Circutor DCP-96 Aac Instruction Manual
Text of the manual
Warns of a risk, which could result in personal injury or material damage.
ATTENTION
Indicates�that�special�attention�should�be�paid�to�a�specifi�c�point.
Follow the warnings described in this manual with the symbols shown below.
If you must handle the unit for its installation, start-up or maintenance, the following
should be taken into consideration:
Incorrect handling or installation of the unit may result in injury to personnel as well as damage
to the unit. In particular, handling with voltages applied may result in electric shock, which may
cause death or serious injury to personnel. Defective installation or maintenance may also
lead�to�the�risk�of�fi�re.
Read the manual carefully prior to connecting the unit. Follow all installation and maintenance
instructions throughout the unit’s working life. Pay special attention to the installation stan-
dards of the National Electrical Code.
Refer to the instruction manual before using the unit
In this manual, if the instructions marked with this symbol are not respected or carried out correctly, it can
result in injury or damage to the unit and /or installations.
CIRCUTOR,�SA�reserves�the�right�to�modify�features�or�the�product�manual�without�prior�notifi�cation.
DISCLAIMER
CIRCUTOR, SA�reserves�the�right�to�make�modifi�cations�to�the�device�or�the�unit�specifi�ca-
tions set out in this instruction manual without prior notice.
CIRCUTOR, SA on its web site, supplies its customers with the latest versions of the device
specifi�cations�and�the�most�updated�manuals.�������������������������������
�
�
�
www.circutor.com
CIRCUTOR, recommends using the original cables and accessories that are
supplied with the device.
SAFETY PRECAUTIONS ���������������������������������������������������������������������������������������������������������������������������������������3
DISCLAIMER ����������������������������������������������������������������������������������������������������������������������������������������������������������3
CONTENTS �������������������������������������������������������������������������������������������������������������������������������������������������������������4
REVISION LOG �������������������������������������������������������������������������������������������������������������������������������������������������������5
SYMBOLS ���������������������������������������������������������������������������������������������������������������������������������������������������������������5
1�- VERIFICATION UPON RECEPTION �����������������������������������������������������������������������������������������������������������������6
2�- PRODUCT DESCRIPTION ��������������������������������������������������������������������������������������������������������������������������������6
3�- DEVICE INSTALLATION �����������������������������������������������������������������������������������������������������������������������������������7
3�1�- PRIOR RECOMMENDATIONS������������������������������������������������������������������������������������������������������������������7
3�2�- INSTALLATION �����������������������������������������������������������������������������������������������������������������������������������������8
3�3�- DEVICE TERMINALS ��������������������������������������������������������������������������������������������������������������������������������9
3�4�-CONNECTION DIAGRAM ������������������������������������������������������������������������������������������������������������������������10
4�- OPERATION ���������������������������������������������������������������������������������������������������������������������������������������������������� 11
4�1�- DISPLAY �������������������������������������������������������������������������������������������������������������������������������������������������� 11
4�2�- KEYBOARD FUNCTIONS ����������������������������������������������������������������������������������������������������������������������� 11
5�- DISPLAY ��������������������������������������������������������������������������������������������������������������������������������������������������������12
5�1�- SINGLE-PHASE NETWORK MEASURING ��������������������������������������������������������������������������������������������12
5�2�- THREE-PHASE NETWORK MEASURE WITH 3 OR 4 WIRE ���������������������������������������������������������������� 13
6�- CONFIGURATION �������������������������������������������������������������������������������������������������������������������������������������������14
6�1�- CONFIGURATION OF THE INPUT ����������������������������������������������������������������������������������������������������������15
6�1�1�- MEASUREMENT SYSTEM ��������������������������������������������������������������������������������������������������������������� 15
6�1�2�- PRIMARY CURRENT ������������������������������������������������������������������������������������������������������������������������16
6�1�3�- SECONDARY CURRENT ������������������������������������������������������������������������������������������������������������������ 16
6�1�4�- SAVE CONFIGURATION������������������������������������������������������������������������������������������������������������������� 17
6�2�- SYSTEM CONFIGURATION �������������������������������������������������������������������������������������������������������������������18
6�2�1�- CYCLIC DISPLAY ����������������������������������������������������������������������������������������������������������������������������� 18
6�2�2�- DISPLAY BACKLIGHT ���������������������������������������������������������������������������������������������������������������������� 19
6�2�3�- INITIAL DISPLAY SCREEN �������������������������������������������������������������������������������������������������������������� 19
6�2�4�- ACCESS PASSWORD ���������������������������������������������������������������������������������������������������������������������� 20
6�2�5�- LIGHT ALARM����������������������������������������������������������������������������������������������������������������������������������� 20
6�2�6�- SAVE CONFIGURATION������������������������������������������������������������������������������������������������������������������� 21
7�- TECHNICAL FEATURES ��������������������������������������������������������������������������������������������������������������������������������22
8�- MAINTENANCE AND TECHNICAL SERVICE ������������������������������������������������������������������������������������������������24
9�- WARRANTY �����������������������������������������������������������������������������������������������������������������������������������������������������24
10�- CE CERTIFICATE ������������������������������������������������������������������������������������������������������������������������������������������25
ANNEX A�- CONFIGURATION MENU ������������������������������������������������������������������������������������������������������������������28
Table 1: Revision log
Date
Revision
Description
11/19
M264B01-03-19A
First Version
Note: The images on the devices are for illustrative use only and may differ from the original
device.
SYMBOLS
Table 2:Symbols�
Symbol
Description
In accordance with the relevant European directive.
In accordance with the CMiM directive.
Device covered by European Directive 2012/19/EC. At the end of its useful life, do not
leave the unit in a household waste container. Follow local regulations on electronic equi-
pment recycling.
Direct current.
~
Alternating current.
1�- VERIFICATION UPON RECEPTION
Upon reception of the device check the following points:
�
a)�The�device�meets�the�specifications�described�in�your�order
b) The device has not suffered any damage during transport
c) Perform an external visual inspection of the device prior to switching it on
d) Check that it has been delivered with the following:
- An installation guide
If any problem is noticed upon reception, immediately contact the transport
company and/or CIRCUTOR’s after-sales service
2�- PRODUCT DESCRIPTION
The DCP-96 Aac is a device designed to measure and display the current and the frequency
AC three-phase.
The device features:
- 3 keys that allow you to browse between the various screens and program the device
- LCD Display to display all the parameters
Table 3: List of DCP-96 Aac models�
DCP-96 Aac
Model
Auxiliary power supply
80 ��� 270 V ~ 80 ��� 270 V
18 �� 36 V
M22450
-
M224500030000
-
-
3�- DEVICE INSTALLATION
3.1.- PRIOR RECOMMENDATIONS
In order to use the device safely, it is critical that individuals who handle it follow
the safety measures set out in the standards of the country where it is being
used, using the personal protective equipment necessary (rubber gloves, face
protection�and�approved�flame-resistant�clothing)�to�prevent�injuries�due�to�elec-
tric shock or electric arc as a consequence of exposure to current-carrying con-
ductors and paying attention to the various warnings indicated in this instruction
manual.
The DCP-96 Aac device�must�be�installed�by�authorised�and�qualified�staff.
The power supply plug must be disconnected and measurement systems switched off before
handling, altering the connections or replacing the device. It is dangerous to handle the device
while it is powered.
It is critical to keep wires in perfect condition to avoid accidents, personal injury or damage to
installations.
Limit�the�operation�of�the�device�to�measuring�the�specified�current�or�voltage�values.
The manufacturer of the device is not responsible for any damage resulting from failure by the
user or installer to heed the warnings and/or recommendations set out in this manual, nor for
damage resulting from the use of non-original products or accessories or those made by other
manufacturers.
Do not use the device to take measurements if you detect an anomaly or malfunction.
Disconnect the device from the mains and from the power supply (both the device
and its measuring system) before performing any maintenance work, repairs or
handling any of the connections of the device.
Contact the after-sales service if you detect that the device is not working prop-
erly.
Terminals, opening covers or removing elements can expose parts that are
hazardous to the touch while the device is powered. Do not use the device until
it is fully installed.
The device should be installed inside an electric panel or enclosure, and panel-mounted.
The following steps must be taken for correct installation:
1�- Make a cut in the panel, according to the dimensions in Figure 1�
91
91
Figure 1: Cut in the panel�
2�- From outside, insert the device into the panel cut-out (Figure 2).
Figure 2: Insert the device�
3�- Fully insert the device and fasten it by using the spring (Figure 3).
Figure 3: Fully insert the device�
The device must be connected to a power circuit protected by a fuse with a maximum nominal
current of 0�25 A.
If more than one device is connected to the current transformer, they must be connected in
series.
Before disconnecting the current measurement connection cables, be sure to disconnect the
transformer’s primary cables and bridge the secondary.
The device can operate in three-wire, three-phase mode or four-wire, three-phase mode, the
user selecting the corresponding connection mode according to the installation. An incorrect
type of connection or an error in phase sequence may cause measurement errors.
3.3.- DEVICE TERMINALS
Table 4: List of DCP-96 Aac terminals�
Device terminals
1: L/+, Power supply
6: I2 S1, Current input L2
2: N/-, Power supply
7: I2 S2, Current input L2
4: I1 S1, Current input L1
8: I3 S1, Current input L3
5: I1 S2, Current input L1
9: I3 S2, Current input L3
2
1
4
1
2
4
5
6
7
5
6
7
8
9
8
9
Figure 4: DCP-96 Aac terminals�
CARGA / LOAD
2
1
4
5
6
7
8
9
Figure 5: Current measurement�
The device has a LCD display with 3 lines, 4 digits each, to view the measured parameters and
to�configure�the�device.
Units
Confguration
0000
L1
0000
0000
A
L2
L3
.
.
.
Figure 6: Display DCP-96 Aac�
4.2.- KEYBOARD FUNCTIONS
The DCP-96 Aac has 3 keys that allow you to browse through and program the device, Table
5 and Table 6.
Display screens:
Table 5: Keyboard function: Display screens�
Key
Keystroke
Previous screen.
Next screen.
Long keystroke (> 3s):
Accesses�the�configuration�menu
Configuration�screens:
Table 6: Keyboard function: Configuration screens.
Key
Keystroke
Browses through the different menu screens.
Browses through the different options.
Browses through the different menu screens.
Browses through the different options.
Skips�to�the�next�configuration�menu.
Changes the digit's value.
Long keystroke (> 3s):
Enables�the�value's�configuration
Validates�the�configuration�parameter
5.1.- SINGLE-PHASE NETWORK MEASURING
The DCP-96 Aac has 2 display screens in the single-phase network measurement system, see
“6.1.1.- MEASUREMENT SYSTEM”, Table 7.
Use the keys
and
to browse through the different screens.
The display screens can change automatically depending on the time programmed in the sec-
tion “6.2.1.- CYCLIC DISPLAY ”.
The�initial�display�screen,�i.e.�the�first�screen�displayed�when�feeding�the�device�or�when�exiting�
the�configuration�menu,�can�be�programmed�in�section “6.2.3.- INITIAL DISPLAY SCREEN”�
Table 7:Display menu: Single-phase network measuring�
Display menu: Single-phase network measuring
5010
A
.
Current (A)
5000
Hz
.
Frequency (Hz)
If the input current value higher than a % of the nominal value, the device can make the digits
on�the�display�start�flashing,�in�the�form�of�a�light�alarm. See “6.2.5.- LIGHT ALARM”
5.2.- THREE-PHASE NETWORK MEASURE WITH 3 OR 4 WIRE
The DCP-96 Aac has 2 display screens in the three-phase network measurement system with
a 3 or 4 wire connection, see “6.1.1.- MEASUREMENT SYSTEM”, Table 8.
Use the keys
and
to browse through the different screens.
The display screens can change automatically depending on the time programmed in the sec-
tion “6.2.1.- CYCLIC DISPLAY”.
The�initial�display�screen,�i.e.�the�first�screen�displayed�when�feeding�the�device�or�when�exiting�
the�configuration�menu,�can�be�programmed�in�section “6.2.3.- INITIAL DISPLAY SCREEN”�
Table 8:Display menu: Three-phase network measuring�
Display menu: Three-phase network measuring
5011
L1
5012
5013
A
L2
L3
.
.
.
Current (A)
5000
Hz
.
Frequency (Hz)
If the input current value higher than a % of the nominal value, the device can make the digits
on�the�display�start�flashing,�in�the�form�of�a�light�alarm.�See�“6.2.5.- LIGHT ALARM”
Press and hold the
�key�for�more�than�3�seconds�to�enter�the�device’s�configuration�menu.�
The�device’s�configuration�is�organised�in�different�menus, Figure 7.
>3s
Confguration of
the input
Software version
System
confguration
2206
L1
2207
2208
V
L2
L3
.
.
.
ProG
CodE
0000
inpt
nEt
n34
.
SyS
CyC
no
dCPU
1002
1906
-
>3s
>3s
>3s
Figure 7: DCP-96 Aac configuration menu�
From�any�screen�of�the�configuration�menus,�if�no�key�is�pressed�for�1�minute,�the�device�
leaves�the�configuration�menu�and�returns�to�the�display�screen.
Note: In “ANNEX A.- CONFIGURATION MENU” you can see the complete configuration menu.
Before�accessing�the�configuration�menu,�it�is�necessary�to�enter�the�access�password.
>3s
2206
L1
2207
2208
V
L2
L3
.
.
.
ProG
CodE
0000
>3s
>3s
CodE
0001
inpt
nEt
n34
Figure 8: Access to the configuration menu in the programming mode.
Use the key
�to�modify�the�value�of�the�flashing�digit.
When the desired value is shown on the screen, press the
and
keys to skip the digit.
Default password: 0001
Note: The password can be modified, see “6.2.4.- ACCESS PASSWORD”�
With a long keystroke (>3s), press
to validate the data.
If the password entered is incorrect, the Err message will appear for a few seconds and the
device�will�return�to�the�password�configuration�screen, Figure 8.
6.1.- CONFIGURATION OF THE INPUT
Figure 9, shows�the�input�configuration�menu�from�which�the�measurement�system�and�the�
primary�and�secondary�current�are�configured.
Measurement system
Primary current
Save confguration
Secondary current
inpt
nEt
n34
.
inpt
Ct 1
0005
.
.
A
k
inpt
Ct 2
0005
.
A
SAuE
>3s
>3s
>3s
>3s
inpt
nEt
n34
.
inpt
Ct 1
0005
.
.
A
k
inpt
Ct 2
0005
.
A
SAuE
no
Figure 9: Input configuration menu.
6�1�1�- MEASUREMENT SYSTEM
In�this�screen�we�can�configure�the�measurement�system�used�in�the�installation.
inpt
nEt
n34
.
>3s inpt
nEt
n34
.
With a long keystroke (>3s), press
�to�access�the�value’s�configuration.
Use the keys
and
to browse through the different options:
n34, three-phase network measuring with 4-wire connection.
n.33, three-phase network measuring with 3-wire connection.
n.12, single-phase measuring.
With a long keystroke, press
to validate the option.
Use the keys
and
to browse through the menu screens.
6�1�2�- PRIMARY CURRENT
This�screen�is�used�to�configure�the�value�of�the�primary�current.
inpt
Ct 1
0005
.
.
A
k
>3s inpt
Ct 1
0005
.
.
A
k
With a long keystroke (>3s), press
�to�access�the�value’s�configuration.
Use the key
�to�modify�the�value�of�the�flashing�digit.
When the desired value is shown on the screen, press the
and
keys to skip the digit.
When you reach the last digit and press the
key, you select the position of the decimal
point. Use the key
to modify the decimal point.
Minimum configuration value: 0.001 kA
Maximum configuration value: 9999 kA
With a long keystroke, press
to validate the option.
Use the keys
and
to browse through the menu screens.
6�1�3�- SECONDARY CURRENT
This�screen�is�used�to�configure�the�value�of�the�secondary�current.
inpt
Ct 2
0005
.
A
>3s inpt
Ct 2
0005
.
A
With a long keystroke (>3s), press
�to�access�the�value’s�configuration.
Use the key
�to�modify�the�value�of�the�flashing�digit.
When the desired value is shown on the screen, press the
and
keys to skip the digit.
Minimum configuration value: 1.000 A
Maximum configuration value: 6.000 A
With a long keystroke, press
to validate the option.
Utilizar las teclas
y
para moverse entre las pantallas del menú.
6�1�4�- SAVE CONFIGURATION
This�screen�is�used�to�save�the�device’s�configuration.
SAuE
>3s SAuE
no
With a long keystroke (>3s), press
�to�access�the�value’s�configuration.
Use the keys
and
to browse through the different options:
no,�to�not�save�the�configuration.
YES,�to�save�the�configuration.
With a long keystroke, press
to validate the option. The device skips to the main screen of
the�next�configuration�menu.
6.2.- SYSTEM CONFIGURATION
Figure 10, shows�the�system�configuration�menu.
Display backlight
Initial display screen
Access password
Save confguration
Light alarm
Cyclic display
sys
CyC
no
SyS
liGH
0000
SyS
diSP
i
SyS
CodE
0001
>3s
>3s
>3s
>3s
Sys
CyC
no
SyS
LiGH
0000
SyS
diSp
i
SyS
CodE
0001
SAuE
>3s SAuE
no
SyS
ALr
120
>3s SyS
ALr
120
%
%
Figure 10:System configuration menu.
6�2�1�- CYCLIC DISPLAY
The display screens can change automatically or not.
sys
CyC
no
>3s Sys
CyC
no
With a long keystroke (>3s), press
�to�access�the�value’s�configuration.
Use the keys
and
to browse through the different options:
no, the cyclic display is not activated.
YES, the cyclic display is activated; the display screen changes every 3 s.
With a long keystroke, press
to validate the option.
Use the keys
and
to browse through the menu screens.
6�2�2�- DISPLAY BACKLIGHT
The time that the display backlight will stay lit in seconds if no key is pressed is programmed
on this screen.
SyS
liGH
0000
>3s SyS
LiGH
0000
With a long keystroke (>3s), press
�to�access�the�value’s�configuration.
When the desired value is shown on the screen, press the
and
keys to skip the digit.
Minimum configuration value: 0 s.
Maximum configuration value: 255 s.
Note: If the value 0 is programmed, the display backlight is not turned off.
With a long keystroke, press
to validate the data.
Use the keys
and
to browse through the menu screens.
6�2�3�- INITIAL DISPLAY SCREEN
In�this�section�the�initial�display�screen�is�configured.
SyS
diSP
i
>3s SyS
diSp
i
With a long keystroke (>3s), press
�to�access�the�value’s�configuration.
Use the keys
and
to browse through the different options:
i, current screen.
F, frequency screen.
With a long keystroke, press
to validate the data.
Use the keys
and
to browse through the menu screens.
6�2�4�- ACCESS PASSWORD
This�screen�is�used�to�configure�the�value�of�the�password�used�to�access�the�configuration�
menu.
SyS
CodE
0001
>3s SyS
CodE
0001
With a long keystroke (>3s), press
�to�access�the�value’s�configuration.
When the desired value is shown on the screen, press the
and
keys to skip the digit.
Minimum configuration value: 0
Maximum configuration value: 9999
With a long keystroke, press
to validate the data.
Use the keys
and
to browse through the menu screens.
6�2�5�- LIGHT ALARM
If the device’s input current value is higher than a % of the nominal value, the device can make
the�digits�on�the�display�start�flashing,�in�the�form�of�a�light�alarm.��
SyS
ALr
120
>3s SyS
ALr
120
%
%
With a long keystroke (>3s), press
�to�access�the�value’s�configuration.
When the desired value is shown on the screen, press the
and
keys to skip the digit.
Minimum configuration value: 30%
Maximum configuration value: 120%
Note: If the value 0 is programmed, the light alarm will be deactivated.
With a long keystroke, press
to validate the data.
Use the keys
and
to browse through the menu screens.
6�2�6�- SAVE CONFIGURATION
This�screen�is�used�to�save�the�device’s�configuration.
SAuE
>3s SAuE
no
With a long keystroke (>3s), press
�to�access�the�value’s�configuration.
Use the keys
and
to browse through the different options:
no,�to�not�save�the�configuration.
YES,�to�save�the�configuration.
With a long keystroke, press
to validate the option. The device skips to the main screen
of�the�next�configuration�menu.
7�- TECHNICAL FEATURES
AC Power supply (1)
Rated voltage
80 ... 270 V ~
Frequency
50 / 60 Hz
Consumption
1 ... 4 VA
Installation category
CAT III 300V
DC Power supply (1)
Rated voltage
80 ... 270 V
18 ... 36 V
Consumption
0.5 ...0.7 W
0.7 ...0.8 W
Installation category
CAT III 300V
(1) Depending on model:
DCP-96 Aac
Model
Power supply
80 ��� 270 V ~
80 ��� 270 V
18 ��� 36 V
M22450
-
M224500030000
-
-
Current measurement circuit
Rated current (In)
1 A / 5 A ~
Frequency measuring margin
45 ... 65 Hz
Overcurrent
1.2 In continuous - 10 In Instantaneous (5 s)
Consumption
< 0.2 VA (per phase)
Impedance
<�20�mΩ
Installation category
CAT III 300V
Accuracy
Current measurement
0.5
Frequency measurement
± 0.01 Hz
User interface
Display
LCD
Keyboard
3 keys
Environmental Features
Operating temperature
-25ºC ... +70ºC
Storage temperature
-40ºC ... +85ºC
Relative humidity (without condensation)
≤�95%
Maximum altitude
2000 m
Protection degree
Front: IP54, Rear case: IP20
Pollution degree
2
Mechanical characteristics
Terminals
1, 2, 4 ... 9, 58 ... 60
2.5 mm2
0.5 Nm
Flat (SZS 0.6x3.5)
Dimensions
Figure 11 (mm)
Weight
202 g.
Enclosure
pc + abs
Electromagnetic compatibility (EMC) Part 4-2: Testing and measurement tech-
niques� Electrostatic discharge immunity test�
IEC 61000-4-2
Electromagnetic compatibility (EMC) Part 4-3: Testing and measurement tech-
niques. Radiated, radio-frequency, electromagnetic field immunity test.
IEC 61000-4-3
Electromagnetic compatibility (EMC) Part 4-4: Testing and measurement tech-
niques� Electrical fast transient/burst immunity test�
IEC 61000-4-4
Electromagnetic compatibility (EMC) Part 4-5: Testing and measurement tech-
niques� Surge immunity test�
IEC 61000-4-5
Electromagnetic compatibility (EMC) Part 4-6: Testing and measurement tech-
niques. Immunity to conducted disturbances, induced by radio-frequency fields.
IEC 61000-4-6
Electromagnetic compatibility (EMC) Part 4-8:Testing and measurement tech-
niques. Power frequency magnetic field immunity test.
IEC 61000-4-8
Electromagnetic compatibility (EMC) Part 4-11: Testing and measurement tech-
niques� Voltage dips, short interruptions and voltage variations immunity tests
IEC 61000-4-11
Safety requirements for electrical equipment for measurement, control and lab-
oratory use� Part 1: General requirements�
IEC 61010-1
96
96
4(max)
34
41.5
Figure 11: Dimensions of the DCP-96 Aac�
8�- MAINTENANCE AND TECHNICAL SERVICE
9�- WARRANTY
• No returns will be accepted and no unit will be repaired or replaced if it is not ac-
companied by a report indicating the defect detected or the reason for the return.
•The guarantee will be void if the units has been improperly used or the stora-
ge, installation and maintenance instructions listed in this manual have not been
followed.�“Improper�usage”�is�defi�ned�as�any�operating�or�storage�condition�con-
trary to the national electrical code or that surpasses the limits indicated in the
technical and environmental features of this manual.
• CIRCUTOR accepts no liability due to the possible damage to the unit or other
parts of the installation, nor will it cover any possible sanctions derived from a pos-
sible failure, improper installation or “improper usage” of the unit. Consequently,
this guarantee does not apply to failures occurring in the following cases:
- Overvoltages and/or electrical disturbances in the supply;
-�Water,�if�the�product�does�not�have�the�appropriate�IP�classifi�cation;
- Poor ventilation and/or excessive temperatures;
- Improper installation and/or lack of maintenance;
-�Buyer�repairs�or�modifi�cations�without�the�manufacturer’s�authorisation.
CIRCUTOR guarantees its products against any manufacturing defect for two years after the
delivery of the units.
CIRCUTOR will repair or replace any defective factory product returned during the guarantee
period.
In the case of any query in relation to device operation or malfunction, please contact the
CIRCUTOR, SA Technical Support Service.
Technical Assistance Service
Vial Sant Jordi, s/n, 08232 - Viladecavalls (Barcelona)
Tel: 902 449 459 ( España) / +34 937 452 919 (outside of Spain)
email: [email protected]
ANNEX A�- CONFIGURATION MENU
Input configuration
Cyclic display
Display backlight
Initial display
screen
Access password
Light alarm
Save confguration
Measurement system
Save confguration
Primary current
Secondary current
SyS
liGH
0000
SyS
diSP
i
SyS
CodE
0001
>3s
>3s
>3s
SyS
LiGH
0000
SyS
diSp
i
SyS
CodE
0001
SyS
ALr
120
>3s SyS
ALr
120
%
%
CyC
no
CyC
no
SyS
>3s sys
sys
>3s
CyC
yES
SyS
diSp
F
>3s
SAuE
>3s SAuE
no
SAuE
yEs
>3s
>3s
2206
L1
2207
2208
V
L2
L3
.
.
.
ProG
CodE
0000
>3s
>3s
CodE
0001
inpt
nEt
n34
inpt
Ct 1
0005
.
.
A
k
inpt
Ct 2
5000
.
.
A
SAuE
>3s
>3s
>3s
>3s
inpt
nEt
n34
.
inpt
Ct 1
0005
.
.
A
inpt
Ct 2
5000
.
.
A
SAuE
no
inpt
nEt
n33
.
inpt
nEt
n12
.
SAuE
yEs
>3s
>3s
k
System configuration