Autonics MT-XGT Technical Support Manual

Text of the manual

© Copyright Reserved Autonics Co., Ltd.

3 Preface Thank you very much for selecting Autonics products. Please familiarize yourself with the information contained in the Safety Precautions section before using this product. This user manual contains information about the product and its proper use, and should be kept in a place where it will be easy to access.

Technical Support Manual Guide

4 © Copyright Reserved Autonics Co., Ltd. Technical Support Manual Guide  Please familiarize yourself with the information in this manual before using the product.  This manual provides detailed information on the product's features. It does not offer any guarantee concerning matters beyond the scope of this manual.  This manual may not be edited or reproduced in either part or whole without permission.  This manual is not provided as part of the product package. Please visit our home-page (www.autonics.com) to download a copy.  The manual's content may vary depending on changes to the product's software and other unforeseen developments within Autonics, and is subject to change without prior notice. Upgrade notice is provided through our homepage.  We contrived to describe this manual more easily and correctly. However, if there are any corrections or questions, please notify us these on our homepage.

Technical Support Manual Symbols

© Copyright Reserved Autonics Co., Ltd. 5 Technical Support Manual Symbols Symbol Description Supplementary information for a particular feature. Failure to follow instructions can result in serious injury or death. Failure to follow instructions can lead to a minor injury or product damage. An example of the concerned feature's use. ※1 Annotation mark.

© Copyright Reserved Autonics Co., Ltd.

Safety Precautions  Following these safety precautions will ensure the safe and proper use of the product and help prevent accidents, as well as minimizing possible hazards.  Safety precautions are categorized as Warnings and Cautions, as defined below: Warning Failure to follow the instructions may lead to a serious injury or accident. Caution Failure to follow the instructions may lead to a minor injury or accident.  Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.) Failure to follow this instruction may result in personal injury, fire, or economic loss.  The unit must be installed on a device panel before use. Failure to follow this instruction may result in electric shock.  Do not connect, repair, or inspect the unit while connected to a power source. Failure to follow this instruction may result in electric shock.  Do not disassemble or modify the unit. Please contact us if necessary. Failure to follow this instruction may result in electric shock or fire.  Check the terminal numbers before connecting the power source and measurement input. Failure to follow this instruction may result in fire.  Do not use the unit outdoors. Failure to follow this instruction may result in electric shock or shorten the life cycle of the unit.  When connecting the power input and relay output cables, use AWG20 (0.05mm2) cables and make sure to tighten the terminal screw bolt above 0.74N.m to 0.90N.m. Failure to follow this instruction may result in fire due to contact failure.  Use the unit within the rated specifications. Failure to follow this instruction may result in electric shock or shorten the life cycle of the unit.  Do not use loads beyond the rated switching capacity of the relay contact. Failure to follow this instruction may result in insulation failure, contact failure, contact bonding, relay damage, or fire.  Do not use water or oil-based detergent when cleaning the unit. Use dry cloth to clean the unit. Failure to follow these instructions may result in electric shock or fire.

© Copyright Reserved Autonics Co., Ltd.

7  Do not use the unit where flammable or explosive gas, humidity, direct sunlight, radiant heat, vibration, and impact may be present. Failure to follow this instruction may result in fire or explosion.  Keep dust and wire residue from flowing into the unit. Failure may result in fire or product malfunction.  Check the polarity of the measurement input contact before wiring the unit. Failure to follow this instruction may result in fire or explosion.

Table of Contents

© Copyright Reserved Autonics Co., Ltd. 9 Table of Contents Preface ............................................................................................................................. 3 Technical Support Manual Guide ..................................................................................... 4 Technical Support Manual Symbols ................................................................................. 5 Safety Precautions ........................................................................................................... 6 Table of Contents ............................................................................................................. 9 1 System ....................................................................................................... 11 1.1 Version ................................................................................................................ 11 1.2 Connections ........................................................................................................ 11 1.3 Communication cable connection ....................................................................... 11 2 Communication Setting ............................................................................ 13 2.1 MT4W Setting ..................................................................................................... 13 2.2 XGB Setting ........................................................................................................ 14 3 Operation Check ....................................................................................... 23

© Copyright Reserved Autonics Co., Ltd.

11 1 System 1.1 Version Software Version Note Operations Windows 7 — XG 5000 V4.07 Release : 2016.03.29 1.2 Connections RS-485 XGK-CPUE MT4W MT4W MT4W MT4W (XGl-CH2A) 1.3 Communication cable connection MT4W Cable connection PLC (XGT – XGL-CH2A) RS – 485 (-) RX - RX + RS – 485 (+) TX - TX +

2 Communication Setting

© Copyright Reserved Autonics Co., Ltd. 13 2 Communication Setting 2.1 MT4W Setting 1st Supply power to the MT4W unit. Hold the MODE key for 5 sec to enter parameter setting group. 2nd Enter PA2 and set the communication settings as below. Parameter Display Setting Note Communication address ADRS 01 User setting Communication speed BPS 96 User setting Communication parity bit PRTY NONE Fixed Communication stop bit STP 2 Fixed Communication response waiting time RSwT 20 User setting * Press the MODE key in RUN mode, it enters to PA0. * Hold the MODE key for 3 sec in RUN mode, it enters to PA1. * Hold the MODE key for 5 sec in RUN mode, it enters to PA2 before PA1. * It is advanced to current display parameter releasing the MODE key at PA1 or PA2. * Hold the MODE key for over 3 sec in any parameter group, it returns to RUN mode. * If any key is not entered for 60 sec in each parameter, it returns to RUN mode. * Only for RS485 communication output model is available.

2 Communication Setting

14 © Copyright Reserved Autonics Co., Ltd. 2.2 XGB Setting 1st Run XG5000, and select [Project] – [New Project] on menu. Enter project name and select CPU Series and type.

2 Communication Setting

© Copyright Reserved Autonics Co., Ltd. 15 2nd After executing, enter the below contents at XG5000. * This communication program is only for test. Before using it at field, review and test the program fully.

2 Communication Setting

16 © Copyright Reserved Autonics Co., Ltd. 3rd Select the desired connection method at [Online] – [Connection Settings]. This test is connected via USB. After connecting completed, select [Online] – [Change Mode] – [Stop]. 4th At [Online] – [I/O Information], click ‘I/O Sync’. When I/O syncronizing is completed, it is set same as the used module. Connection settings Type Type USB Depth Local

2 Communication Setting

© Copyright Reserved Autonics Co., Ltd. 17 5th When I/Osyncronizing is completed, the used communication module is added at the below standard network. Double-click the right communication module. 6th [Standard Settings-Cnet] dialog box appears. At standard settings, set as below. Item Setting Note Standard Settings Channel 2 Communication type RS-485 Fixed Communication speed 9600 User setting Terminating resisters Disable User setting Station No. 0 User setting Operation mode Channel 2 Use P2P

2 Communication Setting

18 © Copyright Reserved Autonics Co., Ltd. 7th At advanced settings, set as below. Item Channel 2 Advanced settings Data bit 8 Stop bit 2 Parity bit NONE 8th Double-click ‘P2P Channel’ and select ‘Modbus RTU client’ of ‘Use P2P’. Click ‘OK’.

2 Communication Setting

© Copyright Reserved Autonics Co., Ltd. 19 9th Double-click ‘P2P Channel’ to select Modbus RTU client at Use P2P and click ‘OK’.

2 Communication Setting

20 © Copyright Reserved Autonics Co., Ltd. 10th Below P2P channel, double-click ‘P2P block’ and set as below. CH P2P function Conditional flag Command type Data type Destination station number 2 READ(PV) M00000 to M00003 2. Continuous WORD (size: 4) Enter destination station (1 to 4) * Variable setting contents are set as belows. Click ‘Setting’ to set variable. * Modbus Mapping Table Address Command Transmission data Note 30001(0000) 04 Present measurement value ㆍ Standard - Transmits 5% to 110% ㆍ Scale - Transmits display range -1999 to 9999 Data transmission for measurement error ㆍ Standard Transmits 9999 when HHHH is displayed. Transmits -1999 when LLLL is displayed. ㆍ Scale Transmits the setting values of H-SC and L-SC. Transmits 9999 for d-HH. Transmits -1999 for d-LL. 30002(0001) 04 Dot setting Transmits dot position setting value of PA1 dot mode. ㆍ Standard 0.000→0003H, 0.00→0002H 0.0→0001H, 0→ 0000H ㆍ Scale 0.000→0103H, 0.00→0102H 0.0→ 0101H, 0→0100H 30003(0002) 04 High peak value Transmits max. display value among the measurement display values. 30004(0004) 04 Low peak value Transmits min. display value among the measurement display values.

2 Communication Setting

© Copyright Reserved Autonics Co., Ltd. 21 * PV setting Address Reading area (setting) Saving area (setting) Address (fixed) Address 1 0x30000 D00000 N00021 Address 2 0x30000 D00004 N00062 Address 3 0x30000 D00008 N00103 Address 4 0x30000 D00012 N00144 11th At [Online] – [Connection Settings], select connection type. Select [Online] – [Write] to execute download.