IBC AHU Series Installation & Operating Manual
Text of the manual
Cabinet and air supply dimensions
9
Dimensions for the AHU 800 model
9
Dimensions for the AHU 1200 model
11
Dimensions for the AHU 1600 model
12
Thermostat connections
14
1.0 Introduction
17
1.1 Standard features and benefits
17
1.2 Conformity
18
2.0 Installation
19
2.1 Locating the appliance
19
2.1.1 Conditioned space
19
2.1.2 Un-conditioned space
19
2.1.3 New construction
19
2.1.4 Mobile home
19
2.1.5 Closet
20
2.1.6 Garage
20
2.1.7 Serviceability
21
2.2 Positioning and mounting the appliance
21
2.2.1 Return air openings for ducting
21
2.2.2 Positioning the air handling unit
22
2.2.3 Adding air conditioning coils or heat pump coils
22
2.2.4 Mounting an appliance on the wall
23
2.2.5 Repositioning the air filter brackets
24
2.3 Duct work
26
2.3.1 Sizing the ducts
26
2.3.2 Ducting installed in conditioned space
27
2.3.3 Ducting installed in un-conditioned spaces
27
2.3.4 Making the return air openings
27
2.4 Connecting the appliance to the boiler
28
2.4.1 Sizing pumps
28
2.4.2 Using Propylene Glycol
30
2.5 Connecting the appliance to a tankless water heater
30
2.6 Electrical connections
32
2.6.1 Wiring of the external pump and 120VAC line
33
2.6.2 Connecting line voltage - examples for different scenarios
33
3.0 Operation
45
3.1 Checklist for electrical conditions, ducting and water connections
45
3.2 Default settings
46
3.3 Default fan speed settings
46
3.4 Sequence of operation
47
3.4.1 Heating Mode
47
3.4.2 Cooling Mode
47
3.4.3 Heat Pump Mode
47
3.4.4 Humidification Mode
48
3.4.5 De-humidification Mode
48
3.4.6 Freeze Protection Mode
48
3.5 LED status indicators
49
Built-in diagnostics feature
49
3.6 Operating the appliance with a mobile app
50
3.6.1 Loading IBCconnect
50
3.6.2 Using the app to connect to IBC's AHU WiFi
51
3.6.3 Programming the air handling unit using the app
53
3.6.4 Using the app to view the AHU's information
55
3.7 Configuring settings and parameters via a USB text file
57
4.0 Service and maintenance
59
4.1 Maintenance checklist for owners
59
4.2 Maintenance for the heating contractor
59
4.2.1 Removing the fan assembly
59
4.2.2 Replacing the hot water coil appliance
61
4.3 Replacing the control board
62
4.4 Temperature sensors
64
5.0 Troubleshooting
67
5.1 Measuring voltage on AHU boards
67
5.2 Pump not energized
67
2
Section: Contents
Manual safety markings
Danger
Points out an immediate hazardous
situation that must be avoided to
prevent serious injury or death.
Warning
Points out a potential hazardous
situation that must be avoided to
prevent serious injury or death.
Caution
Points out a potential hazardous
situation that must be avoided to
prevent possible moderate injury
and/or property damage.
Note
Points out installation, maintenance and
operational notes to enhance efficiency,
longevity and proper operation of the air
handling appliance.
Danger
Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any
other appliance. If you smell gas vapors, do not try to operate any appliance - do not touch
any electrical switch or use any phone in the building. Immediately, call the gas supplier
from a phone located remotely. Follow the gas supplier’s instructions, or if the supplier is
unavailable, contact the fire department.
Warning
Improper installation, adjustment, alteration, service or maintenance can cause property
damage, personal injury, or loss of life. Read and understand the entire manual before
attempting installation, start-up, operation, or service. Installation and service must be
performed only by an experienced, skilled installer or service agency.
Failure to follow all instructions in the proper order can cause personal injury or death. Read
all instructions, including all those contained in component manufacturers’ manuals before
installing, starting up, operating, maintaining, or servicing the appliance.
Warning
Disconnect power supply before any wiring/service is performed. Failure to do so could
result in damage to appliance and/or electric shock.
Caution
Do not pierce cabinet as internal damage may occur to electrical and hydronic components.
5
Safety information
The air handler must be installed so that electrical components are not exposed to water
during operation.
Note
All wiring on IBC air handlers must adhere to the National Electrical Code and/or local
regulations.
Note
All appliances conform to CSA C22.2 NO. 236-15 and UL 1995 Stds. Water coil
conforms to NSF / ANSI Std. 372.
Important safety instructions
Failure to read and comply with all instructions and applicable national and local codes may result in
hazardous conditions that could result in property damage and injury to occupants, and in extreme
cases to death. Keep instructions near the air handling appliance for future reference.
When using electrical appliances, follow safety precautions to reduce the risk of fire, electric shock,
or injury to persons, including:
Install or locate the air handling appliance only in accordance with the provided installation
instructions.
Use the air handling appliance only for its intended use as described in this manual.
Do not operate the air handling appliance if it is not working properly, or if it has been
damaged or dropped.
Installation, start-up and servicing of IBC's air handling appliances must be done with care
and attention, and should only be performed by competent, qualified, licensed and trained
plumbing and heating technicians. Contact your nearest authorized service facility for
examination, repair, or adjustment.
If subjected to flooding, the appliance must be replaced.
6
Section: Safety information
Max. water temperature (°F/C°)
195 / 90
Coil performance at 180°F (Btu/hr)
66,800
80,600
99,300
Water pipe connections (inches)
¾ MPT
External static pressure (" wc)
0.50
Max. operating water pressure (PSI)
150
Width (inches)
17.5
21
24.5
Depth (inches)
26
Height (inches)
32
38
42
Supply air opening width (inches)
16
19.6
23
Supply air opening depth (inches)
19.6
Side return air opening height (inches)
7
10.5
13
Side return air opening width (inches)
23
Bottom return air opening width (inches)
13
10.5
14
Bottom return air opening depth
(inches)
23
Max. internal current power rating
120Volts (Amp)
2.4
External pump supply 120V (Amp)
5
Voltage (V)
120
Max. air flow @ rated static pressure
(CFM)
1138
1334
2900
Maximum return air temperature (°F/C°)
122 / 50
Filter size (MERV 8) (inches)
16 x 25 x 1
25 x 20 x 1 (not
included)
25 x 20 x 1 (not
included)
7
Specifications
AHU 800 - Heating Capacity (Entering Dry Bulb Temperature 70°F) @ 800 CFM
Entering Water Temperature
3 GPM
4 GPM
5 GPM
195°F (90°C)
68.6 MBH
73.2 MBH
76.2 MBH
190°F (88°C)
65.7 MBH
70.2 MBH
73 MBH
180°F (82°C)
60 MBH
64.1 MBH
66.8 MBH
170°F (77°C)
54.4 MBH
58.1 MBH
60.5 MBH
160°F (71°C)
48.7 MBH
52.1 MBH
54.3 MBH
150°F (66°C)
43.1 MBH
46.2 MBH
48.1 MBH
140°F (60°C)
37.6 MBH
40.2 MBH
41.9 MBH
130°F (54°C)
32 MBH
34.3 MBH
35.8 MBH
120°F (49°C)
26.5 MBH
28.5 MBH
29.7 MBH
110°F (43°C)
21.1 MBH
22.6 MBH
23.7 MBH
Table 1 Heating Capacity rating at 800 scfm (cubic feet / minute) - AHU 800
AHU 1200 - Heating Capacity (Entering Dry Bulb Temperature 70°F) @ 1200 CFM
Entering Water Temperature
3 GPM
4 GPM
5 GPM
195°F (90°C)
81.3 MBH
87.7 MBH
91.8 MBH
190°F (88°C)
78 MBH
84.1 MBH
88.1 MBH
180°F (82°C)
71.3 MBH
76.9 MBH
80.6 MBH
170°F (77°C)
64.6 MBH
69.8 MBH
73.1 MBH
160°F (71°C)
58 MBH
62.6 MBH
65.6 MBH
150°F (66°C)
51.4 MBH
55.5 MBH
58.2 MBH
140°F (60°C)
44.8 MBH
48.4 MBH
50.8 MBH
130°F (54°C)
38.3 MBH
41.4 MBH
43.4 MBH
120°F (49°C)
31.8 MBH
34.3 MBH
36 MBH
110°F (43°C)
25.3 MBH
27.4 MBH
28.7 MBH
Table 2 Heating Capacity rating at 1200 scfm (cubic feet / minute) - AHU 1200
8
Section: Specifications
AHU 1600 - Heating Capacity (Entering Dry Bulb Temperature 70°F) @ 1600 CFM
Entering Water Temperature
3 GPM
4 GPM
5 GPM
195°F (90°C)
96.9 MBH
106.7 MBH
113.2 MBH
190°F (88°C)
92.9 MBH
102.3 MBH
108.6 MBH
180°F (82°C)
84.9 MBH
93.5 MBH
99.3 MBH
170°F (77°C)
77 MBH
84.8 MBH
90 MBH
160°F (71°C)
69.1 MBH
76.1 MBH
80.8 MBH
150°F (66°C)
61.2 MBH
67.4 MBH
71.6 MBH
140°F (60°C)
53.3 MBH
58.8 MBH
62.5 MBH
130°F (54°C)
45.5 MBH
50.2 MBH
53.4 MBH
120°F (49°C)
37.7 MBH
41.6 MBH
44.3 MBH
110°F (43°C)
30 MBH
33.2 MBH
35.3 MBH
Table 3 Heating Capacity rating at 1600 scfm (cubic feet / minute) - AHU 1600
Cabinet and air supply dimensions
Dimensions for the AHU 800 model
Figure 1 Supply and return air, boiler supply and return
Figure 2 Frontal view
9
Cabinet and air supply dimensions
Figure 3 Top supply air opening
Figure 4 Bottom return air opening
Figure 5 Left side return air opening
Figure 6 Right side return air opening
10
Section: Specifications
Dimensions for the AHU 1200 model
Figure 7 Supply and return air, boiler supply and return
Figure 8 Frontal view
Figure 9 Top view
Figure 10 Bottom view
11
Dimensions for the AHU 1200 model
Figure 11 Left side return air opening
Figure 12 Right side return air opening
Dimensions for the AHU 1600 model
Figure 13 Supply and return air, boiler supply and
return
Figure 14 Frontal view
12
Section: Specifications
Figure 15 Top view
Figure 16 Bottom view
Figure 17 Left side return air opening
Figure 18 Right side return air opening
13
Dimensions for the AHU 1600 model
Three types of thermostats are compatible with the appliance: conventional, power stealing, and
OpenTherm.
Low Voltage Terminal
Description
Notes
R
24V power
Power to the low voltage
thermostat.
W1
Heating Stage 1
Thermostat connects R to
W1 for first stage heating.
Note: A jumper between W1
and W2 will initiate W2
speed.
W2
Heating Stage 2
Thermostat connects R to
W2 for second stage
heating.
Y1
Cooling Stage 1
Thermostat connects R to
Y1 for first stage cooling.
Y2
Cooling Stage 2
Thermostat connects R to
Y2 for second stage cooling.
G
Fan
Thermostat connects R to G
to energize fan for ventilation
speed.
C
24V common
Common return from the
thermostat – not required for
all thermostats.
T-T
Dry Contacts
Boiler call for heat.
Auxiliary
Com
S1 O/B
Reversing valve
Connects to outdoor
appliance on heat pump.
Note: Energized for cooling.
S2
Not used
Compressor
14
Section: Specifications
Low Voltage Terminal
Description
Notes
Com
Connects to outdoor
appliance.
S1
Compressor Stage 1
Connects to outdoor
appliance.
S2
Compressor Stage 2
Connects to outdoor
appliance (2nd Stage if
applicable).
Humidifier
Com
Humidifier
24VAC powered
Closes to activate the
humidifier.
HUM
Humidifier
De-humidifer
Com
De-humidifier
24VAC powered
Closes to activate the de-
humidifier.
DEH
De-humidifier
OpenTherm
OpenTherm Master
To X-13 (1-2) on boiler (IBC
SFC/SFB series)
The air handling appliance
(master) communicates to
(controls) the boiler
(subordinate).
OpenTherm Slave
From OpenTherm thermostat
The thermostat (master)
controls the air handling
appliance (subordinate).
Note
OpenTherm is a standard communications protocol used in central heating systems for the
communication between a central heating device and thermostat.
15
Thermostat connections
The IBC air handling appliance is designed for ducted heating and cooling. The appliance provides up to
four mounting options for flexibility and ease of installation. Return air duct connections can be
connected left, right, and bottom to suit the appliance's mounting position. For information on mounting
positions and sizing, see Cabinet and air supply dimensions on page 9.
Appliances installed with a right side air opening will require the air filter position to be modified. For
instructions, see Repositioning the air filter brackets on page 24.
1.1 Standard features and benefits
Integrated air handling appliance
High efficiency motor with variable speed (ECM) centrifugal fan
Quiet operation
Slide out fan assembly
Optional filter rack positioning
High efficiency fin tube coil
Industry standard duct sizes – supply air opening compatible with cased and uncased A/C
and heat pump coils
Single stage or 2-stage heating and cooling
Compact design for those awkward spaces; the ability to orient horizontally or vertically
Heat pump capable
Control for external pump (5A - 120V)
Flexible electrical connection knock-outs on left and right sides
Standard thermostat capable
OpenTherm thermostat capable
WiFi connection for programming with the IBCconnect mobile app
Sensors for protection and operation:
Included - sensors for supply air, return air, supply water, return water, humidifier, de-
humidifier, and frost protection
Not included - (optional) outdoor sensor (IBC Part # 240-025), air conditioning coil
supply, air sensor kit
Maximum return air temperature 122°F (50°C)
1.2 Conformity
Installation must conform to the requirements of the authority having jurisdiction. In the absence of
such requirements, the installation must conform to the National Electrical Code ANSI/NFPA No.
70, current edition.
18
Section: Introduction
Inspect shipment carefully for signs of damage. All equipment is carefully inspected and packed. IBC’s
responsibility ceases upon delivery of the air handling appliance to the carrier. Any claims for damage or
shortage must be filed immediately against the carrier. No claims for variances or shortages will be
allowed by the manufacturer.
This section provides installation guidelines for the air handling appliance including locating the
appliance, mounting positions, ducting, piping, and wiring.
2.1 Locating the appliance
2.1.1 Conditioned space
Even though the air handling appliance operates quietly, try to locate the appliance to minimize
noise transmission to conditioned spaces.
Avoid locating the appliance next to bedrooms or other noise sensitive locations.
If connecting a cooling system to the appliance, we recommend insulating the supply air ducting
with a minimum of 1" thick fiberglass insulation with a vapor barrier. All insulated joints must be
sealed with a tape designed for this purpose.
2.1.2 Un-conditioned space
If locating the appliance in an un-conditioned space, protect the hydronic coil from freezing conditions.
Propylene glycol may be required to prevent freezing of the coil. Use a minimum of 25% to a maximum
of 50% mixture of propylene glycol with water.
Insulate the supply air and return air ducting with a minimum 2" thick fiberglass insulation with a vapor
barrier. All insulated joints must be sealed with tape designed for this purpose. The appliance should
also be insulated with a minimum 2" thick fiberglass insulation with a vapor barrier.
2.1.3 New construction
The appliance is not designed to provide temporary heat during construction. If used, you must
thoroughly clean the appliance (including the fan and coil) to remove all contaminates and install with a
new air filter . If used for temporary heating during construction, the warranty may be void.
2.1.4 Mobile home
The appliance can be installed in a mobile home. Appliances installed in a mobile or manufactured home
must conform to the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280
and/or CAN/CSA Z240 MH Series, Mobile Homes.
The appliance is approved for installation in a closet.
Figure 19 View from top of air handling
appliance and duct in a closet
Figure 20 Front view of air handling appliance in a
closet with ducting on the left
Orientation
Clearance to
Combustible
Clearance for servicing
Top
6"
6"
D
Left Side
0"
3" min.
B
Right Side
0"
3" min
Bottom
0"
0" (if no connection)
C
Front
1"
24"
A
Back
0"
0"
Table 4 Recommended minimum clearance for combustibles and servicing
2.1.6 Garage
Garage installations must be in a fully enclosed garage. The appliance is not suitable for outdoor
installations.
Danger
Install the appliance at a minimum of 18" above the garage floor to prevent flammable
vapors reaching the appliance. Failure to follow this directive could result in an explosion
or electric shock, potentially causing serious personal injury and/or property damage.
20
Section: Installation
Install the appliance so that the front access panel is readily accessible for servicing. The front panel
must be removed for access to the filter for replacement and access to the control board for wiring and
setup. For more information on maintenance, see Service and maintenance on page 59. For wiring
diagrams, see Electrical connections on page 32.
2.2 Positioning and mounting the appliance
This section provides guidance on ways to orient and install the appliance. Ensure that:
You install the air handling appliance level and plumb.
If the appliance is sitting on the floor, shim as needed to level the appliance.
If the appliance is suspended, it is secured to the mounting system.
The appliance offers four mounting options for supply air discharge: up, down, left, or right. For diagrams
on the possible orientations including dimensions, see Cabinet and air supply dimensions on page 9.
2.2.1 Return air openings for ducting
The appliance provides three options for return air opening: left or right side return air and bottom return
air.
Figure 21 Left return air opening
Figure 22 Right return air opening
21
2.1.7 Serviceability
If installing the appliance with the air supply opening on the right, you will need to reposition the air
filter brackets. For instructions, see Repositioning the air filter brackets on page 24.
2.2.2 Positioning the air handling unit
You can install the appliance so the air flows in a vertical up-flow or down-flow direction, or in a
horizontal left or right direction.
Figure 23 : Upflow installation
Figure 24 : Downflow installation
Figure 25 : Left side installation
Figure 26 : Right side installation
2.2.3 Adding air conditioning coils or heat pump coils
Cased evaporator coils used for providing cold air can be positioned above or below the air handling
appliance as shown below.
22
Section: Installation
Figure 27 : Air conditioning/heat pump cased coil
mounted on top of the appliance - upflow
Figure 28 : Heat pump cased coil on the bottom of
the appliance on the return side - upflow
2.2.4 Mounting an appliance on the wall
Mount the appliance with a pair of field-supplied wall brackets.
Figure 29 : Wall mounted air handling appliance
23
2.2.4 Mounting an appliance on the wall
2.2.5 Repositioning the air filter brackets
All appliances are delivered with the filter positioned for an appliance installed with a left or bottom
return air supply opening. If you install the appliance with a right return air supply orientation for
ducting, you will need to reposition the air filter brackets in the opposite position.
To reposition the filter:
1. Remove the two screws from the front cover
of the appliance, and set aside.
2.
Slide out the filter.
The filter brackets highlighted below will need to be
repositioned.
3. Remove the two wing nuts securing
the upper left bracket, and set them
aside.
24
Section: Installation
5. Remove the wing nuts from the lower right
bracket.
6. Reposition the top and bottom
brackets on the opposite side.
7. Slide the filter into the repositioned
brackets.
25
2.2.5 Repositioning the air filter brackets
2.3 Duct work
Ducting design and installation should adhere to
SMACNA and/or ASHRAE guidelines. Install the
ducting system to NFPA 90B (latest edition).
Adhere to the following:
Size the supply air plenum duct fitting to
the size of the appliance's supply air
opening, and extend for 3' above the
appliance.
Size the supply and return air ducting
according to ASHRAE standards or
equivalent.
Seal all joints and connections to prevent
air leakage from the ducting system.
Choose accessories that will not
excessively restrict the air flow and create
excessive pressure drop on the system.
2.3.1 Sizing the ducts
If using flex / insulated flex ducting, ensure that you allow for a higher pressure drop.
Branch Duct - CFM at .25"wc external static pressure (galvanized duct)
Round
CFM range
3"
20-30
4"
30-35
5"
55-65
6"
90-100
7"
135-160
Table 5 Sizing round galvanized duct for CFM range
26
Section: Installation
Supply / Return Air Trunk Size CFM at .3"wc external static pressure (galvanized duct)
Round
Rectangular
CFM range
8"
8 x 6
8 x 7
160-190
190-230
9"
8 x 8
230-275
10"
10 x 8
275-360
11"
12 x 8
360-460
12"
14 x 8
460-570
13"
16 x 8
570-650
13"
18 x 8
650-750
14"
20 x 8
750-850
14"
22 x 8
850-950
15"
24 x 8
950-1050
Table 6 Supply air trunk size CFM at galvanized duct .3"wc ESP for return and supply air
2.3.2 Ducting installed in conditioned space
If a cooling system is connected to the appliance, we recommend insulating the supply air ducting with
a minimum of 1" thick fiberglass insulation with a vapor barrier. All insulated joints must be sealed with
tape designed for this purpose.
2.3.3 Ducting installed in un-conditioned spaces
Supply air and return air ducting should be insulated with a minimum 2" thick fiberglass insulation with a
vapor barrier. All insulated joints must be sealed with a tape designed for this purpose.
2.3.4 Making the return air openings
Both sides as well as the bottom of the appliance provide markings for the maximum return air opening.
Use suitable metal cutters to perforate the marked area for the return air supply. Ensure that you cut
within the marked area.
27
2.3.2 Ducting installed in conditioned space
Figure 30 Shears' opening
2.4 Connecting the appliance to the boiler
Generally it’s best to place the appliance as close as practical to the boiler. If placing the appliance
away from the boiler, ensure the piping system is designed to allow the easy removal of air from the
boiler piping and easy flushing of the system.
Copper Pipe Sizing
BTU / HR Capacity
½"
16,000 BTU
¾"
36,000 BTU
1"
72,000 BTU
1¼"
110,000 BTU
Table 7 Pipe sizing
2.4.1 Sizing pumps
Note
To size the pump, refer to the Installation manual of the boiler manufacturer for boiler head
loss specifications.
28
Section: Installation
Check valve (field supplied)
Fill station or glycol feeder (field supplied)
Figure 31 Basic installation: boiler / water heater with pump
Air Handler Coil Head Loss - AHU 800
Flow rate (gpm)
3
4
5
Fluid pressure drop (ft/water)
1.6
2.7
3.5
Table 8 Air handler coil head loss at 180°F (82°C) - AHU 800
29
2.4.1 Sizing pumps
Air Handler Coil Head Loss - AHU 1200
Flow rate (gpm)
3
4
5
Fluid pressure drop (ft/water)
2.7
4.6
6.3
Table 9 Air handler coil head loss at 180°F (82°C) - AHU 1200
Air Handler Coil Head Loss - AHU 1600
Flow rate (gpm)
3
4
5
Fluid pressure drop (ft/water)
2.2
3.4
5.1
Table 10 Air handler coil head loss at 180°F (82°C) - AHU 1600
2.4.2 Using Propylene Glycol
Using a propylene glycol / water mixture with the boiler/ air handling appliance reduces the heating
capacity of the system by up to 10%, and increases the pump head required to circulate the heating
fluid. Use a minimum of 25% to a maximum of 50% mixture.
It is important to install the system with the correct pipe size to achieve optimum heating capacity
from the air handling appliance. It is equally important to choose the correct circulator.
2.5 Connecting the appliance to a tankless water heater
Check local codes to ensure that piping the appliance to a tankless water heater is allowed.
The air handling appliance must be installed in close proximity to a tankless water heater. As a
guideline, we recommend a maximum distance of 10 feet between the appliance and the tankless
water heater using ¾" copper piping.
The table below provides pipe sizing specifications for IBC's tankless water heater. Refer to other
manufacturers' manuals for correct sizing of pipes.
Note
For pipe sizing, refer to the Installation manual of the water heater manufacturer for boiler
head loss specifications.
Tankless Water Heater Head Loss - Superflow SFT 199
Flow rate (gpm)
3
4
5
Head loss @ flow (ft)
14
23
33
Table 11 Tankless water heater head loss: SFT 199
30
Section: Installation
Connection to the space heating circuit through a drinkable water system as shown may be prohibited
by local code.
Non-ferrous pump (sized for combined head loss of boiler/water heater, air handler -
interconnecting piping)
Check valve (may be built into pump)
Potable water expansion tank
Filter required where contaminants are present in the supply water
Figure 32 Basic installation with tankless water heater
Note
The SFT 199 maximum water temperature is 149°F ( 65°C ). Ensure that this is hot enough to
meet the heating requirements of the space being heated.
If piped correctly, DHW takes priority over space heating. When the appliance detects reduced water
temperature (that is, a call for DHW), the system will reduce the fan speed.
31
2.5 Connecting the appliance to a tankless water heater
2.6 Electrical connections
All electrical wiring to the boiler (including grounding) must conform to local electrical codes and/or
the National Electrical Code, ANS/NFPA No. 70 – latest edition, or the Canadian Electrical Code,
C22.1 - Part 1. In addition, you should refer to the boiler's installation manual.
The control board diagram below shows the various wiring connections such as the thermostat,
accessories, heat pump, and external pump.
Figure 33 Air handling appliance - electrical wiring diagram
32
Section: Installation
2.6.1 Wiring of the external pump and 120VAC line
You will need to use a 3 mm flat-bladed screwdriver to wire the external pump and the 120VAC line.
Insert a wire into the connector (at the front of the block). Inserting a screwdriver into the connector
releases the wire.
Figure 34 : Inserting a wire for an external pump and
120VAC line
Figure 35 : Removing a wire
2.6.2 Connecting line voltage - examples for different scenarios
This section provides diagrams for wiring a 120 VAC / 15 amp supply, external Pump – maximum 4
Amps 120 Volts, thermostat connections – Standard TH or OpenTherm (communications thermostat
protocol), external pump control, boiler connection for a call for heat, and connection to an AC or HP
appliance (air handling appliance side only).
33
2.6.1 Wiring of the external pump and 120VAC line
An internal time delay is preset, enabling the W2 blower speed after a preset period of time. A
jumper between W1 and W2 will initialize this speed without the time delay.
Figure 36 Single-stage heating, on-demand heat source
34
Section: Installation
An internal time delay is preset enabling the W2 blower speed after a preset period of time. A
jumper between W1 and W2 will initialize this speed without the time delay.
Optional
Figure 37 Single-stage heating with fan control, on-demand heat source
35
2.6.2 Connecting line voltage - examples for different scenarios
An internal time delay is preset enabling the W2 blower speed after a preset time period. A
jumper between W1 and W2 will initialize this speed without the time delay.
Optional
Figure 38 Single-stage heating, single-stage cooling, fan control, on-demand heat source
36
Section: Installation
An internal time delay is preset enabling the W2 blower speed after a preset duration of time. A
jumper between W1 and W2 will initialize this speed without the time delay.
Optional
Not used
Reversing valve (O or B) is selectable via the blower control interface.
Figure 39 Single-stage heat pump, fan control, on-demand heat source backup
37
2.6.2 Connecting line voltage - examples for different scenarios
Required if boiler does not have an integral pump.
Dry contact from air handler to boiler / enables call for heating
Figure 40 Single-stage heating from boiler, primary/secondary piping
38
Section: Installation
Required if boiler does not have an integral pump.
Dry contact from air handler to boiler / enables call for heat
Figure 41 Single-stage heating with fan control, boiler with primary/secondary piping
39
2.6.2 Connecting line voltage - examples for different scenarios
Required if boiler does not have an integral pump.
Dry contact from air handler to boiler / enables call for heat.
Figure 42 Single-stage heating, single-stage cooling, boiler with primary/secondary piping
40
Section: Installation
Required if boiler does not have an integral pump.
Dry contact from air handler to boiler / enables call for heat.
Timer must close TT to create a boiler-on command in the HP mode. This time delay is
initialized after establishing a W1 signal.
Reversing valve (O or B) is selectable via the blower control interface.
Not used.
Figure 43 Single-stage heat pump with boiler backup - primary/secondary piping
41
2.6.2 Connecting line voltage - examples for different scenarios
Required if boiler does not have an integral pump.
Dry contact from air handler to boiler / enables call for heat.
Reversing valve (O or B) is selectable via the blower control interface
W1 = heat pump, W2 = energize TT for boiler - removes heat pump
Not used
Figure 44 Single-stage heat pump with boiler backup, primary/secondary piping (2-stage thermostat)
42
Section: Installation
Required if boiler does not have an integral pump.
Dry contact from air handler to boiler / enables call for heat
W1 = boiler + low fan, W2 = boiler + high fan
Not used
Figure 45 Two-stage cooling with boiler heating (2-stage thermostat)
43
2.6.2 Connecting line voltage - examples for different scenarios
Required if boiler does not have an integral pump
Dry contact from air handler to boiler / enables call for heat
W1 = boiler + low fan, W2 = boiler + high fan
Not used
Figure 46 Single-stage cooling with boiler heating (2-stage thermostat)
44
Section: Installation
Once installation of the appliance is completed, and before operating the appliance, review the
following guidelines:
Checklists for electrical conditions, ducting and water connections
Default settings
Default fan speed settings
Sequence of operation
LED status indicators.
Operating the appliance with a mobile app
Using the app to view the appliance's settings
3.1 Checklist for electrical conditions, ducting and water
connections
Checking electrical conditions
Check
Ensure the power supply to the air handling appliance is 120V 15A circuit.
The appliance is not designed to work with 208-240V. If connected to 208-240V, electrical
damage will result, and the appliance or components may need to be replaced.
□
Check all line voltage electrical connections to ensure all connections are correct and tight. □
Check thermostat connections.
□
Thermostat is in a suitable location.
□
Checking supply and return water piping connections
Check
All connections are pressure tested and leak-free.
□
All piping flushed to ensure all air is removed.
□
Check valve is installed and the external pump is flowing in the correct direction.
□
Boiler / water heater is installed as per the manufacturer's instructions and is safe to operate. □
Checking ducting connections
Check
All connections are pressure tested and leak-free.
□
All duct work is sized correctly and joints are sealed.
□
All supply air dampers and registers are opened.
□
Duct insulation is installed and sealed as required.
□
Inspect the filter, return air ducting and registers to ensure free air movement.
□
Checking boiler / water heater settings
Check
Ensure the water temperature to the heating coil is sufficient to meet the heating
demands of the space.
□
3.2 Default settings
The following table shows the factory-default settings.
Default - Basic Settings
Heating Mode
1 stage
Cooling Mode
2 stage
Boiler Heating
1 stage and 2 stage
Temperature
°F
Pump Enable
On
Tankless Mode
Off
3.3 Default fan speed settings
For fan speed defaults and ranges, see the table below:
AHU - Fan speed Operation
W1
Heating stage 1 = 600 CFM
Range 300-800
W2
Heating stage 2 = 800 CFM
Range 300 – 1000 (must be ≥ than heating stage 1)
Y1
Cooling stage 1 = 700 CFM
Range 300 – 800
Y2
Cooling stage 2 = 1000 CFM
Range 300-1000 (must be ≥ than cooling stage 1)
G
Fan on speed = 400 CFM
Range 150-1000
Note
For safety reasons, a switch is built into the door. The switch prevents the fan from
operating if the door is not installed. With the door removed, the appliance's control board
will remain powered, enabling programming of the mobile app.
46
Section: Operation
3.4 Sequence of operation
3.4.1 Heating Mode
Upon a call for heat from the thermostat:
R to W1 or W2 is energized.
The External Pump relay is closed, energizing the external pump if connected (required when
connecting the air handling appliance to a tankless water heater or SL series boiler).
The TT (boiler on Heat 1) contacts close creating a call for heat at the boiler.
The fan is energized and:
Operates at W1 or W2 speed.
Fan speed ramps up to the maximum value of its W1 range value or W2 range value.
When a demand for heat is satisfied, the system:
Opens TT (or Heat 1) to remove the boiler's call for heat.
Continues to operate the fan for 45 seconds; also operates the pump contacts for 30 seconds.
3.4.2 Cooling Mode
Upon a call for cooling from the thermostat:
R to Y1 or Y2 is energized
The fan is energized and:
Operates at Y1 or Y2 speed.
Energizes the O/B terminal if there is a heat pump.
When cooling demand is satisfied, the air handling appliance:
Opens the compressor S1 and /or S2 contacts, and de-energizes O/B if there is a heat pump.
The fan continues to operate for 45 seconds.
3.4.3 Heat Pump Mode
Upon a call for heat from a heat pump:
R to Y1 or Y2 is energized.
R to O/B remains de-energized.
The fan is energized and:
Operates at Y1 or Y2 speed.
Operates a low speed for 60 seconds.
47
3.4 Sequence of operation
When heating demand is satisfied:
The air handling appliance opens the compressor S1 and /or S2 contacts.
The fan continues to operate for 45 seconds.
3.4.4 Humidification Mode
Upon a call for humidification from the thermostat:
G to W is energized.
The humidifier's contacts (24V output) will close.
3.4.5 De-humidification Mode
Upon a call for de-humidification from the thermostat:
G to W or Y is energized.
The de-humidifier's contacts (24V output) will close.
3.4.6 Freeze Protection Mode
Freeze protection mode monitors the return air temperature into the air handling appliance.
If the internal return air temperature sensor detects a return air temperature below 41°F, the air
handling appliance will energize the fan, the pump contacts, and the TT (boiler) contacts to create a
call for heat. When the return air temperature increases to 46°F or more the air handling appliance
will turn off the fan, TT (boiler) contacts, and pump contacts.
If the internal return air temperature sensor detects a return air temperature below 35°F, the air
handling appliance will turn off the fan, and continue to energize TT (boiler) contacts and pump
contacts.
48
Section: Operation
3.5 LED status indicators
The appliance displays four LED indicators, each representing an operating status.
POWER (Green background)
FAULT (Red
background)
HEAT (Green
background)
COOL(Green
background)
State
LED(s)
Description
Standby
FAULT
HEAT
COOL
Each LED blinks on and off in a
“chasing” sequence.
Heating
HEAT
LED displays a steady state.
Cooling
COOL
LED displays a steady state.
Fan only (G)
HEAT
COOL
Short synchronized flashing.
Warning
FAULT
LED flashes on. The appliance will
continue to operate; however, certain
operations may not function correctly.
Fault
FAULT
LED displays a steady state. The
appliance will not service heat or cooling
calls.
Table 12 Status indicators
Built-in diagnostics feature
The appliance contains a built-in diagnostic feature that enables you to obtain information on settings,
faults, and errors.
To view diagnostics:
1. Insert a USB stick into the controller, wait approximately 10 seconds, and then remove the USB
stick.
The controller generates a text file that contains all the settings and any faults or warnings that
are present on the appliance.
2. To view the text file, insert the USB stick into any computer, and open the generated text file
with “Wordpad” or a similar program.
The file name will be: “AHUxxxxx.TXT”, where “xxxxx” is the serial number of the controller.
49
3.5 LED status indicators
3.6 Operating the appliance with a mobile app
All air handlers come configured with default factory settings. IBC's free mobile app "IBCconnect"
(Android or iOS app) enables users to monitor and adjust default settings in a single air handling
appliance. This app is compatible only with Android and iOS devices and with the IBC air handler.
Note
Alternatively, it's possible to change settings using a USB stick with a custom
configuration text file. Using a USB with a custom text file is the best approach for
configuring multiple air handlers that will use the same settings (see Configuring settings
and parameters via a USB text file on page 57).
To connect, the following setup steps need to be completed:
1. Loading the app from the app store (Google Play and Apple store).
2. Using the app to connect to IBC's AHU WiFi.
3. Programming the air handling unit with the app.
3.6.1 Loading IBCconnect
Loading the app will depend on whether you are using an Android or Apple iPhone device.
3.6.1.1 Loading IBCconnect from the Android Google Play Store
1. In the Google Play Store search box, enter IBC Technologies (case sensitive).
2. Select the
icon, and tap Install. To verify that the app has loaded, see the icon
in the list with existing apps.
For next steps, see Using the app to connect to IBC's AHU WiFi on page 51.
3.6.1.2 Loading IBCconnect from the iOS Apple Store
1. In the iOs Apple Store search box, enter IBC Technologies (case sensitive).
2. Select the
icon, and tap Install.
50
Section: Operation
Once IBCconnect is installed on your device, you need to change some of the settings. This may
vary slightly depending on the device and the version of iOS your device is using.
3. In the main iPhone Settings, select Cellular.
4. Locate IBCconnect under Cellular Data, and set to Off.
Optionally, in the main iPhone settings, select IBCconnect app, and then go to Siri & Search and set
Search & Siri Suggestions to Off. See the next section for WiFi connection.
3.6.2 Using the app to connect to IBC's AHU WiFi
Once you've loaded the IBCconnect app onto your mobile or tablet, you will need to establish a
connection between the IBCconnect app and the IBC air handler. IBC's AHU has a WiFi access point
built into it. Your device needs to be connected to IBC's AHU WiFi point before the app can be used to
control or monitor IBC's air handler. This is done through the app's WiFi network settings.
3.6.2.1 Connecting an Android device
The following instructions may vary slightly depending on the device being used.
1. Open the IBCconnect app.
The WiFi connection of the device is displayed. If the WiFi connection is not IBC-AHU, a WiFi
SETTINGS button is displayed. Tap the WiFi SETTINGS button.
The WiFi network screen appears. The IBC-AHU will appear in the device’s list of WiFi available
networks as "IBC-AHU-xxxxx", where "xxxxx" is the serial number of the controller in the IBC-
AHU.
51
3.6.2 Using the app to connect to IBC's AHU WiFi
If there are multiple IBC-AHUs in the area, the appliance with the strongest signal will likely
be the controller you want to connect to.
2. Select IBC-AHU-xxxxx.
3. The first time you connect, enter 1234567890 when prompted for a password.
Depending on the version of Android your device has, after a few seconds you may see a
warning, as shown below.
With the AHU cover off, the LEDs on the circuit board will start blinking simultaneously in a
ON-OFF-ON-OFF-OFF-OFF pattern when connected.
4. Tap the device's back button to return to the IBCconnect app, then tap GET STARTED to
access the Home page to start adjusting settings.
3.6.2.2 Connecting an iOs device
The IBCconnect app requires an IBC-AHU WiFi connection. You need to change some app settings
after installation.
1. In the main iPhone settings, select Cellular.
2. Scroll down to IBCconnect (under Cellular Data), and set to Off.
3. Navigate to the device’s WiFi Settings.
4. Connect to the IBC-AHU WiFi.
52
Section: Operation
The IBC-AHU will appear in the device’s list of WiFi Access Points as “IBC-AHU-xxxxx”, where
“xxxxx” is the serial number of the controller in the IBC-AHU. If there are multiple IBC-AHU’s in
the area, the appliance with the strongest signal will likely be the controller you want to connect
to.
5. Select IBC-AHU-xxxxx.
6. The first time you connect, enter 1234567890 when prompted for a password.
With the AHU cover off, the LEDs on the circuit board will start blinking simultaneously in a ON-
OFF-ON-OFF-OFF-OFF pattern when connected.
7. Exit from the "Setting" screen and open the IBCconnect app again.
8. Check your device is connected to the IBC-AHU-xxxxx WiFi connection. This will display the
landing page.
The landing page that appears after starting IBCconnect will depend on the device and whether you have
connected to IBC's AHU WiFi.
3.6.3 Programming the air handling unit using the app
The IBC factory pre-programs the name of the model (AHU 800, AHU 1200 or AHU 1600) in the
appliance. However, you will need to use the app to set the heating and cooling mode and to change
default settings.
53
3.6.3 Programming the air handling unit using the app
To set the mode using the IBCconnect app:
1. Tap
(menu icon), and select Basic Settings.
2. Set the Heat Mode and Cool Mode.
3. To make adjustments to settings, tap
(menu), and then select Advanced Settings.
We recommend setting "Tankless" to "On" in most applications for optimal performance.
54
Section: Operation
4. Configure settings as desired (or accept defaults), and then tap
(SAVE).
5. To check the model and mode, go to
(menu) and select About.
3.6.4 Using the app to view the AHU's information
Once the device is connected to IBC's AHU WiFi, the following screens will display:
Figure 47 : Android mobile showing message device is
connected to WiFi
Figure 48 : iOs mobile showing message device is
connected to WiFi
Do not check the "Don’t ask again for this network” if prompted; the device will likely default to “NO” for
staying connected if this is selected.
55
3.6.4 Using the app to view the AHU's information
If you want to connect to another air handling appliance, on the landing page tap the
WiFi SETTINGS button, and choose the required AHU WiFi connection. To return to
the landing page, exit the app, and then reopen it.
1. Tap the GET STARTED button.
An Android prompt may request that you make your device's location discoverable.
2. Tap Allow and then OK to grant permission.
The AHU app Status screen is displayed showing the air handler's factory default settings. You can
navigate to the Home page, and begin adjusting settings.
56
Section: Operation
Note: If device is not maintaining a connection with IBC's AHU WiFi
If the IBCconnect app is unable to maintain a connection to the IBC AHU WiFi, the
IBCConnect app footer will show an "X" icon above WiFi. It is likely the device is attempting
to perform uploads in the background. To prevent cell phone data and WiFi conflict:
1. Remove the IBC AHU WiFi connection from the device.
2. Go to the device’s WiFi Setting.
3. Press and hold the IBC-AHU-xxxxx entry.
4. Tap Forget Network.
5. Place the device in "Airplane Mode".
6. Reconnect the device to the IBC AHU WiFi by selecting the "IBC-AHU-xxxxx" from
the list of access points. Ensure that the WiFi reconnect option is disabled.
7. Start the IBCconnect app again.
3.7 Configuring settings and parameters via a USB text
file
You can change and customize the default settings in one or more air handlers via a single .config
ASCII text file labeled "ahusetup.cfg". The custom text file can be placed on a USB stick and inserted
into each air handling appliance. To obtain a custom text file, contact IBC.
57
3.7 Configuring settings and parameters via a USB text file
4.0 Service and maintenance
The IBC air handling appliance is designed for durability and easy access to the main components:
control board, fan assembly, hot water coil assembly, and filter. Over time, components such as
sensors may require replacing and servicing. Note that failure to use the correct procedures or parts
could result in unsafe operation.
4.1 Maintenance checklist for owners
Owners should arrange follow-up inspections and simple maintenance procedures according to IBC's
suggested servicing guidelines below.
Maintenance Required
Frequency
Check
Check and replace filter as needed. Replace the filter monthly.
Inspect system for unusual noises. Call your local heating contractor
for service if needed
Monthly
□
Have your local heating contractor inspect the system annually.
This service should include the heat appliance connected to the Air
Handling appliance.
Annually
□
4.2 Maintenance for the heating contractor
4.2.1 Removing the fan assembly
1. Remove the two screws from the front
cover, and set aside.
2. Remove the two bolts from the fan
assembly plate.
3. Remove the two Molex plugs from the
control board.
4.
Detach the cable and grommet.
5.
Slide out the fan assembly.
Note
When you install the replacement fan
assembly:
Ensure that you install the fan
assembly, so that the fan cables
can reach the control board, that
is, the cables are positioned
towards the front left of the fan
assembly.
Reinsert the split fan grommet
correctly. See images below.
Note large and small holes.
60
Section: Service and maintenance
4.2.2 Replacing the hot water coil appliance
1.
Remove the two screws from the front cover, and
set aside.
2. Carefully unclip the three
cables, and lean them away
from the hot water coil.
3.
Remove the nuts and bolts.
4.
Slide out the fan coil.
61
4.2.2 Replacing the hot water coil appliance
4.3 Replacing the control board
After you replace the control board in the appliance, you will need to program some settings using
the IBCconnect app.
To replace the control board:
1. Unplug all the connectors from the control board.
2. Remove the four screws securing the control board to the appliance, and set them aside for
the replacement board. In the next step, you will separate the humidity sensor strip from the
main replacement control board using a scoring knife.
3. Place the replacement board on a flat surface, and using the knife, score a straight line
between the main board and the humidity sensor strip. The strip should snap off by hand,
without force.
Figure 49 Separating the humidity sensor strip from the main replacement board
4. Secure the replacement board in place with the four screws.
5. Insert the humidity sensor strip into the side slit of the black insulation foam, until the 5 pins
engage in the board's 5-pin connector (see below), and secure the strip with a plastic zip tie.
Figure 50 Inserting the humidity sensor strip and securing with a cable tie
62
Section: Service and maintenance
6. Plug in all connectors (temperature sensor from the coil, connector for the transformer, connector
for fan power, connector for fan control, connector to the door switch, and the ground wire
connector).
Now you must use the air handler app (IBCconnect to program the model name, mode, and
change default settings (if desired).
7. To set the model, mode, and to configure settings:
a. Open the IBCconnect app on your phone.
b. Go to Configure AHU.
c. From the AHU Model dropdown, select the model.
63
4.3 Replacing the control board
After saving, the AHU controller will restart.
e. Close the app, and then open it again.
For information on setting the cooling and heating mode and other settings, see Programming
the air handling unit using the app on page 53.
4.4 Temperature sensors
The resistance of the temperature sensors varies inversely with temperature. You need to measure
the temperature of the sensed environment compared with the value from the measurement of the
resistance (obtained by connecting a good quality test meter capable of measuring up to 100 kΩ at
the controller end of the sensor lead).
To obtain a resistance reading, remove power to the boiler. Remove the wire leads by disconnecting
their respective Molex connectors from the sensor(s) in question. Place multi-meter probes into the
sensor’s female Molex connector socket. Do not apply voltage to the sensor - damage may result.
64
Section: Service and maintenance
Ω – Ohm
Temp. °F/°C
Resist.
Ω – Ohm
0 / -18
85,362
100 / 38
5,828
5 / -15
72,918
105 / 41
5,210
10 / -12
62,465
110 / 43
4,665
15 / -9
53,658
115 / 46
4,184
20 / -7
42,218
120 / 49
3,760
25 / -4
39,913
125 / 52
3,383
30 / -1
34,558
130 / 54
3,050
35 / 2
29,996
135 / 57
2,754
40 / 4
26,099
140 / 60
2,490
45 / 7
22,763
145 / 63
2,255
50 / 10
19,900
150 / 66
2,045
55 / 13
17,436
155 / 68
1,857
60 / 16
15,311
160 / 71
1,689
65 / 18
13,474
165 / 74
1,538
70 / 21
11,883
170 / 77
1,403
75 / 24
10,501
175 / 79
1,281
80 / 27
9,299
180 / 82
1,172
85 / 29
8,250
185 / 85
1,073
90 / 35
7,334
190 / 88
983
95 / 35
6,532
195 / 91
903
Table 13 10K Ω Temperature sensor resistance values
65
4.4 Temperature sensors
This section includes a table of warning and error messages that may appear on the appliance as well
faults that may appear on the air handling appliance app.
A problem that does not prevent the operation of the air handler is declared as a "warning". A problem
that prevents the appliance from operating is declared as an "error" and the appliance is shut down.
5.1 Measuring voltage on AHU boards
The control voltage transformer is not bonded to the AHU cabinet. When measuring the voltage supplied
to the individual control circuit, you must reference the common post of the circuit. If you measure to
ground or to another common terminal, misleading readings of approximately 14V will occur.
To test for nominal 24V, reference the adjacent COM connection. For example, to test voltage at
Compressor S1 terminal, measure for VAC between Compressor COM and Compressor S1.
5.2 Pump not energized
If the pump is not energizing:
In the IBCconnect app, go to Advanced Settings, and check that Pump Enabled is set to "on".
In the IBCconnect app, go to Basic Settings, and check that Heat Mode is not set to "Heat
Pump": During Stage 1 heat pump heating, the AHU pump is not energized by design, to avoid
interfering with circulation through the heat pump. AHU pump is energized at Stage 2 call for
heat.
Check the AHU board for blown pump fuse—the only fuse rated for 10A.
5.3 Fault Codes
Fault Code/Error Message
Description
Possible Fix
Inlet Temperature Sensor
Sensor not connected or
faulty.
Check the sensor. For resistance
reading, see Table 13.
Outlet Temperature Sensor
Sensor not connected or
faulty.
Check the sensor. For resistance
reading, see Table 13.
Aux Air In Temperature Sensor
Sensor not connected or
faulty.
Check the sensor. For resistance
reading, see Table 13.
Air Out Temperature Sensor
Sensor not connected or
faulty.
Check the sensor. For resistance
reading, see Table 13.
Cool Air Temperature Sensor
Sensor not connected or
faulty.
Check the sensor. For resistance
reading, see Table 13.
A/C Temperature Sensor
Sensor not connected or
faulty.
Check the sensor. For resistance
reading, see Table 13.
Fault Code/Error Message
Description
Possible Fix
Dehumidifier Temperature Sensor
Sensor not connected or
faulty.
Check the sensor. For resistance
reading, see Table 13.
Outdoor Temperature Sensor
Sensor not connected or
faulty.
Check the sensor. For resistance
reading, see Table 13.
Air In Temp Sensor (Probe)
Sensor not connected or
faulty.
Check the sensor. For resistance
reading, see Table 13.
Barometer
Probe not connected or
device is faulty.
Check the probe.
Humidistat
Probe not connected or
device is faulty.
Check the probe.
Door Open / No Fan Signal
Service door is open or fan
fault.
Check door or if door
switch is faulty.
Check if harness is
disconnected.
Check if fan is turning.
No Fan RPM
No rotation of the fan is
detected.
Check if fan is turning or
disconnected. Check the fuse.
Use a meter to check 120V is
present on the external connection
to the board. If 10V is not coming
from the fan it is not receiving
120V. Check the 10V signal on
the web app.
A/C Freeze
Freezing detected in the A/C
coil.
The coil needs to defrost. Refer to
the manual for the air conditioner
for details on how to prevent
freezing.
Dehumidifier Freeze
Freezing detected in the
dehumidifier appliance.
The coil needs to defrost. Refer to
the manual for the dehumidifier for
details on how to prevent freezing.
Thermostat Fault
Simultaneous heating and
cooling calls detected
Check that the heating lead has
not been crossed with the cooling
lead from the Nest thermostat.
There is also a known bug related
to some thermostat models that
are over 3 years old: the backing
plate allows a short to signal a call
for cooling.
RTOS Fault 1
Software fault
Contact IBC Technical Support
for software upgrade.
68
Section: Find troubleshooting for IBC Technologies' air handling appliances.
Fault Code/Error Message
Description
Possible Fix
RTOS Fault 2
Software fault
Contact IBC Technical Support
for software upgrade.
Table 14 Warnings and error messages shown on the air handler unit app
69
5.0 Troubleshooting
Air handling appliance - parts diagram
70
Section: Find troubleshooting for IBC Technologies' air handling appliances.
Door assembly - AHU 800
P- 1019
Door assembly - AHU 1200
P-1022
Door assembly - AHU 1600
110
P-1001
Air filter size 25 x 16 x 1 - AHU 800
Air filter size 25 x 20 x 1 - AHU 1200, - AHU 1200
120
P-1008
Door switch, SPST-NO. 15A 125V
120
Wiring harness
130
P-1011
Supply water temperature sensor
140
P-1012
Temperature sensor and grommet
150
P-1011
Return water temperature sensor
160
P-1003
Hot water coil 2-ton appliance - AHU 800
P-1020
Hot water coil 3-ton appliance - AHU 1200
P-1022
Hot water coil 4-ton appliance - AHU 1600
170
P-1005
Transformer 40VA 120V
180
P-1001
Control board
190
P-1007
Filter bracket wing nuts x 4
200
Air filter lower bracket
210
Air filter upper bracket
220
P-1017
Coil hex bolts, hex nut, washer x 2
Fan plate hex bolts, washer x 2
230
P-1004
P-1021
P- 1024
Fan and motor assembly - AHU 800
Fan and motor assembly - AHU 1200
Fan and motor assembly - AHU 1600
240
Fan wiring grommet
250
P-1009
Sensor wiring harness
260
P-1017
Door thumb screws x 2
* P-1017 = Part of the hardware kit
71
Air handling appliance - parts diagram
R0 (June 2019) Initial release.
R1 (July 2019) Updated wiring diagrams and made minor edits.
R2 (October 2019) Updated wiring diagrams, added LED status indicators, and information on
using a text file to modify settings in multiple air handlers.
R3 (November) Added table of basic default settings and other minor changes.
R4 (May) Introduction of the AHU 1200 and AHU 1600 models
CAN IBC Technologies Inc.
USA IBC Technologies USA Inc
A 8015 North Fraser Way
A 1702 Taylor’s Lane
Burnaby, BC Canada V5J 5M8
Cinnaminson NJ 08077 USA
T 604-877-0277
T 856-877-0544