Azbil C15 User's Manual For Installation & Configuration
Read Online
Read the Azbil C15 User's Manual For Installation & Configuration online using the built-in PDF viewer.
Text of the manual
Thank you for purchasing an Azbil
Corporation product.
This manual contains information for
ensuring the correct use of this product.
It also provides necessary information
for installation, maintenance, and
troubleshooting.
This manual should be read by those
who design and maintain equipment
that uses this product. Be sure to keep
this manual nearby for handy reference.
No. CP-SP-1148E
Single Loop Controller
Model C15
User’s Manual
for
Installation & Configuration
(Not for use in Japan)
Be sure that the user receives this manual before the product is used.
Copying or duplicating this user’s manual in part or in whole is forbidden.
The information and specifications in this manual are subject to change
without notice.
Considerable effort has been made to ensure that this manual is free from
inaccuracies and omissions. If you should find an error or omission, please
contact the azbil Group.
In no event is Azbil Corporation liable to anyone for any indirect, special or
consequential damages as a result of using this product.
The quick reference guide on pages D-1 to D-8 summarizes key operations, parameters,
and settings, and gives concrete operation examples using illustrations. Try looking at these
pages first, and then read the main text for details.
A separate color version of the quick guide printed on dirt-resistant paper is available for
convenient use on the work site (document No. CP-SP-1213E). Contact the azbil Group or a
distributor for details.
Getting Up to Speed with model C15
© 2003–2020 Azbil Corporation. All Rights Reserved.
Modbus™ is a trademark and the property of Schneider Electric SE, its subsidiaries
and affiliated companies.
To reduce the risk of an electric shock that could cause personal injury,
follow all safety notices in this document.
This symbol warns the user of a potential shock hazard where hazardous
live voltages may be accessible.
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the
equipment must be impaired.
Do not replace any component (or part) not explicitly specified as replaceable by your supplier.
All wiring must be in accordance with local norms and carried out by authorized and experienced personnel.
A switch in the main supply is required near the equipment.
Main power supply wiring requires a (T) 0.2 A, 250 V fuse(s) (IEC 127).
�
z EQUIPMENT RATINGS
Supply voltages:
100 to 240 V AC (operating power supply voltage 85 to 264 V AC)
Frequency:
50/60 Hz
Power consumption:
12 VA max.
�
z EQUIPMENT CONDITIONS
Do not operate the instrument in the presence of flammable liquids or vapors.
Operation of any electrical instrument in such an environment constitutes a safety hazard.
Temperature:
0 to 50 °C
Humidity:
10 to 90 %RH (no condensation)
Vibration:
2 m/s2 (10 to 60 Hz)
Over-voltage category:
Category II (IEC60364-4-443, IEC60664-1)
Pollution degree:
2
Installation location:
Indoors
Altitude:
2000 m or less
�
z EQUIPMENT INSTALLATION
The controller must be mounted into a panel to limit operator access to the rear terminal.
Specifications of common mode voltage: The common mode voltages of all I/O except for main
supply and relay outputs are less than 30 Vrms, 42.4 V peak and 60 V DC.
�
z APPLICABLE STANDARDS
EN61010-1,
EN61326-1 (For use in industrial locations)
During EMC testing, the reading or output may fluctuate by ±10 %FS.
Safety Requirements
� The safety precautions explained in the following section aim to prevent injury to the operator and others, and to
prevent property damage.
WARNING
Warnings are indicated when mishandling this product
might result in death or serious injury.
CAUTION
Cautions are indicated when mishandling this product
might result in minor injury to the user, or only physical
damage to the product.
� In describing the product, this manual uses the icons and conventions listed below.
Use caution when handling the product.
The indicated action is prohibited.
Be sure to follow the indicated instructions.
Handling Precautions:
Handling Precautions indicate items that the user should pay attention to when handling
this device.
:
This indicates the item or page that the user is requested to refer to.
Note:
Notes indicate information that might benefit the user.
(1) (2) (3):
Numbers within the parenthesis indicate steps in a sequence or parts in an explanation.
[para], [mode] etc.: These indicate keys on the keyboard of this unit, and messages and menus that appear
on the personal computer screen.
>> :
Indicates the result of an operation or the status after operation.
Conventions Used in This Manual
z Numeric value and character display on LED
Numeric values
The 7-segment LED expresses numeric values as follows:
0
1
2
3
4
5
6
7
8
9
Alphabetical characters
The 7-segment LED expresses alphabetical characters shown below. There
are some alphabetical characters, which are not displayed on the LED.
A
B
C
D
E
a
b
c
d
e
F
G
H
I
J
f
g
h
i
j
K
L
M
N
O
k
l
m
n
o
P
Q
R
S
T
p
q
r
s
t
U
V
Y
Z
–
u
v
y
z
Handling Precautions
As shown above, numeric value “2” and alphabetic character “Z” are shown
in the same manner.
Accordingly, numeric value “5” and alphabetic character “S”, as well as
numeric value “9” and alphabetic character “Q” are also shown in the same
manner.
Do not use this device in an environment with conductive pollution, or with dry non-
conductive pollution which can become conductive due to condensation, etc.
Otherwise, problems such as tracking phenomena may damage parts, resulting in fire.
When wiring the power for this device, be sure to mount a shutoff switch for the main power
to this unit within reach of the operator.
In addition, when wiring the power for AC power models, install a time-lag (T) fuse (rated
current 0.2 A, rated voltage 250 V) as specified by IEC 127.
Otherwise, tracking phenomena or parts failure due to other factors may cause fire.
Do not disassemble this device.
Doing so might cause electric shock or faulty operation.
Before removing, mounting, or wiring this device, be sure to turn off the power to the device
and all connected devices. Failure to do so might cause electric shock.
Do not touch electrically charged parts such as the power terminals.
Doing so might cause electric shock.
CAUTION
Use this device within the operating ranges recommended in the specifications (temperature,
humidity, voltage, vibration, shock, mounting direction, atmosphere, etc.).
Do not block ventilation holes.
Doing so might cause fire or faulty operation.
Wire this device properly according to predetermined standards.
Also wire the device using specified power leads according to recognized installation
methods. Failure to do so might cause electric shock, fire or faulty operation.
Do not allow lead clippings, metal shavings or water to enter the controller case.
Doing so might cause fire or faulty operation.
Firmly tighten the terminal screws at the torque listed in the specifications.
Insufficient tightening of terminal screws might cause electric shock or fire.
Do not use unused terminals on this device as relay terminals.
Doing so might cause electric shock, fire, or faulty operation.
We recommend attaching the terminal cover (sold separately) after wiring this device.
Failure to do so might cause electric shock, fire, or faulty operation.
Use the relays within the recommended life.
Failure to do so might cause fire or faulty operation.
If there is a risk of a power surge caused by lightning, use a surge absorber (surge protector)
to prevent fire or device failure.
Do not make incorrect connections. If the cables are connected incorrectly, this might cause
the unit to malfunction.
The controller does not function for approximately 6 s. after the power has been turned
ON. Great care should be taken if the relayoutput from the controller is used as an interlock
signal.
There is no isolation between control outputs 1 and 2. When necessary, use an appropriate
isolator.
Do not connect multiple loader cables to multiple units from one personal computer. The
current coming from other circuits might cause an error in the indication of the PV.
When wiring RS-485 communications, do not connect a terminating resistor to either end of
the communication path. A terminating resistor might cause a communication failure.
Do not operate the keys with a mechanical pencil or other sharp-tipped object.
Doing so might cause faulty operation.
In addition to ON/OFF control and conventional PID control, this unit is equipped with self-
tuning control, which does not require manual setting of control constants. Self-tuning
control ensures stable control even after a change in the SP or an external disturbance. This
is achieved by monitoring the control target, learning its characteristics, and automatically
calculating control constants.
Before Using This Unit
The protective film is adhered to the front console of this unit to protect the surface.
After the installation and wiring work has been completed, stick a scotch tape to the corner of the console and pull it
out in the direction indicated by an arrow to peel off the protective film.
Handling Precautions
If you attempt to peel off the protective film with your fingernail, this might
cause damage to the console.
ot2
ot1
ev3
ev2
ev1
man
rdy
para
mode
Scotch tape
Pull out
Five different manuals in total are available for model C15 Single Loop Controller (hereafter referred to as ”this
unit”). Read appropriate manuals according to your requirements. If you do not have a required manual, contact
the azbil Group or its dealer. Additionally, you can download necessary manuals from https://www.azbil.com.
The user level of this unit can be selected from three levels, “Simple configuration”, “Standard configuration”, and “High
function configuration.” The functions you can set up only with “Simple configuration” are described in Single Loop
Controller Model C15 User’s Manual for Basic Operation (CP-SP-1147E). If more advanced application is needed, refer
to this manual. This manual is intended for personnel who have already read SDC15 Single Loop Controller User’s
Manual for Basic Operation and/or operated Azbil Corporation’s Single Loop Controller to fully understand its basic
operation.
Single Loop Controller Model C15 User’s Manual for Installation & Configuration
Manual No. CP-SP-1148E
This manual. The manual describes the hardware and all functions of this unit. Personnel
in charge of design, manufacture, operation, and/or maintenance of a system using this
unit and those in charge of communication software of a system using the communication
functions of this unit must thoroughly read this manual. This manual also describes the
installation, wiring, connections for communication, all functions and settings of this unit,
operating procedures, communication with host station, such as personal computer,
communication addresses, troubleshooting, and detailed specifications.
Single Loop Controller Model C15 User’s Manual for Installation
Manual No. CP-UM-5287JE
This manual is supplied with the product. Personnel in charge of design and/or
manufacture of a system using this unit must thoroughly read this manual. This
manual describes the safety precautions, installation, wiring, list of parameters,
and primary specifications. For further information about operation, refer to
other manuals, Basic Operation and/or Installation & Configuration.
Single Loop Controller Model C15 User’s Manual for Basic Operation
Manual No. CP-SP-1147E
This manual is optional (sold separately). The manual describes the functions you can
set up only with “Simple configuration”. Personnel in charge of design, manufacture,
operation, and/or maintenance of a system using this unit must thoroughly read this
manual. This manual describes the installation, wiring, major functions and settings,
operating procedures, troubleshooting, and detailed specifications.
User’s Manual for Smart Loader Package Model SLP-C35 for Single Loop
Controller Model C15/25/26/35/36
Manual No. CP-UM-5290E
This manual is supplied with the Smart Loader Package. The manual describes
the software used to make various settings for C15/25/26/35/36 using a
personal computer. Personnel in charge of design or setting of a system using
C15/25/26/35/36 must thoroughly read this manual. The manual describes
installation of the software into a personal computer, operation of the personal
computer, various functions, and setup procedures.
CP-SP-XXXXE
Quick Reference Guide for Model XXX
Quick Reference Guide for Model C15
Manual No. CP-UM-1213E
For those using this device for the first time or for operators on the work site, this
guide serves as a reference when setting or modifying parameters. Key operations,
menu flowcharts and parameter settings are presented with color illustrations.
The Role of This Manual
Organization of This User’s Manual
This manual is organized as follows:
Chapter 1.
OVERVIEW
This chapter describes the applications, features, model selection guide, and part
names and functions of this unit. Since the part names described in this chapter are
used in the subsequent descriptions, the part names and functions of this unit must
be understood correctly in this chapter.
Chapter 2.
OUTLINE OF FUNCTIONS
This chapter describes the outline and operation flow of the functions of this unit.
Chapter 3.
INSTALLATION
This chapter describes the environmental conditions, installation dimensions,
installation procedures, and necessary tools when installing this unit.
Chapter 4.
WIRING
This chapter describes the wiring procedures, wiring precautions, and connection
examples.
Chapter 5.
DETAILED DESCRIPTION OF EACH FUNCTION
This chapter describes each function of this unit in detail.
Chapter 6.
LIST OF DISPLAYS AND SETTING DATA
This chapter lists up the display items of this unit and their contents.
Chapter 7.
CPL COMMUNICATIONS FUNCTIONS
This chapter describes how to communicate this unit with a host unit, such
as a personal computer or PLC through Azbil Corporation’s standard CPL
communication using RS-485.
Chapter 8.
Modbus COMMUNICATIONS FUNCTIONS
This chapter describes how to communicate this unit with a host unit, such as a
personal computer or PLC through Modbus communication.
Chapter 9.
LIST OF COMMUNICATION DATA
This chapter shows the list of communication data inside the memory of this unit.
Chapter 10. MAINTENANCE AND TROUBLESHOOTING
This chapter describes the maintenance and inspection of this unit, as well as
troubleshooting.
Chapter 11. CALIBRATION
This chapter describes how to calibrate this unit in order to keep the accuracy and
to safely operate this unit for an extended period of time.
Chapter 12. DISPOSAL
This chapter describes safety precautions and how to dispose of this unit when the
unit is no longer used.
Chapter 13. SPECIFICATIONS
This chapter describes the general specifications, performance specifications, and
optional parts of this unit.
Conventions Used in This Manual
Safety Precautions
Before Using This Unit
The Role of This Manual
Organization of This User’s Manual
Quick Reference Guide for Model C15
Chapter 1.
OVERVIEW
1-1
1 - 1
Overview
1-1
�
� Model selection table
1-2
�
� Accessories
1-3
�
� Optional parts
1-3
1 - 2
Part Names and Functions
1-4
�
� Main unit and console
1-4
�
� Bottom panel
1-5
�
� Rear panel
1-6
Chapter 2.
OUTLINE OF FUNCTIONS
2-1
2 - 1
Input/Output Configuration
2-1
2 - 2
Key Operation
2-2
�
� Standard key operation type
2-2
�
� Special key operation type
2-4
�
� Data setting procedures
2-6
�
� [mode] key operating procedures
2-7
�
� User level
2-8
2 - 3
Operation Modes
2-9
Chapter 3.
INSTALLATION
3-1
�
� Installation place
3-1
�
� External dimensions
3-2
�
� Panel cutout dimensions
3-2
�
� Mounting procedures
3-3
Chapter 4.
WIRING
4-1
4 - 1
Wiring
4-1
�
� Terminal assignment label symbols
4-2
�
� Wiring precautions
4-2
�
� Connection of open collector output to digital input
4-5
�
� Connection of communication (RS-485) cable
4-5
�
� Connection with solid state relay (SSR)
4-7
�
� Connection with current-input type controllers
4-10
�
� Noise preventive measures
4-10
4 - 2
Recommended Cables
4-11
DETAILED DESCRIPTION OF EACH FUNCTION
5-1
5 - 1
PV Input
5-1
�
� PV input range type
5-1
�
� Temperature unit
5-3
�
� Cold junction compensation (T/C)
5-3
�
� PV square root extraction dropout
5-3
�
� Decimal point position
5-4
�
� PV input range low limit/high limit
5-5
�
� PV ratio and PV bias
5-5
�
� PV low limit alarm threshold
5-5
�
� PV filter
5-6
�
� PV hold
5-6
�
� PV low limit/high limit and PV low limit/high limit alarms
5-6
5 - 2
Mode
5-7
�
� AUTO/MANUAL mode
5-7
�
� RUN/READY mode
5-7
�
� AT (Auto Tuning) stop/start
5-8
�
� Release all DO (digital output) latches
5-8
�
� Communication DI (digital input) 1
5-8
5 - 3
Control
5-9
�
� Control method
5-11
�
� Control action and Heat/Cool control
5-12
�
� Special control outputs
5-12
�
� MANUAL mode change
5-13
�
� ON/OFF control
5-13
�
� PID control
5-14
�
� Heat/Cool control
5-15
�
� ST (Self-tuning)
5-17
�
� AT (Auto tuning)
5-18
�
� Just-FiTTER
5-20
�
� RationaLOOP
5-20
�
� SP lag
5-20
5 - 4
AT (auto tuning) Function
5-21
�
� Starting procedures
5-21
�
� Stopping procedures
5-21
5 - 5
ST (Self-tuning) Function
5-24
�
� How to start ST
5-24
�
� How to stop ST
5-25
5 - 6
Precautions for ST (Self-tuning)
5-26
5 - 7
SP
5-27
�
� SP setup in operation display mode
5-28
�
� LSP system group
5-28
�
� LSP1 to 4
5-28
�
� LSP group number
5-28
�
� DI Assignment of LSP group selection
5-29
�
� SP ramp unit
5-30
�
� SP up ramp/down ramp
5-30
� SP low limit/high limit
5-31
�
� DI Assignment of SP ramp enabled/disabled
5-31
5 - 8
DI (Digital Input) and Internal Contact
5-32
�
� Operation type
5-33
�
� Internal event No. assignment
5-34
�
� Input bit function
5-34
�
� Input assign
5-35
�
� Polarity of input assign
5-36
�
� Polarity of input bit function
5-36
�
� DI Assignment setting with Smart Loader Package SLP-C35
5-37
5 - 9
Internal Event
5-38
�
� Operation
5-39
�
� Operation type
5-46
�
� Direct/reverse, standby, and EVENT state at READY
5-47
�
� Alarm OR, special OFF setup, and delay time unit
5-48
�
� Main setting, sub setting, and hysteresis
5-49
�
� ON delay and OFF delay
5-50
5 - 10
DO (Digital Output)
5-51
�
� MV1/MV2 process
5-52
�
� Operation type
5-53
�
� Output assign
5-54
�
� Polarity of output assign
5-56
�
� Polarity of output bit function
5-57
�
� Latch
5-57
�
� DO Assignment setting with Smart Loader Package SLP-C35
5-57
5 - 11
Application Examples
5-59
�
� Examples of applications using assign functions
5-59
5 - 12
Continuous Output
5-66
�
� Output range
5-66
�
� Output type
5-66
�
� Output scaling low limit/high limit
5-67
�
� MV scaling range
5-68
5 - 13
CT (Current Transformer) Input
5-69
�
� CT operation type
5-70
�
� CT output
5-70
�
� CT measurement wait time
5-70
�
� Number of CT turns and number of CT power wire loops
5-71
5 - 14
Console Display and Key Operation
5-73
�
� Key operation type
5-73
�
� [mode] key function
5-73
�
� MODE display setup
5-74
�
� PV/SP display setup
5-75
�
� MV display setup
5-76
�
� Event setting value display setup
5-77
�
� Event remaining time display setup
5-77
�
� CT input current value display setup
5-78
�
� User level
5-78
�
� LED monitor
5-78
� User Function
5-79
�
� Key lock, communication lock, and loader lock
5-83
�
� Password
5-84
Chapter 6.
LIST OF DISPLAYS AND SETTING DATA
6-1
6 - 1
List of Operation Displays
6-1
�
� Operation displays
6-1
6 - 2
List of Parameter Setting Displays
6-3
�
� Mode bank
6-3
�
� SP bank
6-3
�
� Event bank
6-4
�
� PID bank
6-5
�
� Parameter bank
6-6
�
� Extended tuning bank
6-7
6 - 3
List of Setup Setting Displays
6-8
�
� Setup bank
6-8
�
� Event configuration bank
6-13
�
� DI Assignment bank
6-16
�
� DO Assignment bank
6-19
�
� User Function bank
6-23
�
� Lock bank
6-23
�
� Instrument information bank
6-24
Chapter 7.
CPL COMMUNICATIONS FUNCTIONS
7-1
7 - 1
Outline of Communications
7-1
�
� Features
7-1
�
� Setup
7-1
�
� Communications procedures
7-2
7 - 2
Message Structure
7-3
�
� Message structure
7-3
�
� Data link layer
7-3
�
� Application layer
7-5
7 - 3
Description of Commands
7-6
�
� Continuous data read command (RS command)
7-6
�
� Continuous data write command (WS command)
7-7
�
� Fixed length continuous data read command (RD command)
7-8
�
� Fixed length continuous data write command (WD command)
7-9
�
� Fixed length random data read command (RU command)
7-10
�
� Fixed length random data write command (WU command)
7-11
7 - 4
Definition of Word Addresses
7-12
7 - 5
Numeric Representation in the Application Layer
7-13
7 - 6
List of Termination Codes
7-14
7 - 7
Reception and Transmission Timing
7-15
�
� Timing specifications for instruction and response message
7-15
�
� RS-485 driver control timing specifications
7-15
7 - 8
Cautions when Making Communications Programs for the Master Station
7-16
�
� Example of communications program
7-16
Chapter 8.
Modbus COMMUNICATIONS FUNCTIONS
8-1
8 - 1
Outline of Communications
8-1
�
� Features
8-1
�
� Setup
8-1
�
� Communications procedures
8-2
8 - 2
Message Structure
8-3
�
� Message structure
8-3
�
� Command type
8-6
�
� Amount of data
8-6
�
� Other specifications
8-6
8 - 3
Description of Commands
8-7
�
� Read command (03H)
8-7
�
� Write command (10H)
8-9
8 - 4
Specifications Common with CPL Communications Function
8-11
�
� Definition of word addresses
8-11
�
� Numeric representation
8-11
�
� RS-485 driver control timing specifications
8-11
Chapter 9.
LIST OF COMMUNICATION DATA
9-1
�
� List of communication data
9-1
Chapter 10. MAINTENANCE AND TROUBLESHOOTING
10-1
�
� Maintenance
10-1
�
� Alarm displays and corrective action
10-1
�
� Operation in case of PV input failure
10-2
Chapter 11. CALIBRATION
11-1
�
� Starting the calibration
11-1
�
� Exiting the calibration
11-1
�
� Cautions before starting the calibration
11-2
�
� Measuring instruments required for calibration
11-2
�
� Calibration procedures
11-2
Chapter 12. DISPOSAL
12-1
Chapter 13. SPECIFICATIONS
13-1
�
� Specifications
13-1
�
� Accessories
13-5
�
� Optional parts
13-5
Appendix
App.-1
Glossary
App.-1
Index
Quick Reference Guide for Model C15
This guide offers a summary of key operations, parameter flowcharts, and settings, for convenient
reference at the operation site. This guide is made for repeated use. Dirt wipes off easily and even notes
written with an oil-based felt-tip pen can be removed with an eraser. If more detailed information on
model C15 is needed, refer to the user's manuals: CP-SP-1147E for basic operation and CP-SP-1148E for
installation and configuration.
The most convenient way to configure the C15 is with the Smart Loader Package (model No. SLP-
C35J50). Please contact the azbil Group or a distributor for more information.
Upper display
Indicators during AT
[para] key
Mode indicators
Lower display
Various indicators
Loader connector (bottom panel)
[mode] key
[ ], [ ], and [ ] keys
Upper display
This display shows either the PV value or the display value and set value for each displayed item. If an alarm is trig-
gered, the normal display and alarm code are displayed alternately. During auto tuning (AT), the rightmost decimal
point flashes twice repeatedly.
Lower display
This display shows either the SP/MV/CT or the display value and set value for each displayed item. The rightmost
decimal point lights up or flashes to show RUN/READY mode or communications status, depending on the setting.
Mode indicators
rdy:
Lights when READY (RUN mode if not lit)
man:
Lights when MANUAL (AUTO mode if not lit)
ev1, ev2, ev3: Lights when event relays are ON
ot1, ot2:
Lights when the control output is ON (always lit when the current output is used)
[mode] key
• When this key is pressed and held for more than 1 second in the operation display mode, any of the following
operations from 0 to 7 which have been set previously can be executed:
0 : Mode key does not operate (Initial value)
1 : AUTO/MANUAL mode selection
2 : RUN/READY mode selection
3 : AT (Auto Tuning) start/stop selection
4 : LSP (Local SP) group selection
5 : Release all DO (Digital Output) latches
6 : Mode key does not operate
7 : ON/OFF selection of communication DI1
• When pressing the [mode] key in the setup display mode, the display is changed to the operation display
[para] key
• This key is used to change the display item.
• When this key is kept pressed for 2 s. or longer in the operation display mode, the display is then changed to the
setup display
[<], [ ] , [ ] keys
Theses keys are used to increase or decrease the numeric value, or to shift the digit.
Loader connector
The Smart Loader connector is on the bottom of the C15. Use the dedicated cable that is included with the Smart
Loader Package to connect the controller to a PC.
: Initial value
For change from
MANUAL to AUTO
to (2)
(MANUAL)
For change from
AUTO to MANUAL
to (1)
[para] key *3
[mode]
2-second press + hold of [para] key
[SP]
[Event]
[PID]
[Parameter]
[Extended tuning]
(2)
(1)
Upper and lower displays
remain off for 6s after power
ON. Each mode indicator
lights sequentially, and
then the operation display
appears.
When the power
is turned ON
LSP group
number
SP value
Manipulated
variable
MV value
Heat manipulated
variable
MV value
Cool manipulated
variable
MV value
PV value
SP value
Timer remaining
time 3
Internal
event 3
delay time
*1
[para] key
2-second
press + hold
of [para] key
[para] key *3
Flowchart of key operations and displays
(A)
to (A)
Key operations and displays
Setting displays
Operation displays
z Some items are not displayed depending on the availability of optional functions, model number, display setup (C73 to
C78) and display level (C79).
z Pressing [para] key while changing settings has the effect of canceling and moving to the next item.
*1 The parameters and numerical values registered as user functions UF are displayed.
*2 If no key is pressed for 3 minutes, the display automatically returns to (2) , PV display.
*3 If the [<] key is pressed while holding down the [para] key, various displys/settings can be
navigated in reverse order.
*4 Cannot be selected if ROM version 1 (id02) of the instrument information bank is 2.26 or
earlier.
� Explanation of arrows
[para] key :
2-second press + :
hold of [para] key
� Movement through each setup menu
• [para] key
Forward movement
• [para] key + [<] key Backward movement
Internal event 3
sub setting
Setting value
Internal event 3
main setting
Setting value
Timer remaining
time 2
Internal event 2
delay time
Internal event 2
sub setting
Setting value
Internal event 2
main setting
Setting value
[Setup]
[Event configuration] [DI assignment]
[DO assignment]
[User function]
[Instrument information]
[Lock]
[para] key
PV value
AT progress
value
Internal event 1
main setting
Setting value
CT1
Current
value
CT2
Current
value
Internal event 1
sub setting
Setting value
Timer remaining
time 1
Internal event 1
delay time
2-second press + hold of [para] key
*2
*4
to (2)
(B)
to (B)
*4
Setup of PV input range type
1
Start from the opera-
tion display (if nec-
essary press [mode]
once to get the op-
eration display).
If the sensor has not
been wired or is discon-
nected, an alarm for
abnormal PV input (any
one from AL0 1 to AL 1 1)
may appear on the
upper display.
2
Press and hold [para]
for more than 2s to
get the parameter
setup display. a--M
is shown on the
upper display.
In case of ON/OFF con-
trol, r--r appears on
the upper display.
3
Press and hold
[para] for more
than 2s again to get
the setup setting
display.
The current set
value for C0 1 (PV
input range type) is
displayed.
4
When the [<], [ ] or
[ ] key is pressed,
the rightmost digit
on the lower dis-
play flashes. If no
key is pressed for
more than 2s after
changing to the
desired value in the
PV input range list,
the display changes
from flashing to
continuously lit, and
the displayed value
is now set.
Setup of event operation type
In this example, the event 1 operation type is set to deviation high
limit.
1
Start from the opera-
tion display (if nec-
essary press [mode]
once to get the op-
eration display).
2
Press and hold [para]
for more than 2s to
get the parameter
setup display. a--M
is shown on the
upper display.
3
Press and hold
[para] for more
than 2s again to get
the setup setting
display.
The current set
value for C0 1 (PV
input range type) is
displayed.
4
Press [para] repeat-
edly to get e 1.c 1 on
the upper display. 0
is displayed on the
lower display.
0 on the lower display
indicates that the event
operation type is set to
"none."
5
When the [ ] or [ ] key is pressed, the rightmost digit on
the lower display flashes. Change the flashing digit to 4 by
pressing [ ] or [ ].
If no key is pressed for more than 2s, the displayed value
is set and the display changes from flashing to continu-
ously lit.
4 on the lower display indicates that the event operation type is set for
deviation high limit.
Similarly, use e2.C 1 to set the event 2 operation type, and use
e3.C 1 for event 3.
Red letters
: Items before operation
Blue letters
: Items during operation
Execution of auto tuning (AT)
AT forces ON/OFF of the MV a number of times (a limit cycle) to
calculate PID values.
Check that this operation does not create any problems for the as-
sociated equipment before executing AT.
1
Start from the opera-
tion display (if nec-
essary press [mode]
once to get the op-
eration display).
2
Press and hold [para]
for more than 2s to
get the parameter
setup display. a--M
is shown on the
upper display.
3
Press [para] twice.
The upper display
says at and the
lower display says
at.Of.
If the control method
is ON/OFF control and
if Bit 3 (AT stop/start
display) of the mode
display setup (C73) is set
to "disabled: 0," nothing
is displayed.
4
When [ ] or [ ] is
pressed, at.Of
flashes.
Flashing occurs only in
RUN and AUTO modes,
if there is no PV input
abnormality.
Also, if "AT stop/start" is
selected for DI assign-
ment, the display does
not blink and no change
can be made.
5
[Press [ ] once.
The lower display
starts to flash at.On.
6
If no key is pressed
for more than 2s,
at.ON remains
steadily lit and AT
begins.
During AT, the
rightmost decimal
point flashes twice
repeatedly. (When
AT is done, the light
goes off and the
new PID values go
into effect.)
During the AT process, if the mode is changed to READY or
MANUAL, if PV input is faulty, or if a power failure occurs, AT stops
automatically without changing the PID values.
AT can also be stopped by changing the setting from At.ON to
At.OF (return to step 3 above).
Setup of SP value
1
Start from the opera-
tion display (if nec-
essary press [mode]
once to get the op-
eration display).
2
Check that the
operation display is
displaying the SP.
(If not, press [para]
repeatedly until the
SP is displayed.)
3
When the [<], [ ] or
[ ] key is pressed,
the rightmost digit
on the lower display
flashes and the SP
can be changed to
the desired value.
In this case, the flash-
ing of the numerical
value implies that it
is not yet set. A nu-
merical setting that
is being changed
flashes the same
way.
If an SP limit is in effect,
the numerical value
cannot be changed to
a value above the limit.
The SP limit must be
changed first.
4
If no key is pressed
for more than 2s, the
displayed value is
set and the display
changes from flash-
ing to continuously
lit.
If the [mode] key is
pressed when the
display is flashing, the
status returns to that
of step 1.
For step numbers indicated in red like 4 , the following precaution applies:
• If the key lock is set, the numerical value does not flash, and the value cannot be changed.
To change a numerical value, cancel the key lock first.
RUN/READY mode selection
1
Start from the opera-
tion display (if neces-
sary press [mode]
once to get the op-
eration display).
2
Press and hold [para]
for more than 2s to
get the parameter
setup display. a--M
is shown on the
upper display.
In case of ON/OFF con-
trol, r--r appears on
the upper display.
3
Press the [para] key
once. The upper dis-
play says r--r and
the lower display
says rdy (or run).
The current mode is in-
dicated by run for RUN
mode or rdy for READY
mode.
4
When [ ] or [ ] is
pressed, the lower
display flashes.
If the DI assignment is
set to "RUN/READY se-
lection," the display does
not flash and no change
can be made.
5
When [ ] or [ ] is
pressed, run (or
rdy) on the lower
display flashes.
6
If no key is pressed
for more than 2s, the
displayed value is
set and the display
changes from flash-
ing to continuously
lit.
Setup of PID value
1
Start from the opera-
tion display (if neces-
sary press [mode]
once to get the op-
eration display).
2
Press and hold [para]
for more than 2s to
get the parameter
setup display. a--M
is shown on the
upper display.
3
Press [para] repeat-
edly to get p-1 (for
proportional band)
on the upper display.
The value set for p-1
is displayed on the
lower display.
If the control method is
"ON/OFF control," noth-
ing is displayed.
4
When [<], [ ] or [ ]
is pressed, the right-
most digit on the
lower display flashes,
and can be changed
to the desired value
for the proportional
band.
In this case, the flash-
ing of the numerical
value implies that it
is not yet set. A nu-
merical setting that
is being changed
flashes the same
way.
The proportional band
can be set in a range
from 0.1 to 999.9%.
5
If no key is pressed for more than 2s, the displayed value is
set and the display changes from flashing to continuously
lit.
If the [mode] key is pressed when the display is flashing, the status re-
turns to that of step 1.
Similarly, use i-1 to set the integral time (0 to 9999s), and d-1 to set
the derivative time (0 to 9999s).
Setup of event value
1
Start from the opera-
tion display (if neces-
sary press [mode]
once to get the op-
eration display).
2
Press and hold
[para] for more than
2s to get the param-
eter setup display.
a--M is shown on
the upper display.
3
Press [para] repeat-
edly to get e 1 on the
upper display. The
lower display says 0.
0 on the lower display
indicates that the event
main set value is "zero."
4
When [<], [ ] or [
] is pressed, the
rightmost digit on
the lower display
flashes, and can be
changed to the de-
sired value for the
event.
In this case, the
flashing of the
numerical value
implies that it is not
yet set.
A numerical set-
ting that is being
changed flashes the
same way.
5
If no key is pressed for more than 2s, the displayed value
is set and the display changes from flashing to continu-
ously lit.
If the [mode] key is pressed when the display is flashing, the status returns
to that of step 1.
Similarly, use e2 to set a value for event 2, and e3 to set a value
for event 3.
6
To set hysteresis as
well, press [para]
once (or twice,
depending on the
settings) to display
e 1.hy on the upper
display.
The lower display
says 5.
5 on the lower display
indicates that the cur-
rent set value for event
hysteresis is 5.
7
When [<], [ ] or [
] is pressed, the
rightmost digit on
the lower display
flashes, and can
be changed to the
desired value for
hysteresis.
If no key is pressed
for more than 2s,
the displayed value
is set and the dis-
play changes from
flashing to continu-
ously lit.
Similarly, use e2.hy to set a hysteresis value for event 2, and e3.hy
to set a hysteresis value for event 3.
Memo
List of parameters
List of operation displays
Display
Upper display: PV
Lower display: SP
Item
Contents
Initial
value
Setting
value
PV
SP
SP (Target value)
SP low limit to SP high limit
0
LSP 1 (Display example)
LSP
LSP No.
(1st digit: Value at the right end digit)
1 to LSP system group (Max. 4)
1
Out
MV
MV (Manipulated Variable)
-10.0 to +110.0%
Setting is enabled in MANUAL mode
(Numeric value flashed)
–
HEAt
Numeric value
Heat MV (Manipulated Variable)
Setting is disabled.
-10.0 to +110.0%
–
COOL
Numeric value
Cool MV (Manipulated Variable)
–
PV
At 1 (Display example)
AT progress display
(1st digit=Numeric value at right end digit)
Setting is disabled.
–
Ct 1
Numeric value
CT current value 1
Setting is disabled.
–
Ct2
Numeric value
CT current value 2
Setting is disabled.
–
E 1
Numeric value
Internal Event 1 main setting
-1999 to +9999U or 0 to 9999U
0
E 1.Sb
Numeric value
Internal Event 1 sub setting
0
t 1.--(Display example)
Numeric value
Timer remaining time 1
Setting is disabled.
Upper display: The distinction by ON
delay or OFF delay is displayed at the side
location of “t1.”.
–
E2
Numeric value
Internal Event 2 main setting
Same as Internal Event 1 main setting
0
E2.Sb
Numeric value
Internal Event 2 sub setting
Same as Internal Event 1 sub setting
0
t2.--(Display example)
Numeric value
Timer remaining time 2
Same as Timer remaining time 1
–
E3
Numeric value
Internal Event 3 main setting
Same as Internal Event 1 main setting
0
E3.Sb
Numeric value
Internal Event 3 sub setting
Same as Internal Event 1 sub setting
0
t3.--(Display example)
Numeric value
Timer remaining time 3
Same as Timer remaining time 1
–
List of parameter setting displays
MOdE
[Mode bank]
Display
Item
Contents
Initial value Setting value
A--M
AUTO/MANUAL
AUTO: AUTO mode MAN: MANUAL mode
AUTO
r--r
RUN/READY
RUN: RUN mode RDY: READY mode
RUN
At
AT stop/start
At.OF: AT stop At.ON: AT start
AT stop
dO.Lt
Release all DO latches
Lt.ON: Latch continue Lt.OF: Latch release
Latch continue
C.dI 1
Communication DI1
dI .OF: OFF dI .On: ON
OFF
SP
[SP bank]
Display
Item
Contents
Initial value Setting value
SP- 1 to SP-4
SP (for LSP1 to 4)
SP low limit to SP high limit
0
Ev
[Event bank]
Display
Item
Contents
Initial value Setting value
E 1 to E5
Internal Event 1 to 5 main setting
-1999 to +9999 or 0 to 9999 *
0
E 1.Sb to E5.Sb
Internal Event 1 to 5 sub setting
0
E 1.Hy to E5.Hy
Internal Event 1 to 5 hysteresis
0 to 9999 *
5
E 1.On to E5.On
z Internal Event 1 to 5 ON delay time
0.0 to 999.9 or 0 to 9999
0
E 1.OF to E5.OF
z Internal Event 1 to 5 OFF delay time
0
* The decimal point position varies by meeting the internal event operation type.
PI D
[PID bank]
Display
Item
Contents
Initial value Setting value
P- 1
Proportional band (PID1)
0.1 to 999.9%
5.0
I - 1
Integration time (PID1)
0 to 9999s (No integration control action when set at "0")
120
d- 1
Derivative time (PID1)
0 to 9999s (No derivative control action when set at "0")
30
rE- 1
Manual reset (PID1)
-10.0 to +110.0%
50.0
OL- 1
z MV low limit (PID1)
-10.0 to +110.0%
0.0
OH- 1
z MV high limit (PID1)
-10.0 to +110.0%
100.0
P- 1C
Cool-side proportional band (PID1)
0.1 to 999.9%
5.0
I - 1C
Cool-side integration time (PID1)
0 to 9999s (No integration control action when set at "0")
120
d- 1C
Cool-side derivative time (PID1)
0 to 9999s (No derivative control action when set at "0")
30
OL. 1C
z Cool-side MV low limit (PID1)
-10.0 to +110.0%
0.0
OH. 1C
z Cool-side MV high limit (PID1)
-10.0 to +110.0%
100.0
PARA
[Parameter bank]
Display
Item
Contents
Initial value Setting value
Control
CtrL
Control method
0: ON/OFF control 1: Fixed PID 2: ST(Self-tuning)
0 or 1
At. OL
MV low limit at AT
-10.0 to +110.0%
0.0
At. OH
MV high limit at AT
-10.0 to +110.0%
100.0
dI FF
ON/OFF control differential
0 to 9999U
5
OFFS
z ON/OFF control operating
point offset
-1999 to +9999U
0
PV
FL
PV filter
0.0 to 120.0s
0.0
rA
z PV ratio
0.001 to 9.999
1.000
bI
PV bias
-1999 to +9999U
0
Time proportional output
CyU
z Time proportional cycle
unit 1
0 to 3 *1
0
Cy
Time proportional cycle 1
5 to 120s or 1 to 120s *2
10 or 2
CyU2
z Time proportional cycle
unit 2
0 to 3 *1
0
Cy2
Time proportional cycle 2
5 to 120s or 1 to 120s *2
10 or 2
tP. ty
z Time proportional cycle
mode
0: Controllability aiming type
1: Operation end service life aiming type (Only ON/
OFF operation within Time proportional cycle)
0 or 1
SP
SPU
z SP up ramp (U/min)
0.0 to 999.9U(No ramp when set at "0.0U")
0.0
SPd
z SP down ramp (U/min)
0.0
*1 0: Unit of "1s" 1: Fixed at 0.5s 2: Fixed at 0.2s 3: Fixed at 0.1s
*2 5 to 120s when output includes the relay output
U: Unit Maximum unit of Industrial volume in
PV range (°C, Pa,L/min, etc.)
: Essential parameters for PV measurement and control
: Basic parameters
: Required parameters when using optional functions
Et
[Extended tuning bank]
Display
Item
Contents
Initial value Setting value
At.ty
AT type
0: Normal 1: Immediate response 2: Stable *1
1
JF.bd
z Just-FiTTER setting band
0.00 to 10.00
0.30
SP.LG
z SP lag constant
0.0 to 999.9
0.0
At-P
z AT Proportional Band adjust
0.00 to 99.99
1.00
At-I
z AT Integral time adjust
0.00 to 99.99
1.00
At-d
z AT Derivative time adjust
0.00 to 99.99
1.00
Ctr.A
z Control algorithm
0: PID(Conventional PID)
1: Ra-PID(High-performance PID)
0
JF.Ov
z Just-FiTTER assistance coefficient 0 to 100
0
St.SA
z ST step execution resolution band 0.0 to 99.99
10.0
St.Sb
z ST step setting band
0.0 to 10.00
0.50
St.Hb
z ST hunting setting band
0.0 to 10.00
1.00
St.ud
z ST step ramp change
0: ST is executed when the PV moves up or down.
1: ST is executed only when the PV moves up.
0
*1 Normal = Standard control characteristics, Immediate response = Control characteristics that respond immediately to
external disturbance, Stable = Control characteristics having less up/down fluctuation of PV
List of setup setting displays
StUP
[Setup bank]
Display
Item
Contents
Initial value Setting value
Analog input
C0 1
PV input range type
For details, refer to the PV Input Range Table
Depending on
Model No.
C02
Temperature unit
0: Celsius (°C) 1: Fahrenheit (°F)
0
C03
z Cold junction compensation
0: Performed (internal) 1: Not performed (external)
0
C04
Decimal point position
0: No decimal point
1 to 3: 1 to 3 digits below decimal point *1
0
C05
PV range low limit
When the PV input type is DC voltage/DC current,
-1999 to +9999U
0
C06
PV range high limit
1000
C07
z SP low limit
PV input range low limit to PV input range high
limit
–
C08
z SP high limit
–
C09
z PV square root extraction dropout 0.0 to 100.0% (PV square root extraction is not
performed when set at "0.0".)
0.0
Control action
C 13
z PID calculation adjustment function *2 0: Enabled 1: Disabled
0
C 14
Control action (Direct/Reverse) 0: Heat control (Reverse action)
1: Cool control (Direct action)
0
C 15
z Output operation at PV alarm
0: Control calculation is continued.
1: Output at PV alarm is output.
0
C 16
z Output at PV alarm
-10.0 to +110.0%
0.0
C 17
z Output at READY (Heat)
-10.0 to +110.0%
0.0
C 18
z Output at READY (Cool)
-10.0 to +110.0%
0.0
C 19
z Output operation at changing AUTO/MANUAL 0: Bumpless transfer 1: Preset
0
C20
z Preset MANUAL value
-10.0 to +110.0%
0.0 or 50.0
C2 1
z Initial output type (mode) of PID control 0: Auto 1: Not initialized 2: Initialized
0
C22
z Initial output of PID control
-10.0 to +110.0%
0.0 or 50.0
C26
Heat/Cool control
0: Not used 1: Used
0
C27
z Heat/Cool
0: Normal 1: Energy saving
0
C28
Heat/Cool control dead zone
-100.0 to +100.0%
0.0
C29
z Heat/Cool change point
-10.0 to +110.0%
50.0
SP
C30
LSP system group
1 to 4
1
C32
z SP ramp unit
0: 0.1U/s 1: 0.1U/min 2: 0.1U/h
1
C36
CT1 operation type
0: Heater burnout detection 1: Current value measurement
0
C37
CT1 output
0 to 1: Control output 1 to 2, 2 to 4: Event output 1 to 3
0
C38
CT1 measurement wait time
30 to 300ms
30
C39
CT2 operation type
Same as CT1
0
C40
CT2 output
Same as CT1
0
C4 1
CT2 measurement wait time
Same as CT1
30
Continuous output
C42
Control output 1 range
1: 4 to 20mA 2: 0 to 20mA
1
C43
Control output 1 type
0: MV 1: Heat MV 2: Cool MV 3: PV
4: PV before ratio, bias, and filter 5: SP
6: Deviation 7: CT1 current value
8: CT2 current value 10: SP+MV 11: PV+MV
0
C44
Control output 1 scaling low limit -1999 to +9999U
0.0
C45
Control output 1 scaling high limit
100.0
C46
Control output 1 MV scaling bandwidth 0 to 9999 (Valid when control output 1 type is 10 or 11)
200
C47
Control output 2 range
Same as control output 1
1
C48
Control output 2 type
Same as control output 1
3
C49
Control output 2 scaling low limit Same as control output 1
0
C50
Control output 2 scaling high limit Same as control output 1
1000
C5 1
Control output 2 MV scaling bandwidth Same as control output 1
200
Communication
C64
Communication type
0: CPL 1: Modbus (ASCII format)
2: Modbus (RTU format)
0
C65
Station address
0 to 127 (Communication is disabled when set at "0".)
0
C66
Transmission speed (bps)
0: 4800 1: 9600 2: 19200 3: 38400
2
C67
Data format (Data length)
0: 7 bits 1: 8 bits
1
C68
Data format (Parity)
0: Even parity 1: Odd parity 2: No parity
0
C69
Data format (Stop bit)
0: 1 bit 1: 2 bits
0
C70
z Communication minimum response time 1 to 250ms
3
Key operation • display
C7 1
z Key operation type
0: Standard type 1: Special type
0
C72
[mode] key function
0: Invalid 1: AUTO/MANUAL selection
2: RUN/READY selection 3: AT Stop/Start
4: LSP group selection 5: Release all DO latches
6: Invalid 7: Communication DI1 selection 8: Invalid
0
C73
z MODE display setup
(Sum of the weighting)
Bit 0: AUTO/MANUAL display (Enabled: +1)
Bit 1: RUN/READY display (Enabled: +2)
Bit 3: AT Stop/Start display (Enabled: +8)
Bit 4: Release all DO latches display (Enabled: +16)
Bit 5: Communication DI1 ON/OFF display (Enabled: +32)
Other invalid setting, 0, +4, +64, +128
255
C74
z PV/SP display setup
(Sum of the weighting)
Bit 0: PV display (Enabled: +1)
Bit 1: SP display (Enabled: +2)
Bit 2: LSP group number display (Enabled: +4)
Other invalid setting, 0, +8
15
C75
z MV display setup
(Sum of the weighting)
Bit 0: MV display (Enabled: +1)
Bit 1: Heat MV/cool MV display (Enabled: +2)
Bit 3: AT progress display (Enabled: +8)
Other invalid setting: 0, +4
15
C76
z EV display setup
(Operation display)
0: Not displayed
1: Set value of Internal event 1 is displayed
2: Set values of Internal event 1 to 2 are displayed
3: Set values of Internal event 1 to 3 are displayed
0
C77
z Event remaining time display setup
(Operation display)
0: Not displayed
1: Internal event 1 is displayed
2: Internal event 1 to 2 is displayed
3: Internal event 1 to 3 is displayed
0
C78
z CT input current value display setup
(Operation display)
0: Not displayed 1: CT1 current value is displayed
2: CT1 to 2 current values are displayed
0
Initial value Setting value
Key operation • display
C79
User level
0: Simple configuration 1: Standard configuration
2: High function configuration
0
C80
z LED monitor
0: Not used
1: Flashing while data is sending through RS-485 communication.
2: Flashing while data is receiving through RS-485 communication
3: Logical OR of all DI statuses
4: Flashing in READY mode
0
C90
z Number of CT1 turns
0: 800 turns 1 to 40: CT turns divided by 100
8
C9 1
z Number of CT1 power wire loops 0: 1 time 1 to 6: Number of times
1
C92
z Number of CT2 turns
0: 800 turns 1 to 40: CT turns divided by 100
8
C93
z Number of CT2 power wire loops 0: 1 time 1 to 6: Number of times
1
C97
PV input failure (under range)
type *2
0: -10 %FS
1: -5 mV (This setting is applicable if C01 (PV input
range type) is set for sensor type B (No.17) or
PR40-20 (No. 23))
0
*1 Cannot be set for a thermocouple if ROM version 1 ( id02) of the instrument information bank is 2.26 or earlier.
*2 Cannot be selected if ROM version 1 ( id02) of the instrument information bank is 2.26 or earlier.
EvCF
[Event configuration bank]
Display
Item
Contents
Initial value Setting value
E 1.C 1 to E5.C 1
Internal event 1 to 5
Configuration 1
Refer to event type (see page 8)
0
E 1.C2 to E5.C2
Internal event 1 to 5
Configuration 2
The digits are determined to 1st, 2nd, 3rd, and
4th digit from the right end.
1st digit: Direct/Reverse
0: Direct 1: Reverse
0
2nd digit: Standby
0: None 1: Standby 2: Standby + Standby at SP change
0
3rd digit: EVENT state at
READY
0: Continue 1: Forced OFF
0
4th digit: Undefined
0
0
E 1.C3 to E5.C3 z Internal event 1 to 5
Configuration 3
The digits are determined to 1st, 2nd, 3rd, and
4th digit from the right end.
1st digit: Alarm OR
0: None 1: Alarm direct + OR operation
2: Alarm direct + AND operation
3: Alarm reverse + OR operation
4: Alarm reverse + AND operation
0
2nd digit: Special OFF
0: As usual
1: When the event set value (main setting) is 0,
the event is "OFF".
0
3rd digit: Delay time unit
0: 0.1s 1: 1s 2: 1min
0
4th digit: Undefined
0
0
di
[DI assignment bank]
Display
Item
Contents
Initial value Setting value
dI 1. 1 to dI 3. 1
Internal contact 1 to 3
Operation type
0: No function 1: LSP group selection (0/+1)
2: LSP group selection (0/+2)
3: LSP group selection (0/+4) 4: Invalid
5: Invalid 6: Invalid 7: RUN/READY selection
8: AUTO/MANUAL selection
9: LSP/RSP selection 10: AT Stop/Start
11: ST disabled/enabled
12: Control action direct/reverse
13: SP Ramp enabled/disabled
14: PV Hold 15: PV Maximum value hold
16: PV Minimum value hold 17: Timer Stop/Start
18: Release all DO latches (Continue/Release)
19: Invalid 20: Invalid
0
dI 1.2 to dI 3.2 z Internal contact 1 to 3
Input bit operation
0: Not used (Default input)
1: Function 1 ((A and B) or (C and D))
2: Function 2 ((A or B) and (C or D))
3: Function 3 (A or B or C or D)
4: Function 4 (A and B and C and D)
0
dI 1.3 to dI 3.3 z Internal contact 1 to 3
Input assignment A
0: Normally opened 1: Normally closed
2: DI1 3: DI2 4 to 9: Undefined
10 to 14: Internal Event 1to 5
15 to 17: Undefined
18 to 21: Communication DI1 to 4
22: MANUAL 23: READY 24: Undefined
25: AT running 26: During SP ramp 27: Undefined
28: Alarm occurs 29: PV alarm occurs
30: Undefined 31: mode key pressing status
32: Event output 1 status 33: Control output 1 status
2: Contact 1
3: Contact 2
4: Contact 3
dI 1.4 to dI 3.4 z Internal contact 1 to 3
Input assignment B
0
dI 1.5 to dI 3.5 z Internal contact 1 to 3
Input assignment C
0
dI 1.6 to dI 3.6 z Internal contact 1 to 3
Input assignment D
0
dI 1.7 to dI 3.7
z Internal contact 1 to 3
Polarity A to D
The digits are determined to 1st, 2nd, 3rd and
4th digit from the right end.
1st digit: Polarity A
0: Direct 1: Reverse
0
2nd digit: Polarity B
0
3rd digit: Polarity C
0
4th digit: Polarity D
0
dI 1.8 to dI 3.8 z Internal contact 1 to 3 Polarity 0: Direct 1: Reverse
0
dI 1.9 to dI 3.9 z Internal contact 1 to 3
Internal event No. assignment
0: Every Internal Event
1 to 5: Internal Event No.
0
dO
[DO assignment bank]
Display
Item
Contents
Initial value Setting value
Ot 1. 1 to Ot2. 1
Ev 1. 1 to Ev3. 1
z Control output 1 to 2, event
output 1 to 3 Operation type
0: Default output 1 to 2: MV1 to 2
3 to 6: Function 1 to 4
0
Ot 1.2 to Ot2.2
Ev 1.2 to Ev3.2
z Control output 1 to 2, event
output 1 to 3 Output assign-
ment A
0: Normally opened 1: Normally closed
2 to 6: Internal Event 1 to 5
7 to 13: Undefined 14 to 15: MV1 to 2
16 to 17: Undefined 18 to 19: DI1 to 2
20 to 25: Undefined
26 to 28: Internal Contact 1 to 3
29 to 33: Undefined 34 to 37: DI1 to 4
38: MANUAL 39: READY 40: Undefined
41: AT running 42: During SP ramp
43: Undefined 44: Alarm occurs
45: PV alarm occurs 46: Undefined
47: Mode key pressing status
48: Event output 1 status
49: Control output 1 status
14: Output 1
15:
Output 2
2: Event 1
3: Event 2
4: Event 3
Ot 1.3 to Ot2.3
Ev 1.3 to Ev3.3
z Control output 1 to 2, event
output 1 to 3 Output as-
signment B
0
Ot 1.4 to Ot2.4
Ev 1.4 to Ev3.4
z Control output 1 to 2, event
output 1 to 3 Output as-
signment C
0
Ot 1.5 to Ot2.5
Ev 1.5 to Ev3.5
z Control output 1 to 2, event
output 1 to 3 Output assign-
ment D
0
Ot 1.6 to Ot2.6
Ev 1.6 to Ev3.6
z Control output 1 to 2, event
output 1 to 3 Polarity A to D
The digits are determined to 1st, 2nd, 3rd, and
4 th digit from the right end.
1st digit: Polarity A
0: Direct
1: Reverse
0
2nd digit: Polarity B
0
3rd digit: Polarity C
0
4the digit: Polarity D
0
Ot 1.7 to Ot2.7
Ev 1.7 to Ev3.7
z Control output 1 to 2, event
output 1 to 3 Polarity
0: Direct
1: Reverse
0
Ot 1.8 to Ot2.8
Ev 1.8 to Ev3.8
z Control output 1 to 2, event
output 1 to 3 Latch
0: None 1: Latch (Latch at ON)
2: Latch (Latch at OFF except for initialization
at power ON)
0
UF
[User function bank]
Display
Item
Contents
Initial value Setting value
UF- 1 to UF-8
z User function 1 to 8
–
–
LOC
[Lock bank]
Display
Item
Contents
Initial value Setting value
LOC
Key lock
0: All settings are possible
1: Mode, event, operation display, SP, UF, lock,
manual MV, [mode] key can be set
2: Operation display, SP, UF, lock, manual MV,
[mode] key can be set
3: UF, lock, manual MV, [mode] key can be set
0
C.LOC
z Communication lock
0: read/write enabled 1: read/write disabled
0
L.LOC
z Loader lock
0: read/write enabled 1: read/write disabled
0
PASS
Password display
0 to 15 (5: Password 1A to 2B display)
0
PS 1A
Password 1A
0000 to FFFF (Hexadecimal value)
0000
PS2A
Password 2A
0000 to FFFF (Hexadecimal value)
0000
PS 1b
Password 1B
0000 to FFFF (Hexadecimal value)
0000
PS2b
Password 2B
0000 to FFFF (Hexadecimal value)
0000
I d
[Instrument information bank]
Display
Item
Contents
Initial value Setting value
I d0 1
z ROM ID
0: Fixed
0
I d02
z ROM Version 1
XX. XX (2 digits after decimal point)
–
I d03
z ROM Version 2
XX. XX (2 digits after decimal point)
–
I d04
z Loader information
–
I d05
z EST information
–
I d06
z Manufacturing date code
(year)
Subtract 2000 from the year.
Example: "3" means the year 2003.
–
I d07
z Manufacturing date code
(month, day)
Month + day divided by 100.
Example: "12.01" means the 1st day of December.
–
I d08
z Serial No.
–
Precaution for setup
• The type of auto tuning can be changed by changing the value of
At.ty (AT type) in the extended tuning bank. Set it to match the
control characteristics.
Memo
Changing the user level
This controller's user level can be set to 1 of 3 types in setup C79.
The number of possible displays and settings decreases according
to the user level: high function > standard > simple. All items are
displayed when high function is selected.
1
If necessary press
[mode] once to
change to the op-
eration display.
Next, press and hold
[para] for more than
2s to get the param-
eter setup display.
a--M or r--r ap-
pears on the upper
display.
2
Press and hold
[para] for more than
2s again to display
c0 1 on the upper
display.
3
Press [para] repeat-
edly to change the
upper display to c79
(user level).
4
When [<], [ ] or [ ]
is pressed, the lower
display flashes and
can be changed to
the desired numeri-
cal value. Then, if no
key is pressed for
more than 2s, the
displayed value is
set and the display
changes from flash-
ing to continuously
lit.
0: Simple configuration
(initial value)
1: Standard configuration
2: High function configuration
• Items marked z in the tables are displayed in standard and/or high function configuration.
• To change a user level, refer to
Changing the user level
in the lower right part of this page.
PV input range table
[Thermocouple]
[RTD]
C0 1
set value
Sensor
type
Range
(°C)
Range
(°F)
C0 1
set value
Sensor
type
Range
(°C)
Range
(°F)
1
K
-200 to +1200
-300 to +2200
41
Pt100
-200 to +500
-300 to +900
2
K
0 to 1200
0 to 2200
42
JPt100
-200 to +500
-300 to +900
3
K
0.0 to 800.0
0 to 1500
43
Pt100
-200 to +200
-300 to +400
4
K
0.0 to 600.0
0 to 1100
44
JPt100
-200 to +200
-300 to +400
5
K
0.0 to 400.0
0 to 700
45
Pt100
-100 to +300
-150 to +500
6
K
-200.0 to +400.0
-300 to +700
46
JPt100
-100 to +300
-150 to +500
9
J
0.0 to 800.0
0 to 1500
51
Pt100
-50.0 to +200.0
-50 to +400
10
J
0.0 to 600.0
0 to 1100
52
JPt100 -50.0 to +200.0
-50 to +400
11
J
-200.0 to +400.0
-300 to +700
53
Pt100
-50.0 to +100.0
-50 to +200
13
E
0.0 to 600.0
0 to 1100
54
JPt100 -50.0 to +100.0
-50 to +200
14
T
-200.0 to +400.0
-300 to +700
63
Pt100
0.0 to 200.0
0 to 400
15
R
0 to 1600
0 to 3000
64
JPt100
0.0 to 200.0
0 to 400
16
S
0 to 1600
0 to 3000
67
Pt100
0 to 500
0 to 900
17
B
0 to 1800
0 to 3300
68
JPt100
0 to 500
0 to 900
18
N
0 to 1300
0 to 2300
[DC voltage/DC current]
19
PL II
0 to 1300
0 to 2300
20
WRe5-26
0 to 1400
0 to 2400
C0 1
set
value
Input type
Range
21
WRe5-26
0 to 2300
0 to 4200
23
PR40-20
0 to 1900
0 to 3400
84
0 to 1 V
The scaling and decimal
point position can be
changed variably in a
range of –1999 to +9999
24
DIN U -200.0 to +400.0
-300 to +700
86
1 to 5 V
25
DIN L -100.0 to +800.0 -150 to +1500
87
0 to 5 V
88
0 to 10 V
89
0 to 20 mA
Initial value
90
4 to 20 mA
*1
• Accuracy for No. 17 (B thermocouple) is as follows. 260 °C or less: ±5 %FS. 260–800 °C: ±1 %FS.
The PV values under 20 °C are not shown. However, if ROM version 1 (i d02) of the instrument
information bank is 2.04 or earlier, the indicated low limi value is -180 °C.
• Accuracy for No. 23 (sensor type PR40-20) is as follows. 300 °C or less: undefined. 300–800 °C:
±5 % FS. 800–1900 °C: ±2 % FS. However, if ROM version 1 (i d02) of the instrument informa-
tion bank is 2.26 or earlier, No. 23 cannot be selected.
*2
PL II thermocouple is a range, which has been added to the units manufactured from July, 2003.
*3
The decimal point for thermocouples can be displayed if the ROM version is 2.26 or later.
List of alarm codes
Alarm
code
Failure name
Cause
Corrective action
Input failure
AL0 1
PV input failure
(Over-range)
Sensor burnout, incorrect
wiring, incorrect PV input
type setting
Check the wiring.
Set the PV input type
again.
AL02
PV input failure
(Under-range)
Sensor burnout, incorrect
wiring, incorrect PV input
type setting
AL03
CJ failure
Terminal temperature is
faulty (thermocouple).
Check the ambient
temperature.
PV input failure
(RTD)
Sensor burnout, incorrect
wiring
Check the wiring.
AL 1 1
CT input failure
(Over-range)
(CT input 1 or 2,
or both)
A current exceeding the
upper limit of the display
range was measured. The
number of CT turns or the
number of CT power wire
loops is incorrectly set, or
wiring is incorrect.
• Use a CT with the cor-
rect number of turns
for the display range.
• Reset the number of
CT turns.
• Reset the number of
CT power wire loops.
• Check the wiring.
Unit failure
AL70
A/D conversion
failure
A/D converter is faulty.
Replace the unit.
AL95
Parameter failure
Power is shut-down while
the data is being set, or
data is corrupted by noise.
• Restart the unit.
• Set the data again (set
data for AL95/97 and
adjustment data for
AL96/98.
• Replace the unit.
AL96
Adjustment data
failure
Power is shut-down while
the data is being set, or
data is corrupted by noise.
AL97
Parameter failure
(RAM area)
Data is corrupted by
noise.
AL98
Adjustment data
failure (RAM area)
Data is corrupted by
noise.
AL99
ROM failure
ROM (memory) is faulty.
• Reset the unit.
• Replace the unit.
Handling Precautions
• If ROM version 1 (i d02) of the instrument information bank
is 2.04 or earlier, CT input failure (AL 1 1) is not displayed.
Event type
Operation
type
Set
value
Direct action
z: shows that the ON/OFF is changed at this value.
z: shows that the ON/OFF is changed at a point
that "1U" is added to this value.
Reverse action
z: shows that the ON/OFF is changed at this value.
z: shows that the ON/OFF is changed at a point
that "1U" is added to this value.
No event
0
Always OFF
Always OFF
PV high
limit
1
ON
HYS
Main setting
PV
ON
HYS
Main setting PV
PV low limit
2
Main setting
PV
ON
HYS
Main setting
PV
ON
HYS
PV high/low
limit
3
Main setting *
Sub-setting *
PV
ON
HYS
ON
HYS
Main setting *
Sub-setting *
PV
ON
HYS
HYS
Deviation
high limit
4
ON
HYS
SP + Main setting
PV
ON
HYS
SP + Main setting
PV
Deviation
low limit
5
SP + Main setting PV
ON
HYS
SP + Main setting PV
ON
HYS
Deviation
high/low
limit
6
Main setting Sub-setting
SP
PV
ON
HYS
ON
HYS
ON
HYS
HYS
Main setting Sub-setting
SP
PV
Deviation
high limit
(Final SP
reference)
7
ON
HYS
SP + Main setting
PV
ON
HYS
SP + Main setting
PV
Deviation
low limit
(Final SP
reference)
8
SP + Main setting PV
ON
HYS
SP + Main setting PV
ON
HYS
Deviation
high/
low limit
(Final SP
reference)
9
Main setting Sub-setting
SP
PV
ON
HYS
ON
HYS
ON
HYS
HYS
Main setting Sub-setting
SP
PV
Heater 1
burnout/
Over-current
16
CT1 at output ON
Main setting *
Sub-setting *
ON
HYS
ON
HYS
ON
HYS
HYS
Main setting *
Sub-setting *
CT1 at output ON
OFF before measuring the CT1 current value OFF before measuring CT1 current value
Heater 1
short-circuit
17
ON
HYS
Main setting
CT1 at output OFF
ON
HYS
Main setting
CT1 at output OFF
OFF before measuring CT1 current value OFF before measuring CT1 current value
Heater 2
burnout/
Over-current
18
CT2 at output ON
Main setitng *
Sub-setting *
ON
HYS
ON
HYS
ON
HYS
HYS
Main setting *
Sub-setting *
CT2 at output ON
OFF before measuring CT2 current value OFF before measuirng CT2 current value
Heater 2
short-circuit
19
ON
HYS
Main setting
CT2 at output OFF
ON
HYS
Main setting
CT2 at output OFF
OFF before measuring CT2 current value
OFF before measuring CT2 current value
Alarm
(status)
23
ON if alarm occurs (alarm code AL01
to 99).
OFF in other cases.
OFF if alarm occurs (alarm code AL01
to 99).
ON in other cases.
: initial value
*: If the main setting is greater than the sub-setting, operations are performed with the
main setting and sub-setting automatically swapped.
Event types other than the above:
Operation type
Set
value
Operation type
Set
value
Operation type
Set
value
SP high limit
10
Loop diagnosis 1
20
During AT (status)
27
SP low limit
11
Loop diagnosis 2
21
During SP ramp
28
SP high/low limit
12
Loop diagnosis 3
22
Control action (status)
29
MV high limit
13
READY (status)
24
ST setting standby (status)
30
MV low limit
14
MANUAL (status)
25
Timer (status)
32
MV high/low limit
15
1 - 1
Overview
This unit is a compact controller having a mask of 48 × 48 mm and provides the following features:
• The depth is only 60 mm, providing the excellent space-saving.
• The front panel is only 2 mm thick. This ensures the excellent thin design.
• The display panel is large. This provides excellent visibility.
• [mode] key, [para] key, and digit-shift keys are provided on the front panel. This
ensures easy setup operation.
• Various input types are available, thermocouples (K, J, E, T, R, S, B, N, PLII,
WRe5-26, PR40-20, DIN U, DIN L), RTDs (Pt100, JPt100), current signals
(4 to 20 mA DC, 0 to 20 mA DC), and voltage signals (0 to 1 V DC, 1 to 5 V DC,
0 to 5 V DC, and 0 to 10 V DC).
• For control outputs, relay, voltage pulse, and current output are provided.
Additionally, these control outputs can be combined for the 2nd control output.
• The unit can be made applicable to the heat/cool control using the 2nd control
output and/or event relay.
• ON/OFF control, fixed PID, and self-tuning control can be performed.
• In addition to the PID control, two algorithms, RationaLOOP and Just-FiTTER,
are mounted. This ensures excellent controllability.
• With optional functions, a combination among 3- or 2-event points (independent
contacts), 2-point CT input, 2-point digital input, and/or RS-485 can be selected.
• The personal computer loader port is provided as standard function. The setup
can be made easily with use of the personal computer loader.
• Use of optional Smart Loader Package (SLP-C35) makes it possible to easily
perform the read/write operation of the parameters.
In addition to the table format setup, the operation and control status can be
monitored using the trend display. This unit can be operated without use of
program on the host unit.
• The unit is applicable to the IEC directive and the CE marking is put on the unit.
(Applicable standards: EN61010-1 and EN61326-1)
Chapter 1. OVERVIEW
�
� Model selection table
The following shows the model selection table of this unit:
Basic
model No.
Mounting
Control
output
PV input
Power
supply
Option
Additional treatment
Specifications
1
2
C15
T
Panel mount type
*1
S
Socket mount type
Control output 1
Control output 2
*2
R0
Relay contact output
NO
None (relay output for
control output 1: NC)
V0
Voltage pulse output
(for SSR drive)
None
*3
VC
Voltage pulse output
(for SSR drive)
Current output
*3
VV
Voltage pulse output
(for SSR drive)
Voltage pulse output
(for SSR drive)
C0
Current output
None
*3
CC
Current output
Current output
T
Thermocouple input (K, J, E, T, R, S, B, N, PL II,
WRe5-26, PR40-20, DIN U, DIN L)
R
RTD input (Pt100/JPt100)
L
DC voltage/DC current input (0 to 1 V DC,
1 to 5 V DC, 0 to 5 V DC, 0 to 10 V DC,
0 to 20 mA DC, 4 to 20 mA DC)
A
AC Model (100 to 240 V AC)
D
DC Model (24 V AC/24 to 48 V DC)
00
None
01
Event relay output: 3 points
*3 *4
02
Event relay output: 3 points
Current transformer input: 2 points
Digital input: 2 points
*3 *4
03
Event relay output: 3 points
Current transformer input: 2 points
RS-485 communication
*5
04
Event relay output: 2 points
(independent contact)
*3 *4 *5
05
Event relay output: 2 points
(independent contact)
Current transformer input: 2 points
Digital input: 2 points
*3 *4 *5
06
Event relay output: 2 points
(independent contact)
Current transformer input: 2 points
RS-485 communication
0
No additional processing
D
Inspection Certificate provided
*1 Socket sold separately
Y
Complying with the traceability certification
*2 Only 1a contact is applicable for C15S
0
None
*3 Can not be selected for the C15S.
A
UL-marked product
*4 Current transformer sold separately
*5 Can not be selected for the DC Model.
Chapter 1. OVERVIEW
�
� Accessories
Name
Model No.
Mounting bracket (for C15T)
81409651-001
Gasket
81409657-001
�
� Optional parts
Name
Model No.
Mounting bracket (for C15T)
81446403-001
Gasket (20 pcs)
81406918-001
Current transformer (800 turns, 5.8 mm hole dia.)
QN206A*
Current transformer (800 turns, 12 mm hole dia.)
QN212A*
Socket (for C15S)
81446391-001
Hard cover
81446442-001
Soft cover
81446443-001
Terminal cover
81446898-001
Smart Loader Package
SLP-C35J50
L-shaped plug adaptor
81441057-001
* Not UL-certified.
Chapter 1. OVERVIEW
�
� Main unit and console
ot2
ot1
ev3
ev2
ev1
man
rdy
para
mode
Main unit
Console
rdy
man
ev1
ev2
ev3
ot1
ot2
para
mode
pv
sp
Lower Display
Mode indicator
[<], [ ], and [ ] keys
<
<
[para] key
Upper display
[mode] key
Console
SDC15
Main unit: Contains the electric circuit for I/O signals of measuring instruments,
CPU, and memory.
Console:
Contains the display panel showing numeric value and status, and
operation keys.
�
z Detailed description of console
[mode] key
When this key is kept pressed for 1 s or longer in the operation display mode, any
of the following operations, which have been set previously, can be performed:
• AUTO/MANUAL mode selection
• RUN/READY mode selection
• AT (Auto Tuning) start/stop selection
• LSP (Local SP) group selection
• Release all DO (Digital Output) latches
• ON/OFF selection of communication DI (Digital Input) 1
When pressing the [mode] key in the setup display mode, the display is changed
to the operation display.
[para] key
This key is used to change the display item.
When this key is kept pressed for 2 s or longer in the operation display mode, the
display is then changed to the setup display.
[<], [
<
], [
<
] keys
These keys are used to increase or decrease the numeric value, or to shift the
digit.
1 - 2
Part Names and Functions
Chapter 1. OVERVIEW
Upper display
This display shows the PV value or the name of each display item (display value
or set value). If an alarm occurs in the operation display mode, the normal
display and alarm code are displayed alternately.
The decimal point at the right end digit shows AT (auto tuning) or ST (self-
tuning) status. The decimal point flashes twice repeatedly during execution of
AT while it flashes once repeatedly during execution of ST.
Lower display
This display shows the SP value, or the display value or set value of each display
item. The decimal point at the right end digit shows the communication status.
Mode indicators
[rdy]:
RUN/READY mode indicator. Lights when READY
[man]:
AUTO/MANUAL mode indicator. Lights when MANUAL
[ev1], [ev2], [ev3]: Event output 1 to 3 indicator. Lights when event relays are ON.
[ot1], [ot2]:
Control output 1 and 2 indicator. Lights when the control
output is ON. The indicators are always lit when the current
output is used.
Handling Precautions
• To select the LSP group using the [mode] key, it is necessary to set a value
of “2” or more in [LSP system group].
• To show the communication status using the decimal point at the right
end digit on the lower display, select “High function configuration” and
make the [LED monitor] settings.
• Do not operate the key with a sharp object (such as tip of mechanical
pencil or needle). Doing so might cause the unit to malfunction.
�
� Bottom panel
Loader connector
Loader connector: This connector is connected to a personal computer using the
dedicated cable supplied with the Smart Loader Package.
Chapter 1. OVERVIEW
�
� Rear panel
�
z Model C15T (Panel mount type)
Terminal part
Terminal part: The power supply, input, and output are connected to the terminals.
The M3 screw is used. When connecting to the terminal, always use
a correct crimp terminal suitable for the M3 screw.
The tightening torque of the terminal screw is 0.4 to 0.6 N·m.
�
z Model C15S (Socket mount type)
Socket part
Socket part: This socket is inserted into the optional socket. The power supply,
input, and output are connected from the socket.
When performing the wiring from the socket, always use a correct
crimp terminal suitable for the M3.5 screw.
The tightening torque of the socket terminal screw is 0.78 to 0.98 N·m.
Control output 1, 2
(Current output)
Control output 1, 2
(Relay output, voltage
pulse output)
Event output 1 to 3
(Relay output)
CT input 1, 2
Digital input 1, 2
PV input
PV
process
Internal
event
process
Control
process
(ON/OFF
control,
PID control)
Other
Other
Internal
contact
process
CT
process
�
z PV input
Sensor or range is selected for the PV input. The selection range may vary
depending on the input type of the model (T: Thermocouple, R: RTD, L: DC
current, DC voltage).
�
z Control output
When the control output type of the model is “R: Relay” or “V: Voltage pulse”, the
control output becomes the ON-OFF control output or time proportional output.
When the time proportional output is used, the time proportioning cycle time
can be set. When the control output type of the model is “C: Current”, the control
output becomes the continuous output (analog output). When the model has two
control outputs, the heat/cool control can be used only with "Simple configuration".
�
z Event output
When the model provides the event, the alarm or control mode set in [Event type]
can be output as DO (digital output).
�
z DI (digital input)
When the model provides the DI, the function set with the DI assignments can be
selected.
�
z CT (current transformer) input
When the model provides the CT input, the heater burnout alarm can be output
from the event output.
Chapter 2.
OUTLINE OF FUNCTIONS
2 - 1
Input/Output Configuration
Chapter 2. OUTLINE OF FUNCTIONS
Various displays or settings can be called up on the console through key operation.
Two kinds of general key operation flows are provided, standard key operation type and special key operation type.
A desired key operation type can be selected using the setup setting.
• Standard key operation type:
Key operation similar to that of the conventional model SDC10.
• Special key operation type:
A part of key operation of the conventional model SDC30 is added to that of the
conventional model SDC10.
The following describes the general flow of each key operation type:
�
� Standard key operation type
When the key operation mode/type of the setup setting "C7 1" is set at "0", the
standard key operation type is selected. The display and setting data of the standard
key operation type are arranged as shown in the following tree-structure:
Operation display
Mode
Setup
PV and SP
5-75
AUTO/MANUAL
5-7
PV input range type
5-1
LSP group selection
5-29
RUN/READY
5-7
Temperature unit
5-3
MV
5-76
AT stop/start
5-8
Heat MV
5-76
Release all DO latches
5-8
User level
5-78
Cool MV
5-76
Communication DI 1
5-8
Communication monitor display 5-78
AT progress
5-76
CT input 1 current value
5-78
SP
Event configuration
CT input 2 current value
5-78
LSP1 group SP
5-28
Internal Event 1 Configuration 1
5-46
Internal Event 1 main setting
5-49
LSP2 group SP
5-28
Internal Event 1 Configuration 2
5-47
Internal Event 1 sub setting
5-49
LSP3 group SP
5-28
Internal Event 1 remain time
5-77
LSP4 group SP
5-28
Internal Event 5 Configuration 2
5-47
Internal Event 2 main setting
5-49
Internal Event 5 Configuration 3
5-48
Internal Event 2 sub setting
5-49
Event
Internal Event 2 remain time
5-77
Internal Event 1 main setting
5-49
DI Assignment
Internal Event 3 main setting
5-49
Internal Event 1 sub setting
5-49
Internal Contact 1 Operation type 5-33
Internal Event 3 sub setting
5-49
Internal Event 1 hysteresis
5-49
Internal Contact 1 Input bit function 5-34
Internal Event 3 remain time
5-77
Internal Event 5 ON delay
5-50
Internal Contact 3 Polarity
5-36
User Function (Utilization)
Internal Event 5 OFF delay
5-50
Internal Contact 3 Internal event No. assignment 5-34
User Function 1
5-79
User Function 2
5-79
PID
DO Assignment
User Function 3
5-79
P (Proportional band)
5-14
Control output 1 Operation type 5-53
User Function 4
5-79
I (Integration time)
5-14
Control output 1 Output assignment A 5-53
User Function 5
5-79
D (Derivative time)
5-14
User Function 6
5-79
Manual reset
5-14
Event output 3 Polarity
5-57
User Function 7
5-79
Event output 3 Latch
5-57
User Function 8
5-79
Output low limit (Cool)
5-14
Output high limit (Cool)
5-14
User Function
User Function 1
5-79
Parameter
User Function 2
5-79
Control method
5-11
MV low limit at AT
5-18
User Function 7
5-79
MV high limit at AT
5-18
User Function 8
5-79
ON/OFF control differential
5-13
Lock
SP up ramp
5-30
Key lock
5-83
SP down ramp
5-30
Communication lock
5-83
Extended tuning
Password 1B
5-84
AT type
5-18
Password 2B
5-84
Just-FiTTER settling band
5-20
SP lag constant
5-20
Instrument information
ROM ID
6-24
ST step settling band
5-17
ROM version 1
6-24
ST hunting settling band
5-17
ST step ramp change
5-17
Manufacturing date code (month, day) 6-24
Serial No.
6-24
Note. The figures shown on the
right of the display and setting
columns in the tree-structure
indicate the relevant pages.
2 - 2
Key Operation
Chapter 2. OUTLINE OF FUNCTIONS
Display when the power
is turned ON.
Keep the [para]
key pressed for
2 s or longer.
PV/SP display
Press the [para] key.
MV display
Other display and setup
(Operate the [para] key
repeatedly.)
Press the [para] key.
Press the [para] key.
AUTO/MANUAL
selection
Press the [para] key.
RUN/READY
selection
Other display and setup
(Operate the [para] key
repeatedly.)
Press the [para] key.
Press the [para] key.
Operation display
Press the [mode]
key.
Keep the [para]
key pressed for
2 s or longer.
Of.
The mode indicator
is lit sequentially
from the left.
Of.
No key operation for 3 min or more.
No key operation for 3 min
or more.
Keep the [para] key pressed
for 2 s or longer.
Press the [mode] key.
mode
pv
sp
mode
pv
sp
mode
pv
sp
mode
pv
sp
mode
pv
sp
mode
pv
sp
rdy
man
ev1
ev2
ev3
ot1
ot2
para
mode
pv
sp
The mode indicators are lit sequentially from
the left during a period of 6 s. after the power
has been turned ON while both the upper
display and lower display are of. When all
mode indicators have been lit, the display is
changed to the operation display.
Parameter setup
display
PV range type
setup
Press the [para] key.
Temperature unit
setup
Other display and setup
(Operate the [para] key
repeatedly.)
Press the [para] key.
Press the [para] key.
Setup setting display
The display and setup status shown above are examples for
explanation. Therefore, some displays or settings are not shown
actually according to the model and/or setup contents.
Handling Precautions
• For details about display and setup contents of the operation display,
parameter setting display, and setup setting display:
6 - 1 List of Operation Displays (p. 6-1)
6 - 2 List of Parameter Setting Displays (p. 6-3)
6 - 3 List of Setup Setting Displays (p. 6-8)
• When pressing the [<] key with the [para] key kept pressed instead of
pressing of the [para] key, various displays and settings can be operated
in the reverse order. However, the operation that both the [para] key and
[<] key are kept pressed for 2 s or longer, is invalid.
Chapter 2. OUTLINE OF FUNCTIONS
�
� Special key operation type
When the key operation mode/type of the setup setting "C7 1" is set at "1", the
special key operation type is selected.
The display and setting data of the special key operation type are arranged as shown
in the following tree-structure:
Operation display
Bank selection
PV and SP
5-75
Mode
Mode bank
LSP group selection
5-29
SP
AUTO/MANUAL
5-7
MV
5-76
Event
RUN/READY
5-7
Heat MV
5-76
PID
AT stop/start
5-8
Cool MV
5-76
Parameter
Release all DO latches
5-8
AT progress
5-76
Extension tuning
Communication DI 1
5-8
CT input 1 current value
5-78
Set up
CT input 2 current value
5-78
Event configuration
SP bank
Internal Event 1 main setting 5-49
DI assignment
LSP1 group SP
5-28
Internal Event 1 sub setting 5-49
DO assignment
LSP2 group SP
5-28
Internal Event 1 remain time 5-77
Users function
LSP3 group SP
5-28
Internal Event 2 main setting 5-49
Lock
LSP4 group SP
5-28
Internal Event 2 sub setting 5-49
Instrument information
Internal Event 2 remain time 5-77
Various bank
Internal Event 3 main setting 5-49
Internal Event 3 sub setting 5-49
Internal Event 3 remain time 5-77
Lock bank
Key lock
5-83
User Function (Utilization)
Communication lock
5-83
User Function 1
5-79
User Function 2
5-79
Password 1B
5-84
User Function 3
5-79
Password 2B
5-84
User Function 4
5-79
User Function 5
5-79
Instrument information bank
User Function 6
5-79
ROM ID
6-24
User Function 7
5-79
ROM version 1
6-24
User Function 8
5-79
Manufacturing date code (month, day) 6-24
Serial No.
6-24
Note. The figures shown on the right of the display and setting columns in the tree-structure indicate the relevant pages.
Chapter 2. OUTLINE OF FUNCTIONS
Display when the power
is turned ON.
Keep the [para]
key pressed for
2 s or longer.
PV/SP display
Press the [para] key.
MV display
Other display and setup
(Operate the [para] key
repeatedly.)
Press the [para] key.
Press the [para] key.
Mode bank selection
SP bank selection
Operation display
Press the [mode]
key.
Press the [<] key.
Of.
The mode indicator
is lit sequentially
from the left.
Of.
No key operation for 3 min or more.
No key operation for 3 min
or more.
Press the [mode] key.
mode
pv
sp
mode
pv
sp
mode
pv
sp
mode
pv
sp
mode
pv
sp
mode
pv
sp
rdy
man
ev1
ev2
ev3
ot1
ot2
para
mode
pv
sp
The mode indicators are lit sequentially
from the left during a period of 6 s after
the power has been turned ON while both
the upper display and lower display are of.
When all mode indicators have been lit, the
display is changed to the operation display.
Bank selection
PV range type
setup
Press the [para] key.
Temperature unit
setup
Other display and setup
(Operate the [para] key
repeatedly.)
Press the [para] key.
Press the [para] key.
Bank setting display
The display and setup status shown above are examples for explanation. Therefore, some displays or settings are not shown
actually according to the model and/or setup contents.
Keep the [para] key pressed for 2 s or longer.
Press the [para] key.
Press the [ ] or [ ] key.
<
<
Press the [para] key.
Press the [ ] or [ ] key.
<
<
Press the [para] key.
Press the [ ] or [ ] key.
<
<
Other banks
(Operate the [para] key
and the [ ] or [ ] key
repeatedly.)
<
<
Handling Precautions
• For details about display and setup contents of the operation display,
bank selection display, and bank setting display:
6 - 1 List of Operation Displays (p. 6-1)
6 - 2 List of Parameter Setting Displays (p. 6-3)
6 - 3 List of Setup Setting Displays (p. 6-8)
In the lists shown above, a bank belonging to each setting item is
described.
• When pressing the [<] key with the [para] key kept pressed instead of
pressing of the [para] key in the operation display or setting item display
mode, various displays and settings can be operated in the reverse order.
However, the operation becomes invalid that both the [para] key and [<]
key are kept pressed for 2 s or longer.
Chapter 2. OUTLINE OF FUNCTIONS
�
� Data setting procedures
(1) Operate the [para] key to display desired data to be set.
(How to operate the [para] key is described in the previous section, "Flow of
general key operation".)
mode
pv
sp
mode
pv
sp
(This Figure shows the display when
setting the PV range type of the setup
setting [C0 1].)
(This Figure shows the display when
setting the RUN/Ready selection in
the parameter setting [r...r].)
(2) Press any of the [<], [
<
], and [
<
] keys.
>> When the lower display shows a numeric value, the 1st digit starts flashing.
Additionally, when the lower display shows a character string, the entire
character string starts flashing.
When a numeric value is displayed, the value can be increased or decreased
or the flashing digit can be moved using the [<], [
<
], or [
<
] key.
When a character string is displayed, the entire flashing character string can
be changed using the [
<
] or [
<
] key.
mode
pv
sp
mode
pv
sp
(This Figure shows the display when
the 1st digit of "000 1" is fashing.)
(This Figure shows the display when
the entire character string "rUn" is
fashing.)
(3) Release the key and wait for a while.
>> After 2 s have elapsed, the flashing display is stopped, and then the data you
have changed is set.
mode
pv
sp
mode
pv
sp
Handling Precautions
• If the data does not start flashing even though the [<], [
<
], or [
<
] key is
pressed, this data cannot be changed.
For example, when the RUN/READY is assigned in the DI Assignment,
RUN/READY cannot be selected using the key on the front panel.
Chapter 2. OUTLINE OF FUNCTIONS
• If the character string cannot be changed using the [
<
] key while the
entire character string is flashing, press the [
<
] key.
On the contrary, if the character string cannot be changed using the [
<
]
key, press the [
<
] key.
• When pressing the [para] key while the display is flashing, the next data
is displayed without changing of the data. Additionally, when pressing
the [mode] key while the display is flashing, the display is returned to the
operation display without changing of the data.
• The MV (manipulated variable) display in the MANUAL mode continues
the flashing status even after pressing of the key has been stopped. At
this time, the flashing value is output as MV.
�
� [mode] key operating procedures
When the [mode] key is kept pressed for 1 s or longer on the operation display, the
selection operation, which has been set using the [mode] key function (C72) of the
setup setting, can be performed.
The Figure on the right shows an example that the
[mode] key is pressed in the RUN/READY selection
(C72 = 2) setting.
(1) If the current mode is the READY mode when
the PV/SP is shown on the operation display, the
character string "rUn" on the lower display starts
flashing.
(2) When the [mode] key is kept pressed for 1 s or
longer, the READY mode is changed to the RUN
mode and the flashing of the character string "rUn"
is stopped.
(3) When pressing of the [mode] key is stopped, the
display is returned to the PV/SP display.
mode
pv
sp
mode
pv
sp
mode
pv
sp
Handling Precautions
• If the MODE key function of the setup setting is set disabled (C72 = 0) or
if the set selection operation is invalid, the selection operation cannot be
performed using the [mode] key.
• When pressing the [mode] key on the parameter setting display or setup
setting display instead of the operation display, the display is returned
to the operation display. However, even though the [mode] key is kept
pressed continually, the selection operation cannot be performed. In this
case, stop pressing the key once, and then press the [mode] key.
Chapter 2. OUTLINE OF FUNCTIONS
�
� User level
The user level of this unit can be selected from three levels, "Simple configuration",
"Standard configuration", and "High function configuration" using the user level of
the setup setting "C79".
Chapter 6. LIST OF DISPLAYS AND SETTING DATA
Handling Precautions
Even though the user level is changed, the functions other than setting
display cannot be changed. The user level is set to "Standard configuration"
or "High function configuration" and more advanced functions are set.
After that, when the setup is returned to "Simple configuration", this
function setup cannot be displayed, but the function itself is operated.
Chapter 2. OUTLINE OF FUNCTIONS
The following shows the transition of operation modes:
AT stop
ST stop
AT stop
ST stop
AT stop
ST stop
AT stop
ST stop
AT running
ST running
RUN + MANUAL mode
AUTO/MANUAL
selection
AUTO/MANUAL
selection
RUN + AUTO mode
READY + AUTO mode
RUN + MANUAL mode
RUN/READY
selection
RUN/READY
selection
RUN:
Control status
READY:
Control stop status
AUTO:
Automatic operation (This unit automatically determines the MV values.)
MANUAL:
Manual operation (The MV values are operated manually.)
AT:
Auto tuning (The PID constants are set automatically using the limit cycle.)
ST:
Self-tuning (The PID constants are set automatically while the control is kept continuously.)
2 - 3
Operation Modes
Use this device within the operating ranges recommended in the specifications (temperature,
humidity, voltage, vibration, shock, mounting direction, atmosphere, etc.).
Failure to do so might cause fire or faulty operation.
Do not block ventilation holes.
Doing so might cause fire or faulty operation.
�
� Installation place
Install the controller in the following locations:
• With the exception of supply power and relay contact output, the I/O common
mode voltage to ground must be 30 Vrms max., 42.4 V peak max., 60 V DC max.
• Not high or low temperature/humidity.
• Free from silicone gas and other corrosive gases such as sulfide gas.
• Less dust or soot.
• Appropriately processed locations to prevent direct sunlight, wind or rain.
• Less mechanical vibration and shock.
• Not close to the high voltage line, welding machine or electrical noise generating
source.
• The minimum 15 m away from the high voltage ignition device for a boiler.
• Less effect by the magnetic.
• No flammable liquid or gas.
• Indoors.
Chapter 3. INSTALLATION
�
� External dimensions
�
z Model C15T (Panel Mount type)
Unit: mm
59
60
2
44.8
48
48
rdy
man
ev1
ev2
ev3
ot1
ot2
para
mode
SDC15
pv
sp
Mounting bracket
(Accessory)
Terminal
screw M3
�
z Model C15S (Socket Mount type)
Terminal
screw
M3.5
2- M4
Mounting
hole
48
48
40
51
71
3.4
74.2
61.2
26.5
31
rdy
man
ev1
ev2
ev3
ot1
ot2
para
mode
SDC15
pv
sp
1
2
3
4
5
6
7
8
9
10
11
Socket
Stopper
Socket 81446391-001
(sold separately)
�
� Panel cutout dimensions
For panel mounting type, make the mounting holes according to the panel hole
making dimensions.
Unit: mm
0
45 +0.5
50 min.
0
45+0.5
30 min.
0
+0.5
(48xN -3)
0
+0.5
45
("N" shows the number of mounting units.)
Stand-alone mounting
Gang-mounting
Handling Precautions
• When three or more units are gang-mounted horizontally, the maximum
allowable ambient temperature is 40 °C.
• Provide a space of at least 50 mm or more above and below the controller.
• If dustproof or waterproof protection is required, mount the device
using the individual mounting method. If gangmounted, dustproof and
waterproof protection may not be maintained.
Chapter 3. INSTALLATION
�
� Mounting procedures
• The mounting must be horizontal within 10 degrees tilted in back side lowering
or within 10 degrees tilted in back side rising.
• In the case of panel mount type (C15T), the mounting panel should be used with
a thickness of less than 9 mm of firm board.
�
z Model C15T (Panel mount type)
Items to be prepared:
Phillips-head screwdriver
Plate thickness is
9 mm or less.
Screws for
mounting bracket
Mounting bracket
Panel
Panel hole
Main unit
Gasket (Accessory)
Hook
The above Figure shows the waterproof mounting using the gasket.
The gasket is not used for normal panel mounting.
(1) Insert this unit from the front of the panel.
(2) Fit the mounting bracket from the back of the panel.
(3) Push the mounting bracket against the panel until the hook of the mounting
bracket is firmly engaged with the groove of the main unit.
(4) Tighten the upper and lower screws of the mounting bracket.
For waterproof mounting:
The panel mounting type (C15T) can be waterproof-mounted.
To do so, attach the accessory gasket to the main unit before above step (1).
After that, mount the main unit with the gasket attached from above operation
step (1) in order.
Handling Precautions
• To fasten this controller onto the panel, tighten a mounting bracket
screws, and turn one more half turn when there is no play between the
bracket and panel. Excessively tightening the screws may deform the
controller case.
• If gangmounted, dustproof and waterproof protection may not be
maintained.
Chapter 3. INSTALLATION
�
z Model C15T (Using the hard cover for panel mount type)
For panel mounting type, it is possible to attach the hard cover to the front console.
Use of hard cover makes it possible to prevent the settings from being changed due
to accidental operation or to operate the unit in poor installation environment. The
display can be seen with the cover kept closed. When operating the key, raise the
cover and operate the key.
Items to be prepared:
Hard cover Part No. 81446442-001 (Optional unit)
Hard cover
Gasket
Main body
Gasket
Panel
Both gaskets must be used, one is supplied with the main unit and the other is
supplied with the hard cover. Both are the same gaskets.
(1) As shown in the Figure, mount the gasket, hard cover, and gasket on the main
unit in that order so that the hard cover is sandwiched by two gaskets.
(2) Insert this unit from the front of the panel.
(3) Fit the mounting bracket from the back of the panel.
(4) Push the mounting bracket against the panel until the hook of the mounting
bracket is firmly engaged with the groove of the main unit.
(5) Tighten the upper and lower screws of the mounting bracket.
Handling Precautions
• To fasten this controller onto the panel, tighten a mounting bracket
screws, and turn one more half turn when there is no play between the
bracket and panel. Excessively tightening the screws may deform the
controller case.
• It is possible to mount this unit without use of two gaskets if the
waterproof feature is not needed and only the prevention of improper
operation is aimed at.
• If gangmounted, dustproof and waterproof protection may not be
maintained.
Chapter 3. INSTALLATION
�
z Model C15T (Using the soft cover for panel mount type)
For panel mounting type, it is possible to attach the soft cover to the front console.
The key can be operated with the soft cover kept attached.
Additionally, when the soft cover is attached to the front console, this provides the
feature similar to the waterproof mounting using the gasket.
Items to be prepared:
Soft cover Part No. 81446443-001 (Optional unit)
Soft cover
Panel
Soft cover
Panel
Main unit
Main unit
The gasket supplied with the main unit is not used.
(1) Attach the soft cover so that it covers the console of the main unit.
(2) Insert the unit with the soft cover attached from the front of the panel.
(3) Fit the mounting bracket from the back of the panel.
(4) Push the mounting bracket against the panel until the hook of the mounting
bracket is firmly engaged with the groove of the main unit.
(5) Tighten the upper and lower screws of the mounting bracket.
Handling Precautions
• To fasten this controller onto the panel, tighten a mounting bracket
screws, and turn one more half turn when there is no play between the
bracket and panel. Excessively tightening the screws may deform the
controller case.
• If gangmounted, dustproof and waterproof protection may not be
maintained.
Chapter 3. INSTALLATION
�
z C15S (Socket mount type)
Items to be prepared:
Phillips-head screwdriver
DIN rail
Socket
Stopper
Stopper hole
Main unit
The above Figure shows the DIN rail mounting.
(1) Mount the socket inside the panel. (For screw tightening, mount the socket
directly.)
(2) Perform the wiring to the socket.
(3) Push this unit into the socket.
(4) Put the upper and lower socket stoppers in the stopper holes in the main unit,
and then insert them.
Handling Precautions
• For socket mount type, it is necessary that the wiring must be completed
before mounting this unit on the socket.
4 - 1
Wiring
WARNING
Do not use this device in an environment with conductive pollution, or with dry non-
conductive pollution which can become conductive due to condensation, etc.
Otherwise, problems such as tracking phenomena may damage parts, resulting in fire.
When wiring the power for this device, be sure to mount a shutoff switch for the main power
to this unit within reach of the operator.
In addition, when wiring the power for AC power models, install a time-lag (T) fuse (rated
current 0.2 A, rated voltage 250 V) as specified by IEC 127.
Otherwise, tracking phenomena or parts failure due to other factors may cause fire.
Before removing, mounting, or wiring this device, be sure to turn off the power to the device
and all connected devices. Failure to do so might cause electric shock.
Do not touch electrically charged parts such as the power terminals.
Doing so might cause electric shock.
CAUTION
Wire this device properly according to predetermined standards.
Also wire the device using specified power leads according to recognized installation methods.
Failure to do so might cause electric shock, fire or faulty operation.
Do not allow lead clippings, chips or water to enter the controller case.
Doing so might cause fire or faulty operation.
Firmly tighten the terminal screws at the torque listed in the specifications.
Insufficient tightening of terminal screws might cause electric shock or fire.
Do not use unused terminals on this device as relay terminals.
Doing so might cause electric shock, fire, or faulty operation.
We recommend attaching the terminal cover (sold separately) after wiring this device.
Failure to do so might cause electric shock, fire, or faulty operation.
Use the relays within the recommended service life.
Failure to do so might cause fire or faulty operation.
If there is a risk of a power surge caused by lightning, use a surge absorber (surge protector)
to prevent fire or device failure.
Do not make incorrect connections. If the cables are connected incorrectly, this might cause
the unit to malfunction.
The controller does not function for approximately 6 s after the power has been turned ON.
Great care should be taken when the relay output from the controller is used as interlock signals.
The part between the control output 1 and control output 2 is not isolated. When necessary,
use an appropriate isolator.
Do not connect multiple loader cables to multiple units from one personal computer. The
current coming from other circuits might cause the PV value indication error to occur.
Do not connect any terminating resistor to both ends of the communication path when
performing the RS-485 wiring. Doing so might cause the communication to fail.
Chapter 4. WIRING
�
� Terminal assignment label symbols
The following table shows the meanings of the symbols used for the terminal
assignment label attached to the side panel of this unit:
Symbol
Meaning
~
AC
DC
Caution, there is danger of electric shock
Caution
�
� Wiring precautions
• Before starting the wiring work, carefully check the label on the side panel of this
unit to understand the model No. and terminal No. to carry out the wiring properly.
• For panel mount type, use an appropriate crimp type terminal lug suitable for the
M3 screw to connect the terminals. The tightening torque of the terminal screw
must be 0.4 to 0.6 N·m.
• For socket mount type, use an appropriate crimp type terminal lug suitable for
the M3.5 screw to connect the terminals. The tightening torque of the terminal
screw must be 0.78 to 0.98 N·m.
• Pay special attention so that no crimp terminals are in contact with adjacent terminals.
• For the C15T (panel-mount type), to connect 2 crimp terminals
to the same terminal screw, bend the crimp terminals before use.
• For the C15T (panel-mount type), connect wires to terminals 1-6 and 13-18 from
the left (when viewing the terminal block).
A
B
A: 5.8mm max. B: 5.5 to 7.6 mm
Recommended crimp terminal: V1.25-MS3 (manufactured by
J.S.T. Mfg. Co., Ltd.)
• Keep the input/output signal cables 50 cm or more away from the drive power cable
and/or power cable. Additionally, do not pass the input/output signal cables and the
drive power cable and/or power cable together through the same conduit or duct.
• When connecting this unit and other measuring instrument in parallel,
carefully check the conditions necessary for other instrument before starting the
instrumentation.
• The digital input is so designed that it is non-voltage input. A contact for micro
current must be used.
• Pass the conductor, to which the heater current flows, through the current
transformer. Additionally, carefully check that the heater current does not
exceed the allowable current level stated in the specification. If the heater current
exceeds the allowable current level, this might cause damage to this unit.
• The input of the current transformer cannot be used for the phase angle control.
• For panel mounting type (C15T), an optional terminal cover is available to
prevent electric shock. (Model No.: 81446898-001)
Concave part of
main unit case
Terminal cover
Chapter 4. WIRING
• The part between the control output 1 and control output 2 is not isolated. When
necessary, use an appropriate isolator.
• Make sure that devices and equipment connected to this device have reinforced
insulation suitable for the maximum operating voltage of this device's power
supply and input/output ports.
• This unit is so designed that it does not start functioning for up to 6 s after the
power has been turned ON in order to ensure stable operation. After that, the
unit then enters the operation mode. However, to satisfy the specified accuracy, it
is necessary to warm up the unit for at least 30 min.
IMPORTANT
Terminating resistor
• Do not connect any terminating resistor to both ends of the RS-485
communication path. Doing so might cause the communication to fail.
�
z Wiring of C15T
1
2
3
13
14
15
1
2
1
2
3
1
2
3
1
3
1
2
4
5
6
13
14
15
16
17
18
7
8
9
10
11
12
1
2
3
4
5
6
4
5
6
4
5
6
7
8
9
10
7
8
9
10
16
17
18
16
17
18
1
2
+
+
−
−
+−
+
1
2
+−
+−
+
1
2
+−
+
+
+
−
mA
V
CT1
CT2
11
12
DA
DB
SG
1
2
1
2
1
2
3
C
B
A
11
12
2
Control outputs
Current transformer inputs
Event outputs
Relay
Voltage pulse
Voltage pulse
Current
Current
Current
Current
Voltage
Voltage pulse
Voltage pulse
Thermocouple
RTD
Current
Relay
Relay
(independent
contact)
AC power supply
100 to 240 V AC
Digital
inputs
RS-485
Communication
DC power supply
24 V AC/24 to 48 V DC
(nonpolar)
Power supply
DI/COM
PV inputs
Chapter 4. WIRING
�
z Wiring of C15S
1
11
2
3
4
5
6
7
8
9
10
10
11
6
7
8
9
6
7
8
9
2
1
3
1
2
3
2
1
3
2
1
3
2
1
+
−
+
+
mA
V
C
B
A
5
4
5
4
5
4
−
+
−
+
5
4
6
2
3
1
10
9
11
7
8
10
11
Power supply
AC power supply
100 to 240 V AC
Event outputs
Relay
Relay
(independent
contact)
PV inputs
Current
Voltage
RTD
Thermocouple
Control outputs
Relay
Voltage pulse
Current
Socket terminal No.
DC power supply
24 V AC/24 to 48 V DC
(nonpolar)
�
z Recommended crimp type terminal lugs
For C15T, use an appropriate crimp type terminal lug suitable for the M3 screw.
For C15S socket mounting type, use an appropriate crimp type terminal lug suitable
for the M3.5 screw.
A
B or
less
B or
less
C
Mounting method
Applicable
screw
Terminal dimensions (mm) Applicable electric
wire size
J.S.T. Mfg. Co., Ltd
Model No. (Reference)
A
B
C
C15T
panel mounting type
M3
6.1
5.8
5.5 to 7.6
0.3 to 1.2 mm2
AWG22 to 16
V1.25 - MS3 (round terminal lug)
V1.25 B3A (Y terminal lug)
C15S
socket mounting type
M3.5
7.4
6.6
6.3
0.3 to 1.2 mm2
AWG22 to 16
V1.25 - M3 (round terminal lug)
V1.25 YS3A (Y terminal lug)
Handling Precautions
• When installing this unit in a place where the vibration or impact is
large, always use an appropriate round crimp terminal so that it is not
disengaged from the connection terminal.
• Pay special attention so that no crimp terminals are in contact with
adjacent terminals.
Chapter 4. WIRING
�
� Connection of open collector output to digital input
16
17
18
5 V
This unit
�
� Connection of communication (RS-485) cable
�
z 3-wire system
16
17
18
16
Master station
DA
DA
DB
DB
SG
SG
SG
FG
+
-
This unit (slave station)
This unit (slave station)
Shield
Shield
17
18
IMPORTANT
Terminating resistor
• Do not connect any terminating resistor to both ends of the
communication path. Doing so might cause the communication to fail.
• Even though any units requiring the terminating resistor exist in the
communication path, do not connect any terminating resistor.
Handling Precautions
• Do not connect DA and DB. Doing so might cause damage to this unit.
• Ground the shield line to one point on one side of the cable.
• Be sure to connect SG terminals each other.
Failure to do so might cause unstable communications.
Chapter 4. WIRING
�
z 5-wire system
16
17
18
16
Master station
DA
DA
DB
DB
SG
SG
SG
FG
+
−
+
−
This unit (slave station)
This unit (slave station)
Shield
Shield
17
18
IMPORTANT
Terminating resistor
• Do not connect any terminating resistor to both ends of the
communication path. Doing so might cause the communication to fail.
• Even though any units requiring the terminating resistor exist in the
communication path, do not connect any terminating resistor.
Handling Precautions
• Do not connect DA and DB. Doing so might cause damage to this unit.
• Ground the shield line to one point on one side of the cable.
• Be sure to connect SG terminals each other.
Failure to do so might cause unstable communications.
Chapter 4. WIRING
�
� Connection with solid state relay (SSR)
To drive the SSR, a model having voltage pulse outputs (V0, VC or VV) must be
used.
Generally, the SSR is classified into two groups, constant current type and resistor
type.
�
z Constant current type
The two conditions listed below must be satisfied.
• Input current (maximum): Check that the input current is within the maximum
allowable current or less, then the parallel connection
can be made.
• Operating voltage range:
Check that the voltage between the terminals of the
voltage pulse output is within the specified range.
1. Azbil Corporation's PGM10N/PGM10F series
This example shows the calculation for the connection of the SDC15 and the
PGM10N015.
(Note: For connection with other model number, check the specifications of each
model.)
• Input current:
Since the input current is 10 mA or less, up to two
units (10mA × 2 = 20 mA < 24 mA [maximum
allowable current]) can be connected in parallel.
• Operating voltage range (input): The rating voltage is 3.5 to 30 V DC. Therefore,
the voltage between the terminals is within the
range.
Voltage between terminals (two PGM10N units)
= Open voltage - internal resistance × total drive current
= 19 V DC ±15 % - 82 Ω ±0.5 %
× 20 mA
=15 to 20 V
Connection diagram
This unit
+
–
+
–
PGM10N/PGM10F
+
–
PGM10N/PGM10F
Number of connectable units
SSR to be used
Connection
V0/VC model
VV model
PGM10N
Parallel connection
Up to 2 units
Up to 4 units*
PGM10F
Parallel connection
Up to 2 units
Up to 4 units*
* 2 units for each output
Chapter 4. WIRING
2. Omron's G3PA, G3PB, G3NA
• Input current:
Since the input current is 7 mA or less, up to three
units (7 mA × 3 = 21 mA < 24 mA [maximum
allowable current]) can be connected in parallel.
• Operating voltage range (input): The rating voltage is 5 to 24 V DC or 12 to
24 V DC. Therefore, the voltage between the
terminals is within the range.
Voltage between terminals (three G3PA units)
= Open voltage - internal resistance × total drive current
= 19 V DC ±15 % - 82 Ω ±0.5 %
× 21 mA
=14 to 20 V
Connection diagram
This unit
+
+
–
G3PA
+
G3PA
+
G3PA
–
–
–
Number of connectable units
SSR to be used
Connection
V0/VC model
VV model
Omron G3PA
Parallel connection
Up to 3 units
Up to 6 units*
Omron G3PB
Parallel connection
Up to 3 units
Up to 6 units*
Omron G3NA
Parallel connection
Up to 3 units
Up to 6 units*
* 3 units for each output
Chapter 4. WIRING
�
z Resistor type (Azbil Corporation's PGM_ _ 2A1, etc.)
When necessary, an appropriate external resistor is connected in series so that the
voltage between the input terminals of the SSR you are using is within the specified
range.
(Example) Connection of two Azbil Corporation PGM units
Connection diagram
This unit
V
R0
PGM_ _2A1
R2
Vf
3
4
PGM_ _2A1
R2
Vf
3
4
External resistor R1
+
-
V: 19 V ± 15%
R0: 82 Ω ± 0.5%
R1: 680 Ω
R2: 260 Ω
Vf: 1.1 V
Voltage between terminals of PGM = (V - 2 × Vf) / (R0 + R1+ R2 + R2) × R2 + Vf
=4.5 V
Input voltage range of PGM: Since the input voltage range is 3 to 6 V, the
operation is possible.
External resistors
SSR to be used
Number of
units to be
connected
Connection
External
resistor
Notes
PGM_ _2A1
1
–
1kΩ (serial connection)
Rating is 1/2W or more.
2
Serial connection
680Ω (serial connection)
Rating is 1/2W or more.
3
Serial connection
330Ω (serial connection)
Rating is 1/2W or more.
4
Serial connection
None
Number of connectable units
SSR to be used
Connection
V0/VC model
VV model
PGM_ _2A1
Serial connection
Up to 4 units
Up to 8 units*
* 4 units for each output
Chapter 4. WIRING
�
� Connection with current-input type controllers
When the power to this controller is turned off, the current input circuit is cut off.
If multiple current-input type SDCs are connected in series and you want to turn
them on/off individually, convert them to voltage input by adding resistors (No.
81401325, sold separately) to the circuit.
rdy
man
ev1
ev2
ev3
ot1
ot2
para
mode
pv
sp
1 to 5 V
250 Ω
+
−
+
4 to 20 mA
−
−
rdy
man
ev1
ev2
ev3
ot1
ot2
para
mode
pv
sp
1 to 5 V
250 Ω
+
This unit
This unit
Current output device
�
� Noise preventive measures
The power is taken from the single-phase instrumental power supply to consider
noise preventive measures.
If the noise from the power supply is large, an appropriate insulation transformer is
added to the power supply and an appropriate line filter is used.
(Azbil Corporation's line filter model No.: 81442557-001)
If the noise has fast rising edge, an appropriate CR filter is used.
(Azbil Corporation's CR filter model No.: 81446365-001)
Handling Precautions
After the noise preventive measures have been taken, do not bundle the
primary and secondary sides of the insulation transformer together or put
them in the same conduit or duct.
Chapter 4. WIRING
Contact the thermocouple wires to the terminals in case of a thermocouple input. When a thermocouple is
connected to terminals, or wiring distance is long, connect the wire via a shielded compensating lead wire.
• For input/output other than thermocouples, use a JCS 4364 instrument cable or
equivalent (generally called twisted shielded cable for instrumentation use).
Recommended twisted shielded cables.
Fujikura Ltd.
2 conductors
IPEV-S-0.9 mm2 × 1P
3 conductors
ITEV-S-0.9 mm2 × 1T
Hitachi Metals, Ltd. 2 conductors
KPEV-S-0.9 mm2 × 1P
3 conductors
KTEV-S-0.9 mm2 × 1T
• A shielded multiconductor microphone cord (MVVS) may be used, if
electromagnetic induction noise are comparatively low.
4 - 2
Recommended Cables
DETAILED DESCRIPTION OF EACH FUNCTION
5 - 1
PV Input
The following shows the functional block diagram of the PV input:
PV input is thermocouple.
PV input range type
(Setting: Setup C0 1)
Cold junction compensation
(Setting: Setup C03)
Temperature unit
(Setting: Setup C02)
PV input is RTD.
PV input range type
(Setting: Setup C0 1)
Temperature unit
(Setting: Setup C02)
PV high limit/low limit alarm
PV ratio (Setting: Parameter rA)
PV bias (Setting: Parameter bI )
PV flter (Setting: Parameter FL)
PV high limit/low limit
PV hold
(Setting: DI Assignment Operation type dI 1. 1 to dI 3. 1)
PV before ratio, bias, and flter
PV
PV input is DC voltage/DC current.
PV input range type
(Setting: Setup C0 1)
PV square root extraction
(Setting: Setup C09)
Decimal point position and scaling
(Setting: Setup C04 to C06)
�
� PV input range type
When the PV input type is T (thermocouple) or R (RTD), the sensor type and
temperature range can be selected.
When the PV input range type is L (DC voltage/DC current), the signal type can be
selected.
Item (Bank)
Display
Contents
Initial value
User level
PV input range type
(Setup bank)
The contents may vary depending on
the PV input range type.
For details, refer to the PV input range
table.
The initial value may
vary depending on
the PV input range
type as shown below.
"T":
1
"R": 41
"L": 88
Simple, Standard,
High function
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
z PV input range table (Thermocouple)
�
z PV input range table (RTD)
C0 1
set value
Sensor
type
Range
(Celsius)
Range
(Fahrenheit)
C04
display
C04
range
C04 initial value
when C0 1 settings
C0 1
set value
Sensor
type
Range
(Celsius)
Range
(Fahrenheit)
C04
display
C04
range
C04 initial value
when C0 1 settings
1
K
-200 to +1200˚C
-300 to + 2200˚F
----
(Not setting)
(No decimal point)
41
Pt100
-200.0 to +500.0˚C
-300 to + 900˚F
----
(Not setting)
(No decimal point)
2
K
0 to 1200˚C
0 to 2200˚F
----
(Not setting)
(No decimal point)
42
JPt100
-200.0 to +500.0˚C
-300 to + 900˚F
----
(Not setting)
(No decimal point)
3
K
0.0 to 800.0˚C
0 to 1500˚F
0 to 1
0
43
Pt100
-200.0 to +200.0˚C
-300 to + 400˚F
----
(Not setting)
(No decimal point)
4
K
0.0 to 600.0˚C
0 to 1100˚F
0 to 1
0
44
JPt100
-200.0 to +200.0˚C
-300 to + 400˚F
----
(Not setting)
(No decimal point)
5
K
0.0 to 400.0˚C
0 to 700˚F
0 to 1
0
45
Pt100
-100.0 to +300.0˚C
-150 to + 500˚F
----
(Not setting)
(No decimal point)
6
K
-200.0 to +400.0˚C
-300 to + 700˚F
0 to 1
0
46
JPt100
-100.0 to +300.0˚C
-150 to + 500˚F
----
(Not setting)
(No decimal point)
9
J
0.0 to 800.0˚C
0 to 1500˚F
0 to 1
0
51
Pt100
-50.0 to +200.0˚C
-50 to + 400˚F
0 to 1
1
10
J
0.0 to 600.0˚C
0 to 1100˚F
0 to 1
0
52
JPt100
-50.0 to +200.0˚C
-50 to + 400˚F
0 to 1
1
11
J
-200.0 to +400.0˚C
-300 to + 700˚F
0 to 1
0
53
Pt100
-50.0 to +100.0˚C
-50 to + 200˚F
0 to 1
1
13
E
0.0 to 600.0˚C
0 to 1100˚F
0 to 1
0
54
JPt100
-50.0 to +100.0˚C
-50 to + 200˚F
0 to 1
1
14
T
-200.0 to +400.0˚C
-300 to + 700˚F
0 to 1
0
63
Pt100
0.0 to 200.0˚C
0 to + 400˚F
0 to 1
1
15
R
0 to 1600˚C
0 to 3000˚F
----
(Not setting)
(No decimal point)
64
JPt100
0.0 to 200.0˚C
0 to + 400˚F
0 to 1
1
16
S
0 to 1600˚C
0 to 3000˚F
----
(Not setting)
(No decimal point)
67
Pt100
0.0 to 500.0˚C
0 to + 900˚F
----
(Not setting)
(No decimal point)
17
B
0 to 1800˚C
0 to 3300˚F
----
(Not setting)
(No decimal point)
68
JPt100
0.0 to 500.0˚C
0 to + 900˚F
----
(Not setting)
(No decimal point)
18
N
0 to 1300˚C
0 to 2300˚F
----
(Not setting)
(No decimal point)
19
PL II
0 to 1300˚C
0 to 2300˚F
----
(Not setting)
(No decimal point)
20
WRe5-26
0 to 1400˚C
0 to 2400˚F
----
(Not setting)
(No decimal point)
21
WRe5-26
0 to 2300˚C
0 to 4200˚F
----
(Not setting)
(No decimal point)
23
PR40-20
0 to 1900˚C
0 to 3400˚F
----
(Not setting)
(No decimal point)
24
DIN U
-200.0 to +400.0˚C
-300 to + 700˚F
0 to 1
0
25
DIN L
-100.0 to +800.0˚C
-150 to + 1500˚F
0 to 1
0
*1. Accuracy of sensor type B (No.17): ±5 %FS below 260 ˚C, ±1 %FS from 260 to 800 ˚C, not specified below 20 ˚C
However, if ROM version 1 in the instrument information bank (i d02) is 2.04 or earlier, the low limit for display is -180 ˚C.
Accuracy of sensor type PR40-20 (No.23): not specified below 300 ˚C, ±5 %FS from 300 to 800 ˚C, ±2 %FS from 800 to
1900 ˚C
However, if ROM version 1 in the instrument information bank (i d02) is 2.26 or earlier, No.23 cannot be selected.
*2. PL II thermocouple is a range, which has been added to the units manufactured from July, 2003.
*3. The PV range display for thermocouple with a decimal point is available for ROM version 2.26 and later.
�
z PV input range table (DC voltage/DC current)
C0 1
set value
Sensor type
Range
C04
display
C04
range
C04 initial value
when C0 1 settings
84
0 to 1 V
• Scaling range is -1999 to +9999.
• When C0 1 is changed, the
range default defaults to 0 to
1000.
0 to 3
No change
86
1 to 5 V
0 to 3
No change
87
0 to 5 V
0 to 3
No change
88
0 to 10 V
0 to 3
No change
89
0 to 20 mA
0 to 3
No change
90
4 to 20 mA
0 to 3
No change
Handling Precautions
• When the C0 1 PV input range number is set, the decimal point position
and range are initially set automatically as shown in the tables. For details
on the decimal point, refer to the description of setup C04 (decimal point
position) on page 5-4.
• Make sure to set the correct number in setup display C0 1, according to
the type and range of the sensor used. If the setting is wrong, problems
such as large temperature errors in the output may occur.
• For details about the accuracy of each PV range type:
Chapter 13. SPECIFICATIONS (p. 13-1)
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� Temperature unit
When the PV input type is T (thermocouple) or R (RTD), the temperature unit can
be selected.
Item (Bank)
Display
Contents
Initial value
User level
Temperature unit
(Setup bank)
0: Celsius (˚C)
1: Fahrenheit (˚F).
0
Simple, Standard,
High function
• When the PV input type is T (thermocouple) or R (RTD), the display and setting
can be made.
�
� Cold junction compensation (T/C)
When the PV input type is T (thermocouple), any of the following can be selected:
• The cold junction compensation (T/C) is performed inside this unit.
• The cold junction compensation (T/C) is not performed inside this unit since
an external cold junction compensation unit, such as ice bath is used.
• When the PV input type is T (thermocouple), the display and setting can be
made.
Item (Bank)
Display
Contents
Initial value
User level
Cold junction
compensation (T/C)
(Setup bank)
0: Cold junction compensation (T/C) is
performed (internal).
1: Cold junction compensation (T/C) is
not performed (external).
0
High function
�
� PV square root extraction dropout
When the PV input type is L (DC voltage/DC current), a dropout value can be
set so that the result of the PV square root extraction used to convert the pressure
(differential pressure) into the flow becomes "0".
• When the PV input type is L (DC voltage/DC current), the display and setting
can be made.
Item (Bank)
Display
Contents
Initial value
User level
PV square root extraction
dropout
(Setup bank)
0.0 %: Square root extraction is not
performed.
0.1 to 100.0 %
0.0 %
High function
• Details of PV square root extraction
The calculation input in % and the calculation result in % are expressed as PVin
and PVout, respectively.
When the PV input is the PV square root extraction dropout set value or more
and less than 100.0 %, the control formula becomes as shown below.
PVout = √PVin ÷ 100 × 100
When the PV input is larger than 0.0% and smaller than the PV square root
extraction dropout set value, PVout = 0.0 %.
When the PV input is 0.0 % or less or 100.0 % or more, the square root extraction
is not performed. Therefore, PVout = PVin.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Output after PV square root extraction (PVout)
100 %FS
PVin
Dropout value (variable change from 0.1 to 100.0 %)
0
100 %FS
0
Y = Xin/100 ×100
�
� Decimal point position
If the PV input type in the model number is L (DC voltage/current), or if one of the
thermocouple or RTD ranges is selected in C0 1, the decimal point position can be
set.
Item (Bank)
Display
Contents
Initial value
User level
Decimal point position
(Setup bank)
0: No decimal point
1: 1 digit below decimal point
2: 2 digits below decimal point
3: 3 digits below decimal point
0
Simple, Standard,
High function
Handling Precautions
• As this setting is changed, the decimal point position of the parameters
related to the decimal point position of the PV input is also changed.
Th e decimal point position of the following settings is changed:
SP setting
SP low limit/high limit setting
SP up ramp/down ramp setting
Event setting and continuous output setting related to PV
Event setting and continuous output setting related to SP
Event setting and continuous output setting related to deviation
(absolute deviation)
• The PV range display for thermocouple is available for ROM version 2.26
and later.
Note
• For the display conditions, setting range and initial value of range numbers
(C0 1):
PV input range tables (p. 5-2)
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� PV input range low limit/high limit
When the PV input type is L (DC voltage/DC current), the scaling of the PV input
can be set.
Item (Bank)
Display
Contents
Initial value
User level
PV range low limit
(Setup bank)
When the PV input type is "L", the
following contents apply:
-1999 to +9999 (no decimal point)
-199.9 to +999.9 (1 digit after decimal point)
-19.99 to +99.99 (2 digits after decimal
point)
-1.999 to +9.999 (3 digits after decimal
point)
When the PV input type is "T" or "R", the
range low limit and high limit values
selected using the PV input range type
are used.
When the PV input
type is "L", the initial
value is "0".
Simple, Standard,
High function
PV range high limit
(Setup bank)
When the PV input
type is "L", the initial
value is "1000".
• When the PV input type is T (thermocouple) or R (RTD), the setting item can be
displayed, but the setting cannot be made.
• When the PV input type is L (DC voltage/DC current), the display and setting
can be made. The following describes the relationship between the PV input and
PV when setting up the range low limit and high limit.
PV
-10 0
100110
Input (%)
Low limit
Low limit < High limit
Low limit > High limit
High limit
PV
-10 0
100110
Input (%)
Low limit
High limit
�
� PV ratio and PV bias
The PV ratio and PV bias can be set to compensate the PV.
Item (Bank)
Display
Contents
Initial value
User level
PV ratio
(Parameter bank)
0.001 to 9.999
1.000
Standard,
High function
PV bias
(Parameter bank)
-1999 to +9999 U
0 U
Simple, Standard,
High function
• Details of PV ratio and PV bias controls
Assuming that the control input is PVin, control result is PVout, PV ratio is RA,
and PV bias is BI, the following control formula is obtained:
PVout = (PVin × RA) + BI
�
� PV low limit alarm threshold
Item (Bank)
Display
Contents
Initial value
User level
PV input failure (under
range) type
(Setup bank)
0: -10 %FS
1: -5 mV (This setting is applicable if C0 1
(PV input range type) is set for sensor type
B (No. 17) or PR40-20 (No. 23))
0
Simple, Standard,
High function
If ROM version 1 in the instrument information bank (i d02) is 2.26 or earlier, this
item cannot be displayed.
This setting is applicable if C0 1 (PV input range type) is set for sensor type B (No.
17) or PR40-20 (No. 23).
� PV low limit/high limit and PV low limit/high limit alarms (p. 5-6)
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� PV filter
This PV filter is a primary delay filter to be used if the PV repeatedly fluctuates
rapidly and the control cannot be performed or if the PV fluctuates finely due to
influence of noise, etc.
As a larger value is set, it becomes difficult to change the PV used for the control of
this unit.
Normally, the PV filter is used with an initial value of "0.0".
Item (Bank)
Display
Contents
Initial value
User level
PV filter
(Parameter bank)
0.0: No filter
0.1 to 120.0 s
0.0 s
Simple, Standard,
High function
OUT = OUT-1 + (IN – OUT-1)/(T/Ts + 1)
IN:
Input to PV filter
OUT:
Control output of current filter
OUT-1: Control output of previous filter
T:
Filter set value (s)
Ts:
Sampling cycle time (0.5 s)
�
� PV hold
It is possible to set the PV to a fixed value using the PV hold, PV Max. hold, and PV
Min. hold of the DI (digital input) functions.
PV hold: PV is set to a fixed value and it is not updated.
PV Max. hold:
PV maximum value is held.
The PV value is updated only when the new PV value is larger
than the currently held value.
PV Min. hold:
PV minimum value is held.
The PV value is updated only when the new PV value is
smaller than the currently held value.
When using the PV hold, PV Max. hold, or PV Min. hold, the PV indication on the
upper display is flashing.
�
� PV low limit/high limit and PV low limit/high limit alarms
PV low limit and PV high limit are provided for each PV input range type.
In principle, -10 %FS of each range becomes the PV low limit while +110 %FS
becomes the PV high limit.
p. 10-2
The PV is limited so that it is within a range between the PV low limit and PV high
limit.
If the PV before activation of the PV ratio, PV bias, and PV filter is larger than the
PV high limit, PV high limit alarm (AL0 1) occurs. On the contrary, if this PV is
smaller than the PV low limit, the PV low limit alarm (AL02) occurs.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
5 - 2
Mode
It is possible to set the AUTO/MANUAL mode selection, RUN/READY mode selection, AT (Auto Tuning) stop/
start selection, release all DO (digital output) latches, and OFF/ON selection of communication DI (digital input) 1.
�
� AUTO/MANUAL mode
The AUTO/MANUAL mode selection can be set.
Item (Bank)
Display
Contents
Initial value
User level
AUTO/MANUAL
mode selection
(Mode bank)
AUto: AUTO mode [Communication
value is "0".]
MAn: MANUAL mode [Communication
value is "1".]
AUto
Simple, Standard,
High function
• When the AUTO/MANUAL mode is changed, the display is automatically
returned to the operation display.
• If the operation type of internal contacts 1 to 3 is set at “AUTO/MANUAL”, [A--
M: AUTO/MANUAL mode selection] can be displayed, but the setting cannot be
made.
• When [CtrL: Control method] is set at "0" (ON/OFF control), [A--M: AUTO/
MANUAL mode selection] cannot be displayed and set.
• When [bit 0: AUTO/MANUAL display] of [C73: MODE display setup] is set at "0"
(no display), [A--M: AUTO/MANUAL mode selection] cannot be displayed and
set.
�
� RUN/READY mode
The RUN/READY mode selection can be set.
Item (Bank)
Display
Contents
Initial value
User level
RUN/READY
mode selection
(Mode bank)
rUn: RUN mode [Communication value
is "0".]
rdy: READY mode [Communication
value is "1".]
rUn
Simple, Standard,
High function
• If the operation type of internal contacts 1 to 3 is set at “RUN/READY”, [r--r:
RUN/READY] can be displayed, but the setting cannot be made.
• When [bit 1: RUN/READY display] of [C73: MODE display setup] is set at "0" (no
display), [r--r: RUN/READY] cannot be displayed and set.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� AT (Auto Tuning) stop/start
The AT stop/start selection can be set.
Item (Bank)
Display
Contents
Initial value
User level
AT stop/start selection
(Mode bank)
At.OF: AT stop [Communication value
is "0".]
At.ON: AT start [Communication value
is "1".]
At.OF
Simple, Standard,
High function
• The AT is stopped in the MANUAL or READY mode.
• If the PV high limit alarm (AL0 1) or PV low limit alarm (AL02) occurs, the AT is
stopped.
• If the operation type of internal contacts 1 to 3 is set at "AT stop/start", [At: AT
stop/start selection] can be displayed, but the setting cannot be made.
• When [CtrL: Control method] is set at "0" (ON/OFF control), [At: AT stop/start
selection] cannot be displayed and set.
• When [bit 3: AT stop/start display] of [C73: MODE display setup] is set at "0" (no
display), [At: AT stop/start selection] cannot be displayed and set.
AT (p. 5-18) and AT function (p. 5-21)
�
� Release all DO (digital output) latches
Release all DO (digital output) latches can be set.
Item (Bank)
Display
Contents
Initial value
User level
Release all digital output
(DO) latches
(Mode bank)
Lt.ON: Latch is continued.
[Communication value is "0".]
Lt.oF: Latch is released.
[Communication value is "1".])
Lt.ON
Simple, Standard,
High function
• If the operation type of internal contacts 1 to 3 is set at "Release all DO latches",
[dO.Lt: Release all DO latches] can be displayed, but the setting cannot be made.
• When [bit 4: Release all DO latches display] of [C73: MODE display setup] is set
at "0" (no display), [dO.Lt: Release all DO latches] cannot be displayed and set.
�
� Communication DI (digital input) 1
Communication DI (digital input) 1 can be set.
Item (Bank)
Display
Contents
Initial value
User level
Communication digital
input 1 (communication
DI 1)
(Mode bank)
DI.OF: Communication DI1. OFF
[Communication value is "0".]
DI.ON: Communication DI1. ON
[Communication value is "1".]
DI.OF
Simple, Standard,
High function
• Four communication DIs, DI1 to DI4, are provided. However, only
communication DI 1 can be set using the key operation.
• The function (operation) with communication DI 1 can be set using the DI
Assignment.
• When [bit 5: Communication DI 1 display] of [C73: MODE display setup] is set at
"0" (no display), [C.DI 1: Communication DI 1] cannot be displayed and set.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
The following shows the functional block diagram of the control (ON/OFF control, PID control, RationaLOOP
control, and Heat/Cool control, etc.):
MV1 output ON
MV1 output OFF
MV1 output ON or output OFF
ON/OFF control
Control method: ON/OFF control
(Setting: Parameter CtrL
must be set at "0".)
ON/OFF control
(Setting: Parameter dI FF, OFFS)
Branching according to
output at READY
(Setting: Setup C 1 7)
Branching according to
output operation at PV alarm
(Setting: Setup C 15)
Branching according to
RUN/READY mode selection
READY mode
C 1 7 > 0.0 %
C 1 7 ≤ 0.0 %
MV1 output ON
MV1 output OFF
Branching according to
output at PV alarm
(Setting: Setup C 16)
C 16 > 0.0 %
C 16 ≤ 0.0 %
PV is correct or
C 15 = 0:
PV is faulty (AL01/02 occurs)
and C 15 = 1:
RUN mode
5 - 3
Control
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
MV1 = MV
Fixed PID
Control method: Fixed PID
(Setting: Parameter CtrL
must be set at "1".)
ST
Control method: ST (Self-tuning)
(Setting: Parameter CtrL
must be set at "2".)
Adjustment according to
step response/hunting
(Setting: Extended tuning
St.SA, St.Sb, St.Hb, St.Ud)
ST is not run in the following cases:
• Heat/Cool control is used.
• Just-FiTTER is used.
READY mode
AUTO mode
MANUAL mode
RUN mode
SP lag overshoot suppression
(Setting: Extended tuning SP.LG)
RationaLOOP high precision
control logic
(Setting: Extended tuning Ctr.A)
Just-FiTTER overshoot suppression
(Setting: Extended tuning
JF.Ov, JF.bd)
Bumpless transfer/Preset selection
(Setting: Setup C 19, C20)
Branching according to
AUTO/MANUAL mode
Branching according to
RUN/READY mode
MV
MV1 = MV
Branching according to
output operation at PV alarm
(Setting: Setup C 15, C 16)
PID control
(Setting: PI D P- 1, I - 1, d- 1,
rE- 1,OL- 1, OH- 1, P- 1C,
I - 1C, d- 1C,OL. 1C, Oh. 1C)
Output at PV alarm
(Setting: Setup C 16)
Branching according to
Heat/Cool control
(Setting: Setup C26)
C26 = 0
C26 = 1
Branching according to
Heat/Cool control
(Setting: Setup C26)
MV1 = Heat MV
MV2 = Cool MV
MV1 = Heat MV
MV2 = Cool MV
Output at READY
(Setting: Setup C17, C18)
Heat/Cool control
(Setting: Setup C28, C29)
Output at READY
(Setting: Setup C 17)
PV is correct or
C 15 = 0
C26 = 0
C26 = 1
PV is faulty and C 15 = 1
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� Control method
A desired control method can be selected from three kinds of control methods.
Item (Bank)
Display
Contents
Initial value
User level
Control method
(Parameter bank)
0: ON/OFF control
1: Fixed PID
2: ST (Self-tuning)
0 or 1
Simple, Standard,
High function
• When the control output type is relay (R0), the initial value becomes "0". The
initial value is "1" in other cases.
• "Fixed" of [1: Fixed PID] means that the PID constant is not changed automatically
since the ST is not run. However, the AT can be run even in the fixed PID control.
• When using the Heat/Cool control (C26=1) or when using the Just-FiTTER
control (JF.ov > 0), the ST is not run even though [2: ST] is set.
• The following Table shows valid and invalid functions related to [1: Fixed PID]
and [2: ST], as well as other related parameters:
Classification
of Heat/Cool
control
Classification of
RationaLOOP
Classification
of control
action
RationaLOOP
function
AT
ST
Just-FiTTER
Normal control Normal PID
P control
×
*
×
×
PI control
×
*
×
PD control
×
*
×
×
PID control
×
RationaLOOP
P control
×
*
×
×
PI control
×
*
×
PD control
×
*
×
×
PID control
Heat/Cool
control
Normal PID
P control
×
*
×
×
PI control
×
*
×
PD control
×
*
×
×
PID control
×
×
RationaLOOP
P control
×
*
×
×
PI control
×
*
×
PD control
×
*
×
×
PID control
×
Related settings
Control
algorithm
AT type
ST step
execution
resolution band
Just-FiTTER
assistance
coefficient
MV low limit
at AT
ST step settling
band
Just-FiTTER
settling band
MV high limit
at AT
ST hunting
AT Proportional
band adjust
ST step ramp
change
AT Integral time
adjust
AT Derivative
time adjust
* Adjustment result becomes the PID control.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� Control action and Heat/Cool control
The control action (direct/reverse) and Heat/Cool control (enabled/disabled) can
be selected.
Item (Bank)
Display
Contents
Initial value
User level
Control action (direct/
reverse)
(Setup bank)
0: Heat control (Reverse)
1: Cool control (Direct)
0
Simple, Standard,
High function
Heat/Cool control
(Setup bank)
0: Disabled.
1: Enabled.
0
Simple, Standard,
High function
• When the control method is other than the ON/OFF control (CtrL ≠ 0), [Heat/
Cool control: C26] can be displayed and set.
• When the Heat/Cool control is set disabled (C26 = 0), [Control action: C14] can
be displayed and set.
• When the Heat/Cool control is set enabled (C26 = 1), the control action is
changed to the reverse action (C14 = 0), the preset MANUAL value (C20) is
changed to "50.0", and the initial output of PID control (C22) is changed to
"50.0".
• The reverse action (heat control) is a control that decreases (or turns OFF) the
manipulated variable (MV) as the PV increases.
The direct action (cool control) is a control that increases (or turns ON) the
manipulated variable (MV) as the PV increases.
�
� Special control outputs
The control output at PV alarm and control output at READY can be set.
Item (Bank)
Display
Contents
Initial value
User level
Output operation at PV alarm
(Setup bank)
0: Control calculation is continued.
1: Output at PV alarm is output.
0
High function
Output at PV alarm
(Setup bank)
-10.0 to +110.0 %
0.0 %
High function
Output at READY (Heat)
(Setup bank)
-10.0 to +110.0 %
0.0 %
Standard, High
function
Output at READY (Cool)
(Setup bank)
-10.0 to +110.0 %
0.0 %
Standard, High
function
• When the control method is other than the ON/OFF control (CtrL ≠ 0) and the
Heat/Cool control is set enabled (C26 = 1), [Output at READY (cool): C18] can be
displayed and set.
• The PV alarm status means that AL0 1, 02, or 03 occurs.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� MANUAL mode change
The control output when the AUTO mode is changed to the MANUAL mode can
be set.
Item (Bank)
Display
Contents
Initial value
User level
Output operation at
changing Auto/Manual
(Setup bank)
0: Bumpless transfer
1: Preset
0
Standard, High
function
Preset MANUAL value
(Setup bank)
-10.0 to +110.0 %
0.0 or 50.0 %
Standard, High
function
• When [Output operation at changing Auto/Manual: C 19] is set at [0: Bumpless
transfer], the manipulated variable (MV) when the AUTO mode is changed to
the MANUAL mode is retained. When set at [1: Preset], the manipulated variable
(MV) is set to [Preset MANUAL value: C20] when the AUTO mode is changed to
the MANUAL mode.
• When the control method is other than ON/OFF control (CtrL ≠ 0), [Output
operation at changing Auto/Manual: C 19] and [Preset MANUAL value: C20] can
be displayed and set.
• When the Heat/Cool control is not used (C26 = 0), the initial value of [Preset
MANUAL value: C20] is [0.0]. On the contrary, when the Heat/Cool control is
used (C26 =1), this initial value becomes [50.0].
Handling Precautions
When the unit is in the MANUAL mode if the power is turned ON, the set
value of C20 becomes the manipulated variable (MV).
�
� ON/OFF control
The ON/OFF control related items can be set.
Item (Bank)
Display
Contents
Initial value
User level
ON/OFF control differential
(Parameter bank)
0 to 9999 U
5 U
Simple, Standard,
High function
ON/OFF control operation
point offset
(Parameter bank)
-1999 to +9999 U
0 U
High function
• [ON/OFF control differential: dIFF] and [ON/OFF control operation point
offset: OFFS] can be displayed and set when the control method is the ON/OFF
control (CtrL = 0).
• The following Figure shows the operation of the ON/OFF control:
SP + oFFS
Heat control (Reverse action)
Cool control (Direction action)
PV
ON
dIFF
SP + oFFS
PV
ON
dIFF
z shows that the ON/OFF is changed at this value.
shows that the ON/OFF is changed at a point that "1U" is added to this value.
• The following describes examples showing how to use the ON/OFF control
operation point offset:
To turn OFF the output at 205 °C or more and turn ON the output at less than
190 °C with the heat control and SP = 200 °C, the differential is set to 15 °C and
the offset is set to 5 °C.
To turn OFF the output at 5 °C or less and turn ON the output at more than 10 °C
with the cool control and SP = 10 °C, the differential is set to 5 °C and the offset is
set to -5 °C.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� PID control
In the fixed PID control or ST (self-tuning), the PID control related items can be set.
Item (Bank)
Display
Contents
Initial value
User level
Proportional band
(PID bank)
0.1 to 999.9 %
5.0 %
Simple, Standard,
High function
Integration time
(PID bank)
0 to 9999 s
(No integration control action when set
at "0".)
120 s
Derivative time
(PID bank)
0 to 9999 s
(No derivative control action when set
at "0".)
30 s
Manual reset
(PID bank)
-10.0 to +110.0 %
50.0 %
MV low limit
(PID bank)
-10.0 to +110.0 %
0.0 %
Standard, High
function
MV high limit
(PID bank)
-10.0 to +110.0 %
100.0 %
Cool-side proportional
band (PID bank)
0.1 to 999.9 %
5.0 %
Simple, Standard,
High function
Cool-side integration time
(PID bank)
0 to 9999 s
(No integration control action when set
at "0".)
120 s
Cool-side derivative time
(PID bank)
0 to 9999 s
(No derivative control action when set
at "0".)
30 s
Cool-side MV low limit
(PID bank)
-10.0 to +110.0 %
0.0 %
Standard, High
function
Cool-side MV high limit
(PID bank)
-10.0 to +110.0 %
100.0 %
• When the control method is other than the ON/OFF control (CtrL ≠ 0), the
display and setting can be made.
• [(Cool)] related items can be displayed and set when using the Heat/Cool control
(C26 = 1).
• When the I (Integration time) ( I- 1) is set at “0 s” or I (Integration time) (cool)
(I- 1.C) is set at “0 s” in the Heat/Cool control, no integration control action is
performed. The Manual reset (rE- 1) can be used in both the heat and cool
controls.
• Parameter settings for the cool control are displayed only when the Heat/Cool
control is set enabled.
• The Manual reset (rE- 1) is displayed when the set value of either the I
(Integration time) (heat) or (cool) becomes "0".
• When the I (Integration time) (heat) or (cool) is "0 s", the operation is processed
with both I (Integration time) (heat) and (cool) set at "0 s".
• If the setting is made so that the output low limit is greater than the output high
limit, the operation is performed with the low limit swapped for the high limit
automatically.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� Heat/Cool control
The Heat/Cool control related items, such as Heat/Cool, Heat/Cool control dead
zone, and Heat/Cool change point can be set.
Item (Bank)
Display
Contents
Initial value
User level
Heat/Cool
(Setup bank)
0: Normal
1: Energy saving
0
Standard, High
function
Heat/Cool control dead
zone (Setup bank)
-100.0 to +100.0 %
0.0 %
Simple, Standard,
High function
Heat/Cool change point
(Setup bank)
-10.0 to +110.0 %
50.0 %
High function
The following shows the Heat/Cool control calculation:
PID (heat)
PID (cool)
Heat/Cool
PID (heat)
Constants oL, oH
PID (cool)
Constants oL, oH
Heat/Cool output
calculation
PID control
(Fixed at reverse action)
Heat/Cool control dead zone
Heat/Cool control change point
Constants P, I, d, rE
Heat MV
Cool MV
PV
SP
MV (PID control result)
• When using the Heat/Cool control (C26 = 1), the display and setting can be made.
• When MV ≥ 50 %, the control is changed to the PID (heat).
• When MV < 50 %, the control is changed to the PID (cool).
• When the heat/cool change is set at “energy saving” (C27 = 1), the heat/cool
change is suppressed to indirectly obtain the energy saving effect. However,
when the heat/cool dead zone (C28) is less than 0.0 %, the energy saving effect
cannot be obtained.
• How the relationship between the output (heat) and output (cool) is made for the
PID control result (MV) is set.
Note
�
z Heat/cool output
Formulas and limits for the heat/cool MV
“Dead zone” in the explanation below refers to a heat/cool control dead zone.
The cool MV and the heat MV are determined by the following formulas and the
MV high and low limits.
Heat MV = (MV – heat/cool control change point – 0.5 × deadband) × change rate
Cool MV = (heat/cool control change point – MV – 0.5 × deadband) × change rate
Change rate =
100
Heat/cool control change point - 0.5 × deadband
However, MV high and low limits, output low limit (cooling), and output high limit
(cooling) are related to the heat MV and cool MV as follows.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
100 %
100 %
0 %
Cool
MV
Heat
MV
MV
Output high limit (cooling)
Output low limit (cooling)
MV low limit
MV high limit
Note: The thick line and thick dotted line represent heat MV and cool MV respectively.
• MV low limit ≤ heat MV ≤ MV high limit
• Output low limit (cooling) ≤ cool MV ≤ output high limit (cooling)
• Use the controller within the following range: 0.0 < heat/cool control change
point < 100.0.
• In the formula for rate of change, do not make the denominator = 0.
• Regardless of the heat/cool control change point setting, 50 % of MV is always the
point at which the PID group switches.
Examples of output
100.0 %
0.0 %
Heat MV
100.0 %
Cool MV
0.0 %
0.0 %
50.0 %
100.0 % MV
100.0 %
0.0 %
Heat MV
100.0 %
Cool MV
0.0 %
0.0 %
50.0 %
Deadband
Figure 2.
Deadband > 0.0 %
Heat/cool control change point = 50.0 %
Figure 4.
Deadband = 0.0 %
Heat/cool control change point = 75.0 %
Figure 1.
Deadband = 0.0 %
Heat/cool control change point = 50.0 %
100.0 % MV
33.3 %
0.0 %
Heat MV
100.0 %
Cool MV
0.0 %
0.0 %
75.0 %
100.0 % MV
100.0 %
0.0 %
Heat MV
100.0 %
Cool MV
0.0 %
0.0 %
50.0 %
Absolute value
of the deadband
Figure 3.
Deadband < 0.0 %
Heat/cool control change point = 50.0 %
100.0 % MV
In figure 4, when the MV is 100 %, the heat MV is 33.3 %. In this case, when the
heat/cool control change point is 50 % or more, if the MV is 100 %, the heat MV
high limit is less than 100 %. The change rate of the heat MV relative to the MV is
the same as that of the cool MV relative to the MV.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� ST (Self-tuning)
The settings shown below are available for ST.
Item (Bank)
Display
Contents
Initial value
User level
ST step execution
resolution band
(Extended tuning bank)
0.00 to 99.99 %
10.00 %
High function
ST step settling band
(Extended tuning bank)
0.0 to 10.00 %
0.50 %
ST hunting settling band
(Extended tuning bank)
0.0 to 10.00 %
1.00 %
ST step ramp change
(Extended tuning bank)
0: ST is executed during PV increase and
decrease.
1: ST is executed only during PV
increase.
0
Standard, High
function
• If the control method (CtrL) is set to "2" (ST (Self-tuning)), these functions can
be displayed and set.
• ST step execution resolution band (St.SA)
When the amount of SP change exceeds the preset percentage of the PV range, ST
starts, using step response.
When the power is turned on, or READY mode is changed to RUN, if the initial
deviation between the SP and PV is larger than the amount of SP change, ST
starts, using step response.
• ST step settling band (St.Sb)
If the deviation (plus or minus) is a smaller percentage of the PV range than the
preset value, ST judges that the step response has settled.
• ST hunting settling band (St.Hb)
If the PV fluctuates so that the deviation (plus or minus) is a greater percentage
of the PV range than the preset value, hunting is judged to occur, and ST starts.
Afterwards, if the absolute value of the deviation becomes a smaller percentage of
the PV range than the preset value, hunting is judged to have settled.
Handling Precautions
5 - 5 ST (Self-tuning) Function (p. 5-24)
5 - 6 Precautions for ST (Self-tuning) (p. 5-26)
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� AT (Auto tuning)
The settings shown below are available for AT.
Item (Bank)
Display
Contents
Initial value
User level
MV low limit at AT
(Parameter bank)
-10.0 to +110.0 %
0.0 %
Simple, Standard,
High function
MV high limit at AT
(Parameter bank)
-10.0 to +110.0 %
100.0 %
AT type
(Extended tuning bank)
0: Normal (Standard control
characteristics)
1: Immediate response (Control
characteristics that respond
immediately to external disturbance.)
2: Stable (Control characteristics having
less up/down fluctuation of PV)
1
AT Proportional band adjust
(Extended tuning bank)
0.00 to 99.99
1.00
High function
AT Integral time adjust
(Extended tuning bank)
0.00 to 99.99
1.00
AT Derivative time adjust
(Extended tuning bank)
0.00 to 99.99
1.00
• When the control method is other than the ON/OFF control (CtrL ≠ 0), the
display and setting can be made.
• The MV (manipulated variable) during execution of AT can be limited by the
MV low limit at AT (At.OL) and MV high limit at AT (AT.OH).
When the Heat/Cool control is not used, the MV becomes a value limited by both
the MV low limit at AT (At.OL)/MV high limit at AT (At.OH) and MV low limit
(OL- 1)/MV high limit (OH- 1) of the PID constant.
When the Heat/Cool control is used, the MV becomes a value limited by the MV
low limit at AT (At.OL)/MV high limit at AT (At.OH), the heat MV becomes
a value limited by the MV low limit (OL- 1)/MV high limit (OH- 1) of the PID
constant, and the cool MV becomes a value limited by the output low limit (Cool)
(OL 1.C)/output high limit (Cool) (OH 1.C) of the PID constant.
• The AT type (At.ty) is a setting item that the PID constant of the control
characteristics suitable for the system is calculated by the AT.
Set value 1 (immediate response) is adjusted to the process that the heater heating
directly affects the PV to aim at the adjustment considering the immediate
response.
Set value 2 (stability) is adjusted to the process that the heater heating indirectly
affects the PV to aim at the adjustment considering the stability.
Note
When compared to the AT functions of Azbil Corporation's conventional models,
set value 1 (immediate response) is close to the SDC10 and set value 0 (normal) is
close to the SDC20/21.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
The following Figure shows the conceptual diagram expressing differences in
control result using the PID constant calculated by each AT type:
PV
Time
Diference in PV change when SP is changed.
SP
AT type = 1
(Immediate response)
AT type = 0 (Normal)
AT type = 2 (Stable)
• For the AT Proportional band adjust (At-P), AT Integral time adjust (At-I), and
AT Derivative time adjust (At-d), the value that the PID constant calculated by
the AT is multiplied by each coefficient is written into the set value of the PID
constant. However, the coefficient must be a value in the PID constant setting
range.
Note
• Setting that the AT is activated for only the heat PID constant in the Heat/
Co ol control:
50.0 %
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� Just-FiTTER
The Just-FiTTER function suppresses overshoot and the settings shown below are
available for it.
Item (Bank)
Display
Contents
Initial value
User level
Just-FiTTER assistance
coefficient
(Extended tuning bank)
0 to 100
(No JF function when set at “0”.)
0
Standard, High
function
Just-FiTTER settling band
(Extended tuning bank)
0.00 to 10.00 %
0.30 %
High function
• When the control method is other than the ON/OFF control (CtrL ≠ 0), the
display and setting can be made.
• Function of Just-FiTTER assistance coefficient (JF.Ov)
When the Just-FiTTER assistance coefficient (JF.Ov) is “0”, the Just-FiTTER
function becomes invalid.
When this coefficient is “1” or more, the effect of the overshoot limit/restraint/
control becomes larger as the coefficient becomes larger.
• Function of Just-FiTTER settling band (JF.bd)
If the deviation (plus or minus) is a larger percentage of the PV range than the
preset value, Just-FiTTER starts. If the deviation is a smaller percentage, ST
judges that the step response has settled.
�
� RationaLOOP
This RationaLOOP function suppresses the unstable trend if the immediate
response to external disturbance is increased by the high precision control logic.
The setting shown below is available for it.
Item (Bank)
Display
Contents
Initial value
User level
Control algorithm
(Extended tuning bank)
0: PID (Conventional PID)
1: RationaLOOP (High-performance PID)
0
Standard, High
function
• When the control method is other than the ON/OFF control (CtrL ≠ 0), the
display and setting can be made.
�
� SP lag
This SP lag function suppresses changes in MV when the SP is changed. The
setting shown below is available for it.
Item (Bank)
Display
Contents
Initial value
User level
SP lag time
(Extended tuning bank)
0.0 to 999.9
(No effect when set at “0.0”.)
0.0
High function
• When the control method is other than the ON/OFF control (CtrL ≠ 0), the
display and setting can be made.
• Function of SP lag time (SP.LG)
When the SP lag time is set at "0.0", the SP lag function becomes invalid.
When this value is "0.1" or more, changes in MV when the SP is changed become
smaller and the effect of the overshoot suppression becomes larger as the value
becomes larger.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
The AT (auto tuning) function is used in the following cases:
• The PID constants are set automatically with the control method set at “Fixed PID” ([CtrL = 1]).
• The PV rise is slow or overshoot is large in the control with the PID constants, which have been set automatically
using the ST function.
• The PV rise becomes slow or overshoot becomes large with the control method set at ST ([CtrL] = 2).
The AT function can be used when the control method is set at either “Fixed PID” ([CtrL] = 1) or ST ([CtrL = 2]).
�
� Starting procedures
(1) Make sure that the PV input or operation end (heater power, etc.) is
controllable.
(2) Make sure that the mode indicator [rdy] is off and the operation is in the RUN
mode. If the indicator [rdy] is lit and the operation is in the READY mode,
change the mode to the RUN mode.
(3) Make sure that the mode indicator [man] is off and the operation is in
the AUTO mode. If the indicator [man] is lit and the operation is in the
MANUAL mode, change the mode to the AUTO mode.
(4) Set the parameter setting [AT Stop/Start] to “AT start ([At] = [At.On])”.
�
� Stopping procedures
The AT function is completed automatically. To stop the AT function, which is
running, change the parameter setting [AT Stop/Start] to AT stop ([At] = [At.OF]).
Additionally, the AT function is stopped when changing the READY mode to the
MANUAL mode.
�
z Display during execution of AT
rdy
man
ev1
ev2
ev3
ot1
ot2
para
mode
pv
sp
LED
The decimal point at the 1st digit of the upper display (right end digit) flashes twice
repeatedly while the AT function is running. When the AT function is completed
and the PID constants are changed, this LED goes off.
�
z Operation during execution of AT
The AT function calculates the PID constants using the limit cycle.
(1) When the AT function is started, a point, where the SP and PV deviations are
split to “2:1”, is determined as ON/OFF change point of the MV (manipulated
variable).
(2) When the limit cycle is judged as stable, the PID constants are changed and the
AT function is completed.
5 - 4
AT (auto tuning) Function
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
PV
SP
2/3
1/3
Insufcient
stability
AT start
Time
Normal end
Stable
cycle
In the Heat/Cool control, the AT function is run in the status that both the heat MV
and cool MV are operated.
In the first half, the MV is changed to the MV low limit/MV high limit. In the
latter half, the MV is changed in a slightly narrow range.
The following Figure shows an example of the AT execution when the Heat/Cool
control deadband is 0.0 %, Heat/Cool control change point is 50.0 %, MV low limit
is 0.0 %, and MV high limit is 100.0 %:
MV (%)
100.0
Time
50.0
0.0
Heat MV (%)
100.0
Time
50.0
0.0
Cool MV (%)
100.0
Time
50.0
0.0
PV
Time
SP change
point
AT is running.
Handling Precautions
• Before starting the AT function, put the PV input and/or operation end
(heater power, etc.) in the controllable status.
• When the control method is set at “ON/OFF control” ([CtrL] = 0), the AT
function cannot be started. To operate the AT function, set the control
method to “Fixed PID” ([CtrL] = 1) or “ST” ([CtrL] = 2).
• To start the AT, it is absolutely necessary that the operation is in the
READY mode and AUTO mode, and no PV input errors occur.
• If the mode is changed to the READY mode or MANUAL mode or if the PV
input error or power failure occurs during execution of the AT function,
the AT function is stopped without changing of the PID constants.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
• When the Heat/Cool control is not used, the MV becomes a value limited
by both ranges, one range is between the MV low limit at AT (AT.OL)
and MV high limit at AT (AT.OH), and the other is between the MV low
limit (OL-1) and MV high limit (OH-1) of the PID constant. When there
are no common portions in two ranges, the AT function is stopped
automatically.
• When the Heat/Cool control is used, the MV becomes a value limited by
the MV low limit at AT (At.OL)/MV high limit at AT (At.OH), the heat MV
becomes a value limited by the MV low limit (OL-1)/MV high limit (OH-
1) of the PID constant, and the cool MV becomes a value limited by the
output low limit (Cool) (OL.1C)/output high limit (Cool) (OH.1C) of the PID
constant.
• When the MV low limit at AT (At.OL)/high limit (At.OH), MV low limit (OL-
1)/high limit (OH-1), cool-side MV low limit (OL.1C)/cool-side MV high limit
(OH.1C) of the PID constant are set unevenly, the PV may not be changed
up or down even though the MV is changed by the AT. In this case, the
AT is kept continued. If this occurs, the AT is stopped manually, the high
limit and low limit of the manipulated variable are set again, and the AT is
started again.
• The number of limit cycles and period of time from the AT start to AT end
may vary depending on the control subject.
• The MV ON and OFF are repeated several times during execution of the
AT function to perform the limit cycle. (The OFF operation described here
means MV limited by the MV low limit at AT ([At.OL]) or MV high limit
at AT ([OL]). The default setting before shipment is “0 %”. Additionally,
the ON operation described here means MV limited by the MV high limit
at AT ([At.OH]) or MV high limit at AT ([OH]). The default setting before
shipment is “100 %”. If this AT operation does not function correctly, take
any of the following measures:
(1) Change the MV low limit at AT ([At.OL]) or MV high limit at AT ([At.
Oh]) to an appropriate value, and then start the AT function.
(2) Use the ST function.
(3) Set the PID constants manually without use of AT.
• The AT progress value can be seen in the operation display mode.
6 - 1 List of Operation Displays (p. 6-1)
When the Heat/Cool control is not used, the AT progress value
decrements from [4] during execution of the AT function and becomes [0]
at completion of the AT function.
When the Heat/Cool control is used, the AT progress value decrements
from [8] during execution of the AT function and becomes [0] at
completion of the AT function.
In both cases, the AT progress value may be “1” or “0” when the AT process
is in the transient status.
• Appropriate PID constants cannot be obtained depending on the control
subject. If this happens, set the PID constants manually.
• The MV ON/OFF change point determined when the AT function is
started does not change even though the SP is changed while the AT is
running.
AT Stop/Start (p. 5-8) and AT (p. 5-18)
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
When the control method (CtrL) is set to "2" (ST (Self-tuning)), if the following conditions for ST startup are met,
ST starts automatically and changes the PID constants.
(1) Startup due to change of SP
If the SP is changed in RUN mode, ST starts. However, if the amount of SP change is small or if the difference
between the SP and PV is small, ST does not start.
(2) Startup due to large deviation
If the difference between the SP and PV is large while executing control in RUN mode, ST starts.
If the difference between the SP and PV is large when READY mode is changed to RUN, ST starts.
If the difference between the SP and PV is large when control execution begins in RUN mode after the power has
been turned on, ST starts.
Handling Precautions
• For ST to start, it is essential that the integral time and derivative time of the
PID constants be other than "0" ([ I- 1] ≠ 0, [d- 1] ≠ 0).
• For ST to start, RUN and AUTO modes must be selected.
• Set "High function" to configure the reference values used to judge the
amount of SP change or to decide whether the difference between the SP and
PV is large or small. However, for most control targets the default settings can
be used.
• For heat/cool control, ST cannot be used.
�
� How to start ST
(1) Make sure that the PV input and the actuators (heater power, etc.) are ready
for control.
(2) Make sure that the mode indicator [rdy] is off, indicating RUN mode. If [rdy]
is lit, indicating READY mode, change the mode to RUN.
(3) Make sure that the [man] mode light is off, indicating AUTO mode. If [man] is
lit, indicating MANUAL mode, change the mode to AUTO.
(4) Set the control method (CtrL) to "2" (ST (Self-tuning)) in the parameter
setup bank. This operation is not needed from the 2nd time on.
(5) Set the SP.
If ST does not start because the PV is close to the SP (PV≈SP), change the SP
so that it is greatly different from the PV.
5 - 5
ST (Self-tuning) Function
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� How to stop ST
ST stops automatically. If it is necessary to stop the ST while it is running or to
disable ST, set the control method to "Fixed PID" (CtrL = 1) in the parameter setup
bank. Also, ST can be stopped by switching to READY or MANUAL mode.
�
z Display while ST is running
While ST is running, the rightmost decimal point LED on the upper display flashes.
When ST ends and the PID constants have been changed, this LED turns off.
rdy
man
ev1
ev2
ev3
ot1
ot2
para
mode
pv
sp
LED
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
When using ST, follow the rules shown below.
z Before starting ST, make the PV input and the actuators (heater power, etc.)
ready for control.
z Before starting ST, set PID constants that are capable of adequate PID control.
• By default, the proportional band [ P- 1 ] = 5.0 %, integral time [ I- 1 ] = 120 s,
and derivative time [ d- 1 ] = 30 s.
With the above settings, adequate PID control is possible for most control
targets.
• If the integral time [ I- 1 ] = 0 s, ST will not start.
• If the derivative time [ d- 1 ] = 0 s, ST will not start.
z To stop control execution while the controller is turned on, change RUN mode
to READY, and then turn off the actuator (heater). To resume control execution,
turn on the actuator (heater), and then change READY mode to RUN.
z If the ST step execution resolution band (ST.SA) is small, even if ST is executed,
the PID constants may not be adjusted. For this reason, specify an appropriately
large value for the ST step execution resolution band (ST.SA).
Handling Precautions
• If the above rules are not observed, the PID constants may change to
unsuitable values when ST is complete, resulting in poor control.
• While ST is running (the LED will be flashing), if the power to the controller
is turned off, the PID constants will not be changed. Also, if the power is
turned off just before ST finishes, unsuitable PID constants may be set.
If the PID constants are unsuitable, the following methods can be used to correct
them.
(1) Restore the default PID constants Configure as follows: proportional band
[ P- 1 ] = 5.0 %, integral time [ I- 1 ] = 120 s, and derivative time [ d- 1 ] = 30 s.
(2) Start ST.
Or, set the PID constants using AT, and then start ST.
�
z If control targets interfere with each other
If the control targets are located side by side or one above the other, temperature
changes in one may affect ST in the other, resulting in slow control response. In this
case, set the control method to “Fixed PID” ([CtrL] = 1).
�
z If the control target is disturbed intermittently
In a case like heat sealing by a packing machine, intermittent temperature drops
may affect ST. In this case, set the control method to “Fixed PID” ([CtrL] = 1)
�
z If PV alarm and reset recur frequently
While ST is running, if PV alarms and resets are repeated frequently, they may
be interpreted as hunting, resulting in changes of the PID parameters. If these
circumstances arise during instrumentation, etc., put the unit into READY mode or
disable ST.
5 - 6
Precautions for ST (Self-tuning)
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
The following shows the functional block diagram of the SP:
One LSP group exists.
Two or more LSP groups exist.
LSP system group
(Setting: Setup C30)
LSP1
(Setting: SP SP 1)
DI Assignment is not provided.
DI Assignment is provided.
DI Assignment of LSP group selection
provided/not provided.
(Setting: DI Assignment di 1. 1 to di 3. 1)
LSP group number
(Setting: LSP group number in
operation display mode)
Logical operation of DI
(Setting: General DI Assignment)
LSP value in use
SP
SP high limit/low limit
(Setting: Setup C07, C08)
SP ramp unit (Setting: Setup C32)
SP ramp-up/ramp-down
(Setting: Parameter SPU, SPd)
DI Assignment of SP ramp enabled/disabled.
(Setting: DI Assignment di 1. 1 to di 3. 1)
LSP 1 to 4
(Setting: SP SP 1 to SP4)
Note
LSP is a local SP and shows that the data is retained inside this unit.
On the contrary, SP by the analog input from the outside is called RSP or remote SP.
However, the RSP function is not provided on this unit.
5 - 7
SP
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� SP setup in operation display mode
The set value for LSP in use of LSP1 to 4 can be set.
The LSP set value is different from the SP display value during SP ramp.
However, the set value is displayed while the key is being operated to change the
setting.
Item (Bank)
Display
Contents
Initial value
User level
SP (Operation display)
PV is
shown on
the upper
display.
SP low limit to SP high limit U
0 U
Simple, Standard,
High function
• When [bit 1: SP display] of the PV/SP display setup (setup C74) is set at "1"
(display is provided), the display and setting can be made.
�
� LSP system group
The LSP system group can be selected.
Item (Bank)
Display
Contents
Initial value
User level
LSP system group
(Setup bank)
1 to 4
1
Simple, Standard,
High function
�
� LSP1 to 4
The set values can be set for four LSP groups.
Item (Bank)
Display
Contents
Initial value
User level
SP
(SP bank)
SP low limit to SP high limit U
0 U
Simple, Standard,
High function
0 U
0 U
0 U
• The display and setting can be made for the LSP system group selected in [C30:
LSP system group] .
�
� LSP group number
The LSP group number can be set.
Item (Bank)
Display
Contents
Initial value
User level
LSP group No.
(Operation display)
Numeric value at the rightmost digit of
the display.
1 to LSP system group
1
Simple, Standard,
High function
• When [C30: LSP system group] is set at “2” or more and [bit 2: LSP group
number display] of the PV/SP display setup (setup C74) is set at “1” (display is
provided), the display can be made.
• When the display is possible and the DI Assignment of the LSP group selection is
not performed, the setting can be made.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� DI Assignment of LSP group selection
The LSP group selection can be set for internal contacts 1 to 3 using the DI
Assignment.
Item (Bank)
Display
Contents
Initial value
User level
Internal contact 1 to 3
Operation type
(DI Assignment bank)
0: No function
1: LSP group selection (0/+1)
2: LSP group selection (0/+2)
3: LSP group selection (0/+4)
4 to 20: Other functions
0
Simple, Standard,
High function
0
0
• Details of LSP group selection with the internal contact function
The following shows the LSP group selection value according to the ON/OFF
status of each internal contact:
LSP group selection (0/+1)
OFF: 0
ON: 1
LSP group selection (0/+2)
OFF: 0
ON: 2
LSP group selection (0/+4)
OFF: 0
ON: 4
The value, that "1" is added to the sum of the LSP group selection values
according to the ON/OFF status of each internal contact, becomes the LSP group
number.
For example, when the sum of LSP group selection values of internal contact 1 to
3 is "1", the LSP group number becomes "2".
• Even though the LSP system group is "1", the display and setting can be made, but
the LSP group selection with the internal contact function becomes invalid.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� SP ramp unit
The unit of the SP up/down ramp can be set.
Item (Bank)
Display
Contents
Initial value
User level
SP ramp unit
(Setup bank)
0: 0.1 U/s
1: 0.1 U/min
2: 0.1 U/h
0
High function
• "0.1U" shows that the decimal point position of the PV is shifted one digit rightward.
Example: When the thermocouple input is in a range of -200 to +1200 °C, "0.1 U"
is "0.1 °C".
Example: When the DC voltage input is in a range of 0.0 to 100.0, "0.1U" is "0.01".
For the relationship between the decimal point position and the type of PV input
range, refer to the next section, "� SP ramp-up/ramp-down."
Handling Precautions
When using the DC voltage/DC current input with setting of 3 digits after
the decimal point, "0.1U" is "0.0001".
However, the SP up ramp/SP down ramp setting cannot display 4 digits after
the decimal point, the value is displayed without use of the decimal point.
�
� SP up ramp/down ramp
The SP up ramp and down ramp can be set.
Item (Bank)
Display
Contents
Initial value
User level
SP up ramp
(Parameter bank)
0.0U:
No ramp
0.1 to 999.9 U
(The unit of the ramp time is selected
using the SP ramp unit.)
0.0 U
High function
SP down ramp
(Parameter bank)
0.0 U
• When an initial value of “0.0U” is set, the SP ramp function does not function.
Therefore, when the up ramp setting is set to “0.1U” or more and the down ramp is
set to “0.0 U”, the SP ramp functions only during SP up and the SP ramp does not
function during SP down. Additionally, the reverse operation can also be set so that
the SP ramp functions only during SP up and it does not function during SP down.
• Regarding the setting for the number of digits after the decimal point (C04), the
SP ramp display shows one digit more than is shown for the PV. For linear input,
if C04 is set for 3 digits after the decimal point, no decimal point is displayed in
the SP ramp value, but all 4 displayed digits are after the decimal point.
The unit for the SP ramp can be selected from every second, every minute, and
every hour in C32 of the SETUP bank.
The table below shows how the decimal point position varies depending on the
PV input range.
C01 (PV input range type)
C04 (Decimal point position)
SPU (SP ramp up)
SPD (SP ramp down)
2 (0 to 1200°C)
Setting disabled
0.0 to 999.9
0.0 to 999.9
3 (0.0 to 800.0°C)
0 (No decimal point)
0.0 to 999.9
0.0 to 999.9
1 (1 digit after the decimal point)
0.00 to 99.99
0.00 to 99.99
88 (0 to 10V)
0 (No decimal point)
0.0 to 999.9
0.0 to 999.9
1 (1 digit after the decimal point)
0.00 to 99.99
0.00 to 99.99
2 (2 digits after the decimal point)
0.000 to 9.999
0.000 to 9.999
3 (3 digits after the decimal point)
0.0000 to 0.9999
0.0000 to 0.9999
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
• The ramp is started assuming that the current PV value is used as start point
when any of the following conditions is satisfied:
The power is turned ON.
READY+AUTO status is changed to RUN+AUTO status.
RUN+MANUAL status is changed to RUN+AUTO status.
The AT function is completed (both normal end and forced stop).
Handling Precautions
Before changing the slope of the SP ramp, make sure that SP ramping is not
in progress. If the setting is changed while the SP ramp is in progress, the
SP may change suddenly.
�
� SP low limit/high limit
The SP low limit and high limit can be set to limit the SP range.
Item (Bank)
Display
Contents
Initial value
User level
SP low limit
(Setup bank)
PV range low limit to PV range high limit PV range low limit
Standard, High
function
SP high limit
(Setup bank)
PV range low limit to PV range high limit PV range high limit
Standard, High
function
Handling Precautions
When the PV input range type (setup C01) is set, the SP low limit and high
limit are initialized.
�
� DI Assignment of SP ramp enabled/disabled
The LSP group selection can be set for internal contacts 1 to 3 using the DI
Assignment.
Item (Bank)
Display
Contents
Initial value
User level
Internal Contacts 1 to 3
Operation type
(DI Assignment bank)
0: No function
13: SP ramp enabled/disabled.
1 to 12, 14 to 20: Other functions
0
Simple, Standard,
High function
0
0
• Details of SP ramp enabled/disabled with internal contact function
The following shows the SP ramp enabled/disabled setting with the internal
contact ON/OFF:
OFF: SP ramp enabled.
ON: SP ramp disabled.
The SP ramp enabled/disabled is set for only one internal contact.
• When the SP ramp is set disabled, the SP ramp operation is stopped and the SP
value becomes the final SP.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
The following shows the functional block diagram of the DI (digital input) and internal contact:
Input bit function is not used.
(Setting: [Input bit function
is not used.]
must be set using DI Assignment
di 1.2 to di 3.2.)
DI status (ON/OFF)
Input assignment Polarity
(Setting: DI Assignment Polarity A to D di 1.7
to di 3.7)
Internal Contact Input bit function result
Input bit function is not used.
Input assignment
(Setting: DI Assignment Input assignment A di 1.3
to di 3.3,
DI Assignment Input assignment B di 1.4 to di 3.4,
DI Assignment Input assignment C di 1.5 to di 3.6,
DI Assignment Input assignment D di 1.6 to di 3.6)
Input bit function 1 to 4
(Setting: DI Assignment Input bit function di 1.2
to di 3.2)
Input bit function Polarity
(Setting: DI Assignment di 1.8 to di 3.8)
Input bit function is used.
Event channel defnitions
(Setting: DI Assignment di 1.9 to di 3.9)
Operation type (Setting: DI Assignment di 1. 1
to di 3. 1)
Internal contact function
Polarity
(Setting: DI Assignment di 1.8 to di 3.8)
Handling Precautions
Even though three internal contacts 1 to 3 are provided, the number of digital
inputs determined by the optional model is 0 to 2 points.
With the default settings before shipment, the operations of digital input 1 to 2
have already been connected to internal contacts 1 to 2.
To utilize the operation of internal contact 3, it is absolutely necessary to set the
DI Assignment.
5 - 8
DI (Digital Input) and Internal Contact
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� Operation type
The operation type by the internal contact function can be set.
Item (Bank)
Display
Contents
Initial value
User level
Internal Contact 1
Operation type
(DI Assignment bank)
0 to 20
For details about function by each set
value, refer to the Table below.
0
Simple, Standard,
High function
Internal Contact 2
Operation type
(DI Assignment bank)
0
Internal Contact 3
Operation type
(DI Assignment bank)
0
Handling Precautions
• For [1 to 3: LSP group selection], the value that “1” is added to the sum
of weights (+ 1, + 2, +4), the internal contact of which is turned ON,
becomes the LSP group number.
• Do not use [14: PV value hold], [15: PV Max. hold], and [16: PV Min. hold]
with they mixed.
• Do not set the same operation type other than [0: No function] and [1 to
3: LSP group selection] for multiple internal contacts.
• When using the Heat/Cool control, do not use [12: Control action direct/
reverse selection].
• For timer stop/start, set a target Event channel using [Event channel def.
of internal contact].
The following Table shows the contents of the dI settings:
Set value
Function
Operation at OFF
Operation at ON
0
No function
None
None
1
LSP group selection (0/+1)
LSP No.: +0
LSP No.: +1
2
LSP group selection (0/+2)
LSP No.: +0
LSP No.: +2
3
LSP group selection (0/+4)
LSP No.: +0
LSP No.: +4
4
PID group selection (0/+1)
Invalid
Invalid
5
PID group selection (0/+2)
Invalid
Invalid
6
PID group selection (0/+4)
Invalid
Invalid
7
RUN/READY mode selection
RUN
READY
8
AUTO/MANUAL mode selection
AUTO
MANUAL
9
LSP/RSP mode selection
Invalid
Invalid
10
AT (Auto tuning) Stop/Start
AT Stop
AT Start
11
ST (Self-tuning) disabled/enabled
ST disabled
ST enabled
12
Control action direct/reverse selection
Set action
Reverse action of setting
13
SP ramp enabled/disabled
SP ramp enabled
SP ramp disabled
14
PV value hold
No-hold
Hold
15
PV Max. hold
No-hold
Hold
16
PV Min. hold
No-hold
Hold
17
Timer Stop/Start
Timer stop
Timer start
18
Release all DO latches
Continue if latch exists. Latch release
19
Advance operation
Invalid
Invalid
20
Step hold
Invalid
Invalid
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� Internal event No. assignment
When the operation type is the timer start/stop, a target internal event number can
be set.
Item (Bank)
Display
Contents
Initial value
User level
Internal Contact 1 Internal
event No. assignment
(DI Assignment bank)
0: Every Internal Event
1 to 5: Internal Event number
0
High function
Internal Contact 2 Internal
event No. assignment
(DI Assignment bank)
0
Internal Contact 3 Internal
event No. assignment
(DI Assignment bank)
0
• When the operation type of the same internal contact No. is set at “Timer stop/
start”, the display and setting can be made.
�
� Input bit function
Four kinds of input bit functions are provided. What function of four functions is
used or is not used can be set.
Item (Bank)
Display
Contents
Initial value
User level
Internal Contact 1 Input bit
function
(DI Assignment bank)
0: Not used (Default input)
1: Function 1 ((A and B) or (C and D))
2: Function 2 ((A or B) and (C or D))
3: Function 3 (A or B or C or D)
4: Function 4 (A and B and C and D)
0
High function
IInternal Contact 2 Input
bit function
(DI Assignment bank)
0
Internal Contact 3 Input bit
function
(DI Assignment bank)
0
• When the set value is “0”, the input bit function is not used and the default input
is used. The following shows the default input of each internal contact:
Internal Contact 1: DI (digital input) 1
Internal Contact 2: DI (digital input) 2
Internal Contact 3: OFF status
• In the input bit function, the logical operations (AND, OR) of each of internal
contacts 1 to 3 are combined. In input bit functions 1 to 4, the combination of the
logical operations may vary. The following shows one logical operation:
Logical AND
Logical OR
OFF and OFF = OFF
OFF or OFF = OFF
ON and OFF = OFF
ON or OFF = ON
ON and ON = ON
ON or ON = ON
• “OFF” is “contact open (OPEN)” or “0” when expressed using the numerical value.
• “ON” is “contact close (CLOSE)” or “1” when expressed using the numerical value.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� Input assign
The assign of four inputs (A, B, C, D) used for the input bit function can be set.
Item (Bank)
Display
Contents
Initial value
User level
Internal Contact 1 Input
assign A
(DI Assignment bank)
0: Normally opened. (OFF, 0)
1: Normally closed. (ON, 1)
2: DI1
3: DI2
4 to 9: Undefined.
10: Internal Event 1
11: Internal Event 2
12: Internal Event 3
13: Internal Event 4
14: Internal Event 5
15 to 17: Undefined.
18: Communication DI1
19: Communication DI2
20: Communication DI3
21: Communication DI4
22: MANUAL mode
23: READY mode
24: Undefined.
25: AT running
26: During SP ramp
27: Undefined.
28: Alarm occurs.
29: PV alarm occurs.
30: Undefined.
31: mode key pressing status
32: Event output 1 status
33: Control output 1 status
2
High function
Internal Contact 1 Input
assign B
(DI Assignment bank)
0
Internal Contact 1 Input
assign C
(DI Assignment bank)
0
Internal Contact 1 Input
assign D
(DI Assignment bank)
0
Internal Contact 2 Input
assign A
(DI Assignment bank)
3
Internal Contact 2 Input
assign B
(DI Assignment bank)
0
Internal Contact 2 Input
assign C
(DI Assignment bank)
0
Internal Contact 2 Input
assign D
(DI Assignment bank)
0
Internal Contact 3 Input
assign A
(DI Assignment bank)
4
Internal Contact 3 Input
assign B
(DI Assignment bank)
0
Internal Contact 3 Input
assign C
(DI Assignment bank)
0
Internal Contact 3 Input
assign D
(DI Assignment bank)
0
• When the input bit function of the same internal contact No. is set for input bit
functions 1 to 4, the display and setting can be made.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� Polarity of input assign
The polarity of four input assigns (A, B, C, D) used for the input bit function can be
set.
Item (Bank)
Display
Contents
Initial value
User level
Internal Contact 1, Polarity
A to D
(DI Assignment bank)
The digits are called 1st digit, 2nd digit,
3rd digit, and 4th digit from the right end.
1st digit: Input assign A Polarity setting
2nd digit: Input assign B Polarity setting
3rd digit: Input assign C Polarity setting
4th digit: Input assign D Polarity setting
0: Direct
1: Reverse
0000
High function
Internal Contact 2, Polarity
A to D
(DI Assignment bank)
0000
Internal Contact 3, Polarity
A to D
(DI Assignment bank)
0000
• When the input bit function of the same internal contact No. is set for input bit
functions 1 to 4, the display and setting can be made.
�
� Polarity of input bit function
The polarity after the input bit function (functions 1 to 4) can be set.
Item (Bank)
Display
Contents
Initial value
User level
Internal Contact 1 Polarity
(DI Assignment bank)
0: Direct
1: Reverse
0
High function
Internal Contact 2 Polarity
(DI Assignment bank)
0
IInternal Contact 3 Polarity
(DI Assignment bank)
0
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� DI Assignment setting with Smart Loader Package SLP-C35
When setting [DI Assignment] with the Smart Loader Package SLP-C35, select [Edit
(E)] → [Input port setup (O)] in that order from the [Input] menu. The input bit
function, input assign, polarity of input assign, and polarity of input bit function
can be easily set using visual images as shown below.
Select the input bit function. The image of the
ladder is changed according to the selected
input bit function.
Select four input assigns A to D.
Select whether or not the polarity is set for
assigns A to D.
Select whether or not the polarity of
the bit function is made.
Handling Precautions
In addition to the selection through the menu, the Input port setup window
can also be opened using the following procedures:
Click the input/output port setup icon
.
Right-click in the input bit function setting window.
Press the [Ctrl] and [P] keys at the same time.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
The result of the internal event process can be output to the control output or event output through the DO (digital
output) process.
2 - 1 Input/Output Configuration (p. 2-1)
The following shows the functional block diagram of the internal event:
Operation type
(Setting: Event Confguration
Operation type E 1.C 1 to E5.C 1)
Direct/reverse, Standby
(Setting: Event Confguration,
Direct/reverse, Standby E 1.C2 to E5.C2)
Controller alarm OR/AND
(Setting: Event Confguration
E 1.C3 to E5.C3)
EVENT state at READY
(Setting: Event Confguration
E 1.C2 to E5.C2)
Main setting, sub setting,
hysteresis, special OFF setup
(Setting: Event E 1 to E5, E 1 .SB to E5.SB,
E 1 .HY to E5.HY
Event Confguration E 1 .C3 to E5.C3)
ON delay, OFF delay, Delay time unit
(Setting: Event E 1.ON to E5.ON,
E 1.OF to E5.OF,
Event Confguration E 1.C3 to E5.C3)
Internal Event status
Handling Precautions
Even though five internal events 1 to 5 are provided, the number of event
outputs determined by the optional model is 0 to 3 points. With the default
settings before shipment, the operations of internal events 1 to 3 can be output
to event outputs 1 to 3. To utilize the operations of internal events 4 to 5, it is
absolutely necessary to set the DO Assignment.
5 - 9
Internal Event
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
�
� Operation
According to the operation type, direct/reverse, main setting, sub setting, hysteresis,
and other settings, the operation of the internal event becomes as follows:
[List of internal event operations]
Note
For details about U (unit), refer to the attached glossary.
Operation type
Set value of
operation
type
Direct action
z shows that the ON/OFF is changed at
this value.
shows that the ON/OFF is changed at a
point that "1U" is added to this value.
Reverse action
z shows that the ON/OFF is changed at
this value.
shows that the ON/OFF is changed at a
point that "1U" is added to this value.
No event
0
Always OFF
Always OFF
PV high limit
1
ON
HYS
Main setting
PV
ON
HYS
Main setting
PV
PV low limit
2
Main setting
PV
ON
HYS
Main setting
PV
ON
HYS
PV high/low limit
3
Main setting
Sub-setting (*1)
PV
ON
HYS
ON
HYS
(*1)
Main setting (*1)
Sub-setting (*1)
SP
ON
HYS
HYS
Deviation high
limit
4
ON
HYS
SP + Main setting
PV
ON
HYS
SP + Main setting
PV
Deviation low limit
5
SP + Main setting
PV
ON
HYS
SP + Main setting
PV
ON
HYS
Deviation high/
low limit
6
Main setting
Sub-setting
PV
SP
ON
HYS
ON
HYS
Deviation high limit
(Final SP reference)
7
ON
HYS
SP + Main setting
PV
Same as the direct action of the deviation
high limit when the SP ramp is not used.
The difference is that the SP ramp does not
use the current SP, but it uses the final SP.
ON
HYS
SP + Main setting
PV
Same as the reverse action of the deviation
high limit when the SP ramp is not used.
The difference is that the SP ramp does not
use the current SP, but it uses the final SP.
ON
HYS
HYS
Main
setting
Sub-setting
PV
SP
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Operation type
Set value of
operation
type
Direct action
z shows that the ON/OFF is changed at
this value.
shows that the ON/OFF is changed at a
point that "1U" is added to this value.
Reverse action
z shows that the ON/OFF is changed at
this value.
shows that the ON/OFF is changed at a
point that "1U" is added to this value.
Deviation low limit
(Final SP reference)
8
SP + Main setting
PV
ON
HYS
Same as the direct action of the deviation
low limit when the SP ramp is not used. The
difference is that the SP ramp does not use
the current SP, but it uses the final SP.
SP + Main setting
PV
ON
HYS
Same as the reverse action of the deviation
low limit when the SP ramp is not used. The
difference is that the SP ramp does not use
the current SP, but it uses the final SP.
Deviation high/
low limit
(Final SP reference)
9
Main setting
Sub-setting
PV
SP
ON
HYS
ON
HYS
Same as the direct action of the deviation
high/low limit when the SP ramp is not
used. The difference is that the SP ramp
does not use the current SP, but it uses the
final SP.
ON
HYS
HYS
Main
setting
Sub-setting
PV
SP
Same as the reverse action of the deviation
high/low limit when the SP ramp is not
used. The difference is that the SP ramp
does not use the current SP, but it uses the
final SP.
SP high limit
10
ON
HYS
Main setting
SP
ON
HYS
Main setting
SP
SP low limit
11
Main setting
SP
ON
HYS
Main setting
SP
ON
HYS
SP high/low limit
12
Main setting (*1)
Sub-setting (*1)
SP
ON
HYS
ON
HYS
Main setting (*1)
Sub-setting (*1)
SP
ON
HYS
HYS
MV high limit
13
ON
HYS
Main setting
MV
ON
HYS
Main setting
MV
MV low limit
14
Main setting
MV
ON
HYS
Main setting
MV
ON
HYS
MV high/low limit
15
Main setting (*1)
Sub-setting (*1)
MV
ON
HYS
ON
HYS
Main setting (*1)
Sub-setting (*1)
MV
ON
HYS
HYS
Heater 1 burnout/
Over-current*2
16
Main setting
Sub-setting
ON
HYS
ON
HYS
CT1 at output ON.
OFF before measuring the CT1 current value
CT1 at output ON.
ON
HYS
HYS
Main setting
Sub-setting
OFF before measuring the CT1 current value
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Operation type
Set value of
operation
type
Direct action
z shows that the ON/OFF is changed at
this value.
shows that the ON/OFF is changed at a
point that "1U" is added to this value.
Reverse action
z shows that the ON/OFF is changed at
this value.
shows that the ON/OFF is changed at a
point that "1U" is added to this value.
Heater 1 short-
circuit*2
17
ON
HYS
Main setting
CT1 at output OFF.
OFF before measuring the CT1 current value
ON
HYS
Main setting
CT1 at output OFF.
OFF before measuring the CT1 current value
Heater 2 burnout/
Over-current*2
18
Main setting
Sub-setting
ON
HYS
ON
HYS
CT2 at output ON.
OFF before measuring the CT2 current value
CT2 at output ON.
ON
HYS
HYS
Main setting
Sub-setting
OFF before measuring the CT2 current value
Heater 2 short-
circuit*2
19
ON
HYS
Main setting
CT2 at output OFF.
OFF before measuring the CT2 current value
ON
HYS
Main setting
CT2 at output OFF.
OFF before measuring the CT2 current value
*1 If the setting is made so that the main setting is greater than the sub setting, the operation is performed with the main
setting swapped for the sub setting automatically.
*2 When the event type is CT1/2 heater burnout/over-current or CT1/2 heater short-circuit,the status becomes
that the event judgment cannot be made from the time of power ON until that CT input current value is
measured for the first time. In this case, the internal event output is OFF for both of direct action and reverse
action in the direct/reverse setting. To avoid that the output becomes OFF at power ON when used in reverse
action, set as follows:
(Setting example)
For direct/reverse setting of CT1/2 heater burnout/over-current or CT1/2 short-circuit event, select the direct
action, and set the reverse operation in DO assignment calculation of the event output terminal (event
terminal or control output terminal)
CT event(direct action)
[Reverse]
(DO output)
Normally open(0)
Normally open(0)
Normally open(0)
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Operation type
Set value of
operation
type
Direct action
Reverse action
Loop diagnosis 1
20
The event is turned ON when any change in PV corresponding to increase/decrease in
MV (Manipulated variable) is not observed.
This event is used to detect any fault at the operation end.
z Setting items
• Main setting: MV (Manipulated variable)
• Sub-setting: PV
• ON delay time: Diagnosis time
z Operation specifications
The event is turned ON when the value does not reach the PV set in the sub-setting
within the diagnosis time (ON delay time) (conditions 1) even though the MV
exceeding the main setting is held (conditions 2).
z CAUTION
When setting the ON delay, it is necessary to put in "High function configuration".
The default setting of the ON delay before shipment is 0.0 s.
Heat control
Sub-setting
Main setting
Time
Conditions 3
ON delay
set time
ON delay is started when conditions 1 and 2 are satisfed.
Area satisfying
conditions 1
Area satisfying
conditions 2
Time
Time
PV
MV
EV
ON
HYS
Cool control
Sub-setting
Main setting
Time
Conditions 3
ON delay
set time
ON delay is started when conditions 1 and 2 are satisfed.
Area satisfying conditions 1
Area satisfying
conditions 2
Time
Time
PV
MV
EV
ON
HYS