➢➢ To change the UDH network IP address for the UCSC 1. Verify that the HMI computer running the ToolboxST application has been configured (through Windows OS) with the correct IP address for the UDH network. 2. From the ToolboxST Component Editor, verify that the controller Platform is set as UCSCxxx. 3. From the Component Editor General tab Property Editor Network Adapter 0, configure the appropriate controller IP address as a relative subnet to the HMI’s UDH IP address from Step 1. 4. Insert a non-encrypted, USB 2.0 only flash drive with a minimum 4 GB capacity into a USB port of the computer that is running the ToolboxST application. 5. From the ToolboxST Component Editor, select Device, Download, and Controller Setup to launch the Controller Setup Wizard. 6. Follow the on-screen instructions to load the flash drive. Refer to the ToolboxST User Guide for Mark VIeS Functional Safety Systems (GEH-6862), the section Configure and Transfer IPAddress to UCSC Controller for further instructions. ➢➢ To set the controller’s network address using the COM port Attention Use a UCSC COM port adapter, a standard serial to USB cable, and/or a Cat5e or better Ethernet cable for this connection. 1. Connect the UCSC COM port adapter to the Ethernet cable and the other end of the cable to the UCSC COM port. 2. Connect the UCSC COM port adapter to the serial to USB cable, then to the computer that runs the ToolboxST application. 3. From the ToolboxST Component Editor General tab, select Device, Download, and Controller Setup to launch the Controller Setup Wizard. 4. Follow the on-screen instructions to transfer the UDH network address to the controller. Refer to the ToolboxST User Guide for Mark VIeS Functional Safety Systems (GEH-6862), the section Configure and Transfer IPAddress to UCSC Controller for further instructions. Controllers GEH-6855_Vol_II System Guide 29 Public Information

The locations and descriptions of the LED indicators that are located on the front panel of the UCSC controller and the UCEC

module are as follows. 30 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

The UCSC controller uses internal temperature readings and logic to protect its internal electronics. Internal circuitry

generates a warning at 85°C (185 °F) and shuts down at 95°C (203 °F). The UCSC will reboot once the internal circuitry detects the temperature has dropped below 75°C (167 °F). Independently, the microprocessor monitors its operating temperature and generates a warning at 105°C (221 °F) and shuts down at 107°C (225 °F). A power cycle is required to recover from a microprocessor over-temperature shut down. Both of these warnings drive the OT LED and are annunciated as diagnostic alarms. 2.1.5.4 UCSC COM Port Typically used by GE to troubleshoot in the field, the UCSC COM port accepts a UCSC COM port adapter and a standard serial to USB cable is used to connect to another computer. Use Cat5e or better Ethernet cable for this connection. The COM port can also be used to set the controller’s UDH network address. For these instructions, refer to the ToolboxST User Guide for Mark VIeS Functional Safety Systems (GEH-6862), the section Configure and Transfer IPAddress to UCSC Controller. 2.1.6 UCSC Embedded Field Agent (EFA) The Embedded Field Agent (EFA) provides connectivity to GE Predix* cloud-hosted applications and datastores through a local Predix machine interface that runs within a Linux virtual machine on the UCSCH1. The EFA has two primary functions: • Collecting and transmitting machine data securely • A platform for running Predix apps on the Edge directly on the machine Once a Field Agent is up and running, data is transferred from the plant to the cloud over encrypted channels, preserving its time stamp, quality, and fidelity. It also provides a rich domain application environment for edge processing, so logic can be executed at the most appropriate place in the architecture — locally on the machine or in the cloud. Note For more information, refer to the following documentation: • Field Agents User Guide (GFK-2993) • Field Agent Secure Deployment Guide (GFK-3009) • Field Agents Upgrade Guide (GFK-3017) Controllers GEH-6855_Vol_II System Guide 31 Public Information

UCSC Virtual Network

The virtual network is a feature of the hypervisor used in UCSCH1 controllers. The virtual network transfers data between the virtual machines (VMs) in the UCSCH1 controller like an Ethernet network transfers data between physical machines over a physical network. The virtual network in the UCSCH1 controller is used to transfer data between the Mark VIe control running in one VM, and the Embedded Field Agent (EFA) running in another VM. The EFA requires a connection to the Mark VIe control and a connection to the cloud. However, the Mark VIe control must not have a connection to the cloud, so a physical managed switch must be used to segment the networks. To resolve this issue, data is passed through the virtual network so the EFA can connect directly to the cloud and eliminate the need of a managed switch. The virtual network transfers data through memory shared between the VMs instead of the wires of a physical network. The Mark VIe control uses a network firewall to prevent all other traffic. Like a physical network, the virtual network must be configured with an IP address and subnet mask. The VMs in the UCSCH1 controller must be on the same subnet to function properly. The Mark VIe virtual network is configured using the ToolboxST application. The default configurations for the Mark VIe control and the EFA provide a working virtual network. However, changing the configuration in one VM may interrupt communication over the virtual network until a corresponding change is made to the other VM. Note To configure virtual network adapters, refer to the ToolboxST User Guide for Mark VIeS Functional Safety Systems (GEH-6862), the section Virtual Network Adapters. To configure the virtual network in the EFA, refer to the Field Agents User Guide (GFK-2993). 32 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Agency Certifications and Standards

Refer to the UCSC Installation and Maintenance Requirements (IMR) (GFK-3006) for conformance to these standards. Description Marking Comments North America Safety for Programmable Controller for use in Hazardous locations ISA 12.12.01: 2015, Class I Div. 2 Groups ABCD, UL 60079-0 Ed 6.0 (2013), Class I, Zone 2 Gas Group ABCD, UL 60079-15 Edition 4.0 (2013), [Ex nA] CSA C22.2 No. 213-15, CAN/CSA-C22.2 NO. 60079-0:15, Class I, Zone 2, CAN/CSA-C22.2 NO. 60079-15:12 EMC Directive European Restriction of Hazardous Substances (RoHS) IEC/EN 61131-2: 2007(sections 8-10, Zone B), IEC/EN 61000-6-2: 2005 Ed 2.0, IEC/EN 61000-6-4: 2006 Ed 2.0, CISPR 11:2009 +A1: 2010 / EN 55011: 2009 +A1: 2010, CISPR 22: 2010 / EN55022: 2010/AC:2011 (Class A), CISPR 24: 2010 / EN55024: 2010, IEC/EN 61131-2: 2007 (sections 4 & 6), IEC 61000-4-18: 2006 / EN 61000-4-18: 2007 (refer to IEC61131-2: 2007 Annex D for levels) European Safety for Explosive Atmosphere, ATEX Directive Category 3 equipment - [II 3 G], EN 60079-0: 2012 A+11:2013, EN 60079-7: 2015 [Type of Protection Ex ec] European Waste & Collection Compliance with European WEEE Directive 2012/19/EU China Restriction of Hazardous Substances Compliance with “Management Methods for the Restriction of the Use of Hazardous Substances in Electrical and Electronic Products”. (Jan 21, 2016) Declaration Table provided with equipment. Environmental No Marking IEC/EN 61131-2: 2007 (sections 5 & 6) Storage: Dry Heat - IEC 60068-2-2: 1974 test Bb (70°C at 16hrs, unpowered), Cold Temp - IEC 60068-2-1: 2007 test Ab (-40°C at 16hrs, unpowered Sinusoidal Vibration: DIN EN 60068-2-6: (Edition 10/08) (test Fc) Shock: DIN EN 60068-2-27: (Edition 2/10) (test Ea) Controllers GEH-6855_Vol_II System Guide 33 Public Information

UCSB to UCSC Power Cable Adapter

121T6659P0001 UCSC COM Port Adapter (RJ-45 to DB9F) 34 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

UCSC Hardware Replacement

Replacement parts may contain static-sensitive components. Therefore, GE ships replacement parts in anti-static bags. When handling electronics, make sure to store them in anti-static bags or boxes and use a grounding strap. Caution To prevent component damage caused by static electricity, treat all boards with static-sensitive handling techniques. Wear a wrist grounding strap when handling boards or components, but only after boards or components have been removed from potentially energized equipment and are at a normally grounded workstation. Warning In addition to information provided here, always follow all wiring and safety codes that apply to your area or your type of equipment. For example, in the United States, most areas have adopted the National Electrical Code standard and specify that all wiring conform to its requirements. In other countries, different codes will apply. For maximum safety to personnel and property you must follow these codes. Failure to do so can lead to personal injury or death, property damage or destruction, or both. ➢➢ To replace the UCSC with another UCSC 1. Loosen the screws holding the power connector in place. 2. Disconnect the power connector from the controller. 3. Disconnect all Ethernet cables (note which cable is connected to which port). 4. Loosen the screws holding the controller in place. The mounting is a keyhole design. 5. Remove the controller by lifting to align the large portion of the keyhole with the mounting screws and pull forward. 6. Verify that the hardware revision of the old UCSC is the same or compatible with the new UCSC for its particular application. 7. Reinstall the new controller by reversing steps 2 through 4. Do not apply power yet. 8. Perform the UCSC Restore procedure to initialize the new controller. 9. If restore was not successful, configure the new controller’s UDH network address. 10. Use the ToolboxST application to Build and Download to the controller as needed. Refer to the ToolboxST User Guide for Mark VIeS Functional Safety Systems (GEH-6862), the section Download to Controller for instructions. Controllers GEH-6855_Vol_II System Guide 35 Public Information

After installing a replacement controller, perform the following procedure to apply the configuration to the UCSC controller

and allow communication between the UCSC and the ToolboxST application. The Physical Presence (PHY PRES) button located on the front of the controller is used to initiate the procedure. Note The UCSC, as shipped from the factory, does not include the software on the controller to support communication from the PHY PRES button to the EFA. The user needs to download to the controller at least once (using ToolboxST) to enable this. ➢➢ To perform UCSC restore 1. From the ToolboxST Component Editor Device menu, select Download, then select Controller Setup. 2. When the Controller Setup Wizard Welcome window displays, click Next. 3. Select Initialize USB Flash Device, then click Next. 4. Insert a non-encrypted USB 2.0 (only) flash device with a 4 GB minimum capacity into the HMI computer USB port. 5. Click Scan and select the listed flash drive. 6. Select the correct Channel (R, S, or T if using redundant controllers). 7. Click Write, then click Next. 8. Complete the controller restore process using the instructions provided on the Controller Setup Wizard window or using the remaining steps in this procedure. 9. Remove the USB flash device from the HMI computer. 10. Remove power from the controller. 11. Insert the USB flash device into either USB port of the controller. 12. Press and hold in the PHY PRES button, and apply power to the controller. Continue to hold in the PHY PRES button until the USB On LED is lit (~ 15 seconds). 13. Release the PHY PRES button and wait for the process to complete. (The USB On LED remains lit to indicate the restore is in progress. The procedure takes one to two minutes.) When the LED turns off, the restore has completed successfully. Note If the LED flashes at a 1 Hz rate, a failure has occurred. Retry or remove the USB flash device. 14. Remove the USB flash device from the controller. 15. Cycle power on the controller. 16. From the ToolboxST Controller Setup Wizard window, click Finish. 17. Perform a Download to bring the controller back online and in the controlling state. 36 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Controller Password Protection

Beginning with controller firmware V06.00.00C, password protection can be applied as a security measure to restrict access to the controller. The password has an eight-character limit and other requirements. For the instructions to set password protection, change the password, and other details, refer to the ToolboxST User Guide for Mark VIeS Functional Safety Systems (GEH-6862), the section System Password Protection for the component. 2.3 Shared IONet The Shared IONet function (with ControlST V04.06 or higher) enables the sharing of Mark VIeS Safety inputs with another basic process Mark VIe controller set, saving the cost of redundant sensors and I/O. Refer to the Mark Controllers Shared IONet User Guide (GEH-6812) for more information. 2.4 Black Channel Safety Communication Black Channel is a safety communications approach in which the new safety functionality is built over existing protocol without impact to existing safety applications. The Black Channel feature provides the transfer of Safety control data between two Mark VIeS Safety control devices without using the standard UDH network, providing a safer, less congested network. A matching pair of transmitter and receiver blocks, BLACK_TX and BLACK_RX, are configured for the two Mark VIeS Safety control devices in the application. The data is passed through Ethernet (similar to UDH EGD), and the BLACK_TX and BLACK_RX blocks run a data integrity check on each respective side of the Black Channel. For more information on these blocks, refer to the Mark VIeS Safety Control Block Library (GEI-100691), the chapters Black Channel Transmitter (BLACK_ TX) , Black Channel Receiver (BLACK_RX), and Black Channel Example. Transmitting Device Receiving Device App App BLACK _TX Block BLACK_TX Block Vardef EGD EGD EGD Exchange EGD Exchange Produced BlackChannel Page Consumed BlackChannel Page Transmit Block Data Receive Block Data Var1 Var2 Var3 Var4 Sequence Number Connection ID Signature Var1 Var2 Var3 Var4 Sequence Number Connection ID Exp Connection ID Signature EGD Packet Example Black Channel Configuration 2.5 Controller Setup and Download After a controller and associated I/O modules have been added to the system, prepare the controller for use by configuring the IP address and redundancy information using the ToolboxST application. For further instructions and procedures, refer to the ToolboxST User Guide for Mark VIeS Functional Safety Systems (GEH-6862), the sections Controller Setup and Build and Download to Controller. Controllers GEH-6855_Vol_II System Guide 37 Public Information

Initial Download to I/O Modules

2.6.1 Update Terminal Boards Prerequisites • Successfully online with the associated controller set • All I/O modules have been correctly added to the ToolboxST system • Correctly connected IONet cables to all the I/O modules • I/O modules are powered on Complete this procedure to detect the terminal board barcodes. ➢➢ To update terminal boards online 1. If not already online, then from the Component Editor toolbar click the Go On/Offline icon to go online with the ToolboxST application. 2. Have available or create a written record of all installed terminal boards. 3. Enable the I/O modules for configuration. a. From the Component Editor Hardware tab, select all the I/O modules. b. From the Property Editor, under Configuration, Required, select True. 4. From the Tree View, double-click the I/O module icon to display the Modify dialog box. 5. From the Bar Code text box, click the ellipsis button to display the Select Unassigned Terminal Board dialog box with the available terminal boards. 6. From the dialog box, select the correct Bar Code and click OK. 7. Read the warning message, then click Yes. 8. Click OK. 9. Repeat this procedure for the remaining I/O modules. 10. Verify using the written record that all terminal boards have been identified by the ToolboxST application. 2.6.2 Initial Download to I/O Modules ➢➢ To perform an initial download 1. If using Shared IONet, save and close both Component Editors. From the System Editor Tree View, select the Shared IONet Group. Right-click and select Download Shared IONet, then complete the wizard. Go to step 4. 2. From the Component Editor, click Build. 3. Click Download and complete the wizard using the default settings. 4. Cycle power to the panel. Wait for all equipment to power on with correct status LEDs. 5. Click to go online. 6. Wait and reset any alarms, if needed. 7. Build and Download again, if needed. 8. Wait and reset any alarms, if needed. 9. Select the Component InfoView Status tab. 38 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

The color of the Status tab indicates overall health and equality status of the controller, including its associated I/O hardware.

A major difference in controller equality means that the configuration in the ToolboxST application is different from the controller configuration. • Green indicates that the ToolboxST configuration and the controller configuration are equal. • Orange indicates the presence of inequalities or diagnostic warnings. • Red indicates that the configuration in the ToolboxST system, which includes base load, firmware, application code, and I/O module configuration, is significantly different from the component configuration (a Download will correct this). Note Refer to GEH-6855_Vol_I, the chapter Troubleshooting for further assistance. For example, if a particular download fails, this may be fixed by selecting the pack individually from the download wizard and trying again. Controllers GEH-6855_Vol_II System Guide 39 Public Information

Controller Diagnostic Alarms

These diagnostic alarms are common among Mark Controls Platforms. However, some alarms are not applicable to all controller platforms. 0 Description Diagnostic Alarm Reset 20 Description ToolboxST application detects unhealthy link or loss of communication between [ ] and controller. Possible Cause • I/O pack configuration files missing • I/O pack restarted or did not complete startup • I/O pack configured for dual networks, but only one network is connected • Network issue preventing connection to ToolboxST application • Power failure to the I/O pack • Terminal board Bar Code entered incorrectly in ToolboxST configuration • Wrong terminal board is configured in ToolboxST application • I/O pack or module plugged into wrong jack on terminal board, or wrong jack number in ToolboxST configuration • I/O pack configured in ToolboxST application, but configuration not downloaded to the controller • I/O pack in program mode Solution • Verify that the Ethernet cables and network switch are operating correctly. • Verify that the I/O pack configuration (such as Type, HW Form, Bar Code, position) matches the actual hardware. • Manually restart the I/O pack or module. • If ToolboxST communication is working correctly, any additional diagnostics should indicate the cause of the problem. • Build and download parameters to the I/O pack or module. • Download firmware and parameters to the I/O pack or module. • Build and download the configuration to the controller, wait for I/O pack communication status to change, then scan and download to the I/O pack. Note This alarm is not reported to the WorkstationST Alarm Viewer. This alarm is generated by the ToolboxST application, not by the firmware. 40 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Note This alarm is obsolete.

Description Control/Status communication failure between [ ] and controller Possible Cause • Asynchronous Drive Language (ADL) communication unhealthy • Terminal board barcode typed incorrectly in the ToolboxST configuration • Wrong terminal board is configured in the ToolboxST application • I/O pack or module plugged into wrong jack on terminal board, or wrong jack number in ToolboxST configuration • I/O pack or module is configured in the ToolboxST application, but configuration is not downloaded to the controller • I/O pack or module in program mode Solution • Verify that the I/O pack or module configuration (such as Type, HW Form, Bar Code, position) matches the actual hardware. • Perform a build and download the configuration to the controller, wait for pack communication status to change, then scan and download to the I/O pack or module. • Manually restart the I/O pack or module. 22 Description ToolboxST application detects a diagnostic status signal (...L3DIAG, ATTN, and/or LINK_OK...) is [ ]; therefore, the status signal is inaccurate, unknown, or indeterminate Possible Cause • I/O status signal quality in warning state • Signal quality unhealthy, forced, or being simulated • Status information inaccurate Solution • Check status signal health. • Remove the force or simulated condition applied to the status signal. Note This alarm is not reported to the WorkstationST Alarm Viewer. This alarm is generated by the ToolboxST application, not by the firmware. Controllers GEH-6855_Vol_II System Guide 41 Public Information

ToolboxST application detects a major difference in [ ] controller application code

Possible Cause • Compressing variables, EGD pages, distributed I/O, or NVRAM • Changing frame or background period • Changing controller or network redundancy • Changing controller platform or NTP client mode • Changing controller host name or IP address • Changing IONet IP address • Adding/removing first/last linking device (PFFA), respectively • Removing a WCBM module • Changing from multicast to broadcast (or vice-versa) I/O communication • Adding the first Shared I/O module or connecting the first Controller to Controller I/O variable • Removing the last Modbus Slave point • Disabling controller web pages • Disabling Wind Compress Data Log • Disabling Wind Farm Management System Solution Rebuild the controller and download. Note This alarm is not reported to the WorkstationST Alarm Viewer. This alarm is generated by the ToolboxST application, not by the firmware. 42 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

ToolboxST application cannot retrieve diagnostics information from I/O pack [ ]

Possible Cause • Cannot get requested information from I/O pack or module • Communication program failure • I/O pack or module unable to retrieve IP address • Terminal board Bar Code entered incorrectly in ToolboxST configuration • Wrong terminal board configured in ToolboxST application • I/O pack or module plugged into wrong jack on terminal board, or wrong jack number in ToolboxST configuration • I/O pack or module configured in ToolboxST application, but configuration not downloaded to controller • I/O pack or module in program mode • I/O pack or module not able to load firmware • Power failure to the I/O pack or module Solution • Verify that the I/O pack configuration (such as Type, HW Form, Bar Code, position) matches the actual hardware. • Build and download the configuration to the controller, wait for pack communication status to change, then scan and download to the I/O pack or module. • Manually restart the I/O pack or module. • Check network cables for proper connection. • Verify that the switch is functioning correctly. Note This alarm is not reported to the WorkstationST Alarm Viewer. This alarm is generated by the ToolboxST application, not by the firmware. Controllers GEH-6855_Vol_II System Guide 43 Public Information

Note This alarm is obsolete.

Description Control/Status communication Error: [ ] Possible Cause • Cannot get diagnostic information from I/O pack or module • I/O pack or module not able to load firmware Solution • Verify that the I/O pack or module configuration is correct. • Rebuild the application and download the firmware and application to the I/O pack or module. • Check network cables for proper connection. • Verify that the switch is functioning correctly. 259 Description Application Runtime Error - [ ] Frame overruns occurred Possible Cause Overloaded processor sequencer malfunction (one or more frame overruns occurred) Solution For a controller, perform the following to increase the frame idle time: • Reduce the application or increase the EGD period. • Upgrade the controller to one with a faster processor. • Replace the controller. For an I/O module, perform the following: • From the ToolboxST application, rebuild the system, then download the application and configuration to the I/O module. • Replace the I/O module. 44 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Application Runtime Error - [ ] Frame skips occurred

Possible Cause There is an overloaded processor or a processor malfunction. Frame number skips were detected. The frame number should incrementally increase during Controlling state. Solution For a controller, do the following: • Reduce the application or increase the EGD period to reduce the processor load. • Upgrade the controller to one with a faster processor. • Replace the controller. For an I/O module, do the following: • From the ToolboxST application, rebuild the system, then download the application and configuration to the I/O module. • Replace the I/O module. 279 Description Could not determine platform type from hardware Possible Cause • During commissioning/maintenance: Incorrect firmware version or hardware malfunction (firmware could not recognize host hardware type) • During normal operation: Hardware failure Solution • Verify that all connectors are aligned properly and fully seated. • Check the firmware version for compatibility with platform. If correct, replace the controller. Controllers GEH-6855_Vol_II System Guide 45 Public Information

Platform hardware does not match configuration

Possible Cause • During commissioning/maintenance: Platform type identified in the application configuration does not match actual hardware • During normal operation: Hardware failure Solution • Fix the platform type in the ToolboxST application. From the General tab, select General Properties and Platform. • Rebuild and download the application. • If problem persists, replace the controller. 282 Description Firmware Load Error - application independent processes failed to initialize Possible Cause Runtime malfunction. An application-independent firmware process could not be started successfully. Solution • Reload firmware and application and restart. • If controller is a UCSA, try formatting and reloading the flash memory. • If I/O pack has diagnostic: try to re-download the base load. • Replace the controller or I/O module. 283 Description Firmware error - Internal process crashed Possible Cause Runtime or hardware malfunction (runtime process failed). Solution • Reload firmware and application and restart. • If controller is a UCSA, try formatting and reloading the flash memory. • If this does not work, replace the controller. 46 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Application Error - application overrunning the frame

Possible Cause Application cannot start within frame. Solution Check application loading and reduce the amount of application code or frequency of execution. Build application and download to all controllers. 294 Description Controller CPU overtemperature, Temp [ ] °C, Threshold [ ] °C Possible Cause • Excessive ambient temperature • Hardware malfunction • Fan loss Solution • Check the fan (if applicable), the ambient temperature, and for the presence of dust. • Replace the controller. 300 Description Application Code Load Failure Possible Cause During commissioning/maintenance: • Invalid application configuration During normal operation: • Firmware or hardware malfunction Solution • Rebuild and download the application to all controllers. • Reload firmware and application. • If problem persists, replace the controller. Controllers GEH-6855_Vol_II System Guide 47 Public Information

Process Alarm Buffers Full - controller can miss alarm transitions

Possible Cause • Multiple alarm variables changing state too quickly to transmit all transitions • Excessive alarms in queue (Plant-wide system failures) Solution During commissioning/maintenance: • Reduce the number of alarms that can change state at the same time (filter alarm variables in the application code). During normal operation: • Eliminate the conditions causing excessive process alarms. 321 Description Internal Runtime error - Process Alarms not being scanned Possible Cause Runtime malfunction: alarms not being scanned. Controller may restart on software watchdog timeout due to processor overload. Solution • Reload firmware and application, and restart. • If problem persists, replace the controller. 322 Description Configuration Load error - Too many consumed EGD variables for Fault Tolerant EGD Possible Cause Number of relevant, consumed UDH EGD variables exceeds fault tolerant EGD limitation of 1400 bytes of data. Normal UDH EGD operation not affected; however, in the event of UDH EGD failure, some consumed variables may not be transmitted to redundant controllers over the IONet (if applicable). Solution During commissioning/maintenance: • Reduce the amount of relevant, consumed UDH EGD data by removing the appropriate number of variables from EGD pages. 323 Description EGD Error - Fault Tolerant EGD activated Possible Cause EGD exchange timeout occurred on requesting controller. Redundant processor (if applicable) is unable to receive UDH EGD inputs and requested that EGD data be transferred over the IONet. Solution • Verify that all redundant controllers on the UDH network are receiving all expected EGD exchanges. • Verify that all relevant devices are powered on and producing data on the network. 48 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

EGD Error - Fault Tolerant EGD data requested

Possible Cause An EGD exchange timeout occurred on the requesting controller. Redundant processor (if applicable) unable to receive UDH EGD inputs and has requested that EGD data be transferred over the IONet. Solution • Check UDH network and verify that all redundant controllers are receiving all expected EGD exchanges. • Verify that all relevant devices are powered on and producing data on the network. 326 Description Communication lost from R processor Possible Cause • IONet or hardware malfunction • S or T processor in redundant system lost communication with R processor • Missing cable from the controller to the Unit Data Highway (UDH) network switch Solution • Go online with the R processor. Verify that the processor is in the Controlling state. If not communicating or in Controlling state, restart the processor. • Check for disconnected IONet cables or malfunctioning switches. • Rebuild and download the application. • Check for a defective Ethernet cable to network switch. • Check for a defective network switch: − Place the Ethernet cable into empty port. − If the problem persists, replace the network switch. Controllers GEH-6855_Vol_II System Guide 49 Public Information

Communication lost from S processor

Possible Cause • IONet or hardware malfunction • R or T processor in redundant system lost communication with S processor • Missing cable from the controller to the Unit Data Highway (UDH) network switch Solution • Go online with the S processor. Verify that the processor is in the Controlling state. If not communicating or in Controlling state, restart the processor. • Check for disconnected IONet cables or malfunctioning switches. • Rebuild and download the application. • Check for a defective Ethernet cable to network switch. • Check for a defective network switch: − Place the Ethernet cable into empty port. − If the problem persists, replace the network switch. 328 Description Communication lost from T processor Possible Cause • IONet or hardware malfunction • R or S processor in redundant system lost communication with T processor • Missing cable from the controller to the Unit Data Highway (UDH) network switch Solution • Go online with the T processor. Verify that the processor is in the Controlling state. If not communicating or in Controlling state, restart the processor. • Check for disconnected IONet cables or malfunctioning switches. • Rebuild and download the application. • Check for a bad Ethernet cable to network switch. • Check for a bad network switch: − Place the Ethernet cable into empty port. − If the problem persists, replace the network switch. 50 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Startup sequence failed - Data initialization timeout R processor

Possible Cause Controller unable to complete startup data initialization • IONet malfunction • Controllers have different application revisions • One or more controllers powered down • Controller overloaded by external command messages Solution • Check for disconnected IONet cables or malfunctioning network switches. • Rebuild and download the application. • Verify that all controllers are powered on. • Disable all other command senders (for example, Modbus masters) until controller is online. 330 Description Startup sequence failed - Data initialization timeout S processor Possible Cause Controller is unable to complete startup data initialization. • IONet malfunction • Controllers have different application revisions • One or more controllers are powered down • Controller is overloaded by external command messages. Solution • Check for disconnected IONet cables or malfunctioning network switches. • Rebuild and download application. • Ensure all controllers are powered up. • Disable all other command senders (for example, Modbus masters) until controller is online. Controllers GEH-6855_Vol_II System Guide 51 Public Information

Startup sequence failed - Data initialization timeout T processor

Possible Cause Controller is unable to complete startup data initialization. • IONet malfunction • Controllers have different application revisions • One or more controllers are powered down • Controller is overloaded by external command messages Solution • Check for disconnected IONet cables or malfunctioning network switches. • Rebuild and download application. • Ensure all controllers are powered up. • Disable all other command senders (for example, Modbus masters) until controller is online. 332 Description Overtemperature - Controller rebooted and throttled Possible Cause • Excessive ambient temperature • Hardware malfunction • Fan loss Solution • Check ambient temperature. • Check for dust buildup on the cabinet filters, controller, and power supply. • Replace the controller. • Check fans. 334 Description Application Error – [ ] Frame Skips Detected Possible Cause • Hardware or IONet malfunction • Frame number skips detected. Frame number should monotonically increase until rollover; alarm occurs following a single frame number skips in successive frames. Solution • Check IONet (switches, cables). • Replace the controller. 52 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Memory Verification Failed – Firmware Processes

Possible Cause A modification has occurred in the code segment for one of the processes. This indicates that a hardware memory failure has occurred. Solution Replace the controller. 336 Description Controller is Unlocked Possible Cause • Leaving Data Init control state and not locked • The controller is unlocked through the ToolboxST application. Solution From ToolboxST application, lock the controllers before running safety functions. 337 Description Output exchange disagreement detected Possible Cause IONet malfunction or hardware problem. For at least one output, a difference was detected between the controller outputs. This alarm remains active until the controllers agree on all outputs. A difference for non-Boolean data generally indicates a deviation of more than 10% from the median value or no IONet EGD configuration is present. For median values near zero, the variation exceeds integer 2 or real value 0.2. Solution • For the Mark VIe runtime, use the ToolboxST disagreement display (View | Disagreements) to determine which variables are in disagreement. • In the application, avoid use of global variable 'ControllerID' and avoid the use of sequencing block 'USB_HB'. • Check IONet (switches, cables); rebuild and download application to all processors. If the problem persists, replace the processor module. 347 Description Running Application does not match the Branded Application Possible Cause Application not branded or different from branded version. Note The purpose of branding is to label a verified safety application, and to ensure that it is running. Solution • Reload the branded application to the controller and I/O packs. • Use the ToolboxST application to brand the currently running application. Controllers GEH-6855_Vol_II System Guide 53 Public Information

Intermittent Communications on IONet1 – Packet Loss Exceeded [ ]%

Possible Cause • Power cycled on I/O producer (controller or I/O module) • Faulty Ethernet cable from I/O pack to IONet switch and/or from IONet switch to controller. • Faulty IONet switch • I/O message corruption • Communication errors occurred on more than 5% of data transmissions on IONet1 Solution • Check for evidence of I/O pack restart (diagnostic alarms, error logs). • Replace Ethernet cable(s). • Replace the I/O pack. • Move the I/O pack’s Ethernet cable into an empty IONet switch port. If problem persists, replace the IONet switch. 349 Description Intermittent Communications on IONet2 – Packet Loss Exceeded [ ]% Possible Cause • Power cycled on I/O producer (controller or I/O module) • Faulty Ethernet cable from I/O pack to IONet switch and/or from IONet switch to controller. • Faulty IONet switch • I/O message corruption • Communication errors occurred on more than 5% of data transmissions on IONet2 Solution • Check for evidence of I/O pack restart (diagnostic alarms, error logs). • Replace Ethernet cable(s). • Replace the I/O pack. • Move the I/O pack’s Ethernet cable into an empty IONet switch port. If problem persists, replace the IONet switch. 350 Description Intermittent Communications on IONet3 – Packet Loss Exceeded [ ]% Possible Cause • Power cycled on I/O producer (controller or I/O module) • Faulty Ethernet cable from I/O pack to IONet switch and/or from IONet switch to controller. • Faulty IONet switch • I/O message corruption • Communication errors occurred on more than 5% of data transmissions on IONet3 Solution • Check for evidence of I/O pack restart (diagnostic alarms, error logs). • Replace Ethernet cable(s). • Replace the I/O pack. • Move the I/O pack’s Ethernet cable into an empty IONet switch port. If problem persists, replace the IONet switch. 54 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Memory Validation Failed – Blockware Data Structures

Possible Cause A hardware memory failure because application process data was modified (data should not change after controller goes online) Solution Replace the controller. 353 Description Memory Validation Failed – Configuration Shared Memory Possible Cause A hardware memory failure because system process data was modified (data should not change after controller goes online) Solution Replace the controller. 354 Description Memory Validation Failed – IONet Data Structures Possible Cause There is a hardware memory failure because IONet process data was modified (data should not change after the controller goes online) Solution Replace the controller. 355 Description State Exchange Voter disagreement detected Possible Cause • State Exchange disagreement found • Application sequencing error • IONet malfunction or hardware problem Solution • Use the ToolboxST disagreement display (View | Disagreements) to determine which variables are in disagreement. • In the application, avoid use of global variable 'ControllerID' and avoid the use of 'USB_HB' block. • Check IONet (switches, cables). If problem persists, replace the processor module. 356 Description NANs detected in CALC or NAN_BREAKER block Possible Cause • NaN (Invalid floating point number) received from I/O interface • Hardware problem Solution • Check for external devices that may be sending NaNs to the controller. • If conditions persists, replace the controller. Controllers GEH-6855_Vol_II System Guide 55 Public Information

Internal Runtime error - Sequencer out-of-order or overrun detected

Possible Cause There is a possible hardware malfunction. Sequencer critical clients were scheduled out of order or were overrun. This alarm occurs following three successive frames of sequencer critical client out-of-order detections. After five, the controller is put into the FAILURE control state. Solution Replace the controller. 358 Description Internal Runtime error - Sequencer client execution underrun Possible Cause Possible hardware malfunction. Sequencer critical client underrun detected. Alarm occurs after a sequencer critical client has been run slower than its nominal rate three times in a row; after five, controller put in FAILURE control state. Solution • Ignore this alarm if it occurs during a restart of the controller. • If the alarm occurs during normal operation, then replace the controller. 359 Description Internal Runtime error - Sequencer client execution overrun Possible Cause Possible hardware malfunction. Sequencer critical client overrun detected. Alarm occurs after a sequencer critical client has been run faster than its nominal rate three times in a row; after five, controller put in FAILURE control state. Solution • Ignore alarm if it occurs during a restart of the controller. • Replace the controller, if the alarm occurs during normal operation. 360 Description Internal Runtime error - Sequencer frame period out-of-bounds (±15%) Possible Cause Possible hardware malfunction. Frame period greater than ±15% of nominal. Alarm occurs following frame period out-of-bounds condition occurring three frames in a row; after five, controller put in FAILURE control state. Solution • Ignore alarm if it occurs during a restart of the controller. • Replace the controller, if the alarm occurs during normal operation. 56 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Internal Runtime error - Sequencer frame state timeout out-of-bounds (±15%)

Possible Cause Possible hardware malfunction. Sequencer frame state timeout greater than ±15% of nominal. Alarm occurs following a sequencer frame state timeout being out-of-bounds three frames in row; after five, controller put in FAILURE control state. Solution • Ignore alarm if it occurs during a restart of the controller. • Replace the controller, if the alarm occurs during normal operation. 362 Description Internal Runtime error - Sequencer frame number skip detected Possible Cause Possible hardware or IONet malfunction. Frame number skips detected. Frame number should monotonically increase until rollover; alarm occurs following three skips in a row, after five, controller put in FAILURE control state. Solution • Ignore this alarm if it occurs during a restart of the controller. During normal operation: • Check for hardware or network switch malfunction. • Check for loose or defective network cables. • Replace the controller. 363 Description Memory Validation failed - Sequencer data structures Possible Cause Hardware memory failure. Sequencer process data was modified (data should not change after the controller is online). Solution Replace the controller. 364 Description Too many state voter disagreements detected Possible Cause • State exchange voter disagreement overflow. System exceeded the limit of 128 simultaneous disagreements at once. • Application error • Hardware problem or IONet malfunction Solution • Use the ToolboxST disagreement display (View | Disagreements) to determine which variables are in disagreement. • In the application, avoid use of global variable 'ControllerID' and avoid the use of 'USB_HB' block. • Check IONet (switches, cables). • If problem persists, replace the controller. Controllers GEH-6855_Vol_II System Guide 57 Public Information

Invalid Calibration Settings

Possible Cause • Calibration file not detected • Calibration file corrupted • Calibration constants invalid • Hardware Failure Solution Replace the module. 375 Description Controller has entered Quality Control (QC) Mode Possible Cause The device has received a command to enter factory QC mode. Solution Reboot the device. 462 Description Hardware Reconfigured: Reboot by removing and reapplying power Possible Cause Flash memory file system corruption. Solution • After reapplying power, Rebuild and download baseload, firmware and application. • If the problem persists, replace the controller. 463 Description Internal runtime error - Could not create the Command and Event Log (CEL) file Possible Cause Internal runtime error. Could not create the CEL file. Solution • Rebuild and download baseload, firmware, and application to the controller. • If the problem persists, replace the controller. 464 Description Ethernet Interface [ ] disabled due to excessive traffic Possible Cause Network interface has been disabled to protect itself from excessive activity on the network. Solution • Check for network loops. • Monitor network activity and remove excessive traffic. 58 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Ethernet Interface [ ] disabled due to excessive traffic

Possible Cause Network interface has been disabled to protect itself from excessive activity on the network Solution • Check for network loops. • Monitor network activity and remove excessive traffic. 466 Description Ethernet Interface [ ] disabled due to excessive traffic Possible Cause Network interface has been disabled to protect itself from excessive activity on the network Solution • Check for network loops. • Monitor network activity and remove excessive traffic. 467 Description Ethernet Interface [ ] disabled due to excessive traffic Possible Cause Network interface has been disabled to protect itself from excessive activity on the network. Solution • Check for network loops. • Monitor network activity and remove excessive traffic. 468 Description Ethernet Interface [ ] disabled due to excessive traffic Possible Cause Network interface has been disabled to protect itself from excessive activity on the network. Solution • Check for network loops. • Monitor network activity and remove excessive traffic. Controllers GEH-6855_Vol_II System Guide 59 Public Information

UDH EGD fault detected by the R processor

Possible Cause • UDH EGD producer is powered down • Producer is unhealthy • Ethernet connection(s) failure Solution • Ensure all EGD producers are powered on and healthy. • Check for a defective Ethernet cable from producer to network switch. Replace the cable(s). • Check for a defective network switch by placing the producer's Ethernet cable into an empty port. If the problem persists, replace the network switch. • Replace the processor module. 470 Description UDH EGD fault detected by the S processor Possible Cause • UDH EGD producer is powered down • Producer is unhealthy • Ethernet connection(s) failure Solution • Ensure all EGD producers are powered up and healthy. • Check for a defective Ethernet cable from producer to network switch. Replace the cable(s). • Check for a defective network switch by placing the producer's Ethernet cable into an empty port. If the problem persists, replace the network switch. • Replace the producer processor module. 471 Description UDH EGD fault detected by the T processor Possible Cause • UDH EGD producer is powered down • Producer is unhealthy • Ethernet connection(s) failure Solution • Ensure all EGD producers are powered up and healthy. • Check for a defective Ethernet cable from producer to network switch. Replace the cable(s). • Check for a defective network switch by placing the producer's Ethernet cable into an empty port. If the problem persists, replace the network switch. • Replace the producer processor module. 60 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Auto-Reconfiguration server installation is incomplete

Possible Cause • A download from the ToolboxST application to an I/O pack and/or the Auto-Reconfiguration server has failed • Not all of the I/O packs were selected for download Solution Perform a scan and download using the ToolboxST application. 487 Description Auto-Reconfiguration server failed scanning or downloading an I/O pack Possible Cause At least one I/O pack is in an unexpected state that the Auto-Reconfiguration server is unable to handle Solution • Cycle power on the I/O pack. • Perform a scan and download using the ToolboxST application. • Replace the I/O pack. 488 Description EGD Error - Could not configure consumed exchanges from one or more Producers Possible Cause • Producer EGD Page(s) configured incorrectly • Producer(s) powered down • Network connectivity intermittent or severed • Internal Firmware failure Solution • Rectify configuration error. Compress all pages and download application to Producer. • Ensure each Producer is powered on and in the Controlling state. • Refer to the Network Troubleshooting guide for possible solutions. • Replace the Consumer and/or Producer hardware. Controllers GEH-6855_Vol_II System Guide 61 Public Information

EGD Error - One or more consumed exchanges contain unbound variables

Possible Cause • An EGD variable has been removed from a Producer's EGD configuration • An EGD variable has been added to a different Producer's EGD Page from its original EGD Page Solution • Add the offending variable to the Producer's EGD configuration, compress the Page and download the application to the Producer. • Remove the reference to the offending variable from the Consumer's application code; build and download application to the Consumer. • Compress the EGD Page in the Producer where the variable has been added; build and download the application to the Producer. 490 Description Software watchdog has been disabled Possible Cause • A runtime malfunction has disabled the software watchdog protective function • An invalid version of firmware has been downloaded Solution • Reload base load, firmware, and application and restart. • If using a UCSA, reformat the flash and reload the firmware. • I/O pack or module: re-download the base load. • If this does not work, replace the controller or I/O module. 491 Description Hardware watchdog has been disabled Possible Cause • A runtime malfunction has disabled the hardware watchdog protective function • A hardware failure has disabled the hardware watchdog protective function Solution • Reload firmware and restart. • If problem persists, replace hardware. 62 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

CDH EGD fault detected by the R processor

Possible Cause • CDH EGD producer is powered down • Producer is unhealthy • Ethernet connection(s) failure Solution • Ensure all EGD producers are powered up and healthy. • Check for a defective Ethernet cable from producer to network switch. Replace the cable(s). • Check for a defective network switch by placing the producer's Ethernet cable into an empty port. If the problem persists, replace the network switch. • Replace the producer processor module. 494 Description CDH EGD fault detected by the S processor Possible Cause • CDH EGD producer is powered down • Producer is unhealthy • Ethernet connection(s) failure Solution • Ensure all EGD producers are powered up and healthy. • Check for a defective Ethernet cable from producer to network switch. Replace the cable(s). • Check for a defective network switch by placing the producer's Ethernet cable into an empty port. If the problem persists, replace the network switch. • Replace the producer processor module. Controllers GEH-6855_Vol_II System Guide 63 Public Information

CDH EGD fault detected by the T processor

Possible Cause • CDH EGD producer is powered down • Producer is unhealthy • Ethernet connection(s) failure Solution • Ensure all EGD producers are powered up and healthy. • Check for a defective Ethernet cable from producer to network switch. Replace the cable(s). • Check for a defective network switch by placing the producer's Ethernet cable into an empty port. If the problem persists, replace the network switch. • Replace the producer processor module. 496 Description Failed to incorporate the user-configured frame state timeouts Possible Cause • Invalid user-configured frame state timeout values • Failed to parse the user-configured frame state timeouts file Solution • Timeout values configured by the user must satisfy the condition Frame Rate > Output Timeout > App Timeout > Input Timeout > 0. • Rebuild the application and force an offline download of the application to the controller. 497-498 Description Fan loss detected for controller fan [ ] Possible Cause • Hardware malfunction • Fan power not applied Solution • Check the fan. • Verify that the power connector is properly inserted. • Replace the fan. 64 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Total memory consumption has exceeded [ ] percent

Possible Cause Memory usage is driven from three functions: • The online download procedure temporarily stores the previous and new application configuration in memory. • The footprint of the application configuration/code has been enlarged. • Memory usage can grow over time if there is a memory leak. Solution • The alarm should return to normal state after download is complete. • Reduce the content of the application configuration/code. • To address a memory leak, reboot the device to reinitialize baseline memory use. Monitor for reoccurrence and contact your GE representative. 502 Description Syspage inconsistency detected Possible Cause Memory corruption Solution Restart the controller to re-initialize QNX syspage. 503 Description Communications timeout with Remote System Log Server Possible Cause • Remote Syslog server not in network • Remote Syslog server down • Incorrect Remote Syslog server IP address in system configuration • Network issue (cables/switch) connecting controller to Remote Syslog server Solution • Verify that the Remote Syslog server is in operation. • Verify that the correct Remote Syslog server IP address in the system configuration. • Check the network connections. Controllers GEH-6855_Vol_II System Guide 65 Public Information

Unauthorized executable was detected and terminated

Possible Cause When in Secure mode, the controller only permits authorized executables. An unauthorized executable has been detected and dismissed. Solution • Inspect the syslog/error log messages • Rebuild and download the baseload, firmware, and application to the controller. • Re-install the ControlST application, then rebuild and download the baseload, firmware, and application to the controller. 505 Description R network shared I/O module inputs unhealthy Possible Cause • I/O module restarting or restarted • I/O module application/configuration missing • Application/configuration does not match in I/O module and controller • Failed Ethernet connection between I/O module and controller • Ethernet cable inserted into wrong connector on I/O module Note When using the Shared IONet feature, this alarm is generated if there is a problem with receiving inputs from any shared I/O module on the R IONet. Refer to Mark Controllers Shared IONet User Guide (GEH-6812). Solution • Rebuild and download application/parameters to all controllers and I/O modules. • Reload firmware and parameters to the affected I/O module. • Reload firmware and application to all controllers. • If the problem persists, replace the affected I/O module, then replace the controller. 66 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

S network shared I/O module inputs unhealthy

Possible Cause • I/O module restarting or restarted • I/O module application/configuration missing • Application/configuration does not match in I/O module and controller • Failed Ethernet connection between I/O module and controller • Ethernet cable inserted into wrong connector on I/O module Note When using the Shared IONet feature, this alarm is generated if there is a problem with receiving inputs from any shared I/O module on the S IONet. Refer to Mark Controllers Shared IONet User Guide (GEH-6812). Solution • Rebuild and download application/parameters to all controllers and I/O modules. • Reload firmware and parameters to the affected I/O module. • Reload firmware and application to all controllers. • If the problem persists, replace the affected I/O module, then replace the controller. 507 Description T network shared I/O module inputs unhealthy Possible Cause • I/O module restarting or restarted • I/O module application/configuration missing • Application/configuration does not match in I/O module and controller • Failed Ethernet connection between I/O module and controller • Ethernet cable inserted into wrong connector on I/O module Note When using the Shared IONet feature, this alarm is generated if there is a problem with receiving inputs from any shared I/O module on the T IONet. Refer to Mark Controllers Shared IONet User Guide (GEH-6812). Solution • Rebuild and download application/parameters to all controllers and I/O modules. • Reload firmware and parameters to the affected I/O module. • Reload firmware and application to all controllers. • If the problem persists, replace the affected I/O module, then replace the controller. Controllers GEH-6855_Vol_II System Guide 67 Public Information

Application mismatch between redundant controllers

Possible Cause • One processor installed new application code while the other processor(s) did not • Processor was replaced and application code was built with a different version of the ToolboxST application Solution • Rebuild and download the application code to all controllers. • Verify that the Application Code checkbox is selected in the download wizard for all controllers prior to downloading. 509 Description Controller certificate has been revoked Possible Cause • Controller certificate is in the Certificate Revocation List (CRL) • Certificate Authority (CA) Administrator revoked the certificate Solution • Transition the controller from Secure to Open state then back to Secure to generate a new certificate and private key. • Contact the Certificate Authority (CA) Administrator. 510 Description Controller certificate will expire within 30 days Possible Cause Controller certificate will expire within 30 days Solution • Transition the controller from Secure to Open state then back to Secure to generate a new certificate and private key. • Contact the Certificate Authority (CA) Administrator. 68 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Controller certificate will expire within seven days

Possible Cause Controller certificate will expire within seven days Solution • Transition the controller from Secure to Open state then back to Secure to generate a new certificate and private key. • Contact the Certificate Authority (CA) Administrator. 512 Description Controller certificate will expire in one day Possible Cause Controller certificate will expire in one day Solution • Transition the controller from Secure to Open state then back to Secure to generate a new certificate and private key. • Contact the Certificate Authority (CA) Administrator. 513 Description Controller certificate has expired; controller is no longer in Secure state Possible Cause • Controller is not in Secure state • Controller certificate has expired Solution • Place the controller in the Secure state. • Contact the Certificate Authority (CA) Administrator. Controllers GEH-6855_Vol_II System Guide 69 Public Information

Controller To Controller (C2C) Inputs Unhealthy on IONet [ ] from ControlSet [ ]

Possible Cause • Failed Ethernet connection between controllers • Ethernet cable is inserted into the wrong connector on the IONet switch • Controller to Controller (C2C) packet production is restarting or not occurring • Application or configuration is missing in the controller or does not match in both controllers Note A control set is a controller in a Shared IONet group. There are 24 Controller to Controller (C2C) diagnostic alarms assigned for eight control sets. Each control set contains three diagnostics for its IONets. Solution • Check for Ethernet connectivity between the controllers. • Rebuild and download the application to all controllers. • Reload the firmware and application to all controllers. • If the problem persists, replace the affected switch and Ethernet cables, then replace the controller. 538 Description Certificate Authority (CA) certificate will expire within 30 days Possible Cause CA certificate will expire within 30 days Solution Contact the CA Administrator. 539 Description Certificate Authority (CA) certificate will expire within seven days Possible Cause CA certificate will expire within seven days Solution Contact the CA Administrator. 540 Description Certificate Authority (CA) certificate will expire within one day Possible Cause CA certificate will expire within one day Solution Contact the CA Administrator. 70 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Certificate Authority (CA) certificate has expired; controller is no longer in Secure state

Possible Cause CA certificate has expired Solution Contact the CA Administrator. 542 Description Certificate Revocation List (CRL) has expired Possible Cause CRL has expired Solution 1. Contact the CA Administrator and request/confirm the renewal of the CRL. 2. After the CRL is renewed, from the Mark VIe Device menu select View | Diagnostics | Controller Advanced Diagnostics. 3. Expand the Commands tree, expand the Diagnostics tree, and double-click Get CRL for controller from CA Server. 4. Confirm the reply, CRL received successfully, which indicates that the Mark VIe to CA Server connection is healthy. 5. Close the Advanced Diagnostics Commands window. 543 Description Total memory consumption has exceeded [ ] percent Possible Cause • Memory leak • Application code is too large Solution • Decrease memory usage. • Restart the controller. 544 Description Communications error with Certificate Authority Server Possible Cause • Certificate Authority (CA) server not in network or not in operation (server is down) • Incorrect CA server IP address in system configuration • Network issue (cables/switch) connecting controller to CA server Solution • Verify that the CA server is in operation. • Verify that the CA server IP address is correct in the system configuration. • Check the network connections. Controllers GEH-6855_Vol_II System Guide 71 Public Information

Active PFFA diagnostics detected

Possible Cause At least one configured PFFA module contains an active diagnostic. Since each controller within a control set monitors the diagnostic conditions of PFFA modules and connected Fieldbus devices, PFFA diagnostics may differ between the individual controllers. Solution • If there are active PFFA diagnostics in the WorkstationST Alarm Viewer, correct those issues. • If there are no active PFFA diagnostics in the Alarm Viewer, go online specifically to the controller with this 545 diagnostic using the ToolboxST application. From the Component Editor Hardware tab, select the PFFA with active diagnostics, and correct the identified issues. 546 Description This component is or has been in factory test mode. Possible Cause The controller or I/O pack has received the command to enter factory test mode. Solution Reboot the I/O pack or controller. 547 Description Default user password detected Possible Cause The controller password is the default value. Solution From the ToolboxST application, set the password. Note It is the user’s responsibility to change the default password to a unique password. If you do not know the default password, contact the nearest GE Sales or Service Office, or an authorized GE Sales Representative. To change the controller password, refer to the ToolboxST User Guide for Mark VIeS Functional Safety Systems (GEH-6862), the section Controller Password Change. 72 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Inputs unhealthy on IO Module [ ], R pack IONet [ ] - Message Timeout

Possible Cause • I/O pack restarting or restarted • I/O pack application/configuration is missing • Application/configuration does not match in the I/O pack and controller • Failed Ethernet connection between I/O pack and controller • Ethernet cable inserted into wrong connector on I/O pack Solution • Reset all diagnostic alarms. • Rebuild and download application to all controllers and I/O packs. • Reload firmware and application. • Verify that Ethernet cable on I/O pack matches the ToolboxST configuration. • Check for faulty Ethernet cable from pack to network switch and/or from switch to controller. Replace cable(s) if necessary. • Replace the I/O pack. • Defective network switch, place I/O pack's Ethernet cable into empty port. If problem persists, replace network switch. Controllers GEH-6855_Vol_II System Guide 73 Public Information

Inputs unhealthy on IO Module [ ], S pack IONet [ ] - Message Timeout

Possible Cause • I/O pack restarting or restarted • I/O pack application/configuration is missing • Application/configuration does not match in the I/O pack and controller • Failed Ethernet connection between I/O pack and controller • Ethernet cable inserted into wrong connector on I/O pack Solution • Reset all diagnostic alarms. • Rebuild and download application to all controllers and I/O packs. • Reload firmware and application. • Verify that Ethernet cable on I/O pack matches the ToolboxST configuration. • Check for faulty Ethernet cable from I/O pack to network switch and/or from switch to controller. Replace cable(s) if necessary. • Replace the I/O pack. • Defective network switch, place I/O pack's Ethernet cable into empty port. If problem persists, replace network switch. 1000-2024 Description Inputs unhealthy on IO Module [ ], T pack IONet [ ] - Message Timeout Possible Cause • Pack restarting or restarted • I/O pack application/configuration is missing • Application/configuration does not match in the I/O pack and controller • Failed Ethernet connection between I/O pack and controller • Ethernet cable inserted into wrong connector on I/O pack Solution • Reset all diagnostic alarms. • Rebuild and download application to all controllers and I/O packs. • Reload firmware and application. • Verify that Ethernet cable on I/O pack matches the ToolboxST configuration. • Check for faulty Ethernet cable from I/O pack to network switch and/or from switch to controller. Replace cable(s) if necessary. • Replace the I/O pack. • Defective network switch, place I/O pack's Ethernet cable into empty port. If problem persists, replace network switch. 74 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Inputs unhealthy on IO Module [ ], IONet [ ] - Message Timeout

Possible Cause • I/O pack restarting or restarted • I/O pack application/configuration is missing • Application/configuration does not match in the I/O pack and controller • Failed Ethernet connection between I/O pack and controller • Ethernet cable inserted into wrong connector on I/O pack Solution • Reset all diagnostic alarms. • Rebuild and download application to all controllers and I/O packs. • Reload firmware and application. • Verify that Ethernet cable on I/O pack matches the ToolboxST configuration. • Check for faulty Ethernet cable from I/O pack to network switch and/or from switch to controller. Replace cable(s) if necessary. • Replace the I/O pack. • Defective network switch, place I/O pack's Ethernet cable into empty port. If problem persists, replace network switch. 1000-2024 Description Inputs unhealthy on IO Module [ ], R pack IONet [ ] - Message Length not valid Possible Cause Application/configuration does not match in the I/O pack and controller. Solution • Rebuild and download application/parameters to all controllers and I/O packs. • Reload firmware and parameters to the affected I/O pack. • Reload firmware and application to all controllers. • If problem persists, replace affected I/O pack, then replace controller. 1000-2024 Description Inputs unhealthy on IO Module [ ], S pack IONet [ ] - Message Length not valid Possible Cause Application/configuration does not match in the I/O pack and controller. Solution • Rebuild and download application/parameters to all controllers and I/O packs. • Reload firmware and parameters to the affected I/O pack. • Reload firmware and application to all controllers. • If problem persists, replace affected I/O pack, then replace controller. Controllers GEH-6855_Vol_II System Guide 75 Public Information

Inputs unhealthy on IO Module [ ], T pack IONet [ ] - Message Length not valid

Possible Cause Application/configuration does not match in the I/O pack and controller. Solution • Rebuild and download application/parameters to all controllers and I/O packs. • Reload firmware and parameters to the affected I/O pack. • Reload firmware and application to all controllers. • If problem persists, replace affected I/O pack, then replace controller. 1000-2024 Description Inputs unhealthy on IO Module [ ], IONet [ ] - Message Length not valid Possible Cause Application/configuration does not match in the I/O pack and controller. Solution • Rebuild and download application/parameters to all controllers and I/O packs. • Reload firmware and parameters to the affected I/O pack. • Reload firmware and application to all controllers. • If problem persists, replace affected I/O pack, then replace controller. 1000-2024 Description Inputs unhealthy on IO Module [ ], R Pack IONet [ ] - Major Signature Mismatch Possible Cause Application/configuration does not match in the I/O pack and controller. Solution • Rebuild and download application/parameters to all controllers and I/O packs. • Reload firmware and parameters to the affected I/O pack. • Reload firmware and application to all controllers. • If problem persists, replace affected I/O pack, then replace controller. 76 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Inputs unhealthy on IO Module [ ], S Pack IONet [ ] - Major Signature Mismatch

Possible Cause Application/configuration does not match in the I/O pack and controller. Solution • Rebuild and download application/parameters to all controllers and I/O packs. • Reload firmware and parameters to the affected I/O pack. • Reload firmware and application to all controllers. • If problem persists, replace affected I/O pack, then replace controller. 1000-2024 Description Inputs unhealthy on IO Module [ ], T Pack IONet [ ] - Major Signature Mismatch Possible Cause Application/configuration does not match in the I/O pack and controller. Solution • Rebuild and download application/parameters to all controllers and I/O packs. • Reload firmware and parameters to the affected I/O pack. • Reload firmware and application to all controllers. • If problem persists, replace affected I/O pack, then replace controller. 1000-2024 Description Inputs unhealthy on IO Module [ ] IONet [ ] - Major Signature Mismatch Possible Cause Application/configuration does not match in the I/O pack and controller. Solution • Rebuild and download application/parameters to all controllers and I/O packs. • Reload firmware and parameters to the affected I/O pack. • Reload firmware and application to all controllers. • If problem persists, replace affected I/O pack, then replace controller. Controllers GEH-6855_Vol_II System Guide 77 Public Information

Inputs unhealthy on IO Module [ ], R Pack IONet [ ] - Minor Signature Mismatch

Possible Cause Application/configuration does not match in the I/O pack and controller. Solution • Rebuild and download application/parameters to all controllers and I/O packs. • Reload firmware and parameters to the affected I/O pack. • Reload firmware and application to all controllers. • If problem persists, replace affected I/O pack, then replace controller. 1000-2024 Description Inputs unhealthy on IO Module [ ], S Pack IONet [ ] - Minor Signature Mismatch Possible Cause Application/configuration does not match in the I/O pack and controller. Solution • Rebuild and download application/parameters to all controllers and I/O packs. • Reload firmware and parameters to the affected I/O pack. • Reload firmware and application to all controllers. • If problem persists, replace affected I/O pack, then replace controller. 1000-2024 Description Inputs unhealthy on IO Module [ ], T Pack IONet [ ] - Minor Signature Mismatch Possible Cause Application/configuration does not match in the I/O pack and controller. Solution • Rebuild and download application/parameters to all controllers and I/O packs. • Reload firmware and parameters to the affected I/O pack. • Reload firmware and application to all controllers. • If problem persists, replace affected I/O pack, then replace controller. 78 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Inputs unhealthy on IO Module [ ] IONet [ ] - Minor Signature Mismatch

Possible Cause Application/configuration does not match in the I/O pack and controller. Solution • Rebuild and download application/parameters to all controllers and I/O packs. • Reload firmware and parameters to the affected I/O pack. • Reload firmware and application to all controllers. • If problem persists, replace affected I/O pack, then replace controller. 1000-2024 Description Inputs unhealthy on IO Module [ ], R Pack IONet [ ] - Timestamp Mismatch Possible Cause Application/configuration does not match in the I/O pack and controller. Solution • Rebuild and download application/parameters to all controllers and I/O packs. • Reload firmware and parameters to the affected I/O pack. • Reload firmware and application to all controllers. • If problem persists, replace affected I/O pack, then replace controller. 1000-2024 Description Inputs unhealthy on IO Module [ ], S Pack IONet [ ] - Timestamp Mismatch Possible Cause Application/configuration does not match in the I/O pack and controller. Solution • Rebuild and download application/parameters to all controllers and I/O packs. • Reload firmware and parameters to the affected I/O pack. • Reload firmware and application to all controllers. • If problem persists, replace affected I/O pack, then replace controller. Controllers GEH-6855_Vol_II System Guide 79 Public Information

Inputs unhealthy on IO Module [ ], T Pack IONet [ ] - Timestamp Mismatch

Possible Cause Application/configuration does not match in the I/O pack and controller. Solution • Rebuild and download application/parameters to all controllers and I/O packs. • Reload firmware and parameters to the affected I/O pack. • Reload firmware and application to all controllers. • If problem persists, Immediate Attention Required: Fieldbus I/O Module [ ] Not Detected on IoNet [ ]ts, replace affected I/O pack, then replace controller. 1000-2024 Description Inputs unhealthy on IO Module [ ] IONet [ ] - Timestamp Mismatch Possible Cause Application/configuration does not match in the I/O pack and controller. Solution • Rebuild and download application/parameters to all controllers and I/O packs. • Reload firmware and parameters to the affected I/O pack. • Reload firmware and application to all controllers. • If problem persists, replace affected I/O pack, then replace controller. 1000-2024 Description Inputs unhealthy on IO Module [ ] IONet [ ] - Message Timeout Possible Cause Application/configuration does not match in the I/O pack and controller. Solution • Rebuild and download application/parameters to all controllers and I/O packs. • Reload firmware and parameters to the affected I/O pack. • Reload firmware and application to all controllers. • If problem persists, replace affected I/O pack, then replace controller. 80 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Immediate Attention Required: Fieldbus I/O Module [ ] Not Detected on IoNet [ ]

Possible Cause Note: If this diagnostic is active, the module needs to be replaced immediately. If it is simplex, the devices under this PFFA have lost communication. If it is redundant and not replaced, and a controller on the remaining module's IONet goes down, then control is lost for all devices under the PFFA modules. • PFFA module did not complete Start • PFFA module configuration files missing • PFFA module restarted • PFFA module configured for Hot Backup, but only one network is connected • Serial connection between PFFA modules is broken • Network issue Solution • If the Control/Status communication is working correctly, any additional diagnostics should indicate the cause of the problem. • Build and download parameters to the PFFA module and controller. • Verify Serial cable is attached correctly. • Verify that the Ethernet cables and network switch are operating correctly. • Manually restart the PFFA module. 2400 Description EtherCAT scan bus error Possible Cause • EtherCAT device(s) is unplugged or without power • An Ethernet cable is disconnected or damaged • Redundancy mode is not set correctly • Redundant Ring is broken Solution • Ensure all devices are connected and powered. • Verify all Ethernet LINK lights are lit. • Verify redundant configuration is correct. 2401 Description EtherCAT All Ethernet links disconnected Possible Cause • Ethernet LINK between Mark VIe controller and EtherCAT network is lost • EtherCAT device(s) are unplugged or without power Solution • Reconnect Ethernet cables. • Verify all Ethernet LINK lights are lit. • Verify all EtherCAT devices are powered. Controllers GEH-6855_Vol_II System Guide 81 Public Information

EtherCAT linebreak detected between devices [ ] and [ ]

Possible Cause • An Ethernet cable is disconnected or damaged • EtherCAT device(s) is unplugged or without power Solution • Reconnect Ethernet cables. • Verify all Ethernet LINK lights are lit. • Verify all EtherCAT devices are powered. 2404 Description EtherCAT limit for lost frames has been exceeded Possible Cause • A device or network component is corrupting the EtherCAT frame • An Ethernet cable is damaged Solution Use Controller Advanced Diagnostic tool to determine where network issues are located in the device topology. 2405 Description EtherCAT device disconnected Possible Cause • EtherCAT device(s) is unplugged or without power • An Ethernet cable is disconnected or damaged Solution • Ensure all devices are connected and powered. • Verify all Ethernet LINK lights are lit. 2406 Description EtherCAT device in unexpected state Possible Cause EtherCAT device(s) have invalid configuration or have experienced a watchdog event. Solution Check the EtherCAT device configuration in the ENI file and EtherCAT Configuration Tool. 2407 Description EtherCAT Master in unexpected state Possible Cause Bus does not match ENI file. Solution Download a new ENI file or plug in all devices. 82 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

EtherCAT ENI file does not match bus configuration

Possible Cause ENI File imported in ToolboxST does not match the discovered network. Solution • Verify ENI file matches the network connected to the Mark VIe controller. • Verify EtherCAT network is connected and intact. 2409 Description EtherCAT redundant Ethernet links crossed Possible Cause Main and Redundant Ethernet links are swapped on the controller. Solution Switch the EtherCAT Network connections on the controller. 2410 Description EtherCAT configuration is not supported Possible Cause • The ENI file contains unsupported commands or features • The ENI file contains commands that are unsupported in redundancy Solution • Remove unsupported commands or disable unsupported features. • In redundant operation, replace LRW commands with LRD / LWR. Controllers GEH-6855_Vol_II System Guide 83 Public Information

GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II

Public Information

Unmanaged Ethernet Switches

GE’s product line of industrial unmanaged Ethernet 10/100 switches, ESWA and ESW, are specifically designed to meet the needs of real-time industrial control solutions. To meet the requirements for speed and functionality, the following features are provided: • 802.3, 802.3u, and 802.3x compatibility • 10/100 base copper with auto negotiation • Full/half duplex auto-negotiation • 100 Mbps FX uplink port • HP-MDIX auto sensing • LEDs for Link Presence, Activity and Duplex, and Speed per port (each LED has two colors) • LED for Power • Minimum 256 KB buffer with 4K media access control (MAC) addresses Unmanaged Ethernet Switches GEH-6855_Vol_II System Guide 85 Public Information

Available Form Factors

The ESWx switch is available in the following form factors: Part # Description IS420ESWAH1A 8 ports 10/100BASE-TX + 1 port 100BASE-FX LC-type connection IS420ESWAH2A 8 ports 10/100BASE-TX + 2 ports 100BASE-FX LC-type connection IS420ESWAH3A 8 ports 10/100BASE-TX IS420ESWAH4A 8 ports 10/100BASE-TX + 1 port 100BASE-LX10 LC-type connection IS420ESWAH5A 8 ports 10/100BASE-TX + 2 ports 100BASE-LX10 LC-type connection IS420ESWBH1A 16 ports 10/100BASE-TX + 1 port 100BASE-FX LC-type connection IS420ESWBH2A 16 ports 10/100BASE-TX + 2 ports 100BASE-FX LC-type connection IS420ESWBH3A 16 ports 10/100BASE-TX IS420ESWBH4A 16 ports 10/100BASE-TX + 1 port 100BASE-LX10 LC-type connection IS420ESWBH5A 16 ports 10/100BASE-TX + 2 ports 100BASE-LX10 LC-type connection 3.2 Installation For new installations, mount the switch or switches onto the control system panel(s) using a DIN-rail. Connect the copper and/or fiber cables in accordance with system requirements and redundancy. Connect the 28 V dc power from the power distribution board to the switch. Note For system requirements, redundancy, and other related information, refer to the Mark VIe Industrial Ethernet / IONet Switches Summary Sheet (GEI-100869) and the Mark VIeS Functional Safety Systems for General Market Volume I: System Guide (GEH-6855_Vol_I), the chapter Ethernet Networks. GE has qualified the following DIN-rail clips for use with the ESWx switches. Clip Part # Switch Usage Mounting Orientation 259B2451BVP1 ESWA (8-port) or ESWB (16-port) Long edge of switch body parallel to rail 259B2451BVP2 ESWA (8-port) Long edge of switch body perpendicular to rail 259B2451BVP4 ESWB (16-port) Long edge of switch body perpendicular to rail 86 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

The RJ-45 connectors support multiple insertions and removals with an estimated service life expectancy of 200

insertion/removal cycles. Connector components are exposed to torsion forces across any axis of the connector and tension forces that are static from cable weight and cable dressing. Dynamic stresses are imposed on the connectors from transients in assembled system transport to the plant site and operation in a high vibration power production environment. Connector design anticipated static forces of three pounds force (89.9 Newton) per connection while complying with the other dynamic operating load requirements. Connector Description 28 V dc power Phoenix® contact part number MC 1.5/S-STF-3.81 Copper RJ-45 ports for Cat 5e UTP Fiber LC-type † Single Mode Fiber (SMF) requires the additional IR SFP single-mode transducer, GE part # 65G2100–008. † A port adapter is used if needing to interface an existing SC fiber termination to the LC fiber port. GE part # 336A5026P01 SC to LC adapter is required for multi-mode fiber (most common). GE part # 336A5026P02 SC to LC adapter is required for single-mode fiber. 3.4 IONet Switch Specifications Item Description Mounting DIN-rail mounted with separately purchased mounting clip. DIN-rail mounting meets vibration and shock specifications. Dimensions (width x depth x height) ESWA: 138 x 86 x 56 mm (5.45 x 3.40 x 2.20 in) ESWB: 188 x 86 x 56 mm (7.40 x 3.40 x 2.20 in) Incoming power connection Supports two redundant Diode-OR module power supply inputs of 18 to 36 V dc Cooling Convection cooled when mounted vertically or horizontally Coating Resistant to corrosion with provisions made for grounding per IEC 60721-3-3 Class 3C2 Ambient rating for enclosure design IS420ESWAHxA and IS420ESWBHxA are rated for -40 to 70°C (-40 to 158 °F) Refer to the Mark VIeS Functional Safety Systems for General Market Volume I: System Guide (GEH-6855_Vol_I), the chapter Technical Regulations, Standards, and Environments for more details. Absolute Maximum Current IS420ESWAHxA: < 0.5 A IS420ESWBHxA: < 1.0 A Shipping vibration, shock The switch can survive 72 hours at 0.3 G rms between frequencies of 4 to 16 Hz. Three shocks of 15G, 2-millisecond impulse each repeated for all three axes as mounted on panel base. Operating vibration Can survive 1.0 G Horizontal, 0.5 G vertical at 15 to 120 Hz Unmanaged Ethernet Switches GEH-6855_Vol_II System Guide 87 Public Information

The performance of a level 1 Ethernet switch is mainly centered on the ability to buffer packets. When a level 1 switch has a

continuous stream of incoming broadcast or multicast packets, the switch must in turn send those packets out upon complete reception. A single incoming stream should require enough space to buffer one packet or at the most one packet per port. When the switch has multiple incoming streams, it is only able to relieve one of the incoming streams and must buffer the rest for later transmission. 3.5.1 Conformance Criteria The packet traffic can be synchronized by IEEE 1588 timing and triggered to initiate within a 1-microsecond packet start window. The switch’s capability and conformance is tested to meet the following four criteria: • Initiation of the required Multicast packet load on one port, without IEEE 802.3x flow control negotiated • Initiation of the required Multicast packet load on one port, with IEEE 802.3x flow control negotiated • Initiation of the required Multicast packet load distributed across all ports, packet count per port must average required per number of switch ports with no IEEE 802.3x flow control • Initiation of the required packet Multicast load distributed across all ports, packet count per port must average 200 per number of switch ports with IEEE 802.3x flow control negotiated on half the ports 3.5.2 Flow Control (Pause) The switch supports flow control between switches. It uses IEEE defined pause packets to receive and honor pause packets. The switch only sends the pause packets if it needs flow control on a port. 3.5.3 Reliability and Performance Because high reliability is critical to any controls solutions business, the switch exceeds 4 million hours Mean Time Between Failures (MTBF) at 35°C (95 °F) ambient temperature, ground fixed controlled environment. The switch also meets the following performance criteria: Performance Criteria Feature Description Switch latency Switch packet latency does not exceed required application limits. Switch architecture The switch supports store and forward architecture, providing high data confidence. Inrush current The switch provides soft start capability that limits inrush current to less than 200% of the normal operating current. 88 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

The following figure defines the LED functions on the ESWx switch.

Power is solid green when internal power supply is up and regulating For each of the 16 ports (and SPF ports), the Activity LED functions as follows: • flashes green for activity at full duplex • flashes yellow for activity at half duplex For each of the 16 ports (and SPF ports), the Link LED functions as follows: • Solid green with 100 MB link • Solid yellow with 10 MB link • Not lit if no link Attention In certain conditions, an input voltage sag, known as a brownout, may cause the GE IS420ESWBH#_ (ESWB) I/O Network (IONet) switch to incorrectly reboot and fail to re-establish communication with the system. If the ESWB switch experiences a brownout condition that reduces the input 28 V line below the minimum operating voltage but not completely to 0 V, when the input voltage returns to above the minimum operating voltage, the switch may not correctly reboot. If this occurs, the ESWB LEDs will either remain on solid, flash in sync, or scroll from one side to the other, and the switch will not re-establish communication. If the site experiences a brownout, after the voltage returns and the IONet loses communication, observe the LEDs on the front of the switch. If they are solid, flashing in sync, or scrolling, cycle power to manually reboot the switch. Unmanaged Ethernet Switches GEH-6855_Vol_II System Guide 89 Public Information

Third-party Switch Replacement

When the ESWA or ESWB is used to replace a different unmanaged switch, it uses the existing mounting brackets, which can either be panel or DIN-rail mounts. There are seven screw holes used on the existing switch to support panel mounting. The following drawing displays the pattern and dimensions for these holes. Holes to Support Panel Mounting 90 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

YAIC Analog I/O Modules

4.1 Mark VIeS YAIC Analog I/O Pack The Analog I/O pack (IS420YAICS1B) provides the electrical interface between one or two I/O Ethernet networks and an analog I/O terminal board. The YAIC contains a common processor board and an acquisition board specific to the analog input function. The I/O pack is capable of handling up to 10 analog inputs, the first eight of which can be configured as ±5 Vor ±10 V inputs, or 4-20 mA current loop inputs. The last two inputs can be configured as ±1 mA or 4-20 mA current inputs. The load terminal resistors for current loop inputs are located on the terminal board and voltage is sensed across these resistors by the YAIC. The I/O pack also includes support for two 0-20 mA current loop outputs. The I/O pack receives or sends data through dual RJ-45 Ethernet connectors to the controller and has a three-pin connector to power it on. Output is through a DC-37 pin connector that connects directly with the associated terminal board connector. Visual diagnostics are provided through indicator LEDs. TBAI Analog Input Terminal Board YAIC Analog I/O Pack Analog Inputs (10) Processor board BPAI board One I/O pack for Simplex (connect to JR1) Dual is not available Single or dual Ethernet cables ENET1 ENET2 External 28 V dc power supply ENET1 ENET2 28 V dc Three I /O packs for TMR Analog Outputs (2) ENET1 ENET2 28 V dc YAIC Analog I/O Modules GEH-6855_Vol_II System Guide 91 Public Information

The YAIC I/O pack contains an internal processor board.

YAIC Version Compatibility I/O Pack Processor Board Compatible (Supported) Firmware ControlST Software Suite Versions YAICS1B BPPC V05.01 and later Supported in V06.01 and later versions Attention YAICS1A and YAICS1B I/O pack versions cannot be mixed on the same T-type terminal board. All three YAIC I/O packs in a TMR set must be the same hardware form. To upgrade or replace the YAIC, refer to the following replacement procedures for specific instructions: • Replace Mark VIeS Safety I/O Pack with Same Hardware Form • Replace Mark VIeS Safety I/O Pack with Upgraded Hardware Form The YAIC I/O pack is compatible with the TBAISIC and STAIS2A terminal boards. YAIC Terminal Board Compatibility Terminal Board Description I/O Pack Redundancy Simplex Dual TMR TBAIS1C TMR Analog input/output terminal board Yes No Yes STAIS2A Simplex Analog input/output terminal board Yes No No I/O pack redundancy refers to the number of I/O packs used in a signal path, as follows: • Simplex uses one I/O pack. • TMR uses three I/O packs. 92 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

To install a new YAIC I/O module into an existing Mark VIeS panel

1. Securely mount the desired terminal board. 2. Directly plug one YAIC I/O pack for simplex or three YAIC I/O packs for TMR into the terminal board connectors. 3. Mechanically secure the packs using the threaded studs adjacent to the Ethernet ports. The studs slide into a mounting bracket specific to the terminal board type. The bracket location should be adjusted such that there is no right-angle force applied to the DC-37 connector between the pack and the terminal board. The adjustment should only be required once in the life of the product. 4. Plug in one or two Ethernet cables depending on the system configuration. The pack will operate over either port. If dual connections are used, the standard practice is to connect ENET1 to the network associated with the R controller. These choices are also defined in the ToolboxST configuration. 5. Apply power to the pack by plugging in the connector on the side of the pack. It is not necessary to insert this connector with the power removed from the cable as the I/O pack has inherent soft-start capability that controls current inrush on power application. 6. Configure the I/O pack as necessary using the ToolboxST application. 4.1.2.1 Connectors The I/O pack contains the following connectors: • A DC-37 pin connector on the underside of the YAIC connects directly to the discrete input terminal board. The connector contains the 24 input signals, ID signal, relay coil power, and feedback multiplex command. • An RJ-45 Ethernet connector named ENET1 on the side of the pack is the primary system interface. • A second RJ-45 Ethernet connector named ENET2 on the side of the I/O pack is the redundant or secondary system interface. • A 3-pin power connector on the side of the pack is for 28 V dc power for the pack and terminal board. YAIC Analog I/O Modules GEH-6855_Vol_II System Guide 93 Public Information

Analog Input Hardware

The YAIC accepts input voltage signals from the terminal board for all 10 input channels. The analog input section consists of an analog multiplexer block, several gain and scaling selections, and a 16-bit analog-to-digital converter (ADC). Inputs 1–8 can be individually configured as ±5 Vor ±10 V, or 4–20 mA scale signals, depending on the input configuration. Inputs 9–10 can only be configured for ±1 mA or 4-20 mA. The terminal board provides a 250 Ωburden resistor when configured for current inputs yielding a 5 V signal at 20 mA. These analog input signals are first passed through a passive, low pass filter network with a pole at 75.15 Hz. Voltage signal feedbacks from the analog output circuits and calibration voltages are also sensed by the YAIC analog input section. 94 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

Analog Output Hardware

The YAIC includes two 0-20 mA analog outputs capable of 18 V compliance running simplex or TMR. A 14-bit digital-to-analog converter (DAC) commands a current reference to the current regulator loop in the YAIC that senses current both in the YAIC pack and on the terminal board. In TMR mode, the three current regulators in each YAIC share the commanded current loads among themselves. Analog output status feedbacks for each output include: • Current reference voltage • Individual current (output current sourced from within the YAIC) • Total current (as sensed from the terminal board, summed current in TMR mode) Each analog output circuit also includes a normally open mechanical relay to enable or disable operation of the output. The relay is used to remove a failed output from a TMR system allowing the remaining two YAICs to create the correct output without interference from the failed circuit. When the suicide relay is de-activated, the output opens through the relay, open-circuiting the analog output from the customer load that is connected to the terminal board. The mechanical relay has a second normally open contact that is used as a status to indicate position of the relay to the control and includes visual indication with an LED. YAIC Analog I/O Modules GEH-6855_Vol_II System Guide 95 Public Information

Number of Channels

12 channels per terminal board (10 AI, 2 AO) AI Types Supported Inputs 1 to 8: ±5 V dc, ±10 V dc, or 4–20 mA Inputs 9 to 10: 4–20 mA or ±1 mA Input Converter Resolution 16-bit ADC I/O Scan Time Supported Controller I/O Scan rates: 10 ms, 40 ms, 80 ms, 160 ms Input Accuracy 0.1% of full scale over the full operating temperature range. Noise Suppression on Inputs The 10 circuits have hardware filter with single pole down break at 500 rad/s. A software filter, using a two pole low pass filter, is configurable for: 0.75 Hz, 1.5 Hz, 3 Hz, 6 Hz, 12 Hz Common Mode Rejection AC CMR 60 dB at 60 Hz, with up to ±5 V common mode voltage. DC CMR 80 dB with -5 to +7 peak V common mode voltage Common Mode Voltage Range ±5 V (±2 V CMR for the ±10 V inputs) Output Converter 14-bit D/A converter with 0.5% accuracy Output Load 800 Ωmax for 0-20 mA output Output Accuracy ±0.5% of full measurement range Power Consumption 5.3 watts typical, 6.2 watts worst case Compressor Stall Detection Not supported Size 8.26 cm high x 4.19 cm wide x 12.1 cm deep (3.25 in x 1.65 in x 4.78 in) Ambient Rating for Enclosure Design -40 to 70°C (-40 to 158 °F) Technology Surface mount Note For further details, refer to the Mark VIeS Functional Safety Analog I/O Module Summary Sheet (GEI-100866). 96 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

The YAIC performs the following self-diagnostic tests:

• A power-up self-test that includes checks of RAM, flash memory, Ethernet ports, and most of the processor board hardware • Continuous monitoring of the internal power supplies for correct operation • A check of the electronic ID information from the terminal board, acquisition board, and processor board to confirm that the hardware set matches, followed by a check that the application code loaded from flash memory is correct for the hardware set • Each analog input has hardware limit checking based on configurable high and low levels for 4-20 mA inputs and preset (non-configurable) levels for ± 5 V, ± 10 V, and ± 1 mA inputs. If the limit is exceeded, then the I/O pack raises an alarm and marks the input as unhealthy. A logic signal (L3DIAG_pack) is set, which refers to the entire board. • Each input has configurable system limit checking with high and low levels, latching, and non-latching selection options. These limits can be used in the programming of the controller to generate process alarms. This controller logic requires using a RSTSYS pin on a SYS_OUTPUTS block to reset the out of limits status when the latch is enabled. System limit checking can be configured as Enable/Disable at point level, and are only functional only when system limits are enabled at module level (Parameters tab). • The analog input hardware includes precision reference voltages in each scan. Measured values are compared against expected values and are used to confirm health of the analog to digital converter circuits. • Analog output current is sensed on the terminal board using a small burden resistor. The I/O pack conditions this signal and compares it to the commanded current to confirm health of the digital to analog converter circuits. • The analog output suicide relay is continuously monitored for agreement between commanded state and feedback indication. Details of the individual diagnostics are available from the ToolboxST application. The diagnostic signals can be individually latched and then reset with the RSTDIAG signal if they go healthy. 4.1.5.1 Status LEDs Relay Application LEDs LED Label Description Yellow ENA1 Indicates the closure of the relay controlling output 1 Yellow ENA2 Indicate the closure of the relay controlling output 2 YAIC Analog I/O Modules GEH-6855_Vol_II System Guide 97 Public Information

Enable or temporarily disable all system limit checks.

Setting this parameter to Disable will cause a diagnostic alarm to occur. Enable, Disable Min_ MA_Input Select minimum current for healthy 4-20 mA input 0 to 22.5 mA Max_ MA_Input Select maximum current for healthy 4-20 mA input 0 to 22.5 mA 4.1.6.2 Inputs Input Description Choices AnalogInput01 through AnalogInput10 First of 10 Analog Inputs – board point. Point edit (Input REAL) InputType Current or voltage input type Unused or 4-20 mA (for all Analog Inputs) ±5 V or ±10 V (for AnalogInput01 to 08 only) ±1 mA (for AnalogInput09 and 10 only) Low_Input Value of input current (mA) or voltage (V) at low end of input scale -10 to 20 Low_Value Value of input in engineering units at Low_Input -3.4082 e + 038 to 3.4028 e + 038 High_Input Value of input current (mA) or voltage (V) at high end of input scale -10 to 20 High_Value Value of input in engineering units at High_Input -3.4082 e + 038 to 3.4028 e + 038 InputFilter Bandwidth of input signal filter Unused, 0.75hz, 1.5hz, 3hz, 6hz, 12hz TMR_DiffLimit Difference limit for voted inputs in % of High_Value - Low_Value 0 to 200 SysLim1Enabl Enable System Limit 1 fault check Enable, Disable SysLim1Latch System Limit 1 fault latch - if set, requires a Reset System Limits (RSTSYS) on SYS_OUTPUTS block to clear Latch, NotLatch SysLim1Type System Limit 1 Check Type >= or <= SysLim1 System Limit 1 in engineering units -3.4082 e + 038 to 3.4028 e + 038 SysLim2Enabl Enable System Limit 1 fault check Enable, Disable SysLim2Latch System Limit 2 fault latch - if set, requires a Reset System Limits (RSTSYS) on SYS_OUTPUTS block to clear Latch, NotLatch SysLim2Type System Limit 2 Check Type >= or <= SysLimit2 System Limit 2 in Engineering Units -3.4082 e + 038 to 3.4028 e + 038 DiagHighEnab Enables the generation of a high limit diagnostic alarm when the value of the 4-20 mA input is greater than the value of parameter Max_MA_Input Enable, Disable DiagLowEnab Enables the generation of a low limit diagnostic alarm when the value of the 4-20 mA input is less than the value of parameter Min_ MA_Input Enable, Disable TMR_DiffLimt Diag limit, TMR input vote difference, in percent of (High_Value - Low_Value) 0 to 200 % 98 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information

First of two analog outputs - board point, Point edit

Output REAL Output_MA Output current, mA selection. Unused, 0-20 mA OutputState State of the outputs when offline. When the YAIC loses communication with the controller, this parameter determines how it drives the outputs: PwrDownMode - Open the output relay and drive outputs to zero current HoldLastVal - Hold the last value received from the controller Output_Value - Go to the configured output value set by the parameter Output_Value PwrDownMode HoldLastVal Output_Value Output_Value Pre-determined value for the outputs -3.4082 e + 038 to 3.4028 e + 038 Low_MA Output mA at low value 0 to 200 mA Low_Value Output in Engineering Units at Low_MA -3.4082 e + 038 to 3.4028 e + 038 High_MA Output mA at high value 0 to 200 mA High_Value Output value in Engineering Units at High_MA -3.4082 e + 038 to 3.4028 e + 038 TMR_Suicide Enables suicide for faulty output current, TMR only Enable, Disable TMR_SuicLimit Suicide threshold (Load sharing margin) for TMR operation, in mA 0 to 200 mA D/A_ErrLimit Difference between D/A reference and feedback, in % for suicide, TMR only 0 to 200 % Dither_Ampl Dither % current of Scaled Output mA 0 to 10 Dither_Freq Dither rate in Hertz Unused, 12.5hz, 25hz, 33.33hz, 50hz, 100hz YAIC Analog I/O Modules GEH-6855_Vol_II System Guide 99 Public Information

I/O Link OK indication

Input BOOL ATTN_YAIC Module Diagnostic Input BOOL IOPackTmpr I/O Pack Temperature (deg F) Input REAL PS18V_YAIC I/O 18V Power Supply Indication Input BOOL PS28V_YAIC I/O 28V Power Supply Indication Input BOOL SysLimit1_1 System Limit 1 Input BOOL ↓ ↓ Input BOOL SysLimit1_10 System Limit 1 Input BOOL SysLimit2_1 System Limit 2 Input BOOL ↓ ↓ Input BOOL SysLimit2_10 System Limit 2 Input BOOL OutSuicide1 Status of Suicide Relay for Output 1 Input BOOL OutSuicide2 Status of Suicide Relay for Output 2 Input BOOL Out1MA Feedback, Total Output Current, mA Input REAL Out2MA Feedback, Total Output Current, mA Input REAL 100 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information