APPLICATION ----------------------------------------------------- 1

FEATURES ------------------------------------------------------- 2 SPECIFICATIONS -------------------------------------------------- 3 INSTALLATION ---------------------------------------------------- 5 WIRING -------------------------------------------------------- 13 POWER THE THERMOSTAT ----------------------------------------- 30 INSTALLER SETUP ------------------------------------------------ 32 OPERATION ----------------------------------------------------- 43 PROGRAMMING -------------------------------------------------- 64 TROUBLESHOOTING ---------------------------------------------- 70

Lake Extra Wi-Fi touchscreen programmable thermostat is an effortless and 7-Day

programmable thermostat that provides universal system compatibility, precise comfort control and easy to program. Lake Extra provides temperature control for gas, oil, electric and heat pumps for up to 3 heat 2 cool systems. Above all you can remotely monitor and control the heating and cooling system in your home or business — you can stay connected to your comfort system wherever you go.

· Large, clear display with backlight shows temperature, set temperature and humidity.

· Menu-driven programming make setup effortless. · Beautiful ergonomic design is smart and sophisticated to match your customer lifestyle. · Capacitance touchscreen interaction. · Connect to the Internet to monitor and control your heating/cooling system · Compressor protection

Temperature Setting Range:

Heating: 40°F to 90°F (4°C to 32°C). Cooling: 50°F to 99°F (10°C to 37°C). Operating Ambient Temperature: 32°F to 122°F (0°C to 50°C). Shipping Temperature: -4°F to 150°F (-20°C to 65°C). Operating Relative Humidity (Non-condensing): IRS–1: 5% to 95%. ORS-1: 5% to 95%. Humidity Display Range:

0% to 99%.

Clock Accuracy: +/- 2 minute per month. Cool Indication: Show "Cool On" on the screen when Cool is activated. Heat Indication: Show "Heat On" on the screen when Heat is activated. Auxiliary Heat Indication: Show "Aux On" on the screen when Auxiliary Heat is activated.

When Installing this Product...

1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition. 2. Check the ratings given in the instructions to make sure the product is suitable for your application. 3. Installer must be a trained, experienced service technician. 4. After completing installation, use these instructions to check out the product operation. Selecting Location Install the thermostat about 5 feet (1.5m), above the floor in an area with good air circulation at average temperature. See Fig.4. Do not install the thermostat where it can be affected by: ---Drafts or dead spots behind doors and in corners.

---Hot or cold air from ducts.

---Radiant heat from sun or appliances Concealed pipes and chimneys. ---Unheated or uncooled areas such as an outside wall behind the thermostat. Mounting Means: Mounts directly on the wall in the living space using mounting screws and anchors provided. Dimensions: 1. Lake Extra dimensions: see Fig. 1. 2. Lake Extra back case: see Fig. 2. 3. Lake Extra cover plate: see Fig. 3.

Installing Wall plate

CAUTION Electrical hazard can cause electrical shock or equipment damage. Disconnect power before wiring. The thermostat can be mounted horizontally on the wall. 1. Position and level the wall plate (for appearance only). 2. Use a pencil to mark the mounting holes. 3. Remove the wall plate from the wall and if drywall, drill two holes in the wall as marked. For firmer material such as plaster, drill two holes. Gently tap anchors (provided) into the drilled holes until flush with the wall. 4. Position the wall plate over the holes, pulling wires through the wiring opening. See Fig.5. 5. Insert the mounting screws into the holes and tighten.

All wiring must comply with local electrical codes and ordinances.

1. See Table 1 and Fig.6 for terminal designation descriptions. Insert wires in the terminal block under the loosened screw. See Fig.7. 2. Securely tighten each screw. 3. Push excess wire back into the hole. 4. Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat.

Table 1. Terminal Designation Descriptions.

Terminal Designation Description RC (see Note 1) Power for cooling--connect to secondary side of cooling system transformer R (see Note 1) Power for heating--connect to secondary side of heating system transformer C (see Note 2) Common wire from secondary side of cooling system transformer Y Compressor contactor G Fan relay Y2 Second stage cooling O/B/W (see Note 3) Changeover valve for heat pump systems or Heat relay AUX/W2 Auxiliary heat relay for heat pump systems or Second stage heat relay E Emergency heat relay for heat pump systems L (see note 4) Equipment monitor for heat pump systems

1. When used in a single-transformer system, leave metal jumper wire in place between

RC and R. If used on a two-transformer system, remove metal jumper wire between RC and R. 2. Common wire is optional when thermostat is used with batteries. 3. If thermostat is configured for a heat pump system, configure changeover valve for cool or heat. 4. L terminal is an input port as system monitor. Fig.6.Terminal identifications for system.

1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2. FACTORY INSTALLED JUMPER. Fig. 8. Typical hookup of conventional single-stage heat and cool system with single Transformer (1H/1C conventional).

1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2. FACTORY INSTALLED JUMPER. Fig. 9. Typical hookup of conventional single-stage heat and cool system with two transformers (1H/1C conventional).

1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2. FACTORY INSTALLED JUMPER. Fig. 10. Typical hookup of heat-only system (1 H conventional).

1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2. FACTORY INSTALLED JUMPER. Fig. 11. Typical hookup of heat only system with fan (1H conventional).

1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2. FACTORY INSTALLED JUMPER. Fig. 12. Typical hookup of heat only power to open and power to close zone valve System.

1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2. FACTORY INSTALLED JUMPER. Fig. 13. Typical hookup of heat only system with normally open zone valves.

1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2. FACTORY INSTALLED JUMPER. Fig. 14. Typical hookup of cool only system (1C conventional).

1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2. FACTORY INSTALLED JUMPER. Fig. 15. Typical hookup of conventional multistage two-stage heating and two-stage cooling in a single-transformer system (2H/2C, 2H/1C or 1H/2C conventional).

1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2. FACTORY INSTALLED JUMPER. Fig. 16. Typical hookup of conventional multistage two-stage heating and two-stage cooling in a two-transformer system (2H/2C, 2H/1C or1H/2C conventional).

1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2. FACTORY INSTALLED JUMPER. 3. "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP. Fig. 17. Typical hookup of single-stage heat pump with no auxiliary/backup heat (1H/1C heat pump).

1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2. FACTORY INSTALLED JUMPER. 3. MUST CONNECT THE 24VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR. 4. "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP. Fig. 18. Typical hookup of multistage heat pump with no auxiliary/backup heat (2H/2C heat pump).

1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2. FACTORY INSTALLED JUMPER. 3. MUST CONNECT THE 24VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR. 4."O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP. Fig. 19. Typical hookup of single-stage heat pump with auxiliary/backup heat (2H/1C heat pump).

1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2. FACTORY INSTALLED JUMPER. 3. MUST CONNECT THE 24VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR. 4. "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP. Fig. 20. Typical hookup of multistage heat pump with auxiliary/backup heat (3H/2C heat pump).

POWER THE THERMOSTAT

Wiring 24VAC Common ·Single-Transformer System: Connect the common side of the transformer to the C screw terminal of the thermostat wall plate. Leave the metal jumper wire in place between RC and R. ·Two-Transformer System: Connect the common side of the cooling transformer to the C screw terminal of the thermostat wall plate. Remove the metal jumper wire between RC and R. Mount Thermostat to Wall Plate Align the terminal screw blocks with the pins on the back of the thermostat. Push the thermostat straight onto the wall plate until it snaps into place. See Fig. 21.

Follow these steps to enter the

Installer Setup: 1. See Fig. 22-1. Press and release the Key. System mode will blink, then Press and hold the key for approximately 5 seconds until the screen change. Menu number display at bottom right corner. See Fig. 22-2. Fig.22-1 Fig.22-2.

key to cutover

submenu, and press key enter submenu. Under submenu Use or to set parameters. See Fig.22-3. Fig.22-3. Note: See Tables 2 for the Installer Setup Numbers and Settings. 3.Press key to exit and confirm the installer setup, or press to exit without saving changes.

Table 2.installer Setup Menu.

Number Name Settings Notes 0140 MAC and version See MAC and firmware version 0150 Date and time Set calendar date and time 0160 Schedule Options 0-non-programmable 1-7 day programmable The schedule setting will default if changed

1-1heat/1cool conventional (default setting)

2-single-stage heat pump (no auxiliary heat) 3-Heat only conventional (no fan) 4-heat only conventional (with fan) 5-heat only (power to open and close zone valves or normally-open zone valves) 6-cool only conventional 7-2heat/1cool heat pump (with auxiliary heat) 8-2heat/2cool multistage conventional 9-2heat/1cool multistage conventional 10-1heat/2cool multistage conventional 11-2heat/2cool heat pump (no auxiliary heat) 12-3heat/2cool heat pump (with auxiliary heat) Available options and defaults vary by thermostat. System selection automatically modifies some default settings and/or hides other Installer Setup options.

Fan Control in

Heating 0-gas or oil furnace equipment controls fan in heating (factory setting) 1-electric furnace thermostat controls fan in heating Only shown if conventional system is selected. If heat pump is chosen, fan defaults to electric. 0190 Changeover Valve O/B Terminal Energized in Heating or Cooling (Heat Pumps Only) 0-changeover valve O/B terminal is energized in cooling 1-changeover valve O/B terminal is energized in heating Only shown if heat pump system is chosen.

40 ℉ - 62 ℉ : leave mode heating, the

range of setting temperature(1 ℉ difference) 4 ℃ - 16 ℃: leave mode heating, the range of setting temperature(0.5 ℃ difference) 0230 Leave mode cooling setting temperature 76 ℉ - 99 ℉leave mode cooling, the range of setting temperature(1 ℉ difference) 24 ℃- 37 ℃leave mode cooling, the range of setting temperature(0.5 ℃ difference) 0280 Close backlit display 0 - show temperature only 1 - show main menu 0300 Changeover 0-manual changeover (factory setting) 1-auto changeover

2 - 2°F (1.5°C) 3 - 3°F (2°C) 4 - 4°F (2.5°C)

5 - 5°F (3°C) 6 - 6°F (3.5°C) 7 - 7°F (4°C) 8 - 8°F (4.5°C) 9 - 9°F (5°C) Shown only if 0300 is selected. 0320 Temperature Indication Scale 0 - Fahrenheit (factory setting) 1 - Celsius when it is changed, the schedule need to be reprogrammed 0330 1stage hysteresis 1 F - 3 F(default 2F) Fahrenheit value is 2 times of centigrade value 0340 2stage hysteresis 1 F - 3 F(default 2F) Fahrenheit value is 2 times of centigrade value

1 F - 3 F(default 2F)

Fahrenheit value is 2 times of centigrade value 0500 Furnace Change Reminder 0 - furnace filter reminder off 1 - 10 run time days 2 - 30 run time days 3 - 60 run time days 4 - 90 run time days 5 - 120 run time days 6 - 365 run time days Run time based on call for fan. 0530 Adaptive Intelligent Recovery 1 - Adaptive Intelligent Recovery control is activated (system starts early so set point is reached by start of program period). 0 - Conventional Recovery (system starts recovery at programmed time)

2 - two periods available (Wake and Sleep)

4 - four periods available (Wake, Leave, Return and Sleep) Only shown if schedule is enable. Schedule will default if changed 0580 Minimum Compressor Off Time 5 - five-minute compressor off-time setting (factory setting) 0,2,3,4 - other compressor off-time settings 0600 Heat Temperature Range Stop 40-90 - temperature range (1°F increments) of heating set point. Shown in 1/2 °C. 0610 Cool Temperature Range Stop 50-99 - temperature range (1°F increments) of cooling set point. Shown in 1/2 °C.

12 - 12 hour clock (factory setting)

24 - 24 hour clock 0650 Extended Fan On Time Heat 0 - No extended fan operation after call for heat ends. 90 - Fan operation is extended 90 seconds after call for heat ends. Not shown in Cool Only Systems 0660 Extended Fan On Time Cool 0 - No extended fan operation after call for cool ends 90 - Fan operation is extended 90 seconds after call for cool ends. Not shown in Heat Only Systems.

0 - unlocked keypad

1 - locked keypad When key Locked only ability to enter User Setup to unlock. 0700 Temperature Display Offset -9°F ~ 9°F (°F as temperature format) -4.5°C ~ 4.5°C (°C as temperature format) 0°F (0°C) (factory setting) 0710 Reset thermostat 0 - no thermostat reset. 1 - Resets all Installer Setup Options to default values and resets schedule to default setting. Only calendar settings and time are retained.

Follow these steps to enter the User Setup:

1. Press and hold the key for approximately 3 seconds until the screen change. Menu number display at bottom right corner. 2. Press or key to cutover submenu, and press key enter submenu. Under submenu Use or to set parameters. 3. Press key to exit and confirm the user setup, or press to exit without saving changes. Note: See Tables 3 for the User Setup Numbers and Settings, and see chapter INSTALLER SETUP for Operations Reference.

Table 3. User Setup Settings.

Number Description Settings 0140 See MAC and version 0150 Date and time current calendar date and time 0320 Display temperature in °F or °C 0 - °F setting (factory setting) 1 - °C setting 0640 Clock format 12 - 12-hour clock(factory setting) 24 - 24-hour clock

0 - unlocked keypad

1 - locked keypad 0700 Temperature Display Offset -3°F ~ 3°F (°F as temperature format) -1.5°C ~ 1.5°C (°C as temperature format) 0°F (0°C) (factory setting) 0710 Reset Thermostat 0 - No thermostat reset. 1 - Resets all Installer Setup Options to default values and resets schedule to default setting.

Consult USER SETUP, choose

submenu number 0150 enter date and time setting. 2. Press to switch date to time follows order: year, month, day, hour, and minute. Press or to adjust the time. (You can advance the time more quickly by holding the key or key buttons.) 3. Press to save changes and exit or press to exit without change the date and time. Fig.25

Setting the fan

1. Press to select fan operation. 2. Press again to select ON or AUTO (toggle to re-select). The selected option blinks. 4. Press to save setting. Your selection, or press to exit without saving changes. ON: Fan is always on. AUTO: Fan runs only when the heating or cooling system is on. Fig.26

Selecting system mode

1. Press to display options. 2. Press again to select an option. You may need to press two or three times to make a selection—the selected option blinks. 3. Press to save setting. Your selection, or press to exit without saving changes. Fig.27

Possible system modes:

HEAT: Controls only the heating system. COOL: Controls only the cooling system. OFF: Heating/cooling systems are off. AUTO: Selects heating or cooling depending on the indoor temperature. EMER (heat pumps with aux. heat): Controls auxiliary/emergency heat. Compressor is locked out. Note: The AUTO and EMER system settings may not appear, depending on how your thermostat was installed. Note: when under auto mode press key can switch set temperature between heat and cool.

Set Temperature Overrides

Lake has two temperature override options: Override Until and Permanent Override. Override Until Holds temperature temporarily until the next scheduled period time. 1. Press or key to adjust temperature you want, the icon until appears above time, and the time becomes next scheduled period time. 2. Press key to exit and confirm the changes, or press to exit without saving changes. 3. If you want to exit Override Until, please press key. Override Until will be also exit until reach the next scheduled period time. Note: The current day of the week should already be set correctly. If not, see User Setup to set the date and time setting.

Keep user set-point permanently.

1. Press key once. Screen shows Permanent Hold. 2. Press or key to adjust temperature you want. 3. If you want to exit, please press key again.

Clean Thermostat Screen

The thermostat has a touch screen interaction. Follow these steps to clean the screen without making thermostat changes: 1. Press and hold the key for approximately 3 seconds until the screen changes. Thermostat locks out all touch keys for 30 seconds to allow for cleaning. See Fig. 28. 2. Use damp cloth slightly moistened with water or house-hold glass cleaner to clean the screen. Fig.28. When time up, press key to return

to the Home Screen and normal

operation. See Fig.29. Fig.29. IMPORTANT: Do not spray any type of liquid directly on the thermostat itself. If using household glass cleaner, spray cleaner on cloth. Then use a cloth to clean the thermostat screen.

In User or Installer Setup, menu 0670 allows you to prevent changes to all of the

touchscreen functions. In this case, all keys are locked and not functional, the screen displays a lock icon continuously. Even so, you can though User setup to unlock keys and restore the touchscreen functions.

Setting filter reminder

intervals If activated during installation, the filter reminder alerts you with flashes one screen above the time when it is time to replace your filter. Press after changing the filter, to restart the timer. To change the reminder interval: 1. Press and hold the key for approximately 3 seconds until the screen changes. 2. Press or to select the desired interval (in days), then press to save and exit, or press to exit without save. Fig.30

1. System setting function 0500

governs the filter interval maximum. 2. The days are counted as fan run time, so anytime the fan is running, the reminder is counting that time against the number of days selected.

Connecting to your Wi-Fi network

To complete this process, you must have a smart phone connected to your home wireless network. Please scan the following code to download “Lake Plus” APP. If you get stuck... At any point in this procedure, restart the thermostat by removing the thermostat from the wall plate, wait a few seconds, and snap it back onto the wall plate. Return to Step 1 in this procedure, which starts on the next page.

1. Please be sure your phone has

connected WIFI (don’t connect the hidden internet), download “Lake Plus”. 2. Open APP and register. Fig. 31. Fig. 32. 3. After login, press top left corner , choose WIFI connection and input the WIFI password, DON’T press the “connect” and continue next step first. Fig. 33. Fig. 34.

4. Press the key

on thermostat screen till the “ ” flash. 5. Now you can press the “connect” on app, app will show processing and after seconds it will show successfully. Fig. 36. Fig. 37.

1. IF connect WIFI successfully, it will

show on the thermostat, otherwise will show . 2. Each configuration need to be finished within 5minutes, otherwise the thermostat will quit to configure.

Just need to press the

on homepage,Lake will switch to leave mode. (You can set the temperature you need under leave mode, see the following programming to set the temperature) If Lake has been under leave mode, press on homepage to quit the mode and recover the previous status. Fig. 38.

Table 4. Schedule Default Program Settings.

Schedule Period Time Set points Fan Setting Heat Cool Wake 6:00AM 68°F (20°C) 78°F (26°C) Auto Leave 8:00AM 60°F (16°C) 85°F (29°C) Auto Return 4:00PM 68°F (20°C) 78°F (26°C) Auto Sleep 10:00PM 60°F (16°C) 82°F (28°C) Auto

Program Heating and Cooling Schedule

Your thermostat can control up to four different schedule periods per day: Wake - Period when you awaken and want your home at a comfortable temperature. Leave - Period when you are away from home and want an energy-saving temperature. Return - Period when you return home and want your home back to a comfortable temperature. Sleep - Period when you are asleep and want an energy-saving temperature. NOTE: Schedule times are in 15-minute intervals.

, the screen will

change. See Fig. 39 and 40. Fig.39. 2. In this case, the time will blink, press or to adjust the time. Press to turn to next setting. 3. Then, the temperature will start to blink, press or to adjust the temperature. Press to turn to next time period. Fig.40.

Repeat the above steps until completing the setting of four time periods. Then, Press

to turn to next day, until completing the setting of a week. 5. End of Program Setting, You may press key to exit and confirm the program setting, or press to exit without saving changes. NOTE: The Fan setting is auto as default and cannot be programmed.

Copy one-day program

After entering a day program you can copy this into another day to save time when creating a weekly program: for example, if you want to copy the program of Monday to Thursday, the methods are as follows: 1. Select the program for Monday, complete the setting of Monday and press , the icon appears on the screen, and the icon Will blink, that indicates Waiting to be selected or skipped. Press to select, press to skip. 2. Copy to Thursday: press or to select Thursday, then press to finish the copying and the icon disappears. 3. Copying for other days, please repeat from the Step 1 to 2. One time you can copy to one day or many days.

Your thermostat can reset schedule setup option to default setting.

Press and hold key for approximately 3 seconds until the screen change as Fig.41, then release key. Now, the setting of schedule reset to default setting as table 4. Fig. 41.

No LCD display

Thermostat is not being powered. Check 24VAC between C and R. Temperature settings do not change. The upper or lower temperature limits were reached. Check temperature set-points. Check Installer Setup Numbers 0600 or 0610, modify as needed. The keypad is fully locked. Check Installer Setup Number 0670 to change keypad locked options.

Heating or cooling

does not come on. Thermostat minimum off-time is activated. Wait up to five minutes for the system to respond. System selection is not set to Heat or Cool. Set system Selection to correct position. System type Selection is incorrect. Check Installer Setup Number 0170 and make sure correct System type is chosen.

Thermostat is calling

for Heat (Heat on) or Cool (Cool on) but no heating or cooling is running. Heating or cooling equipment is not operating. Check wiring. Check Installer Setup Number 0170 and make sure correct system type is chosen. Verify operation of equipment in System Test mode. Fan does not turn on in a call for heat (electric furnace). Fan Control in Heating is set to Gas or Oil Furnace (Setting 0180). Set Fan Control in Heating to Electric Furnace (Setting 0180).

Heat pump puts out

cool air in the heat mode and warm air in the cool mode. Changeover Valve is not configured to match the changeover required by the installed heat pump. Set Changeover Valve (Installer Setup Number 0190) to match the changeover required by the installed heat pump. Both the heating and cooling equipment are running at the same time. The heating equipment is not a heat pump but the System Type is set to Heat Pump. Set System Type (Installer Setup Number 0170) to match the installed heating and/or cooling equipment. Heating and cooling wires are shorted together. Separate the shorted heating and cooling wires.

Heating equipment is

running in the cool mode. Heating equipment is not a heat pump but System Type (Installer Setup Number 0170) is set to Heat Pump. Set System Type (Installer Setup Number 0170) to match the installed heating and/or cooling equipment. Heating equipment does not turn off and heat temperature setting is set below room temperature Heating equipment is not a heat pump but System Type (Installer Setup Number 0170) is set to Heat Pump. Set System Type (Installer Setup Number 0170) to match the installed heating and/or cooling equipment.

Heat or Cool.

System Type is set to Cool Only or Heat Only or Heat Only with Fan. Set System Type (Installer Setup Number 0170) to match the installed equipment. Heat On is not in the display. System is not set to Heat and/or temperature is not above room temperature. Set the system setting to Heat and set the temperature setting above the room temperature. Cool On is not in the display. System is not set to Cool and/or temperature is not below room temperature. Set the system setting to Cool and set the temperature setting below the room temperature.

Wait is in the display.

Compressor minimum off timer is active. Wait up to five minutes for the cooling or heating (heat pump) equipment to turn on. Screen Locked appears on the screen and the keys do not respond. The keypad is locked. Check Installer Setup Number 0670 to change keypad locked options.