Assa Abloy Orion Installation Manual
Read Online
Read the Assa Abloy Orion Installation Manual online using the built-in PDF viewer.
Text of the manual
ASSA ABLOY Hospitality
66 8003 016-3
Copyrights
The information in this document is subject to change at the sole discretion of
ASSA ABLOY without notice.
Any use, operation or repair in contravention of this document is at your own risk.
ASSA ABLOY does not assume any responsibility for incidental or consequential
damages arising from the use of this manual.
All information and drawings in this document are the property of ASSA ABLOY.
Unauthorized use and reproduction is prohibited.
VingCard and Elsafe are registered trademarks of ASSA ABLOY.
ASSA ABLOY Hospitality
66 8003 016-3
Table of contents
.................................................................................................6
FCC and ISED(IC) statements
........................................................................................................................ 6
FCC statements
........................................................................................................................ 7
ISED (IC) statements
................................................................................................................................................ 7
End product labeling
.................................................................................................8
1. Introduction
.................................................................................................9
2. To install the software
........................................................................................................................ 9
2.1 To install a Visionline option
........................................................................................................................ 9
2.2 To install an Orion EMS client
................................................................................................................................................ 9
2.2.1 To start an Orion EMS client
.................................................................................................10
3. To install the Orion EMS devices
........................................................................................................................ 10
3.1 To install a thermostat
................................................................................................................................................ 11
3.1.1 Step-by-step procedure
................................................................................................................................................ 12
3.1.2 Thermostat dimensions
................................................................................................................................................ 13
3.1.3 To mount a thermostat
................................................................................................................................................ 14
3.1.4 To wire a thermostat
....................................................................................................................................... 15
3.1.4.1 Low voltage terminal block (12 pole; 3.5mm spacing)
....................................................................................................................................... 16
3.1.4.2 High voltage terminal block (8 pole; 5.0mm spacing)
....................................................................................................................................... 17
3.1.4.3 Switch output
....................................................................................................................................... 17
3.1.4.4 Proportional output
....................................................................................................................................... 18
3.1.4.5 Extra input
....................................................................................................................................... 19
3.1.4.6 Wired door switch
....................................................................................................................................... 20
3.1.4.7 Outputs N, L, RV, Y and W
....................................................................................................................................... 22
3.1.4.8 More about live output
....................................................................................................................................... 23
3.1.4.9 Fan outputs
....................................................................................................................................... 23
3.1.4.10 Connection example for floating valve
........................................................................................................................ 24
3.2 To install an RF door switch
................................................................................................................................................ 24
3.2.1 RF door switch dimensions
................................................................................................................................................ 25
3.2.2 RF door switch magnet dimensions
................................................................................................................................................ 25
3.2.3 Wall-mounted casing
.................................................................................................26
4. To set up a thermostat profile
........................................................................................................................ 26
4.1 General
........................................................................................................................ 27
4.2 HVAC
................................................................................................................................................ 28
4.2.1 Heating
....................................................................................................................................... 28
4.2.1.1 2-pipe fan coil with automatic switching
....................................................................................................................................... 29
4.2.1.2 Proportional
....................................................................................................................................... 30
4.2.1.3 Floating valve
................................................................................................................................................ 31
4.2.2 Cooling
....................................................................................................................................... 31
4.2.2.1 2-pipe fan coil with automatic switching
....................................................................................................................................... 32
4.2.2.2 Proportional
....................................................................................................................................... 33
4.2.2.3 Floating valve
................................................................................................................................................ 34
4.2.3 Consumption
........................................................................................................................ 34
4.3 Fan
ASSA ABLOY Hospitality
66 8003 016-3
........................................................................................................................ 35
4.4 Limits
........................................................................................................................ 37
4.5 Timeout
........................................................................................................................ 37
4.6 Deadband
........................................................................................................................ 38
4.7 Misc
.................................................................................................43
5. To commission the system
........................................................................................................................ 43
5.1 To join the thermostat to the network
........................................................................................................................ 45
5.2 To commission when thermostat controller is not used
.................................................................................................47
6. To check the installation
........................................................................................................................ 47
6.1 To check diagnostics
........................................................................................................................ 48
6.2 To test the in-room devices
.................................................................................................50
Appendix A: Quick reference of technical data
.................................................................................................52
Appendix B: Firmware upgrade
.................................................................................................54
Appendix C: To set up a suite
........................................................................................................................ 54
Introduction
........................................................................................................................ 54
To set up a suite with foyer door
................................................................................................................................................ 55
To enable 'suite with foyer door' in Visionline
................................................................................................................................................ 55
To set up the online network
................................................................................................................................................ 56
To initialize the master thermostat with suite settings
................................................................................................................................................ 57
To read out the thermostat status
................................................................................................................................................ 57
Online network tree
........................................................................................................................ 58
To set up a suite with two rooms (not foyer)
................................................................................................................................................ 58
VingCard door locks
....................................................................................................................................... 59
Visionline settings
....................................................................................................................................... 60
To set up the online network
....................................................................................................................................... 61
To initialize the master thermostat with suite settings
....................................................................................................................................... 61
Online network tree
................................................................................................................................................ 62
Other guest door locks than VingCard
....................................................................................................................................... 63
To set up the online network
....................................................................................................................................... 64
To configure the door switches
....................................................................................................................................... 64
Online network tree
........................................................................................................................ 65
To set up a suite with one door only
................................................................................................................................................ 66
To set up the online network
................................................................................................................................................ 67
To initialize thermostats with suite settings
....................................................................................................................................... 67
To initialize the thermostat in the first room of the suite
....................................................................................................................................... 68
To initialize the thermostat in the second room of the suite
................................................................................................................................................ 69
To read out the thermostat status
................................................................................................................................................ 69
Online network tree
........................................................................................................................ 70
More about how the suite works
................................................................................................................................................ 70
Suite with foyer
....................................................................................................................................... 70
Suite card
....................................................................................................................................... 71
Regular guest card
................................................................................................................................................ 71
Suite with one door only
ASSA ABLOY Hospitality
66 8003 016-3
.................................................................................................72
Appendix D: Configuration in offline scenarios
........................................................................................................................ 73
To add the lock to the in-room network
.................................................................................................77
Appendix E: To install an external motion sensor
........................................................................................................................ 78
Quick reference of technical data
........................................................................................................................ 78
Motion sensor dimensions
........................................................................................................................ 79
Motion sensor locations
.................................................................................................80
Appendix F: Read more
.................................................................................................80
Revision history
ASSA ABLOY Hospitality
66 8003 016-3
FCC and ISED (IC) statements
FCC (Federal Communications Commission) statements
These devices comply with Part 15 of the FCC Rules. Operation is subject to the following
two conditions:
(1) these devices may not cause harmful interference, and
(2) these devices must accept any interference received, including interference that may
cause undesired operation.
Important note: To maintain compliance with FCC´s RF exposure guidelines, this equipment
should be installed and operated with minimum distance 20 cm between the radiator and your
body. Use only the supplied antenna.
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment.
These transmitters must not be co-located or operating in conjunction with any other antennas
or transmitters.
Changes or modifications not expressly approved by the party responsible for compliance could
void the user's authority to operate the equipment.
Note: This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential installation. This equipment generates,
uses and can radiate radio frequency energy and, if not installed and used in accordance with
the instructions, may cause harmful interference to radio communications. However, there is
no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by turning
the equipment off and on, the user is encouraged to try to correct the interference by one or
more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
The concerned end product must be labeled to say 'Contains FCC ID: Y7V-683081118C1'.
The concerned end product must be labeled to say 'FCC ID: Y7V-TZENHV'.
ASSA ABLOY Hospitality
66 8003 016-3
ISED (IC) statements
These devices comply with Industry Canada licence-exempt RSS standard CAN ICES-3 (B)/NMB-3(B) B.
Operation is subject to the following two conditions:
(1) these devices may not cause interference, and
(2) these devices must accept any interference, including interference that may cause undesired
operation of the devices.
Les présents appareils sont conformes aux CNR d’Industrie Canada applicables aux appareils radio
exempts de licence. L’exploitation est autorisée aux deux conditions suivantes:
(1) les appareils ne doivent pas produire de brouillage, et
(2) l’utilisateur des appareils doit accepter tout brouillage radioélectrique subi,
même si le brouillage est susceptible d’en compromettre le fonctionnement.
Important note: To comply with Industry Canada RF radiation exposure limits for general population,
the antennas used for these transmitters must be installed such that a minimum separation distance
of 20 cm is maintained between the radiator (antenna) and all persons at all times and must not be
co-located or operating in conjunction with any other antenna or transmitter.
Under Industry Canada regulations, these radio transmitters may only operate using an antenna of a
type and maximum (or lesser) gain approved for the transmitter by Industry Canada. To reduce potential
radio interference to other users, the antenna type and its gain should be so chosen that the equivalent
isotropically radiated power (e.i.r.p.) is not more than that necessary for successful communication.
These radio transmitters IC9514A-683081118C1 and IC9514A-TZENHV have been approved by Industry
Canada to operate with the antenna types listed below with the maximum permissible gain and required
antenna impedance for each antenna type indicated. Antenna types not included in this list, having
a gain greater than the maximum gain indicated for that type, are strictly prohibited for use with
these devices.
Name/Model
Gain
Impedance
Inverted F-antenna
3.0 dBi
50 ohm
The term "IC" before the equipment certification number only signifies that the Industry Canada
technical specifications were met.
Le terme "IC" devant le numéro de certification signifie seulement que les specifications techniques
Industrie Canada ont été respectées.
End product labeling
The radio module is labeled with its own IC Certification Number. If the IC Certification Number is not visible
when a module is installed inside another device, then the outside of the device into which the module is
installed must also display a label referring to the enclosed module. In that case, the final end product must
be labeled in a visible area with the following:
'Contains IC: 9514A-683081118C1'
'IC: 9514A-TZENHV'
ASSA ABLOY Hospitality
66 8003 016-3
1. Introduction
Energy is a large cost for hotels, and EMS (Energy Management System) is a way
of achieving energy savings in guest rooms. With the Orion EMS software option
to Visionline it is possible to
view the Orion EMS status of different rooms
modify the configurable parameters for a room/group of rooms/entire property)
provide alarm conditions
provide energy savings reports
provide preventative maintenance reports
This manual
describes how to install the Orion EMS (Energy Management System) option
and if applicable an Orion EMS client; see chapter 2
- for the Orion EMS features to be shown in the Visionline software, it is
necessary to install the Orion EMS option; follow the steps in section 2.1
- if the Orion EMS features should also be available in a separate client where
the operators do not see the "ordinary" Visionline items such as doors,
follow the steps in section 2.2; this requires that the Orion EMS option
has been installed in the Visionline software
describes how to install the Orion EMS devices; chapter 3
describes how to set up a thermostat profile; chapter 4
describes how to commission the Orion EMS devices in an online network;
chapter 5
Note: For daily operations when the system is in use, see Daily use manual Orion High
Voltage Thermostat. In that document, more information about SysMon (System Monitor)
features is also found. For more information about the Orion Service software, see Quick
reference guide Orion Service.
A main task for Orion EMS is to determine whether or not a guest room is physically
occupied. When a room is not occupied, Orion EMS controls the HVAC (Heating
Ventilation and Air Conditioning) systems based on the configurable settings of
the system. The items used together with Orion EMS are:
digital thermostat Orion High Voltage Thermostat; in the rest of this document
simply called 'thermostat'
motion sensor
Note: The thermostat has a built-in motion sensor, but in some cases
(depending on the location of the Orion High Voltage Thermostat in the room)
it can be necessary to use an external motion sensor in addition.
door monitoring device; lock, switch
gateway (the same as is used for online doors; requires the Online option which
is also installed according to section 2.1)
Note: The gateway is not used in offline scenarios; see Appendix D for details.
Note: For each room number, it is possible to have
one wired thermostat
up to five motion sensors
up to five door switches
Note: The best conditions for Orion EMS are obtained if also the locks are online and
commissioned to the same online network as the thermostat and the motion sensor.
ASSA ABLOY Hospitality
66 8003 016-3
2. To install the software
2.1 To install a Visionline option
If the Orion EMS option (and Online option) has been ordered together withthe
Visionline software, it is included in the license code and will be set in the software
when the license code is entered. If the option(s) should be added to the system at
a later occasion, when the license code has already been entered and system ID is
therefore set, an option code is used instead. Several software options can be included
in one option code. An operator with the authority to handle option codes must be
logged on. Normally, options are set by the system manager or the distributor.
When ordering the option, the system code must be communicated to the
ordering department:
1. Double click on System settings under the Reports tab in the navigation window
of Visionline. System settings is available even if you are not logged on.
2. Communicate your system code to the order department; see order
acknowledgement for phone number and e-mail address. The system code
can also be entered in the Ordering web page when making the order.
To install an option:
1. Go to Tools/Option code
in Visionline.
2. Enter the option code and click Apply
Figure 1
2.2 To install an Orion EMS client
If there should be a separate Orion EMS client (see chapter 1 for more information),
this is installed according to the ReadMe file for the applicable operating system.
The ReadMe files are found on the Orion EMS software CD.
2.2.1 To start an Orion EMS client
1. Click the Start button and go to Programs/Orion EMS/Orion EMS.
2. When requested, log on with the same user ID and password as for Visionline.
ASSA ABLOY Hospitality
66 8003 016-3
3. To install the Orion EMS devices
3.1 To install a thermostat
Important: This thermostat directly controls high voltage circuits
and must be installed by a licensed electrician.
Important: All local codes must be followed when installing this thermostat.
The thermostat will control a variety of HVAC systems and the installation will
vary based on the type of system to which it is installed.
Figure 2
The master controller of the in-room system is the thermostat, shown in Figure 2.
To the guest, this device appears and operates as a standard digital thermostat;
however, this device also receives entry and exit information from the door lock
or switch as well as motion detected information from the motion sensor. This
information is used to determine the occupancy status of the room and implement
energy savings strategy based on this information. The guest operates the
thermostat, which communicates directly with the Visionline software/Orion EMS
software and the devices within the room.
ASSA ABLOY Hospitality
66 8003 016-3
3.1.1 Step-by-step procedure
For a new thermostat, the following steps must be followed:
Figure 3: Service cable RJ12 to 3.5mm
stereo jack (Art. No 205 999 008)
Figure 4
1. Make sure that the thermostat has got the
latest available firmware:
- Plug the service cable (see Figure 3) into
the thermostat.
- In Orion Service (see Figure 4): choose
the Versions alternative and click the
Readout button. See Quick reference guide
Orion Service for more information about
the software.
2. Mount the thermostat according to here.
3. Add the thermostat to the Thermostats list in
Visionline; in the Thermostat details dialog
you should also choose the profile to which
the thermostat should belong. If no applicable
thermostat profile exists in Visionline, create
one according to chapter 4.
4. Initialize the thermostat with room number
and also with parameters according to the
chosen thermostat profile; follow the Initialize
section in Quick reference guide Orion Service.
Note: If one or more parameters of a
thermostat profile are at a later occasion
updated, these new parameters will
automatically be sent to all concerned online
thermostats. If the thermostats are not online,
they are updated via the Initialize alternative
in Orion Service.
5. Make external connections according to here.
6. If the thermostat should be online, set it up in
the online network according to the chapter To
commission the system.
ASSA ABLOY Hospitality
66 8003 016-3
3.1.2 Thermostat dimensions
Dimensions in mm (inches)
Figure 5
Note: This thermostat is an independently mounted control for surface mounting.
ASSA ABLOY Hospitality
66 8003 016-3
3.1.3 To mount a thermostat
Figure 6
Figure 7
Figure 8
1a. If US single gang box is
applicable: mount the wall
bracket to the US single gang
box according to Figure 6,
using the two screws that are
enclosed with the US single
gang box.
1b. If EU junction box is applicable:
mount the wall bracket to the
EU junction box according to Figure 7, using
the two screws that are enclosed with the EU
junction box.
1c. If the fastening holes do not fit
the installed junction box, or if no
junction box is installed: use a PZD-2
screw driver to mount the wall bracket
with the four enclosed 3.5x25 screws.
2. Connect to the two terminal blocks according to here. Note: See a description of the different inputs and outputs in
the sections Low voltage terminal block and High voltage terminal block.
Figure 9
Figure 10
Figure 11
3. Use a PZD-2 screw driver to
fasten the cover for
wall bracket with the two
enclosed 3.5X9.5 screws.
4. Snap the front plate onto the thermostat.
5. Snap the thermostat onto the
wall bracket.
Figure 12
Figure 13
6. Push to lock the thermostat from the top and from the bottom.
ASSA ABLOY Hospitality
66 8003 016-3
3.1.4 To wire a thermostat (Orion High Voltage Thermostat)
The thermostat has got two terminal blocks for external connections; one for low
voltage and one for high voltage. The different terminals are specified in Figure 14
below. See details about the low voltage terminal block here and about the high
voltage terminal block here.
For connection examples, click the links below:
Switch output
Proportional output
Extra input and wired door switch
Outputs N, L, RW, Y and W
Fan outputs
Figure 14
Important: The cabling is different for the two terminal blocks, due to different sizes of the blocks.
Low voltage cable: maximum cable cross section 1.0mm2
High voltage cable: maximum cable cross section 1.5mm2
ASSA ABLOY Hospitality
66 8003 016-3
3.1.4.1 Low voltage terminal block (12 pole; 3.5mm spacing)
Note: The parameters are set up in Visionline; see the section To set up a thermostat profile for details.
Note: For connection examples, click the links in the left column of Table 1 below.
Switch output
Warning: The switch output must not be used to switch the mains voltage.
Max 24V AC/DC, SELV, max 0.1A
Potential free switch output
Primary function: contact closed when the room is occupied; can e.g. be used for
giving a signal to a light control system
Note: This is a switch output only; no voltages are output.
Alternative use of this output (e.g. use for intelligent switch and welcome scene)
must be set up in Visionline.
Proportional
output
(0-10V)
Outputs an analog voltage between 0V and 10V, where 0V is off and 10V is max
on.
Note: This is to control actuators with a 0-10V control input*.
Cool: output to a proportional cool actuator
GND: common reference for the heat and cool outputs
Heat: output to a proportional heat actuator
*) Some actuators require other voltages, e.g. 2-10V or 0-5V.
Extra input
Important: Do not apply any voltage. This is an input for a switch,
connected between the input and the GND terminal.
Primary function: Used as input from a card switch or a wired motion sensor
Alternative function: Input for 2-pipe temperature sensor (hot/cold water); this
sensor can either be a bimetal switch (open or closed depending on the
temperature it senses) or a 1k NTC resistor connected between this input and the
GND terminal. The 1k NTC resistor is a temperature-depending resistor, giving an
analog value determined by the temperature it senses. Note: If the 2-pipe
temperature sensor is used, it is not possible to have a wired motion sensor.
Exterior door
Important: Do not apply any voltage. This is an input for a switch,
connected between the input and the GND terminal.
Used as input from a switch mounted on an exterior door or window;
will turn the AC off when the door/window is open
Interior door
Important: Do not apply any voltage. This is an input for a switch,
connected between the input and the GND terminal.
Used as input from a switch mounted on an interior door;
applicable when no VingCard online lock is installed
RS-485 (not in
use)
For communication with other equipment (e.g. light control equipment)
using the RS-485 standard
A shielded twisted pair cable, made for this communication standard,
must be used
A = non-inverting pin
B = inverting pin
C = common
Table 1
ASSA ABLOY Hospitality
66 8003 016-3
3.1.4.2 High voltage terminal block (8 pole; 5.0mm spacing)
Note: The parameters are set up in Visionline; see the section To set up a thermostat profile for details.
Note: For connection examples, click the links in the left column of Table 2 below.
Mains voltage input
Universal voltage input 100VAC-277VAC; 50/60Hz;
rated impulse voltage 4kV
This is the voltage that is output on the high voltage terminals,
but it is also used as power supply input for the thermostat
internal circuits
N = Neutral
L = Live
Fan outputs
Type 1.B action. Max load 3A (3FLA/18LRA)
Mains voltage output at
- G1: Fan 1, when the fan is to be run at lowest speed
- G2: Fan 2, when the fan is to be run at medium speed
- G3: Fan 3, when the fan is to be run at high speed
Note: For information about fan settings in Visionline, click here.
Note: For information about live output, click here.
RV: Reversing valve
Type 1 action. Max load 0.5A
Primary function: Used for switching between summer/winter
(cold/hot water in the pipes of a 2-pipe system)
Alternative functions (must be set up in Visionline):
- Mains voltage output when the room is occupied
- Mains voltage output when the guest enters the
room for the first time; welcome scene
Note: These alternative functions can also be set up for G2.
- Can be used as return (close) for floating valves
Note: For information about live output, click here.
Y: Cool output
Type 1 action. Max load 0.5A
Mains output for cool actuator
Primary function: Mains voltage output when the temperature
is above the set temperature (plus deadband)
W: Heat output
Type 1 action. Max load 0.5A
Mains output for heat actuator
Primary function: Mains voltage output when the temperature
is below the set temperature (minus deadband)
Table 2
ASSA ABLOY Hospitality
66 8003 016-3
3.1.4.3 Connection examples for switch output
Figure 15
3.1.4.4 Connection example for proportional output
Figure 16
ASSA ABLOY Hospitality
66 8003 016-3
3.1.4.5 Connection examples for extra input
Note: NO (normally open)/NC (normally closed) in the below pictures refer to the
state of the switch when the card is not inserted, or motion is not detected.
Figure 17
ASSA ABLOY Hospitality
66 8003 016-3
3.1.4.6 Connection examples for wired door switch
Note: NO (normally open)/NC (normally closed) refers to the state of the switch when
the door or window is open.
Figure 18
ASSA ABLOY Hospitality
66 8003 016-3
3.1.4.7 Connection examples for outputs N, L, RV, Y and W
In HVAC (Heating Ventilation and Air Conditioning) systems, a difference is often
made between 2-pipe systems and 4-pipe systems.
In a 2-pipe system there is one pipe in and one pipe out; both pipes either have cold
water or hot water. If there is cold water in the pipes, the air conditioning can only
be used for cooling. If there is hot water in the pipes, the air conditioning can only
be used for heating. In most cases, cold/hot water in the pipes is changed twice a
year (Spring/Autumn) through an actuator connected to the cool output on the
thermostat.
In a 4-pipe system there are two pipes in and two pipes out; one set of pipes in/out
has cold water and the other set of pipes in/out has hot water. The thermostat can
choose whether cooling or heating is applicable by activating either the cool output
or the heat output on the thermostat.
For a thermostat to know whether the water in a pipe is cold or hot, a pipe
temperature sensor is used. There are two types of pipe temperature sensors;
see details here.
Figure 19
ASSA ABLOY Hospitality
66 8003 016-3
Other connection examples for the outputs N, L, RV, Y and W:
Figure 20
ASSA ABLOY Hospitality
66 8003 016-3
3.1.4.8 More about live output
All loads below each have two connections:
Fan 1 - Fan 3
W output (heat output)
Y output (cool output)
RV output
The thermostat is connected to 110 VAC or 230VAC. To be able to disconnect a load,
one of the connections is broken by one of the two items below:
relay (applicable for Fan 1 - Fan 3)
tria (applicable for W output, Y output and RV output)
'Neutral' is connected to one of the load connections, while 'Live' is connected to the
other connection; see Figure 21.
Figure 21
ASSA ABLOY Hospitality
66 8003 016-3
3.1.4.9 Connection examples for fan outputs
Figure 22
3.1.4.10 Connection example for floating valve
A floating valve has three connections:
one for opening the valve (W for heating valve and Y for cooling valve)
one for closing the valve (RV output)
one for ground; COM (neutral)
One of the three connections is always fully closed. While one of the valves is activated,
the valves open slowly during the desired time, and while deactivating the valves close slowly
for the desired time.
Example:
Figure 23
When the thermostat is in heating mode, the W output is used for increasing the temperature
and the RV output is used for decreasing the temperature.
When the thermostat is in cooling mode, the Y output is used for decreasing the temperature
and the RV output is used for increasing the temperature.
To control the floating valves, the below parameters must be configured in Visionline.
Note: Heating and cooling must be configured separately, under HVAC/Heating and HVAC/
Cooling respectively in Visionline. For information about the settings that can be made for
floating valves, click here.
ASSA ABLOY Hospitality
66 8003 016-3
3.2 To install an RF door switch
If VingCard online locks are not applicable at the installation, an RF door switch can
instead be used for monitoring the position of the door. The door switch is powered
by 2 AA batteries and the kit also includes a magnet (see Figure 25) and two screws.
The door switch can be mounted as it is or on a wall-mounted casing (see Figure 26)
which is purchased separately.
Note: For best operation, the magnet should be installed maximum 10 mm (25/6'')
from the reed switch which is located as in Figure 24.
Note: It is also possible to use a wired door switch without radio; click here for
details.
3.2.1 RF door switch dimensions
Figure 24
ASSA ABLOY Hospitality
66 8003 016-3
3.2.2 RF door switch magnet dimensions
Note: The magnet must be mounted maximum 10 mm (25/64'') from the
door switch.
Figure 25
3.2.3 Wall-mounted casing
Figure 26
ASSA ABLOY Hospitality
66 8003 016-3
4. To set up a thermostat profile
Each thermostat which is set up in the Thermostats list of the Visionline software
(see Daily use manual Orion high voltage thermostat for details about that list) must
belong to a thermostat profile, e.g. a template with certain thermostat parameters.
When a thermostat is first set up, it must be initialized with the thermostat profile
parameters via the Initialize alternative in Orion Service; see Quick reference guide
Orion Service for details.
Note: If one or more parameters of a thermostat profile are at a later occasion
updated, these new parameters are automatically sent to all concerned online
thermostats. If the thermostats are not online, they must be updated via the
Initialize alternative in Orion Service.
1. Double click on Thermostat profiles under the Lists tab in the Visionline
navigation window.
2. Click Add to add a new thermostat profile, or mark an existing profile and click
Properties.
3. Go through the different alternatives in the left pane of the Thermostat profile
details dialog; see details in sections 4.1-4.7.
4. When all settings have been made, click Save and Close (or Update and Close
if an existing profile was modified).
4.1 General
1. Enter Name and,
if desired, Description.
Figure 27
ASSA ABLOY Hospitality
66 8003 016-3
4.2 HVAC
1. At Model, choose
'High voltage'.
2. Under Input configuration,
make the applicable choices
under Extra input, DSW
ext. input and DSW int.
input; see Table 3 below.
3. Under Extra input
configuration, make the
applicable choice 'Not used',
'Wired motion sensor' or
'Pipe temperature sensor';
see Table 3 for details.
Figure 28
Parameter
Available choices
Default setting
Extra input
Normally open/normally closed
Normally open
DSW ext. input
(door switch
exterior input)
Normally open/normally closed
Normally open
DSW int. input
(door switch
interior input)
Normally open/normally closed
Normally open
Extra input
Not used/wired motion sensor/
pipe temperature sensor
Note: If 'Wired motion sensor' is
chosen, it is also possible to make
a further choice 'Delay wired
motion sensor'. This can be
applicable in warm countries
where there is a great difference
in temperature inside and outside
the room, to avoid that motion is
triggered when someone opens
the door, leaves the room and
locks the door. The 'Delay wired
motion sensor' parameter will also
be applicable for the internal
motion sensor.
Not used
Table 3
ASSA ABLOY Hospitality
66 8003 016-3
4.2.1 Heating
1. Click the plus sign at
HVAC in the left pane of
the Thermostat profile
details dialog and mark
Heating.
2. In the drop-down-menu
at Type, the following
alternatives are
available:
n/a; default
4 pipe fan coil
Heat pump reversed
valve (Type B)
2 pipe fan coil
2 pipe fan coil with
automatic switching
Proportional
Floating valve
Figure 29
4.2.1.1 2-pipe fan coil with automatic switching
Figure 30
If '2-pipe fan coil with automatic switching' is chosen as HVAC type, the further
alternatives Pipe temperature sensor and Trigger level are available.
If the pipe temperature sensor is a bimetal switch (open or closed depending on the
temperature it senses), choose for Pipe temperature sensor whether it should be
'Cooling' or 'Heating'.
If the pipe temperature sensor is an 1k NTC resistor, a Trigger level (in the range
0-100%) for switching between heat and cool should be chosen. When the
temperature reaches the switch-over-temperature (default 3 ºF; this is chosen
under the Deadband alternative in the Thermostat profile details dialog), it is
checked whether the pipe temperature sensor has reached the trigger level so that
the thermostat can change mode from heating to cooling or vice versa.
Note: When '2-pipe fan coil with automatic switching' is chosen as HVAC type,
the cooling relay (Y) is the only relay that applies, forced by the thermostat.
ASSA ABLOY Hospitality
66 8003 016-3
4.2.1.2 Proportional
If 'Proportional' is
chosen as HVAC type, the
parameters shown in Figure
31 (which shows the default
values) are applicable. For
details about each
parameter, see Table 4
below.
Figure 31
Parameter
Description
Prop. band/gain
The value at Prop. band/gain describes the regulator output of the HVAC system
related to the difference between measured temperature and set temperature.
Example:
Measured temperature = 23 ºC
Set temperature = 20 ºC
Gain = 1.9V
The regulator will set 3x1.9V=5.7V on the output (if all default values are used).
The range for the regular output value is 0-10V.
Integral gain/reset The Integral gain/reset describes to the HVAC system regulator what gain it can
use when integrating the previous average temperature values, in order to settle
the temperature around the desired set value.
Derivative time
The Derivative time describes to the HVAC system regulator what gain it can use
when looking at the rate of the temperature change.
Cycle time
The Cycle time describes how fast the HVAC system regulator makes calculations
for a new output.
Min output
At Min output, the minimum output voltage is chosen; can be 0V, 1V or 2V.
Max output
At Max output, the maximum output voltage is chosen; can be 5V or 10V.
Table 4
ASSA ABLOY Hospitality
66 8003 016-3
4.2.1.3 Floating valve
If 'Floating valve' is
chosen as HVAC type,
the parameters shown in
Figure 32 (which shows the
default values) are
applicable. For details about
each parameter, see Table
5 below.
Figure 32
Parameter
Description
Max opening
Max opening states the maximum number of seconds
required to fully open or fully close the floating valve.
Start position
The floating valve should typically move to a given position,
so that the thermostat can try to close or open to decrease or
increase the temperature. Start position states the number of
seconds it takes to run the thermostat to the desired position of
the floating valve.
Max runtime
There are three different values for runtime, i.e. how long the
floating valve should operate related to the difference between
measured temperature and setpoint: Max runtime, Medium
runtime and Min runtime. Based on a calculation of the selected
deadband and the temperature deviation from setpoint, the
thermostat chooses an applicable valve throttle.
Example 1: If the temperature difference is 1 degree outside
the thermostat deadband that has been set up in the dialog shown
here, the floating valve is opened/closed according to 'Medium
runtime'.
Example 2: If the temperature difference is -3 degrees, the
thermostat will use 'Max runtime' and run the floating valve
for 16 seconds "back" to a new position 90s-16s = 74s.
Medium
runtime
Min runtime
Check interval
Check interval describes how often the regulator checks the
real temperature against the setpoint.
Table 5
ASSA ABLOY Hospitality
66 8003 016-3
4.2.2 Cooling
1. Click the plus sign at HVAC in
the left pane of the
Thermostat profile details
dialog and mark Heating.
2. In the drop-down-menu at
Type, the following
alternatives are available:
n/a; default
4 pipe fan coil
Heat pump reversed valve
(Type O)
2 pipe fan coil
2 pipe fan coil with
automatic switching
Proportional
Floating valve
Figure 33
4.2.2.1 2-pipe fan coil with automatic switching
Figure 34
If '2-pipe fan coil with automatic switching' is chosen as HVAC type, the further
alternatives Pipe temperature sensor and Trigger level are available.
If the pipe temperature sensor is a bimetal switch (open or closed depending
on the temperature it senses), choose for Pipe temperature sensor whether
it should be 'Cooling' or 'Heating'.
If the pipe temperature sensor is an 1k NTC resistor, a Trigger level (in the
range 0-100%) for switching between heat and cool should be chosen. When the
temperature reaches the switch-over-temperature (default 3 ºF; this is chosen
under the Deadband alternative in the Thermostat profile details dialog),
it is checked whether the pipe temperature sensor has reached the trigger level
so that the thermostat can change mode from heating to cooling or vice versa.
Note: When '2-pipe fan coil with automatic switching' is chosen as HVAC type,
the cooling relay (Y) is the only relay that applies, forced by the thermostat.
ASSA ABLOY Hospitality
66 8003 016-3
4.2.2.2 Proportional
If 'Proportional' is
chosen as HVAC type, the
parameters shown in
Figure 35 (which shows
the default values) are
applicable. For details
about each parameter,
see Table 6 below.
Figure 35
Parameter
Description
Prop. band/
gain
The value at Prop. band/gain describes the regulator output of
the HVAC system related to the difference between measured
temperature and set temperature.
Example:
Measured temperature = 23 ºC
Set temperature = 20 ºC
Gain = 1.9V
The regulator will set 3x1.9V=5.7V on the output (if all default
values are used). The range for the regular output value is 0-10V.
Integral gain/
reset
The Integral gain/reset describes to the HVAC system regulator
what gain it can use when integrating the previous average
temperature values, in order to settle the temperature around the
desired set value.
Derivative
time
The Derivative time describes to the HVAC system regulator what
gain it can use when looking at the rate of the temperature
change.
Cycle time
The Cycle time describes how fast the HVAC system regulator
makes calculations for a new output.
Min output
At Min output, the minimum output voltage is chosen; can be 0V,
1V or 2V.
Max output
At Max output, the maximum output voltage is chosen; can be 5V
or 10V.
Table 6
ASSA ABLOY Hospitality
66 8003 016-3
4.2.2.3 Floating valve
If 'Floating valve' is
chosen as HVAC type, the
parameters shown in
Figure 36 (which shows the
default values) are
applicable.
For details about each
parameter, see Table 7
below.
Figure 36
Parameter
Description
Max opening
Max opening states the maximum number of seconds required
to fully open or fully close the floating valve.
Start position
The floating valve should typically move to a given position,
so that the thermostat can try to close or open to decrease or
increase the temperature. Start position states the number of
seconds it takes to run the thermostat to the desired position of
the floating valve.
Max runtime
There are three different values for runtime, i.e. how long the
floating valve should operate related to the difference between
measured temperature and setpoint: Max runtime, Medium
runtime and Min runtime. Based on a calculation of the
selected deadband and the temperature deviation from setpoint,
the thermostat chooses an applicable valve throttle.
Example 1: If the temperature difference is 1 degree outside the
thermostat deadband that has been set up in the dialog shown
here, the floating valve is opened/closed according to 'Medium
runtime'.
Example 2: If the temperature difference is -3 degrees, the
thermostat will use 'Max runtime' and run the floating valve
for 16 seconds "back" to a new position 90s-16s = 74s.
Medium
runtime
Min runtime
Check interval
Check interval describes how often the regulator checks the
real temperature against the setpoint.
Table 7
ASSA ABLOY Hospitality
66 8003 016-3
4.2.3 Consumption
1. If the Integrated Room
Control dashboard is
applicable, values for
estimated HVAC power
consumption for the
three cases 'Cooling',
'Heating' and 'Fan only'
can be entered at
Estimated consumtion;
first expand HVAC in
the left pane of the
Thermostat profile
details dialog and
choose Consumption.
Figure 37
4.3 Fan
Figure 38
1. At Control, choose whether the control should be
manual; default
auto; this choice will disable the fan button of the thermostat
ASSA ABLOY Hospitality
66 8003 016-3
2. Max fan cool is the maximum setting that the customer can make via the
thermostat. Choose between
low
mid
high; default
Note: The ability to control fan speeds depends on the capability of the air handler
as some systems do not have three fan speeds.
3. Max fan heat is the maximum setting that the customer can make via the
thermostat. Choose between
low
mid
high; default
Note: The ability to control fan speeds depends on the capability of the air handler
as some systems do not have three fan speeds.
4. If applicable, mark the checkbox 'Fan on when satisfied'. This is applicable if the
background sounds in the room should for guest comfort reasons not change.
Note: The 'Fan on when satisfied' function will only apply to an occupied room.
5. At Cool down, duration (Fan time) and Fan speed of the fan during cool down
period can be chosen. It can also be chosen whether cool down should apply only
when in cool or only when in heat (mark the applicable checkbox).
Fan time; default is 2 minutes, can be in the range 1-10 minutes
Fan speed; default is 'Low', can be low, mid or high.
4.4 Limits
Note: For more information about 'unoccupied' and 'unsold', see section Basic EMS
logic in Daily use manual Orion high voltage thermostat.
1. At Setback type, choose
static; default (the static
setback temperatures
are configured in the
system and do not
change based on the
guest settings)
dynamic (the dynamic
setback temperatures
are configured as a set
number of degrees
above or below the
guest setting)
Figure 39
ASSA ABLOY Hospitality
66 8003 016-3
2. If 'Static' is chosen as
Setback type: enter the
applicable number of
degrees at Upper limit
(default is 78° F) and
Lower limit (default is 68°
F) for setback if a room is
unoccupied.
1. If 'Dynamic' is chosen as
Setback type: enter the
applicable number of
degrees offset at Upper
limit (default is 4° F offset)
and Lower limit (default is
4° F offset) for setback if a
room is unoccupied.
Figure 40
1. At Unsold setback, enter
the applicable number of
degrees as Upper limit
(default is 84° F) and
Lower limit (default is 64°
F) for setback if a room is
unsold.
Figure 41
1. At Occupied limits, it is
possible to limit the allowed
temperature range when
the room is occupied. If this
is the case, mark the
checkbox 'Use occupied
limits' and enter the values
for Upper limit (default is
84° F) and Lower limit
(default is 68° F).
Figure 42
ASSA ABLOY Hospitality
66 8003 016-3
4.5 Timeout
1. At Ext. door timeout,
choose between
normal; default
short; 20 seconds
2. At Room not occupied,
enter the applicable
number of minutes
(default is 8) after which
timeout should occur.
3. At Room not sold,
enter the applicable
number of hours (default
is 16) after which an
unoccupied room should
enter the unsold mode.
Note: If the PMS system
sends a check-out
command, the Room not
sold parameter will be
overridden and timeout
will immediately take
place.
Figure 43
4.6 Deadband
1. At Thermostat, enter
the applicable number of
degrees; default is 2° F.
2. At Heat/cool, enter the
applicable number of
degrees; default is 3° F.
Figure 44
ASSA ABLOY Hospitality
66 8003 016-3
4.7 Misc
1. If the checkbox Freeze
guard is marked (which
is default), there will be
an alarm and the HVAC
will start heating if the
temperature in any
room with a thermostat
goes below 39° F (4° C).
Figure 45
2. If the checkbox Refresh
cycle is marked (default
is unmarked), the Orion
EMS system will in
setback control run the
A/C unit every 25
minutes for a period of
2 minutes to re-circulate
the air in the room; only
for cooling mode.
Figure 46
3. Dwell off time should
normally be unmarked;
see details here.
Figure 47
4. If the checkbox Guest
door is exterior is
marked (default is
unmarked), the door to
the room will be treated
as an exterior door.
If the door is opened,
the HVAC will turn off
either when the door has
been open for 20 seconds
(short timeout) or when
the door has been open
for the unoccupied
timeout. This depends on
whether short or normal
has been chosen under
the Timeout tab in the
Thermostat profile
details dialog.
Figure 48
ASSA ABLOY Hospitality
66 8003 016-3
5. If the checkbox Suite
with foyer door is
marked (default is
unmarked), the
thermostat will in non-
suite mode not react on
the foyer door.
Note: This checkbox
must be marked if a suite
shall listen to the foyer
door when in suite mode.
Figure 49
6. If the checkbox
Humidity control is
chosen (default is
unmarked), the
thermostat will
implement control
measures if the
humidity in the room
gets
too high.
Note: The control
measures will only be
implemented when the
room is unoccupied
or unsold.
Figure 50
7. If the checkbox On
exterior open, keep
lights on is marked
(default is unmarked),
the lights will be left on
if the exterior door
timeout has been
triggered by
- the wired input for
exterior door open on
the thermostat
OR
- a non-wired door switch
configured as exterior
Figure 51
ASSA ABLOY Hospitality
66 8003 016-3
8. If the checkbox Exterior
input behaves as
window is marked
(default is unmarked),
the HVAC will be shut off
after a configured time
(short or normal), but
the thermostat does not
change the occupancy
status. The exterior door
timeout is triggered by
the wired input for
exterior door open (EX1)
on the thermostat.
Figure 52
9. If the checkbox Enable
lights during pre-
condition time is
marked (which is
default), the lights are
enabled according to the
chosen intelligent switch
setting during the pre-
condition time.
Note: This parameter
requires that the Online
option has been set in
Visionline.
Figure 53
10.If the checkbox Set
door state to closed
when door ajar alarm
received is marked
(default is unmarked),
the door state is set to
closed once the door
ajar timeout has been
triggered. This allows
the thermostat to go to
occupied state even if
the door is not physically
closed. Note: This
checkbox is applicable
if you have a
malfunctioning
door switch.
Figure 54
ASSA ABLOY Hospitality
66 8003 016-3
11.At Temperature
display, choose
between
room temperature;
default
set temperature,
i.e. the temperature
which has been set on
the thermostat by
the guest
Figure 55
12.At Intelligent switch,
choose between
disabled; default
use RV output
use G2 output
The intelligent switch is an
output for lighting control
which works according to
the occupancy status.
If intelligent switch is
applicable, normally 'Use
RV output' should be
marked unless the air
handler is a heat pump.
In the latter case, mark
'Use G2 output' instead.
Figure 56
13.If desired, it is possible
to have a Welcome
scene which is activated
when the occupancy
state for a room
changes from unsold to
unoccupied. The available
alternatives for welcome
scene are (default is
'disabled'):
disabled
use RV output
use G2 output
14.At Pulse length, the
welcome scene can be
set up to have a
pulse length:
0 = welcome scene
always off
chosen length in the
interval 1-255 s
Figure 57
ASSA ABLOY Hospitality
66 8003 016-3
Figure 58
15.Pre-condition time is
the number of hours the
thermostat shall run at
the default setpoint
after check-in. If no
entry has been done
when this time expires,
the unoccupied setback
will be assumed.
The pre-condition time
can be 1-12 hours or
'disabled' (default is
2 hours).
Note: This parameter
requires that the Online
option has been set in
Visionline.
Figure 59
16.Default set point is
the temperature which
the thermostat is set
to until a guest changes
the temperature. The
thermostat will also
return to the Default
set point after check-
out.
Figure 60
ASSA ABLOY Hospitality
66 8003 016-3
5. To commission the system
Before the devices can communicate, they must be joined to the online network.
For detailed instructions and rules on this network, see User manual Online option.
Note: The online network, including gateway and router locations, must first be
specified by a qualified technician. No online setup can be done until this step
is completed.
Note: The online thermostat is equipped with the a ZigBee endnode with which can
have either router firmware or coordinator firmware. The coordinator firmware is for
offline scenarios when there is no connection to the server; see Appendix D for details
about setting up the in-room network in that case.
The thermostat may be joined directly to a gateway, router, or another Orion EMS
online thermostat as specified in the network layout. The thermostat is the primary
device in the room, and the lock and motion sensor will be joined to this thermostat.
When the steps in sections 5.1 and 5.2 have been performed, the in-room network
is operational.
Note: To use the Orion Service software, connections to the application server must
be made according to Quick reference guide Orion Service.
5.1 To join the thermostat to the network
1. To be able to join the thermostat
to the gateway or router, it is first
necessary to permit joining on the
gateway or router. This is done in
the System Monitor, SysMon; to
open this, double click on
SysMon.exe in the software
installation folder and log on at
File/Log on.
2. In SysMon, choose View/Online
Network to see the online network.
Right click on the designated
gateway/ router in the Online
Network tree and select Permit
Joining in the right-click menu;
see Figure 61.
3. When the gateway/router has been
set in the permit joining mode, it is
"open". It will remain in this status
for approximately 15 minutes or
until a forbid joining command
is executed.
4. With the gateway/router open,
plug the service cable in the service
device into the thermostat.
Figure 61
ASSA ABLOY Hospitality
66 8003 016-3
5. In the Orion Service software (go to
Start/Programs/Orion Service/
Orion Service), choose Configure
device in the left pane of the
window. Let the tab Thermostat
(default) be open and click the
Discovery button; see Figure 62.
The thermostat will connect to the
open gateway/router.
6. To see if the thermostat was able
to join the network, click the Check
status button in the Configure
Device section of Orion Service.
If the joining was successful, the
message 'Device is online' is shown.
7. With the thermostat joined to its
gateway/router, right click on the
gateway/router in SysMon and
select Forbid Joining.
Figure 62
ASSA ABLOY Hospitality
66 8003 016-3
5.2 To join the in-room devices to the thermostat
1. Plug the service cable into
the thermostat.
2. Click the Permit Join button in
the Configure device section of
Orion Service; see Figure 63.
Note: The thermostat will remain
open for 15 minutes or until a
Forbid Join command is received.
Figure 63
If external motion sensor is applicable,
performs steps 3-6 (else go directly
to step 7):
3. Once the thermostat has been
opened for joining, plug the service
cable into the motion sensor.
4. Choose the Motion sensor tab in
the Configure device section of
Orion Service.
5. Click the Discovery button;
see Figure 64.
Figure 64
6. Wait a few seconds and then click
the Check status button in the
Motion sensor tab of Configure
device; see Figure 65. If the device
has joined successfully, the
message 'Device is online' is shown.
If that message is not displayed,
wait a few more seconds and check
the status again. If still offline,
repeat the discovery process.
Figure 65
7. The lock is joined to the thermostat by using a Discovery card*. Depending on
lock model there will be a green flash and/or a chirp, indicating that the lock
has been set into discovery mode. Wait a few seconds and then present the
Check Status card* at the lock. If the light flashes the green light only and/or a
chirp
is heard, the lock has successfully joined the network. If you instead see a green
flash followed by red flashes, and/or a beep is heard, the lock has not joined.
In this case, wait a few seconds and then try the Check Status card again.
If still not successful, repeat the discovery process.
8. In order for the lock to send door events to the thermostats, EMI events must
be enabled; this is done by presenting an Enable EMI events card* at the lock.
9. If an RF door switch is applicable instead of a lock, repeat steps 3-5 with the
RF door switch; in step 4, use the Door switch tab.
ASSA ABLOY Hospitality
66 8003 016-3
9. Once the devices have been joined,
plug the service cable into the
thermostat.
10. Choose the Thermostat tab of
the Configure device section in
Orion Service. Click the Forbid
Join button; see Figure 66. Failure
to perform this step will result in
problems when setting up the
network in nearby rooms.
11. Right click on the thermostat
in the Online network tree in
SysMon and choose Get user
description. Make sure that
the description says 'no' at
'Join permitted'.
Figure 66
*) See User manual Online option for information about issuing these cards.
ASSA ABLOY Hospitality
66 8003 016-3
6. To check the installation
6.1 To check diagnostics
When a new thermostat has been set up according to this step-by-step procedure,
the status of the thermostat should be checked in Orion Service:
Figure 67
1. Choose Diagnostics in the left pane of the Orion Service window.
2. Connect the service cable to the thermostat and click the Start button
in Orion Service.
Item
Status shown
Door switch
Yes/No
Motion sensor
Yes/No
HVAC
Fan speed
Occupancy
Unsold/unoccupied/occupied/unknown
Temp sensed/set
'Temp sensed' is the temperature in the room; 'temp set' is
the temperature which the guest has set on the thermostat
Door state
Opened/closed
Ext. door state
Opened/closed for an external door (applicable if a
door switch has been configured as 'external door')
Table 8
Note: If exterior or interior door is left open for more than 2 minutes, the word
'DOOR' is shown in the thermostat display until the door is closed again.
ASSA ABLOY Hospitality
66 8003 016-3
6.2 To test the in-room devices
With the network successfully formed, it is now possible to test the devices to ensure
proper functionality.
1. Open and close the door.
2. Engage and disengage
the deadbolt.
3. Walk around the room to
ensure a motion event.
4. Run an event log of the thermostat
using the service device. To make
this, plug insert the service cable
into of the service device in the
thermostat, choose the Log section
under Readout in the left part of
the Orion Service software window,
choose the applicable No. of
events and click the Readout
button. Ensure that the door and
motion events are logged as shown
in the example in Figure 68.
Figure 68
5. Run a status check by selecting the
Status section in the left part of
the Orion Service software window,
making sure that the service cable
is plugged into plugged into the
thermostat and clicking the
Readout button. Make sure
that the motion sensor, lock and
thermostat all say 'Offline: No';
see Figure 69.
Figure 69
6. Test the range of the motion sensor.
First, make sure that the door is
open as this will ensure that the
motion sensor is not deactivated
by the thermostat.
7. Go to the Configure device section
in the left part of the Orion Service
software window and choose the
Motion sensor tab. Make sure
that the service cable is plugged
into the motion sensor and click
the Activate LED button; see
Figure 70.
Figure 70
ASSA ABLOY Hospitality
66 8003 016-3
8. Walk around the room; the LED of the motion sensor will light up as motion
is detected. Ensure that the range is sufficient to pick up motion in the room.
The LED will be active for 10 minutes and then automatically turn off.
9. The system is now ready for use.
10. Choose the Configure device section in the left part of the Orion Service
software window. Make sure that the service cable is plugged into the motion
sensor and click the Activate LED button; see Figure 70.
11. Walk around the room; the LED of the motion sensor will light up as motion is
detected. Ensure that the range is sufficient to pick up motion in the room.
The LED will be active for 10 minutes and then automatically turn off. The
system is now ready for use.
12. Test the range of the motion sensor. First, make sure that the door is open
as this will ensure that the motion sensor is not deactivated by the
thermostat. Choose the Configure device section in the left part of the
Orion Service software window. Make sure that the service cable is plugged
into the motion sensor and click the Activate LED button; see Figure 70.
Walk around the room; the LED of the motion sensor will light up as motion is
detected.
Ensure that the range is sufficient to pick up motion in the room. The LED will
be active for 10 minutes and then automatically turn off. The system is now
ready for use.
ASSA ABLOY Hospitality
66 8003 016-3
Appendix A: Quick reference of technical data
Dimensions (WxHxD)
112 x 117 x 35 mm (4 13/32" x 4 19/32" x 1 3/8")
Mains voltage input
Universal voltage input 100VAC-277VAC; 50/60 Hz;
rated impulse voltage 4kV
Switch input
Door switch - 1 exterior/1 interior
Multifunction input
Motion sensor/card switch/pipe temp sensor
High voltage outputs
- G1 (Fan 1): Type 1.B action. Max load 3A (3FLA/18LRA)
- G2 (Fan 2): Type 1.B action. Max load 3A (3FLA/18LRA)
- G3 (Fan 3): Type 1.B action. Max load 3A (3FLA/18LRA)
- RV (reversing valve): Type 1 action. Max load 0.5A
- Y (cooling/compressor): Type 1 action. Max load 0.5A
- W (heating): Type 1 action. Max load 0.5A
Low voltage outputs
- Proportional 0-10V; heating
- Proportional 0-10V; cooling
- Switch output (max 24V AC/DC, SELV, max 0.1A)
Temperature sensor
Integrated in thermostat
Temperature display
Configurable: room temperature (default) or guest setting
Temperature display range
2-digit display
Adjustable setpoint temperature
range
17°C -32°C / 62°F - 90°F
Environment
Normal indoor environment - Pollution degree 2
Operating temperature range 0°C -55°C / 32°F - 130°F
Service device
Orion Service software and
service cable RJ12 to 3.5mm stereo jack
Radio (RF) signals
ZigBee 2006
Lock to thermostat:
Door open - staff card
Door open - guest card
Door open from inside
Door closed
Deadbolt thrown/released
Thermostat to lock:
Room occupied
Motion sensor to thermostat:
Motion detected
Battery status
Thermostat to motion sensor:
Turn off when the room is occupied and door is closed
Turn on when the door is opened again
Thermostat deadband
Configurable 1-3°F; default is 2°F
Heat/cool switching deadband
Configurable 2-4°F; default is 3°F
Freeze guard
39°F / 4°C
Refresh cycle
Optional
Humidity
Optional
Intelligent switch
Configurable: Disabled/use RV output/use G2 output;
default is disabled
Room not occupied timer
Configurable 1-120 minutes; default is 8 minutes
Room not sold timer
Configurable 12-24 hours; default is 16 hours
Table continued on next page
ASSA ABLOY Hospitality
66 8003 016-3
Compressor delay (dwell-off time)
Default is that the dwell-off time is off; it is only applicable when
'heat pump' is chosen as HVAC type. In the 'heat pump' case, the
thermostat will automatically force the dwell-off time to be on -
it is then 5 minutes and cannot be changed. The dwell-off time
prevents short-cycling of the compressor.
Required Visionline version
1.15.0 or higher
Required Orion Service version
1.3.0 or higher for full functionality
Table A1
ASSA ABLOY Hospitality
66 8003 016-3
Appendix B: Firmware upgrade
At delivery, the thermostat (and if applicable, the external motion sensor) contains
the correct module firmware. However, if a firmware upgrade is needed at a later
occasion, the Orion Service software and a service cable RJ12 to 3.5mm stereo jack
is used. Orion Service contains the latest released firmwares at the time when Orion
Service was released, so in most cases it is possible to direcly use the Upload
firmware alternative in Orion Service; see Quick reference guide Orion Service for
details. If however a later firmware than what is included in Orion Service is to be
used, the firmware should first be saved on the Visionline server and then be
downloaded from there to Orion Service.
Note: Upgrading the endnode firmware in the thermostat may take several minutes.
Note: If the firmware in thermostat controller and thermostat should be upgraded at
the same time, it is recommended to start upgrading the thermostat controller first.
1. Check under Upload firmware in
Orion Service what firmware that is
included there; if no later firmware
exists, follow the steps under
Upload firmware in Quick
reference guide Orion Service. The
firmware upgrade is now ready. If
you know that a later firmware
version exists, instead follow steps
2-10 below.
2. Go to Tools/Module firmware in
the Visionline software. The dialog
to the right is shown.
Figure B1
3. Click Read file and browse to the
applicable module firmware file (tmf
file).
4. Mark the tmf file and click Open.
The tmf file will be read into the
memory and the tmf version will
appear at 'Loaded version' in the
lower left corner of the Module
firmware dialog.
Figure B2
ASSA ABLOY Hospitality
66 8003 016-3
5. Click Save to store the tmf version
in the database. The version will
appear in the list below 'Versions
stored in the database' in the
Module firmware dialog.
Figure B3
6. To enter an optional description for
the tmf version, mark the version in
the Module firmware dialog and
click the Properties button. The
Additional note dialog to the right
is shown. Enter a description and
click OK.
Figure B4
7. In the Orion Service software,
choose Download firmware.
Click Query to list the available
module firmware versions on the
Visionline server.
8. Mark the applicable firmware
version and click Download.
9. If applicable, repeat step 7 with
other firmware that is to be
uploaded.
10.Plug the service cable into the
thermostat or motion sensor,
depending on which module
that is to be upgraded.
Figure B5
11.In the Orion Service software,
choose Upload firmware.
The firmware version(s) that have
been downloaded according to step
7 above will be shown. Mark the
applicable firmware version and
click Upload.
Figure B6
ASSA ABLOY Hospitality
66 8003 016-3
Appendix C: To set up a suite
Introduction
If two or more rooms should form a suite, all concerned thermostats must be connected as a
suite and the thermostat in the master room (main room of the suite) or master rooms (if there
are more than two rooms in the suite) must be initialized with suite settings. Follow the steps in
chapter 5 to set up the online network, but
do not initialize the thermostat with suite settings at that point. There are three suite
configurations:
One foyer door leading to two rooms, each with one guest door; see details here
Connected doors: two rooms connected by internal mechanical doors, no foyer door in
front of the two guest doors; see details here
One guest door leading to a suite of rooms (two or more rooms); see details here
To set up a suite with foyer door
One possible suite configuration is to have a foyer door, and behind the foyer door two rooms which form
a suite. In the example shown in Figure C1, the suite contains the rooms 102 and 103; each room has
one thermostat and one motion sensor. Room 102 is the master room of the suite, and hence the foyer
lock 102-103 is connected to the thermostat in room 102 when the online network is set up.
Note: For more information about the suite functionality, click here. Note: The foyer door must be
online; this is however not set up in the Door details dialog, instead the online type 'ZigBee' is
automatically sent to the server with the first event from the door. Note: Only one of the thermostats,
the master thermostat, is initialized with suite settings. The link between the two thermostats is set up
in Orion Service.
Figure C1
ASSA ABLOY Hospitality
66 8003 016-3
To enable 'suite with foyer door' in Visionline
Note: All concerned thermostats must be set up according to below, i.e. if the
different thermostats in the suite belong to different thermostat profiles, make
sure that the 'Suite with foyer door' checkbox is marked for each profile.
1. Double click on Thermostat
profiles under the Lists tab.
2. In the Thermostat profiles
dialog: click Add to add a new
thermostat profile, or mark an
existing thermostat profile and
click Properties.
3. In the Thermostat profile
details dialog, choose the Misc
alternative in the left pane.
4. Mark 'Suite with foyer door'.
5. If it is a new thermostat profile,
fill in all necessary information
under the different alternatives
in the left pane of the dialog.
6. Click Save and Close.
Figure C2
To set up the online network
The online network for the example in Figure C1 looks as in Figure C3. The two
thermostats 102 and 103 must be set up under the same parent in the network,
i.e. be set up in the same PAN (personal area network). To set up the network,
follow the steps below:
1. Double click on SysMon.exe in the Visionline installation folder to open
SysMon (System Monitor) which is used for managing the online network.
2. Log on to SysMon; go to File/Log on and enter user ID and password. At
'Operator card', choose the applicable card encoder and click Enter.
3. Go to View/Online Network to show the Online Network tree.
4. Install the gateway; see User manual Online option for details.
5. Initialize thermostat 102 with 'normal parameter', i.e. all parameters except
for those related to suite. To do this, use the Initialize alternative in Orion
Service but leave the Suite settings empty. See Quick reference guide Orion
Service for details about Initialize.
6. Connect thermostat 102 to the gateway; see chapter 5 for details.
7. Connect motion sensor 102 to thermostat 102; see chapter 5 for details.
8. Connect lock 102 to thermostat 102; see chapter 5 for details.
9. Connect the foyer lock to thermostat 102; see chapter 5 for details.
10.Repeat steps 5-8 for the devices in room 103.
11.Initialize thermostat 102 with suite settings; click here for details.
12.Read out the thermostat status for thermostats 102 and 103 respectively;
ASSA ABLOY Hospitality
66 8003 016-3
click here for details.
13.See the final Online Network tree in Figure C9.
Figure C3
To initialize the master thermostat with suite settings
1. Choose Initialize in the left pane
of the Orion Service window.
2. Connect the service cable to the
thermostat in room 102.
3. Click the plus sign for the applicable
door area (in this example 'Floor 1')
and mark the master room, in this
example 102.
Figure C4
4. At Suite settings:
- Enter the Suite room (slave
room); in this example it is 103.
- Leave the Share occupancy
checkbox empty; this is only
applicable when there is just one
door to the entire suite;
click here for more information
about that configuration.
Figure C5
5. Click the Initialize button.
Note: It is only the master room
that is initialized with suite settings,
so steps 1-4 above are never
performed for the slave room.
Figure C6
ASSA ABLOY Hospitality
66 8003 016-3
To read out the thermostat status
1. Choose Status in the left pane of
the Orion Service window.
2. Connect the service cable to the
thermostat.
3. Click the Readout button.
Example of suite status for master room
thermostat:
Figure C7
Example of suite status for slave room
thermostat:
Figure C8
Online network tree
When steps 1-5 below have been performed, the Online Network tree in SysMon
will typically look as in the example in Figure C9:
1. The thermostats have been initialized with "regular
parameters", i.e. all parameters except for those
related to suite.
2. Thermostats, motion sensors and guest room locks
have been connected to the online network according
to chapter 5.
3. The foyer lock has been connected to the master
room thermostat according to chapter 5.
4. The master room thermostat has been initialized with
suite settings according to here.
5. The status of the master room thermostat and of the
slave room thermostat has been read out according
to here.
Figure C9
ASSA ABLOY Hospitality
66 8003 016-3
To set up a suite with two rooms (not foyer)
One possible suite configuration is to have two guest rooms connected by internal
mechanical doors; no foyer door in front of the two guest doors. The connecting doors
can be locked and the rooms be used separately, or the two rooms can be used as a
suite with full access to both rooms. The thermostats in the two rooms share events
when the two rooms are used as suite, and if the rooms are not used as a suite the
events are handled independently.
Note: Only one of the thermostats, the master thermostat, is initialized with suite
settings. Once initialized, the two thermostats are equal and share events as above.
The link between the two thermostats is set up in Orion Service.
The two rooms can either be used separately or as a suite with the connecting doors
unlocked. The connecting doors are mechanical doors that are unlocked with a key
by staff, or by the guest with access to both rooms.
The Orion system must be connected to a server via a gateway in order for the
thermostats in the two rooms to be able to communicate. The link between the two
rooms is configured via Orion Service. The suite activation will be automatic if the
requirements mentioned in the sections VingCard guest door locks and Other guest
door locks than VingCard are met.
Note: If the doors A and B do not have VingCard locks, extra hardware must be
installed on the connecting doors to have the suite functionality enabled; see
details in section Other guest door locks than VingCard.
VingCard guest door locks
Figure C10
When a suite card is presented at one of the concerned VingCard locks (to either lock
102 or lock 103 in the example in Figure C10), the thermostat communicates with
the other connected room to activate suite mode and share events. The suite will be
active and events will be shared between the two thermostats, even if the connecting
doors are closed. Upon check-out or if the suite card expires, the thermostat disables
event sharing.
ASSA ABLOY Hospitality
66 8003 016-3
Visionline settings
1. Double click on Thermostat
profiles under the Lists tab
in the navigation window.
2. In the Thermostat profiles dialog:
click Add to add a new thermostat
profile, or mark an existing
thermostat profile and click
properties.
3. In the Thermostat profile details
dialog, choose the Misc alternative
in the left pane.
4. Make sure that the checkbox 'Suite
with foyer door' is unmarked.
5. If it is a new thermostat profile,
fill in all necessary information
under the different alternatives in
the left pane of the dialog.
6. Click Save and Close.
Figure C11
ASSA ABLOY Hospitality
66 8003 016-3
To set up the online network
The online network for the example in Figure C10 looks as in Figure C12. The two
thermostats 102 and 103 must be set up under the same parent in the network,
i.e. be set up in the same PAN (personal area network). To set up the network,
follow the steps below:
1. Open SysMon (System Monitor) which is used for managing the online network;
double click on SysMon.exe in the Visionline installation folder.
2. Log on to SysMon; go to File/Log on and enter user ID and password. At
'Operator card', choose the applicable card encoder and click Enter.
3. Go to View/Online Network to show the Online Network tree.
4. Install the gateway; see User manual Online option for details.
5. Initialize thermostat 102 with 'normal parameters', i.e. all parameters except for
those related to suite. To do this, use the Initialize alternative in Orion Service
but leave the Suite settings empty. See Daily use manual Orion EMS for details
about Initialize.
6. Connect thermostat 102 to the gateway; see chapter 5 for details.
7. Connect motion sensor 102 to thermostat 102; see chapter 5 for details.
8. Connect lock 102 to thermostat 102; see chapter 5 for details.
9. Repeat steps 5-8 for the devices in room 103.
10.Initialize thermostat 102 with suite settings; click here for details.
11.Read out the thermostat status for thermostat 102; click here for details.
12.Read out the thermostat status for thermostat 103; click here for details.
13.See the final Online Network tree in Figure C16.
Figure C12
ASSA ABLOY Hospitality
66 8003 016-3
To initialize the master thermostat with suite settings
1. Choose Initialize in the left pane of the
Orion Service window.
2. In this example, the master thermostat
is in room 102 (room A in Figure C10).
Connect the service cable to the
thermostat in room 102.
3. Click the plus sign for the applicable
door area(in this example 'Floor 1') and
mark room 102.
Figure C13
4. At Suite settings:
- Enter the Suite room (slave room);
in this example 103 (room B in Figure
C10).
- Leave the Share occupancy
checkbox empty; this is only
applicable when there is just one door
to the entire suite;
click here for more information about
that configuration.
Figure C14
5. Click the Initialize button.
Note: It is only the master room that
is initialized with suite settings, so
steps 1-4 above are never performed
for the slave room.
Figure C15
Online network tree
When steps 1-4 below have been performed, the Online Network tree in SysMon
will typically look as in the example in Figure C16:
1. The thermostats have been initialized
with "regular parameters", i.e. all
parameters except for those related to
suite.
2. Thermostats, motion sensors and guest
room locks have been connected to the
online network according to chapter 5.
3. The master room thermostat has been
initialized with suite settings according
to here.
4. The status of the master room
thermostat and of the slave room
thermostat has been read out according
to here.
Figure C16
ASSA ABLOY Hospitality
66 8003 016-3
Other guest door locks than VingCard
Figure C17
In the scenario when VingCard locks are not used, the two rooms (in the example in
Figure C17 they are called room 102 and room 103) each have two door switches set
up as Connecting door under the master thermostat (in our example the thermostat
in room 102). This will not disturb occupancy; the only trigger is suite activation.
See Quick reference guide Orion Service for information on how to configure for
Connecting door.
Note: For each room, one door switch is located at the guest door and one at the
connecting door; see Figure C17.
Note: If there is only one connecting door between the two rooms, there should be
three door switches set up under the master room; one door switch at the guest door
and two door switches at the connecting door.
When the master thermostat reads both door switches as open, it will activate the
suite by sending a message to the slave thermostat (thermostat 103 in Figure C17)
and share events from that point. If one or both of the connecting doors are closed,
the suite is deactivated. To set up a suite with two rooms when other locks than
VingCard locks are use, follow the steps below:
1. Follow this section to make Visionline settings.
2. Follow this section below to set up the online network.
3. Follow this section to initialize the master thermostat with suite settings.
4. Follow this section below to configure the door switches.
5. Follow this section below regarding the online network tree.
ASSA ABLOY Hospitality
66 8003 016-3
To set up the online network
The online network for the example in Figure C17, i.e. if other locks than VingCard
locks are used at the guest doors, looks as in Figure C18. The two thermostats 102
and 103 must be set up under the same parent in the network, i.e. be set up in the
same PAN (personal area network). To set up the network, follow the steps below:
1. Open SysMon (System Monitor) which is used for managing the online network;
double click on SysMon.exe in the Visionline installation folder.
2. Log on to SysMon; go to File/Log on and enter user ID and password.
At 'Operator card', choose the applicable card encoder and click Enter.
3. Go to View/Online Network to show the Online Network tree.
4. Install the gateway; see User manual Online option for details.
5. Initialize thermostat 102 with 'normal parameters', i.e. all parameters except
for those related to suite. To do this, use the Initialize alternative in Orion
Service but leave the Suite settings empty. See Daily use manual Orion EMS
for details about Initialize.
6. Connect thermostat 102 to the gateway; see chapter 5 for details.
7. Connect motion sensor 102 to thermostat 102; see chapter 5 for details.
8. Connect door switch guest 102 (door switch at the guest door in room 102) to
thermostat 102; see chapter 5 for details.
9. Connect door switch connecting 102 (door switch at the connecting door in
room 102) to thermostat 102; see chapter 5 for details.
10.Connect door switch connecting 103 (door switch at the connecting door in
room 102) to thermostat 102; see chapter 5 for details.
11.Repeat steps 5-7 for the devices in room 103.
12.Connect door switch guest 103 (door switch at the guest door in room 103) to
thermostat 103; see chapter 5 for details.
13.Initialize thermostat 102 with suite settings; click here for details.
14.Read out the thermostat status for thermostat 102; click here for details.
15.Read out the thermostat status for thermostat 103; click here for details.
16.See the final Online Network tree in Figure C20.
Figure C18
ASSA ABLOY Hospitality
66 8003 016-3
To configure the door switches
1. Choose Configure device in the
left pane of the Orion Service
window.
2. Choose Door switch in the upper
part of the Orion Service window.
3. Plug the service cable into the
door switch at the guest door in
room 102.
4. Select Connecting door in the
Orion Service window.
5. Repeat steps 3-4 for:
- the door switch at the
connecting door in room 102
- the door switch at the guest door
in room 103
- the door switch at the connecting
door in room 103
Example of suite status for
master room thermostat:
Figure C19
Online network tree
When steps 1-4 below have been performed, the Online Network tree in SysMon
will typically look as in the example in Figure C20:
1. The thermostats have been
initialized with "regular
parameters", i.e. all parameters
except for those related to suite.
2. Thermostats, motion sensors and
door switches have been connected
to the online network according to
chapter 5.
3. The master room thermostat has
been initialized with suite settings
according to here.
4. The status of the master room
thermostat and of the slave room
thermostat has been read out
according to here.
Figure C20
ASSA ABLOY Hospitality
66 8003 016-3
To set up a suite with one door only
One possible suite configuration is to have only one door to the entire suite. In the
example shown in Figure C21, the suite contains the rooms 1021, 1022 and 1023;
each room has one thermostat and one motion sensor. Room 1021 is the master
room for room 1022 and room 1022 is the master room for room 1023. The lock 102
is connected to the thermostat in the first room, i.e. to thermostat 1021, when the
online network is set up. Note: For more information about the suite functionality,
see section More about how the suite works.
Figure C21
ASSA ABLOY Hospitality
66 8003 016-3
To set up the online network
The online network for the above example looks as in Figure C22. The three
thermostats 1021, 1022 and 1023 must be set up under the same parent in the
network, i.e. be set up in the same PAN (personal area network). To set up the
network, follow the steps below:
1. Double click on SysMon.exe in the Visionline installation folder to open
SysMon (System Monitor) which is used for managing the online network.
2. Log on to SysMon; go to File/Log on and enter user ID and password. At
'Operator card', choose the applicable card encoder and click Enter.
3. Go to View/Online Network to show the Online Network tree.
4. Install the gateway; see User manual Online option for details.
5. Initialize thermostat 1021 with "regular parameters", i.e. all parameters except
for those related to suite. To do this, use the Initialize alternative in Orion
Service but leave the Suite settings empty. See Daily use manual Orion EMS
for details about Initialize.
6. Connect thermostat 1021 to the gateway; see chapter 5 for details.
7. Connect motion sensor 1021 to thermostat 1021; see chapter 5 for details.
8. Connect lock 102 to thermostat 1021; see chapter 5 for details.
9. Repeat steps 5-7 for the devices in rooms 1022 and 1023 respectively.
10.Initialize thermostat 1021 with suite settings; click here for details.
11.Initialize thermostat 1022 with suite settings; click here for details.
12.Read out the thermostat status for thermostat 1021; click here for details.
13.Read out the thermostat status for thermostat 1022; click here for details.
14.See Figure C32 for a picture of the final Online Network tree.
Figure C22
ASSA ABLOY Hospitality
66 8003 016-3
To initialize thermostats with suite settings
Figure C23
In the configuration with only one door to the entire suite, the thermostats are
initialized in a chain. The principle is described in Figure C23; room A in the room
chain is master for room B, which is in turn master for room C etc. This and this
section describe the example from Figure C21, i.e. three rooms in a chain.
To initialize the thermostat in the first room of the suite
1. Choose Initialize in the left pane of
the Orion Service window.
2. Click the plus sign for the applicable
door area (in this example 'Floor 1')
and mark the master room, in this
example 1021.
Figure C24
3. At Suite settings:
- Enter the Suite room (slave
room); in this
example 1022.
- Mark the Share occupancy
checkbox.
Figure C25
4. Click the Initialize button.
Note: It is only the master room
that is initialized with suite settings,
so steps 1-3 above are never
performed for the slave room.
Figure C26
ASSA ABLOY Hospitality
66 8003 016-3
To initialize the thermostat in the second room of the suite
1. Choose Initialize in the left pane
of the Orion Service window.
2. Click the plus sign for the
applicable door area (in this
example 'Floor 1') and mark the
master room, in this example
1022.
Figure C27
3. At Suite settings:
- Enter the Suite room (slave
room); in
this example 1023.
- Mark the Share occupancy
checkbox.
Figure C28
4. Click the Initialize button.
Note: It is only the master room
that is initialized with suite
settings, so steps 1-3 above are
never performed for the slave
room.
Figure C29
ASSA ABLOY Hospitality
66 8003 016-3
To read out the thermostat status
1. Choose Status in the left pane of
the Orion Service window.
2. Connect the service cable to the
thermostat.
3. Click the Readout button.
Example of suite status for the
first thermostat in the chain:
Figure C30
Example of suite status for the
second thermostat in the chain:
Figure C31
Online network tree
When steps 1-4 below have been performed, the online network tree in SysMon will
typically look as in the example in Figure C32:
1. The thermostats have been
initialized with "regular
parameters", i.e. all parameters
except for those related to suite.
2. Thermostats, motion sensors and
the lock have been connected to
the online network according to
chapter 5.
3. All thermostats except for the last
one in the chain (see Figure C23
for a description of the principle)
have been initialized with suite
settings according to this section.
4. The status of all master room
thermostats have been read out
according to this section.
Figure C32
ASSA ABLOY Hospitality
66 8003 016-3
More about how the suite works
Note: Check-out is made separately from each room in the suite, i.e. check-out from
the master room will not automatically check out all cards that are valid in the entire
suite. If the check-out is made from PMS, it can however be made with one
command, even if the concerned rooms must be defined separately in the PMS
command.
Suite with foyer
Suite card
In the example described in this section, i.e. a foyer door with two guest rooms
behind (see Figure C33), the suite guest will get a suite card which gives access to
both rooms in the suite
the foyer door, which should be closed when the guest arrives
Figure C33
When the guest uses the suite card in the foyer door, the door will
send information to the thermostat in the master room, i.e. in this example 102,
that a suite card has been used in the foyer door and the thermostats should
now share the state (occupied or unoccupied). When there is movement in any
of the two guest rooms 102 or 103, the thermostat in the concerned room will
send information to the thermostat in the other room that the state is changed
to occupied.
send information about when the suite card will expire; after this expiration
time, the thermostats in rooms 102 and 103 will leave the suite mode.
ASSA ABLOY Hospitality
66 8003 016-3
Regular guest card
If the suite guests have checked out and a "regular guest" arrives, i.e. a guest which
should only have access to one of the rooms in the former suite, the regular guest
will get a guest card with access to
the concerned guest room
the foyer door
Since the guest room is no longer part of a suite, it does not matter if the foyer door
is open or closed when the guest arrives. In both cases, the foyer door as well as the
guest room door will send information to the thermostat in the concerned guest room
that
the room is rented as a single room and not as part of a suite
the card is valid in the room to a certain date and time.
Note: The thermostats in rooms 102 and 103 will now only consider the door events
for their "own" room and will not share the occupancy state with the thermostat in
the other room.
Suite with one door only
For the suite configuration described in this section, i.e. with only one guest door
leading to two or more rooms (see Figure C34), the rooms are a "permanent suite"
and are never rented as separate, regular guest rooms. When the guest uses his
suite card in the door, the door will send information to the first master thermostat
in the chain, i.e. in this example to the thermostat in room 1021 (see Figure C35)
that will share the occupancy state with the other thermostats.
Figure C34
Figure C35
ASSA ABLOY Hospitality
66 8003 016-3
Appendix D: Configuration in offline scenarios
In Orion EMS offline scenarios, there is no connection to the Visionline server; each
room can be seen as a PAN (personal area network) .
The firmware in the thermostat is a coordinator firmware instead of a router firmware.
Figure D1
The RFID lock in the configuration pictures above must be prepared in two ways:
it must be online with the in-room network
EMI events must be enabled in the lock. This can be done either with
an Enable EMI events card or via Lock Service; see the applicable one
of sections Enabling EMI events via card and Enabling EMI events via
Lock Service.
Note: The EMI events will be sent to the closest parent in the in-room network,
since there is no connection to the Visionline server.
ASSA ABLOY Hospitality
66 8003 016-3
To add the lock to the in-room network
The in-room network is configured under the Configure device section in Orion
Service.
Configuration
Description
Form new
network
This configuration removes all nodes in the PAN and resets
the coordinator.
Permit join
When this configuration is used, an in-room device (RF door
switch, motion sensor or lock) can join the coordinator.
Forbid join
When the RF door switch, motion sensor or lock has joined
the coordinator, this configuration should be used on the
coordinator.
Note: If the Forbid join command is for some reason
forgotten, it will automatically be executed 15 minutes after
the Permit join command was executed.
Set channels
Default is that all channels are ON (the '1' indicates ON);
the best channel will automatically be chosen, so normally
the Set channels command is not needed.
Get network
This configuration shows the in-room network.
Note: When hovering with the cursor over an item in the
network, the tooltip will show what type of item it is; e.g.
'Coordinator' as in the screenshot example above. The
tooltip will also show e.g. IEEE address and firmware
version.
Table D1
1. Go to Start/Programs/
Orion Service/Orion Service.
2. Choose Configure device in the
left pane of the Orion Service
window.
3. Plug the service cable into
the thermostat.
4. Choose the Coordinator tab.
5. Click Form new network.
Figure D2
ASSA ABLOY Hospitality
66 8003 016-3
6. Click the Get network button;
the thermostat will appear in
the window below Get network.
Figure D3
7. Put the cursor on the thermostat
in the Orion Service window; an
information box, showing e.g. the
thermostat channel, will appear.
If the channel should be changed,
click the applicable channel (in the
picture example '26') and click the
Set channels button.
8. Mark the thermostat and click the
Permit join button.
Figure D4
9. Right click on the thermostat and
choose Get user description.
Information about the thermostat
will be shown; see picture to the
right. Make sure that:
- the channel is correct
- it says 'yes'at 'Join permitted'
Note: If it does not say 'yes' at
'Join permitted', click the Permit
join button again.
Figure D5
10.Plug the service cable into the
motion sensor.
11.Choose the Motion sensor tab
and click Discovery.
Figure D6
ASSA ABLOY Hospitality
66 8003 016-3
12. Plug the service cable into the
thermostat.
13. Choose the Coordinator tab
and click Get network.
Figure D7
14. Click the plus sign in front of the
thermostat; the motion sensor will
appear in the network tree.
15. Right click on the thermostat to
make sure that is still says 'yes' at
'Join permitted'.
Figure D8
16. Issue a Discovery card in
Visionline:
- Go to Start/Programs/
VisiOnline/VisiOnline and log on.
- Double click on ZigBee
configuration under the Cards
tab in the navigation window.
- Browse to choose a Card holder
and enter No. of days.
- At Type, choose 'Start discovery
in ZigBee'.
- If applicable, tick the checkbox
'Print receipt'.
- Click Make card and present
a card at the encoder.
17. Present the Discovery card at
the lock.
Figure D9
18. In Orion Service, Configure
device section: click Get network
under the Coordinator tab.
Figure D10
ASSA ABLOY Hospitality
66 8003 016-3
19. Click the plus sign in front of the
thermostat; the lock will appear
in the network tree.
20. Mark the thermostat and click the
Forbid join button.
21. Right click on the thermostat and
choose Get user description.
Make sure that the description
says 'no' at 'Join permitted'.
Figure D11
ASSA ABLOY Hospitality
66 8003 016-3
Appendix E: To install an
external motion sensor
Note: Orion High Voltage Thermostat has a built-in motion sensor, but in some
cases (depending on thermostat location in the room) it can be applicable to also
have an external motion sensor as the one described in this section.
The motion sensor is used to detect motion in the room and send this information
via the ZigBee endnode to the to the room controller (thermostat). The device
is designed to be ceiling or wall mounted and is powered by 3AA batteries.
No physical connections are required; thus making the installation simple.
Figure E1
The motion sensor is a battery operated device that may be installed on the ceiling
or wall. The mounting bracket is installed with two screws as shown in Figure E2.
Figure E2
ASSA ABLOY Hospitality
66 8003 016-3
Quick reference of technical data
Dimensions
Ø: 120 mm (4 23/32)''
H: 44.2 mm (1 3/4)''
Input power
3 AA batteries (4.5 VDC)
Mounting
Ceiling or wall surface mounting
Keyhole type for easy installation and
battery relpacement access
Range
360 degrees/ 8 meters horizontal /
3 meters vertical
Messages transmitted
Motion detected
Battery status
Diagnostics
Integrated LED only enabled for diagnostics
Table E1
Motion sensor dimensions in mm (inches)
Figure E3
ASSA ABLOY Hospitality
66 8003 016-3
Motion sensor locations
Figure E4
For optimal coverage, the motion sensor should be installed on the ceiling as close to the middle
of the room as possible. When ceiling mounting is not feasible, either due to the construction or
for the aesthetics of the room, the sensor may be placed on the wall. The location should be as
high as possible and give as much coverage to the room as possible. Figure E4 shows the range
of the motion sensor when placed on the ceiling. This range is somewhat reduced when installed
on the wall. The range shown is a general guideline, and the sensor is designed to cover an area
of about 8m (26 feet) in diameter. To check the location, it is advisable to activate the motion
LED using the service device and test the range of the motion sensor. This process will help to
determine the best location of the sensor. See section To test the in-room devices for
instructions on this process.
ASSA ABLOY Hospitality
66 8003 016-3
Appendix F: Read more
Document name
Document number
User manual Online option
66 3081 004
User manual Orion High Voltage Thermostat
66 8003 015
Revision history
Date
Change
By
August 19, 2010
Initial version
KG
November 15,
2010
‘Configure device’ in Orion Service modified
KG
July 5, 2011
Information about thermostat controller added
Information about service indicators added
Appendix about Orion Service connections
added
Appendix about configuration in offline
scenarios added
KG
October 6, 2011
Logotypes changed
Information about commissioning when
thermostat controller is used has been added
KG
October 20, 2011
Section about Recommended wire specification
modified due to
requirements for UL certification
Picture in section Line to low voltage conversion
exchanged
due to requirements for UL certification
KG
February 16, 2012
Added reference to Upgrading an RFID lock for
an Orion EMS offline scenario for information
about what firmware to use in different
configurations
Added information about RF door switch
Modified the section Commissioning the system;
use the Thermostat tab also for battery
thermostats
Added information to Appendix D: Configuration
in offline scenario:
- configuration pictures
- how to enable and log EMI events in locks
KG
June 5, 2012
Updated to match Orion Service 1.2.0
KG
ASSA ABLOY Hospitality
66 8003 016-3
July 5, 2012
Info added to chapter 1 General about the
number of Orion EMS devices that each room
number can have a certain number of Orion
EMS devices
KG
September 13,
2012
Clarified about V+ in section 3.3
Clarified about V+ and signal inputs in section
4.1
Added section 4.1.1 about RS-485 interface
Removed information about USB Xpress in
Appendix A
KG
March 7, 2014
Added information about suites
KG
February 19, 2016
Layout updated
Added 'cool down' parameter
KG
October 12, 2016
Modified maximum value of 'room not occupied
timer' to 120 minutes
KG
ASSA ABLOY Hospitality
66 8003 016-3
E-mail: [email protected]
ASSA ABLOY Hospitality APAC
Phone: +65 6305 7670
ASSA ABLOY Hospitality EMEA
ASSA ABLOY Hospitality North America
Phone: +47 69 24 50 00
E-mail: [email protected]
E-mail: [email protected]
Phone: +1 972 907 2273
ASSA ABLOY Hospitality Latin America
E-mail: [email protected]
Phone: +52 55 36 40 12 00
www.assaabloyhospitality.com