Thank you for purchasing an Azbil

Corporation product. This manual contains information for ensuring the correct use of this product. It also provides necessary information for installation, maintenance, and troubleshooting. This manual should be read by those who design and maintain equipment that uses this product. Be sure to keep this manual nearby for handy reference. No. CP-SP-1148E Single Loop Controller Model C15 User’s Manual for Installation & Configuration (Not for use in Japan)

Be sure that the user receives this manual before the product is used.

Copying or duplicating this user’s manual in part or in whole is forbidden. The information and specifications in this manual are subject to change without notice. Considerable effort has been made to ensure that this manual is free from inaccuracies and omissions. If you should find an error or omission, please contact the azbil Group. In no event is Azbil Corporation liable to anyone for any indirect, special or consequential damages as a result of using this product. The quick reference guide on pages D-1 to D-8 summarizes key operations, parameters, and settings, and gives concrete operation examples using illustrations. Try looking at these pages first, and then read the main text for details. A separate color version of the quick guide printed on dirt-resistant paper is available for convenient use on the work site (document No. CP-SP-1213E). Contact the azbil Group or a distributor for details. Getting Up to Speed with model C15 © 2003–2020 Azbil Corporation. All Rights Reserved. Modbus™ is a trademark and the property of Schneider Electric SE, its subsidiaries and affiliated companies.

To reduce the risk of an electric shock that could cause personal injury,

follow all safety notices in this document. This symbol warns the user of a potential shock hazard where hazardous live voltages may be accessible. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment must be impaired. Do not replace any component (or part) not explicitly specified as replaceable by your supplier. All wiring must be in accordance with local norms and carried out by authorized and experienced personnel. A switch in the main supply is required near the equipment. Main power supply wiring requires a (T) 0.2 A, 250 V fuse(s) (IEC 127). � z EQUIPMENT RATINGS Supply voltages: 100 to 240 V AC (operating power supply voltage 85 to 264 V AC) Frequency: 50/60 Hz Power consumption: 12 VA max. � z EQUIPMENT CONDITIONS Do not operate the instrument in the presence of flammable liquids or vapors. Operation of any electrical instrument in such an environment constitutes a safety hazard. Temperature: 0 to 50 °C Humidity: 10 to 90 %RH (no condensation) Vibration: 2 m/s2 (10 to 60 Hz) Over-voltage category: Category II (IEC60364-4-443, IEC60664-1) Pollution degree: 2 Installation location: Indoors Altitude: 2000 m or less � z EQUIPMENT INSTALLATION The controller must be mounted into a panel to limit operator access to the rear terminal. Specifications of common mode voltage: The common mode voltages of all I/O except for main supply and relay outputs are less than 30 Vrms, 42.4 V peak and 60 V DC. � z APPLICABLE STANDARDS EN61010-1, EN61326-1 (For use in industrial locations) During EMC testing, the reading or output may fluctuate by ±10 %FS. Safety Requirements

� The safety precautions explained in the following section aim to prevent injury to the operator and others, and to

prevent property damage. WARNING Warnings are indicated when mishandling this product might result in death or serious injury. CAUTION Cautions are indicated when mishandling this product might result in minor injury to the user, or only physical damage to the product. � In describing the product, this manual uses the icons and conventions listed below. Use caution when handling the product. The indicated action is prohibited. Be sure to follow the indicated instructions. Handling Precautions: Handling Precautions indicate items that the user should pay attention to when handling this device. : This indicates the item or page that the user is requested to refer to. Note: Notes indicate information that might benefit the user. (1) (2) (3): Numbers within the parenthesis indicate steps in a sequence or parts in an explanation. [para], [mode] etc.: These indicate keys on the keyboard of this unit, and messages and menus that appear on the personal computer screen. >> : Indicates the result of an operation or the status after operation. Conventions Used in This Manual

z Numeric value and character display on LED

Numeric values The 7-segment LED expresses numeric values as follows: 0 1 2 3 4 5 6 7 8 9 Alphabetical characters The 7-segment LED expresses alphabetical characters shown below. There are some alphabetical characters, which are not displayed on the LED. A B C D E a b c d e F G H I J f g h i j K L M N O k l m n o P Q R S T p q r s t U V Y Z – u v y z Handling Precautions As shown above, numeric value “2” and alphabetic character “Z” are shown in the same manner. Accordingly, numeric value “5” and alphabetic character “S”, as well as numeric value “9” and alphabetic character “Q” are also shown in the same manner.

Do not use this device in an environment with conductive pollution, or with dry non-

conductive pollution which can become conductive due to condensation, etc. Otherwise, problems such as tracking phenomena may damage parts, resulting in fire. When wiring the power for this device, be sure to mount a shutoff switch for the main power to this unit within reach of the operator. In addition, when wiring the power for AC power models, install a time-lag (T) fuse (rated current 0.2 A, rated voltage 250 V) as specified by IEC 127. Otherwise, tracking phenomena or parts failure due to other factors may cause fire. Do not disassemble this device. Doing so might cause electric shock or faulty operation. Before removing, mounting, or wiring this device, be sure to turn off the power to the device and all connected devices. Failure to do so might cause electric shock. Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock. CAUTION Use this device within the operating ranges recommended in the specifications (temperature, humidity, voltage, vibration, shock, mounting direction, atmosphere, etc.). Do not block ventilation holes. Doing so might cause fire or faulty operation. Wire this device properly according to predetermined standards. Also wire the device using specified power leads according to recognized installation methods. Failure to do so might cause electric shock, fire or faulty operation. Do not allow lead clippings, metal shavings or water to enter the controller case. Doing so might cause fire or faulty operation. Firmly tighten the terminal screws at the torque listed in the specifications. Insufficient tightening of terminal screws might cause electric shock or fire. Do not use unused terminals on this device as relay terminals. Doing so might cause electric shock, fire, or faulty operation. We recommend attaching the terminal cover (sold separately) after wiring this device. Failure to do so might cause electric shock, fire, or faulty operation. Use the relays within the recommended life. Failure to do so might cause fire or faulty operation. If there is a risk of a power surge caused by lightning, use a surge absorber (surge protector) to prevent fire or device failure. Do not make incorrect connections. If the cables are connected incorrectly, this might cause the unit to malfunction. The controller does not function for approximately 6 s. after the power has been turned ON. Great care should be taken if the relayoutput from the controller is used as an interlock signal.

There is no isolation between control outputs 1 and 2. When necessary, use an appropriate

isolator. Do not connect multiple loader cables to multiple units from one personal computer. The current coming from other circuits might cause an error in the indication of the PV. When wiring RS-485 communications, do not connect a terminating resistor to either end of the communication path. A terminating resistor might cause a communication failure. Do not operate the keys with a mechanical pencil or other sharp-tipped object. Doing so might cause faulty operation. In addition to ON/OFF control and conventional PID control, this unit is equipped with self- tuning control, which does not require manual setting of control constants. Self-tuning control ensures stable control even after a change in the SP or an external disturbance. This is achieved by monitoring the control target, learning its characteristics, and automatically calculating control constants. Before Using This Unit The protective film is adhered to the front console of this unit to protect the surface. After the installation and wiring work has been completed, stick a scotch tape to the corner of the console and pull it out in the direction indicated by an arrow to peel off the protective film. Handling Precautions If you attempt to peel off the protective film with your fingernail, this might cause damage to the console. ot2 ot1 ev3 ev2 ev1 man rdy para mode Scotch tape Pull out

Five different manuals in total are available for model C15 Single Loop Controller (hereafter referred to as ”this

unit”). Read appropriate manuals according to your requirements. If you do not have a required manual, contact the azbil Group or its dealer. Additionally, you can download necessary manuals from https://www.azbil.com. The user level of this unit can be selected from three levels, “Simple configuration”, “Standard configuration”, and “High function configuration.” The functions you can set up only with “Simple configuration” are described in Single Loop Controller Model C15 User’s Manual for Basic Operation (CP-SP-1147E). If more advanced application is needed, refer to this manual. This manual is intended for personnel who have already read SDC15 Single Loop Controller User’s Manual for Basic Operation and/or operated Azbil Corporation’s Single Loop Controller to fully understand its basic operation. Single Loop Controller Model C15 User’s Manual for Installation & Configuration Manual No. CP-SP-1148E This manual. The manual describes the hardware and all functions of this unit. Personnel in charge of design, manufacture, operation, and/or maintenance of a system using this unit and those in charge of communication software of a system using the communication functions of this unit must thoroughly read this manual. This manual also describes the installation, wiring, connections for communication, all functions and settings of this unit, operating procedures, communication with host station, such as personal computer, communication addresses, troubleshooting, and detailed specifications. Single Loop Controller Model C15 User’s Manual for Installation Manual No. CP-UM-5287JE This manual is supplied with the product. Personnel in charge of design and/or manufacture of a system using this unit must thoroughly read this manual. This manual describes the safety precautions, installation, wiring, list of parameters, and primary specifications. For further information about operation, refer to other manuals, Basic Operation and/or Installation & Configuration. Single Loop Controller Model C15 User’s Manual for Basic Operation Manual No. CP-SP-1147E This manual is optional (sold separately). The manual describes the functions you can set up only with “Simple configuration”. Personnel in charge of design, manufacture, operation, and/or maintenance of a system using this unit must thoroughly read this manual. This manual describes the installation, wiring, major functions and settings, operating procedures, troubleshooting, and detailed specifications. User’s Manual for Smart Loader Package Model SLP-C35 for Single Loop Controller Model C15/25/26/35/36 Manual No. CP-UM-5290E This manual is supplied with the Smart Loader Package. The manual describes the software used to make various settings for C15/25/26/35/36 using a personal computer. Personnel in charge of design or setting of a system using C15/25/26/35/36 must thoroughly read this manual. The manual describes installation of the software into a personal computer, operation of the personal computer, various functions, and setup procedures. CP-SP-XXXXE Quick Reference Guide for Model XXX Quick Reference Guide for Model C15 Manual No. CP-UM-1213E For those using this device for the first time or for operators on the work site, this guide serves as a reference when setting or modifying parameters. Key operations, menu flowcharts and parameter settings are presented with color illustrations. The Role of This Manual

Organization of This User’s Manual

This manual is organized as follows: Chapter 1. OVERVIEW This chapter describes the applications, features, model selection guide, and part names and functions of this unit. Since the part names described in this chapter are used in the subsequent descriptions, the part names and functions of this unit must be understood correctly in this chapter. Chapter 2. OUTLINE OF FUNCTIONS This chapter describes the outline and operation flow of the functions of this unit. Chapter 3. INSTALLATION This chapter describes the environmental conditions, installation dimensions, installation procedures, and necessary tools when installing this unit. Chapter 4. WIRING This chapter describes the wiring procedures, wiring precautions, and connection examples. Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION This chapter describes each function of this unit in detail. Chapter 6. LIST OF DISPLAYS AND SETTING DATA This chapter lists up the display items of this unit and their contents. Chapter 7. CPL COMMUNICATIONS FUNCTIONS This chapter describes how to communicate this unit with a host unit, such as a personal computer or PLC through Azbil Corporation’s standard CPL communication using RS-485. Chapter 8. Modbus COMMUNICATIONS FUNCTIONS This chapter describes how to communicate this unit with a host unit, such as a personal computer or PLC through Modbus communication. Chapter 9. LIST OF COMMUNICATION DATA This chapter shows the list of communication data inside the memory of this unit. Chapter 10. MAINTENANCE AND TROUBLESHOOTING This chapter describes the maintenance and inspection of this unit, as well as troubleshooting. Chapter 11. CALIBRATION This chapter describes how to calibrate this unit in order to keep the accuracy and to safely operate this unit for an extended period of time. Chapter 12. DISPOSAL This chapter describes safety precautions and how to dispose of this unit when the unit is no longer used. Chapter 13. SPECIFICATIONS This chapter describes the general specifications, performance specifications, and optional parts of this unit.

Conventions Used in This Manual

Safety Precautions Before Using This Unit The Role of This Manual Organization of This User’s Manual Quick Reference Guide for Model C15 Chapter 1. OVERVIEW 1-1 1 - 1 Overview 1-1 � � Model selection table 1-2 � � Accessories 1-3 � � Optional parts 1-3 1 - 2 Part Names and Functions 1-4 � � Main unit and console 1-4 � � Bottom panel 1-5 � � Rear panel 1-6 Chapter 2. OUTLINE OF FUNCTIONS 2-1 2 - 1 Input/Output Configuration 2-1 2 - 2 Key Operation 2-2 � � Standard key operation type 2-2 � � Special key operation type 2-4 � � Data setting procedures 2-6 � � [mode] key operating procedures 2-7 � � User level 2-8 2 - 3 Operation Modes 2-9 Chapter 3. INSTALLATION 3-1 � � Installation place 3-1 � � External dimensions 3-2 � � Panel cutout dimensions 3-2 � � Mounting procedures 3-3 Chapter 4. WIRING 4-1 4 - 1 Wiring 4-1 � � Terminal assignment label symbols 4-2 � � Wiring precautions 4-2 � � Connection of open collector output to digital input 4-5 � � Connection of communication (RS-485) cable 4-5 � � Connection with solid state relay (SSR) 4-7 � � Connection with current-input type controllers 4-10 � � Noise preventive measures 4-10 4 - 2 Recommended Cables 4-11

DETAILED DESCRIPTION OF EACH FUNCTION

5-1 5 - 1 PV Input 5-1 � � PV input range type 5-1 � � Temperature unit 5-3 � � Cold junction compensation (T/C) 5-3 � � PV square root extraction dropout 5-3 � � Decimal point position 5-4 � � PV input range low limit/high limit 5-5 � � PV ratio and PV bias 5-5 � � PV low limit alarm threshold 5-5 � � PV filter 5-6 � � PV hold 5-6 � � PV low limit/high limit and PV low limit/high limit alarms 5-6 5 - 2 Mode 5-7 � � AUTO/MANUAL mode 5-7 � � RUN/READY mode 5-7 � � AT (Auto Tuning) stop/start 5-8 � � Release all DO (digital output) latches 5-8 � � Communication DI (digital input) 1 5-8 5 - 3 Control 5-9 � � Control method 5-11 � � Control action and Heat/Cool control 5-12 � � Special control outputs 5-12 � � MANUAL mode change 5-13 � � ON/OFF control 5-13 � � PID control 5-14 � � Heat/Cool control 5-15 � � ST (Self-tuning) 5-17 � � AT (Auto tuning) 5-18 � � Just-FiTTER 5-20 � � RationaLOOP 5-20 � � SP lag 5-20 5 - 4 AT (auto tuning) Function 5-21 � � Starting procedures 5-21 � � Stopping procedures 5-21 5 - 5 ST (Self-tuning) Function 5-24 � � How to start ST 5-24 � � How to stop ST 5-25 5 - 6 Precautions for ST (Self-tuning) 5-26 5 - 7 SP 5-27 � � SP setup in operation display mode 5-28 � � LSP system group 5-28 � � LSP1 to 4 5-28 � � LSP group number 5-28 � � DI Assignment of LSP group selection 5-29 � � SP ramp unit 5-30 � � SP up ramp/down ramp 5-30

� SP low limit/high limit

5-31 � � DI Assignment of SP ramp enabled/disabled 5-31 5 - 8 DI (Digital Input) and Internal Contact 5-32 � � Operation type 5-33 � � Internal event No. assignment 5-34 � � Input bit function 5-34 � � Input assign 5-35 � � Polarity of input assign 5-36 � � Polarity of input bit function 5-36 � � DI Assignment setting with Smart Loader Package SLP-C35 5-37 5 - 9 Internal Event 5-38 � � Operation 5-39 � � Operation type 5-46 � � Direct/reverse, standby, and EVENT state at READY 5-47 � � Alarm OR, special OFF setup, and delay time unit 5-48 � � Main setting, sub setting, and hysteresis 5-49 � � ON delay and OFF delay 5-50 5 - 10 DO (Digital Output) 5-51 � � MV1/MV2 process 5-52 � � Operation type 5-53 � � Output assign 5-54 � � Polarity of output assign 5-56 � � Polarity of output bit function 5-57 � � Latch 5-57 � � DO Assignment setting with Smart Loader Package SLP-C35 5-57 5 - 11 Application Examples 5-59 � � Examples of applications using assign functions 5-59 5 - 12 Continuous Output 5-66 � � Output range 5-66 � � Output type 5-66 � � Output scaling low limit/high limit 5-67 � � MV scaling range 5-68 5 - 13 CT (Current Transformer) Input 5-69 � � CT operation type 5-70 � � CT output 5-70 � � CT measurement wait time 5-70 � � Number of CT turns and number of CT power wire loops 5-71 5 - 14 Console Display and Key Operation 5-73 � � Key operation type 5-73 � � [mode] key function 5-73 � � MODE display setup 5-74 � � PV/SP display setup 5-75 � � MV display setup 5-76 � � Event setting value display setup 5-77 � � Event remaining time display setup 5-77 � � CT input current value display setup 5-78 � � User level 5-78 � � LED monitor 5-78

� User Function

5-79 � � Key lock, communication lock, and loader lock 5-83 � � Password 5-84 Chapter 6. LIST OF DISPLAYS AND SETTING DATA 6-1 6 - 1 List of Operation Displays 6-1 � � Operation displays 6-1 6 - 2 List of Parameter Setting Displays 6-3 � � Mode bank 6-3 � � SP bank 6-3 � � Event bank 6-4 � � PID bank 6-5 � � Parameter bank 6-6 � � Extended tuning bank 6-7 6 - 3 List of Setup Setting Displays 6-8 � � Setup bank 6-8 � � Event configuration bank 6-13 � � DI Assignment bank 6-16 � � DO Assignment bank 6-19 � � User Function bank 6-23 � � Lock bank 6-23 � � Instrument information bank 6-24 Chapter 7. CPL COMMUNICATIONS FUNCTIONS 7-1 7 - 1 Outline of Communications 7-1 � � Features 7-1 � � Setup 7-1 � � Communications procedures 7-2 7 - 2 Message Structure 7-3 � � Message structure 7-3 � � Data link layer 7-3 � � Application layer 7-5 7 - 3 Description of Commands 7-6 � � Continuous data read command (RS command) 7-6 � � Continuous data write command (WS command) 7-7 � � Fixed length continuous data read command (RD command) 7-8 � � Fixed length continuous data write command (WD command) 7-9 � � Fixed length random data read command (RU command) 7-10 � � Fixed length random data write command (WU command) 7-11 7 - 4 Definition of Word Addresses 7-12 7 - 5 Numeric Representation in the Application Layer 7-13 7 - 6 List of Termination Codes 7-14 7 - 7 Reception and Transmission Timing 7-15 � � Timing specifications for instruction and response message 7-15 � � RS-485 driver control timing specifications 7-15

7 - 8

Cautions when Making Communications Programs for the Master Station 7-16 � � Example of communications program 7-16 Chapter 8. Modbus COMMUNICATIONS FUNCTIONS 8-1 8 - 1 Outline of Communications 8-1 � � Features 8-1 � � Setup 8-1 � � Communications procedures 8-2 8 - 2 Message Structure 8-3 � � Message structure 8-3 � � Command type 8-6 � � Amount of data 8-6 � � Other specifications 8-6 8 - 3 Description of Commands 8-7 � � Read command (03H) 8-7 � � Write command (10H) 8-9 8 - 4 Specifications Common with CPL Communications Function 8-11 � � Definition of word addresses 8-11 � � Numeric representation 8-11 � � RS-485 driver control timing specifications 8-11 Chapter 9. LIST OF COMMUNICATION DATA 9-1 � � List of communication data 9-1 Chapter 10. MAINTENANCE AND TROUBLESHOOTING 10-1 � � Maintenance 10-1 � � Alarm displays and corrective action 10-1 � � Operation in case of PV input failure 10-2 Chapter 11. CALIBRATION 11-1 � � Starting the calibration 11-1 � � Exiting the calibration 11-1 � � Cautions before starting the calibration 11-2 � � Measuring instruments required for calibration 11-2 � � Calibration procedures 11-2 Chapter 12. DISPOSAL 12-1

Chapter 13. SPECIFICATIONS

13-1 � � Specifications 13-1 � � Accessories 13-5 � � Optional parts 13-5 Appendix App.-1 Glossary App.-1 Index

Quick Reference Guide for Model C15

This guide offers a summary of key operations, parameter flowcharts, and settings, for convenient reference at the operation site. This guide is made for repeated use. Dirt wipes off easily and even notes written with an oil-based felt-tip pen can be removed with an eraser. If more detailed information on model C15 is needed, refer to the user's manuals: CP-SP-1147E for basic operation and CP-SP-1148E for installation and configuration. The most convenient way to configure the C15 is with the Smart Loader Package (model No. SLP- C35J50). Please contact the azbil Group or a distributor for more information. Upper display Indicators during AT [para] key Mode indicators Lower display Various indicators Loader connector (bottom panel) [mode] key [ ], [ ], and [ ] keys Upper display This display shows either the PV value or the display value and set value for each displayed item. If an alarm is trig- gered, the normal display and alarm code are displayed alternately. During auto tuning (AT), the rightmost decimal point flashes twice repeatedly. Lower display This display shows either the SP/MV/CT or the display value and set value for each displayed item. The rightmost decimal point lights up or flashes to show RUN/READY mode or communications status, depending on the setting. Mode indicators rdy: Lights when READY (RUN mode if not lit) man: Lights when MANUAL (AUTO mode if not lit) ev1, ev2, ev3: Lights when event relays are ON ot1, ot2: Lights when the control output is ON (always lit when the current output is used) [mode] key • When this key is pressed and held for more than 1 second in the operation display mode, any of the following operations from 0 to 7 which have been set previously can be executed: 0 : Mode key does not operate (Initial value) 1 : AUTO/MANUAL mode selection 2 : RUN/READY mode selection 3 : AT (Auto Tuning) start/stop selection 4 : LSP (Local SP) group selection 5 : Release all DO (Digital Output) latches 6 : Mode key does not operate 7 : ON/OFF selection of communication DI1 • When pressing the [mode] key in the setup display mode, the display is changed to the operation display [para] key • This key is used to change the display item. • When this key is kept pressed for 2 s. or longer in the operation display mode, the display is then changed to the setup display [<], [ ] , [ ] keys Theses keys are used to increase or decrease the numeric value, or to shift the digit. Loader connector The Smart Loader connector is on the bottom of the C15. Use the dedicated cable that is included with the Smart Loader Package to connect the controller to a PC. : Initial value

For change from

MANUAL to AUTO to (2) (MANUAL) For change from AUTO to MANUAL to (1) [para] key *3 [mode] 2-second press + hold of [para] key [SP] [Event] [PID] [Parameter] [Extended tuning] (2) (1) Upper and lower displays remain off for 6s after power ON. Each mode indicator lights sequentially, and then the operation display appears. When the power is turned ON LSP group number SP value Manipulated variable MV value Heat manipulated variable MV value Cool manipulated variable MV value PV value SP value Timer remaining time 3 Internal event 3 delay time *1 [para] key 2-second press + hold of [para] key [para] key *3 Flowchart of key operations and displays (A) to (A)

Key operations and displays

Setting displays Operation displays z Some items are not displayed depending on the availability of optional functions, model number, display setup (C73 to C78) and display level (C79). z Pressing [para] key while changing settings has the effect of canceling and moving to the next item. *1 The parameters and numerical values registered as user functions UF are displayed. *2 If no key is pressed for 3 minutes, the display automatically returns to (2) , PV display. *3 If the [<] key is pressed while holding down the [para] key, various displys/settings can be navigated in reverse order. *4 Cannot be selected if ROM version 1 (id02) of the instrument information bank is 2.26 or earlier. � Explanation of arrows [para] key : 2-second press + : hold of [para] key � Movement through each setup menu • [para] key Forward movement • [para] key + [<] key Backward movement Internal event 3 sub setting Setting value Internal event 3 main setting Setting value Timer remaining time 2 Internal event 2 delay time Internal event 2 sub setting Setting value Internal event 2 main setting Setting value [Setup] [Event configuration] [DI assignment] [DO assignment] [User function] [Instrument information] [Lock] [para] key PV value AT progress value Internal event 1 main setting Setting value CT1 Current value CT2 Current value Internal event 1 sub setting Setting value Timer remaining time 1 Internal event 1 delay time 2-second press + hold of [para] key *2 *4 to (2) (B) to (B) *4

Setup of PV input range type

1 Start from the opera- tion display (if nec- essary press [mode] once to get the op- eration display). If the sensor has not been wired or is discon- nected, an alarm for abnormal PV input (any one from AL0 1 to AL 1 1) may appear on the upper display. 2 Press and hold [para] for more than 2s to get the parameter setup display. a--M is shown on the upper display. In case of ON/OFF con- trol, r--r appears on the upper display. 3 Press and hold [para] for more than 2s again to get the setup setting display. The current set value for C0 1 (PV input range type) is displayed. 4 When the [<], [ ] or [ ] key is pressed, the rightmost digit on the lower dis- play flashes. If no key is pressed for more than 2s after changing to the desired value in the PV input range list, the display changes from flashing to continuously lit, and the displayed value is now set. Setup of event operation type In this example, the event 1 operation type is set to deviation high limit. 1 Start from the opera- tion display (if nec- essary press [mode] once to get the op- eration display). 2 Press and hold [para] for more than 2s to get the parameter setup display. a--M is shown on the upper display. 3 Press and hold [para] for more than 2s again to get the setup setting display. The current set value for C0 1 (PV input range type) is displayed. 4 Press [para] repeat- edly to get e 1.c 1 on the upper display. 0 is displayed on the lower display. 0 on the lower display indicates that the event operation type is set to "none." 5 When the [ ] or [ ] key is pressed, the rightmost digit on the lower display flashes. Change the flashing digit to 4 by pressing [ ] or [ ]. If no key is pressed for more than 2s, the displayed value is set and the display changes from flashing to continu- ously lit. 4 on the lower display indicates that the event operation type is set for deviation high limit. Similarly, use e2.C 1 to set the event 2 operation type, and use e3.C 1 for event 3. Red letters : Items before operation Blue letters : Items during operation Execution of auto tuning (AT) AT forces ON/OFF of the MV a number of times (a limit cycle) to calculate PID values. Check that this operation does not create any problems for the as- sociated equipment before executing AT. 1 Start from the opera- tion display (if nec- essary press [mode] once to get the op- eration display). 2 Press and hold [para] for more than 2s to get the parameter setup display. a--M is shown on the upper display. 3 Press [para] twice. The upper display says at and the lower display says at.Of. If the control method is ON/OFF control and if Bit 3 (AT stop/start display) of the mode display setup (C73) is set to "disabled: 0," nothing is displayed. 4 When [ ] or [ ] is pressed, at.Of flashes. Flashing occurs only in RUN and AUTO modes, if there is no PV input abnormality. Also, if "AT stop/start" is selected for DI assign- ment, the display does not blink and no change can be made. 5 [Press [ ] once. The lower display starts to flash at.On. 6 If no key is pressed for more than 2s, at.ON remains steadily lit and AT begins. During AT, the rightmost decimal point flashes twice repeatedly. (When AT is done, the light goes off and the new PID values go into effect.) During the AT process, if the mode is changed to READY or MANUAL, if PV input is faulty, or if a power failure occurs, AT stops automatically without changing the PID values. AT can also be stopped by changing the setting from At.ON to At.OF (return to step 3 above). Setup of SP value 1 Start from the opera- tion display (if nec- essary press [mode] once to get the op- eration display). 2 Check that the operation display is displaying the SP. (If not, press [para] repeatedly until the SP is displayed.) 3 When the [<], [ ] or [ ] key is pressed, the rightmost digit on the lower display flashes and the SP can be changed to the desired value. In this case, the flash- ing of the numerical value implies that it is not yet set. A nu- merical setting that is being changed flashes the same way. If an SP limit is in effect, the numerical value cannot be changed to a value above the limit. The SP limit must be changed first. 4 If no key is pressed for more than 2s, the displayed value is set and the display changes from flash- ing to continuously lit. If the [mode] key is pressed when the display is flashing, the status returns to that of step 1.

For step numbers indicated in red like 4 , the following precaution applies:

• If the key lock is set, the numerical value does not flash, and the value cannot be changed. To change a numerical value, cancel the key lock first. RUN/READY mode selection 1 Start from the opera- tion display (if neces- sary press [mode] once to get the op- eration display). 2 Press and hold [para] for more than 2s to get the parameter setup display. a--M is shown on the upper display. In case of ON/OFF con- trol, r--r appears on the upper display. 3 Press the [para] key once. The upper dis- play says r--r and the lower display says rdy (or run). The current mode is in- dicated by run for RUN mode or rdy for READY mode. 4 When [ ] or [ ] is pressed, the lower display flashes. If the DI assignment is set to "RUN/READY se- lection," the display does not flash and no change can be made. 5 When [ ] or [ ] is pressed, run (or rdy) on the lower display flashes. 6 If no key is pressed for more than 2s, the displayed value is set and the display changes from flash- ing to continuously lit. Setup of PID value 1 Start from the opera- tion display (if neces- sary press [mode] once to get the op- eration display). 2 Press and hold [para] for more than 2s to get the parameter setup display. a--M is shown on the upper display. 3 Press [para] repeat- edly to get p-1 (for proportional band) on the upper display. The value set for p-1 is displayed on the lower display. If the control method is "ON/OFF control," noth- ing is displayed. 4 When [<], [ ] or [ ] is pressed, the right- most digit on the lower display flashes, and can be changed to the desired value for the proportional band. In this case, the flash- ing of the numerical value implies that it is not yet set. A nu- merical setting that is being changed flashes the same way. The proportional band can be set in a range from 0.1 to 999.9%. 5 If no key is pressed for more than 2s, the displayed value is set and the display changes from flashing to continuously lit. If the [mode] key is pressed when the display is flashing, the status re- turns to that of step 1. Similarly, use i-1 to set the integral time (0 to 9999s), and d-1 to set the derivative time (0 to 9999s). Setup of event value 1 Start from the opera- tion display (if neces- sary press [mode] once to get the op- eration display). 2 Press and hold [para] for more than 2s to get the param- eter setup display. a--M is shown on the upper display. 3 Press [para] repeat- edly to get e 1 on the upper display. The lower display says 0. 0 on the lower display indicates that the event main set value is "zero." 4 When [<], [ ] or [ ] is pressed, the rightmost digit on the lower display flashes, and can be changed to the de- sired value for the event. In this case, the flashing of the numerical value implies that it is not yet set. A numerical set- ting that is being changed flashes the same way. 5 If no key is pressed for more than 2s, the displayed value is set and the display changes from flashing to continu- ously lit. If the [mode] key is pressed when the display is flashing, the status returns to that of step 1. Similarly, use e2 to set a value for event 2, and e3 to set a value for event 3. 6 To set hysteresis as well, press [para] once (or twice, depending on the settings) to display e 1.hy on the upper display. The lower display says 5. 5 on the lower display indicates that the cur- rent set value for event hysteresis is 5. 7 When [<], [ ] or [ ] is pressed, the rightmost digit on the lower display flashes, and can be changed to the desired value for hysteresis. If no key is pressed for more than 2s, the displayed value is set and the dis- play changes from flashing to continu- ously lit. Similarly, use e2.hy to set a hysteresis value for event 2, and e3.hy to set a hysteresis value for event 3. Memo

List of parameters

List of operation displays Display Upper display: PV Lower display: SP Item Contents Initial value Setting value PV SP SP (Target value) SP low limit to SP high limit 0 LSP 1 (Display example) LSP LSP No. (1st digit: Value at the right end digit) 1 to LSP system group (Max. 4) 1 Out MV MV (Manipulated Variable) -10.0 to +110.0% Setting is enabled in MANUAL mode (Numeric value flashed) – HEAt Numeric value Heat MV (Manipulated Variable) Setting is disabled. -10.0 to +110.0% – COOL Numeric value Cool MV (Manipulated Variable) – PV At 1 (Display example) AT progress display (1st digit=Numeric value at right end digit) Setting is disabled. – Ct 1 Numeric value CT current value 1 Setting is disabled. – Ct2 Numeric value CT current value 2 Setting is disabled. – E 1 Numeric value Internal Event 1 main setting -1999 to +9999U or 0 to 9999U 0 E 1.Sb Numeric value Internal Event 1 sub setting 0 t 1.--(Display example) Numeric value Timer remaining time 1 Setting is disabled. Upper display: The distinction by ON delay or OFF delay is displayed at the side location of “t1.”. – E2 Numeric value Internal Event 2 main setting Same as Internal Event 1 main setting 0 E2.Sb Numeric value Internal Event 2 sub setting Same as Internal Event 1 sub setting 0 t2.--(Display example) Numeric value Timer remaining time 2 Same as Timer remaining time 1 – E3 Numeric value Internal Event 3 main setting Same as Internal Event 1 main setting 0 E3.Sb Numeric value Internal Event 3 sub setting Same as Internal Event 1 sub setting 0 t3.--(Display example) Numeric value Timer remaining time 3 Same as Timer remaining time 1 – List of parameter setting displays MOdE [Mode bank] Display Item Contents Initial value Setting value A--M AUTO/MANUAL AUTO: AUTO mode MAN: MANUAL mode AUTO r--r RUN/READY RUN: RUN mode RDY: READY mode RUN At AT stop/start At.OF: AT stop At.ON: AT start AT stop dO.Lt Release all DO latches Lt.ON: Latch continue Lt.OF: Latch release Latch continue C.dI 1 Communication DI1 dI .OF: OFF dI .On: ON OFF SP [SP bank] Display Item Contents Initial value Setting value SP- 1 to SP-4 SP (for LSP1 to 4) SP low limit to SP high limit 0 Ev [Event bank] Display Item Contents Initial value Setting value E 1 to E5 Internal Event 1 to 5 main setting -1999 to +9999 or 0 to 9999 * 0 E 1.Sb to E5.Sb Internal Event 1 to 5 sub setting 0 E 1.Hy to E5.Hy Internal Event 1 to 5 hysteresis 0 to 9999 * 5 E 1.On to E5.On z Internal Event 1 to 5 ON delay time 0.0 to 999.9 or 0 to 9999 0 E 1.OF to E5.OF z Internal Event 1 to 5 OFF delay time 0 * The decimal point position varies by meeting the internal event operation type. PI D [PID bank] Display Item Contents Initial value Setting value P- 1 Proportional band (PID1) 0.1 to 999.9% 5.0 I - 1 Integration time (PID1) 0 to 9999s (No integration control action when set at "0") 120 d- 1 Derivative time (PID1) 0 to 9999s (No derivative control action when set at "0") 30 rE- 1 Manual reset (PID1) -10.0 to +110.0% 50.0 OL- 1 z MV low limit (PID1) -10.0 to +110.0% 0.0 OH- 1 z MV high limit (PID1) -10.0 to +110.0% 100.0 P- 1C Cool-side proportional band (PID1) 0.1 to 999.9% 5.0 I - 1C Cool-side integration time (PID1) 0 to 9999s (No integration control action when set at "0") 120 d- 1C Cool-side derivative time (PID1) 0 to 9999s (No derivative control action when set at "0") 30 OL. 1C z Cool-side MV low limit (PID1) -10.0 to +110.0% 0.0 OH. 1C z Cool-side MV high limit (PID1) -10.0 to +110.0% 100.0 PARA [Parameter bank] Display Item Contents Initial value Setting value Control CtrL Control method 0: ON/OFF control 1: Fixed PID 2: ST(Self-tuning) 0 or 1 At. OL MV low limit at AT -10.0 to +110.0% 0.0 At. OH MV high limit at AT -10.0 to +110.0% 100.0 dI FF ON/OFF control differential 0 to 9999U 5 OFFS z ON/OFF control operating point offset -1999 to +9999U 0 PV FL PV filter 0.0 to 120.0s 0.0 rA z PV ratio 0.001 to 9.999 1.000 bI PV bias -1999 to +9999U 0 Time proportional output CyU z Time proportional cycle unit 1 0 to 3 *1 0 Cy Time proportional cycle 1 5 to 120s or 1 to 120s *2 10 or 2 CyU2 z Time proportional cycle unit 2 0 to 3 *1 0 Cy2 Time proportional cycle 2 5 to 120s or 1 to 120s *2 10 or 2 tP. ty z Time proportional cycle mode 0: Controllability aiming type 1: Operation end service life aiming type (Only ON/ OFF operation within Time proportional cycle) 0 or 1 SP SPU z SP up ramp (U/min) 0.0 to 999.9U(No ramp when set at "0.0U") 0.0 SPd z SP down ramp (U/min) 0.0 *1 0: Unit of "1s" 1: Fixed at 0.5s 2: Fixed at 0.2s 3: Fixed at 0.1s *2 5 to 120s when output includes the relay output U: Unit Maximum unit of Industrial volume in PV range (°C, Pa,L/min, etc.) : Essential parameters for PV measurement and control : Basic parameters : Required parameters when using optional functions Et [Extended tuning bank] Display Item Contents Initial value Setting value At.ty AT type 0: Normal 1: Immediate response 2: Stable *1 1 JF.bd z Just-FiTTER setting band 0.00 to 10.00 0.30 SP.LG z SP lag constant 0.0 to 999.9 0.0 At-P z AT Proportional Band adjust 0.00 to 99.99 1.00 At-I z AT Integral time adjust 0.00 to 99.99 1.00 At-d z AT Derivative time adjust 0.00 to 99.99 1.00 Ctr.A z Control algorithm 0: PID(Conventional PID) 1: Ra-PID(High-performance PID) 0 JF.Ov z Just-FiTTER assistance coefficient 0 to 100 0 St.SA z ST step execution resolution band 0.0 to 99.99 10.0 St.Sb z ST step setting band 0.0 to 10.00 0.50 St.Hb z ST hunting setting band 0.0 to 10.00 1.00 St.ud z ST step ramp change 0: ST is executed when the PV moves up or down. 1: ST is executed only when the PV moves up. 0 *1 Normal = Standard control characteristics, Immediate response = Control characteristics that respond immediately to external disturbance, Stable = Control characteristics having less up/down fluctuation of PV List of setup setting displays StUP [Setup bank] Display Item Contents Initial value Setting value Analog input C0 1 PV input range type For details, refer to the PV Input Range Table Depending on Model No. C02 Temperature unit 0: Celsius (°C) 1: Fahrenheit (°F) 0 C03 z Cold junction compensation 0: Performed (internal) 1: Not performed (external) 0 C04 Decimal point position 0: No decimal point 1 to 3: 1 to 3 digits below decimal point *1 0 C05 PV range low limit When the PV input type is DC voltage/DC current, -1999 to +9999U 0 C06 PV range high limit 1000 C07 z SP low limit PV input range low limit to PV input range high limit – C08 z SP high limit – C09 z PV square root extraction dropout 0.0 to 100.0% (PV square root extraction is not performed when set at "0.0".) 0.0 Control action C 13 z PID calculation adjustment function *2 0: Enabled 1: Disabled 0 C 14 Control action (Direct/Reverse) 0: Heat control (Reverse action) 1: Cool control (Direct action) 0 C 15 z Output operation at PV alarm 0: Control calculation is continued. 1: Output at PV alarm is output. 0 C 16 z Output at PV alarm -10.0 to +110.0% 0.0 C 17 z Output at READY (Heat) -10.0 to +110.0% 0.0 C 18 z Output at READY (Cool) -10.0 to +110.0% 0.0 C 19 z Output operation at changing AUTO/MANUAL 0: Bumpless transfer 1: Preset 0 C20 z Preset MANUAL value -10.0 to +110.0% 0.0 or 50.0 C2 1 z Initial output type (mode) of PID control 0: Auto 1: Not initialized 2: Initialized 0 C22 z Initial output of PID control -10.0 to +110.0% 0.0 or 50.0 C26 Heat/Cool control 0: Not used 1: Used 0 C27 z Heat/Cool 0: Normal 1: Energy saving 0 C28 Heat/Cool control dead zone -100.0 to +100.0% 0.0 C29 z Heat/Cool change point -10.0 to +110.0% 50.0 SP C30 LSP system group 1 to 4 1 C32 z SP ramp unit 0: 0.1U/s 1: 0.1U/min 2: 0.1U/h 1 C36 CT1 operation type 0: Heater burnout detection 1: Current value measurement 0 C37 CT1 output 0 to 1: Control output 1 to 2, 2 to 4: Event output 1 to 3 0 C38 CT1 measurement wait time 30 to 300ms 30 C39 CT2 operation type Same as CT1 0 C40 CT2 output Same as CT1 0 C4 1 CT2 measurement wait time Same as CT1 30 Continuous output C42 Control output 1 range 1: 4 to 20mA 2: 0 to 20mA 1 C43 Control output 1 type 0: MV 1: Heat MV 2: Cool MV 3: PV 4: PV before ratio, bias, and filter 5: SP 6: Deviation 7: CT1 current value 8: CT2 current value 10: SP+MV 11: PV+MV 0 C44 Control output 1 scaling low limit -1999 to +9999U 0.0 C45 Control output 1 scaling high limit 100.0 C46 Control output 1 MV scaling bandwidth 0 to 9999 (Valid when control output 1 type is 10 or 11) 200 C47 Control output 2 range Same as control output 1 1 C48 Control output 2 type Same as control output 1 3 C49 Control output 2 scaling low limit Same as control output 1 0 C50 Control output 2 scaling high limit Same as control output 1 1000 C5 1 Control output 2 MV scaling bandwidth Same as control output 1 200 Communication C64 Communication type 0: CPL 1: Modbus (ASCII format) 2: Modbus (RTU format) 0 C65 Station address 0 to 127 (Communication is disabled when set at "0".) 0 C66 Transmission speed (bps) 0: 4800 1: 9600 2: 19200 3: 38400 2 C67 Data format (Data length) 0: 7 bits 1: 8 bits 1 C68 Data format (Parity) 0: Even parity 1: Odd parity 2: No parity 0 C69 Data format (Stop bit) 0: 1 bit 1: 2 bits 0 C70 z Communication minimum response time 1 to 250ms 3 Key operation • display C7 1 z Key operation type 0: Standard type 1: Special type 0 C72 [mode] key function 0: Invalid 1: AUTO/MANUAL selection 2: RUN/READY selection 3: AT Stop/Start 4: LSP group selection 5: Release all DO latches 6: Invalid 7: Communication DI1 selection 8: Invalid 0 C73 z MODE display setup (Sum of the weighting) Bit 0: AUTO/MANUAL display (Enabled: +1) Bit 1: RUN/READY display (Enabled: +2) Bit 3: AT Stop/Start display (Enabled: +8) Bit 4: Release all DO latches display (Enabled: +16) Bit 5: Communication DI1 ON/OFF display (Enabled: +32) Other invalid setting, 0, +4, +64, +128 255 C74 z PV/SP display setup (Sum of the weighting) Bit 0: PV display (Enabled: +1) Bit 1: SP display (Enabled: +2) Bit 2: LSP group number display (Enabled: +4) Other invalid setting, 0, +8 15 C75 z MV display setup (Sum of the weighting) Bit 0: MV display (Enabled: +1) Bit 1: Heat MV/cool MV display (Enabled: +2) Bit 3: AT progress display (Enabled: +8) Other invalid setting: 0, +4 15 C76 z EV display setup (Operation display) 0: Not displayed 1: Set value of Internal event 1 is displayed 2: Set values of Internal event 1 to 2 are displayed 3: Set values of Internal event 1 to 3 are displayed 0 C77 z Event remaining time display setup (Operation display) 0: Not displayed 1: Internal event 1 is displayed 2: Internal event 1 to 2 is displayed 3: Internal event 1 to 3 is displayed 0 C78 z CT input current value display setup (Operation display) 0: Not displayed 1: CT1 current value is displayed 2: CT1 to 2 current values are displayed 0

Initial value Setting value

Key operation • display C79 User level 0: Simple configuration 1: Standard configuration 2: High function configuration 0 C80 z LED monitor 0: Not used 1: Flashing while data is sending through RS-485 communication. 2: Flashing while data is receiving through RS-485 communication 3: Logical OR of all DI statuses 4: Flashing in READY mode 0 C90 z Number of CT1 turns 0: 800 turns 1 to 40: CT turns divided by 100 8 C9 1 z Number of CT1 power wire loops 0: 1 time 1 to 6: Number of times 1 C92 z Number of CT2 turns 0: 800 turns 1 to 40: CT turns divided by 100 8 C93 z Number of CT2 power wire loops 0: 1 time 1 to 6: Number of times 1 C97 PV input failure (under range) type *2 0: -10 %FS 1: -5 mV (This setting is applicable if C01 (PV input range type) is set for sensor type B (No.17) or PR40-20 (No. 23)) 0 *1 Cannot be set for a thermocouple if ROM version 1 ( id02) of the instrument information bank is 2.26 or earlier. *2 Cannot be selected if ROM version 1 ( id02) of the instrument information bank is 2.26 or earlier. EvCF [Event configuration bank] Display Item Contents Initial value Setting value E 1.C 1 to E5.C 1 Internal event 1 to 5 Configuration 1 Refer to event type (see page 8) 0 E 1.C2 to E5.C2 Internal event 1 to 5 Configuration 2 The digits are determined to 1st, 2nd, 3rd, and 4th digit from the right end. 1st digit: Direct/Reverse 0: Direct 1: Reverse 0 2nd digit: Standby 0: None 1: Standby 2: Standby + Standby at SP change 0 3rd digit: EVENT state at READY 0: Continue 1: Forced OFF 0 4th digit: Undefined 0 0 E 1.C3 to E5.C3 z Internal event 1 to 5 Configuration 3 The digits are determined to 1st, 2nd, 3rd, and 4th digit from the right end. 1st digit: Alarm OR 0: None 1: Alarm direct + OR operation 2: Alarm direct + AND operation 3: Alarm reverse + OR operation 4: Alarm reverse + AND operation 0 2nd digit: Special OFF 0: As usual 1: When the event set value (main setting) is 0, the event is "OFF". 0 3rd digit: Delay time unit 0: 0.1s 1: 1s 2: 1min 0 4th digit: Undefined 0 0 di [DI assignment bank] Display Item Contents Initial value Setting value dI 1. 1 to dI 3. 1 Internal contact 1 to 3 Operation type 0: No function 1: LSP group selection (0/+1) 2: LSP group selection (0/+2) 3: LSP group selection (0/+4) 4: Invalid 5: Invalid 6: Invalid 7: RUN/READY selection 8: AUTO/MANUAL selection 9: LSP/RSP selection 10: AT Stop/Start 11: ST disabled/enabled 12: Control action direct/reverse 13: SP Ramp enabled/disabled 14: PV Hold 15: PV Maximum value hold 16: PV Minimum value hold 17: Timer Stop/Start 18: Release all DO latches (Continue/Release) 19: Invalid 20: Invalid 0 dI 1.2 to dI 3.2 z Internal contact 1 to 3 Input bit operation 0: Not used (Default input) 1: Function 1 ((A and B) or (C and D)) 2: Function 2 ((A or B) and (C or D)) 3: Function 3 (A or B or C or D) 4: Function 4 (A and B and C and D) 0 dI 1.3 to dI 3.3 z Internal contact 1 to 3 Input assignment A 0: Normally opened 1: Normally closed 2: DI1 3: DI2 4 to 9: Undefined 10 to 14: Internal Event 1to 5 15 to 17: Undefined 18 to 21: Communication DI1 to 4 22: MANUAL 23: READY 24: Undefined 25: AT running 26: During SP ramp 27: Undefined 28: Alarm occurs 29: PV alarm occurs 30: Undefined 31: mode key pressing status 32: Event output 1 status 33: Control output 1 status 2: Contact 1 3: Contact 2 4: Contact 3 dI 1.4 to dI 3.4 z Internal contact 1 to 3 Input assignment B 0 dI 1.5 to dI 3.5 z Internal contact 1 to 3 Input assignment C 0 dI 1.6 to dI 3.6 z Internal contact 1 to 3 Input assignment D 0 dI 1.7 to dI 3.7 z Internal contact 1 to 3 Polarity A to D The digits are determined to 1st, 2nd, 3rd and 4th digit from the right end. 1st digit: Polarity A 0: Direct 1: Reverse 0 2nd digit: Polarity B 0 3rd digit: Polarity C 0 4th digit: Polarity D 0 dI 1.8 to dI 3.8 z Internal contact 1 to 3 Polarity 0: Direct 1: Reverse 0 dI 1.9 to dI 3.9 z Internal contact 1 to 3 Internal event No. assignment 0: Every Internal Event 1 to 5: Internal Event No. 0 dO [DO assignment bank] Display Item Contents Initial value Setting value Ot 1. 1 to Ot2. 1 Ev 1. 1 to Ev3. 1 z Control output 1 to 2, event output 1 to 3 Operation type 0: Default output 1 to 2: MV1 to 2 3 to 6: Function 1 to 4 0 Ot 1.2 to Ot2.2 Ev 1.2 to Ev3.2 z Control output 1 to 2, event output 1 to 3 Output assign- ment A 0: Normally opened 1: Normally closed 2 to 6: Internal Event 1 to 5 7 to 13: Undefined 14 to 15: MV1 to 2 16 to 17: Undefined 18 to 19: DI1 to 2 20 to 25: Undefined 26 to 28: Internal Contact 1 to 3 29 to 33: Undefined 34 to 37: DI1 to 4 38: MANUAL 39: READY 40: Undefined 41: AT running 42: During SP ramp 43: Undefined 44: Alarm occurs 45: PV alarm occurs 46: Undefined 47: Mode key pressing status 48: Event output 1 status 49: Control output 1 status 14: Output 1 15: Output 2 2: Event 1 3: Event 2 4: Event 3 Ot 1.3 to Ot2.3 Ev 1.3 to Ev3.3 z Control output 1 to 2, event output 1 to 3 Output as- signment B 0 Ot 1.4 to Ot2.4 Ev 1.4 to Ev3.4 z Control output 1 to 2, event output 1 to 3 Output as- signment C 0 Ot 1.5 to Ot2.5 Ev 1.5 to Ev3.5 z Control output 1 to 2, event output 1 to 3 Output assign- ment D 0 Ot 1.6 to Ot2.6 Ev 1.6 to Ev3.6 z Control output 1 to 2, event output 1 to 3 Polarity A to D The digits are determined to 1st, 2nd, 3rd, and 4 th digit from the right end. 1st digit: Polarity A 0: Direct 1: Reverse 0 2nd digit: Polarity B 0 3rd digit: Polarity C 0 4the digit: Polarity D 0 Ot 1.7 to Ot2.7 Ev 1.7 to Ev3.7 z Control output 1 to 2, event output 1 to 3 Polarity 0: Direct 1: Reverse 0 Ot 1.8 to Ot2.8 Ev 1.8 to Ev3.8 z Control output 1 to 2, event output 1 to 3 Latch 0: None 1: Latch (Latch at ON) 2: Latch (Latch at OFF except for initialization at power ON) 0 UF [User function bank] Display Item Contents Initial value Setting value UF- 1 to UF-8 z User function 1 to 8 – – LOC [Lock bank] Display Item Contents Initial value Setting value LOC Key lock 0: All settings are possible 1: Mode, event, operation display, SP, UF, lock, manual MV, [mode] key can be set 2: Operation display, SP, UF, lock, manual MV, [mode] key can be set 3: UF, lock, manual MV, [mode] key can be set 0 C.LOC z Communication lock 0: read/write enabled 1: read/write disabled 0 L.LOC z Loader lock 0: read/write enabled 1: read/write disabled 0 PASS Password display 0 to 15 (5: Password 1A to 2B display) 0 PS 1A Password 1A 0000 to FFFF (Hexadecimal value) 0000 PS2A Password 2A 0000 to FFFF (Hexadecimal value) 0000 PS 1b Password 1B 0000 to FFFF (Hexadecimal value) 0000 PS2b Password 2B 0000 to FFFF (Hexadecimal value) 0000 I d [Instrument information bank] Display Item Contents Initial value Setting value I d0 1 z ROM ID 0: Fixed 0 I d02 z ROM Version 1 XX. XX (2 digits after decimal point) – I d03 z ROM Version 2 XX. XX (2 digits after decimal point) – I d04 z Loader information – I d05 z EST information – I d06 z Manufacturing date code (year) Subtract 2000 from the year. Example: "3" means the year 2003. – I d07 z Manufacturing date code (month, day) Month + day divided by 100. Example: "12.01" means the 1st day of December. – I d08 z Serial No. – Precaution for setup • The type of auto tuning can be changed by changing the value of At.ty (AT type) in the extended tuning bank. Set it to match the control characteristics. Memo Changing the user level This controller's user level can be set to 1 of 3 types in setup C79. The number of possible displays and settings decreases according to the user level: high function > standard > simple. All items are displayed when high function is selected. 1 If necessary press [mode] once to change to the op- eration display. Next, press and hold [para] for more than 2s to get the param- eter setup display. a--M or r--r ap- pears on the upper display. 2 Press and hold [para] for more than 2s again to display c0 1 on the upper display. 3 Press [para] repeat- edly to change the upper display to c79 (user level). 4 When [<], [ ] or [ ] is pressed, the lower display flashes and can be changed to the desired numeri- cal value. Then, if no key is pressed for more than 2s, the displayed value is set and the display changes from flash- ing to continuously lit. 0: Simple configuration (initial value) 1: Standard configuration 2: High function configuration • Items marked z in the tables are displayed in standard and/or high function configuration. • To change a user level, refer to Changing the user level in the lower right part of this page.

PV input range table

[Thermocouple] [RTD] C0 1 set value Sensor type Range (°C) Range (°F) C0 1 set value Sensor type Range (°C) Range (°F) 1 K -200 to +1200 -300 to +2200 41 Pt100 -200 to +500 -300 to +900 2 K 0 to 1200 0 to 2200 42 JPt100 -200 to +500 -300 to +900 3 K 0.0 to 800.0 0 to 1500 43 Pt100 -200 to +200 -300 to +400 4 K 0.0 to 600.0 0 to 1100 44 JPt100 -200 to +200 -300 to +400 5 K 0.0 to 400.0 0 to 700 45 Pt100 -100 to +300 -150 to +500 6 K -200.0 to +400.0 -300 to +700 46 JPt100 -100 to +300 -150 to +500 9 J 0.0 to 800.0 0 to 1500 51 Pt100 -50.0 to +200.0 -50 to +400 10 J 0.0 to 600.0 0 to 1100 52 JPt100 -50.0 to +200.0 -50 to +400 11 J -200.0 to +400.0 -300 to +700 53 Pt100 -50.0 to +100.0 -50 to +200 13 E 0.0 to 600.0 0 to 1100 54 JPt100 -50.0 to +100.0 -50 to +200 14 T -200.0 to +400.0 -300 to +700 63 Pt100 0.0 to 200.0 0 to 400 15 R 0 to 1600 0 to 3000 64 JPt100 0.0 to 200.0 0 to 400 16 S 0 to 1600 0 to 3000 67 Pt100 0 to 500 0 to 900 17 B 0 to 1800 0 to 3300 68 JPt100 0 to 500 0 to 900 18 N 0 to 1300 0 to 2300 [DC voltage/DC current] 19 PL II 0 to 1300 0 to 2300 20 WRe5-26 0 to 1400 0 to 2400 C0 1 set value Input type Range 21 WRe5-26 0 to 2300 0 to 4200 23 PR40-20 0 to 1900 0 to 3400 84 0 to 1 V The scaling and decimal point position can be changed variably in a range of –1999 to +9999 24 DIN U -200.0 to +400.0 -300 to +700 86 1 to 5 V 25 DIN L -100.0 to +800.0 -150 to +1500 87 0 to 5 V 88 0 to 10 V 89 0 to 20 mA Initial value 90 4 to 20 mA *1 • Accuracy for No. 17 (B thermocouple) is as follows. 260 °C or less: ±5 %FS. 260–800 °C: ±1 %FS. The PV values under 20 °C are not shown. However, if ROM version 1 (i d02) of the instrument information bank is 2.04 or earlier, the indicated low limi value is -180 °C. • Accuracy for No. 23 (sensor type PR40-20) is as follows. 300 °C or less: undefined. 300–800 °C: ±5 % FS. 800–1900 °C: ±2 % FS. However, if ROM version 1 (i d02) of the instrument informa- tion bank is 2.26 or earlier, No. 23 cannot be selected. *2 PL II thermocouple is a range, which has been added to the units manufactured from July, 2003. *3 The decimal point for thermocouples can be displayed if the ROM version is 2.26 or later. List of alarm codes Alarm code Failure name Cause Corrective action Input failure AL0 1 PV input failure (Over-range) Sensor burnout, incorrect wiring, incorrect PV input type setting Check the wiring. Set the PV input type again. AL02 PV input failure (Under-range) Sensor burnout, incorrect wiring, incorrect PV input type setting AL03 CJ failure Terminal temperature is faulty (thermocouple). Check the ambient temperature. PV input failure (RTD) Sensor burnout, incorrect wiring Check the wiring. AL 1 1 CT input failure (Over-range) (CT input 1 or 2, or both) A current exceeding the upper limit of the display range was measured. The number of CT turns or the number of CT power wire loops is incorrectly set, or wiring is incorrect. • Use a CT with the cor- rect number of turns for the display range. • Reset the number of CT turns. • Reset the number of CT power wire loops. • Check the wiring. Unit failure AL70 A/D conversion failure A/D converter is faulty. Replace the unit. AL95 Parameter failure Power is shut-down while the data is being set, or data is corrupted by noise. • Restart the unit. • Set the data again (set data for AL95/97 and adjustment data for AL96/98. • Replace the unit. AL96 Adjustment data failure Power is shut-down while the data is being set, or data is corrupted by noise. AL97 Parameter failure (RAM area) Data is corrupted by noise. AL98 Adjustment data failure (RAM area) Data is corrupted by noise. AL99 ROM failure ROM (memory) is faulty. • Reset the unit. • Replace the unit. Handling Precautions • If ROM version 1 (i d02) of the instrument information bank is 2.04 or earlier, CT input failure (AL 1 1) is not displayed. Event type Operation type Set value Direct action z: shows that the ON/OFF is changed at this value. z: shows that the ON/OFF is changed at a point that "1U" is added to this value. Reverse action z: shows that the ON/OFF is changed at this value. z: shows that the ON/OFF is changed at a point that "1U" is added to this value. No event 0 Always OFF Always OFF PV high limit 1 ON HYS Main setting PV ON HYS Main setting PV PV low limit 2 Main setting PV ON HYS Main setting PV ON HYS PV high/low limit 3 Main setting * Sub-setting * PV ON HYS ON HYS Main setting * Sub-setting * PV ON HYS HYS Deviation high limit 4 ON HYS SP + Main setting PV ON HYS SP + Main setting PV Deviation low limit 5 SP + Main setting PV ON HYS SP + Main setting PV ON HYS Deviation high/low limit 6 Main setting Sub-setting SP PV ON HYS ON HYS ON HYS HYS Main setting Sub-setting SP PV Deviation high limit (Final SP reference) 7 ON HYS SP + Main setting PV ON HYS SP + Main setting PV Deviation low limit (Final SP reference) 8 SP + Main setting PV ON HYS SP + Main setting PV ON HYS Deviation high/ low limit (Final SP reference) 9 Main setting Sub-setting SP PV ON HYS ON HYS ON HYS HYS Main setting Sub-setting SP PV Heater 1 burnout/ Over-current 16 CT1 at output ON Main setting * Sub-setting * ON HYS ON HYS ON HYS HYS Main setting * Sub-setting * CT1 at output ON OFF before measuring the CT1 current value OFF before measuring CT1 current value Heater 1 short-circuit 17 ON HYS Main setting CT1 at output OFF ON HYS Main setting CT1 at output OFF OFF before measuring CT1 current value OFF before measuring CT1 current value Heater 2 burnout/ Over-current 18 CT2 at output ON Main setitng * Sub-setting * ON HYS ON HYS ON HYS HYS Main setting * Sub-setting * CT2 at output ON OFF before measuring CT2 current value OFF before measuirng CT2 current value Heater 2 short-circuit 19 ON HYS Main setting CT2 at output OFF ON HYS Main setting CT2 at output OFF OFF before measuring CT2 current value OFF before measuring CT2 current value Alarm (status) 23 ON if alarm occurs (alarm code AL01 to 99). OFF in other cases. OFF if alarm occurs (alarm code AL01 to 99). ON in other cases. : initial value *: If the main setting is greater than the sub-setting, operations are performed with the main setting and sub-setting automatically swapped. Event types other than the above: Operation type Set value Operation type Set value Operation type Set value SP high limit 10 Loop diagnosis 1 20 During AT (status) 27 SP low limit 11 Loop diagnosis 2 21 During SP ramp 28 SP high/low limit 12 Loop diagnosis 3 22 Control action (status) 29 MV high limit 13 READY (status) 24 ST setting standby (status) 30 MV low limit 14 MANUAL (status) 25 Timer (status) 32 MV high/low limit 15

1 - 1

Overview This unit is a compact controller having a mask of 48 × 48 mm and provides the following features: • The depth is only 60 mm, providing the excellent space-saving. • The front panel is only 2 mm thick. This ensures the excellent thin design. • The display panel is large. This provides excellent visibility. • [mode] key, [para] key, and digit-shift keys are provided on the front panel. This ensures easy setup operation. • Various input types are available, thermocouples (K, J, E, T, R, S, B, N, PLII, WRe5-26, PR40-20, DIN U, DIN L), RTDs (Pt100, JPt100), current signals (4 to 20 mA DC, 0 to 20 mA DC), and voltage signals (0 to 1 V DC, 1 to 5 V DC, 0 to 5 V DC, and 0 to 10 V DC). • For control outputs, relay, voltage pulse, and current output are provided. Additionally, these control outputs can be combined for the 2nd control output. • The unit can be made applicable to the heat/cool control using the 2nd control output and/or event relay. • ON/OFF control, fixed PID, and self-tuning control can be performed. • In addition to the PID control, two algorithms, RationaLOOP and Just-FiTTER, are mounted. This ensures excellent controllability. • With optional functions, a combination among 3- or 2-event points (independent contacts), 2-point CT input, 2-point digital input, and/or RS-485 can be selected. • The personal computer loader port is provided as standard function. The setup can be made easily with use of the personal computer loader. • Use of optional Smart Loader Package (SLP-C35) makes it possible to easily perform the read/write operation of the parameters. In addition to the table format setup, the operation and control status can be monitored using the trend display. This unit can be operated without use of program on the host unit. • The unit is applicable to the IEC directive and the CE marking is put on the unit. (Applicable standards: EN61010-1 and EN61326-1)

Chapter 1. OVERVIEW

� � Model selection table The following shows the model selection table of this unit: Basic model No. Mounting Control output PV input Power supply Option Additional treatment Specifications 1 2 C15 T Panel mount type *1 S Socket mount type Control output 1 Control output 2 *2 R0 Relay contact output NO None (relay output for control output 1: NC) V0 Voltage pulse output (for SSR drive) None *3 VC Voltage pulse output (for SSR drive) Current output *3 VV Voltage pulse output (for SSR drive) Voltage pulse output (for SSR drive) C0 Current output None *3 CC Current output Current output T Thermocouple input (K, J, E, T, R, S, B, N, PL II, WRe5-26, PR40-20, DIN U, DIN L) R RTD input (Pt100/JPt100) L DC voltage/DC current input (0 to 1 V DC, 1 to 5 V DC, 0 to 5 V DC, 0 to 10 V DC, 0 to 20 mA DC, 4 to 20 mA DC) A AC Model (100 to 240 V AC) D DC Model (24 V AC/24 to 48 V DC) 00 None 01 Event relay output: 3 points *3 *4 02 Event relay output: 3 points Current transformer input: 2 points Digital input: 2 points *3 *4 03 Event relay output: 3 points Current transformer input: 2 points RS-485 communication *5 04 Event relay output: 2 points (independent contact) *3 *4 *5 05 Event relay output: 2 points (independent contact) Current transformer input: 2 points Digital input: 2 points *3 *4 *5 06 Event relay output: 2 points (independent contact) Current transformer input: 2 points RS-485 communication 0 No additional processing D Inspection Certificate provided *1 Socket sold separately Y Complying with the traceability certification *2 Only 1a contact is applicable for C15S 0 None *3 Can not be selected for the C15S. A UL-marked product *4 Current transformer sold separately *5 Can not be selected for the DC Model.

Chapter 1. OVERVIEW

� � Accessories Name Model No. Mounting bracket (for C15T) 81409651-001 Gasket 81409657-001 � � Optional parts Name Model No. Mounting bracket (for C15T) 81446403-001 Gasket (20 pcs) 81406918-001 Current transformer (800 turns, 5.8 mm hole dia.) QN206A* Current transformer (800 turns, 12 mm hole dia.) QN212A* Socket (for C15S) 81446391-001 Hard cover 81446442-001 Soft cover 81446443-001 Terminal cover 81446898-001 Smart Loader Package SLP-C35J50 L-shaped plug adaptor 81441057-001 * Not UL-certified.

Chapter 1. OVERVIEW

� � Main unit and console ot2 ot1 ev3 ev2 ev1 man rdy para mode Main unit Console rdy man ev1 ev2 ev3 ot1 ot2 para mode pv sp Lower Display Mode indicator [<], [ ], and [ ] keys < < [para] key Upper display [mode] key Console SDC15 Main unit: Contains the electric circuit for I/O signals of measuring instruments, CPU, and memory. Console: Contains the display panel showing numeric value and status, and operation keys. � z Detailed description of console [mode] key When this key is kept pressed for 1 s or longer in the operation display mode, any of the following operations, which have been set previously, can be performed: • AUTO/MANUAL mode selection • RUN/READY mode selection • AT (Auto Tuning) start/stop selection • LSP (Local SP) group selection • Release all DO (Digital Output) latches • ON/OFF selection of communication DI (Digital Input) 1 When pressing the [mode] key in the setup display mode, the display is changed to the operation display. [para] key This key is used to change the display item. When this key is kept pressed for 2 s or longer in the operation display mode, the display is then changed to the setup display. [<], [ < ], [ < ] keys These keys are used to increase or decrease the numeric value, or to shift the digit. 1 - 2 Part Names and Functions

Chapter 1. OVERVIEW

Upper display This display shows the PV value or the name of each display item (display value or set value). If an alarm occurs in the operation display mode, the normal display and alarm code are displayed alternately. The decimal point at the right end digit shows AT (auto tuning) or ST (self- tuning) status. The decimal point flashes twice repeatedly during execution of AT while it flashes once repeatedly during execution of ST. Lower display This display shows the SP value, or the display value or set value of each display item. The decimal point at the right end digit shows the communication status. Mode indicators [rdy]: RUN/READY mode indicator. Lights when READY [man]: AUTO/MANUAL mode indicator. Lights when MANUAL [ev1], [ev2], [ev3]: Event output 1 to 3 indicator. Lights when event relays are ON. [ot1], [ot2]: Control output 1 and 2 indicator. Lights when the control output is ON. The indicators are always lit when the current output is used. Handling Precautions • To select the LSP group using the [mode] key, it is necessary to set a value of “2” or more in [LSP system group]. • To show the communication status using the decimal point at the right end digit on the lower display, select “High function configuration” and make the [LED monitor] settings. • Do not operate the key with a sharp object (such as tip of mechanical pencil or needle). Doing so might cause the unit to malfunction. � � Bottom panel Loader connector Loader connector: This connector is connected to a personal computer using the dedicated cable supplied with the Smart Loader Package.

Chapter 1. OVERVIEW

� � Rear panel � z Model C15T (Panel mount type) Terminal part Terminal part: The power supply, input, and output are connected to the terminals. The M3 screw is used. When connecting to the terminal, always use a correct crimp terminal suitable for the M3 screw. The tightening torque of the terminal screw is 0.4 to 0.6 N·m. � z Model C15S (Socket mount type) Socket part Socket part: This socket is inserted into the optional socket. The power supply, input, and output are connected from the socket. When performing the wiring from the socket, always use a correct crimp terminal suitable for the M3.5 screw. The tightening torque of the socket terminal screw is 0.78 to 0.98 N·m.

Control output 1, 2

(Current output) Control output 1, 2 (Relay output, voltage pulse output) Event output 1 to 3 (Relay output) CT input 1, 2 Digital input 1, 2 PV input PV process Internal event process Control process (ON/OFF control, PID control) Other Other Internal contact process CT process � z PV input Sensor or range is selected for the PV input. The selection range may vary depending on the input type of the model (T: Thermocouple, R: RTD, L: DC current, DC voltage). � z Control output When the control output type of the model is “R: Relay” or “V: Voltage pulse”, the control output becomes the ON-OFF control output or time proportional output. When the time proportional output is used, the time proportioning cycle time can be set. When the control output type of the model is “C: Current”, the control output becomes the continuous output (analog output). When the model has two control outputs, the heat/cool control can be used only with "Simple configuration". � z Event output When the model provides the event, the alarm or control mode set in [Event type] can be output as DO (digital output). � z DI (digital input) When the model provides the DI, the function set with the DI assignments can be selected. � z CT (current transformer) input When the model provides the CT input, the heater burnout alarm can be output from the event output. Chapter 2. OUTLINE OF FUNCTIONS 2 - 1 Input/Output Configuration

Chapter 2. OUTLINE OF FUNCTIONS

Various displays or settings can be called up on the console through key operation. Two kinds of general key operation flows are provided, standard key operation type and special key operation type. A desired key operation type can be selected using the setup setting. • Standard key operation type: Key operation similar to that of the conventional model SDC10. • Special key operation type: A part of key operation of the conventional model SDC30 is added to that of the conventional model SDC10. The following describes the general flow of each key operation type: � � Standard key operation type When the key operation mode/type of the setup setting "C7 1" is set at "0", the standard key operation type is selected. The display and setting data of the standard key operation type are arranged as shown in the following tree-structure: Operation display Mode Setup PV and SP 5-75 AUTO/MANUAL 5-7 PV input range type 5-1 LSP group selection 5-29 RUN/READY 5-7 Temperature unit 5-3 MV 5-76 AT stop/start 5-8 Heat MV 5-76 Release all DO latches 5-8 User level 5-78 Cool MV 5-76 Communication DI 1 5-8 Communication monitor display 5-78 AT progress 5-76 CT input 1 current value 5-78 SP Event configuration CT input 2 current value 5-78 LSP1 group SP 5-28 Internal Event 1 Configuration 1 5-46 Internal Event 1 main setting 5-49 LSP2 group SP 5-28 Internal Event 1 Configuration 2 5-47 Internal Event 1 sub setting 5-49 LSP3 group SP 5-28 Internal Event 1 remain time 5-77 LSP4 group SP 5-28 Internal Event 5 Configuration 2 5-47 Internal Event 2 main setting 5-49 Internal Event 5 Configuration 3 5-48 Internal Event 2 sub setting 5-49 Event Internal Event 2 remain time 5-77 Internal Event 1 main setting 5-49 DI Assignment Internal Event 3 main setting 5-49 Internal Event 1 sub setting 5-49 Internal Contact 1 Operation type 5-33 Internal Event 3 sub setting 5-49 Internal Event 1 hysteresis 5-49 Internal Contact 1 Input bit function 5-34 Internal Event 3 remain time 5-77 Internal Event 5 ON delay 5-50 Internal Contact 3 Polarity 5-36 User Function (Utilization) Internal Event 5 OFF delay 5-50 Internal Contact 3 Internal event No. assignment 5-34 User Function 1 5-79 User Function 2 5-79 PID DO Assignment User Function 3 5-79 P (Proportional band) 5-14 Control output 1 Operation type 5-53 User Function 4 5-79 I (Integration time) 5-14 Control output 1 Output assignment A 5-53 User Function 5 5-79 D (Derivative time) 5-14 User Function 6 5-79 Manual reset 5-14 Event output 3 Polarity 5-57 User Function 7 5-79 Event output 3 Latch 5-57 User Function 8 5-79 Output low limit (Cool) 5-14 Output high limit (Cool) 5-14 User Function User Function 1 5-79 Parameter User Function 2 5-79 Control method 5-11 MV low limit at AT 5-18 User Function 7 5-79 MV high limit at AT 5-18 User Function 8 5-79 ON/OFF control differential 5-13 Lock SP up ramp 5-30 Key lock 5-83 SP down ramp 5-30 Communication lock 5-83 Extended tuning Password 1B 5-84 AT type 5-18 Password 2B 5-84 Just-FiTTER settling band 5-20 SP lag constant 5-20 Instrument information ROM ID 6-24 ST step settling band 5-17 ROM version 1 6-24 ST hunting settling band 5-17 ST step ramp change 5-17 Manufacturing date code (month, day) 6-24 Serial No. 6-24 Note. The figures shown on the right of the display and setting columns in the tree-structure indicate the relevant pages. 2 - 2 Key Operation

Chapter 2. OUTLINE OF FUNCTIONS

Display when the power is turned ON. Keep the [para] key pressed for 2 s or longer. PV/SP display Press the [para] key. MV display Other display and setup (Operate the [para] key repeatedly.) Press the [para] key. Press the [para] key. AUTO/MANUAL selection Press the [para] key. RUN/READY selection Other display and setup (Operate the [para] key repeatedly.) Press the [para] key. Press the [para] key. Operation display Press the [mode] key. Keep the [para] key pressed for 2 s or longer. Of. The mode indicator is lit sequentially from the left. Of. No key operation for 3 min or more. No key operation for 3 min or more. Keep the [para] key pressed for 2 s or longer. Press the [mode] key. mode pv sp mode pv sp mode pv sp mode pv sp mode pv sp mode pv sp rdy man ev1 ev2 ev3 ot1 ot2 para mode pv sp The mode indicators are lit sequentially from the left during a period of 6 s. after the power has been turned ON while both the upper display and lower display are of. When all mode indicators have been lit, the display is changed to the operation display. Parameter setup display PV range type setup Press the [para] key. Temperature unit setup Other display and setup (Operate the [para] key repeatedly.) Press the [para] key. Press the [para] key. Setup setting display The display and setup status shown above are examples for explanation. Therefore, some displays or settings are not shown actually according to the model and/or setup contents. Handling Precautions • For details about display and setup contents of the operation display, parameter setting display, and setup setting display: 6 - 1 List of Operation Displays (p. 6-1) 6 - 2 List of Parameter Setting Displays (p. 6-3) 6 - 3 List of Setup Setting Displays (p. 6-8) • When pressing the [<] key with the [para] key kept pressed instead of pressing of the [para] key, various displays and settings can be operated in the reverse order. However, the operation that both the [para] key and [<] key are kept pressed for 2 s or longer, is invalid.

Chapter 2. OUTLINE OF FUNCTIONS

� � Special key operation type When the key operation mode/type of the setup setting "C7 1" is set at "1", the special key operation type is selected. The display and setting data of the special key operation type are arranged as shown in the following tree-structure: Operation display Bank selection PV and SP 5-75 Mode Mode bank LSP group selection 5-29 SP AUTO/MANUAL 5-7 MV 5-76 Event RUN/READY 5-7 Heat MV 5-76 PID AT stop/start 5-8 Cool MV 5-76 Parameter Release all DO latches 5-8 AT progress 5-76 Extension tuning Communication DI 1 5-8 CT input 1 current value 5-78 Set up CT input 2 current value 5-78 Event configuration SP bank Internal Event 1 main setting 5-49 DI assignment LSP1 group SP 5-28 Internal Event 1 sub setting 5-49 DO assignment LSP2 group SP 5-28 Internal Event 1 remain time 5-77 Users function LSP3 group SP 5-28 Internal Event 2 main setting 5-49 Lock LSP4 group SP 5-28 Internal Event 2 sub setting 5-49 Instrument information Internal Event 2 remain time 5-77 Various bank Internal Event 3 main setting 5-49 Internal Event 3 sub setting 5-49 Internal Event 3 remain time 5-77 Lock bank Key lock 5-83 User Function (Utilization) Communication lock 5-83 User Function 1 5-79 User Function 2 5-79 Password 1B 5-84 User Function 3 5-79 Password 2B 5-84 User Function 4 5-79 User Function 5 5-79 Instrument information bank User Function 6 5-79 ROM ID 6-24 User Function 7 5-79 ROM version 1 6-24 User Function 8 5-79 Manufacturing date code (month, day) 6-24 Serial No. 6-24 Note. The figures shown on the right of the display and setting columns in the tree-structure indicate the relevant pages.

Chapter 2. OUTLINE OF FUNCTIONS

Display when the power is turned ON. Keep the [para] key pressed for 2 s or longer. PV/SP display Press the [para] key. MV display Other display and setup (Operate the [para] key repeatedly.) Press the [para] key. Press the [para] key. Mode bank selection SP bank selection Operation display Press the [mode] key. Press the [<] key. Of. The mode indicator is lit sequentially from the left. Of. No key operation for 3 min or more. No key operation for 3 min or more. Press the [mode] key. mode pv sp mode pv sp mode pv sp mode pv sp mode pv sp mode pv sp rdy man ev1 ev2 ev3 ot1 ot2 para mode pv sp The mode indicators are lit sequentially from the left during a period of 6 s after the power has been turned ON while both the upper display and lower display are of. When all mode indicators have been lit, the display is changed to the operation display. Bank selection PV range type setup Press the [para] key. Temperature unit setup Other display and setup (Operate the [para] key repeatedly.) Press the [para] key. Press the [para] key. Bank setting display The display and setup status shown above are examples for explanation. Therefore, some displays or settings are not shown actually according to the model and/or setup contents. Keep the [para] key pressed for 2 s or longer. Press the [para] key. Press the [ ] or [ ] key. < < Press the [para] key. Press the [ ] or [ ] key. < < Press the [para] key. Press the [ ] or [ ] key. < < Other banks (Operate the [para] key and the [ ] or [ ] key repeatedly.) < < Handling Precautions • For details about display and setup contents of the operation display, bank selection display, and bank setting display: 6 - 1 List of Operation Displays (p. 6-1) 6 - 2 List of Parameter Setting Displays (p. 6-3) 6 - 3 List of Setup Setting Displays (p. 6-8) In the lists shown above, a bank belonging to each setting item is described. • When pressing the [<] key with the [para] key kept pressed instead of pressing of the [para] key in the operation display or setting item display mode, various displays and settings can be operated in the reverse order. However, the operation becomes invalid that both the [para] key and [<] key are kept pressed for 2 s or longer.

Chapter 2. OUTLINE OF FUNCTIONS

� � Data setting procedures (1) Operate the [para] key to display desired data to be set. (How to operate the [para] key is described in the previous section, "Flow of general key operation".) mode pv sp mode pv sp (This Figure shows the display when setting the PV range type of the setup setting [C0 1].) (This Figure shows the display when setting the RUN/Ready selection in the parameter setting [r...r].) (2) Press any of the [<], [ < ], and [ < ] keys. >> When the lower display shows a numeric value, the 1st digit starts flashing. Additionally, when the lower display shows a character string, the entire character string starts flashing. When a numeric value is displayed, the value can be increased or decreased or the flashing digit can be moved using the [<], [ < ], or [ < ] key. When a character string is displayed, the entire flashing character string can be changed using the [ < ] or [ < ] key. mode pv sp mode pv sp (This Figure shows the display when the 1st digit of "000 1" is fashing.) (This Figure shows the display when the entire character string "rUn" is fashing.) (3) Release the key and wait for a while. >> After 2 s have elapsed, the flashing display is stopped, and then the data you have changed is set. mode pv sp mode pv sp Handling Precautions • If the data does not start flashing even though the [<], [ < ], or [ < ] key is pressed, this data cannot be changed. For example, when the RUN/READY is assigned in the DI Assignment, RUN/READY cannot be selected using the key on the front panel.

Chapter 2. OUTLINE OF FUNCTIONS

• If the character string cannot be changed using the [ < ] key while the entire character string is flashing, press the [ < ] key. On the contrary, if the character string cannot be changed using the [ < ] key, press the [ < ] key. • When pressing the [para] key while the display is flashing, the next data is displayed without changing of the data. Additionally, when pressing the [mode] key while the display is flashing, the display is returned to the operation display without changing of the data. • The MV (manipulated variable) display in the MANUAL mode continues the flashing status even after pressing of the key has been stopped. At this time, the flashing value is output as MV. � � [mode] key operating procedures When the [mode] key is kept pressed for 1 s or longer on the operation display, the selection operation, which has been set using the [mode] key function (C72) of the setup setting, can be performed. The Figure on the right shows an example that the [mode] key is pressed in the RUN/READY selection (C72 = 2) setting. (1) If the current mode is the READY mode when the PV/SP is shown on the operation display, the character string "rUn" on the lower display starts flashing. (2) When the [mode] key is kept pressed for 1 s or longer, the READY mode is changed to the RUN mode and the flashing of the character string "rUn" is stopped. (3) When pressing of the [mode] key is stopped, the display is returned to the PV/SP display. mode pv sp mode pv sp mode pv sp Handling Precautions • If the MODE key function of the setup setting is set disabled (C72 = 0) or if the set selection operation is invalid, the selection operation cannot be performed using the [mode] key. • When pressing the [mode] key on the parameter setting display or setup setting display instead of the operation display, the display is returned to the operation display. However, even though the [mode] key is kept pressed continually, the selection operation cannot be performed. In this case, stop pressing the key once, and then press the [mode] key.

Chapter 2. OUTLINE OF FUNCTIONS

� � User level The user level of this unit can be selected from three levels, "Simple configuration", "Standard configuration", and "High function configuration" using the user level of the setup setting "C79". Chapter 6. LIST OF DISPLAYS AND SETTING DATA Handling Precautions Even though the user level is changed, the functions other than setting display cannot be changed. The user level is set to "Standard configuration" or "High function configuration" and more advanced functions are set. After that, when the setup is returned to "Simple configuration", this function setup cannot be displayed, but the function itself is operated.

Chapter 2. OUTLINE OF FUNCTIONS

The following shows the transition of operation modes: AT stop ST stop AT stop ST stop AT stop ST stop AT stop ST stop AT running ST running RUN + MANUAL mode AUTO/MANUAL selection AUTO/MANUAL selection RUN + AUTO mode READY + AUTO mode RUN + MANUAL mode RUN/READY selection RUN/READY selection RUN: Control status READY: Control stop status AUTO: Automatic operation (This unit automatically determines the MV values.) MANUAL: Manual operation (The MV values are operated manually.) AT: Auto tuning (The PID constants are set automatically using the limit cycle.) ST: Self-tuning (The PID constants are set automatically while the control is kept continuously.) 2 - 3 Operation Modes

Use this device within the operating ranges recommended in the specifications (temperature,

humidity, voltage, vibration, shock, mounting direction, atmosphere, etc.). Failure to do so might cause fire or faulty operation. Do not block ventilation holes. Doing so might cause fire or faulty operation. � � Installation place Install the controller in the following locations: • With the exception of supply power and relay contact output, the I/O common mode voltage to ground must be 30 Vrms max., 42.4 V peak max., 60 V DC max. • Not high or low temperature/humidity. • Free from silicone gas and other corrosive gases such as sulfide gas. • Less dust or soot. • Appropriately processed locations to prevent direct sunlight, wind or rain. • Less mechanical vibration and shock. • Not close to the high voltage line, welding machine or electrical noise generating source. • The minimum 15 m away from the high voltage ignition device for a boiler. • Less effect by the magnetic. • No flammable liquid or gas. • Indoors.

Chapter 3. INSTALLATION

� � External dimensions � z Model C15T (Panel Mount type) Unit: mm 59 60 2 44.8 48 48 rdy man ev1 ev2 ev3 ot1 ot2 para mode SDC15 pv sp Mounting bracket (Accessory) Terminal screw M3 � z Model C15S (Socket Mount type) Terminal screw M3.5 2- M4 Mounting hole 48 48 40 51 71 3.4 74.2 61.2 26.5 31 rdy man ev1 ev2 ev3 ot1 ot2 para mode SDC15 pv sp 1 2 3 4 5 6 7 8 9 10 11 Socket Stopper Socket 81446391-001 (sold separately) � � Panel cutout dimensions For panel mounting type, make the mounting holes according to the panel hole making dimensions. Unit: mm 0 45 +0.5 50 min. 0 45+0.5 30 min. 0 +0.5 (48xN -3) 0 +0.5 45 ("N" shows the number of mounting units.) Stand-alone mounting Gang-mounting Handling Precautions • When three or more units are gang-mounted horizontally, the maximum allowable ambient temperature is 40 °C. • Provide a space of at least 50 mm or more above and below the controller. • If dustproof or waterproof protection is required, mount the device using the individual mounting method. If gangmounted, dustproof and waterproof protection may not be maintained.

Chapter 3. INSTALLATION

� � Mounting procedures • The mounting must be horizontal within 10 degrees tilted in back side lowering or within 10 degrees tilted in back side rising. • In the case of panel mount type (C15T), the mounting panel should be used with a thickness of less than 9 mm of firm board. � z Model C15T (Panel mount type) Items to be prepared: Phillips-head screwdriver Plate thickness is 9 mm or less. Screws for mounting bracket Mounting bracket Panel Panel hole Main unit Gasket (Accessory) Hook The above Figure shows the waterproof mounting using the gasket. The gasket is not used for normal panel mounting. (1) Insert this unit from the front of the panel. (2) Fit the mounting bracket from the back of the panel. (3) Push the mounting bracket against the panel until the hook of the mounting bracket is firmly engaged with the groove of the main unit. (4) Tighten the upper and lower screws of the mounting bracket. For waterproof mounting: The panel mounting type (C15T) can be waterproof-mounted. To do so, attach the accessory gasket to the main unit before above step (1). After that, mount the main unit with the gasket attached from above operation step (1) in order. Handling Precautions • To fasten this controller onto the panel, tighten a mounting bracket screws, and turn one more half turn when there is no play between the bracket and panel. Excessively tightening the screws may deform the controller case. • If gangmounted, dustproof and waterproof protection may not be maintained.

Chapter 3. INSTALLATION

� z Model C15T (Using the hard cover for panel mount type) For panel mounting type, it is possible to attach the hard cover to the front console. Use of hard cover makes it possible to prevent the settings from being changed due to accidental operation or to operate the unit in poor installation environment. The display can be seen with the cover kept closed. When operating the key, raise the cover and operate the key. Items to be prepared: Hard cover Part No. 81446442-001 (Optional unit) Hard cover Gasket Main body Gasket Panel Both gaskets must be used, one is supplied with the main unit and the other is supplied with the hard cover. Both are the same gaskets. (1) As shown in the Figure, mount the gasket, hard cover, and gasket on the main unit in that order so that the hard cover is sandwiched by two gaskets. (2) Insert this unit from the front of the panel. (3) Fit the mounting bracket from the back of the panel. (4) Push the mounting bracket against the panel until the hook of the mounting bracket is firmly engaged with the groove of the main unit. (5) Tighten the upper and lower screws of the mounting bracket. Handling Precautions • To fasten this controller onto the panel, tighten a mounting bracket screws, and turn one more half turn when there is no play between the bracket and panel. Excessively tightening the screws may deform the controller case. • It is possible to mount this unit without use of two gaskets if the waterproof feature is not needed and only the prevention of improper operation is aimed at. • If gangmounted, dustproof and waterproof protection may not be maintained.

Chapter 3. INSTALLATION

� z Model C15T (Using the soft cover for panel mount type) For panel mounting type, it is possible to attach the soft cover to the front console. The key can be operated with the soft cover kept attached. Additionally, when the soft cover is attached to the front console, this provides the feature similar to the waterproof mounting using the gasket. Items to be prepared: Soft cover Part No. 81446443-001 (Optional unit) Soft cover Panel Soft cover Panel Main unit Main unit The gasket supplied with the main unit is not used. (1) Attach the soft cover so that it covers the console of the main unit. (2) Insert the unit with the soft cover attached from the front of the panel. (3) Fit the mounting bracket from the back of the panel. (4) Push the mounting bracket against the panel until the hook of the mounting bracket is firmly engaged with the groove of the main unit. (5) Tighten the upper and lower screws of the mounting bracket. Handling Precautions • To fasten this controller onto the panel, tighten a mounting bracket screws, and turn one more half turn when there is no play between the bracket and panel. Excessively tightening the screws may deform the controller case. • If gangmounted, dustproof and waterproof protection may not be maintained.

Chapter 3. INSTALLATION

� z C15S (Socket mount type) Items to be prepared: Phillips-head screwdriver DIN rail Socket Stopper Stopper hole Main unit The above Figure shows the DIN rail mounting. (1) Mount the socket inside the panel. (For screw tightening, mount the socket directly.) (2) Perform the wiring to the socket. (3) Push this unit into the socket. (4) Put the upper and lower socket stoppers in the stopper holes in the main unit, and then insert them. Handling Precautions • For socket mount type, it is necessary that the wiring must be completed before mounting this unit on the socket.

4 - 1

Wiring WARNING Do not use this device in an environment with conductive pollution, or with dry non- conductive pollution which can become conductive due to condensation, etc. Otherwise, problems such as tracking phenomena may damage parts, resulting in fire. When wiring the power for this device, be sure to mount a shutoff switch for the main power to this unit within reach of the operator. In addition, when wiring the power for AC power models, install a time-lag (T) fuse (rated current 0.2 A, rated voltage 250 V) as specified by IEC 127. Otherwise, tracking phenomena or parts failure due to other factors may cause fire. Before removing, mounting, or wiring this device, be sure to turn off the power to the device and all connected devices. Failure to do so might cause electric shock. Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock. CAUTION Wire this device properly according to predetermined standards. Also wire the device using specified power leads according to recognized installation methods. Failure to do so might cause electric shock, fire or faulty operation. Do not allow lead clippings, chips or water to enter the controller case. Doing so might cause fire or faulty operation. Firmly tighten the terminal screws at the torque listed in the specifications. Insufficient tightening of terminal screws might cause electric shock or fire. Do not use unused terminals on this device as relay terminals. Doing so might cause electric shock, fire, or faulty operation. We recommend attaching the terminal cover (sold separately) after wiring this device. Failure to do so might cause electric shock, fire, or faulty operation. Use the relays within the recommended service life. Failure to do so might cause fire or faulty operation. If there is a risk of a power surge caused by lightning, use a surge absorber (surge protector) to prevent fire or device failure. Do not make incorrect connections. If the cables are connected incorrectly, this might cause the unit to malfunction. The controller does not function for approximately 6 s after the power has been turned ON. Great care should be taken when the relay output from the controller is used as interlock signals. The part between the control output 1 and control output 2 is not isolated. When necessary, use an appropriate isolator. Do not connect multiple loader cables to multiple units from one personal computer. The current coming from other circuits might cause the PV value indication error to occur. Do not connect any terminating resistor to both ends of the communication path when performing the RS-485 wiring. Doing so might cause the communication to fail.

Chapter 4. WIRING

� � Terminal assignment label symbols The following table shows the meanings of the symbols used for the terminal assignment label attached to the side panel of this unit: Symbol Meaning ~ AC DC Caution, there is danger of electric shock Caution � � Wiring precautions • Before starting the wiring work, carefully check the label on the side panel of this unit to understand the model No. and terminal No. to carry out the wiring properly. • For panel mount type, use an appropriate crimp type terminal lug suitable for the M3 screw to connect the terminals. The tightening torque of the terminal screw must be 0.4 to 0.6 N·m. • For socket mount type, use an appropriate crimp type terminal lug suitable for the M3.5 screw to connect the terminals. The tightening torque of the terminal screw must be 0.78 to 0.98 N·m. • Pay special attention so that no crimp terminals are in contact with adjacent terminals. • For the C15T (panel-mount type), to connect 2 crimp terminals to the same terminal screw, bend the crimp terminals before use. • For the C15T (panel-mount type), connect wires to terminals 1-6 and 13-18 from the left (when viewing the terminal block). A B A: 5.8mm max. B: 5.5 to 7.6 mm Recommended crimp terminal: V1.25-MS3 (manufactured by J.S.T. Mfg. Co., Ltd.) • Keep the input/output signal cables 50 cm or more away from the drive power cable and/or power cable. Additionally, do not pass the input/output signal cables and the drive power cable and/or power cable together through the same conduit or duct. • When connecting this unit and other measuring instrument in parallel, carefully check the conditions necessary for other instrument before starting the instrumentation. • The digital input is so designed that it is non-voltage input. A contact for micro current must be used. • Pass the conductor, to which the heater current flows, through the current transformer. Additionally, carefully check that the heater current does not exceed the allowable current level stated in the specification. If the heater current exceeds the allowable current level, this might cause damage to this unit. • The input of the current transformer cannot be used for the phase angle control. • For panel mounting type (C15T), an optional terminal cover is available to prevent electric shock. (Model No.: 81446898-001) Concave part of main unit case Terminal cover

Chapter 4. WIRING

• The part between the control output 1 and control output 2 is not isolated. When necessary, use an appropriate isolator. • Make sure that devices and equipment connected to this device have reinforced insulation suitable for the maximum operating voltage of this device's power supply and input/output ports. • This unit is so designed that it does not start functioning for up to 6 s after the power has been turned ON in order to ensure stable operation. After that, the unit then enters the operation mode. However, to satisfy the specified accuracy, it is necessary to warm up the unit for at least 30 min. IMPORTANT Terminating resistor • Do not connect any terminating resistor to both ends of the RS-485 communication path. Doing so might cause the communication to fail. � z Wiring of C15T 1 2 3 13 14 15 1 2 1 2 3 1 2 3 1 3 1 2 4 5 6 13 14 15 16 17 18 7 8 9 10 11 12 1 2 3 4 5 6 4 5 6 4 5 6 7 8 9 10 7 8 9 10 16 17 18 16 17 18 1 2 + + − − +− + 1 2 +− +− + 1 2 +− + + + − mA V CT1 CT2 11 12 DA DB SG 1 2 1 2 1 2 3 C B A 11 12 2 Control outputs Current transformer inputs Event outputs Relay Voltage pulse Voltage pulse Current Current Current Current Voltage Voltage pulse Voltage pulse Thermocouple RTD Current Relay Relay (independent contact) AC power supply 100 to 240 V AC Digital inputs RS-485 Communication DC power supply 24 V AC/24 to 48 V DC (nonpolar) Power supply DI/COM PV inputs

Chapter 4. WIRING

� z Wiring of C15S 1 11 2 3 4 5 6 7 8 9 10 10 11 6 7 8 9 6 7 8 9 2 1 3 1 2 3 2 1 3 2 1 3 2 1 + − + + mA V C B A 5 4 5 4 5 4 − + − + 5 4 6 2 3 1 10 9 11 7 8 10 11 Power supply AC power supply 100 to 240 V AC Event outputs Relay Relay (independent contact) PV inputs Current Voltage RTD Thermocouple Control outputs Relay Voltage pulse Current Socket terminal No. DC power supply 24 V AC/24 to 48 V DC (nonpolar) � z Recommended crimp type terminal lugs For C15T, use an appropriate crimp type terminal lug suitable for the M3 screw. For C15S socket mounting type, use an appropriate crimp type terminal lug suitable for the M3.5 screw. A B or less B or less C Mounting method Applicable screw Terminal dimensions (mm) Applicable electric wire size J.S.T. Mfg. Co., Ltd Model No. (Reference) A B C C15T panel mounting type M3 6.1 5.8 5.5 to 7.6 0.3 to 1.2 mm2 AWG22 to 16 V1.25 - MS3 (round terminal lug) V1.25 B3A (Y terminal lug) C15S socket mounting type M3.5 7.4 6.6 6.3 0.3 to 1.2 mm2 AWG22 to 16 V1.25 - M3 (round terminal lug) V1.25 YS3A (Y terminal lug) Handling Precautions • When installing this unit in a place where the vibration or impact is large, always use an appropriate round crimp terminal so that it is not disengaged from the connection terminal. • Pay special attention so that no crimp terminals are in contact with adjacent terminals.

Chapter 4. WIRING

� � Connection of open collector output to digital input 16 17 18 5 V This unit � � Connection of communication (RS-485) cable � z 3-wire system 16 17 18 16 Master station DA DA DB DB SG SG SG FG + - This unit (slave station) This unit (slave station) Shield Shield 17 18 IMPORTANT Terminating resistor • Do not connect any terminating resistor to both ends of the communication path. Doing so might cause the communication to fail. • Even though any units requiring the terminating resistor exist in the communication path, do not connect any terminating resistor. Handling Precautions • Do not connect DA and DB. Doing so might cause damage to this unit. • Ground the shield line to one point on one side of the cable. • Be sure to connect SG terminals each other. Failure to do so might cause unstable communications.

Chapter 4. WIRING

� z 5-wire system 16 17 18 16 Master station DA DA DB DB SG SG SG FG + − + − This unit (slave station) This unit (slave station) Shield Shield 17 18 IMPORTANT Terminating resistor • Do not connect any terminating resistor to both ends of the communication path. Doing so might cause the communication to fail. • Even though any units requiring the terminating resistor exist in the communication path, do not connect any terminating resistor. Handling Precautions • Do not connect DA and DB. Doing so might cause damage to this unit. • Ground the shield line to one point on one side of the cable. • Be sure to connect SG terminals each other. Failure to do so might cause unstable communications.

Chapter 4. WIRING

� � Connection with solid state relay (SSR) To drive the SSR, a model having voltage pulse outputs (V0, VC or VV) must be used. Generally, the SSR is classified into two groups, constant current type and resistor type. � z Constant current type The two conditions listed below must be satisfied. • Input current (maximum): Check that the input current is within the maximum allowable current or less, then the parallel connection can be made. • Operating voltage range: Check that the voltage between the terminals of the voltage pulse output is within the specified range. 1. Azbil Corporation's PGM10N/PGM10F series This example shows the calculation for the connection of the SDC15 and the PGM10N015. (Note: For connection with other model number, check the specifications of each model.) • Input current: Since the input current is 10 mA or less, up to two units (10mA × 2 = 20 mA < 24 mA [maximum allowable current]) can be connected in parallel. • Operating voltage range (input): The rating voltage is 3.5 to 30 V DC. Therefore, the voltage between the terminals is within the range. Voltage between terminals (two PGM10N units) = Open voltage - internal resistance × total drive current = 19 V DC ±15 % - 82 Ω ±0.5 % × 20 mA =15 to 20 V Connection diagram This unit + – + – PGM10N/PGM10F + – PGM10N/PGM10F Number of connectable units SSR to be used Connection V0/VC model VV model PGM10N Parallel connection Up to 2 units Up to 4 units* PGM10F Parallel connection Up to 2 units Up to 4 units* * 2 units for each output

Chapter 4. WIRING

2. Omron's G3PA, G3PB, G3NA • Input current: Since the input current is 7 mA or less, up to three units (7 mA × 3 = 21 mA < 24 mA [maximum allowable current]) can be connected in parallel. • Operating voltage range (input): The rating voltage is 5 to 24 V DC or 12 to 24 V DC. Therefore, the voltage between the terminals is within the range. Voltage between terminals (three G3PA units) = Open voltage - internal resistance × total drive current = 19 V DC ±15 % - 82 Ω ±0.5 % × 21 mA =14 to 20 V Connection diagram This unit + + – G3PA + G3PA + G3PA – – – Number of connectable units SSR to be used Connection V0/VC model VV model Omron G3PA Parallel connection Up to 3 units Up to 6 units* Omron G3PB Parallel connection Up to 3 units Up to 6 units* Omron G3NA Parallel connection Up to 3 units Up to 6 units* * 3 units for each output

Chapter 4. WIRING

� z Resistor type (Azbil Corporation's PGM_ _ 2A1, etc.) When necessary, an appropriate external resistor is connected in series so that the voltage between the input terminals of the SSR you are using is within the specified range. (Example) Connection of two Azbil Corporation PGM units Connection diagram This unit V R0 PGM_ _2A1 R2 Vf 3 4 PGM_ _2A1 R2 Vf 3 4 External resistor R1 + - V: 19 V ± 15% R0: 82 Ω ± 0.5% R1: 680 Ω R2: 260 Ω Vf: 1.1 V Voltage between terminals of PGM = (V - 2 × Vf) / (R0 + R1+ R2 + R2) × R2 + Vf =4.5 V Input voltage range of PGM: Since the input voltage range is 3 to 6 V, the operation is possible. External resistors SSR to be used Number of units to be connected Connection External resistor Notes PGM_ _2A1 1 – 1kΩ (serial connection) Rating is 1/2W or more. 2 Serial connection 680Ω (serial connection) Rating is 1/2W or more. 3 Serial connection 330Ω (serial connection) Rating is 1/2W or more. 4 Serial connection None Number of connectable units SSR to be used Connection V0/VC model VV model PGM_ _2A1 Serial connection Up to 4 units Up to 8 units* * 4 units for each output

Chapter 4. WIRING

� � Connection with current-input type controllers When the power to this controller is turned off, the current input circuit is cut off. If multiple current-input type SDCs are connected in series and you want to turn them on/off individually, convert them to voltage input by adding resistors (No. 81401325, sold separately) to the circuit. rdy man ev1 ev2 ev3 ot1 ot2 para mode pv sp 1 to 5 V 250 Ω + − + 4 to 20 mA − − rdy man ev1 ev2 ev3 ot1 ot2 para mode pv sp 1 to 5 V 250 Ω + This unit This unit Current output device � � Noise preventive measures The power is taken from the single-phase instrumental power supply to consider noise preventive measures. If the noise from the power supply is large, an appropriate insulation transformer is added to the power supply and an appropriate line filter is used. (Azbil Corporation's line filter model No.: 81442557-001) If the noise has fast rising edge, an appropriate CR filter is used. (Azbil Corporation's CR filter model No.: 81446365-001) Handling Precautions After the noise preventive measures have been taken, do not bundle the primary and secondary sides of the insulation transformer together or put them in the same conduit or duct.

Chapter 4. WIRING

Contact the thermocouple wires to the terminals in case of a thermocouple input. When a thermocouple is connected to terminals, or wiring distance is long, connect the wire via a shielded compensating lead wire. • For input/output other than thermocouples, use a JCS 4364 instrument cable or equivalent (generally called twisted shielded cable for instrumentation use). Recommended twisted shielded cables. Fujikura Ltd. 2 conductors IPEV-S-0.9 mm2 × 1P 3 conductors ITEV-S-0.9 mm2 × 1T Hitachi Metals, Ltd. 2 conductors KPEV-S-0.9 mm2 × 1P 3 conductors KTEV-S-0.9 mm2 × 1T • A shielded multiconductor microphone cord (MVVS) may be used, if electromagnetic induction noise are comparatively low. 4 - 2 Recommended Cables

DETAILED DESCRIPTION OF EACH FUNCTION

5 - 1 PV Input The following shows the functional block diagram of the PV input: PV input is thermocouple. PV input range type (Setting: Setup C0 1) Cold junction compensation (Setting: Setup C03) Temperature unit (Setting: Setup C02) PV input is RTD. PV input range type (Setting: Setup C0 1) Temperature unit (Setting: Setup C02) PV high limit/low limit alarm PV ratio (Setting: Parameter rA) PV bias (Setting: Parameter bI ) PV flter (Setting: Parameter FL) PV high limit/low limit PV hold (Setting: DI Assignment Operation type dI 1. 1 to dI 3. 1) PV before ratio, bias, and flter PV PV input is DC voltage/DC current. PV input range type (Setting: Setup C0 1) PV square root extraction (Setting: Setup C09) Decimal point position and scaling (Setting: Setup C04 to C06) � � PV input range type When the PV input type is T (thermocouple) or R (RTD), the sensor type and temperature range can be selected. When the PV input range type is L (DC voltage/DC current), the signal type can be selected. Item (Bank) Display Contents Initial value User level PV input range type (Setup bank) The contents may vary depending on the PV input range type. For details, refer to the PV input range table. The initial value may vary depending on the PV input range type as shown below. "T": 1 "R": 41 "L": 88 Simple, Standard, High function

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� z PV input range table (Thermocouple) � z PV input range table (RTD) C0 1 set value Sensor type Range (Celsius) Range (Fahrenheit) C04 display C04 range C04 initial value when C0 1 settings C0 1 set value Sensor type Range (Celsius) Range (Fahrenheit) C04 display C04 range C04 initial value when C0 1 settings 1 K -200 to +1200˚C -300 to + 2200˚F ---- (Not setting) (No decimal point) 41 Pt100 -200.0 to +500.0˚C -300 to + 900˚F ---- (Not setting) (No decimal point) 2 K 0 to 1200˚C 0 to 2200˚F ---- (Not setting) (No decimal point) 42 JPt100 -200.0 to +500.0˚C -300 to + 900˚F ---- (Not setting) (No decimal point) 3 K 0.0 to 800.0˚C 0 to 1500˚F  0 to 1 0 43 Pt100 -200.0 to +200.0˚C -300 to + 400˚F ---- (Not setting) (No decimal point) 4 K 0.0 to 600.0˚C 0 to 1100˚F  0 to 1 0 44 JPt100 -200.0 to +200.0˚C -300 to + 400˚F ---- (Not setting) (No decimal point) 5 K 0.0 to 400.0˚C 0 to 700˚F  0 to 1 0 45 Pt100 -100.0 to +300.0˚C -150 to + 500˚F ---- (Not setting) (No decimal point) 6 K -200.0 to +400.0˚C -300 to + 700˚F  0 to 1 0 46 JPt100 -100.0 to +300.0˚C -150 to + 500˚F ---- (Not setting) (No decimal point) 9 J 0.0 to 800.0˚C 0 to 1500˚F  0 to 1 0 51 Pt100 -50.0 to +200.0˚C -50 to + 400˚F  0 to 1 1 10 J 0.0 to 600.0˚C 0 to 1100˚F  0 to 1 0 52 JPt100 -50.0 to +200.0˚C -50 to + 400˚F  0 to 1 1 11 J -200.0 to +400.0˚C -300 to + 700˚F  0 to 1 0 53 Pt100 -50.0 to +100.0˚C -50 to + 200˚F  0 to 1 1 13 E 0.0 to 600.0˚C 0 to 1100˚F  0 to 1 0 54 JPt100 -50.0 to +100.0˚C -50 to + 200˚F  0 to 1 1 14 T -200.0 to +400.0˚C -300 to + 700˚F  0 to 1 0 63 Pt100 0.0 to 200.0˚C 0 to + 400˚F  0 to 1 1 15 R 0 to 1600˚C 0 to 3000˚F ---- (Not setting) (No decimal point) 64 JPt100 0.0 to 200.0˚C 0 to + 400˚F  0 to 1 1 16 S 0 to 1600˚C 0 to 3000˚F ---- (Not setting) (No decimal point) 67 Pt100 0.0 to 500.0˚C 0 to + 900˚F ---- (Not setting) (No decimal point) 17 B 0 to 1800˚C 0 to 3300˚F ---- (Not setting) (No decimal point) 68 JPt100 0.0 to 500.0˚C 0 to + 900˚F ---- (Not setting) (No decimal point) 18 N 0 to 1300˚C 0 to 2300˚F ---- (Not setting) (No decimal point) 19 PL II 0 to 1300˚C 0 to 2300˚F ---- (Not setting) (No decimal point) 20 WRe5-26 0 to 1400˚C 0 to 2400˚F ---- (Not setting) (No decimal point) 21 WRe5-26 0 to 2300˚C 0 to 4200˚F ---- (Not setting) (No decimal point) 23 PR40-20 0 to 1900˚C 0 to 3400˚F ---- (Not setting) (No decimal point) 24 DIN U -200.0 to +400.0˚C -300 to + 700˚F  0 to 1 0 25 DIN L -100.0 to +800.0˚C -150 to + 1500˚F  0 to 1 0 *1. Accuracy of sensor type B (No.17): ±5 %FS below 260 ˚C, ±1 %FS from 260 to 800 ˚C, not specified below 20 ˚C However, if ROM version 1 in the instrument information bank (i d02) is 2.04 or earlier, the low limit for display is -180 ˚C. Accuracy of sensor type PR40-20 (No.23): not specified below 300 ˚C, ±5 %FS from 300 to 800 ˚C, ±2 %FS from 800 to 1900 ˚C However, if ROM version 1 in the instrument information bank (i d02) is 2.26 or earlier, No.23 cannot be selected. *2. PL II thermocouple is a range, which has been added to the units manufactured from July, 2003. *3. The PV range display for thermocouple with a decimal point is available for ROM version 2.26 and later. � z PV input range table (DC voltage/DC current) C0 1 set value Sensor type Range C04 display C04 range C04 initial value when C0 1 settings 84 0 to 1 V • Scaling range is -1999 to +9999. • When C0 1 is changed, the range default defaults to 0 to 1000.  0 to 3 No change 86 1 to 5 V  0 to 3 No change 87 0 to 5 V  0 to 3 No change 88 0 to 10 V  0 to 3 No change 89 0 to 20 mA  0 to 3 No change 90 4 to 20 mA  0 to 3 No change Handling Precautions • When the C0 1 PV input range number is set, the decimal point position and range are initially set automatically as shown in the tables. For details on the decimal point, refer to the description of setup C04 (decimal point position) on page 5-4. • Make sure to set the correct number in setup display C0 1, according to the type and range of the sensor used. If the setting is wrong, problems such as large temperature errors in the output may occur. • For details about the accuracy of each PV range type: Chapter 13. SPECIFICATIONS (p. 13-1)

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � Temperature unit When the PV input type is T (thermocouple) or R (RTD), the temperature unit can be selected. Item (Bank) Display Contents Initial value User level Temperature unit (Setup bank) 0: Celsius (˚C) 1: Fahrenheit (˚F). 0 Simple, Standard, High function • When the PV input type is T (thermocouple) or R (RTD), the display and setting can be made. � � Cold junction compensation (T/C) When the PV input type is T (thermocouple), any of the following can be selected: • The cold junction compensation (T/C) is performed inside this unit. • The cold junction compensation (T/C) is not performed inside this unit since an external cold junction compensation unit, such as ice bath is used. • When the PV input type is T (thermocouple), the display and setting can be made. Item (Bank) Display Contents Initial value User level Cold junction compensation (T/C) (Setup bank) 0: Cold junction compensation (T/C) is performed (internal). 1: Cold junction compensation (T/C) is not performed (external). 0 High function � � PV square root extraction dropout When the PV input type is L (DC voltage/DC current), a dropout value can be set so that the result of the PV square root extraction used to convert the pressure (differential pressure) into the flow becomes "0". • When the PV input type is L (DC voltage/DC current), the display and setting can be made. Item (Bank) Display Contents Initial value User level PV square root extraction dropout (Setup bank) 0.0 %: Square root extraction is not performed. 0.1 to 100.0 % 0.0 % High function • Details of PV square root extraction The calculation input in % and the calculation result in % are expressed as PVin and PVout, respectively. When the PV input is the PV square root extraction dropout set value or more and less than 100.0 %, the control formula becomes as shown below. PVout = √PVin ÷ 100 × 100 When the PV input is larger than 0.0% and smaller than the PV square root extraction dropout set value, PVout = 0.0 %. When the PV input is 0.0 % or less or 100.0 % or more, the square root extraction is not performed. Therefore, PVout = PVin.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Output after PV square root extraction (PVout) 100 %FS PVin Dropout value (variable change from 0.1 to 100.0 %) 0 100 %FS 0 Y = Xin/100 ×100 � � Decimal point position If the PV input type in the model number is L (DC voltage/current), or if one of the thermocouple or RTD ranges is selected in C0 1, the decimal point position can be set. Item (Bank) Display Contents Initial value User level Decimal point position (Setup bank) 0: No decimal point 1: 1 digit below decimal point 2: 2 digits below decimal point 3: 3 digits below decimal point 0 Simple, Standard, High function Handling Precautions • As this setting is changed, the decimal point position of the parameters related to the decimal point position of the PV input is also changed. Th e decimal point position of the following settings is changed: SP setting SP low limit/high limit setting SP up ramp/down ramp setting Event setting and continuous output setting related to PV Event setting and continuous output setting related to SP Event setting and continuous output setting related to deviation (absolute deviation) • The PV range display for thermocouple is available for ROM version 2.26 and later. Note • For the display conditions, setting range and initial value of range numbers (C0 1): PV input range tables (p. 5-2)

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � PV input range low limit/high limit When the PV input type is L (DC voltage/DC current), the scaling of the PV input can be set. Item (Bank) Display Contents Initial value User level PV range low limit (Setup bank) When the PV input type is "L", the following contents apply: -1999 to +9999 (no decimal point) -199.9 to +999.9 (1 digit after decimal point) -19.99 to +99.99 (2 digits after decimal point) -1.999 to +9.999 (3 digits after decimal point) When the PV input type is "T" or "R", the range low limit and high limit values selected using the PV input range type are used. When the PV input type is "L", the initial value is "0". Simple, Standard, High function PV range high limit (Setup bank) When the PV input type is "L", the initial value is "1000". • When the PV input type is T (thermocouple) or R (RTD), the setting item can be displayed, but the setting cannot be made. • When the PV input type is L (DC voltage/DC current), the display and setting can be made. The following describes the relationship between the PV input and PV when setting up the range low limit and high limit. PV -10 0 100110 Input (%) Low limit Low limit < High limit Low limit > High limit High limit PV -10 0 100110 Input (%) Low limit High limit � � PV ratio and PV bias The PV ratio and PV bias can be set to compensate the PV. Item (Bank) Display Contents Initial value User level PV ratio (Parameter bank) 0.001 to 9.999 1.000 Standard, High function PV bias (Parameter bank) -1999 to +9999 U 0 U Simple, Standard, High function • Details of PV ratio and PV bias controls Assuming that the control input is PVin, control result is PVout, PV ratio is RA, and PV bias is BI, the following control formula is obtained: PVout = (PVin × RA) + BI � � PV low limit alarm threshold Item (Bank) Display Contents Initial value User level PV input failure (under range) type (Setup bank) 0: -10 %FS 1: -5 mV (This setting is applicable if C0 1 (PV input range type) is set for sensor type B (No. 17) or PR40-20 (No. 23)) 0 Simple, Standard, High function If ROM version 1 in the instrument information bank (i d02) is 2.26 or earlier, this item cannot be displayed. This setting is applicable if C0 1 (PV input range type) is set for sensor type B (No. 17) or PR40-20 (No. 23). � PV low limit/high limit and PV low limit/high limit alarms (p. 5-6)

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � PV filter This PV filter is a primary delay filter to be used if the PV repeatedly fluctuates rapidly and the control cannot be performed or if the PV fluctuates finely due to influence of noise, etc. As a larger value is set, it becomes difficult to change the PV used for the control of this unit. Normally, the PV filter is used with an initial value of "0.0". Item (Bank) Display Contents Initial value User level PV filter (Parameter bank) 0.0: No filter 0.1 to 120.0 s 0.0 s Simple, Standard, High function OUT = OUT-1 + (IN – OUT-1)/(T/Ts + 1) IN: Input to PV filter OUT: Control output of current filter OUT-1: Control output of previous filter T: Filter set value (s) Ts: Sampling cycle time (0.5 s) � � PV hold It is possible to set the PV to a fixed value using the PV hold, PV Max. hold, and PV Min. hold of the DI (digital input) functions. PV hold: PV is set to a fixed value and it is not updated. PV Max. hold: PV maximum value is held. The PV value is updated only when the new PV value is larger than the currently held value. PV Min. hold: PV minimum value is held. The PV value is updated only when the new PV value is smaller than the currently held value. When using the PV hold, PV Max. hold, or PV Min. hold, the PV indication on the upper display is flashing. � � PV low limit/high limit and PV low limit/high limit alarms PV low limit and PV high limit are provided for each PV input range type. In principle, -10 %FS of each range becomes the PV low limit while +110 %FS becomes the PV high limit. p. 10-2 The PV is limited so that it is within a range between the PV low limit and PV high limit. If the PV before activation of the PV ratio, PV bias, and PV filter is larger than the PV high limit, PV high limit alarm (AL0 1) occurs. On the contrary, if this PV is smaller than the PV low limit, the PV low limit alarm (AL02) occurs.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

5 - 2 Mode It is possible to set the AUTO/MANUAL mode selection, RUN/READY mode selection, AT (Auto Tuning) stop/ start selection, release all DO (digital output) latches, and OFF/ON selection of communication DI (digital input) 1. � � AUTO/MANUAL mode The AUTO/MANUAL mode selection can be set. Item (Bank) Display Contents Initial value User level AUTO/MANUAL mode selection (Mode bank) AUto: AUTO mode [Communication value is "0".] MAn: MANUAL mode [Communication value is "1".] AUto Simple, Standard, High function • When the AUTO/MANUAL mode is changed, the display is automatically returned to the operation display. • If the operation type of internal contacts 1 to 3 is set at “AUTO/MANUAL”, [A-- M: AUTO/MANUAL mode selection] can be displayed, but the setting cannot be made. • When [CtrL: Control method] is set at "0" (ON/OFF control), [A--M: AUTO/ MANUAL mode selection] cannot be displayed and set. • When [bit 0: AUTO/MANUAL display] of [C73: MODE display setup] is set at "0" (no display), [A--M: AUTO/MANUAL mode selection] cannot be displayed and set. � � RUN/READY mode The RUN/READY mode selection can be set. Item (Bank) Display Contents Initial value User level RUN/READY mode selection (Mode bank) rUn: RUN mode [Communication value is "0".] rdy: READY mode [Communication value is "1".] rUn Simple, Standard, High function • If the operation type of internal contacts 1 to 3 is set at “RUN/READY”, [r--r: RUN/READY] can be displayed, but the setting cannot be made. • When [bit 1: RUN/READY display] of [C73: MODE display setup] is set at "0" (no display), [r--r: RUN/READY] cannot be displayed and set.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � AT (Auto Tuning) stop/start The AT stop/start selection can be set. Item (Bank) Display Contents Initial value User level AT stop/start selection (Mode bank) At.OF: AT stop [Communication value is "0".] At.ON: AT start [Communication value is "1".] At.OF Simple, Standard, High function • The AT is stopped in the MANUAL or READY mode. • If the PV high limit alarm (AL0 1) or PV low limit alarm (AL02) occurs, the AT is stopped. • If the operation type of internal contacts 1 to 3 is set at "AT stop/start", [At: AT stop/start selection] can be displayed, but the setting cannot be made. • When [CtrL: Control method] is set at "0" (ON/OFF control), [At: AT stop/start selection] cannot be displayed and set. • When [bit 3: AT stop/start display] of [C73: MODE display setup] is set at "0" (no display), [At: AT stop/start selection] cannot be displayed and set. AT (p. 5-18) and AT function (p. 5-21) � � Release all DO (digital output) latches Release all DO (digital output) latches can be set. Item (Bank) Display Contents Initial value User level Release all digital output (DO) latches (Mode bank) Lt.ON: Latch is continued. [Communication value is "0".] Lt.oF: Latch is released. [Communication value is "1".]) Lt.ON Simple, Standard, High function • If the operation type of internal contacts 1 to 3 is set at "Release all DO latches", [dO.Lt: Release all DO latches] can be displayed, but the setting cannot be made. • When [bit 4: Release all DO latches display] of [C73: MODE display setup] is set at "0" (no display), [dO.Lt: Release all DO latches] cannot be displayed and set. � � Communication DI (digital input) 1 Communication DI (digital input) 1 can be set. Item (Bank) Display Contents Initial value User level Communication digital input 1 (communication DI 1) (Mode bank) DI.OF: Communication DI1. OFF [Communication value is "0".] DI.ON: Communication DI1. ON [Communication value is "1".] DI.OF Simple, Standard, High function • Four communication DIs, DI1 to DI4, are provided. However, only communication DI 1 can be set using the key operation. • The function (operation) with communication DI 1 can be set using the DI Assignment. • When [bit 5: Communication DI 1 display] of [C73: MODE display setup] is set at "0" (no display), [C.DI 1: Communication DI 1] cannot be displayed and set.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

The following shows the functional block diagram of the control (ON/OFF control, PID control, RationaLOOP control, and Heat/Cool control, etc.): MV1 output ON MV1 output OFF MV1 output ON or output OFF ON/OFF control Control method: ON/OFF control (Setting: Parameter CtrL must be set at "0".) ON/OFF control (Setting: Parameter dI FF, OFFS) Branching according to output at READY (Setting: Setup C 1 7) Branching according to output operation at PV alarm (Setting: Setup C 15) Branching according to RUN/READY mode selection READY mode C 1 7 > 0.0 % C 1 7 ≤ 0.0 % MV1 output ON MV1 output OFF Branching according to output at PV alarm (Setting: Setup C 16) C 16 > 0.0 % C 16 ≤ 0.0 % PV is correct or C 15 = 0: PV is faulty (AL01/02 occurs) and C 15 = 1: RUN mode 5 - 3 Control

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

MV1 = MV Fixed PID Control method: Fixed PID (Setting: Parameter CtrL must be set at "1".) ST Control method: ST (Self-tuning) (Setting: Parameter CtrL must be set at "2".) Adjustment according to step response/hunting (Setting: Extended tuning St.SA, St.Sb, St.Hb, St.Ud) ST is not run in the following cases: • Heat/Cool control is used. • Just-FiTTER is used. READY mode AUTO mode MANUAL mode RUN mode SP lag overshoot suppression (Setting: Extended tuning SP.LG) RationaLOOP high precision control logic (Setting: Extended tuning Ctr.A) Just-FiTTER overshoot suppression (Setting: Extended tuning JF.Ov, JF.bd) Bumpless transfer/Preset selection (Setting: Setup C 19, C20) Branching according to AUTO/MANUAL mode Branching according to RUN/READY mode MV MV1 = MV Branching according to output operation at PV alarm (Setting: Setup C 15, C 16) PID control (Setting: PI D P- 1, I - 1, d- 1, rE- 1,OL- 1, OH- 1, P- 1C, I - 1C, d- 1C,OL. 1C, Oh. 1C) Output at PV alarm (Setting: Setup C 16) Branching according to Heat/Cool control (Setting: Setup C26) C26 = 0 C26 = 1 Branching according to Heat/Cool control (Setting: Setup C26) MV1 = Heat MV MV2 = Cool MV MV1 = Heat MV MV2 = Cool MV Output at READY (Setting: Setup C17, C18) Heat/Cool control (Setting: Setup C28, C29) Output at READY (Setting: Setup C 17) PV is correct or C 15 = 0 C26 = 0 C26 = 1 PV is faulty and C 15 = 1

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � Control method A desired control method can be selected from three kinds of control methods. Item (Bank) Display Contents Initial value User level Control method (Parameter bank) 0: ON/OFF control 1: Fixed PID 2: ST (Self-tuning) 0 or 1 Simple, Standard, High function • When the control output type is relay (R0), the initial value becomes "0". The initial value is "1" in other cases. • "Fixed" of [1: Fixed PID] means that the PID constant is not changed automatically since the ST is not run. However, the AT can be run even in the fixed PID control. • When using the Heat/Cool control (C26=1) or when using the Just-FiTTER control (JF.ov > 0), the ST is not run even though [2: ST] is set. • The following Table shows valid and invalid functions related to [1: Fixed PID] and [2: ST], as well as other related parameters: Classification of Heat/Cool control Classification of RationaLOOP Classification of control action RationaLOOP function AT ST Just-FiTTER Normal control Normal PID P control ×  * × × PI control ×  * ×  PD control ×  * × × PID control ×    RationaLOOP P control ×  * × × PI control ×  * ×  PD control ×  * × × PID control     Heat/Cool control Normal PID P control ×  * × × PI control ×  * ×  PD control ×  * × × PID control ×  ×  RationaLOOP P control ×  * × × PI control ×  * ×  PD control ×  * × × PID control   ×  Related settings Control algorithm AT type ST step execution resolution band Just-FiTTER assistance coefficient MV low limit at AT ST step settling band Just-FiTTER settling band MV high limit at AT ST hunting AT Proportional band adjust ST step ramp change AT Integral time adjust AT Derivative time adjust * Adjustment result becomes the PID control.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � Control action and Heat/Cool control The control action (direct/reverse) and Heat/Cool control (enabled/disabled) can be selected. Item (Bank) Display Contents Initial value User level Control action (direct/ reverse) (Setup bank) 0: Heat control (Reverse) 1: Cool control (Direct) 0 Simple, Standard, High function Heat/Cool control (Setup bank) 0: Disabled. 1: Enabled. 0 Simple, Standard, High function • When the control method is other than the ON/OFF control (CtrL ≠ 0), [Heat/ Cool control: C26] can be displayed and set. • When the Heat/Cool control is set disabled (C26 = 0), [Control action: C14] can be displayed and set. • When the Heat/Cool control is set enabled (C26 = 1), the control action is changed to the reverse action (C14 = 0), the preset MANUAL value (C20) is changed to "50.0", and the initial output of PID control (C22) is changed to "50.0". • The reverse action (heat control) is a control that decreases (or turns OFF) the manipulated variable (MV) as the PV increases. The direct action (cool control) is a control that increases (or turns ON) the manipulated variable (MV) as the PV increases. � � Special control outputs The control output at PV alarm and control output at READY can be set. Item (Bank) Display Contents Initial value User level Output operation at PV alarm (Setup bank) 0: Control calculation is continued. 1: Output at PV alarm is output. 0 High function Output at PV alarm (Setup bank) -10.0 to +110.0 % 0.0 % High function Output at READY (Heat) (Setup bank) -10.0 to +110.0 % 0.0 % Standard, High function Output at READY (Cool) (Setup bank) -10.0 to +110.0 % 0.0 % Standard, High function • When the control method is other than the ON/OFF control (CtrL ≠ 0) and the Heat/Cool control is set enabled (C26 = 1), [Output at READY (cool): C18] can be displayed and set. • The PV alarm status means that AL0 1, 02, or 03 occurs.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � MANUAL mode change The control output when the AUTO mode is changed to the MANUAL mode can be set. Item (Bank) Display Contents Initial value User level Output operation at changing Auto/Manual (Setup bank) 0: Bumpless transfer 1: Preset 0 Standard, High function Preset MANUAL value (Setup bank) -10.0 to +110.0 % 0.0 or 50.0 % Standard, High function • When [Output operation at changing Auto/Manual: C 19] is set at [0: Bumpless transfer], the manipulated variable (MV) when the AUTO mode is changed to the MANUAL mode is retained. When set at [1: Preset], the manipulated variable (MV) is set to [Preset MANUAL value: C20] when the AUTO mode is changed to the MANUAL mode. • When the control method is other than ON/OFF control (CtrL ≠ 0), [Output operation at changing Auto/Manual: C 19] and [Preset MANUAL value: C20] can be displayed and set. • When the Heat/Cool control is not used (C26 = 0), the initial value of [Preset MANUAL value: C20] is [0.0]. On the contrary, when the Heat/Cool control is used (C26 =1), this initial value becomes [50.0]. Handling Precautions When the unit is in the MANUAL mode if the power is turned ON, the set value of C20 becomes the manipulated variable (MV). � � ON/OFF control The ON/OFF control related items can be set. Item (Bank) Display Contents Initial value User level ON/OFF control differential (Parameter bank) 0 to 9999 U 5 U Simple, Standard, High function ON/OFF control operation point offset (Parameter bank) -1999 to +9999 U 0 U High function • [ON/OFF control differential: dIFF] and [ON/OFF control operation point offset: OFFS] can be displayed and set when the control method is the ON/OFF control (CtrL = 0). • The following Figure shows the operation of the ON/OFF control: SP + oFFS Heat control (Reverse action) Cool control (Direction action) PV ON dIFF SP + oFFS PV ON dIFF z shows that the ON/OFF is changed at this value.  shows that the ON/OFF is changed at a point that "1U" is added to this value. • The following describes examples showing how to use the ON/OFF control operation point offset: To turn OFF the output at 205 °C or more and turn ON the output at less than 190 °C with the heat control and SP = 200 °C, the differential is set to 15 °C and the offset is set to 5 °C. To turn OFF the output at 5 °C or less and turn ON the output at more than 10 °C with the cool control and SP = 10 °C, the differential is set to 5 °C and the offset is set to -5 °C.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � PID control In the fixed PID control or ST (self-tuning), the PID control related items can be set. Item (Bank) Display Contents Initial value User level Proportional band (PID bank) 0.1 to 999.9 % 5.0 % Simple, Standard, High function Integration time (PID bank) 0 to 9999 s (No integration control action when set at "0".) 120 s Derivative time (PID bank) 0 to 9999 s (No derivative control action when set at "0".) 30 s Manual reset (PID bank) -10.0 to +110.0 % 50.0 % MV low limit (PID bank) -10.0 to +110.0 % 0.0 % Standard, High function MV high limit (PID bank) -10.0 to +110.0 % 100.0 % Cool-side proportional band (PID bank) 0.1 to 999.9 % 5.0 % Simple, Standard, High function Cool-side integration time (PID bank) 0 to 9999 s (No integration control action when set at "0".) 120 s Cool-side derivative time (PID bank) 0 to 9999 s (No derivative control action when set at "0".) 30 s Cool-side MV low limit (PID bank) -10.0 to +110.0 % 0.0 % Standard, High function Cool-side MV high limit (PID bank) -10.0 to +110.0 % 100.0 % • When the control method is other than the ON/OFF control (CtrL ≠ 0), the display and setting can be made. • [(Cool)] related items can be displayed and set when using the Heat/Cool control (C26 = 1). • When the I (Integration time) ( I- 1) is set at “0 s” or I (Integration time) (cool) (I- 1.C) is set at “0 s” in the Heat/Cool control, no integration control action is performed. The Manual reset (rE- 1) can be used in both the heat and cool controls. • Parameter settings for the cool control are displayed only when the Heat/Cool control is set enabled. • The Manual reset (rE- 1) is displayed when the set value of either the I (Integration time) (heat) or (cool) becomes "0". • When the I (Integration time) (heat) or (cool) is "0 s", the operation is processed with both I (Integration time) (heat) and (cool) set at "0 s". • If the setting is made so that the output low limit is greater than the output high limit, the operation is performed with the low limit swapped for the high limit automatically.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � Heat/Cool control The Heat/Cool control related items, such as Heat/Cool, Heat/Cool control dead zone, and Heat/Cool change point can be set. Item (Bank) Display Contents Initial value User level Heat/Cool (Setup bank) 0: Normal 1: Energy saving 0 Standard, High function Heat/Cool control dead zone (Setup bank) -100.0 to +100.0 % 0.0 % Simple, Standard, High function Heat/Cool change point (Setup bank) -10.0 to +110.0 % 50.0 % High function The following shows the Heat/Cool control calculation: PID (heat) PID (cool) Heat/Cool PID (heat) Constants oL, oH PID (cool) Constants oL, oH Heat/Cool output calculation PID control (Fixed at reverse action) Heat/Cool control dead zone Heat/Cool control change point Constants P, I, d, rE Heat MV Cool MV PV SP MV (PID control result) • When using the Heat/Cool control (C26 = 1), the display and setting can be made. • When MV ≥ 50 %, the control is changed to the PID (heat). • When MV < 50 %, the control is changed to the PID (cool). • When the heat/cool change is set at “energy saving” (C27 = 1), the heat/cool change is suppressed to indirectly obtain the energy saving effect. However, when the heat/cool dead zone (C28) is less than 0.0 %, the energy saving effect cannot be obtained. • How the relationship between the output (heat) and output (cool) is made for the PID control result (MV) is set. Note � z Heat/cool output  Formulas and limits for the heat/cool MV “Dead zone” in the explanation below refers to a heat/cool control dead zone. The cool MV and the heat MV are determined by the following formulas and the MV high and low limits. Heat MV = (MV – heat/cool control change point – 0.5 × deadband) × change rate Cool MV = (heat/cool control change point – MV – 0.5 × deadband) × change rate Change rate = 100 Heat/cool control change point - 0.5 × deadband However, MV high and low limits, output low limit (cooling), and output high limit (cooling) are related to the heat MV and cool MV as follows.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

100 % 100 % 0 % Cool MV Heat MV MV Output high limit (cooling) Output low limit (cooling) MV low limit MV high limit Note: The thick line and thick dotted line represent heat MV and cool MV respectively. • MV low limit ≤ heat MV ≤ MV high limit • Output low limit (cooling) ≤ cool MV ≤ output high limit (cooling) • Use the controller within the following range: 0.0 < heat/cool control change point < 100.0. • In the formula for rate of change, do not make the denominator = 0. • Regardless of the heat/cool control change point setting, 50 % of MV is always the point at which the PID group switches.  Examples of output 100.0 % 0.0 % Heat MV 100.0 % Cool MV 0.0 % 0.0 % 50.0 % 100.0 % MV 100.0 % 0.0 % Heat MV 100.0 % Cool MV 0.0 % 0.0 % 50.0 % Deadband Figure 2. Deadband > 0.0 % Heat/cool control change point = 50.0 % Figure 4. Deadband = 0.0 % Heat/cool control change point = 75.0 % Figure 1. Deadband = 0.0 % Heat/cool control change point = 50.0 % 100.0 % MV 33.3 % 0.0 % Heat MV 100.0 % Cool MV 0.0 % 0.0 % 75.0 % 100.0 % MV 100.0 % 0.0 % Heat MV 100.0 % Cool MV 0.0 % 0.0 % 50.0 % Absolute value of the deadband Figure 3. Deadband < 0.0 % Heat/cool control change point = 50.0 % 100.0 % MV In figure 4, when the MV is 100 %, the heat MV is 33.3 %. In this case, when the heat/cool control change point is 50 % or more, if the MV is 100 %, the heat MV high limit is less than 100 %. The change rate of the heat MV relative to the MV is the same as that of the cool MV relative to the MV.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � ST (Self-tuning) The settings shown below are available for ST. Item (Bank) Display Contents Initial value User level ST step execution resolution band (Extended tuning bank) 0.00 to 99.99 % 10.00 % High function ST step settling band (Extended tuning bank) 0.0 to 10.00 % 0.50 % ST hunting settling band (Extended tuning bank) 0.0 to 10.00 % 1.00 % ST step ramp change (Extended tuning bank) 0: ST is executed during PV increase and decrease. 1: ST is executed only during PV increase. 0 Standard, High function • If the control method (CtrL) is set to "2" (ST (Self-tuning)), these functions can be displayed and set. • ST step execution resolution band (St.SA) When the amount of SP change exceeds the preset percentage of the PV range, ST starts, using step response. When the power is turned on, or READY mode is changed to RUN, if the initial deviation between the SP and PV is larger than the amount of SP change, ST starts, using step response. • ST step settling band (St.Sb) If the deviation (plus or minus) is a smaller percentage of the PV range than the preset value, ST judges that the step response has settled. • ST hunting settling band (St.Hb) If the PV fluctuates so that the deviation (plus or minus) is a greater percentage of the PV range than the preset value, hunting is judged to occur, and ST starts. Afterwards, if the absolute value of the deviation becomes a smaller percentage of the PV range than the preset value, hunting is judged to have settled. Handling Precautions 5 - 5 ST (Self-tuning) Function (p. 5-24) 5 - 6 Precautions for ST (Self-tuning) (p. 5-26)

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � AT (Auto tuning) The settings shown below are available for AT. Item (Bank) Display Contents Initial value User level MV low limit at AT (Parameter bank) -10.0 to +110.0 % 0.0 % Simple, Standard, High function MV high limit at AT (Parameter bank) -10.0 to +110.0 % 100.0 % AT type (Extended tuning bank) 0: Normal (Standard control characteristics) 1: Immediate response (Control characteristics that respond immediately to external disturbance.) 2: Stable (Control characteristics having less up/down fluctuation of PV) 1 AT Proportional band adjust (Extended tuning bank) 0.00 to 99.99 1.00 High function AT Integral time adjust (Extended tuning bank) 0.00 to 99.99 1.00 AT Derivative time adjust (Extended tuning bank) 0.00 to 99.99 1.00 • When the control method is other than the ON/OFF control (CtrL ≠ 0), the display and setting can be made. • The MV (manipulated variable) during execution of AT can be limited by the MV low limit at AT (At.OL) and MV high limit at AT (AT.OH). When the Heat/Cool control is not used, the MV becomes a value limited by both the MV low limit at AT (At.OL)/MV high limit at AT (At.OH) and MV low limit (OL- 1)/MV high limit (OH- 1) of the PID constant. When the Heat/Cool control is used, the MV becomes a value limited by the MV low limit at AT (At.OL)/MV high limit at AT (At.OH), the heat MV becomes a value limited by the MV low limit (OL- 1)/MV high limit (OH- 1) of the PID constant, and the cool MV becomes a value limited by the output low limit (Cool) (OL 1.C)/output high limit (Cool) (OH 1.C) of the PID constant. • The AT type (At.ty) is a setting item that the PID constant of the control characteristics suitable for the system is calculated by the AT. Set value 1 (immediate response) is adjusted to the process that the heater heating directly affects the PV to aim at the adjustment considering the immediate response. Set value 2 (stability) is adjusted to the process that the heater heating indirectly affects the PV to aim at the adjustment considering the stability. Note When compared to the AT functions of Azbil Corporation's conventional models, set value 1 (immediate response) is close to the SDC10 and set value 0 (normal) is close to the SDC20/21.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

The following Figure shows the conceptual diagram expressing differences in control result using the PID constant calculated by each AT type: PV Time Diference in PV change when SP is changed. SP AT type = 1 (Immediate response) AT type = 0 (Normal) AT type = 2 (Stable) • For the AT Proportional band adjust (At-P), AT Integral time adjust (At-I), and AT Derivative time adjust (At-d), the value that the PID constant calculated by the AT is multiplied by each coefficient is written into the set value of the PID constant. However, the coefficient must be a value in the PID constant setting range. Note • Setting that the AT is activated for only the heat PID constant in the Heat/ Co ol control: 50.0 %

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � Just-FiTTER The Just-FiTTER function suppresses overshoot and the settings shown below are available for it. Item (Bank) Display Contents Initial value User level Just-FiTTER assistance coefficient (Extended tuning bank) 0 to 100 (No JF function when set at “0”.) 0 Standard, High function Just-FiTTER settling band (Extended tuning bank) 0.00 to 10.00 % 0.30 % High function • When the control method is other than the ON/OFF control (CtrL ≠ 0), the display and setting can be made. • Function of Just-FiTTER assistance coefficient (JF.Ov) When the Just-FiTTER assistance coefficient (JF.Ov) is “0”, the Just-FiTTER function becomes invalid. When this coefficient is “1” or more, the effect of the overshoot limit/restraint/ control becomes larger as the coefficient becomes larger. • Function of Just-FiTTER settling band (JF.bd) If the deviation (plus or minus) is a larger percentage of the PV range than the preset value, Just-FiTTER starts. If the deviation is a smaller percentage, ST judges that the step response has settled. � � RationaLOOP This RationaLOOP function suppresses the unstable trend if the immediate response to external disturbance is increased by the high precision control logic. The setting shown below is available for it. Item (Bank) Display Contents Initial value User level Control algorithm (Extended tuning bank) 0: PID (Conventional PID) 1: RationaLOOP (High-performance PID) 0 Standard, High function • When the control method is other than the ON/OFF control (CtrL ≠ 0), the display and setting can be made. � � SP lag This SP lag function suppresses changes in MV when the SP is changed. The setting shown below is available for it. Item (Bank) Display Contents Initial value User level SP lag time (Extended tuning bank) 0.0 to 999.9 (No effect when set at “0.0”.) 0.0 High function • When the control method is other than the ON/OFF control (CtrL ≠ 0), the display and setting can be made. • Function of SP lag time (SP.LG) When the SP lag time is set at "0.0", the SP lag function becomes invalid. When this value is "0.1" or more, changes in MV when the SP is changed become smaller and the effect of the overshoot suppression becomes larger as the value becomes larger.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

The AT (auto tuning) function is used in the following cases: • The PID constants are set automatically with the control method set at “Fixed PID” ([CtrL = 1]). • The PV rise is slow or overshoot is large in the control with the PID constants, which have been set automatically using the ST function. • The PV rise becomes slow or overshoot becomes large with the control method set at ST ([CtrL] = 2). The AT function can be used when the control method is set at either “Fixed PID” ([CtrL] = 1) or ST ([CtrL = 2]). � � Starting procedures (1) Make sure that the PV input or operation end (heater power, etc.) is controllable. (2) Make sure that the mode indicator [rdy] is off and the operation is in the RUN mode. If the indicator [rdy] is lit and the operation is in the READY mode, change the mode to the RUN mode. (3) Make sure that the mode indicator [man] is off and the operation is in the AUTO mode. If the indicator [man] is lit and the operation is in the MANUAL mode, change the mode to the AUTO mode. (4) Set the parameter setting [AT Stop/Start] to “AT start ([At] = [At.On])”. � � Stopping procedures The AT function is completed automatically. To stop the AT function, which is running, change the parameter setting [AT Stop/Start] to AT stop ([At] = [At.OF]). Additionally, the AT function is stopped when changing the READY mode to the MANUAL mode. � z Display during execution of AT rdy man ev1 ev2 ev3 ot1 ot2 para mode pv sp LED The decimal point at the 1st digit of the upper display (right end digit) flashes twice repeatedly while the AT function is running. When the AT function is completed and the PID constants are changed, this LED goes off. � z Operation during execution of AT The AT function calculates the PID constants using the limit cycle. (1) When the AT function is started, a point, where the SP and PV deviations are split to “2:1”, is determined as ON/OFF change point of the MV (manipulated variable). (2) When the limit cycle is judged as stable, the PID constants are changed and the AT function is completed. 5 - 4 AT (auto tuning) Function

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

PV SP 2/3 1/3 Insufcient stability AT start Time Normal end Stable cycle In the Heat/Cool control, the AT function is run in the status that both the heat MV and cool MV are operated. In the first half, the MV is changed to the MV low limit/MV high limit. In the latter half, the MV is changed in a slightly narrow range. The following Figure shows an example of the AT execution when the Heat/Cool control deadband is 0.0 %, Heat/Cool control change point is 50.0 %, MV low limit is 0.0 %, and MV high limit is 100.0 %: MV (%) 100.0 Time 50.0 0.0 Heat MV (%) 100.0 Time 50.0 0.0 Cool MV (%) 100.0 Time 50.0 0.0 PV Time SP change point AT is running. Handling Precautions • Before starting the AT function, put the PV input and/or operation end (heater power, etc.) in the controllable status. • When the control method is set at “ON/OFF control” ([CtrL] = 0), the AT function cannot be started. To operate the AT function, set the control method to “Fixed PID” ([CtrL] = 1) or “ST” ([CtrL] = 2). • To start the AT, it is absolutely necessary that the operation is in the READY mode and AUTO mode, and no PV input errors occur. • If the mode is changed to the READY mode or MANUAL mode or if the PV input error or power failure occurs during execution of the AT function, the AT function is stopped without changing of the PID constants.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

• When the Heat/Cool control is not used, the MV becomes a value limited by both ranges, one range is between the MV low limit at AT (AT.OL) and MV high limit at AT (AT.OH), and the other is between the MV low limit (OL-1) and MV high limit (OH-1) of the PID constant. When there are no common portions in two ranges, the AT function is stopped automatically. • When the Heat/Cool control is used, the MV becomes a value limited by the MV low limit at AT (At.OL)/MV high limit at AT (At.OH), the heat MV becomes a value limited by the MV low limit (OL-1)/MV high limit (OH- 1) of the PID constant, and the cool MV becomes a value limited by the output low limit (Cool) (OL.1C)/output high limit (Cool) (OH.1C) of the PID constant. • When the MV low limit at AT (At.OL)/high limit (At.OH), MV low limit (OL- 1)/high limit (OH-1), cool-side MV low limit (OL.1C)/cool-side MV high limit (OH.1C) of the PID constant are set unevenly, the PV may not be changed up or down even though the MV is changed by the AT. In this case, the AT is kept continued. If this occurs, the AT is stopped manually, the high limit and low limit of the manipulated variable are set again, and the AT is started again. • The number of limit cycles and period of time from the AT start to AT end may vary depending on the control subject. • The MV ON and OFF are repeated several times during execution of the AT function to perform the limit cycle. (The OFF operation described here means MV limited by the MV low limit at AT ([At.OL]) or MV high limit at AT ([OL]). The default setting before shipment is “0 %”. Additionally, the ON operation described here means MV limited by the MV high limit at AT ([At.OH]) or MV high limit at AT ([OH]). The default setting before shipment is “100 %”. If this AT operation does not function correctly, take any of the following measures: (1) Change the MV low limit at AT ([At.OL]) or MV high limit at AT ([At. Oh]) to an appropriate value, and then start the AT function. (2) Use the ST function. (3) Set the PID constants manually without use of AT. • The AT progress value can be seen in the operation display mode. 6 - 1 List of Operation Displays (p. 6-1) When the Heat/Cool control is not used, the AT progress value decrements from [4] during execution of the AT function and becomes [0] at completion of the AT function. When the Heat/Cool control is used, the AT progress value decrements from [8] during execution of the AT function and becomes [0] at completion of the AT function. In both cases, the AT progress value may be “1” or “0” when the AT process is in the transient status. • Appropriate PID constants cannot be obtained depending on the control subject. If this happens, set the PID constants manually. • The MV ON/OFF change point determined when the AT function is started does not change even though the SP is changed while the AT is running. AT Stop/Start (p. 5-8) and AT (p. 5-18)

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

When the control method (CtrL) is set to "2" (ST (Self-tuning)), if the following conditions for ST startup are met, ST starts automatically and changes the PID constants. (1) Startup due to change of SP If the SP is changed in RUN mode, ST starts. However, if the amount of SP change is small or if the difference between the SP and PV is small, ST does not start. (2) Startup due to large deviation If the difference between the SP and PV is large while executing control in RUN mode, ST starts. If the difference between the SP and PV is large when READY mode is changed to RUN, ST starts. If the difference between the SP and PV is large when control execution begins in RUN mode after the power has been turned on, ST starts. Handling Precautions • For ST to start, it is essential that the integral time and derivative time of the PID constants be other than "0" ([ I- 1] ≠ 0, [d- 1] ≠ 0). • For ST to start, RUN and AUTO modes must be selected. • Set "High function" to configure the reference values used to judge the amount of SP change or to decide whether the difference between the SP and PV is large or small. However, for most control targets the default settings can be used. • For heat/cool control, ST cannot be used. � � How to start ST (1) Make sure that the PV input and the actuators (heater power, etc.) are ready for control. (2) Make sure that the mode indicator [rdy] is off, indicating RUN mode. If [rdy] is lit, indicating READY mode, change the mode to RUN. (3) Make sure that the [man] mode light is off, indicating AUTO mode. If [man] is lit, indicating MANUAL mode, change the mode to AUTO. (4) Set the control method (CtrL) to "2" (ST (Self-tuning)) in the parameter setup bank. This operation is not needed from the 2nd time on. (5) Set the SP. If ST does not start because the PV is close to the SP (PV≈SP), change the SP so that it is greatly different from the PV. 5 - 5 ST (Self-tuning) Function

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � How to stop ST ST stops automatically. If it is necessary to stop the ST while it is running or to disable ST, set the control method to "Fixed PID" (CtrL = 1) in the parameter setup bank. Also, ST can be stopped by switching to READY or MANUAL mode. � z Display while ST is running While ST is running, the rightmost decimal point LED on the upper display flashes. When ST ends and the PID constants have been changed, this LED turns off. rdy man ev1 ev2 ev3 ot1 ot2 para mode pv sp LED

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

When using ST, follow the rules shown below. z Before starting ST, make the PV input and the actuators (heater power, etc.) ready for control. z Before starting ST, set PID constants that are capable of adequate PID control. • By default, the proportional band [ P- 1 ] = 5.0 %, integral time [  I- 1 ] = 120 s, and derivative time [ d- 1 ] = 30 s. With the above settings, adequate PID control is possible for most control targets. • If the integral time [  I- 1 ] = 0 s, ST will not start. • If the derivative time [ d- 1 ] = 0 s, ST will not start. z To stop control execution while the controller is turned on, change RUN mode to READY, and then turn off the actuator (heater). To resume control execution, turn on the actuator (heater), and then change READY mode to RUN. z If the ST step execution resolution band (ST.SA) is small, even if ST is executed, the PID constants may not be adjusted. For this reason, specify an appropriately large value for the ST step execution resolution band (ST.SA). Handling Precautions • If the above rules are not observed, the PID constants may change to unsuitable values when ST is complete, resulting in poor control. • While ST is running (the LED will be flashing), if the power to the controller is turned off, the PID constants will not be changed. Also, if the power is turned off just before ST finishes, unsuitable PID constants may be set. If the PID constants are unsuitable, the following methods can be used to correct them. (1) Restore the default PID constants Configure as follows: proportional band [ P- 1 ] = 5.0 %, integral time [  I- 1 ] = 120 s, and derivative time [ d- 1 ] = 30 s. (2) Start ST. Or, set the PID constants using AT, and then start ST. � z If control targets interfere with each other If the control targets are located side by side or one above the other, temperature changes in one may affect ST in the other, resulting in slow control response. In this case, set the control method to “Fixed PID” ([CtrL] = 1). � z If the control target is disturbed intermittently In a case like heat sealing by a packing machine, intermittent temperature drops may affect ST. In this case, set the control method to “Fixed PID” ([CtrL] = 1) � z If PV alarm and reset recur frequently While ST is running, if PV alarms and resets are repeated frequently, they may be interpreted as hunting, resulting in changes of the PID parameters. If these circumstances arise during instrumentation, etc., put the unit into READY mode or disable ST. 5 - 6 Precautions for ST (Self-tuning)

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

The following shows the functional block diagram of the SP: One LSP group exists. Two or more LSP groups exist. LSP system group (Setting: Setup C30) LSP1 (Setting: SP SP 1) DI Assignment is not provided. DI Assignment is provided. DI Assignment of LSP group selection provided/not provided. (Setting: DI Assignment di 1. 1 to di 3. 1) LSP group number (Setting: LSP group number in operation display mode) Logical operation of DI (Setting: General DI Assignment) LSP value in use SP SP high limit/low limit (Setting: Setup C07, C08) SP ramp unit (Setting: Setup C32) SP ramp-up/ramp-down (Setting: Parameter SPU, SPd) DI Assignment of SP ramp enabled/disabled. (Setting: DI Assignment di 1. 1 to di 3. 1) LSP 1 to 4 (Setting: SP SP 1 to SP4) Note LSP is a local SP and shows that the data is retained inside this unit. On the contrary, SP by the analog input from the outside is called RSP or remote SP. However, the RSP function is not provided on this unit. 5 - 7 SP

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � SP setup in operation display mode The set value for LSP in use of LSP1 to 4 can be set. The LSP set value is different from the SP display value during SP ramp. However, the set value is displayed while the key is being operated to change the setting. Item (Bank) Display Contents Initial value User level SP (Operation display) PV is shown on the upper display. SP low limit to SP high limit U 0 U Simple, Standard, High function • When [bit 1: SP display] of the PV/SP display setup (setup C74) is set at "1" (display is provided), the display and setting can be made. � � LSP system group The LSP system group can be selected. Item (Bank) Display Contents Initial value User level LSP system group (Setup bank) 1 to 4 1 Simple, Standard, High function � � LSP1 to 4 The set values can be set for four LSP groups. Item (Bank) Display Contents Initial value User level SP (SP bank) SP low limit to SP high limit U 0 U Simple, Standard, High function 0 U 0 U 0 U • The display and setting can be made for the LSP system group selected in [C30: LSP system group] . � � LSP group number The LSP group number can be set. Item (Bank) Display Contents Initial value User level LSP group No. (Operation display) Numeric value at the rightmost digit of the display. 1 to LSP system group 1 Simple, Standard, High function • When [C30: LSP system group] is set at “2” or more and [bit 2: LSP group number display] of the PV/SP display setup (setup C74) is set at “1” (display is provided), the display can be made. • When the display is possible and the DI Assignment of the LSP group selection is not performed, the setting can be made.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � DI Assignment of LSP group selection The LSP group selection can be set for internal contacts 1 to 3 using the DI Assignment. Item (Bank) Display Contents Initial value User level Internal contact 1 to 3 Operation type (DI Assignment bank) 0: No function 1: LSP group selection (0/+1) 2: LSP group selection (0/+2) 3: LSP group selection (0/+4) 4 to 20: Other functions 0 Simple, Standard, High function 0 0 • Details of LSP group selection with the internal contact function The following shows the LSP group selection value according to the ON/OFF status of each internal contact: LSP group selection (0/+1) OFF: 0 ON: 1 LSP group selection (0/+2) OFF: 0 ON: 2 LSP group selection (0/+4) OFF: 0 ON: 4 The value, that "1" is added to the sum of the LSP group selection values according to the ON/OFF status of each internal contact, becomes the LSP group number. For example, when the sum of LSP group selection values of internal contact 1 to 3 is "1", the LSP group number becomes "2". • Even though the LSP system group is "1", the display and setting can be made, but the LSP group selection with the internal contact function becomes invalid.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � SP ramp unit The unit of the SP up/down ramp can be set. Item (Bank) Display Contents Initial value User level SP ramp unit (Setup bank) 0: 0.1 U/s 1: 0.1 U/min 2: 0.1 U/h 0 High function • "0.1U" shows that the decimal point position of the PV is shifted one digit rightward. Example: When the thermocouple input is in a range of -200 to +1200 °C, "0.1 U" is "0.1 °C". Example: When the DC voltage input is in a range of 0.0 to 100.0, "0.1U" is "0.01". For the relationship between the decimal point position and the type of PV input range, refer to the next section, "� SP ramp-up/ramp-down." Handling Precautions When using the DC voltage/DC current input with setting of 3 digits after the decimal point, "0.1U" is "0.0001". However, the SP up ramp/SP down ramp setting cannot display 4 digits after the decimal point, the value is displayed without use of the decimal point. � � SP up ramp/down ramp The SP up ramp and down ramp can be set. Item (Bank) Display Contents Initial value User level SP up ramp (Parameter bank) 0.0U: No ramp 0.1 to 999.9 U (The unit of the ramp time is selected using the SP ramp unit.) 0.0 U High function SP down ramp (Parameter bank) 0.0 U • When an initial value of “0.0U” is set, the SP ramp function does not function. Therefore, when the up ramp setting is set to “0.1U” or more and the down ramp is set to “0.0 U”, the SP ramp functions only during SP up and the SP ramp does not function during SP down. Additionally, the reverse operation can also be set so that the SP ramp functions only during SP up and it does not function during SP down. • Regarding the setting for the number of digits after the decimal point (C04), the SP ramp display shows one digit more than is shown for the PV. For linear input, if C04 is set for 3 digits after the decimal point, no decimal point is displayed in the SP ramp value, but all 4 displayed digits are after the decimal point. The unit for the SP ramp can be selected from every second, every minute, and every hour in C32 of the SETUP bank. The table below shows how the decimal point position varies depending on the PV input range. C01 (PV input range type) C04 (Decimal point position) SPU (SP ramp up) SPD (SP ramp down) 2 (0 to 1200°C) Setting disabled 0.0 to 999.9 0.0 to 999.9 3 (0.0 to 800.0°C) 0 (No decimal point) 0.0 to 999.9 0.0 to 999.9 1 (1 digit after the decimal point) 0.00 to 99.99 0.00 to 99.99 88 (0 to 10V) 0 (No decimal point) 0.0 to 999.9 0.0 to 999.9 1 (1 digit after the decimal point) 0.00 to 99.99 0.00 to 99.99 2 (2 digits after the decimal point) 0.000 to 9.999 0.000 to 9.999 3 (3 digits after the decimal point) 0.0000 to 0.9999 0.0000 to 0.9999

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

• The ramp is started assuming that the current PV value is used as start point when any of the following conditions is satisfied: The power is turned ON. READY+AUTO status is changed to RUN+AUTO status. RUN+MANUAL status is changed to RUN+AUTO status. The AT function is completed (both normal end and forced stop). Handling Precautions Before changing the slope of the SP ramp, make sure that SP ramping is not in progress. If the setting is changed while the SP ramp is in progress, the SP may change suddenly. � � SP low limit/high limit The SP low limit and high limit can be set to limit the SP range. Item (Bank) Display Contents Initial value User level SP low limit (Setup bank) PV range low limit to PV range high limit PV range low limit Standard, High function SP high limit (Setup bank) PV range low limit to PV range high limit PV range high limit Standard, High function Handling Precautions When the PV input range type (setup C01) is set, the SP low limit and high limit are initialized. � � DI Assignment of SP ramp enabled/disabled The LSP group selection can be set for internal contacts 1 to 3 using the DI Assignment. Item (Bank) Display Contents Initial value User level Internal Contacts 1 to 3 Operation type (DI Assignment bank) 0: No function 13: SP ramp enabled/disabled. 1 to 12, 14 to 20: Other functions 0 Simple, Standard, High function 0 0 • Details of SP ramp enabled/disabled with internal contact function The following shows the SP ramp enabled/disabled setting with the internal contact ON/OFF: OFF: SP ramp enabled. ON: SP ramp disabled. The SP ramp enabled/disabled is set for only one internal contact. • When the SP ramp is set disabled, the SP ramp operation is stopped and the SP value becomes the final SP.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

The following shows the functional block diagram of the DI (digital input) and internal contact: Input bit function is not used. (Setting: [Input bit function is not used.] must be set using DI Assignment di 1.2 to di 3.2.) DI status (ON/OFF) Input assignment Polarity (Setting: DI Assignment Polarity A to D di 1.7 to di 3.7) Internal Contact Input bit function result Input bit function is not used. Input assignment (Setting: DI Assignment Input assignment A di 1.3 to di 3.3, DI Assignment Input assignment B di 1.4 to di 3.4, DI Assignment Input assignment C di 1.5 to di 3.6, DI Assignment Input assignment D di 1.6 to di 3.6) Input bit function 1 to 4 (Setting: DI Assignment Input bit function di 1.2 to di 3.2) Input bit function Polarity (Setting: DI Assignment di 1.8 to di 3.8) Input bit function is used. Event channel defnitions (Setting: DI Assignment di 1.9 to di 3.9) Operation type (Setting: DI Assignment di 1. 1 to di 3. 1) Internal contact function Polarity (Setting: DI Assignment di 1.8 to di 3.8) Handling Precautions Even though three internal contacts 1 to 3 are provided, the number of digital inputs determined by the optional model is 0 to 2 points. With the default settings before shipment, the operations of digital input 1 to 2 have already been connected to internal contacts 1 to 2. To utilize the operation of internal contact 3, it is absolutely necessary to set the DI Assignment. 5 - 8 DI (Digital Input) and Internal Contact

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � Operation type The operation type by the internal contact function can be set. Item (Bank) Display Contents Initial value User level Internal Contact 1 Operation type (DI Assignment bank) 0 to 20 For details about function by each set value, refer to the Table below. 0 Simple, Standard, High function Internal Contact 2 Operation type (DI Assignment bank) 0 Internal Contact 3 Operation type (DI Assignment bank) 0 Handling Precautions • For [1 to 3: LSP group selection], the value that “1” is added to the sum of weights (+ 1, + 2, +4), the internal contact of which is turned ON, becomes the LSP group number. • Do not use [14: PV value hold], [15: PV Max. hold], and [16: PV Min. hold] with they mixed. • Do not set the same operation type other than [0: No function] and [1 to 3: LSP group selection] for multiple internal contacts. • When using the Heat/Cool control, do not use [12: Control action direct/ reverse selection]. • For timer stop/start, set a target Event channel using [Event channel def. of internal contact]. The following Table shows the contents of the dI settings: Set value Function Operation at OFF Operation at ON 0 No function None None 1 LSP group selection (0/+1) LSP No.: +0 LSP No.: +1 2 LSP group selection (0/+2) LSP No.: +0 LSP No.: +2 3 LSP group selection (0/+4) LSP No.: +0 LSP No.: +4 4 PID group selection (0/+1) Invalid Invalid 5 PID group selection (0/+2) Invalid Invalid 6 PID group selection (0/+4) Invalid Invalid 7 RUN/READY mode selection RUN READY 8 AUTO/MANUAL mode selection AUTO MANUAL 9 LSP/RSP mode selection Invalid Invalid 10 AT (Auto tuning) Stop/Start AT Stop AT Start 11 ST (Self-tuning) disabled/enabled ST disabled ST enabled 12 Control action direct/reverse selection Set action Reverse action of setting 13 SP ramp enabled/disabled SP ramp enabled SP ramp disabled 14 PV value hold No-hold Hold 15 PV Max. hold No-hold Hold 16 PV Min. hold No-hold Hold 17 Timer Stop/Start Timer stop Timer start 18 Release all DO latches Continue if latch exists. Latch release 19 Advance operation Invalid Invalid 20 Step hold Invalid Invalid

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � Internal event No. assignment When the operation type is the timer start/stop, a target internal event number can be set. Item (Bank) Display Contents Initial value User level Internal Contact 1 Internal event No. assignment (DI Assignment bank) 0: Every Internal Event 1 to 5: Internal Event number 0 High function Internal Contact 2 Internal event No. assignment (DI Assignment bank) 0 Internal Contact 3 Internal event No. assignment (DI Assignment bank) 0 • When the operation type of the same internal contact No. is set at “Timer stop/ start”, the display and setting can be made. � � Input bit function Four kinds of input bit functions are provided. What function of four functions is used or is not used can be set. Item (Bank) Display Contents Initial value User level Internal Contact 1 Input bit function (DI Assignment bank) 0: Not used (Default input) 1: Function 1 ((A and B) or (C and D)) 2: Function 2 ((A or B) and (C or D)) 3: Function 3 (A or B or C or D) 4: Function 4 (A and B and C and D) 0 High function IInternal Contact 2 Input bit function (DI Assignment bank) 0 Internal Contact 3 Input bit function (DI Assignment bank) 0 • When the set value is “0”, the input bit function is not used and the default input is used. The following shows the default input of each internal contact: Internal Contact 1: DI (digital input) 1 Internal Contact 2: DI (digital input) 2 Internal Contact 3: OFF status • In the input bit function, the logical operations (AND, OR) of each of internal contacts 1 to 3 are combined. In input bit functions 1 to 4, the combination of the logical operations may vary. The following shows one logical operation: Logical AND Logical OR OFF and OFF = OFF OFF or OFF = OFF ON and OFF = OFF ON or OFF = ON ON and ON = ON ON or ON = ON • “OFF” is “contact open (OPEN)” or “0” when expressed using the numerical value. • “ON” is “contact close (CLOSE)” or “1” when expressed using the numerical value.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � Input assign The assign of four inputs (A, B, C, D) used for the input bit function can be set. Item (Bank) Display Contents Initial value User level Internal Contact 1 Input assign A (DI Assignment bank) 0: Normally opened. (OFF, 0) 1: Normally closed. (ON, 1) 2: DI1 3: DI2 4 to 9: Undefined. 10: Internal Event 1 11: Internal Event 2 12: Internal Event 3 13: Internal Event 4 14: Internal Event 5 15 to 17: Undefined. 18: Communication DI1 19: Communication DI2 20: Communication DI3 21: Communication DI4 22: MANUAL mode 23: READY mode 24: Undefined. 25: AT running 26: During SP ramp 27: Undefined. 28: Alarm occurs. 29: PV alarm occurs. 30: Undefined. 31: mode key pressing status 32: Event output 1 status 33: Control output 1 status 2 High function Internal Contact 1 Input assign B (DI Assignment bank) 0 Internal Contact 1 Input assign C (DI Assignment bank) 0 Internal Contact 1 Input assign D (DI Assignment bank) 0 Internal Contact 2 Input assign A (DI Assignment bank) 3 Internal Contact 2 Input assign B (DI Assignment bank) 0 Internal Contact 2 Input assign C (DI Assignment bank) 0 Internal Contact 2 Input assign D (DI Assignment bank) 0 Internal Contact 3 Input assign A (DI Assignment bank) 4 Internal Contact 3 Input assign B (DI Assignment bank) 0 Internal Contact 3 Input assign C (DI Assignment bank) 0 Internal Contact 3 Input assign D (DI Assignment bank) 0 • When the input bit function of the same internal contact No. is set for input bit functions 1 to 4, the display and setting can be made.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � Polarity of input assign The polarity of four input assigns (A, B, C, D) used for the input bit function can be set. Item (Bank) Display Contents Initial value User level Internal Contact 1, Polarity A to D (DI Assignment bank) The digits are called 1st digit, 2nd digit, 3rd digit, and 4th digit from the right end. 1st digit: Input assign A Polarity setting 2nd digit: Input assign B Polarity setting 3rd digit: Input assign C Polarity setting 4th digit: Input assign D Polarity setting 0: Direct 1: Reverse 0000 High function Internal Contact 2, Polarity A to D (DI Assignment bank) 0000 Internal Contact 3, Polarity A to D (DI Assignment bank) 0000 • When the input bit function of the same internal contact No. is set for input bit functions 1 to 4, the display and setting can be made. � � Polarity of input bit function The polarity after the input bit function (functions 1 to 4) can be set. Item (Bank) Display Contents Initial value User level Internal Contact 1 Polarity (DI Assignment bank) 0: Direct 1: Reverse 0 High function Internal Contact 2 Polarity (DI Assignment bank) 0 IInternal Contact 3 Polarity (DI Assignment bank) 0

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � DI Assignment setting with Smart Loader Package SLP-C35 When setting [DI Assignment] with the Smart Loader Package SLP-C35, select [Edit (E)] → [Input port setup (O)] in that order from the [Input] menu. The input bit function, input assign, polarity of input assign, and polarity of input bit function can be easily set using visual images as shown below. Select the input bit function. The image of the ladder is changed according to the selected input bit function. Select four input assigns A to D. Select whether or not the polarity is set for assigns A to D. Select whether or not the polarity of the bit function is made. Handling Precautions In addition to the selection through the menu, the Input port setup window can also be opened using the following procedures: Click the input/output port setup icon . Right-click in the input bit function setting window. Press the [Ctrl] and [P] keys at the same time.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

The result of the internal event process can be output to the control output or event output through the DO (digital output) process. 2 - 1 Input/Output Configuration (p. 2-1) The following shows the functional block diagram of the internal event: Operation type (Setting: Event Confguration Operation type E 1.C 1 to E5.C 1) Direct/reverse, Standby (Setting: Event Confguration, Direct/reverse, Standby E 1.C2 to E5.C2) Controller alarm OR/AND (Setting: Event Confguration E 1.C3 to E5.C3) EVENT state at READY (Setting: Event Confguration E 1.C2 to E5.C2) Main setting, sub setting, hysteresis, special OFF setup (Setting: Event E 1 to E5, E 1 .SB to E5.SB, E 1 .HY to E5.HY Event Confguration E 1 .C3 to E5.C3) ON delay, OFF delay, Delay time unit (Setting: Event E 1.ON to E5.ON, E 1.OF to E5.OF, Event Confguration E 1.C3 to E5.C3) Internal Event status Handling Precautions Even though five internal events 1 to 5 are provided, the number of event outputs determined by the optional model is 0 to 3 points. With the default settings before shipment, the operations of internal events 1 to 3 can be output to event outputs 1 to 3. To utilize the operations of internal events 4 to 5, it is absolutely necessary to set the DO Assignment. 5 - 9 Internal Event

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

� � Operation According to the operation type, direct/reverse, main setting, sub setting, hysteresis, and other settings, the operation of the internal event becomes as follows: [List of internal event operations] Note For details about U (unit), refer to the attached glossary. Operation type Set value of operation type Direct action z shows that the ON/OFF is changed at this value.  shows that the ON/OFF is changed at a point that "1U" is added to this value. Reverse action z shows that the ON/OFF is changed at this value.  shows that the ON/OFF is changed at a point that "1U" is added to this value. No event 0 Always OFF Always OFF PV high limit 1 ON HYS Main setting PV ON HYS Main setting PV PV low limit 2 Main setting PV ON HYS Main setting PV ON HYS PV high/low limit 3 Main setting Sub-setting (*1) PV ON HYS ON HYS (*1) Main setting (*1) Sub-setting (*1) SP ON HYS HYS Deviation high limit 4 ON HYS SP + Main setting PV ON HYS SP + Main setting PV Deviation low limit 5 SP + Main setting PV ON HYS SP + Main setting PV ON HYS Deviation high/ low limit 6 Main setting Sub-setting PV SP ON HYS ON HYS Deviation high limit (Final SP reference) 7 ON HYS SP + Main setting PV Same as the direct action of the deviation high limit when the SP ramp is not used. The difference is that the SP ramp does not use the current SP, but it uses the final SP. ON HYS SP + Main setting PV Same as the reverse action of the deviation high limit when the SP ramp is not used. The difference is that the SP ramp does not use the current SP, but it uses the final SP. ON HYS HYS Main setting Sub-setting PV SP

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Operation type Set value of operation type Direct action z shows that the ON/OFF is changed at this value.  shows that the ON/OFF is changed at a point that "1U" is added to this value. Reverse action z shows that the ON/OFF is changed at this value.  shows that the ON/OFF is changed at a point that "1U" is added to this value. Deviation low limit (Final SP reference) 8 SP + Main setting PV ON HYS Same as the direct action of the deviation low limit when the SP ramp is not used. The difference is that the SP ramp does not use the current SP, but it uses the final SP. SP + Main setting PV ON HYS Same as the reverse action of the deviation low limit when the SP ramp is not used. The difference is that the SP ramp does not use the current SP, but it uses the final SP. Deviation high/ low limit (Final SP reference) 9 Main setting Sub-setting PV SP ON HYS ON HYS Same as the direct action of the deviation high/low limit when the SP ramp is not used. The difference is that the SP ramp does not use the current SP, but it uses the final SP. ON HYS HYS Main setting Sub-setting PV SP Same as the reverse action of the deviation high/low limit when the SP ramp is not used. The difference is that the SP ramp does not use the current SP, but it uses the final SP. SP high limit 10 ON HYS Main setting SP ON HYS Main setting SP SP low limit 11 Main setting SP ON HYS Main setting SP ON HYS SP high/low limit 12 Main setting (*1) Sub-setting (*1) SP ON HYS ON HYS Main setting (*1) Sub-setting (*1) SP ON HYS HYS MV high limit 13 ON HYS Main setting MV ON HYS Main setting MV MV low limit 14 Main setting MV ON HYS Main setting MV ON HYS MV high/low limit 15 Main setting (*1) Sub-setting (*1) MV ON HYS ON HYS Main setting (*1) Sub-setting (*1) MV ON HYS HYS Heater 1 burnout/ Over-current*2 16 Main setting Sub-setting ON HYS ON HYS CT1 at output ON. OFF before measuring the CT1 current value CT1 at output ON. ON HYS HYS Main setting Sub-setting OFF before measuring the CT1 current value

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Operation type Set value of operation type Direct action z shows that the ON/OFF is changed at this value.  shows that the ON/OFF is changed at a point that "1U" is added to this value. Reverse action z shows that the ON/OFF is changed at this value.  shows that the ON/OFF is changed at a point that "1U" is added to this value. Heater 1 short- circuit*2 17 ON HYS Main setting CT1 at output OFF. OFF before measuring the CT1 current value ON HYS Main setting CT1 at output OFF. OFF before measuring the CT1 current value Heater 2 burnout/ Over-current*2 18 Main setting Sub-setting ON HYS ON HYS CT2 at output ON. OFF before measuring the CT2 current value CT2 at output ON. ON HYS HYS Main setting Sub-setting OFF before measuring the CT2 current value Heater 2 short- circuit*2 19 ON HYS Main setting CT2 at output OFF. OFF before measuring the CT2 current value ON HYS Main setting CT2 at output OFF. OFF before measuring the CT2 current value *1 If the setting is made so that the main setting is greater than the sub setting, the operation is performed with the main setting swapped for the sub setting automatically. *2 When the event type is CT1/2 heater burnout/over-current or CT1/2 heater short-circuit,the status becomes that the event judgment cannot be made from the time of power ON until that CT input current value is measured for the first time. In this case, the internal event output is OFF for both of direct action and reverse action in the direct/reverse setting. To avoid that the output becomes OFF at power ON when used in reverse action, set as follows: (Setting example) For direct/reverse setting of CT1/2 heater burnout/over-current or CT1/2 short-circuit event, select the direct action, and set the reverse operation in DO assignment calculation of the event output terminal (event terminal or control output terminal) CT event(direct action) [Reverse] (DO output) Normally open(0) Normally open(0) Normally open(0)

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Operation type Set value of operation type Direct action Reverse action Loop diagnosis 1 20 The event is turned ON when any change in PV corresponding to increase/decrease in MV (Manipulated variable) is not observed. This event is used to detect any fault at the operation end. z Setting items • Main setting: MV (Manipulated variable) • Sub-setting: PV • ON delay time: Diagnosis time z Operation specifications The event is turned ON when the value does not reach the PV set in the sub-setting within the diagnosis time (ON delay time) (conditions 1) even though the MV exceeding the main setting is held (conditions 2). z CAUTION When setting the ON delay, it is necessary to put in "High function configuration". The default setting of the ON delay before shipment is 0.0 s. Heat control Sub-setting Main setting Time Conditions 3 ON delay set time ON delay is started when conditions 1 and 2 are satisfed. Area satisfying conditions 1 Area satisfying conditions 2 Time Time PV MV EV ON HYS Cool control Sub-setting Main setting Time Conditions 3 ON delay set time ON delay is started when conditions 1 and 2 are satisfed. Area satisfying conditions 1 Area satisfying conditions 2 Time Time PV MV EV ON HYS