Cordex® 24-400W Rectifier Shelf System Manual
NOTE: Photographs contained in this manual are for illustrative purposes only. These photographs may
not match your installation.
NOTE: Operator is cautioned to review the drawings and illustrations contained in this manual before
proceeding. If there are questions regarding the safe operation of this powering system, contact Alpha
Technologies or your nearest Alpha representative.
NOTE: Alpha shall not be held liable for any damage or injury involving its enclosures, power supplies,
generators, batteries, or other hardware if used or operated in any manner or subject to any condition
inconsistent with its intended purpose, or if installed or operated in an unapproved manner, or
improperly maintained.
��������������������������������������������������
�
������������������������������
������������������������������
Copyright
Copyright © 2020 Alpha Technologies Ltd. All rights reserved. Alpha is a registered trademark of Alpha
Technologies.
No part of this documentation shall be reproduced, stored in a retrieval system, translated, transcribed,
or transmitted in any form or by any means manual, electric, electronic, electromechanical, chemical,
optical, or other-wise without prior explicit written permission from Alpha Technologies.
This document, the software it describes, and the information and know-how they contain constitute the
proprietary, confidential and valuable trade secret information of Alpha Technologies, and may not be
used for any unauthorized purpose, or disclosed to others without the prior written permission of Alpha
Technologies.
The material contained in this document is for information only and is subject to change without notice.
While reasonable efforts have been made in the preparation of this document to assure its accuracy,
Alpha Technologies assumes no liability resulting from errors or omissions in this document, or from the
use of the information contained herein. Alpha Technologies reserves the right to make changes in the
product design without reservation and without notification to its users.
List of Figures...............................................................................................................................................4
List of Tables.................................................................................................................................................5
1. Safety....................................................................................................................................................... 6
2. Introduction.............................................................................................................................................9
2.1. Scope..............................................................................................................................................9
2.2. Product Overview...........................................................................................................................9
3. Features.................................................................................................................................................11
3.1. Rectifier.........................................................................................................................................11
3.2. Overview of the CXCi HP............................................................................................................ 14
3.3. Overview of the CXCi+................................................................................................................ 16
3.4. Controller Input and Output......................................................................................................... 18
4. Inspection..............................................................................................................................................20
5. Installation.............................................................................................................................................21
5.1. Safety Precautions....................................................................................................................... 21
5.2. Shelf Preparation/Mounting..........................................................................................................21
5.3. Module Insertion and Removal....................................................................................................22
5.4. Removing a CXRC Rectifier........................................................................................................ 22
5.5. Removing the CXCi HP and CXCi+ Controller............................................................................22
6. Wiring and Connections......................................................................................................................24
6.1. Safety Precautions....................................................................................................................... 24
6.2. Tools Required............................................................................................................................. 24
6.3. Power System Chassis Ground and DC Ground........................................................................ 24
6.4. AC Feeder Protection/Sizing........................................................................................................24
6.5. AC Input....................................................................................................................................... 25
6.6. Calculating Output Wire Size Requirements............................................................................... 25
6.7. DC Output.................................................................................................................................... 26
6.8. CAN Ports.................................................................................................................................... 27
6.9. Network Connection and Remote Communications via the Controller........................................27
6.10. Signal Wiring Connections.........................................................................................................27
7. Operation...............................................................................................................................................31
7.1. Main Rectifier States....................................................................................................................31
7.2. Main Rectifier Modes................................................................................................................... 32
Page 2
9400021-J0 Rev B
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide
7.3. CAN Bus Communication............................................................................................................ 33
7.4. Factory Ranges and Defaults...................................................................................................... 33
8. System Startup..................................................................................................................................... 34
8.1. Check System Connections.........................................................................................................34
8.2. Verify AC and Power the Shelf....................................................................................................34
8.3. Check Battery Polarity and Connect............................................................................................34
8.4. Controller Reset - CXCi+............................................................................................................. 34
8.5. Controller Reset - CXCi HP.........................................................................................................35
9. Maintenance.......................................................................................................................................... 36
9.1. Replacing a CXCi+ Controller......................................................................................................36
9.2. Replacing a CXCi HP Controller..................................................................................................38
10. Warranty and Service Information....................................................................................................39
11. Certification......................................................................................................................................... 40
12. Glossary...............................................................................................................................................41
13. Specifications......................................................................................................................................43
13.1. 2RU, 24-400W, 19", 4 Module System......................................................................................43
13.2. 2RU, 24-400W, 19", 5 Module System......................................................................................44
13.3. Cordex 24-400W Switched Mode Rectifier................................................................................45
13.4. CXCi HP Controller.................................................................................................................... 48
13.5. CXCi+ Controller........................................................................................................................ 50
9400021-J0 Rev B
Page 3
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide
List of Figures
Figure 1: Four Module System, 030-763-20-XXX......................................................................................10
Figure 2: Five Module System, 030-773-20-XXX...................................................................................... 10
Figure 3: Rectifier Front Panel...................................................................................................................11
Figure 4: CXCi HP Controller.....................................................................................................................14
Figure 5: In-Shelf Controller Dashboard Screens......................................................................................15
Figure 6: In-Shelf Controller Menu.............................................................................................................15
Figure 7: In-Shelf Controller Buttons..........................................................................................................16
Figure 8: Cordex CXCi+ model system controller front panel................................................................... 17
Figure 9: Packing Materials and Environmental Codes.............................................................................20
Figure 10: Digital Input Connection Method.............................................................................................. 29
Figure 11: Relay Connections.................................................................................................................... 30
Figure 12: Removing the CXCi HP............................................................................................................38
Page 4
9400021-J0 Rev B
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide
List of Tables
Table 1: In-Shelf Controller Full Menu....................................................................................................... 15
Table 2: Recommended AC Supply Configuration.....................................................................................25
Table 3: Wiring Connections for the CXCi Series of Controllers................................................................27
Table 4: Voltage Level Definitions for Digital Inputs...................................................................................30
Table 5: Output Voltage Modes..................................................................................................................32
Table 6: Output Current/Power Modes.......................................................................................................32
Table 7: Factory Ranges and Defaults.......................................................................................................33
Table 8: Sample Maintenance Log.............................................................................................................36
Table 9: Specifications: 24-400W 19", 4 Module System.......................................................................... 43
Table 10: Specifications: 24-400W 19”, 5 Module System........................................................................ 44
Table 11: Specifications: Cordex 24-400W, Switched Mode Rectifier........................................................45
Table 12: Specifications: CXCi HP Controller............................................................................................ 48
Table 13: Specifications: CXCi+ Controller................................................................................................ 50
9400021-J0 Rev B
Page 5
SAVE THESE INSTRUCTIONS: This manual contains important safety instructions that must be followed
during the installation, servicing, and maintenance of the product. Keep it in a safe place. Review
the drawings and illustrations contained in this manual before proceeding. If there are any questions
regarding the safe installation or operation of this product, contact Alpha Technologies or the nearest
Alpha representative.
Safety Wording/Symbols
To reduce the risk of injury or death, and to ensure the continued safe operation of this product, the
following symbols have been placed throughout this manual. Where these symbols appear, use extra
care and attention.
Attention: The use of attention indicates specific regulatory/code requirements that may affect the
placement of equipment and /or installation procedures.
Note: Notes provide additional information to help complete a specific task or procedure.
CAUTION: Cautions indicate safety information intended to PREVENT DAMAGE to material or
equipment.
Warning: Warnings present safety information to PREVENT INJURY OR DEATH to personnel.
Note: HOT! The use of Hot presents safety information to PREVENT BURNS to the technician or
user.
General Warning and Cautions
Warning:
You must read and understand the following warnings before installing the system and its components.
Failure to do so could result in personal injury or death.
• Read and follow all instructions included in this manual.
• Only trained personnel are qualified to install or replace this equipment and its components.
• Use proper lifting techniques whenever handling equipment, parts, or batteries.
• To be installed in a restricted access location that is inaccessible to the general public.
Electrical Safety
Warning:
Hazardous voltages are present at the input of power systems. The DC output from some rectifiers and
batteries can have high voltage and high short-circuit current capacity that may cause severe burns and
electrical arcing.
Before working with any live battery or power system, follow these precautions:
Page 6
9400021-J0 Rev B
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 1 - Safety
• Remove all metallic jewelry, such as watches, rings, metal rimmed glasses, or necklaces.
• Wear safety glasses with side shields at all times during the installation.
• Use OSHA approved insulated hand tools. Do not rest tools on top of batteries.
Warning:
Lethal voltages are present within the power system. Always assume that an electrical connection or
conductor is energized. Check the circuit with a voltmeter with respect to the grounded portion of the
enclosure (both AC and DC) before performing any installation or removal procedure.
• Do not work alone under hazardous conditions.
• A licensed electrician is required to install permanently wired equipment. Input voltages can range
up to 240Vac. Ensure that the utility power is disconnected and locked out before performing any
installation or removal procedure.
• Ensure that no liquids or wet clothes come into contact with internal components.
• Hazardous electrically live parts inside this unit are energized from the batteries even when the AC
input power is disconnected.
• The enclosure which contains the DC or AC power system along with customer installed
equipment must remain locked at all times, except when authorized service personnel are present.
• Always assume electrical connections or conductors are live. Turn off all circuit breakers and
double-check with a voltmeter before performing installation or maintenance.
• Place a warning label on the utility panel to warn emergency personnel that a reserve battery
source is present which will power the loads in a power outage condition or if the AC disconnect
breaker is turned off.
• At high ambient temperature conditions, the internal temperature can be hot so use caution when
touching the equipment.
Warning:
The intra-building ports (Ethernet, CAN, Alarm relays) of the equipment or subassembly are suitable for
connection to intra-building or unexposed wiring or cabling only. The intra-building ports of the equipment
or subassembly MUST NOT be metallically connected to interfaces that connect to the OSP or its wiring.
These interfaces are designed for use as intra-building interfaces only (Type 2 or Type 4 ports) and
require isolation from the exposed OSP cabling. The addition of Primary Protectors is not sufficient
protection in order to connect these interfaces metallically to OSP wiring.
Warning:
Controller Ethernet port is not designed to withstand lightning and AC power cross surges according to
the NEBS requirements in GR-1089-CORE. Ensure that any Ethernet cable used (not provided by Alpha)
does not exceed a maximum length of 6 meters.
Battery Safety
• Never transport an enclosure with batteries installed. Batteries must ONLY be installed after the
enclosure has been securely set in place at its permanent installation location. Transporting the
9400021-J0 Rev B
Page 7
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 1 - Safety
unit with batteries installed may cause a short circuit, fire, explosion, and/or damage to the battery
pack, enclosure and installed equipment.
• Servicing and connection of batteries must be performed by, or under the direct supervision of,
personnel knowledgeable of batteries and the required safety precautions.
• Batteries contain or emit chemicals known to cause cancer and birth defects or other reproductive
harm. Battery post terminals and related accessories contain lead and lead compounds. Wash
your hands after handling batteries.
Warning:
Follow battery manufacturer’s safety recommendations when working around battery systems. Do not
smoke or introduce an open flame when batteries (especially vented batteries) are charging. When
charging, batteries vent hydrogen gas, which can explode.
• Batteries are hazardous to the environment and should be disposed at a recycling facility. Consult
the battery manufacturer for recommended local authorized recyclers.
Page 8
9400021-J0 Rev B
This manual explains the installation, interconnection, and operation of the following Alpha Technologies
shelf systems:
• Cordex® 24-400W integrated 19" 2RU shelf system with up to 1600W output power and
distribution.
• Cordex® 24-400W integrated 19" 2RU shelf system with up to 2000W bulk output power.
• Operation of the Cordex® 24-400W rectifier.
2.2. Product Overview
A complete Cordex® rectifier system consists of a controller with one or more power modules
in a common shelf enclosure. The shelf has connections for AC inputs, DC output, and system
communications.
Cordex rectifier modules use a high frequency, switched mode conversion technique to provide a fully
regulated and isolated DC output from the AC mains. The rectifier input is wide range to allow use on
120/208/220/240Vac 50/60Hz electrical service.
Rectifier power modules are “hot swappable” meaning they can be inserted or removed from the shelf
without cutting power to or from the system or the load.
Additional power modules can be included with the system at the time of ordering or added after the shelf
has been installed.
The shelf rectifier system is designed to operate with the Alpha CXCi series of controllers (includes CXCi+
and CXCi HP), which is built into the rectifier system shelf.
All models of the controller allow the user to set up, control and monitor the entire power system and its
components from one central, easy-to-use source: your web browser. The CXCi series of controllers do
not have a touch screen display, system setup and management is performed exclusively with the web
interface. Details of controller operation are provided in the current version software manual.
The following figures are examples of:
1. Cordex 48-400W integrated 19" 2RU shelf system: four rectifiers, controller, and breaker
distribution.
2. Cordex 48-400W integrated 19" 2RU shelf system: five rectifiers and controller.
9400021-J0 Rev B
Page 9
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 2 - Introduction
Figure 1. Four Module System, 030-763-20-XXX
Figure 2. Five Module System, 030-773-20-XXX
Page 10
9400021-J0 Rev B
The Cordex® CXRC series of 24V 400W rectifier modules employ an advanced resonant power
conversion technology featuring high power conversion efficiency. All internal semiconductor devices
operate under “soft-switching” conditions and exhibit very low power loss. The reduced power loss leads
to lower thermal stress on the semiconductors and thus improves reliability.
Rectifier Front Panel
Figure 3. Rectifier Front Panel
LEDs
The front panel LEDs provide rectifier status summary and help to locate a specific module with the
controller.
OK
The top LED (green) is on when AC is within valid range and the rectifier is delivering power to the load.
The LED will flash (~2Hz) when AC is outside the nominal range – AC voltage is invalid if the AC Mains
Low or AC Mains High alarm is active. The LED turns off when AC has failed (or no AC power is present).
9400021-J0 Rev B
Page 11
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 3 - Features
Alarm
The bottom LED (red) is on continuously in the event of an active Module Fail alarm. The LED flashes
(~2Hz) when a minor alarm is detected. The LED remains off in the absence of an alarm.
LED Activity During “Locate Module” Command from Controller
When the “locate module” command has been received from the controller, the LEDs behave in a
distinctly different way so that the rectifier is easier to visually identify among adjacent rectifiers.
This state is entered when commanded via the controller. The LEDs flash in a distinct pattern repeating
every two seconds.
LED Activity During Firmware Upload
When a rectifier firmware upload is in progress, the LEDs behave in the same way as the locate module
command described above.
Mechanical
A thumbscrew is provided to secure the rectifier into the shelf. During normal operation the rectifier shall
be locked into position. A handle (or grip) is incorporated into the front panel to facilitate the removal of
the rectifier from the shelf. No special tools are required.
True Module Fail Alarm
The power modules have a “true” fail alarm. This provides a true indication of the power module’s ability
to source current. When the module’s output current drops below 2.5% of the rated output a low output
current condition is detected and the Module Fail detection circuit is activated. This circuit momentarily
ramps up the output voltage to determine if the module will source current. If no increase in current is
detected, the Module Fail alarm is activated. The module will test once every 60 seconds for the condition
until current is detected. Output voltage ramping will cease upon detection of current1. A minimum 2.5%
load is required to avoid the Ramp Test Fail alarm; this can typically be provided with the parallel system
battery. Activation of this alarm could indicate a failed module or a failed load.
Note: For rectifier systems without batteries (or with a very light load; below 2.5% of rated output)
it is recommended that the ramp test be disabled to avoid nuisance alarms. The Ramp Test feature is
enabled/disabled via the controller. Refer to the software manual for detailed information.
Heat Dissipation
Heat dissipation is achieved through natural (bottom to top) convection cooling
Over Temperature Protection
Each rectifier module is protected in the event of an excessive increase in temperature due to component
failure or cooling airflow blockage. During over temperature conditions, the rectifier limits the output power
as well as the output current. If temperature continues to increase, a shutdown of the rectifier is initiated.
The rectifier shall restart automatically if the temperature has returned to a safe level.
1. Under normal conditions, a battery connected to the output of the rectifier will draw current when the
voltage ramp occurs. Therefore the rectifier fail alarm will not be generated with a battery connected.
Page 12
9400021-J0 Rev B
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 3 - Features
Wide AC Range
A minor alarm is generated when the AC input voltage drops below specification. The unit will deliver
derated output power down to 60Vac.
•
Note: Output power is reduced linearly between 90Vac to 60Vac to 0% of the rated output
power. At a lower voltage the module will shutdown and will not restart until the AC is greater than
65Vac. For voltages between 276Vac and 320Vac, the rectifier may not be operational but shall not
suffer any damage.
AC Inrush/Transient Suppression
An external surge suppressor is not required at the AC input, modules are protected from input lightning
and transient surges in accordance with IEEE/ANSI C62.41 Category B3.
Soft Start
To eliminate an instantaneous demand on the AC source, a soft start feature is employed. Soft Start,
sometimes referred to as “current walk-in”, works by gradually (up to five seconds) ramping the current
limit up from zero to the actual or defined customer setting. The rectifier output voltage is ramped up from
the minimum voltage to the float voltage.
Start Delay
The rectifier modules are equipped with a delay timer in order to stagger start a series of modules to
prevent excessive loading of generators upon start up. The built-in timer delays the start up of the module
depending on the value selected (up to 120 seconds on CXCi and 250 seconds on CXCi HP) via the
controller. A minimum one-second delay is preset to allow charging of the input capacitors.
Current Limit/Short Circuit Protection
The current limit function determines the maximum output current limit of the rectifier module, regardless
of output voltage or power. Maximum output current is limited to a constant value down to short circuit
condition. Current limiting can be used to mate the rectifier output current ampacity to the needs of the
load and parallel battery to minimize excessive battery recharge current.
The rectifier will sustain a short circuit at the output terminals indefinitely. The maximum short circuit
current cannot exceed 105% of the rated full load current.
Power Limiting
Each rectifier module is designed to limit power output to the module specification. This enables more
current to be supplied at lower output voltages, and allows matching of output to the demand of constant
power loads, normally seen with telecom equipment.
This feature may also be used for a faster recharge of flooded batteries paralleled with the load.
Note: Current limiting overrides the power-limiting feature.
9400021-J0 Rev B
Page 13
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 3 - Features
High Voltage Shutdown (HVSD)
This feature provides protection to the load from over voltage conditions originating from the rectifiers.
It operates by shutting down the offending rectifier module when a high output voltage condition occurs.
Indication is through the red Alarm (Module Fail) LED. Modules will restart automatically; however, if more
than three over voltage conditions occur in one minute, the module will latch off and remain shut down
until it is reset.
Battery Eliminator Operation
Rectifier modules maintain all specifications (except where indicated) with or without a battery attached
in parallel to the output; however, if a battery or another module supplying DC voltage in parallel is not
present, there will be no monitoring or control activity if there is an AC power failure or input fuse failure.
3.2. Overview of the CXCi HP
The CXC HP in-shelf controllers have a small organic LED (OLED) display. This display shows 30
characters total (five lines high, six characters wide) and the controller has three navigation buttons and
one reset button.
The in-shelf display has three main operating modes: dashboard, menu and screen saver. After 20
minutes with no activity, the in-shelf controller goes into screen saver mode and the display shuts off.
From screen saver mode, press any of the three navigation buttons to re-activate the screen and enter
dashboard mode.
Figure 4. CXCi HP Controller
System Status LEDs
LED Screen
Forward and Back buttons
to scroll through menus
and Select button to execute
Ethernet Port
USB Port
Reset
Display
In dashboard mode, the in-shelf display shows the key operating parameters of a system. For example,
output voltage and load current. If more than one system is defined, you can cycle between systems
using the Forward and Back buttons. With multiple systems, you can specify a default system, which is
then displayed first.
Refer to the software manual for set up.
Page 14
9400021-J0 Rev B
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 3 - Features
The following figure below shows examples of the screens.
Figure 5. In-Shelf Controller Dashboard Screens
A C - 1 2 0
1 2 0 . 1 V
7 8 7 2 V A
8 0 2 3 V A
7 9 0 2 V A
D C - - 4 8
5 4 . 0 9 V
1 0 3 . 1 A
F l o a t
D C - - 2 4
2 6 . 9 2 V
3 7 . 2 3 A
System
Output Type
AC or DC
Nominal
Output
Voltage
Output Voltage
Phase 1 Output Power
Phase 2 Output Power
Phase 3 Output Power
Output Voltage
Output Current
Output Voltage
Output Current
Battery Mode
In-Shelf Display: Menu
From the OLED dashboard, use the Select button to enter a menu. From the menu, the OLED display
lets you execute a set of commands much like the LCD screens on the CXC HP.
When you enter a menu, the top item is highlighted. To go to another menu scroll through using the
Forward and Back buttons. To execute a highlighted menu item, press the Select button.
To exit a menu and return to the main OLED dashboard, scroll to the Back command, and then press the
Select button. The figure below shows an example of the menu screen. The following table provides a full
list of menus available via the in-shelf display.
Figure 6. In-Shelf Controller Menu
M e n u
A L C O
R e s e t
I P v 4
I P v 6
A L C O
Table 1. In-Shelf Controller Full Menu
Menu Label
Description
ALCO
Perform the alarm cut-off command
Reset
Perform a software reset of the controller
IPv4
Display the IPv4 address, subnet and gateway for this controller
IPv6
Display the IPv6 addresses assigned to this controller
9400021-J0 Rev B
Page 15
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 3 - Features
Table 1. In-Shelf Controller Full Menu (continued)
Menu Label
Description
Backup
Backup the controller application and configuration to a file on a USB device
Restore
Restore the controller application and configuration from a file on a USB device
Upgra...
Upgrade the controller application from a file on a USB device
OS Upg
Upgrade the controller’s operating system from a file on a USB device
Info
Display controller information including serial number, part number, software and hard-
ware version
Rotate
Rotate the in-shelf controller display information by 90 degrees
Back
Exit the menu and return to the OLED dashboard
In-Shelf Controller Buttons
The following figure shows how the buttons are interpreted.
Figure 7. In-Shelf Controller Buttons
M e n u
A L C O
R e s e t
I P v 4
I P v 6
A L C O
Back
Forward
Select
3.3. Overview of the CXCi+
The CXCi+ has a 4-digit display for monitoring system voltage (V) and current (A). A pushbutton toggle
switch allows the user to alternate the display reading.
Page 16
9400021-J0 Rev B
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 3 - Features
Figure 8. Cordex CXCi+ model system controller front panel
LCD Screen
Display Mode: pushbutton
toggle switch
Ethernet Port
Hard Reset (push once)
System Status LEDs
Soft Reset (push once)
Hold for three seconds
to reset IP address
LEDs
The controller has three LEDs to display the alarm status of the power system, controller progress and
status during startup, files transfers and lamp tests.
Alarm Conditions
The CXC illuminates the LED that corresponds to the alarm status. Only one LED is illuminated at a time
during alarm conditions:
• Green: OK, no alarms present
• Yellow: Minor alarm is present (no major alarms)
• Red: Major alarm is present.
Progress and Status Indication
The LEDs are also used in the following situations:
• Base unit validation: All three LEDs on simultaneously
• File transfer: Red LED illuminates when recovering from invalid firmware application
• Lamp Test: All three LEDs flash in sync for two seconds
Reset (CXCi+ only)
A reset button is located on the front panel for restarting the controller. During reset, the controller may
occasionally need to run a defragmentation cycle. This can be recognized by the LEDs cycling on
9400021-J0 Rev B
Page 17
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 3 - Features
the front panel. A full defragmentation may take up to 20 minutes to perform, do not power down the
controller during this time.
Note: Refer also to the software manual – always select the Reset menu item before pressing the
reset button.
3.4. Controller Input and Output
The inputs and outputs refer to both the CXCi+ and the CXCi HP controllers.
Ethernet Port
The Ethernet port is designed for connection to a user supplied network (TCP/IP secured by user) via a
front panel RJ-45 jack and a standard network cable. Local access (e.g. laptop computer) is also possible
from the Ethernet port connection using a standard network cable.
Analog Input Channels
The controller is provided with analog input channels for voltage, current, and temperature.
Voltage Inputs
Two voltage input channels, V1 and V2, provide monitoring of discharge and charge voltage. The
controller software is pre-configured to monitor V1 for battery voltage and V2 for load voltage.
V2 is wired internally to the rectifier shelf to provide a reference for rectifier float voltage, low voltage
disconnect (LVD), system high voltage alarm, and system low voltage alarm.
Wire V1 to battery to monitor battery voltage or change battery setting from V1 to V2 in Signals >
Configure Signals.
Current Inputs
The controller software is pre-configured to monitor I1 for load current wired internally to the load current
shunt.
Temperature Inputs
Two temperature input channels, T1 and T2, provide monitoring of battery temperature and temperature
compensation (temp comp) or room/ambient temperature. A voltage is supplied to these terminals to
power the temperature sensors.
Digital Input Channels
The controller can accommodate up to two channels and can monitor digital alarm/control signals from
rectifiers, converters and many other types of equipment.
Alarm and Control Output Relays
The controller contains four Form C digital alarm output relays to extend alarms and control external
apparatus. Each internally generated alarm or control signal may be mapped to any one of the relays, or,
several signals may be mapped to just one relay or none at all.
Page 18
9400021-J0 Rev B
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 3 - Features
Network Connection and Remote Communication
The Cordex® system can be set up, monitored and tested via an Ethernet connection. The
communication protocol supports a web interface. All alarming and control of the rectifiers is
accomplished with a controller via a CAN bus.
A step-by-step connection wizard – provided to establish remote communications with your controller – is
available via the Alpha website (http://www.alpha.ca/downloads).
Controller Connections
Located on the rear of the shelf are terminal block connections for the system control I/O; such as, digital
signals, analog inputs, and alarm relay outputs.
USB Port (CXCi HP Only)
A USB 2.0 port is located on the front of the CXCi HP controller. It is used for upgrading operating system
software.
9400021-J0 Rev B
Page 19
The inventory included with your shipment is dependent upon the options you have ordered. The options
are clearly marked on the shipping container labels and on the bill of materials (BOM).
Check for Damage
Prior to unpacking the product, note any damage to the shipping container. Unpack the product and
inspect the exterior for damage. If any damage is observed contact the carrier immediately. Continue the
inspection for any internal damage. In the unlikely event of internal damage, inform the carrier and contact
Alpha Technologies for advice on the impact of any damage.
Packing Materials
Alpha is committed to providing products and services that meet our customers’ needs and expectations
in a sustainable manner, while complying with all relevant regulatory requirements. As such Alpha strives
to follow our quality and environmental objectives from product supply and development through to the
packaging for our products. Rectifiers, UPSs, and batteries are shipped on individual pallets and are
packaged according to the manufacturer’s guidelines. Almost all of Alpha’s packaging material is from
sustainable resources and or is recyclable. See the following table for the material and its environmental
codes.
Figure 9. Packing Materials and Environmental Codes
Cardboard
Polyethylene
Terephthalate
Low Density
Polyethylene
Polystyrene
Steel
Aluminum
Wood
Packing boxes
Caps
Flexible film
Packaging
Bubble wrap
Shrink wrap
Plastic bags
Foam
Strapping on
pallets
Strapping on
pallets
Pallets
Lumber
Returns for Service
Save the original shipping container. If the product needs to be returned for service, it should be
packaged in its original shipping container. If the original container is unavailable, make sure that the
product is packed with at least three inches of shock-absorbing material to prevent shipping damage.
Alpha Technologies is not responsible for damage caused by improper packaging of returned products.
If you have any questions before you proceed, call Alpha Technologies: 1 888 462-7487.
Page 20
9400021-J0 Rev B
This chapter is provided for qualified personnel to install the product. Mount the unit horizontally in a clean
and dry environment.
Note: Drawings are located at the rear of the manual.
Warning: This system is designed to be installed in a restricted access location that is inaccessible
to the general public.
5.1. Safety Precautions
Warning: Hazardous voltages are present at the input of power systems. The DC output from the
rectifiers and battery system, though not dangerous in voltage, has a high short circuit current capacity
that may cause severe burns and electrical arcing.
Before working with any live battery or power system/distribution center, follow these precautions:
• Remove all metallic jewelry; e.g., watches, rings, metal rimmed glasses, necklaces.
• Wear safety glasses with side shields (and prescription lenses if necessary) at all times during
installation.
• Use insulated hand tools.
The installer should follow all applicable local rules and regulations for electrical and battery installations;
e.g., CSA, UL, CEC, NEC, OSHA, and local fire codes.
5.2. Shelf Preparation/Mounting
Warning: This system is designed to be installed in a restricted access location that is inaccessible
to the general public.
Note: The shelf is designed for mounting in a clean and dry environment. Allow at least 1.75" (44mm,
1 RU) of free space above and below the unit for unrestricted cooling airflow. 3.5" (89mm, 2RU) is
recommended.
Each shelf has been designed for flush or offset mounting in a 19" (483mm) or 23" (584mm) rack. See
drawings at the end of this manual.
Mounting brackets accommodate either 1" (25.4mm) or 1.75" (44mm) rack spacing. Mount the shelf to the
rack using at least two #12 – 24 x 1/2" (12.7mm) screws in each bracket. Use Phillips-type screws and
screwdriver to eliminate the possibility of slippage and scratching of the unit’s exterior.
An electrical conducting path must exist between the unit’s chassis and the metalwork of the enclosure in
which it is mounted or a grounding conductor. The electrical continuity requirement can be met by the use
of thread-forming type unit mounting screws and star washers that remove any paint or non-conductive
coatings and establish metal-to-metal contact.
9400021-J0 Rev B
Page 21
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 5 - Installation
5.3. Module Insertion and Removal
The rectifier is plug and play. When a rectifier module is added to the system, the controller will detect and
update the inventory automatically. Replacing an installed rectifier requires a manual Inventory Update
at the controller to clear the removed rectifier from its current list of rectifiers.
Insert rectifiers by placing the module on the shelf bottom and sliding the module into the rear connector
(inside of the shelf). Apply pressure on the front of the module to engage the rear connector in the shelf
receptacle. A thumbscrew is provided to secure the rectifier into the shelf.
Note: Do not force a module into position if it does not seat properly. All modules are keyed to ensure
that the correct module (polarity/voltage) type is used.
5.4. Removing a CXRC Rectifier
1. To remove a module, loosen the screw on the bottom of the faceplate.
Thumb Screw
2. Grasp the handle and pull out, sliding the module away from the rear connector and out of the
shelf.
3. Place the new rectifier module on the shelf bottom and slide the module into the rear connector
(inside the shelf).
4. Apply pressure to the module front panel to engage the rear connector in the shelf receptacle.
5. Tighten the thumb screw to secure the rectifier to the shelf.
6. Refer to the respective controller software manual to perform an inventory update or module
assignment.
5.5. Removing the CXCi HP and CXCi+ Controller
To remove the controller:
1. Remove at minimum the left most rectifier adjacent to the controller.
2. Remove the controller mounting screws as highlighted in figure below.
Page 22
9400021-J0 Rev B
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 5 - Installation
Remove controller mounting screws
3. Pull from the location noted in the following image to remove the controller.
Pull here to remove the
controller from the shelf
CAUTION: When removing the controller in a live system that has an LVD, ensure that the LVD
override jumper is set to correct position to avoid possible service disruption. Refer to the wiring and
connections section of the manual and the connection drawings.
9400021-J0 Rev B
Page 23
6. Wiring and Connections
6.1. Safety Precautions
Warning: Hazardous AC voltages may be present. Ensure power at the AC service panel is off
before attempting work on the AC connections. Use a voltmeter to verify the absence of voltage. Clearly
mark the correct polarity of the battery leads before commencing work on DC connections.
Refer to the chapter on Installation for additional safety precautions.
6.2. Tools Required
Various tools are essential for product installation. Insulated tools are recommended. Use this list as a
guide:
• Slot head screwdrivers (blade sizes: 1/4", 1/8", 1/16")
• Phillips head screwdriver, #2 (tip size 3/16")
• Digital voltmeter equipped with test leads
• Adjustable 24/48Vdc load (optional)
• Cutters and wire strippers
• Crimping tool (optional for large gauge wire)
• Socket and ratchet set (Imperial measure)
• Anti-static wrist strap
• Computer (laptop) with web browser
• Standard network cable (for access using the Ethernet port)
6.3. Power System Chassis Ground and DC Ground
Warning: For safety reasons, ensure the system is properly bonded to the building’s ground.
Both the shelf chassis ground (via power system chassis ground) and common return (DC ground) shall
be connected to the site ground to ensure correct operation of the system and to prevent drifting floating
analog (especially current) readings.
6.4. AC Feeder Protection/Sizing
To maximize system reliability, the AC feed divides the rectifiers into groups to be supplied by separate
feeds. See customer connections drawing (modules are numbered left to right).
• Shelves with integrated distribution have TB3 feed modules 1 and 2 while TB4 feeds modules 3
and 4.
• Shelves with bulk outputs have TB3 feed modules 1 and 2 while TB4 feeds modules 3, 4 and 5.
Page 24
9400021-J0 Rev B
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 6 - Wiring and Connections
It is recommended, for each feed, to use a dedicated protection feeder breaker located at the AC
distribution panel. The feeder breaker can also act as the disconnect device for the connected modules.
Table 2. Recommended AC Supply Configuration
AC Input (Vac)
Number of Recti-
fiers on AC Feed
Circuit Breaker, Ex-
act Value to Use (A)
90° C Wire Gauge
to use at 30° C
ambient (AWG)
120/240
1
10 or 15
14
120/240
2
20
12
120/240
3
20
12
An external surge protection device is not required. The rectifiers are protected by internal MOVs.
6.5. AC Input
CAUTION: Route the AC input wires in flexible or rigid conduit as far away as possible from the DC
power wires to minimize EMI disturbances.
1. If the shelf is factory-equipped with a line cord, proceed to the next section.
2. Refer to the -08 customer connections drawings (rear view – back cover removed).
3. Remove the metal cover from the rear of the shelf to expose the wire-way for the input terminal
blocks.
4. Attach the conduit retainers to the wire-way hole(s) and route the AC cables through.
5. Secure the wires to the AC input and chassis ground terminals as required. Tighten the cable
connector to the AC cable (conduit similar).
6. Replace rear cover once all connections have been completed.
6.6. Calculating Output Wire Size Requirements
Wire size is calculated by first determining the appropriate maximum voltage drop requirement. Using the
formula below calculate the CMA wire size requirement. Determine the size and number of conductors
required to satisfy the CMA requirement.
CMA = (A x LF x K) / AVD, where:
• CMA: Cross section of wire in circular MIL area
• A: Ultimate drain in amps
• LF: Conductor loop feet
• K: 11.1 constant factor for commercial (TW type) copper wire
• AVD: Allowable voltage drop
9400021-J0 Rev B
Page 25
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 6 - Wiring and Connections
Check again that the ampacity rating of the cable meets the requirement for the installation application.
Consult local electrical codes (NEC, CEC, etc.) for guidelines. If required, increase the size of the cable to
meet the code.
Example:
A = 40A
LF = 20 feet
K = 11.1
AVD = 0.5V
CMA = (A x LF x K) / AVD
CMA = (40A x 20ft x 11.1) / 0.5A
CMA = 17,760
In this example the technician would need to use a 7 AWG or larger. This value can be found from a
standard AWG table.
6.7. DC Output
Warning: Leave cables disconnected at battery and verify output polarity using a voltmeter. Make
battery connections only after all other wiring is completed.
DC output wire must be UL approved XHHW or RHH/RHW (for Canadian users RW90; for European
users, must be EN or IEC approved wire). Control and sense wires must be UL approved 1015 (for
Canadian users TEW type; for European users, must be EN or IEC approved wire).
Circuit Breaker Distribution
Four Module shelf: equipped with four AM-style bullet type breakers, factory configurable as four load
breakers or two load breakers plus two battery breakers, or three load breakers plus one battery breaker.
Five Module shelf: bulk output only.
Note: Battery breakers should be series-trip to ensure effective alarm operation; service personnel
must reset the breaker to clear the alarm.
Note: When there is no AC power to the rectifiers and there is only one battery circuit breaker, there
will be no alarm if the circuit breaker trips.
Secure the positive and negative cable leads to the shelf output terminal blocks of the correct polarity; i.e.,
+Vcable to +Vpost.
The common output leg of the rectifier system should be connected to ground. This is typically done at
the load common termination point. For the output terminal block configurations, refer to the schematics
drawings at the rear of this manual.
Page 26
9400021-J0 Rev B
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 6 - Wiring and Connections
6.8. CAN Ports
Four Module shelf: one CAN OUT port located at the rear of the shelf.
Five Module shelf: one CAN IN and one CAN OUT port. Located at the back of the shelf.
Daisy-chain from node to node (CAN OUT of one node to CAN IN of another) as necessary and ensure
that only the last node is terminated.
Note: This system can accommodate up to a maximum of 12 Cordex® small convection cooled
rectifiers (650W, 400W, 250W). The individual rectifiers do not provide their own CAN bus power and
must draw it from the controller.
6.9. Network Connection and Remote Communications via the
Controller
The Cordex® rectifier shelf systems can be set up, monitored and tested via modem or Ethernet 10/100
Base-T serial data connection. The communication protocol supports a web interface. Some standard
scenarios are described in the following sections.
Ethernet Port for Network Connection
The Ethernet port is designed for controller connection to a user supplied network (TCP/IP secured by
user) via a front panel RJ-45 jack.
Connect to the controller using a standard network cable. Pinouts are shown in the connection drawings.
Ethernet Port for Local Connection
Local access (e.g. laptop computer) is also possible from the Ethernet port connection using a standard
network cable.
Note: Older CXCi models must use a crossover Ethernet cable for direct connection to a computer.
6.10. Signal Wiring Connections
For terminal block connections, the recommended wire sizes are #16 to #26 AWG (1.5 to 0.129mm2).
Control and sense wires shall be UL approved Style 1015 (for Canadian users, TEW type; for European
users, EN or IEC approved wire).
CAUTION: To reduce the risk of fire, use only #26 AWG (0.129mm2) or thicker wire.
Table 3. Wiring Connections for the CXCi Series of Controllers
Terminal
Description
Default Name
Signal Type
Range
1, 2, 3*
LVD Control (inter-
nal)
K1, Relay 1
NO/COM/NC
60VDC / 1A
4, 5, 6*
Alarm Output 2
K2, Relay 2
NO/COM/NC
60VDC / 1A
9400021-J0 Rev B
Page 27
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 6 - Wiring and Connections
Table 3. Wiring Connections for the CXCi Series of Controllers (continued)
Terminal
Description
Default Name
Signal Type
Range
7, 8, 9*
Alarm Output 3
K3, Relay 3
NO/COM/NC
60VDC / 1A
10, 11, 12*
Alarm Output 4
K4, Relay 4
NO/COM/NC
60VDC / 1A
13, 14**
Digital Input 1 (inter-
nal)
D1, Digital 1
Pos (+) or Neg (-)
0—60VDC
15, 16**
Digital Input 2
D2, Digital 2
Pos (+) or Neg (-)
0—60VDC
17, 18***
Voltage Input 1
V1, Load Voltage
Pos (+) / Neg (-)
0—60VDC
19, 20***
Temp Probe 1
T1, Analog Input T1
Pos (+) / Neg (-)
0—5VDC
21, 22***
Temp Probe 2
T2, Analog Input T2
Pos (+) / Neg (-)
0—5VDC
23
Battery –48V
Batt Hot
Neg (-)
20—60VDC
24, 25
Current Input 1 (in-
ternal)
I1, Load Current
Pos (+) / Neg (-)
±50mV
* NO and NC Form C contacts available. Can be configured to de-energize on alarm (DOA) or energize on
alarm (EOA).** See Table 4: Voltage Level Definitions for Digital Inputs (on page 30) for definitions of logic
and system.*** Voltage (Input) is 0—60VDC, Temp Probe is 0—5VDC with power source.
Note: To aid the user with installation, frequent reference is made to drawings located at the rear
of this manual. Custom configurations may be detailed within the Alpha power system documentation
package.
Bundle the signal cables together and route them through the entry holes of the shelf.
Analog Inputs
CAUTION: Ensure the correct polarity is used for all input cable terminations.
The analog input channels are used to monitor various types of electrical signals. The Voltage Input is
-60 to +60Vdc. The Temperature Input (designed for Alpha supplied temp sensor only) is 0 to 5Vdc with
power source.
Voltage
Voltage Input #1 terminals on the shelf provide connections to an optional secondary voltage input.
Voltage Input #2 is wired internally to the rectifier output voltage of the shelf. This is used as the reference
for Voltage regulation of rectifiers, system alarming (such as high voltage) and control (such as LVD).
See the software manual for information on configuring Alarms and LVD control. The battery should be
connected at the battery system voltage terminal for redundant power feed to the CXCi series controller
when a battery disconnect device is used. It is critical to controller operation as it ensures an auxiliary
source of power to the controller should the disconnect device open the circuit.
Current
Page 28
9400021-J0 Rev B
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 6 - Wiring and Connections
Current input #1 is wired internally to the system current shunt for shelves with integrated distribution, and
wired to an external shunt for bulk distribution shelves.
Temperature Sensor
Temperature Probe input channels provide connections for up to two temperature sensors. A voltage is
supplied to these terminals for sensor measurements. Temperature sensors are available from Alpha in
various lengths.
Digital Inputs
The digital input channels are used to monitor various alarm and control signals. All input channels are
voltage activated and accept a bipolar (i.e. negative or positive) DC signal directly.
For shelf modules with integrated distribution, D1 is wired internally for CB/fuse trip. D2 is available for
customer connections as required.
Connection Method
Typical Alpha systems use the “reset with Hot and trigger with Ground” connection. The digital input is
wired in such a way that the Hot is wired directly into one of the input terminals:
• positive input for +12V and +24V systems
• negative input for -48V systems
The other input terminal is wired to the Ground (common) of the system through a relay (dry contact –
usually located on the equipment requiring monitoring). This method allows the digital input to receive (or
not receive) a Ground signal on an alarm.
Figure 10. Digital Input Connection Method
VE Ground
Hot
Hot
VE Hot
Relay from
Equipment
VE Hot
VE Ground
Relay from
Equipment
Digital Input 12V and 24V
Systems
Digital Input 48V
Systems
Programming the Digital Input
The digital input channels can be programmed for “active high” or “active low. Active high indicates,
“alarm on the presence of a ground signal” and active low indicates, “alarm on the removal of a ground
signal.” See controller software manual for detailed instruction on programming.
9400021-J0 Rev B
Page 29
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 6 - Wiring and Connections
Table 4. Voltage Level Definitions for Digital Inputs
V
Voltage Level (Vdc),
Considered As “0” (Off)
Voltage Level (Vdc),
Considered As “1” (On)
0 - 60 (System Voltage Setting)
0 to 3V
9 to 60V
Alarm Relay Outputs
Terminals provide contacts for extending various alarm or control signals. Each relay output can be wired
for NO or NC operation during an alarm or control condition.
Figure 11. Relay Connections
NO
Normally
Open
Normally
Closed
Common
C
NC
Relays can be programmed to energize or de-energize during an alarm condition (see controller software
manual). When the controller reset button is pressed or power is lost, all relays de-energize.
These relays could be used for additional external LVD contactor control; however, this would not provide
the redundant LVD control as with the assigned output pins described below.
LVD Control (Load Disconnect or Battery Disconnect)
The disconnect option is controlled by and connected internally to relay K1, when applicable.
LVD Inhibit
Should it be necessary to remove a CXCI series controller, the customer connection board (on the rear of
the shelf) provides shorting pins (JP2) to inhibit (or override) the LVD Control function.
See the customer connections drawings.
If the LVD is controlled on NC contacts (factory default for LVD option), then JP2 pins 1 and 2 must be
shorted together to maintain LVD operation. If the LVD is controlled on NO contacts, then pins 2 and 3
must be shorted together. For normal operation, the factory-supplied shorting jumper should be left on
pins 3 and 4.
LVD Control Alternative
The LVD Control functions can be hardwired directly from an alarm output relay to an external LVD
contactor (or panel). See Controls Menu Defaults in the controller software manual.
Page 30
9400021-J0 Rev B
7.1. Main Rectifier States
Rectifier operation has five main states; each state is distinct and necessary for the operation of the
rectifier.
• Off
• Start Delay
• Soft Start
• Normal Operation
• Turning Off
Off
The rectifier is in the Off state immediately after power is applied to the rectifier or after a rectifier
shutdown (remote or local shutdown, AC shutdown, OVP or thermal shutdown).
In this state the DC-DC converter is turned off and the controller monitors its inputs for the proper
conditions to begin the start up sequence.
When the conditions have been met for the rectifier to start up, it transitions to the Start Delay state.
Start Delay
When the rectifier is in the Start Delay state, the DC-DC converter is held off and still not sourcing power,
waiting for a given amount of time before transitioning to the next state.
The controller continues to monitor its inputs.
After the Start Delay state the rectifier transitions to the Soft Start state.
Note: Soft start, or current walk-in, gradually increases the voltage and current output of the rectifier
upon startup. This is done to reduce the instantaneous load on the AC source.
Soft Start
When the Soft Start state is entered, the rectifier is turned on and the output voltage and output current
gradually increased. If a load is present, the rectifier begins to source power.
When the voltage and current limit ramps have finished, the rectifier will transition to the Normal
Operation state.
Normal Operation
The Normal Operation state is the state that the rectifier will be in performing all of the rectifier functions
and features specified herein.
From this state, the only valid transition is to the Turning Off state. This transition will happen if the
rectifier is required to shut down.
9400021-J0 Rev B
Page 31
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 7 - Operation
Turning Off
The Turning Off state is entered because a short delay is required before the rectifier actually turns off to
take care of any initialization requirements.
When this short delay has elapsed, a transition to the Off state is made.
7.2. Main Rectifier Modes
In addition to main rectifier states, there is a set of main rectifier modes. These modes are divided into
two categories:
Output Voltage Modes
Voltage modes, under software control, can directly adjust the output voltage. Situations, such as the
rectifier being in current limit, can change the output voltage with no software control.
The following table describes the five output voltage modes.
Table 5. Output Voltage Modes
Output Volt-
age Modes
Active when...
Float
Output voltage is set to the float voltage setting.
Equalize
Output voltage is set to the equalize voltage setting.
Battery Test
Output voltage is set to the battery test voltage setting.
Safe
Output voltage is set to the safe mode voltage setting.
Manual Test
Output voltage can be manually adjusted outside of the standard adjustment
ranges.
Output Current/Power Modes
These four output current/power modes directly affect the output current and power:
Table 6. Output Current/Power Modes
Output Cur-
rent/Power Mode
Output current and power limit have been reduced due to:
Temperature foldback mode
High temperature of the heatsink or internal ambient temperature sensor.
AC foldback mode
Low AC input voltage.
Note: Reduces the risk of tripping an AC breaker due to increased AC
current draw as the AC voltage decreases.
Short circuit foldback mode
Short circuit at the output.
Internal fault foldback mode
Internal fault.
Page 32
9400021-J0 Rev B
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 7 - Operation
7.3. CAN Bus Communication
The CAN bus is used for commands and data transfer between the rectifier and controller to configure the
rectifier with system settings and to monitor rectifier status.
7.4. Factory Ranges and Defaults
The following table lists the rectifier controller settings/ranges/defaults. These settings are for a 24V
system.
Table 7. Factory Ranges and Defaults
Setting
Range (minimum to maximum)
Default
Float (FL) Voltage
23.75 – 29.30V
27.00V
Equalize (EQ) Voltage
24.90 – 29.30V
27.50V
Battery Test (BT) Voltage
22.00 – 26.00V
23.00V
Over Voltage Protection (OVP)
See note below – 30.30V
28.50V
Current Limit (CL)
23 – 100%
100%
Power Limit (PL)
0 – 100%
100%
Module Start Delay
0 – 250s
1s
System Start Delay
0 – 600s
0s
Low Voltage Alarm (LVA)
21.00 – 26.00V
22.00V
High Voltage Alarm (HVA)
26.00 – 30.30V
27.75V
Equalization (EQ) Timeout
1 – 2399h
30h
Battery Test (BT) Timeout
1 – 250h
8h
Softstart Ramp-rate
Normal/Fast
Normal
Current Limit / Power Limit Alarm
Enable/Disable
Enable
Remote Shutdown
Enable/Disable
Enable
Ramp Test
Enable/Disable
Enable
Note: OVP cannot be set below the present system/FL/EQ/BT voltage setting or the safe mode
voltage of 25.7V.
9400021-J0 Rev B
Page 33
8. System Startup
8.1. Check System Connections
• Ensure AC is off, battery is disconnected, and all power modules are removed from the shelf.
• Verify the polarity of all connections.
8.2. Verify AC and Power the Shelf
• Install one power module.
• Verify AC input voltage is correct and turn on the corresponding AC input feeder breaker.
• The power module OK LED should illuminate after a preset start delay.
• Using the controller, test functionality of various module alarms and controls.
8.3. Check Battery Polarity and Connect
• Verify correct battery polarity using a voltmeter (ensuring no cells or batteries are reversed).
• Connect battery as required to the output of the system or turn on battery breaker.
• Install remaining power modules.
• On the controller, set Float and Equalize voltage to the levels specified by the battery
manufacturer.
• For some systems, the default setting for low AC voltage alarming is 180Vac. For nominal 120Vac
operation, it is recommended to reset this value to 100Vac.
• Using the controller, test the functionality of various module alarms and controls. In addition,
perform a load test with the system using a resistive load box as needed.
8.4. Controller Reset - CXCi+
Soft Reset
CAUTION: Before removing a CXCi+ from a live system or performing controller maintenance, and
external LVD inhibit (or override) is required to avoid a disruption of service.
The reset button located on the front panel of the CXCi+ is for restarting the microprocessor. When
pressed momentarily, the unit beeps twice then resets. The front-panel LEDs illuminate temporarily, and
then extinguish after the system has finished its 15-second self-test.
CAUTION: During a reset the controller may need to run a defragmentation cycle. Cycling LEDs
in the front panel indicate that defragmentation is in progress. All full defragmentation can take up to 20
minutes to perform. DO NOT power down the controller during this time.
Page 34
9400021-J0 Rev B
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 8 - System Startup
IP Address Reset
To reset the IP address, press and hold the front panel soft reset button for three seconds. The CXCi+
unit beeps three times, IP address resets to 10.10.10.201 and DHCP is disabled. The settings are saved
and the unit then resets.
This reset allows local access; e.g., with a laptop and a standard network cable. See current version
software manual for details.
Hard Reset
A hard reset of the controller can be performed by pressing the front panel hard reset button. This
procedure will restart the microprocessor if the front panel (soft) reset button fails to operate.
CAUTION: Move the LVD control jumper to the override position before unplugging the controller.
The load and batteries are still connected. Use of hard reset may cause loss of data.
8.5. Controller Reset - CXCi HP
Soft Reset
CAUTION: Ensure that a backup has been performed before starting this process. Use the Backup
feature accessed through the LCD at Shortcuts > Backup.
Note: When the controller is being reset, the DC output voltage is maintained. Temperature
compensation, user inputs, and relay controls are not available until the controller has finished restarting.
1. From the main dashboard, go to Controller > Controller Status.
2. Click the Reset Controller button. The Controller Restart window displays progress via a blue
bar.
3. The controller screen goes black, and the LEDs lights cycle while restart is in progress.
Hard Reset
A hard reset of the controller can be performed by pressing the front panel hard reset button. This
procedure will restart the microprocessor if the front panel (soft) reset button fails to operate.
CAUTION: Move the LVD control jumper to the override position before unplugging the controller.
The load and batteries are still connected. Use of hard reset may cause loss of data.
9400021-J0 Rev B
Page 35
Although very little maintenance is required with Alpha systems, routine checks and adjustments are
recommended to ensure optimum system performance. Qualified service personnel should do repairs.
The following table lists a few maintenance procedures for this system. These procedures should be
performed at least once a year.
Warning: HIGH VOLTAGE AND SHOCK HAZARD. Use extreme care when working inside the shelf
while the system is energized. Do not make contact with live components or parts.
Important: Circuit cards can be damaged by static electricity. Always wear a grounded wrist strap
when handling or installing circuit cards.
Table 8. Sample Maintenance Log
Procedure
Date Completed
Clean ventilation openings
Inspect all system connections (re-torque as necessary)
Verify alarm/control settings
Verify alarm relay operation
9.1. Replacing a CXCi+ Controller
This procedure is for replacing a CXCi+ controller.
Write down the controller communication information: dynamic or static IP, IP address, and gateway.
1. Connect a laptop to controller per software manual; standard network cable to the Ethernet port.
2. Save the CXC configuration file (see software manual Logs and Files > Manage Configuration File
> Save Full Site Configuration).
3. Save the CXC text file if necessary: Logs and Files > Manage Editable Text Files > Save
Dynamic Text File. If applicable, bypass the system LVD:
a. Locate JP2 on the back of CXCi+ system shelf (see below).
Page 36
9400021-J0 Rev B
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 9 - Maintenance
I1
-
+
25
24
TB13
NC C NO
K1
NC C NO
K2
NC C NO
K3
K4
C NO
NC
1
12 11 10
9
8
7
6
5
4
3
2
-
+
-
+
-
+
BATT
HOT
(+)
T2
T1
V1
D2
D1
14 15 16 17 18 19 20 21 22 23
13
TB11
TB12
Customer Connection Board Detail
1 2 3 4
Used internally for LVD control
(if equipped)
See below for
jumper settings
JP2
b. If the LVD is controlled on NC contacts (factory default for LVD option), then JP2 pins 1 and
2 must be shorted together to maintain LVD operation.
c. If the LVD is controlled on NO contacts, then JP2 pins 2 and 3 must be shorted together.
4. Gently pull the controller from the slot.
5. Place the new CXCi+ controller on the shelf bottom and slide into the rear connector at the back of
the slot.
6. Log on to the controller and go to Logs and Files > Manage Configuration File > Upload Site
Configuration and select the saved *.cfg file. After the upload do a Submit Changes. Make sure
the site information is checked to save it, and click Accept.
7. Go to Logs and Files > Manage Editable Text Files > Upload Dynamic Text File and select
the saved *.tfg file. You do not need to submit changes; it is already saved.
9400021-J0 Rev B
Page 37
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 9 - Maintenance
8. Use a meter to verify the bus voltage and current shunt. Recalibrate as required due to differences
in the new CXCi+.
9. Replace rectifiers and remove LVD bypass.
9.2. Replacing a CXCi HP Controller
This procedure is for replacing a CXCi HP controller.
Write down the controller communication information: dynamic or static IP, IP address, and gateway.
Figure 12. Removing the CXCi HP
Pull here to remove the
controller from the shelf
1. Login to the web user interface.
2. From the main dashboard go to Controller > Advanced Functions > Configuration File.
3. Click on the Export Controller Clone button to save the configuration file. Save the configuration
file in a location easily accessed as it will be uploaded into the new controller.
4. Gently pull the controller from the slot.
5. Place the new controller on the shelf bottom and slide in the rear connector at the back of the slot.
6. Log back into the web user interface.
7. From the main dashboard go to Controller > Advanced Functions > Configuration File.
8. Press the Import button to upload the last saved configuration file.
Page 38
9400021-J0 Rev B
10. Warranty and Service Information
Technical Support
In Canada and the USA, call toll free 1-888-462-7487.
Customers outside Canada and the USA, call +1-604-436-5547.
Warranty Statement
For full information details review Alpha's online Warranty Statement at www.alpha.ca.
Product Warranty
Alpha warrants that for a period of two (2) years from the date of shipment its products shall be free from
defects under normal authorized use consistent with the product specifications and Alpha’s instructions,
the terms of the manual will take precedence. The warranty provides for repairing, replacing or issuing
credit (at Alpha’s discretion) for any equipment manufactured by it and returned by the customer to the
factory or other authorized location during the warranty period. There are limitations to this warranty
coverage. The warranty does not provide to the customer or other parties any remedies other than the
above. It does not provide coverage for any loss of profits, loss of use, costs for removal or installation of
defective equipment, damages or consequential damages based upon equipment failure during or after
the warranty period. No other obligations are expressed or implied. Warranty also does not cover damage
or equipment failure due to cause(s) external to the unit including, but not limited to, environmental
conditions, water damage, power surges or any other external influence. The customer is responsible for
all shipping and handling charges. Where products are covered under warranty Alpha will pay the cost of
shipping the repaired or replacement unit back to the customer.
Battery Warranty
Note that battery warranty terms and conditions vary by battery and by intended use. Contact your Alpha
sales representative or the Technical Support team at the above number to understand your entitlements
under Battery Warranty.
Warranty Claims
Any claim under this Limited Warranty must be made in writing to Alpha BEFORE sending material back.
Alpha will provide Product return instructions upon approval of return request. A Service Repair Order
(SRO) and / or Return Authorization (RA) number will be issued ensuring that your service needs are
handled promptly and efficiently. Claims must be made online at: www.alpha.ca.
Service Information
For a list of international service centers, visit: www.alpha.ca.
9400021-J0 Rev B
Page 39
CSA (Canadian Standards Association also known as CSA Group) was established in 1919 as an
independent testing laboratory in Canada. CSA received its recognition as an NRTL (Nationally
Recognized Testing Laboratory) in 1992 from OSHA (Occupational Safety and Health Administration) in
the United States of America (Docket No. NRTL-2-92).
When these marks appear with the indicator “C and US” or “NRTL/C” it means that the product is certified
for both the US and Canadian markets, to the applicable US and Canadian standards. (1)
As part of the reciprocal, US/Canada agreement regarding testing laboratories, the Standards Council of
Canada (Canada’s national accreditation body) granted Underwriters Laboratories (UL) authority to certify
products for sale in Canada. (2) Only Underwriters Laboratories may grant a license for the use of this
mark, which indicates compliance with both Canadian and US requirements.(3)
NRTL’s Capabilities
NRTLs are third party organizations recognized by OSHA, US Department of Labor, under the NRTL
program. The testing and certifications are based on product safety standards developed by US based
standards developing organizations and are often issued by the American National Standards Institute
(ANSI). (4) The NRTL determines that a product meets the requirements of an appropriate consensus-
based product safety standard either by successfully testing the product itself, or by verifying that a
contract laboratory has done so, and the NRTL certifies that the product meets the requirements of the
product safety standard. (4)
Governance of NRTL
The NRTL Program is both national and international in scope with foreign labs permitted.
(1) www.csagroup.org
(2)www.scc.ca
(3)www.ulc.ca
(4)www.osha.gov
Page 40
9400021-J0 Rev B
Alternating Current Current Transducer
ADIO
Analog-digital input-output
Alarm
An alarm has user configurable fields like a name, priority and it can is able to sent SNMP or
email notifications when it becomes active or cleared
ALCO
Alarm cutoff
Alert
An alert is status information about a module like a converter or rectifier. For example, "Module
Fail" or "Current Limit"
CAN
Controller Area Network
CT
Current Transducer
CX
Cordex series; e.g. CXC for Cordex® System Controller
CXC
Cordex® Controller
CXC
HP
Cordex® Controller High Performance
CXD
Cordex® DC-DC Converter
CXR
Cordex® Rectifier
DC
Direct current
DCCT
Direct Current Current Transducer
DHCP
Dynamic Host Configuration Protocol
DOD
Depth of discharge
FCC
Federal Communications Commission
GUI
Graphical User Interface
Hint
A hint is information about the state of the system or possible configuration problems.
ICMP
Internet control message protocol
IEC
International Electrotechnical Commission
IETF
Internet Engineering Task Force
IP
Internet Protocol
IPv4
Internet Protocol version 4
IPv6
Internet Protocol version 6
ISO
International Organization for Standardization
LCD
Liquid Crystal Display
LED
Light Emitting Diode
LVD
Low voltage disconnect
LVBD
Low voltage battery disconnect
9400021-J0 Rev B
Page 41
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 12 - Glossary
MAC
Media Access Control; e.g. MAC address
MIB
Management Information Base; a database of entities most often associated with SNMP
MOV
Metal Oxide Varistor
MUX
Multiplexer
NEBS
Network Equipment-Building System; a set of safety, spatial and environmental guidelines for
telecom
OLED
Organic LED, in-shelf controller display
RFC
Request For Comments; a formal document (or standard) from the Internet Engineering Task
Force (IETF)
SCI
Serial Communication Interface
SELV
Safety Extra Low Voltage
SMTP
Simple Mail Transfer Protocol
SNMP
Simple Network Management Protocol
SNTP
Simple Network Time Protocol
SOC
State of Charge
TCP/IP
Transmission Control Protocol / Internet Protocol
Trap
An unsolicited SNMP event notification
Page 42
9400021-J0 Rev B
13.1. 2RU, 24-400W, 19", 4 Module System
Table 9. Specifications: 24-400W 19", 4 Module System
Specifications: 24-400W 19", 4 Module System
Basic Unit: Shelf
Maximum Output:
53A, 30VDC
Recommended
Feed Breaker, Sin-
gle Phase:
20A, #12 AWG per feed
Mechanical
Dimensions:
88mm H x 444mm W x 307mm D, rectifier front panel 18mm D (3.5" H x 17.5" W x 12.1"
D, rectifier front panel 0.7" D)
Mounting:
19" or 23" rack, flush or 5" offset or 6" offset
Weight:
6.39kg (15.2lb)
Connections
AC Input:
Dual feed terminal blocks, 4 to 6mm2 (#12 to #10 AWG)
Chassis ground:
M4 studs
Communications:
CAN bus out RJ-12 offset
DC Output:
Terminal blocks #6 AWG (16mm2) maximum.
Signal wiring:
Terminal blocks #26 to #18 AWG (0.14 to 0.75mm2)
Compliance
EN 60950:
Rectifier output shall be rated SELV suitable for connections to TNV-1 circuits
UL:
UL 60950-1-2014
CSA:
CAN/CSA C22.2 No.60950-1-07, +A1:2011 +A2:2014
CE IEC/EN:
EN 60950-1:2006 / A11:2009 / A1:2010 / A12:2011 / A2:2013, CB Scheme
2014/35/EU Low Voltage Directive
2014/30/EC EMC Directive
* See drawings at the rear of this manual. The above information is valid at the time of publication. Consult fac-
tory for up-to-date ordering information. Specifications are subject to change without notice.
9400021-J0 Rev B
Page 43
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 13 - Specifications
13.2. 2RU, 24-400W, 19", 5 Module System
Table 10. Specifications: 24-400W 19”, 5 Module System
Specifications: 24-400W 19", 5 Module System
Basic Unit: Shelf
Maximum Output:
67A, 30VDC
Recommended
Feed Breaker, Sin-
gle Phase:
20A, #12 AWG per feed
Mechanical
Dimensions:
88mm H x 444mm W x 307mm D, rectifier front panel 18mm D (3.5" H x 17.5" W x 12.1"
D, rectifier front panel 0.7" D)
Mounting:
19" or 23" rack, flush or 5" offset or 6" offset
Weight:
8.5kg (18.7lb)
Connections
AC Input:
Dual feed terminal blocks, 4 to 6mm2 (#12 to #10 AWG)
Chassis ground:
M4 studs
Communications:
CAN bus out RJ-12 offset
DC Output:
1/4 - 20 x 5/8 inch studs
Signal wiring:
Terminal blocks #26 to #18 AWG (0.14 to 0.75mm2)
Compliance
EN 60950:
Rectifier output shall be rated SELV suitable for connections to TNV-1 circuits
UL:
UL 60950-1-2014
CSA:
CAN/CSA C22.2 No.60950-1-07, +A1:2011 +A2:2014
CE IEC/EN:
EN 60950-1:2006 / A11:2009 / A1:2010 / A12:2011 / A2:2013, CB Scheme
2014/35/EU Low Voltage Directive
2014/30/EC EMC Directive
* See drawings at the rear of this manual. The above information is valid at the time of publication. Consult fac-
tory for up-to-date ordering information. Specifications are subject to change without notice.
Page 44
9400021-J0 Rev B
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 13 - Specifications
13.3. Cordex 24-400W Switched Mode Rectifier
Table 11. Specifications: Cordex 24-400W, Switched Mode Rectifier
Specifications: Cordex 24-400W, Switched Mode Rectifier
Power Module Output
Voltage:
21 to 30Vdc within rated limits
Power:
380W continuous/module @ 90-276Vac nominal
Current:
15A maximum @ 24Vdc
Static Load Regulation:
Better than ±1% for any load change within rated limits
Static Line Regulation:
Better than ±0.1% for any change in input voltage within rated limits
Dynamic Load Regula-
tion:
Better than ±5% for 40% - 90% - 40% (50% load step) [output shall recover to sta-
tic limits within 30ms]
Dynamic Line Regulation:
Better than ±1% for any change in input voltage within rated limits (output voltage
shall recover to static limits within 2ms)
Hold up Time:
>20ms @ 100% load 208-240Vac
Time Stability:
≤0.2% per year
Temperature Stability:
100ppm/°C over the operating range
Heat Dissipation:
200 BTU Max @ 100% load 90Vac; <151 BTU @ 208-240Vac
Electrical Noise:
<=32dBrnC voice band (25Hz to 10kHz)
<=10mV wide band (RMS to 10kHz)
<=100mV wide band (p-p to 100MHz)
In accordance with FCC requirements, we provide the following statement as specified in the FCC guidelines
for conformance to Part 15, Class B:
Note: This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment generates, uses, and can radiate radio fre-
quency energy and, if not installed and used in accordance with the instructions, may cause harmful interfer-
ence to radio communications. However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or television reception, which can be de-
termined by turning the equipment off and on, the user is encouraged to try to correct the interference by one
or more of the following measures:
• Reorient or relocate the receiving antenna
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
9400021-J0 Rev B
Page 45
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 13 - Specifications
Table 11. Specifications: Cordex 24-400W, Switched Mode Rectifier (continued)
Specifications: Cordex 24-400W, Switched Mode Rectifier
Any changes or modifications to this equipment not expressly described in this manual could void the FCC
compliance.
Power Module Input
Voltage:
Nominal: 208-240Vac
Extended: 90-276Vac
Extended Low: 60-90Vac (derated linearly to 0% output power)
Extended High: 276-320Vac (derated input power factor)
Frequency:
50/60Hz nominal (45 to 66Hz)
Current:
1.7 to 2.0A (208-240Vac), 5.2A maximum @ 90Vac
Power Factor:
>0.98 at 208-240Vac and 50-100% load
Protection:
1.5kA-interrupting capacity fuses in active and neutral lines
Efficiency:
>87% at 208-240Vac and 50-100% load
92.2% peak
Inrush current:
≤ full load steady state current of the rectifier within rated limits
Start-up Ready Time:
<5 seconds (excluding soft start) to complete inrush limit routine and ac measure-
ment (for OK signal)
Start-up Delay:
Programmable up to 120 seconds to enable stagger-start of multiple rectifiers and
to minimize the effect on a supply source
Soft Start:
User adjustable to at least 5 seconds (not including start-up delay time) and is de-
termined by output current limit ramp-up
THD (Current):
<6% at 100% load 208-240Vac
Input Leakage Current:
<3.5mA @ 265Vac 60Hz for up to two rectifiers
Environmental
Operating Temperature:
-40 to +50°C (derated linearly to 0 watts @ 70°C)
-40 to +122°F (derated linearly to 0 watts @ 158°F)
Storage Temperature:
-40 to +85°C (-40 to 185°F)
Humidity:
0 to 95% RH non-condensing
Elevation:
-500 to 3000m (-1640 feet to 9843ft)
Mechanical
MTBF:
>405,000 hours
Page 46
9400021-J0 Rev B
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 13 - Specifications
Table 11. Specifications: Cordex 24-400W, Switched Mode Rectifier (continued)
Specifications: Cordex 24-400W, Switched Mode Rectifier
Dimensions:
88.1mm H x 71.6mm W x 242mm D (excluding connector) [3.47" H x 2.82" W x
9.5" D]
Weight:
1.6kg (3.5lb.)
Compliance
EN 61000-6-2:2005
EMC - Part 6-5: Generic standards - Immunity for equipment used in power station
and substation environment
EN 61000-6-4:2007/
A1:2011
EMC Part 6-4: Generic standards - Emission standard for industrial environments
EN 61000-3-2:
Harmonic Current Emissions
EN 61000-3-3:
Voltage Fluctuations and Flicker
EN 61000-4-2:
ESD Immunity
EN 61000-4-3:
Radiated Electromagnetic Immunity
EN 61000-4-4:
Electrical Fast Transient/Burst Immunity
EN 61000-4-5:
Power Line Surge Immunity
EN 61000-4-6:
Conducted Electromagnetic Immunity
EN 61000-4-8:
Power Frequency Magnetic Field
EN 61000-4-11
Voltage Dips, Short Interruptions and Variations
ETS 300 019-1-1
Environmental Conditions; Storage
ETS 300 019-1-2
Environmental Conditions; Transportation
ETS 300 132-2
Power Supply Interface at the Input to Telecommunications Equipment; Operated
by Direct Current (DC)
ETS 300 753
Acoustic Noise Emissions
IEC 60950
Safety of Information Technology Equipment, Including Electrical Business Equip-
ment (IECUL/CSA 60950-1 Ed. 2)
Input Transient Suppres-
sion:
Meets ANSI/IEEE C62.41 Category B3
The above information is valid at the time of publication. Consult factory for up-to-date ordering
information. Specifications are subject to change without notice.
9400021-J0 Rev B
Page 47
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 13 - Specifications
13.4. CXCi HP Controller
Table 12. Specifications: CXCi HP Controller
Specifications: Basic Unit, CXCi HP
Input Voltage:
12 to 60Vdc within rated limits
Current:
<200mA @ 52Vdc, <400mA @ 26.5Vdc, <800mA @ 13.2Vdc
MTBF:
95,000 hours (10.9 years), with display off
OLED 84,000 hours @ 10% usage, 9,800 atv100% usage, at 25°C
EMC:
The unit meets requirements of:
• EN 300 386-2 EMC and EMR, Telecommunications Network Equipment
Emissions:
• EN 55022 Class B (CISPR 22)
• CFR47 (FCC) Part 15 Class B
Immunity:
• EN 61000-4-2 ESD EN 61000-4-3
• Radiated EN 61000-4-4 EFT /Burst
• EN 61000-4-6 Conducted
Environmental:
• ETS 300 019-1-1 Environmental Conditions, Storage
• ETS 300 019-1-2 Environmental Conditions, Transportation
In accordance with FCC requirements, we provide the following statement as specified in the FCC guidelines
for conformance to Part 15, Class B:
Note: This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment in a residential
area is likely to cause harmful interference in which case the user will be required to correct the interference at
his own expense.
Any changes or modifications to this equipment not expressly described in this manual could void the FCC
compliance.
Environmental
Page 48
9400021-J0 Rev B
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 13 - Specifications
Table 12. Specifications: CXCi HP Controller (continued)
Specifications: Basic Unit, CXCi HP
Temperature:
-40 to 65°C (-40 to 149°F) operating -40 to 80°C (-40 to 176°F) storage
Humidity:
5% to 95% RH non-condensing
Elevation:
-500 to +4000m (-1640 to +13124ft)
Hardware: CXCi HP
Hardware
CPU:
ARM A8
RAM:
128MB
Flash:
256MB
Display:
5-line, LED matrix
Front Panel Con-
trols:
Menu up and down, home and select buttons
LED’s:
System OK (Green) Power System Minor Alarm (Yellow) Power System Major Alarm /
Controller Fail (Red)
Audio:
Built-in speaker for alarm and popup message tones 70dbl
Dimensions:
44mm H x 88mm W x 318mm D (1.73" H x 3.5" W x 12.5" D)
Weight:
0.62kg (1.36lb.)
Mounting:
Modular on Cordex series shelves
Relay Outputs:
Four (4) Form C, 60Vdc 1A maximum
Digital Inputs:
Two (2), ±60Vdc
Analog Inputs:
Two DC voltage, 0 to 60Vdc, One DC current, compatible with ±25mV to ±200mV
shunts, Two temperature, 0 to 5Vdc with power source
Communication
Ports:
Ethernet RJ-45, USB 2.0, CAN (see shelf specifications)
Recommended Signal Wire Sizes
Wire Size Range:
#16 to #26 AWG (1.5 to 0.14mm2)
Temperature Rating: 90°C (194°F)
CAUTION:
TO REDUCE RISK OF FIRE, USE ONLY #26 AWG (0.14mm2) OR LARGER WIRE.
The above information is valid at the time of publication. Consult factory for up-to-date ordering information.
Specifications are subject to change without notice.
9400021-J0 Rev B
Page 49
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 13 - Specifications
13.5. CXCi+ Controller
Table 13. Specifications: CXCi+ Controller
Specifications: Basic Unit, CXCi+
Input Voltage:
10 to 65Vdc within rated limits
Current:
<100mA @ 48Vdc
<200mA @ 24Vdc
MTBF:
1,500,000 hrs @30°C (86°F) ambient
EMC:
Radiated and Conducted Emissions:
North America Regions
• CFR 47, Part 15 Subpart B, Class B
• ICES-003 Issue 2, Rev 1, Class
European Regions
• EN 55022 Class B
• EN 300 386-2
• EN61000-3-2; Harmonics
• EN61000-3-3; Flicker
Immunity:
• EN 300 386-2
• EN61000-4-2:2005, ESD ± 8 kV Air, ± 6 kV Contact
• EN61000-4-3:2005, RF Immunity 10 V/m
• EN61000-4-4:2005, EFT, 1kV/0.5kV
• EN61000-4-5:2005, Surge; 2 kV line to line, 1 kV line to earth
• EN61000-4-6:2005, Conducted Susceptibility, 10 Vrms
• EN61000-4-11: Voltage Dips and Interruptions
In accordance with FCC requirements, we provide the following statement as specified in the FCC guidelines
for conformance to Part 15, Class B:
Warning: The CXCi+ has been tested and found to comply with the limits for a Class B digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment generates, uses, and can radiate radio fre-
quency energy and, if not installed and used in accordance with the instructions, may cause harmful interfer-
ence to radio communications. However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or television reception, which can be de-
termined by turning the equipment off and on, the user is encouraged to try to correct the interference by one
or more of the following measures:
Page 50
9400021-J0 Rev B
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 13 - Specifications
Table 13. Specifications: CXCi+ Controller (continued)
Specifications: Basic Unit, CXCi+
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
Any changes or modifications to this equipment not expressly described in this manual could void the FCC
compliance.
Environmental
Temperature:
-40 to 65°C (-40 to 149°F) standard @ 3000m (9843ft), derate to 55°C (131°F) @
4000m (13124ft)
Humidity:
0 to 95% non-condensing
Elevation:
-500 to +4000m (-1640 to +13124ft)
Hardware Specifications
CPU:
Coldfire
Display:
4 digit LCD
Front Panel Con-
trols:
Display pushbutton toggle switch for voltage (V) or current (A), Reset switch (soft reset
button; hold for 3 seconds to reset IP)
LEDs:
System OK (Green), Power System Minor Alarm (Yellow), Power System Major Alarm /
Controller Fail (Red)
Audio:
Built-in speaker for alarm and popup message tones
Dimensions:
88mm H x 26mm W x 280mm D (3.5” H x 1” W x 11“ D)
Weight:
0.34kg (0.75lb.)
Mounting:
Integrated on Cordex 2RU series 19” and 23” shelves
Relay Outputs:
Four (4) Form C, 60Vdc 1A maximum
Digital Inputs:
Two (2), 0 to 60Vdc
Analog Inputs:
One (1) DC voltage, 0 to 60Vdc One (1) DC current, ±50mV
Two (2) temperature, self-powered Alpha sensor (max 12Vdc)
Communication
Ports:
Ethernet RJ-45, CAN [see shelf specifications]
Recommended Signal Wire Sizes (as per UL/CSA)
Wire Size Range:
#16 to #26 AWG (1.5 to 0.14mm2)
Temperature Rating: 90°C (194°F)
9400021-J0 Rev B
Page 51
Cordex® 24-400W 19” Integrated Shelf Installation and Operations Guide | 13 - Specifications
Table 13. Specifications: CXCi+ Controller (continued)
Specifications: Basic Unit, CXCi+
CAUTION: TO REDUCE RISK OF FIRE, USE ONLY #26 AWG (0.14mm2) OR LARGER WIRE.
The above information is valid at the time of publication. Consult factory for up-to-date ordering information.
Specifications are subject to change without notice.
Page 52
9400021-J0 Rev B
I1 (LOAD CURRENT)
+
T2
+
T1
+
C
TECHNOLOGIES
TM
NOT BE COPIED OR USED WITHOUT ITS WRITTEN CONSENT.
REMAIN THE PROPERTY OF ALPHA TECHNOLOGIES AND SHALL
THESE DESIGNS AND SPECIFICATIONS ARE CONFIDETIAL,
C ALPHA TECHNOLOGIES
S3
SHEET
of
SIZE
REV
DWG NO.
TITLE
DATE
ISSUE
DESIGN
DRAWN
CHECKED
APPROVED
1
1
030-773-05
CXRC 24-400W
19", 5 MDL, CXCI,
SCHEMATIC, SHELF,
J.K
W.S
B
W.S 2006/04
2006/04
2006/01
REVISION
LTR
DESCRIPTION
DATE
APP
DRW
CHK
E1
E6
E5
(+)
(-)
(+)
(-)
(+)
(-)
(+)
(-)
5 MDL, POS GND, CORDEX CXRC
SCHEMATIC: 707-461-05
PART NUMBER: 707-461-20
PCB ASSY, 19" 2RU BACKPLANE,
BATTERY HOT
I1
D1
T1
T2
V1
D2
+
+
+
-
-
-
+
-
1
2
1
2
C
NC
NO
C
NC
NO
C
NC
NO
NC
NO
C
-
-
-
(-)
J1
J2
(-)
(+)
(+)
TB13
I1
-
+
25
24
TB12
23
22
D2
NC
C
NO
K4
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
BATTERY
V1
T2
T1
D1
+
+
+
K3
K2
K1
NO
C
NC
NO
C
NC
NO
C
NC
TB11
P4
SCHEMATIC: 707-479-05
PART NUMBER: 707-479-20
PCB ASSY, I/O INTERFACE, 19" SHELF 2RU,
19
20
21
J12
J10
J9
CANCOM
CANH
CANL
+5VCAN
CAN IN
(-)
(-)
(+)
(+)
+5VCAN
CANH
CANCOM
CANL
CAN OUT
+5VCAN
CANL
CANH
CANCOM
P12
J4
D1 (CB/FUSE TRIP)
2
1
K4 (AC FAIL)
K3 (SYSTEM MAJOR)
K2 (SYTEM MINOR)
K1 (LVD1)
NO
NC
COM
NO
NC
COM
NO
NC
COM
NC
NO
COM
2
1
-
+
V1
D2
-
-
-
+5VCAN
V2 -
V2 +
POWER -
POWER +
CAN COM
CANL
CANH
PCB ASSY, CX, MOTHERBOARD
BATTERY HOT
JP1
JUMPER
CAN TERMINATION
RECTIFIER #5
AC
INTLK (+)
DC
INTLK (-)
J6
CANCOM
CANL
+5VCAN
CANH
FAN ENABLE
FAN ENABLE
CANH
+5VCAN
CANL
CANCOM
J5
INTLK (-)
DC
INTLK (+)
AC
RECTIFIER #4
FAN ENABLE
CANH
+5VCAN
CANL
CANCOM
J4
INTLK (-)
DC
INTLK (+)
AC
RECTIFIER #3
FAN ENABLE
CANH
+5VCAN
CANL
CANCOM
J3
INTLK (-)
DC
INTLK (+)
AC
RECTIFIER #2
P2
P1
RECTIFIER #1
(+)
(-)
AC #2
AC #1
AC
INTLK (+)
DC
INTLK (-)
J2
L1
L2
GND
GND
L2
L1
TB4
TB3
CANCOM
CANL
+5VCAN
CANH
FAN ENABLE
J3-1
J3-2
J3-3
J3-4
J3-7
J3-8
J3-9
J3-10
J3-13
J3-14
J3-37
J3-38
J3-39
J3-40
J3-41
J3-42
J3-43
J3-44
J3-27
J3-28
J3-29
J3-30
J3-31
J3-32
J3-33
J3-34
J3-17
J3-18
J3-19
J3-20
J3-23
J3-24
J3-25
J3-26
J2-26
J2-25
J2-24
J2-23
J2-20
J2-19
J2-18
J2-17
J2-34
J2-33
J2-32
J2-31
J2-30
J2-29
J2-28
J2-27
J2-44
J2-43
J2-42
J2-41
J2-40
J2-39
J2-38
J2-37
J2-14
J2-13
J2-10
J2-9
J2-8
J2-7
J2-4
J2-3
J2-2
J2-1
J4-26
J4-25
J4-24
J4-23
J4-20
J4-19
J4-18
J4-17
J4-34
J4-33
J4-32
J4-31
J4-30
J4-29
J4-28
J4-27
J4-44
J4-43
J4-42
J4-41
J4-40
J4-39
J4-38
J4-37
J4-14
J4-13
J4-10
J4-9
J4-8
J4-7
J4-4
J4-3
J4-2
J4-1
J5-26
J5-25
J5-24
J5-23
J5-20
J5-19
J5-18
J5-17
J5-34
J5-33
J5-32
J5-31
J5-30
J5-29
J5-28
J5-27
J5-44
J5-43
J5-42
J5-41
J5-40
J5-39
J5-38
J5-37
J5-14
J5-13
J5-10
J5-9
J5-8
J5-7
J5-4
J5-3
J5-2
J5-1
J6-26
J6-25
J6-24
J6-23
J6-20
J6-19
J6-18
J6-17
J6-34
J6-33
J6-32
J6-31
J6-30
J6-29
J6-28
J6-27
J6-44
J6-43
J6-42
J6-41
J6-40
J6-39
J6-38
J6-37
J6-14
J6-13
J6-10
J6-9
J6-8
J6-7
J6-4
J6-3
J6-2
J6-1
E7
LVD
LIST 86
24V/100A
FEEDS
MDLS 1 & 2
MDLS 3,4 & 5
FEEDS
5 MDL, CORDEX CXRC
TB6
TB1
TB2
-
-
+
+
AUX. OUTPUT
POWER
LVD AUTO OVERRIDE
JUMPER
NC
C
NO
(OPTIONAL)
E3
(+)
E2
JP2
(+)
(-)
LOAD
OR
BATT
BATT
OR
LOAD
THESE CONNECTIONS REQUIRED
WHEN LVD CONTROLLED OUTPUT
IS USED FOR BATTERY
CUSTOMER
BREAKERS
HOT (+)
TB12
3
2
1
1
2
3
2
3
1
1
4
3
2
1
2
3
4
5
6
12
11
10
9
2
1
6
5
4
3
6
5
4
3
2
1
25
12
24
11
23
10
22
9
21
8
20
7
19
6
18
4
17
5
15
3
2
16
14
1
13
9 10
8
7
6
5
4
3
2
1
7
8
13
14
13
1
14
16
2
3
15
5
17
4
18
6
19
7
20
8
21
9
22
10
23
11
24
12
25
4
3
2
1
1
2
3
4
2
1
4
1
2
1
2
1
2
3
4
B
2008/01
WS
ADDED LIST 86
WH
C
2008/01
LS
ADDED OPTION 441
WH
SIZE DWG NO.
TITLE:
OF
E
NTS
B
1
2
030-763-06
OUTLINE,SELF,19"FLUSH,
2RU,4MDL,CXC,DISTRN,400W
THESE DESIGNS AND SPECIFICATIONS ARE
CONFIDENTIAL, REMAIN THE PROPERTY OF
ALPHA TECHNOLOGIES LTD., AND SHALL NOT BE
COPIED OR USED WITHOUT ITS WRITTEN CONSENT
© ALPHA TECHNOLOGIES LTD
CHECKED
DRAWN
DATE
APPROVALS
RP
2005/05
2005/05
EOF
X
X.X
X.XX
ANGULAR:
INTERPRET DIM AND TOL PER
ASME Y14.5M-1994
UNLESS OTHERWISE SPECIFIED
DIM ARE IN MM
THIRD ANGLE PROJECTION
0.25
0.5
1
1
2006/02
RP
GS
UPDATED TO REV C ASSY
B
SDW
UPDATED CXCI CONTR
C
LS
2011/07
CF
LS
ADD LIST 98, BP00337
D
LS
2015/10
WH
LS
ADD LIST 400
E
DESCRIPTION
LTR
APPD
DATE
DWN
REVISIONS
CHKD
OPTION 19 - 6" OFFSET
19" RACK MOUNT OPTIONS
OPTION 98, 99 OR 400
CXCI-CONTROLLER
010-582-20
CXRC POWER MODULE
OPTION 90
MODULE BLANK
OPTION 80, 83 OR 84
DISTRIBUTION
OPTION 22 - 5" OFFSET
OPTION 21 - FLUSH MOUNT
OPTION 400
REF
OPTION 23 - 6" OFFSET
23" RACK MOUNT OPTIONS
OPTION 98, 99 OR 400
CXCI-CONTROLLER
010-582-20
CXRC POWER MODULE
OPTION 90
MODULE BLANK
OPTION 80, 83 OR 84
DISTRIBUTION
OPTION 26 - 5" OFFSET
OPTION 25 - FLUSH MOUNT
A
B
C
D
E
1
2
3
4
5
D
A
C
E
B
1
3
5
4
2
DO NOT SCALE DRAWING
SIZE DWG NO.
TITLE:
OF
E
NTS
B
2
2
030-763-06
OUTLINE,SELF,19"FLUSH,
2RU,4MDL,CXC,DISTRN,400W
0
5.0 127
12.1 307
0.7 18
0
6.0 152
OPTION 22 - 5" OFFSET
OPTION 19 - 6" OFFSET
OPTION 21 - FLUSH MOUNT
19.0 482
0
0.2 6
1.5 38
2.0 51
3.2 82
3.5 88
18.3 465
19" RACK OPTION
0
5.0 127
12.1 307
0
6.0 152
0.7 18
OPTION 23 - 6" OFFSET
OPTION 26 - 5" OFFSET
OPTION 25 - FLUSH MOUNT
23.0 583
22.3 566
0
0.2 6
1.5 38
2.0 51
3.2 82
3.5 88
23" RACK OPTION
DO NOT SCALE DRAWING
2
4
5
3
1
B
E
C
A
D
5
4
3
2
1
E
D
C
B
A
SIZE DWG NO.
TITLE:
OF
L
NTS
1
4
030-763-08
CUSTOMER_CONNECTION
2RU,4MDL,CXC,DISTRN,400W
THESE DESIGNS AND SPECIFICATIONS ARE
CONFIDENTIAL, REMAIN THE PROPERTY OF
ALPHA TECHNOLOGIES LTD., AND SHALL NOT BE
COPIED OR USED WITHOUT ITS WRITTEN CONSENT
© ALPHA TECHNOLOGIES LTD
CHECKED
DRAWN
DATE
APPROVALS
RP
2005/05
2005/05
EOF
THIRD ANGLE PROJECTION
UNLESS OTHERWISE SPECIFIED
DIM ARE IN MM
INTERPRET DIM AND TOL PER
ASME Y14.5M-1994
X
X.X
X.XX
ANGULAR:
1
1
0.5
0.25
2015/10
WH
LS
ADD Option 400
L
DESCRIPTION
LTR
APPD
DATE
DWN
REVISIONS
CHKD
2006/02
RP
GS
UPDATED TO REV C ASSY
B
2006/03
RP
GS
CORRECTED CUST INT PCB LABELING
C
2006/06
JU
GS
CORRECTED DETAIL ON SHEET4
D
SDW 2006/08
GS
CORRECTED RJ45 DETAIL
E
SDW 2006/09
JK
UPDATED CXCI SUPERVISORY
F
2007/04
MP
GS
CHANGED AC I/P FROM L2 TO L2/N
G
2007/10
JK
GS
CORRECTED JP2 PINOUT (SHT.4)
H
SDW 2008/01
JK
UPDATED NOTES
J
2011/07
CF
LS
ADD LIST 98 (SHT.2), BP00337
K
CX
SUPERVISORY
CORDEX 400W
MODULES
DISPLAY PUSHBUTTON
TOGGLE SWITCH(V/A)
SYSTEM STATUS LEDS
CXCI RESET SWITCH
SOFT RESET - PUSH ONCE
I/P RESET - HOLD FOR 3 SEC.
4 CB POSITION DISTRIBUTION
LCD SCREEN (V/A)
MODULE BLANK
MODEM
NETWORK
RST
OK
MIN
MAJ
CXCI
V/A
DB9
ETHERNET RJ45
TX+
1.
TX-
2.
RX+
3.
NOT CONNECTED
4.
NOT CONNECTED
5.
RX-
6.
NOT CONNECTED
7.
NOT CONNECTED
8.
DCD
1.
RX
2.
TX
3.
DTR
4.
COM
5.
DSR
6.
RTS
7.
CTS
8.
RI
9.
DB9
FOR ARGUS DC
MODEM USE ONLY
1
8
1
9
OPTION 400
STATUS DISPLAY
RESET
USB 2.0
PORT
ETHERNET
10/100
MENU SELECT /
BUTTON C
MENU CONTROL
ALARM
STATUS
OPTION 99
HARD RESET-PUSH ONCE
OPTION 99 ONLY
A
B
C
D
E
1
2
3
4
5
D
A
C
E
B
1
3
5
4
2
DO NOT SCALE DRAWING
SIZE DWG NO.
TITLE:
OF
L
NTS
2
4
030-763-08
CUSTOMER_CONNECTION
2RU,4MDL,CXC,DISTRN,400W
CXCI
SUPERVISORY
CORDEX 400W
MODULES
SYSTEM STATUS LEDS
4 CB POSITION DISTRIBUTION
MODULE BLANK
LCD
HARD RESET-PUSH
ONCE
DISP. TOGGLE
CXCI RESET
RST
ETHERNET RJ45
TX+
1.
TX-
2.
RX+
3.
NOT CONNECTED
4.
NOT CONNECTED
5.
RX-
6.
NOT CONNECTED
7.
NOT CONNECTED
8.
LIST 98 ONLY
DO NOT SCALE DRAWING
2
4
5
3
1
B
E
C
A
D
5
4
3
2
1
E
D
C
B
A
SIZE DWG NO.
TITLE:
OF
L
NTS
B
3
4
030-763-08
CUST.,CONN, 2RU,4MDL,
CXC,DISTRN,400W
JUMPER SETTINGS FOR JP1
CAN UNTERMINATED
CAN TERMINATED
REAR VIEW
(BACK COVER REMOVED)
(CUSTOMER CONNECTION BOARD NOT SHOWN)
L2/N
L1
L2/N
L1
DC OUTPUT TERMINAL BLOCKS
(MAX. WIRE GAUGE #6 AWG)
TB3 FEEDS MODULES 1 AND 2
TB4 FEEDS MODULES 3 AND 4
TB3
TB4
TB1
TB2
(+)
(-)
AC CABLE ENTRY
0.875"
CAN COM
1.
CAN H
2.
NOT CONNECTED
3.
CAN L
4.
NOT CONNECTED
5.
+5 V CAN
6.
CAN OUT RJ12
PIN OUT (J6)
JP1
J6
DO NOT SCALE DRAWING
2
4
5
3
1
B
E
C
A
D
5
4
3
2
1
E
D
C
B
A
SIZE DWG NO.
TITLE:
OF
L
NTS
B
4
4
030-763-08
CUST.,CONN, 2RU,4MDL,
CXC,DISTRN,400W
REAR VIEW
(BACK COVER REMOVED)
(CUSTOMER CONNECTION BOARD SHOWN)
TB3
TB4
TB1
TB2
(-)
(+)
I1
-
+
25
24
TB13
NC C NO
K1
NC C NO
K2
NC C NO
K3
K4
NC C NO
1
12 11 10
9
8
7
6
5
4
3
2
-
+
-
+
-
+
BATT
HOT
(+)
T2
T1
V1
D2
D1
14 15 16 17 18 19 20 21 22 23
13
TB11
TB12
CUSTOMER CONNECTION BOARD DETAIL
USED INTERNALLY
1 2 3 4
USED INTERNALLY FOR LVD CONTROL
(IF EQUIPPED)
REFER TO MANUAL FOR
JUMPER SETTINGS
JP2
DO NOT SCALE DRAWING
2
4
5
3
1
B
E
C
A
D
5
4
3
2
1
E
D
C
B
A
SIZE DWG NO.
TITLE:
OF
D
N.T.S.
B
1
2
030-773-06
OUTL., SHELF,19",5 MDL,
CXCI,CXRC 24-400W
THESE DESIGNS AND SPECIFICATIONS ARE
CONFIDENTIAL, REMAIN THE PROPERTY OF
ALPHA TECHNOLOGIES LTD., AND SHALL NOT BE
COPIED OR USED WITHOUT ITS WRITTEN CONSENT
© ALPHA TECHNOLOGIES LTD
CHECKED
DRAWN
DATE
APPROVALS
GS
2006/04
2006/04
RP
THIRD ANGLE PROJECTION
UNLESS OTHERWISE SPECIFIED
DIM ARE IN MM
INTERPRET DIM AND TOL PER
ASME Y14.5M-1994
X
X.X
X.XX
ANGULAR:
1
1
0.5
0.25
OPTION 21 - FLUSH MOUNT
OPTION 19 - 6" OFFSET
19" RACK MOUNT OPTIONS
OPTION 80 SHOWN
OPTION 90
MODULE BLANK
010-582-20
CXRC POWER MODULE
OPTION 99
OR OPTION 400
OPTION 25 - FLUSH MOUNT
OPTION 23 - 6" OFFSET
23" RACK MOUNT OPTIONS
OPTION 80 SHOWN
OPTION 90
MODULE BLANK
010-582-20
CXRC POWER MODULE
OPTION 99
OR OPTION 400
REVISIONS
LTR
DESCRIPTION
DWN
DATE
CHK
B
UPDATED CXCI CONTROLLER
JU
2006/10
SS
C
UPDATED CXRC POWER MODULE
SDW
2006/12
JK
D
ADDED OPTION 400
WH
2017/05
LS
A
B
C
D
E
1
2
3
4
5
D
A
C
E
B
1
3
5
4
2
DO NOT SCALE DRAWING
SIZE DWG NO.
TITLE:
OF
D
N.T.S.
B
2
2
030-773-06
OUTL., SHELF,19",5 MDL,
CXCI,CXRC 24-400W
19.0 482
18.3 465
0
0.2 6
1.5 38
2.0 51
3.2 82
3.5 88
19" RACK MOUNT OPTIONS
0
0.7 18
6.0 152
12.1 307
OPTION 19 - 6" OFFSET
OPTION 21 - FLUSH MOUNT
23.0 583
22.3 566
0
0.2 6
1.5 38
2.0 51
3.2 82
3.5 88
23" RACK MOUNT OPTIONS
0
0.7 18
6.0 152
12.1 307
OPTION 25 - FLUSH MOUNT
OPTION 23 - 6" OFFSET
DO NOT SCALE DRAWING
2
4
5
3
1
B
E
C
A
D
5
4
3
2
1
E
D
C
B
A
SIZE DWG NO.
TITLE:
OF
H
NTS
B
1
3
030-773-08
CUST. CONN.,19",5 MDL,
CXCI,CXRC 24-400W
THESE DESIGNS AND SPECIFICATIONS ARE
CONFIDENTIAL, REMAIN THE PROPERTY OF
ALPHA TECHNOLOGIES LTD., AND SHALL NOT BE
COPIED OR USED WITHOUT ITS WRITTEN CONSENT
© ALPHA TECHNOLOGIES LTD
CHECKED
DRAWN
DATE
APPROVALS
GS
2006/04
2006/04
RP
LIST 80
MODULE BLANK
CORDEX 400W
MODULES
CXCI
SUPERVISORY
CXCI RESET SWITCH
SOFT RESET-PUSH ONCE
I/P RESET-HOLD FOR 3 SEC.
DISPLAY PUSHBUTTON
TOGGLE SWITCH(V/A)
LCD SCREEN
(V/A)
SYSTEM STATUS LEDS
DB9
MODEM
NETWORK
RST
OK
MIN
MAJ
CXCI
V/A
OPTION 99
CXCi
ETHERNET RJ45
TX+
1.
TX-
2.
RX+
3.
NOT CONNECTED
4.
NOT CONNECTED
5.
RX-
6.
NOT CONNECTED
7.
NOT CONNECTED
8.
DCD
1.
RX
2.
TX
3.
DTR
4.
COM
5.
DSR
6.
RTS
7.
CTS
8.
RI
9.
DB9
FOR ARGUS DC
MODEM USE ONLY
8
1
9
1
OPTION 98
CXCi+
OPTION 400
CXCi HP
STATUS DISPLAY
RESET
ETHERNET
10/100
USB 2.0
PORT
MENU CONTROL
MENU SELECT /
BUTTON C
ALARM
STATUS
HARD RESET-PUSH ONCE
REVISIONS
LTR
DESCRIPTION
DWN
DATE
CHK
D
CHANGED AD I/P FROM 'L2' TO 'L2/N'
MP
2007/04
JK
E
CORRECTED JP2 PINOUT (SHT. 3)
JK
2007/10
JK
F
UPDATED NOTES
SWD
2008/01
JK
G
ADDED CXCI+ MODULE
FC
2013/12
JK
H
ADDED CXCI HP
WH
2015/11
LS
A
B
C
D
E
1
2
3
4
5
D
A
C
E
B
1
3
5
4
2
DO NOT SCALE DRAWING
SIZE DWG NO.
TITLE:
OF
H
NTS
B
2
3
030-773-08
CUST. CONN.,19",5 MDL,
CXCI,CXRC 24-400W
TB4
TB3
REAR VIEW
(BACK COVERS REMOVED)
AC CABLE ENTRY
0.875"
DC OUTPUT STUDS
USES 1/4-20 x 5/8" OUTPUT LUGS
(TIGHTEN TO 8 ft-lbs)
TB3 FEEDS MODULES 1 AND 2
TB4 FEEDS MODULES 3, 4 AND 5
( - )
( - )
(+)
(+)
TB1
( - )
TB2
(+)
THIS OUTPUT IS LVD
CONTROLLED (IF EQUIPPED)
L2/N
L1
L2/N
L1
JUMPER SETTINGS FOR JP1
CAN UNTERMINATED
CAN TERMINATED
LIST 0 - CAN OUT RJ12
PIN OUT (J9)
1. CAN COM
2. CAN H
3. NOT CONNECTED
4. CAN L
5. NOT CONNECTED
6. +5 V CAN
LIST 80 - CAN IN RJ12
PIN OUT (J10)
1. CAN COM
2. CAN H
3. NOT CONNECTED
4. CAN L
5. NOT CONNECTED
6. +5 V CAN
J9
JP1
J10
DO NOT SCALE DRAWING
2
4
5
3
1
B
E
C
A
D
5
4
3
2
1
E
D
C
B
A
SIZE DWG NO.
TITLE:
OF
H
NTS
B
3
3
030-773-08
CUST. CONN.,19",5 MDL,
CXCI,CXRC 24-400W
I1
-
+
25
24
TB13
NC C NO
K1
NC C NO
K2
NC C NO
K3
K4
NC C NO
1
12 11 10
9
8
7
6
5
4
3
2
-
+
-
+
-
+
BATT
HOT
(+)
T2
T1
V1
D2
D1
14 15 16 17 18 19 20 21 22 23
13
TB11
TB12
TB4
TB3
REAR VIEW
(BACK COVERS REMOVED)
TB1
( - )
TB2
(+)
L2/N
L1
L2/N
L1
REFER TO MANUAL FOR
JUMPER SETTINGS FOR JP2
CUSTOMER CONNECTION BOARD DETAIL
USED INTERNALLY FOR LVD CONTROL
(IF EQUIPPED)
1 2 3 4
JP2
DO NOT SCALE DRAWING
2
4
5
3
1
B
E
C
A
D
5
4
3
2
1
E
D
C
B
A
#9400021-J0 REV B (07/2020)
Alpha Technologies Ltd.| 7700 Riverfront Gate, Burnaby, BC V5J 5M4 CANADA