Huawei NetCol5000-C Operation & User’s Manual
Read Online
Read the Huawei NetCol5000-C Operation & User’s Manual online using the built-in PDF viewer.
Text of the manual
NetCol5000-C(065, 080) In-row Chilled Water
Smart Cooling Product
User Manual
Issue
07
Date
2020-03-16
HUAWEI TECHNOLOGIES CO., LTD.
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
i
Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.
Trademarks and Permissions
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Huawei Technologies Co., Ltd.
Address:
Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China
Website:
https://e.huawei.com
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
About This Document
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
ii
About This Document
Purpose
This document describes the NetCol5000-C(065, 080) full-size chilled water smart cooling
product (NetCol5000-C for short) in terms of the product description, indoor unit installation,
commissioning, and system operation and maintenance, helping readers to systematically
master the usage and maintenance of the NetCol5000-C.
The figures provided in this document are for reference only.
Intended Audience
This document is intended for:
Sales engineers
Technical support engineers
System engineers
Hardware installation engineers
Commissioning engineers
Data configuration engineers
Maintenance engineers
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol
Description
Indicates a hazard with a high level of risk which, if not avoided,
will result in death or serious injury.
Indicates a hazard with a medium level of risk which, if not
avoided, could result in death or serious injury.
Indicates a hazard with a low level of risk which, if not avoided,
could result in minor or moderate injury.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
About This Document
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
iii
Symbol
Description
Indicates a potentially hazardous situation which, if not avoided,
could result in equipment damage, data loss, performance
deterioration, or unanticipated results.
NOTICE is used to address practices not related to personal
injury.
Supplements the important information in the main text.
NOTE is used to address information not related to personal
injury, equipment damage, and environment deterioration.
Change History
Changes between document issues are cumulative. The latest document issue contains all the
changes made in earlier issues.
Issue 07 (2020-03-16)
Optimized the Preparations and WebUI Login section.
Issue 06 (2019-12-20)
Updated the safety information.
Issue 05 (2019-06-26)
Updated chilled water valve.
Issue 04 (2019-04-20)
Added the description of installing a water sensor.
Issue 03 (2019-01-15)
Updated the manual name and so on.
Issue 02 (2018-09-15)
Canceled the configuration of the condensate pump.
Issue 01 (2018-01-25)
This issue is the first official release.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Contents
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
iv
Contents
About This Document ............................................................................................................... ii
1 Safety Information ................................................................................................................... 1
1.1 General Safety ....................................................................................................................................................... 1
1.2 Personnel Requirements ........................................................................................................................................ 4
1.3 Electrical Safety .................................................................................................................................................... 4
1.4 Installation Environment Requirements .................................................................................................................. 6
1.5 Mechanical Safety ................................................................................................................................................. 7
1.6 Cooling System Safety .........................................................................................................................................10
1.7 Others ..................................................................................................................................................................10
2 Product Description ............................................................................................................... 11
2.1 Model Description ................................................................................................................................................ 11
2.2 Component ...........................................................................................................................................................12
2.2.1 Appearance and Components .............................................................................................................................12
2.2.2 Controller ..........................................................................................................................................................14
2.2.2.1 Appearance and Ports ......................................................................................................................................14
2.2.2.2 Functions and Features ....................................................................................................................................17
2.2.3 Monitoring System ............................................................................................................................................18
2.3 Application Conditions .........................................................................................................................................20
2.4 Technical Specifications .......................................................................................................................................23
2.5 Performance Curves .............................................................................................................................................24
3 Installation .............................................................................................................................. 26
3.1 Installation Precautions .........................................................................................................................................26
3.1.1 Tools .................................................................................................................................................................27
3.1.2 Pipe Connection ................................................................................................................................................28
3.1.3 Material Preparations .........................................................................................................................................29
3.1.3.1 Automatic Drainpipe .......................................................................................................................................29
3.1.3.2 (Optional) Condensate Pump Drainpipe ..........................................................................................................30
3.1.3.3 (Optional) Humidifier Water Inlet Pipe ............................................................................................................31
3.1.3.4 Chilled Water Inlet and Outlet Pipes ................................................................................................................32
3.1.3.5 Pipe Support ...................................................................................................................................................32
3.1.3.6 Cables ............................................................................................................................................................33
3.1.4 Structural Specifications ....................................................................................................................................34
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Contents
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
v
3.1.4.1 NetCol5000-C065 external structure ...............................................................................................................34
3.1.4.2 NetCol5000-C080 external structure ...............................................................................................................35
3.1.4.3 Cabinet Holes .................................................................................................................................................35
3.2 Unpacking ............................................................................................................................................................36
3.3 Installation Process ...............................................................................................................................................37
3.4 Checking the nitrogen pressure .............................................................................................................................37
3.5 Removing the Pallet .............................................................................................................................................39
3.6 Leveling and Combining Cabinets ........................................................................................................................40
3.7 Securing the NetCol5000-C ..................................................................................................................................42
3.8 Connecting Water Pipes ........................................................................................................................................42
3.8.1 Connect Automatic Drainpipe ............................................................................................................................42
3.8.2 (Optional) Connecting the Water Pump Drainpipe ..............................................................................................44
3.8.3 (Optional) Connecting the Humidifier Water Inlet Pipe .......................................................................................45
3.8.4 Connecting the Chilled Water Inlet and Outlet Pipes ...........................................................................................46
3.8.4.1 Connecting Seamless Steel Pipes .....................................................................................................................46
3.8.4.2 Connecting Aluminum Plastic Pipes ................................................................................................................47
3.9 (Optional) Performing a Leakage Test with Nitrogen .............................................................................................49
3.10 Injecting Water to Expel Gas ...............................................................................................................................50
3.11 (Optional) Leakage Test with Water ....................................................................................................................51
3.12 Cable Connections ..............................................................................................................................................51
3.12.1 Overview and Precautions ................................................................................................................................51
3.12.2 Connecting Power Cables ................................................................................................................................51
3.12.3 Connecting an Equipotential PE Cable .............................................................................................................53
3.12.4 Teamwork Networking and Monitoring ............................................................................................................54
3.12.4.1 Main Control Panel .......................................................................................................................................54
3.12.4.2 Signal Ports ..................................................................................................................................................55
3.12.4.3 Connecting the Teamwork Network Cable .....................................................................................................55
3.12.4.3.1 Connecting the FE Teamwork Network Cable .............................................................................................55
3.12.4.3.2 Connecting the CAN Teamwork Cable .......................................................................................................56
3.12.4.4 Connecting the Monitoring Network Cable ....................................................................................................57
3.12.4.4.1 Connecting the FE Monitoring Network Cable (SNMP/Modbus-TCP) ........................................................57
3.12.4.4.2 Connecting the RS485 Monitoring Network Cable (Modbus-RTU) .............................................................57
3.12.5 Connecting the Water Sensor............................................................................................................................59
3.12.6 Connecting the T/H Sensor Outside the Cabinet ...............................................................................................59
3.12.7 (Optional) Installing a Differential Pressure Sensor ..........................................................................................61
3.13 Checking After Installation .................................................................................................................................62
4 Commissioning....................................................................................................................... 64
4.1 Power-On .............................................................................................................................................................64
4.2 Home Screen ........................................................................................................................................................69
4.3 Initial Configuration .............................................................................................................................................71
4.3.1 Setting Temperature and Humidity Values and (Optional) Enabling T/H Sensors.................................................71
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Contents
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
vi
4.3.2 (Optional) Setting the Pressure Difference Control .............................................................................................74
4.3.3 Setting Teamwork Control Parameters................................................................................................................75
4.3.4 Setting Communications Parameters ..................................................................................................................81
4.3.4.1 Setting Communications Parameters (Modbus RTU Protocol) .........................................................................81
4.3.4.2 Setting Communications Parameters (Modbus TCP Protocol) ..........................................................................81
4.3.4.3 Setting Communications Parameters (SNMP Protocol) ....................................................................................83
4.3.5 (Optional) Setting WIFI Parameters ...................................................................................................................88
4.4 Startup..................................................................................................................................................................89
4.5 Startup Wizard ......................................................................................................................................................93
4.6 (Optional) Power-off ............................................................................................................................................97
4.7 Checking After Commissioning ............................................................................................................................98
5 WebUI ...................................................................................................................................... 99
5.1 Preparations and WebUI Login .............................................................................................................................99
5.2 WebUI Introduction ............................................................................................................................................ 101
6 System Operation and Maintenance ................................................................................. 105
6.1 Routine Maintenance .......................................................................................................................................... 105
6.1.1 Routine Maintenance Overview ....................................................................................................................... 105
6.1.2 Routine Maintenance Item ............................................................................................................................... 106
6.2 Alarm References ............................................................................................................................................... 108
6.3 Troubleshooting.................................................................................................................................................. 153
6.4 Parts Replacement .............................................................................................................................................. 155
6.4.1 Replacement Requirements .............................................................................................................................. 155
6.4.2 Replacing the Air Filter .................................................................................................................................... 156
6.4.3 Replacing the Humidifier Pump ....................................................................................................................... 157
6.4.4 Replacing the Fan ............................................................................................................................................ 159
6.4.5 Replacing the Wet Film Humidifier .................................................................................................................. 160
6.4.6 Replacing the Differential Pressure Switch ....................................................................................................... 161
6.4.7 Replacing the T/H Sensor ................................................................................................................................ 162
6.4.8 Replacing the Return Air Temperature Sensor .................................................................................................. 163
6.4.9 Replacing the Supply Air Temperature Sensor .................................................................................................. 164
6.4.10 Replacing the Water Inlet or Outlet Temperature Sensor ................................................................................. 166
6.4.11 Replacing a rectifier ....................................................................................................................................... 167
6.4.12 Replacing the Water Valve Actuator 1 ............................................................................................................. 168
6.4.13 Replacing Water Valve Actuator 2 .................................................................................................................. 169
6.4.14 Replacing the Chilled Water Valve ................................................................................................................. 172
6.4.15 Replacing the Controller Panel ....................................................................................................................... 173
7 FAQ ........................................................................................................................................ 175
7.1 Operations on the LCD ....................................................................................................................................... 175
7.1.1 Querying Temperature and Humidity Curves .................................................................................................... 175
7.1.2 Querying Logs ................................................................................................................................................. 176
7.1.3 Querying Component Status............................................................................................................................. 176
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Contents
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
vii
7.1.4 Querying System Parameters ........................................................................................................................... 177
7.1.5 Querying Version Details ................................................................................................................................. 178
7.1.6 How to View Teamwork Control Information ................................................................................................... 179
7.1.7 How to Silence the Buzzer ............................................................................................................................... 180
7.1.8 How Can I Handle Active Alarms? ................................................................................................................... 181
7.1.9 Deleting Historical Alarms ............................................................................................................................... 182
7.1.10 Deleting Logs ................................................................................................................................................ 183
7.1.11 Clearing the Runtime ..................................................................................................................................... 184
7.1.12 Calibrating a Sensor ....................................................................................................................................... 184
7.1.13 Calibrating the Screen .................................................................................................................................... 185
7.1.14 How to Modify a Password ............................................................................................................................ 186
7.1.15 How to Set Alarm Parameters ........................................................................................................................ 188
7.1.16 How to Commission Single Component ......................................................................................................... 189
7.1.17 Restoring Factory Settings ............................................................................................................................. 190
7.1.18 Which Parameters Are Restored to Default Values After Default Settings Are Operated .................................. 193
7.1.19 Exporting Data .............................................................................................................................................. 193
7.1.20 How to Export and Import a Configuration file ............................................................................................... 195
7.1.21 How to Import a Certificate and a Key ........................................................................................................... 198
7.1.22 Correlation Relationship of Parameters .......................................................................................................... 199
7.2 WebUI Operations .............................................................................................................................................. 201
7.2.1 How to Manage WebUI Users? ........................................................................................................................ 201
7.2.2 How to Install a Network Security Certificate? ................................................................................................. 203
7.2.3 How Can I View Active Alarms and Historical Alarms?.................................................................................... 204
7.2.4 How Can I Export or Import a Configuration File? ........................................................................................... 204
7.2.5 How Can I Export Fault Information? .............................................................................................................. 205
7.2.6 How Can I Change the Smart Cooling Product IP Address on the WebUI? ........................................................ 205
7.2.7 How Can I View Version Information? ............................................................................................................. 206
A Glycol Adding Requirements............................................................................................ 207
B Acronyms and Abbreviations ............................................................................................ 208
C Base Dimensions ................................................................................................................. 209
D Electrical Conceptual Diagram .......................................................................................... 210
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
1 Safety Information
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
1
1 Safety Information
1.1 General Safety
Statement
Before installing, operating, and maintaining the equipment, read this document and observe
all the safety instructions on the equipment and in this document.
The "NOTICE", "CAUTION", "WARNING", and "DANGER" statements in this document
do not cover all the safety instructions. They are only supplements to the safety instructions.
Huawei will not be liable for any consequence caused by the violation of general safety
requirements or design, production, and usage safety standards.
Ensure that the equipment is used in environments that meet its design specifications.
Otherwise, the equipment may become faulty, and the resulting equipment malfunction,
component damage, personal injuries, or property damage are not covered under the warranty.
Follow local laws and regulations when installing, operating, or maintaining the equipment.
The safety instructions in this document are only supplements to local laws and regulations.
Huawei will not be liable for any consequences of the following circumstances:
Operation beyond the conditions specified in this document
Installation or use in environments which are not specified in relevant international or
national standards
Unauthorized modifications to the product or software code or removal of the product
Failure to follow the operation instructions and safety precautions on the product and in
this document
Equipment damage due to force majeure, such as earthquakes, fire, and storms
Damage caused during transportation by the customer
Storage conditions that do not meet the requirements specified in this document
General Requirements
Do not install, use, or operate outdoor equipment and cables (including but not limited to
moving equipment, operating equipment and cables, inserting connectors to or removing
connectors from signal ports connected to outdoor facilities, working at heights, and
performing outdoor installation) in harsh weather conditions such as lightning, rain,
snow, and level 6 or stronger wind.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
1 Safety Information
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
2
Before installing, operating, or maintaining the equipment, remove any conductive
objects such as watches or metal jewelry like bracelets, bangles, and rings to avoid
electric shock.
When installing, operating, or maintaining the equipment, wear dedicated protective
gears such as insulation gloves, goggles, and safety clothing, helmet, and shoes, as
shown in the following figure.
Follow the specified procedures for installation, operation, and maintenance.
Before handling a conductor surface or terminal, measure the contact point voltage and
ensure that there is no risk of electric shock.
After installing the equipment, remove idle packing materials such as cartons, foam,
plastics, and cable ties from the equipment area.
In the case of a fire, immediately leave the building or the equipment area, and turn on
the fire alarm bell or make an emergency call. Do not enter the building on fire in any
case.
Do not stop using protective devices. Pay attention to the warnings, cautions, and related
precautionary measures in this document and on the equipment. Promptly replace
warning labels that have worn out.
Keep irrelevant people away from the equipment. Only operators are allowed to access
the equipment.
Use insulated tools or tools with insulated handles, as shown in the following figure.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
1 Safety Information
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
3
All cable holes should be sealed. Seal the used cable holes with firestop putty. Seal the
unused cable holes with the caps delivered with the cabinet. The following figure shows
the criteria for correct sealing with firestop putty.
Do not scrawl, damage, or block any warning label on the equipment.
Tighten the screws using tools when installing the equipment.
Do not work with power on during installation.
Repaint any paint scratches caused during equipment transportation or installation in a
timely manner. Equipment with scratches cannot be exposed to an outdoor environment
for a long period of time.
Before operations, ensure that the equipment is firmly secured to the floor or other solid
objects, such as a wall or an installation rack.
Do not use water to clean electrical components inside or outside of a cabinet.
Do not change the structure or installation sequence of equipment without permission.
Do not touch a running fan with your fingers, components, screws, tools, or boards
before the fan is powered off or stops running.
Personal Safety
If there is a probability of personal injury or equipment damage during operations on the
equipment, immediately stop the operations, report the case to the supervisor, and take
feasible protective measures.
To avoid electric shock, do not connect safety extra-low voltage (SELV) circuits to
telecommunication network voltage (TNV) circuits.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
1 Safety Information
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
4
Do not power on the equipment before it is installed or confirmed by professionals.
1.2 Personnel Requirements
Personnel who plan to install or maintain Huawei equipment must receive thorough
training, understand all necessary safety precautions, and be able to correctly perform all
operations.
Only qualified professionals or trained personnel are allowed to install, operate, and
maintain the equipment.
Only qualified professionals are allowed to remove safety facilities and inspect the
equipment.
Personnel who will operate the equipment, including operators, trained personnel, and
professionals, should possess the local national required qualifications in special
operations such as high-voltage operations, working at heights, and operations of special
equipment.
Professionals: personnel who are trained or experienced in equipment operations and are
clear of the sources and degree of various potential hazards in equipment installation,
operation, maintenance
Trained personnel: personnel who are technically trained, have required experience, are
aware of possible hazards on themselves in certain operations, and are able to take
protective measures to minimize the hazards on themselves and other people
Operators: operation personnel who may come in contact with the equipment, except
trained personnel and professionals
Only professionals or authorized personnel are allowed to replace the equipment or
components (including software).
1.3 Electrical Safety
Grounding
For the equipment that needs to be grounded, install the ground cable first when
installing the equipment and remove the ground cable last when removing the
equipment.
Do not damage the ground conductor.
Do not operate the equipment in the absence of a properly installed ground conductor.
Ensure that the equipment is connected permanently to the protective ground. Before
operating the equipment, check its electrical connection to ensure that it is securely
grounded.
General Requirements
Use dedicated insulated tools when performing high-voltage operations.
AC and DC Power
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
1 Safety Information
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
5
Do not connect or disconnect power cables with power on. Transient contact between the core
of the power cable and the conductor will generate electric arcs or sparks, which may cause
fire or personal injury.
If a "high electricity leakage" tag is attached on the equipment, ground the protective
ground terminal on the equipment enclosure before connecting the AC power supply;
otherwise, electric shock as a result of electricity leakage may occur.
Before installing or removing a power cable, turn off the power switch.
Before connecting a power cable, check that the label on the power cable is correct.
If the equipment has multiple inputs, disconnect all the inputs before operating the
equipment.
A circuit breaker equipped with a residual current device (RCD) is not recommended.
A damaged power cable must be replaced by the manufacturer, service agent, or
professionals to avoid risks.
High voltage operations and installation of AC-powered facilities must be performed by
qualified personnel.
Cabling
When routing cables, ensure that a distance of at least 30 mm exists between the cables
and heat-generating components or areas. This prevents damage to the insulation layer of
the cables.
Do not route cables behind the air intake and exhaust vents of the equipment.
Ensure that cables meet the VW-1 flame spread rating requirements.
Bind cables of the same type together. When routing cables of different types, ensure that
they are at least 30 mm away from each other.
If an AC input power cable is connected to the cabinet from the top, bend the cable in a
U shape outside the cabinet and then route it into the cabinet.
When the temperature is low, violent impact or vibration may damage the plastic cable
sheathing. To ensure safety, comply with the following requirements:
Cables can be laid or installed only when the temperature is higher than 0°C. Handle
cables with caution, especially at a low temperature.
Cables stored at subzero temperatures must be stored at room temperature for at least 24
hours before they are laid out.
Do not perform any improper operations, for example, dropping cables directly from a
vehicle.
When selecting, connecting, and routing cables, follow local safety regulations and rules.
ESD
The static electricity generated by human bodies may damage the electrostatic-sensitive
components on boards, for example, the large-scale integrated (LSI) circuits.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
1 Safety Information
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
6
Wear ESD gloves or a well-grounded ESD wrist strap when touching the device or
handling boards or application-specific integrated circuits (ASICs).
When holding a board, hold its edge without touching any components. Do not touch the
components with your bare hands.
Package boards with ESD packaging materials before storing or transporting them.
Figure 1-1 Wearing an ESD wrist strap
Neutral-Ground Voltage
It is recommended that the three-phase loads be equalized and the neutral-ground voltage be
kept at less than 2 V to meet power distribution requirements.
1.4 Installation Environment Requirements
To prevent fire due to high temperature, ensure that the ventilation vents or heat
dissipation system are not blocked when the equipment is running.
Install the equipment in an area far away from liquids. Do not install it under areas prone
to condensation, such as under water pipes and air exhaust vents, or areas prone to water
leakage, such as air conditioner vents, ventilation vents, or feeder windows of the
equipment room. Ensure that no liquid enters the equipment to prevent faults or short
circuits.
If any liquid is detected inside the equipment, immediately disconnect the power supply
and contact the administrator.
Do not expose the equipment to flammable or explosive gas or smoke. Do not perform
any operation on the equipment in such environments.
Ensure that the equipment room provides good heat insulation, and the walls and floor
are dampproof.
Install a rat guard at the door of the equipment room.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
1 Safety Information
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
7
Installation at Heights
Working at heights refers to operations that are performed at least 2 meters above the
ground.
Do not work at heights if the steel pipes are wet or other potential danger exists. After the
preceding conditions no longer exist, the safety director and relevant technical personnel
need to check the involved equipment. Operators can begin working only after obtaining
consent.
When working at heights, comply with local relevant laws and regulations.
Only trained and qualified personnel are allowed to work at heights.
Before working at heights, check the climbing tools and safety gears such as safety
helmets, safety belts, ladders, springboards, scaffolding, and lifting equipment. If they do
not meet the requirements, take corrective measures or disallow working at heights.
Wear personal protective equipment such as the safety helmet and safety belt or waist
rope and fasten it to a solid structure. Do not mount it on an insecure moveable object or
metal object with sharp edges. Make sure that the hooks will not slide off.
Set a restricted area and eye-catching signs for working at heights to warn away
irrelevant personnel.
Carry the operation machinery and tools properly to prevent them from falling off and
causing injuries.
Personnel involving working at heights are not allowed to throw objects from the height
to the ground, or vice versa. Objects should be transported by tough slings, hanging
baskets, highline trolleys, or cranes.
Ensure that guard rails and warning signs are set at the edges and openings of the area
involving working at heights to prevent falls.
Do not pile up scaffolding, springboards, or other sundries on the ground under the area
involving working at heights. Do not allow people to stay or pass under the area
involving working at heights.
Inspect the scaffolding, springboards, and workbenches used for working at heights in
advance to ensure that their structures are solid and not overloaded.
Any violations must be promptly pointed out by the site manager or safety supervisor
and the involved personnel should be prompted for correction. Personnel who fail to stop
violations will be forbidden from working.
1.5 Mechanical Safety
Hoisting Devices
Do not walk under hoisted objects.
Only trained and qualified personnel should perform hoisting operations.
Check that hoisting tools are available and in good condition.
Before hoisting objects, ensure that hoisting tools are firmly secured onto a load-bearing
object or wall.
Ensure that the angle formed by two hoisting cables is no more than 90 degrees, as
shown in the following figure.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
1 Safety Information
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
8
Do not drag steel ropes and hoisting tools or bump hoisted objects against hard objects
during hoisting.
Using Ladders
Use wooden or fiberglass ladders when you need to perform live working at heights.
When a step ladder is used, ensure that the pull ropes are secured and the ladder is held
firm.
Before using a ladder, check that it is intact and confirm its load bearing capacity. Do not
overload it.
Ensure that the ladder is securely positioned. The recommended angle for a ladder
against the floor is 75 degrees, as shown in the following figure. An angle rule can be
used to measure the angle. Ensure that the wider end of the ladder is at the bottom, or
protective measures have been taken at the bottom to prevent the ladder from sliding.
When climbing a ladder, take the following precautions to reduce risks and ensure
safety:
Keep your body steady.
Do not climb higher than the fourth rung of the ladder from the top.
Ensure that your body's center of gravity does not shift outside the legs of the ladder.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
1 Safety Information
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
9
Drilling Holes
When drilling holes into a wall or floor, observe the following safety precautions:
Do not drill holes into the equipment. Doing so may affect the electromagnetic shielding of
the equipment and damage components or cables inside. Metal shavings from drilling may
short-circuit boards inside the equipment.
Obtain the consent from the customer, subcontractor, and Huawei before drilling.
Wear goggles and protective gloves when drilling holes.
When drilling holes, protect the equipment from shavings. After drilling, clean up any
shavings that have accumulated inside or outside the equipment.
Moving Heavy Objects
When removing a heavy or unstable component from a cabinet, be aware of unstable or heavy
objects on the cabinet.
Be cautious to avoid injury when moving heavy objects.
When moving the equipment by hand, wear protective gloves to prevent injuries.
Move or lift the equipment by holding its handles or lower edges. Do not hold the
handles of modules (such as power supply units, fans, and boards) that are installed in
the equipment because they cannot support the weight of the equipment.
Avoid scratching the cabinet surface or damaging cabinet components and cables during
equipment transportation.
When transporting the equipment using a forklift truck, ensure that the forks are properly
positioned to ensure that the equipment does not topple. Before moving the equipment,
secure it to the forklift truck using ropes. When moving the equipment, assign dedicated
personnel to take care of it.
Choose railways, sea, or a road with good condition for transportation to ensure
equipment safety. Avoid tilt or jolt during transportation.
Move a cabinet with caution. Any bumping or falling may damage the equipment.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
1 Safety Information
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
10
1.6 Cooling System Safety
Welding
At least two persons are required on a welding site.
A welder must have a work permit.
A welding site must be free from inflammables.
Ensure that a fire extinguisher, wet wiper, and water container are available.
A burning welding torch must not be placed on a component or on the floor, and must
not be placed in a metal container with acetylene and oxygen. Otherwise, the gas may
leak and cause a fire.
High-temperature pipes after welding must be promptly cooled.
Do not weld or cut on pressurized containers or pipes. Electric devices must be powered
off before welding.
High Temperature and Pressure
When maintaining or replacing components, pay attention to high-temperature
components (such as the compressor, refrigerant pipe, and electric heater) to prevent
scalds.
When maintaining or replacing components, pay attention to high-pressure components
(such as the compressor and refrigerant pipe) to prevent the refrigerant system from
being cracked or exploded due to misoperations.
Refrigerant Frostbite
Refrigerant leakage may cause frostbite. Take protective measures (for example, wear
antifreeze gloves) when handling refrigerant.
Storage and Recycling
Do not store devices near a heat source or under direct sunshine.
Keep devices away from fire or high-temperature objects, especially devices injected
with pressurized nitrogen or refrigerant; otherwise, explosion or refrigerant leakage may
occur, causing personal injury.
The sign indicates that the product cannot be disposed of with other wastes that
have a shell in European Union (EU) areas. To avoid environment pollution and harm to
human health, wastes must be classified and recycled. This also promotes resource reuse.
When recycling a device, fill in the device information in the recycling collection system
or contact your dealer for help. The dealer can help you recycle devices in a safe and
environment-friendly way.
1.7 Others
Exercise caution when shutting down the smart cooling product. Doing so may cause
equipment and room overheating, which will damage the equipment.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
2 Product Description
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
11
2 Product Description
2.1 Model Description
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
2 Product Description
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
12
2.2 Component
2.2.1 Appearance and Components
Appearance
Figure 2-1 NetCol5000-C065
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
2 Product Description
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
13
Figure 2-2 NetCol5000-C080
Figure 2-3 Component appearance
Components
The smart cooling product consists of the heat exchanger, chilled water valve, EC fan, air
filter, condensate pump, wet film humidifier (optional), and micro differential pressure sensor
(optional).
Heat exchanger
The I-type finned-tube exchanger with a high cooling efficiency adopts the synergy field
principle and computational fluid dynamics (CFD) to optimize the flow path design,
which greatly improves the heat exchange efficiency.
Chilled water valve
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
2 Product Description
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
14
The chilled water valve, also known as the chilled water proportional integral regulating
valve, features incremental proportional-integral-derivative (PID) control with precise
adjustment and accurate control.
EC fan
−
The axial fan comes from a high-end brand and provides high reliability and a long
service life.
−
The highly efficient EC fan saves more than 30% of energy than a common fan.
−
You can view the power and speed status as well as obtain fault information in real
time over the LCD, allowing you to view the status and locate a fault.
Air filter
The G4 (optional F5) air filter meets requirements for equipment room cleanliness.
Condensate pump
Enhances the reliability in drainage.
Wet film humidifier
−
The wet film humidifier has low water quality requirements and high environment
adaptability. In most cases, tap water can be used without special water treatment.
−
The wet film humidifier has a simple structure and is easy to remove, clean, and
maintain.
−
The wet film humidifier quickly starts and generates huge humidification capacity.
−
The wet film humidifier consumes less than over 95% of energy compared with a
traditional electrode humidifier.
Micro differential pressure sensor
Intelligent differential pressure control (optional): Saves energy compared with the
control mode of a normal fan.
2.2.2 Controller
2.2.2.1 Appearance and Ports
Appearance
The controller provides a 7-inch true color touchscreen and man-machine interfaces for query,
setting, monitoring, and maintenance.
The indicator on the panel displays operating status of the smart cooling product. Figure 2-4
shows the position of the indicator. Table 2-1 describes the mapping between indicators,
buzzers, and alarms. If alarms of different severities (critical, major, minor, or warning) are
raised simultaneously, the indicator status corresponds to the alarm with the highest severity
level and the buzzer status corresponds to the unacknowledged alarm with the highest severity
level.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
2 Product Description
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
15
Figure 2-4 Display panel
(1) Indicator
(2) Display panel
Table 2-1 Indicator and buzzer status description
Alarm Status
Indicator
Buzzer
The device is operating properly, or a
warning is generated.
Green
No buzzing
There is an unacknowledged major
alarm.
Yellow
Intermittent buzzing
There is an unacknowledged critical
alarm.
Red
Constant buzzing
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
2 Product Description
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
16
Ports
Figure 2-5 Controller side ports
Table 2-2 Ports
No.
Name
Note
1
MUS05A
Reserved
2
FE (fast Ethernet)
communications port
3
CAN
communications port for the main control board and
LCD
4
RS485_1
Reserved
5
USB Host
After installing the WiFi module, locally connect to
the smart cooling product over the Service Expert
app. Obtain the initial startup password during
deployment. View or obtain the running information
about the smart cooling product during preventive
maintenance. (Applicable to V200R001C20 and later
versions)
NOTE
Only Huawei service engineers or authorized service engineers
are allowed to use the WiFi module. To ensure security, remove
the WiFi module immediately after use.
Insert the USB flash drive, import and export the
configuration file, export run logs, and upgrade
software.
6
RST
restart switch for the display
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
2 Product Description
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
17
No.
Name
Note
7
SD
Reserved
8
SW1-4
Dual in-line package (DIP) switch on LCD
2.2.2.2 Functions and Features
Functions
Single unit control: Each smart cooling product has an independent control system, LCD,
humidifier, and T/H sensor to ensure its normal operating and high-precision operating.
The controller provides logic control over components in each smart cooling product to
meet the indoor temperature and humidity requirements.
Display and operations: The 7-inch touchscreen of the controller allows you to set
parameters for the device and query the device status.
The smart cooling product has the following four remote functions.
−
Telemetry: supply air temperature, return air temperature, supply air humidity,
return air humidity, and working status of the unit
−
Teleindication: startup/shutdown, overvoltage/undervoltage, supply water
overtemperature/undertemperature, return air overtemperature/undertemperature,
return air overhumidity/underhumidity, air filter normal/blocked, and fan
normal/fault
−
Teleadjust: smart cooling product startup/shutdown
−
Teleadjusting: temperature, humidity, and alarm threshold
Teamwork control: Up to 32 smart cooling products can be networked for teamwork.
When multiple smart cooling products work cooperatively, heat load is optimally
distributed to reduce power consumption and backup is provided to improve reliability.
−
Backup: When a smart cooling product in the group is faulty, the backup smart
cooling product starts to operate automatically to improve the reliability of the
smart cooling product system.
−
Rotation: Each smart cooling product enters the backup mode periodically.
−
On-demand operation: The number of operating smart cooling products varies
depending on the thermal load in the equipment room to meet requirements
promptly, eliminate hot spots, and save energy.
−
Anti-competitive running: A mechanism is adopted to prevent the smart cooling
products in the same equipment room operating in opposite status to save energy.
Remote management: You can monitor, manage, and upgrade one or more smart cooling
products using the remote management software (NetEco, ECC, app, and Web) provided
by Huawei.
A large space is available for recording and storing fault alarm data, and 1500 historical
alarms can be stored.
Access logs can be traced back. At least 1000 historical login and setting records can be
stored.
The monitoring system displays 30 days' temperature and humidity in colored curves.
O&M personnel can view the unit operating status onsite.
A comprehensive power monitoring function is provided. Faults such as overvoltage,
undervoltage, mains power failure, high frequency, and low frequency are diagnosed and
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
2 Product Description
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
18
appropriate alarms are reported and recorded. Automatic protection, recovery, and restart
are also provided.
The embedded wizard commissioning program guides the operator through the startup
commissioning. The controller automatically collects or instructs the operator to collect
the operating data produced in the process, and analyzes the commissioning result
automatically. This ensures the commissioning quality, simplifies the startup
commissioning, and shortens the commissioning duration.
The embedded professional fault diagnosis system automatically locates the fault cause
and instructs the operator to rectify the fault. This simplifies fault handling and improves
efficiency.
The controller displays the current cooling load rate and recommended optimal water
temperature (intelligently calculated to meet current load requirements), which helps
lower the power consumption of chillers.
Features
The controller provides a touchscreen with a user-friendly interface.
The controller is highly precise and responsive.
The controller is protected by a multi-level password protection mechanism, avoiding
misoperations.
Password verification upon the first startup is required to ensure that the smart cooling
product is started after valid authentication to avoid quality or security issues caused by
unauthorized startup.
The LCD displays the margin of cooling capacity at the moment so that you can improve
the operating efficiency of the equipment room.
The controller protects the smart cooling product against overvoltage, undervoltage,
abnormal power failure, and water leakage, which ensures the reliable operation of the
system.
The cooling capacity, air volume, as well as the operating status and runtime of each
component in the smart cooling product are displayed on the LCD in real time.
The controller provides a professional fault locating system that automatically displays
the root cause and maintenance policy for the fault, facilitating maintenance.
The controller provides abundant external ports such as FE ports, CAN ports, RS485
ports, and USB ports that are protected by a security mechanism. These ports flexibly
meet the communication requirements and feature good electrical isolation (signal
terminals will not break down or flash over within 1 minute at a 500 V DC voltage to
ground).
The smart cooling product supports communications protocols such as Modbus RTU,
Modbus TCP, and SNMP, facilitating connection to the NetEco.
The controller intelligently identifies abnormal parameter settings (incorrect commands)
and rejects them automatically.
If the indoor temperature is out of the normal range, an audible and visible alarm signal
is sent automatically.
Fans can be maintained without power-off so that the normal operations of other fans
will not be affected.
2.2.3 Monitoring System
The monitoring system provides logic control, data collection, control demand delivering,
alarm reporting, data storage, user right management, and teamwork control functions.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
2 Product Description
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
19
The smart cooling product can interwork with the customer's monitoring system over an
RS485 port or FE port on the monitoring system. If RS485 connection is used, the
Modbus-RTU protocol is supported. If FE connection is used, the Modbus-TCP and SNMP
protocols are supported. Key smart cooling product parameters, including but not limited to
the temperatures and humidity of the supply and return air, power supply status, operating
status, fan status, and alarms, can be uploaded to the monitoring system.
Up to 32 smart cooling products can be connected over an FE port or a controller area
network (CAN) port for teamwork to save energy and extend the service life. Any smart
cooling product can be set as the master unit. The following figure shows the monitoring
system network diagram.
Figure 2-6 FE teamwork network diagram
Figure 2-7 FE monitoring network diagram
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
2 Product Description
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
20
Figure 2-8 Northbound RS485 monitoring network diagram
Figure 2-9 CAN teamwork network diagram
2.3 Application Conditions
If the water inlet temperature exceeds 10°C or the total load is less than 30% of the
cooling capacity of a single smart cooling product, the humidity may be high. The
customer is advised to add a dehumidifier (engineering procurement).
Do not install the smart cooling product near a noise-sensitive place such as an office or a
conference room.
Pipe Ports
The following table describes the ports reserved on the device.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
2 Product Description
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
21
Table 2-3 Pipe Ports
Item
Description
Water outlet pipe
G 1–1/2 in. port with inner threads
Water inlet pipe
G 1–1/2 in. port with inner threads
(Optional) Humidifier water inlet pipe
G 1/2 in. port with inner threads
Automatic drainpipe
BSPP 1/2 in. port with inner threads
Installation Requirements
Table 2-4 Installation Requirements
Item
Description
Room door
2000 mm high: width ≥ 1.2 m, height ≥
2.3 m. The cabinet may topple over in a
short time.
2500 mm high: width ≥ 1.2 m, height ≥
2.8 m. The cabinet may topple over in a
short time.
Floor
Floor bearing capacity ≥ 530 kg/m2
Floor height ≥ 300 mm
Pipe routing
Bottom pipe routing
Cabling mode
Top cabling
Drainage requirements
Automatic drainage
Water supply requirements of wet film
The inlet water pressure should be in the
range of 0.1–0.7 MPa (A reducing valve
must be installed if the inlet water pressure
exceeds 0.7 MPa.), and the temperature
should be in the range of 1°C–40°C.
The wet film humidifier should use tap
water (no water treatment facility needed
for the inlet water) that meets the following
requirements:
Non-freezing and nephelometric
turbidity units (NTU): < 3
No visible substances
6.5 ≤ pH value ≤ 8.5
Total hardness (in CaCO3): ≤ 450 mg/L
Power distribution
Leakage circuit breakers are not used for the
main power route. If leakage circuit
breakers are required by the customer or by
local regulations, use the residual current
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
2 Product Description
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
22
Item
Description
circuit breakers (RCCBs) that are not
sensitive to the single-phase DC pulses and
transient current pulses.
Operating Specifications
Table 2-5 Operating specifications
Item
Specifications
Operating ambient temperature
4–55°C
Operating humidity
5%–95% RH
Inlet water temperature of chilled water or
glycol solution
7–20°C (water, glycol solution)
Requirements for humidifying water supply
The inlet water pressure should be in the
range of 0.1–0.7 MPa (A reducing valve
must be installed if the inlet water pressure
exceeds 0.7 MPa.), and the temperature
should be in the range of 1°C–40°C. The
wet film humidifier should use tap water (no
water treatment facility needed for the inlet
water)
Storage temperature
–40°C to +70°C
Storage humidity
5%–95% RH (non-condensing)
Altitude
0–1000 m: normal use; 1000–4000 m:
derated
Temperature adjustment range
Return air: 18–45°C
Supply air: 15–35°C
Temperature adjustment precision
±1°C
Humidity adjustment range
20%–80% RH
Humidity adjustment precision
±5% RH
Air outlet static pressure
0–50 Pa
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
2 Product Description
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
23
2.4 Technical Specifications
Table 2-6 Technical specifications of NetCol5000-C065
Item
NetCol5000-C065H9B202
0030D0
NetCol5000-C065H9B202
W030D0
Power system
220–240 V AC, 1 PH, 50/60 Hz
Number of fans
10
Cooling capacity (kW)
65
Air volume (m3/h)
10000
Water flow (m3/h)
12
Water pressure drop (kPa)
100
Humidification
No
Yes
Humidification capacity
(kg/h)
0
3
Maximum operating current
(A)
15
Recommended upstream
circuit breaker (A)
32
External dimensions (H x W
x D, mm)
2000 x 600 x 1200
Air filter level
G4
Net weight/Gross weight
(kg)
200/234
202/236
Note: Rated working conditions are that the return air temperature is 37°C; the return air
relative humidity is 24%; the supply/return water temperatures are 10°C/15°C respectively;
and the static pressure outside the smart cooling product is 0 Pa.
Table 2-7 Technical specifications of NetCol5000-C080
Item
NetCol5000-C080H9B20200
30D0
NetCol5000-C080H9B2
02W030D0
Power system
220–240 V AC, 1 PH, 50/60 Hz
Number of fans
12
Cooling capacity (kW)
80
Air volume (m3/h)
12000
Water flow (m3/h)
14
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
2 Product Description
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
24
Item
NetCol5000-C080H9B20200
30D0
NetCol5000-C080H9B2
02W030D0
Water pressure drop (kPa)
100
Humidification
No
Yes
Humidification capacity
(kg/h)
0
3
Maximum operating current
(A)
17
Recommended upstream
circuit breaker (A)
32
External dimensions (H x W
x D, mm)
2500 x 600 x 1200
Air filter level
G4
Net weight/Gross weight
(kg)
238/268
240/270
Note: Rated working conditions are that the return air temperature is 37°C; the return air
relative humidity is 24%; the supply/return water temperatures are 10°C/15°C respectively;
and the static pressure outside the smart cooling product is 0 Pa.
2.5 Performance Curves
Figure 2-10 and Figure 2-11 show the cooling capacity derating coefficient curve in
proportion to the altitude when the NetCol5000-C works under rated power and air flow.
Cooling Capacity Derating Coefficient Curve in Proportion to the Altitude
Figure 2-10 Cooling capacity derating coefficient curve in proportion to the altitude
When the altitude is within 1000 m, the cooling capacity deviation is in the tolerance range and can be
ignored.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
2 Product Description
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
25
Cooling Capacity Curve in Proportion to the Glycol Solution Density
The cooling capacity is obtained by multiplying the glycol solution density by the rated
cooling capacity.
Figure 2-11 Cooling capacity curve in proportion to the glycol solution density
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
26
3 Installation
3.1 Installation Precautions
To ensure the optimal operating condition and longest service life, install the NetCol5000-C
correctly as required.
Check whether the environment meets the requirements before installation, and whether
reconstruction is needed for routing pipes and cables.
Install the NetCol5000-C according to the design drawing and reserve space for
maintenance.
Reserve more than 1200 mm maintenance space at the front or rear of the smart cooling
product and more than 1000 mm maintenance space at the other end. Figure 3-1 uses
more than 1200 mm maintenance space at the front door and more than 1000 mm
maintenance space at the rear door as an example.
Install the water inlet and outlet pipes to the predefined paths and reserve proper length
for connecting water inlet and outlet pipes.
Figure 3-1 Maintenance space
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
27
3.1.1 Tools
Table 3-1, Table 3-2, and Table 3-3 list the main tools for installing the NetCol5000-C.
Prepare tools based on site requirements.
Table 3-1 General tools
Appearance, Parameter, and Name
Flat-head
screwdriver
Phillips screwdriver
Adjustable wrench
36 mm (2 PCS)
Socket wrench
M10/M12
Hex key (5 mm)
Open end torque
wrench
Diagonal pliers
Wire stripper
Crimping tool
Torch
Electrician's knife
Step ladder (2 m)
ESD gloves
PVC insulation tape
Vacuum cleaner
Steel wire brush
Multimeter
Claw hammer
Level
Hot melt device
(used when water
pipes are made of
PPR or
aluminum-plastic
material)
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
28
Appearance, Parameter, and Name
Heat gun
N/A
N/A
N/A
N/A
N/A
N/A
Table 3-2 Transportation tools
Appearance, Parameter, and Name
Diesel pallet truck
Manual pallet truck
N/A
N/A
N/A
N/A
Table 3-3 Nitrogen injection and pressure preservation tools
Appearance, Parameter, and Name
Nitrogen cylinder
Pressure gauge
Fluorine injection
hose
Reducing valve
3.1.2 Pipe Connection
NetCol5000-C pipes are routed from the bottom onsite, as shown in Figure 3-2.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
29
It is recommended that you close the inlet valve in the unit when there is chilled water
circulation in the system and the unit is not in use.
Figure 3-2 Connection diagram for bottom pipe routing
(1) Copper gate valve
(2) Y-shaped strainer
3.1.3 Material Preparations
Materials are classified to Huawei-provided, self-purchased, and onsite prepared materials,
which are marked as mandatory, optional, and engineering purchasing in this document.
Mandatory: materials that are provided by Huawei and can be found in the delivered
fittings.
Optional: materials that can be purchased from Huawei or any other vendor (if you have
ordered the materials from Huawei, you do not need to purchase them elsewhere). For
details about the specifications of such materials to be purchased, see the following
sections.
Engineering procurement: materials that are not configured by Huawei and need to be
purchased from another vendor.
3.1.3.1 Automatic Drainpipe
The drainpipe supports the rigid pipe connection.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
30
Figure 3-3 Connecting an automatic drainpipe
(1) Connector with inner screw
threads: BSPP 1/2 inch;
delivered with smart cooling
products
(2) Conversion adapter: BSPT
1/2 inch; connected to a rigid
pipe with external threads
(3) Rigid pipe: made
of PP-R, C-PVC, or
other materials
The object shown in the dotted line box is the drainpipe connector with inner screw threads delivered
with smart cooling products. Other parts are not provided and need to be purchased.
3.1.3.2 (Optional) Condensate Pump Drainpipe
If condensate water needs to be drained by using a water pump, you can customize a
condensate pump.
The water pump drainpipe uses the hose connection, as shown in the following figure.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
31
Figure 3-4 Connecting a water pump drainpipe
(1) Water pump port with an
outer diameter of 9.8 mm
(2) Hose
clamp
(3) Hose (inner diameter of 9 mm; made
of EPDM or other materials)
The object shown in the dotted line box is the water pump port supplied with the smart cooling product.
Other parts are not provided and need to be purchased.
3.1.3.3 (Optional) Humidifier Water Inlet Pipe
The humidifier water inlet pipe can be connected using a hose or a rigid pipe. Figure 3-5
shows how to connect the pipe.
Figure 3-5 Connecting a water inlet pipe
(1) Connector with inner screw
threads: G 1/2 inch, delivered with
the water inlet pipe for the smart
cooling product
(2) Rigid pipe conversion
adapter: G 1/2 inch; connected
to a rigid pipe with outer screw
threads
(3) Rigid pipe:
made of PP-R or
other materials
(4) Pagoda connector: G 1/2 inch;
connected to a pagoda connector
with outer screw threads
(5) Hose clamp
(6) Hose: made of
EPDM or other
materials
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
32
The object shown in the dotted line box is the water inlet pipe connector with inner screw threads
delivered with smart cooling products. Other parts are not provided and need to be purchased.
3.1.3.4 Chilled Water Inlet and Outlet Pipes
The following illustrates how to connect water inlet and outlet pipes to reserved ports on the
cabinet.
Figure 3-6 Connecting the water inlet and outlet pipes
(1) G 1–1/2 in. port with inner
threads (reserved device port)
(2) Seamless steel pipe with a G 1–1/2 in. external
threaded connector (engineering purchase)
(3) Direct connection of external
teeth (engineering purchase)
(4) Sealing ring
(5) Nut
(6) Aluminum plastic pipe with an inner diameter of
41 mm (engineering purchase)
3.1.3.5 Pipe Support
Supports for pipes and water pipes as shown in the figure. The actual appearance of the
supports will be different based on onsite situations.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
33
Figure 3-7 Pipe supports (unit: mm)
The height of the U-shaped pipe clamp is 5 mm less than the pipe diameter (including the thermal
insulation foam).
Install a support every 2500 mm for the straight sections of pipes, and 1000 mm away from each
bending point in turning sections.
3.1.3.6 Cables
The cable flame spread rating must be at least VB.
The following lists the cables and devices to be connected. When connecting cables, fit them
with protective hoses.
Table 3-4 Cables and switches required
Name
Specifications
Quantity
Remarks
Power cable
Electronic|Electric Cable,
600 V/1000 V, ZA-RVV,
3 x 6 mm2, Black (3
Cores: Brown, Blue,
Yellow/Green), 46 A,
Outdoor Cable, CE
2 PCS
Optional; same cable
parameters for the active
and standby routes
Teamwork
networking and
monitoring cable
Signal cable, Shielded
straight-through cable, 10
m, MP8-II, CC4P0.5GY
(S), MP8-II, FTP
1 PCS
Optional
Fuse
Slow Blow Fuse, 250 V,
4 A, IEC Specification,
0.03 ohm, 38.7 A x A x
Sec, UL/CSA Approved
2 PCS
Standard configuration;
delivered with the
product
OT terminal
Naked Crimping
Terminal, OT, 6 mm2,
6 PCS
Standard configuration;
delivered with the
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
34
Name
Specifications
Quantity
Remarks
M6, Tin Plating,
Insulated Ring Terminal,
12-10 AWG, yellow
product
Cord end terminal
Common Terminal,
Conductor Cross Section
6 mm2, Length 20 mm,
Insertion Depth 12 mm,
Black
12 PCS
Standard configuration;
delivered with the
product
Cable tie
G200IUV (3.6 x 200),
Anti-Ultraviolet and
Anti-Freeze, Black
15 PCS
Standard configuration;
delivered with the
product
3.1.4 Structural Specifications
3.1.4.1 NetCol5000-C065 external structure
Figure 3-8 NetCol5000-C065 external structure
(1) Controller panel
(2) Door lock
(3) Front door
(4) Side panel
(5) Rear door
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
35
3.1.4.2 NetCol5000-C080 external structure
Figure 3-9 NetCol5000-C080 external structure
(1) Controller panel
(2) Door lock
(3) Front door
(4) Side panel
(5) Rear door
3.1.4.3 Cabinet Holes
Figure 3-10 Top view (unit: mm)
(1) Power cable hole
(2) Signal cable hole
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
36
Figure 3-11 Bottom view (unit: mm)
(1) Humidifier water inlet pipe hole
(2) Automatic drainpipe hole
(3) Equipotential PE cable hole
(4) Forcible drainpipe hole (Optional)
(5) Chilled water outlet pipe hole
(6) Chilled water inlet pipe hole
3.2 Unpacking
Prerequisites
To avoid damage during transportation, move the smart cooling product closest to the
installation position before unpacking.
Procedure
Step 1 Inspect the outer packaging for signs of damage. If any damage is found, contact the shipping
company immediately.
Step 2 Remove the packaging.
1.
Cut off the straps and remove the cartons.
2.
Inspect the cabinet exterior for signs of collision or scratches. If any damage is found,
contact the shipping company immediately.
Step 3 Check the type and quantity of fittings against the packing list. If fittings are missing or
inconsistent with those in the packing list, contact your local Huawei office immediately.
----End
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
37
3.3 Installation Process
Remove the protective plastic bag from the cabinet only immediately before installation. Do
not remove the bag during equipment room renovation or infrastructure construction;
otherwise, dust may enter the cabinet and affect the internal components.
Figure 3-12 Installation flowchart
3.4 Checking the nitrogen pressure
Context
The device has been injected with 0.3–0.5 MPa nitrogen before delivery. Check the
nitrogen pressure for nitrogen leakage.
You can open or close the exhaust valve using a flat-head screwdriver.
Procedure
Step 1 Open the door lock using a key, and open the cabinet rear door.
Step 2 Unfasten the rotating baffle plates, and remove the air filters.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
38
Figure 3-13 Removing an air filter
Step 3 Take out the desiccant bag.
Step 4 Press and hold the manual adjustment switch and manually turn the chilled water valve to the
100% state, as shown in Figure 3-14.
Figure 3-14 Adjusting the chilled water valve
Step 5 Use a screwdriver to open the exhaust valve shown in Figure 3-15 and discharge gas through
the hose.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
39
If gas emits, the system is normal. Slowly open the exhaust valve to discharge nitrogen
and close the valve when there is no airflow through the valve.
If no gas emits out of the valve, contact Huawei technical support.
Figure 3-15 Checking the nitrogen pressure
----End
Follow-up Procedure
Check that thermal insulation foam is in close contact with the pipes, there is no crack in each
cutting position, and the chilled water valve is tightly wrapped by thermal insulation foam.
3.5 Removing the Pallet
Procedure
Step 1 Remove the connecting kit that secures the cabinet to the pallet from the bottom of the two
side panels of the cabinet, as shown in Figure 3-16.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
40
Figure 3-16 Removing the connecting kit that secures the cabinet to the pallet
1.
Use a 10# socket wrench to remove eight M6x16 bolts that secure the connecting kit to
the cabinet.
2.
Use an 18# socket wrench to remove four M12x35 bolts that secure the connecting kit to
the pallet.
3.
Remove the connecting kit.
Save the removed bolts for future use.
Step 2 Transport the cabinet to the specified position. You are advised to use a pallet truck to
transport devices.
Exercise caution when moving the cabinet to prevent falling down.
----End
3.6 Leveling and Combining Cabinets
Procedure
Step 1 Level the cabinet. Use a socket wrench to adjust the leveling feet at the bottom of the smart
cooling product, and use a measuring tape and a level to adjust the horizontal and vertical
distances of the smart cooling product. Ensure that the leveling feet touch the floor after
adjustment, as shown in Figure 3-17.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
41
Figure 3-17 Leveling a cabinet
Wrench an anchor bolt clockwise to elevate a cabinet, wrench an anchor bolt anticlockwise
to lower a cabinet. The leveling feet can be adjusted within a range of 0–8 mm.
To prevent damaged caused by cabinet tilt, adjust all the leveling feet at the four corners
instead of one foot.
Use a measuring tape to check that the vertical distance between the top of the cabinet and
the floor is 2000 mm±2 mm or 2500 mm±2 mm.
Do not remove the leveling feet. Otherwise, you need to rework them for use.
Step 2 Combine cabinets, as shown in the following figure.
Figure 3-18 Combining cabinets (front door)
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
42
Figure 3-19 Combining cabinets (rear door)
1.
Remove the connecting kits from the cabinets.
2.
Secure the connecting kits at the connection positions on the front door using screws.
Step 3 Secure the connecting kits at the connection positions on the rear door using screws in the
same way.
Ensure that the vertical distance between each device top and the floor is 2000 mm (±2 mm) or 2500
mm (±2 mm) and that all device tops are on the same plane.
----End
3.7 Securing the NetCol5000-C
Secure the smart cooling product to the base. If there are no bases onsite, prepare one by
referring to C Base Dimensions.
3.8 Connecting Water Pipes
3.8.1 Connect Automatic Drainpipe
Context
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
43
The external drainpipe must have a certain gradient (> 1:50), and no accumulated water is
allowed.
The entire drainpipe should be closely wrapped with thermal insulation foam.
The drainpipe can be secured along the door post using cable ties inside a cabinet.
The water pump drainpipe and the automatic drainpipe should not be connected together
to the external drainage system.
Procedure
Step 1 Remove the drainpipe plug.
Figure 3-20 Connecting an automatic drainpipe
Step 2 Install a pipe adapter and seal it with sealant.
Step 3 Connect the PPR water pipe using a heat gun and wrap the pipe with thermal insulation foam.
Step 4 Connect the drainpipe to the external drainage system.
----End
Follow-up Procedure
After installing the condensate pump drainpipe and automatic drainpipe, connect them to the
main pipe and bind them with a cable tie according to step 1 in Figure 3-21. Then wrap the
pipes with tape or use other materials to secure them, as shown by step 2 in Figure 3-21.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
44
Figure 3-21 Fastening pipes
3.8.2 (Optional) Connecting the Water Pump Drainpipe
Context
Do not bend pipes by a large angle when securing pipes. The water pump drainpipe needs
to be wrapped with thermal insulation foam and the water pump inlet pipe does not need
thermal insulation foam.
In the cabinet, fasten the pipe to vertical pillar of rear door with cable ties.
Procedure
Step 1 Use a Phillips screwdriver to loosen the screw on the connector of the water pump drainpipe
to loosen the hose clamp, and remove the plug of the drainpipe.
Step 2 Connect the hose, and use a Phillips screwdriver to re-tighten the screw on the water pump
drainpipe to secure the hose clamp.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
45
Figure 3-22 Water pump drainpipe
Step 3 Connect the water pump drainpipe to the external drainage system.
Step 4 Wrap the water pump drainpipe with thermal insulation foam.
----End
3.8.3 (Optional) Connecting the Humidifier Water Inlet Pipe
Context
A reducing valve must be installed if the inlet water pressure exceeds 0.7 MPa.
Appliance is intended to be permanently connected to the water mains and not connected
by a hose-set.
Procedure
Step 1 Straighten the water inlet pipe delivered with the smart cooling product, and route it from the
inside to the outside through the water inlet hole at the bottom of the smart cooling product.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
46
Figure 3-23 Downward routing of the water inlet pipe
The other end is a reserved G 1/2 inch connector with inner screw threads. Connect the other end to a
hose or rigid pipe based on site requirements.
Step 2 Clean the engineering pipes before connecting the water inlet pipe to the engineer pipe to
avoid impurities entering into the humidifier.
Step 3 Connect the water inlet pipe to the engineer pipe and wrap the pipe with thermal insulation
foam.
----End
3.8.4 Connecting the Chilled Water Inlet and Outlet Pipes
Context
A Y-shaped strainer has been installed on the chilled water inlet.
Connect the water inlet and outlet pipes from the inside to the outside and from the
bottom to the top.
Water inlet and outlet pipes are connected using thread connectors.
Chilled water inlet and outlet pipes can be connected in two ways. Select one based on
site requirements.
3.8.4.1 Connecting Seamless Steel Pipes
Procedure
Step 1 Open the rear door and remove the air filter.
Step 2 Knock off the knock-out holes for the chilled water inlet and outlet pipes.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
47
Ensure that pipes and power cables are routed through separate holes.
Do not prepare extra knock-out holes to avoid performance loss.
Step 3 Remove the water pipe plug using an open-end wrench.
Step 4 Apply screw thread sealant evenly on the connecting position of external screw threads at
pipe ends, and install the pipes from inside out.
Step 5 Use a common wrench (open end: 53 mm) and trimo wrench (18#) to connect and secure
water inlet and outlet pipes.
Step 6 Attach thermal insulation foam to the pipes and ensure that the foam is in close contact with
the pipes.
Step 7 After pipes are connected, seal the gaps between the knock-out holes and the pipes using
sealant or foaming agent.
Figure 3-24 Connecting the water inlet and outlet pipes
----End
3.8.4.2 Connecting Aluminum Plastic Pipes
Procedure
Step 1 Open the rear door and remove the air filter.
Step 2 Knock off the knock-out holes for the chilled water inlet and outlet pipes.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
48
Ensure that pipes and power cables are routed through separate holes.
Do not prepare extra knock-out holes to avoid performance loss.
In connecting the pipes, ensure that the aluminum plastic pipes are in proper contact with
the straight male connectors.
In connecting the pipes, avoid violent shake.
Step 3 Remove the water pipe plug using an open-end wrench.
Step 4 Apply screw thread sealant evenly on the connecting position of external screw threads of the
straight male connector shown in Figure 3-6, and use a torque wrench (recommended torque:
130±10 N·m) and a common wrench (open end: 53 mm) in collaboration to secure the straight
male connector to the connector on the device.
Step 5 Install the sealing ring and nut shown in Figure 3-6 at the end of the aluminum plastic pipe
that ran through the hole rubber ring.
Step 6 After the aluminum plastic pipe and the straight male connector are connected, secure them to
the aluminum plastic pipe with the installed sealing ring and nut, as shown in the following
figure.
Step 7 Attach thermal insulation foam to the pipes and ensure that the foam is in close contact with
the pipes.
Step 8 After pipes are connected, seal the gaps between the knock-out holes and the pipes using
sealant or foaming agent.
Figure 3-25 Connecting the water inlet and outlet pipes
----End
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
49
3.9 (Optional) Performing a Leakage Test with Nitrogen
Prerequisites
You can decide whether a leakage test with nitrogen needs to be performed or not based on
the site situation.
Pipes have been properly connected.
Procedure
Step 1 Manually turn the chilled water valve to the maximum (100%), as shown in Figure 3-14.
Step 2 Connect a reducing valve, pressure gauge, and nitrogen cylinder to any needle valve of the
smart cooling product, as shown in Figure 3-26. Inject 0.8 MPa nitrogen (the pressure should
reach 0.8 MPa after it is stabilized), and keep it for 24 hours.
Figure 3-26 Injecting nitrogen
Step 3 After 24 hours, if the pressure drop is less than 0.01 MPa, the pipes do not leak. Open the
exhaust valve using a screwdriver, and close the valve when there is no airflow through the
valve. Then you can perform the following operations.
Step 4 After the leakage test has been performed and gas has drained, re-wrap the needle valve with
thermal insulation foam.
----End
Exception Handling
If the pressure decreases, find out and repair the leakage point by using soap bubbles.
If the pressure is preserved properly, exhaust nitrogen and wrap pipes and joints with
thermal insulation foams.
----End
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
50
3.10 Injecting Water to Expel Gas
Prerequisites
Nitrogen must be expelled before injecting water.
To avoid blockage of the heat exchanger in the smart cooling product due to foreign
matter from the main pipe during the construction, you are advised to clean the main
pipe before water is supplied to the smart cooling product. Turn off the isolation valves
on the water inlet and outlet pipes before the cleaning and turn them on afterwards.
Procedure
Step 1 Ensure that the needle valve and exhaust valve on the pipe are closed and the chilled water
valve is in the 100% state, as shown in Figure 3-27.
Figure 3-27 Adjusting the chilled water valve
Step 2 Open the main water inlet valve.
Step 3 Gradually open the exhaust valve, as shown in Figure 3-15. Air and chilled water flow out of
the exhaust hose together.
Step 4 Adjust the air exhausting speed until no bubble flows out of the hose.
Step 5 After air is expelled, manually turn the chilled water valve to the 0 state.
Step 6 Close the exhaust valve.
----End
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
51
3.11 (Optional) Leakage Test with Water
If the leakage test has been done with nitrogen, skip the test with water.
Ensure that the indoor temperature is always above 0°C during the leakage test with water,
otherwise, the pipes may experience frost cracks. If the indoor temperature is below 0°C,
take anti-freezing measures for the pipes.
Manually open the chilled water valve. Inject water to 0.8 MPa, and preserve the pressure for
24 hours. Then connect a pressure gauge to a needle valve on the pipeline to measure the
pressure. If the reading remains unchanged, the pipe is not leaking. You can perform the
following operations.
3.12 Cable Connections
3.12.1 Overview and Precautions
Precautions
Connections of all power cables, control cables, and ground cables must comply with the
local electrical code, and the cable specifications should comply with the local cabling
specifications.
For details about the maximum current, see the equipment nameplate.
Ensure that the voltage and frequency of the primary power supply meet the
requirements.
Only trained and qualified personnel are allowed to connect cables.
Before connecting cables, use a multimeter to measure the input voltage and ensure that
the power supply is off.
Ensure that all smart cooling products are safely grounded before powering them on.
Keep cables away from the fan, and so on (if unavoidable, take protective measures), and
ensure that cables are securely connected.
When laying out cables, ensure that the power and signal cables are reliably separated
and that the strong- and weak-current cables are bound separately.
3.12.2 Connecting Power Cables
Prerequisites
Check that the voltage is less than 1 V between wires by using a multimeter before connecting
power cables.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
52
Procedure
Step 1 Take out OT terminals and cord end terminals from the fittings bag, and prepare cables.
Crimp the cables firmly and ensure that they are not loose after pulling.
If the cables are not recommended specifications, you need to prepare the terminals by
yourself.
Step 2 Connect power cables, as shown in the following figure.
Exercise caution while connecting cables. Prepare protective tools in advance.
Figure 3-28 Connecting power cables
1.
Connect the cables with crimped terminals to the L, N, and PE shown in Figure 3-28.
2.
Remove screws from both ends of the clip to remove it.
3.
Place the connected power cables vertically, use the clip to secure them in a proper
position, and use screws to secure the clip.
4.
Fasten the power cable to the vertical pillar by cable ties every 150 mm to 200 mm.
Step 3 Use a multimeter to check for a short circuit between L and N of AC1 and AC2. Use a
multimeter to check for a short circuit between L, N, and PE.
If there is a short circuit, remove the cable and reconnect it using the method described
in Step 2.1. After verifying the connection, perform Step 4.
If there is no short circuit, perform Step 4.
Step 4 Check that the cable connections are secure.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
53
If the cable connections are loose, fasten the connections.
If the cable connections are secure, the connection is complete.
----End
3.12.3 Connecting an Equipotential PE Cable
Smart cooling product resistance to ground ≤ 0.1 ohm.
Connect the PE cable to the marked position in the lower part of the cabinet, and connect the
cable to the external ground system, as shown in Figure 3-29.
Figure 3-29 Connecting an equipotential PE cable
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
54
3.12.4 Teamwork Networking and Monitoring
3.12.4.1 Main Control Panel
Figure 3-30 Main control panel
(1) T/H_1 (T/H RS485 communications
port) (used for connecting to the external
temperature and humidity sensor)
(2) T/H_2 (T/H RS485 communications
port) (used for connecting to the external
temperature and humidity sensor)
(3) CAN_IN (CAN communications port)
(used for teamwork networking)
(4) CAN_OUT (CAN communications port)
(used for teamwork networking)
(5) COM_IN (RS485 communications port)
(used for connecting to the monitoring
system)
(6) COM_OUT (RS485 communications
port) (used for connecting to the monitoring
system)
(7) FE (used for connecting to the
monitoring system)
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
55
3.12.4.2 Signal Ports
Figure 3-31 Signal ports
(1) Common alarm 2 (ALM_2 COM)
(2) Common alarm 2 (ALM_2 NO)
(3) Common alarm 1 (ALM_1 COM)
(4) Common alarm 1 (ALM_1 NO)
(5) External water sensor (Water -)
(6) External water sensor (Water +)
(7) Remote on/off (Remote COM)
(8) Remote on/off (Remote +)
(9) Smoke sensor (Smoke AI)
(10) Smoke sensor (Smoke 12VDC)
3.12.4.3 Connecting the Teamwork Network Cable
Smart cooling products in a teamwork group must be of the same model.
The default networking mode is CAN networking.
The smart cooling product supports two teamwork networking modes: FE teamwork
networking and CAN teamwork networking (hand-in-hand).
3.12.4.3.1 Connecting the FE Teamwork Network Cable
Procedure
Step 1 (Optional) Make FE teamwork network cables by referring to Figure 3-32 if required onsite.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
56
Figure 3-32 Pin sequence of FE network cable
Step 2 Connect one end of the FE network cable to the FE port on the main control module, as
shown by 7 in Figure 3-30, and connect the other end to the POE port on the smart ETH
gateway, as shown in Figure 3-33.
Figure 3-33 Connecting the FE teamwork network cable
----End
3.12.4.3.2 Connecting the CAN Teamwork Cable
Context
In CAN networking, one teamwork network supports a maximum of 32 smart cooling
products. If CAN networking is required onsite, set Teamwork CAN resistor enable on the
Teamwork settings page for the first and last smart cooling products to Yes.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
57
Procedure
Step 1 Use a CAN teamwork cable to connect the CAN_OUT port on a smart cooling product to the
CAN_IN port on the following smart cooling product, as shown in Figure 3-35.
Figure 3-34 Pin sequence of a CAN teamwork cable
Figure 3-35 Connecting a CAN teamwork cable
----End
3.12.4.4 Connecting the Monitoring Network Cable
The smart cooling product supports both RS485 and FE monitoring.
3.12.4.4.1 Connecting the FE Monitoring Network Cable (SNMP/Modbus-TCP)
The FE monitoring and FE teamwork control use the same network cable. For the connection
method, refer to 3.12.4.3.1 Connecting the FE Teamwork Network Cable.
3.12.4.4.2 Connecting the RS485 Monitoring Network Cable (Modbus-RTU)
When monitoring smart cooling products over northbound RS485, the EMS needs 4 seconds
to collect data from one smart cooling product. Therefore, the time required for collecting
data from N smart cooling products in a group is 4 x N. If the data collection time is longer
than the performance requirement, you can divide the smart cooling products into several
groups. For example, if the EMS needs to finish data collection in 16 seconds, you are advised
to group smart cooling products by four and connect the COM–IN port of the main control
module of the first smart cooling product in each group to the RS485 port of the EMS.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
58
(Optional) Make the RS485 monitoring network cable by referring to Figure 3-36 if required
onsite.
Figure 3-36 Pin sequence of an RS485 monitoring network cable
The figure shows the connection diagram of monitoring network cables when 32 smart
cooling products are teamworked with four in each group connected to the host
respectively. The number of smart cooling products in each monitoring group can be
adjusted based on performance requirements.
In CAN networking, a maximum of 32 smart cooling products can be teamworked. If
CAN networking is required onsite, set Teamwork CAN resistor enable for the first and
last smart cooling products to Yes over the LCD.
If CAN teamwork networking has been implemented, connect the RS485 monitoring cables,
as shown in the following figure.
Figure 3-37 Connecting the RS485 monitoring network cable
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
59
3.12.5 Connecting the Water Sensor
Context
A water sensor monitors resistance changes at terminals to determine whether the floor is
watery. When the terminals of a water sensor detect water or other conductive liquid,
resistance between the two terminals decreases. Keep water sensors far away from water traps
or floor drains.
Procedure
Step 1 Connect one end of the water sensor cable to the water sensor.
Step 2 Connect the other end of the water sensor cable to Water– and Water+ on the water sensor at
the signal port through the signal cable hole at the top of the cabinet.
Step 3 Secure the cable to the left post of the cabinet using cable ties.
Place the sheet metal of the water sensor upwards and its detection board downwards on the
ground.
----End
3.12.6 Connecting the T/H Sensor Outside the Cabinet
Context
T/H sensors outside the cabinet are configured to detect the temperatures of cold/hot aisles.
They can be flexibly installed on the server cabinet based on onsite situation. It is
recommended that the T/H sensors be deployed near heat sources in the hot aisle, or in places
which lacks cooling air in the cold aisle. The T/H sensors outside the cabinet must be near the
smart cooling product to sense the temperature of the outlet air, and must be away from the air
exhaust vents of other smart cooling products
Procedure
Step 1 Connect the T/H sensors outside the cabinet and the T/H sensors at the return air side in series.
Figure 3-38 shows how to route the cables.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
60
Figure 3-38 Cables routed outside the cabinet
The T/H sensors inside the cabinet are secured at the return air side and their IN ports are connected
to the main control board. When connecting the T/H sensors outside the cabinet, connect the OUT
port of one T/H sensor inside the cabinet to the IN port of the next T/H sensor outside the cabinet.
Connect all T/H sensors in series in this way.
The T/H sensors should be 1.5 m above the ground (33 U).
Each smart cooling product supports a maximum of ten T/H sensors.
Step 2 Table 3-5 shows how to set the DIP switches for T/H sensors.
Figure 3-39 DIP switches
Table 3-5 DIP switch setting on a T/H sensor
Position
Name
Address DIP Switch ID
1
2
3
4
5
6
Return air
Return air 2
temp/humid
1
ON
OFF
OFF
OFF
OFF
OFF
Cold aisle
Cold aisle 1
11
ON
ON
OFF
ON
OFF
OFF
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
61
Position
Name
Address DIP Switch ID
1
2
3
4
5
6
temp/humid
Cold aisle 2
temp/humid
12
OFF
OFF
ON
ON
OFF
OFF
Cold aisle 3
temp/humid
13
ON
OFF
ON
ON
OFF
OFF
Cold aisle 4
temp/humid
14
OFF
ON
ON
ON
OFF
OFF
Cold aisle 5
temp/humid
15
ON
ON
ON
ON
OFF
OFF
Hot aisle
Hot aisle 1
temp/humid
21
ON
OFF
ON
OFF
ON
OFF
Hot aisle 2
temp/humid
22
OFF
ON
ON
OFF
ON
OFF
Hot aisle 3
temp/humid
23
ON
ON
ON
OFF
ON
OFF
Hot aisle 4
temp/humid
24
OFF
OFF
OFF
ON
ON
OFF
Hot aisle 5
temp/humid
25
ON
OFF
OFF
ON
ON
OFF
The default addresses of T/H sensors purchased from Huawei are 1.
Keep the last RS485_R toggle switch at OFF.
After the addresses are set, power on the device. On the display's home screen, choose
Settings > System Settings > T/H Sensor and set the sensors in the aisles corresponding
to the addresses to Enable. Otherwise, the sensors will not work.
----End
3.12.7 (Optional) Installing a Differential Pressure Sensor
Procedure
Step 1 Secure the differential pressure sensor and the fasteners using M5 tapping screws, as shown in
step 1 in Figure 3-40.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
62
Figure 3-40 Securing a differential pressure sensor
Step 2 Connect the pressure inlet tube.
Cold aisle containment: Connect a pressure inlet tube to the + mark and route it to the
aisle through the hole on the top of the cabinet. Ensure that the pressure inlet faces
downwards. Connect another pressure inlet tube to the – mark and route it to the cabinet
top through the hole atop.
Hot aisle containment: Connect a pressure inlet tube to the + mark and route it to the
cabinet top through the hole atop. Connect another pressure inlet tube to the – mark and
route it to the aisle through the hole on the top of the cabinet. Ensure that the pressure
inlet faces downwards.
Step 3 Connect the cable terminal of thedifferential pressure sensor to the DPT terminal.
----End
3.13 Checking After Installation
1.
Check the drainpipes are securely installed, clear, free of leakage, and not over bent.
2.
Check that the chilled water connector joints have been tightly wrapped with thermal
insulation foam, and no metal or hose is exposed.
3.
Check that the liquid level detector is horizontal, that the water pan is free of foreign
matter, such as residual cables and thermal insulation foam, and that the cables are
secured bound and not in the water pan.
4.
Check that the distance between two chilled water pipes outside the cabinet is sufficient
(recommended distance: longer than 25 mm), the hose is tightly wrapped with insulation
foam, and that junctions are secured using glue.
5.
Check that the pipe lines have completed pressure preservation and air tightness test.
6.
Check that the needle valve plugs and the nuts are tightened.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
63
7.
Check that the cabinet is grounded.
8.
Check that the power and signal cables are routed correctly and separately.
9.
Check that strong- and weak-current cables are bound separately.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
64
4 Commissioning
4.1 Power-On
Procedure
Step 1 Turn on the smart cooling product switch in the power distribution cabinet and the AC1 and
AC2 switches on the smart cooling product.
Step 2 After the system is powered on for the first time, the Quick Settings screen is displayed. Log
in as the admin user, as shown in Figure 4-1.
Figure 4-1 Initial power-on
Table 4-1 Preset password
User
Preset Password
Permission Description
admin (administrator
user)
000001
People can operate all menus.
operator (common
user)
000001
People can only view parameter settings
and set a part of parameters in the
menus.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
65
The operator user can access customer and delivery parameters. Parameters in the
advanced menu are the delivery parameters. The admin user can access customer, delivery,
maintenance, and R&D parameters. Parameters in the advanced menu are the R&D
parameters.
To prevent the effect of misoperation on the system during the O&M, log in as the
operator user first before modifying parameters. Confirm with Huawei before modifying
parameters that cannot be modified by operator users; otherwise, Huawei will not be liable
for any consequences of the unauthorized modification.
Only certified pros are allowed to modify the advanced parameters. Unauthorized
modifications may lead to device malfunction or damage.
After the first login, change the password in time to ensure account security and prevent
unauthorized network attacks, such as data tampering. Huawei will not be liable for any
security issues caused by your failure to change the preset password in time or password
loss after changing.
After login, you are allowed to perform operations until being logged out if no operation is
performed within 3 minutes (user set). For security purposes, tap
at the
lower-right corner of the screen to manually log out after you have completed all
operations.
Step 3 Figure 4-2 shows how to configure relevant parameters. Click Next until the LCD home
screen is displayed after the configuration.
Figure 4-2 Quick Settings
Table 4-2 Parameter description
Menu
Parameter
Description
Configuration Principle
Select
Language
/
Choose language of
the ACC
Set the parameter according to
the actual situation.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
66
Menu
Parameter
Description
Configuration Principle
Date & Time
Settings
Date format
Specifies the date
display format for
the ACC.
Set the parameter according to
reading habits.
Date settings
Specifies the date
displayed on the
ACC.
Set the parameter according to
the actual situation.
Time
Specifies the time
displayed on the
ACC.
Set the parameter according to
the actual situation.
Time zone
Specifies the time
zone displayed on
the ACC.
Set the parameter according to
the actual situation.
Teamwork
Settings (visible
for V200R002
version)
Teamwork
group No.
Set the assigned
teamwork control
number.
The number of the teamwork
controlled group, which is the
same for all the devices in the
group.
Air
conditioner
address
Set the assigned unit
address.
Air conditioner addresses should
be different from each other.
Teamwork
function
Disable or enable
the teamwork
function. If the
teamwork function
is disabled, this
device is operating
according to its own
control. If the
teamwork function
is enabled, this
device works in
harmony with others
that in the same
group.
Set this parameter based on the
onsite device heat distribution.
Networking
mode
Networking mode
for the teamwork.
The networking
mode set on the
screen must be
consistent with the
actual networking
mode. Otherwise,
the teamwork
control function will
be unavailable.
Networked over CAN or
MAC_CAN. CAN network
indicates teamwork control over
a CAN bus, MAC_CAN
network teamwork control over
an FE port.
Number of
smart cooling
products in
Number of the smart
cooling products in
this group (1 to 32
Total number of the smart
cooling products in this group.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
67
Menu
Parameter
Description
Configuration Principle
this group
can be set).
Number of
running
smart cooling
products in
this group
Number of active
units in a group. The
value ranges from 1
to Number of smart
cooling products in
this group.
The host allocates running units
by smart cooling product unit
address in ascending order,
which is from 1 to 32. The rest
will become the standby ones.
System Settings
(visible for
V200R002
version)
Humidifying
function
The humidifying
function can be set
to Enable, Disable,
or Enabled when
active power.
Enable indicates that the
electric humidifier will be
started when the ambient
humidity is lower than the
certain humidity range of the
humidity set point. Disable
indicates that the electric
humidifier will not be started.
Enabled when active power
indicates that the electric
humidifier will be started when
the main power is active and the
ambient humidity is lower than
the certain humidity range of the
humidity set point.
Dehumidifyi
ng function
The dehumidifying
function can be set
to Enable, Disable,
or Enabled when
active power.
Enable indicates that the
dehumidification function will
be enabled when the ambient
humidity exceeds the certain
humidity range of the humidity
set point. Disable indicates that
the dehumidification function
will not be enabled. Enabled
when active power indicates
that the dehumidification
function will be enabled when
the main power is active and the
ambient humidity exceeds the
certain humidity range of the
humidity set point.
T/H sensor
(visible for
V200R002
version)
Temperature
and humidity
control type
Cold aisle, Hot
aisle, Return air, or
Supply air can be
set as required. The
temperature and
humidity set points
correspond to the
selected control type
can be set.
When the application
scenario is cold or hot aisle
containment, you are advised
to choose Cold aisle if the
cold aisle T/H sensors are
configured, and choose
Supply air if the cold aisle
T/H sensors are not
configured.
When the application
scenario is non-aisle
containment, you are advised
to choose Return air, and
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
68
Menu
Parameter
Description
Configuration Principle
choose Cold aisle if the cold
aisle T/H sensors are
configured.
Hot aisle is not
recommended.
Temperature
control mode
This parameter
controls the
temperature inside
the room or aisles
based on the
Average value,
Max value, or Min
value of the
temperatures
collected by each
sensor.
Average value: Select
Average value if the
temperature is to be
controlled based on the
averaged data value collected
by the collector.
Max value: Select Max
value if the temperature is to
be controlled based on the
maximum data value
collected by the collector.
Min value: Select Min value
if the temperature is to be
controlled based on the
minimum data value
collected by the collector.
Temperature
setpoint
After the
Temperature and
humidity control
type and the
temperature value
under this type are
set, the device
conducts cooling or
heating based on the
settings.
Set this parameter as required.
Return air temperature:
26–35°C recommended
Supply air temperature:
18–24°C recommended
Cold aisle temperature:
18–24°C recommended
Hot aisle temperature:
26–35°C recommended
Humidity
setpoint
After the
Temperature and
humidity control
type and the
humidity value
under this type are
set, the device
conducts
humidifying or
dehumidifying based
on the settings.
Set this parameter as required.
40%–60% RH recommended
Cold aisle
sensor 1
Cold aisle
sensor 2
Cold aisle
sensor 3
The sensors in cold
aisles can be set to
Enable or Disable.
The cold aisle sensors outside
the cabinet need to be enabled
when they are installed.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
69
Menu
Parameter
Description
Configuration Principle
Cold aisle
sensor 4
Cold aisle
sensor 5
Hot aisle
sensor 1
Hot aisle
sensor 2
Hot aisle
sensor 3
Hot aisle
sensor 4
Hot aisle
sensor 5
The sensors in hot
aisles can be set to
Enable or Disable.
The hot aisle sensors outside the
cabinet need to be enabled when
they are installed.
Comm Settings
(visible for
V200R002
version)
Modbus
Comm
address
Set the
communication
address of the smart
cooling product as
planned. The EMS
communicates with
the smart cooling
product through this
address.
The communication addresses
of two smart cooling products
connecting to the same EMS
must be unique.
----End
4.2 Home Screen
You can tap the menu items, buttons, or icons on the screen to enter related screens or perform
operations, such as Running, Alarms and Settings. The controller main screen is shown in
Figure 4-3.
User interfaces displayed in this document are for reference only.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
70
Figure 4-3 Home screen
Table 4-3 Note for the page
No.
Items
Note
1
Permission status
indicates that you have not logged in to the
system.
indicates that you have logged in to
the system as an operator user.
indicates that
you have logged in to the system as an admin user.
2
USB status
in the status bar indicates that the USB flash
drive is successfully connected to the display panel.
3
Diagnostic mode
in the status bar indicates that the smart
cooling product is in diagnostic mode. Tap the icon
to exit from the diagnostic mode.
4
The buzzer status
The buzzer status can be set to On or Off. The
icon indicates that the buzzer is on. When the buzzer
is on, it buzzes when an alarm is generated. When
the buzzer is buzzing, you can tap anywhere on the
screen to mute the buzzer. After the buzzer is muted,
it still buzzes when a new alarm is generated. The
icon indicates that the buzzer is off (silenced).
After the buzzer is silenced, it does not buzz when
an alarm is generated.
5
The current critical alarm
and their quantity
refers to the current critical alarm and their
quantity.
6
The current major alarm
and their quantity
refers to the current major alarm and their
quantity.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
71
No.
Items
Note
7
The current minor alarm
and their quantity (visible
for V200R002 version)
refers to the current major alarm and their
quantity.
8
The current warning alarm
and their quantity
refers to the current warning alarm and
their quantity.
9
The status bar
N/A
10
The alarm bar
You can tap
in the
alarm bar to enter the active alarm screen that
displays all active alarms.
11
Login button / Logout
button
indicates that you have not logged in
to the system, and can tap the icon to log in.
indicates that you have logged in to
the system as admin or operator user, and can tap the
icon to log out.
12
Teamwork control button
indicates that there is no teamwork control at
present.
indicates that there is teamwork
control without alarms at present.
indicates
that there is teamwork control with alarms at present.
4.3 Initial Configuration
4.3.1 Setting Temperature and Humidity Values and (Optional)
Enabling T/H Sensors
Prerequisites
The T/H sensors outside the cabinet need to be enabled when they are installed,
otherwise, skip Step 2.
If you need to enable a humidity and temperature sensor, log in as the admin user.
This section describes how to enable Cold aisle sensor 1.
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H sensor. Figure 4-4 is
displayed.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
72
Figure 4-4 Setting temperature and humidity values
Step 2 Set Cold aisle sensor 1 to Enable.
Step 3 Set the temperature and humidity values by referring to Table 4-4.
You are not recommended to modify the parameters not listed in Table 4-4.
Table 4-4 Parameter description
Parameter
Description
Configuration Principle
Temperature and
humidity control
type
Cold aisle, Hot aisle, Return
air, or Supply air can be set as
required. The temperature and
humidity set points correspond
to the selected control type can
be set.
When the application scenario is
cold or hot aisle containment,
you are advised to choose Cold
aisle if the cold aisle T/H
sensors are configured, and
choose Supply air if the cold
aisle T/H sensors are not
configured.
When the application scenario is
non-aisle containment, you are
advised to choose Return air,
and choose Cold aisle if the
cold aisle T/H sensors are
configured.
Hot aisle is not recommended.
Temperature
control mode
This parameter controls the
temperature inside the room or
aisles based on the Average
value, Max value, or Min value
of the temperatures collected by
each sensor.
Average value: Select Average
value if the temperature is to be
controlled based on the averaged
data value collected by the
collector.
Max value: Select Max value if
the temperature is to be
controlled based on the
maximum data value collected
by the collector.
Min value: Select Min value if
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
73
Parameter
Description
Configuration Principle
the temperature is to be
controlled based on the
minimum data value collected
by the collector.
Control point
temperature
setpoint
After the Temperature and
humidity control type and the
temperature value under this
type are set, the device conducts
cooling or heating based on the
settings.
Set this parameter as required.
Return air temperature: 26–35°C
recommended
Supply air temperature:
18–24°C recommended
Cold aisle temperature: 18–24°C
recommended
Hot aisle temperature: 26–35°C
recommended
Control point
humidity setpoint
After the Temperature and
humidity control type and the
humidity value under this type
are set, the device conducts
humidifying or dehumidifying
based on the settings.
Set this parameter as
required.40%–60% RH
recommended
Step 4 Go back to home screen, and tap Running > Device Details > T/H sensor to check that the
cold aisle temperature and humidity are displayed and the values are reasonable.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
74
Figure 4-5 Cold aisle temperature and humidity
----End
4.3.2 (Optional) Setting the Pressure Difference Control
Prerequisites
If the differential pressure sensor is installed, perform the following operations accordingly. If
the differential pressure sensor is not installed, skip this part.
Procedure
Step 1 On the home screen, choose Settings > System Settings > Indoor fan, set Air-side
difference pressure sensor type to 0~50 Pa.
Step 2 Set Indoor fan control type to Pressure diff ctrl.
Step 3 Change the other parameters based on the following instructions.
Table 4-5 Parameter description
Parameter
Description
Configuration Principle
Indoor fan control type
Sets the control type for the
indoor fan.
Normally, retain R/S air
temp diff rate ctrl. If the
differential pressure sensors
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
75
Parameter
Description
Configuration Principle
are configured, change to
Pressure diff ctrl.
Indoor fan pressure
difference setpoint
Sets the value for the
pressure difference control.
The default value is 10 Pa.
Air-side difference pressure
sensor type
Sets the measuring range for
the air side differential
pressure sensor.
There is no default value.
Set it to 0–50 Pa.
Min indoor fan speed
Sets the minimum speed for
the indoor fan.
You are advised not to
change the value.
Max indoor fan speed
Sets the maximum speed for
the indoor fan.
You are advised not to
change the value.
----End
4.3.3 Setting Teamwork Control Parameters
Prerequisites
Assign teamwork group number and teamwork unit address for the teamwork controlled
smart cooling products as follows:
Teamwork group no.: Group the smart cooling products in adjacent areas as one, that is,
assign one teamwork group number for them. At most four teamwork groups can be
assigned (1–4).
Teamwork unit address: The address for the smart cooling product in the same group
cannot be the same (address range: 1–32). The smart cooling product with minimum
address is the master one that collects, processes, and delivers data.
Context
The parameters in this section are for reference only. Set actually parameter values as
required.
Procedure
Step 1 On the home screen, tap
> Teamwork Settings, to enter Teamwork Settings page, as
shown in Figure 4-6.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
76
Figure 4-6 Teamwork settings
Step 2 Set teamwork control parameters.
All teamwork control parameters can be set on the master smart cooling product. Only
Teamwork group No., Air conditioner address, Enable teamwork CAN resistor,
Teamwork function and Networking mode can be set on slave smart cooling products.
Other parameters of the slave units will be modified by the master unit synchronously. Table
4-6 describes how to set the parameters.
Table 4-6 Teamwork settings
Parameter
Description
Configuration
Principle
Default
Value
Teamwork
group No.
Set the assigned
teamwork control
number.
The number of the
teamwork controlled
group, which is the same
for all the devices in the
group.
1
Air conditioner
address
Set the assigned smart
cooling product address.
Smart cooling product
addresses should be
different from each other.
NA
Enable
Teamwork
CAN resistor
Indicates the build-out
resistor status of each
smart cooling product in
a teamwork group. Set
the parameter if CAN
network is used.
Set this parameter to
No for non-teamwork
scenarios.
For teamwork
scenarios, set this
parameter to Yes for
the first and last smart
cooling products in a
teamwork group, and
set it to No for other
smart cooling products.
No
Teamwork
function
Disable or enable the
teamwork function. If the
teamwork function is
Set this parameter based
on the onsite device heat
Disable
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
77
Parameter
Description
Configuration
Principle
Default
Value
disabled, this device is
operating according to its
own control. If the
teamwork function is
enabled, this device
works in harmony with
others that in the same
group.
distribution.
Networking
mode
Networking mode for the
teamwork. The
networking mode set on
the screen must be
consistent with the actual
networking mode.
Otherwise, the teamwork
control function will be
unavailable. If the
networking mode
changes, select the
corresponding
networking mode on the
screen. If the networking
mode is changed on the
screen, the software will
restart and then run in the
new networking mode.
(For V200R002 version,
the software will not
restart when the
networking mode is
changed )
Networked over CAN or
MAC_CAN. CAN
network indicates
teamwork control over a
CAN bus, MAC_CAN
network teamwork control
over an FE port.
MAC_CAN
network
Number of
smart cooling
products in this
group
Number of the smart
cooling products in this
group (1 to 32 can be
set).
Total number of the smart
cooling products in this
group.
3
Number of
running smart
cooling
products in this
group
Number of active units in
a group. The value ranges
from 1 to Number of
smart cooling products
in this group.
The host allocates running
units by smart cooling
product unit address in
ascending order, which is
from 1 to 32. The rest will
become the standby ones.
2
Rotation
function
Disable or enable the
active and standby smart
cooling products to
change identity after a
certain time, maximizing
their service life.
This function is
recommended when the
heat is even.
Disable
Rotation
Rotation days (1–30).
7 by default
7 day (s)
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
78
Parameter
Description
Configuration
Principle
Default
Value
period
Rotation time
24 hours in a day (0–23).
0 by default
0
Forced rotation
Forced rotation
specifies whether to
enable a forcible rotation
on the group before the
specified rotation time.
After a forced rotation,
the accumulated time is
recalculated.
This item is set to No by
default. If forced rotation
is required, the function is
set to Yes.
No
Requirement
control
Enable or disable the
requirement control for
the master device.
When the requirement
control is Disable, the
master device does
not synchronize data
to the slave device,
and all the smart
cooling products
operate based on their
own requirements, not
referring to the mode
delivered by the
master device.
When the requirement
control is
Anti-competitive
running, the master
device synchronizes
data (the temperature
and humidity control
type and set points of
the master device and
other parameters) to
the slave device, and
all the smart cooling
products in the group
refer to the mode
delivered by the
master device.
When the requirement
control is Indoor fan
unified control, all
smart cooling product
fans in the group
rotate at the same
speed.
Anti-competitive running
is recommended for the
following scenario: In one
teamwork, the temperature
and humidity control type
and temperature and
humidity set point of units
are the same, and device
heat loads are distributed
evenly.
Disable
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
79
Parameter
Description
Configuration
Principle
Default
Value
Cascade
function
After the requirement
control is enabled, you
can configure Cascade
function. The cascade
function starts standby
smart cooling products if
the active one cannot
meet the refrigerating
requirements.
If the heat load to the
device increases, the
cascade function is
recommended.
Disable
Step 3 Complete the teamwork settings for all the smart cooling products by performing Step 1 and
Step 2.
Step 4 On the home screen of any teamwork controlled smart cooling product, tap
. If the
teamwork control succeeds, the teamwork topology of the smart cooling product in the group
is displayed, as shown in Figure 4-7. Table 4-7 describes the note for the screen.
Figure 4-7 Teamwork topology
Table 4-7 Notes for the screen
No.
Parameters
Note
1
On/Off
On indicates that the smart cooling product is started and Off
indicates that the smart cooling product is shut down.
2
01, 02, 03
Indicates the smart cooling product address. 01 is the master one
and the rest are all slave ones.
NOTE
If the master one offline, the teamwork networking failed.
3
Active/Stand
Active: properly responds to the requirement control.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
80
No.
Parameters
Note
by
Standby: responds to the requirement control when active one is
faulty (critical alarms, shutdown, and offline) or cannot meet
cooling requirements.
4
M/S
M indicates the master unit, and S indicates a slave unit. Blue
indicates that the device is operating, and gray indicates that the
device is idle.
5
Frame:
green/non-gr
een
A device with green frame indicates the device itself,
as shown in
.
A non-green frame indicates the other device in the group,
as shown in
.
6
Ground
color: red,
bright gray
Red indicates that a critical alarm is generated,
as shown in
.
Bright gray indicates that the device is operating without any
critical alarms,
as shown in
.
If teamwork succeeds, the teamwork icon is green. If teamwork fails, the teamwork icon is red. If
teamwork mode is disabled, the teamwork icon is gray.
----End
Follow-up Procedure
After you have completed the settings, perform the following checks to confirm whether the
teamwork control is available:
1.
Check whether the device number on the topology is the same as the actual device
number.
−
If yes, go to 2.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
81
−
If no, check the cable connection and the settings of teamwork control parameters.
2.
Check whether the number of active devices on the topology is the same as the actual
device number.
−
If yes, go to 3.
−
If no, check the cable connection and the settings of teamwork control parameters.
3.
Check whether the number of standby devices on the topology is the same as the actual
device number.
−
If yes, go to 4.
−
If no, check the cable connection and the settings of teamwork control parameters.
4.
Check whether the number of online devices on the topology is the same as the actual
device number.
−
If yes, the check is complete.
−
If no, check the cable connection and the settings of teamwork control parameters.
4.3.4 Setting Communications Parameters
4.3.4.1 Setting Communications Parameters (Modbus RTU Protocol)
Context
To set communications parameters, log in as the admin user.
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > Modbus Settings.
Step 2 Set baud rate and communication address by following instructions in Table 4-8.
Table 4-8 Baud rate and communication address settings
Parameter
Setting
Setting Method
Baud rate
9600, 19200
Set the baud rate as required. The value should be
consistent with that set on the EMS.
Communicat
ion address
1–255
Set the communication address of the smart cooling
product as planned. The EMS communicates with the
smart cooling product through this address, and the
communication addresses of two smart cooling products
connecting to the same EMS must be unique.
----End
4.3.4.2 Setting Communications Parameters (Modbus TCP Protocol)
Context
To set communications parameters, log in as the admin user.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
82
If Link mode is Server, a smart cooling product can be accessed by element
management system (EMS) client. If Link mode is Client, a smart cooling product can
be connected only to the EMS with the corresponding IP address. If Link mode is
Server and client, a smart cooling product can be accessed by EMS client and connect
to the EMS with the corresponding IP address at the same time.
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > IP Settings.
Step 2 Set the parameters by referring to Table 4-9.
Table 4-9 IP parameter settings
Parameter
Setting Method
IP assigning
mode
Set according to the actual plan.
IP address
Set according to the actual plan.
Subnet mask
Set according to the actual plan.
Gateway
Set according to the actual plan.
Step 3 Tap Submit.
Step 4 On the home screen, choose Settings > Comm Settings > Modbus Settings.
Step 5 Set parameters for Modbus TCP by following instructions.
Table 4-10 Modbus TCP parameter settings
Parameter
Setting
Setting Method
Link mode
Server, Client,
Server and
client
If you set Link mode to Server, the smart cooling
product, as a server, supports two client connection
and establishes communication.
If you set Link mode to Client, the smart cooling
product, as a client, can connect to a remote server and
establish communication.
If you set Link mode to Server and client, the smart
cooling product, as a server, supports two client
connection and establishes communication. In
addition, the smart cooling product, as a client, can
connect to a remote server and establish
communication.
Client
encryption
Enable,
Disable
This parameter is configurable when Link mode is set to
Client.
Server
encryption
Enable,
Disable
This parameter is configurable when Link mode is set to
Server.
NMS IP
N/A
Enter the actual IP address of the EMS. IP addresses of
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
83
Parameter
Setting
Setting Method
address
the display panel, EMS client, and EMS server must be
unique. This parameter is configurable when Link mode
is set to Client.
NMS port
number
N/A
It is recommended that you retain the default value. If you
need to change the value, enter a value as required. This
parameter is configurable when Link mode is set to
Client.
----End
4.3.4.3 Setting Communications Parameters (SNMP Protocol)
Context
To set communications parameters, log in as the admin user.
This section is suitable only for SNMP. Skip this section if you use Modbus.
Record the values entered in this section. They will be used when you access a smart
cooling product to an EMS (element management system).
One smart cooling product supports concurrent access of up to 6 EMSs through SNMP.
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > SNMP Settings. Figure 4-8 is
displayed.
Figure 4-8 Setting SNMP communications parameters
Step 2 Set SNMP Version based on site requirements, and then tap Submit.
If you set SNMP Version to ALL or SNMPv1&v2c, you can set Read Community and
Write Community by performing Step 3.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
84
If you set SNMP Version to ALL or SNMPv3, you can add SNMPv3 users by
performing Step 4.
Step 3 Set Read Community and Write Community.
1.
Tap the text box after Read Community, as shown in Figure 4-9. Set Read Community
as planned, tap
, and then tap Submit.
Figure 4-9 Setting read community
2.
Tap the text box after Write Community, as shown in Figure 4-10. Set Write
Community as planned, tap
and then tap Submit.
Figure 4-10 Setting write community
Step 4 Add an SNMPv3 user.
1.
Tap Add under SNMP V3.
2.
Enter a planned value for User Name, select values for Auth Protocol and Prop
Protocol from drop-down list boxes, and tap
, as shown in Figure 4-11.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
85
MD5 and DES protocols are not secure. It is recommended that you set Auth Protocol
to SHA, and set Prop Protocol to AES. The following operations use the recommended
settings as an example.
Figure 4-11 Setting the protocol type
Passwords of an authentication protocol and proprietary protocol must comply with the
following policies:
The password must consist of 8–15 characters and contain at least two types of characters
among uppercase letters (A–Z), lowercase letters (a–z), and digits (0–9).
A password must be different from the corresponding user name or inverted user name.
A password must not be a string containing duplicate sections, such as 12a12a12a.
3.
Set SHA Password and Confirm Password as planned, and tap
, as shown in
Figure 4-12.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
86
Figure 4-12 Setting an SHA password
4.
Set AES Password and Confirm Password as planned, and tap
, as shown in
Figure 4-13.
Figure 4-13 Setting an AES password
5.
Tap Submit.
Step 5 Tap the text box after SNMP Port, as shown in Figure 4-14. Set SNMP Port to the actual
port number, tap
, and then tap Submit.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
87
Figure 4-14 Setting SNMP port
SNMP Port is set to 161 by default.
Step 6 Tap Next Page.
Step 7 Set SNMP trap parameters.
1.
Tap Add under SNMP Trap.
2.
Set Trap Address as planned and Trap Port to the actual port number.
Trap Port is set to null by default.
3.
Select the SNMP Version. If an SNMPv3 user is configured, it is recommended that
SNMP Version be set to SNMPv3.
4.
If SNMP Version is set to SNMPv3, select an SNMPv3 user name, and then tap
as shown in Figure 4-15.
Figure 4-15 Setting SNMP trap parameters
5.
Tap Submit under SNMP Trap.
----End
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
88
Follow-up Procedure
After a USB flash drive has been inserted into the controller USB port and successfully
identified, tap Export File under MIB File to export the MIB file to the USB flash drive for
the customer's use in accessing a third-party EMS. Figure 4-16 shows successful file export.
Before using a USB flash drive, ensure that its data has been scanned by antivirus software
and is secure.
Figure 4-16 Exporting the MIB file successfully
4.3.5 (Optional) Setting WIFI Parameters
Prerequisites
After connecting the WIFI module of the USB interface to the USB port of the smart cooling
product display, WIFI Settings is enabled to be set.
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > WIFI Settings.
Step 2 Set the parameters by referring to Table 4-11.
Table 4-11 WiFi settings
Parameter
Setting Method
WiFi SSID
Set WiFi SSID based on the actual configuration; WiFi SSID is the
name used for the WiFi hotspot over which a mobile phone can
connect to the smart cooling product.
WiFi Password
Enter the WiFi password when you use a mobile phone to connect
to the WiFi. When you enable the WiFi function for the first time,
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
89
Parameter
Setting Method
you need to set a password (the WiFi has no preset password).
Enable WiFi
Enable the WiFi function. The default status is Disable.
Step 3 Tap Submit.
----End
4.4 Startup
Download the Service Expert app from Huawei app store and runs on Android. Apply for
permission after downloading the app.
Step 1 Tap Start on the home screen of the ACC.
If the screen shown in Figure 4-17 is displayed, indicating initial startup, perform Step 2
for initial startup verification.
Figure 4-17 Initial startup
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
90
Figure 4-18 Password screen
If the software version is after V200R002C00SPC050, a QR code will generate in the Start Password
page, used for inputing the barcode and verify code when offline boot is used.
If the screen shown in Figure 4-19 is displayed, tap Confirm to start the smart cooling
product.
Figure 4-19 Startup
Step 2 Select Offline Boot or Online Boot as required on the Service Expert app for initial startup
verification.
The Service Expert app can be downloaded from Huawei app store and runs on Android.
User interfaces displayed in this document correspond to the APP software version
V100R001C00B043T007 and are for reference only.
For offline boot, enter the barcode and the verification code on the mobile phone app. The
app automatically generates a startup password for the smart cooling product. Then enter
the password on the home screen of the ACC to start the smart cooling product.
For online boot, activate the startup password on the mobile phone app to start the smart
cooling product.
If the initial startup verification is passed, startup verification is not required afterwards.
After factory settings are restored, re-verification for startup is required.
----End
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
91
Offline Boot
Step 1 Open the Service Expert app.
Step 2 Tap StartUp on the home screen of the app and the screen shown in Figure 4-20 is displayed.
Figure 4-20 Offline boot
Step 3 Tap Offline Activation and the screen shown in Figure 4-21 is displayed.
Figure 4-21 Generating a startup password
If the software version is after V200R002C00SPC050, an icon
will generate in the right of
BarCode. After clicking it and scanning the QR code generated in the Start Password page, the
barcode and verify code can be automatically entered into the APP.
NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
92
Step 4 On the Offline Activation screen, enter Bar code and Verification code, which are available
on the home screen. Tap Generate PWD to generate a startup password.
If startup verification fails (when you do not enter the password within 5 min or the password you enter
is incorrect), the generated password will be invalid for the sake of security. The initial startup
verification fails, you need to generate a new startup password.
Step 5 Tap Password on the home screen of the ACC and enter the generated startup password in
the displayed dialog box.
----End
Online Boot
Step 1 Insert the WiFi module to the USB port on the ACC.
Step 2 Choose Settings > Comm Settings > WIFI Settings on the home screen of the ACC. Then
set WiFi parameters and enable the WiFi function.
Step 3 Connect the mobile phone to the smart cooling product WiFi and ensure proper
communications between the mobile phone app and the smart cooling product.
Step 4 Open the Service Expert app.
Step 5 Tap StartUp on the home screen of the app and the screen shown in Figure 4-22 is displayed.
Figure 4-22 Login screen
The preset user name is admin, and the preset password is Changeme.
If you change the login password on the smart cooling product LCD, the password for logging in to
the Service Export app will be changed to what you set on the LCD.