HaiLin Controls Lake Extra Manual
Read Online
Read the HaiLin Controls Lake Extra Manual online using the built-in PDF viewer.
Text of the manual
APPLICATION ----------------------------------------------------- 1
FEATURES ------------------------------------------------------- 2
SPECIFICATIONS -------------------------------------------------- 3
INSTALLATION ---------------------------------------------------- 5
WIRING -------------------------------------------------------- 13
POWER THE THERMOSTAT ----------------------------------------- 30
INSTALLER SETUP ------------------------------------------------ 32
OPERATION ----------------------------------------------------- 43
PROGRAMMING -------------------------------------------------- 64
TROUBLESHOOTING ---------------------------------------------- 70
Lake Extra Wi-Fi touchscreen programmable thermostat is an effortless and 7-Day
programmable thermostat that provides universal system compatibility, precise comfort
control and easy to program.
Lake Extra provides temperature control for gas, oil, electric and heat pumps for up to 3
heat 2 cool systems.
Above all you can remotely monitor and control the heating and cooling system in your
home or business — you can stay connected to your comfort system wherever you go.
· Large, clear display with backlight shows temperature, set temperature and humidity.
· Menu-driven programming make setup effortless.
· Beautiful ergonomic design is smart and sophisticated to match your customer
lifestyle.
· Capacitance touchscreen interaction.
· Connect to the Internet to monitor and control your heating/cooling system
· Compressor protection
Temperature Setting Range:
Heating: 40°F to 90°F (4°C to 32°C).
Cooling: 50°F to 99°F (10°C to 37°C).
Operating Ambient Temperature:
32°F to 122°F (0°C to 50°C).
Shipping Temperature:
-4°F to 150°F (-20°C to 65°C).
Operating Relative Humidity (Non-condensing):
IRS–1: 5% to 95%.
ORS-1: 5% to 95%.
Humidity Display Range:
0% to 99%.
Clock Accuracy:
+/- 2 minute per month.
Cool Indication:
Show "Cool On" on the screen when Cool is activated.
Heat Indication:
Show "Heat On" on the screen when Heat is activated.
Auxiliary Heat Indication:
Show "Aux On" on the screen when Auxiliary Heat is activated.
When Installing this Product...
1. Read these instructions carefully. Failure to follow the instructions can damage the
product or cause a hazardous condition.
2. Check the ratings given in the instructions to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service technician.
4. After completing installation, use these instructions to check out the product operation.
Selecting Location
Install the thermostat about 5 feet (1.5m), above the floor in an area with good air
circulation at average temperature. See Fig.4.
Do not install the thermostat where it can be affected by:
---Drafts or dead spots behind doors and in corners.
---Hot or cold air from ducts.
---Radiant heat from sun or appliances Concealed pipes and chimneys.
---Unheated or uncooled areas such as an outside wall behind the thermostat.
Mounting Means:
Mounts directly on the wall in the living space using mounting screws and anchors
provided.
Dimensions:
1.
Lake Extra dimensions: see Fig. 1.
2.
Lake Extra back case: see Fig. 2.
3.
Lake Extra cover plate: see Fig. 3.
Installing Wall plate
CAUTION
Electrical hazard can cause electrical shock or equipment damage.
Disconnect power before wiring.
The thermostat can be mounted horizontally on the wall.
1. Position and level the wall plate (for appearance only).
2. Use a pencil to mark the mounting holes.
3. Remove the wall plate from the wall and if drywall, drill two holes in the wall as marked.
For firmer material such as plaster, drill two holes. Gently tap anchors (provided) into the
drilled holes until flush with the wall.
4. Position the wall plate over the holes, pulling wires through the wiring opening. See
Fig.5.
5. Insert the mounting screws into the holes and tighten.
All wiring must comply with local electrical codes and ordinances.
1. See Table 1 and Fig.6 for terminal designation descriptions. Insert wires in the terminal
block under the loosened screw. See Fig.7.
2. Securely tighten each screw.
3. Push excess wire back into the hole.
4. Plug the hole with nonflammable insulation to prevent drafts from affecting the
thermostat.
Table 1. Terminal Designation Descriptions.
Terminal Designation
Description
RC (see Note 1)
Power for cooling--connect to secondary side of cooling system
transformer
R (see Note 1)
Power for heating--connect to secondary side of heating system
transformer
C (see Note 2)
Common wire from secondary side of cooling system transformer
Y
Compressor contactor
G
Fan relay
Y2
Second stage cooling
O/B/W (see Note 3)
Changeover valve for heat pump systems or Heat relay
AUX/W2
Auxiliary heat relay for heat pump systems or Second stage heat relay
E
Emergency heat relay for heat pump systems
L (see note 4)
Equipment monitor for heat pump systems
1. When used in a single-transformer system, leave metal jumper wire in place between
RC and R. If used on a two-transformer system, remove metal jumper wire between RC
and R.
2. Common wire is optional when thermostat is used with batteries.
3. If thermostat is configured for a heat pump system, configure changeover valve for cool
or heat.
4. L terminal is an input port as system monitor.
Fig.6.Terminal identifications for system.
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
Fig. 8. Typical hookup of conventional single-stage heat and cool system with single
Transformer (1H/1C conventional).
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
Fig. 9. Typical hookup of conventional single-stage heat and cool system with two
transformers (1H/1C conventional).
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
Fig. 10. Typical hookup of heat-only system (1 H conventional).
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
Fig. 11. Typical hookup of heat only system with fan (1H conventional).
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
Fig. 12. Typical hookup of heat only power to open and power to close zone valve
System.
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
Fig. 13. Typical hookup of heat only system with normally open zone valves.
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
Fig. 14. Typical hookup of cool only system (1C conventional).
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
Fig. 15. Typical hookup of conventional multistage two-stage heating and two-stage
cooling in a single-transformer system (2H/2C, 2H/1C or 1H/2C conventional).
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
Fig. 16. Typical hookup of conventional multistage two-stage heating and two-stage
cooling in a two-transformer system (2H/2C, 2H/1C or1H/2C conventional).
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
Fig. 17. Typical hookup of single-stage heat pump with no auxiliary/backup heat (1H/1C
heat pump).
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. MUST CONNECT THE 24VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR.
4. "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
Fig. 18. Typical hookup of multistage heat pump with no auxiliary/backup heat (2H/2C heat pump).
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. MUST CONNECT THE 24VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR.
4."O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
Fig. 19. Typical hookup of single-stage heat pump with auxiliary/backup heat (2H/1C heat pump).
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. MUST CONNECT THE 24VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR.
4. "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
Fig. 20. Typical hookup of multistage heat pump with auxiliary/backup heat (3H/2C heat pump).
POWER THE THERMOSTAT
Wiring 24VAC Common
·Single-Transformer System:
Connect the common side of the transformer to the C screw terminal of the thermostat
wall plate. Leave the metal jumper wire in place between RC and R.
·Two-Transformer System:
Connect the common side of the cooling transformer to the C screw terminal of the
thermostat wall plate. Remove the metal jumper wire between RC and R.
Mount Thermostat to Wall Plate
Align the terminal screw blocks with the pins on the back of the thermostat. Push the
thermostat straight onto the wall plate until it snaps into place. See Fig. 21.
Follow these steps to enter the
Installer Setup:
1. See Fig. 22-1. Press and release
the
Key. System mode will blink,
then Press and hold the
key for
approximately 5 seconds until the
screen change. Menu number display
at bottom right corner. See Fig. 22-2.
Fig.22-1
Fig.22-2.
key to cutover
submenu, and press
key enter
submenu. Under submenu Use
or
to set parameters. See
Fig.22-3.
Fig.22-3.
Note: See Tables 2 for the Installer
Setup Numbers and Settings.
3.Press
key to exit and confirm
the installer setup, or press
to
exit without saving changes.
Table 2.installer Setup Menu.
Number
Name
Settings
Notes
0140
MAC
and
version
See MAC and firmware version
0150
Date and time
Set calendar date and time
0160
Schedule
Options
0-non-programmable
1-7 day programmable
The schedule setting
will default if changed
1-1heat/1cool conventional (default setting)
2-single-stage heat pump (no auxiliary heat)
3-Heat only conventional (no fan)
4-heat only conventional (with fan)
5-heat only (power to open and close zone
valves or normally-open zone valves)
6-cool only conventional
7-2heat/1cool heat pump (with auxiliary heat)
8-2heat/2cool multistage conventional
9-2heat/1cool multistage conventional
10-1heat/2cool multistage conventional
11-2heat/2cool heat pump (no auxiliary heat)
12-3heat/2cool heat pump (with auxiliary heat)
Available options and
defaults
vary
by
thermostat.
System
selection automatically
modifies some default
settings and/or hides
other Installer Setup
options.
Fan Control in
Heating
0-gas or oil furnace equipment controls fan in
heating (factory setting)
1-electric furnace thermostat controls fan in
heating
Only
shown
if
conventional system is
selected. If heat pump
is chosen, fan defaults
to electric.
0190
Changeover
Valve
O/B
Terminal
Energized in
Heating
or
Cooling (Heat
Pumps Only)
0-changeover valve O/B terminal is energized
in cooling
1-changeover valve O/B terminal is energized
in heating
Only shown if heat
pump
system
is
chosen.
40 ℉ - 62 ℉ : leave mode heating, the
range of setting temperature(1 ℉ difference)
4 ℃ - 16 ℃: leave mode heating, the range
of setting temperature(0.5 ℃ difference)
0230
Leave mode
cooling
setting
temperature
76 ℉ - 99 ℉leave mode cooling, the range
of setting temperature(1 ℉ difference)
24 ℃- 37 ℃leave mode cooling, the range of
setting temperature(0.5 ℃ difference)
0280
Close backlit
display
0 - show temperature only
1 - show main menu
0300
Changeover
0-manual changeover (factory setting)
1-auto changeover
2 - 2°F (1.5°C) 3 - 3°F (2°C) 4 - 4°F (2.5°C)
5 - 5°F (3°C) 6 - 6°F (3.5°C) 7 - 7°F (4°C)
8 - 8°F (4.5°C) 9 - 9°F (5°C)
Shown only if 0300 is
selected.
0320
Temperature
Indication
Scale
0 - Fahrenheit (factory setting)
1 - Celsius
when it is changed, the
schedule need to be
reprogrammed
0330
1stage
hysteresis
1 F - 3 F(default 2F)
Fahrenheit value is 2
times
of
centigrade
value
0340
2stage
hysteresis
1 F - 3 F(default 2F)
Fahrenheit value is 2
times
of
centigrade
value
1 F - 3 F(default 2F)
Fahrenheit value is 2
times
of
centigrade
value
0500
Furnace
Change
Reminder
0 - furnace filter reminder off
1 - 10 run time days 2 - 30 run time days
3 - 60 run time days 4 - 90 run time days
5 - 120 run time days 6 - 365 run time days
Run time based on call
for fan.
0530
Adaptive
Intelligent
Recovery
1 - Adaptive Intelligent Recovery control is
activated (system starts early so set point is
reached by start of program period).
0 - Conventional Recovery (system starts
recovery at programmed time)
2 - two periods available (Wake and Sleep)
4 - four periods available (Wake, Leave,
Return and Sleep)
Only shown if schedule
is enable. Schedule will
default if changed
0580
Minimum
Compressor
Off Time
5 - five-minute compressor off-time setting
(factory setting)
0,2,3,4 - other compressor off-time settings
0600
Heat
Temperature
Range Stop
40-90 - temperature range (1°F increments) of
heating set point.
Shown in 1/2 °C.
0610
Cool
Temperature
Range Stop
50-99 - temperature range (1°F increments) of
cooling set point.
Shown in 1/2 °C.
12 - 12 hour clock (factory setting)
24 - 24 hour clock
0650
Extended Fan
On Time Heat
0 - No extended fan operation after call for
heat ends.
90 - Fan operation is extended 90 seconds
after call for heat ends.
Not shown in Cool Only
Systems
0660
Extended Fan
On Time Cool
0 - No extended fan operation after call for
cool ends
90 - Fan operation is extended 90 seconds
after call for cool ends.
Not shown in Heat Only
Systems.
0 - unlocked keypad
1 - locked keypad
When key Locked only
ability to enter User
Setup to unlock.
0700
Temperature
Display
Offset
-9°F ~ 9°F (°F as temperature format)
-4.5°C ~ 4.5°C (°C as temperature format)
0°F (0°C) (factory setting)
0710
Reset
thermostat
0 - no thermostat reset.
1 - Resets all Installer Setup Options to default
values and resets schedule to default setting.
Only calendar settings
and time are retained.
Follow these steps to enter the User Setup:
1.
Press and hold the
key for approximately 3 seconds until the screen change.
Menu number display at bottom right corner.
2.
Press
or
key to cutover submenu, and press
key enter submenu.
Under submenu Use
or
to set parameters.
3.
Press
key to exit and confirm the user setup, or press
to exit without
saving changes.
Note: See Tables 3 for the User Setup Numbers and Settings, and see chapter
INSTALLER SETUP for Operations Reference.
Table 3. User Setup Settings.
Number
Description
Settings
0140
See MAC and version
0150
Date and time
current calendar date and time
0320
Display temperature in °F
or °C
0 - °F setting (factory setting)
1 - °C setting
0640
Clock format
12 - 12-hour clock(factory setting)
24 - 24-hour clock
0 - unlocked keypad
1 - locked keypad
0700
Temperature Display
Offset
-3°F ~ 3°F (°F as temperature format)
-1.5°C ~ 1.5°C (°C as temperature format)
0°F (0°C) (factory setting)
0710
Reset Thermostat
0 - No thermostat reset.
1 - Resets all Installer Setup Options to default values and
resets schedule to default setting.
Consult USER SETUP, choose
submenu number 0150 enter date
and time setting.
2.
Press
to switch date to time
follows order: year, month, day,
hour, and minute. Press
or
to adjust the time. (You can
advance the time more quickly by
holding the
key or
key
buttons.)
3.
Press
to save changes and
exit or press
to exit without
change the date and time.
Fig.25
Setting the fan
1.
Press
to select fan operation.
2.
Press
again to select ON or
AUTO (toggle to re-select). The
selected option blinks.
4.
Press
to save setting. Your
selection, or press
to exit
without saving changes.
ON: Fan is always on.
AUTO: Fan runs only when the heating
or cooling system is on.
Fig.26
Selecting system mode
1.
Press
to display options.
2.
Press
again to select an
option. You may need to press two
or three times to make a
selection—the selected option
blinks.
3.
Press
to save setting. Your
selection, or press
to exit
without saving changes.
Fig.27
Possible system modes:
HEAT: Controls only the heating system.
COOL: Controls only the cooling system.
OFF: Heating/cooling systems are off.
AUTO: Selects heating or cooling depending on the indoor temperature.
EMER (heat pumps with aux. heat):
Controls auxiliary/emergency heat. Compressor is locked out.
Note: The AUTO and EMER system settings may not appear, depending on how your
thermostat was installed.
Note: when under auto mode press
key can switch set temperature between heat
and cool.
Set Temperature Overrides
Lake has two temperature override options: Override Until and Permanent Override.
Override Until
Holds temperature temporarily until the next scheduled period time.
1.
Press
or
key to adjust temperature you want, the icon until appears
above time, and the time becomes next scheduled period time.
2.
Press
key to exit and confirm the changes, or press
to exit without
saving changes.
3.
If you want to exit Override Until, please press
key. Override Until will be also
exit until reach the next scheduled period time.
Note: The current day of the week should already be set correctly. If not, see User Setup
to set the date and time setting.
Keep user set-point permanently.
1.
Press
key once. Screen shows Permanent Hold.
2.
Press
or
key to adjust temperature you want.
3.
If you want to exit, please press
key again.
Clean Thermostat Screen
The thermostat has a touch screen
interaction. Follow these steps to clean
the screen without making thermostat
changes:
1.
Press and hold the
key for
approximately 3 seconds until the
screen changes. Thermostat locks
out all touch keys for 30 seconds to
allow for cleaning. See Fig. 28.
2.
Use damp cloth slightly moistened
with water or house-hold glass
cleaner to clean the screen.
Fig.28.
When time up, press
key to return
to the Home Screen and normal
operation. See Fig.29.
Fig.29.
IMPORTANT:
Do not spray any type of liquid directly
on the thermostat itself. If using
household glass cleaner, spray cleaner
on cloth. Then use a cloth to clean the
thermostat screen.
In User or Installer Setup, menu 0670 allows you to prevent changes to all of the
touchscreen functions. In this case, all keys are locked and not functional, the screen
displays a lock icon
continuously. Even so, you can though User setup to unlock keys
and restore the touchscreen functions.
Setting filter reminder
intervals
If activated during installation, the filter
reminder alerts you with flashes
one screen above the time when it is
time to replace your filter.
Press
after changing the filter, to
restart the timer.
To change the reminder interval:
1.
Press and hold the
key for
approximately 3 seconds until the
screen changes.
2.
Press
or
to select the
desired interval (in days), then
press
to save and exit, or
press
to exit without save.
Fig.30
1. System setting function 0500
governs the filter interval maximum.
2. The days are counted as fan run time,
so anytime the fan is running, the
reminder is counting that time against
the number of days selected.
Connecting to your Wi-Fi network
To complete this process, you must have a smart phone connected to your home wireless
network. Please scan the following code to download “Lake Plus” APP.
If you get stuck...
At any point in this procedure, restart the thermostat by removing the thermostat from the
wall plate, wait a few seconds, and snap it back onto the wall plate. Return to Step 1 in
this procedure, which starts on the next page.
1. Please be sure your phone has
connected WIFI (don’t connect the
hidden internet), download “Lake Plus”.
2. Open APP and register.
Fig. 31. Fig. 32.
3. After login, press top left corner
,
choose WIFI connection and input the
WIFI password, DON’T press the
“connect” and continue next step first.
Fig. 33. Fig. 34.
4. Press the key
on thermostat
screen till the “
” flash.
5. Now you can press the “connect” on
app, app will show processing and after
seconds it will show successfully.
Fig. 36. Fig. 37.
1. IF connect WIFI successfully, it will
show
on the
thermostat, otherwise will
show
.
2. Each configuration need to be
finished within 5minutes, otherwise
the thermostat will quit to configure.
Just need to press the
on
homepage,Lake will switch to leave
mode. (You can set the temperature
you need under leave mode, see the
following programming to set the
temperature)
If Lake has been under leave mode,
press
on homepage to quit the
mode and recover the previous status.
Fig. 38.
Table 4. Schedule Default Program Settings.
Schedule Period
Time
Set points
Fan Setting
Heat
Cool
Wake
6:00AM
68°F (20°C)
78°F (26°C)
Auto
Leave
8:00AM
60°F (16°C)
85°F (29°C)
Auto
Return
4:00PM
68°F (20°C)
78°F (26°C)
Auto
Sleep
10:00PM
60°F (16°C)
82°F (28°C)
Auto
Program Heating and Cooling Schedule
Your thermostat can control up to four different schedule periods per day:
Wake - Period when you awaken and want your home at a comfortable temperature.
Leave - Period when you are away from home and want an energy-saving
temperature.
Return - Period when you return home and want your home back to a comfortable
temperature.
Sleep - Period when you are asleep and want an energy-saving temperature.
NOTE: Schedule times are in 15-minute intervals.
, the screen will
change. See Fig. 39 and 40.
Fig.39.
2.
In this case, the time will blink,
press
or
to adjust the
time. Press
to turn to next
setting.
3.
Then, the temperature will start to
blink, press
or
to
adjust the temperature. Press
to turn to next time period.
Fig.40.
Repeat the above steps until completing the setting of four time periods. Then, Press
to turn to next day, until completing the setting of a week.
5.
End of Program Setting, You may press
key to exit and confirm the program
setting, or press
to exit without saving changes.
NOTE: The Fan setting is auto as default and cannot be programmed.
Copy one-day program
After entering a day program you can copy this into another day to save time when
creating a weekly program: for example, if you want to copy the program of Monday to
Thursday, the methods are as follows:
1.
Select the program for Monday, complete the setting of Monday and press
, the
icon
appears on the screen, and the icon
Will blink, that indicates
Waiting to be selected or skipped. Press
to select, press
to skip.
2.
Copy to Thursday: press
or
to select Thursday, then press
to finish
the copying and the icon
disappears.
3.
Copying for other days, please repeat from the Step 1 to 2. One time you can copy to
one day or many days.
Your thermostat can reset schedule setup option to default setting.
Press and hold
key for approximately 3 seconds until the screen change as Fig.41,
then release
key. Now, the setting of schedule reset to default setting as table 4.
Fig. 41.
No LCD display
Thermostat is not being
powered.
Check 24VAC between C and R.
Temperature settings
do not change.
The
upper
or
lower
temperature
limits
were
reached.
Check temperature set-points.
Check Installer Setup Numbers
0600 or 0610, modify as needed.
The keypad is fully locked.
Check Installer Setup Number
0670 to change keypad locked
options.
Heating or cooling
does not come on.
Thermostat
minimum
off-time is activated.
Wait up to five minutes for the
system to respond.
System selection is not set
to Heat or Cool.
Set system Selection to correct
position.
System type Selection is
incorrect.
Check Installer Setup Number
0170 and make sure correct
System type is chosen.
Thermostat is calling
for Heat (Heat on) or
Cool (Cool on) but no
heating or cooling is
running.
Heating
or
cooling
equipment is not operating.
Check wiring.
Check Installer Setup Number
0170 and make sure correct
system type is chosen.
Verify operation of equipment in
System Test mode.
Fan does not turn on
in a call for heat
(electric furnace).
Fan Control in Heating is set
to Gas or Oil Furnace
(Setting 0180).
Set Fan Control in Heating to
Electric Furnace (Setting 0180).
Heat pump puts out
cool air in the heat
mode and warm air in
the cool mode.
Changeover Valve is not
configured to match the
changeover required by the
installed heat pump.
Set Changeover Valve (Installer
Setup Number 0190) to match
the changeover required by the
installed heat pump.
Both the heating and
cooling
equipment
are running at the
same time.
The heating equipment is
not a heat pump but the
System Type is set to Heat
Pump.
Set System Type (Installer Setup
Number 0170) to match the
installed heating and/or cooling
equipment.
Heating and cooling wires
are shorted together.
Separate the shorted heating
and cooling wires.
Heating equipment is
running in the cool
mode.
Heating equipment is not a
heat pump but System Type
(Installer
Setup
Number
0170) is set to Heat Pump.
Set System Type (Installer Setup
Number 0170) to match the
installed heating and/or cooling
equipment.
Heating
equipment
does not turn off and
heat
temperature
setting is set below
room temperature
Heating equipment is not a
heat pump but System Type
(Installer
Setup
Number
0170) is set to Heat Pump.
Set System Type (Installer Setup
Number 0170) to match the
installed heating and/or cooling
equipment.
Heat or Cool.
System Type is set to Cool
Only or Heat Only or Heat
Only with Fan.
Set System Type (Installer Setup
Number 0170) to match the
installed equipment.
Heat On is not in the
display.
System is not set to Heat
and/or temperature is not
above room temperature.
Set the system setting to Heat
and set the temperature setting
above the room temperature.
Cool On is not in the
display.
System is not set to Cool
and/or temperature is not
below room temperature.
Set the system setting to Cool
and set the temperature setting
below the room temperature.
Wait is in the display.
Compressor minimum off
timer is active.
Wait up to five minutes for the
cooling or heating (heat pump)
equipment to turn on.
Screen
Locked
appears
on
the
screen and the keys
do not respond.
The keypad is locked.
Check Installer Setup Number
0670 to change keypad locked
options.