EDS SCL-01 Technical Information

Text of the manual

EDS - TECHNICAL INFORMATION

Explosion-proof ATEX Spark Detector SCL-01 TECHNICAL MANUAL EDS srl - V. Ca' Nova Zampieri 6 - 37057 S. G. Lupatoto - VERONA - Tel. +39045547529 - Fax +390458750065 Email: [email protected] - Web: www.eds.eu

EDS - TECHNICAL INFORMATION

SPARK DETECTOR SCL-01 The SCL-01 is a spark detector suitable for the detection of very fast sparks that can be transported by pipelines of silos or warehouses for the storage of flammable materials such as sawdust, cotton yarn, cereal powders, metal powders, etc. . The possibility of detection in an extremely short time of this

EDS - TECHNICAL INFORMATION

1.9 - The detector has two internal settings (Figure 2) - sensitivity level adjustment - adjustment of the duration of the time of activation of the output relay (using the jumpers JP3-4-5-6-7) They must be adjusted to achieve optimum perfor- mance 1.10 - The detector is equipped with internal microprocessor which not only prov

EDS - TECHNICAL INFORMATION

the relay output of EV521 (if present) T4 - response time of VL electrovalve T5 - time of water filling of the part of the pipe between the electrovalve and the SS nozzle and time of formation of the cone of extinguishing water If the system does not use the EV521 control panel, signal processing time and response time of the re

EDS - TECHNICAL INFORMATION

6.3 - Periodically check the operation and thightness of the electrovalves. A defect in the seal can result in flooding of the pipeline and can cause damage. It would be good to install a tap and a filter to trap impurities that may affect the electrovalve upstream the valve. It would be also good to provide some elements of wat